Safer. Smarter.

TycoTM

A Training Guide for the


Local Instructional
Valve Experience
(EMEA Region)
DPV-1 DATASHEET

Contents

Page 3 Introduction to Tyco Fire Protection Products

Page 4 Valve Setting Exercises

Page 5 - 39 Model DPV-1


- Datasheets (DPV-1: TFP 1020, ACC-1: TFP 1112, AMD-1: TFP 1221)
- Notes

Page 40 - 83 Model AV-1


- Datasheet (AV-1 TFP 990)
- Notes

Page 84 - 115 Valve Model DV-5


- Datasheet (TFP 1338)
- Notes

Page 116 Feedback Form for L.I.V.E Training Session

Page 117-127 Appendix/L.I.V.E set-up Manual Instructions

/2/
DPV-1 DATASHEET
Protecting
Life and
Property

Tyco Fire Protection Products is the leading All products can either be supplied directly from stock
manufacturer and distributor of water-based fire or at very short notice. If required, products can be
suppression systems and components, offering one of engraved, assembled or otherwise modified according
the broadest lines of fire protection system equipment to your own specifications. In our Assembly Shop we
worldwide. Continually expanding its capabilities can pre-trim any type of alarm valve to local specific
through proactive research and product development, requirement. Each valve assembly is functionally and
it provides its customers with effective fire protection hydrostatically tested before it leaves our facilities.
and construction solutions for residential, commercial,
We can assist you to find safe and efficient solutions
industrial, and institutional buildings.
when using our products. We can provide technical
We supply a wide range of sprinklers, alarm valves support, training and courses for anyone who installs
and accessories as well as CPVC pipe & fittings, our products on a regular or project basis.
flowmeters, general purpose valves, hydrants,
For the latest information about our organisation,
couplings and grooved fittings, sprinkler support
product approvals or innovations, please visit us at
materials, foam products and hardware.
www.tfppemea.com.
Tyco has branches strategically located throughout
Europe and the Middle East to provide customers with
the best possible service.

007

/3/
DPV-1 DATASHEET

Valve Setting
Exercises

When the L.I.V.E display is set up you can exercise the valve setting and test procedure. To do this exercise you
need to let the valve you want to exercise trip. Tripping of the Dry DPV-1 and Wet AV-1 valve can be done by
opening the 1 ball valve downstream the valve. The Deluge DV-5 can be tripped by either activating the solenoid
with the red push button or by opening the manual control valve, MC-1.
When you have tripped a valve you can go to the accompanying data sheet. Here you will find the exercise you
can do highlighted in blue.

/4/
DPV-1 DATASHEET
Worldwide
www.tyco-fire.com
Contacts

Model DPV-1 Dry Pipe Valve, External Resetting


2-1/2 thru 6 Inch (DN65 thru DN150)
250 psi (17,2 bar)

General
Description
The TYCO Model DPV-1 Dry Pipe
Valves are differential valves used to
automatically control the flow of water
into dry pipe fire protection sprinkler
systems upon operation of one or more
automatic sprinklers. The DPV-1 also
provides for actuation of fire alarms
upon system operation. The Model
DPV-1 features are as follows:
External reset.
250 psi (17,2 bar) pressure rating.
Unique offset single clapper design
enabling a simple compact valve to
minimize installation labor.
Ductile iron construction to ensure a
lightweight valve to minimize shipping
cost.
A variety of inlet and outlet
connections. Available End Connections and Sizes
Compact, Pre-Trimmed, and Semi- Nominal Valve Size
Assembled, easy to operate valve End Connection 2-1/2 Inch 3 Inch 4 Inch 6 Inch
trim.
(DN65) (DN80) (DN100) (DN150)
Simple reset procedure through the
Flange x Flange N/A N/A
elimination of priming water.
Dry pipe sprinkler systems are used Flange x Groove N/A N/A
in unheated warehouses, parking
Groove x Groove
garages, store windows, attic spaces,
loading docks, and other areas
exposed to freezing temperatures, Available
where water filled pipe cannot be N/A Not Available
utilized. When set for service, the dry
pipe sprinkler system is pressurized NOTICE The owner is responsible for
with air (or nitrogen). The loss of maintaining their fire protection system
pressure through an operated The Model DPV-1 Dry Pipe Valves
described herein must be installed and devices in proper operating
automatic sprinkler in response to condition. The installing contractor or
heat from a fire permits the DPV-1 Dry and maintained in compliance with
this document, as well as with the manufacturer should be contacted with
Pipe Valve to open and allow a flow of any questions
water into the sprinkler system piping. applicable standards of the National
Table B establishes the minimum Fire Protection Association, in addition
required system air pressure that to the standards of any other authorities
includes a safety factor to help prevent having jurisdiction. Failure to do so
false operations that might occur due to may impair the performance of these
water supply fluctuations. devices.

Page 1 of 20 MARCH 2013 TFP1020

/5/
TFP1020
Page 2 of 20
DPV-1 DATASHEET

NO. DESCRIPTION QTY. REF.


1 Valve Body . . . . . . . 1 NR
2 Air and Water
Seat . . . . . . . . . . . . 1 NR
3 Handhole Cover . . . 1 NR
4 Handhole Cover
11 Gasket . . . . . . . . . . 1 See (b)
5 1/2-13 UNC x 1" Hex
12 Head Cap Screw:
2-1/2 & 3 Inch
6 Valves . . . . . . . . . . . 5 CH
13 4 Inch Valve . . . . . . 6 CH
7 6 Clapper . . . . . . . . . . 1 See (a)
RESET 7 Clapper Facing . . . . 1 See (a) or (b)
CLAPPER
14 PLUNGER
ASSEMBLY 8 Clapper Facing
PARTS
8 Retaining Plate . . . . 1 See (a)
15, 18 9 2-1/2 and 3 Inch Valves:
1/4" x 3/8" Long
9
#10-32 Shoulder
16 Screw . . . . . . . . . . . 5 See (a)
4 Inch Valve:
1/4-20 UNC x 1/2"
17
Socket Head Cap
Screw . . . . . . . . . . . 7 See (a)
10 Clapper Hinge
Pin . . . . . . . . . . . . . 1 See (a)
11 Reset Knob . . . . . . 1 See (c)
12 Reset Spring . . . . . 1 See (c)
13 Reset Bushing . . . . 1 See (c)
14 Reset Bushing
O-Ring. . . . . . . . . . . 1 See (b) or (c)
15 Reset Plunger
O-Ring . . . . . . . . . . 1 See (b) or (c)
16 Reset Plunger . . . . . 1 See (c)
17 Reset Latch
Subassembly . . . . . 1 See (c)
18 Dow Corning FS3452
1 Flourosilicone
4 Grease, 1.5 g . . . . . 1 See (b) or (c)
3 NR: Not Replaceable
2
CH: Common Hardware

REPLACEMENT PARTS
NO. DESCRIPTION P/N
(a) Clapper Assembly
Includes Items 6-10:
2-1/2 & 3 Inch Valves . . 92-309-2-203
4 Inch Valve . . . . . . . . . 92-309-2-403
10 (b) Repair Parts Kit
5 Includes Items
4, 7, 14, 15, & 18:
2-1/2 & 3 Inch Valves . . 92-309-1-204
4 Inch Valve . . . . . . . . . 92-309-1-404
(c) Reset Plunger Parts Kit
Includes Items 11-18 . . 92-310-1-405

FIGURE 1 - PART 1 OF 2
MODEL DPV-1 DRY PIPE VALVE
2-1/2, 3, AND 4 INCH (DN65, DN80, DN100) ASSEMBLIES

/6/ /6/
TFP1020
Page 3 of 20

DPV-1 DATASHEET
NO. DESCRIPTION QTY. REP. PART NO. DESCRIPTION QTY. REP. PART NO. DESCRIPTION QTY. REP. PART
1 Valve Body . . . . . . . 1 NR 5 Socket Head Cap 8 Hex Head Cap Screw
2 Air and Water Screw 5/8-11 UNC x 1" . . . 6 CH
Seat . . . . . . . . . . . . 1 NR 3/8-16 UNC x 1" . . . 8 NR 9 Clapper . . . . . . . . . . 1 See (a)
3 Water Seal 6 Handhole Cover . . . 1 NR 10 Clapper Facing . . . . 1 See (a) or (b)
O-Ring . . . . . . . . . . 1 NR 7 Handhole Cover 11 Clapper Facing
4 Air Seal O-Ring . . . . 1 NR Gasket . . . . . . . . . . 1 See (b) Retaining Plate . . . . 1 See (a)
12 Socket Head Cap
Screw
1/4-20 UNC x 1/2". . 9 See (a)
14 13 Clapper Hinge Pin. . 1 See (a)
14 Reset Knob . . . . . . 1 See (c)
15 Reset Spring . . . . . 1 See (c)
15
9 16 Reset Bushing . . . . 1 See (c)
17 Reset Bushing
16 O-Ring. . . . . . . . . . . 1 See (b) or (c)
10 18 Reset Plunger
CLAPPER RESET O-Ring. . . . . . . . . . . 1 See (b) or (c)
ASSEMBLY 17 PLUNGER 19 Reset Plunger . . . . . 1 See (c)
11 PARTS 20 Reset Latch
18, 21 Subassembly . . . . . 1 See (c)
12 21 Dow Corning FS3452
Flourosilicone
19 Grease, 1.5 g . . . . . 1 See (b) or (c)

NR: Not Replaceable


20 CH: Common Hardware

REPLACEMENT PARTS
NO. DESCRIPTION P/N
(a) Clapper Assembly
Includes Items 9-13 . . . 92-309-2-603
(b) Repair Parts Kit
Includes Items
7, 10, 17, 18, 21 . . . . . . 92-309-1-604
(c) Reset Plunger Parts Kit
2 Includes Items 14-21 . . 92-310-1-405

4 1
7
6

5
3

13

FIGURE 1 - PART 2 OF 2
MODEL DPV-1 DRY PIPE VALVE
6 INCH (DN150) ASSEMBLY

/7//7/
TFP1020
Page 4 of 20

Technical Data Handhole Cover are ductile iron. The


Handhole Cover Gasket is neoprene,
PS10-2 waterflow alarm switch
DPV-1 DATASHEET

PS40-2 low air pressure alarm switch


Approvals and the Clapper Facing is EPDM.
UL and C-UL Listed. FM Approved. The Air/Water Seat Ring is brass, the Note: When the system pressure is
NYC under MEA 172-02-E (4 and 6 Clapper is bronze or aluminum bronze, greater than 175 psi (12,1 bar), provision
inch). and both the Clapper Retaining Plate is to be made to replace the standard
and Latch are bronze. The Hinge Pin is order 300 psi (20,7 bar) Water Pressure
Dry Pipe Valve aluminum bronze, and the fasteners for gauge with a separately ordered 600
The TYCO Model DPV-1 Dry Pipe the Handhole Cover are carbon steel. psi (41,4 bar) Water Pressure Gauge.
Valves are for vertical installations (flow
going up), and they are rated for use Valve Trim Air Supply
at a maximum service pressure of 250 Installation dimensions are given Table B shows the system air pressure
psi (17,2 bar). The Valve dimensions are in Figure 7, and the Valve Trim and requirements as a function of the
shown in Figure 7. Pre-Trimmed Valve Assemblies are water supply pressure. The air (or
illustrated in Figures 4, 5, and 6. The nitrogen) pressure in the sprinkler
Flanged connections are available Valve Trim and Pre-Trimmed Valve system is recommended to be
and drilled per ANSI, ISO, AS, and forms a part of the laboratory listings automatically maintained by using one
JIS specifications (Ref. Table A). and approval of the DPV-1 Valve and is of the following pressure maintenance
The grooved outlet connections, as necessary for the proper operation of devices, as appropriate:
applicable, are cut in accordance with the DPV-1 Valve. Each package of trim
standard groove specifications for Model AMD-1 Air Maintenance
and pre-trimmed includes the following Device (pressure reducing type).
steel pipe. They are suitable for use items:
with grooved end pipe couplings that Model AMD-2 Air Maintenance
are listed or approved for fire protection Water Supply Pressure Gauge Device (compressor control type).
system service. Available combinations System Air Pressure Gauge
of inlet and outlet connections are Model AMD-3 Nitrogen Maintenance
detailed in the Ordering Procedure Air Supply Connections Device (high pressure reducing type).
section. They are also noted in the Main Drain Valve The Pressure Relief Valve provided with
Available End Connection and Sizes the valve trim is factory set to relieve
table located on Page 1. Low Body Drain Valve at a pressure of approximately 45 psi
Threaded port connections of valves Alarm Test Valve (3,1 bar). If the normal system air
having flanges drilled to ANSI, AS, or pressure is less than or exceeds 40 psi
Automatic Drain Valve
JIS specifications are NPT threaded per (2,8 bar), then the pressure Relief Valve
Drip Funnel must be reset to relieve at a pressure
ANSI Standard B1.20.1. Threaded port
connections of valves having flanges Connections For Optional Quick that is in accordance with the authority
drilled to ISO are available either Opening Device (Accelerator) having jurisdiction.
threaded per ISO 7-1 or NPT threaded Also included in the Pre-Trimmed Quick Opening Device
per ANSI Standard B1.20.1. Valves with Valve Assembly, which can be ordered As an option, the Model DPV-1 Dry Pipe
NPT threaded ports will readily accept separately for the Valve Trim, includes Valve may be equipped with the VIZOR
the trim arrangements detailed in Parts the following items: Electronic Dry Pipe Valve Accelerator
2 and 3 of Figures 4, 5, and 6. (4 and 6 inch sizes) as detailed in
Model BFV-N butterfly vlave Technical Data Sheet TFP1105 or the
Components of the DPV-1 Valves
are shown in Figure 1. The Body and Figure 577 grooved coupling Model ACC-1 Mechanical Dry Pipe

Flange Drilling Specification


Nominal Dimensions in Inches and (mm)
Nominal ANSI B16.1 1 ISO 7005-2 JIS B 2210 AS 2129
Valve Size (Class 125) (PN16)2 (10K) (Table E)
Dim. Dim. Qty. Dim. Dim. Qty. Dim. Dim. Qty. Dim. Dim. Qty.
A B N A B N A B N A B N
4 Inch 7.50 0.75 8 7.09 0.75 8 6.89 0.59 8 7.00 0.71 8
(DN100) (190,5) (19,0) (180,0) (19,0) (175,0) (15,0) (178,0) (18,0)
6 Inch 9.50 0.88 8 9.45 0.91 8 9.45 0.75 8 9.25 0.87 8
(DN150) (241,3) (22,2) (240,0) (23,0) (240,0) (19,0) (235,0) (22,0)

1 Same drilling as for ANSI B16.5 (Class 150) and ANSI B16.42 (Class 150).
Dim. A Qty. N
2 Same drilling as for BS 4504 Section 3.2 (PN16) and DIN 2532 (PN16). Bolt Circle Number of
Diameter Bolt Holes

Dim. B
Bolt Hole
TABLE A Diameter
DIMENSIONAL SPECIFICATIONS
FOR SELECTION OF FLANGE DRILLING

/8/
TFP1020
Page 5 of 20

Valve Accelerator (2-1/2, 3, 4, and 6 When one or more automatic sprinklers


inch sizes) as detailed in Technical Data operate in response to a fire, air

DPV-1 DATASHEET
Sheet TFP1112. pressure within the system piping is Maximum System Air
relieved through the open sprinklers. Water Supply Pressure Range,
The VIZOR or the ACC-1 is used to Pressure, psi
reduce the time to valve actuation When the air pressure is sufficiently psi
reduced, the water pressure overcomes
following the operation of one or more 20 10
automatic sprinklers. In some cases the differential holding the Clapper
the use of a quick opening device such Assembly closed and the Clapper 60 15 - 23
as the VIZOR or the ACC-1 may be Assembly swings clear of the water
seat, as shown in Figure 3C, This 80 20 - 28
required to meet the requirements of
the National Fire Protection Association action permits water flow into the 100 25 - 33
system piping and subsequently to be
to meet water delivery times. 120 30 - 38
discharged from any open sprinklers.
Also, with the Clapper Assembly 145 35 - 43
Operation open, the intermediate chamber is
pressurized and water flows through
165 40 - 48
The TYCO Model DPV-1 Dry Pipe Valve the alarm port (Ref. Figure 3B) at the 185 45 - 53
is a differential type valve that utilizes rear of the DPV-1 Valve to actuate 205 50 - 58
a substantially lower system (air or system water flow alarms. The flow
nitrogen) pressure than the supply from the alarm port is also sufficient 225 55 - 63
(water) pressure, to maintain the set to close the otherwise normally open 250 60 - 68
position shown in Figure 3A. The Automatic Drain Valve in the valve trim.
differential nature of the DPV-1 is based
on the area difference between the air After a valve actuation and upon TABLE B
seat and the water seat in combination sub-sequent closing of a system main SYSTEM AIR PRESSURE
with the ratio of the radial difference control valve to stop water flow, the REQUIREMENTS
from the Hinge Pin to the center of the Clapper Assembly will latch open as
Water Seat and the Hinge Pin to the shown in Figure 3D. Latching open of
Continued on page 16
center of the Air Seat. The difference
is such that 1 psi (0,07 bar) of system FLOW RATE IN LITRES PER MINUTE (LPM)
air pressure can hold approximately 5.5 (1 GPM = 3.785 LPM)
psi (0,38 bar) of water supply pressure. 500 700 1000 2000 3000 5000 10000
Table B establishes the minimum 9.0 0,60
NOMINAL PRESSURE DROP IN POUNDS PER SQUARE INCH (PSI)

required system air pressure that 7.0 0,50


includes a safety factor to help prevent
0,40
false operations that occur due to water 5.0
supply fluctuations. 0,30
4.0
80)

The Intermediate Chamber of the DPV-1


DN

is formed by the area between the 3.0

NOMINAL PRESSURE DROP IN BAR


0,20
H(

Air Seat and Water Seat as shown in


INC

Figure 3B. The Intermediate Chamber 2.0

(1 PSI = 0.06895 BAR)


normally remains at atmospheric
&3

)
100

pressure through the Alarm Port 0,10


65)

)
(DN

connection and the valve trim to


150

0,08
DN

the normally open Automatic Drain 1.0


(DN
CH
H(

Valve (Fig. 4, 5, or 6). Having the 0,06


4 IN
INC

CH

Intermediate Chamber, Figure 3B, 0.7 0,05


6 IN

open to atmosphere is critical to the


/2

0,04
2-1

DPV-1 Valve remaining set, otherwise 0.5


the full resulting pressure of the system 0.4
0,03
air pressure on top of the Clapper
Assembly cannot be realized. 0.3 0,02
For example, and assuming a water
supply pressure of 100 psi (6,9 bar), if 0.2
the system air pressure is 25 psi (1,7
bar) and there was 15 psi (1,0 bar) 0,01
pressure trapped in the Intermediate
Chamber, the resulting pressure 0.1
across the top of the Clapper would 200 300 500 700 1000 2000 3000100
only be 10 psi (0,7 bar). This pressure FLOW RATE IN GALLONS PER MINUTE (GPM)
would be insufficient to hold the The approximate friction losses, based on the Hazen and Williams formula and ex-
Clapper Assembly closed against pressed in equivalent length of Schedule 40 pipe with C=100 are as follows:
a water supply pressure of 100 psi 2.2 feet for the 2-1/2 inch valve at a typical flow rate of 250 GPM
(6,9 bar). It is for this reason that the 4.9 feet for the 3 inch valve at a typical flow rate of 350 GPM
plunger of the Automatic Drain Valve 8.9 feet for the 4 inch valve at a typical flow rate of 600 GPM
must be depressed during several of 22 feet for the 6 inch valve at a typical flow rate of 1500 GPM
the resetting steps, as well as during FIGURE 2
inspections, making certain that the MODEL DPV-1 DRY PIPE VALVES
Automatic Drain Valve is open. NOMINAL PRESSURE LOSS VS. FLOW

/9/
TFP1020
Page 6 of 20

AIR PRESSURE WATERFLOW


DPV-1 DATASHEET

TO SYSTEM TO SYSTEM

CLAPPER CLAPPER
1" NPT ASSEMBLY ASSEMBLY
AIR SUPPLY IN SET FULLY OPEN
PORT POSITION

01

CLAPPER LATCH
PIVOTS TO ALLOW
1/2" NPT
CLAPPER ASSEMBLY
WATER
TO FULLY OPEN
SUPPLY
PRESSURE 3/4" NPT ALARM
& ALARM PORT OPEN TO
TEST PORT ATMOSPHERE
02 03 ALARM PORT
WATERFLOW
CLAPPER TO ALARM
ASSEMBLY
FROM FROM
WATER SUPPLY AIR WATER SUPPLY
SEAT
FIGURE 3A FIGURE 3C
SET POSITION WATER OPERATED POSITION
ALARM
SEAT 03
PORT
DRAIN FROM
DRAIN FROM SYSTEM
SYSTEM VALVE INTERMEDIATE COMPLETE
WATERWAY CHAMBER PUSH HERE
FIGURE 3B TO RESET
VALVE
SET POSITION
INTERMEDIATE
CHAMBER RESET
KNOB
CLAPPER
ASSEMBLY
LATCHED
RESET
OPEN
ASSEMBLY CLAPPER
LATCH
PIVOTS TO
CLAPPER UNLATCH
LATCH CLAPPER
ASSEMBLY
04 MAIN DRAIN PORT:
3/4" NPT 1-1/4" NPT* (2-1/2 INCH CLAPPER
05
LOW BODY & 3 INCH VALVES) ASSEMBLY
DRAIN 2" NPT (4 INCH VALVE) RESEATED
PORT
WATER SUPPLY * DN40 FOR VALVES WITH WATER SUPPLY
SHUT OFF ISO THREADED PORTS SHUT OFF

FIGURE 3D FIGURE 3E
DRAIN POSITION RESET POSITION

FIGURE 3 - PART 1 OF 2
MODEL DPV-1 DRY PIPE VALVES
2-1/2, 3, AND 4 INCH (DN65, DN80, AND DN100)
SET AND OPEN POSITIONS

/10/
TFP1020
Page 7 of 20

AIR PRESSURE WATERFLOW

DPV-1 DATASHEET
TO SYSTEM TO SYSTEM
CLAPPER
ASSEMBLY
FULLY OPEN

1" NPT CLAPPER LATCH


AIR SUPPLY PIVOTS TO ALLOW
PORT CLAPPER ASSEMBLY
01 TO FULLY OPEN

3/4" NPT ALARM


03 PORT OPEN TO
CLAPPER ATMOSPHERE
ASSEMBLY
IN SET
POSITION 1/2" NPT
WATER SUPPLY
02 PRESSURE
& ALARM
TEST PORT ALARM PORT
WATERFLOW
CLAPPER TO ALARM
ASSEMBLY AIR
FROM SEAT FROM
WATER SUPPLY WATER SUPPLY

FIGURE 3A ALARM FIGURE 3C


SET POSITION WATER PORT OPERATED POSITION
SEAT
03 DRAIN FROM
DRAIN FROM SYSTEM
SYSTEM INTERMEDIATE VALVE COMPLETE
CHAMBER WATERWAY
FIGURE 3B PUSH HERE
TO RESET
SET POSITION
VALVE
INTERMEDIATE
CLAPPER CHAMBER
ASSEMBLY RESET
LATCHED KNOB
OPEN RESET
ASSEMBLY

3/4" NPT
CLAPPER
LOW BODY
LATCH
DRAIN
PIVOTS TO
PORT
UNLATCH
04 CLAPPER
ASSEMBLY

2" NPT CLAPPER


MAIN DRAIN LATCH
PORT CLAPPER
ASSEMBLY
05 RESEATED

WATER SUPPLY WATER SUPPLY


SHUT OFF SHUT OFF

FIGURE 3D FIGURE 3E
DRAIN POSITION RESET POSITION

FIGURE 3 - PART 2 OF 2
MODEL DPV-1 DRY PIPE VALVES
6 INCH (DN150)
SET AND OPEN POSITIONS

/11/
TFP1020
Page 8 of 20

NOTES:
DPV-1 DATASHEET

1. SEE FIGURE 4 PART 3 FOR TRIM ARRANGEMENT WITH BILL OF MATERIALS LOW AIR
AND COMPONENT PART NUMBERS. PRESSURE
2. TRIM SHOWN FULLY ASSEMBLED; COMPONENTS SUCH AS GAUGES AND ALARM
SWITCHES MAY REQUIRE ASSEMBLY IN TRIM AT INSTALLATION. SWITCH SYSTEM
AIR SUPPLY
CONTROL VALVE
1 INCH NPT SYSTEM
(NORMALLY
CONNECTION AIR SUPPLY
OPEN)
FOR LOCAL PRESSURE
SPRINKLER GAUGE
2-1/2 INCH (DN65) WATERFLOW
or 3 INCH (DN80) PRESSURE
1/2 INCH NPT
MODEL DPV-1 ALARM
CONNECTION
DRY PIPE VALVE SWITCH
FOR SYSTEM
(GxG ONLY)
AIR SUPPLY
GROOVED
ALARM MAIN COUPLING
TEST VALVE DRAIN VALVE
(NORMALLY (NORMALLY 1/2 INCH NPT
CLOSED) SYSTEM CLOSED) CONNECTION
3/4 INCH NPT SYSTEM FOR OPTIONAL
WATER CONNECTION SHUT-OFF ACCELERATOR
SUPPLY 1-1/4 INCH NPT
TO DRAIN VALVE CONNECTION
PRESSURE (NORMALLY
GAUGE TO DRAIN AUTOMATIC
LOW BODY OPEN)
DRAIN VALVE DRAIN VALVE
(NORMALLY 1-1/4 INCH NPT
CLOSED) CONNECTION DRIP
TO DRAIN FUNNEL

FIGURE 4 - PART 1 OF 3
2-1/2 AND 3 INCH (DN65 AND DN80) MODEL DPV-1 DRY PIPE VALVE
PRE-TRIMMED ASSEMBLY

AIR SUPPLY 1/2 INCH NPT 1/2 INCH NPT NOTES:


CONTROL VALVE CONNECTION CONNECTION 1. INSTALL TRIM ASSEMBLIES IN
(NORMALLY OPEN) FOR OPTIONAL FOR OPTIONAL ALPHABETICAL ORDER.
ACCELERATOR AIR PRESSURE
AUTOMATIC SWITCH 2. SEE FIGURE 3 FOR VALVE PORT
1/2 INCH NPT DRAIN VALVE IDENTIFICATION.
CONNECTION
3. ROUTE 1/4" TUBING TO DRIP
FOR SYSTEM
AIR SUPPLY H FUNNEL.
SYSTEM
AIR SUPPLY MAIN
PRESSURE DRAIN VALVE
1/2 INCH NPT D GAUGE (NORMALLY
CONNECTION G A
FOR WATERFLOW E CLOSED)
PRESSURE ALARM
SWITCH

1-1/4 INCH NPT DRIP


CONNECTION FUNNEL
TO DRAIN 1-1/4 INCH NPT
CONNECTION
2-1/2 INCH (DN65) TO DRAIN
1 INCH NPT or 3 INCH (DN80)
CONNECTION C MODEL DPV-1
FOR LOCAL DRY PIPE VALVE
SPRINKLER (GxG ONLY)

ALARM F B
LOW BODY
DRAIN VALVE
TEST VALVE SYSTEM (NORMALLY
(NORMALLY WATER SUPPLY 3/4 INCH NPT CLOSED)
CLOSED) PRESSURE CONNECTION
GAUGE TO DRAIN

FIGURE 4 - PART 2 OF 3
2-1/2 AND 3 INCH (DN65 AND DN80) MODEL DPV-1 DRY PIPE VALVE
EXPLODED ARRANGEMENT OF SEMI-ASSEMBLED TRIM

/12/
TFP1020
Page 9 of 20

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N

DPV-1 DATASHEET
1 250 psi/ 1750 kPa 13 3/32" Vent 28 1" x 1" x 1/2"
Air Pressure Fitting . . . . . . . . . . . 1 92-032-1-002 Reducing Tee . . . . . 1 CH
Gauge . . . . . . . . . . . 1 92-343-1-012 14 1/4" Tube, 29 Not Used
2 300 psi/ 2000 kPa 18" Long . . . . . . . . . 1 CH PIPE NIPPLES:
Water Pressure 15 1/4" Plug . . . . . . . . . 2 CH 30 1/4" x 3" . . . . . . . . . 2 CH
Gauge . . . . . . . . . . . 1 92-343-1-005 16 1/2" Plug . . . . . . . . . 2 CH 31 1/2" x Close . . . . . . 4 CH
3 1/4" Gauge Test 17 1" Plug . . . . . . . . . . 1 CH 32 1/2" x 1-1/2" . . . . . . 8 CH
Valve . . . . . . . . . . . . 2 46-005-1-002 18 1/2" Union. . . . . . . . 1 CH 33 1/2" x 2" . . . . . . . . . 1 CH
4 Model AD-1 19 1/2" x 1/4" Reducing 34 1/2" x 4-1/2" . . . . . . 1 CH
Automatic Bushing . . . . . . . . . 1 CH 35 1/2" x 6" . . . . . . . . . 1 CH
Drain Valve . . . . . . . 1 52-793-2-004 20 1/2" 90 Elbow . . . . 3 CH 36 3/4" x Close . . . . . . 1 CH
5 1/4" Pressure 21 3/4" 90 Elbow . . . . 1 CH 37 3/4" x 1-1/2" . . . . . . 1 CH
Relief Valve . . . . . . . 1 92-343-1-020 22 1-1/4" 90 Elbow. . . 1 CH 38 3/4" x 2-1/2" . . . . . . 1 CH
6 1/2" Ball Valve . . . . 2 46-050-1-004 23 1/2" Cross. . . . . . . . 2 CH 39 1" x Close . . . . . . . . 1 CH
7 3/4" Angle Valve . . . 1 46-048-1-005 24 1/2" x 1/2" x 1/4" 40 1-1/4" x Close . . . . 1 CH
8 1-1/4" Angle Valve . 1 46-048-1-007 Reducing Tee . . . . . 1 CH 41 1-1/4" x 4". . . . . . . . 1 CH
9 1/2" Swing 25 1/2" Tee . . . . . . . . . 1 CH COMPONENTS INCLUDED ONLY IN
Check Valve . . . . . . 2 46-049-1-004 26 1/2" x 1/4" x 1/2" PRE-TRIMMED VALVE ASSEMBLIES:
10 Drip Funnel Reducing Tee . . . . . 2 CH
Connector . . . . . . . . 1 92-211-1-005 27 1/2" x 1/2" x 3/4" 42 Model BFV-N
11 Drip Funnel Reducing Tee . . . . . 1 CH Butterfly Valve,
Bracket . . . . . . . . . . 1 92-211-1-003 2-1/2" (DN65) . . . . . 1 59300F025N
12 Drip Funnel . . . . . . . 1 92-343-1-007 3" (DN80) . . . . . . . . 1 59300F030N
45 43 Figure 577 Coupling,
2-1/2" (DN65) . . . . . 1 57725ACP
16 3" (DN80) . . . . . . . . 1 57730ACP
44 Waterflow Pressure
20 Alarm Switch,
1 Model PS10-2. . . . . 1 25710
19 45 Low Air Pressure
9 32 30 Alarm Switch,
6 32
23 Model PS40-2. . . . . 1 25730
5 32
32

24 32
20 15
17
34 39 3
28
2-1/2 INCH (DN65)
44 33 or 3 INCH (DN80)
9 16 4 MODEL DPV-1
25 31 27 DRY PIPE VALVE
(GxG ONLY)
31 LOCATION 32 23
FOR OPTIONAL 36
41
ELECTRICALLY 10 8
18
SUPERVISED 32
22
N.O. ALARM 20
31 40
CONTROL 11
VALVE
26

12 37 NOTES:
13
(GREEN 43 1. SEE FIGURE 3 FOR VALVE
TINT) 14 21 PORT IDENTIFICATION.
38
42 2. ROUTE 1/4" TUBING, ITEM 14,
31 7 TO DRIP FUNNEL, ITEM 12.
6 3. ALL FITTINGS AND NIPPLES
35 ARE GALVANIZED.
32
26 2 4. CH: COMMON HARDWARE
30 5. ITEMS 4245 INCLUDED
3 15 ONLY IN PRE-TRIMMED
VALVE ASSEMBLIES AS
APPLICABLE; OTHERWISE
SEPARATELY ORDERED.
FIGURE 4 - PART 3 OF 3
2-1/2 AND 3 INCH (DN65 AND DN80) MODEL DPV-1 DRY PIPE VALVE
EXPLODED ARRANGEMENT OF VALVE TRIM

/13/
TFP1020
Page 10 of 20

1. SEE FIGURE 5 PART 3 FOR TRIM ARRANGEMENT WITH BILL OF MATERIALS


DPV-1 DATASHEET

LOW AIR
AND COMPONENT PART NUMBERS. PRESSURE
2. TRIM SHOWN FULLY ASSEMBLED; COMPONENTS SUCH AS GAUGES AND ALARM
SWITCHES MAY REQUIRE ASSEMBLY IN TRIM AT INSTALLATION. SWITCH SYSTEM
AIR SUPPLY
4 INCH (DN100) CONTROL VALVE
1/2 INCH NPT SYSTEM
MODEL DPV-1 (NORMALLY
CONNECTION AIR SUPPLY
DRY PIPE VALVE OPEN)
FOR SYSTEM PRESSURE
AIR SUPPLY GAUGE (FxG SHOWN)
3/4 INCH NPT
1 INCH NPT FLANGE ADAPTER CONNECTION
CONNECTION OR GROOVED FOR WATER
FOR LOCAL COUPLING MOTOR ALARM
SPRINKLER
MAIN WATERFLOW
3/4 INCH NPT DRAIN VALVE PRESSURE
CONNECTION (NORMALLY ALARM
TO DRAIN CLOSED) 1/2 INCH NPT SWITCH
CONNECTION
ALARM FOR OPTIONAL
TEST VALVE 2 INCH NPT ACCELERATOR
SYSTEM
(NORMALLY LOW BODY CONNECTION
SYSTEM SHUT-OFF
CLOSED) DRAIN VALVE TO DRAIN AUTOMATIC
WATER VALVE
(NORMALLY (NORMALLY DRAIN VALVE
SUPPLY
CLOSED) OPEN) 1-1/4 INCH NPT
PRESSURE
CONNECTION DRIP
GAUGE
TO DRAIN FUNNEL

FIGURE 5 - PART 1 OF 3
4 INCH (DN100) MODEL DPV-1 DRY PIPE VALVE
PRE-TRIMMED ASSEMBLY

1/2 INCH NPT AIR SUPPLY


CONNECTION CONTROL VALVE
FOR OPTIONAL (NORMALLY
ACCELERATOR OPEN) 1/2 INCH NPT MAIN
CONNECTION SYSTEM DRAIN VALVE
1/2 INCH NPT AUTOMATIC AIR SUPPLY (NORMALLY
DRAIN VALVE FOR OPTIONAL
CONNECTION AIR PRESSURE PRESSURE CLOSED)
FOR WATERFLOW GAUGE
B PRESSURE ALARM
SWITCH
SLOPE
DOWN SWITCH D
3/4 INCH NPT
CONNECTION
FOR WATER A
MOTOR ALARM
2 INCH NPT
1/2 INCH NPT
CONNECTION
CONNECTION
TO DRAIN
FOR SYSTEM
AIR SUPPLY C 4 INCH (DN100)
ALARM MODEL DPV-1
TEST VALVE DRY PIPE VALVE
(NORMALLY (FxG SHOWN)
CLOSED) 1 INCH NPT NOTES:
3/4
INCH NPT
B CONNECTION 1. INSTALL TRIM ASSEMBLIES IN
SYSTEM FOR LOCAL ALPHABETICAL ORDER.
CONNECTION SPRINKLER
WATER SUPPLY 2. SEE FIGURE 3 FOR VALVE PORT
TO DRAIN
PRESSURE IDENTIFICATION.
GAUGE LOW BODY
DRIP DRAIN VALVE 3. ROUTE 1/4" TUBING TO DRIP FUNNEL.
FUNNEL (NORMALLY
1-1/4 INCH NPT CLOSED) 4. SLOPE ASSEMBLY B DOWN TOWARD
CONNECTION BACK OF VALVE TO FACILITATE
TO DRAIN SUFFICIENT LOW BODY DRAINAGE.

FIGURE 5 - PART 2 OF 3
4 INCH (DN100) MODEL DPV-1 DRY PIPE VALVE
EXPLODED ARRANGEMENT OF SEMI-ASSEMBLED TRIM

/14/
TFP1020
Page 11 of 20

NOTES:

DPV-1 DATASHEET
47
16 48 1. SEE FIGURE 3 FOR VALVE
PORT IDENTIFICATION.
28 18
6 2. ROUTE 1/4" TUBING, ITEM 16,
4 5
15 27 TO DRIP FUNNEL, ITEM 14.
34
(GREEN 3. SLOPE 3/4" ANGLE VALVE,
TINT) 12 ITEM 9, DOWN TOWARD
9 29 18
SLOPE 34 14 BACK OF VALVE TO
DOWN 34 FACILITATE SUFFICIENT
26 LOW BODY DRAINAGE.
8 34
19 34 27 4. ALL FITTINGS AND NIPPLES
36 ARE GALVANIZED.
LOCATION 1
30 5. CH: COMMON HARDWARE
FOR OPTIONAL 21
ELECTRICALLY 17 13 6. ITEMS 4548 INCLUDED
32
SUPERVISED ONLY IN PRE-TRIMMED
30 3
N.O. ALARM 41 VALVE ASSEMBLIES AS
CONTROL 39 40 APPLICABLE; OTHERWISE
VALVE 10 SEPARATELY ORDERED.
39 23
30 40 4 INCH (DN100)
34 43 MODEL DPV-1
24 34
DRY PIPE VALVE
42 (FxG SHOWN)
33 31
9
7 20
25
38
33 46

37
11
2 44
NO. DESCRIPTION QTY. P/N 22
1 250 psi/ 1750 kPa 28 3 45
Air Pressure 35
Gauge . . . . . . . . . . . 1 92-343-1-012 17
2 300 psi/ 2000 kPa 32
Water Pressure
Gauge . . . . . . . . . . . 1 92-343-1-005
3 1/4" Gauge Test
NO. DESCRIPTION QTY. P/N
Valve . . . . . . . . . . . . 2 46-005-1-002
4 1/4" Pressure 21 1/2" x 1/4" Reducing
Relief Valve . . . . . . . 1 92-343-1-020 Bushing . . . . . . . . . 1 CH
5 1/2" Angle Valve . . . 1 46-048-1-004 22 1/2" Union. . . . . . . . 1 CH NO. DESCRIPTION QTY. P/N
6 Model AD-1 23 3/4" Union. . . . . . . . 1 CH 41 3/4" x 2" . . . . . . . . . 1 CH
Automatic 24 1/2" 90 Elbow . . . . 1 CH 42 3/4" x 3" . . . . . . . . . 1 CH
Drain Valve . . . . . . . 1 52-793-2-004 25 1/2" 45 Elbow . . . . 1 CH 43 1" x 4" . . . . . . . . . . . 1 CH
7 1/2" Ball Valve . . . . 1 46-050-1-004 26 1/2" Cross. . . . . . . . 1 CH 44 2" x 4-1/2". . . . . . . . 1 CH
8 1/2" Swing 27 1/2" Tee . . . . . . . . . 2 CH
COMPONENTS INCLUDED ONLY IN
Check Valve . . . . . . 1 46-049-1-004 28 1/2" x 1/4" x 1/2"
PRE-TRIMMED VALVE ASSEMBLIES:
9 3/4" Angle Valve . . . 1 46-048-1-005 Reducing Tee . . . . . 2 CH
10 3/4" Swing 29 1/2" x 1/2" x 1/4" 45 Model BFV-N Butterfly
Check Valve . . . . . . 1 46-049-1-005 Reducing Tee . . . . . 1 CH Valve, 4" (DN100) . . 1 59300F040N
11 2" Angle Valve . . . . 1 46-048-1-009 30 3/4" x 1/2" x 3/4" 46 Butterfy Valve
12 Drip Funnel Reducing Tee . . . . . 3 CH Assembly Component:
Connector . . . . . . . . 1 92-211-1-005 31 1" x 1" x 1/2" GxG DPV-1 Valves,
13 Drip Funnel Reducing Tee . . . . . 1 CH Figure 577 Coupling,
Bracket . . . . . . . . . . 1 92-211-1-003 PIPE NIPPLES: 4" (DN100) . . . . . . . 1 57740ACP
14 Drip Funnel . . . . . . . 1 92-343-1-007 32 1/4" x 3". . . . . . . . . . 2 CH FxF, FxG DPV-1 Valves,
15 3/32" Vent 33 1/2" x Close . . . . . . 2 CH Figure 71 Flange Adapter,
Fitting . . . . . . . . . . . 1 92-032-1-002 34 1/2" x 1-1/2" . . . . . . 7 CH 4" (DN100) . . . . . . . 1 7140S
16 1/4" Tube, 35 1/2" x 2" . . . . . . . . . 1 CH 47 Waterflow Pressure
24" Long . . . . . . . . . 1 CH 36 1/2" x 2-1/2" . . . . . . 1 CH Alarm Switch,
17 1/4" Plug . . . . . . . . . 2 CH 37 1/2" x 3" . . . . . . . . . 1 CH Model PS10-2. . . . . 1 25710
18 1/2" Plug . . . . . . . . . 2 CH 38 1/2" x 3-1/2" . . . . . . 1 CH 48 Low Air Pressure
19 3/4" Plug . . . . . . . . . 1 CH 39 3/4" x Close . . . . . . 2 CH Alarm Switch,
20 1" Plug . . . . . . . . . . 1 CH 40 3/4" x 1-1/2" . . . . . . 2 CH Model PS40-2. . . . . 1 25730

FIGURE 5 - PART 3 OF 3
4 INCH (DN100) MODEL DPV-1 DRY PIPE VALVE
EXPLODED ARRANGEMENT OF VALVE TRIM

/15/
TFP1020
Page 12 of 20

NOTES:
DPV-1 DATASHEET

1. SEE FIGURE 6 PART 3 FOR TRIM ARRANGEMENT WITH BILL OF MATERIALS LOW AIR
AND COMPONENT PART NUMBERS. PRESSURE
2. TRIM SHOWN FULLY ASSEMBLED; COMPONENTS SUCH AS GAUGES AND ALARM
SWITCHES MAY REQUIRE ASSEMBLY IN TRIM AT INSTALLATION. SWITCH SYSTEM
AIR SUPPLY
CONTROL VALVE
SYSTEM
(NORMALLY
AIR SUPPLY
OPEN)
PRESSURE
1/2 INCH NPT
GAUGE SYSTEM
CONNECTION LOW BODY
FOR SYSTEM WATER
DRAIN VALVE
AIR SUPPLY SUPPLY
(NORMALLY
PRESSURE
CLOSED)
1 INCH NPT GAUGE
CONNECTION AUTOMATIC
FOR LOCAL GROOVED DRAIN VALVE
SPRINKLER COUPLING
OR FLANGE 1/2 INCH NPT
DRIP FUNNEL ADAPTER CONNECTION
FOR OPTIONAL
MAIN ACCELERATOR
DRAIN VALVE ALARM
(NORMALLY 2 INCH NPT TEST VALVE 1-1/4 INCH NPT
CLOSED) CONNECTION SYSTEM (NORMALLY WATERFLOW
6 INCH (DN150) 3/4 INCH NPT CONNECTION
SHUT-OFF CLOSED) PRESSURE
TO DRAIN MODEL DPV-1 CONNECTION TO DRAIN
VALVE ALARM
DRY PIPE VALVE (NORMALLY FOR WATER SWITCH
(GxG SHOWN) OPEN) MOTOR ALARM
FIGURE 6 - PART 1 OF 3
6 INCH (DN150) MODEL DPV-1 DRY PIPE VALVE
PRE-TRIMMED ASSEMBLY

1/2 INCH NPT 1/2 INCH NPT NOTES:


CONNECTION CONNECTION
B
4. SLOPE 3/4" ANGLE VALVE AND
FOR OPTIONAL FOR SYSTEM 3/4" x 4-1/2" NIPPLE (OF ASSEMBLY B)
AIR PRESSURE AIR SUPPLY INTO DRIP FUNNEL TO FACILITATE
SYSTEM SWITCH
AIR SUPPLY SUFFICIENT LOW BODY DRAINAGE.
PRESSURE AIR SUPPLY DRIP
GAUGE CONTROL VALVE LOW BODY 1/2 INCH NPT FUNNEL
(NORMALLY DRAIN VALVE CONNECTION SLOPE
1 INCH NPT OPEN) (NORMALLY FOR OPTIONAL TO FIT
CONNECTION CLOSED) ACCELERATOR 1/2 INCH NPT
FOR LOCAL CONNECTION
SPRINKLER A AUTOMATIC FOR WATERFLOW
DRAIN VALVE PRESSURE ALARM
SWITCH

MAIN
B 3/4 INCH NPT
CONNECTION
DRAIN VALVE FOR WATER
(NORMALLY MOTOR ALARM
CLOSED)
D
2 INCH NPT
CONNECTION 6 INCH (DN150)
TO DRAIN MODEL DPV-1 DRIP
DRY PIPE VALVE
(FxF SHOWN)
FUNNEL C
NOTES:
1. INSTALL TRIM ASSEMBLIES IN
ALPHABETICAL ORDER.
ALARM
2. SEE FIGURE 3 FOR VALVE PORT 1-1/4 INCH NPT SYSTEM TEST VALVE
IDENTIFICATION. CONNECTION WATER SUPPLY (NORMALLY
3. ROUTE 1/4" TUBING TO DRIP TO DRAIN PRESSURE CLOSED)
FUNNEL. GAUGE

