RESISTENCIA RMG
CODIGO ELECTRICA Radio (m) TABLA
AC A 75C (ohm/km) (m)
5.040 0.0025
5.660 0.0028
6.360 0.0032
6.540 0.0033
8.020 0.0040
8.250 0.0041
9.320 0.0047
9.000 0.0045
11.700 0.0059
10.110 0.0051
12.210 0.0061
11.350 0.0057
13.450 0.0067
14.620 0.0073
12.740 0.0064
15.420 0.0077
16.020 0.0080
18.140 0.0091
16.860 0.0084
14.310 0.0072
15.460 0.0077
16.300 0.0082
17.280 0.0086
17.370 0.0087
18.300 0.0092
18.830 0.0094
18.880 0.0094
19.620 0.0098
19.890 0.0099
20.470 0.0102
20.680 0.0103
21.490 0.0107
21.790 0.0109
22.420 0.0112
22.330 0.0112
23.210 0.0116
23.540 0.0118
24.220 0.0121
24.200 0.0121
24.540 0.0123
25.250 0.0126
25.260 0.0126
23.880 0.0119
24.810 0.0124
25.160 0.0126
25.890 0.0129
25.900 0.0130
23.640 0.0118
25.400 0.0127
25.760 0.0129
26.690 0.0133
27.460 0.0137
26.320 0.0132
27.740 0.0139
27.020 0.0135
28.950 0.0145
28.130 0.0141
26.430 0.0132
27.740 0.0139
28.750 0.0144
29.520 0.0148
28.950 0.0145
29.600 0.0148
30.390 0.0152
30.130 0.0152
30.800 0.0151
31.620 0.0158
31.970 0.0160
32.830 0.0164
33.080 0.0165
33.980 0.0170
33.430 0.0167
34.170 0.0171
35.090 0.0175
35.210 0.0176
36.170 0.0181
36.240 0.0181
37.220 0.0186
37.230 0.0186
38.230 0.0191
38.200 0.0191
39.240 0.0196
NOMBRE VALOR UNIDAD DE MEDIDA
POTENCIA 100 MVA
FACTOR DE POTENCIA F.P 0.9 Adimensional
VOLTAJE LINEA - LINEA 230 KV
REGULACION 10% Porcentaje
LONGITUD DE LA LINEA 165 KM
TEMPERATURA AMBIENTE 25 Grados celcius
ALTITUD 800 mts
CONFIGURACION DE LA TORRE Circuito sencillo Adimensional
FACTOR DE CARGA F.C 0.5 Adimensional
FACTOR i 11% Porcentaje
TIEMPO PROYECCION LINEA (n) 25 An os
COSTO DE LA ENERGIA 0.06 USD/KW-h
DISTANCIA AB 10.63 mts
DISTANCIA AC 6 mts
DISTANCIA BD 10.63 mts
COSTO DEL CABLE 3.51 USD/Kg
AN O EN HORAS 8760 h/an o
RESISTENCIA
CODIGO CALIBRE ELECTRICA
AC 75C (ohm/km)
12543696.5
11785270.18
10295884.3
9241528.847
8666742.731
8292842.707
7843389.173
4130974.962
3736369.194
3420660.962
3460781.013
3014283.406
3029384.177
3079639.353
2668847.473
2690145.149
2767924.994
2458257.228
2485578.064
2561547.499
2362547.037
2393342.773
2492377.423
2352230.345
2306974.203
2355043.653
2444912.689
2319562.374
2266358.483
2317323.683
2269043.173
2262712.901
2222081.63
2168019.846
2089391.286
2239713.802
2221352.039
2214386.9
2042329.696
2181804.06
2034624.739
2181628.053
2051823.233
2179916.169
2039686.649
2206960.213
2056885.143
2220205.443
2074662.787
2263364.901
2106818.394
2306524.358
2139553.152
2349683.816
2186665.874
2392843.274
2233778.596
2451539
NOMBRE VALOR UNIDAD DE MEDIDA
POTENCIA 100 MVA
FACTOR DE POTENCIA F.P 0.9 Adimensional
VOLTAJE LINEA - LINEA 230 KV
REGULACION 10% Porcentaje
LONGITUD DE LA LINEA 165 KM
TEMPERATURA AMBIENTE 25 Grados celcius
ALTITUD 800 mts
CONFIGURACION DE LA TORRE Circuito sencillo Adimensional
FACTOR DE CARGA F.C 0.5 Adimensional
FACTOR i 11% Porcentaje
TIEMPO PROYECCION LINEA (n) 25 An os
COSTO DE LA ENERGIA 0.0625 USD/KW
DISTANCIA AB 10.63 mts
DISTANCIA AC 6 mts
DISTANCIA BD 10.63 mts
COSTO DEL CABLE 3.51 USD/Kg
AN O EN HORAS 8760 h/an o
0.9044 59.0271228433
0.9044 65.345515946
0.9044 72.3622687222
0.9044 74.1481773688
