CHAPTER 1
POWER SYSTEM ANALYSIS
THE SUPPLY SYSTEM
The supply system consists of the network of conductors and associated
equipment over which energy is
transmitted from the generating
station to the consumer; it may
be divided into two distinct parts,
the transmission system and the
distribution system. The former
may again be divided into primary
and secondary transmission, and
the latter may be divided into
primary, secondary and tertiary
distribution. In general in an a.c.
system there will be a change in
voltage at each point where the
subdivision takes place, thechange
being effected by transformation,
usually at a substation, and there-
fore there may be several working
voltages in the same system. For
equipment manufacturing reasons
and in order that corresponding
sections of adjacent systems may
be inter-connected it has been
found necessary to standardise
voltages, the voltages at present
in use in this country being as
follows:
Primary transmission, 400 kV Fig. 1.1 Eleme
and 275 kV.
Secondary transmission, 132 kV and 66 kV.
O
Generator
14,000V
Tronsformers
14,000/275,000V
Primory transmission
275,000V
Tronsformers
275,000/132,000V
Secondary transmission
132,000V
Tronsformers
132,000/33,000V
Primary distribution
33,000V
Transformers .
33,000/11,000V
L Secondary distribution
M,OOOV
Tronstormers
1100074 15V
|
Tertiary distribution
4isv
nts of a transmission systemTHE TRANSMISSION AND DISTRIBUTION OF ELECTRICAL ENERGY
Primary distribution, 33 kV.
Secondary distribution, 11 kV and 66 kV.
Tertiary distribution, 415 V between phases, 240 V to neutral.
A typical system is shown in Fig, 1.1, although it must be noted that
all existing systems do not include all the parts shown in the figure, e.g.
some may have no primary transmission and others may be so small
that there is, in effect, distribution only, and so on. It should be noted
that, in addition to the above, there is in existence some d.c. distribu-
tion; what is more important, the use of d.c. for high voltage trans-
mission is becoming of increasing significance.
For a.c. working the standard frequency in this and many other
Service mains
Distributor
Fig, 1.2 Elements of a distribution system
countries is 50 Hz. In America a frequency of 60 Hz is most common,
although 25 Hz is also used.
Consumers taking large amounts of power, i.e. in excess of 500 kVA,
may be supplied directly from the secondary distribution network, but
the bulk of consumers have a much smaller load than this and are
supplied from the tertiary distribution system.
Tn general the conductors in the distribution system may be grouped
under three headings; feeders, distributors and service mains. The
feeders are the conductors which connect the substations, or in some
cases the generating stations, to the areas served by these stations. The
distributors are characterised by numerous tappings which are taken
from them for the supply to the various consumers, and the service
mains are the connecting links between the distributors and the con-
sumers’ terminals. The essential difference between feeders and distri-
butors is thus that, whereas the current loading of a feeder is the same
along the whole of its length, a distributor has a variable loading due
to the large number of individual tappings taken from it. The functions
of these three types of main are illustrated in Fig. 1.2.
2POWER SYSTEM ANALYSIS
/
THE ANALYSIS OF POWER SYSTEMS
In order that the power system may be designed and operated satis-
factorily it is important that means should be available for determining
the performance of the system when it is operating under given condi-
tions and supplying given loads. This usually means that it is necessary
to calculate the currents in the various branches of the system and the
voltages at various interconnecting points. The power system will
consist of a number of components, i.e. generators, transformers, over-
head lines and underground cables, each of which will possess resistance
and reactance and which will be interconnected together in a more or
less complicated fashion.
The following steps will usually be necessary in order to arrive at a
solution to the problems which arise:
(1) First a picture of the system must be developed in the form of a
single line diagram on which all the relevant circuits and equipment
appear. Although the great majority of a.c. systems will be three-
phase the conditions are often such that they are balanced, i.e. the
currents in each phase are identical and the impedances of each phase
are the same; in these circumstances it is only necessary to consider
one phase, since the magnitudes of currents and voltage will be the
same in the other two. Special techniques are necessary if the system
is unbalanced; these are described in Chapter 15.
