Vous êtes sur la page 1sur 16

Ocean Engineering 89 (2014) 157172

Contents lists available at ScienceDirect

Ocean Engineering
journal homepage: www.elsevier.com/locate/oceaneng

Flushing ballast tanks


Zhixin Qi n, Ian Eames, Alistair Greig
University College London, Torrington Place, London WC1E 7JE, UK

art ic l e i nf o a b s t r a c t

Article history: The International Maritime Organization requires ballast water tanks to be ushed through with three
Received 7 May 2013 tank volumes to remove aquatic species. We apply a network model for multiply connected compart-
Accepted 30 July 2014 ments to analyse the inuence of internal geometry and inletoutlet positions on how much of the
initial water of each compartment is ushed in time. A complementary experimental study was
Keywords: undertaken to quantify the ushing from 2  2, 3  3 and 5  4 tank congurations by an optical method.
Ballast water The agreement between the predictions and measurements is good. The results show that the ushing in
Flushing efciency a multi-compartment tank is generally more efcient than perfect mixing. The 95% reduction is met after
Fluid mixing three exchange volumes in all cases. The outlet needs to be positioned far from the inlet to reduce
Multi-compartment tank
bypassing through the tank. These results are nally discussed in the context of international regulations
for ushing ballast tanks.
& 2014 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY license
(http://creativecommons.org/licenses/by/3.0/).

1. Introduction pumping through three times the volume of each ballast tank
was considered to meet the standard. Pumping through less than
The largest fraction of the world's trade is transported by ships three times the volume may be acceptable if the procedure can
with estimates varying from 66% to 80% (see Wright and Mackey, demonstrate that at least 95% of original ballast water is removed.
2006). Ballast is essential for the safe operation of ships; it ensures The original intention of the Ballast Water Convention was that
stability, trim, and structural integrity by maintaining shear the water exchange technique would be a short-term solution and
stresses and bending moments within acceptable limits. The be replaced by water treatment. When the Convention was
ballast on most ships is usually achieved using water, and the written no ballast water treatment plants were in production.
amount of ballast water transferred globally each year is estimated Their development has been slower than expected due to various
to be 10 billion tonnes (see Wright and Mackey, 2006; MacPhee, reasons including an underestimation of the technical challenges,
2006). Ships usually discharge ballast water in ports while loading insufcient resources and market economics (see King et al., 2012).
and take up ballast water in destination ports while unloading, The magnitude of the logistical effort required for effective
where the water is shallow and rich in aquatic organisms. Taking enforcement and regulation of various aspects of the Convention
up non-indigenous species (NIS) in one port and transporting have also been identied as potential barriers to implementation
them to another sea can lead to signicant environmental pro- (see Wright, 2012). These are some of the reasons that the
blems. Zebra mussels, native to the Caspian Sea region of Asia but Convention is still not ratied even though some of its initial
transported to the Great Lakes via ballast water, reduce the deadlines for implementation have already passed. The situation is
amount of phytoplankton available for other organisms and cost complex but the outcome is that ballast water exchange is still in
$100 M/year to manage control measures (see Pimentel et al., widespread use and will continue to be so for quite some time.
2000). In order to prevent the transfer of aquatic organisms from Moreover some authorities are now insisting on a combination of
one region to another via ballast water, the International Maritime ballast water exchange and treatment. It is also becoming clear
Organization adopted the Ballast Water Management Convention that a much more detailed understanding of the ow behaviour
in 2004. According to Ballast Water Exchange Standard, Regulation within ballast tanks is required for compliance assessment and
D-1 of the Convention, ships utilising the exchange method need enforcement once ballast water treatment is introduced.
to exchange ballast water at least 95% by volume; for ships Ballast tank designs are currently driven entirely by structural
exchanging ballast water by the pumping-through method, considerations of the vessel, customised for maximum cargo
capacity and practicality of human access and construction. The
tanks are structurally complex and composed of interconnected
n
Correspondence to: Mechanical Engineering, University College London, Tor-
bays, longitudinal and transverse stringers/stiffeners to improve
rington Place, London WC1E 7JE, UK. the strength of the vessel. The usual layout of ballast tanks on a
E-mail address: zhixin.qi.10@ucl.ac.uk (Z. Qi). bulk carrier consists of the tanks located at the fore peak, aft peak,

http://dx.doi.org/10.1016/j.oceaneng.2014.07.022
0029-8018/& 2014 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY license (http://creativecommons.org/licenses/by/3.0/).
158 Z. Qi et al. / Ocean Engineering 89 (2014) 157172

upper/topside wing, lower/hopper wing and bottom. The double shown in Fig. 2. The ballast tank ushing is achieved either from
bottom tank and hopper tank are unied and in some cases are the inlet as shown in Fig. 1(b) by the sequential (empty/rell)
connected with the upper wing/topside tanks by a trunk that method or through overow arrangements by the ow through
allows the ballast water to ow between them. Fig. 1 shows a method. For the ow-through method, the overow is achieved
schematic of the ballast tanks of a bulk carrier. Other tankers have from two air/sounding pipes either on the deck or to the side,
slimmer ballast water tanks along the ship and do not alternate. typically with a diameter of 0.150.2 m.
These ballast tanks are large with a simple box design, and have a The NIS that can be drawn into a ballast tank range from
capacity of 40,500 m3 of water serviced by pumps with a ow rate bacteria, plankton, sh eggs or crabs to sh (see Wonham and
of 3000 m3/h (or  1 m3/s). Carlton, 2005). Associated with these is a settling or swimming
Inside the double bottom tank, individual compartments are velocity, ranging from 0.1 to 150 mm/s (see Wong and Piedrahita,
generated by crossing longitudinal and transverse stiffeners and 2000; Magill et al., 2006). The smaller species are essentially
frames with lightening holes. The neighbouring compartments are advected with the ow and can be regarded as essentially passive
associated with lightening holes, stringers and limber holes, during ushing. When the species are passive, the fraction of the

Fig. 1. Schematic drawings showing (a) oblique and (b) cross-section view of a ballast tank. The tanks are separated into port and starboard chambers (redrawn from
Armstrong, 1997).

Fig. 2. Photographs of the interior geometry of a ballast tank showing (a) an inlet nozzle, (b) a lightening hole, (c) top limber holes, and (d) stringers with lower limber holes
(taken from Steinhauer, 2007).
Z. Qi et al. / Ocean Engineering 89 (2014) 157172 159

