Vous êtes sur la page 1sur 105

POW ER+

M o d u la r U P S s y s t e m
1 0 k V A t o 1 0 0 k V A , 3 x4 0 0 V
Technical Guide

Release 1.5, May 2008

Har Hotzvim Industrial Park,


14 Hartom St., PO Box 45029, Jerusalem 91450, Israel
Tel: +972-2-588-8222 Fax: +972-2-582-8875
Email: info@gamatronic.co.il Website: www.gamatronic.com
Gamatronic Electronic Industries Ltd.
Har Hotzvim Industrial Park
14 Hartom St.
PO Box 45029
Jerusalem 91450
Israel
Tel: +972-2-588-8222
Fax: +972-2-582-8875
Email: info@gamatronic.co.il
Website: www.gamatronic.com

The equipment described in this document is not intended for use in


connection with any application requiring fail-safe performance, such
as the operation of nuclear power facilities, air traffic control or
navigation systems, weapons control systems, life support systems, or
any other system whose failure could lead to injury, death,
environmental damage or mass destruction.

Copyright 2008 by Gamatronic Electronic Industries Ltd. All rights reserved worldwide.
The information contained in this document is proprietary and is subject to all relevant copyright, patent and other
laws protecting intellectual property, as well as any specific agreement protecting Gamatronic Electronic Industries
Ltd. rights in the aforesaid information. Neither this document nor the information contained herein may be published,
reproduced or disclosed to third parties, in whole or in part, without the express, prior, written permission of
Gamatronic Electronic Industries Ltd. In addition, any use of this document or the information contained herein for
any purposes other than those for which it was disclosed is strictly forbidden.
Gamatronic Electronic Industries Ltd. reserves the right, without prior notice or liability, to make changes in
equipment design or specifications.
Information supplied by Gamatronic Electronic Industries Ltd. is believed to be accurate and reliable. However, no
responsibility is assumed by Gamatronic Electronic Industries Ltd. for the use thereof nor for the rights of third parties
which may be affected in any way by the use thereof.
Any representation(s) in this document concerning performance of Gamatronic Electronic Industries Ltd. product(s)
are for informational purposes only and are not warranties of future performance, either express or implied.
Gamatronic Electronic Industries Ltd. standard limited warranty, stated in its sales contract or order confirmation form,
is the only warranty offered by Gamatronic Electronic Industries Ltd. in relation thereto.
This document may contain flaws, omissions or typesetting errors; no warranty is granted nor liability assumed in
relation thereto unless specifically undertaken in Gamatronic Electronic Industries Ltd. sales contract or order
confirmation. Information contained herein is periodically updated and changes will be incorporated into subsequent
editions. If you have encountered an error, please notify Gamatronic Electronic Industries Ltd. All specifications are
subject to change without prior notice.

ii Power+ Technical Guide, Release 1.5


Gamatronic Electronic Industries Ltd.

TABLE OF CONTENTS
1. SYSTEM STRUCTURE ........................................................................................................1

2. FUNCTIONAL OVERVIEW ..................................................................................................4


2.1. UPS Basic Module (10kVA / 8KW) ..........................................................................4
2.1.1. Single UPS Module Specifications........................................................ 9
2.2. UPS System Controller..........................................................................................10
2.2.1. System Controller Specifications........................................................12
2.3. Static Switch (ST/SW) Module ..............................................................................12

3. SYSTEM INTERCONNECTION .........................................................................................15


3.1. internal System wiring...........................................................................................16
3.1.1. The Power+ always requires a neutral line ........................................20
3.1.2. UPS Module Connectors Description ..............................................24
3.1.3. UPS Module Pin Assignment Table .................................................... 25
3.2. DC Distribution Panel Cabling..............................................................................26
3.2.1. DC Fuses................................................................................................28
3.3. AC Input Fuses.......................................................................................................29
3.4. AC Distribution Compartment ..............................................................................30
3.5. AC Input/Output Main Terminals ..........................................................................31
3.6. Static Switch Connections....................................................................................32
3.7. System Controller Connections ...........................................................................33
3.8. Setting the Shelf Address .....................................................................................34
3.9. F.A.Q. (Frequently Asked Questions) ..................................................................37
3.9.1. Batteries .................................................................................................37
3.9.2. General ...................................................................................................39
3.9.3. Menus .....................................................................................................40
3.9.4. Installation .............................................................................................41
3.9.5. Mechanics ..............................................................................................42
3.9.6. Common problems ...............................................................................42

4. SYSTEM INSTALLATION..................................................................................................44
4.1. Inspections to be Performed Prior to Installation ..............................................46
4.2. Installation Procedure and System Start-up .......................................................47
4.3. Initial Start-up Sequence .......................................................................................48
4.4. Checks to be Performed Following Initial Startup ............................................. 50
4.5. Special considerations for 1-phase output .........................................................51
4.5.1. Dip-switch settings on the modules ...................................................51
4.5.2. Wiring of input and output terminals ..................................................51
4.5.3. System start-up .....................................................................................52
4.6. dip switch SETTINGS of THE UPS modules .......................................................53

5. USING THE SYSTEM CONTROLLER ..............................................................................54


5.1. System information display ..................................................................................55
5.2. Display UPS module data......................................................................................57
5.3. Setting the Number of UPS Modules ...................................................................59
5.4. Retrieving History (LOG of Events)......................................................................60
5.5. Control Communications ......................................................................................60
5.6. System Controller Alarms .....................................................................................61

6. BATTERIES........................................................................................................................ 62

Power+ Technical Guide, Release 1.5 iii


Gamatronic Electronic Industries Ltd.

6.1. Batteries and Configurations................................................................................62


6.1.1. Internal Batteries...................................................................................62
6.1.2. External Batteries..................................................................................63
6.2. Installing and connecting the Batteries...............................................................63

7. DRY CONTACTS AND ALARM TERMINALS ..................................................................66


7.1. DC Current measurement .....................................................................................67
7.2. Temperature sensor...............................................................................................67
7.3. User-defined alarms...............................................................................................68

8. TROUBLESHOOTING .......................................................................................................69

9. SYSTEM CONTROLLER AND COMMUNICATIONS .......................................................73


9.1. Introduction ............................................................................................................73
9.2. SCC POWER+ characteristics ..............................................................................73
9.3. Controller User Interface .......................................................................................74
9.4. Service Utilities ......................................................................................................74
9.4.1. Start-up Screens ...................................................................................74
9.4.2. The Main Menu ......................................................................................77

10. SETUP PROCEDURES......................................................................................................78


10.1. Setting Alarm Thresholds .....................................................................................78
10.1.1. Setting Alarm Vibration Parameters ...................................................79
10.1.2. Setting the Integration Factor for Alarms...........................................79
10.1.3. 'Auto' Test Batteries .............................................................................79
10.2. Setting Password Level 1......................................................................................79
10.3. Adding a POWER module .....................................................................................80
10.4. System Controller setup verification ...................................................................81

11. REPLACEMENT PROCEDURES ......................................................................................83


11.1. UPS module ............................................................................................................83
11.2. System Controller module ....................................................................................84
11.3. Static Switch module .............................................................................................85

12. USING SERVICE PROGRAMS .........................................................................................86


12.1. Access to Service Mode ........................................................................................86
12.2. Selecting the Controllers Low Level Utilities.....................................................87
12.3. Setting the Network Addresses............................................................................87
12.3.1. Setting the SNMP Factor ......................................................................87
12.4. Configuring Dry Contacts and Alarms.................................................................88
12.4.1. Linking Alarms to Dry Contacts ..........................................................88
12.4.2. Enabling and disabling specific alarms..............................................88
12.5. Calibrating Measurements ....................................................................................89
12.6. Controller Self-Test................................................................................................89
12.7. Battery Test.............................................................................................................89
12.7.1. Periodic/Automatic Battery Test .........................................................89

13. MONITORING THE SYSTEM.............................................................................................90

iv Power+ Technical Guide, Release 1.5


Gamatronic Electronic Industries Ltd.

13.1. Power Meter............................................................................................................90


13.2. System Operating Times .......................................................................................91
13.3. Main DIP Switch Status .........................................................................................91
13.4. Panel and Slave DIP Switch Status ......................................................................92
13.5. SC POWER+ Internal Power Supply ....................................................................92
13.6. System Temperature..............................................................................................92
13.7. Internal Communication ........................................................................................93
13.8. Monitoring System Components..........................................................................94
13.8.1. Monitoring the Batteries.......................................................................94
13.8.2. Monitoring Alarms ................................................................................95
13.9. After Using the Emergency Power Off.................................................................95

14. SYSTEM SPECIFICATIONS ..............................................................................................96

15. SYSTEM MODULES ORDERING INFORMATION ...........................................................97

LIST OF FIGURES
Figure 1-1: Block diagram.......................................................................................................1
Figure 1-2: Sub-assemblies ....................................................................................................2
Figure 1-3: 10kVA configuration............................................................................................. 2
Figure 1-4: 50kVA configuration............................................................................................. 3
Figure 1-5: 100kVA configuration .......................................................................................... 3
Figure 2-1: Single UPS Module- Front/Rear View .................................................................4
Figure 2-2: Block diagram of a single UPS Module.............................................................. 5
Figure 2-3: Power section of the PFC in a single UPS module ........................................... 6
Figure 2-4: Input currents of the PFC (without filters) ......................................................... 6
Figure 2-5: PFC control scheme............................................................................................. 7
Figure 2-6: DC/AC inverter principal topology...................................................................... 8
Figure 2-7: System controller - Front panel ........................................................................10
Figure 2-8: System controller - Block diagram ...................................................................11
Figure 2-9: ST/SW front panel view......................................................................................13
Figure 2-10: ST/SW block diagram.......................................................................................13
Figure 2-11: 3-Phase ST/SW block diagram........................................................................14
Figure 3-1: Power+ system - Modular structure .................................................................15
Figure 3-2: Schematic of a 3:1 Phase 30kVA POWER+ System .......................................16
Figure 3-3: Schematic of a 3-Phase 30kVA POWER+ System ..........................................17
Figure 3-4: POWER+ System - Rear View ...........................................................................18
Figure 3-5: Control PCB and flat cable ................................................................................19
Figure 3-6: Wrong way to connect UPS with grounded-neutral-generator ..................... 21
Figure 3-7: Acceptable connection for grounded generator and 4-pole switch .............22
Figure 3-8: Preferred generator (neutralized) and connection (3-pole) ...........................23
Figure 3-9: UPS module Rear view ...................................................................................24
Figure 3-10: UPS module connectors - Pin assignments..................................................24
Figure 3-11: DC distribution panel (50KVA model) ............................................................27
Figure 3-12: DC distribution. panel (100kVA model)..........................................................27
Figure 3-13: DC fuses on front side of DC dist. panel (50KVA model)............................. 28
Figure 3-14: DC fuses on front of DC dist. panel (100KVA model)................................... 28
Figure 3-15: UPS modules - AC input fuses (100KVA model)............................................ 29
Figure 3-16: AC input fuse assignments (50KVA model) ..................................................29
Figure 3-17: AC distribution..................................................................................................30
Figure 3-18: AC distribution panel (100KVA model) ..........................................................30
Figure 3-19: AC distribution panel (50KVA model) ............................................................30
Figure 3-20: Input & output main terminals ........................................................................31
Figure 3-21: Static switch terminals Rear view................................................................32
Figure 3-22: System controller outside the shelf - Rear view ...........................................33
Figure 3-23: The PC917 Control PCB on a shelf general view .......................................34

Power+ Technical Guide, Release 1.5 v


Gamatronic Electronic Industries Ltd.

Figure 3-24: DIP switches on PC719 card close-up .........................................................35


Figure 3-25: Recommended master/slave DIP switch settings ........................................35
Figure 3-26: DIP switch settings ...........................................................................................36
Figure 4-1: POWER+ system connections ..........................................................................44
Figure 4-2: Switch and wire ratings for 10-100kVA installation........................................45
Figure 4-3: Start-up screen 1 ................................................................................................48
Figure 4-4: Start-up screen 2 ................................................................................................48
Figure 4-5: Start-up screen 3 ................................................................................................48
Figure 4-6: Start-up screen 4 ................................................................................................48
Figure 4-7: Normal display of the controller LCD (default) ...............................................49
Figure 4-8: Example of dip switch setting for 3/3 phase, 50 Hz UPS ...............................52
Figure 5-1: The controllers main menu ..............................................................................54
Figure 5-2: Main menu option 1 ("System") ........................................................................55
Figure 5-3: System DC voltages ...........................................................................................55
Figure 5-4: Overall phase voltages/currents.......................................................................56
Figure 5-5: Output power factor 1 ........................................................................................56
Figure 5-6: Input power factor 1 ...........................................................................................56
Figure 5-7: Main Menu option 2 (UPS Module).................................................................57
Figure 5-8: LCD Panel Selection........................................................................................58
Figure 5-9: Module phase voltages/currents ......................................................................58
Figure 5-10: Battery voltages, I-active current....................................................................58
Figure 5-11: Controller menu #2...........................................................................................59
Figure 5-12: Controller menu #3...........................................................................................59
Figure 5-13: Controller menu #4...........................................................................................59
Figure 5-14: Number of UPS modules .................................................................................59
Figure 5-15: Log display........................................................................................................60
Figure 5-16: Communications ..............................................................................................60
Figure 6-1: 40kVA N+1 System with Internal Batteries ......................................................62
Figure 6-2: Internal Battery Drawer Exploded View ........................................................63
Figure 6-3: Connection diagram for external battery.........................................................64
Figure 7-1: Location of dry contacts at rear of POWER+ controller module...................66
Figure 7-2: Dry Contacts group A (as per Figure 7-1) ....................................................66
Figure 7-3: Dry Contacts group B (as per Figure 7-1) ....................................................67
Figure 8-1: UPS module front panel.....................................................................................69
Figure 12-1: Low level utility menu (SC2012 menu) ...........................................................87
Figure 13-1: Key panel...........................................................................................................90

LIST OF TABLES
Table 2-1 Single UPS Module Specifications ........................................................................9
Table 2-2: System controller specifications........................................................................12
Table 3-1: UPS module pin assignment and function........................................................25
Table 3-2: DIP switch setup in a 100kVA system (X = don't care). ...................................36
Table 4-1: Power Configuration DIP Switch Settings ........................................................52
Table 5-1: Controller main menu options .............................................................................54
Table 5-2: System controller alarms .....................................................................................61
Table 8-1: UPS Module Indicators ........................................................................................70
Table 8-2: Troubleshooting table .........................................................................................71
Table 9-1: General information screen ................................................................................76
Table 9-2: Main Menu functions ...........................................................................................77
Table 10-1: Setup Menu options...........................................................................................78
Table 10-2: Setting alarm thresholds ...................................................................................78
Table 12-1: Calibrating battery current measurements .....................................................89
Table 13-1: Time displays......................................................................................................91
Table 13-2: Main dip switch statuses...................................................................................91
Table 13-3: Panel and slave dip switch statuses................................................................92
Table 13-4: Controller external and internal power statuses ............................................92
vi Power+ Technical Guide, Release 1.5
Gamatronic Electronic Industries Ltd.