0.9044 88.5786735903
0.9044 90.7840186246
0.9044 100.9264651943
0.9044 97.912677523
0.9044 122.8788435101
0.9044 108.3002812005
0.9044 127.4870735059
0.9044 119.6979424406
0.9044 138.5661888652
0.9044 148.8688952097
0.9044 132.2436163168
0.9044 155.8353694786
0.9044 161.0209322976
0.9044 179.0924479107
0.9044 168.2267633463
0.9044 146.1526714588
0.9044 156.1821024285
0.9044 163.4297437106
0.9044 171.8069500972
0.9044 172.5722136588
0.9044 180.4413451262
0.9044 184.8953153504
0.9044 185.3143860007
0.9044 191.4946670893
0.9044 193.7395743344
0.9044 198.5442632811
0.9044 200.2780378344
0.9044 206.9370428756
0.9044 209.3921261473
0.9044 214.5285922901
0.9044 213.796384588
0.9044 220.9337146577
0.9044 223.5977623488
0.9044 229.0664704376
0.9044 228.9060211832
0.9044 231.63044666
0.9044 237.2979853231
0.9044 237.3776031743
0.9044 226.3355919428
0.9044 233.7891378818
0.9044 236.581168494
0.9044 242.3821607249
0.9044 242.4614192388
0.9044 224.4037337859
0.9044 238.4916572536
0.9044 241.3512945728
0.9044 248.7054963343
0.9044 254.7591717272
0.9044 245.7852968819
0.9044 256.9527751656
0.9044 251.3037815867
0.9044 266.3861247017
0.9044 260.0013974743
0.9044 246.6542397068
0.9044 256.9527751656
0.9044 264.831985913
0.9044 270.8045817364
0.9044 266.3861247017
0.9044 271.4234443341
0.9044 277.518173836
0.9044 277.518173836
0.9044 275.5156069174
0.9044 286.9490109995
0.9044 289.6199075695
0.9044 296.1594358852
0.9044 298.054354969
0.9044 304.8537460082
0.9044 300.702688581
0.9044 306.2847664517
0.9044 313.192612617
0.9044 314.0910629755
0.9044 321.2576912116
0.9044 321.7788148498
0.9044 329.0543290441
0.9044 329.128376343
0.9044 336.5137999671
0.9044 336.292788711
0.9044 343.9349527619
NOMBRE VALOR UNIDAD DE MEDIDA
POTENCIA 100 MVA
FACTOR DE POTENCIA F.P 0.9 Adimensional
VOLTAJE LINEA - LINEA 230 KV
REGULACION 10% Porcentaje
LONGITUD DE LA LINEA 165 KM
TEMPERATURA AMBIENTE 25 Grados celcius
ALTITUD 800 mts
CONFIGURACION DE LA TORRE Circuito sencillo Adimensional
FACTOR DE CARGA F.C 0.5 Adimensional
FACTOR i 11% Porcentaje
TIEMPO PROYECCION LINEA (n) 25 An os
COSTO DE LA ENERGIA 0.0625 USD/KW
DISTANCIA AB 10.63 mts
DISTANCIA AC 6 mts
DISTANCIA BD 10.63 mts
COSTO DEL CABLE 3.51 USD/Kg
AN O EN HORAS 8760 h/an o
RESISTENCIA RMG
CODIGO ELECTRICA Radio (m) TABLA
AC A 75C (ohm/km) (m)
TURKEY 2.3730 0.0025 0.00162
THRUSH 1.8758 0.0028 0.00182
SWAN 1.7000 0.0032 0.00205
SWANATE 1.1000 0.0033 0.00211
SPARROW 1.1000 0.0040 0.00258
SPARATE 0.9255 0.0041 0.00266
GROUSE 0.7170 0.0047 0.00300
ROBIN 0.8840 0.0045 0.00290
PETREL 0.8240 0.0059 0.00454
RAVEN 0.7170 0.0051 0.00326
MINORCA 0.7720 0.0061 0.00474
QUAIL 0.5840 0.0057 0.00366
LEGHORN 0.6690 0.0067 0.00522
GUINEA 0.5950 0.0073 0.00567
PIGEON 0.4790 0.0064 0.00410
DOTTEREL 0.5540 0.0077 0.00598
DORKING 0.5270 0.0080 0.00621
BRAHMA 0.2791 0.0091 0.00736
COCHIN 0.4940 0.0084 0.00654
PENGUIN 0.3960 0.0072 0.00461
WAXWING 0.2590 0.0077 0.00600
PARTRIDGE 0.2550 0.0082 0.00662
OSTRICH 0.2260 0.0086 0.00702
WIDGEON 0.2050 0.0087 0.00674
LINNET 0.2020 0.0092 0.00743
ORIOLE 0.2010 0.0094 0.00778
CHICADEE 0.1740 0.0094 0.00732