original water that is ushed out of the ballast tank can be used as nodes represent rooms/spaces and the connectors represent path-
a proxy for estimating the removal of NIS from the tanks. The ways. The system enables the average ow and mass transfer rate
current legislation deals with the number of exchange volumes between different rooms based on the mass conservation and
that are required to achieve a level of ushing. Future treatment energy balance equations to approximate how materials or ener-
strategies are likely to do with reushing and cleaning while the gies are transmitted among the compartments of the multibody
ship is in transit, and again, knowledge of the distribution of uid delivery system by assuming each room homogenous (see
treated ballast water will be useful. Chang et al., 2003). In the context of the ventilation literature,
There are comparatively few theoretical studies of the ow within researchers dealt with an algebraic set of equations detailing the
multi-compartment tanks. Wilson et al. (2006) and Chang et al. (2009) ux between rooms/windows with empirical closures for the
used CFD to examine the movement of uid in a 1/3-scale double pressure drop coefcients characterising the ow between spaces.
bottom tank and a full-scale ballast tank from a typical bulk carrier. For example, Zhao et al. (2003), Engdahl (1999) and Chu et al.
When density contrast between the incoming seawater and the (2009, 2010) have applied multizone models to simulate air
original freshwater was relatively large, the predicted ushing ef- velocity and temperature distributions in ventilated rooms.
ciency fell short of the required 95% replacement after three volumes Available methodologies to study ballast water exchange
exchange for both tanks, due to trappage in the tank tops. They found include eld measurements, CFD, reduced models and small-
that the introduction of stringers encouraged plug ow where it might scale experiments. Although eld experiments are the most
be expected that a more complex internal geometry would enhance convincing method, they are expensive and restricted to specic
mixing, and inferred that the addition of vent holes in the tank tops types and therefore cannot provide general laws for all kinds of
would allow for some movement of the trapped uid. In the context of ships. For example, at three volumes ushing, the ballast water
water treatment, Ta and Hague (2004) examined the ow through a exchange efciency is 99% for commercial oil tankers (Ruiz et al.,
multi-compartment ozone contactor, and achieved a mixed ow 2005), 95% for bulk carriers (Rigby and Hallegraeff, 1994) and 87%
condition in the contact zone and a plug ow condition in the decay for containerships (Ruiz and Reid, 2007). The dye samples were
zone. However, due to the complexity of the calculations and long collected from the surface, 10 m deep and bottom of deck hatches.
running time, it is difcult to implement CFD for practical design Due to limitations on tank access and sampling equipment, on-
purposes (see Chu et al., 2009). board experiments generally rely on measurements taken at the
Meanwhile, there are few experimental studies of ow and overow outlet of the tank do not necessarily represent the
ushing in ballast tanks. Kamada et al. (2004) measured the volume mixture that remains in the ballast tank (Wilson et al.,
dilution rate of the uid inside a two-dimensional square single 2006). CFD can provide detailed results, but the major challenge is
tank using an optical method and also numerically analysed the grid generation for such complex geometry and grid resolution.
uid ow. After three exchange volumes by the ow through There is limited understanding of the vortex shedding ow due to
method, about 95% of the original uid was removed. The the sharp edge of the lightening holes between compartments.
inuence of density contrast between the injected water and The reduced mathematical model is restricted to simple ows, but
ballast water was examined by Eames et al. (2008) for a J-type time saving and easy to extend. The dimensionless groups char-
ballast tank with a planar geometry. In the absence of density acterising small-scale tests may not match those of eld problems,
contrast between the ballast water and that used to ush the tank, which may restrict their applicability, but they tend to be easier to
the high aspect ratio of tank geometry (along the base and the operate. Therefore, in this study a reduced model is developed and
vertical sections) meant that a bulk Pclet number (based on a validated by laboratory scale experiments.
turbulent diffusivity) was high 4 100 so that the transport out of There is currently a signicant gap in understanding how water
the tank was largely through displacement. This is because the that is initially in a ballast tank is removed by ushing. The purpose of
mixed interface between the incoming and the original uid this paper is to examine quantitatively how much of the initial water
(perpendicular to the mean ow) was much smaller than the in idealised models of ballast tanks is removed using the current
overall distance from the source and exit. Wilson et al. (2006) and strategy of ushing. The focus in this paper is on scenarios where
Chang et al. (2009) tested a 1/3-scale 2  2 compartmented double ushing occurs in waters with similar composition of the port water,
bottom tank. When density contrast was large, there was still where buoyancy effects are negligible. In the context of relatively
mostly unmixed original uid trapped between the stringers near closed systems, such as the Mediterranean and Baltic Seas, this
the tank tops after three volumes exchange. They found that assumption of uniform density is appropriate especially since the
decreasing the density contrast and increasing the inow rate ballast water is taken at depths of 12 m beneath the free surface,
may improve mixing within the tank. similarly for seawater ports such as Singapore. For those ports near
There are considerably more studies in a closely related area of estuaries (e.g. Shanghai, New York, Hamburg, etc.), the change in
air movement and ventilation within rooms and between rooms density may be signicant, this assumption is clearly not appropriate.
within buildings. Chen et al. (2010) assessed various types of In also trying to assess the inuence of proposed cleaning technologies
models used to predict the ventilation performance in buildings. (ozone, UV, centrifugal separation), which are applied in transit, the
Many studies have focused on ow between rooms or boxes. density contrast between re-injected (cleaner) water and ballast water
Bolster and Linden (2007) examined ushing of contaminants can be neglected. However, if ballast water is cleaned by heat, the
from naturally ventilated rooms with comparison with Hunt and treated water is lighter than the original water. The new element of
Kaye (2006), and found displacement ventilation may not be the paper involves development of a robust multizone model for
better than traditional mixing systems at removing contaminants. ballast water ushing and a detailed comparison against experimental
In the context of forced ventilation, Eames et al. (2009) examined results. To understand the inuence of outlet arrangements and
the transient concentration of a continuous source of passive dye, compartment congurations on the ushing efciency, we examine
which was injected into an acrylic model of a hospital isolation the temporal and spatial uid exchange experimentally.
room. The measurement of the average concentration for the case The paper is structured as follows. In Section 2, we describe how
of forced ventilation was in agreement with a simple model based we set up the mathematical model and the diagnostic tools used to
on perfect mixing. Multizone transport models are an alternative interpret the results which are discussed in the context of simplied
to CFD models for investigating heat and pollutant transport in geometries; in Section 3, we apply the model on ballast tanks with
multi-room structure, which simplify the behaviour of spatially different compartment congurations and outlet arrangements; in
distributed physical systems into a topological network where Section 4, we present the experimental setup and methodology; in
160 Z. Qi et al. / Ocean Engineering 89 (2014) 157172

Section 5, we analyse the experimental results and compare with perfect. The water exchange within the tank represents the
the model prediction; in Section 6, we conclude. removal of the NIS. Fig. 3(a) shows a schematic plan view of a
general tank conguration consisting of m by n interconnected
rectangular compartments, and the notation used in the mathe-
2. Mathematical model of multizone ow
matical model. The box structure of most ballast tanks means that
this topological network (see Wu et al., 2012; Weinlder et al.,
The water used to ush a ballast tank is typically pumped into
2012; Joekar-Niasar et al., 2010) is appropriate. This type of
the tank at a rate Q  1 m3 =s. As we move farther away from the
analysis is easily extendable to other topological networks. A
inlet nozzle, the mean ow decays quite quickly. It is important to
compartment at the ith row and the jth column of the tank is
estimate typical values as these variables determine the type of
referenced as ij. The bottom right-hand corner compartment is
modelling approach and the validity of the experimental analogue
the pipe entrance to the ballast tank, while the top left-hand and
described later. The ballast tanks in a large ship are characterised
right-hand corner compartments are two outlets. The tank is not
by a typical length L 50 m, width Wh 20 m of the base and
constrained to the horizontal plane and may fold as it progresses
Wv 0.5 m of the vertical region, height Hh 2 m of the horizontal
from the double bottom of a ship up its sides. Water with the same
region and Hv 25 m of the vertical region, and the nominal
density as the water in the tank is injected through the inlet. Fig. 3
diameter of the inlet nozzle D 0.5 m. The mean ow velocity
(b) shows a schematic of a generic compartment within the ballast
through the nozzle is U n 4Q = D2  5 m=s. The ow in a ballast
tank. pij is the pressure of compartment ij. The volume ux
tank is characterised by the Reynolds number Re UL=, where
from compartment i1 j1  to its neighbouring compartment i2 j2 
is the kinematic viscosity of water, 10  6 m2 =s. We start using
(here i1 i2 , jj1 j2 j 1 or j1 j2 , ji1  i2 j 1) through an orice
an assessment of the typical velocity and length scales in a ballast
with cross sectional area Ai1 j1 ;i2 j2  is dened as
tank, where U and L are the characteristic velocity and lengthscale Z
of the ow, respectively. The inlet nozzle Reynolds number is f i1 j1 ;i2 j2  u  n^ dA; 1
Ren U n D=  106 . Based on the horizontal section, U h Z Ai1 j1 ;i2 j2 