Table 13-5: System temperature displays ...........................................................................92


Table 13-6: Battery test information ....................................................................................94
Table 14-1: Technical specifications ...................................................................................96
Table 15-1: Ordering parts ....................................................................................................97

Power+ Technical Guide, Release 1.5 vii


Gamatronic Electronic Industries Ltd.

WARNING: RISK OF
SEVERE DAMAGE TO THE UPS!!!

THIS SYSTEM USES THE NEUTRAL LINE FOR


OPERATION. THEREFORE, IT IS STRICTLY
FORBIDDEN TO CONNECT THIS SYSTEM TO
THE AC POWER SOURCE WITHOUT A NEUTRAL
(NULL) CONDUCTOR!!
FAILURE TO USE A NEUTRAL CONDUCTOR MAY
CAUSE PERMANENT DAMAGE TO THE SYSTEM.

viii Power+ Technical Guide, Release 1.5


Gamatronic Electronic Industries Ltd.

1. SYSTEM STRUCTURE
The Power+ is a parallel redundant UPS. A block diagram is shown in Figure 1-1 below.

RS232, TCP/IP, Cellular,

System
Controller

Bypass Power
Output

Static Switch
Isolation
Mains Power
UPS Transformer
10KVA
(optional)

UPS
10KVA

UPS
10KVA

UPS
10KVA

Centralized

Figure 1-1: Block diagram

Power+ Technical Guide 1


Gamatronic Electronic Industries Ltd.

The system comprises the following sub-assemblies.

1-10 UPS modules 10kVA (4 in the example in Figure 1-2 below)

System Controller

Static Switch Module

Power Distribution Block

System
Controller

4 x 10kVA UPS
Modules

DC Distribution

Static Switch
(ST.SW) Module
AC Distribution
(Behind ST.SW.)

Figure 1-2: Sub-assemblies

Figure 1-3: 10kVA configuration

2 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

Figure 1-4: 50kVA configuration

Figure 1-5: 100kVA configuration

Power+ Technical Guide 3


Gamatronic Electronic Industries Ltd.

2. FUNCTIONAL OVERVIEW

2.1. UPS BASIC MODULE (10KVA / 8KW)


The UPS Basic Module is the core of the system, which comprises 1 to 10 identical parallel
modules depending on capacity requirements.

A general module view is shown in Figure 2-1. The module classic on-line double-
conversion type block diagram is illustrated in Figure 2-2.

This design has proved to be very stable. No transfer time is required for the UPS to switch
from normal to backup mode; the load is supplied constantly by stable and clean power. A
Power Factor Correction (PFC) 1 is responsible for the low Total Harmonic Distortion (THD)
and unity Power Factor (PF) at the input.

The input voltage(s) is converted to a stable 425V at the DC link.

This stage can maintain current sharing between the three input phases as well as among
other parallel units, because of the current sharing signal that it produces.

Figure 2-1: Single UPS Module- Front/Rear View

1
PFC is a feature included that reduces the amount of generated reactive power. Reactive power
operates at right angles to true power and energizes the magnetic field. Reactive power has no real
value for an electronic device, but electric companies charge for both true and reactive power
resulting in unnecessary charges.
In power factor correction, the power factor (represented as "k") is the ratio of true power (kwatts)
divided by reactive power (kvar). The power factor value is between 0.0 and 1.00. If the power factor
is above 0.8, the device is using power efficiently. A standard power supply has a power factor of
0.70-0.75, and a power supply with PFC has a power factor of 0.95-0.99.

4 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

Figure 2-2: Block diagram of a single UPS Module

Power+ Technical Guide 5


Gamatronic Electronic Industries Ltd.

The PFC power section block diagram is shown in Figure 2-3. Input currents of the PFC
(without filters) is shown in Figure 2-4; the control scheme is illustrated in Figure 2-5.

+
Ir

-
Control

+
Is

-
Control

+
It

R S T
-

Control

N
Figure 2-3: Power section of the PFC in a single UPS module

Ipeak Ir Is
(CCM)
t

-Ipeak It
Figure 2-4: Input currents of the PFC (without filters)

As shown in Figure 2-3, the PFC section operates in Continuous Current Mode (CCM)
conduction, which has many advantages. Input currents are shaped in such a way that they
follow the input voltages with precision.
This makes the system appear to be nothing more than a resistive load with respect to the
line voltage. In other words, the system corrects the input current waveform of the connected
load, and acts as an active power filter.
The PFC section also draws symmetrical currents from each phase, and maintains good
current sharing among identical UPS modules in parallel.

Each phase input is sensed for voltage and current, required to force the input current drawn
from the phase input to follow its voltage and emulate a resistor. Two feedback loops are

6 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

required for the proper operation, an inner current loop for maintaining a correct wave shape
and an outer voltage loop to ensure a correct DC output level.

The voltage sample (k*Vin) is multiplied by the error voltage from a common voltage
feedback amplifier (Integrator). The result is than compared to the actual sampled phase
current which forces the current amplifier current to follow the phase input voltage. The
output of the integrator is connected to a current sharing bus causing all other modules to be
connected to this bus via the same resistor. This ensures that all the multipliers of each UPS
module receive the same input and all that modules are equally loaded.

Current
MULT Amplifier
Comparator
K1*V1 +

-
+ PWM
POWER Vout (DC)
-
BLOCK
Triangle

PH1

NEUTRAL

Current
MULT Amplifier
Comparator
K1*V2 +

-
+ PWM
POWER
-
BLOCK
Triangle

PH2

NEUTRAL

Current
MULT Amplifier
Comparator
K1*V3 +

-
+ PWM
POWER
-
BLOCK
Triangle

PH3 Verror

DC
NEUTRAL share K2*Vout
bus -

Integarator Vref

Figure 2-5: PFC control scheme

Power+ Technical Guide 7


Gamatronic Electronic Industries Ltd.

The second stage of the UPS module is the DC/AC inverter.

This stage is fed by the DC symmetrical voltage produced by the PFC stage which then it
inverts to create clean sinusoidal output(s).

POWER+ employs 3-L (3-level) topology which achieves very high efficiency (over 96%)
which in turn enhances the overall AC-AC efficiency of the entire system.

As shown in Figure 2-6 the inverter voltage is produced using three levels of DC voltage
(unlike standard two-level system).

The POWER+ inverter uses Insulated Gate Bipolar Transistors (IGBT) as efficient high
frequency switches.

Apart from the AC/DC PFC and DC/AC inverter each UPS module also contains a digital
controller, responsible for all the control mechanism and all communications with other
modules of the system.

Each UPS module also provides the system controller with a report related to its condition
and operation status. All the data available from all modules is displayed on an LCD display.

The UPS module is cooled using forced convection. The fan varies with the load level,
making for improved reliability, reduced noise, and less dust is introduced.

L
Vr
L
Vs
L
Vt
C
- + - + - + C

C
N

Control

Figure 2-6: DC/AC inverter principal topology

8 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

2.1.1. SINGLE UPS MODULE SPECIFICATIONS

Table 2-1 Single UPS Module Specifications

TECHNICAL DATA UPS MODULE


Output Rated Power 10kVA/8KW
Topology Online Battery, Double Conversion
Construction Modular parallel hot-plugged modules
Input Voltage (V) 3 400+N (3 230V)
Input Voltage range (%) 27 and + 20
Input Current (A) 15A
Input Frequency (Hz) 47-63Hz
Frequency tracking range (Hz) 1, 2, 3 (selectable)
Output slew rate 1 Hz/sec
Power walk-in (sec) > 60
Input Power Factor 0.99
Input THDI (%) 5
Output Voltage (V) 3 400+N (3 230V)
Output Static Regulation (%) 1
Output Regulation for unbalanced load (%) 1 for 100% unbalanced load
Dynamic response to 100% load step (%) 2
110% for 10 minutes
Overload 125% for 60 seconds
1000% for 1 cycle
Output Waveform Sinusoidal
Output THD (%) Less than 2 for linear load
Load CF (max) 6:1
Fuse clearance capability Input, Output, DC link
AC-AC efficiency (nominal) Up to 96 at full load
Maximum power dissipation (Po=8KW) 421W (1437 BTU)
-10 to +40 (operating)
Ambient temperature (C)
-20 to +60 (storage)
Relative humidity (%) 95 max non-condensing
Altitude (m) 1500 w/o de-rating
DC-Link Voltage 340V to 425V
Cooling system Multi-Fan with speed control (forced)
Dimensions (mm) 19"(W), 2U(H), 455(D) Excluding shelf
Weight 9.5Kg

Power+ Technical Guide 9


Gamatronic Electronic Industries Ltd.

2.2. UPS SYSTEM CONTROLLER


The POWER+ system controller is designed primarily for monitoring, diagnostics and
communications.

Some other useful features include temperature compensation of the battery voltage.

The POWER+ can work without the system controller but with reduced functionality.

Figure 2-8 shows the system controller block diagram. The core of the controller is a
powerful embedded micro-controller, surrounded by many peripherals (analog, digital,
communication).

The controller front panel is shown in Figure 2-7.

Figure 2-7: System controller - Front panel

10 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

Figure 2-8: System controller - Block diagram

Power+ Technical Guide 11


Gamatronic Electronic Industries Ltd.

2.2.1. SYSTEM CONTROLLER SPECIFICATIONS

Table 2-2: System controller specifications

TECHNICAL DATA SYSTEM CONTROLLER


Micro Controller core 16 bit
Display 4 x 40 characters LCD with backlight
Other indicators 8 LEDs, buzzer
Analog input channels 4
Digital input channels 8
Real Time Clock (RTC) Yes, with backup
Power meter kVA, kW, PF
Volt-free outputs (dry contacts) 6
RS232 user port Yes, isolated
Optional communication TCP/IP, GPRS/SMS Wireless
communication (Optional)
Communications with system modules Serial, isolated
Events log 255 events
System operation without controller Unchanged
On-screen parameters Load bar-graph
3-phase voltages
3-phase currents
Battery voltage
Status of each UPS module
Static-switch parameters and status
Battery sensor temperature
Alarms AC abnormal
DC abnormal
UPS module(s) failure
Load on bypass
Battery test failed
Over/under temperature
Overload
RTC operation without power 2 weeks
Power requirements 12V10%, 1A via 2.1mm phono jack

2.3. STATIC SWITCH (ST/SW) MODULE


The static switch module is used for overriding the input to output in case of a system failure
or heavy load start or if specifically requested by the user.

The module receives two AC inputs and supplies only one.

Generally the ST/SW connects the output of the paralleled UPS modules to the main output
of the system. However, if the modules fail to provide an adequate voltage for a determined
time, i.e. detection time, the ST/SW module instantly switches to the alternative power
source, that is the AC input, as illustrated in Figure 2-10. The unit employs an efficient AC
switch for this purpose using a combination of fast semiconductors and an
electromechanical relay.
The module monitors all the inputs in real time to determine the method of operation. The
ST/SW modules front panel is shown in Figure 2-9.

12 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

Figure 2-9: ST/SW front panel view

Figure 2-10: ST/SW block diagram

Power+ Technical Guide 13


Gamatronic Electronic Industries Ltd.

Outputs

INV BP

INV BP

INV BP

Monitoring & Control

Figure 2-11: 3-Phase ST/SW block diagram

14 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

3. SYSTEM INTERCONNECTION
The POWER+ system comprises UPS Modules, a System Controller, Static Switch and
distribution elements such as AC, DC and fuses. These components are assembled as
shown in Figure 3-1.

A major advantage of the POWER+ is its upgradability simply by adding UPS modules and
shelves as required.

The system controller occupies the same space as the UPS module and although not
critical, is most often mounted at the top shelf for convenience. This permits easier viewing
of the display. The static switch module however, is always mounted at the bottom of the
system (see Figure 3-1).

Figure 3-1: Power+ system - Modular structure

Power+ Technical Guide 15


Gamatronic Electronic Industries Ltd.