BRANT 0.1720 0.0098 0.00788
IBIS 0.1710 0.0099 0.00807
LARK 0.1700 0.0102 0.00845
PELICAN 0.1450 0.0103 0.00802
FLICKER 0.1430 0.0107 0.00863
HAWK 0.1420 0.0109 0.00885
HEN 0.1420 0.0112 0.00926
OSPREY 0.1240 0.0112 0.00867
PARAKEET 0.1230 0.0116 0.00932
DOVE 0.1220 0.0118 0.00956
EAGLE 0.1210 0.0121 0.01000
PEACOCK 0.1130 0.0121 0.00972
SQUAB 0.1120 0.0123 0.00996
WOOD-DUCK 0.1120 0.0126 0.01043
TEAL 0.1031 0.0126 0.01043
KINGBIRD 0.1090 0.0119 0.00926
ROOK 0.1070 0.0124 0.00996
GROSBECK 0.1070 0.0126 0.01021
SCOTER 0.1060 0.0129 0.01069
EGRET 0.0981 0.0130 0.01070
SWIFT 0.1002 0.0118 0.00976
FLAMINGO 0.1020 0.0127 0.01020
GANNET 0.1020 0.0129 0.01046
STARLING 0.0949 0.0133 0.01083
REDWING 0.0872 0.0137 0.01134
STILT 0.0954 0.0132 0.01057
CUKOO 0.0859 0.0139 0.01114
TERN 0.0880 0.0135 0.01072
MALLARD 0.0785 0.0145 0.01196
DRAKE 0.0854 0.0141 0.01142
COOT 0.0802 0.0132 0.01091
CONDOR 0.0890 0.0139 0.01123
RUDDY 0.0780 0.0144 0.01141
CANARY 0.0790 0.0148 0.01196
CATBIRD 0.0669 0.0145 0.01195
RAIL 0.0740 0.0148 0.01175
CARDINAL 0.0750 0.0152 0.01231
TANAGER 0.0750 0.0152 0.01231
ORTOLAN 0.0700 0.0151 0.01244
CURLEW 0.069 0.0158 0.0128
BLUEJAY 0.064 0.0160 0.0127
FINCH 0.065 0.0164 0.0133
BUNTING 0.06 0.0165 0.0131
GRACKLE 0.06 0.0170 0.0138
SKYLARK 0.06 0.0167 0.0138
BITTERN 0.056 0.0171 0.0136
PHEASANT 0.057 0.0175 0.0142
DIPPER 0.053 0.0176 0.0140
MARTIN 0.054 0.0181 0.0147
BOBOLINK 0.05 0.0181 0.0144
PLOVER 0.051 0.0186 0.0151
NUTHATCH 0.048 0.0186 0.0148
PARROT 0.048 0.0191 0.0155
LAPWING 0.046 0.0191 0.0152
FALCON 0.046 0.0196 0.0159
DME POTENCIA EN INDUCTANCIA REGULACION (%)
(mts) KVA TOTAL
8.7849493078 100000 0.6483032713 75.4308955272
8.7849493078 100000 0.639526117 61.3542171759
8.7849493078 100000 0.6305534592 56.2971674588
8.7849493078 100000 0.6283783546 39.4244874908
8.7849493078 100000 0.6132156269 39.2182858596
8.7849493078 100000 0.6109132068 34.2875975603
8.7849493078 100000 0.6018438223 28.3121256289
8.7849493078 100000 0.6043999451 33.0348831848
8.7849493078 100000 0.5706051551 30.8909895757
8.7849493078 100000 0.5955770913 28.2269028261
8.7849493078 100000 0.5673547207 29.3870507767
8.7849493078 100000 0.5868507857 24.3746777929
8.7849493078 100000 0.560081771 26.3967452939
8.7849493078 100000 0.5538469479 24.2346407246
8.7849493078 100000 0.5782912709 21.3107323299
8.7849493078 100000 0.5498333817 23.0291140798
8.7849493078 100000 0.5469878214 22.2324771023
8.7849493078 100000 0.5341777059 15.0995423742
8.7849493078 100000 0.5430839735 21.2530172126
8.7849493078 100000 0.5694514958 18.860555881
8.7849493078 100000 0.5495816339 14.7444995737
8.7849493078 100000 0.5421672644 14.5313824192
8.7849493078 100000 0.5377438025 13.6571435066
8.7849493078 100000 0.5408127656 13.1093705786
8.7849493078 100000 0.5334639902 12.9252172881
8.7849493078 100000 0.5299933657 12.8499475855
8.7849493078 100000 0.5345885973 12.1544997529
8.7849493078 100000 0.5290304101 12.0227689414
8.7849493078 100000 0.5272339996 11.9702672834
8.7849493078 100000 0.5237646961 11.8950155455
8.7849493078 100000 0.5277026052 11.2467722905
