Ihaveincludedacollectionofnotesthatwehavepulledtogetherovertheyearsthat
guideusthroughtypicalcoilselectionsforcustomairhandlingunits.
CoilsBasics:
HeaderOrientationSupplylowleaving,returnhighentering
CoilHandFacetheenteringairsideofthecoiltodetermineitshandconnection.
Withairatyourbackwhichside(hand)aretheheaderson?
PlateFinTypeMuchmorecommon,easiertoclean
SpiralFinTypeLesscommon.Lesspressuredrop.SpiralFinhasadvantagein
steamheatcoilasseparatetubescanhandlehigherthermalexpansion.
#Rows/Circuits=#ofPasses
CoilConstruction:
TubesCopperisstandard
5/8TubeO.D.isstandard.1/2TubeO.D.ismoretypicalonDX
Tubethicknessforwatercoilsusuallystartsat.020,butweusuallyspecifya
.025or.035.BelledendsallowforlargerUbendsandlesspressuredrop.
Wetypicallyusethem
FinsAluminumisstandardstandardfinthickness.0075,wesometimesuse
.0095forhospitals/labs/highquality,.006forlowercost
CasingGalvanizedisOKonSteamorHWCoilsbutChilledWater(CW)coilsare
typically16gauge304stainlesssteel
typicalcasingis11/2legbutonmostcoilsifspacingistightcanbe0.75or1
HeaderseitherCarbonSteelorCopperHeadersarestandard
oftenusenonferrousheadersforcoolingcoilswheretherewillalotof
moistureandcondensation
MPT(MalePipeThread)istypicalforcoilconnections
CoilSizingFinHeight
heatingcoilsmaxFHof60ismaxreasonablehandlingsizeinashop
coolingcoilsmaxFHforindividualcoolingcoilswithadrainpanexpectedto
havesignificantcondensationis42sincecondensationfromupperpartcancut
airflowinbottompart
CoilSizingFinLength
withnoglycol,finlengthcanbewhateverisneededupto180.Withglycolthe
WPDgoesupsignificantlywithhigherFLsoprobablyneedtobreakbigcoilsup
intoshorterlengthsections.
typicalmaxcoilwidthorlengthinanAHUisFL+15toouterdimensionsof2
wallAHU
Coatingsifacoilisgoinginunitwithin35milesoftheoceanorinanareawhere
corrosionmightbeafactor,needtoincludecoating.Electrofinisthebest,goodup
toanynumberofrows,highlyflexiblesowontchipeasily.
SelectionCriteria:
FaceVelocities
CoilType AllowableVelocity
HotWater(HW) 2001200FPM
Steam 2001200FPM
ChilledWater(CW) 200550FPM
DX 200550FPM
TypicalHotWaterCoil600700FPM
TypicalChilledWaterCoil500FPM
OnaCoolingCoilAirvelocitiesabove500fpmisthepointwherewater
dropletscanleavetheouteredgeofthefin.Thisiscalledmoisturecarryover.
Wedesigntoavoidthis.
AirPressureDropWetypicallydesignforlessthananinchonallapplications
andlookforapressuredropnear1/2.
WaterCoilPressureDrop25WaterPressureDrop(WPD)isaboutmaximum
usebellendstodecreasepressuredrop.
forHWcoils,WPDupto10ftisusuallyOK
forCHWcoils,WPDupto1520ftisusuallyOK
TubeVelocitystaybelow8ft/sec,3to6ft/secistypical.Numberishigherwith
glycol
Optimizevelocitythroughcircuiting
ReynoldsFlowNumberunder2100cancauselaminarflow.Caneitherchange
circuit(preferred)oraddTurbulators(turbulatorsaddpressuredrop)
MaxGPMtypicallylistedbyconnectionsizes
GlycolPolypropylene(propyleneglycol=PG)ismorecommonlyusedantifreeze
FoulingFactorsUse0ifyoucan.Typical#sareRis(inside).0005Ros
(outside).001
OtherRecommendations:
Ifspaceallows,makingcoilsectionlargertoreducevelocity.Movingto300400
FPMvelocityaddsasmall%firstcostbutsavesbiginsupplyfanHPoverlifeof
unit.
Glycol%hasadrasticnegativeeffectontransferpropertiesmakingGPM,coiland
pipingsizinggoup.Alwaysquestionunitdesignandoperationiftheyrequest40%
IfcoilsaretobeinalargeVAVAHUapplication,velocityshouldnotdropbelow250
fpmorlaminarairsidewillreduceeffectiveness.Facedampersmaybeneededto
controlairflow.
Seemanufacturerforfurtherinformationoncoils:Aerofin(http://www.dachvac.com/our
manufacturers/aerofin/)
(http://www.dachvac.com/category/askrick/)
Filedunder:AirHandlingUnits(http://www.dachvac.com/category/airhandlingunits/)
2Comments
DEEPAKSUNNAGERE
November24th,2013(http://www.dachvac.com/customairhandlingunitscoilselection
guidelines/#comment2884)
HELLO,
WHYALWAYSINAHUS&FCUSCHILLEDWATERSUPPLYCONNECTIONISIN
BOTTOMSIDE&RETURNATTHETOP.COULDYOUPLEASETELLME
TECHNICALREASONBEHINDTHIS.
Reply(http://www.dachvac.com/customairhandlingunitscoilselectionguidelines/?
replytocom=2884#respond)
prashant
March10th,2014(http://www.dachvac.com/customairhandlingunitscoilselection
guidelines/#comment3467)
airpressuredropacrosscoolingoftheahuinmmh2o,inch,pascaletc
Reply(http://www.dachvac.com/customairhandlingunitscoilselectionguidelines/?
replytocom=3467#respond)
LeaveaReply
Youremailaddresswillnotbepublished.Requiredfieldsaremarked*
Comment
Name*
Email*
Website
PostComment