3.1. INTERNAL SYSTEM WIRING


The cabling and wiring of a 30kVA Power+ system are illustrated in schematics in Figure 3-2
(single-phase output) and Figure 3-3 (3-phase output) below.

Figure 3-2: Schematic of a 3:1 Phase 30kVA POWER+ System

Note: For use with single-phase input, all 3 phases of each AC input are connected together
internally inside the cabinet. REFER TO SINGLE-PHASE OUTPUT INSTRUCTIONS.

16 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

Figure 3-3: Schematic of a 3-Phase 30kVA POWER+ System

Cables for the POWER+ are all connected at the rear of the system.

Cables are routed between the UPS modules system controller and static switch down to
the AC and DC distribution sections that are mounted at the bottom of the rack. Figure 3-1
shows the rear view of the POWER+ system. (Note that 3 UPS modules are in use in this
illustration). UPS modules are numbered from bottom to top; i.e. the lowest UPS module is
"UPS #1"; the UPS above it is "UPS #2" and so on.

Power+ Technical Guide 17


Gamatronic Electronic Industries Ltd.

Figure 3-4: POWER+ System - Rear View

18 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

UPS modules are inter-connected by a flat cable which is used for the transmission of digital
and analog data.
This data is essential for maintaining synchronization and current sharing between modules.
This flat cable is connected to a small PCB in the UPS shelf and is connected to the control
DIN48 connector described on page 24.

NOTE:
PROPER CONNECTION OF THE FLAT CABLE
IS OF CRITICAL IMPORTANCE.
INCORRECT OR WEAK CONNECTION
WILL PREVENT THE SYSTEM FROM OPERATING.

Each shelf has a digital address that is preset at the factory and determined by the DIP
switch mounted on the small control board as shown in Figure 3-5.

Figure 3-5: Control PCB and flat cable

Power+ Technical Guide 19


Gamatronic Electronic Industries Ltd.

3.1.1. THE POWER+ ALWAYS REQUIRES A NEUTRAL LINE


During both installation and operation of the Power +, a neutral line must always be
connected to the UPS. This neutral line shall be connected during the entire period that the
UPS is working, and shall not be disconnected at any time!

Caution: If at any time the neutral line becomes disconnected, there will be no input or
output reference voltage, because the input neutral line and the output neutral line are
physically linked together. That may result in system defining its own reference voltage,
which will be set by the load distribution between the three phases. This can result in
serious damage to the UPS.

A 4-pole switch might disconnect the neutral line


WARNING! If you have a mains-to-generator four-pole switching system you are in danger
of having the neutral line disconnected when the four-pole switch is operated. This can
result in the problems described above.

To avoid these problems, we strongly recommend that, if you use a four-pole mains-to-
generator switching system, you install an isolation transformer that will constantly provide
the UPS with a neutral line.

Figure 3-6 on page 21 illustrates the wrong way to connect the UPS with a grounded-neutral
generator.

Figure 3-7 on page 22 illustrates an acceptable connection solution if you already have a
grounded-neutral generator.

Figure 3-8 on page 23 shows the preferred generator (neutralized, not grounded) and the
preferred connection (three-pole).

20 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

Figure 3-6: Wrong way to connect UPS with grounded-neutral-generator

Power+ Technical Guide 21


Gamatronic Electronic Industries Ltd.

Figure 3-7: Acceptable connection for grounded generator and 4-pole switch

22 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

Figure 3

Figure 3-8: Preferred generator (neutralized) and connection (3-pole)

Power+ Technical Guide 23


Gamatronic Electronic Industries Ltd.

3.1.2. UPS MODULE CONNECTORS DESCRIPTION


The UPS module includes three connectors (see Figure 3-9) on the rear panel. Two 15-pin
DIN connectors (DIN15) are for power connections and one 48-pin (DIN48) DIN
connector for signaling and control.

WARNING
ALL THE CONNECTOR PINS CARRY HAZARDOUS VOLTAGES
ALWAYS AVOID ACCESS TO THESE PINS!

Input Connector Output Connector Control Connector


(15-Pin DIN) (15-pin DIN) (48-Pin DIN)

Figure 3-9: UPS module Rear view

The connectors pin assignments are illustrated in Figure 3-10 and described in Table 3-1
below.

a b c
1
2
3
4
5
6
30 26 22 18 14 10 6 7
b8
8
9
10
32 28 24 20 16 12 8 4 11
12
"DIN 15" CONNECTOR 13
14
15
16

"DIN 48" CONNECTOR


Figure 3-10: UPS module connectors - Pin assignments

24 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

3.1.3. UPS MODULE PIN ASSIGNMENT TABLE

WARNING
THE DATA PROVIDED BELOW IS FOR INFORMATION ONLY.
DO NOT ATTEMPT TO MAKE ANY CONNECTIONS.

Table 3-1: UPS module pin assignment and function


Input Connector
4 = (-425V) 6 = (-425V) 8 = (-425V) 10 = Neutral 12 = Neutral
14 = T phase 16 = T phase 18 = S phase 20 = S phase 22 = R phase
24 = R phase 26 = Neutral 28 = (+425V) 30 = (+425V) 32 = (+425V)

Output Connector
4 = OUT3 (T) 6 = OUT3 (T) 8 = OUT2 (S) 10 = OUT2 (S) 12 = OUT1 (R)
14 = OUT1 (R) 16 = N.C. 18 = N.C. 20 = N.C. 22 = Neutral
24 = Neutral 26 = Neutral 28 = N.C. 30 = N.C. 32 = N.C.

Control Connector
"a" Column "b" Column "c" Column

1 = System Controller Com 1 = Controller TX 1 = Controller RX


2 = Dry2_opto_E 2 = N.C. 2 = N.C.
3 = Dry2_opto_C 3 = N.C. 3 = N.C.
4 = N.C. 4 = N.C. 4 = N.C.
5 = N.C. 5 = N.C. 5 = N.C.
6 = DRY 0 6 = UPS OFF 6 = Vout_Sum
7 = DRY 1 7 = CAN BUS 7 = WANT
8 = +12V BUS 8 = Stand Alone 8 = Vcc (+5V)
9 = Force B/P Inv 9 = AC on INV 1 9 = Address Com.
10 = Common BUS 10 = Common BUS 10 = Common BUS
11 = Dry 2 11 = Device Address (#3) 11 = PLL DATA BUS
12 = Reference Frequency 12 = Device Address (#2) 12 = PLL SYNC BUS
13 = SPI Select 13 = Device Address (#1) 13 = Sharing BUS (S)
14 = MIS 0 14 = Device Address (#0) 14 = Sharing BUS (R)
15 = MIS 1 15 = +12V BUS 15 = Sharing BUS (T)
16 = SPI_SCK 16 = Address Common 16 = +12V BUS

Power+ Technical Guide 25


Gamatronic Electronic Industries Ltd.
Legend
N.C. = Not Connected (Unused)

PLL = Phase Locked Loop (Synchronization system)

Sharing = Current Sharing circuit (Among modules)

Device Address = Identifies the location of a UPS module within the system

WANT / CAN = Signals related to the parallel mechanism

3.2. DC DISTRIBUTION PANEL CABLING

WARNING
BATTERY CABINETS MAY BE CONNECTED AND
MAINTAINED BY A QUALIFIED TECHNICIAN ONLY!!!
NOTE:
The Neutral line is common to the input and
output as well as to the battery "0V" point!

The DC distribution panel is located at the bottom of the system on the rear, below the first
UPS module (UPS #1).

This panel receives the DC wires from the systems UPS modules and from the controller, as
well as from internal or external battery cabinets.

The DC voltages are very high and dangerous ( 425Vdc).

External battery connections are performed at the right side of this panel.

The DC distribution panel on your system will have one of two possible layouts, depending
on whether your system has a maximum capacity of 50KV or 100KV. maximum capacity, as
shown in Figure 3-11.

The Anderson connector plugs on the DC distribution panel are color coded: RED=positive,
BLACK=negative, BLUE=neutral.

Refer also to Figure 6-3 on page 64 for battery connection details.

26 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

Figure 3-11: DC distribution panel (50KVA model)

Figure 3-12: DC distribution. panel (100kVA model)

Power+ Technical Guide 27


Gamatronic Electronic Industries Ltd.

3.2.1. DC FUSES
All DC fuses are located on the opposite side (the front side) of the DC distribution panel.
There are two fuses for each power module and for the controller one for the positive line
and one for the negative line. Figure 3-13 and Figure 3-14 show the assignments.

Figure 3-13: DC fuses on front side of DC dist. panel (50KVA model)

Figure 3-14: DC fuses on front of DC dist. panel (100KVA model)

28 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

3.3. AC INPUT FUSES


The input of each UPS module is protected by a 15A fuse for each phase, so that each
module, including the controller, has 3 fuses (for R, S, T phases). 10 modules plus the
controller would require 33 fuses, as illustrated in Figure 3-15. Fuse receptacles are
numbered from right to left, i.e. the 3 fuses on the far right protect UPS #1.

Figure 3-15: UPS modules - AC input fuses (100KVA model)

WARNING
ALWAYS REPLACE FUSES WITH THE SAME TYPE AND RATINGS !!!

Figure 3-16: AC input fuse assignments (50KVA model)

Power+ Technical Guide 29


Gamatronic Electronic Industries Ltd.

3.4. AC DISTRIBUTION COMPARTMENT


The AC distribution compartment (Figure 3-17) distributes AC voltages to and from the UPS
modules and is located on the rear of the UPS, below the DC distribution panel. Connections
are as shown below.

The AC input to the modules are protected by the AC fuses as described above.

Figure 3-17: AC distribution

Figure 3-18: AC distribution panel (100KVA model)

Figure 3-19: AC distribution panel (50KVA model)

30 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

3.5. AC INPUT/OUTPUT MAIN TERMINALS


The main terminals section is critical for system installation. The terminals are used to
connect the AC inputs and AC output to the mains electricity cabinet. The terminals section
is illustrated in Figure 3-20. The installation procedure is detailed in Section 4.

NOTE:
The Neutral line is common to the input and
output as well as to the battery "0V" point!

Figure 3-20: Input & output main terminals

Power+ Technical Guide 31


Gamatronic Electronic Industries Ltd.

3.6. STATIC SWITCH CONNECTIONS


The static switchs internal connections include two AC inputs and one AC output.
As shown in Figure 3-21, three groups of terminals are located accordingly on top of the unit.
A separate terminal is dedicated for the Neutral line (which does not carry current) and is
used for measurements.

This module communicates with the rest of the system via the communication port located at
the right side of the unit.

Additional terminals are provided as shown for Emergency Power-Off (EPO) and for Load
On Bypass indication.

Figure 3-21: Static switch terminals Rear view

32 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

3.7. SYSTEM CONTROLLER CONNECTIONS


The controller is typically located in the top housing shelf of the UPS for easier access.

Although the UPS modules reads their digital address number from the Control PCB
(discussed later) the controller does not!

Connections to the System Controller are from the rear, as shown in Figure 3-22.

NOTE:
Several Controller options are available
(e.g TCP/IP, cellular and more).
Refer to your dealer for further details.

Figure 3-22: System controller outside the shelf - Rear view

Power+ Technical Guide 33


Gamatronic Electronic Industries Ltd.

3.8. SETTING THE SHELF ADDRESS


Each UPS module shelf including the controller module shelf has a digital address that
can be accessed by the module once it has been initialized. The module addresses are used
to identify each module during the normal operation and monitoring of the system.

No two shelves can have the same address. The address is related to the physical location
of a specific shelf, and is preset at the factory by the Module Location DIP switch
mounted on the control PCB. (See Figure 3-23). When adding a new module to an existing
system, the address of the newly added shelf must be set correctly.

The control PCB contains an additional DIP switch the Master/Slave DIP switch that
is used to indicate which of the UPS modules is the Master, and which UPS modules are
the Slaves. Only one UPS module is designated as Master; all of the other UPS modules
are Slaves.

Figure 3-23: The PC917 Control PCB on a shelf general view

34 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

Figure 3-24: DIP switches on PC719 card close-up

Figure 3-24 shows the DIP switches on the PC719 card, which is located on the back of
each shelf housing a UPS or the controller module.

Master/Slave DIP Switch Settings


The two DIP switches on the left determine which UPS will be the master UPS. Best
practice is to make UPS#1 (the first UPS) the master, and let the others be slaves.

Figure 3-25: Recommended master/slave DIP switch settings

Power+ Technical Guide 35


Gamatronic Electronic Industries Ltd.

Module Location DIP switch Settings


In the example shown the FIRST UPS DIP switch is set as follows:

1= "on", 2= "on", 3= "on", 4="on, indicating UPS #1. See Table 3-2 below and FIGURE
3-26.

Table 3-2: DIP switch setup in a 100kVA system (X = don't care).

Figure 3-26: DIP switch settings

Lowest Module Select (LMS) jumper: The first module (UPS #1) must be assigned as
such by a jumper on the MOLEX-2 connector.
Other versions of the Control PCB may have a 2 level DIP switch instead of this connector,
in which case both switches must be ON.

36 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

3.9. F.A.Q. (FREQUENTLY ASKED QUESTIONS)

3.9.1. BATTERIES

Q. What is the DC voltage of the system? What is the number of batteries


needed?
A. The nominal DC voltage of the system is 424v to 432. Power Plus units operate with positive
and negative voltage independently. There are 64 batteries in series in each battery bank, with a
middle connection point which has additional wire connected, so there are two groups positive and
negative, 32 batteries in each. The DC voltage is measured between the center point and one of the
poles. The middle point is interconnected with the input neutral. If the DC voltage is measured
between the positive side and the negative side, it will be in range of 848v to 864v DC.

