Académique Documents
Professionnel Documents
Culture Documents
1 , , 1 , , , ,
, , 0 1
, , 2
C. ATP Simulations
To make the analysis of CGS at steady state and transient,
performed a set of simulations from circuit model obtained Fig. 6. Voltage by lightning wave (1,2/50 s).
computational tool, where the data of their constitutive
parameters for each of the elements componene the system are
shown in Table I (two elements per component) for a
homogeneous soil resistivity 100 *m.
This is used for simulation software ATP (Alternative
Transient Program) in order to observe the behavior of the
maximum ground potential rise (GPR), in presence a lightning
wave or short-circuit.
The voltage at the CGS and traditional grounding that
consisting of a single rod of 5/8 and 2,4 m buried to 30 cm
deep, is shown in Fig 6, for a lightning wave 1.2/50 s to 1000
amperes, the maximum voltage rise of the ground is about 18
kV and 38 kV respectively.
In this way CGS presents a reduction in surges that occurs
due to the lightning corresponding to a decrease of 20kV/kA, Fig. 7. Voltage by short circuit (10 A, 60 Hz)
implying that the CGS greatly attenuates the GPR, improving
human security and protection of distribution system TABLE I
equipment. CIRCUIT PARAMETERS OF THE GROUNDING SYSTEM
Similarly ATP software is used to simulate the performance Rod 1 Wire Rod 2
of the CGS under short circuit of 10A and 60Hz, this generates
Circuit
a voltage of 177V in CGS and 376V in a conventional system Parameter
Element1 Element2 Element3 Element4 Element5 Element6
which corresponds to the GPR, as shown in Fig. 7, This
C Shunt/2
elevation is more than double in the traditional system than in (pF)
162,1 166,9 121 121 162,1 166,9
CGS which reaffirms a substantial improvement of human
security and protection of distribution system equipment. R Shunt/2
()
196,7 191 263,4 263,4 196,7 191
D. Other Configurations based in CGS L(H) 1,78 1,73 2,38 2,38 1,78 1,73
Table II shows a comparison between the CGS and other Self-R
similar configurations with different number of rods, distance 0,1 0,1 0,98 0,98 0,1 0,1
(m)
between them and adding counterpoise, in order to evaluate
configuration alternatives that can improve the system
III. VALIDATION AND MEASUREMENTS OF THE FIELD
performance, for all the simulation the soil resistivity is
homogeneous with a value of 100 *m, the current short The CGS has been implemented by CODENSA S.A. ESP. in
circuit was assumed in 10 Amps. a pilot test in about 50 transformers from 2011 to the first half
In each case it is compared grounding resistance and step of 2013, mainly in the area of Cundinamarca with isokeraunic
and touch voltages maximum that may occur by short circuit, high level and reiterative transformers for failures associated
is noted as increasing as the number of rods or counterpoise t to lightning.
can be significantly reduced these parameters and improve the Table III presents the results of measurements of the
performance of earth of any kind of disturbance in the power grounding resistance for thirteen transformers with a
system. traditional system (single electrode), then the implementation
It can be found in various configurations which substantially CGS with reduction in all cases more than 65% in the
improve the behavior of the grounding, this is carried out resistance grounding value, which validates the performance
without significantly affecting the cost of the same with the exhibited by the computational tool.
application of the counterpoise and reducing the depth of In turn, when comparing the results obtained in respect to
burial of the cable connection between ground rods. ground computational model, it is clear similarity between
these as outlined below:
4