FIGURE 6 - PART 2 OF 3
6 INCH (DN150) MODEL DPV-1 DRY PIPE VALVE
EXPLODED ARRANGEMENT OF SEMI-ASSEMBLED TRIM

/16/
TFP1020
Page 13 of 20

9 BACK OF 4 NOTES: 1. SEE FIGURE 3 FOR VALVE 4. ALL FITTINGS AND NIPPLES

DPV-1 DATASHEET
VALVE 29 PORT IDENTIFICATION. ARE GALVANIZED.
42 35 2. ROUTE 1/4" TUBING, ITEM 16, 5. CH: COMMON HARDWARE
5 TO DRIP FUNNEL, ITEM 14. 6. ITEMS 4548 INCLUDED
14 18 3. SLOPE 3/4" ANGLE VALVE, ONLY IN PRE-TRIMMED
48 ITEM 9, AND 3/4" x 4-1/2" VALVE ASSEMBLIES AS
SLOPE
NIPPLE, ITEM 42, INTO APPLICABLE; OTHERWISE
TO FIT 35
26 DRIP FUNNEL, ITEM 14, TO SEPARATELY ORDERED.
1 8 FACILITATE SUFFICIENT 15
21 40 (GREEN
LOW BODY DRAINAGE. LOCATION
35 TINT) FOR OPTIONAL
3 18
9 35 ELECTRICALLY
30 27 SUPERVISED
17 35 47
33 42 6 16 N.O. ALARM
43 CONTROL
11 27 35 28
20 VALVE
32 31 37
40 31
44 10
40
19
40 41
23
6 INCH (DN150) 42 12
MODEL DPV-1 DRY PIPE VALVE 40
(GxG SHOWN) 31
13
35 24
NO. DESCRIPTION QTY. P/N 39 14 38
22 7 34
1 250 psi/ 1750 kPa
Air Pressure 36 35 25
Gauge . . . . . . . . . . . 1 92-343-1-012 28
2 300 psi/ 2000 kPa 2
Water Pressure
Gauge . . . . . . . . . . . 1 92-343-1-005
3 1/4" Gauge Test
Valve . . . . . . . . . . . . 2 46-005-1-002 33
4 1/4" Pressure 46 3
Relief Valve . . . . . . . 1 92-343-1-020 17 NO. DESCRIPTION QTY. P/N
5 1/2" Angle Valve . . . 1 46-048-1-004 45 35 1/2" x 1-1/2" . . . . . . 8 CH
6 Model AD-1 36 1/2" x 2" . . . . . . . . . 1 CH
Automatic 37 1/2" x 2-1/2" . . . . . . 1 CH
Drain Valve . . . . . . . 1 52-793-2-004 38 1/2" x 3" . . . . . . . . . 1 CH
7 1/2" Ball Valve . . . . 1 46-050-1-004 39 1/2" x 6" . . . . . . . . . 1 CH
8 1/2" Swing 40 3/4" x 1-1/2" . . . . . . 5 CH
Check Valve . . . . . . 1 46-049-1-004 41 3/4" x 2" . . . . . . . . . 1 CH
9 3/4" Angle Valve . . . 1 46-048-1-005 42 3/4" x 4-1/2" . . . . . . 2 CH
10 3/4" Swing 43 1" x 4" . . . . . . . . . . . 1 CH
Check Valve . . . . . . 1 46-049-1-005 44 2" x 4-1/2". . . . . . . . 1 CH
11 2" Angle Valve . . . . 1 46-048-1-009
COMPONENTS INCLUDED ONLY IN
12 Drip Funnel
PRE-TRIMMED VALVE ASSEMBLIES:
Connector . . . . . . . . 1 92-211-1-005
NO. DESCRIPTION QTY. P/N
13 Drip Funnel 45 Model BFV-N Butterfly
Bracket . . . . . . . . . . 1 92-211-1-003 25 1/2" 45 Elbow . . . . 1 CH Valve, 6" (DN150) . . 1 59300F060N
14 Drip Funnel . . . . . . . 1 92-343-1-007 26 1/2" Cross . . . . . . . 1 CH 46 Butterfy Valve
15 3/32" Vent 27 1/2" Tee . . . . . . . . . 2 CH Assembly Component:
Fitting . . . . . . . . . . . 1 92-032-1-002 28 1/2" x 1/4" x 1/2" GxG DPV-1 Valves,
16 1/4" Tube, Reducing Tee . . . . . 2 CH Figure 577 Coupling,
24" Long . . . . . . . . . 1 CH 29 1/2" x 1/2" x 1/4" 6" (DN150) . . . . . . . 1 57760ACP
17 1/4" Plug . . . . . . . . . 2 CH Reducing Tee . . . . . 1 CH FxF, FxG DPV-1 Valves,
18 1/2" Plug . . . . . . . . . 2 CH 30 3/4" 90 Elbow . . . . 1 CH Figure 71 Flange Adapter,
19 3/4" Plug . . . . . . . . . 1 CH 31 3/4" x 1/2" x 3/4" 6" (DN150) . . . . . . . 1 7160S
20 1" Plug . . . . . . . . . . 1 CH Reducing Tee . . . . . 3 CH 47 Waterflow Pressure
21 1/2" x 1/4" Reducing 32 1" x 1" x 1/2" Alarm Switch,
Bushing . . . . . . . . . 1 CH Reducing Tee . . . . . 1 CH Model PS10-2. . . . . 1 25710
22 1/2" Union. . . . . . . . 1 CH PIPE NIPPLES: 48 Low Air Pressure
23 3/4" Union. . . . . . . . 1 CH 33 1/4" x 3" . . . . . . . . . 2 CH Alarm Switch,
24 1/2" 90 Elbow . . . . 1 CH 34 1/2" x Close . . . . . . 1 CH Model PS40-2. . . . . 1 25730
FIGURE 6 - PART 3 OF 3
6 INCH (DN150) MODEL DPV-1 DRY PIPE VALVE
EXPLODED ARRANGEMENT OF VALVE TRIM

/17/
TFP1020
Page 14 of 20

7-1/8" 9" 14-7/8" 9-1/4"


DPV-1 DATASHEET

(180 mm) (230 mm) (380 mm) (235 mm)

2-1/2 & 3 INCH


(DN65 & DN80)
VALVE
20-7/16"
(520 mm)
16-1/8"
(409,6 mm)
2-1/2 or 3 INCH
VALVES

12" 6" 12" 14"


(300 mm) (150 mm) (300 mm) (355 mm)

4 INCH
(DN100)
VALVE

21-7/8"
(555 mm)

18-5/16"
(465 mm)

11-1/2" 7-1/4" 15" 14-3/4"


(290 mm) (190 mm) (380 mm) (375 mm)

6 INCH
(DN150)
VALVE

24-1/2"
(620 mm)

21-7/8"
(555,6 mm)

FIGURE 7 - PART 1 OF 2
MODEL DPV-1 DRY PIPE VALVE
INSTALLATION DIMENSIONS, PRE-TRIMMED VALVE

/18/
TFP1020
Page 15 of 20

6-3/4" 8" 14-7/8" 9-1/4"

DPV-1 DATASHEET
(170 mm) (200 mm) (380 mm) (235 mm)

2-1/2 & 3 INCH


16-9/16" (DN65 & DN80)
(420,7 mm) VALVE

12-1/4"
(311,2 mm)
2-1/2 or 3 INCH
VALVES

6"
(150 mm)

12" 6" 12" 14"


(300 mm) (150 mm) (300 mm) (355 mm)

4 INCH
17-1/4" (DN100)
(440 mm) VALVE

FxF: 13-5/8" (346,1 mm)


FxG: 13-11/16" (347,7 mm)
GxG: 13-3/4" (349,3 mm)

2-1/2" (65 mm)

11-1/2" 7-1/4" 15" 14-3/4"


(290 mm) (190 mm) (380 mm) (375 mm)

6 INCH
(DN150)
VALVE
18-3/4"
(475 mm)

16"
(406,4 mm)
FxF, FxG,
or GxG

4-1/2"
(115 mm)

FIGURE 7 - PART 2 OF 2
MODEL DPV-1 DRY PIPE VALVE
INSTALLATION DIMENSIONS, VALVE AND SEMI-ASSEMBLED TRIM

/19/
TFP1020
Page 16 of 20

the DPV-1 will permit complete draining The main drain and drip funnel drain
Valve Setting
DPV-1 DATASHEET

of the system (including any loose may be interconnected provided


scale) through the main drain port.
During the valve resetting procedure
a check valve is located at least
12 inches (300 mm) below the drip Procedure
funnel. The Low Body Drain Valve Steps 1 through 11 are to be performed
and after the system is completely
(Figure 4, 5, or 6) may be piped so as when initially setting the Model DPV-1
drained, the external reset knob can be
to discharge into the Drip Funnel or to Dry Pipe Valve; after an operational test
easily depressed to externally unlatch
a separate drain. of the fire protection system; or, after
the Clapper Assembly, as shown
in Figure 3E. As such, the Clapper Suitable provision must be made system operation due to a fire.
Assembly is returned to its normal set for disposal of drain water. Drainage NOTES: If the DPV-1 is equipped with
position to facilitate setting of the dry water must be directed such that it a Dry Pipe Valve Accelerator, refer to its
pipe sprinkler system, without having to will not cause accidental damage to resetting instructions before resetting
remove the Handhole Cover. property or danger to persons. the DPV-1. Refer to TFP1105 for the
Unused pressure alarm switch and/or VIZOR or TFP1112 for the ACC-1.
Installation water motor alarm connections must
be plugged.
Based on the instructions provided,
reset the Accelerator at the appropriate
General Instructions The Pressure Relief Valve provided time during the resetting of the DPV-1.
Proper operation of the Model DPV-1 with the Valve Trim is factory set to
Dry Pipe Valve depends upon its trim Unless otherwise noted, refer to Figure
relieve at a pressure of approximately 4, 5, or 6 to identify functional trim
being installed in accordance with the 45 psi (3,1 bar), which can typically be
instructions given in this Technical Data components.
used for a maximum normal system
Sheet. Failure to follow the appropriate air pressure of 40 psi (2,8 bar). The Step 1. Close the Main Control Valve,
trim diagram may prevent the DPV-1 Pressure Relief Valve may be reset to and close the Air Supply Control Valve.
Valve from functioning properly, as a lower or higher pressure; however, it If the DPV-1 is equipped with a Dry
well as void listings, approvals, and the must be reset to relieve at a pressure Pipe Valve Accelerator, remove the Dry
manufacturers warranties. which is in accordance with the Pipe Valve Accelerator from service
Failure to latch open the Clapper requirements of the authority having in accordance with its Technical Data
Assembly prior to a system hydrostatic jurisdiction. Sheet (Refer to TFP1105 for the VIZOR
test may result in damage to the or TFP1112 for the ACC-1).
To reset the Pressure Relief Valve, first
Clapper Assembly. loosen the jam nut and then adjust Step 2. Open the Main Drain Valve and
The DPV-1 Valve must be installed in a the cap accordingly clockwise for all auxiliary drains in the system. Close
readily visible and accessible location. a higher pressure setting or counter- the auxiliary drain valves after water
clockwise for a lower pressure ceases to discharge. Leave the Main
The DPV-1 Valve and associated trim setting. After verifying the desired Drain Valve open.
must be maintained at a minimum pressure setting, tighten the jam nut.
temperature of 40F (4C). Step 3. Depress the plunger of the
Installation of an Air Maintenance Automatic Drain Valve to verify that
Heat tracing of the DPV-1 Valve or its Device, as described in the Technical it is open and that the DPV-1 Valve is
associated trim is not permitted. Heat Data Section, is recommended. completely drained.
tracing can result in the formation of
hardened mineral deposits that are An Inspectors Test Connection Step 4. Open the Optional Alarm
capable of preventing proper operation. as required By NFPA 13 must be Control Valve, as applicable, if it was
provided on the system piping at the closed to silence local alarms.
The Model DPV-1 Dry Pipe Valve is most remote location from the Model
to be installed in accordance with the Step 5. As necessary, replace
DPV-1 Valve. all sprinklers that have operated.
following criteria:
Conduit and electrical connections Replacement sprinklers must be of the
All nipples, fittings, and devices must are to be made in accordance with same type and temperature rating as
be clean and free of scale and burrs the requirements of the authority those which have operated.
before installation. Use pipe thread having jurisdiction and/or the National
sealant sparingly on male pipe Electric Code. NOTICE
NOTICE
threads only.
Before a system hydrostatic test In order to prevent the possibility of
The DPV-1 Valve must be trimmed is performed in accordance with a subsequent operation of an over-
in accordance with Figures 4, 5, NFPA 13 system acceptance test heated solder type sprinkler, any solder
or 6, as applicable. If the DPV-1 requirements, the Clapper Assembly type sprinklers which were possibly
is to be equipped with a Dry Pipe is to be manually latched open (Ref. exposed to a temperature greater than
Valve Accelerator, refer to the Figure 3D); the Automatic Drain Valve their maximum rated ambient must be
Technical Data Sheet TFP1105 for (Figure 4, 5, or 6) is to be temporarily replaced.
the VIZOR Electronic Dry Pipe Valve replaced with a 1/2 inch NPT plug, the
Accelerator or TFP1112 for the Model Step 6. Push down on the Reset
3/32 inch Vent Fitting (Item 13, Figure
ACC-1 Mechanical Dry Pipe Valve Knob (Figure 3E) to allow the Clapper
4; Item 15, Figure 5; or Item 15, Figure
Accelerator. Assembly to re-seat.
6) is to be temporarily replaced with a
Care must be taken to make sure that 1/4 inch NPT plug, and the Handhole Step 7. Pressurize the system with air
check valves, strainers, globe valves, Cover Bolts are to be tightened using (or nitrogen) to 10 psi (0,7 bar), and
etc. are installed with the flow arrows a cross-draw sequence. then individually open all auxiliary drain
in the proper direction. valves in the system piping to drain any
remaining water in trapped sections.
Drain tubing to the drip funnel must Close each drain valve as soon as
be installed with smooth bends that water ceases to discharge.
will not restrict flow.

/20/
TFP1020
Page 17 of 20

Also partially open the Low Body Before closing a fire protection system inspect the inside of the valve be

DPV-1 DATASHEET
Drain Valve to assure that the riser is main control valve for maintenance performed at this time and prior to
completely drained. Close the Low work on the fire protection system that resetting the DPV-1 Valve. Refer to
Body Drain Valve as soon as water it controls, permission to shut down the the Automatic Drain Valve Inspection
ceases to discharge. affected fire protection system must be sub-section Steps 2 through 5
obtained from the proper authorities for instructions with regard to the
Step 8. Refer to Table B and then
and notify all personnel who may be inspection of the Clapper Facing.
restore the system to the normal
affected by action.
system air pressure as necessary to Quarterly Waterflow
hold the DPV-1 Valve closed. The owner is responsible for the Alarm Test Procedure
inspection, testing, and maintenance of Testing of the system waterflow alarms
Step 9. Depress the plunger on the
their fire protection system and devices should be performed quarterly. To test
Automatic Drain Valve to make sure
in compliance with this document, as the waterflow alarm, open the Alarm
it is open and that there is no air
well as with the applicable standards Test Valve, which will allow a flow of
discharging.
of the National Fire Protection water to the Waterflow Pressure Alarm
The absence of air discharging from the Association (e.g., NFPA 25), in addition Switch and/or Water Motor Alarm.
Automatic Drain Valve is an indication to the standards of any authority having Upon satisfactory completion of the
of a properly set air seat within the jurisdiction. Contact the installing test, close the Alarm Test Valve.
DPV-1 Valve. If air is discharging, refer contractor or sprinkler manufacturer
to the Care and Maintenance section regarding any questions. Water Pressure Inspection
under Automatic Drain Valve Inspection The Water Pressure Gauge is to be
Automatic sprinkler systems are inspected monthly (per NFPA 25)
to determine/correct the cause of the
recommended to be inspected, to ensure that normal system water
leakage problem.
tested, and maintained by a qualified pressure is being maintained.
Step 10. Partially open the Main Control Inspection Service in accordance with
Valve. Slowly close the Main Drain Valve local requirements and/or national Air Pressure Inspection
as soon as water discharges from the codes. The Air Pressure Gauge is to be
drain connection. inspected monthly (per NFPA 25) to
The operational test procedure ensure that normal system air pressure
Depress the plunger on the Automatic and waterflow pressure alarm test is being maintained.
Drain Valve to make sure that it is procedure will result in operation of
open and that there is no water the associated alarms. Consequently, Automatic Drain Valve Inspection
discharging. The absence of water notification must first be given to the The Automatic Drain Valve should be
discharging from the Automatic Drain owner and the fire department, central inspected monthly (per NFPA 25) by
Valve is an indication of a properly set station, or other signal station to which depressing the plunger and checking
water seat within the DPV-1 Valve. If the alarms are connected. to ensure that the Automatic Drain
water is discharging, refer to the Care Valve is not discharging water and/
and Maintenance section under the Annual Operation Test Procedure or air. A discharge of water and/or
Automatic Drain Valve Inspection to Note: Unless otherwise noted, refer to air is an indication that the air and/or
determine/correct the cause of the Figure 4, 5, or 6 to identify functional water seats are leaking, which could
leakage problem. trim components. subsequently cause a false operation
Proper operation of the DPV-1 Valve should the intermediate chamber
If there are no leaks, the DPV-1 Valve is become inadvertently pressurized.
ready to be placed in service and the (i.e., opening of the DPV-1 Valve during
Main Control Valve must then be fully a fire condition) should be verified at If leakage is present, take the DPV-1
opened. least once a year as follows: Valve out of service (i.e., close the
Step 1. If water must be prevented from main control valve, open the main
Note: After setting a fire protection drain valve, close the air supply control
system, notify the proper authorities flowing beyond the riser, perform the
following steps. valve, remove the Dry Pipe Valve
and advise those responsible for Accelerator from service, as applicable,
monitoring proprietary and/or central Close the Main Control Valve. in accordance with its Technical Data
station alarms. Sheet (Refer to TFP1105 for the VIZOR
Open the Main Drain Valve.
Step 11. Once a week after a valve is or TFP1112 for the ACC-1), and open
Open the Main Control Valve one turn the Inspectors Test Connection to
reset following an operational test or
beyond the position at which water relieve the system air pressure to 0 psig
system operation, the Low Body Drain
just begins to flow from the Main as indicated on the System Air Pressure
Valve (and any low point drain valves)
Drain Valve. Gauge), and then after removing the
should be partially opened (and then
subsequently closed) to relieve drain- Close the Main Drain Valve. Handhole Cover, perform the following
back water. Continue this procedure steps:
Step 2. Open the systems Inspectors
until drain-back water is no longer Test Connection. Step 1. Make sure that the Seat
present. Ring is clean and free of any nicks or
Step 3. Verify that the DPV-1 Valve significant scratches.
Care and has operated, as indicated by the flow
of water into the system and that all Step 2. Remove the Clapper Assembly
from the valve by first pulling out the
Maintenance waterflow alarms operate properly.
Step 4. Close the systems Main
Hinge Pin.
The following procedures and Control Valve. Step 3. Disassemble the Clapper
inspections should be performed as Facing Retainer from the Clapper
Step 5. Reset the DPV-1 Valve in so that the Clapper Facing can be
indicated, in addition to any specific accordance with the Valve Setting
requirements of the NFPA, and any removed and inspected. Make sure
Procedure. that the Clapper Facing does not show
impairment must be immediately
corrected. Note: It is recommended that the signs of compression set, damage, etc.
requirement of NFPA 25 to annually Replace the Clapper Facing if there is
any signs of wear.

/21/
TFP1020
Page 18 of 20

Step 4. Clean the Clapper Facing, Pre-Trimmed DPV-1 Assemblies Accessories


DPV-1 DATASHEET

Clapper, and Clapper Facing Retainer, with Butterfly Valve Order the Technical Data Sheets for the
and then reassemble the Clapper Specify: 2-1/2 Inch DPV-1 Pre-Trimmed following, as applicable, for details and
Assembly. Valve Assembly, P/N 52-310-3-925 additional accessories:
Step 5. Reinstall the Clapper Assembly Specify: 3 Inch DPV-1 Pre-Trimmed Model PS10-2
with its Hinge Pin and then reinstall the Valve Assembly, P/N 52-310-3-930 Potter Electric Waterflow
Handhole Cover. Pressure Alarm Switch
Specify: 4 Inch DPV-1 Pre-Trimmed
Valve Assembly, P/N (specify) . . . . . . . . . . . . . . . . . . . . . . P/N 25710
Ordering FxF . . . . . . . . . . . . . . . . P/N 52-310-3-040
Model PS40-2
Potter Electric Low Air Pressure Alarm
Procedure FxG . . . . . . . . . . . . . . . . P/N 52-310-3-440
GxG . . . . . . . . . . . . . . . P/N 52-310-3-940
Switch . . . . . . . . . . . . . . . . P/N 25730
Model WMA1
Refer to Table A for Flange Drilling Specify: 6 Inch DPV-1 Pre-Trimmed Water Motor Alarm
Specifications. Valve Assembly, P/N (specify) . . . . . . . . . . . . . . . . P/N 52-630-1-001
Model AMD-1
Standard DPV-1 Dry Pipe Valve FxF . . . . . . . . . . . . . . . . P/N 52-310-3-060
Air Maintenance Device
(American Standard Flange Drilling, FxG . . . . . . . . . . . . . . . . P/N 52-310-3-460
. . . . . . . . . . . . . . . . P/N 52-324-2-002
Threaded Ports, and Groove GxG . . . . . . . . . . . . . . . P/N 52-310-3-960
Model AMD-2
Outside Diameter, as applicable) Pre-Trimmed DPV-1 Assemblies Air Maintenance Device
Specify: (specify size) Model DPV-1 Dry without Butterfly Valve . . . . . . . . . . . . . . . . P/N 52-326-2-001
Pipe Valve with (specify Inlet x Outlet) Specify: 4 Inch DVP-1 Pre-Trimmed Model AMD-3
end connections, P/N (specify). Valve Assembly without Butterfly, P/N Nitrogen Maintenance Device
2-1/2 Inch (DN65) (specify)
. . . . . . . . . . . . . . . . P/N 52-328-2-001
GxG, FxF . . . . . . . . . . . . . . . . P/N 52-310-4-040
2.88 inch (73,1 mm) O.D. FxG . . . . . . . . . . . . . . . . P/N 52-310-4-440 Replacement Valve Parts
Groove x 2.88 inch (73,1 mm) Specify: (description) for use with
O.D. Groove . . . . . . P/N 52-310-1-925
Specify: 6 Inch DVP-1 Pre-Trimmed (specify size) Model DPV-1 Dry Pipe
Valve Assembly without Butterfly, P/N Valve, P/N (see Figure 1 Parts 1 and 2
3 Inch (DN80) (specify) as applicable).
GxG,
3.50 inch (88,9 mm) O.D. FxF . . . . . . . . . . . . . . . . P/N 52-310-4-060 Replacement Trim Parts
Groove x 3.50 inch (88,9 mm) FxG . . . . . . . . . . . . . . . . P/N 52-310-4-460 Specify: (description) for use with
O.D. Groove . . . . . . P/N 52-310-1-930 Standard Galvanized (specify size) Model DPV-1 Dry Pipe
Semi-Assembled DPV-1 Trim Valve, P/N (Figures 4, 5, or 6, Part 3 as
4 Inch (DN100)
Specify: 2-1/2 and 3 Inch DPV-1 Semi- applicable).
GxG,
Assembled Galvanized Trim, P/N
4.50 inch (114,3 mm) O.D. Weights
52-309-2-005.
Groove x 4.50 inch (114,3 mm) The following are the nominal weights
O.D. Groove . . . . . . P/N 52-310-1-940 Specify: 4 Inch DPV-1 Semi-Assembled for the valves and trim:
FxG, Galvanized Trim, P/N 52-309-2-001
ANSI Drilled Flange Pre-Trimmed DPV-1 Valve
Specify: 6 Inch DPV-1 Semi-Assembled
x 4.50 inch (114,3 mm) Galvanized Trim, P/N 52-309-2-002 Assemblies:
O.D. Groove . . . . . . P/N 52-310-1-440 2-1/2 Inch (DN65)
FxF, Optional Accelerator GxG Dry Pipe Valve . . . . . 87lbs.(40kg)
ANSI Drilled Flange x ANSI VIZOR Electronic Dry Pipe 3 Inch (DN80)
Drilled Flanged . . . . P/N 52-310-1-040 Accelerator (with Trim) GxG Dry Pipe Valve . . . . . 90lbs.(42kg)
(Details provided in TFP1105) 4 Inch (DN100)
6 Inch (DN150)
GxG, Specify: VIZOR Electronic Dry Pipe GxG Dry Pipe Valve . . . . 121lbs.(56kg)
6.62 inch (168,3 mm) O.D. Accelerator for use with the 4 or 6 4 Inch (DN100)
Groove x 6.62 inch (168,3 mm) inch TYCO Model DPV-1 Dry Pipe FxG Dry Pipe Valve. . . . . 135lbs.(64kg)
O.D. Groove . . . . . . P/N 52-310-1-960 Valve trim, P/N 52-312-3-001 4 Inch (DN100)
FxG, FxF Dry Pipe Valve . . . . . 145lbs.(69kg)
Model ACC-1 Mechanical 6 Inch (DN150)
ANSI Drilled Flange Accelerator
x 6.62 inch (168,3 mm) GxG Dry Pipe Valve . . . . 175lbs.(81kg)
(Details provided in TFP1112)
O.D. Groove . . . . . . P/N 52-310-1-460 6 Inch (DN150)
FxF, Specify: Model ACC-1 Dry Pipe FxG Dry Pipe Valve. . . . . 195lbs. (90kg)
Accelerator, P/N 52-311-1-001, and 6 Inch(DN150)
ANSI Drilled Flange x ANSI
Drilled Flanged . . . . P/N 52-310-1-060 Galvanized Accelerator Trim for FxF Dry Pipe Valve . . . . 208lbs. (96kg)
Model DPV-1 Dry Pipe Valve, Standard Galvanised
P/N 52-311-2-010 Semi-Assembled DPV-1 Trim:
2-1/2 Inch (DN65)
Optional 600 PSI Water Pressure Valve Trim . . . . . . . . . . . . 23lbs. (11kg)
Gauge 3 Inch (DN80)
Specify: 600 PSI Water Pressure Valve Trim . . . . . . . . . . . . 23lbs. (11kg)
Gauge, P/N 92-343-1-004 4 Inch (DN100)
Valve Trim . . . . . . . . . . . . 30lbs. (14kg)
6 Inch (DN150)
Valve Trim . . . . . . . . . . . . . 30lbs. (14kg)

/22/
TFP1020
Page 19 of 20

DPV-1 Valve: Part Numbers For Other 4 Inch FxG,

DPV-1 DATASHEET
2-1/2 Inch (DN65) (DN100) Dry Pipe Valves JIS Flange x 6.62 (168,3 mm)
GxG Dry Pipe Valve . . . . . 37lbs. (17kg) Valves with NPT Ports Outside Dia. Groove
3 Inch (DN80) FxG, . . . . . . . . . . . . . . . . P/N 52-309-1-815
GxG Dry Pipe Valve . . . . . 38lbs. (18kg) ISO Flange x 4.50 (114,3 mm) FxG,
4 Inch (DN100) Outside Dia. Groove JIS Flange x 6.50 (165,1 mm)
GxG Dry Pipe Valve . . . . .57lbs. (26kg) . . . . . . . . . . . . . . . . P/N 52-309-1-253 Outside Dia. Groove
4 Inch (DN100) FxG, . . . . . . . . . . . . . . . . P/N 52-309-1-835
FxG Dry Pipe Valve. . . . . . 67lbs. (31kg) AS Flange x 4.50 (114,3 mm) FxF,
4 Inch (DN100) Outside Dia. Groove ISO Flange x ISO Flange
FxF Dry Pipe Valve . . . . . .77lbs. (36kg) . . . . . . . . . . . . . . . . P/N 52-309-1-613 . . . . . . . . . . . . . . . . P/N 52-309-1-135
6 Inch (DN150) FxG, FxF,
GxG Dry Pipe Valve . . . . .95lbs. (44kg) JIS Flange x 4.50 (114,3 mm) AS Flange x AS Flange
6 Inch (DN150) Outside Dia. Groove . . . . . . . . . . . . . . . . P/N 52-309-1-515
FxG Dry Pipe Valve. . . . 108 lbs. (50kg) . . . . . . . . . . . . . . . . P/N 52-309-1-813 FxF,
6 Inch(DN150) FxF, JIS Flange x JIS Flange
FxF Dry Pipe Valve . . . . . 121lbs. (56kg) ISO Flange x ISO Flange . . . . . . . . . . . . . . . . P/N 52-309-1-715
Other DPV-1 Dry Pipe Valves . . . . . . . . . . . . . . . . P/N 52-309-1-133 Valves with ISO Ports
Notes: Other DPV-1 Dry Pipe Valves are FxF, GxG,
valves ordered with a any combination AS Flange x AS Flange 6.62(168,3 mm) Outside Dia.
of flange, threaded ports, or groove . . . . . . . . . . . . . . . . P/N 52-309-1-513 Groove x 6.62(168,3 mm)
outside diameter not offered under FxF, Outside Dia. Groove
Standard DPV-1 Dry Pipe Valve JIS Flange x JIS Flange . . . . . . . . . . . . . . . . P/N 52-309-1-925
offerings. . . . . . . . . . . . . . . . . P/N 52-309-1-713 GxG,
Valves with NPT threaded ports are Valves with ISO Ports 6.50(165,1 mm) Outside Dia.
intended for use with the Standard GxG, Groove x 6.50(165,1 mm)
Galvanized Semi-Assembled DPV-1 4.50(114,3 mm) Outside Dia. Outside Dia. Groove
Valve Trim offered and detailed in this Groove x 4.50 (114,3 mm) . . . . . . . . . . . . . . . . P/N 52-309-1-945
document. Valves with ISO threaded Outside Dia. Groove FxG,
ports are intended for use with special . . . . . . . . . . . . . . . . P/N 52-309-1-923 ISO Flange x 6.62(168,3 mm)
order trim that is provided by local FxG, Outside Dia. Groove
distributors to meet the specific needs ISO Flange x 4.50 (114,3 mm) . . . . . . . . . . . . . . . . P/N 52-309-1-215
of certain localities. Please contact your Outside Dia. Groove FxG,
local distributor regarding valves and . . . . . . . . . . . . . . . . P/N 52-309-1-213 ISO Flange x 6.50(165,1 mm)
valve trim for specific localities. FxF, Outside Dia. Groove
Specify: (specify size) Model DPV-1 Dry ISO Flange x ISO Flange . . . . . . . . . . . . . . . . P/N 52-309-1-315
Pipe Valve with (specify inlet x outlet) . . . . . . . . . . . . . . . . P/N 52-309-1-113 FxF,
connections with (specify NPT or ISO) ISO Flange x ISO Flange
threaded ports, P/N (specify). Part Numbers For Other 6 Inch . . . . . . . . . . . . . . . . P/N 52-309-1-115
(DN150) Dry Pipe Valves
Part Numbers For Other 2-1/2 Inch Valves with NPT Ports
(DN65) Dry Pipe Valves GxG,
Valves with NPT Ports 6.50(165,1 mm) Outside Dia.
GxG, Groove x 6.50 (165,1 mm)
3.00(76,1 mm) Outside Dia. Outside Dia. Groove
Groove x 3.00 (76,1 mm) . . . . . . . . . . . . . . . . P/N 52-309-1-935
Outside Dia. Groove FxG,
. . . . . . . . . . . . . . . . P/N 52-309-1-930 ANSI Flange x 6.50 (165,1 mm)
Valves with ISO Ports Outside Dia. Groove
GxG, . . . . . . . . . . . . . . . . P/N 52-309-1-435
2.88(73,0 mm) Outside Dia. FxG,
Groove x 2.88 (73,0 mm) ISO Flange x 6.62 (168,3 mm)
Outside Dia. Groove Outside Dia. Groove
. . . . . . . . . . . . . . . . P/N 52-309-1-920 . . . . . . . . . . . . . . . . P/N 52-309-1-255
GxG, FxG,
3.00(76,1 mm) Outside Dia. ISO Flange x 6.50 (165,1 mm)
Groove x 3.00 (76,1 mm) Outside Dia. Groove
Outside Dia. Groove . . . . . . . . . . . . . . . . P/N 52-309-1-335
. . . . . . . . . . . . . . . . P/N 52-309-1-940 FxG,
AS Flange x 6.62 (168,3 mm)
Part Numbers For Other 3 Inch
Outside Dia. Groove
(DN80) Dry Pipe Valves
. . . . . . . . . . . . . . . . P/N 52-309-1-615
Valves with ISO Ports FxG,
GxG,
AS Flange x 6.50 (165,1 mm)
3.50(88,9 mm) Outside Dia.
Outside Dia. Groove
Groove x 3.50 (88,9 mm)
. . . . . . . . . . . . . . . . P/N 52-309-1-635
Outside Dia. Groove
. . . . . . . . . . . . . . . . P/N 52-309-1-922

/23/
ACC-1 DATASHEET

Worldwide
www.tyco-fire.com
Contacts

Model ACC-1 Dry Pipe Valve Accelerator


Extenal Resetting Quick Opening Device
For Dry Pipe Valves
General NOTICE
The TYCO Model ACC-1 Dry Pipe Valve
Description Accelerator described herein must be
installed and maintained in compliance
The TYCO Model ACC-1 Dry Pipe Valve with this document, as well as with the
Accelerator is a quick opening device applicable standards of the National
intended for attachment to the TYCO Fire Protection Association, in addition
Fire Protection Products, 2-1/2, 3, 4 or to the standards of any other authorities
6 inch Model DPV-1 Dry Pipe Valve. The having jurisdiction. Failure to do so may
Model ACC-1 Accelerator reduces the impair the performance of this device.
time for valve operation following the
operation of one or more automatic The owner is responsible for
sprinklers. maintaining their fire protection system
and devices in proper operating
The Model ACC-1 Dry Pipe Valve condition. Contact the installing
Accelerator automatically adjusts to contractor or product manufacturer
both small and slow changes in system
pressure, but trips when there is a rapid
with any questions. Design
and steady drop in pressure (as in the
case of a sprinkler operation). Upon Technical Data
tripping, the Accelerator transmits
system air pressure to the intermediate Data The connection to the system piping,
Figure 4, must be located so that
chamber of the Model DPV-1 Dry Pipe Approvals drain back water will not flow into
Valve. This neutralizes the differential UL and ULC Listed the Accelerator piping and it must be
pressure holding the Model DPV-1 FM Approved located at a point above the maximum
Dry Pipe Valve closed and permits it LPCB Approved expected level of the drain back/
to open. condensate water.
Maximum Working Water Pressure
The Model ACC-1 Dry Pipe Valve 250 psi (17,2 bar) If the connection is made to the riser,
Accelerator has a unique, positive it must be located at least two feet
action, internal anti- flood device and Maximum Working Air Pressure above the level of the dry pipe valve.
a ball float which combine to prevent 70 psi (4,8 bar) Connections to a feed or cross main
water and water borne debris from must be made either to the side or top
Pressure Decay For Trip
entering the more sensitive operating of the main.
1 psi/min (0,07 bar/min)
areas of the accelerator. The anti-flood
NOTES:
device seals and latches immediately Physical Characteristics
upon operation of the Model ACC-1 Body components constructed of Failure to follow the above instructions
Accelerator without waiting for a alodine coated aluminum alloy with can result in accidental tripping due to
pressure build-up in the intermediate austenitic series stainless steel closure of the ball float.
chamber of the dry pipe valve. The internal components. Seals are EPDM Quick operation of the Accelerator
latching feature keeps the anti-flood and silicone. does not ensure that the fire protection
device sealed, even while the system system will meet the water delivery
is being drained. The ball float seals the time requirement of the authority
pilot chamber inlet port if there is an having jurisdiction (following opening
inadvertent trip of the dry pipe valve, of the Inspectors Test Connection).
due for example, to an air compressor The sprinkler system designer needs
failure combined with a slow loss in to be aware that water delivery
system air pressure due to a leak. time is primarily determined by the
The Model ACC-1 Dry Pipe Valve configuration and volume of the piping
Accelerator is a direct replacement network, system air pressure at time
for the Central Model B, Gem Model of Accelerator trip, and water supply
F311, and Star Model S430. Contact characteristics.
the Technical Services Department
for information concerning the use of
the ACC-1 for use with dry pipe valves
other than the Model DPV-1.

Page 1 of 10 MARCH 2011 TFP1112

/24/
TFP1112
Page 2 of 10

Operation 1/4" NPT GAUGE

DPV-1
CONNECTION

ACC-1DATASHEET
The Inlet Chamber of the Accelerator, RESTRICTION
Figure 1, is pressurized via its
connection to the system (at a point

DATASHEET
above the maximum expected level of DIFFERENTIAL
drain back water). The Pilot Chamber CHAMBER
is, in turn, pressurized through its inlet
port which is formed by the annular
opening around the lower tip of the
Anti-Flood Valve. As the Pilot Chamber
increases in pressure, the Differential PILOT
Chamber is pressurized through the CHAMBER
Restriction.
SPRING
The Accelerator is in its set position
while it is being pressurized as well ANTI-FLOOD VALVE
as after the Inlet, Pilot Chamber and BALL FLOAT
Differential Chamber pressures have
1/2" NPT INLET
equalized. When in the Set position,
the Outlet Chamber is sealed off by
the Exhaust Valve which is held against PILOT CHAMBER
its seat by a combination of the Spring INLET PORT RELIEF VALVE
pushing up against the Lever and the
net downward force exerted by the INLET CHAMBER EXHAUST VALVE
pressure in the Pilot Chamber. 1/2" NPT OUTLET OUTLET CHAMBER
Both small and slow changes in FIGURE 1
system pressure are accommodated MODEL ACC-1 ACCELERATOR
by flow through the Restriction. When, IN SET POSITION
however, there is a rapid and steady
drop in system (i.e., Inlet and Pilot
Chamber) pressure, the pressure in
the Differential Chamber reduces at a
substantially lower rate. This condition
creates a net downward force on the PLUNGER
Plunger which rotates the Lever. As
the Lever is rotated, Figure 2, the Relief
Valve is raised out of the Relief Port
and the Anti-Flood Valve is depressed
downward into the Pilot Chamber Inlet
Port, venting the Pilot Chamber. LATCH
The system pressure in the Inlet RESET KNOB
LEVER
Chamber then forces (raises) the
Exhaust Valve off its seat. This
continues the rotation of the Lever into FROM
SYSTEM
the tripped (latched) position, Figure 2. PIPING
As the Exhaust Valve is raised off its RELIEF PORT
seat, system pressure is transmitted
to the intermediate chamber of the TO DRY
dry pipe valve which neutralizes the PIPE VALVE
INTERMEDIATE
differential pressure holding the valve CHAMBER
closed.
FIGURE 2
Following the dry pipe valve trip, MODEL ACC-1 ACCELERATOR
major water borne debris is prevented IN TRIPPED POSITION
from entering the Accelerator (via the
connection to the system piping) by the
Strainer located at its Inlet. Water and
any fine water borne debris such as
silt is prevented from entering the Pilot
Chamber by virtue of the Anti-Flood
Valve having sealed off its inlet port.
The Check Valve located downstream
of the Accelerator Outlet prevents any
water borne debris from entering the
Accelerator via the connection to the
intermediate chamber of the dry pipe
valve.
After the accelerator/dry pipe valve
has tripped and the sprinkler system

/25/
TFP1112
Page 3 of 10

NO. DESCRIPTION QTY. P/N


Replacement Part Kits
1 Base 1 NR
ACC-1 DATASHEET

2 Cover 1 NR Kit Description P/N


3 Upper Diaphragm 1 Repair Parts Includes Items 5, 6, 8, 10, 11, 23, 27
Plate See (c) 92-311-1-116
Kit (a) & 1.5 grams of FS3452
4 Pivot Plate Assembly 1 See (b) Replacement Include Items 4, 13-22, 29
92-311-1-117
4a Spirol Pin 1 Parts Kit (b) & 1.5 grams of FS3452
4b Pivot Plate 1 Replacement Includes Items 3, 7, 9, 12, 24-26, 28,
92-311-1-118
Parts Kit (c) & 1.5 grams of FS3452
5 Plunger 1 See (a)
5a Pan Hd. Machine Screw 1
5b Upper Diaphragm
Retaining Ring 2
5c Upper Diaphragm 1
5d Jam Nut 1
5a 5
6 Exhaust Valve 1 See (a)
6a Upper Plug 1
5b
6b Washer 1
5c
6c Lower Diaphragm 1 5b
6d Lower Plug 1 5d
6e O-Ring* 1
6f O-Ring Retainer 1
6g Exhaust Valve Screw 1
7 Rd. Head Machine 2
Screw 6 See (c)
1/4-20 UNC x 5/8
8 Cover Gasket 1 See (a)
9 Vent Plug 1 See (c)
10 O-Ring* 1 See (a) 9 (VENT
11 Restriction 1 See (a) PLUG
12 Restriction Access Plug 1 See (c) 3
13 Pan Hd. Machine Screw 5 7
10-32 UNF x 5/8 4 See (b) 3 11
8
14 Cotter Pin 1 See (b) 12 (RESTRICTION
15 Lever 1 See (b) 10 ACCESS PLUG)
16 Retaining Ring 1 See (b) 13
14 4
17 Anti-Flood Valve 1 See (b) 29a
4a
18 Relief Valve 1 See (b) 4b
19 Spring 1 See (b) 15
29b 16
20 Relief Valve Seat 1 See (b)
16 6a
21 O-Ring* 1 See (b) 18
22 Seal Washer 1 See (b) 29c
6
23 Latch 1 See (a) 6b
17 20
24 Fillerster Hd. Machine
Screw 29d
8 See (c) 21 6c
1/4-20 UNC x 1-1/2 19
25 Plug Seat 1 See (c) 29e 22 23
26 O-Ring* 1 See (c) 29 6d
27 O-Ring* 1 See (a)
28 Reset Knob 1 See (c) 29f
6e
29 Anti-Flood Seat
Assembly w/Ball Float 1 See (b)
29a Insert 1 6f
29b Seal 1
29c Guide 1 6g
29d Ball 1 1
29e Clip 1 27
29f O-Ring* 1 24

* Requires thin film of FS3452 25


Fluorosilicone Grease 28 (RESET
KNOB)
NR: Not Replaceable 26

FIGURE 3
MODEL ACC-1 ACCELERATOR
ASSEMBLY

/26/
TFP1112
Page 4 of 10

NO. DESCRIPTION QTY P/N NO. DESCRIPTION QTY P/N NO. DESCRIPTION QTY P/N

DPV-1
ACC-1DATASHEET
1 250 psi/ 1750 kPa 3 1/2" Ball Valve . . . . 1 46-050-1-004 6 1/2" 90 Elbow . . . . 3 CH
Air Pressure 4 1/2" Swing 7 1/2" x 1-1/2"
Gauge . . . . . . . . . . . 1 92-343-1-012 Check Valve . . . . . . 1 46-049-1-004 Nipple . . . . . . . . . . . 6 CH

DATASHEET
2 1/2" Y-Strainer . . . . 1 52-353-1-005 5 1/2" Union. . . . . . . . 2 CH 8 1/2" x 3" Nipple. . . . 1 CH
9 1/2" x 3-1/2"
Nipple . . . . . . . . . . . 1 CH
* In accordance with the 2007 edition of NFPA 13, 7.2.4.4, the Accelerator Control Valve
shall be supervised. Where a signaling service is to be utilized, replace the Ball Valve 10 1/2" x 5-1/2"
with a BVS-1/2" electrically supervised control valve. Nipple . . . . . . . . . . . 1 CH

CH: Common Hardware


ACCELERATOR 1/2" NPT
CONTROL VALVE * CONNECTION TO
(NORMALLY OPEN) SYSTEM PIPING

ACCELERATOR RESTRICTION
ACCELERATOR
PRESSURE 3* PRESSURE ACCESS PLUG
GAUGE GAUGE
7 VENT
DRY PLUG
DRY 5
PIPE VALVE 1 PIPE VALVE
7 RESET
ACCELERATOR ACCELERATOR KNOB
6 ACCELERATOR
7
2 NOMENCLATURE
8
6
7
7 4
10 1/2" NPT
5 ACCELERATOR
TRIM CONNECTION
7 9 TO INTERMEDIATE ACCELERATOR
CHAMBER DRY PRESSURE
6 PIPE VALVE GAUGE
2-1/2 or 3 INCH (DN65 or DN80) ACCELERATOR

ACCELERATOR 1/2" NPT 1


ACCELERATOR
CONTROL VALVE * CONNECTION TO CONTROL VALVE *
(NORMALLY OPEN) SYSTEM PIPING (NORMALLY OPEN)
3*
ACCELERATOR
PRESSURE 3* 1/2" NPT 7 8
GAUGE CONNECTION TO 5
7 7
SYSTEM PIPING 7
DRY 5
PIPE VALVE 1 5
7 2
ACCELERATOR 7
6 7
6
7 6
2 10
8 4
6
7 7
4 6
7 10
9
5
7 9
1/2" NPT
6 1/2" NPT ACCELERATOR
ACCELERATOR TRIM CONNECTION
TRIM CONNECTION TO INTERMEDIATE
TO INTERMEDIATE CHAMBER
CHAMBER
4 INCH (DN100) 6 INCH (DN150)
FIGURE 4
MODEL ACC-1 DRY PIPE VALVE ACCELERATOR TRIM FOR
2-1/2, 3, 4, AND 6 INCH MODEL DPV-1 DRY PIPE VALVES

/27/
TFP1112
Page 5 of 10

8" 15"
(200 mm) 2-1/2 & 3 INCH (380 mm)
ACC-1 DATASHEET

(DN65 & DN80)


VALVE

21-1/8"
(540 mm)

12" 15"
(300 mm) (380 mm)
4 INCH
(DN100)
VALVE

24-1/2"
(625 mm)

11-1/2" 11-1/8"
(290 mm) (283 mm)

6 INCH
(DN150)
VALVE

23-3/4"
(600 mm)

FIGURE 5
MODEL ACC-1 DRY PIPE VALVE ACCELERATOR TRIM
MODEL DPV-1 DRY PIPE VALVE INSTALLATION DIMENSIONS

/28/
TFP1112
Page 6 of 10

has been drained, the piping from the


Pressure, psi Minimum, sec. Maximum, sec.