(2) The relevant data for each item of equipment must then be
collected and marked or. the diagram; this will include the impedance
of the circuit elements, and the magnitude and power factor of the
loads and the generated voltages. It is important to note in this
connection that the effect of an impedance, i.e. the volt drop across
it, will depend on the current flowing through it, and will therefore be
affected by its position in the system. In other words, an impedance
connected to the high-voltage side of a transformer will not produce
the same voltage drop as the identical impedance connected to the
low-voltage side, since the currents will differ according to the ratio
of transformation. This effect must be allowed for in the calculations
by referring all the impedances to one particular voltage and carrying
out the calculations on this basis. The procedure for doing this is
described in Chapter 15.
(3) The network is then solved for the various currents and
voltages, making use of the theorems and techniques outlined below.
NETWORK THEOREMS
The main tools used in the solution of networks are the laws ascribed to
Kirchoff, but before considering the application of these, other network
3THE TRANSMISSION AND DISTRIBUTION OF ELECTRICAL ENERGY
theorems are given below, each of which finds a use in particular aspects
of the work.
It should be noted that the circuit parameters in the case of trans-
mission and distribution systems operating at a frequency of 50 Hz can
be considered as bilateral and linear. A bilateral impedance is one
which is independent of the direction of current flow, whilst a linear
impedance is one in which the current produced by an applied p.d. is
proportional to the magnitude of that p.d. This latter is not strictly
true of the circuit parameters, since usually a change in current will
have some effect on the value of the parameter. Thus increased current
will, because of increased temperature, cause an increase in the resist-
ance of normal conducting materials. An increased current will cause
an increase in the electro-magnetic forces acting between parallel con-
ductors, thereby producing possible deformation with a change in
inductance and capacitance, and so on. However, for practical purposes,
the linearity of circuit parameters can be assumed, the resistance being
that corresponding to a known or assumed temperature.
(1) The Reciprocity Theorem
If an e.m.f. E acting in any branch p of a network consisting of linear
bilateral impedances results in
« c E a current J in a second branch
q, then the same e.m.f. acting
2304 = Ze54y0 Z:4-J3 in branch q will result in the
5 branch qbranch flow of the same current J in
branch p.
8 . F The ratio of the emf. in
Fig. 13 branch p to the resulting current
i in branch q is called the transfer
impedance (Z,,) between p and q, thus the reciprocity theorem states
that
Zo = Zap
Example: Consider the network of Fig. 1.3:
Let an e.m.f. of E = 100 + 0 act in branch AB,
; 4
= 55 + j317
= 100+ 0 _ 1-47 — js:
Tas = 53 phaT = NAT —J85)A
5
Tep = (11°47 — j8'5) x = (7:16 — j2°32)A
@- 7)POWER SYSTEM ANALYSIS
Now let the e.m.f. E = 100 + j0 be transferred from branch AB to
branch EF,
. 53 +74)
Zer= 4) + CEA
= 65 —j1-74
100 + j0
Jeg = es ji = (1434 — j3-9) A
: 53: Does = (F-16935
Tap = (1434 — 739) x Pay = (716 — j232) A
=z —_100+/0_ _ 9.74 4.
and, Zp, = Zyp = 76 = 232 ~ 12:7 + j412 ohms.
(2) The Superposition Theorem
If several e.m.f.s of the same frequency act in a network composed of
linear impedances then the current in any branch is the sum of the
currents which would flow if the various e.m.f.s acted independently
and all the other sources were replaced by their internal impedances.