Q. Why should the battery capacity be entered in the system controller?


A. The battery capacity has to be entered for the calculation of the battery test duration. Power Plus
units offer smart battery handling, and one of the features is a smart battery test. It uses the relevant
information to provide the best information about the current battery status. This information includes
global battery Ah rating, current load level, battery current (if available) and some calculations.

Q. What will happen if the battery capacity was not setup correctly?
A. Right values of Ah battery capacity should be entered; otherwise the reliability of the smart battery
test will be lower.

Q. Why does my battery test last for more then 1 minute?


A. Battery test can last for a number of minutes, it is not a problem. For a unit with large batteries and
low load, checking the battery condition in the best way will take more then one minute. Power Plus
units have smart battery test feature implemented, which discharges the batteries by 5% of the
capacity during the test to check them in the best way.

Power+ Technical Guide 37


Gamatronic Electronic Industries Ltd.

Q. What is the maximum charging current for the batteries?


A. Under full load each module can provide 1.3A to charge the batteries. In case that a module is not
loaded, the entire rectifier current (11.7A) can be passed to the batteries. Another example, if one
module is loaded at 50% on the output it can provide around 6.5A to the batteries. This means that in
Gamatronic systems with on-line battery topology all current that doesnt go to inverter is available for
battery charging.

Q. Should the battery current limit feature be activated?


A. The battery current limit is an optional feature. Before enabling it please make sure that you have
this option in the system. In order to check it, please see the rear side of the controller. There are
three battery current sensors connections there, in a green plug. If nothing is connected there, then
this option is not available in your system and must be disabled.

Q. Why should I use the battery current limit? If I activate it, what
parameters do I use?
A. Correct parameters for battery current limit are specified by a battery manufacturer, in a datasheet.
It improves the battery lifetime and protects from overcharging. Caution: Incorrect setting might cause
unexpected system operation.

Q. Should the battery temperature compensation be activated?


A. The battery temperature compensation is an optional feature, which consists of a temperature
sensor with wires for specified length for external or going into the unit for internal batteries. It
connects to the rear side of the controller, to a green plug with its own specific connection. Before
enabling this feature, make sure you have it in your system.

Q. Why should I use the battery temperature compensation? What is the


correct value?
A. The battery temperature compensation should be corrected according to the battery
manufacturers recommendations; it protects the batteries form overcharging in a high temperature
environment.

Q. When the Ah value for the batteries is entered, and there are two or
three battery cabinets selected, will the unit add the entered values or
divide them between the cabinets?
A. If the number of battery cabinets is set to more than one, then you will have to select the battery Ah
rating for each battery cabinet independently, as it can be different. Eventually the unit will add these
values and obtain the global Ah value.

38 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

3.9.2. GENERAL

Q. Does Power Plus unit have equalizing (boost charge) mode?


A. Gamatronic UPS systems do not use equalizing (boost) battery charging. If you have equalizing
menu entry in your controller menu, please arrange software version upgrade for your controller.

Q. What will happen to the unit if the system controller is removed?


A. When the controller is removed, the system will continue with normal operation, including battery
charging and backup operation upon power failure. It will also start normally when mains power is
turned on.

Q. Can I use the system without system controller module at all?


A. Yes, the UPS system will provide the basic functionality; however, many important features will not
be available. Major features include battery test, measurements, control etc. Without a system
controller the system will function as a rectifier, batteries and an inverter (with ST/SW) only with no
additional features. This kind of operation is not recommended.

Q. How can this system work as a single and triple phase (selectable) on
the input?
A. This unit features advanced rectifier technology which allows you to connect triple phase voltage to
the inputs or just a single phase linked together on R (L1), S (L2) and T (L3) inputs. The unit will
accept both connection types on the input, no additional settings are needed.

Q. How can this system work as a single and triple phase (selectable) on
the output?
A. The special inverter function allows single phase output operation. To switch the system to single
phase operation, each UPS module should be removed while the system is off and its dip switch
number 3 (they are located in a small window on the left side of each module) should be moved to the
OFF position (ON for 3 phase output operation). Then the output phases R (L1), S (L2) and T (L3)
should be linked altogether to a single phase wire output (used with the output neutral), as the phase
angle will be switched to 00 and each module will have its inverters operating in parallel.

Q. How can this system be switched to 60Hz output?


A. The unit will auto-detect input frequency and have same frequency on the output. To switch the
system to 60Hz output operation manually, each UPS module should be removed while the system is
off and its dip switch number 2 (they are located in a small window on the left side of each module)
should be moved to the on position (off for 50Hz or auto-detect output operation).

Power+ Technical Guide 39


Gamatronic Electronic Industries Ltd.

Q. How will the ST/SW module react to a change from triple to single
phase and vice versa on the output?
A. The bypass input of the unit should fit the output voltage. If the output voltage is triple phase, then
the bypass input should be triple phase as well. If the output is single phase, and the output phases
are linked altogether, then the same thing should be done with the bypass input of the unit one
phase connected and the R (L1), S (L2) and the T (L3) inputs of the bypass linked altogether. The
ST/SW module will detect it and function as a triple or single phase unit automatically.

Q. Does this unit have dry contact outputs, and for what alarms?
A. These systems have 6 dry contacts on the controllers rear panel. Two of them are in a DB9
connector (pins 3, 4 alarm no. 1 and pins 5, 4 alarm no. 2). The other four are located in a marked
wide green connector with screw wire attachments. There are N.O., N.C. and the COMMON
connections for each dry contact. All dry contacts are programmable through the controller, selectable
from the global list of 32 alarms. Any number of alarms can be set for any dry contact. All the contacts
are rated at 24V 1A.

Q. Does this unit have input dry contacts?


A. There are 4 input normally closed dry contacts, located in specific green plug on the rear side of
the system controller. As a standard they are all linked to the common on the plug, and provide no
alarms.

3.9.3. MENUS

Q. What is the alarm hysteresis setting?


A. The voltage alarm hysteresis is the value of voltage difference for finalizing the alarm. For example,
if the alarm value is 245v and the hysteresis is 5v, then when the voltage grows above 245v and the
alarm will activate, it will end only when the voltage drops below 240v.

Q. What is the Integrat. menu entry?


A. The Integrat., which is the integration factor, is a value for confirming the internal RS232
communications. This option should not be changed usually and is preset for optimal performance.

Q. Why should I use the individual UPS module turn on/off feature?
A. The individual UPS turn on/off feature is disabled.

40 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

Q. Why are there two settings for a number of UPS modules in the system?
A. A total number of modules represent the units with which the controller will communicate and
monitor. The redundancy number of modules shows how many units are functioning as a backup,
without being calculated in a global load level of the system. For example, if you have a 30KVA unit
with a setting for 1 redundant module, when the output load will reach 20KVA the unit will show a full
load condition. It will still not switch to bypass, but will alarm you with overload if the output load will
rise above 20KVA. For the user this means that the unit does not have the redundancy anymore
under this load. If the redundant modules value is set to 0, then a 40KVA unit will function as a
standard unit of 40KVA output load maximum. It you set this parameter to 3, the same unit will have a
load bar-graph of a 10k system and will alert the customer with overload when there is more then 10k
of load on the output.

Q. What is the DC-I offset removal and the DC-I calibration menu entries?
A. The DC-I offset removal and the DC-I calibration should be performed only if the battery current
measurement is not correct. It is being used on new controllers only upon current sensors connection.
You might have do use these features if adding current sensors on a later stage. To perform it the unit
should work without a load and with batteries disconnected. Then the offset removal should be
preformed (only if the measurement current is not zero) and then the unit should be connected to
some load and batteries and operated in input power failure mode. Then the actual current is being
measured and corrected live in the controller using the calibration menu entry.

3.9.4. INSTALLATION

Q. Does the unit have EPO (Emergency Power Off) connection?


A. Yes. The connection is on the ST/SW module. Unscrew two mounting screws on the front panel of
the ST/SW module and slightly pull it out. The EPO connection is on its top.

Q. When the EPO is deactivated, the unit still wont return to normal
operation. Why is that?
A. When the EPO function was activated, the unit stopped functioning and provided voltage to battery
breaker trip coil (option of the battery cabinet) to switch the batteries off as well. To restore normal
operation of the UPS system, it should be completely restarted.

Q. Upon the installation, the unit wont switch to inverter and the Sync
LED on ST/SW module is in red. Everything else is ok. Why is that?
A. Usually this means that the phase sequence on the ST/SW input (the bypass) is not correct. These
units get synchronized on the bypass and therefore check the phase sequence there. Swapping
phase S (L2) and T (L3) on the bypass input should correct the situation.

Q. When I press the Inv/Byp button on the ST/SW module, it doesnt switch
to/from bypass. How do I do the manual transfer?
A. The Inv/Byp button is a press and hold button for protection. It should be held for a number of
seconds until the alarm LED lights in green, and then released. There is the same button on the
controller; there it should be pressed twice to initiate a manual transfer.

Power+ Technical Guide 41


Gamatronic Electronic Industries Ltd.

Q. Does this unit have dual inputs?


A. Power Plus systems, as any other standard Gamatronic systems above 10Kva, use dual inputs,
meaning independent input for the rectifier and a bypass input for the ST/SW.

Q. What should be the connection wire size in mm2?


A. The wires should fit he current they stand for. Each P+ module consumes 15A of current maximum
on the input of each phase. This current has to be multiplied by the total number of modules. Each
country can have different accepted standards for wire size assignment. The size of the neutral wire
should stand for 1.5 times the maximum current of the phase wires, because the rectifier in each
phase works with the neutral independently. When connecting a unit with two input cables, the neutral
wire is double size anyway because the input and the bypass of Power Plus have single common
neutral connection.

Q. Is there a neutral connection on the input and the output of the unit?
A. Power Plus units operate with neutral on input and on the output. To achieve three-phase
operation without neutral delta to star (or the opposite for output) transformers can be used.

Q. What is the terminals type of the unit for the installation?


A. The terminals are 70mm screw type on all models. To connect you will need to use cable ends with
your cables with 8mm or 10mm hole.

Q. Does the unit have dry contact for the Load on bypass signal?
A. Yes, it is located on the ST/SW module. Unscrew two mounting screws on the front panel of the
ST/SW module and slightly pull it out. The dry contact connection is on its top, 230v rated, usually for
use with electricity switchboards with make-before-break load transfer function for protection.

3.9.5. MECHANICS

Q. There are 50/40KVA and 100/80KVA ST/SW modules. Why?


A. There are two types of ST/SW modules, for 50/40KVA and for 100/80KVA. For example, for a 30k
unit you should think if after all additional upgrades (an additional module each time) more then
50KVA load will be reached. If so, then its better to order a unit with ST/SW module for 100Kva. Of
course, there is a price difference. Dont forget that the base module for these units can also be
50/40Kva or 100/80Kva. So, every customer might require different solution.

Q. How can the unit be upgraded if there are no free shelves?


A. In these systems the housing is modular. In order to upgrade the system with a new module an
additional shelf should be installed. This is a simple process, which might take no mode then half an
hour for single person.

3.9.6. COMMON PROBLEMS

Q. An alarm LED is in red on the front panel. How can I quickly understand
what is wrong?

42 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

A. On the left side of the controller there is an alarm off button. When you press it, you will see the
list of all the alarms for the system and their state. They can be browsed using the up and down
arrows. The active alarms will have an asterisk (*) sign near them.

Q. When I look at the list of the alarms, I can see some alarms which are
always on. Why is that?
A. There is a number of alarms that might be on. One of them is the STRTUP alarm, which stands
for the startup time stamp. This alarm only means that the unit is on, and it will not raise an alarm
signal. Other alarms can be the user alarm 1-4, which are the input dry contacts. If they are not in
use, you can disable them through the controller menus.

Q. What will happen if the equalizing mode was activated in the unit?
A. The equalizing mode should always be set to DISABLED, this feature is not available. If you had it
on in your system, please note that it could simulate a failure condition and a shutdown to the
computers. On all the units today this feature is absent. Please contact your Gamatronic
representative to upgrade your controller software version.

Q. The unit always shows battery test fault alarm. The batteries are OK.
What is wrong?
A. On some older systems the controller might show false battery alarms. This was corrected, so in
case that you have this problem and positively sure that the batteries are alright, please contact your
Gamatronic representative to upgrade your controller software version. After you perform this action,
the unit will still show battery test fault. Please perform manual battery test to restore normal
operation.

Power+ Technical Guide 43


Gamatronic Electronic Industries Ltd.

4. SYSTEM INSTALLATION
RISK OF ELECTRICAL SHOCK OR INJURY!
INSTALLATION MAY BE PERFORMED BY
QUALIFIED TECHNICIAN ONLY!
WARNING
Figure 4-1 illustrates the cabling of the POWER+ system to the mains electricity cabinet.

Figure 4-1: POWER+ system connections

44 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

Figure 4-2 below shows required switch and wire ratings for 10-100kVA installation.
For battery connections, see Figure 6-3 on page 64.

Figure 4-2: Switch and wire ratings for 10-100kVA installation

POWER+ 400 V MODEL


S2 S6 RA101
UPS OUTPUT WIRES
AND RA101 (OPTION)
CAPACITY (KVA) (mm2)
(AMPS) (AMPS)

10 16 2.5 32

20 32 6 63

30 50 10 100

40 63 16 120

50 80 25 140

60 100 35 175

70 100 35 200

80 125 50 225

90 140 50 250

100 160 50 300

Power+ Technical Guide 45


Gamatronic Electronic Industries Ltd.