8.7849493078 100000 0.5221754438 11.1154634077
8.7849493078 100000 0.5202774433 11.0615802031
8.7849493078 100000 0.5168629069 11.01514509
8.7849493078 100000 0.5218267801 10.5773570051
8.7849493078 100000 0.5163759403 10.4751578731
8.7849493078 100000 0.5144589286 10.4210161294
8.7849493078 100000 0.5110661992 10.3468057413
8.7849493078 100000 0.5132074742 10.1513507922
8.7849493078 100000 0.5113683976 10.0982689082
8.7849493078 100000 0.5078918379 10.0509903249
8.7849493078 100000 0.5078918379 9.7999158448
8.7849493078 100000 0.5168629069 10.0887745796
8.7849493078 100000 0.5113683976 9.95790974
8.7849493078 100000 0.509499229 9.9324904604
8.7849493078 100000 0.5060353441 9.8573124113
8.7849493078 100000 0.5059648454 9.6341370466
8.7849493078 100000 0.5128978294 9.7886906134
8.7849493078 100000 0.5095731128 9.7931360558
8.7849493078 100000 0.5076752794 9.7673269566
8.7849493078 100000 0.5050543102 9.5323737384
8.7849493078 100000 0.5015847595 9.2700479397
8.7849493078 100000 0.506886511 9.5713262008
8.7849493078 100000 0.5029264035 9.2507893131
8.7849493078 100000 0.5058240453 9.349145902
8.7849493078 100000 0.4975711934 8.97121345
8.7849493078 100000 0.5010547159 9.2112998602
8.7849493078 100000 0.5044993977 9.1130135479
8.7849493078 100000 0.5023197077 9.3295613932
8.7849493078 100000 0.5011207679 9.004466549
8.7849493078 100000 0.4975711934 8.9842668526
8.7849493078 100000 0.4976342619 8.6453430622
8.7849493078 100000 0.4989068389 8.862071454
8.7849493078 100000 0.4953963875 8.8424038022
8.7849493078 100000 0.4953963875 8.8424038022
8.7849493078 100000 0.4946043162 8.6912730635
8.7849493078 100000 0.4923944623 8.6331488883
8.7849493078 100000 0.4931040996 8.5024402499
8.7849493078 100000 0.4895641633 8.4823716266
8.7849493078 100000 0.4905341144 8.3552030609
8.7849493078 100000 0.4870004821 8.3071483338
8.7849493078 100000 0.4867816187 8.3041719566
8.7849493078 100000 0.4880488485 8.2091179894
8.7849493078 100000 0.4845741534 8.1899365961
8.7849493078 100000 0.4858045199 8.0943813166
8.7849493078 100000 0.4822749249 8.0744533266
8.7849493078 100000 0.4836250701 7.9805269453
8.7849493078 100000 0.4801437381 7.9612552962
8.7849493078 100000 0.4816088117 7.8969636888
8.7849493078 100000 0.4781198297 7.8495161719
8.7849493078 100000 0.4796450696 7.8141146136
8.7849493078 100000 0.4761488317 7.7665684215
NOMBRE VALOR
Temperatura Ambiente 25
Tempertura maxima 32
Temperatura coincidente 12
Angulo de la torre 22
A.S.N.M 800
Velocidad del viento maxima (Vrp max) 74.556
Velocidad del viento promedio (Vrp prom) 44.7336
Angulo del viento 90
Altura del suelo a primera fase 19.5
Altura del suelo a segunda fase 22.5
Altura del suelo a tercera fase 25.5
Altura del suelo a guarda 29.5
Vano viento suspension 1279.5275590551
Vano viento retencion 2329.3963254593
Vano peso suspension 890
Vano peso retencion 1100
Vano regulador suspension 400
Vano regulador retencion 1 250
Vano regulador retencion 2 850
Categoria del terreno C
Cantidas de discos 14
Peso de aislador 5
Largo del aislador 0.254
ancho del aislador 0.146
Longitud herrajes 0.6
Area de la cadena de aisladores 0.671576