Zazl54+52
Zg22+dl2
Zorl 4025
T'=100 amps
Fig. 1.4
Example: A three-phase generating station at A with a line voltage of
6-6 kV supplies two substations at B and C through two independent
feeders, the two substations are also interconnected. The impedances
per phase of the interconnectors are; A to B (1 + j2:5) ohms; A to C
(2 + j1:2) ohms and the interconnector (1-5 + j2) ohms. The load at
B is 150 A at a power factor of 0°7 lagging, and at C is 100 A at 0°9
lagging, both power factors being referred to the voltage at A. Calou-
late the current flowing in each feeder. Find also the voltage difference
between the two substations if the interconnector is removed, the loads
being maintained at the above values. The solution will first of all be
obtained by the use of Kirchoff’s Laws.THE TRANSMISSION AND DISTRIBUTION OF ELECTRICAL ENERGY
Take the voltage to neutral at A as the reference vector, Fig. 1.4,
then, when cos ¢ = 0-7, sin 6 = 0-714; when cos $ = 0-9, sin $ = 0-436
Te = 14 + 150(0'7 — j0'714)
Ty = 100(0°9 — j0436) — I
and, O=1,(1'5 + j2) — (90 — j43°6 — L,)(2 + j1'2) +
(4 + 105 — j107)(1 + j2°5)
—26'5 + j3°8 = 267A
90 — j43-6 — (—26°5 + j3°8) = 116 — j474 = 125A
Te = —26°5 + j3'8 + j105 — j107 = 79 — j103 = 130A
When the interconnector BC is removed:
Vy = V4 — 1500-7 — j0714)Ze
6,600 ; 72
= Sy — (1085 — fl07)(1 + 72°5)
= 3,437 — j155 = 3,440 V = 5,960 V line to line
Ve = V4 — 100(0°9 — j0-436)Zp
= 3,810 — (90 — j43°6)(2 ++ j1-2)
3,578 — j21 = 3,579 V = 6,910 V line to line.
‘As an alternative to the above the superposition theorem may be
used, this can be stated in a modified form as follows: ‘If a number of
currents of the same frequency are tapped off from points in a network
of linear conductors, then the current in any particular member is the
vector sum of the currents it would carry if the currents from the net-
work were tapped off.one at a time and all the others were zero.”
This may be applied to the above problem as follows:
Let the load taken off at B be J’ and that taken off at C be 7”, then,
TU’ = 150(0°7 — j0'714) and 1” = 100(0°9 — j0-436)
Consider I’ alone, (I’’ being zero)
then,
a > eee 35 4+j22
Toa x AAG AP, = 15007 — J0714) x FETT
= 568 — j79°9
1+ j2°5
vx
Zc = 7 — j0"
ZieZte 150(0°7 — j0'714) x #34557
= 48:5 — j269
Now let I’ be tapped off (I’ now being zero):
” Zz — 220 — j23°
Ie =I, =1 ZF Ze Fz = 220 —J23'1
7 ZatZ A
Giz: —ZatZe _ .. 67-5 — j20
p= I’ x J, 4 2at Le 67-5 — j20°5POWER SYSTEM ANALYSIS
The iotal currents are therefore:
i Te
48:5 — j269 370 — j79°9
22-0 — j231 67:5 — j20°5 22-0 — j23-1
—265 + j3BA 1160 — ATF A 70:0 — j103 A
(3) Thevenin’s Theorem
This theorem, which is sometimes credited to Helmholtz, states that any
system of linear impedances with two accessible terminals may be re-
placed by an e.m.f. acting in series with an impedance. The e.m-f. is
that acting between the terminals when they are unconnected externally,
and the impedance is that presented by the system when all the e.m.fs,
in the system are zero, the sources being represented by their internal
impedances only.
A modified form of this is the redundant impedance theorem, the
method of applying it is to remove branches until the network is
supplied by one path only. The p.d. across a point from which a
branch was removed is calculated and the impedance of the resultant
network between these two points is also determined, to this is added
the impedance of the branch itself. The quotient of the calculated p.d.
and the impedance then gives the current in that particular branch.
In the previous example imagine the interconnector BC to be dis-
connected. We have already calculated the corresponding values of Vg
and Vc, namely:
V_ = 3,437 — 1553 Ve = 3,578 — j21
The potential of C with respect to B is thus:
(3,437 — 155) — (3,578 — j21) = —141 — 134
Total impedance = (1°S + j2) + (2 + jl'2) + (1 + j2'5) = 4:5 + j57
—141 — j134
F5 + j57
= —265 + j3'8 A as before.
Hence, the current in the interconnector =
(4) Star-delta and Delta~star Transformations
The impedances are, in general, complex and the equations are there-
fore phasor equations. Consider first of all the transformation from
delta to star as shown in Fig. 1.5. The two systems will be equivalent if
the corresponding line currents are identical in magnitude and phase
when corresponding terminals are connected to identical supply systems
or networks. This requires that the impedances, and therefore the
admittances, between corresponding terminals must be the same in each
system.