Q =0:5 W h H h  10  2 m=s, Reh U h H h =  104 . Up the riser sec-


where u is the velocity, n^ is a unit normal vector directed from
tion, U v Q =LW v  10  2 m=s, so Rev U v W v =  104 . Thus the
compartment i1 j1  to compartment i2 j2 . The fraction of water
ow in a ballast tank is inertially dominant so that Re is high and
in compartment ij (of volume V ij ) that has been ushed out is
the ow is turbulent.
dened as
The purpose of this model is to quantify how ushing efciency Z
varies within a tank. The fraction of initial water that is ushed out 1
C ij C dV : 2
of the tank serves as a useful metric of the ability of ushing to V ij V ij
remove NIS. This can be estimated experimentally by dyeing the
The ushed fraction is calculated as a function of dimensionless
inlet water used for ushing and measuring the fraction of water
time T, based on ushing the total tank volume (V), i.e.
in the tank which is dyed. Mathematically, this is equivalent to
setting the dye water fraction as C 0 initially within the tank and Qt
T ; 3
C 1 on the inlet ow the average of C over the tank represents a V
measure of the ushed fraction. where T 0 corresponds to the tank starting to be ushed.
We develop a system of ordinary differential equations by
2.1. Mathematical modelling integrating over individual compartments. The inertial force of
the uid is sufciently large when compared to the buoyancy force
The model assumptions are (a) the density difference between so that the latter can be ignored. The basis of the model is that the
the inlet and the ballast water has a negligible effect dynamically, incoming matter is well mixed and p is the same within each
(b) the NIS are passive and (c) mixing within the compartments is compartment, but the gradients of p and C between compartments

Fig. 3. Plan view of the congurations of (a) an m  n tank with one inlet and two outlets; (b) its generic compartment ij with notations of pressure, ushed fraction as
well as ow rate; (c) a bafe with an orice between two neighbouring compartments. Inlet is taken to be located in compartment 11 and two outlets are in compartments
m1 and mn.
Z. Qi et al. / Ocean Engineering 89 (2014) 157172 161

are important. Integrating the continuity equation over compart- identied when half of the original uid in compartment [i][j] has
ment [i][j] gives been ushed out, mentioned as half ushed time
f ij;in  f ij;out 0; 4 T 1=2;ij TjC ij 1=2 ; 8

where f ij;in and f ij;out are the volume inow rate and the volume and 1=2;ij represents the characteristic ushing rate, at which
outow rate, respectively. compartment [i][j] is being ushed when half of its original uid
For steady ows, the multizone model of ow between has been ushed out (that is, when T T 1=2;ij )
compartments employs a semi-empirical closure model to relate V dC 
the pressure drop with the average velocity through the holes. The 1=2;ij ij ij T T 1=2;ij : 9
V dT
approach adopted here is consistent with other studies (see Chu
et al., 2009; Mora et al., 2003; Tan and Glicksman, 2005). The The ushing efciency C , is dened as the fraction of the
pressure difference between two neighbouring compartments original uid that has been ushed out of the whole tank, i.e.
i1 j1  and i2 j2  is i j C ij V ij
C T : 10
jf i1 j1 ;i2 j2  jf i1 j1 ;i2 j2  i j V ij
pi1 j1   pi2 j2  i1 j1 ;i2 j2  : 5
A2i1 j1 ;i2 j2  The diagnostics are applied to analyse the results from the multi-
zone model and the experimental results.
Here i1 j1 ;i2 j2  is the local pressure loss coefcient between
compartment i1 j1  and i2 j2 , which is assumed to be constant.
The pressure loss coefcient is usually determined empirically. 3. Application of the model
For instance, for ow through a sharp-edged circle orice (see Cao
et al., 2011; Charles et al., 2005; Chu et al., 2009) which is typical We illustrate the effect of geometry on ushing by examining a
of the connection between compartments in ballast tanks, the series of tanks with increasing geometrical complexity from a
pressure loss coefcient can be estimated by (Chu et al., 2010) 2  2, 3  3 to 5  4 tank. To build up a physical picture of the
2:581  exp  60; 6 dynamics, we rst analyse the simplest conguration a four
connected compartment arrangement with one inlet and two
where is the ratio of the cross-sectional area of the orice to the outlets, shown in Fig. 4(a). In order to simplify the analysis, we
cross-sectional area of the partition wall. assume that the four compartments have the same shape and
The uid is transported by the mean ow and mixed by dimensions, and all the four holes between neighbouring com-
turbulent dispersion. The mean ow is largest in the passage partments are the same thin-wall circular orices in size, height
between compartments and is smallest within compartments. and resistance. Similarly for the 3  3 case (see Fig. 4(b)), all the
Integrating the ushed fraction over compartment ij, we have circular orices between neighbouring compartments are geome-
an approximate model describing the variation of the ushed trically congruent and same in height.
fraction with time, i.e.
dC ij 3.1. Application to a 2  2 tank
V ij f ij;in C ij;in  f ij;out C ij ; 7
dt
The solution is determined by four mass conservation equa-
where C ij;in is the ushed fraction in the compartment(s) owing
into compartment [i][j]. The general multizone model that consists tions by setting m n 2 in Appendix A:
of (4), (5) and (7) for an m  n tank is described in more detail in f 11;12 f 11;21 Q ; f 11;12 f 12;22 ; f 11;21 f 21;22 Q 21;out ;
Appendix A. f 12;22 f 21;22 Q 22;out ; 11

and four empirical closures for the pressure drop:


2.2. Diagnostic tools
jf 11;12 jf 11;12 jf 21;22 jf 21;22
p11  p12 11;12 ; p21  p22 21;22 ;
The mathematical model generates a time series for the ushed A211;12 A221;22
fraction of water in each compartment. A set of diagnostic tools jf 11;21 jf 11;21 jf 12;22 jf 12;22
are required to quantify the timescale when each compartment is p11  p21 11;21 ; p12  p22 12;22 :
A211;21 A212;22
ushed and the rate at which they are ushed by the incoming
water. The dimensionless characteristic time T 1=2;ij for ushing is 12

Fig. 4. Elevated schematic of a (a) 2  2 square tank, (b) 3  3 square tank, and (c) 5  4 J-type tank with one inlet and two outlets. The inlet and outlets on the top of the
tanks are indicated.
162 Z. Qi et al. / Ocean Engineering 89 (2014) 157172