DPV-1
system to the Accelerator must also

ACC-1DATASHEET
be drained and the Accelerator reset/ 20 24 160
inspected according to the instructions
given in the Setting Procedure section. 25 18 116

DATASHEET
The rate-of-flow through the Restriction 32 15 92
has been set such that the Model 40 10 60
ACC-1 Accelerator provides the
50 8 48
maximum practical sensitivity to a loss
in system pressure due to a sprinkler 60 6 36
operation while still being capable
of automatically compensating for TABLE A
normal variations in system pressure DIFFERENTIAL CHAMBER FILL TIMES TO 10 PSI
such as are caused by environmental
temperature changes. A test for Step 6. Close the Accelerator Control the first time, since the Accelerator is
verifying that the rate-of-flow through Valve until the Model ACC-1 Accelerator shipped in the set position. Proceed to
the Restriction is within the range for is ready to be placed in service. Step 6.)
optimum Accelerator performance is The Accelerator Control Valve must Step 6. Clean out the Strainer at the
given in the Setting Procedure section. be closed during hydrostatic testing of Accelerator Inlet.
the system in order to prevent damage
Installation to the Ball Float. After the system is
hydrostatically tested and drained,
NOTE: A clogged strainer can prevent
the Accelerator from properly tripping
The TYCO Model ACC-1 Dry Pipe the dry pipe valve.
the Accelerator connection to the
Valve Accelerator must be installed in system must be independently drained Step 7. Slowly remove the Vent Plug
accordance with this section. through the Strainer clean-out plug by located in the front of the Accelerator
first removing the Strainer clean-out Cover and bleed off any residual air
NOTICE plug and then opening the Accelerator pressure in the Differential Chamber.
Failure to follow these instructions can Control Valve to vent the line. Step 8. Unscrew (counter-clockwise
result in flooding of the Accelerator rotation) the knurled Reset Knob at the
and accidental tripping due to closure
of the ball float.
Setting front of the Accelerator until it resists
further turning. A click, which is the
Step 1. The Accelerator must be Procedure sound of the Lever snapping back into
the Set Position, may be heard. Screw
positioned vertically and trimmed per The TYCO Model ACC-1 Dry Pipe Valve
the arrangement shown in Figure 4. the Reset Knob back in until it is finger
Accelerator must be reset and restored tight.
Apply pipe thread sealant sparingly to to service as soon as possible after
male threads only. an operation. Follow the procedure NOTE: Do not wrench on the reset
Step 2. The Strainer located at the indicated below. Knob, since damage may result. The
Accelerator Inlet must be installed Reset Knob will turn with finger torque
Step 1. Close the system main control only.
with its arrow pointed towards the valve, the air supply control valve (to
Accelerator. the system) and the Accelerator Control Step 9. Replace the Vent Plug.
Step 3. The Check Valve located in the Valve. Step 10. Verify that the system air
line between the Accelerator Outlet and Step 2. Open the Inspectors Test pressure has returned to normal.
the intermediate chamber of the dry Connection and then open the main Step 11. Partially open the Accelerator
pipe valve must be installed horizontally drain valve as well as all auxiliary (low Control Valve just enough to allow air
with its arrow pointed in the direction of point) drains. to slowly pass through the Accelerator
flow to the intermediate chamber.
Step 3. After the system has been Control Valve.
Step 4. The connection to the system drained, close the Inspectors Test Using a watch, note the time for the
piping must be located so that drain Connection and all auxiliary drain pressure in the Differential Chamber of
back water will not flow into the valves. Leave the main drain valve the Accelerator to increase to 10 psi.
Accelerator piping and it must be open. The time should be within the range of
located at a point above the maximum
Step 4. Set the dry pipe valve in values indicated in Table A for optimum
expected level of the drain back/
accordance with the instructions given performance of the Accelerator.
condensate water.
in the appropriate technical data sheet. NOTE: If the time to pressurize the
If the connection is made to the riser, it Restore normal system air pressure. Differential Chamber to 10 psi is not
must be located at least two feet above Leave the main control valve closed within the range of values given in
the level of the dry pipe valve priming and the main drain valve open. the Table A, then the Accelerator
water. Connections to a feed or cross
Step 5. While holding the plunger of control Valve should be closed and
main must be made either to the side
the dry pipe valves automatic drain the corrective procedure described
or top of the main.
valve depressed, partially open the in the Care and Maintenance Section
Step 5. The accelerator/dry pipe valve Accelerator Control Valve, and allow followed.
combination must be installed in a the water in the Accelerator piping Step 12. When the air pressure in the
heated enclosure which is maintained to blow out. After water spray stops Differential Chamber of the Accelerator
at a minimum temperature of 40F/4C. discharging, close the Accelerator is equal to that in the system, then the
Heat tracing is not permitted. Control Valve and then release the Accelerator is set and ready for service.
plunger. (This instruction does not
apply when the Model ACC-1 Dry Step 13. Close the Accelerator Control
Pipe Valve Accelerator is being set for Valve and then slowly open the dry

/29/
TFP1112
Page 7 of 10

pipe valves low body drain valve, to It is recommended that the following Relief Port.
bleed off any excess water above the Accelerator inspection procedure be
ACC-1 DATASHEET

Step 3. Reset the accelerator and


priming level. Re-close the low body performed at quarterly. dry pipe valve in accordance with the
drain valve, return system pressure to
Step 1. Verify that the Reset Knob is Setting Procedure Section
its normal value, and then completely
screwed in.
open the Accelerator Control Valve.
Step 14. Partially open the main control
Step 2. Close the systems main Trouble-
control valve and open the main drain
valve. Close the main drain valve as
soon as water discharges from the
valve to relieve the supply pressure to Shooting
the dry pipe valve.
drain connection, and then completely Refer to the following subsections,
open the main control valve. The fire Step 3. Verify that the Accelerator as applicable. If the designated
protection system is now ready for Control Valve is open. instructions do not remedy the
service. Step 4. Open the Inspectors Test particular problem, refer to the
NOTE: After placing a fire protection Connection. Verify that the time to Accele rator D isas sembly and
system in service, notify the proper Accelerator trip is essentially the same Reassembly subsection.
authorities and advise those as in previous tests. A momentary Water Discharge From
responsible for monitoring proprietary burst of air from the Automatic Drain Accelerator Relief Port
and/or central station alarms. Valve indicates that the Accelerator has Use the following instructions if water is
tripped. discharged from the Accelerator Relief
Care and NOTE: As the system pressure is
decreasing, check for any sign of water
Port during a trip.

Maintenance being discharged from the Accelerator


Relief Port.
Step 1. Verify that the connection from
the Accelerator to the system piping
The following procedures and is installed in accordance with Step 4
inspections should be performed as Step 5. Depress the plunger of the of the Installation Section. Correct if
indicated, in addition to any specific Automatic Drain Valve. A steady stream necessary.
requirements of the NFPA, and any of exhausting air indicates that the Step 2. Investigate for and correct
impairment must be immediately Accelerator has properly latched in the any condition which could result in an
corrected. Tripped position. excessive build-up of drain back and/
The owner is responsible for the Step 6. Close the Accelerator Control or condensate water.
inspection, testing, and maintenance of Valve and the Inspectors Test Step 3. Review procedures which
their fire protection system and devices Connection. were used to set the Accelerator.
in compliance with this document, as Step 7. Clean out the Strainer at the Failure to perform Step 5 of the Setting
well as with the applicable standards Accelerator inlet. Procedure can permit a small amount
of the National Fire Protection of water to enter the Pilot Chamber of
Association (e.g., NFPA 25), in addition NOTE: A clogged strainer can prevent the Accelerator.
to the standards of any authority having the Accelerator from properly tripping
jurisdiction. Contact the installing the dry pipe valve. Slow Fill of Differential Chamber
contractor or product manufacturer Use the following instructions if the
Step 8. Reset the Accelerator in time to fill the Differential Chamber
with any questions. accordance with Steps 7 through 14 of is longer than the maximum value
It is recommended that automatic the Setting Procedure Section. indicated in Step 11 of the Setting
sprinkler systems be inspected, System Inspection Procedure Procedure Section.
tested, and maintained by a qualified It is recommended that the following
Inspection Service. Step 1. Check to see that the
Accelerator and dry pipe valve Accelerator was reset per Step 8 of the
The TYCO Model ACC-1 Dry Pipe inspection procedure be performed at Setting Procedure Section.
Valve Accelerator must be maintained least annually, preferably in the spring
and serviced in accordance with the or summer of the year. This procedure Step 2. Close the systems main control
following instructions: can only be used whenever there is no valve and open the main drain valve.
danger that flooding the system will Step 3. Check for any sign of external
NOTES: expose the water to freezing conditions. leakage past the Accelerator Pressure
If an Accelerator is to be temporarily Step 1. Verify that the Reset Knob is Gauge, Vent, and Restriction Access
taken out of service, then the proper screwed in. Plug connections.
authorities and all personnel who may
be affected must be notified. Step 2. Open the Inspectors Test Step 4. Check for any sign of external
Connection. Verify that tripping of the leakage past the Reset Knob and Cover
Before performing an alarm test, notify Accelerator operates the dry pipe valve Gasket.
the proper authorities and all personnel and that water is delivered out of the
who may be affected. Step 5. Close the Accelerator Control
Inspectors Test connection within the Valve.
Before closing a fire protection system elapsed time required by the authority
main control valve for inspection or having jurisdiction. Step 6. Gently insert a 3/32 inch or
maintenance work on the fire protection smaller diameter probe into the Relief
NOTE: As the system pressure is Port. If the probe can be inserted more
system that it controls, permission to decreasing, check for any sign of water
shut down the affected fire protection than 1/4 inch then the Lever has not
being discharged from the Accelerator reset and the Accelerator must be
system must be obtained from the
proper authorities and all personnel disassembled for internal inspection.
who may be affected by this action See the instructions for Accelerator
must be notified. Disassembly and Reassembly.

Accelerator Inspection Procedure

/30/
TFP1112
Page 8 of 10

Step 7. Slowly remove the Accelerator Corning FS3452). Replace the Vent Step 5. Remove the eight screws

DPV-1
Vent Plug to bleed all pressure from the Plug and Restriction Access Plug. holding the Cover to the Base and

ACC-1DATASHEET
Differential Chamber and then slowly Step 6. If the Restriction and its O-ring remove the Cover.
remove the Restriction Access Plug are found to be in good condition, then Step 6. Remove the six screws holding
to bleed all pressure from the Pilot it is likely that there is leakage past the Upper Diaphragm Plate to the

DATASHEET
Chamber. the Plunger. Remove the Cover from Cover. Remove the Plunger and inspect
Step 8. Replace the Restriction and the Base. Check that the six screws the Upper Diaphragm to be sure that
then the Restriction Access Plug. securing the Upper Diaphragm Plate it is flexible and free from physical
to the Cover are tight. damage or deterioration due to age.
Step 9. Place the fire protection
system back in service in accordance Inspect the Upper Diaphragm for any Check the Jam Nut to assure that
with Steps 9 through 14 of the Setting sign of cracks, pin holes or deterioration it is assembled tightly to its Screw.
Procedure Section. due to age. Replace the Plunger if there Re-mount the Plunger and Upper
is any possibility of leakage past the Diaphragm Plate taking care to cross-
Unexplained Accelerator Trip Upper Diaphragm. tighten the screws uniformly.
Use the following instructions if there
is an unexplained accidental trip of the Step 7. Reassemble the Accelerator Step 7. Replace the Restriction if it
Accelerator. and place the fire protection system has been wetted. Clean and lubricate
back in service in accordance with the Restriction O-ring seal with a non-
Step 1. Verify that the connection from Steps 10 through 14 of the Setting petroleum based grease (such as Dow
the Accelerator to the system piping Procedure Section. Corning FS3452).
is installed in accordance with Step 4
of the Installation Section. Correct if Air Leakage Out Automatic Drain Replace the Vent Plug and Restriction
necessary. If there is leakage of air out the Access Plug.
Automatic Drain of the dry pipe valve, Step 8. Remove the Retaining Ring
Step 2. Verify the time to fill the
after the Accelerator and dry pipe valve from the Upper Plug portion of the
Differential Chamber as described
have been placed in service, then it will Exhaust Valve. Remove the four screws
in Step 11 of the Setting Procedure
be necessary to first determine whether holding the Pivot Plate. Remove the
Section. If the time to fill the Differential
the leakage is past the Accelerator or sub-assembly of the Lever and Pivot
Chamber to 10 psi is longer than the
the dry pipe valve. Plate, the Exhaust Valve, the Anti-Flood
maximum indicated value, then follow
the instructions given under Slow Fill Close the Accelerator Control Valve. Valve and the Relief Valve.
of Differential Chamber. Slowly remove the Accelerator Vent Step 9. Inspect the Lower Diaphragm
Plug to bleed all pressure from the to be sure that it is flexible and free
Step 3. If the time to fill the Differential
Differential Chamber and then slowly from physical damage or deterioration
Chamber is within the indicated range
remove the Restriction Access Plug due to age.
of values, then investigate for and
to bleed all pressure from the Pilot
correct any condition which could Step 10. Check to see that the Exhaust
Chamber.
result in excessive leakage of system Valve components are securely
air pressure. If leakage out the Automatic Drain assembled together. Only tighten by
persists then refer to the dry pipe valve gripping the flats using an open end
Fast Fill of Differential Chamber or Technical Data Sheet for maintenance
Long Time to Accelerator Trip type wrench.
instructions. If leakage out of the
Use the following instructions if the time Automatic Drain stops, then the Step 11. Inspect the O-ring on the
to fill the Differential Chamber is shorter Accelerator will have to be taken out of Lower Plug. It must be replaced if
than the minimum value indicated service and the Accelerator Plug Seat there are any signs of nicks, cuts or
in Step 11 of the Setting Procedure removed for cleaning of the seat and deterioration.
Section. This procedure should also be the lower O-ring area on the Exhaust
followed if the time to Accelerator trip Step 12. Inspect the Relief and Anti-
Valve. Flood Valves. If either is bent or nicked
(following opening of the Inspectors
Test Connection) is significantly longer Accelerator Disassembly and Re- it must be replaced.
than expected. assembly (For Internal Inspection Step 13. Remove and inspect the
Step 1. Close the systems main control As Necessary) Latch. The catch leaf should extend
valve and open the main drain valve. Step 1. Close the systems main control 5/16 to 3/8 inches in the free state.
valve and open the main drain valve.
Step 2. Close the Accelerator Control Step 14. Remove the Relief Valve Seat.
Valve. Step 2. Close the Accelerator Control Remove the O-ring and Seal Washer.
Valve. Carefully clean the O-ring and Seal
Step 3. Slowly remove the Accelerator Washer seating surfaces in the valve
Vent Plug to bleed all pressure from the Step 3. Slowly remove the Accelerator
Vent Plug to bleed all pressure from the seat and Accelerator Base. If the
Differential Chamber and then slowly O-ring or Seal Washer is nicked, cut,
remove the Restriction Access Plug Differential Chamber and then slowly
remove the Restriction Access Plug or shows signs of deterioration, it must
to bleed all pressure from the Pilot be replaced.
Chamber. to bleed all pressure from the Pilot
Chamber. Step 15. Replace the Seal Washer in
Step 4. Using a slotted screw driver, the Accelerator Base. Apply a thin film
check the tightness of the Restriction. Step 4. Break the union connections at
the Inlet and Outlet of the Accelerator of Dow Corning FS3452 Fluorosilicone
Step 5. Inspect the Restrictions O-ring and remove it from the line. Plug Grease to the valve seat. Place the
seal. The O-ring must be replaced the connection to the intermediate O-ring in its seat (the lubricant will hold
if there are any signs of nicks, cuts, chamber of the dry pipe valve and it in place) and then thread the Relief
or deterioration due to age. Replace place the fire protection system in Valve Seat into the Body with 10 to 15
the Restriction after cleaning and service while the Accelerator is out for ft.-lbs. of torque.
lubricating its O-ring with a non- maintenance. Step 16. Remove the Anti-Flood Seat
petroleum based grease (such as Dow Assembly w/Ball Float. Check for

/31/
TFP1112
Page 9 of 10

damaged parts and for freedom of j. Replace the Vent Plug and the
Ball movement. If parts are damaged Restriction Access Plug.
ACC-1 DATASHEET

or inoperative, the Assembly must be k. Reinstall the Accelerator and


replaced. return the system to service in
Step 17. After checking the Anti-Flood accordance with the Setting
Seat Assembly w/Ball Float, lubricate Procedure Section.
the O-ring with a thin film of Dow
Corning FS3452 Fluorosilicone Grease,
and thread the Assembly into the Body
Limited
with 10 to 15 ft.-lbs. of torque. Warranty
Step 18. Remove the Reset Knob. For warranty terms and conditions, visit
Carefully clean the O-ring and its www.tyco-fire.com.
seating surface. If the O-ring is cut,
nicked, or shows signs of deterioration
it must be replaced. Lubricate the Ordering
O-ring with a thin film of Dow Corning
FS3452 Fluorosilicone Grease. Procedure
Step 19. Reassemble the Accelerator Orders for the TYCO Model ACC-1
in the following order. Dry Pipe Valve Accelerator, trim and
replacement parts must include the
a. Thread the Reset Knob into the
Base finger tight. description and Part Number (P/N). The
Complete Model ACC-1 Accelerator
b. Set the Anti-Flood Valve (with Package includes the Accelerator and
Retaining Ring in place) and the Basic Galvanized Trim.
Compression Spring into their seat.
Complete Package
c. Set the Exhaust Valve in place. Specify: Complete TYCO Model ACC-1
d. Slide the Relief Valve into the slot Dry Pipe Valve Accelerator Package,
at the end of the Lever and then P/N 52-311-2-002
remount the sub-assembly of the
Lever and Pivot Plate in the Base, Accelerator Only
taking care to cross-tighten the Specify: Model ACC-1 Dry Pipe Valve
screws uniformly. Accelerator, P/N 52-311-1-001
e. Replace the Retaining Ring on Basic Galvanized Trim Only
the Upper Plug. Specify: Model ACC-1 Dry Pipe Valve
Accelerator, Basic Galvanized Trim for
f. Push the Anti-Flood Valve end of
the Lever down and release it twice 2-1/2 thru 6 inch Model DPV-1 Dry Pipe
to assure that there is no binding. Valves, P/N 52-311-2-010
g. Replace the Latch making Replacement Parts for Accelerator
sure that the notch in the bottom (Specify description) for use with Model
straddles the Reset Knob and that ACC-1 Dry Pipe Valve Accelerator, P/N
the tabs at the top are seated in the (see Figure 3)
Base. Place the Lever in the Tripped Replacement Trim Parts
(latched) position.
Specify: (specify description), P/N (see
h. Place the Cover upside down. Figure 4)
Set the Cover Gasket in place and
then push all eight screws through
the Gasket to assist in assembling
the Cover to the Base.
i. Align the Cover with the Base and
tighten all of the screws uniformly.

/32/
DPV-1
AMD-1DATASHEET
DATASHEET
Technical Services 800-381-9312 | +1-401-781-8220
www.tyco-fire.com

Model AMD-1 Automatic Air Maintenance Device


Pressure Reducing Type with
Field-Adjustable Pressure Regulator
General Technical
Description Data
The TYCO Model AMD-1 Automatic Air Approvals
Maintenance Device is an automatic, UL and C-UL Listed
field-adjustable, pressure reducing FM Approved
device. It is used to control the pressure NYC Approved under MEA 206-02-E
in a dry pipe sprinkler system, preaction
Maximum Inlet Air (or Nitrogen)
system, or dry pilot line system of a Supply Pressure
dry pilot actuated deluge or preaction 200 psi (13,8 bar)
valve.
The Model AMD-1 Device is utilized
in applications where there is a
Field-Adjustable Outlet Pressure
Range Installation
5 to 70 psi (0,4 to 4,8 bar) The TYCO Model AMD-1 Automatic Air
compressed air (or nitrogen) source
controlled at a higher pressure than Assembly Maintenance Device must be installed
the desired system pressure. Pressure Major components illustrated in in accordance with the following
sources include plant air supplies Figure 1 are factory assembled with instructions.
with their own automatic compressor galvanized steel nipples and malleable
controls or nitrogen supplies with iron pipe fittings. NOTICE
single-stage, cylinder-mounted
Moisture build-up can adversely affect
Operation
pressure regulators.
performance. Suitable consideration
The Model AMD-1 Automatic Air must be given to the removal
Maintenance Device is a re-designation The By-Pass Valve in the Model AMD-1 of excessive moisture from the
for the Central Model D-2, Gem Model Automatic Air Maintenance Device is compressed air supply.
F324, and Star Model S460. opened to quickly fill the system during 1. Make connections a minimum of
initial pressurization. Once the required 1/2 inch (DN15) pipe size between
NOTICE system pressure has been reached, the inlet air supply and the Model
The Model AMD-1 Automatic Air the By-Pass Valve is closed and the AMD-1 Device, as well as between
Maintenance Devices described herein Air Supply Control Valve is left open the Model AMD-1 Device and the
must be installed and maintained in to place the Model AMD-1 Device in system to pressurize.
compliance with this document and with automatic operation.
2. Place a 1/2 inch (DN15), non-spring
the applicable standards of the National When there is a small leak in the loaded, rubber-faced, swing-type
Fire Protection Association, in addition system, the Pressure Regulator check valve between the Model
to the standards of any authorities automatically maintains system AMD-1 Device and the system to
having jurisdiction. Failure to do so pressure at the preset level. The 3/32 pressurize. A check valve of this
may impair the performance of these inch (2,4 mm) orifice in the Restrictor type is provided in the air supply
devices. Check Valve limits the flow of air from trim of TYCO dry pipe valves,
Owners are responsible for maintaining the Pressure Regulator into the system preaction valves, and dry pilot trim.
their fire protection system and devices to a value significantly less than that
in proper operating condition. The exhausted by the operation of a 5.6
installing contractor or sprinkler K-factor sprinkler.
manufacturer should be contacted with
any questions.

Page 1 of 4 JULY 2010 TFP1221

/33/
Page 2 of 4
AMD-1 DATASHEET

2" 16-1/8""
(50,8 mm) (409,6 mm)
BY-PASS VALVE
1/4" NPT
(NORMALLY
GAUGE
CLOSED)
TEST PORT
3-1/4" 1/2" NPT P/N 46-047-1-004
(82,6 mm) OUTLET
CONNECTION
(TO SYSTEM)
8-1/2"
(215,9 mm) 1/2" NPT
LABEL INLET CONNECTION
(FROM COMPRESSED
AIR SUPPLY)

RESTRICTOR
CHECK VALVE
P/N 92-326-1-003
PRESSURE AIR SUPPLY
REGULATOR STRAINER CONTROL VALVE
(ADJUSTABLE) P/N 52-353-1-002 (NORMALLY OPEN)
P/N 92-324-1-012 P/N 46-048-1-002

FIGURE 1
MODEL AMD-1
AUTOMATIC AIR MAINTENANCE DEVICE

Setting 7. While observing the relocated


pressure gauge, adjust the output
10. Open the control valve in the
air supply trim to the system to
Procedure pressure of the Pressure Regulator.
Pull the knob out and away from the
pressurize.
11. Open the Air Supply Control Valve
The TYCO Model AMD-1 Automatic Pressure Regulator body and then
in the Model AMD-1 Device.
Air Maintenance Device must be set slowly turn the knob clockwise, as
in accordance with the following viewed from the knob end of the 12. Open the By-Pass Valve in the
instructions. Pressure Regulator, to increase Model AMD-1 Device.
pressure, and counter-clockwise to 13. Close the By-Pass Valve after
1. Determine the pressure that meets decrease pressure.
the minimum requirements of the the system is pressurized to
system to pressurize. When decreasing pressure, the air approximately 5 psi (0,4 bar) less
pressure must be relieved down- than the minimum required system
2. Close the Model AMD-1 By-Pass stream of the Pressure Regulator pressure determined in Step 1.
Valve, and close the Model AMD-1 by temporarily opening the control
Air Supply Control Valve. 14. After the system pressure stabilizes,
valve in the air supply trim of the note the value and compare with
3. Open the control valve in the system to pressurize, assuming that the requirement. Re-adjust the
air supply trim of the system to the system to pressurize is at 0 psi. Pressure Regulator, as required.
pressurize and then reduce the After the Pressure Regulator is set,
system air pressure to 0 psi. push the knob in and towards the NOTICE
Pressure Regulator body to snap
4. Close the control valve in the If the system was over-pressurized
it in a locked position.
air supply trim of the system to during manual fill, open a suitable
pressurize. 8. Close the Air Supply Control Valve connection to the system and
5. Remove the system pressure gauge in the Model AMD-1 Device. manually reduce the pressure
from its connection and temporarily 9. Return the system air pressure to the desired value. The Model
install it in the 1/4 inch NPT Model gauge to its normal location. AMD-1 Automatic Air Maintenance
AMD-1 Gauge Test Port. Re-install the 1/4 inch pipe plug in Device then automatically maintains
the Model AMD-1 Gauge Test Port. the preset system pressure. The
Restrictor Check Valve prevents the
CAUTION Apply pipe-thread sealant sparingly
Pressure Regulator from bleeding
Before removing the plug, make to the plug threads only.
down the system pressure.
certain that the piping to which the
Model AMD-1 Gauge Test Port is CAUTION In order to minimize the time for
connected is at 0 psi. Failure to do system trip in the event of a sprinkler
Before removing the pressure
so may result in personal injury or operation, set the system pressure
gauge, make certain that the at the minimum required value.
property damage. piping to which the Model AMD-1
6. Open the Air Supply Control Valve in Gauge Test Port is connected is at
the Model AMD-1 Device. 0 psi. Failure to do so may result in
personal injury or property damage.

/34/
TFP1221
Page 3 of 4

Care and system to pressurize is open. event shall TFSBPs liability exceed an

DPV-1
amount equal to the sales price.

AMD-1DATASHEET
Maintenance
4. Verify that the system pressure
is essentially the same as the The foregoing warranty is made in
previously established requirement. lieu of any and all other warranties,
The TYCO Model AMD-1 Automatic If not, adjust the system pressure as express or implied, including warranties

DATASHEET
Air Maintenance Device must be follows: of merchantability and fitness for a
maintained and serviced in accordance particular purpose.
with the following instructions, in a. Close the systems main control
valve and open the main This limited warranty sets forth the
addition to any specific requirements exclusive remedy for claims based
of the NFPA. Any impairment must be drain valve. If the system is so
equipped, close the Accelerator on failure of or defect in products,
immediately corrected. materials or components, whether the
Control Valve.
claim is made in contract, tort, strict
NOTICE b. Follow Steps 1 through 14 in the liability or any other legal theory.
Setting Procedure section.
Before closing a fire protection system This warranty will apply to the full
main control valve for maintenance c. Slowly open the Accelerator extent permitted by law. The invalidity,
work on the fire protection system that Control Valve, as applicable. in whole or part, of any portion of this
it controls, obtain permission to shut d. Slowly open the main control warranty will not affect the remainder.
down the affected fire protection system valve. After water begins to flow,
from the proper authorities and notify all
personnel who may be affected by this
slowly close the main drain valve,
then completely open the main
Ordering
action.
It is recommended that accumulated
control valve. The Model AMD-1
Automatic Air Maintenance
Procedure
moisture be removed from air supply Device is now ready for service. Contact your local distributor for
moisture filtration equipment at least availability. When placing an order,
quarterly. More frequent inspections
may be necessary in particularly humid
Limited indicate the full product name,
including description and Part Number
environments. Warranty (P/N).
After placing a fire protection system Products manufactured by Tyco Fire Model AMD-1 Device
in service, notify the proper authorities Suppression & Building Products Specify: Model AMD-1 Automatic Air
and advise those responsible for (TFSBP) are warranted solely to the Maintenance Device,
monitoring proprietary and/or central original Buyer for ten (10) years against P/N 52-324-2-002.
station alarms. defects in material and workmanship
when paid for and properly installed Replacement Parts
Responsibility lies with owners for the Specify: (description) for use with
inspection, testing, and maintenance of and maintained under normal use
and service. This warranty will the Model AMD-1 Automatic Air
their fire protection system and devices Maintenance Device, P/N (from Figure
in compliance with this document, as expire ten (10) years from date of
shipment by TFSBP. No warranty is 1).
well as with the applicable standards
of the National Fire Protection given for products or components
Association (for example, NFPA 25), in manufactured by companies not
addition to the standards of any other affiliated by ownership with TFSBP or
for products and components which
authorities having jurisdiction. Contact
have been subject to misuse, improper
the installing contractor or sprinkler installation, corrosion, or which
manufacturer regarding any questions. have not been installed, maintained,
Automatic sprinkler systems are modified or repaired in accordance with
recommend to be inspected, tested, applicable Standards of the National
and maintained by a qualified Fire Protection Association, and/or
Inspection Service in accordance with the standards of any other Authorities
local requirements and/or national Having Jurisdiction. Materials found by
code. TFSBP to be defective shall be either
repaired or replaced, at TFSBPs sole
The Model AMD-1 Device must be option. TFSBP neither assumes, nor
inspected quarterly in accordance with authorizes any person to assume for
the following instructions. it, any other obligation in connection
1. Verify that the By-Pass Valve is with the sale of products or parts
closed. of products. TFSBP shall not be
responsible for sprinkler system design
2. Close the Model AMD-1 Air Supply errors or inaccurate or incomplete
Control Valve and clean out the 1/4 information supplied by Buyer or
inch Strainer located at the inlet to Buyers representatives.
the Restrictor Check Valve. Be sure
to reinstall the strainer screen and In no event shall TFSBP be liable, in
tighten the cap securely. contract, tort, strict liability or under
any other legal theory, for incidental,
3. Open the Model AMD-1 Air Supply indirect, special or consequential
Valve and verify that the control damages, including but not limited to
valve in the air supply trim to the labor charges, regardless of whether
TFSBP was informed about the
possibility of such damages, and in no

/35/
Notes

NOTES





























/36/
Notes

DPV-1 DATASHEET


NOTES




























/37/
Notes

NOTES





























/38/
Notes

DPV-1 DATASHEET


NOTES




























/39/
AV-1 DATASHEET

Worldwide
www.tyco-fire.com
Contacts

Model AV-1-300 Alarm Valve (DN65 to DN200)


With and Without Model RC-1 Retard Chamber
European Conformity Valve Trim
General
Description
The TYCO Model AV-1-300 Alarm
Valves DN65, DN100, DN150, and
DN200 (European Conformity) are
divided-seat ring, rubber-faced
clapper, waterflow alarm valves that are
intended for use in wet pipe (automatic
sprinkler) fire protection systems.
They are designed to automatically
actuate electric and/or hydraulic
alarms when there is a steady flow of
water into the system that is equivalent
to the discharge rate of one or more
sprinklers.
An optional Model RC-1 Retard
Chamber is required for installations
subject to variable pressures. It is used
to help prevent false alarms associated
with pressure variations in public water
supplies.
The Model AV-1-300 Alarm Check
Valve Trim includes pressure gauges
to monitor system pressure conditions,
a by-pass check valve, a main drain
valve, and an alarm test valve. The
bypass check valve reduces the
possibility of false alarms by permitting
slow as well as small transient
increases in water supply pressure
through the system without opening Nominal
Groove x Groove Flange x Groove Flange x Flange
the waterway clapper. Valve Size

NOTICE DN65
76,1 mm 10,0 Kg 12,7 Kg N/A
The TYCO Model AV-1-300 Alarm
Check Valves and TYCO Model RC-1 DN100
17,2 Kg 21,3 Kg 25,9 Kg
Retard Chamber described herein 114,3 mm
must be installed and maintained in
compliance with this document as well DN150
26,3 Kg 31,8 Kg 38,1 Kg
as the standards recognized by the 165,1 mm
Approval agency, in addition to any DN150
other authorities having jurisdiction. 26,3 Kg 31,8 Kg 38,1 Kg
168,3 mm
Failure to do so may impair the
performance of these devices. DN200
46,3 Kg 54,4 Kg 67,6 Kg
219,1 mm
The owner is responsible for
maintaining their fire protection system TABLE A
and devices in proper operating AVAILABLE VALVE END CONNECTIONS
condition. The installing contractor or AND WEIGHTS
manufacturer should be contacted with
any questions.

Page 1 of 24 DECEMBER 2013 TFP990

/40/
TFP990
Page 2 of 24

VALVE PARTS VALVE PARTS REPLACEMENT PARTS

AV-1 DATASHEET
NO. DESCRIPTION QTY. REF. NO. DESCRIPTION QTY. REF. NO. DESCRIPTION P/N
1 Valve Body . . . . . . . 1 NR 12 Handhole Cover (a) Repair Parts Kit,
2 Handhole Cover . . . 1 NR Hex Bolt, Includes 3 & 6
3 Handhole Cover DN65 Valve, DN65 Valve . . . . . . . . . 92-200-1-216
Gasket . . . . . . . . . . 1 See (a) 1/2-13 UNC-2A DN100 Valve . . . . . . . . 92-200-1-416
4 Seat Ring . . . . . . . . 1 NR x 1-1/4" Long . . . . . 4 CH DN150 Valve . . . . . . . . 92-200-1-620
5 Clapper . . . . . . . . . . 1 See (b) DN100 Valve, DN200 Valve . . . . . . . . 92-200-1-816
6 Clapper Facing . . . . 1 See (a) or (b) 1/2-13 UNC-2A (b) Clapper Assembly,
7 Clapper Washer . . . 1 See (b) x 1-3/4" Long . . . . . 4 CH Includes 5-9, 11
8 Lock Nut, DN150 Valve, DN65 Valve . . . . . . . . . 92-200-1-218
DN65 Valve . . . . . . 1 See (b) 1/2-13 UNC-2A Includes 5-11
Self-Locking Hex x 1-3/4" Long . . . . . 6 CH DN100 Valve . . . . . . . . 92-200-1-423
Cap Screw, DN100, DN200 Valve, DN150 Valve . . . . . . . . 92-200-1-623
150 & 200 Valves . . 1 See (b) 3/4-10 UNC-2A DN200 Valve . . . . . . . . 92-200-1-823
9 Clapper Hinge Pin. . 1 See (b) x 2" Long. . . . . . . . . 6 CH
10 Clapper Hinge 13 Clapper Hinge Pin NOTES:
Pin Bushing, Square Head Pipe 1. F x F valve shown for reference;
DN65 Valve . . . . . . 2 NR Plug, 3/8" NPT, components for G x G and F x G
DN100, 150 & 200 DN100, 150 & 200 valves are shared.
Valves . . . . . . . . . . . 4 NR Valves only . . . . . . . 1 CH 2. NR: Not Replaceable
11 Clapper Spring . . . . 1 See (b) 3. CH: Common Hardware

1
11
11

5
5

10
6
10
7
8 9 13
CLAPPER
ASSEMBLY 6 10
DN65 7 4
VALVE
8
CLAPPER
ASSEMBLY 2
3
DN100, 150 & 200
VALVES 12

FIGURE 3
DN65, DN100, DN150, & DN200 MODEL AV-1-300 ALARM VALVE
ASSEMBLY

225 mm
(GxG, FxG)

305 mm 356 mm
254 mm (FxF, FxG) FxF, FxG
(FxF, FxG) 311 mm or GxG
260 mm (GxG)
(GxG)

DN65 DN100 DN150 DN200

FIGURE 4
DN65, DN100, DN150, & DN200 MODEL AV-1-300 ALARM VALVE
TAKE-OUT DIMENSIONS

/41/
TFP990
Page 3 of 24

Technical the Model AV-1-300 Alarm Valve.


Each package of trim includes the
a successive transient surge in supply
pressure.
AV-1 DATASHEET

Data following items:

Sizes
Water Supply Pressure Gauge Design
DN65, DN100, DN150, and DN200 System Pressure Gauge
Main Drain / Alarm Test Valve
Criteria
Approvals Bypass Check Valve In planning the installation of the
The TYCO Model AV-1-300 Alarm TYCO Model AV-1-300 Alarm Valve,
Valves DN65, DN100, DN150, and Automatic Drain Valve consideration must be given to the
DN200 (European Conformity) with Waterflow Pressure Alarm Switch disposal of the large quantities of water
or without the Model RC-1 Retard that may be associated with draining
Retard Chamber, as applicable the system or performing a flow test.
Chamber are FM, VdS, and LPCB
Approved as with European Conformity The sprinkler system designer must
Valve Trim. Refer to Figures 5A through
12A.
Operating be aware that the configuration of the
piping network and its tendency to trap
For more information on LPCB Principles pockets of air (such as in the case of a
peaked-roof gridded system) can affect
Approval, contact Tyco Fire Protection When the fire protection system is
Products at the following office: initially being pressurized, water will the performance of the alarm system.
flow into the system until the water Although a slight amount of trapped
Kopersteden 1 air is desirable to prevent significant
7547 TJ Enschede supply and system pressure become
equalized, and the Spring closes the pressure increases due to thermally
The Netherlands Clapper in the Alarm Valve. Once the induced expansion of the water, a large
Tel: +31-(0)53-428-4444 pressures have stabilized, the Alarm quantity of trapped air in a system may
Fax: +31-(0)53-428-3377 Valve is in service and the centrally result in the possibility of an intermittent
located groove in the Seat Ring is alarm.
Alarm Valve sealed. Consequently, with the Alarm
The DN65, DN100, DN150, and DN200, The possibility of an intermittent alarm
Check Valve set for service, there is condition is a consequence of the fact
Model AV-1-300 Valves with European no flow through the alarm port to the
Conformity Valve Trim are for vertical that the flow out of the system through
alarm devices (that is, water motor the test valve or a single sprinkler is
installations (flow going up), and they alarm and/or pressure alarm switch).
are rated for use at a maximum service very small relative to the flow that can
When there is a steady flow of water be passed through the valve. This
pressure of 16 bar. Nominal pressure
into the sprinkler system due to a difference increases with valve size. If
loss versus flow is shown in Figure 1, the system were free of trapped air, flow
and the valve take-out dimensions are sprinkler operation, the Clapper opens
as shown in Figure 2. Water is then in would equal flow out and the Clapper
shown in Figure 4. permitted to flow into the centrally would always stabilize at some open
Flanged connections are drilled per located groove in the Seat Ring and position (as needed to accommodate
ISO 2084 (PN10/16) or ANSI B16.1 out through the alarm port towards the the required flow). With trapped air
(Class 125). Refer to Table B. Grooved Automatic Drain Valve. When the flow in the system, however, the Clapper
connections, as applicable, are cut from the alarm port exceeds the drain first opens wider since the system
in accordance with standard groove capacity of the Automatic Drain Valve, initially demands greater flow until the
specifications for steel pipe. They are the Retard Chamber (where provided air pockets are compressed (back to
suitable for use with grooved end pipe in the case of systems with variable nearly the supply pressure), and then
couplings listed or approved for fire pressure), begins to fill as a function it will tend to return closer to the Seat
of the amount of water that can pass
protection system service. through the Restriction. Subsequently, Ring. If the volume of the air pockets
the water motor alarm and/or the is excessive, flow into the system can
Threaded port connections are per
pressure alarm switch will be actuated. be momentarily reduced to nearly zero
ISO 7/1 to readily accept the trim
The alarms will continue to actuate (once the air pockets are compressed)
arrangements detailed in Figures 5A
as long as the Clapper remains and the Clapper may close, causing
through 12A.
opened. Water in the alarm lines flow to the alarms to be shutoff.
Components of the Alarm Valve are will automatically drain out through Once the Clapper has closed, sufficient
shown in Figure 3. The body and Hand- the Automatic Drain Valve when the water must flow out of the system
Hole Cover are ductile iron. The Seat Clapper closes (due to discontinuation before the Clapper will again open.
Ring is bronze. The Clapper is ductile in the flow of water into the sprinkler
system). A repetition of the above described
iron. All valve sizes utilize an EPDM
condition is termed an intermittent
Clapper Facing. In the case of variable pressure alarm.
systems, slow as well as small transient
Retard Chamber increases in water supply pressure Using a vent (which can also serve
The Model RC-1 Retard Chamber is may continue to build up in the system as an end-of-line Inspectors Test
cast iron. (via the bypass check valve) without Connection) piped from the top of a
opening the Clapper. A transient surge cross main or end of a branch line at
Valve Trim in supply pressure which is sufficient the point most remote from the alarm
The Valve Trim is illustrated in Figures valve, and filling the system slowly in
5A through 12A. The Valve Trim forms to only momentarily open the Clapper
a part of the laboratory approval of the will not cause a false alarm, and a
Model AV-1-300 Alarm Valve and is portion of the increase in pressure will
necessary for the proper operation of be trapped within the system, thus
reducing the possibility of another
opening. Any water in the alarm line is
automatically drained, further reducing
the possibility of a false alarm due to

/42/
TFP990
Page 4 of 24

AV-1 DATASHEET
Nominal Dimensions in millimeters
Nominal
Valve ANSI B16.1 ISO 2084 ISO 2084
Size (Class 125) 1 (PN10) 2 (PN16) 3
Dim. Dim. Qty. Dim. Dim. Qty. Dim. Dim. Qty.
A B N A B N A B N
DN65 139,7 19,0 4 145,0 18,0 4
USE
DN100 190,5 19,0 8 ISO 2084 180,0) 18,0 8
(PN16)
DN150 241,3 22,2 8 240,0 22,0 8

DN200 298,5 22,2 8 295,0 22,0 8 295,0 22,0 12

1
Dim. A Same drilling as for B16.5 (Class 150)
Bolt Circle and B16.42 (Class 250).
Diameter 2
Same drilling as for BS 4504 Section 3.2 (PN10)
and DIN 2532 (PN10).
Dim. B 3
Bolt Hole Same drilling as for BS 4504 Section 3.2 (PN16)
Diameter and DIN 2532 (PN16).

Qty. N
Number of
Bolt Holes
TABLE B
FLANGE DRILLING SPECIFICATIONS

0,30
NOMINAL PRESSURE DROP IN BAR

0,20
100

150

0
65

20
DN

DN

DN

0,10 DN
0,09
0,08
0,07
0,06

0,05
400 600 1000 2000 3000 5000 7000 10000 15000
FLOW RATE IN LITRES PER MINUTE (LPM)

FIGURE 1
DN65, DN100, DN150, & DN200 MODEL AV-1-300 ALARM VALVE
NOMINAL PRESSURE LOSS VERSUS FLOW

/43/
TFP990
Page 5 of 24

WATERFLOW
AV-1 DATASHEET

PRESSURE
ALARM SWITCH
4
ONCE RETARD
CHAMBER FILLS,
WATERFLOW PRESSURE
ALARM SWITCH AND
RETARD WATER MOTOR
CHAMBER ALARM ACTUATE
WATERFLOW
TO WATER 1
MOTOR ALARM
UPON SPRINKLER
FLOW, WATERWAY SYSTEM
CLAPPER OPENS PRESSURE
GAUGE
WATERFLOW
ALARM LINE
TO SYSTEM
STRAINER
RESTRICTION

BY-PASS
AUTOMATIC CHECK
DRAIN VALVE VALVE

3
WHEN FLOW
EXCEEDS DRAIN SUPPLY
CAPACITY, RETARD PRESSURE
CHAMBER BEGINS GAUGE
TO FILL MAIN DRAIN/ 2
ALARM TEST WATERFLOW
VALVE THROUGH SEAT
RING GROOVE AND
ALARM PORT

FIGURE 2
DN65, DN100, DN150, & DN200 MODEL AV-1-300 ALARM VALVE
OPERATION

accordance with the steps described readily visible area. Step 5. Install the check valve in the
in the Valve Setting Procedure section, Wet pipe fire protection systems externally mounted bypass around
can prevent an excessive amount of air the waterway clapper with its arrow
must be maintained at a minimum
from being trapped. pointed up.
temperature of 4C.
Step 6. It is recommended that a vent
Installation Step 1. When trimming valves in the
field (that is, other than valves provided connection, which may also be used
as an end-of-line Inspectors Test
with factory assembled trim), verify all
General Instructions nipples, fittings, and devices are clean Connection, be piped from a cross
Proper operation of the TYCO Model and free of scale and burrs before main or branch line at the point most
AV-1-300 Alarm Valves depends upon installation. Use pipe-thread sealant remote from the alarm valve. Connect
its trim being installed in accordance sparingly on male pipe threads only. the vent line to the top of a cross main
with Figures 5A through 12A, as or to the end of a branch line. Position
applicable. Failure to follow the Step 2. Plug unused alarm the vent line at the highest level of a
appropriate trim diagram may prevent connections. multi-level installation.
the valve from functioning, may void Step 3. Ensure suitable disposal of The vent connection can be used
the Manufacturers Warranty, and will alarm line and system drainage water. to bleed-off excessive air from the
void listings and approvals. Direct drainage water so that it will not system, and therefore, minimize the
The Alarm Valves must be installed in cause damage or result in dangerous possibility of a false alarm due to a
readily visible and accessible locations. conditions. transient surge in supply pressure. The
contraction/expansion associated with
It is recommended that provision be Step 4. Position the alarm line drain so
an excessive amount of trapped air
made for viewing the alarm line drain that there will be no danger of freezing.
could also cause the waterway Clapper
water by locating the drain outlet in a to cycle open and shut during an

/44/
TFP990
Page 6 of 24

NO. DESCRIPTION QTY.