7THE TRANSMISSION AND DISTRIBUTION OF ELECTRICAL ENERGY
For equal impedances between 4, B and C:
Za t Ze = ZZ, + Zs)(Z + Z2 + Zs) qd)
Ze + Za = Z{Zs + ZZ, + Z2 + Zs) Q
Za 4 Zp = ZZ, + ZIM (Zi + Zz + Zs) G3)
adding (1) to (2) and subtracting (3) we have:
Ze = (Z:Zy + ZiZs + ZsZ, + ZyZ2 — Z,Zs — ZrZs)(Zi + Zr + Zs)
WZ = Z,Z,[(Z, + Z2 + Zs)
Similarly,
Za=Zr2M(Zi+Z2 +23) and Zp= Z,Zs[(Z, + 22+ Zs)
Fig. 1.5
Now consider the star—delta transformation in Fig. 1.6. It is con-
venient to make the transformation in terms of admittances, and for
equal admittances between A and B:
YaYol(Ya + Ys) = Yat YaYai(%i + ¥2)
The solution of equations in this form is cumbersome and a more
convenient technique is to make use of the fact that the circuits will still
be equivalent if equal impedances are connected between any pair of
~Fig. 1.6
terminals in both the star and the delta cases. So long as they are equal
these impedances may have any value; in particular they may be zero.
Thus suppose that terminals B and C are joined together in each case,
then equating the admittances between terminal A and the common
junction of B and C gives:
YA¥a+ YdMYa+ Yet Y= Vet Vs
8POWER SYSTEM ANALYSIS
Similarly:
Ys ¥a+ ¥o(Ya + Yo + Yc) = Ys + Y, when A and C are joined
and
Y¥a + ¥s)/(Ya + ¥a + Yo) = Yi + Y2 when A and B are joined.
These are similar in form to equations (1), (2) and (3) above, they may
be solved in the same way to give:
Y= Ys¥ch(Ya + Ys + Ye)
Y= YeVal(Va + Ya + Yo)
Ys = YaYal(Ya + Ye + Yo)
This shows that the form of the equations in the star-delta trans-
formation of admittances is similar to that of the delta-star transforma-
tion of impedances.
These transformations are used extensively in the simplification of
networks, in particular, using the star-delta version, an unwanted
junction (or ‘node’) may be eliminated.
(5) Millman’s Theorem
This theorem is very valuable for the solution of three-phase systems
supplying an unbalanced set of star-connected loads, particularly in the
qe
Fig. 1.7 Petaining to Millman’s Theorem
four-wire case. Fig. 1.7 shows a three-phase four-wire system, the load
admittances ¥,, ¥; and Y; being, in each case, the total admittance of
the load and the circuit. Yy is the admittance of the neutral con-
nection. The relationships between the supply e.m.fs. and the load
voltages are:
Ey = Eww — Eay = Vio — V0
Ex; = Exy — Eyy = Vio — V0
Ey, = Eyy — Ew = Van — VioTHE TRANSMISSION AND DISTRIBUTION OF ELECTRICAL ENERGY
For the voltage to neutral at the load end we have:
Von = Eww — Vio = Exw — Vio = Esw — Vao a
The current relationship is:
L+h+h+ly=0
Vio¥: + Vio ¥2 + Vio ¥s — Vow¥n = 0
Substituting for Vio, V2o and Vsy from equation (1) this reduces to:
Vow = (Eww Yi + Eww Ya + Esw ¥s)\/(¥i + Ya + Ya + Yn)
which can be generalised as:
Vow = SEY/EY
In the three-phase four-wire system the summation includes all four
admittances, but only three voltages, since there is no applied voltage
in the neutral circuit. In the three-wire case the equation still holds and
Yy = 0.
Example: A three-phase 230-volt supply, total phase impedances
(5 +j0), (3 + j0'5) and (5 + j5), neutral impedance (2 + jl).
Taking E,y as the reference quantity:
Eyy = 230 +j0 ;
Eqy = —115 —j199
Eyy = —115 +199
Z,=54+0 J. ¥; = 0-200 — 0-000
Z,=3 +05 1. ¥_ = 0324 —j0-054
Zy=54-J5 1%
Zya24jl .