In this example, we consider the inuence of outlet arrangement 3.2. Application to a 3  3 tank
on ushing where the geometry of the lightening holes is the
same. Here 11;12 21;22 11;21 12;22 and A11;12 A21;22 As the number of compartments increases, the complexity of
A11;21 A12;22 . When only the far outlet is open (Q 21;out 0, the dynamics increases. The predictions of the variation of the
p22 0), the solution to the equation array is ushed fraction in compartments 12, 13, 22 and 23 of the 3  3
tank are shown by the curves in Fig. 7. For all the three outlet
Q
f 11;12 f 11;21 f 12;22 f 21;22 ; Q 22;out Q ; 13 arrangements, C 12 4 C 22 4 C 13 4 C 23 . Compartment 12 is ushed in
2
a similar manner for the three cases because the ux through
when only the near outlet is open (Q 22;out 0, p21 0), after these compartments is weakly dependent on the global inuence
manipulation, the solution is of the boundary condition. Compared with far open, compart-
p p p ments 13, 22 and 23 for the near open case are ushed more
3  1Q 1  3Q 3  3Q slowly. For the both open case, these compartments are ushed
f 11;12 f 12;22 ; f 21;22 ; f 11;21 ;
2 2 2 more slowly than those for far open, but faster than those for
Q 21;out Q ; 14 near open. The model predicted characteristic ushing rate
versus the half ushed time for each compartment is shown in
when both outlets are open p21 p22 0, the uxes between the the left of Fig. 8. In all cases, compartment 11 is characterised by
compartments are 1=2;11 1=2 and T 1=2;11 ln 2=9. For the far open case, due to the
p symmetry of the ow, 1=2;12 1=2;21 , 1=2;13 1=2;31 , and
f 11;12 f 12;22 Q 22;out 2  1Q ; f 21;22 0; 1=2;23 1=2;32 (see Fig. 8(a,i)). Compartment 33 is always ushed
p at a slower rate than all the other compartments. The farther a
f 11;21 Q 21;out 2  2Q : 15
compartment is from the inlet, the more slowly it is ushed. From
The ushed fraction in each compartment evolves according to Fig. 8(b,i), it can be seen that there are three groups of accumu-
the following: lated points: compartments 21 and 12, compartments 31, 22 and
13, and compartments 32 and 23. In general, compartments are
dC 11 V
1  C 11 ; half ushed at a later time in the both open case than in the far
dT V 11 open case, but earlier than those in the near open case.
 
dC 12 V f 11;12 f
C 11  12;22 C 12 ;
dT V 12 Q Q 3.3. Application to a 5  4 tank

dC 21 V f 11;21 f
C 11  21;22 Hf 21;22 C 21 Fig. 4(c) shows a schematic of a 5  4 tank which consists of
dT V 21 Q Q
compartments which have a rectangular footprint, and holes between

Q neighbouring compartments are not the same in size and number (see
H f 21;22 C 22  21;out C 21 ;
Q Table 1). The resistance coefcients used to close the system of
 equations were estimated using (6). The theoretical predictions of
dC 22 V f 12;22 f 21;22
C 12 Hf 21;22 C 21 the variation of the ushed fraction eld are shown in Fig. 9(ac;i). For
dT V 22 Q Q
all the three outlet arrangements, the tank is ushed from the right

Q 22;out bottom to the left top. At T0.25, the difference of the fraction eld
H f 21;22 C 22  C 22 ; 16
Q among these three cases is not signicant. But at a later time, the tank
is most efciently ushed for the far open case, and more original
and satises the initial condition uid remains on the left corner compartments for the near open case.
C ij jT 0 0: The predictions of the characteristic ushing rate versus the half
ushed time for each compartment are shown in the left of Fig. 10. The
The Heaviside function (where HX 1 for X Z0 and HX 0 for points donating 1=2 versus T 1=2 are grouped into two parts associated
X o0) is needed to prevent ow in the wrong direction. with the equal sized horizontal compartments (the rst to the fourth
The system of coupled linear differential equations can be rows of the tank) and the larger vertical compartments (the fth row).
solved analytically and the solution for V ij =V 1=4 is given in The horizontal compartments behave similarly for each case, because
Appendix B. The curves in Fig. 5 show the predicted ushed the global character of the ushing depends more weakly on the
fraction variation in each compartment of the 2  2 tank for the outlet arrangement as the number of compartments increases. In
three cases considered. In all cases, C22 is the slowest to be ushed general, the nearer a compartment is located to the inlet, the faster
as a consequence of being the farthest from the inlet. For the far and earlier it is ushed, leading to a bow-shaped decrease of the
open case, the symmetry in the ow pathways means that scatter plot of 1=2;ij versus T 1=2;ij (see Fig. 10(ac;i)). For all cases,
C 12 C 21 . For the near open case, there is a crossover between T 1=2;11 ln 2V 11 =V, 1=2;11 1=2. For a large number of compart-
C12 and C21. This is because while f 11;21 4 f 11;12 leads to an initially ments, we expect that the ow is radial for short time where
faster increase in C21, at a later time, the uid with a lower ushed ur  2Q = rH h , where r is the distance from the inlet. This gives an
fraction is being transported from compartment 22 to 21 leading approximate relation 1=2  T 1=2 1
, which is conrmed by plotting
to C 12 4 C 21 . For the both open case, the ow largely passes Fig. 10 on a loglog scale. The relative positions of the points denoting
through compartment 21 as C 21 4 C 12 . the vertical compartments to those for the horizontal compartments
Fig. 6(ac;i) summarises the characteristic ushing rate versus are different for different outlet arrangements. The vertical compart-
the half ushed time in each of the compartments. In all cases, ments are ushed more slowly and later in the both open case than
1=2;11 1=2, T 1=2;11 ln 2=4 since the compartments are all the in the far open case, but faster and earlier than in the near open case.
same size. The increases for compartments 12 and 21 are quite
similar in all cases. While from Fig. 6(b,i), compartment 12 is 3.4. Flushing efciency of the tanks
ultimately ushed slightly faster than 21, the values of 1=2 , T 1=2
do not capture this because they describe the initial characteristics The ushing efciency in the whole tank (dened by (10)) is
of ushing. Compartment 22 is ushed at similar rates in both the shown in the left of Fig. 11 for the three tanks, and compared against
near open and both open cases. the pure displacement and perfect mixing. For each case, the ushing
Z. Qi et al. / Ocean Engineering 89 (2014) 157172 163

Fig. 5. The theoretical predictions and the corresponding experimental measurements of the ushed fraction variation in each compartment of a 2  2 tank. C ij;T represents
theoretical predictions, while C ij;E represents experimental measurements. The gures correspond to (a) far open, (b) near open, and (c) both open cases.

efciency is intermediated between the pure displacement and perfect 4.1. Experimental apparatus
mixing. Table 2 summarises the ushing efciency at T3. For all the
three tanks, the ushing efciency is the highest in the far open case, Two acrylic model tanks were employed in the experimental
and the lowest in the near open case. This is because when the outlet study. The geometric scale ratio is 50. One was a square tank of
is placed far from the inlet, the incoming uid has more chance to mix width 61 cm and height 20 cm, shown in Fig. 12(a and b). Three
with the initial uid and thus the latter can be replaced more PVC pipes with valves were inserted through the cover into the
efciently. Also, it can be seen that when a tank is divided into many tank as potential inlets, and on the other side of the cover, another
compartments, the ow behaves like the displacement mode, as the three PVC pipes were inserted into the tank as potential outlets.
incoming uid will leave the tank when it has mixed more sufciently Clamps and sealing trips were used to give a water tight seal to the
with the initial uid (except for some near open cases). Therefore, tank. To generate the 2  2 and 3  3 internal congurations, six
subdividing a ballast tank would improve the total ushing efciency. plates in total were employed, each of which was 61 cm long,
The critical point is that for all the tanks considered, the ushing 20 cm high and 1 cm thick. There was a 10 cm long and 1 cm thick
efciency is greater than 95% at three exchange volumes (T3) that is gap in the middle of each plate, so that the two plates each of
required by the IMO protocols. The model predictions will be which has two circular holes could be crossed each other and
compared against laboratory scale experiments. inserted into the tank to generate the 2  2 internal conguration
(see Fig. 12(a)) and the other four plates each of which has three
circular holes could be crossed each other to generate the 3  3
4. Experimental study internal conguration (see Fig. 12(b)). All these circular holes had a
diameter of 10 cm and located in the middle height between two
A series of experiments were undertaken to provide a means of neighbouring compartments. The tank volume is 75 l.
testing quantitatively the capability of the ushing model to capture The second was a J-type tank consisting of 5  4 compartments
the exchange processes in multi-compartment tanks. We studied with one inlet and two outlets, which was designed based on the
the ushing processes in a 2  2, 3  3 and 5  4 tank. To reduce the typical geometry of a ballast tank (see Fig. 12(c)). The orices
number of variables, the ow rate was xed to examine different between compartments in the longitudinal and transverse directions
outlet arrangements for each compartment conguration. were different. This tank was characterised by a horizontal section
164 Z. Qi et al. / Ocean Engineering 89 (2014) 157172

Fig. 6. The theoretical predictions of the scatter plot 1=2 versus T 1=2 in each compartment are shown on the left (i), with the corresponding experimental results on the right
(ii) for a 2  2 tank. The gures correspond to (a) far open, (b) near open, and (c) both open cases. The bar on point 22 gives an indication of the experimental error.