Peso de los herrajes 22
Carga de mantenimiento 100
Coeficiete de dilatacion lineal guarda 0.00001455
Modulo de elasticidad guarda 12700
Carga de rotura guarda 8900
Peso guarda 565
Diametro guarda 14.25
Area guarda 98.9
EDS guarda 14%
Pv (Retencion viento max) 9.2290423902
Pv (Retencion viento prom) 3.3224552605
Pv (Suspension viento max) 9.808213562
Pv (Suspension viento prom) 3.5309568823
Pv (Aisladores viento max) 15.3804380536
Pv (Aisladores viento prom) 5.5369576993
Pv (Cable guarda retencion viento max) 9.6915698273
Pv (Cable guarda retencion viento prom) 3.4889651378
Pv (Cable guarda suspension viento max) 10.281455033
Pv (Cable guarda suspension viento prom) 3.7013238119
Q 0.00225
Factor de carga 1
Kz 1.1872678253
Kz (Guarda) 1.2569410466
Zh 73.8188976378
Zg 900
9.5
Kzt 1
Gw (Suspensio n) 0.6605314452
Gw (Retencion) 0.6215273219
Gw (Suspension guarda) 0.6540213929
Gw (Retencion guarda) 0.61649776
Gt 0.863159476
Kv 1.43
E 0.3088378822
E (Guarda) 0.2971152362
fm 7
K 0.005
Ls 220
Bt 0.8418198252
Bw (Suspension) 0.1769026212
Bw (Retencion) 0.1055906881
Cf (Cable) 1
Cf (Aislador) 1.2
Modulo de elasticidad fase 7251
Coeficiente de dilatacion lineal 0.0000208
Diametro del conductor de fase 29.59
Area del conductor fase 687.6695776694
Carga de rotura fase 11750
EDS fase 20%
Peso del cable de fase 1.605
Tension Vano regulador 1 retencion viento max fase 2627.34
Tension Vano regulador 2 retencion viento max fase 2406.08
Tension Vano regulador 1 retencion viento prom fase 2601.67
Tension Vano regulador 2 retencion viento prom fase 2376.94
Tension Vano regulador 1 retencion viento max guarda 1427.3
Tension Vano regulador 2 retencion viento max guarda 1304.04
Tension Vano regulador 1 retencion viento prom guarda 1411.94
Tension Vano regulador 2 retencion viento prom guarda 1274.18
UNIDAD DE MEDIDA
C
C
C
m
milla/H
milla/H
m
m
m
m
ft
ft
m
m
m
m
m
Kgf
m
m
m
m^2
Kgf
Kgf
1/C
Kg/mm^2
Kgf
Kg/Km
mm
mm^2
Lb/Pie^2
Lb/Pie^2
Lb/Pie^2
Lb/Pie^2
Lb/Pie^2
Lb/Pie^2
Lb/Pie^2
Lb/Pie^2
Lb/Pie^2
Lb/Pie^2
ft
ft
ft
Kgf/mm^2
1/C
mm
mm^2
Kgf
Kgf/m
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
CONDICION NORMAL
NOMBRE VALOR
Carga longitudinal (Retencion) FASE R 221.2600
Carga longitudinal (Retencion) FASE S 221.2600
Carga longitudinal (Retencion) FASE T 221.2600
Carga longitudinal (Suspension) FASE R 0.0000
Carga longitudinal (Suspension) FASE S 0.0000
Carga longitudinal (Suspension) FASE T 0.0000
Carga longitudinal (Retencion) GUARDA 123.2600
Carga longitudinal (Suspension) GUARDA 0.0000
CONDICION ANORMAL 1
NOMBRE VALOR
Carga longitudinal (Retencion) FASE R (ROTO) 1,411.9400
Carga longitudinal (Retencion) FASE S 224.7300
Carga longitudinal (Retencion) FASE T 224.7300
Carga longitudinal (Suspension) FASE R (ROTO) 2,601.6700
Carga longitudinal (Suspension) FASE S 0.0000
Carga longitudinal (Suspension) FASE T 0.0000
Carga longitudinal (Retencion) GUARDA (ROTO) 1,411.9400
Carga longitudinal (Suspension) GUARDA 0.0000
CONDICION ANORMAL 2
NOMBRE VALOR
Carga longitudinal (Retencion) FASE R (ROTO) 1,411.9400
Carga longitudinal (Retencion) FASE S (ROTO) 1,411.9400