E,wY, = 230(0-2 — j0)
EwY. =
Ew Ys=(-115+f19)O1—jOl) = 84 4314
EEY = 645 — j2689
Von = LEY/EY = 13-73 —j25V
and Vio = E,w — Vow = (230 + j0) — (13°73 — j21-5) = 2163 + j21°5
Similarly
Veg = —128-7 —f177-5V
and V3 = —128-7 + j2205V
10POWER SYSTEM ANALYSIS
The currents may be obtained as follows:
Ty = Vy Y, = (2163 + j21-5)(0'2 + j0) = 43:26 + j43 A
Ty = Vay ¥y = 51:28 — j50°55 A
Ty = Vp Ys = 9°18 + j3492 A
Ty = Vn Yy = 1:20 —f1135A
(6) Kouwenhoven’s Short Circuit Theorem
This theorem states that if a number of generators in parallel are
supplying a load of a given impedance, the common terminal p.d. is
equal to the product of the sum of the generator short circuit currents
and the total network impedance.
Is Tt Iyt Tat
ee
Fig. 1.8 Kouwenhoven's Theorem
Consider Fig. 1.8 which shows » generators in parallel feeding a load
of total impedance Z,, the internal impedance of generator being
Zr, ete.
Let Ing = Ep/Z, be the short circuit current of generator n at its open
circuit e.m.f. of E,,
then £,—-4Z,=V
' os
eral iasea
i
E, — TZ = V.
IZ, —1.Z, =V
i i i
' H i
InZn— Zn = V
le —h = Viz)
pee
hy ho =VisTHE TRANSMISSION AND DISTRIBUTION OF ELECTRICAL ENERGY
Adding this latter set of equations:
Ll, — LI = 2V/Z
o Shs T+ LV/Z
= VIZ, + VEI/Z
= V(I/Z, + S1/Z) = V/Z_ where Z; is the total
impedance.
V = XI,Z,y which proves the theorem.
(7) The Equivalence of Current and Voltage Sources
The solution of problems may involve the substitution of a voltage
source by an equivalent current source or vice versa since it is usually
more convenient to deal with one form only. Voltage sources are most
commonly met with in power system analysis; from the calculation
I Eo
Zee
Voltage
source a i { Zs Zz
ef
=—
(a) Current (b)
source
Fig. 1.9
point of view these may be represented by a source of e.m.f., E, in series
with an impedance, Z,., equal to the internal impedance of the source.
In some instances, however, current sources (e.g. current transformers)
may be involved, these may be considered as an ideal current source, J,
in parallel with an impedance, Z,,.
A voltage source and a current source may be considered to be
equivalent if identical load currents flow in equal impedances con-
nected across their terminals. Thus the current from the voltage source
shown in Fig. 1.9(a) flowing in the load impedance Z, is given by:
E
HS Fe ZE
Fig. 1.9(b) shows a current source which drives a current through its
load impedance equal to
Zul |
Za t+ Z
The two sources are equivalent if:
E=IZ, and Z,y=Zy
=
12POWER SYSTEM ANALYSIS
LOOP AND NODE EQUATIONS
One of the most convenient methods of solving power system networks
is the systematic application of Kirchoff’s Laws. These may be used to
obtain a set of simultaneous equations which can then be solved either
by manipulative techniques or by the use of a digital computer.
Consider Fig. 1.10 which shows a simple network supplied from
voltage sources, the nodes are identified as a, b, etc. and the impedances
between them as Z,), etc. The loop currents are drawn in as J,, J;, etc.
Fig. 1.10 Loop equations
Then, for the path of Jy:
E, — E, = I(—Zaa) + 1p .0 + Is(—Zagh + L(Zoe + Zea + Zaz) (1)
The left-hand side of this equation is the sum of the voltage rises round
the loop in the assumed positive direction for J,. The right-hand side
consists of the loop current multiplied by the sum of the impedances
around the loop plus the voltage drops (with the correct sign) due to
every other loop current flowing in each impedance of the original loop.