(double bottom tank), turning section (hopper tank), internal geo- 4.2. Experimental procedure
metry with longitudinal and transverse frames, the lling pipes and
two overow arrangements with xed height. Semicircular limber For each tank conguration, similar to the theoretical study,
holes were added at the top and bottom of each interconnecting wall three outlet arrangements were considered: far open, near open,
of width and depth 0.8 cm. The model tank was designed to be and both open. The inow rate was xed at Q0.25 l/s, which is
geometrically complex, the detailed structure and dimensions of the maximum ow rate we can achieve accurately in our labora-
which are listed in Table 1. Water was pumped in through a 2-cm tory. For both tanks, the Reynolds number at the nozzle exit was
diameter hole at the ceiling of the horizontal section, and exited from Ren  8000. At some corner compartments, Re  1000 for the
funnels xed at height 28 cm of the tank. The total volume of the square tank, Re  600 for the J-type tank.
tank is 75 l: each of the 16 horizontal compartments has a volume of At the start of each experiment, the tank was lled with clear
2.5 l, and the volume of compartments 51, 52, 53 and 54 is 8 l, 9.5 l, water, and then a dilute methylene blue dye solution (concentration
9.5 l and 8 l, respectively. of 0.1 mg/l) was pumped into the tank via the inlet. Images were
The acrylic models were placed in a large tank and illuminated taken at a rate of 7.5 frames per second by an Allied Vision Dolphin
by a uniform diffuse light source placed beneath; an inclined mirror machine vision and saved as a BMP le every 100 frames. Matlab
was placed above the tank to obtain the plan view (see Fig. 12(c)). Image Processing Toolbox was employed to analyse these images.
Z. Qi et al. / Ocean Engineering 89 (2014) 157172 165

Fig. 7. The theoretical predictions and the corresponding experimental measurements of the ushed fraction variation in four selected compartments of the 3  3 tank. C ij;T
represents theoretical predictions, while C ij;E represents experimental measurements. The gures correspond to (a) far open, (b) near open, and (c) both open cases.

4.3. Experimental principle and analytical tools in compartment [i][j] is


R
A C I dA
The experiments involved measuring the fraction of initial water in C ij T R ij ; 18
each compartment that is ushed out when water is injected into the Aij C I; dA

tank. With the help of the inclined mirror, the camera captured a plan where C I; is the depth integrated dye concentration when
view of the tank. Dye water was injected into the tank (see Kamada compartment [i][j] is completely lled with dye water, calculated
et al., 2004). An optical method was used to assess the mass of dye from (17), and A[i][j] is the base area of compartment [i][j].
within each compartment based on the classical absorption theory of The main point was to determine the fraction of initial uid in
LambertBeer (see Cenedese and Dalziel, 1998; Rahim et al., 2010; each compartment that is removed, as a function of time. The
Zeng et al., 2010; Suhling et al., 2001). The image processing was based diagnostic tools dened in Section 2.2 to analyse the model
on the principle that the depth integrated dye concentration in water predictions were applied to analyse the experimental data. For
can be related to the intensity of light passing through the water and images captured from the experiments, each compartment from
the distance travelled by the light in the water. The dye concentration the plan view was individually masked so that its time series (18)
in the water at point (x,y) can then be related to the change in light could be evaluated.
intensity through We estimated T 1=2;ij by interpolating C ij to determine when
Z l   C ij 0:5. We estimated 1=2;ij by linearly regressing C ij with T
I 0 x; y over the interval jC ij 0:5jr 0:1 and identied 1=2;ij propor-
C I x; y Cx; y; zdz f log ; 17
0 Ix; y tional to the slope of the curve.

where l is the distance in the z-direction that the light travels in


the water, I0 is the light intensity after the light travels through 4.4. Experimental errors
clear water, and I is the light intensity after the light travels
through dye water. The function f(x) is determined by a series of The major experimental measurement errors are caused by
calibration tests for xed l. The volume averaged ushed fraction masking and calibration. From a series of calibration tests, a
166 Z. Qi et al. / Ocean Engineering 89 (2014) 157172

Fig. 8. The theoretical predictions of the scatter plot 1=2 versus T 1=2 in each compartment are shown on the left (i), with the corresponding experimental results on the right
(ii) for a 3  3 tank. The gures correspond to (a) far open, (b) near open, and (c) both open cases. The bar on point 33 gives an indication of the experimental error.

Table 1 concentration by about 1%. The compartments of the tank are


The structure and dimensions of the 5  4 tank used in the experiment. individually assessed by masking part of the total image. The
compartments have dimensions of around 100  100 pixels; mask-
Item Horizontal section Vertical section
ing is accurate to within 10 pixels and thus gives an error of 1%.
Row number 4 1
During the pumping and ushing, small bubbles attached to the
Column number 4 4 wall that form due to temperature change inside the tank may
Compartment length (cm) 25 25 lead to a maximum error of 1%. In total, the experimental
Compartment width (cm) 10 13 measurements have an error less than 5%.
Compartment height (cm) 10 30
Number of lightening holes Longitudinal 1 3
between two compartments Transverse 2
Diameter of lightening holes (cm) 5 8 5. Experimental results

The experimental results reveal the characteristics of ballast


standard error of 2% was observed in relating dye concentration to water exchange in the 2  2, 3  3 and 5  4 compartment cong-
light intensity. On the top and bottom of the tank, lack of urations, with a steady inow rate. We will see how these
transparency in some points may decrease the measured dye experimental results match the model predictions.
Z. Qi et al. / Ocean Engineering 89 (2014) 157172 167

Fig. 9. The theoretical predictions of the ushed fraction eld in each compartment of the 5  4 tank at T 0.25, 0.5, 1 and 1.5 are shown in the upper row (i) of (ac), with
the corresponding experimental measurements in the lower row (ii). The gures correspond to (a) far open, (b) near open, and (c) both open cases. A black circle
represents an inlet, and a white circle represents an outlet.