4.1. INSPECTIONS TO BE PERFORMED PRIOR TO


INSTALLATION
Value,
Type of check Requirement
Verification

Ambient temperature in the immediate Recommended: between 15C and 25C


1.
location of the equipment
Required: between 0C and 40C
Verify that there is no water condensation or
2. Humidity and condensation
dampness within the installation site

3. Ventilation Verify that sufficient airflow or forced ventilation is


provided for battery cabinets location

Verification of adequate structure, space and


4. Foundation and route to installation site clearance for dimensions and weights of the UPS
units and their battery cabinets
When planning the location of the UPS
5. Verify 40 cm clearance at rear for cable connections
units, room for access to battery
and 100cm at front for user access and service
cabinets and electrical boards is critical.
Circuit breakers on the electrical board Must be in accordance with Gamatronic system
6.
supplying the system specifications and connection schematic
Diameter of input and output power Must comply with local and international codes, and
7. cable connections, PE (Gnd) and neutral be appropriate for the circuit breakers protecting
lines. them. Refer to connections schematic.
Voltage surge suppressors type B must be installed
Lightning / Voltage surge protection on between each phase and the neutral line:
8.
electrical board supplying the system.
Ratings: 300VAC for 220-230VAC mains.
R-S
Phase-to-Phase: 380*VAC, +10%, -15% S-T
T-R
9. AC input voltage
R
Phase-to-Neutral: 220*VAC, +10%, -15% S
T
10. Voltage between neutral and ground 0 2 VAC
Must be performed only by authorized personnel in
11. System installation and start-up accordance with connection schematic, Gamatronic
system specifications and this User Guide

* Or other, according to nominal voltage rating of local power mains.

46 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

4.2. INSTALLATION PROCEDURE AND SYSTEM START-UP


Operation

Remove rear covers and connect AC input and output power cables to terminals according to markings as shown
1. in this User Guide and according to connection schematic.
Verify correct phase sequence between board and UPS

Connect ground lines to busses according to markings as shown in the connection schematics (Figure 3-2 on
2.
page 16, Figure 3-3 on page 17, Figure 4-1 on page 44). Verify secure connections.

Connect the DC power cables of the battery cabinets to the UPS terminals according to markings as shown in
Figure 4-1 on page 44 and Figure 6-3 on page 64. Connect neutral and ground lines to busses as above.
3. Verify correct polarity of the connections (+ / N / -) Between the Battery Cabinets C.B.s / Terminals and the UPS
terminals. Auxiliary contacts of Battery C.B.s are connected to UPS Controller inputs Bat CB and Com as
marked, and as shown in Figure 7-2 on page 66.
An external dual-pole / N.C. EPO switch may be connected according to connection schematic.
4.
EPO wiring and switch rating must be rated for at least 5A / 230VAC.
Before connecting power to each system verify again that all connections are secure and are according to
5.
instructions and schematics.
6. Follow the instructions in section 4.3, Initial Start-up Sequence, on page 48.

Power+ Technical Guide 47


Gamatronic Electronic Industries Ltd.

4.3. INITIAL START-UP SEQUENCE


Note: Before first setting up the UPS, make sure that the load is not connected.

1. Ensure that the maintenance bypass switch (if installed) is disconnected.


2. Turn the AC input and AC bypass switch ON and wait (for about 2 minutes) for the
POWER+ to initialize.
When applying power to the POWER+, the system automatically runs the startup
process without a need to press the On/Off button.
The start-up sequence will begin and the control panel will show the following
sequence. (The details will vary, depending on your application.)
During this step, the LEDs are also checked sequentially.

Power up

Start-up 1

Figure 4-3: Start-up screen 1

Power up

Start-up 2

Figure 4-4: Start-up screen 2

Power up

Start-up 3

Figure 4-5: Start-up screen 3

Power up

Start-up 4

Figure 4-6: Start-up screen 4

48 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

3. Ensure that you have a normal reading on the System Controller display. The bar
graph on the left side displays loads of all 3 phases as shown in Figure 4-7.

Power up

Default
window

Figure 4-7: Normal display of the controller LCD (default)


4. Switch all battery switches ON on all battery cabinets.

Checks to be performed following initial startup


Type of check Requirement

Phase to Phase:
AC input voltage during operation under load. Not less than 2% below no-load values measured in item 5 below.
1. Take measurements on the input terminals of
the system Phase to Neutral:
Not less than 2% below no-load values measured in item 5 below.
With no load on the system, measure current
2. Irst should be <15A
circulation between the units.
With no load on the system, measure the DC Total DC voltage between + and terminals should be
3.
voltage of the system. between 850V and 880V.
Voltage between neutral and ground during
4. operation under load 02VAC
On the input terminals of the system
220V +/- 2%
5. System output voltage
or other according to system specifications
Verify that the system is not overloaded in relation to system
6. Total system load / output current
specifications
Verify that the UPS is operating normally in accordance with this
7. Correct and orderly operation
User Guide and that no alarms or fault indications are evident

NOTE: It is the responsibility of the customer to notify Gamatronic Electronic Industries Ltd. and receive
approval for any deviations from these requirements.

Power+ Technical Guide 49


Gamatronic Electronic Industries Ltd.

4.4. CHECKS TO BE PERFORMED FOLLOWING INITIAL


STARTUP
Type of check Requirement Result

R-
S
Phase to Phase:
S-
Not less than 2% below no-load values measured in T
AC input voltage during operation under load. item 5 below.
8. Take measurements on the input terminals of T-
the system R
Phase to Neutral: R
Not less than 2% below no-load values measured in S
item 5 below. T
With no load on the system, measure current
9. Irst should be <15A
circulation between the units.
R
With no load on the system, measure the DC Total DC voltage between + and terminals
10. S
voltage of the system. should be between 850V and 880V.
T
Voltage between neutral and ground during
11. operation under load 02VAC
On the input terminals of the system
220V +/- 2%
12. System output voltage
or other according to system specifications
Verify that the system is not overloaded in relation to
13. Total system load / output current
system specifications
Verify that the UPS is operating normally in accordance
14. Correct and orderly operation with this User Guide and that no alarms or fault
indications are evident

NOTE: It is the responsibility of the customer to notify Gamatronic Electronic Industries Ltd. and receive
approval for any deviations from these requirements.

50 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

4.5. SPECIAL CONSIDERATIONS FOR 1-PHASE OUTPUT


This section discusses some special considerations for Power+ UPS System single-phase
output (3/1 and 1/1 configuration).

4.5.1. DIP-SWITCH SETTINGS ON THE MODULES


1. On the left side of each module, close to the front panel is a small window with access
to three dip-switches.
2. For standard three-phase input and output (3/3 configuration) dip-switch no. 3 is set to
ON(LEFT) position.
3. For single-phase output (3/1 or 1/1 configuration) set the dip-switch no. 3 to
OFF(RIGHT) position on all of the modules of the System.

4.5.2. WIRING OF INPUT AND OUTPUT TERMINALS


1. For 3/1 configuration (Three phase input and single-phase output) the Bypass AC
input terminals R,S&T must be shorted between them with 35mm wiring and so must
be the AC output terminals R,S&T.
2. For 1/1 configuration (Single-phase input & output) The UPS (Rectifier) AC input
terminals R, S & T must also be shorted between them.
3. Illustrations of 3/3 3/1 and 1/1 External wiring configurations are presented in attached
files.

Power+ Technical Guide 51


Gamatronic Electronic Industries Ltd.

4.5.3. SYSTEM START-UP


After start-up of the system the POWER+ controller automatically displays the Phase
readings according to the System configuration.

Table 4-1: Power Configuration DIP Switch Settings

Switch Purpose Set left (on) Set right (off)

SW1 Master module Preferred master Automatic via


preference select(not used) console

SW2 Output power 60 Hz 50Hz


frequency selection

SW3 Output power phase 3-phase Single-phase


selection

Figure 4-8: Example of dip switch setting for 3/3 phase, 50 Hz UPS

52 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

4.6. DIP SWITCH SETTINGS OF THE UPS MODULES


y Dip switch #1(in bottom) should always be OFF(RIGHT), designed for manual master
operation in stand-alone mode.
y Dip switch #2(in middle) should be ON(LEFT) for 60Hz and OFF(RIGHT) for 50Hz
inverter operation.
y Dip switch #3(in top) should be ON(LEFT) for 3 phase and OFF(RIGHT) for 1 phase
inverter output.

NOTE: All settings must kept the same on each of the modules in a single system.

The location of the dip switches on a UPS module is shown in the picture below.

Power+ Technical Guide 53


Gamatronic Electronic Industries Ltd.

5. USING THE SYSTEM CONTROLLER


From the default system screen (the Main Screen), pressing the "ENTER" button displays
the main menu.

Figure 5-1: The controllers main menu

Table 5-1: Controller main menu options


SYSTEM General information such as voltages, currents etc.
UPS Information for a specific UPS module
SELFTEST Self checking of the Controller's components (supply, RTC, memory)
HISTORY History log events (last 255 events, dated and timed)
BATTERY Charging / discharging voltages and currents, battery test etc.
ALARM Detailed alarm status
SETUP Configuring the system (number of modules, alarm, time etc.)
STATIC SW Static Switch data
COMM Determining the type of communication (TCP/IP, RS232 or WING)

54 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

5.1. SYSTEM INFORMATION DISPLAY

Figure 5-2: Main menu option 1 ("System")

The SYSTEM option on the Main Menu (option 1) shows the DC voltages and current
(positive, negative and summary):

Figure 5-3: System DC voltages

Power+ Technical Guide 55


Gamatronic Electronic Industries Ltd.

1. From the DC voltages screen, scroll down to view the three-phase input and
output total voltage and current:

Figure 5-4: Overall phase voltages/currents

2. From the DC voltages screen, press the key to view the current output power
factors 2.

Figure 5-5: Output power factor 1

3. Press again to view the current input power factor.

Figure 5-6: Input power factor 1

4. Press "ENTER" again to return to the menu (Figure 5-1).

2
1KVA is 1000 VA. Apparent power is measured in VA which is a reactive (i.e. a mix of both
capacitive and inductive) loads RMS voltage multiplied the RMS current. True power is VA multiplied
by the power factor, and the power factor is the cosine of the phase angle between voltage and
current. A reactive load that draws an apparent power of 1000VA and has a 0.5 power factor is
consuming 500 watts of power. If a device were purely inductive, it would have a power factor 0. See
also footnote 1, on page 4.
56 Power+ Technical Guide
Gamatronic Electronic Industries Ltd.

5.2. DISPLAY UPS MODULE DATA

1. From the Main Menu, select option 2 UPS MODULE. The message shown in
Figure 5-8) appears.
2. Use the and keys to scroll between UPS modules. The display shows the
voltage and current measurements for each module (see Figure 5-9 on page 58).
3. Scroll and keys to view additional information for the specific module chosen
(see Figure 5-10 on page 58).

Figure 5-7: Main Menu option 2 (UPS Module)

Power+ Technical Guide 57


Gamatronic Electronic Industries Ltd.

Figure 5-8: LCD Panel Selection

Figure 5-9 and Figure 5-10 show parameters for the first module of a UPS system with four
modules. (UPS: #01/04).

Figure 5-9: Module phase voltages/currents

Figure 5-10: Battery voltages, I-active current

58 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

5.3. SETTING THE NUMBER OF UPS MODULES


(The default system password is 8 left arrows [8x<]. To change the password, see 10.2,
Setting Password Level 1 on page 79.

1. From the Main Screen, press Ent to display the Main Menu
2. Select "7>SETUP" (Figure 5-1).
3. Enter the password and press Ent (default password is 8 x <).
4. Select "8>Service" (Figure 5-11).
5. Select "5>Configure" (Figure 5-12).
6. Select "2> # of UPSs" (Figure 5-13).
7. Set the number of UPS modules by using the and keys (Figure 5-14).
8. Press Enter to complete the setup.
The controller applies and saves the new number of modules.

Figure 5-11: Controller menu #2

Figure 5-12: Controller menu #3

Figure 5-13: Controller menu #4

Figure 5-14: Number of UPS modules

Power+ Technical Guide 59


Gamatronic Electronic Industries Ltd.

5.4. RETRIEVING HISTORY (LOG OF EVENTS)

1. Select "4>HISTORY" (Figure 5-1). The last 255 events reserved in the LOG are
displayed, as shown in Figure 5-15.
2. Navigate the LOG by scrolling using the and keys.

Figure 5-15: Log display

5.5. CONTROL COMMUNICATIONS


Note: The availability of the COMM option (option 9) on the Main Menu is optional, and depends on
the factory configuration of your UPS.

1. From the main menu (Figure 5-1), select item 9, COMM.


2. Select the appropriate mode using the and keys.

Figure 5-16: Communications

60 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

5.6. SYSTEM CONTROLLER ALARMS


System Controller alarms are described in Table 5-2.