AV-1 DATASHEET
1 AP80D2; Pipe Nipple, 1/2" x 80mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 AP60D2; Pipe Nipple, 1/2" x 60mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3 AP100H2; Pipe Nipple, 1-1/2" x 100mm Galvanized Steel. . . . . . . . . . . . . . . . . . . . . . . 1
4 AP100D2; Pipe Nipple, 1/2" x 100mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 1
5 A92D2; Elbow 90 M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
6 A41H2; Elbow 45 F x F 1-1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
7 A341D2; Union M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
8 A290B2; Plug Male 1/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
9 A280D2; Nipple Male 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
10 A246IH2; Nipple F x M 2" x 1-1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
11 A246ED2; Nipple F x M 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
12 A241IH2; Nipple M x F 2" x 1-1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
13 A241DB2; Nipple M x F 1/2" x 1/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
14 A134D2; Tee M x F x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
15 A133D2; Tee M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
16 A130RDBD2; Reducing Tee Female 1/2" x 1/4" x 1/2" BSP Galvanized . . . . . . . . . . . . 1
17 A130D2; Tee Female 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
18 700487; Test and Drain Valve 2" NPT Inlet x 2" BSP Outlet x 1/2" Test Facility . . . . . . 1
19 59304FO; Ball Valve DN15-1/2" ISO 7/1 Full Bore PN40 Venthole Threaded M5 . . . . . 2 PRE-TRIMMED
20 522034120; Alarm Valve Model AV-1-300 2-1/2"/76,1mm G x G . . . . . . . . . . . . . . . . . . 1 VALVE ASSEMBLY
21 460491004D; Check Valve, Swing Type, 1/2" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
22 406012; Elbow WES 3mm x M5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
23 2162156; Self-Closing Drain Valve 1/2" Brass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
24 1610000210; Ball Valve, DN15 - 1/2" BSP Full Bore . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
25 0260; Pressure Switch Model PS10-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
26 025500013; Water Pressure Gauge 300 psi / 21 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
27 Pressure Relief Hose 3 x 6 x 0,6m Transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

26

13
22

19
27

14
9
2 9
15 8
25
11 21
16
24 1
5 26
4 5
7
14 22
13
2
23 27
17 19
7
1
20 2
10 5
18
12
3
6

FIGURE 5A
DN65 MODEL AV-1-300 ALARM VALVE
TRIM ARRANGEMENT WITHOUT MODEL RC-1 RETARD CHAMBER

/45/
TFP990
Page 7 of 24

NO. DESCRIPTION QTY.


AV-1 DATASHEET

1 AP90D2; Pipe Nipple, 1/2" x 90mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1


2 AP80D2; Pipe Nipple, 1/2" x 80mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3 AP60D2; Pipe Nipple, 1/2" x 60mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 2
4 AP100H2; Pipe Nipple, 1-1/2" x 100mm Galvanized Steel. . . . . . . . . . . . . . . . . . . . . . . 1
5 A92D2; Elbow 90 M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
6 A41H2; Elbow 45 F x F 1-1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
7 A341D2; Union M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
8 A290B2; Plug Male 1/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
9 A280D2; Nipple Male 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
10 A270D2; Nipple Female 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
11 A246IH2; Nipple F x M 2" x 1-1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
12 A246ED2; Nipple F x M 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
13 A241IH2; Nipple M x F 2" x 1-1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
14 A241DB2; Nipple M x F 1/2" x 1/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
15 A134D2; Tee M x F x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
16 A133D2; Tee M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
17 A130RDBD2; Reducing Tee Female 1/2" x 1/4" x 1/2" BSP Galvanized . . . . . . . . . . . . 1
18 A130D2; Tee Female 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRE-TRIMMED
19 700487; Test and Drain Valve 2" NPT Inlet x 2" BSP Outlet x 1/2" Test Facility . . . . . . 1 VALVE ASSEMBLY
20 59304FO; Ball Valve DN15-1/2" ISO 7/1 Full Bore PN40 Venthole Threaded M5 . . . . . 2
21 522034120; Alarm Valve Model AV-1-300 2-1/2"/76,1mm G x G . . . . . . . . . . . . . . . . . . 1 (SHOWN WITH
22 460491004D; Check Valve, Swing Type, 1/2" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 SEPARATELY ORDERED
23 406012; Elbow WES 3mm x M5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 SUPERVISORY SWITCH)
24 2162156; Self-Closing Drain Valve 1/2" Brass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
25 1610000210; Ball Valve, DN15 - 1/2" BSP Full Bore . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
26 0260; Pressure Switch Model PS10-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
27 025500013; Water Pressure Gauge 300 psi / 21 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
28 Pressure Relief Hose 3 x 6 x 0,6m Transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

27

14
POSITION 23
FOR
SUPERVISORY 20
26 12 28
SWITCH
7 (ORDERED
15
16 SEPARATELY) 9
5
9
10 8
10
22
9 17
15 25 2 27
5
7
1 23
24 14
3
28
18 20
7
2
21 3
11 5
19
13
4
6

FIGURE 5B
DN65 MODEL AV-1-300 ALARM VALVE
TRIM ARRANGEMENT WITHOUT MODEL RC-1 RETARD CHAMBER
(Suitable for Supervisory)

/46/
TFP990
Page 8 of 24

NO. DESCRIPTION QTY.

AV-1 DATASHEET
1 AP80D2; Pipe Nipple, 1/2" x 80mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 AP60D2; Pipe Nipple, 1/2" x 60mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3 AP160D2; Pipe Nipple, 1/2" x 160mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 1
4 AP100H2; Pipe Nipple, 1-1/2" x 100mm Galvanized Steel. . . . . . . . . . . . . . . . . . . . . . . 1
5 A92D2; Elbow 90 M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
6 A41H2; Elbow 45 F x F 1-1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
7 A341D2; Union M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
8 A290B2; Plug Male 1/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
9 A280E2; Nipple Male 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
10 A280D2; Nipple Male 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
11 A246IH2; Nipple F x M 2" x 1-1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
12 A246ED2; Nipple F x M 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
13 A241IH2; Nipple M x F 2" x 1-1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
14 A241DB2; Nipple M x F 1/2" x 1/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
15 A134D2; Tee M x F x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
16 A130RDED2; Reducing Tee Female 1/2" x 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . 1
17 A130RDBD2; Reducing Tee Female 1/2" x 1/4" x 1/2" BSP Galvanized . . . . . . . . . . . . 1
18 A130D2; Tee Female 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
19 700487; Test and Drain Valve 2" NPT Inlet x 2" BSP Outlet x 1/2" Test Facility . . . . . . 1
20 700484; Nipple M x F 1/2" x 3,56mm Orifice x 45,5mm . . . . . . . . . . . . . . . . . . . . . . . . . 1
21 59304FO; Ball Valve DN15-1/2" ISO 7/1 Full Bore PN40 Venthole Threaded M5 . . . . . 1
22 522111002; Retarding Chamber RC-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
23 522034120; Alarm Valve Model AV-1-300 2-1/2"/76,1mm G x G . . . . . . . . . . . . . . . . . . 1
24 460491004D; Check Valve, Swing Type, 1/2" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
25 406012; Elbow WES 3mm x M5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
PRE-TRIMMED
26 305003; Strainer 1/2" Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 VALVE ASSEMBLY
27 2162156; Self-Closing Drain Valve 1/2" Brass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
28 1610000210; Ball Valve DN15-1/2" BSP Full Bore . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
29 0260; Pressure Switch Model PS10-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
30 025500013; Water Pressure Gauge 300 psi / 21 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
31 Pressure Relief Hose 3 x 6 x 0,6m Transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2
29
12 30
5 28
16 14
25
9
21
31
22
15
10
7
10
3 8
24
17
20 10
1 30
26 5
7
15 10 25
14
2
27 31
11 18 21
19 7
13 1
4 23 2
6 5

FIGURE 6A
DN65 MODEL AV-1-300 ALARM VALVE
TRIM ARRANGEMENT WITH MODEL RC-1 RETARD CHAMBER

/47/
TFP990
Page 9 of 24

NO. DESCRIPTION QTY.


AV-1 DATASHEET

1 WS00000004; Pressure Relief Hose 3 x 6 x 1,2m Transparent . . . . . . . . . . . . . . . . . . . 1


2 AP80D2; Pipe Nipple, 1/2" x 80mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3 AP60D2; Pipe Nipple, 1/2" x 60mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1
4 AP100H2; Pipe Nipple, 1-1/2" x 100mm Galvanized Steel. . . . . . . . . . . . . . . . . . . . . . . 1
5 AP100D2; Pipe Nipple, 1/2" x 100mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 1
6 A92D2; Elbow 90 M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
7 A41H2; Elbow 45 F x F 1-1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
8 A341D2; Union M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
9 A290B2; Plug Male 1/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
10 A280E2; Nipple Male 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
11 A280D2; Nipple Male 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
12 A246IH2; Nipple F x M 2" x 1-1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
13 A246ED2; Nipple F x M 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
14 A241IH2; Nipple M x F 2" x 1-1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
15 A241DB2; Nipple M x F 1/2" x 1/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
16 A134D2; Tee M x F x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
17 A130RDED2; Reducing Tee Female 1/2" x 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . 1
18 A130RDBD2; Reducing Tee Female 1/2" x 1/4" x 1/2" BSP Galvanized . . . . . . . . . . . . 1
19 A130D2; Tee Female 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
20 700487; Test and Drain Valve 2" NPT Inlet x 2" BSP Outlet x 1/2" Test Facility . . . . . . 1
21 700484; Nipple M x F 1/2" x 3,56mm Orifice x 45,5mm . . . . . . . . . . . . . . . . . . . . . . . . . 1
22 59304FO; Ball Valve DN15-1/2" ISO 7/1 Full Bore PN40 Venthole Threaded M5 . . . . . 1
23 522111002; Retarding Chamber RC-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
24 522034120; Alarm Valve Model AV-1-300 2-1/2"/76,1mm G x G . . . . . . . . . . . . . . . . . . 1
PRE-TRIMMED
25 460491004D; Check Valve, Swing Type, 1/2" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 VALVE ASSEMBLY
26 406012; Elbow WES 3mm x M5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 (SHOWN WITH
27 305003; Strainer 1/2" Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 SEPARATELY ORDERED
28 2162156; Self-Closing Drain Valve 1/2" Brass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
29 0260; Pressure Switch Model PS10-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 SUPERVISORY SWITCH)
30 025500013; Water Pressure Gauge 300 psi / 21 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
31 Pressure Relief Hose 3 x 6 x 0,6m Transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

29
8

6 13
17
10 30

23 15
26
POSITION
8 FOR 22
SUPERVISORY 31
SWITCH
5
(ORDERED 16
11
SEPARATELY)
26
11
22 9
1 11 25
18
16
3 2 30
27 6
8
11 26
21 28 15
3
31
12 19 22
20 8
14 2
4 24 3
7 6

FIGURE 6B
DN65 MODEL AV-1-300 ALARM VALVE
TRIM ARRANGEMENT WITH MODEL RC-1 RETARD CHAMBER
(Suitable for Supervisory)

/48/
TFP990
Page 10 of 24

NO. DESCRIPTION QTY.

AV-1 DATASHEET
1 AP90D2; Pipe Nipple, 1/2" x 90mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 AP60D2; Pipe Nipple, 1/2" x 60mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3 AP200I2; Pipe Nipple, 2" x 200mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1
4 AP120D2; Pipe Nipple, 1/2" x 120mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 2
5 A92D2; Elbow 90 M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
6 A341D2; Union M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
7 A291D2; Plug Male 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
8 A246ED2; Nipple F x M 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
9 A241DB2; Nipple M x F 1/2" x 1/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
10 A134D2; Tee M x F x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
11 A133D2; Tee M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
12 A120I2; Elbow 45 F x F 2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
13 700487; Test and Drain Valve 2" NPT Inlet x 2" BSP Outlet x 1/2" Test Facility . . . . . . 1
14 59304FO; Ball Valve DN15-1/2" ISO 7/1 Full Bore PN40 Venthole Threaded M5 . . . . . 2
15 522031923; Alarm Valve Model AV-1-300 4"/114,3mm G x G . . . . . . . . . . . . . . . . . . . . 1
16 460491004D; Check Valve, Swing Type, 1/2" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
17 406012; Elbow WES 3mm x M5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 PRE-TRIMMED
18 2162156; Self-Closing Drain Valve 1/2" Brass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 VALVE ASSEMBLY
19 1610000210; Ball Valve, DN15 - 1/2" BSP Full Bore . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
20 0260; Pressure Switch Model PS10-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
21 025500013; Water Pressure Gauge 300 psi / 21 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
22 Pressure Relief Hose 3 x 6 x 0,6m Transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

21 2 21
11
17 9 20 17
8 9
19
22 14 5 22
10 14
4
10 1 18 7
5
4 6
1
5
16 6 6 2
15
13
3
12

FIGURE 7A
DN100 MODEL AV-1-300 ALARM VALVE
TRIM ARRANGEMENT WITHOUT MODEL RC-1 RETARD CHAMBER

/49/
TFP990
Page 11 of 24

NO. DESCRIPTION QTY.


AV-1 DATASHEET

1 AP90D2; Pipe Nipple, 1/2" x 90mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1


2 AP80D2; Pipe Nipple, 1/2" x 80mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3 AP60D2; Pipe Nipple, 1/2" x 60mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1
4 AP200I2; Pipe Nipple, 2" x 200mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1
5 AP120D2; Pipe Nipple, 1/2" x 120mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 1
6 A92D2; Elbow 90 M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
7 A341D2; Union M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
8 A291D2; Plug Male 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
9 A280D2; Nipple Male 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
10 A270D2; Nipple Female 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
11 A246ED2; Nipple F x M 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
12 A241DB2; Nipple M x F 1/2" x 1/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
13 A134D2; Tee M x F x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
14 A133D2; Tee M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
15 A120I2; Elbow 45 F x F 2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
16 700487; Test and Drain Valve 2" NPT Inlet x 2" BSP Outlet x 1/2" Test Facility . . . . . . 1 PRE-TRIMMED
17 59304FO; Ball Valve DN15-1/2" ISO 7/1 Full Bore PN40 Venthole Threaded M5 . . . . . 2
18 522031923; Alarm Valve Model AV-1-300 4"/114,3mm G x G . . . . . . . . . . . . . . . . . . . . 1
VALVE ASSEMBLY
19 460491004D; Check Valve, Swing Type, 1/2" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 (SHOWN WITH
20 406012; Elbow WES 3mm x M5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 SEPARATELY ORDERED
21 2162156; Self-Closing Drain Valve 1/2" Brass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 SUPERVISORY SWITCH)
22 1610000210; Ball Valve, DN15 - 1/2" BSP Full Bore . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
23 0260; Pressure Switch Model PS10-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
24 025500013; Water Pressure Gauge 300 psi / 21 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
25 Pressure Relief Hose 3 x 6 x 0,6m Transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

23 11
7 POSITION
14 FOR
24 6 SUPERVISORY
SWITCH 24
10
20 (ORDERED 20
12 2 SEPARATELY) 12
9
25 17 13 22 25
17
13 1 8
1 21
6
5 7
2
6
19 7 7 3
18
16
4
15

FIGURE 7B
DN100 MODEL AV-1-300 ALARM VALVE
TRIM ARRANGEMENT WITHOUT MODEL RC-1 RETARD CHAMBER
(Suitable for Supervisory)

/50/
TFP990
Page 12 of 24

NO. DESCRIPTION QTY.

AV-1 DATASHEET
1 AP90D2; Pipe Nipple, 1/2" x 90mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 AP60D2; Pipe Nipple, 1/2" x 60mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3 AP200I2; Pipe Nipple, 2" x 200mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1
4 AP200D2; Pipe Nipple, 1/2" x 200mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 1
5 AP120D2; Pipe Nipple, 1/2" x 120mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 1
6 A92D2; Elbow 90 M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
7 A341D2; Union M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
8 A291D2; Plug Male 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
9 A280E2; Nipple Male 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
10 A280D2; Nipple Male 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
11 A246ED2; Nipple F x M 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
12 A241DB2; Nipple M x F 1/2" x 1/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
13 A134D2; Tee M x F x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
14 A130RDED2; Reducing Tee Female 1/2" x 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . 1
15 A120I2; Elbow 45 F x F 2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
16 700487; Test and Drain Valve 2" NPT Inlet x 2" BSP Outlet x 1/2" Test Facility . . . . . . 1
17 700484; Nipple M x F 1/2" x 3,56mm Orifice x 45,5mm . . . . . . . . . . . . . . . . . . . . . . . . . 1
18 59304FO; Ball Valve DN15-1/2" ISO 7/1 Full Bore PN40 Venthole Threaded M5 . . . . . 2
19 522111002; Retarding Chamber RC-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
20 522031923; Alarm Valve Model AV-1-300 4"/114,3mm G x G . . . . . . . . . . . . . . . . . . . . 1
21 460491004D; Check Valve, Swing Type, 1/2" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
22 406012; Elbow WES 3mm x M5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
23 305003; Strainer 1/2" Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRE-TRIMMED
24 2162156; Self-Closing Drain Valve 1/2" Brass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
25 1610000210; Ball Valve DN15-1/2" BSP Full Bore . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
VALVE ASSEMBLY
26 0260; Pressure Switch Model PS10-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
27 025500013; Water Pressure Gauge 300 psi / 21 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
28 Pressure Relief Hose 3 x 6 x 0,6m Transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

26
11
25
6
14

9 19

27 4 27
22 12 17 22
12
10
28 18 13 28
23 18
10
13 1 24 8
6
5 7
1
6
21 7 7 2
20
16
3
15

FIGURE 8A
DN100 MODEL AV-1-300 ALARM VALVE
TRIM ARRANGEMENT WITH MODEL RC-1 RETARD CHAMBER

/51/
TFP990
Page 13 of 24

NO. DESCRIPTION QTY.


AV-1 DATASHEET

1 WS00000004; Pressure Relief Hose 3 x 6 x 1,2m Transparent . . . . . . . . . . . . . . . . . . . 1


2 AP90D2; Pipe Nipple, 1/2" x 90mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3 AP60D2; Pipe Nipple, 1/2" x 60mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1
4 AP200I2; Pipe Nipple, 2" x 200mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1
5 AP120D2; Pipe Nipple, 1/2" x 120mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 1
6 A92D2; Elbow 90 M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
7 A341D2; Union M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
8 A291D2; Plug Male 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
9 A280E2; Nipple Male 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
10 A280D2; Nipple Male 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
11 A246ED2; Nipple F x M 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
12 A241DB2; Nipple M x F 1/2" x 1/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
13 A134D2; Tee M x F x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
14 A130RDED2; Reducing Tee Female 1/2" x 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . 1
15 A120I2; Elbow 45 F x F 2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
16 700487; Test and Drain Valve 2" NPT Inlet x 2" BSP Outlet x 1/2" Test Facility . . . . . . 1
17 700484; Nipple M x F 1/2" x 3,56mm Orifice x 45,5mm . . . . . . . . . . . . . . . . . . . . . . . . . 1
18 59304FO; Ball Valve DN15-1/2" ISO 7/1 Full Bore PN40 Venthole Threaded M5 . . . . . 1
19 522111002; Retarding Chamber RC-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
20 522031923; Alarm Valve Model AV-1-300 4"/114,3mm G x G . . . . . . . . . . . . . . . . . . . . 1
21 460491004D; Check Valve, Swing Type, 1/2" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRE-TRIMMED
22 406012; Elbow WES 3mm x M5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 VALVE ASSEMBLY
23 305003; Strainer 1/2" Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
24 2162156; Self-Closing Drain Valve 1/2" Brass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 (SHOWN WITH
25 0260; Pressure Switch Model PS10-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 SEPARATELY ORDERED
26 025500013; Water Pressure Gauge 300 psi / 21 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 SUPERVISORY SWITCH)
27 Pressure Relief Hose 3 x 6 x 0,6m Transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

25
7

6 11
14
9

19
POSITION
7 FOR
SUPERVISORY
SWITCH
5
(ORDERED
SEPARATELY)
26 22 26
18
22 12 1 22
10 12
13
27 18 3 27
23 18
10
13 2 17 24 8
6
5 7
2
6
21 7 7 3
20
16
4
15

FIGURE 8B
DN100 MODEL AV-1-300 ALARM VALVE
TRIM ARRANGEMENT WITH MODEL RC-1 RETARD CHAMBER
(Suitable for Supervisory)

/52/
TFP990
Page 14 of 24

NO. DESCRIPTION QTY.

AV-1 DATASHEET
1 AP90D2; Pipe Nipple, 1/2" x 90mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 AP60D2; Pipe Nipple, 1/2" x 60mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3 AP200I2; Pipe Nipple, 2" x 200mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1
4 AP120D2; Pipe Nipple, 1/2" x 120mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 2
5 A92D2; Elbow 90 M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
6 A341D2; Union M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
7 A291D2; Plug Male 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
8 A246ED2; Nipple F x M 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
9 A241DB2; Nipple M x F 1/2" x 1/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
10 A134D2; Tee M x F x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
11 A133D2; Tee M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
12 A120I2; Elbow 45 F x F 2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
13 700487; Test and Drain Valve 2" NPT Inlet x 2" BSP Outlet x 1/2" Test Facility . . . . . . 1
14 59304FO; Ball Valve DN15-1/2" ISO 7/1 Full Bore PN40 Venthole Threaded M5 . . . . . 2
15 522031925; Alarm Valve Model AV-1-300 6"/168,3mm G x G . . . . . . . . . . . . . . . . . . . . 1
16 460491004D; Check Valve, Swing Type, 1/2" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
17 406012; Elbow WES 3mm x M5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 PRE-TRIMMED
18 2162156; Self-Closing Drain Valve 1/2" Brass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
19 1610000210; Ball Valve, DN15 - 1/2" BSP Full Bore . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
VALVE ASSEMBLY
20 0260; Pressure Switch Model PS10-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
21 025500013; Water Pressure Gauge 300 psi / 21 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
22 Pressure Relief Hose 3 x 6 x 0,6m Transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

21 2 21
11
17 9 20 17
8 9
19
22 14 5 22
10 14
4
10 1 18 7
5
4 6
1
5
16 6 6 2
15
13
3
12

FIGURE 9A
DN150 MODEL AV-1-300 ALARM VALVE
TRIM ARRANGEMENT WITHOUT MODEL RC-1 RETARD CHAMBER

/53/
TFP990
Page 15 of 24

NO. DESCRIPTION QTY.


AV-1 DATASHEET

1 AP90D2; Pipe Nipple, 1/2" x 90mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1


2 AP80D2; Pipe Nipple, 1/2" x 80mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3 AP60D2; Pipe Nipple, 1/2" x 60mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1
4 AP200I2; Pipe Nipple, 2" x 200mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1
5 AP120D2; Pipe Nipple, 1/2" x 120mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 1
6 A92D2; Elbow 90 M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
7 A341D2; Union M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
8 A291D2; Plug Male 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
9 A280D2; Nipple Male 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
10 A270D2; Nipple Female 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
11 A246ED2; Nipple F x M 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
12 A241DB2; Nipple M x F 1/2" x 1/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
13 A134D2; Tee M x F x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
14 A133D2; Tee M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
15 A120I2; Elbow 45 F x F 2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
16 700487; Test and Drain Valve 2" NPT Inlet x 2" BSP Outlet x 1/2" Test Facility . . . . . . 1
17 59304FO; Ball Valve DN15-1/2" ISO 7/1 Full Bore PN40 Venthole Threaded M5 . . . . . 2 PRE-TRIMMED
18 522031925; Alarm Valve Model AV-1-300 6"/168,3mm G x G . . . . . . . . . . . . . . . . . . . . 1 VALVE ASSEMBLY
19 460491004D; Check Valve, Swing Type, 1/2" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 (SHOWN WITH
20 406012; Elbow WES 3mm x M5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
21 2162156; Self-Closing Drain Valve 1/2" Brass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 SEPARATELY ORDERED
22 1610000210; Ball Valve, DN15 - 1/2" BSP Full Bore . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 SUPERVISORY SWITCH)
23 0260; Pressure Switch Model PS10-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
24 025500013; Water Pressure Gauge 300 psi / 21 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
25 Pressure Relief Hose 3 x 6 x 0,6m Transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

23 11
7 POSITION
14 FOR
24 6 SUPERVISORY
SWITCH 24
10
20 (ORDERED 20
12 2 SEPARATELY) 12
9
25 17 13 22 25
17
13 1 8
1 21
6
5 7
2
6
19 7 7 3
18
16
4
15

FIGURE 9B
DN150 MODEL AV-1-300 ALARM VALVE
TRIM ARRANGEMENT WITHOUT MODEL RC-1 RETARD CHAMBER
(Suitable for Supervisory)

/54/
TFP990
Page 16 of 24

NO. DESCRIPTION QTY.

AV-1 DATASHEET
1 AP90D2; Pipe Nipple, 1/2" x 90mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . .2
2 AP60D2; Pipe Nipple, 1/2" x 60mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . .2
3 AP200I2; Pipe Nipple, 2" x 200mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . .1
4 AP200D2; Pipe Nipple, 1/2" x 200mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . .1
5 AP120D2; Pipe Nipple, 1/2" x 120mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . .1
6 A92D2; Elbow 90 M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
7 A341D2; Union M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
8 A291D2; Plug Male 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
9 A280E2; Nipple Male 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
10 A280D2; Nipple Male 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
11 A246ED2; Nipple F x M 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . .1
12 A241DB2; Nipple M x F 1/2" x 1/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . .2
13 A134D2; Tee M x F x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
14 A130RDED2; Reducing Tee Female 1/2" x 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . .1
15 A120I2; Elbow 45 F x F 2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
16 700487; Test and Drain Valve 2" NPT Inlet x 2" BSP Outlet x 1/2" Test Facility . . . . . .1
17 700484; Nipple M x F 1/2" x 3,56mm Orifice x 45,5mm . . . . . . . . . . . . . . . . . . . . . . . . .1
18 59304FO; Ball Valve DN15-1/2" ISO 7/1 Full Bore PN40 Venthole Threaded M5 . . . . .2
19 522111002; Retarding Chamber RC-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
20 522031925; Alarm Valve Model AV-1-300 6"/168,3mm G x G . . . . . . . . . . . . . . . . . . . .1
21 460491004D; Check Valve, Swing Type, 1/2" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
22 406012; Elbow WES 3mm x M5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
23 305003; Strainer 1/2" Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
24 2162156; Self-Closing Drain Valve 1/2" Brass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 PRE-TRIMMED
25 1610000210; Ball Valve DN15-1/2" BSP Full Bore . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 VALVE ASSEMBLY
26 0260; Pressure Switch Model PS10-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
27 025500013; Water Pressure Gauge 300 psi / 21 bar . . . . . . . . . . . . . . . . . . . . . . . . . . .2
28 Pressure Relief Hose 3 x 6 x 0,6m Transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

26
11
25
6
14

9 19

27 4 27
22 12 17 22
12
10
28 18 13 28
23 18
10
13 1 24 8
6
5 7
1
6
21 7 7 2
20
16
3
15

FIGURE 10A
DN150 MODEL AV-1-300 ALARM VALVE
TRIM ARRANGEMENT WITH MODEL RC-1 RETARD CHAMBER

/55/
TFP990
Page 17 of 24

NO. DESCRIPTION QTY.


AV-1 DATASHEET

1 WS00000004; Pressure Relief Hose 3 x 6 x 1,2m Transparent . . . . . . . . . . . . . . . . . . . 1


2 AP90D2; Pipe Nipple, 1/2" x 90mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3 AP60D2; Pipe Nipple, 1/2" x 60mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1
4 AP200I2; Pipe Nipple, 2" x 200mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1
5 AP120D2; Pipe Nipple, 1/2" x 120mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 1
6 A92D2; Elbow 90 M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
7 A341D2; Union M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
8 A291D2; Plug Male 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
9 A280E2; Nipple Male 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
10 A280D2; Nipple Male 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
11 A246ED2; Nipple F x M 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
12 A241DB2; Nipple M x F 1/2" x 1/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
13 A134D2; Tee M x F x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
14 A130RDED2; Reducing Tee Female 1/2" x 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . 1
15 A120I2; Elbow 45 F x F 2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
16 700487; Test and Drain Valve 2" NPT Inlet x 2" BSP Outlet x 1/2" Test Facility . . . . . . 1
17 700484; Nipple M x F 1/2" x 3,56mm Orifice x 45,5mm . . . . . . . . . . . . . . . . . . . . . . . . . 1
18 59304FO; Ball Valve DN15-1/2" ISO 7/1 Full Bore PN40 Venthole Threaded M5 . . . . . 1
19 522111002; Retarding Chamber RC-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
20 522031925; Alarm Valve Model AV-1-300 6"/168,3mm G x G . . . . . . . . . . . . . . . . . . . . 1
21 460491004D; Check Valve, Swing Type, 1/2" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
22 406012; Elbow WES 3mm x M5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
PRE-TRIMMED
23 305003; Strainer 1/2" Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 VALVE ASSEMBLY
24 2162156; Self-Closing Drain Valve 1/2" Brass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 (SHOWN WITH
25 0260; Pressure Switch Model PS10-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 SEPARATELY ORDERED
26 025500013; Water Pressure Gauge 300 psi / 21 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
27 Pressure Relief Hose 3 x 6 x 0,6m Transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 SUPERVISORY SWITCH)

25
7

6 11
14
9

19
POSITION
7 FOR
SUPERVISORY
SWITCH
5
(ORDERED
SEPARATELY)
26 22 26
18
22 22
12 1 10 12
13
27 18 3 27
23 18
10
13 8
2 17 24
6
5 7
2
6
21 7 7 3
20
16
4
15

FIGURE10B
DN150 MODEL AV-1-300 ALARM VALVE
TRIM ARRANGEMENT WITH MODEL RC-1 RETARD CHAMBER
(Suitable for Supervisory)

/56/
TFP990
Page 18 of 24

NO. DESCRIPTION QTY.

AV-1 DATASHEET
1 AP60D2; Pipe Nipple, 1/2" x 60mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2 AP200I2; Pipe Nipple, 2" x 200mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3 AP160E2; Pipe Nipple, 3/4" x 160mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 1
4 AP120E2; Pipe Nipple, 3/4" x 120mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 1
5 AP120D2; Pipe Nipple, 1/2" x 120mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 1
6 AP110E2; Pipe Nipple, 3/4" x 110mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 1
7 A92E2; Elbow 90 M x F 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
8 A92D2; Elbow 90 M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
9 A596E2; Plug Male 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
10 A341E2; Union M x F 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
11 A246ED2; Nipple F x M 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
12 A245ED2; Nipple M x F 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
13 A241DB2; Nipple M x F 1/2" x 1/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
14 A134E2; Tee M x F x F 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
15 A134D2; Tee M x F x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
16 A133D2; Tee M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
17 A130E2; Tee Female 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
18 A120I2; Elbow 45 F x F 2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
19 700487; Test and Drain Valve 2" NPT Inlet x 2" BSP Outlet x 1/2" Test Facility . . . . . . 1
20 59304FO; Ball Valve DN15-1/2" ISO 7/1 Full Bore PN40 Venthole Threaded M5 . . . . . 2
21 522031926; Alarm Valve Model AV-1-300 8" G x G . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRE-TRIMMED
22 460491005; Check Valve, Swing Type, 3/4" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 VALVE ASSEMBLY
23 406012; Elbow WES 3mm x M5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
24 2162156; Self-Closing Drain Valve 1/2" Brass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
25 1610000210; Ball Valve, DN15 - 1/2" BSP Full Bore . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
26 0260; Pressure Switch Model PS10-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
27 025500013; Water Pressure Gauge 300 psi / 21 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
28 Pressure Relief Hose 3 x 6 x 0,6m Transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

27
23

13
28

20
12
3
1 14
10
16
26 4 22
11
27
25
8 7 23
15
10 13
5
24 6 28
20
9 17
21
9 12
19 8
2
18

FIGURE 11A
DN200 MODEL AV-1-300 ALARM VALVE
TRIM ARRANGEMENT WITHOUT MODEL RC-1 RETARD CHAMBER

/57/
TFP990
Page 19 of 24

NO. DESCRIPTION QTY.


AV-1 DATASHEET

1 AP90D2; Pipe Nipple, 1/2" x 90mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1


2 AP80D2; Pipe Nipple, 1/2" x 80mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3 AP200I2; Pipe Nipple, 2" x 200mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1
4 AP160E2; Pipe Nipple, 3/4" x 160mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 1
5 AP120E2; Pipe Nipple, 3/4" x 120mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 1
6 AP110E2; Pipe Nipple, 3/4" x 110mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 1
7 A92E2; Elbow 90 M x F 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
8 A92D2; Elbow 90 M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
9 A596E2; Plug Male 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
10 A341E2; Union M x F 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
11 A341D2; Union M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
12 A280D2; Nipple Male 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
13 A270D2; Nipple Female 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
14 A246ED2; Nipple F x M 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
15 A245ED2; Nipple M x F 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
16 A241DB2; Nipple M x F 1/2" x 1/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
17 A134E2; Tee M x F x F 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
18 A134D2; Tee M x F x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
19 A133D2; Tee M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
20 A130E2; Tee Female 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
21 A120I2; Elbow 45 F x F 2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
22 700487; Test and Drain Valve 2" NPT Inlet x 2" BSP Outlet x 1/2" Test Facility . . . . . . 1 PRE-TRIMMED
23 59304FO; Ball Valve DN15-1/2" ISO 7/1 Full Bore PN40 Venthole Threaded M5 . . . . . 2 VALVE ASSEMBLY
24 522031926; Alarm Valve Model AV-1-300 8" G x G . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 (SHOWN WITH
25 460491005; Check Valve, Swing Type, 3/4" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
26 406012; Elbow WES 3mm x M5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 SEPARATELY ORDERED
27 2162156; Self-Closing Drain Valve 1/2" Brass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 SUPERVISORY SWITCH)
28 1610000210; Ball Valve, DN15 - 1/2" BSP Full Bore . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
29 0260; Pressure Switch Model PS10-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
30 025500013; Water Pressure Gauge 300 psi / 21 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
31 Pressure Relief Hose 3 x 6 x 0,6m Transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

30
26

16
31
29 14
11 23
15
POSITION 4
8 FOR 17
SUPERVISORY 10
19
13 SWITCH 5
(ORDERED 25
30
12 SEPARATELY)
2 7 26
10 16
18 1 6 31
27 23
28 9 20
24
9 15
22 8
3
21

FIGURE 11B
DN200 MODEL AV-1-300 ALARM VALVE
TRIM ARRANGEMENT WITHOUT MODEL RC-1 RETARD CHAMBER
(Suitable for Supervisory)

/58/
TFP990
Page 20 of 24

NO. DESCRIPTION QTY.

AV-1 DATASHEET
1 AP60D2; Pipe Nipple, 1/2" x 60mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 AP200I2; Pipe Nipple, 2" x 200mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3 AP200D2; Pipe Nipple, 1/2" x 200mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 1
4 AP160E2; Pipe Nipple, 3/4" x 160mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 1
5 AP120E2; Pipe Nipple, 3/4" x 120mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 1
6 AP110E2; Pipe Nipple, 3/4" x 110mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 1
7 A92E2; Elbow 90 M x F 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
8 A92D2; Elbow 90 M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
9 A596E2; Plug Male 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
10 A341E2; Union M x F 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
11 A341D2; Union M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
12 A280E2; Nipple Male 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
13 A280D2; Nipple Male 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
14 A246ED2; Nipple F x M 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
15 A245ED2; Nipple M x F 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
16 A241DB2; Nipple M x F 1/2" x 1/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
17 A134E2; Tee M x F x F 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
18 A134D2; Tee M x F x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
19 A130RDED2; Reducing Tee Female 1/2" x 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . 1
20 A130E2; Tee Female 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
21 A120I2; Elbow 45 F x F 2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
22 700487; Test and Drain Valve 2" NPT Inlet x 2" BSP Outlet x 1/2" Test Facility . . . . . . 1
23 700484; Nipple M x F 1/2" x 3,56mm Orifice x 45,5mm . . . . . . . . . . . . . . . . . . . . . . . . . 1
24 59304FO; Ball Valve DN15-1/2" ISO 7/1 Full Bore PN40 Venthole Threaded M5 . . . . . 2
25 522111002; Retarding Chamber RC-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
26 522031926; Alarm Valve Model AV-1-300 8" G x G . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
27 460491005; Check Valve, Swing Type, 3/4" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRE-TRIMMED
28 406012; Elbow WES 3mm x M5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 VALVE ASSEMBLY
29 305003; Strainer 1/2" Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
30 2162156; Self-Closing Drain Valve 1/2" Brass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
31 1610000210; Ball Valve DN15-1/2" BSP Full Bore . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
32 0260; Pressure Switch Model PS10-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
33 025500013; Water Pressure Gauge 300 psi / 21 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
34 Pressure Relief Hose 3 x 6 x 0,6m Transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

32
14
31
8 33
19 28
12 25 16
34
11 24
15
3 4
17
10
23 5 27
33
1
18 7 28
29 16
10
13
30 6 34
24
9 20
26
9 15
22 8
2
21

FIGURE 12A
DN200 MODEL AV-1-300 ALARM VALVE
TRIM ARRANGEMENT WITH MODEL RC-1 RETARD CHAMBER

/59/
TFP990
Page 21 of 24

NO. DESCRIPTION QTY.


AV-1 DATASHEET

1 WS00000004; Pressure Relief Hose 3 x 6 x 1,2m Transparent . . . . . . . . . . . . . . . . . . . 1


2 AP60D2; Pipe Nipple, 1/2" x 60mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3 AP200I2; Pipe Nipple, 2" x 200mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . . . 1
4 AP160E2; Pipe Nipple, 3/4" x 160mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 1
5 AP120E2; Pipe Nipple, 3/4" x 120mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 1
6 AP120D2; Pipe Nipple, 1/2" x 120mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 1
7 AP110E2; Pipe Nipple, 3/4" x 110mm Galvanized Steel . . . . . . . . . . . . . . . . . . . . . . . . 1
8 A92E2; Elbow 90 M x F 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
9 A92D2; Elbow 90 M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
10 A596E2; Plug Male 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
11 A341E2; Union M x F 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
12 A341D2; Union M x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
13 A280E2; Nipple Male 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
14 A280D2; Nipple Male 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
15 A246ED2; Nipple F x M 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
16 A245ED2; Nipple M x F 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
17 A241DB2; Nipple M x F 1/2" x 1/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
18 A134E2; Tee M x F x F 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
19 A134D2; Tee M x F x F 1/2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
20 A130RDED2; Reducing Tee Female 1/2" x 3/4" x 1/2" BSP Galvanized . . . . . . . . . . . . 1
21 A130E2; Tee Female 3/4" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
22 A120I2; Elbow 45 F x F 2" BSP Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
23 700487; Test and Drain Valve 2" NPT Inlet x 2" BSP Outlet x 1/2" Test Facility . . . . . . 1
24 700484; Nipple M x F 1/2" x 3,56mm Orifice x 45,5mm . . . . . . . . . . . . . . . . . . . . . . . . . 1
25 59304FO; Ball Valve DN15-1/2" ISO 7/1 Full Bore PN40 Venthole Threaded M5 . . . . . 1
26 522111002; Retarding Chamber RC-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
27 522031926; Alarm Valve Model AV-1-300 8" G x G . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
PRE-TRIMMED
28 460491005; Check Valve, Swing Type, 3/4" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 VALVE ASSEMBLY
29 406012; Elbow WES 3mm x M5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 (SHOWN WITH
30 305003; Strainer 1/2" Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 SEPARATELY ORDERED
31 2162156; Self-Closing Drain Valve 1/2" Brass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
32 0260; Pressure Switch Model PS10-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 SUPERVISORY SWITCH)
33 025500013; Water Pressure Gauge 300 psi / 21 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
34 Pressure Relief Hose 3 x 6 x 0,6m Transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

32
12

9 15
20
13

26 33
29
POSITION
12 FOR 17
SUPERVISORY 34
SWITCH
6 25
(ORDERED 16
SEPARATELY)
29 4
18
11
25
1 5 28
33
2
2 8 29
30 17
11
14
24 7 34
25
19 31 10 21
27
10 16
23 9
3
22

FIGURE 12B
DN200 MODEL AV-1-300 ALARM VALVE
TRIM ARRANGEMENT WITH MODEL RC-1 RETARD CHAMBER
(Suitable for Supervisory)

/60/
TFP990
Page 22 of 24

Step 5. Open the remote cross main or The owner is responsible for the
NO. DESCRIPTION QTY. P/N branch line vent connection. Refer to inspection, testing, and maintenance of

AV-1 DATASHEET
1 3/4" x 1/4" Hex Step 6 in the Installation section. their fire protection system and devices
Bushing . . . . . . . . . 1 CH in compliance with this document, as
2 3/32" Vent Step 6. Slowly open the main control
valve until the sound of flowing water well as in addition to the standards
Fitting . . . . . . . . . . . 1 92-032-1-002
3 1/4" x 5'-0" just begins, then open the valve one of any authority having jurisdiction.
Tubing . . . . . . . . . . 1 CH more turn. The installing contractor or product
manufacturer should be contacted
PRESSURE Step 7. Close the remote branch line relative to any questions.
SWITCH vent connection after the discharge of
aerated water ceases and the outlet Automatic sprinkler systems are
has flowed full for at least 15 seconds. recommended to be inspected,
1 tested, and maintained by a qualified
3 Step 8. Fully open the Main Control Inspection Service.
(ROUTE TO Valve.
The Model AV-1-300 Alarm Valves do
DRAIN) Step 9. Open the end-of-line not require any regularly scheduled
2 Inspectors Test Connection (or maintenance. It is recommended,
(GREEN Alarm Test Valve, if acceptable to the however, that proper operation of
MODEL RC-1 authority having jurisdiction). Verify that
RETARD TINT) the alarms be periodically verified in
the system alarms operate. accordance with a procedure that is
CHAMBER
Step 10. Close the end-of-line acceptable to the authority having
Trim kit is ordered separately when a jurisdiction. Any impairment must be
Water Motor Alarm (P/N 52-201-2-012) Inspectors Test Connection (or Alarm
Test Valve). immediately corrected.
is not installed.
Step 11. Verify that water ceases to Periodic Waterflow Alarm Test
FIGURE 13 flow from the alarm line drain. If water Procedure
ALARM VENT TRIM KIT continues to flow, follow the corrective Testing of the system waterflow alarms
procedure described in the Care and should be performed periodically
inspectors test or during a discharge Maintenance section. based on the requirements of the
by a single sprinkler. authority having jurisdiction.
Allow sufficient time for drainage of
the Retard Chamber and the piping to Step 1. Notify the proper authorities
Valve Setting the water motor alarm. If needed, the and all personnel who may be affected
plunger on the Automatic Drain Valve that an alarm test is to be performed.
Procedure can be pressed to accelerate draining
Step 2. Open the Alarm Test Valve
of the Retard Chamber.
(or end-of-line Inspectors Test
NOTICE
NOTICE Step 12. Once it has been verified that Connection, if acceptable to the
After placing a fire protection system the flow of water out of the alarm line authority having jurisdiction) and verify
in service, notify the proper authorities drain has stopped, the alarm valve is that the system alarms operate in
and advise those responsible for set and is ready for service. accordance with the requirements of
monitoring proprietary and/or central the authority having jurisdiction. Verify
station alarms.
Filling the system with water will result
Care and that the water motor alarm and/or the
pressure alarm switch properly actuate
in operation of the associated alarms.
Consequently, notify the owner and
Maintenance and within the elapsed time required by
the authority having jurisdiction.
the fire department, central station, or The following procedures and Step 3. Verify that water is draining
other signal station to which the alarms inspections should be performed as from the Automatic Drain Valve.
are connected. indicated, in addition to any specific
requirements of the authority having Step 4. Close the Alarm Test Valve
The following steps are to be jurisdiction. Any impairment must be (or end-of-line Inspectors Test
performed when initially setting the immediately corrected. Connection).
TYCO Model AV-1-300 Alarm Check
Valve or after system operation due to Performing the care and maintenance Step 5. Verify that water ceases to flow
a fire. procedures will result in operation of from the Automatic Drain Valve after
the associated alarms. Consequently, allowing sufficient time for the Retard
Step 1. Close the Main Control Valve notification must first be given to the Chamber and alarm line to the water
and open the Main Drain Valve, as well owner and fire department, central motor alarm, as applicable, to drain.
as any auxiliary drain valves. station, or other signal station to which If desired, the plunger on the
Step 2.Check to see that the Hand- the alarms are connected. Automatic Drain Valve can be pressed
Hole Cover bolts are tight. If not, cross- Before closing a fire protection system to accelerate draining of the Retard
tighten them. main control valve for maintenance Chamber.
Step 3. Clean the strainers in the alarm work on the fire protection systems Step 6. Clean the Strainer located at
line and open the Water Motor Alarm that it controls, obtain permission to the connection to the Retard Chamber,
Control Valve. shut down the affected fire protection as applicable. Be sure to replace the
systems must first be obtained from strainer basket and tighten the cap
Step 4. Close the Main Drain Valve, as the proper authorities, and notify all
well as any auxiliary drain valves, and securely.
personnel who may be affected by this
the Alarm Test Valve. action.