5.1. 2  2 tank while C12 and C21 lay between C11 and C22. From Fig. 5(a) for the
far open case, C12 and C21 behaved nearly the same, which is
The scatter plots in Fig. 5 show the experimental measure- expected due to the inherent symmetry of the ow; from Fig. 5
ments of how the ushed fraction in each compartment of the (b) for near open, C21 grew faster from the beginning, until
2  2 tank, C ij , varied in time for the far open, near open and T  1:3 when it was exceeded by C12; from Fig. 5(c) for both
both open cases. The results compare quite well with the model open, C21 was always higher than C12 was. For the both open
predictions. For all cases, C11 grew the fastest, C22 the most slowly, case, C22 is underestimated because we assume that p21 p22 . In
168 Z. Qi et al. / Ocean Engineering 89 (2014) 157172

Fig. 10. The theoretical predictions of the scatter plot 1=2 versus T 1=2 in each compartment are shown on the left (i), with the corresponding experimental results on the
right (ii) for a 5  4 tank. The gures correspond to (a) far open, (b) near open, and (c) both open cases. The bar on point 54 gives an indication of the experimental error.

fact, there existed a small ow from compartment 21 to 22, which mixed with the original uid in the compartment when it left, that
accelerated the increase of C22. Meanwhile, from Fig. 6(ac;ii), the is, the existence of orices between neighbouring compartments
corresponding 1=2;ij versus T 1=2;ij matched the model predic- challenged the perfect mixing assumption within each compart-
tions. Overall, the experimental results were in close agreement ment; compartment 11 was the rst and fastest ushed compart-
with the model predictions for the 2  2 tank. ment, so its ushing rate was inuenced most severely by the non-
perfect mixing condition. For the near open case, the model
5.2. 3  3 tank successfully predicted the three grouped points: 12 and 21; 22, 13
and 31; and 23 and 32 (see Fig. 8(b)). Overall, the experimental
The scatter plots in Fig. 7 show the experimental measure- results captured the main character of the ushing predicted by
ments of the ushed fraction in the four selected compartments of the model. The measurements of the ushed fractions were
the 3  3 tank as a function of time. For all cases, C12 and C22 are a consistent with the model predictions on the performance of the
little overestimated. The agreement with the values of 1=2;ij four selected compartments. Meanwhile, the characteristic ush-
versus T 1=2;ij (see Fig. 8) is quite good, although for all cases, ing rate and the half ushed time predicted by the model for each
compartment 11 was ushed a little more slowly than expected. compartment of the tank were validated by the experiments for
The probable reason is that the incoming uid had not completely the three outlet arrangements.
Z. Qi et al. / Ocean Engineering 89 (2014) 157172 169

Fig. 11. The theoretical predictions of the ushing efciency of the whole tanks with three outlet arrangements are shown on the left (i), with the corresponding
experimental results on the right (ii). The gures correspond to the (a) 2  2, (b) 3  3, and (c) 5  4 tanks.

Table 2 experimental results agreed well with the model predictions. At an


The theoretical and experimental ushing efciencies at T 3 of the tanks with early time, the performance of each compartment was not
different compartment congurations and outlet arrangements. signicantly different among different outlet arrangements; at a
later time, the residual uid was the least for the far open case,
Compartment conguration Theoretical/experimental ushing efciency (%)
but the most for the near open case. The bow-shaped decrease of
Far open Near open Both open 1=2;ij versus T 1=2;ij in Fig. 10(ac;ii) indicated that the farther a
compartment was from the inlet, the more slowly and later it was
22 99.5/99.0 96.0/95.7 98.1/97.2 half ushed. 1=2;11 was more underestimated than that in the
33 99.8/99.6 95.6/96.4 99.4/98.4
3  3 tank. The probable reason is that the perfect mixing
54 99.9/99.3 98.1/97.9 99.6/98.5
assumption of the model was challenged when the ratio of the
orice area to the partition wall area between compartments ()
was too large. When the area of the hole of a compartment to its
5.3. 5  4 tank neighbouring compartment was too large, the incoming water
could not mix sufciently with the original water when it left the
The model predictions and experimental measurements of the compartment. In our tests, 19.638.6% for the 5  4 tank, which
variation of the ushed fraction eld are shown in Fig. 9. The was much larger than that of the 2  2 tank ( 13.1%) and the
170 Z. Qi et al. / Ocean Engineering 89 (2014) 157172

Fig. 12. Photograph of the (a) 2  2 square tank, (b) 3  3 square tank, and (c) 5  4 'J'-type tank used in the experimental study.

3  3 tank ( 4.91%). In real ballast tanks, the ratio is normally 6. Discussion and conclusion
less than 15%. A possible reason for the longer residence of the
original water in some compartments (e.g. compartment 44) for In this paper, we have examined theoretically and experimen-
the near open and both open cases is that the ux in the tally the ushing of water from a multi-compartment ballast tank.
peripheral compartments decreased to  0:2Q , giving a character- The model is based on perfect mixing within compartments and
istic Reynolds number of Re C 600, so that the turbulence was advection between compartments. To test the model predictions, a
weak, leading to insufcient mixing and high residence times for series of detailed experiments on tanks with 2  2 and 3  3
uid parcels in the recirculating region attached to the outlet compartment congurations were undertaken. When the light-
holes. Compartments 21 and 12 were half ushed at relatively ening holes between compartments are identical, the model has
high rates, their neighbouring compartments 31, 22 and 13 were no adjustable free parameters, and the agreement between the
ushed at lower rates, and other horizontal compartments were measurements of the ushed fraction of water in each compart-
then half ushed at even lower rates. It can be seen that the ment and predictions is quite good. When the holes between
relative position of the points denoting the vertical compartments compartments of a tank are different in size, an empirical closure
to those denoting the horizontal compartments agreed with the is required to estimate pressure drop coefcients.
predictions. The model is able to capture the variation of the The ushing from a tank with more complex geometry, typical
ushed fraction of each compartment with time and discern the of a ballast tank, was also analysed. The agreement between
performance difference of each compartment among the three predictions and measurements for the ushing efciency is good.
outlet arrangements. The increased complexity means that the ow through the edge
compartments is reduced and in the laboratory study, probably to
5.4. Flushing efciency of the whole tanks the extent that the ow within these regions was not turbulent.
Insufcient mixing, caused by weak turbulent diffusion in some
The variation of the tank ushing efciency with time is shown compartments where the ow rate was low, led to a long
in the right of Fig. 11. It can be found that for a short time, the residence time of the original uid and thus a slow exchange, that
original uid was removed by displacement and the increase in C is why the American Bureau of Shipping (2010) requires that aft
was roughly linear; for a long time, mixing was important and then and fore peak tanks are to be provided with additional pipework
C followed more closely the perfect mixing rule. For all tank to improve the mixing conditions.
congurations the ushing efciencies of far open and both open The IMO requires that after three exchange volumes, the
were similar and higher than that of the near open case. For the ushing efciency should be greater than 95% and these estimates
far open and both open cases, the ushing efciency increased were based on a perfect mixing model for the whole tank. The
linearly with time up until T C 0:6, because the water exiting theoretical model and experiments show that for homogeneous
consisted entirely of water that was initially in the tank. When uids within multi-compartment tanks, ushing is more efcient
T0:6, the water exiting the tank consisted of an increasing fraction than estimated by the IMO, and can be improved by subdividing
of the water that was being used for ushing the tank. In total, the the tanks. The results show that to enhance ushing the outlet
ushing efciency at T 3 of these two cases was lower than the should be placed far from the inlet to reduce bypassing, which is
pure displacement, but higher than estimates based on perfect consistent with the requirement by the American Bureau of
mixing in the whole tank. For the near open case, the transition Shipping. There is currently no guidance about where the water
from displacement ushing to mixing occurred earlier at T C 0:5, in the ballast tanks should be sampled. This is not trivial because
because the incoming water bypassed a large part of the tank and there are usually multiple discharge ports. And as we see in the
was not able to exchange the initial water efciently. Table 2 ushed fraction curves there is a signicant variability between
summarises the ushing efciency at T3 for each case. Generally, compartments and the validated theoretical framework in this
the ushing efciency at T 3 obtained from the experiments was paper will go some way to assessing tanks in practice.
slightly lower than predicted, except for the near open case in the The current analysis is applicable to cases when the initial
3  3 tank. In these experiments, the effective Re decreased in the ballast water and the water used for ushing have the same
peripheral compartments leading to lower increase rates of ushed density. There are a number of scenarios where the density
fraction and higher residence time. Since the total ushing ef- contrast may be important (e.g. using a heat treatment to sterilise
ciency is an integrated measure over the whole tank, the impact of the water or ports in warm shallow seas or near fresh water
the peripheral compartments is not signicant and this is why the sources). Some initial insight can already be obtained for a line of
agreement between the theory and the experiments is generally connected compartments (e.g. Eames et al., 2008) but further
good. The discrepancy between the model predictions and the work is required to extend this analysis to more realistic geome-
experimental measurements for C jT 3 is within 1.1%, lower than tries. More work is needed to extend the model to account for the
the limit of experimental errors  5%. Therefore, the model is able settling and sticking dynamics of non-passive substances. A
to understand how the ushing efciency depends on the outlet number of authors have included this effect by the inclusion of a
arrangements and tank geometries. sink term in the mass conservation equation (e.g. Eq. (13) of
Z. Qi et al. / Ocean Engineering 89 (2014) 157172 171