Carga longitudinal (Retencion) FASE T 224.7300
Carga longitudinal (Suspension) FASE R 0.0000
Carga longitudinal (Suspension) FASE S 0.0000
Carga longitudinal (Suspension) FASE T 0.0000
Carga longitudinal (Retencion) GUARDA 1,411.9400
Carga longitudinal (Suspension) GUARDA (ROTO) 1,411.9400
UNIDAD DE MEDIDA
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
UNIDAD DE MEDIDA
Kgf roto
Kgf
Kgf
Kgf roto
Kgf
Kgf
Kgf roto
Kgf
UNIDAD DE MEDIDA
Kgf roto
Kgf roto
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf roto
CONDICION NORMAL
NOMBRE VALOR
Carga vertical (Retencion) FASE R 1,762,370.0000
Carga vertical (Retencion) FASE S 1,762,370.0000
Carga vertical (Retencion) FASE T 1,762,370.0000
Carga vertical (Suspension) FASE R 1,425,950.0000
Carga vertical (Suspension) FASE S 1,425,950.0000
Carga vertical (Suspension) FASE T 1,425,950.0000
Carga vertical (Retencion) GUARDA 721.5000
Carga vertical (Suspension) GUARDA 602.8500
CONDICION ANORMAL 1
NOMBRE VALOR
Carga vertical (Retencion) FASE R (ROT0) 1,321,820.0000
Carga vertical (Retencion) FASE S 1,762,370.0000
Carga vertical (Retencion) FASE T 1,762,370.0000
Carga vertical (Suspension) FASE R (ROTO) 1,069,505.0000
Carga vertical (Suspension) FASE S 1,425,950.0000
Carga vertical (Suspension) FASE T 1,425,950.0000
Carga vertical (Retencion) GUARDA (ROTO) 566.1250
Carga vertical (Suspension) GUARDA 602.8500
CONDICION ANORMAL 2
NOMBRE VALOR
Carga vertical (Retencion) FASE R (ROTO) 1,321,820.0000
Carga vertical (Retencion) FASE S (ROTO) 1,321,820.0000
Carga vertical (Retencion) FASE T 1,762,370.0000
Carga vertical (Suspension) FASE R 1,425,950.0000
Carga vertical (Suspension) FASE S 1,425,950.0000
Carga vertical (Suspension) FASE T 1,425,950.0000
Carga vertical (Retencion) GUARDA 721.5000
Carga vertical (Suspension) GUARDA (ROTO) 477.1375
UNIDAD DE MEDIDA
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
UNIDAD DE MEDIDA
Kgf roto vano peso al 75%
Kgf
Kgf
Kgf roto vano peso al 75%
Kgf
Kgf
Kgf roto vano peso al 75%
Kgf
UNIDAD DE MEDIDA
Kgf roto vano peso al 75%
Kgf roto vano peso al 75%
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf roto vano peso al 75%
CONDICION NORMAL
NOMBRE VALOR
Carga transversal viento (Retencion) FASE R 946.9838
Carga transversal viento (Retencion) FASE S 946.9838
Carga transversal viento (Retencion) FASE T 946.9838
Carga transversal viento (Suspension) FASE R 552.8179
Carga transversal viento (Suspension) FASE S 552.8179
Carga transversal viento (Suspension) FASE T 552.8179
Carga transversal viento(Aisladores) 50.4312
Carga transversal viento (Retencion) GUARDA 478.7438
Carga transversal viento (Suspension) GUARDA 278.9780
CONDICION ANORMAL 1
NOMBRE VALOR
Carga transversal viento (Retencion) FASE R (ROTO) 255.6856
Carga transversal viento (Retencion) FASE S 340.9142
Carga transversal viento (Retencion) FASE T 340.9142
Carga transversal viento (Suspension) FASE R (ROTO) 149.2608
Carga transversal viento (Suspension) FASE S 199.0144
Carga transversal viento (Suspension) FASE T 199.0144
Carga transversal viento (Aisladores) 18.1552