/61/
TFP990
Page 23 of 24

NOTICE
NOTICE Step 5. Check for and remove to ambient temperatures in excess
any debris that may have become of 38C can experience significant
AV-1 DATASHEET

Cleaning of the Strainer after each


operation of the alarms is especially lodged in the Clapper Facing. If a increases in system pressure due to
important in the case of water supplies minor imperfection remains in the the thermal expansion of the water. In
(such as lakes and rivers) having a Clapper Facing, then turn it over after particular, a gridded wet-pipe system
large quantity of suspended matter. thoroughly cleaning both surfaces with a relatively small air pocket and
A clogged alarm line can prevent with a clean cloth. Replace the no relief valve can be subjected to an
operation of the alarms. Clapper Facing if necessary. Be sure increase of more than 6,9 bar, due to
to securely re-tighten the retaining an increase in ambient temperature of
Step 7. Notify all authorities fastener for the Clapper Washer. approximately 28C.
responsible for monitoring the
installation that the fire protection Step 6. Replace the Spring and As necessary, install a pressure
system has been returned to service. Clapper Assembly as shown in Figure relief valve, in accordance with the
3. While holding the coils of the Spring requirements of the authority having
Sprinkler System Drain-Down down, re-insert the Hinge Pin. Be sure jurisdiction, to automatically relieve the
Draining the sprinkler system must be that the Hinge Pin is pushed all the way excess pressure which could otherwise
done in accordance with the following to the rear of the valve. be created in wet-pipe systems that
procedure: are exposed to significant increases in
Step 7. Replace the Hand-Hole Cover.
Return the Alarm Valve to operation in ambient temperature.
Step 1. Close the main control valve, if
this has not already been done. accordance with the steps described in For information on Pressure Release
the Setting Procedure section. Trim for Alarm Check Valves refer to
Step 2. Open the remote cross main or TFP930.
branch line vent connection (Refer to Loss of Excess System
Step 6 in the Installation section). Pressure False Alarms
Step 3. Open the Main Drain Valve. In the case of a variable pressure If repeated false alarms occur in a
Check first to see that the drainage system, the System Pressure Gauge variable pressure system:
water discharge will not cause damage should normally indicate a pressure Step 1. Check for and correct the
or result in dangerous conditions. greater than that shown by the Supply cause of continued leakage out the
Pressure Gauge. Also, the value should Automatic Drain Valve.
Step 4. Wait until the Supply Pressure be close to that of the peak supply
Gauge reads zero pressure and the pressure that has occurred after the Step 2. Check for and clean a clogged
sound of draining water has stopped system was placed in service. Self Closing Drain Valve.
before performing any maintenance
work on the fire protection system. Step 3. Check for and correct the
NOTICE cause of a loss in excess system
Leakage from Automatic Drain Loss of excess system pressure will pressure.
Valve increase the likelihood of a false alarm Step 4. Drain the sprinkler system
Follow the steps indicated below until in the case of a variable pressure and re-fill it in accordance with the
water ceases to flow from the alarm system. steps described in the Valve Setting
line drain. After each step check if Procedure section.
Follow the procedure indicated below
leakage has stopped.
to correct a loss of excess system
Step 1. Open the Main Drain Valve. Let pressure condition. Intermittent Alarms
the water flow for about 5 seconds and If the pressure alarm switch gives a
Step 1. Check for signs of continued steady signal, but the water motor
then close the Main Drain Valve. This
leakage from the Automatic Drain generates an intermittent alarm, check
should flush any loose debris that may
Valve. If rust stains and/or water for binding in the water motor alarm
have become trapped between the
deposits indicate that continued drive shaft.
Clapper Facing and the Seat Ring or
leakage has been taking place, take
in the seating area of the Drain Valve. If the water motor alarm and/or the
corrective action according to the
Step 2. Repeat Step 1 if the rate of procedure described in the sub-section pressure alarm switch provide an
continued flow out of the drain was entitled Leakage From Automatic intermittent alarm, it is likely the
noticeably reduced. Drain Valve. consequence of an excessive amount
of air being trapped within the sprinkler
Step 3. If leakage from the Automatic Step 2. If there are no signs of system. Drain down the sprinkler
Drain Valve does not stop, drain continued leakage from the Automatic system and re-fill it in accordance with
the system in accordance with the Drain Valve, drain the system in the steps described in the Valve Setting
prescribed procedure. After the system accordance with the prescribed Procedure section.
has been drained, remove the Hand- procedure and then clean or replace
Hole Cover. the Bypass Check Valve as required. A discontinuance of an alarm may also
be caused by the Clapper closing due
While holding the Spring down by the After replacing the Bypass Check Valve to a sudden drop in supply pressure
coils, remove the Hinge Pin. Remove as required, return the fire protection or the shut-off of a pump in the supply
the Spring and Clapper Assembly). system to operation in accordance with line. These types of problems can only
Step 4. Using a light, check for and the steps described in the Valve Setting be corrected by maintaining a steady
remove any debris that may have Procedure section. supply pressure.
become lodged within the Seat Ring Step 3. If loss of excess system
groove. Inspect the Seat Ring seat pressure continues, inspect the
for any damage. If the Seat Ring has sprinkler system for leakage.
become dented across the seat then
the Alarm Check Valve will have to be Excess Pressure Due To Thermal
replaced. It is impractical to re-face a Expansion
Seat Ring in the field. Wet pipe sprinkler systems subject

/62/
TFP990
Page 24 of 24

P/N XXXXXXXXXX

AV-1 DATASHEET
ALARM VALVE
SWITCH
11 Grooved / Grooved
TRIM 0 None
12 Flanged / Grooved ANSI
88 EUR Supervised 1 PS10-1
13 Flanged / Flanged ANSI
89 EUR
14 Flanged / Flanged PN10/16 SIZE

15 Flanged / Flanged PN16 (8) DN65


0
76,1 mm*
16 Flanged / Grooved PN16 (8) DN100
4
114,3 mm STOP VALVE
DN150
6
168,3 mm To Be Ordered
00
DN150 Separately
7
165,1 mm
DN200 ACCESSORIES
8
219,1 mm
00 None
* Flange x Flange is not
available for (76,1 mm). Model RC-1
01
Retard Chamber
None for Supervised
03
Version (88)
Model RC-1
Retard Chamber for
05
Supervised Version
(88)

TABLE C
MODEL AV-1-300 ALARM VALVE TRIM
WITH EUROPEAN CONFORMITY VALVE TRIM
FULLY ASSEMBLED

Ordering Model PS10-1


Waterflow Pressure

Procedure
Alarm Switch . . . . . . . . . . . . . . . . . . . . . P/N 0260
Model PS10-2
Contact your local distributor for Dual-Contact Waterflow Pressure
availability. When placing an order, Alarm Switch . . . . . . . . . . . . . . . . . . . . . .P/N 0261
indicate the full product name and Part Model WMA-1
Number (P/N). Water Motor Alarm
Red Finish Gong . . . . . . . . . . . P/N 52-630-1-021
Model AV-1-300 Alarm Valve Supervisory Switch for
with Assembled European Water Motor Alarm
Conformity Valve Trim Control Valve. . . . . . . .P/N SUPSWITCHBI2DN15
Specify: Fully Assembled Model
AV-1-300 Alarm Valve with European
Conformity Valve Trim, P/N (Table C).
Accessories
Specify (description) for use with (size)
Model AV-1-300 Alarm Valve, P/N
(below).
Alarm Vent Trim (Figure 21)
When Water Motor Alarm
Not Installed . . . . . . . . . . . . . .P/N 52-201-1-012E
A through Z Labels for
Attaching to Valve
Components . . . . . . . . . . . . . . P/N WS00000033

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


Copyright 2013 Tyco Fire Products, LP. All rights reserved.

/63/
Appendix A of TFP990 (09/2013)
Summary Instructions (If problems occur, consult full document)
AV-1 DATASHEET

Wet Alarm Valve, AV-1-300, DN65, Without Retarding Chamber

D C

E H J

375 mm
F B K

390 mm 320 mm 230 mm

Normal Conditions Removing System from Service Step 9. Fully open the Main Control
The Main Control Valve (A) is opened Step 1. Close the Main Control Valve Valve (A) and lock it open.
and locked. (A). Close the Water Motor Alarm Step 10. Open the Water Motor Alarm
Control Valve (K).
The sprinkler system is filled with Control Valve (K).
water and is pressurized. Step 2. Drain the system with the
Step 11. Reset the fire alarm panel and
The Alarm Test Valve (E) and Main Main Drain Valve (F). Open all valves notify the central alarm station.
Drain Valve (F) are closed. in the system to make sure that cross-
mains and branch lines are vented and Weekly Test
The Water Motor Alarm Control Valve drained.
(K) is open. NOTICE
Placing the System Back in Service Prior to closing any valves or activating
The Pressure Gauge Valve (B) is Step 1. Replace sprinklers that have
open. any alarms, notify local security
operated and sprinklers that are close guards and the central alarm station if
The Pressure Gauge Valve (H) is to the fire. applicable.
open. Step 2. Remove the Hand-Hole Cover Step 1. Open the Alarm Test Valve (E).
System Pressure Gauge (G) reads from the Alarm Check Valve (D). Check Verify that the alarm signal created
downstream pressure. and clean the Clapper Facing and Seat by the Waterflow Pressure Alarm
Ring. Switch (J) is visible at the fire panel.
Water Supply Pressure Gauge (C)
reads upstream pressure. Step 3. Mount the Hand-Hole Cover. If applicable, check the sound of the
Water Motor Alarm it must be clear
Operation Step 4. Close Main Drain Valve (F) and and steady.
When one or more sprinklers are other valves in the system.
Step 2. Close the Alarm Test Valve
activated, pressure is reduced Step 5. Clean the strainers in the alarm (E). Verify that the normal supply and
downstream of the Alarm Valve. line and the Water Motor Alarm Trim. system pressures are restored. If the
This reduction in pressure opens the supply pressure is below normal, use
Step 6. Open the remote cross-main or
Clapper in the Alarm Valve and allows the instructions from the water supply
branch-line vent connection.
water to flow through the alarm port to obtain the usual pressure.
into the alarm line, operating the Step 7. Slowly open the Main Control
Waterflow Pressure Alarm Switch (J) Valve (A) until the sound of flowing
and the Water Motor Alarm via the water just begins, then open the valve
Water Motor Alarm Control Valve (K). one more turn.
The main waterway is now open and Step 8. Close the remote branch-line
water flows into the piping system. vent connection after the discharge of
aerated water ceases, and the outlet
has flowed fully for at least 15 seconds.

/64/
Appendix B of TFP990 (09/2013)
Summary Instructions (If problems occur, consult full document)

AV-1 DATASHEET
Wet Alarm Valve, AV-1-300, DN65, Without Retarding Chamber (Suitable for Supervisory)

J G

D C

E H
410 mm

F B

390 mm 320 mm 290 mm

Normal Conditions Removing System from Service Step 9. Fully open the Main Control
The Main Control Valve (A) is opened Step 1. Close the Main Control Valve Valve (A) and lock it open.
and locked. (A). Close the Water Motor Alarm Step 10. Open the Water Motor Alarm
Control Valve (K).
The sprinkler system is filled with Control Valve (K).
water and is pressurized. Step 2. Drain the system with the Step 11. Reset the fire alarm panel and
Main Drain Valve (F). Open all valves
The Alarm Test Valve (E) and Main notify the central alarm station.
Drain Valve (F) are closed. in the system to make sure that cross-
mains and branch lines are vented and Weekly Test
The Water Motor Alarm Control Valve drained.
(K) is open. NOTICE
Placing the System Back in Service Prior to closing any valves or activating
The Pressure Gauge Valve (B) is Step 1. Replace sprinklers that have
open. any alarms, notify local security
operated and sprinklers that are close guards and the central alarm station if
The Pressure Gauge Valve (H) is to the fire. applicable.
open. Step 2. Remove the Hand-Hole Cover Step 1. Open the Alarm Test Valve (E).
System Pressure Gauge (G) reads from the Alarm Check Valve (D). Check Verify that the alarm signal created
downstream pressure. and clean the Clapper Facing and Seat by the Waterflow Pressure Alarm
Ring. Switch (J) is visible at the fire panel.
Water Supply Pressure Gauge (C)
reads upstream pressure. Step 3. Mount the Hand-Hole Cover. If applicable, check the sound of the
Water Motor Alarm - it must be clear
Operation Step 4. Close Main Drain Valve (F) and and steady - and the signal of the
When one or more sprinklers are other valves in the system. supervisory switch.
activated, pressure is reduced Step 5. Clean the strainers in the alarm Step 2. Close the Alarm Test Valve
downstream of the Alarm Valve. line and the Water Motor Alarm Trim. (E). Verify that the normal supply and
This reduction in pressure opens the system pressures are restored. If the
Clapper in the Alarm Valve and allows Step 6. Open the remote cross-main or
branch-line vent connection. supply pressure is below normal, use
water to flow through the alarm port the instructions from the water supply
into the alarm line, operating the Step 7. Slowly open the Main Control to obtain the usual pressure.
Waterflow Pressure Alarm Switch (J) Valve (A) until the sound of flowing
and the Water Motor Alarm via the water just begins, then open the valve
Water Motor Alarm Control Valve (K). one more turn.
The main waterway is now open and Step 8. Close the remote branch-line
water flows into the piping system.
vent connection after the discharge of
aerated water ceases, and the outlet
has flowed fully for at least 15 seconds.

/65/
Appendix C of TFP990 (09/2013)
Summary Instructions (If problems occur, consult full document)
AV-1 DATASHEET

Wet Alarm Valve, AV-1-300, DN65, With Retarding Chamber

J K

L G

D C 745 mm

E H

F B

390 mm 320 mm 310 mm

Normal Conditions Removing System from Service Step 9. Fully open the Main Control
The Main Control Valve (A) is opened Step 1. Close the Main Control Valve Valve (A) and lock it open.
and locked. (A). Close the Water Motor Alarm Step 10. Open the Water Motor Alarm
Control Valve (K).
The sprinkler system is filled with Control Valve (K).
water and is pressurized. Step 2. Drain the system with the Step 11. Reset the fire alarm panel and
The Alarm Test Valve (E) and Main Main Drain Valve (F). Open all valves notify the central alarm station.
Drain Valve (F) are closed. in the system to make sure that cross-
mains and branch lines are vented and Weekly Test
The Water Motor Alarm Control Valve drained.
(K) is open. NOTICE
Placing the System Back in Service Prior to closing any valves or activating
The Pressure Gauge Valve (B) is Step 1. Replace sprinklers that have
open. any alarms, notify local security
operated and sprinklers that are close guards and the central alarm station if
The Pressure Gauge Valve (H) is to the fire. applicable.
open. Step 2. Remove the Hand-Hole Cover Step 1. Open the Alarm Test Valve (E).
System Pressure Gauge (G) reads from the Alarm Check Valve (D). Check Verify that the alarm signal created
downstream pressure. and clean the Clapper Facing and Seat by the Waterflow Pressure Alarm
Ring. Switch (J) is visible at the fire panel.
Water Supply Pressure Gauge (C)
reads upstream pressure. Step 3. Mount the Hand-Hole Cover. If applicable, check the sound of the
Water Motor Alarm it must be clear
Operation Step 4. Close Main Drain Valve (F) and and steady.
When one or more sprinklers are other valves in the system.
Step 2. Close the Alarm Test Valve
activated, pressure is reduced Step 5. Clean the strainers in the alarm (E). Verify that the normal supply and
downstream of the Alarm Valve. line and the Water Motor Alarm Trim. system pressures are restored. If the
This reduction in pressure opens supply pressure is below normal, use
Step 6. Open the remote cross-main or
the Clapper in the Alarm Valve and the instructions from the water supply
branch-line vent connection.
allows water to flow through the to obtain the usual pressure.
alarm port into the alarm line, filling Step 7. Slowly open the Main Control
the Model RC-1 Retard Chamber (L) Valve (A) until the sound of flowing
and operating the Waterflow Pressure water just begins, then open the valve
Alarm Switch (J) and the Water Motor one more turn.
Alarm via the Water Motor Alarm
Step 8. Close the remote branch-line
Control Valve (K). The main waterway vent connection after the discharge of
is now open and water flows into the
aerated water ceases, and the outlet
piping system.
has flowed fully for at least 15 seconds.

/66/
Appendix D of TFP990 (09/2013)
Summary Instructions (If problems occur, consult full document)

AV-1 DATASHEET
Wet Alarm Valve, AV-1-300, DN65, With Retarding Chamber (Suitable for Supervisory)

L G

830 mm
D C

E H K

F B

390 mm 320 mm 315 mm

Normal Conditions Removing System from Service Step 9. Fully open the Main Control
The Main Control Valve (A) is opened Step 1. Close the Main Control Valve Valve (A) and lock it open.
and locked. (A). Close the Water Motor Alarm Step 10. Open the Water Motor Alarm
Control Valve (K).
The sprinkler system is filled with Control Valve (K).
water and is pressurized. Step 2. Drain the system with the
Step 11. Reset the fire alarm panel and
Main Drain Valve (F). Open all valves
The Alarm Test Valve (E) and Main notify the central alarm station.
in the system to make sure that cross-
Drain Valve (F) are closed.
mains and branch lines are vented and Weekly Test
The Water Motor Alarm Control Valve drained.
(K) is open. NOTICE
Placing the System Back in Service Prior to closing any valves or activating
The Pressure Gauge Valve (B) is Step 1. Replace sprinklers that have
open. any alarms, notify local security
operated and sprinklers that are close guards and the central alarm station if
The Pressure Gauge Valve (H) is to the fire. applicable.
open. Step 2. Remove the Hand-Hole Cover Step 1. Open the Alarm Test Valve (E).
System Pressure Gauge (G) reads from the Alarm Check Valve (D). Check Verify that the alarm signal created
downstream pressure. and clean the Clapper Facing and Seat by the Waterflow Pressure Alarm
Ring. Switch (J) is visible at the fire panel.
Water Supply Pressure Gauge (C)
reads upstream pressure. Step 3. Mount the Hand-Hole Cover. If applicable, check the sound of the
Water Motor Alarm - it must be clear
Operation Step 4. Close Main Drain Valve (F) and and steady - and the signal of the
When one or more sprinklers are other valves in the system. supervisory switch.
activated, pressure is reduced Step 5. Clean the strainers in the alarm Step 2. Close the Alarm Test Valve
downstream of the Alarm Valve. line and the Water Motor Alarm Trim. (E). Verify that the normal supply and
This reduction in pressure opens system pressures are restored. If the
Step 6. Open the remote cross-main or
the Clapper in the Alarm Valve and supply pressure is below normal, use
branch-line vent connection.
allows water to flow through the the instructions from the water supply
alarm port into the alarm line, filling Step 7. Slowly open the Main Control to obtain the usual pressure.
the Model RC-1 Retard Chamber (L) Valve (A) until the sound of flowing
and operating the Waterflow Pressure water just begins, then open the valve
Alarm Switch (J) and the Water Motor one more turn.
Alarm via the Water Motor Alarm
Step 8. Close the remote branch-line
Control Valve (K). The main waterway vent connection after the discharge of
is now open and water flows into the aerated water ceases, and the outlet
piping system. has flowed fully for at least 15 seconds.

/67/
Appendix E of TFP990 (09/2013)
Summary Instructions (If problems occur, consult full document)
AV-1 DATASHEET

Wet Alarm Valve, AV-1-300, DN100, Without Retarding Chamber

H
D

E
J
C
410 mm
F
K
B

340 mm 260 mm 255 mm

Normal Conditions Removing System from Service Step 9. Fully open the Main Control
The Main Control Valve (A) is opened Step 1. Close the Main Control Valve Valve (A) and lock it open.
and locked. (A). Close the Water Motor Alarm Step 10. Open the Water Motor Alarm
Control Valve (K).
The sprinkler system is filled with Control Valve (K).
water and is pressurized. Step 2. Drain the system with the
Step 11. Reset the fire alarm panel and
Main Drain Valve (F). Open all valves
The Alarm Test Valve (E) and Main notify the central alarm station.
in the system to make sure that cross-
Drain Valve (F) are closed.
mains and branch lines are vented and Weekly Test
The Water Motor Alarm Control Valve drained.
(K) is open. NOTICE
Placing the System Back in Service Prior to closing any valves or activating
The Pressure Gauge Valve (B) is Step 1. Replace sprinklers that have
open. any alarms, notify local security
operated and sprinklers that are close guards and the central alarm station if
The Pressure Gauge Valve (H) is to the fire. applicable.
open. Step 2. Remove the Hand-Hole Cover Step 1. Open the Alarm Test Valve (E).
System Pressure Gauge (G) reads from the Alarm Check Valve (D). Check Verify that the alarm signal created
downstream pressure. and clean the Clapper Facing and Seat by the Waterflow Pressure Alarm
Ring. Switch (J) is visible at the fire panel.
Water Supply Pressure Gauge (C)
reads upstream pressure. Step 3. Mount the Hand-Hole Cover. If applicable, check the sound of the
Water Motor Alarm it must be clear
Operation Step 4. Close Main Drain Valve (F) and and steady.
When one or more sprinklers are other valves in the system.
Step 2. Close the Alarm Test Valve
activated, pressure is reduced Step 5. Clean the strainers in the alarm (E). Verify that the normal supply and
downstream of the Alarm Valve. line and the Water Motor Alarm Trim. system pressures are restored. If the
This reduction in pressure opens the supply pressure is below normal, use
Step 6. Open the remote cross-main or
Clapper in the Alarm Valve and allows the instructions from the water supply
water to flow through the alarm port branch-line vent connection.
to obtain the usual pressure.
into the alarm line, operating the Step 7. Slowly open the Main Control
Waterflow Pressure Alarm Switch (J) Valve (A) until the sound of flowing
and the Water Motor Alarm via the water just begins, then open the valve
Water Motor Alarm Control Valve (K). one more turn.
The main waterway is now open and Step 8. Close the remote branch-line
water flows into the piping system. vent connection after the discharge of
aerated water ceases, and the outlet
has flowed fully for at least 15 seconds.

/68/
Appendix F of TFP990 (09/2013)
Summary Instructions (If problems occur, consult full document)

AV-1 DATASHEET
Wet Alarm Valve, AV-1-300, DN100, Without Retarding Chamber (Suitable for Supervisory)

H
D
J
E
C
410 mm
K
F
B

340 mm 250 mm 295 mm

Normal Conditions Removing System from Service Step 9. Fully open the Main Control
The Main Control Valve (A) is opened Step 1. Close the Main Control Valve Valve (A) and lock it open.
and locked. (A). Close the Water Motor Alarm Step 10. Open the Water Motor Alarm
Control Valve (K).
The sprinkler system is filled with Control Valve (K).
water and is pressurized. Step 2. Drain the system with the
Step 11. Reset the fire alarm panel and
Main Drain Valve (F). Open all valves
The Alarm Test Valve (E) and Main notify the central alarm station.
in the system to make sure that cross-
Drain Valve (F) are closed.
mains and branch lines are vented and Weekly Test
The Water Motor Alarm Control Valve drained.
(K) is open. NOTICE
Placing the System Back in Service Prior to closing any valves or activating
The Pressure Gauge Valve (B) is Step 1. Replace sprinklers that have
open. any alarms, notify local security
operated and sprinklers that are close guards and the central alarm station if
The Pressure Gauge Valve (H) is to the fire. applicable.
open. Step 2. Remove the Hand-Hole Cover Step 1. Open the Alarm Test Valve (E).
System Pressure Gauge (G) reads from the Alarm Check Valve (D). Check Verify that the alarm signal created
downstream pressure. and clean the Clapper Facing and Seat by the Waterflow Pressure Alarm
Ring. Switch (J) is visible at the fire panel.
Water Supply Pressure Gauge (C)
reads upstream pressure. Step 3. Mount the Hand-Hole Cover. If applicable, check the sound of the
Water Motor Alarm - it must be clear
Operation Step 4. Close Main Drain Valve (F) and and steady - and the signal of the
When one or more sprinklers are other valves in the system. supervisory switch.
activated, pressure is reduced Step 5. Clean the strainers in the alarm Step 2. Close the Alarm Test Valve
downstream of the Alarm Valve. line and the Water Motor Alarm Trim. (E). Verify that the normal supply and
This reduction in pressure opens the system pressures are restored. If the
Clapper in the Alarm Valve and allows Step 6. Open the remote cross-main or
branch-line vent connection. supply pressure is below normal, use
water to flow through the alarm port the instructions from the water supply
into the alarm line, operating the Step 7. Slowly open the Main Control to obtain the usual pressure.
Waterflow Pressure Alarm Switch (J) Valve (A) until the sound of flowing
and the Water Motor Alarm via the water just begins, then open the valve
Water Motor Alarm Control Valve (K). one more turn.
The main waterway is now open and Step 8. Close the remote branch-line
water flows into the piping system.
vent connection after the discharge of
aerated water ceases, and the outlet
has flowed fully for at least 15 seconds.

/69/
Appendix G of TFP990 (09/2013)
Summary Instructions (If problems occur, consult full document)
AV-1 DATASHEET

Wet Alarm Valve, AV-1-300, DN100, With Retarding Chamber

J
K

G
L

H
D 760 mm

E
C

F
B

340 mm 260 mm 315 mm

Normal Conditions Removing System from Service Step 9. Fully open the Main Control
The Main Control Valve (A) is opened Step 1. Close the Main Control Valve Valve (A) and lock it open.
and locked. (A). Close the Water Motor Alarm Step 10. Open the Water Motor Alarm
Control Valve (K).
The sprinkler system is filled with Control Valve (K).
water and is pressurized. Step 2. Drain the system with the
Step 11. Reset the fire alarm panel and
The Alarm Test Valve (E) and Main Main Drain Valve (F). Open all valves notify the central alarm station.
Drain Valve (F) are closed. in the system to make sure that cross-
mains and branch lines are vented and Weekly Test
The Water Motor Alarm Control Valve drained.
(K) is open. NOTICE
Placing the System Back in Service Prior to closing any valves or activating
The Pressure Gauge Valve (B) is Step 1. Replace sprinklers that have
open. any alarms, notify local security
operated and sprinklers that are close guards and the central alarm station if
The Pressure Gauge Valve (H) is to the fire. applicable.
open. Step 2. Remove the Hand-Hole Cover Step 1. Open the Alarm Test Valve (E).
System Pressure Gauge (G) reads from the Alarm Check Valve (D). Check Verify that the alarm signal created
downstream pressure. and clean the Clapper Facing and Seat by the Waterflow Pressure Alarm
Ring. Switch (J) is visible at the fire panel.
Water Supply Pressure Gauge (C)
reads upstream pressure. Step 3. Mount the Hand-Hole Cover. If applicable, check the sound of the
Water Motor Alarm it must be clear
Operation Step 4. Close Main Drain Valve (F) and and steady.
When one or more sprinklers are other valves in the system.
Step 2. Close the Alarm Test Valve
activated, pressure is reduced Step 5. Clean the strainers in the alarm (E). Verify that the normal supply and
downstream of the Alarm Valve. line and the Water Motor Alarm Trim. system pressures are restored. If the
This reduction in pressure opens supply pressure is below normal, use
Step 6. Open the remote cross-main or
the Clapper in the Alarm Valve and the instructions from the water supply
branch-line vent connection.
allows water to flow through the to obtain the usual pressure.
alarm port into the alarm line, filling Step 7. Slowly open the Main Control
the Model RC-1 Retard Chamber (L) Valve (A) until the sound of flowing
and operating the Waterflow Pressure water just begins, then open the valve
Alarm Switch (J) and the Water Motor one more turn.
Alarm via the Water Motor Alarm Step 8. Close the remote branch-line
Control Valve (K). The main waterway vent connection after the discharge of
is now open and water flows into the aerated water ceases, and the outlet
piping system. has flowed fully for at least 15 seconds.

/70/
Appendix H of TFP990 (09/2013)
Summary Instructions (If problems occur, consult full document)

AV-1 DATASHEET
Wet Alarm Valve, AV-1-300, DN100, With Retarding Chamber (Suitable for Supervisory)

G
L

H 830 mm
D

E
C K

F
B

340 mm 260 mm 315 mm

Normal Conditions Removing System from Service Step 9. Fully open the Main Control
The Main Control Valve (A) is opened Step 1. Close the Main Control Valve Valve (A) and lock it open.
and locked. (A). Close the Water Motor Alarm Step 10. Open the Water Motor Alarm
Control Valve (K).
The sprinkler system is filled with Control Valve (K).
water and is pressurized. Step 2. Drain the system with the Step 11. Reset the fire alarm panel and
Main Drain Valve (F). Open all valves
The Alarm Test Valve (E) and Main notify the central alarm station.
in the system to make sure that cross-
Drain Valve (F) are closed.
mains and branch lines are vented and Weekly Test
The Water Motor Alarm Control Valve drained.
(K) is open. NOTICE
Placing the System Back in Service Prior to closing any valves or activating
The Pressure Gauge Valve (B) is Step 1. Replace sprinklers that have
open. any alarms, notify local security
operated and sprinklers that are close guards and the central alarm station if
The Pressure Gauge Valve (H) is to the fire. applicable.
open. Step 2. Remove the Hand-Hole Cover Step 1. Open the Alarm Test Valve (E).
System Pressure Gauge (G) reads from the Alarm Check Valve (D). Check Verify that the alarm signal created
downstream pressure. and clean the Clapper Facing and Seat by the Waterflow Pressure Alarm
Ring. Switch (J) is visible at the fire panel.
Water Supply Pressure Gauge (C)
reads upstream pressure. Step 3. Mount the Hand-Hole Cover. If applicable, check the sound of the
Water Motor Alarm - it must be clear
Operation Step 4. Close Main Drain Valve (F) and and steady - and the signal of the
When one or more sprinklers are other valves in the system. supervisory switch.
activated, pressure is reduced Step 5. Clean the strainers in the alarm Step 2. Close the Alarm Test Valve
downstream of the Alarm Valve. line and the Water Motor Alarm Trim. (E). Verify that the normal supply and
This reduction in pressure opens system pressures are restored. If the
Step 6. Open the remote cross-main or
the Clapper in the Alarm Valve and supply pressure is below normal, use
branch-line vent connection.
allows water to flow through the the instructions from the water supply
alarm port into the alarm line, filling Step 7. Slowly open the Main Control to obtain the usual pressure.
the Model RC-1 Retard Chamber (L) Valve (A) until the sound of flowing
and operating the Waterflow Pressure water just begins, then open the valve
Alarm Switch (J) and the Water Motor one more turn.
Alarm via the Water Motor Alarm Step 8. Close the remote branch-line
Control Valve (K). The main waterway
vent connection after the discharge of
is now open and water flows into the
aerated water ceases, and the outlet
piping system.
has flowed fully for at least 15 seconds.

/71/
Appendix J of TFP990 (09/2013)
Summary Instructions (If problems occur, consult full document)
AV-1 DATASHEET

Wet Alarm Valve, AV-1-300, DN150, Without Retarding Chamber

H
D

E J
C
415 mm
F K
B

360 mm 285 mm 285 mm

Normal Conditions Removing System from Service Step 9. Fully open the Main Control
The Main Control Valve (A) is opened Step 1. Close the Main Control Valve Valve (A) and lock it open.
and locked. (A). Close the Water Motor Alarm Step 10. Open the Water Motor Alarm
Control Valve (K).
The sprinkler system is filled with Control Valve (K).
water and is pressurized. Step 2. Drain the system with the
Step 11. Reset the fire alarm panel and
The Alarm Test Valve (E) and Main Main Drain Valve (F). Open all valves notify the central alarm station.
Drain Valve (F) are closed. in the system to make sure that cross-
mains and branch lines are vented and Weekly Test
The Water Motor Alarm Control Valve drained.
(K) is open. NOTICE
Placing the System Back in Service Prior to closing any valves or activating
The Pressure Gauge Valve (B) is Step 1. Replace sprinklers that have
open. any alarms, notify local security
operated and sprinklers that are close guards and the central alarm station if
The Pressure Gauge Valve (H) is to the fire. applicable.
open. Step 2. Remove the Hand-Hole Cover Step 1. Open the Alarm Test Valve (E).
System Pressure Gauge (G) reads from the Alarm Check Valve (D). Check Verify that the alarm signal created
downstream pressure. and clean the Clapper Facing and Seat by the Waterflow Pressure Alarm
Ring. Switch (J) is visible at the fire panel.
Water Supply Pressure Gauge (C)
reads upstream pressure. Step 3. Mount the Hand-Hole Cover. If applicable, check the sound of the
Water Motor Alarm it must be clear
Operation Step 4. Close Main Drain Valve (F) and and steady.
When one or more sprinklers are other valves in the system.
Step 2. Close the Alarm Test Valve
activated, pressure is reduced Step 5. Clean the strainers in the alarm (E). Verify that the normal supply and
downstream of the Alarm Valve. line and the Water Motor Alarm Trim. system pressures are restored. If the
This reduction in pressure opens the supply pressure is below normal, use
Clapper in the Alarm Valve and allows Step 6. Open the remote cross-main or
branch-line vent connection. the instructions from the water supply
water to flow through the alarm port to obtain the usual pressure.
into the alarm line, operating the Step 7. Slowly open the Main Control
Waterflow Pressure Alarm Switch (J) Valve (A) until the sound of flowing
and the Water Motor Alarm via the water just begins, then open the valve
Water Motor Alarm Control Valve (K). one more turn.
The main waterway is now open and Step 8. Close the remote branch-line
water flows into the piping system. vent connection after the discharge of
aerated water ceases, and the outlet
has flowed fully for at least 15 seconds.

/72/
Appendix K of TFP990 (09/2013)
Summary Instructions (If problems occur, consult full document)

AV-1 DATASHEET
Wet Alarm Valve, AV-1-300, DN150, Without Retarding Chamber (Suitable for Supervisory)

H
D J

E
C
K 415 mm
F
B

360 mm 280 mm 320 mm

Normal Conditions Removing System from Service Step 9. Fully open the Main Control
The Main Control Valve (A) is opened Step 1. Close the Main Control Valve Valve (A) and lock it open.
and locked. (A). Close the Water Motor Alarm Step 10. Open the Water Motor Alarm
Control Valve (K).
The sprinkler system is filled with Control Valve (K).
water and is pressurized. Step 2. Drain the system with the Step 11. Reset the fire alarm panel and
Main Drain Valve (F). Open all valves
The Alarm Test Valve (E) and Main notify the central alarm station.
in the system to make sure that cross-
Drain Valve (F) are closed.
mains and branch lines are vented and Weekly Test
The Water Motor Alarm Control Valve drained.
(K) is open. NOTICE
Placing the System Back in Service Prior to closing any valves or activating
The Pressure Gauge Valve (B) is Step 1. Replace sprinklers that have
open. any alarms, notify local security
operated and sprinklers that are close guards and the central alarm station if
The Pressure Gauge Valve (H) is to the fire. applicable.
open. Step 2. Remove the Hand-Hole Cover Step 1. Open the Alarm Test Valve (E).
System Pressure Gauge (G) reads from the Alarm Check Valve (D). Check Verify that the alarm signal created
downstream pressure. and clean the Clapper Facing and Seat by the Waterflow Pressure Alarm
Ring. Switch (J) is visible at the fire panel.
Water Supply Pressure Gauge (C)
reads upstream pressure. Step 3. Mount the Hand-Hole Cover. If applicable, check the sound of the
Water Motor Alarm - it must be clear
Operation Step 4. Close Main Drain Valve (F) and and steady - and the signal of the
When one or more sprinklers are other valves in the system. supervisory switch.
activated, pressure is reduced Step 5. Clean the strainers in the alarm Step 2. Close the Alarm Test Valve
downstream of the Alarm Valve. line and the Water Motor Alarm Trim. (E). Verify that the normal supply and
This reduction in pressure opens the system pressures are restored. If the
Step 6. Open the remote cross-main or
Clapper in the Alarm Valve and allows supply pressure is below normal, use
water to flow through the alarm port branch-line vent connection.
the instructions from the water supply
into the alarm line, operating the Step 7. Slowly open the Main Control to obtain the usual pressure.
Waterflow Pressure Alarm Switch (J) Valve (A) until the sound of flowing
and the Water Motor Alarm via the water just begins, then open the valve
Water Motor Alarm Control Valve (K). one more turn.
The main waterway is now open and Step 8. Close the remote branch-line
water flows into the piping system. vent connection after the discharge of
aerated water ceases, and the outlet
has flowed fully for at least 15 seconds.

/73/
Appendix L of TFP990 (09/2013)
AV-1 DATASHEET

Summary Instructions (If problems occur, consult full document)


Wet Alarm Valve, AV-1-300, DN150, With Retarding Chamber

J
K

G
L

H
770 mm
D

E
C

F
B

360 mm 285 mm 340 mm

Normal Conditions Removing System from Service Step 9. Fully open the Main Control
The Main Control Valve (A) is opened Step 1. Close the Main Control Valve Valve (A) and lock it open.
and locked. (A). Close the Water Motor Alarm Step 10. Open the Water Motor Alarm
Control Valve (K).
The sprinkler system is filled with Control Valve (K).
water and is pressurized. Step 2. Drain the system with the Step 11. Reset the fire alarm panel and
Main Drain Valve (F). Open all valves
The Alarm Test Valve (E) and Main notify the central alarm station.
Drain Valve (F) are closed. in the system to make sure that cross-
mains and branch lines are vented and Weekly Test
The Water Motor Alarm Control Valve drained.
(K) is open. NOTICE
Placing the System Back in Service Prior to closing any valves or activating
The Pressure Gauge Valve (B) is Step 1. Replace sprinklers that have
open. any alarms, notify local security
operated and sprinklers that are close guards and the central alarm station if
The Pressure Gauge Valve (H) is to the fire. applicable.
open. Step 2. Remove the Hand-Hole Cover Step 1. Open the Alarm Test Valve (E).
System Pressure Gauge (G) reads from the Alarm Check Valve (D). Check Verify that the alarm signal created
downstream pressure. and clean the Clapper Facing and Seat by the Waterflow Pressure Alarm
Ring. Switch (J) is visible at the fire panel.
Water Supply Pressure Gauge (C)
reads upstream pressure. Step 3. Mount the Hand-Hole Cover. If applicable, check the sound of the
Water Motor Alarm it must be clear
Operation Step 4. Close Main Drain Valve (F) and and steady.
When one or more sprinklers are other valves in the system.
Step 2. Close the Alarm Test Valve
activated, pressure is reduced Step 5. Clean the strainers in the alarm (E). Verify that the normal supply and
downstream of the Alarm Valve. line and the Water Motor Alarm Trim. system pressures are restored. If the
This reduction in pressure opens supply pressure is below normal, use
Step 6. Open the remote cross-main or
the Clapper in the Alarm Valve and the instructions from the water supply
branch-line vent connection.
allows water to flow through the to obtain the usual pressure.
alarm port into the alarm line, filling Step 7. Slowly open the Main Control
the Model RC-1 Retard Chamber (L) Valve (A) until the sound of flowing
and operating the Waterflow Pressure water just begins, then open the valve
Alarm Switch (J) and the Water Motor one more turn.
Alarm via the Water Motor Alarm Step 8. Close the remote branch-line
Control Valve (K). The main waterway vent connection after the discharge of
is now open and water flows into the aerated water ceases, and the outlet
piping system. has flowed fully for at least 15 seconds.

/74/
Appendix M of TFP990 (09/2013)
Summary Instructions (If problems occur, consult full document)

AV-1 DATASHEET
Wet Alarm Valve, AV-1-300, DN150, With Retarding Chamber (Suitable for Supervisory)

G
L
830 mm
H
D

E
C K

F
B

360 mm 280 mm 340 mm

Normal Conditions Removing System from Service Step 9. Fully open the Main Control
The Main Control Valve (A) is opened Step 1. Close the Main Control Valve Valve (A) and lock it open.
and locked. (A). Close the Water Motor Alarm Step 10. Open the Water Motor Alarm
Control Valve (K).
The sprinkler system is filled with Control Valve (K).
water and is pressurized. Step 2. Drain the system with the
Step 11. Reset the fire alarm panel and
The Alarm Test Valve (E) and Main Main Drain Valve (F). Open all valves notify the central alarm station.
Drain Valve (F) are closed. in the system to make sure that cross-
mains and branch lines are vented and Weekly Test
The Water Motor Alarm Control Valve drained.
(K) is open. NOTICE
Placing the System Back in Service Prior to closing any valves or activating
The Pressure Gauge Valve (B) is Step 1. Replace sprinklers that have
open. any alarms, notify local security
operated and sprinklers that are close guards and the central alarm station if
The Pressure Gauge Valve (H) is to the fire. applicable.
open. Step 2. Remove the Hand-Hole Cover Step 1. Open the Alarm Test Valve (E).
System Pressure Gauge (G) reads from the Alarm Check Valve (D). Check Verify that the alarm signal created
downstream pressure. and clean the Clapper Facing and Seat by the Waterflow Pressure Alarm
Ring. Switch (J) is visible at the fire panel.
Water Supply Pressure Gauge (C)
reads upstream pressure. Step 3. Mount the Hand-Hole Cover. If applicable, check the sound of the
Water Motor Alarm - it must be clear
Operation Step 4. Close Main Drain Valve (F) and and steady - and the signal of the
When one or more sprinklers are other valves in the system. supervisory switch.
activated, pressure is reduced Step 5. Clean the strainers in the alarm Step 2. Close the Alarm Test Valve
downstream of the Alarm Valve. line and the Water Motor Alarm Trim. (E). Verify that the normal supply and
This reduction in pressure opens system pressures are restored. If the
Step 6. Open the remote cross-main or
the Clapper in the Alarm Valve and supply pressure is below normal, use
branch-line vent connection.
allows water to flow through the the instructions from the water supply
alarm port into the alarm line, filling Step 7. Slowly open the Main Control to obtain the usual pressure.
the Model RC-1 Retard Chamber (L) Valve (A) until the sound of flowing
and operating the Waterflow Pressure water just begins, then open the valve
Alarm Switch (J) and the Water Motor one more turn.
Alarm via the Water Motor Alarm Step 8. Close the remote branch-line
Control Valve (K). The main waterway vent connection after the discharge of
is now open and water flows into the aerated water ceases, and the outlet
piping system. has flowed fully for at least 15 seconds.

/75/
Appendix N of TFP990 (09/2013)
Summary Instructions (If problems occur, consult full document)
AV-1 DATASHEET

Wet Alarm Valve, AV-1-300, DN200, Without Retarding Chamber

G
E

H
F
J 520 mm
C

K
B

390 mm 405 mm 320 mm

Normal Conditions Removing System from Service Step 9. Fully open the Main Control
The Main Control Valve (A) is opened Step 1. Close the Main Control Valve Valve (A) and lock it open.
and locked. (A). Close the Water Motor Alarm Step 10. Open the Water Motor Alarm
Control Valve (K).
The sprinkler system is filled with Control Valve (K).
water and is pressurized. Step 2. Drain the system with the Step 11. Reset the fire alarm panel and
The Alarm Test Valve (E) and Main Main Drain Valve (F). Open all valves notify the central alarm station.
Drain Valve (F) are closed. in the system to make sure that cross-
mains and branch lines are vented and Weekly Test
The Water Motor Alarm Control Valve drained.
(K) is open. NOTICE
Placing the System Back in Service Prior to closing any valves or activating
The Pressure Gauge Valve (B) is Step 1. Replace sprinklers that have
open. any alarms, notify local security
operated and sprinklers that are close guards and the central alarm station if
The Pressure Gauge Valve (H) is to the fire. applicable.
open. Step 2. Remove the Hand-Hole Cover Step 1. Open the Alarm Test Valve (E).
System Pressure Gauge (G) reads from the Alarm Check Valve (D). Check Verify that the alarm signal created
downstream pressure. and clean the Clapper Facing and Seat by the Waterflow Pressure Alarm
Ring. Switch (J) is visible at the fire panel.
Water Supply Pressure Gauge (C)
reads upstream pressure. Step 3. Mount the Hand-Hole Cover. If applicable, check the sound of the
Water Motor Alarm it must be clear
Operation Step 4. Close Main Drain Valve (F) and and steady.
When one or more sprinklers are other valves in the system.
Step 2. Close the Alarm Test Valve
activated, pressure is reduced Step 5. Clean the strainers in the alarm (E). Verify that the normal supply and
downstream of the Alarm Valve. line and the Water Motor Alarm Trim. system pressures are restored. If the
This reduction in pressure opens the supply pressure is below normal, use
Clapper in the Alarm Valve and allows Step 6. Open the remote cross-main or
branch-line vent connection. the instructions from the water supply
water to flow through the alarm port to obtain the usual pressure.
into the alarm line, operating the Step 7. Slowly open the Main Control
Waterflow Pressure Alarm Switch (J) Valve (A) until the sound of flowing
and the Water Motor Alarm via the water just begins, then open the valve
Water Motor Alarm Control Valve (K). one more turn.
The main waterway is now open and Step 8. Close the remote branch-line
water flows into the piping system. vent connection after the discharge of
aerated water ceases, and the outlet
has flowed fully for at least 15 seconds.

/76/
Appendix P of TFP990 (09/2013)
Summary Instructions (If problems occur, consult full document)

AV-1 DATASHEET
Wet Alarm Valve, AV-1-300, DN200, Without Retarding Chamber (Suitable for Supervisory)

G
E

H J
F

C K 520 mm

390 mm 400 mm 365 mm

Normal Conditions Removing System from Service Step 9. Fully open the Main Control
The Main Control Valve (A) is opened Step 1. Close the Main Control Valve Valve (A) and lock it open.
and locked. (A). Close the Water Motor Alarm Step 10. Open the Water Motor Alarm
Control Valve (K).
The sprinkler system is filled with Control Valve (K).
water and is pressurized. Step 2. Drain the system with the Step 11. Reset the fire alarm panel and
The Alarm Test Valve (E) and Main Main Drain Valve (F). Open all valves notify the central alarm station.
in the system to make sure that cross-
Drain Valve (F) are closed.
mains and branch lines are vented and Weekly Test
The Water Motor Alarm Control Valve drained.
(K) is open. NOTICE
Placing the System Back in Service Prior to closing any valves or activating
The Pressure Gauge Valve (B) is Step 1. Replace sprinklers that have
open. any alarms, notify local security
operated and sprinklers that are close guards and the central alarm station if
The Pressure Gauge Valve (H) is to the fire. applicable.
open. Step 2. Remove the Hand-Hole Cover Step 1. Open the Alarm Test Valve (E).
System Pressure Gauge (G) reads from the Alarm Check Valve (D). Check Verify that the alarm signal created
downstream pressure. and clean the Clapper Facing and Seat by the Waterflow Pressure Alarm
Ring. Switch (J) is visible at the fire panel.
Water Supply Pressure Gauge (C)
reads upstream pressure. Step 3. Mount the Hand-Hole Cover. If applicable, check the sound of the
Water Motor Alarm - it must be clear
Operation Step 4. Close Main Drain Valve (F) and and steady - and the signal of the
When one or more sprinklers are other valves in the system. supervisory switch.
activated, pressure is reduced Step 5. Clean the strainers in the alarm Step 2. Close the Alarm Test Valve
downstream of the Alarm Valve. line and the Water Motor Alarm Trim. (E). Verify that the normal supply and
This reduction in pressure opens the system pressures are restored. If the
Step 6. Open the remote cross-main or
Clapper in the Alarm Valve and allows supply pressure is below normal, use
branch-line vent connection.
water to flow through the alarm port the instructions from the water supply
into the alarm line, operating the Step 7. Slowly open the Main Control to obtain the usual pressure.
Waterflow Pressure Alarm Switch (J) Valve (A) until the sound of flowing
and the Water Motor Alarm via the water just begins, then open the valve
Water Motor Alarm Control Valve (K). one more turn.
The main waterway is now open and Step 8. Close the remote branch-line
water flows into the piping system.
vent connection after the discharge of
aerated water ceases, and the outlet
has flowed fully for at least 15 seconds.