Bolster and Linden, 2009)  vT Aij C ij =h (where vT is the terminal dC mj V f mj  1;mj
Hf mj  1;mj C mj  1
fall velocity) on the right-hand side of (7). dT V mj Q
H  f mj  1;mj C mj
Acknowledgement f m  1j;mj f mj;mj 1
C m  1j  Hf mj;mj 1 C mj
Q Q

The Erasmus Mundus External Cooperation Programme H  f mj;mj 1 C mj 1 ; j 2; 3; ; n  1;
nanced by the European Commission is acknowledged.

dC i1 V f i  11;i1 f i1;i2
C i  11  Hf i1;i2 C i1
Appendix A. Mathematical model for an m  n tank dT V i1 Q Q

f i1;i 11
H  f i1;i2 C i2  C i1 ; i 2; 3; ; m  1;
The ballast tank for this study from the plan view has m rows Q
by n columns compartments with a steady ow rate Q into 
compartment 11. There are two outlets, with ow rate Q m1;out dC in V f i  1n;in f in  1;in
C i  1n Hf in  1;in C in  1
out of compartment m1 and Q mn;out out of compartment mn, dT V in Q Q
respectively. To mathematically study this ballast tank following 
f in;i 1n
the way of the above analysis, it is abstracted as a model in Fig. 3. H  f in  1;in C in  C in ;
Q
The model consists of mn mass conservation equations:
i 2; 3; ; m 1;
Q f 11;12 f 11;21 ;

f 1n  1;1n f 1n;2n ; dC ij V f ij  1;ij
Hf ij  1;ij C ij  1 H  f ij  1;ij C ij
f m  11;m1 f m1;m2 Q m1;out ; dT V ij Q
f m  1n;mn f mn  1;mn Q mn;out ; f i  1j;ij f ij;ij 1
C i  1j  Hf ij;ij 1 C ij
f 1j  1;1j f 1j;1j 1 f 1j;2j ; j 2; 3; ; n  1; Q Q

f mj  1;mj f m  1j;mj f mj;mj 1 ; j 2; 3; ; n 1; f ij;i 1j
H  f ij;ij 1 C ij 1  C ij ;
f i  11;i1 f i1;i2 f i1;i 11 ; i 2; 3; ; m  1; Q
i 2; 3; ; m 1 and j 2; 3; ; n  1 A:3
f i  1n;in f in  1;in f in;i 1n ; i 2; 3; ; m  1;
f i  1j;1j f ij  1;ij f ij;ij 1 f ij;i 1j ; i 2; 3; ; m  1 along with
and j 2; 3; ; n  1; A:1 C ij jT 0 0:
and 2mn  m  n momentum equations: Here H(X) is the Heaviside step function with the properties
jf ij;ij 1 jf ij;ij 1 HX 1 for X Z 0 and HX 0 for X o 0.
pij pij 1 ij;ij 1 ; i 1; 2; ; m and
A2ij;ij 1

j 1; 2; ; n  1; Appendix B. Analytical solutions to C ij of a 2  2 tank


jf ij;i 1j jf ij;i 1j
pij pi 1j ij;i 1j ; For the case of a 2  2 tank, where the ux between each
A2ij;i 1j
compartment is known, the ushed fraction can be explicitly
i 1; 2; ; m  1 and j 1; 2; ; n: A:2 determined from (16) for the case of V ij =V 1=4. For the far
When only the far outlet is open, Q m1;out 0, pmn 0; when open case,
only the near outlet is open, Q mn;out 0, pm1 0; when both C 11 1  exp  4T;
outlets are open, pm1 pmn 0. The equations describing the C 12 1  2exp  2T exp  4T;
variation of the ushed fraction in time are
C 21 1  2exp  2T exp  4T;
dC 11 V dC 1n C 22 1  4exp  2T 4T 3exp  4T; B:1
1  C 11 ;
dT V 11 dT
  for the near open case,
V f 1n  1;1n f 1n;2n
C 1n  1  C 1n ;
V 1n Q Q C 11 1  exp  4T;
p p
 33 p 3
dC m1 V f m  11;m1 f m1;m2 C 12 1  exp2 2 3T exp  4T;
C m  11  Hf m1;m2 C m1 3 3
dT V m1 Q Q p
12T 3  3 p
 C 21 1  exp2 2 3T
Q m1;out 9
H  f m1;m2 C m2  C m1 ; p p
Q 12 3  48T 3  12
exp  4T;
 9
f m  1n;mn p
dC mn V 4 3T 2 p 1
C m  1n C 22 1  exp2  2 3T  exp  4T; B:2
dT V mn Q 3 3
f mn  1;mn
Hf mn  1;mn C mn  1 for the both open case,
Q
 C 11 1  exp  4T;
Q mn;out p p
H  f mn  1;mn C mn  C mn ; 22 p 2
Q C 12 1  exp4 4 2T exp  4T;
2 2
  p p p
dC 1j V f 1j  1;1j f 1j;2j f 1j;1j 1 C 21 1  2 1 exp4 2  8T 2 exp  4T;
C 1j  1  C 1j  C 1j ; p
dT V 1j Q Q Q 4 2T 1 p 1
C 22 1  exp4  4 2T  exp  4T: B:3
j 2; 3; ; n  1; 2 2
172 Z. Qi et al. / Ocean Engineering 89 (2014) 157172

References sensitivity analysis using measured data in a deposition model. Aquaculture