Table 5-2: System controller alarms

AC-BRN Input AC supply Brown Out


ACFAIL AC input failure
ACIN_H AC input excessive
BAT-CB Battery Circuit Breaker Open
BATEND End of battery backup. Battery is discharged to shutdown limit
BATFLT Batteries failed last test
BAT-HI Excessive battery voltage
BATLOW Low battery voltage
CURSHR Current Sharing fault, load current is not equally divided between modules
E.P.O. Emergency Power Off is active
Battery is currently charging in equalizing mode, dc voltage is temporarily
EQ-HST
increased
LOADBP Load is now running on bypass
OUTFLT No AC output to load
OVLOAD Load current is high
OVTEMP Excess temperature
SLFFLT Last controller self-test failed
STRTUP Startup time-stamp
STSWCM Static Switch does not respond
STSWRN Static Switch Warning or alarm
UPS-CM One or more UPSs not responding
UPSHDN UPS shutdown by EPO, Battery Discharge, ON/OFF pressed
UPSMAJ More than 1 UPS Module is sending an alarm or fault warning
UPSMIN Single UPS Module is sending an alarm or fault warning
UPSOUT Fault (no current) in 1 or more output stage
USER-1 User 1 input open
USER-2 User 2 input open
USER-3 User 3 input open
Alarm(s) vibrating. Alarm is frequently raised and lowered. Ignore to avoid
VIBRA_
loading the log filling up.

Power+ Technical Guide 61


Gamatronic Electronic Industries Ltd.

6. BATTERIES

6.1. BATTERIES AND CONFIGURATIONS


The POWER+ is flexible in structure, in that it may be extended by adding modules as
required. The battery bank is common to all modules and may comprise one or more
branches to include a redundant battery if desired.

For systems from 10kVA through 30kVA, the batteries may be internal; otherwise, the
batteries are housed in external cabinets. See Figure 6-3 on page 64 for details on battery
cabinet wiring and connections.

6.1.1. INTERNAL BATTERIES


Up to 3 internal packs, each containing 64 12v/5Ah batteries, may be housed in the
Power+ system cabinet. This would provide 4 minutes of backup time at full load, on a
redundant system of 5 modules (total 40kVA). See Figure 6-1 below.

Each battery pack is 6U high and weighs about 135kg on average, depending on the
manufacturer and model. It comprises. 4 drawers, each containing 16 batteries, to help
facilitate removal and replacement. See Figure 6-2 on page 63.

System controller

4 x 10kVA UPS modules


(plus 1 x redundant)

DC distribution

Static switch

Battery drawers

Figure 6-1: 40kVA N+1 System with Internal Batteries

62 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

Figure 6-2: Internal Battery Drawer Exploded View

6.1.2. EXTERNAL BATTERIES


External batteries are housed in separate cabinets.

These batteries are connected to the system by heavy duty cables, care must be taken to
ensure correct polarity. Overall voltage may be as high as 870vDC + to -, i.e. +435vDC and
435vDC with respect to ground/earth. Precautionary measures must be taken whenever
connecting the battery or servicing the battery cabinets.

6.2. INSTALLING AND CONNECTING THE BATTERIES


As shown in the diagram, the DC output cable from the batteries is connected directly to the small
Anderson connectors on the UPS rear panel.
WARNING: When connecting the batteries to the UPS:

y The UPSs AC INPUT circuit breaker must be in the OFF position,


AND

y The battery circuit breaker must be in the OFF position.

WARNING: After connecting the batteries to the UPS, do not turn on the battery circuit breaker until
the UPSs AC INPUT circuit breaker is turned on.

Cables from battery banks are connected to the Anderson connectors on the DC distribution
shelf as indicated in Figure 3-11 on page 27 and Figure 3-12 on page 27.

Power+ Technical Guide 63


Gamatronic Electronic Industries Ltd.

Figure 6-3: Connection diagram for external battery

64 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

Configuring the batteries to the system

When you are installing the battery for the first time, or if you have changed either

y the number of battery sets (1 battery set = 64 batteries)


OR

y the total Ampere/hour capacity of your batteries,


you must reconfigure the batteries to the system.

To (re)configure the number of battery sets:


1. On the system control panel, press Ent.
2. Choose Setup, press Ent.
3. Enter the system password (the default password is eight left arrows),
press Ent.
4. Select Service, press Ent.
5. Select Configure, press Ent.
6. Select # of Batteries, press Ent.
7. Use the up and down arrow keys to modify the number of batteries,
then press Ent.

To (re)configure the Ampere/hour rating of the batteries:


1. On the system control panel, press Ent.
2. Choose Setup, press Ent.
3. Enter the system password (the default password is eight left arrows),
press Ent.
4. Select Battery, press Ent.
5. Select Capacity, press Ent.
6. Choose the battery set that you want to configure and press Ent.
7. Use the arrow keys to set the desired number of Ampere/hours,
then press Ent.

Power+ Technical Guide 65


Gamatronic Electronic Industries Ltd.

7. DRY CONTACTS AND ALARM TERMINALS


Dry Contact terminals are located on the right side of the rear of the POWER+ controller
module, as shown in Figure 7-1, labeled A and B.

Figure 7-1: Location of dry contacts at rear of POWER+ controller module

Figure 7-2: Dry Contacts group A (as per Figure 7-1)

NAME IN
INPUTS DRY CONTACT DESCRIPTION
ALARM DISPLAY
COM Shared contact ---

Auxiliary contact (N.C.) for battery Circuit


BAT CB BAT CB
Breaker trip indication

N.C.1 USER1 user assigned dry contact USER-1

N.C.2 USER2 user assigned dry contact USER-2

66 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

7.1. DC CURRENT MEASUREMENT


The dry contacts in Figure 7-2 labeled DC CURRENT MEASUREMENT are for monitoring
battery current. Each group may be connected to a different current sensor. Measurements
can be taken from up to three battery sets, as per the three groups of Current Measurement
contacts.

7.2. TEMPERATURE SENSOR


An optional temperature sensor (see Figure 7-3) may be attached to the contacts labeled
TEMP to monitor the temperature of the batteries.

Figure 7-3: Dry Contacts group B (as per Figure 7-1)

To install the temperature sensor, connect the sensor according to Figure 7-3 and Figure
7-1.

To see the temperature reading, a configuration change must be made to the controller.
Enter the following commands on the system controller panel:

Ent, Setup, Password (default password is 8 left-arrows),


Battery, Enable/Disable Options, Enable Batt Temp Sensor

To see the temperature reading, enter the following commands on the system controller
panel:

Ent, System, 5 x down arrow. Press Esc to exit.

Power+ Technical Guide 67


Gamatronic Electronic Industries Ltd.

7.3. USER-DEFINED ALARMS


There are four groups of 3 contacts each (see Figure 7-3) that can be used for user-defined
alarms. In each group, either the N.C. or N.O. contact is used together with the COM
contact.

68 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

8. TROUBLESHOOTING

Reading the UPS module's front panel may provide the user with indication of malfunctions.

Figure 8-1: UPS module front panel

As shown in Figure 8-1 there are three LEDs on the front panel of each UPS module: Alarm,
Output and Line. The internal buzzer in the UPS module sounds when there is no
communication with the system controller.

These 3 LEDs and the buzzer indicate the status of the UPS module (see Table 8-1 below).

The alarm LED is red, line and output LEDs are green.
Normal condition is indicated by the green line LED and output LED on, with no beeps from
the buzzer.

Power+ Technical Guide 69


Gamatronic Electronic Industries Ltd.

Table 8-1: UPS Module Indicators


CONDITION LINE OUTPUT ALARM BEEPS REMARKS
(GREEN) (GREEN) (RED)

Wake-up On On On
Start Off Off Off About 1 minute
Normal On On Off
Operation

Abnormal Off On On
Input voltage

One phase Blinks On Off


abnormal input

High Input Blinks On On


Current

Vdc > 450V On Off Off High Vdc


Vdc > 500V On Off On Very high Vdc
DC imbalance On On Blinks
Low Vdc< 360V On* On Blinks * Mostly will be
caused by Vin
Vdc very low, On* Off On
< 320V fault that will turn
off LINE LED
DC critical fail Blinks Off On
< 200V

Circulation On Off On
Current

Output overload On Blinks Off


Output is On Blinks On Result of output
disconnected overload
Communication On On On Or absence of
failed System
Controller
Output Blinks Off On
short-circuit

70 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

Table 8-2: Troubleshooting table

PROBLEM SOLUTION

1 After the startup the unit wont 1. Check the phase sequence of the bypass
switch to inverter. input. Swap phases S (L2) and T (L3) on this
input for proper phase rotation.
2. Make sure that the bypass input voltage and
frequency is within the tolerance.

2 On a module OUTPUT and 1. Try resetting the module by pushing the


ALARM LEDs are flickering. RESET button on its front.
2. Check its output voltage through the controller.
If no voltage replace the module.

3 The unit shows output load while 1. Check and compare each modules output
there is no load connected. voltage on each phase. One of the modules
might be configured to a voltage different from
others, thus causing circulation currents on the
output.
2. Compare I-BUS and I-ACT for each module in
the UPS module menu on the controller. If
these values are not similar for one of the
modules, check it individually.

4 Contactor sounds can be heard These units have internal synchronization


from the unit from time to time, contactor, which should protect from switching to
but no transfers to bypass have bypass and feedbacks while the bypass input is not
been registered. synchronized with inverter. It will switch off
automatically each time bypass frequency gets out
of tolerance, and when the problem is restored it
will switch back on. Check the supply. Power+
units frequency window is adjustable from 0.5Hz
to 4Hz.

5 Red alarm LED is lit on the 1. To see the list of active alarms with short
controller. descriptions, press the ALARM OFF button
(the middle one on the right hand side of the
controller). Navigate with arrow keys.
2. To see the list of active alarms with full
description, press and hold ESC key to get in
to the menu and choose Alarms Status.
Navigate with arrow keys.

6 LINE LED blinks in green on a A phase is missing on the main input. If the problem
module, while output is green and exists on one module only, check the input fuses
alarm is not lit. (located on the rear side of base unit, above the AC
terminals). There is one fuse for each phase of
each module.

Power+ Technical Guide 71


Gamatronic Electronic Industries Ltd.

7 DC voltage gets low, sometimes 1. The unit might be in the middle of the battery
until the unit switches off and test. Check it through the controller. If it is,
goes on bypass. either let it finish or stop it manually.
2. Check the current limit and battery temperature
compensation settings in the controller. They
can cause severe drop in DC voltage if not
configured properly.
3. Try to remove the system controller and check
if the DC voltage restores to normal. If it does,
check controller settings. This will not stop P+
operation or cause interference with the load.
4. If battery temperature compensation and/or
battery current limit are enabled, make sure
that the unit has the required optional sensors
installed. If not, disable the corresponding
feature.

8 The modules are working 1. Check AC fuses (located on the rear side of
normally, but the system base unit, above the AC terminals) and DC
controller is off. fuses (located behind a blank cover above the
ST/SW module).
2. Replace PC093 power supply PCB inside the
system controller.
3. Replace the system controller.

9 The system is running normally, Check the number of modules value in the
but shows UPS-CM alarm. controller. If the system is set up for more modules
then actually exist, it will fail to communicate with
non-existing modules.

10 No values are received from the In the COMM. menu there are three communication
unit through the communication options. In units with PC375 communication boards
port or through the WING. (before 2006) the first option should be selected,
TCP/IP Comm. Board. On units with PC575 boards,
which appeared from the beginning of 2006, the
second option should be selected PC575. WING
will work with both options, and the third option,
WING communication, should not be used. It is
designed for special units without communication
cards only.

72 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

9. SYSTEM CONTROLLER AND


COMMUNICATIONS

9.1. INTRODUCTION
The SCC POWER+ controller enables you to control and monitor all the individual
components of the POWER+ system. Flexibility in setting the various configurations allows
you to adjust the system to suit specific individual needs.

The system is equipped with clear, simple, user-friendly menus and submenus for easy
monitoring, parameter definition and control of the system. The SCC provides
communication with a wide range of management equipment, such as computers and
mobile phones.

9.2. SCC POWER+ CHARACTERISTICS


The controllers main functions include:

y Real-time 32 alarm display


y Manual and periodic battery testing
y An event log that records recent 254 events
y Service utility software
y Remote control of the system (via TCP/IP, SNMP, PPP, GSM, GPRS, SMS,CDMA).
y Three levels of access to the controller: factory, supervisor and service
y Easy restoration of factory defaults
y Easy setting and saving of user defaults
y Flexible output dry contacts
y Manual bypass command
y System turn off with or without bypass

Power+ Technical Guide 73


Gamatronic Electronic Industries Ltd.

9.3. CONTROLLER USER INTERFACE


The controllers user interface includes:

y 40 4 LCD panel
y 6 Navigation Keys
y 3 Quick Command Buttons
y 8 Indication LEDs
y 2 Communication LEDs

9.4. SERVICE UTILITIES


There are several service programs intended for higher-level users (i.e. technicians,
maintenance staff, etc.).

These programs allow canceling and performance of low-level operations in the system at
the same time. These operations are complex and can modify the system configuration,
affecting its operation. The service utilities should only be used by authorized personnel.

These service utilities allow the operator to:

y Change configuration
y Manually turn off and on UPS
y Test dry contact outputs
y Switch to alternative version of the software
y Change communication settings
y Restart the controller
y Restart the network adapter

9.4.1. START-UP SCREENS


The welcome screen is displayed for a few seconds when the controller is switched on or
restarted, and is immediately followed by a self-check test.

On completion of the self-check test the initializing screen appears and remains on display
until the controllers restarting process is completed. The softwares version is shown on the
second row. The time remaining in the restart process appears on the fourth row of the
screen. The main screen appears once the initializing screen closed.

The main screen provides the basic and essential information about the real-time status of
the power system. The LED indicator lights located to the right of the screen, warn if there is
a problem. The main menu remains displayed until one of the keys is pressed. The controller
automatically returns to this main menu screen whenever a key is not pressed for five
minutes.