In this particular case the coefficient of J, is zero since it does not flow
in any of the impedances of the original loop. Equation (1) may be re-
written as: :
Ey = Za, + Zaalr + Zasls + Zaale
where Zs; (= — Zea), Za2 (= 0) and Z,3 (= —Zy,) are impedances com-
mon to the loop current in question and one other current as indicated
by the suffixes, e.g. Z,, carries J, and J,. These are called the mutual
impedances. Z,4 is the total impedance of the loop in question and is
called the self-impedance, whilst £, is the effective applied voltage
13THE TRANSMISSION AND DISTRIBUTION OF ELECTRICAL ENERGY
included in the loop. This rule may be applied to all of the loops in
turn to obtain a set of equations of the form:
Ex = UZ pal
These equations may then be solved simultaneously to obtain the loop
currents which can then be combined to give the current in each in-
dividual impedance.
Fig. 1.11 represents the same system as that shown in Fig. 1.10 with
the voltage sources replaced by equivalent current sources using the
theorem given previously, and the impedances replaced by the corre-
sponding values of admittance. The voltages between each junction (or
Fig. 1.11 Node equations
node) and earth are denoted by V,, etc. Applying Kirchoff’s current
Law to node a gives:
hai, hy
but, J, = V,/Z, = V,Y, and
Jan = (Va — Vo)/Zan = Va — Vr)» Yan
Hence, J, == Vs¥e + (Va — Vo)» Yan + (Va — Va)» Yos
Yan + You) > Vn (— Yan) + V0) + Va(— Vea)
In this case the left-hand side is the current flowing directly into a node
from a current source whilst the right-hand side is the voltage at the
node multiplied by the sum of the admittances terminating on the node
plus the voltages at cach of the other nodes connected through one
series admittance only to the node in question and multiplied in each
case by the negative of the particular series admittance.
14POWER SYSTEM ANALYSIS
The equation may now be re-written:
Ta = Yaa» Va + Yao + Y'acVe + ¥'aaVa
where Y's, (= —Yas)s Y'ec (= 0) and Y'qa(=.— Yaa) are the transfer,
or mutual, admittances and are equal to the negative of the admittance
connected between the nodes identified by the two subscripts, Yq is the
sum of all the admittances terminating at the node and is called the self,
or driving-point, admittance and J, is the current flowing directly into
the node from a constant-current source. Equations may be obtained
in this way for each node in the circuit and solved simultaneously to
obtain the node voltages which may then be used to calculate the branch
Fig. 1.12
currents. It is important to note that the self and mutual admittances
are not necessarily the reciprocals of the particular self and mutual
impedances.
Having obtained a set of either the loop or node equations then these
must be solved and, in all but the most simple networks, the number of
equations is likely to be large, the solution being extremely tedious.
‘As an example consider the network shown in Fig. 1.12, the e.m.f.s
and resistances have the values shown on the diagram, the loop currents
are I, I, and J;. The branch currents are i,, i2, is, ig, is and ig.
Loop abco: Ey = Eoa — Exe = 5
LZ = 184142) = 6h hy = -1.13 b2n = —2h
5=6,—h—2h (1)
Similarly, from a consideration of loops bde and doc
—10 = —I, + 7h, — 5h (2)
and 5 = —2/,— 5h + 9, (3)
From (1) I, = 3%, — 0°51, — 25 (4)THE TRANSMISSION AND DISTRIBUTION OF ELECTRICAL ENERGY
Substitute in (2);
1, = 16841, — 2:368 (5)
From (4) I, = 21581, — 1316
Substituting in (3)
1, =0611A
“ = —1365A
and
The branch currents may then be found as follows:
i, = 1, = 0°661 A; i, = —, = 1365 A; i, =, — 1, = 1-976
ig = I, — 1p = —1:368 A; is = 1, — ; = 0608 A; is = 5 = 0003 A
As an alternative the above example may be solved by the nodal
voltage method. The circuit is redrawn in Fig. 1.13, the voltage sources
‘io
AW
Fig. 1.13
having been replaced by their current equivalents and the resistances
by the corresponding conductances.
For node B:
Current entering node = 3333 + 10 = 13333 A
Applying the nodal equation rules:
13333 = V,(0'333 + 1+ 1) + Ve(— 1) 4 Vp (— 1)
It is not necessary to consider the term incorporating Vy since this node
can be considered as a reference and its voltage put equal to zero. The
voltages of the remaining nodes will then be found relative to that of
node 0.