251, 295305.
Mora, L., Gadgil, A.J., Wurtz, E., 2003. Comparing zonal and CFD model predictions
American Bureau of Shipping, 2010. Guide for Ballast Water Exchange. of isothermal indoor airows to experimental data. Indoor Air 13 (2), 7785.
Armstrong, G., 1997. Ballast system design for ow-through exchange of ballast Pimentel, D., Lach, L., Zuniga, R., Morrison, D., 2000. Environmental and economic
water. Trans. IMarE. 109, 257269. costs of nonindigenous species in the United States. BioScience 5, 5365.
Bolster, D.T., Linden, P.F., 2007. Contaminants in ventilated lling boxes. J. Fluid Rahim, R.A., Rahiman, M.H.F., Goh, C.L., Muji, S.Z.M., Rahim, H.A., Yunos, Y.M., 2010.
Mech. 591, 97116. Modeling orthogonal and rectilinear mixed-modality projection of optical
Bolster, D.T., Linden, P.F., 2009. Particle transport in low-energy ventilation systems. tomography for solid-particles concentration measurement. Sensor. Actuat.
Part 2: transients and experiments. Indoor Air 19, 130144. A: Phys. 161 (12), 5361.
Cao, R., Liu, Y.S., Yan, C., 2011. A criterion for ow mechanisms through vertical Rigby, G., Hallegraeff, G., 1994. The transfer and control of harmful marine
sharp-edged orice and model for the orice discharge coefcient. Petrol. Sci. 8 organisms in shipping ballast water: behaviour of marine plankton and ballast
(1), 108113. water exchange trials on the mv iron whyalla. J. Mar. Environ. Eng. 1, 91110.
Cenedese, C., Dalziel, S.B., 1998. Concentration and depth eld determined by the Ruiz, G.M., Murphy, K.R., Verling, E., Smith, G., Chaves, S., Hines, A.H., 2005. Ballast
light transmitted through a dyed solution. In: Eighth International Symposium water exchange: efcacy of treating ships' ballast water to reduce marine
on Flow Visualization, pp. 15. species transfers and invasion success? Technical Report. Report Submitted to
Chang, III, P.A., Wilson, W., Carneal, J., Atsavapranee, P., Verosto, S., Reid, D., Jenkins, Prince William Sound Regional Citizens' Advisory Council and the US Fish &
P., 2009. Computational modeling of ballast water tanks to improve under- Wildlife Service, 14p.
standing and maximize effectiveness of management practices and treatment Ruiz, G.M., Reid, D.F., 2007. Current state of understanding about the effectiveness
mechanisms. Phase iiExtension of Laboratory Study (Final Report). Technical of ballast water exchange (bwe) in reducing aquatic nonindigenous species
Report, NOAA Technical Memorandum GLERL-148, National Oceanic and Atmo- (ans) introductions to the great lakes basin and chesapeake bay, USA: synthesis
spheric Administration, Great Lakes Environmental Research Laboratory, Ann and analysis of existing information. Technical Report. National Oceanic and
Arbor, MI, and NSWCCD-50-TR-2009/028, Naval Surface Warfare Center Car- Atmospheric Administration, United States Department of Commerce.
derock Division, West Bethesda, MD, USA. Steinhauer, F., 2007. Ballast water exchange and the destruction of non-indigeneous
Chang, T.J., Huang, M.Y., Wu, Y.T., Liao, C.M., 2003. Quantitative prediction of trafc species (Master's thesis). University College London.
pollutant transmission into buildings. J. Environ. Sci. Health A 38 (6), Suhling, K., Hungerford, G., Airey, R.W., Morgan, B.L., 2001. A position-sensitive
10251040. photon event counting detector applied to uorescence imaging of dyes in sol
Charles, S., Bonneau, O., Frene, J., 2005. Determination of the discharge coefcient gel matrices. Meas. Sci. Technol. 12 (2), 131141.
of a thin-walled orice used in hydrostatic bearings. J. Tribol. 127 (3), 679684. Ta, C.T., Hague, J., 2004. A two-phase computational uid dynamics model for ozone
Chen, Q.Y., Lee, K., Mazumdar, S., Poussou, S., Wang, L.Z., Wang, M., Zhang, Z., 2010. tank design and troubleshooting in water treatment. Ozone-Sci. Eng. 26 (4),
Ventilation performance prediction for buildings: model assessment. Build. 403411.
Environ. 45 (2), 295303. Tan, G., Glicksman, L., 2005. Application of integrating multi-zone model with CFD
Chu, C.R., Chiu, Y.H., Chen, Y., Wang, Y.W., Chou, C.P., 2009. Turbulence effects on the simulation to natural ventilation prediction. Energ. Build. 37 (10), 10491057.
discharge coefcient and mean ow rate of wind-driven cross-ventilation. Weinlder, A., Wu, W., Tenbohlen, S., Wang, Z., 2012. Prediction of the oil ow
Build. Environ. 44 (10), 20642072. distribution in oil-immersed transformer windings by network modelling and
Chu, C.R., Chiu, Y.H., Wang, Y.W., 2010. An experimental study of wind-driven cross computational uid dynamics. IET Electr. Power Appl. 6, 8290.
ventilation in partitioned buildings. Energ. Build. 42 (5), 667673. Wilson, W., Chang, P., Verosto, S., Atsavapranee, P., Reid, D.F., Jenkins, P.T., 2006.
Eames, I., Landeryou, M., Greig, A., Snellings, J., 2008. Continuous ushing of Computational and experimental analysis of ballast water exchange. Nav. Eng.
contaminants from ballast water tanks. Mar. Pollut. Bull. 56 (2), 250260. J. 118 (3), 2536.
Eames, I., Shoaib, D., Klettner, C.A., Taban, V., 2009. Movement of airborne Wong, K.B., Piedrahita, R.H., 2000. Settling velocity characterization of aquacultural
contaminants in a hospital isolation room. J. R. Soc. Interface 6, 757766. solids. Aquacult. Eng. 21, 233246.
Engdahl, F., 1999. Stability of mechanical exhaust systems. Indoor Air 9 (4), Wonham, M.J., Carlton, J.T., 2005. Trends in marine biological invasions at local and
282289. regional scales: the northeast Pacic Ocean as a model system. Biol. Invasions
Hunt, G.R., Kaye, N.B., 2006. Pollutant ushing with natural displacement ventila- 7, 369392.
tion. Build. Environ. 41 (9), 11901197. Wright, D.A., 2012. Logistics of compliance assessment and enforcement of the
Joekar-Niasar, V., Hassanizadeh, S.M., Dahle, H.K., 2010. Non-equilibrium effects in 2004 ballast water convention. J. Mar. Eng. Technol. 11 (1), 1724.
capillarity and interfacial area in two-phase ow: dynamic pore-network Wright, D.A., Mackey, T.P., 2006. Shipboard and dockside trials of ballast water
modelling. J. Fluid Mech. 655, 3871. treatment technology. Nav. Eng. J. 118 (3), 3743.
Kamada, K., Minami, K., Shoji, K., Shiotani, S., Ishida, H., 2004. Study of ballast water Wu, W., Wang, Z.D., Revell, A., Jarman, P., 2012. Computational uid dynamics
exchange by pumping-through method. In: Oceans '04 MTS/IEEE Techno-Ocean calibration for network modelling of transformer cooling ows. Part ii: pressure
'04, vols. 12, Conference Proceedings, vols. 14, pp. 707712. loss at junction nodes. IET Electr. Power Appl. 6, 2834.
King, D.M., Hagan, P.T., Riggio, M., Wright, D.A., 2012. Preview of global ballast Zeng, N.Y., Li, Y.R., Du, M., 2010. Rapid quantitative image analysis of hCG by gold
water treatment markets. J. Mar. Eng. Technol. 11 (1), 316. immunochromatographic assay and genetic fast FCM algorithm. In: Third
MacPhee, B., 2006. Alien otillas: the expansion of invasive species through ship ballast International Conference on Biomedical Engineering and Informatics,
water. In: EarthTrends Environmental Essay Competition Winner, pp. 18. pp. 15601564.
Magill, S.H., Thetmeyer, H., Cromey, C.J., 2006. Settling velocity of faecal pellets of Zhao, B., Li, X.T., Yan, Q.S., 2003. A simplied system for indoor air ow simulation.
gilthead sea bream (sparus aurata l.) and sea bass (dicentrarchus labrax l.) and Build. Environ. 38 (4), 543552.

Vous aimerez peut-être aussi