74 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

The following information is displayed on this screen:

y DATE - Current date


y TIME - Current time
y AC-VOLT - System input voltage from mains
y AC-CURRENT - System input current from mains
y AC-Output Voltage System output voltage
y FL - Number of the active flash
y PD - Peripheral device status
y UP UPS general status

From the main screen you can navigate to:

y The Fast Information Menu through which you can access the 7 Fast Information
screens
y The Main Menu from which you can access:
y Monitor Screens that let you monitor the system and components
y Calibration Screens that let you calibrate the system and components
y Control Screens that let you control the system and components

Fast Information Screens


In addition to the many screens displaying detailed information about all aspects of the
system, there are seven Fast Information screens that contain further details about the
real-time status of the system. These screens can be accessed from the Fast Information
Menu.

Network Fast Information Screen


This screen provides information about network related parameters such as the IP address,
the gateway address and the mask.

There is also a counter that shows the number of times the controller failed to connect with
the server. The maximum value that the counter can display is 225. Under normal operating
conditions the value should be 0.

There is also a count of the number of times there was no SNMP link. This value resets the
Network card.
Dry Contact Fast Information Screen
This screen provides real-time data on the status of the input and output dry contacts.

For both input and output dry contacts:

y A filled circle appears when the dry contact is closed.


y An unfilled circle appears when the dry contact is open.

Power+ Technical Guide 75


Gamatronic Electronic Industries Ltd.

System Alarm Status Fast Information Screen


This screen shows the status of the existing system faults, indicating whether or not they are
active. This screen shows:

y A filled circle indicates an active fault.


y An empty circle indicates an inactive fault.

General Information Screen


The following table describes the information displayed on the Information screen:

Table 9-1: General information screen


FIELD DESCRIPTION

REV Software revision number


T.C. Temperature
V-SET Output voltage
MAINT Last maintenance date
V-AUX Input Voltage
SITE ID number of the site
BATT General battery information

76 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

9.4.2. THE MAIN MENU


The Main Menu enables you to access screens that monitor and control every aspect of the
system including setting parameter limits, activating the system checks and monitoring the
status of individual components of the system.

The Main Menu functions are listed in Table 9-2 below.

Table 9-2: Main Menu functions


Screen Description

0 SYSTEM Monitoring the System


1 UPS Monitoring UPS
2 SELFTEST Initiates a Self Test of the Controller
3 HISTORY Event Log
4 BATTERY Monitoring the Batteries
5 ALARM Monitoring the Alarms
6 SETUP Submenu for setting parameters and starting tests
7 COMMS Communication (not implemented)

Power+ Technical Guide 77


Gamatronic Electronic Industries Ltd.

10. SETUP PROCEDURES


The options in the Setup Menu enable you to configure system parameters.

Table 10-1: Setup Menu options


Option Description

1 ALARM SET Opens menu with options for setting the threshold levels that
trigger alarms
2 UPS Sets the UPS Parameters
3 BATTERY Sets the Battery current parameters
4 CHARGE Sets the Charge mode parameters
5 TIME Sets the systems clock which sets a time stamp on log entries
6 SITE Sets the power system's ID number
7 PASSWORD Sets Level 1 Password
8 SERVICE Opens menu of service utility programs
9 SILICON Opens menu with options for restoring factory-defined default
values to parameters

10.1. SETTING ALARM THRESHOLDS


It is possible to define the threshold values for setting off alarms for the parameters of
system components. An alarm is set off each time a parameter value is outside the defined
range of permitted values.

Press the number that appears beside a menu option to open a screen in which you can set
the alarm thresholds for that option.

Table 10-2: Setting alarm thresholds


Option Description

0 AC VOLT Sets the permitted AC voltage range (minimum and maximum input
voltage) and the AC voltage hysteresis
1 OUTPUT VOLT Sets the permitted DC voltage range (minimum and maximum
output voltage)
6 BATTERY Sets the permitted battery voltage range (minimum and maximum
output voltage) (indicates possible battery fault)
7 TEMPERATURE Sets the permitted battery temperature range (minimum and
maximum temperature)
8 VIBRATION Sets the number of times an alarm must occur within a specified
period of time to be considered a vibrating alarm
9 INTEGRATION Sets the number of times the controller must receive an
alarm from the system before it logs the alarm

78 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

10.1.1. SETTING ALARM VIBRATION PARAMETERS


A vibrating alarm is an alarm that is activated often. A vibrating alarm can fill a log with
alarm messages for the same alarm. To avoid filling the alarm with this kind of messages,
you can define a vibrating alarm (setting the number of times an alarm must occur as well as
the period of time in which it must occur).

10.1.2. SETTING THE INTEGRATION FACTOR FOR ALARMS


The integration factor is the coefficient that determines the number of times an alarm must
occur before the controller records it. The smaller the value of the coefficient is, the sooner
the warning notification is received. However, with a small coefficient there is a chance that
an alarm may be given for a glitch rather than a fault. The larger the value of the coefficient
is, the more notification is delayed and the greater the reliability.

10.1.3. 'AUTO' TEST BATTERIES


The 'Auto' test option checks the periodic/automatic testing of the batteries.

10.2. SETTING PASSWORD LEVEL 1


A level 1 (supervisor) password allows you to monitor and control the system.

Power+ Technical Guide 79


Gamatronic Electronic Industries Ltd.

10.3. ADDING A POWER MODULE


If an additional shelf is attached at the top of the system, the DIP switch of the Control PCB
must be changed to the next address code as shown in Table 3-2 on page 36.
Updating the number of modules in the Power Plus processor:
(Ent represents a press of the Ent key.)

Ent, Setup,

Ent, Password (default password is 8 left arrows [] ),

Ent, Service ,

Ent, Configure

Ent, Total # of UPS,

Ent, (enter number of UPSs),

Ent , Ent

The system reinititializes itself.

Turning off the output current limit:

Ent, Setup,

Ent, Password (default password is 8 left arrows [] ),

Ent, Battery,

Ent, Current Limit,

Ent, Enable current limit (off)

Esc.

80 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

10.4. SYSTEM CONTROLLER SETUP VERIFICATION


The system verification is available for software versions beginning from 050106.

ACCESS

Press ESCAPE key and hold it for 3S. Using ARROW UP/DOWN key, select GENERAL (8)
and press ENTER. Screen 1 is presented.

SCREEN 1

a) ACV: nominal value of the input/output AC voltage (220 for 2x32 batteries ; 110 for 2x16
batteries)
b) ALM: input AC voltage alarm HIGH/LOW
c) TEMP.ALARM: high temperature limit for external thermosensor
d) MODULES: QUANTITY/REDUNDANCY 07/02 in the screen means that 7 modules are
presented in the system, 2 modules are reserve (full load is 10KVA*(7-2)=50KVA/40KW)
e) C.LIM.=off (VALUE)- battery current limit function is de-activated (off) or max. battery current
value in Amps. In C.LIM is activated, the system must be equipped with optional battery
current sensor.
f) T.C.=2.0mV negative temperature coefficient of the battery DC voltage in mV per C per
battery cell. Nominal temperature is 25C. For DC nominal voltage 432V , temperature 35C,
32 batteries of 6 cells, T.C.=2mV, the voltage is 432- 2*6*32*(35-25)~=428V. NOTE. For
most applications T.C. must be 0 (off).
g) DCV: DC nominal voltage for both positive and negative battery sets. For 32 batteries in the
set DCV=432V, for 16 batteries 216V.
h) DCV ALM: DC voltage alarms HIGH/LOW/SHUTDOWN. SHUTDOWN alarm is DC voltage
value when the unit is stopped due to battery discharge.
i) BATT.TEST: PERIOD IN WEEKS/MAX.DURATION IN HOURS/ALARM
VOLTAGE/CHARGER DERATED VOLTAGE. In the screen: the test is performed
automatically once per 4 weeks, max. test duration is 5 Hours, if battery voltage drops below
360V alarm Battery Low is given, the chargers of the modules continue to supply voltage
352V to prevent shutdown if battery is faulty.
j) CAP: CAPACITY in Amp-Hours. Is used to calculate estimated back up time of the system
and battery test duration.

Power+ Technical Guide 81


Gamatronic Electronic Industries Ltd.

SCREEN 2
To access SCREEN 2 press the key ARROW RIGHT when SCREEN 1 is selected.

a) #OF PHASE: FORCE 3 for 3 phase output, FORCE 1 for single phase output or AUTO when
the mode is defined by DIP SWITCH of the modules.
b) REV: revision of system controllers (SC) software
c) LVD BY AC FAIL: DIS (disabled) or EN (enabled). This function, if enabled, performs system
shutdown after 3 Hours of AC failure to prevent deep battery discharge by low current. In
most application the function must be DIS.
d) MAINT: YEAR.MONTH.DAY: date of last maintenance
e) TEMP. SENSOR: DIS or EN . External thermosensor is disabled/ enabled. In most
applications must be DIS.
f) SITE: the site identification number. Is used in network applications.
g) CURR.SENSOR: DIS or EN. Optional battery current sensor is disabled/ enabled. In most
applications must be DIS.

SCREEN 3
To access SCREEN 3 press the key ARROW RIGHT when SCREEN 2 is selected.

The screen presents status of controller boards jumpers.

a) Not HARD Silicon. Must be HARD only initially, during first activation of non-configured
controller. After production should be Not HARD Silicon.
b) Silicon Mode. Regular mode allowing setups change. The setups are saved in EEPROM
chip.
c) CAPACITY HI (LO). High/low battery capacity mode when battery capacity is more/less than
100AH to achieve optimal resolution of battery current displayed value.
d) No/Yes Rmt Pan. Outputs of SC are not configured/ configured for optional remote panel
connection.
e) AC: 220V. Nominal AC input voltage: 220V for 2x32 batteries, 110V for 2x16 batteries in
series.

82 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

11. REPLACEMENT PROCEDURES

11.1. UPS MODULE

To remove a UPS module from the system:


1. Unscrew the mounting screws on both sides on the front module panel.
2. Hold the front handle of the module and remove it by pulling out.
3. If the module is being permanently removed, update the total amount of modules in the
system controller.

WARNING: Do not touch or short-circuit metal pins on rear plugs of the module, as they might still be
energized. Let the module discharge for at least 15 minutes prior to any operation or disassembly.

NOTE: Other UPS modules operation will not be affected by this removal, unless the load will
become too high for them with less power in total. For instance, if the load is 25Kva and one module
out of three was removed, the system might switch to bypass due to overload of the remaining UPS
modules.

To insert a UPS module in to the system:


1. Insert the module firmly in to the housing and slide it in until it stops.
2. Screw the module in with two mounting screws located on the sides of its front panel.
3. It might be required to reconfigure the system controller with the new amount of modules in
the system

WARNING: Make sure that the module has the same configuration as other modules in the system.
This includes the dip switch settings (on the module itself) for frequency and number of output
phases, as well as the internal output voltage configuration, like 240v or 230v, which can be changed
through the system controller only. If the UPS module configuration will diverse from other modules
configuration, this and/or other modules might be damaged.

NOTE: If the Power+ system was energized during modules connection, the module will switch on
automatically within one minute. This will not affect other modules or the load.

Power+ Technical Guide 83


Gamatronic Electronic Industries Ltd.

11.2. SYSTEM CONTROLLER MODULE

To remove a system controller module from the system:


1. Ensure that there are no cables connected to the rear plugs of the controller. If there are any,
disconnect them prior to controller removal. This includes LAN cable and the WING (optional)
connections.
2. Unscrew the mounting screws on both sides of the system controller and pull it out of the
housing.

NOTE: Controller removal will not affect modules operation and the load. Every module has its own
internal control and will keep up with proper operation, like current sharing and battery charging.
Some functions will not be available while the system controller is removed: battery test, battery
conditioning systems etc.

To insert a system controller module in to the system:


1. Confirm that the rear cables/plugs (if any) will not hinder the process; take them out of the
housing.
2. Hold the controller firmly and slide it in to the housing.
3. Screw the controller in with two mounting screws located on both sides of its front panel.
4. Connect rear external cables (if any) including LAN and WING (optional) connections.
5. If the controller was replaced with a new one, make sure that its configuration matches the
system with number of modules, battery settings, etc.

WARNING: If the controller is not properly configured for the given Power+ system, it might produce
false alarms and incorrect DC voltage handling.

NOTE: If the system was energized, the controller will start automatically within one minute.

84 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

11.3. STATIC SWITCH MODULE

To remove a ST/SW from the system:


1. Switch the entire Power+ system off, including input power and the batteries.
2. Unscrew two mounting screws on both sides of the ST/SW front panel, and slightly
pull it out, not more than 20cm.
3. Disconnect:
A. Communication flat cable (mounted with 2 screws)
B. EPO/dry contact connections (if any)
C. 9 phase wires from the terminals (marked according to their order)
D. 1 neutral wire from its terminal
E. 1 earth wire from a dedicated screw
4. Pull the ST/SW module out from the system.

WARNING: This operation is not possible to perform live, without load and Power+ system
disconnection. The system should be switched off completely. Ensure that there are no AC voltages
on the terminals. If another ST/SW module will not be mounted immediately, all disconnected wires
should be isolated to prevent accidental damage and protect from electrocution.

To connect a ST/SW in to the system:


1. Make sure that there are no AC voltages on the systems terminals and that the
system is switched off completely.
2. Slide the ST/SW module into its housing.
3. Connect in opposite order to its disconnection (above).

Power+ Technical Guide 85


Gamatronic Electronic Industries Ltd.