16POWER SYSTEM ANALYSIS
Thus, 13:333 = 2:333Vy — Vo — Vp 6)
Similarly, for node C25 = —Vy + 1-7Ve — 0-2Vp a
and fornode D > —10 = —V,—02Ve + 1-7Vp (8)
From equation (6) Vp = 2°333Vy — Ve — 13°333
Substituting in (7) Ve = —0°088 + 0°772Vy
and, from (8) Vz = 8333 V
which gives Ve = 6345V and Vy = —0:233V
The currents may then be found by dividing the voltage difference
between a pair of nodes by the resistance between them, e.g.
,-vanVe
; Roc
AIDS TO NETWORK ANALYSIS
Modern power systems are extremely complex and although equations
for current flow, etc., in each branch may be developed using techniques
outlined previously, the solution of these equations is excessively time-
consuming. In order to simplify the work and to carry out detailed in-
vestigations into the planning and operation of power systems under a
number of different operating conditions, automatic aids to network
analysis have been developed. These may be grouped under the follow-
ing headings:
(1) Models.
(2) Analogues.
(3) Computers.
(1) Models
These are small-scale replicas of the system in which the voltages and
currents are reproduced to a smaller scale and impedances to a larger
scale. The results of the investigations performed are converted to
actual values of system currents and voltages using the appropriate
scale factors. An attempt has been made to construct model networks
supplied by small-scale replicas of the actua! rotating machines. The
design of such a network is relatively simple, but it is much more
difficult to construct a model machine which has exactly the same
characteristics as the original
A more widely used technique is to represent the machine by a device
which gives a voltage. variable in magnitude and phase, together with
a variable series impedance, this combination being used to feed the
model network. The behaviour of the network can thus be studied in
detail, but only limited information is provided regarding the perform-
17THE TRANSMISSION AND DISTRIBUTION OF ELECTRICAL ENERGY
(o)
Weotral
bt
Fig. 1.14
18POWER SYSTEM ANALYSIS
ance of the actual machines in the power system. Models of this type are
called a.c. network analysers. The major problem in their design is the
size of the inductor units and, in order to reduce this size it may be
found preferable to operate the model at a relatively high frequency
(400 Hz-1,000 Hz) although this introduces an additional scale factor,
time. An alternative is the conjugate impedance analyser. Since the
significant parameters of a power system are nearly all inductive a
simple analyser can be built in which inductance is represented by
capacitor units and vice versa. The number of inductor units required
is small and since accurate and almost lossless capacitors are available
for low frequencies such analysers may be built economically for use at
50 Hz. A simplification of this method, which may be adequate for
some requirements, is to neglect system resistance entirely and to
represent system inductance by resistance units on the analyser.
Although this device can only be used for limited types of calculation
its cost is reduced to about 10% of that of the conventional analyser.
Fig. 1.14 shows a simple power system, its equivalent circuit and the
method of connecting individual units on the analyser to represent the
actual system.
(2) Analogues
These are devices whose behaviour follows equations which are identical
to those applicable to the power system in the particular problem under
consideration. The main developments in this field are the transformer
analogue and the analogue computer.
The transformer analogue uses a number of specially wound trans-
formers, each of which represents one branch of the system under study
and each of which has two output windings. Across one of these is
developed a voltage proportional to that across the resistive part of the
branch in the actual circuit, and a voltage proportional to that developed
across the reactive part is produced across the second winding. These
transformer units may then be interconnected to represent the complete
system and the device can be used for the solution of simultaneous
equations with complex coefficients such as those met with in power
system analysis.
In the analogue computer electronic circuit elements are used which
obey equations identical with those obtained when the behaviour of
machines operating under transient conditions is studied, and this
device is suitable for such work.
(3) Digital Computers
These are machines which are capable of carrying out large numbers of
mathematical operations in a very short time. In order to use such a
machine it must first be programmed, i.e. instructions must be fed into
the machine detailing the operations which it is to perform, the problem
19THE TRANSMISSION AND DISTRIBUTION OF ELECTRICAL ENERGY
having been broken down into a number of simple steps. The data for
the particular problem is then fed into the machine and the solutions
are printed out. This is a very valuable and flexible tool which finds
many applications in the field of power system analysis, and it will no
doubt be used to an ever-increasing extent in the future. Due to its
complexity, however, it is an extremely expensive item of equipment and
expert mathematical help must be available to prepare the initial
programme.
20