/77/
Appendix Q of TFP990 (09/2013)
Summary Instructions (If problems occur, consult full document)
AV-1 DATASHEET

Wet Alarm Valve, AV-1-300, DN200, With Retarding Chamber

K
D

G
E

770 mm
H
F

390 mm 405 mm 410 mm

Normal Conditions Removing System from Service Step 9. Fully open the Main Control
The Main Control Valve (A) is opened Step 1. Close the Main Control Valve Valve (A) and lock it open.
and locked. (A). Close the Water Motor Alarm Step 10. Open the Water Motor Alarm
Control Valve (K).
The sprinkler system is filled with Control Valve (K).
water and is pressurized. Step 2. Drain the system with the Step 11. Reset the fire alarm panel and
Main Drain Valve (F). Open all valves
The Alarm Test Valve (E) and Main notify the central alarm station.
in the system to make sure that cross-
Drain Valve (F) are closed.
mains and branch lines are vented and Weekly Test
The Water Motor Alarm Control Valve drained.
(K) is open. NOTICE
Placing the System Back in Service Prior to closing any valves or activating
The Pressure Gauge Valve (B) is Step 1. Replace sprinklers that have
open. any alarms, notify local security
operated and sprinklers that are close guards and the central alarm station if
The Pressure Gauge Valve (H) is to the fire. applicable.
open. Step 2. Remove the Hand-Hole Cover Step 1. Open the Alarm Test Valve (E).
System Pressure Gauge (G) reads from the Alarm Check Valve (D). Check Verify that the alarm signal created
downstream pressure. and clean the Clapper Facing and Seat by the Waterflow Pressure Alarm
Ring. Switch (J) is visible at the fire panel.
Water Supply Pressure Gauge (C)
reads upstream pressure. Step 3. Mount the Hand-Hole Cover. If applicable, check the sound of the
Water Motor Alarm it must be clear
Operation Step 4. Close Main Drain Valve (F) and and steady.
When one or more sprinklers are other valves in the system.
Step 2. Close the Alarm Test Valve
activated, pressure is reduced Step 5. Clean the strainers in the alarm (E). Verify that the normal supply and
downstream of the Alarm Valve. line and the Water Motor Alarm Trim. system pressures are restored. If the
This reduction in pressure opens supply pressure is below normal, use
Step 6. Open the remote cross-main or
the Clapper in the Alarm Valve and the instructions from the water supply
allows water to flow through the alarm branch-line vent connection.
to obtain the usual pressure.
port into the alarm line, filling the Step 7. Slowly open the Main Control
Model RC-1 Retard Chamber (L) and Valve (A) until the sound of flowing
operating the Model RC-1 Waterflow water just begins, then open the valve
Pressure Alarm Switch (J) and the one more turn.
Water Motor Alarm via the Water Motor
Step 8. Close the remote branch-line
Alarm Control Valve (K). The main
vent connection after the discharge of
waterway is now open and water flows aerated water ceases, and the outlet
into the piping system.
has flowed fully for at least 15 seconds.

/78/
Appendix R of TFP990 (09/2013)
Summary Instructions (If problems occur, consult full document)

AV-1 DATASHEET
Wet Alarm Valve, AV-1-300, DN200, With Retarding Chamber (Suitable for Supervisory)

G
E
830 mm
H
F

390 mm 400 mm 410 mm

Normal Conditions Removing System from Service Step 9. Fully open the Main Control
The Main Control Valve (A) is opened Step 1. Close the Main Control Valve Valve (A) and lock it open.
and locked. (A). Close the Water Motor Alarm Step 10. Open the Water Motor Alarm
Control Valve (K).
The sprinkler system is filled with Control Valve (K).
water and is pressurized. Step 2. Drain the system with the
Step 11. Reset the fire alarm panel and
Main Drain Valve (F). Open all valves
The Alarm Test Valve (E) and Main notify the central alarm station.
in the system to make sure that cross-
Drain Valve (F) are closed.
mains and branch lines are vented and Weekly Test
The Water Motor Alarm Control Valve drained.
(K) is open. NOTICE
Placing the System Back in Service Prior to closing any valves or activating
The Pressure Gauge Valve (B) is Step 1. Replace sprinklers that have
open. any alarms, notify local security
operated and sprinklers that are close guards and the central alarm station if
The Pressure Gauge Valve (H) is to the fire. applicable.
open. Step 2. Remove the Hand-Hole Cover Step 1. Open the Alarm Test Valve (E).
System Pressure Gauge (G) reads from the Alarm Check Valve (D). Check Verify that the alarm signal created
downstream pressure. and clean the Clapper Facing and Seat by the Waterflow Pressure Alarm
Ring. Switch (J) is visible at the fire panel.
Water Supply Pressure Gauge (C)
reads upstream pressure. Step 3. Mount the Hand-Hole Cover. If applicable, check the sound of the
Water Motor Alarm - it must be clear
Operation Step 4. Close Main Drain Valve (F) and and steady - and the signal of the
When one or more sprinklers are other valves in the system. supervisory switch.
activated, pressure is reduced Step 5. Clean the strainers in the alarm Step 2. Close the Alarm Test Valve
downstream of the Alarm Valve. line and the Water Motor Alarm Trim. (E). Verify that the normal supply and
This reduction in pressure opens system pressures are restored. If the
Step 6. Open the remote cross-main or
the Clapper in the Alarm Valve and supply pressure is below normal, use
allows water to flow through the alarm branch-line vent connection.
the instructions from the water supply
port into the alarm line, filling the Step 7. Slowly open the Main Control to obtain the usual pressure.
Model RC-1 Retard Chamber (L) and Valve (A) until the sound of flowing
operating the Model RC-1 Waterflow water just begins, then open the valve
Pressure Alarm Switch (J) and the one more turn.
Water Motor Alarm via the Water Motor Step 8. Close the remote branch-line
Alarm Control Valve (K). The main vent connection after the discharge of
waterway is now open and water flows aerated water ceases, and the outlet
into the piping system. has flowed fully for at least 15 seconds.

/79/
Notes

NOTES





























/80/
Notes

AV-1 DATASHEET


NOTES




























/81/
Notes

NOTES





























/82/
Notes

AV-1 DATASHEET


NOTES




























/83/
DV-5 DATASHEET

Worldwide
www.tyco-fire.com
Contacts

DV-5 Deluge Valves, Diaphragm Style


VdS/LPCB European Conformity Valve Trim

General
Description
TYCO DV-5 Deluge Valves (DN40 thru
DN200) are diaphragm-type valves
used as automatic water control valves
in deluge fire protection systems. When
properly trimmed, the DV-5 Valves are
also able to provide actuation of fire
alarms upon system operation.
The diaphragm style design of the
DV-5 Valve allows external resetting,
providing for easy resetting of a deluge
system withouta having to open a valve
handhole cover to manually reposition
a clapper and/or latch mechanism.
Simply re-pressurizing the diaphragm
chamber resets the valve.
The DV-5 also features internal and
external coating of the valve to provide
corrosion resistance. The external
corrosion resistance of the RISLAN
coating permits the use of the DV-5 in
corrosive atmospheres associated with
many types of industrial processing
plants and outdoor installations.
End Connections Available and Weights

NOTICE
End Connection Nominal Valve Size
The DV-5 Deluge Valves described
herein must be installed and maintained
in compliance with this document, as Inlet Outlet DN40 DN50 DN80 DN100 DN150 DN200
well as with the applicable standards
of the approval agency, in addition to Thread Thread 4,1 kg 5,4 kg N/A N/A N/A N/A
the standards of any other authorities
having jurisdiction. Failure to do so
may impair the performance of these Groove Groove 3,6 kg 4,5 kg 14,1 kg 27,7 kg 44,9 kg 68,1 kg
devices.
The owner is responsible for maintaining Flange Groove N/A N/A 17,7 kg 33,6 kg 48,5 kg 77,8 kg
their fire protection system and de
vices in proper operating condition. Flange Flange N/A N/A 21,3 kg 36,3 kg 52,3 kg 87,5 kg
Contact the installing contractor
or product manufacturer with any
questions.

Page 1 of 26 JANUARY 2015 TFP1338

/84/
TFP1338
Page 2 of 26

NOTES:
VALVE PARTS REPLACEMENT PARTS

DV-5 DATASHEET
1. NR - Not Replaceable
No. Description Qty. Repair Parts No. Description P/N
2. CH - Common Hardware
1 Valve Body . . . . . . . . . . . 1 NR (a) Diaphragm Kit,
2 Diaphragm . . . . . . . . . . . 1 (a) 3. Valve Bodies of DN100, DN150 & DN200 Includes Item 2:
3 Diaphragm Cover. . . . . . . 1 NR valves are equipped with studs and Valve DN40 Valve . . . . . . . . . . . . . . 92-477-1-105
4 Flat Washer: Covers are secured by Hex Nuts and Hex DN50 Valve . . . . . . . . . . . . . . 92-477-1-107
DN40 Valve, Bolts. DN80 Valve . . . . . . . . . . . . . . 92-477-1-109
M12 . . . . . . . . . . . . . . . . . 4 CH DN100 Valve . . . . . . . . . . . . . 92-477-1-101
4. V-Ring is attached to Diaphragm of DN100,
DN50 & DN80 Valve, DN150 Valve . . . . . . . . . . . . . 92-477-1-103
M16 . . . . . . . . . . . . . . . . . 4 CH
DN150 & DN200 valves at factory. If, during DN200 Valve . . . . . . . . . . . . . 92-477-1-111
DN100 & DN150 Valve, internal valve inspection, V-Ring is
M16 . . . . . . . . . . . . . . . . . 8 CH discovered to be detached from Diaphragm,
DN200 Valve, be advised that V-Ring is a required valve
M20 . . . . . . . . . . . . . . . . . 8 CH component and that detachment will not
5 Hex Bolt: affect normal valve operation or
DN40 Valve, performance. Should V-Ring become STUDS
M12 x 30 mm. . . . . . . . . . 4 CH detached, reinstall between Diaphragm (NOTE 3)
DN50 & DN80 Valve, 2
and Diaphragm Cover concentrically as
M16 x 50 mm. . . . . . . . . . 4 CH (NOTE 4)
DN100 Valve,
shown.
M16 x 50 mm. . . . . . . . . . 6 CH NOTE: Do not apply adhesives, lubricants,
DN150 Valve,
or other substances to Diaphragm, V-Ring,
M16 x 55 mm. . . . . . . . . . 6 CH
DN200 Valve, or Valve Body.
M20 x 70 mm. . . . . . . . . . 6 CH
6 Hex Nut:
DN100 & DN150 Valve,
M16 . . . . . . . . . . . . . . . . . 2 CH 4
DN200 Valve, 6
M20 . . . . . . . . . . . . . . . . . 2 CH (NOTE 3)
1

DIAPHRAGM
ORIENTATION
ORIENT TAB
DIAPHRAGM TAB V-RING
PERPENDICULAR (NOTE 4)
5
TO VALVE BODY
CENTERLINE 4 3

FIGURE 1
DN40 thru DN200 DV-5 DELUGE VALVES
ASSEMBLY

Flange Drilling Specification


Nominal Dimensions in Millimeters
Nominal
Valve ANSI B16.1 ISO 7005-2 ISO 7005-2 JIS B 2210 AS 2129
Size (a) (Class 125) (b) (PN10) (c) (PN16) (d) (10K) (Table E)
Dim. Dim. Qty. Dim. Dim. Qty. Dim. Dim. Qty. Dim. Dim. Qty. Dim. Dim. Qty.
A B N A B N A B N A B N A B N
DN80 152,4 19,0 4 160,0 19,0 8 N/A N/A
USE
DN100 190,5 19,0 8 ISO 2084 180,0 19,0 8 175,0 15,0 8 178,0 18,0 8
(PN16)
DN150 241,3 22,2 8 240,0 23,0 8 240,0 19,0 8 235,0 22,0 8
DN200 298,5 22,2 8 295,0 23,0 8 295,0 23,0 12 N/A 292,0 22,0 8
Notes: Dim. A
a. Flange ends DN40 and DN50 DV-5 Valves are not offered.
b. Same drilling as for B16.5 (Class 150) and B16.42 (Class 250) Bolt Circle
c. Same drilling as for BS 4504 Section 3.2 (PN10) and DIN 2532 (PN10) Diameter
d. Same drilling as for BS 4504 Section 3.2 (PN16) and DIN 2532 (PN16)

Dim. B
Bolt Hole
Diameter

Qty. N
Number of
Bolt Holes
TABLE A
DIMENSIONAL SPECIFICATIONS FOR SELECTION OF FLANGE DRILLING

/85/
TFP1338
Page 3 of 26

Technical Operating
DV-5 DATASHEET

204 mm Data Principles


Approvals The TYCO DV-5 Deluge Valve is a
VdS and LPCB Approved when diaphragm-style valve that depends
DN40 trimmed as detailed in this technical upon water pressure in the Diaphragm
Groove x Groove & Thread x Thread data sheet for European Conformity Chamber (Ref. Figure 3A) to hold the
applications. Diaphragm closed against the water
DV-5 Deluge Valve supply pressure.
Components for the DN40 thru DN200 When the DV-5 Valve is set for service,
220 mm DV-5 Deluge Valves are shown in Figure the Diaphragm Chamber is pressurized
1. The DV-5 Valves are for vertical through the trim connections from the
installations. They are rated for use at inlet side of the systems stop valve.
a service pressures of 1,4 to 16,0 bar,
except that the DN50 has a minimum Opening an actuation device, for
DN50
operating pressure of 2,0 bar, and the example the solenoid valve in the
Groove x Groove & Thread x Thread
minimum residual pressure for sizes Electric Actuation Trim (Ref. Figure 6),
DN40 thru DN200 must be 2,0 bar for releases water from the Diaphragm
flow velocities greater than 8,5 m/s. Chamber faster than it can be
replenished through the 3,2 mm
The take-out dimensions are shown in restriction within the Automatic Shut-
324 mm
Figure 2, and the flanged connections off Valve provided in the diaphragm
are available drilled per ANSI, ISO, AS, chamber supply connection. Release
and JIS specifications (Ref. Table A). of water pressure results in a rapid
The DV-5 Valves are provided with pressure drop in the Diaphragm
DN80 Chamber and the force differential
ISO 7-1 threaded ports that will readily
Groove x Groove, Flange x Flange,
accept the trim arrangements detailed applied through the Diaphragm to hold
& Flange x Groove the Diaphragm in the set position is
in this technical data sheet.
reduced below the valve trip point. The
Pressure Loss water supply pressure then forces the
Refer to Graph A. Diaphragm open permitting water to
400 mm flow into the system piping, as well as
Materials of through the Alarm Port to actuate the
system alarms (Ref. Figure 3B).

DN100 Construction
Groove x Groove, Flange x Flange,
& Flange x Groove
Body
RISLAN* coated Ductile Iron
per ASTM A536-77
Grade 65-45-12
Handhole Cover
460 mm RISLAN* coated Ductile Iron
per ASTM A536-77
Grade 65-45-12
Diaphragm
DN150 Nylon fabric reinforced, Natural Rubber
Groove x Groove, Flange x Flange,
& Flange x Groove
per ASTM D2000
Diaphragm Cover Fasteners
Galvanized Carbon Steel
* The RISLAN coating is a polyamide (Nylon 11) coating.

570 mm

DN200
Groove x Groove, Flange x Flange,
& Flange x Groove

FIGURE 2
DV-5 DELUGE VALVES
TAKE-OUT DIMENSIONS
(Applies to all available
end configurations)

/86/
TFP1338
Page 4 of 26

Port Sizes

DV-5 DATASHEET
Port Description Port
DN40 DN50 DN80 DN100 DN150 DN200
Diaphragm Chamber Supply P1 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
Water Supply Pressure & Alarm Test P2 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
Alarm Actuation & System Drain P3 3/4" 3/4" 3/4" 1" 1" 1"
Main Drain P4 3/4" 3/4" 1-1/4" 2" 2" 2"
Diaphragm Chamber Supply Automatic Shut-Off Valve Actuation P5 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"

SYSTEM OPEN TO ATMOSPHERE WATERFLOW TO SYSTEM


DIAPHRAGM
CHAMBER
ALARM PORT
OPEN TO WATERFLOW
ATMOSPHERE TO AUTOMATIC
ALARM PORT SHUT-OFF
WATERFLOW VALVE
TO ALARM

VALVE DIAPHRAGM
WATERWAY VALVE CHAMBER
DIAPHRAGM WATERWAY OPEN TO
SEAT ATMOSPHERE

DIAPHRAGM
RETRACTS
DIAPHRAGM
OPENING
CHAMBER
WATER VALVE
SUPPLY
SUPPLY WATERWAY
PORT
PRESSURE
& ALARM
17,2 BAR MAX. WATER SUPPLY WATERFLOW FROM WATER SUPPLY
TEST PORT
FIGURE 3A FIGURE 3B
SET POSITION OPERATED POSITION

DRAIN FROM SYSTEM RESIDUAL DRAIN FROM SYSTEM

DIAPHRAGM
AUTOMATICALLY
SYSTEM FLEXES TO
SYSTEM
DRAIN ITS SEATED
DRAIN
PORT POSTION
DIAPHRAGM
CHAMBER
VALVE OPEN TO
WATERWAY ATMOSPHERE

MAIN
DRAIN
PORT

WATER SUPPLY SHUT OFF WATER SUPPLY SHUT OFF


FIGURE 3C FIGURE 3D
SYSTEM DRAIN POSITION RESIDUAL DRAIN POSITION
FIGURE 3
DN40 thru DN200 DV-5 DELUGE VALVES
SET AND OPEN POSITIONS

/87/
TFP1338
Page 5 of 26

0,60
DV-5 DATASHEET

0,50

0,40

0,30

40
DN

50
DN
NOMINAL PRESSURE DROP IN BAR

0,20

80
DN

100
DN

150
0,10
0,09

DN

200
0,08

DN
0,07
0,06

0,05

0,04

0,03

0,02
200 400 600 1000 2000 3000 5000 7000 10000 15000
FLOW RATE IN LITRES PER MINUTE (LPM)
GRAPH A
DN40 thru DN200 DV-5 DELUGE VALVES
NOMINAL PRESSURE LOSS VERSUS FLOW

/88/
TFP1338
Page 6 of 26

DV-5 DATASHEET
Item Description
A DV-5 Valve
E B Stop Valve
C C Waterflow Switch
K D (Not used)
A
E System Drain Valve
3 F Automatic Drain Valve
G Alarm Test Valve
H Alarm Control Valve
F
2 H J Water Supply Gauge
K Diaphragm Gauge
J L System Gauge
G
M Manual Control Station
N Automatic Shut-Off Valve
M
P Diaphragm Supply Valve
N Q Diaphragm Supply Strainer
Q 1 Diaphragm Supply Connection
2 Water Motor Alarm Connection
3 Wet Pilot Line Connection
P
B
1

FIGURE 4
WET PILOT ACTUATION
(Refer to Figures 7 thru 10 for specific Bills of Material)

Wet Pilot Installation dimensions are provided in


Figure 19.
Provision must be made for installing
a 80 K-factor orifice, Inspectors Test
Actuation Pilot sprinklers are to be minimum
80 K-factor orifice approved automatic
Connection at the most hydraulically
demanding location of a wet pilot line
The Wet Pilot Actuation Trim forms a sprinklers. Manual Control Stations (usually adjacent to the highest and
part of the laboratory approval of the are to be the Model MC-1 described in most remote wet pilot sprinkler or
DV-5 Valves and is necessary for their Technical Data Sheet TFP1382. manual control station).
proper operation. Notes:
The maximum height of a wet pilot
The Wet Pilot Actuation Trim provides Wet pilot lines must be maintained at a
line above the DV-5 Valve must not
for connection of a detection system minimum temperature of 4C.
exceed the limitations shown in Table
consisting of wet pilot line sprinklers B as a function of the minimum water At a minimum, it is recommended that
(heat detectors) and manual control supply pressure to the DV-5 Valve for internally galvanized pipe and cast
stations interconnected with minimum an equivalent length (pipe plus fittings) iron fittings be used for wet pilot lines.
DN15 steel pipe. The pilot line is of the pilot line up to 150 meters to the
connected to the Wet Pilot Line most remote pilot sprinkler.
Connection shown in Figure 4.

/89/
TFP1338
Page 7 of 26

S T Item Description
DV-5 DATASHEET

L
4
A DV-5 Valve
U B Stop Valve
C Waterflow Switch
E V D (Not used)
C E System Drain Valve
3 K F Automatic Drain Valve
G Alarm Test Valve
H Alarm Control Valve
A
J Water Supply Gauge
R K Diaphragm Gauge
H F
L System Gauge
M Manual Control Station
2 N Automatic Shut-Off Valve
G P Diaphragm Supply Valve
3,0 J Q Diaphragm Supply Strainer
R Dry Pilot Actuator
SUR E
PRES S Dry Pilot Low Pressure Switch
M AIR
AIR PRESSURE IN BAR

UM S
YSTE M T Dry Pilot Air Supply Valve
2,0 MINIM
URE
Q N U Dry Pilot Line Gauge
RESS
ING P V Pressure Relief Valve
R OPEN
UATO
1,0 EO F ACT
RANG P 1 Diaphragm Supply Connection
2 Water Motor Alarm Connection
B
3 Dry Pilot Line Connection
0
1,0 4,0 7,0 10,0 13,0 16,0 1 4 Dry Pilot Air Supply Connection
WATER SUPPLY PRESSURE IN BAR

FIGURE 5
DRY PILOT ACTUATION
(Refer to Figures 11 thru 14 for specific Bills of Material)

Dry Pilot for use at a maximum pilot service


pressure of 3,4 bar and a maximum
that separately indicates operation of
the detection system is provided by
Actuation water supply service pressure of 16 bar.
Graph B shows the minimum pilot line
a low pressure alarm switch set as
follows:
The Dry Pilot Actuation Trim forms a service pressure as a function of the low pressure alarm setting at
part of the laboratory approval of the water supply pressure. The pressure in approximately 0,4 bar below the
DV-5 Valves and is necessary for their the dry pilot actuation system must be minimum pilot line service pressure
proper operation. automatically maintained using one of requirement shown in Graph B
The Dry Pilot Actuation Trim provides the following maintenance devices, as
fire alarm setting at approximately
for installation of a detection system appropriate:
1,0 bar below the minimum pilot line
consisting of pilot sprinklers (heat Model AMD-1 service pressure requirement shown
detectors) and manual control stations Air Maintenance Device in Graph B
interconnected with minimum DN15 (pressure reducing type)
The Dry Pilot Low Pressure Switch may
steel pipe. The dry pilot line, which is (Refer to Technical Data Sheet be ordered as option with the valve trim
to be pressurized with air or nitrogen, TFP1221.) or separately ordered.
is connected to the Dry Pilot Line
Connection shown in Figure 5. Model AMD-2 The Pressure Relief Valve provided
Air Maintenance Device in the trim is factory set to relieve at
Installation dimensions are provided in (compressor control type) a pressure of approximately 3,1 bar;
Figure 19.
(Refer to Technical Data Sheet however, it may be field adjusted to a
Pilot sprinklers are to be minimum TFP1231.) lower pressure, if required.
80 K-factor orifice approved automatic
Model AMD-3 The dry pilot line is to be provided with
sprinklers. Manual Control Stations
Nitrogen Maintenance Device low point drains to enable draining on
are to be the Model MC-1 described in
(high pressure reducing type) condensate.
Technical Data Sheet TFP1382.
(Refer to Technical Data Sheet Note: At a minimum, it is recommended
The Dry Pilot Actuation Trim is provided
TFP1241.) that internally galvanized pipe and cast iron
with a Model DP-1 Dry Pilot Actuator,
fittings be used for dry pilot lines.
which is described in Technical Data Supervision of the pressure in the dry
Sheet TFP1380. The actuator is rated pilot actuation system and an alarm

/90/
TFP1338
Page 8 of 26

DV-5 DATASHEET
Item Description
A DV-5 Valve
E B Stop Valve
C R C Waterflow Switch
K D (Not used)
A
E System Drain Valve
F Automatic Drain Valve
G Alarm Test Valve
H Alarm Control Valve
F
2 H J Water Supply Gauge
K Diaphragm Gauge
J L System Gauge
G
M Manual Control Station
N Automatic Shut-Off Valve
M
P Diaphragm Supply Valve
N Q Diaphragm Supply Strainer
R Solenoid Valve
Q
1 Diaphragm Supply Connection
2 Water Motor Alarm Connection
P
B
1

FIGURE 6
ELECTRIC ACTUATION
(Refer to Figures 15 thru 18 for specific Bills of Material)

Electric The Solenoid Valve provided in the


valve trim (P/N 52-287-1-124 described
The Electric Actuation Trim is provided
with a Model ASV-1 Automatic Shut-
Actuation in Technical Data Sheet TFP2180) is
rated as follows:
off Valve; consequently, the release
circuit of the releasing panel need only
The Electric Actuation Trim forms a part Pressure: 17,2 bar provide the standard ten minutes of
of the laboratory approval of the DV-5 alarm condition intended to energize
Voltage: 24 VDC the Solenoid Valve to open. After the
Valves and is necessary for their proper
operation. Power Consumption: 22 Watts ten minute duration, at which point
should the Solenoid Valve become
The Electric Actuation Trim is required Current Draw: 0,83 Amps de-energized and close (especially
for electric operation of the DV-5 Valve Note: Approval by VdS and LPCB is while operating under battery back-
by a detection system consisting of contingent on the use of the Solenoid up), the Automatic Shut-off Valve
electrical devices such as heat sensitive Valve provided with the valve trim. VdS will have already automatically
thermostats, smoke detectors, and/or and LPCB only approve solenoid valves closed, thereby preventing the DV-5
electric manual pull stations. for use in non-hazardous locations. Diaphragm Chamber from becoming
Installation dimensions are provided in Consult with the applicable standards re-pressurized, and preventing an
Figure 19. of the approval agency regarding inadvertent closing of the DV-5 during
installation criteria pertaining to electric a fire event.
actuation circuitry.

/91/
TFP1338
Page 9 of 26

3,0
DV-5 DATASHEET

URE
RESS
AIR P
Notes:

AIR PRESSURE IN BAR


EM The dew point of the pilot line air pressure must be maintained below
UM SYST the lowest ambient temperature to which the dry pilot actuation system
2,0 MINIM will be exposed. Accumulation of water in the pilot line connection to the
Actuator will lower the air pressure at which the actuator will open and
URE
RESS
possibly prevent proper operation. Also, introduction of moisture into the
GP pilot lines exposed to freezing temperatures can create an ice buildup
OPENIN that could prevent proper operation of the Actuator.
ATOR
ACTU
An air dryer must be installed where the moisture content of the air supply
OF is not properly controlled at less than the required value.
1,0
RANGE It is recommended that an AMD-3 Nitrogen Maintenance Device be uti-
lized in dry pilot actuation system applications where the dew point must
be maintained below -29C. See Technical Data Sheet TFP1241.

0
1,0 4,0 7,0 10,0 13,0 16,0
WATER SUPPLY PRESSURE IN BAR
GRAPH B
DN40 thru DN200 DV-5 DELUGE VALVES
DRY PILOT LINE PRESSURE REQUIREMENTS

Maximum Pilot Height(b),


Supply Meters
Pressure(a),
bar DN40 DN50 DN80 DN100 DN150 DN200

1,4 1,4 0,9 1,4 5,2 5,5 2,7

2,8 7,3 5,8 9,1 11,9 11,6 11,6

4,1 14,0 11,6 15,8 16,5 17,1 13,4

5,5 17,8 16,5 21,3 18,3 21,3 17,8

6,9 23,8 23,8 28,3 23,8 30,2 19,8

8,3 26,5 26,5 35,7 35,10 39,6 29,3

9,7 32,0 32,6 42,4 43,3 46,9 43,0

11,0 38,7 37,5 49,1 53,6 49,1 51,8

12,1 40,8 42,1 52,4 52,1 59,1 50,1

13,8 48,8 48,8 62,8 68,0 65,8 62,8

15,5 56,4 50,6 72,2 71,0 75,0 76,2

17,2 61,3 60,7 76,5 75,3 83,8 78,3

Notes:
a. If supply pressure is variable, assume minimum expected value.
b. Maximum pilot height for up to 150 meters of equivalent length of pilot line (pipe plus fittings).
Interpolation between data points is permitted.
TABLE B
DN40 thru DN200 DV-5 DELUGE VALVES
WET PILOT DESIGN CRITERIA FOR UP TO
150 METERS OF EQUIVALENT LENGTH OF PILOT LINE (PIPE PLUS FITTINGS)

/92/
TFP1338
Page 10 of 26

NO. DESCRIPTION QTY. NO. DESCRIPTION QTY.

DV-5 DATASHEET
1 025500013; Water gauge; class 1.6 0-25 bar 25 ATDDMN; Adapter fitting; brass;
or UL/FM 0-300 PSI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 thr. DN15 x DN15 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2 Optional 03128601; Bolt M4 x 25 . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 26 ATDMCON; Adapter fitting; brass;
3 Optional 05566800; Bolt M8 x 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 thr. DN15 male x compr.15mm; nickel pl . . . . . . . . . . . . . . . . . . . . . 4
4 Optional 06620086; Washer M4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 27 ATEEMN; Adapter fitting; brass;
5 1610000210; Ball valve; brass; full bore; 1/2" BSP; PN30; thr. male DN20 x DN20; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
kv=16.3; ul & fpr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 28 Deluge valve DV-5; 1-1/2" & 2'';
6 1610000270; Ball valve; brass; full bore; 3/4" BSP; PN30; Grv x Grv or Thr x Thr; 3/4" drain . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
kv=29.5; ul & fpr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 29 ETDDFN; Adapter elbow; brass;
7 20005025; Strainer y-type; NPT 1/2"; 50 mesh; SS304 screen; thr. DN15 fem x DN15 fem; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . 2
bronze body . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 30 ETDDMN; Adapter elbow; brass;
8 2162156; Automatic drain valve; 1/2"; thr. DN15 male x DN15 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . 1
oper: k=25 & non oper: k=5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 31 ETDMDFN; Adapter elbow; brass;
9 Optional 280200272 pipe saddle DN20 30 x 4 mm hole 11mm. . . . 1 thr. DN15 male x DN15fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . 3
10 Optional 2850750251; Mounting plate for supervisory switch 32 Pressure switch: CE, VDS, LPCB, or FM approved . . . . . . . . . . . . . 1
fall valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 33 RTDMBFN; Adapter reduce; brass;
11 406012; Elbow 3 mm x m5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 thr. DN15 male x DN8 fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . 3
12 460491005; Swing type check valve 3/4". . . . . . . . . . . . . . . . . . . . . 1 34 RTEDMN; Adapter reduce; brass;
13 522892001; Break rod station thr. DN20 male x DN15 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . 2
model MC-1 for manual release . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 35 RTEMDFN; Adapter reduce; brass;
14 59304FO; Ball valve; size 1/2"; full bore; PN40; venthole thread . . . 2 thr. DN20 male x DN15 fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . 1
15 81900211; Straight tube connector 12 mm x 1/2" male nr 36 TTDMDDFN; Adapter tee; brass;
661273 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN15 male x DN15 fem x DN15 fem; nickel pl . . . . . . . . . . . . . 5
16 923431021; Automatic shut-off valve; 37 TTEEEFN; Adap tee; brass;
Model ASV-1 for DV-5 trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN20 fem x DN20 fem x DN20 fem; nickel pl . . . . . . . . . . . . . . 2
17 Optional 997908 Supervisory switch CE/VdS/LPCB/FM or UL . . . . 1 38 TTEMEEFN; Adap tee; brass;
18 A291E2; malleable fitting; plug male; thr. DN20 male x DN20 fem x DN20 fem; nickel pl . . . . . . . . . . . . . 2
BSP thr. size 3/4"; galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 39 V923221002; Check valve brass;
19 A341D4; malleable fitting; union; BSP thr. 1/2" male/fem; S.S. . . . . 2 NPT 1/2" male/male; seat buna-n . . . . . . . . . . . . . . . . . . . . . . . . . . 1
20 AP100E4; pipe nipple; stainless steel 316; 3/4" x 100 mm . . . . . . . 1 40 WS00000004; Pressure relief hose;
21 AP180D4; pipe nipple; stainless steel 316; 1/2" x 180 mm . . . . . . . 1 3 x 6 length 1.2 m; transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
22 AP300D4; pipe nipple; stainless steel 316; 1/2" x 300 mm . . . . . . . 1 41 WS00000007: Copper pipe; 10 x 12 mm; length 900 mm . . . . . . . . 1
23 AP60D4; pipe nipple; stainless steel 316; 1/2" x 60 mm . . . . . . . . . 2 42 WS00000096; Nickel pl copper tube; 15 x 1mm for DV-5 . . . . . . . . 2
24 AP80E4; pipe nipple; stainless steel 316; 3/4" x 80 mm . . . . . . . . . 2

34 33
37
38 29
35 27
32
18
20 6
36 1
34 27 11
26
38 28 29 33
6
37 24 23 26 40
42 14
42
26 34
18 19 36
8 23
25 1
5 26
17 33 36
4
14 31
10 11
3 22 13
21
9
2 40 36 36
31 16
30
39 41
31
7 15
19

FIGURE 7
DN40 and DN50 DV-5 DELUGE VALVES
WET PILOT ACTUATION TRIM

/93/
TFP1338
Page 11 of 26

NO. DESCRIPTION QTY. NO. DESCRIPTION QTY.


DV-5 DATASHEET

1 025500013; Water gauge; class 1.6 0-25 bar 24 AP80D4; pipe nipple; stainless steel 316; 1/2" x 80 mm . . . . . . . . . 2
or UL/FM 0-300 PSI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 25 AP80E4; pipe nipple; stainless steel 316; 3/4" x 80 mm . . . . . . . . . 2
2 Optional 03128601; Bolt M4 x 25 . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 26 ATDMCON; Adapter fitting; brass;
3 Optional 05566800; Bolt M8 x 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 thr. DN15 male x compr.15mm; nickel pl . . . . . . . . . . . . . . . . . . . . . 4
4 Optional 06620086; Washer M4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 27 ATEEMN; Adapter fitting; brass;
5 1610000210; Ball valve; brass; full bore; 1/2" BSP; PN30; thr. male DN20 x DN20; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
kv=16.3; ul & fpr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 28 Deluge valve DV-5; 3'';
6 1610000270; Ball valve; brass; full bore; 3/4" BSP; PN30; Flg x Flg or Flg x Grv or Grv x Grv; 1-1/4" drain. . . . . . . . . . . . . . . . 1
kv=29.5; ul & fpr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 29 ETDDFN; Adapter elbow; brass;
7 20005025; Strainer y-type; NPT 1/2"; 50 mesh; SS304 screen; thr. DN15 fem x DN15 fem; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . 2
bronze body . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 30 ETDDMN; Adapter elbow; brass;
8 2162156; Automatic drain valve; 1/2"; thr. DN15 male x DN15 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . 1
oper: k=25 & non oper: k=5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 31 ETDMDFN; Adapter elbow; brass;
9 Optional 280200272 pipe saddle DN20 30 x 4 mm hole 11mm. . . . 1 thr. DN15 male x DN15fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . 3
10 Optional 2850750251; Mounting plate for supervisory switch 32 Pressure switch: CE, VDS, LPCB, or FM approved . . . . . . . . . . . . . 1
fall valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 33 RTDMBFN; Adapter reduce; brass;
11 406012; Elbow 3 mm x m5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 thr. DN15 male x DN8 fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . 3
12 460491005; Swing type check valve 3/4". . . . . . . . . . . . . . . . . . . . . 1 34 RTEDMN; Adapter reduce; brass;
13 522892001; Break rod station thr. DN20 male x DN15 male; nickel pl. . . . . . . . . . . . . . . . . . . . . . . 2
model MC-1 for manual release . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 35 RTEMDFN; Adapter reduce; brass;
14 59304FO; Ball valve; size 1/2"; full bore; PN40; venthole thread . . . 2 thr. DN20 male x DN15 fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . 1
15 81900211; Straight tube connector 12 mm x 1/2" male nr 36 TTDMDDFN; Adapter tee; brass;
661273 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN15 male x DN15 fem x DN15 fem; nickel pl . . . . . . . . . . . . . 5
16 923431021; Automatic shut-off valve; 37 TTEEEFN; Adap tee; brass;
Model ASV-1 for DV-5 trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN20 fem x DN20 fem x DN20 fem; nickel pl . . . . . . . . . . . . . . 2
17 Optional 997908 Supervisory switch CE/VdS/LPCB/FM or UL . . . . 1 38 TTEMEEFN; Adap tee; brass;
18 A291G2; malleable fitting; plug male; thr. DN20 male x DN20 fem x DN20 fem; nickel pl . . . . . . . . . . . . . 2
BSP thr. size 1-1/4"; galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 39 V923221002; Check valve brass;
19 A341D4; malleable fitting; union; BSP thr. 1/2" male/fem; S.S. . . . . 2 NPT 1/2" male/male; seat buna-n . . . . . . . . . . . . . . . . . . . . . . . . . . 1
20 AP100E4; pipe nipple; stainless steel 316; 3/4" x 100 mm . . . . . . . 1 40 WS00000004; Pressure relief hose;
21 AP140D4; pipe nipple; stainless steel 316; 1/2" x 140 mm . . . . . . . 1 3 x 6 length 1.2 m; transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
22 AP300D4; pipe nipple; stainless steel 316; 1/2" x 300 mm . . . . . . . 1 41 WS00000007: Copper pipe; 10 x 12 mm; length 900 mm . . . . . . . . 1
23 AP60D4; pipe nipple; stainless steel 316; 1/2" x 60 mm . . . . . . . . . 1 42 WS00000096; Nickel pl copper tube; 15 x 1mm for DV-5 . . . . . . . . 2

34 33
37
38 29
35 27
32
12
20 6
36 25 27
26 1
38 28 11
6
37 25 33
29
42 26 40
26 34 42 14
8 18
24 24 19
5 36
23
17 1
4 26 36
10 33
3 14 31
9 11 13
2 21 22
40 36 36
31 16 41
30 31
39 15
7
19

FIGURE 8
DN80 DV-5 DELUGE VALVE
WET PILOT ACTUATION TRIM

/94/
TFP1338
Page 12 of 26

NO. DESCRIPTION QTY. NO. DESCRIPTION QTY.

DV-5 DATASHEET
1 025500013; Water gauge; class 1.6 0-25 bar 25 ATDMCON; Adapter fitting; brass;
or UL/FM 0-300 PSI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 thr. DN15 male x compr.15mm; nickel pl . . . . . . . . . . . . . . . . . . . . . 4
2 Optional 03128601; Bolt M4 x 25 . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 26 ATEEMN; Adapter fitting; brass;
3 Optional 05566800; Bolt M8 x 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 thr. male DN20 x DN20; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
4 Optional 06620086; Washer M4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 27 Deluge valve DV-5; 4'' & 6";
5 1610000210; Ball valve; brass; full bore; 1/2" BSP; PN30; Flg x Flg or Flg x Grv or Grv x Grv; 2" drain . . . . . . . . . . . . . . . . . . . 1
kv=16.3; ul & fpr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 28 ETDDFN; Adapter elbow; brass;
6 1610000270; Ball valve; brass; full bore; 3/4" BSP; PN30; thr. DN15 fem x DN15 fem; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . 2
kv=29.5; ul & fpr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 29 ETDDMN; Adapter elbow; brass;
7 20005025; Strainer y-type; NPT 1/2"; 50 mesh; SS304 screen; thr. DN15 male x DN15 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . 1
bronze body . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 30 ETDMDFN; Adapter elbow; brass;
8 2162156; Automatic drain valve; 1/2"; thr. DN15 male x DN15fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . 3
oper: k=25 & non oper: k=5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 31 Pressure switch: CE, VDS, LPCB, or FM approved . . . . . . . . . . . . . 1
9 Optional 280200272 pipe saddle DN20 30 x 4 mm hole 11mm. . . . 1 32 RTDMBFN; Adapter reduce; brass;
10 Optional 2850750251; Mounting plate for supervisory switch thr. DN15 male x DN8 fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . 3
fall valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 33 RTEDMN; Adapter reduce; brass;
11 406012; Elbow 3 mm x m5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 thr. DN20 male x DN15 male; nickel pl. . . . . . . . . . . . . . . . . . . . . . . 2
12 460491005; Swing type check valve 3/4". . . . . . . . . . . . . . . . . . . . . 1 34 RTEMDFN; Adapter reduce; brass;
13 522892001; Break rod station thr. DN20 male x DN15 fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . 1
model MC-1 for manual release . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 35 RTFEMN; Reduce thr. fitting; nickel pl brass;
14 59304FO; Ball valve; size 1/2"; full bore; PN40; venthole thread . . . 2 male DN20 x DN25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
15 81900211; Straight tube connector 12 mm x 1/2" male nr 36 TTDMDDFN; Adapter tee; brass;
661273 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN15 male x DN15 fem x DN15 fem; nickel pl . . . . . . . . . . . . . 5
16 923431021; Automatic shut-off valve; 37 TTEEEFN; Adap tee; brass;
Model ASV-1 for DV-5 trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN20 fem x DN20 fem x DN20 fem; nickel pl . . . . . . . . . . . . . . 2
17 Optional 997908 Supervisory switch CE/VdS/LPCB/FM or UL . . . . 1 38 TTEMEEFN; Adap tee; brass;
18 A291I2; malleable fitting; plug male; thr. DN20 male x DN20 fem x DN20 fem; nickel pl . . . . . . . . . . . . . 2
BSP thr. size 2"; galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 39 V923221002; Check valve brass;
19 A341D4; malleable fitting; union; BSP thr. 1/2" male/fem; S.S. . . . . 2 NPT 1/2" male/male; seat buna-n . . . . . . . . . . . . . . . . . . . . . . . . . . 1
20 AP100E4; pipe nipple; stainless steel 316; 3/4" x 100 mm . . . . . . . 1 40 WS00000004; Pressure relief hose;
21 AP120D4; pipe nipple; stainless steel 316; 1/2" x 120 mm . . . . . . . 2 3 x 6 length 1.2 m; transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
22 AP300D4; pipe nipple; stainless steel 316; 1/2" x 300 mm . . . . . . . 1 41 WS00000007: Copper pipe; 10 x 12 mm; length 900 mm . . . . . . . . 1
23 AP60D4; pipe nipple; stainless steel 316; 1/2" x 60 mm . . . . . . . . . 2 42 WS00000096; Nickel pl copper tube; 15 x 1mm for DV-5 . . . . . . . . 2
24 AP80E4; pipe nipple; stainless steel 316; 3/4" x 80 mm . . . . . . . . . 2

33 32
37
38 28
34 26
31
12
20 6
36 24 26
25
38 1
6 27
37 24 11
42 32
28
25 33 40
23 25
8 14
21 18 42
5
1 19 36
17
23
4 32
10 25 36
3 14
11
9 30
2 21 13
40 36 22
30 36
16 41
29 30
39 15
7
19

FIGURE 9
DN100 and DN150 DV-5 DELUGE VALVES
WET PILOT ACTUATION TRIM

/95/
TFP1338
Page 13 of 26

NO. DESCRIPTION QTY. NO. DESCRIPTION QTY.


DV-5 DATASHEET

1 025500013; Water gauge; class 1.6 0-25 bar 26 ATDMCON; Adapter fitting; brass;
or UL/FM 0-300 PSI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 thr. DN15 male x compr.15mm; nickel pl . . . . . . . . . . . . . . . . . . . . . 4
2 Optional 03128601; Bolt M4 x 25 . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 27 ATEEMN; Adapter fitting; brass;
3 Optional 05566800; Bolt M8 x 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 thr. male DN20 x DN20; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
4 Optional 06620086; Washer M4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 28 Deluge valve DV-5; 8";
5 1610000210; Ball valve; brass; full bore; 1/2" BSP; PN30; Flg x Flg or Flg x Grv or Grv x Grv; 2" drain . . . . . . . . . . . . . . . . . . . 1
kv=16.3; ul & fpr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 29 ETDDFN; Adapter elbow; brass;
6 1610000270; Ball valve; brass; full bore; 3/4" BSP; PN30; thr. DN15 fem x DN15 fem; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . 2
kv=29.5; ul & fpr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 30 ETDDMN; Adapter elbow; brass;
7 20005025; Strainer y-type; NPT 1/2"; 50 mesh; SS304 screen; thr. DN15 male x DN15 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . 1
bronze body . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 31 ETDMDFN; Adapter elbow; brass;
8 2162156; Automatic drain valve; 1/2"; thr. DN15 male x DN15fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . 3
oper: k=25 & non oper: k=5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 32 Pressure switch: CE, VDS, LPCB, or FM approved . . . . . . . . . . . . . 1
9 Optional 280200272 pipe saddle DN20 30 x 4 mm hole 11mm. . . . 1 33 RTDMBFN; Adapter reduce; brass;
10 Optional 2850750251; Mounting plate for supervisory switch thr. DN15 male x DN8 fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . 3
fall valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 34 RTEDMN; Adapter reduce; brass;
11 406012; Elbow 3 mm x m5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 thr. DN20 male x DN15 male; nickel pl. . . . . . . . . . . . . . . . . . . . . . . 2
12 460491005; Swing type check valve 3/4". . . . . . . . . . . . . . . . . . . . . 1 35 RTEMDFN; Adapter reduce; brass;
13 522892001; Break rod station thr. DN20 male x DN15 fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . 1
model MC-1 for manual release . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 36 RTFEMN; Reduce thr. fitting; nickel pl brass;
14 59304FO; Ball valve; size 1/2"; full bore; PN40; venthole thread . . . 2 male DN20 x DN25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
15 81900211; Straight tube connector 12 mm x 1/2" male nr 37 TTDMDDFN; Adapter tee; brass;
661273 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN15 male x DN15 fem x DN15 fem; nickel pl . . . . . . . . . . . . . 5
16 923431021; Automatic shut-off valve; 38 TTEEEFN; Adap tee; brass;
Model ASV-1 for DV-5 trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN20 fem x DN20 fem x DN20 fem; nickel pl . . . . . . . . . . . . . . 2
17 Optional 997908 Supervisory switch CE/VdS/LPCB/FM or UL . . . . 1 39 TTEMEEFN; Adap tee; brass;
18 A291I2; malleable fitting; plug male; thr. DN20 male x DN20 fem x DN20 fem; nickel pl . . . . . . . . . . . . . 2
BSP thr. size 2"; galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 40 V923221002; Check valve brass;
19 A341D4; malleable fitting; union; BSP thr. 1/2" male/fem; S.S. . . . . 2 NPT 1/2" male/male; seat buna-n . . . . . . . . . . . . . . . . . . . . . . . . . . 1
20 AP100D4; pipe nipple; stainless steel 316; 1/2" x 100 mm . . . . . . . 1 41 WS00000004; Pressure relief hose;
21 AP100E4; pipe nipple; stainless steel 316; 3/4" x 100 mm . . . . . . . 1 3 x 6 length 1.2 m; transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
22 AP120D4; pipe nipple; stainless steel 316; 1/2" x 120 mm . . . . . . . 2 42 WS00000007: Copper pipe; 10 x 12 mm; length 900 mm . . . . . . . . 1
23 AP300D4; pipe nipple; stainless steel 316; 1/2" x 300 mm . . . . . . . 1 43 WS00000096; Nickel pl copper tube; 15 x 1mm for DV-5 . . . . . . . . 2
24 AP60D4; pipe nipple; stainless steel 316; 1/2" x 60 mm . . . . . . . . . 1
25 AP80E4; pipe nipple; stainless steel 316; 3/4" x 80 mm . . . . . . . . . 2

34 33
38
39 29
35 27
32
12
21 6
37 25 36
26 28 1
6 39 11
38 25 33
29
43 26 41
26 34 43 14
8 18
22 20 19
5 37
24
17 1
4 26 37
10 33
3 14 31
9 11 13
2 22 23
41 37 37
31 16 42
30 31
40 15
7
19

FIGURE 10
DN200 DV-5 DELUGE VALVE
WET PILOT ACTUATION TRIM

/96/
TFP1338
Page 14 of 26

NO. DESCRIPTION QTY. NO. DESCRIPTION QTY.