Carga transversal viento (Retencion) GUARDA (ROTO) 129.2608
Carga transversal viento (Suspension) GUARDA 75.3241
CONDICION ANORMAL 2
NOMBRE VALOR
Carga transversal viento (Retencion) FASE R (ROTO) 255.6856
Carga transversal viento (Retencion) FASE S (ROTO) 255.6856
Carga transversal viento (Retencion) FASE T 340.9142
Carga transversal viento (Suspension) FASE R 199.0144
Carga transversal viento (Suspension) FASE S 199.0144
Carga transversal viento (Suspension) FASE T 199.0144
Carga transversal viento (Aisladores) 18.1552
Carga transversal viento (Retencion) GUARDA 172.3478
Carga transversal viento (Suspension) GUARDA (ROTO) 75.3241
UNIDAD DE MEDIDA
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
UNIDAD DE MEDIDA
Kgf roto
Kgf
Kgf
Kgf roto
Kgf
Kgf
Kgf
Kgf roto
Kgf
UNIDAD DE MEDIDA
Kgf roto
Kgf roto
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf roto
CONDICION NORMAL
NOMBRE VALOR
Carga transversal angulo VR1 FASE R 1,002.6402
Carga transversal angulo VR1 FASE S 1,002.6402
Carga transversal angulo VR1 FASE T 1,002.6402
Carga transversal angulo VR2 FASE R 918.2034
Carga transversal angulo VR2 FASE S 918.2034
Carga transversal angulo VR2 FASE T 918.2034
Carga transversal angulo VR1 GUARDA 544.6834
Carga transversal angulo VR2 GUARDA 497.6451
CONDICION ANORMAL 1
NOMBRE VALOR
Carga transversal angulo VR1 FASE R 992.8441
Carga transversal angulo VR1 FASE S 992.8441
Carga transversal angulo VR1 FASE T 992.8441
Carga transversal angulo VR2 FASE R 907.0831
Carga transversal angulo VR2 FASE S 907.0831
Carga transversal angulo VR2 FASE T 907.0831
Carga transversal angulo VR1 GUARDA 538.8217
Carga transversal angulo VR2 GUARDA 486.2500
CONDICION ANORMAL 2
NOMBRE VALOR
Carga transversal angulo VR1 FASE R 992.8441
Carga transversal angulo VR1 FASE S 992.8441
Carga transversal angulo VR1 FASE T 992.8441
Carga transversal angulo VR2 FASE R 907.0831
Carga transversal angulo VR2 FASE S 907.0831
Carga transversal angulo VR2 FASE T 907.0831
Carga transversal angulo VR1 GUARDA 538.8217
Carga transversal angulo VR2 GUARDA 486.2500
UNIDAD DE MEDIDA
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
UNIDAD DE MEDIDA
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
UNIDAD DE MEDIDA
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
CONDICION NORMAL SUSPENSION
CARGA VERTICAL (V) VALOR
Carga vertical (Suspension) FASE R 1,425,950.0000
Carga vertical (Suspension) FASE S 1,425,950.0000
Carga vertical (Suspension) FASE T 1,425,950.0000
Carga vertical (Suspension) GUARDA 602.8500
TOTAL 4,278,452.8500
CARGA LONGITUDINAL (L) VALOR
Carga longitudinal (Suspension) FASE R 0.0000
Carga longitudinal (Suspension) FASE S 0.0000
Carga longitudinal (Suspension) FASE T 0.0000
Carga longitudinal (Suspension) GUARDA 0.0000
TOTAL 0.0000
CARGA TRANSVERSAL (T) VALOR
Carga transversal viento (Suspension) FASE R 552.8179
Carga transversal viento (Suspension) FASE S 552.8179
Carga transversal viento (Suspension) FASE T 552.8179
Carga transversal viento(Aisladores) 50.4312
Carga transversal viento (Suspension) GUARDA 278.9780
TOTAL 1,987.8628
UNIDAD DE MEDIDA
Kgf
Kgf
Kgf
Kgf
Kgf
UNIDAD DE MEDIDA