12. USING SERVICE PROGRAMS


Only users with a password (technicians) can enter the service mode.

The service programs enable access to the systems database. It is


possible to use these programs to modify both the systems database
and critical parameters. Changing the preset data may endanger the
systems intact operating state causing severe damage to its output,
WARNING components and consumers.

Only authorized personnel may use the service programs.

The following procedures can be performed in service mode:

y UPS shutdown or activation via a command from the controller


y Adding an integration coefficient to the alarm activation criteria
y System configuration
y Calibration of the systems voltage and current measurements
y Configuration of output dry contacts
y Alarm enabling or disabling
y Selecting the active flash memory
y Soft reset to the controller
y Setting the three network addresses (IP, Gateway, Mask)
y Resetting the network communication card

12.1. ACCESS TO SERVICE MODE


To enable entry into Service Mode:

Jumper J2 on card PC714 determines access to setup mode, and therefore controls access
to service mode. When the jumper is removed, access to setup mode is denied, and access
to service mode is impossible. When jumper J2 is in place, access to setup and service
modes is permitted.

86 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

12.2. SELECTING THE CONTROLLERS LOW LEVEL


UTILITIES

Access to the controllers low level utilities is as follows:

Main menu > Setup > Password > Service menu > SC2012.

The options on the SC2012 menu are the controllers low level utilities. These options are described
in Figure 12-1.

Figure 12-1: Low level utility menu (SC2012 menu)


Option Description

1 Restart Controller Restarts the controller


2 Factory Settings Restores the controller's factory default settings
3 Network Sets the controller's network addresses
4 Reset MBX Resets the controllers' network card
5 MBX SW Upgrade Prevents the network card from resetting while the card is being
upgraded

12.3. SETTING THE NETWORK ADDRESSES

12.3.1. SETTING THE SNMP FACTOR


The SNMP communication protocol communicates every few seconds with the controller to
obtain updated data to send over the network. An SNMP failure to communicate indicates a
possible need to reset the communications card. The SNMP factor sets the number of
communication cycles that must pass without communication between the SNMP and the
controller before the controller automatically resets the communication card.

Power+ Technical Guide 87


Gamatronic Electronic Industries Ltd.

12.4. CONFIGURING DRY CONTACTS AND ALARMS

12.4.1. LINKING ALARMS TO DRY CONTACTS


Configuring the dry contacts involves associating a given dry contact with a specific alarm or
alarms. To configure the dry contacts:
1. Main menu > Setup > Password > Service menu > Configure > Dry Alarms.
2. Choose the desired Dry Alarm (1 through 6). Each dry contact can be linked to any of
32 alarms. An alarm can be linked to more than one dry contact and a dry contact can
be linked to more than one alarm.

12.4.2. ENABLING AND DISABLING SPECIFIC ALARMS


An alarm can be disabled or enabled as follows:
1. Main menu > Setup > Password > Service menu > Configure > Dry Alarms.
2. Choose the option Enable / Disable Alarms.
A screen is displayed representing the 32 alarms.
3. Use the left and right arrow keys to move the cursor through the alarms.
Use the up arrow to ENABLE an alarm. This causes a black circle to appear under
the alarm.
Use the down arrow to DISABLE an alarm. This causes a dash () to be displayed
under the alarm.
4. Press Enter to save your changes, or Esc to exit.
5. After saving your changes press Esc to exit.

88 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

12.5. CALIBRATING MEASUREMENTS


To perform calibration on the battery current measurement:

Main menu > Setup > Password > Service menu > Configure > Calibration

Table 12-1: Calibrating battery current measurements


Option Description

Removes battery current offset. Load and


2> DC-I Offset Removal
batteries must be disconnected.
Measure the actual battery current, then use this
3> DC-I Calibration
option to enter the measured value.

12.6. CONTROLLER SELF-TEST


This verifies that all the controllers individual components including the controllers main
card and the internal voltage DC/DC supply unit are functioning correctly.

The self-test is performed either automatically at midnight or following controller activation.


In addition, the self-test may also be performed at any time, as required, particularly if a
malfunction is suspected.

12.7. BATTERY TEST


There are two types of battery tests: automatic and manual. It is possible to test both.

12.7.1. PERIODIC/AUTOMATIC BATTERY TEST


There is usually a waiting period of a number of days between the times that the system is
programmed to perform an automatic or periodic battery test. An option therefore, is to
simulate the passing of time so you can check at any time whether the periodic/automatic
battery test occurs as configured.

Power+ Technical Guide 89


Gamatronic Electronic Industries Ltd.

13. MONITORING THE SYSTEM


The system is monitored by the controller and displays the following system information on
LCD screens and menus.

y Power Meter
y System operating times
y System configuration
y Status of input dry contact
y Status of the UPSs
y Status of the batteries
y System temperature
y Communication status

Figure 13-1: Key panel

13.1. POWER METER


The Power+ UPS contains a built-in digital power meter, allowing you to monitor the line
supply, the load current, and overall efficiency, avoiding the need for external monitoring
equipment.

To view the power meter on-line:

1) Press Enter to display the main menu. (See Figure 5-1, page 54.)

2) Press Enter to view the battery voltages. (See Figure 5-3, page 55.)

3) Press > (right) to switch to the performance analyzer.

4) Press > (right) to view

90 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

13.2. SYSTEM OPERATING TIMES


Table 13-1: Time displays
Information Description

Total Time Total elapsed time the system has been running
Boots Number of times the system has been rebooted
Current Sess. Total time the system has run since the last restart
(19:33:58) When the system was last restarted
Previous Controller Duration of the previous session
Session

HH:MM:SS YYYY.MM.DD When the last session began and ended, format :
hours,minutes, seconds year, month, day

13.3. MAIN DIP SWITCH STATUS


Table 13-2: Main dip switch statuses
Information Description

DIP Dual Inline Pin switch


Position of the circuit breakers in the DIP switch
= Circuit breaker is up
= Circuit breaker is down
1. Out Output voltage
2. Eq Equalizing mode
3. Mains Mains supply voltage
4. Mode Operating mode

Power+ Technical Guide 91


Gamatronic Electronic Industries Ltd.

13.4. PANEL AND SLAVE DIP SWITCH STATUS


Table 13-3: Panel and slave dip switch statuses
Information Description

DIP Dual Inline Pin switch


Position of the circuit breakers in the DIP switch
= Circuit breaker is up
= Circuit breaker is down
N-ID New ID of rectifier
Norm Battery test execution by command is normal
(internal rectifier command)
HiCap High capacity battery set
F2 Number of active flash memory
R/W Flash is upgradable (Read/Write)
chgbl It is possible to switch the active Flash memory (Changeable)
noecH No echo when the slave contacts the communication board

13.5. SC POWER+ INTERNAL POWER SUPPLY


Table 13-4: Controller external and internal power statuses
Information Description

MBRC Exact value of the voltage of the 5V power supply


AUX Power supplies in the controller
Good The power supply is ok
Bad A malfunction has occured in the power supply

13.6. SYSTEM TEMPERATURE


Table 13-5: System temperature displays
Information Description

Main Menu > System > press down arrow five times
Battery Temperature Temperature reading from a sensor located near the batteries.

92 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

13.7. INTERNAL COMMUNICATION


There are several sets of system screens that provide information on the status of the
internal communications between the controller and components of the power system.
These sets appear as follows:

y Screens displaying information about the dialog between the controller card and the
P.D. card. The function of the P.D. card is to measure voltages (AC, DC) and currents
(AC, DC), check the dry contactors input value, and control the LVDs. There are
seven screens displaying data about the controller-P.D. dialog.
y Screens displaying information about the dialog between the controller and the
rectifiers. There is a screen for each rectifier in the system
y Screens displaying information about the dialog between the controller and the
converters. There is a screen for each converter in the system
y Screens displaying information about the performance record sent by the controller to
all the converters and the rectifiers at once. The rectifiers and converters carry out the
commands in the record according to the priority the record provides.
In these screens:
T Indicates that the data in that row is transmitted by the controller

R Indicates that the data in that row is received by the controller

Power+ Technical Guide 93


Gamatronic Electronic Industries Ltd.

13.8. MONITORING SYSTEM COMPONENTS


Screens monitoring the status of the following system components are accessed from the
Main Menu:

y UPSs
y Batteries

13.8.1. MONITORING THE BATTERIES


You can monitor the information about the system batteries:

y General information
y Information on the battery test progress and the status of the last battery test

Battery Test Progress


Table 13-6: Battery test information

Information Description

Max/Estim. Time Left Maximum or estimated time remaining until the end of
the current battery test
Battery Test in Progress Time elapsed since the start of the battery test
Batt. Volt Battery voltage during the battery test
Batt. Current Discharge current during the battery test
Last Test Status of the last battery test
Days Left Time remaining until the next periodic or automatic test

94 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

13.8.2. MONITORING ALARMS


Information about the alarms in the system is available in a number of screens according to
the following topics:

y A series of screens containing the names of the alarms and their status (i.e. whether
each alarm is enabled or disabled and whether the alarm is active or inactive.
y The status of the output dry contacts.
y A series of screens detailing the relationship between the alarms to the serial number
in the alarm list.
y 6 screens (corresponding to the number of dry contacts) detailing the dependency of
each dry contact to the alarms.
y Six screens showing the relationship of the LED lights which can be user-programmed
to the alarms.
y 4 screens corresponding to the alarm severity definitions which may be programmed
by you
y Use the Up and Down arrows to scroll through all the screens in a series.

13.9. AFTER USING THE EMERGENCY POWER OFF

1. To return the UPS system to normal operation after use of the Emergency Power Off
(EPO) switch, you must do the following:
2. Turn OFF the AC Input circuit breaker.
3. Turn OFF the Battery circuit breaker.
4. Return the EPO switch to its normal position.
5. Turn ON the AC Input circuit breaker.
6. Turn ON the battery circuit breaker.
7. Wait about 2 minutes until the UPS initialization procedure has completed.

Power+ Technical Guide 95


Gamatronic Electronic Industries Ltd.

14. SYSTEM SPECIFICATIONS


Table 14-1: Technical specifications
+
Power TECHNICAL DATA
Topology On line Battery, Double Conversion, VFI
Construction Modular parallel hot-plugged modules
Operation Continuous
Input
Voltage (V) 3 400+ N
Voltage range (%) 27 and + 20
Current (A) 3 15A per module no inrush current at startup
Frequency (Hz) 47-63
Power walk-in (sec) > 60
Power Factor 0.99
THDI (%) 5
Output
Rated Power 10kVA/8KW to 100kVA/80KW
Frequency (in free-running mode, Hz) 50/60Hz 0.1%
Frequency tracking range (Hz) 1, 2, 3 (selectable)
Slew rate 1 Hz/sec
Voltage (V) 3 400 +N
Static Regulation % 1
Regulation for unbalanced load % 1 for 100% unbalanced load
Dynamic response to 100% load step % 2
Overload 110% : 10 minutes, 125% : 60 seconds, 1000% : 1 cycle
Waveform Sinusoidal
THD (%) Less than 2 for linear load
Load CF (max) 6:1
AC-AC efficiency (nominal) % Up to 96 at full load
DC-AC efficiency (nominal) % Up to 98 at full load
Batteries
DC-Link Voltage (V) 340 to 425
Quantity 64 12V
Type Sealed, lead acid, rechargeable
General
Maximum power dissipation (Po=8KW) N*333W (N*1136 BTU)
Ambient temperature (C) -10 to +40 (operating)
-20 to +60 (storage)
Relative humidity (%) 95 max non-condensing
Altitude (m) 1500 without derating
Enclosure IP20
Cooling system Multi-Fan with speed control (forced)
Standards
EMC EN50091-2 Class A; IEC 62040-2 Class A
Design EN50091-3; IEC 62040-3
Safety EN50091-1; IEC 62040-1-1
Low magnetic field radiation EMF as per ICNIRP
Dimensions
UPS type 10 kVA 20 kVA 30 kVA 40 kVA 50 kVA 60 kVA 70 kVA 80 kVA 90 kVA 100 kVA
Height (cm) 71 80 90 99 108 118 127 136 146 155
Width (cm) 59.8
Depth (cm) 67.3
Weight (Kg) 84 99 114 129 144 159 174 189 204 219
Acoustic Noise
Noise (dBA)
48 52 53 54 55 55.8 56.4 57 57.5 58
with half load
Noise (dBA)
51 54 55 57 58 58.8 59.4 60 60.5 61
with full load

All specifications are subject to change without notice.

96 Power+ Technical Guide


Gamatronic Electronic Industries Ltd.

15. SYSTEM MODULES ORDERING


INFORMATION
Table 15-1: Ordering parts
Weight
Description Catalog No. U
CONTROLLER
1 (SC Power +)
3Kg
SNMP 101SC-PP 2U

UPS MODULE
2
10KVA 10110033H-PP 2U 9.5Kg

HOUSING

3 UPS and 6Kg


CONTROLLER 101H-PP 2U

4 DC/AC DISTRIBUTION
and BASE 50KVA 101B050-PP 11U 40Kg

5 DC/AC DISTRIBUTION
and BASE 100KVA 101B100-PP 11U 40Kg

6 14kg
Static switch 50KVA 1090503H-PP 6U

7 16kg
Static Switch 100KVA 1091003H-PP 6U

BATTERY PACK
64 5AH
(up to 3 packs per
8 system; minimum 1 pack 6U 130kg
per 10KVA. 29B004064-PP ea. ea.

Power+ Technical Guide 97

Vous aimerez peut-être aussi