DV-5 DATASHEET
1 025500013; Water gauge; class 1.6 0-25 bar 27 AP300D4; pipe nipple; stainless steel 316; 1/2" x 300 mm . . . . . . . 1
or UL/FM 0-300 PSI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 28 AP60D4; pipe nipple; stainless steel 316; 1/2" x 60 mm . . . . . . . . . 3
2 Optional 03128601; Bolt M4 x 25 . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 29 AP80E4; pipe nipple; stainless steel 316; 3/4" x 80 mm . . . . . . . . . 2
3 Optional 05566800; Bolt M8 x 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 30 ATDDMN; Adapter fitting; brass;
4 Optional 06620086; Washer M4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 thr. DN15 x DN15 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
5 1610000210; Ball valve; brass; full bore; 1/2" BSP; PN30; 31 ATDMCON; Adapter fitting; brass;
kv=16.3; ul & fpr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 thr. DN15 male x compr.15mm; nickel pl . . . . . . . . . . . . . . . . . . . . . 4
6 1610000270; Ball valve; brass; full bore; 3/4" BSP; PN30; 32 ATEEMN; Adapter fitting; brass;
kv=29.5; ul & fpr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 thr. male DN20 x DN20; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
7 20005025; Strainer y-type; NPT 1/2"; 50 mesh; SS304 screen; 33 Deluge valve DV-5; 1-1/2" & 2'';
bronze body . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Grv x Grv or Thr x Thr; 3/4" drain . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
8 2162156; Automatic drain valve; 1/2"; 34 ETDDFN; Adapter elbow; brass;
oper: k=25 & non oper: k=5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN15 fem x DN15 fem; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . 2
9 Optional Low pressure switch; 35 ETDDMN; Adapter elbow; brass;
CE, VdS, LPCB or FM approved . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN15 male x DN15 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . 1
10 280200212; Pipe saddle DN15; mat: electro zinc plated . . . . . . . . . 1 36 ETDMDFN; Adapter elbow; brass;
11 Optional 280200272 pipe saddle DN20 30 x 4 mm hole 11mm. . . . 1 thr. DN15 male x DN15fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . 4
12 Optional 2850750251; Mounting plate for supervisory switch 37 ETEEMN; Adapter elbow; brass;
fall valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 thr. DN20 male x DN20 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . 1
13 406012; Elbow 3 mm x m5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 38 PTDN; Plug; brass; thr. DN15 male; nickel pl . . . . . . . . . . . . . . . . . 1
14 460491005; Swing type check valve 3/4". . . . . . . . . . . . . . . . . . . . . 1 39 Pressure switch: CE, VDS, LPCB, or FM approved . . . . . . . . . . . . . 1
15 522801001; Dry pilot actuator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 40 RTDMBFN; Adapter reduce; brass;
16 522892001; Break rod station thr. DN15 male x DN8 fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . 5
model MC-1 for manual release . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 41 RTEDMN; Adapter reduce; brass;
17 59304FO; Ball valve; size 1/2"; full bore; PN40; venthole thread . . . 3 thr. DN20 male x DN15 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . 2
18 81900211; Straight tube connector 12 mm x 1/2" male nr 42 RTEMDFN; Adapter reduce; brass;
661273 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 thr. DN20 male x DN15 fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . 1
19 Air pressure gauge 0-10 bar; 43 TTDMDDFN; Adapter tee; brass;
fm&ul approved; 0-250 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN15 male x DN15 fem x DN15 fem; nickel pl . . . . . . . . . . . . . 9
20 923431020; Pressure relief valve; 44 TTEEEFN; Adap tee; brass;
NPT1/4"; set to relief at 45 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN20 fem x DN20 fem x DN20 fem; nickel pl . . . . . . . . . . . . . . 2
21 923431021; Automatic shut-off valve; 45 TTEMEEFN; Adap tee; brass;
Model ASV-1 for DV-5 trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN20 male x DN20 fem x DN20 fem; nickel pl . . . . . . . . . . . . . 2
22 Optional 997908 Supervisory switch CE/VdS/LPCB/FM or UL . . . . 2 46 V923221002; Check valve brass;
23 A291E2; malleable fitting; plug male; NPT 1/2" male/male; seat buna-n . . . . . . . . . . . . . . . . . . . . . . . . . . 1
BSP thr. size 3/4"; galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 47 WS00000004; Pressure relief hose;
24 A341D4; malleable fitting; union; BSP thr. 1/2" male/fem; S.S. . . . . 2 3 x 6 length 1.2 m; transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
25 AP100E4; pipe nipple; stainless steel 316; 3/4" x 100 mm . . . . . . . 1 48 WS00000007: Copper pipe; 10 x 12 mm; length 900 mm . . . . . . . . 2
26 AP180D4; pipe nipple; stainless steel 316; 1/2" x 180 mm . . . . . . . 1 49 WS00000096; Nickel pl copper tube; 15 x 1mm for DV-5 . . . . . . . . 2

5 22 12 10 4 3 2
9

20 19
28
38
1
13 40
36
40
41 40 43
44 47 17
43
45 34 43
42 32 30
39 48
14
25 6 18
43 43 1
29 32 15
13
31
45 33 34 37 40
6
44 29 28 31 47
49 17
49
31 41
23 47 43
8 28
30 1
5 31
22 40 43
4
17 36
12 13
3 27 16
26
11
2 47 43 43
36 21
35
46 48
36
7 18
24

FIGURE 11
DN40 and DN50 DV-5 DELUGE VALVES
DRY PILOT ACTUATION TRIM

/97/
TFP1338
Page 15 of 26

NO. DESCRIPTION QTY. NO. DESCRIPTION QTY.


DV-5 DATASHEET

1 025500013; Water gauge; class 1.6 0-25 bar 22 AP60D4; pipe nipple; stainless steel 316; 1/2" x 60 mm . . . . . . . . . 2
or UL/FM 0-300 PSI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 24 AP80D4; pipe nipple; stainless steel 316; 1/2" x 80 mm . . . . . . . . . 2
2 Optional 03128601; Bolt M4 x 25 . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 25 AP80E4; pipe nipple; stainless steel 316; 3/4" x 80 mm . . . . . . . . . 2
3 Optional 05566800; Bolt M8 x 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 31 ATDDMN; Adapter fitting; brass;
4 Optional 06620086; Washer M4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 thr. DN15 x DN15 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
5 1610000210; Ball valve; brass; full bore; 1/2" BSP; PN30; 32 ATDMCON; Adapter fitting; brass;
kv=16.3; ul & fpr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 thr. DN15 male x compr.15mm; nickel pl . . . . . . . . . . . . . . . . . . . . . 4
6 1610000270; Ball valve; brass; full bore; 3/4" BSP; PN30; 33 ATEEMN; Adapter fitting; brass;
kv=29.5; ul & fpr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 thr. male DN20 x DN20; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
7 20005025; Strainer y-type; NPT 1/2"; 50 mesh; SS304 screen; 34 Deluge valve DV-5; 3'';
bronze body . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Flg x Flg or Flg x Grv or Grv x Grv; 1-1/4" drain. . . . . . . . . . . . . . . . 1
8 2162156; Automatic drain valve; 1/2"; 35 ETDDFN; Adapter elbow; brass;
oper: k=25 & non oper: k=5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN15 fem x DN15 fem; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . 2
9 Optional Low pressure switch; 36 ETDDMN; Adapter elbow; brass;
CE, VdS, LPCB or FM approved . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN15 male x DN15 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . 1
10 280200212; Pipe saddle DN15; mat: electro zinc plated . . . . . . . . . 1 37 ETDMDFN; Adapter elbow; brass;
11 Optional 280200272 pipe saddle DN20 30 x 4 mm hole 11mm. . . . 1 thr. DN15 male x DN15fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . 4
12 Optional 2850750251; Mounting plate for supervisory switch 38 ETEEMN; Adapter elbow; brass;
fall valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 thr. DN20 male x DN20 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . 1
13 406012; Elbow 3 mm x m5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 39 PTDN; Plug; brass; thr. DN15 male; nickel pl . . . . . . . . . . . . . . . . . 1
14 460491005; Swing type check valve 3/4". . . . . . . . . . . . . . . . . . . . . 1 40 Pressure switch: CE, VDS, LPCB, or FM approved . . . . . . . . . . . . . 1
15 522801001; Dry pilot actuator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 41 RTDMBFN; Adapter reduce; brass;
16 522892001; Break rod station thr. DN15 male x DN8 fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . 5
model MC-1 for manual release . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 42 RTEDMN; Adapter reduce; brass;
17 59304FO; Ball valve; size 1/2"; full bore; PN40; venthole thread . . . 3 thr. DN20 male x DN15 male; nickel pl. . . . . . . . . . . . . . . . . . . . . . . 2
18 81900211; Straight tube connector 12 mm x 1/2" male nr 43 RTEMDFN; Adapter reduce; brass;
661273 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 thr. DN20 male x DN15 fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . 1
19 Air pressure gauge 0-10 bar; 44 TTDMDDFN; Adapter tee; brass;
fm&ul approved; 0-250 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN15 male x DN15 fem x DN15 fem; nickel pl . . . . . . . . . . . . . 9
20 923431020; Pressure relief valve; 45 TTEEEFN; Adap tee; brass;
NPT1/4"; set to relief at 45 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN20 fem x DN20 fem x DN20 fem; nickel pl . . . . . . . . . . . . . . 2
21 923431021; Automatic shut-off valve; 46 TTEMEEFN; Adap tee; brass;
Model ASV-1 for DV-5 trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN20 male x DN20 fem x DN20 fem; nickel pl . . . . . . . . . . . . . 2
22 Optional 997908 Supervisory switch CE/VdS/LPCB/FM or UL . . . . 2 47 V923221002; Check valve brass;
23 A291G2; malleable fitting; plug male; NPT 1/2" male/male; seat buna-n . . . . . . . . . . . . . . . . . . . . . . . . . . 1
BSP thr. size 1-1/4"; galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 48 WS00000004; Pressure relief hose;
24 A341D4; malleable fitting; union; BSP thr. 1/2" male/fem; S.S. . . . . 2 3 x 6 length 1.2 m; transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
25 AP100E4; pipe nipple; stainless steel 316; 3/4" x 100 mm . . . . . . . 1 44 WS00000007: Copper pipe; 10 x 12 mm; length 900 mm . . . . . . . . 2
26 AP140D4; pipe nipple; stainless steel 316; 1/2" x 140 mm . . . . . . . 1 45 WS00000096; Nickel pl copper tube; 15 x 1mm for DV-5 . . . . . . . . 2
27 AP300D4; pipe nipple; stainless steel 316; 1/2" x 300 mm . . . . . . . 1

4 10 12 22 5 20 19
2 3
1 28 41 13 41

42 41 39 17
45 37
46 35 44
44 9 31
43 33 44 48
40
14 44
25 6 49
44 30 18
33
32 15 1
34 38
6 46 13
45 30 41
35
50 32 48
32 42 50 17
8 23
29 29 24
5 44
28
22 1
4 32 44
12 41
3 17 37
11 13 16
2 26 27
48 44 44
37 21 49
36 37
47 18
7
24

FIGURE 12
DN80 DV-5 DELUGE VALVE
DRY PILOT ACTUATION TRIM

/98/
TFP1338
Page 16 of 26

NO. DESCRIPTION QTY. NO. DESCRIPTION QTY.

DV-5 DATASHEET
1 025500013; Water gauge; class 1.6 0-25 bar 28 AP60D4; pipe nipple; stainless steel 316; 1/2" x 60 mm . . . . . . . . . 3
or UL/FM 0-300 PSI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 29 AP80E4; pipe nipple; stainless steel 316; 3/4" x 80 mm . . . . . . . . . 2
2 Optional 03128601; Bolt M4 x 25 . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 30 ATDDMN; Adapter fitting; brass;
3 Optional 05566800; Bolt M8 x 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 thr. DN15 x DN15 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
4 Optional 06620086; Washer M4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 31 ATDMCON; Adapter fitting; brass;
5 1610000210; Ball valve; brass; full bore; 1/2" BSP; PN30; thr. DN15 male x compr.15mm; nickel pl . . . . . . . . . . . . . . . . . . . . . 4
kv=16.3; ul & fpr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 32 ATEEMN; Adapter fitting; brass;
6 1610000270; Ball valve; brass; full bore; 3/4" BSP; PN30; thr. male DN20 x DN20; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
kv=29.5; ul & fpr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 33 Deluge valve DV-5; 4" & 6";
7 20005025; Strainer y-type; NPT 1/2"; 50 mesh; SS304 screen; Flg x Flg or Flg x Grv or Grv x Grv; 2" drain . . . . . . . . . . . . . . . . . . . 1
bronze body . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 34 ETDDFN; Adapter elbow; brass;
8 2162156; Automatic drain valve; 1/2"; thr. DN15 fem x DN15 fem; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . 2
oper: k=25 & non oper: k=5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 35 ETDDMN; Adapter elbow; brass;
9 Optional Low pressure switch; thr. DN15 male x DN15 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . 1
CE, VdS, LPCB or FM approved . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 36 ETDMDFN; Adapter elbow; brass;
10 280200212; Pipe saddle DN15; mat: electro zinc plated . . . . . . . . . 1 thr. DN15 male x DN15fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . 4
11 Optional 280200272 pipe saddle DN20 30 x 4 mm hole 11mm. . . . 1 37 ETEEMN; Adapter elbow; brass;
12 Optional 2850750251; Mounting plate for supervisory switch thr. DN20 male x DN20 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . 1
fall valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 38 PTDN; Plug; brass; thr. DN15 male; nickel pl . . . . . . . . . . . . . . . . . 1
13 406012; Elbow 3 mm x m5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 39 Pressure switch: CE, VDS, LPCB, or FM approved . . . . . . . . . . . . . 1
14 460491005; Swing type check valve 3/4". . . . . . . . . . . . . . . . . . . . . 1 40 RTDMBFN; Adapter reduce; brass;
15 522801001; Dry pilot actuator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN15 male x DN8 fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . 5
16 522892001; Break rod station 41 RTEDMN; Adapter reduce; brass;
model MC-1 for manual release . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN20 male x DN15 male; nickel pl. . . . . . . . . . . . . . . . . . . . . . . 2
17 59304FO; Ball valve; size 1/2"; full bore; PN40; venthole thread . . . 3 42 RTEMDFN; Adapter reduce; brass;
18 81900211; Straight tube connector 12 mm x 1/2" male nr thr. DN20 male x DN15 fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . 1
661273 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 43 RTFEMN; Reduce thr. fitting; nickel pl brass;
19 Air pressure gauge 0-10 bar; male DN20 x DN25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
fm&ul approved; 0-250 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 44 TTDMDDFN; Adapter tee; brass;
20 923431020; Pressure relief valve; thr. DN15 male x DN15 fem x DN15 fem; nickel pl . . . . . . . . . . . . . 9
NPT1/4"; set to relief at 45 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 45 TTEEEFN; Adap tee; brass;
21 923431021; Automatic shut-off valve; thr. DN20 fem x DN20 fem x DN20 fem; nickel pl . . . . . . . . . . . . . . 2
Model ASV-1 for DV-5 trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 46 TTEMEEFN; Adap tee; brass;
22 Optional 997908 Supervisory switch CE/VdS/LPCB/FM or UL . . . . 2 thr. DN20 male x DN20 fem x DN20 fem; nickel pl . . . . . . . . . . . . . 2
23 A291I2; malleable fitting; plug male; 47 V923221002; Check valve brass;
BSP thr. size 2"; galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 NPT 1/2" male/male; seat buna-n . . . . . . . . . . . . . . . . . . . . . . . . . . 1
24 A341D4; malleable fitting; union; BSP thr. 1/2" male/fem; S.S. . . . . 2 48 WS00000004; Pressure relief hose;
25 AP100E4; pipe nipple; stainless steel 316; 3/4" x 100 mm . . . . . . . 1 3 x 6 length 1.2 m; transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
26 AP120D4; pipe nipple; stainless steel 316; 1/2" x 120 mm . . . . . . . 2 49 WS00000007: Copper pipe; 10 x 12 mm; length 900 mm . . . . . . . . 2
27 AP300D4; pipe nipple; stainless steel 316; 1/2" x 300 mm . . . . . . . 1 50 WS00000096; Nickel pl copper tube; 15 x 1mm for DV-5 . . . . . . . . 2

22 12 10 5 20 19
1
4 3
28 40 13 40
41 40 2
45 38 17
46 34 36
42 32 44 44
39 9 30
14 44 48
25 6
44 29 44
43 49
31 18
29 15 1
6 33 37
45 29 13
50 40
34
31 41 48
28 31
8 17
26 23 50
5
1 24 44
22
28
4 40
12 31 44
3 17
13
11 36
2 26 16
48 44 27
36 44
21 49
35 36
47 18
7
24

FIGURE 13
DN100 and DN150 DV-5 DELUGE VALVES
DRY PILOT ACTUATION TRIM

/99/
TFP1338
Page 17 of 26

NO. DESCRIPTION QTY. NO. DESCRIPTION QTY.


DV-5 DATASHEET

1 025500013; Water gauge; class 1.6 0-25 bar 28 AP300D4; pipe nipple; stainless steel 316; 1/2" x 300 mm . . . . . . . 1
or UL/FM 0-300 PSI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 29 AP60D4; pipe nipple; stainless steel 316; 1/2" x 60 mm . . . . . . . . . 2
2 Optional 03128601; Bolt M4 x 25 . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 30 AP80E4; pipe nipple; stainless steel 316; 3/4" x 80 mm . . . . . . . . . 2
3 Optional 05566800; Bolt M8 x 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 31 ATDDMN; Adapter fitting; brass;
4 Optional 06620086; Washer M4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 thr. DN15 x DN15 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
5 1610000210; Ball valve; brass; full bore; 1/2" BSP; PN30; 32 ATDMCON; Adapter fitting; brass;
kv=16.3; ul & fpr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 thr. DN15 male x compr.15mm; nickel pl . . . . . . . . . . . . . . . . . . . . . 4
6 1610000270; Ball valve; brass; full bore; 3/4" BSP; PN30; 33 ATEEMN; Adapter fitting; brass;
kv=29.5; ul & fpr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 thr. male DN20 x DN20; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
7 20005025; Strainer y-type; NPT 1/2"; 50 mesh; SS304 screen; 34 Deluge valve DV-5; 8";
bronze body . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Flg x Flg or Flg x Grv or Grv x Grv; 2" drain . . . . . . . . . . . . . . . . . . . 1
8 2162156; Automatic drain valve; 1/2"; 35 ETDDFN; Adapter elbow; brass;
oper: k=25 & non oper: k=5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN15 fem x DN15 fem; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . 2
9 Optional Low pressure switch; 36 ETDDMN; Adapter elbow; brass;
CE, VdS, LPCB or FM approved . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN15 male x DN15 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . 1
10 280200212; Pipe saddle DN15; mat: electro zinc plated . . . . . . . . . 1 37 ETDMDFN; Adapter elbow; brass;
11 Optional 280200272 pipe saddle DN20 30 x 4 mm hole 11mm. . . . 1 thr. DN15 male x DN15fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . 4
12 Optional 2850750251; Mounting plate for supervisory switch 38 ETEEMN; Adapter elbow; brass;
fall valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 thr. DN20 male x DN20 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . 1
13 406012; Elbow 3 mm x m5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 39 PTDN; Plug; brass; thr. DN15 male; nickel pl . . . . . . . . . . . . . . . . . 1
14 460491005; Swing type check valve 3/4". . . . . . . . . . . . . . . . . . . . . 1 40 Pressure switch: CE, VDS, LPCB, or FM approved . . . . . . . . . . . . . 1
15 522801001; Dry pilot actuator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 41 RTDMBFN; Adapter reduce; brass;
16 522892001; Break rod station thr. DN15 male x DN8 fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . 5
model MC-1 for manual release . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 42 RTEDMN; Adapter reduce; brass;
17 59304FO; Ball valve; size 1/2"; full bore; PN40; venthole thread . . . 3 thr. DN20 male x DN15 male; nickel pl. . . . . . . . . . . . . . . . . . . . . . . 2
43 RTEMDFN; Adapter reduce; brass;
18 81900211; Straight tube connector 12 mm x 1/2" male nr thr. DN20 male x DN15 fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . 1
661273 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 44 RTFEMN; Reduce thr. fitting; nickel pl brass;
19 Air pressure gauge 0-10 bar; male DN20 x DN25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
fm&ul approved; 0-250 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 45 TTDMDDFN; Adapter tee; brass;
20 923431020; Pressure relief valve; thr. DN15 male x DN15 fem x DN15 fem; nickel pl . . . . . . . . . . . . . 9
NPT1/4"; set to relief at 45 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 46 TTEEEFN; Adap tee; brass;
21 923431021; Automatic shut-off valve; thr. DN20 fem x DN20 fem x DN20 fem; nickel pl . . . . . . . . . . . . . . 2
Model ASV-1 for DV-5 trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 47 TTEMEEFN; Adap tee; brass;
22 Optional 997908 Supervisory switch CE/VdS/LPCB/FM or UL . . . . 2 thr. DN20 male x DN20 fem x DN20 fem; nickel pl . . . . . . . . . . . . . 2
23 A291I2; malleable fitting; plug male; 48 V923221002; Check valve brass;
BSP thr. size 2"; galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 NPT 1/2" male/male; seat buna-n. . . . . . . . . . . . . . . . . . . . . . . . . . . 1
24 A341D4; malleable fitting; union; BSP thr. 1/2" male/fem; S.S. . . . . 2 49 WS00000004; Pressure relief hose;
25 AP100D4; pipe nipple; stainless steel 316; 1/2" x 100 mm . . . . . . . 1 3 x 6 length 1.2 m; transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
26 AP100E4; pipe nipple; stainless steel 316; 3/4" x 100 mm . . . . . . . 1 50 WS00000007: Copper pipe; 10 x 12 mm; length 900 mm . . . . . . . . 2
27 AP120D4; pipe nipple; stainless steel 316; 1/2" x 120 mm . . . . . . . 2 51 WS00000096; Nickel pl copper tube; 15 x 1mm for DV-5 . . . . . . . . 2

5 20 19
1 22 12 10
4 3 29 41 13 41
42 41
46 2
47 35 39 17
37
43 33
40 45 45
14 9 31
26 45 49
6
45 30 44 45
50 1
32 34
47 18 38 13
6 15
46 30 41
51 35 32 49
32 42 51 17
8 23
27 25 24
5 45
29
22 1
4 32 45
12 41
3 17 37
11 13 16
2 27 28
49 45 45
37 21 50
36 37
48 18
7
24

FIGURE 14
DN200 DV-5 DELUGE VALVE
DRY PILOT ACTUATION TRIM

/100/
TFP1338
Page 18 of 26

NO. DESCRIPTION QTY. NO. DESCRIPTION QTY.

DV-5 DATASHEET
1 025500013; Water gauge; class 1.6 0-25 bar 25 AP60D4; pipe nipple; stainless steel 316; 1/2" x 60 mm . . . . . . . . . 2
or UL/FM 0-300 PSI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 26 AP80E4; pipe nipple; stainless steel 316; 3/4" x 80 mm . . . . . . . . . 2
2 Optional 03128601; Bolt M4 x 25 . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 27 ATDDMN; Adapter fitting; brass;
3 Optional 05566800; Bolt M8 x 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 thr. DN15 x DN15 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
4 Optional 06620086; Washer M4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 28 ATDMCON; Adapter fitting; brass;
5 1610000210; Ball valve; brass; full bore; 1/2" BSP; PN30; thr. DN15 male x compr.15mm; nickel pl . . . . . . . . . . . . . . . . . . . . . 4
kv=16.3; ul & fpr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 29 ATEEMN; Adapter fitting; brass;
6 1610000270; Ball valve; brass; full bore; 3/4" BSP; PN30; thr. male DN20 x DN20; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
kv=29.5; ul & fpr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 30 Deluge valve DV-5; 1-1/2" & 2'';
7 20005025; Strainer y-type; NPT 1/2"; 50 mesh; SS304 screen; Grv x Grv or Thr x Thr; 3/4" drain . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
bronze body . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 31 ETDDFN; Adapter elbow; brass;
8 2162156; Automatic drain valve; 1/2"; thr. DN15 fem x DN15 fem; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . 2
oper: k=25 & non oper: k=5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 32 ETDDMN; Adapter elbow; brass;
9 Optional 280200272 pipe saddle DN20 30 x 4 mm hole 11mm. . . . 1 thr. DN15 male x DN15 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . 1
10 Optional 2850750251; Mounting plate for supervisory switch 33 ETDMDFN; Adapter elbow; brass;
fall valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN15 male x DN15fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . 3
11 406012; Elbow 3 mm x m5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 34 Pressure switch: CE, VDS, LPCB, or FM approved . . . . . . . . . . . . . 1
12 460491005; Swing type check valve 3/4". . . . . . . . . . . . . . . . . . . . . 1 35 RTDMBFN; Adapter reduce; brass;
13 Solenoid valve; 1/2" 12,1 bar or 17.2 bar . . . . . . . . . . . . . . . . . . . . . 1 thr. DN15 male x DN8 fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . 3
14 522892001; Break rod station 36 RTEDMN; Adapter reduce; brass;
model MC-1 for manual release . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN20 male x DN15 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . 2
15 59304FO; Ball valve; size 1/2"; full bore; PN40; venthole thread . . . 2 37 RTEMDFN; Adapter reduce; brass;
16 81900211; Straight tube connector 12 mm x 1/2" male nr thr. DN20 male x DN15 fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . 1
661273 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 38 TTDMDDFN; Adapter tee; brass;
17 923431021; Automatic shut-off valve; thr. DN15 male x DN15 fem x DN15 fem; nickel pl . . . . . . . . . . . . . 5
Model ASV-1 for DV-5 trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 39 TTEEEFN; Adap tee; brass;
18 Optional 997908 Supervisory switch CE/VdS/LPCB/FM or UL . . . . 1 thr. DN20 fem x DN20 fem x DN20 fem; nickel pl . . . . . . . . . . . . . . 2
19 A280D2; malleable fitting; nipple male; 40 TTEMEEFN; Adap tee; brass;
BSP size 1/2"; galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN20 male x DN20 fem x DN20 fem; nickel pl . . . . . . . . . . . . . 2
20 A291E2; malleable fitting; plug male; 41 V923221002; Check valve brass;
BSP thr. size 3/4"; galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 NPT 1/2" male/male; seat buna-n . . . . . . . . . . . . . . . . . . . . . . . . . . 1
21 A341D4; malleable fitting; union; BSP thr. 1/2" male/fem; S.S. . . . . 2 42 WS00000004; Pressure relief hose;
22 AP100E4; pipe nipple; stainless steel 316; 3/4" x 100 mm . . . . . . . 1 3 x 6 length 1.2 m; transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
23 AP180D4; pipe nipple; stainless steel 316; 1/2" x 180 mm . . . . . . . 1 43 WS00000007: Copper pipe; 10 x 12 mm; length 900 mm . . . . . . . . 2
24 AP300D4; pipe nipple; stainless steel 316; 1/2" x 300 mm . . . . . . . 1 44 WS00000096; Nickel pl copper tube; 15 x 1mm for DV-5 . . . . . . . . 2

36 35
39
40 31 43
37 29 16 13
34
12
22 6
38 19 1
26 29 11
28
40 30 31 35
6
39 26 25 28 42
44 15
44
28 36
20 21 38
8 25
27 1
5 28
18 35 38
4
15 33
10 11
3 24 14
23
9
2 42 38 38
33 17
32
41 43
33
7 16
21

FIGURE 15
DN40 and DN50 DV-5 DELUGE VALVES
ELECTRIC ACTUATION TRIM

/101/
TFP1338
Page 19 of 26

NO. DESCRIPTION QTY. NO. DESCRIPTION QTY.


DV-5 DATASHEET

1 025500013; Water gauge; class 1.6 0-25 bar 25 AP60D4; pipe nipple; stainless steel 316; 1/2" x 60 mm . . . . . . . . . 1
or UL/FM 0-300 PSI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 26 AP80D4; pipe nipple; stainless steel 316; 1/2" x 80 mm . . . . . . . . . 2
2 Optional 03128601; Bolt M4 x 25 . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 27 AP80E4; pipe nipple; stainless steel 316; 3/4" x 80 mm . . . . . . . . . 2
3 Optional 05566800; Bolt M8 x 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 28 ATDMCON; Adapter fitting; brass;
4 Optional 06620086; Washer M4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 thr. DN15 male x compr.15mm; nickel pl . . . . . . . . . . . . . . . . . . . . . 4
5 1610000210; Ball valve; brass; full bore; 1/2" BSP; PN30; 29 ATEEMN; Adapter fitting; brass;
kv=16.3; ul & fpr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 thr. male DN20 x DN20; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
6 1610000270; Ball valve; brass; full bore; 3/4" BSP; PN30; 30 Deluge valve DV-5; 3'';
kv=29.5; ul & fpr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Flg x Flg or Flg x Grv or Grv x Grv; 1-1/4" drain. . . . . . . . . . . . . . . . 1
7 20005025; Strainer y-type; NPT 1/2"; 50 mesh; SS304 screen; 31 ETDDFN; Adapter elbow; brass;
bronze body . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN15 fem x DN15 fem; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . 2
8 2162156; Automatic drain valve; 1/2"; 32 ETDDMN; Adapter elbow; brass;
oper: k=25 & non oper: k=5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN15 male x DN15 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . 1
9 Optional 280200272 pipe saddle DN20 30 x 4 mm hole 11mm. . . . 1 33 ETDMDFN; Adapter elbow; brass;
10 Optional 2850750251; Mounting plate for supervisory switch thr. DN15 male x DN15fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . 3
fall valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 34 Pressure switch: CE, VDS, LPCB, or FM approved . . . . . . . . . . . . . 1
11 406012; Elbow 3 mm x m5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 35 RTDMBFN; Adapter reduce; brass;
12 460491005; Swing type check valve 3/4". . . . . . . . . . . . . . . . . . . . . 1 thr. DN15 male x DN8 fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . 3
13 Solenoid valve; 1/2" 12,1 bar or 17.2 bar . . . . . . . . . . . . . . . . . . . . . 1 36 RTEDMN; Adapter reduce; brass;
14 522892001; Break rod station thr. DN20 male x DN15 male; nickel pl. . . . . . . . . . . . . . . . . . . . . . . 2
model MC-1 for manual release . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 37 RTEMDFN; Adapter reduce; brass;
15 59304FO; Ball valve; size 1/2"; full bore; PN40; venthole thread . . . 2 thr. DN20 male x DN15 fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . 1
16 81900211; Straight tube connector 12 mm x 1/2" male nr 38 TTDMDDFN; Adapter tee; brass;
661273 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 thr. DN15 male x DN15 fem x DN15 fem; nickel pl . . . . . . . . . . . . . 5
17 923431021; Automatic shut-off valve; 39 TTEEEFN; Adap tee; brass;
Model ASV-1 for DV-5 trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN20 fem x DN20 fem x DN20 fem; nickel pl . . . . . . . . . . . . . . 2
18 Optional 997908 Supervisory switch CE/VdS/LPCB/FM or UL . . . . 1 40 TTEMEEFN; Adap tee; brass;
19 A280D2; malleable fitting; nipple male; thr. DN20 male x DN20 fem x DN20 fem; nickel pl . . . . . . . . . . . . . 2
BSP size 1/2"; galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 41 V923221002; Check valve brass;
20 A291G2; malleable fitting; plug male; NPT 1/2" male/male; seat buna-n . . . . . . . . . . . . . . . . . . . . . . . . . . 1
BSP thr. size 1-1/4"; galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 42 WS00000004; Pressure relief hose;
21 A341D4; malleable fitting; union; BSP thr. 1/2" male/fem; S.S. . . . . 2 3 x 6 length 1.2 m; transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
22 AP100E4; pipe nipple; stainless steel 316; 3/4" x 100 mm . . . . . . . 1 43 WS00000007: Copper pipe; 10 x 12 mm; length 900 mm . . . . . . . . 2
23 AP140D4; pipe nipple; stainless steel 316; 1/2" x 140 mm . . . . . . . 1 44 WS00000096; Nickel pl copper tube; 15 x 1mm for DV-5 . . . . . . . . 2
24 AP300D4; pipe nipple; stainless steel 316; 1/2" x 300 mm . . . . . . . 1

36 35
39
40 31
37 29
34 43
12
22 16 13
6
38 27 29
28 19 1
40 30 11
6
39 27 31 35
44 28 42
28 36 44 15
8 20
26 26 21
5 38
25
18 1
4 28 38
10 35
3 15 33
9 11 14
2 23 24
42 38 38
33 17 43
32 33
41 16
7
21

FIGURE 16
DN80 DV-5 DELUGE VALVE
ELECTRIC ACTUATION TRIM

/102/
TFP1338
Page 20 of 26

NO. DESCRIPTION QTY. NO. DESCRIPTION QTY.

DV-5 DATASHEET
1 025500013; Water gauge; class 1.6 0-25 bar 26 ATDDMN; Adapter fitting; brass;
or UL/FM 0-300 PSI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 thr. DN15 x DN15 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2 Optional 03128601; Bolt M4 x 25 . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 27 ATDMCON; Adapter fitting; brass;
3 Optional 05566800; Bolt M8 x 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 thr. DN15 male x compr.15mm; nickel pl . . . . . . . . . . . . . . . . . . . . . 4
4 Optional 06620086; Washer M4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 28 ATEEMN; Adapter fitting; brass;
5 1610000210; Ball valve; brass; full bore; 1/2" BSP; PN30; thr. male DN20 x DN20; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
kv=16.3; ul & fpr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 29 Deluge valve DV-5; 4'' & 6";
6 1610000270; Ball valve; brass; full bore; 3/4" BSP; PN30; Flg x Flg or Flg x Grv or Grv x Grv; 2" drain . . . . . . . . . . . . . . . . . . . 1
kv=29.5; ul & fpr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 30 ETDDFN; Adapter elbow; brass;
7 20005025; Strainer y-type; NPT 1/2"; 50 mesh; SS304 screen; thr. DN15 fem x DN15 fem; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . 2
bronze body . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 31 ETDDMN; Adapter elbow; brass;
8 2162156; Automatic drain valve; 1/2"; thr. DN15 male x DN15 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . 1
oper: k=25 & non oper: k=5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 32 ETDMDFN; Adapter elbow; brass;
9 Optional 280200272 pipe saddle DN20 30 x 4 mm hole 11mm. . . . 1 thr. DN15 male x DN15fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . 3
10 Optional 2850750251; Mounting plate for supervisory switch 33 Pressure switch: CE, VDS, LPCB, or FM approved . . . . . . . . . . . . . 1
fall valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 34 RTDMBFN; Adapter reduce; brass;
11 406012; Elbow 3 mm x m5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 thr. DN15 male x DN8 fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . 3
12 460491005; Swing type check valve 3/4". . . . . . . . . . . . . . . . . . . . . 1 35 RTEDMN; Adapter reduce; brass;
13 Solenoid valve; 1/2" 12,1 bar or 17.2 bar . . . . . . . . . . . . . . . . . . . . . 1 thr. DN20 male x DN15 male; nickel pl. . . . . . . . . . . . . . . . . . . . . . . 2
14 522892001; Break rod station 36 RTEMDFN; Adapter reduce; brass;
model MC-1 for manual release . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN20 male x DN15 fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . 1
15 59304FO; Ball valve; size 1/2"; full bore; PN40; venthole thread . . . 2 37 RTFEMN; Reduce thr. fitting; nickel pl brass;
16 81900211; Straight tube connector 12 mm x 1/2" male nr male DN20 x DN25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
661273 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 38 TTDMDDFN; Adapter tee; brass;
17 923431021; Automatic shut-off valve; thr. DN15 male x DN15 fem x DN15 fem; nickel pl . . . . . . . . . . . . . 5
Model ASV-1 for DV-5 trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 39 TTEEEFN; Adap tee; brass;
18 Optional 997908 Supervisory switch CE/VdS/LPCB/FM or UL . . . . 1 thr. DN20 fem x DN20 fem x DN20 fem; nickel pl . . . . . . . . . . . . . . 2
19 A291I2; malleable fitting; plug male; 40 TTEMEEFN; Adap tee; brass;
BSP thr. size 2"; galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN20 male x DN20 fem x DN20 fem; nickel pl . . . . . . . . . . . . . 2
20 A341D4; malleable fitting; union; BSP thr. 1/2" male/fem; S.S. . . . . 2 41 V923221002; Check valve brass;
21 AP100E4; pipe nipple; stainless steel 316; 3/4" x 100 mm . . . . . . . 1 NPT 1/2" male/male; seat buna-n . . . . . . . . . . . . . . . . . . . . . . . . . . 1
22 AP120D4; pipe nipple; stainless steel 316; 1/2" x 120 mm . . . . . . . 2 42 WS00000004; Pressure relief hose;
23 AP300D4; pipe nipple; stainless steel 316; 1/2" x 300 mm . . . . . . . 1 3 x 6 length 1.2 m; transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
24 AP60D4; pipe nipple; stainless steel 316; 1/2" x 60 mm . . . . . . . . . 2 43 WS00000007: Copper pipe; 10 x 12 mm; length 900 mm . . . . . . . . 2
25 AP80E4; pipe nipple; stainless steel 316; 3/4" x 80 mm . . . . . . . . . 2 44 WS00000096; Nickel pl copper tube; 15 x 1mm for DV-5 . . . . . . . . 2

35 34
39
40 30
36 28
33
12 43
21 6
38 25 16 13
28
27
40 26 1
6 29
39 25 11
44 34
30
27 35 42
24 27
8 15
22 19 44
5
1 20 38
18
24
4 34
10 27 38
3 15
11
9 32
2 22 14
42 38 23
32 38
17 43
31 32
41 16
7
20

FIGURE 17
DN100 and DN150 DV-5 DELUGE VALVES
ELECTRIC ACTUATION TRIM

/103/
TFP1338
Page 21 of 26

NO. DESCRIPTION QTY. NO. DESCRIPTION QTY.


DV-5 DATASHEET

1 025500013; Water gauge; class 1.6 0-25 bar 26 AP60D4; pipe nipple; stainless steel 316; 1/2" x 60 mm . . . . . . . . . 1
or UL/FM 0-300 PSI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 27 AP80E4; pipe nipple; stainless steel 316; 3/4" x 80 mm . . . . . . . . . 2
2 Optional 03128601; Bolt M4 x 25 . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 28 ATDMCON; Adapter fitting; brass;
3 Optional 05566800; Bolt M8 x 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 thr. DN15 male x compr.15mm; nickel pl . . . . . . . . . . . . . . . . . . . . . 4
4 Optional 06620086; Washer M4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 29 ATEEMN; Adapter fitting; brass;
5 1610000210; Ball valve; brass; full bore; 1/2" BSP; PN30; thr. male DN20 x DN20; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
kv=16.3; ul & fpr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 30 Deluge valve DV-5; 8";
6 1610000270; Ball valve; brass; full bore; 3/4" BSP; PN30; Flg x Flg or Flg x Grv or Grv x Grv; 2" drain . . . . . . . . . . . . . . . . . . . 1
kv=29.5; ul & fpr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 31 ETDDFN; Adapter elbow; brass;
7 20005025; Strainer y-type; NPT 1/2"; 50 mesh; SS304 screen; thr. DN15 fem x DN15 fem; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . 2
bronze body . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 32 ETDDMN; Adapter elbow; brass;
8 2162156; Automatic drain valve; 1/2"; thr. DN15 male x DN15 male; nickel pl . . . . . . . . . . . . . . . . . . . . . . 1
oper: k=25 & non oper: k=5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 33 ETDMDFN; Adapter elbow; brass;
9 Optional 280200272 pipe saddle DN20 30 x 4 mm hole 11mm. . . . 1 thr. DN15 male x DN15fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . 3
10 Optional 2850750251; Mounting plate for supervisory switch 34 Pressure switch: CE, VDS, LPCB, or FM approved . . . . . . . . . . . . . 1
fall valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 35 RTDMBFN; Adapter reduce; brass;
11 406012; Elbow 3 mm x m5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 thr. DN15 male x DN8 fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . . 3
12 460491005; Swing type check valve 3/4". . . . . . . . . . . . . . . . . . . . . 1 36 RTEDMN; Adapter reduce; brass;
13 Solenoid valve; 1/2" 12,1 bar or 17.2 bar . . . . . . . . . . . . . . . . . . . . . 1 thr. DN20 male x DN15 male; nickel pl. . . . . . . . . . . . . . . . . . . . . . . 2
14 522892001; Break rod station 37 RTEMDFN; Adapter reduce; brass;
model MC-1 for manual release . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN20 male x DN15 fem.; nickel pl . . . . . . . . . . . . . . . . . . . . . . . 1
15 59304FO; Ball valve; size 1/2"; full bore; PN40; venthole thread . . . 2 38 RTFEMN; Reduce thr. fitting; nickel pl brass;
16 81900211; Straight tube connector 12 mm x 1/2" male nr male DN20 x DN25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
661273 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 39 TTDMDDFN; Adapter tee; brass;
17 923431021; Automatic shut-off valve; thr. DN15 male x DN15 fem x DN15 fem; nickel pl . . . . . . . . . . . . . 5
Model ASV-1 for DV-5 trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 40 TTEEEFN; Adap tee; brass;
18 Optional 997908 Supervisory switch CE/VdS/LPCB/FM or UL . . . . 1 thr. DN20 fem x DN20 fem x DN20 fem; nickel pl . . . . . . . . . . . . . . 2
19 A280D2; malleable fitting; nipple male; 41 TTEMEEFN; Adap tee; brass;
BSP size 1/2"; galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 thr. DN20 male x DN20 fem x DN20 fem; nickel pl . . . . . . . . . . . . . 2
20 A291I2; malleable fitting; plug male; 42 V923221002; Check valve brass;
BSP thr. size 2"; galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 NPT 1/2" male/male; seat buna-n . . . . . . . . . . . . . . . . . . . . . . . . . . 1
21 A341D4; malleable fitting; union; BSP thr. 1/2" male/fem; S.S. . . . . 2 43 WS00000004; Pressure relief hose;
22 AP100D4; pipe nipple; stainless steel 316; 1/2" x 100 mm . . . . . . . 1 3 x 6 length 1.2 m; transparent . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
23 AP100E4; pipe nipple; stainless steel 316; 3/4" x 100 mm . . . . . . . 1 40 WS00000007: Copper pipe; 10 x 12 mm; length 900 mm . . . . . . . . 2
24 AP120D4; pipe nipple; stainless steel 316; 1/2" x 120 mm . . . . . . . 2 41 WS00000096; Nickel pl copper tube; 15 x 1mm for DV-5 . . . . . . . . 2
25 AP300D4; pipe nipple; stainless steel 316; 1/2" x 300 mm . . . . . . . 1

36 35
40
41 31
37 29
34 44
12
23 16 13
6
39 27 38
28 30 19 1
6 41 11
40 27 35
31
45 28 43
28 36 45 15
8 20
24 22 21
5 39
26
18 1
4 28 39
10 35
3 15 33
9 11 14
2 24 25
43 39 39
33 17 44
32 33
42 16
7
21

FIGURE 18
DN200 DV-5 DELUGE VALVE
ELECTRIC ACTUATION TRIM

/104/
TFP1338
Page 22 of 26

Installation Step 9. The Low Pressure Alarm Switch


for Dry Pilot Actuation is to be adjusted
At this time make certain that the
Pressure Gauge Valves and the Alarm

DV-5 DATASHEET
TYCO DV-5 Deluge Valves are to as follows: Control Valve (H) are open.
be installed in accordance with this low pressure alarm setting at Step 4. Depress the plunger of the
section. approximately 0,4 bar below the Automatic Drain Valve (F) to verify that
minimum pilot line service pressure it is open and that the DV-5 Valve is
NOTICE requirement shown in Graph B completely drained.
Proper operation of the DV-5 Deluge fire alarm setting at approximately Step 5. Clean the Diaphragm Supply
Valves depends upon their trim being 1,0 bar below the minimum pilot Strainer (Q) by removing the clean-
installed in accordance with the line service pressure requirement out plug and strainer basket. The
instructions given in this technical data shown in Graph B Diaphragm Supply Strainer (Q) may be
sheet. Failure to follow the appropriate Step 10. The Pressure Relief Valve flushed out by momentarily opening the
trim diagram may prevent the DV-5 provided with the Dry Pilot Actuation Diaphragm Supply Valve (P).
Valve from functioning properly, Trim is factory set to relieve at a Step 6. Reset the actuation system.
as well as void approvals and the pressure of approximately 3,1 bar,
manufacturers warranties. Manual Actuation Push the operating
which can typically be used for a
lever up; however, do not close the
The DV-5 Valve must be installed in a maximum dry pilot actuation system
hinged cover at this time.
readily visible and accessible location. pressure of 2,8 bar. The Pressure Relief
Valve may be reset; however, it must be Wet Pilot Actuation Replace
The DV-5 Valve, associated trim, and operated pilot sprinklers and/or reset
reset to relieve at a pressure which is
wet pilot lines must be maintained at a the remote manual control stations.
in accordance with the requirements of
minimum temperature of 4C.
the authority having jurisdiction. Dry Pilot Actuation Replace operated
Heat tracing of the DV-5 Valve or its pilot sprinklers and/or reset the remote
To reset the Pressure Relief Valve, first
associated trim is not permitted. Heat manual control stations. Reestablish
loosen the jam nut and then adjust the
tracing can result in the formation of dry pilot pneumatic pressure.
cap accordingly, clockwise for a higher
hardened mineral deposits that are
pressure setting or counter clockwise Electric Actuation Reset the electric
capable of preventing proper operation.
for a lower pressure setting. After detection system in accordance with
Step 1. All nipples, fittings, and devices verifying the desired pressure setting, the manufacturers instructions to
must be clean and free of scale and tighten the jam nut. de-energize the solenoid valve.
burrs before installation. Use pipe
Step 11. Conduit and electrical
thread sealant sparingly on male pipe
connections are to be made in NOTICE
NOTICE
threads only.
accordance with the applicable
Step 2. The DV-5 Valve must be In order to prevent the possibility of a
standards of the approval agency.
trimmed in accordance with one of the subsequent operation of an overheated
Step 12. Before a system hydrostatic solder type pilot sprinkler, any solder
trim illustrations shown in Figures 7 thru
test is performed, the DV-5 Diaphragm type pilot sprinklers that were possibly
18, as applicable.
Chamber is to be depressurized, exposed to a temperature greater than
Step 3. Care must be taken to ensure the Automatic Drain Valve is to be their maximum rated ambient must be
that check valves, strainers, globe temporarily replaced with a plug, replaced.
valves, etc. are installed with the flow and the Diaphragm Cover Bolts must
arrows in the proper direction. Step 7. Open the Diaphragm Supply
be uniformly and securely tightened
Valve (P) and allow time for full pressure
Step 4. Suitable provision must be using a cross-draw sequence. After
to build up in the DV-5 Diaphragm
made for disposal of drain water. tightening, double-check to make
Chamber.
Drainage water must be directed such certain that all of the Diaphragm Cover
that it will not cause accidental damage Bolts are securely tightened. Step 8. Operate (open) the Manual
to property or danger to persons. Control Station (M) to vent trapped air

Step 5. Connect the Diaphragm Supply Valve Setting from the DV-5 Diaphragm Chamber.
If necessary, first open the hinged
Valve to the inlet side of the systems
Stop Valve in order to facilitate setting Procedure cover, and then fully pull down on the
operating lever. SLOWLY close the
of the DV-5 Valve (Ref. Figure 19). Steps 1 through 10 are to be performed operating lever, by pushing it up, after
Step 6. An Inspectors Test Connection, when initially setting the TYCO DV-5 aerated water ceases to discharge from
as described in the Wet Pilot Actuation Deluge Valve, after an operational test the Manual Control Station. Close the
and Dry Pilot Actuation sections (Pages of the fire protection system, or after hinged cover and insert a new break
6 and 7), must be provided for Wet or system operation due to a fire. Refer to rod in the small hole through the top of
Dry Pilot Actuation systems. Figures 4, 5, or 6, as applicable. the enclosing box.
Step 7. An Air Maintenance Device, Step 1. Close the Stop Valve (B). For Wet Pilot Actuation, crack open
as described in the Dry Pilot Actuation the Inspectors Test Connection and
Step 2. Close the Diaphragm Supply any other vent valves on the wet pilot
section (Page 7), must be provided for Valve (P). For Dry Pilot Actuation, close
Dry Pilot Actuation. line to relieve trapped air. After the
the Dry Pilot Air Supply Valve (T). discharge of air has stopped, close
Step 8. A desiccant dryer, when Step 3. Open the Alarm Test Valve (G), the vent valves and the Inspectors Test
specified for Dry Pilot Actuation, is to System Drain Valve (E), and all auxiliary Connection.
be installed between a drip leg and the drains in the system. Close the auxiliary
Air Maintenance Device. drain valves after water ceases to
discharge. Leave the Alarm Test Valve
(G) and System Drain Valve (E) open.