Kgf
Kgf
Kgf
Kgf
Kgf
UNIDAD DE MEDIDA
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
CONDICION ANORMAL SUSPENSION (CONDUCTOR FASE ROTO)
CARGA VERTICAL (V) VALOR
Carga vertical (Suspension) FASE R (ROTO) 1,069,505.0000
Carga vertical (Suspension) FASE S 1,425,950.0000
Carga vertical (Suspension) FASE T 1,425,950.0000
Carga vertical (Suspension) GUARDA 602.8500
TOTAL 3,922,007.8500
CARGA LONGITUDINAL (L) VALOR
Carga longitudinal (Suspension) FASE R (ROTO) 2,601.6700
Carga longitudinal (Suspension) FASE S 0.0000
Carga longitudinal (Suspension) FASE T 0.0000
Carga longitudinal (Suspension) GUARDA 0.0000
TOTAL 2,601.6700
CARGA TRANSVERSAL (T) VALOR
Carga transversal viento (Suspension) FASE R (ROTO) 149.2608
Carga transversal viento (Suspension) FASE S 199.0144
Carga transversal viento (Suspension) FASE T 199.0144
Carga transversal viento (Aisladores) 18.1552
Carga transversal viento (Suspension) GUARDA 75.3241
TOTAL 640.7690
O)
UNIDAD DE MEDIDA
Kgf
Kgf
Kgf
Kgf
Kgf
UNIDAD DE MEDIDA
Kgf
Kgf
Kgf
Kgf
Kgf
UNIDAD DE MEDIDA
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
CONDICION ANORMAL RETENCION (CONDUCTOR FASE Y GUARDA ROTO)
CARGA VERTICAL (V) VALOR
Carga vertical (Retencion) FASE R (ROT0) 1,321,820.0000
Carga vertical (Retencion) FASE S 1,762,370.0000
Carga vertical (Retencion) FASE T 1,762,370.0000
Carga vertical (Retencion) GUARDA (ROTO) 566.1250
TOTAL 4,847,126.1250
CARGA LONGITUDINAL (L) VALOR
Carga longitudinal (Retencion) FASE R (ROTO) 1,411.9400
Carga longitudinal (Retencion) FASE S 224.7300
Carga longitudinal (Retencion) FASE T 224.7300
Carga longitudinal (Retencion) GUARDA (ROTO) 1,411.9400
TOTAL 3,273.3400
CARGA TRANSVERSAL (T) VALOR
Carga transversal viento (Retencion) FASE R (ROTO) 255.6856
Carga transversal viento (Retencion) FASE S 340.9142
Carga transversal viento (Retencion) FASE T 340.9142
Carga transversal viento (Aisladores) 18.1552
Carga transversal viento (Retencion) GUARDA (ROTO) 129.2608
Carga transversal angulo VR1 FASE R 992.8441
Carga transversal angulo VR1 FASE S 992.8441
Carga transversal angulo VR1 FASE T 992.8441
Carga transversal angulo VR1 GUARDA 538.8217
TOTAL 4,602.2840
E ROTOS)
UNIDAD DE MEDIDA
Kgf
Kgf
Kgf
Kgf
Kgf
UNIDAD DE MEDIDA
Kgf
Kgf
Kgf
Kgf
Kgf
UNIDAD DE MEDIDA
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
Kgf
ECUACIN DE CAMBIO DE ESTADO
DATOS DE ENTRADA
E (kgf/mm )2
7251.00
rea (mm2) 687.67
a ( /C) 2.08E-05
Temperatura inicial ( C) 25.00
Fuerza en EDS (kgf) 2350.00
w1 (kgf/m) 1.605
Dimetro (mm) 29.59
Presin del viento (kg/m2) 3.322
Fuerza del viento sobre Conductor 0.098
Fuerza del viento Total 0.098
w2 1.608
Vano regulador (m) 250
CAMBIO DE ESTADO
T final (C) 12
A 2358.75
B 33575537357.07
Xo 2601.67
Xn 2601.67
DATOS DE ENTRADA
E (kgf/mm )2
12700.00
rea (mm2) 98.90
a ( /C) 1.46E-05
Temperatura inicial ( C) 25.00
Fuerza en EDS (kgf) 1246.00
w1 (kgf/m) 0.565
Dimetro (mm) 14.25
Presin del viento (kg/m2) 3.489
Fuerza del viento sobre Conductor 0.050
Fuerza del viento Total 0.050
w2 0.567
Vano regulador (m) 850
CAMBIO DE ESTADO
T final (C) 8
A 6218.09
B 12163916700.15
Xo 1274.18
Xn 1274.18