/105/
TFP1338
Page 23 of 26

Step 9. Verify the ability for the DV-5


Diaphragm to hold pressure as follows: Care and condition) constitutes an emergency
impairment. Should this condition
DV-5 DATASHEET

With the diaphragm chamber


pressurized per Step 8, temporarily
Maintenance occur, immediately close the stop
valve and use the following procedure
close the Diaphragm Supply Valve The following procedures and to reset the system:
(P), and then observe the Diaphragm inspections must be performed as Step 1. Prior to the water supply
Gauge (K) for a drop in pressure. indicated, in addition to any specific pressure being restored to the closed
requirements of the standards stop valve, note the pressure indicated
If a drop in pressure is noted, the DV-5
recognized by the approval agency, and by the diaphragm chamber pressure
Diaphragm is to be replaced and/or
any impairment must be immediately gauge and determine if the pressure
any leaks must be corrected before
corrected. is within the normally expected range.
proceeding to the next step.
Step 2. If the diaphragm chamber
If the Diaphragm Chamber Pressure NOTICE
Gauge (K) indicates no drop in pressure is below the normal range,
pressure, re-open the Diaphragm The frequency at which the following check for and correct any source of
Supply Valve (P) and proceed to the procedures and inspections are to be leakage from the diaphragm chamber
next step. performed are to be in accordance prior to resetting the system.
with any specific requirements of the Step 3. After the water supply pressure
Step 10. Partially open the Stop Valve standards recognized by the approval
(B). Close the Alarm Test Valve (G) as is restored to the stop valve, reset the
agency. DV-5 Deluge Valve in accordance with
soon as water discharges from the
System Drain Valve (E) and then close The owner is responsible for the the Valve Setting Procedure section.
the System Drain Valve (E) after water inspection, testing, and maintenance of
ceases to drain. Observe the Automatic their fire protection system and devices NOTICE
Drain Valve (F) for leaks. If there are in compliance with this document, as
For fire protection systems subject to
leaks, determine/correct the cause of well as with the applicable standards
an emergency impairment caused by
the leakage problem. If there are no recognized by the approval agency.
an interrupted water supply condition,
leaks, the DV-5 Valve is ready to be Contact the installing contractor
it is recommended that consideration
placed in service and the Stop Valve or product manufacturer with any
be given to installing a low water supply
must then be fully opened. questions.
pressure switch with the appropriate
It is recommended that automatic alarm/indications to monitor the water
NOTICE sprinkler systems be inspected, supply pressure.
tested, and maintained by a qualified
If the Alarm Test Valve is not closed Internal Valve Inspection
Inspection Service in accordance
as soon as water discharges from the Once every five years during the
with the standards recognized by the
System Drain Valve, a false alarm may annual operational test procedure and
Approval agency.
occur. prior to the DV-5 Deluge Valve being
Note: Before closing a fire protection reset, the interior of the Deluge Valve
When the Stop Valve (B) is opened,
system main control valve for must be cleaned and inspected for
the pressure on the DV-5 Diaphragm
maintenance work on the fire protection wear and damage. Damaged or worn
Chamber may increase. This increase in
system that it controls, permission to parts must be replaced. (Replacement
pressure is normal, and if the pressure
shut down the affected fire protection of the Diaphragm every ten years is
is greater than 16 bar, the pressure is to
systems must first be obtained from recommended, or more frequently
be relieved by partially and temporarily
the proper authorities and all personnel if inspections and/or wear and tear
opening the Manual Control Station
who may be affected by this action warrant more frequent replacement.)
(M); however, do not allow the pressure
must be notified.
as indicated on the Diaphragm Gauge When reinstalling the Diaphragm Cover,
(K) to drop below the supply pressure Drop in Water Supply Pressure the Diaphragm Cover Fasteners must
shown on the Water Supply Gauge (J), Below Normal Range be uniformly and securely tightened
since this action may result in tripping using a cross-draw sequence.
of the DV-5 Valve. NOTICE
After tightening, double check to make
After setting a fire protection system, If the water supply pressure is certain that all of the Diaphragm Cover
notify the proper authorities and advise significantly reduced below the Fasteners are securely tightened.
those responsible for monitoring normally expected static pressure
proprietary and/or central station range (as could occur in the case of a
water main break or repair), and there NOTICE
alarms.
is a subsequent drop in the diaphragm If the water supply contains chemicals
chamber water pressure below its which tend to attack a nylon fabric-
normal range (due, for example, to a reinforced, natural rubber or the five year
leak in a piping connection to or from inspection indicates a build-up of debris
the diaphragm chamber or, a leak in within the Deluge Valve that could affect
the diaphragm chamber check valve its proper operation, then the frequency
caused by dirt or debris in the check of the internal valve inspection procedure
valve seal area), a deluge valve such as must be appropriately increased. If the
the TYCO DV-5 could inadvertently trip, system has a seawater or brackish water
if its water supply pressure is quickly supply, then the frequency of the internal
restored. valve inspection procedure must be
A drop in the water supply pressure appropriately increased. (An annual
to below its normal range (as in the internal valve inspection for a system
case of an interrupted water supply having a seawater or brackish water

/106/
TFP1338
Page 24 of 26

supply is recommended.) in accordance with the Valve Setting Step 3. Verify that the DV-5 Valve has
Procedure. tripped, as indicated by the flow of

DV-5 DATASHEET
With reference to Figure 1, make
water into the system.
certain that the Diaphragm is correctly Dry Pilot Actuation
oriented; otherwise, the DV-5 Deluge Operation Test Procedure Step 4. Close the systems Main
Valve cannot be properly set. Proper operation of the DV-5 Valve (i.e., Control Valve (D).
Under-tightening the Diaphragm Cover opening of the DV-5 Valve as during Step 5. Close the Diaphragm Chamber
Bolts can result in internal and external a fire condition) must be verified as Supply Control Valve (P).
leakage. follows:
Step 6. Reset the DV-5 Deluge Valve
The V-Ring is attached to the Step 1. If water must be prevented in accordance with the Valve Setting
Diaphragm at the factory. If, during an from flowing beyond the riser, perform Procedure.
internal valve inspection, the V-Ring the following steps:
is discovered to be detached from Dry Pilot Actuator
Close the Stop Valve (B). Open the Test Procedure for
the Diaphragm, be advised that the Alarm Test Valve (G) and System
V-Ring is a required valve component Drain Valve (E). Dry Pilot Actuation
and that detachment will not affect Proper operation of the Dry Pilot
normal valve operation or performance. Open the Stop Valve (B) one turn Actuator for dry pilot actuation must
Should the V-Ring become detached, beyond the position at which water be verified as follows:
reinstall it between the Diaphragm and just begins to flow from the System
Drain Valve (E). Step 1. Close the Stop Valve (B).
Diaphragm Cover concentrically as
shown in Figure 1. Close the Alarm Test Valve (G) and Step 2. Open the Alarm Test Valve (G)
then close the System Drain Valve (E). and the System Drain Valve (E).
Note: Do not apply adhesives,
lubricants, or other substances to the Step 2. Open the Inspectors Test Step 3. Open the Inspectors Test
Diaphragm, V-Ring, or Valve Body. Connection. Connection on the Dry Pilot Line.
Waterflow Alarm Test Procedure Note: Be prepared to quickly perform Step 4. Verify that the flow of water
To test the waterflow alarm, open the Steps 3, 4, and 5 if water must be from the Dry Pilot Actuator (R) drain
Alarm Test Valve (G), which will allow a prevented from flowing beyond the connection increases to a full flow.
flow of water to the Waterflow Switch riser. Step 5. Verify that the Diaphragm
(C) and/or Water Motor Alarm. Upon Chamber pressure has decreased
satisfactory completion of the test, Step 3. Verify that the DV-5 Valve has
tripped, as indicated by the flow of to below 25% of the water supply
close the Alarm Test Valve (G). pressure.
water into the system.
Wet Pilot Actuation Step 4. Close the Main Control Valve Step 6. Close the Inspectors Test
Operation Test Procedure (D). Connection and allow the dry pilot line
Proper operation of the DV-5 Valve (i.e., pressure to re-establish. Check the
opening of the DV-5 Valve as during Step 5. Close the Diaphragm Supply Dry Pilot Actuator (R) drain for leaks.
a fire condition) must be verified as Valve (P). Any leaks must be corrected before
follows: Step 6. Reset the DV-5 Deluge Valve proceeding to the next step.
Step 1. If water must be prevented in accordance with the Valve Setting Step 7. Partially open the Stop Valve
from flowing beyond the riser, perform Procedure. (B). Close the Alarm Test Valve (G) as
the following steps: soon as water discharges from the
Electric Actuation System Drain Valve (E) and then close
Close the Stop Valve (B). Open the Operation Test Procedure the System Drain Valve (E) after water
Alarm Test Valve (G) and System Proper operation of the DV-5 Valve (i.e., ceases to drain. Observe the Automatic
Drain Valve (E). opening of the DV-5 Valve as during Drain Valve (F) for leaks. If there are
Open the Stop Valve (B) one turn a fire condition) must be verified as leaks, determine/correct the cause of
beyond the position at which water follows: the leakage problem. If there are no
just begins to flow from the System Step 1. If water must be prevented leaks, the DV-5 Valve is ready to be
Drain Valve (E). from flowing beyond the riser, perform placed in service and the Stop Valve
the following steps. (B) must then be fully opened.
Close the Alarm Test Valve (G) and
then close the System Drain Valve Close the Stop Valve (B). Open the Low Pressure Alarm
(E). Alarm Test Valve (G) and System Test Procedure and
Step 2. Open the Inspectors Test Drain Valve (E). Condensate Drain Procedure for
Connection. Open the Stop Valve (B) one turn Dry Pilot Actuation
beyond the position at which water For Dry Pilot Actuation, testing of the
Note: Be prepared to quickly perform
just begins to flow from the System Dry Pilot Low Pressure Switch (S) and
Steps 3, 4, and 5 if water must be
Drain Valve (E). drainage of the pilot line condensate
prevented from flowing beyond the
must be performed as follows:
riser. Close the Alarm Test Valve (G) and
then close the System Drain Valve Step 1. Close the Stop Valve (B).
Step 3. Verify that the DV-5 Valve has
tripped, as indicated by the flow of (E). Step 2. Close the Diaphragm Supply
water into the system. Step 2. Test the deluge releasing panel Valve (P).
Step 4. Close the Main Control Valve in accordance with the manufacturers Step 3. Open the Alarm Test Valve (G)
(D). instructions to energize the solenoid and the System Drain Valve (E).
valve.
Step 5. Close the Diaphragm Supply Step 4. Open the Inspectors Test
Valve (P). Note: Be prepared to quickly perform Connection, and slowly relieve
Steps 3, 4, and 5 if water must be pneumatic pressure. Verify that the
Step 6. Reset the DV-5 Deluge Valve prevented from flowing beyond the Dry Pilot Low Pressure Switch (S) is
riser. operational and that the low pressure

/107/
TFP1338
Page 25 of 26

Dimensions in mm
DV-5 DATASHEET

Valve
Size A B C D E F G
NOTES:
DN40 340 400 550 200 210 370 530 1 Minimum clearance.
2 Dimension applies to
DN50 340 400 550 200 210 370 530 Wet Pilot and Electric
Actuation trims only.
DN80 315 400 550 230 220 430 580 3 Dimension applies to
Dry Pilot Actuation
DN100 310 400 450 270 310 460 610 trim only.
4 Dimension applies to
DN150 340 400 550 330 280 500 650 all trims.

DN200 360 400 550 370 290 610 700

1,3
C
1 1,2 4 1
A B D E

1,3
G
1,2
F

DN15 DIAPHRAGM
CHAMBER SUPPLY
CONNECTING TRIM STOP
(FIELD FABRICATED) VALVE
FRONT VIEW RIGHT VIEW

FIGURE 19
DN40 thru DN200 DV-5 DELUGE VALVES
INSTALLATION DIMENSIONS

set points are as follows: System Drain Valve (E) and then close the Solenoid Valve drain connection
low pressure alarm setting at the System Drain Valve (E) after water increases to a full flow.
ceases to drain. Observe the Automatic
approximately 0,4 bar below the Step 5. Verify that the Diaphragm
minimum pilot line service pressure Drain Valve (F) for leaks. If there are
Chamber pressure has decreased
requirement shown in Graph B leaks, determine/correct the cause of
to below 25% of the water supply
the leakage problem. If there are no
fire alarm setting at approximately pressure.
leaks, the DV-5 Valve is ready to be
1,0 bar below the minimum pilot placed in service and the Stop Valve Step 6. Reset the electric detection
line service pressure requirement (B) must then be fully opened. system in accordance with the
shown in Graph B. manufacturers instructions to
Solenoid Valve Test Procedure de-energize the solenoid valve. Check
Step 5. Close the Inspectors Test For Electric Actuation
Connection and allow the Dry Pilot Line the Solenoid Valve drain for leaks.
Proper operation of the Solenoid Valve Any leaks must be corrected before
to automatically repressurize. for electric actuation must be verified proceeding to the next step.
Step 6. Individually open each low point at as follows:
drain and then close after discharge of Step 7. Partially open the Stop Valve
Step 1. Close the Stop Valve (B). (B). Close the Alarm Test Valve (G) as
any trapped condensate.
Step 2. Open the Alarm Test Valve (G) soon as water discharges from the
Step 7. Allow the Dry Pilot Line to and the System Drain Valve (E). System Drain Valve (E) and then close
automatically repressurize. the System Drain Valve (E) after water
Step 3. Test the deluge releasing panel ceases to drain. Observe the Automatic
Step 8. Open the Diaphragm Supply in accordance with the manufacturers
Valve (P). Drain Valve (F) for leaks. If there are
instructions to energize the solenoid leaks, determine/correct the cause of
Step 9. Partially open the Stop Valve valve. the leakage problem. If there are no
(B). Close the Alarm Test Valve (G) as Step 4. Verify that the flow of water from leaks, the DV-5 Valve is ready to be
soon as water discharges from the

/108/
TTFP1338
Page 26 of 26

P/N XX X XX XX X XX

DV-5 DATASHEET
DELUGE VALVE TRIM SWITCH
Flanged/Flanged
80 PN10/16 SIZE 89 EUR 0 None

81 Flanged/Flanged
ANSI A DN40 1 PS10-1A

82 Flanged/Grooved
PN10/16 2 DN50

Flanged/Grooved STOP VALVE


83 3 DN80
ANSI
To Be Ordered
00 Separately
84 Grooved/Grooved 4 DN100

Threaded/Threaded
85 ISO 7-1 6 DN150 (168,3 mm)

Flanged/Grooved ACCESSORIES
86 PN16 (DN200) 7 DN150 (165,1 mm)
Wet Pilot Actuation
Flanged/Flanged 50 w/o Drain Valve
87 PN16 (DN200) 8 DN200

51 Electric Actuation
w/o Drain Valve
Dry Pilot Actuation
52 w/o Drain Valve

Dry Pilot Actuation


53 w/o Drain Valve
w/ Low Air Pressure Switch

TABLE C
DV-5 DELUGE VALVES
PART NUMBER SELECTION

placed in service and the Stop Valve For warranty terms and conditions, visit Deluge Valve with VdS/LPCB European
(B) must then be fully opened. www.tyco-fire.com. Conformity Valve Trim, P/N (Table C)

Limited
Accessories
Ordering Specify: (specify product name), P/N

Warranty
(specify from Table C)
Procedure Supervisory Switch for
Model DV-5 Deluge Valves with Water Motor Alarm
Control Valve . . . . . . . . . . . . . . P/N CEDPV1ASS
Assembled VdS/LPCB
European Conformity Valve Trim Model WMA-1
Water Motor Alarm with
Specify: Fully Assembled Model DV-5 Red Finish Gong . . . . . . . . . P/N 52-630-1-001P
A-thru-Z Labels . . . . . . . . . . . P/N WS00000033
(for attaching to valve trim components)

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


Copyright 2015 Tyco Fire Products, LP. All rights reserved.
RISLAN is trademark of Arkema Inc.
TEFLON is trademark of the DuPont Corporation.

/109/
Appendix A of TFP1338 (06/2007)
DV-5 DATASHEET

Summary Instructions (if problems occur, consult full document)


Deluge Valves, DV-5, DN40 thru DN200, Wet Pilot Actuation

Item Description
A DV-5 Valve
E B Stop Valve
C C Waterflow Switch
K D (Not used)
A
E System Drain Valve
3 F Automatic Drain Valve
G Alarm Test Valve
H Alarm Control Valve
F
2 H J Water Supply Gauge
K Diaphragm Gauge
J L System Gauge
G
M Manual Control Station
N Automatic Shut-Off Valve
M
P Diaphragm Supply Valve
N Q Diaphragm Supply Strainer
Q 1 Diaphragm Supply Connection
2 Water Motor Alarm Connection
3 Wet Pilot Line Connection
P
B
1

I. Normal conditions IV. Returning the system to service If the Diaphragm Chamber Pressure
The Stop Valve (B) is opened and Step 1. Close the Stop Valve (B). Gauge (K) indicates no drop in
locked. pressure, re-open the Diaphragm
Step 2. Close the Diaphragm Supply Supply Valve (P) and proceed to the
The System Drain Valve (E) is Valve (P). next step.
closed.
Step 3. Open the Alarm Test Valve (G), Step 10. Partially open the Stop Valve
The Diaphragm Supply Valve (P) System Drain Valve (E), and all auxiliary (B). Close the Alarm Test Valve (G) and
and Alarm Control Valve (H) are drains in the system. Close the auxiliary then close the System Drain Valve (E)
open. drain valves after water ceases to after water ceases to drain. Observe
The Manual Control Station (M) and discharge. Leave the Alarm Test Valve the Automatic Drain Valve (F) for leaks.
Alarm Test Valve (G) are closed. (G) and System Drain Valve (E) open. If there are no leaks, the DV-5 Valve is
Step 4. Depress the plunger of the ready to be placed in service and the
Water Supply Gauge (J) reads the Stop Valve must then be fully opened.
upstream water pressure. Automatic Drain Valve (F) to verify that
it is open and that the DV-5 Valve is
The System Gauge (L) reads zero. completely drained. V. Weekly test
The Diaphragm Gauge (K) is equal Step 5. Clean the Diaphragm Supply NOTICE
to or greater than the Water Supply Strainer (Q).
Gauge (J). Prior to closing any valves or activating
Step 6. Reset the actuation system. any alarms, notify local security
II. Operation Manual Actuation Push the operating guards and the central alarm station if
lever up; however, do not close the applicable.
When set for service, the DV-5
Diaphragm Chamber is pressurized hinged cover at this time. Step 1. Open the Alarm Test Valve (G),
from the inlet side of the Stop Valve Wet Pilot Actuation Replace verify that the alarm signal created by
(B). Opening of the Manual Control operated pilot sprinklers and/or reset the Waterflow Switch (C) is visible at
Station (M) or a Wet Pilot Sprinkler the remote manual control stations. the fire panel. If applicable, check the
(fire detection) releases water from sound of the water motor alarm it
Step 7. Open the Diaphragm Supply must be clear and steady.
the Diaphragm Chamber faster than
Valve (P) to pressurize the DV-5
it can be replenished through the Step 2. Return the Alarm Test Valve (G)
Diaphragm Chamber.
Automatic Shut-off Valve (N). The water to the normally closed position after
supply pressure then forces the DV-5 Step 8. Open and then close the verifying that the alarm signal is visible
Diaphragm open permitting water to Manual Control Station (M) to vent at the fire panel.
flow into the system piping, as well as trapped air from the DV-5 Diaphragm
to the Waterflow Switch (C). Chamber. Step 3. Drain the alarm line by
squeezing the Automatic Drain Valve
Relieve trapped air from the wet pilot (F). If the supply is below the normal,
III. Removing system from service line. After the discharge of air has use the instructions from the water
Step 1. Close the Diaphragm Supply stopped, close the vent valves and the supply to obtain the usual pressure.
Valve (P). Inspectors Test Connection.
Step 2. Close the Stop Valve (B). Step 9. Temporarily close the
Diaphragm Supply Valve (P), and then
Step 3. Open the Alarm Test Valve (G)
observe the Diaphragm Gauge (K) for
and System Drain Valve (E).
a drop in pressure.

/110/
Appendix B of TFP1338 (06/2007)

DV-5 DATASHEET
Summary Instructions (if problems occur, consult full document)
Deluge Valves, DV-5, DN40 thru DN200, Dry Pilot Actuation

L S T Item Description
4
A DV-5 Valve
U B Stop Valve
C Waterflow Switch
E V D (Not used)
C E System Drain Valve
3 K F Automatic Drain Valve
G Alarm Test Valve
H Alarm Control Valve
A
J Water Supply Gauge
R K Diaphragm Gauge
H F
L System Gauge
M Manual Control Station
2 N Automatic Shut-Off Valve
G P Diaphragm Supply Valve
3,0 J Q Diaphragm Supply Strainer
R Dry Pilot Actuator
RESSURE S Dry Pilot Low Pressure Switch
AIR P
AIR PRESSURE IN BAR

UM S
YSTE
M M T Dry Pilot Air Supply Valve
2,0 MINIM
E Q N U Dry Pilot Line Gauge
RE SSUR
ING P V Pressure Relief Valve
R OPEN
ACT UATO
1,0 E OF
RANG P 1 Diaphragm Supply Connection
2 Water Motor Alarm Connection
B
3 Dry Pilot Line Connection
0
1,0 4,0 7,0 10,0 13,0 16,0 1 4 Dry Pilot Air Supply Connection
WATER SUPPLY PRESSURE IN BAR

I. Normal conditions Step 3. Open the Alarm Test Valve (G) trapped air from the DV-5 Diaphragm
The Stop Valve (B) is opened and and System Drain Valve (E). Chamber.
locked. Step 4. Close the Dry Pilot Air Supply Step 9. Temporarily close the
The System Drain Valve (E) is Valve (T). Diaphragm Supply Valve (P), and then
closed. observe the Diaphragm Gauge (K) for
IV. Returning system to service
a drop in pressure.
The Diaphragm Supply Valve (P), Step 1. Close the Stop Valve (B).
Alarm Control Valve (H), and Dry If the Diaphragm Chamber Pressure
Pilot Air Supply Valve (T) are open. Step 2. Close the Diaphragm Supply Gauge (K) indicates no drop in
The Manual Control Station (M) and Valve (P) and the Dry Pilot Air Supply pressure, re-open the Diaphragm
Alarm Test Valve (G) are closed. Valve (T). Supply Valve (P) and proceed to the
Step 3. Open the Alarm Test Valve (G), next step.
Water Supply Gauge (J) reads the
upstream water pressure. System Drain Valve (E), and all auxiliary Step 10. Partially open the Stop Valve
drains in the system. Close the auxiliary (B). Close the Alarm Test Valve (G) and
The System Gauge (L) reads zero.
drain valves after water ceases to then close the System Drain Valve (E)
The Diaphragm Gauge (K) is equal discharge. Leave the Alarm Test Valve after water ceases to drain. Observe
to or greater than the Water Supply (G) and System Drain Valve (E) open. the Automatic Drain Valve (F) for leaks.
Gauge (J). If there are no leaks, the DV-5 Valve is
Step 4. Depress the plunger of the
The Dry Pilot Line Gauge (U) reads Automatic Drain Valve (F) to verify that ready to be placed in service and the
dry pilot line pressure. it is open and that the DV-5 Valve is Stop Valve must then be fully opened.
II. Operation completely drained. V. Weekly test
When set for service, the DV-5 Step 5. Clean the Diaphragm Supply Important: Prior to closing any valves
Diaphragm Chamber is pressurized Strainer (Q). or activating any alarms, notify local
from the inlet side of the Stop Valve Step 6. Reset the actuation system. security guards and the central alarm
(B). Opening of the Manual Control station if applicable.
Station (M) or the Dry Pilot Actuator (R) Manual Actuation Push the operating
lever up; however, do not close the Step 1. Open the Alarm Test Valve (G),
via operation of a Dry Pilot Sprinkler verify that the alarm signal created by
(fire detection) releases water from hinged cover at this time.
the Waterflow Switch (C) is visible at
the Diaphragm Chamber faster than Dry Pilot Actuation Replace the fire panel. If applicable, check the
it can be replenished through the operated pilot sprinklers, reset the sound of the water motor alarm it
Automatic Shut-Off Valve (N). The water remote manual control stations, and must be clear and steady.
supply pressure then forces the DV-5 open the Dry Pilot Air Supply Valve (T)
Diaphragm open permitting water to to re-establish dry pilot air pressure as Step 2. Return the Alarm Test Valve (G)
flow into the system piping, as well as indicated on the Dry Pilot Line Gauge to the normally closed position after
to the Waterflow Switch (C). (U) per the graph. verifying that the alarm signal is visible
at the fire panel.
III. Removing system from service Step 7. Open the Diaphragm Supply
Valve (P) to pressurize the DV-5 Step 3. Drain the alarm line by
Step 1. Close the Diaphragm Supply squeezing the Automatic Drain Valve
Valve (P). Diaphragm Chamber.
(F). If the supply is below the normal,
Step 2. Close the Stop Valve (B). Step 8. Open and then close the use the instructions from the water
Manual Control Station (M) to vent supply to obtain the usual pressure.

/111/
Appendix C of TFP1338 (06/2007)
DV-5 DATASHEET

Summary Instructions (if problems occur, consult full document)


Deluge Valves, DV-5, DN40 thru DN200, Electric Actuation

Item Description
A DV-5 Valve
E B Stop Valve
C R C Waterflow Switch
K D (Not used)
A
E System Drain Valve
F Automatic Drain Valve
G Alarm Test Valve
H Alarm Control Valve
F
2 H J Water Supply Gauge
K Diaphragm Gauge
J L System Gauge
G
M Manual Control Station
N Automatic Shut-Off Valve
M
P Diaphragm Supply Valve
N Q Diaphragm Supply Strainer
R Solenoid Valve
Q
1 Diaphragm Supply Connection
2 Water Motor Alarm Connection
P
B
1

I. Normal conditions IV. Returning system to service Step 10. Partially open the Stop Valve
Step 1. Close the Stop Valve (B). (B). Close the Alarm Test Valve (G) and
The Stop Valve (B) is opened and
locked. then close the System Drain Valve (E)
Step 2. Close the Diaphragm Supply after water ceases to drain. Observe
The System Drain Valve (E) is Valve (P). the Automatic Drain Valve (F) for leaks.
closed. Step 3. Open the Alarm Test Valve (G), If there are no leaks, the DV-5 Valve is
The Diaphragm Supply Valve (P) System Drain Valve (E), and all auxiliary ready to be placed in service and the
and Alarm Control Valve (H) are drains in the system. Close the auxiliary Stop Valve must then be fully opened.
open. drain valves after water ceases to
discharge. Leave the Alarm Test Valve V. Weekly test
The Manual Control Station (M) and
Alarm Test Valve (G) are closed. (G) and System Drain Valve (E) open.
NOTICE
Water Supply Gauge (J) reads the Step 4. Depress the plunger of the
Automatic Drain Valve (F) to verify that Prior to closing any valves or activating
upstream water pressure. any alarms, notify local security
it is open and that the DV-5 Valve is
The System Gauge (L) reads zero. completely drained. guards and the central alarm station if
applicable.
The Diaphragm Gauge (K) is equal Step 5. Clean the Diaphragm Supply
to or greater than the Water Supply Strainer (Q). Step 1. Open the Alarm Test Valve (G),
Gauge (J). verify that the alarm signal created by
Step 6. Reset the actuation system. the Waterflow Switch (C) is visible at
II. Operation Manual Actuation Push the operating the fire panel. If applicable, check the
lever up; however, do not close the sound of the water motor alarm; it must
When set for service, the DV-5 be clear and steady.
hinged cover at this time.
Diaphragm Chamber is pressurized
from the inlet side of the Stop Valve Electric Actuation Reset the electric Step 2. Return the Alarm Test Valve (G)
(B). Opening of the Manual Control detection system to de-energize the to the normally closed position after
Station (M) or the Solenoid Valve (R) Solenoid Valve (R). verifying that the alarm signal is visible
upon fire detection releases water at the fire panel.
Step 7. Open the Diaphragm Supply
from the Diaphragm Chamber faster Valve (P) to pressurize the DV-5 Step 3. Drain the alarm line by
than it can be replenished through the Diaphragm Chamber. squeezing the Automatic Drain Valve
Automatic Shut-off Valve (N). The water (F). If the supply is below the normal,
supply pressure then forces the DV-5 Step 8. Open and then close the use the instructions from the water
Diaphragm open permitting water to Manual Control Station (M) to vent supply to obtain the usual pressure.
flow into the system piping, as well as trapped air from the DV-5 Diaphragm
to the Waterflow Switch (C). Chamber.
Step 9. Temporarily close the
III. Removing system from service Diaphragm Supply Valve (P), and then
Step 1. Close the Diaphragm Supply observe the Diaphragm Gauge (K) for
Valve (P). a drop in pressure.
Step 2. Close the Stop Valve (B). If the Diaphragm Chamber Pressure
Gauge (K) indicates no drop in
Step 3. Open the Alarm Test Valve (G) pressure, re-open the Diaphragm
and System Drain Valve (E). Supply Valve (P) and proceed to the
next step.

/112/
Notes

DV-5 DATASHEET


NOTES




























/113/
Notes

NOTES





























/114/
Notes

DV-5 DATASHEET


NOTES




























/115/
FEEDBACK FORM

Feedback
Form

Your input in this survey will help us improve the quality of our Local Instruction Valve Experience (L.I.V.E). As such
we would appreciate it if you could take some time to answer these questions. Kindly tick an appropriate response.

// Tell us about your L.I.V.E experience

Strongly Disagree Neutral Agree Strongly


Disagree Agree
1. The training demonstration content met
my expectations.
2. The examples and applications were relevant
and Insightful.
3. The solutions provided will benefit me in
my work.
4. The training demonstration has given me an
appreciation of overall system performance
and cost considerations.
5. The handouts provided contain
useful information.

6. What other applications/topics below would you be interested in? (Please tick no more than 3)
Storage Applications Water Mist
Commercial Applications Sprinklers
(e.g. commercial & retail, high rise, hotels) Others, please specify 
Residential Solutions 

// Tell us about yourself


7. My main job responsibility is (please select the most appropriate response)
Enforcement of Fire Protection Codes and Standards Contracting and Installing Fire Protection Systems
Designing of Fire Protection Systems Owner/Operator of a facility, type of facility 

8. How did you hear about the L.I.V.E. Demonstrations?


I received an email from Tyco Others, please specify 
A business contact / colleague forwarded the 
details to me

9. I would/would not like to receive news/product 10. I would/would not like to know more about other
updates from Tyco. Tyco products
My email address is  Name: 
 Company: 
Email: 
Or affix your business card

Please return this form to your LIVE Training Instructor or email to: firevalves@tycoint.com

/116/
APPENDIX

/117/
APPENDIX

General

Before working with the Tyco L.I.V.E Display, it is important to thoroughly read and understand all the instructions
in this manual. The L.I.V.E setup and shutdown requires at least two people to prevent injuries or damage to the
equipment. Additionally, ensure that the display location for the L.I.V.E has access to water and electrical service
(230V) and a place to drain the water (a simple garden hose long enough to reach a water source and drain will
suffice). Please confirm guidelines with the facilitys owner.

Tools:
The following tools are necessary for setup. (Except where otherwise noted, tools can be found packed with in
the control box at the back of the display)
// Gloves (recommended due to the sharp, metal edges on the L.I.V.E)
// Wrench 15 and 17 (for resetting ACC-1 / bolts for couplings)
// Phillips and slotted screwdriver
// Adjustable wrench
// Electrical plug for conversion to UK plug
// Fill/Discharge hose

Warning:
This installation makes use of electricity. After connecting the control box (grey box at the backside of the display)
to the mains the master switches in the box are under electric tension. When all the master switches are turned
on: the pump and compressor will have 230V and the panel 24V.
As the tank will be filled with both potable and non potable water, the water / installation is subjected to
temperature changes and as the water might get polluted over the time it is forbidden to drink the water used.

/118/
Set-up

APPENDIX
Instructions
for Instructor
Use Only

1. 2. 3.

The following valves are on the display: Now you can easily remove the re-usable wooden
packaging by loosening the quick releases. First remove
Position 1: GxG DPV-1 FM Trimming (TFP 1020)
the long-side panels, then the short-side panels and
Position 2: AV-1 89 trim (TFP 990) finally the hood of the packaging. The panels have a
Position 3: DV-5 Electric actuation (TFP 1338) foam layer on the inside to protect the tank
Dimension: (An unpacking instruction is on the packaging).
Crated: 2440mm x 740mm x 1920mm
Uncrated: 2400mm x 750mm x 1900mm
Set-up of the L.I.V.E display
Attached in this document you will find the following
Weight:
datasheets to help you when any information is needed
Crated: 650kg on the products in the L.I.V.E display unit:
Uncrated: 600kg
DPV-1: TFP 1020
Uncrating the L.I.V.E display ACC-1: TFP 1112
AMD-1: TFP 1221
The L.I.V.E is equipped with castors so it is easy to
AV-1: TFP 990
move to the location where the display will be used.
DV-5: TFP 1338

/119/
APPENDIX

Make sure that the location where the display will be used has access to
both water and electrical service. When the display is in the right location,
lock the castor wheels.
The tank can be filled in two different ways. However before filling, make
sure that drain valve (1) is closed and that valve (2) to the sight glass is open:
3. P
 ut the hose in the Drain Cup of the DPV-1 and fill the tank.
4. C
 onnect the supplied hose to a tapping point, open the ball valve, open
the tapping point and fill the tank.
When the water level has reached the marked level in the sight glass, close
the tapping point. The system is now filled with enough water to run the
system. The tank can contain up to 550 litres of water when filled.

1 2 3 4

To check if the pump (5) contains


water after the tank is filled open the
venting plug (6) of the pump. Slowly
open the vent plug with your hand
and when a little water comes out it
is filled. If the pump does not contain
water remove the venting plug and
fill the chamber with water. Put the
plug back and screw it hand tight.
5 6

/120/
APPENDIX
Open the control box (1) at the back of the display with the key (hanging on a chain). Make sure all the three main
switches BMC (Fire Panel), Pump, Compressor are in the out position (down) (2,3). Make sure that the main
switch is turned off (4). Plug the connector into the mains (5). (6) (A UK plug is available in the control box)

1 2

3 4

5 6

/121/
APPENDIX

Setting Up
the System

Pressurize the DPV-1


Make sure:
1. T
 he DPV-1 (TFP1020) valve is closed by
making use of the reset plunger
2. T
 he ACC-1 (TFP1112) is in the set position
1 2 3
3. T
 he Air supply valve to the AMD-1
(TFP1221) is open
4. T
 he Air supply control valve of the DPV-1
is open
5. The valve to the system air gauge is open
6. C
 lose the ball valve on top of the valve
(this valve is to simulate an alarm later on) 4 5 6

Next Steps
1. Put the Main switch in the on position
2. Put the switch for the compressor in the
on position
3. The system will be pressurized up to 2
bar. This is a factory set value.
See gauge on AMD-1 1 2 3

Pressurize the water side


of the system
1. Close the MC-1 in the DV-5 (TFP1338) trim
2&3. Close all other drains / valves 6x
4. Put system Control Valves (BFV) under 1 2 3
DPV-1 and AV-1 (TFP990) in open position
and under DV-5 in closed position. 4
5. Close the ball valve on top of the AV-1
(alarm simulation valve)
6. Put the switch for the pump in the
on position
5 6

The pump will pressurize the system


between 3-5 bar (1,2). By opening the main
drain valve of the DPV-1 slightly you can
let the last air escape and make sure the
clapper is closed (3).

1 2 3

/122/
APPENDIX
1. Make sure the MC-1 is closed and that the ball valve in
downstream is open
2. The button for smoke detection / solenoid should be in
Out (pull) position
3. Pressurize the diaphragm chamber of the DV-5 by
opening the water supply valve
4. On the pressure gauge you will see the Diaphragm
Chamber pressure
5. Open the System Control Valve underneath the DV-5.
The Valve is now set
6. By opening the MC-1 a little you can bring the pressure
in the diaphragm chamber and upstream in balance 1 2

3 4 5 6

1. Open the BMC, The key is in the control box (Tyco key cord). Connect the backup
battery in the BMC The BMC will give a sound when:
a) The backup battery is not connected
b) One of the System Control Valves is (partly) closed
c) One of the valves tripped
2. Now the BMC can be switched on
3. When there is alarm this can be reset by using the reset button (3)
All valves are now set;
the system has air and
water pressure. The best
sequence to trip the valves
or perform an alarm test
is AV-1, DV-5 and then
DPV-1 All relevant valve
and device data sheets are
included and can be used
for reference. 1 2 3

/123/
DPV-1
APPENDIX

Testing and
Tripping

DPV-1 Testing
1. Open the Alarm
Test Valve a little to
drop pressure and
close it again
2. T
 he pressure switch will
give an alarm signal and
the strobe will give a
light and sound signal
3. T
 he BMC will show
the alarm on Output 3.
Press reset 1 2 3

DPV-1 Tripping
1. Open the ball valve downstream to simulate an alarm 6. Close the air supply and drain the valve.
2. Water will flow through the sight glass Set the ACC-1
3. The pressure switch will give an alarm signal and the 7. Reset the clapper
strobe will give a light and sound signal 8. Follow the steps previously described about putting
4. The BMC will show the alarm on Output 1. air pressure on the DPV
Press reset
Thereafter open the System Control Valve and open
5. Close the System Control Valve the Main Drain a little to determine if the clapper is
closed (hissing sound).

1 2 3 4

5 6 7 8

/124/
APPENDIX
AV-1 Testing
and Tripping

AV-1 Testing
1. Open the test valve. Water will flow to the retard chamber and a little will be drained
2. W
 hen the retard chamber is filled the pressure switch will give an alarm signal and the strobe will give a light
and sound signal
3. The BMC will show the alarm on Output 2. Press reset
4. Drain the alarm line by opening the drip valve

1 2

3 4

AV-1 Tripping
1. Open the downstream to simulate an alarm
2. T
 he valve will trip. In the sight glass between DPV-1 and AV-1 you will see water flowing the pressure switch
will give an alarm signal and the strobe will give a light and sound signal
3. The BMC will show the alarm on Output 2. Press reset. (3)
4. Set the valve by closing the ball valve downstream and drain the alarm line

1 2 3 4

/125/
APPENDIX

DV-5 Testing
and Tripping

DV-5 Testing
1&2. To test the DV-5 alarm open the test valve a little and then close it again
3. The pressure switch will give an alarm signal and the strobe will give a light and sound signal
4. The BMC will show the alarm on Output 3. Press reset

1 2 3 4

DV-5 Tripping
1&2. Either operate the button simulating the smoke detection or use the MC-1 to simulate an alarm
3. The pressure switch will give an alarm signal and the strobe will give a light and sound signal
4. The BMC will show the alarm on Output 3. Press reset
5. Close the System Control Valve
6. And additional alarm on the BMC will occur
7. Drain the system
8. Pressurize the diaphragm chamber and open the System Control Valve

In

1
Out 2 3 4

5 6 7 8

/126/
APPENDIX
Summary

Remarks
The Electric Actuated DV-5 is in practice operated
by a detection device. In this case we simulate this
detection device by a button.
To actuate the valve push the button. This is a two
position switch which needs to be put back in the out
position when resetting the valve.

The panel can be switched on with the main switch in


the control box.

The panel is programmed with program 14, which


means that there are three different zones for
detecting a pressure drop:

Zone 1 for the DPV-1


Zone 2 for AV-1
Zone 3 for DV-5

When there is an alarm simulated in one of the three


systems the pressure drop will operate the strobe and
a sound will be emitted. The alarm can be switched off
by pressing the reset button on the panel. As the alarm
comes with a sound it might be sometimes favorable
to cut off the mains to the BMC.

There is one input for the supervisory switches which


are on the butterfly valves. These three switches
are connected in series so when one of the valves
is closed or partially closed there will be an alarm.
The valves should be open like in a real working
environment when demonstrating the valves.

Breaking down the L.I.V.E display


At the end of a demonstration event the breakdown of
a display will be the reverse of the set up procedure.

// M
 ake sure the pump, compressor and panel are
shut down
// D
 rain the valves and make sure the clapper of the
DPV-1 is down
// Drain the tank
// Close all drain valves
// D
 isconnect the batteries from releasing panel (1) and
close the panel and put the keys back in the panel
// P
 lace all accessories / tools in the control box at the
back of the display
// Put the display back in the packaging

/127/
DPV-1 DATASHEET

Global Strength. Local expertise.


At your service.

WORLDWIDE HEADQUARTERS EUROPE, MIDDLE EAST & AFRICA ASIA PACIFIC


Tyco Fire Protection Products, 1400 Kopersteden 1 Tyco Fire Protection Products
Penbrook Parkway, Lansdale P.O. Box 198 2 Serangoon North Avenue 5
PA 19446 7500 AD Enschede #07-01, Singapore 554911
Tel: +1 215-362-0700, (Toll Free) The Netherlands Tel. +65-6577-4360,
Tel: +1 800-558-5236 Tel. +31 (0)53-428-4444 Fax: +65-6481-8791
Fax: +1 800-877-1295 www.tfppemea.com www.tyco-fire.com
www.tyco-fire.com

www.tfppemea.com Copyright 2015 Tyco Fire Products LP. All rights reserved.

/128/