Vous êtes sur la page 1sur 4

Stat-X

Stat-X Thermal / Manual Unit Stat-X Electrical Unit

Marine Detection & Suppression System



Stat-X Application Guide

What Stat-X system do I need?

Is stand alone automatic


actuation required?

YES NO

Stat-X Is a manual or electrical actuation


Thermal Unit system required?

Stat-X Stat-X
Model Size: Manual Unit Electrical Unit
30T-500T

Thermal Actuation:
Model Size: Model Size:
70C
30T-500T 30E-2500E
95C
123C

Manual Pull Actuation: NOTE:


Horizontal Installation as part of
an electrical detection
Vertical and actuation system

Stat-X Electrical Units

Electrical Unit General Specifications:


Model 30E 60E 100E 250E 500E 1000E 1500E 2500E
Part Number 129984 129985 129986 129987 129988 129989 129990 129991
Aerosol Mass (grams) 30 60 100 250 500 1000 1500 2500
Ship Wt./unit Packaging 0.36 0.48 1.44 2.72 3.63 7.05 8.60 11.33
(kg)
Length (mm) 74 107 121 150 180 170 203 267
Diameter (mm) 51 51 76 127 127 203 203 203
Discharge Time (sec) 8.0 11 12.0 12.0 23.0 16.0 23.0 36.0
Initiation Current (Amp) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Pulse Duration 50 50 50 50 50 50 50 50
(millisecond)
Max. Supervisory .005 .005 .005 .005 .005 .005 .005 .005
Current (Amp)

Coverage Parameters (Class B Fuels):


Model Maximum Volume Coverage Maximum Area Coverage Maximum Installation Height
(m3) (m x m) (m)
30 E 0.48 1.20 x 1.20 1.8
60 E 0.97 1.70 x 1.70 2.0
100 E 1.61 2.18 x 2.18 2.50
250 E 4.03 3.45 x 3.45 4.50
500 E 8.06 4.88 x 4.88 4.50
1000 E 16.1 4.88 x 4.88 5.00
1500 E 24.2 4.88 x 4.88 5.00
2500 E 40.3 4.88 x 4.88 5.00

Minimum Application Densities:

Class of Fire Stat-X minimum applications density grams / m3


Class A, surface fires 97.0
Class B 62.0
Class E Based upon involvement of Class A or B fuels

Mounting Bracket:

Generator Size 30 & 60 100 250 & 500 1000, 1500 & 2500
Bracket Part number 129993 129994 129995 129996
(ordered separately)
Heavy Duty Vehicle Bracket 130396 130397

Stat-X Thermal / Manual Units
Thermal / Manual Unit General Specifications:

Model 30T 60T 100T 250T 500T


Part Number 129997 129998 129999 130000 130001
Aerosol Mass (grams) 30 60 100 250 500
Ship Wt./unit Packaging (kg) 0.26 0.35 1.44 2.72 3.63
Length (with actuator) (mm) 109 142 152 168 218
Diameter (mm) 51 51 76 127 127
Discharge Time(sec) 8.0 10.5 11.5 12.0 21.0

Coverage Parameters (Class B Fuels):


Model Maximum Volume Coverage Maximum Area Coverage Maximum Installation Height
(m3) (m x m) (m)
30 T 0.48 0.50 1.1
60 T 0.97 0.61 1.8
100 T 1.61 0.92 1.8
250 T 4.03 2.13 2.0
500 T 8.06 3.72 2.5

Activation Temperature:

Activation Temperature Options Manual 70C 95C 123C


Part Number (ordered separately) 130006 (horizontal) 130002 130003 130004
130007 (vertical)

Minimum Application Densities:

Class of Fire Stat-X minimum applications density grams / m3


Class A, surface fires 97.0
Class B 62.0
Class E Based upon involvement of Class A or B fuels

Mounting Bracket:
Generator Size 30 & 60 100 250 & 500 1000, 1500 & 2500
Bracket Part number 129993 129994 129995 129996
(ordered separately)
Heavy Duty Vehicle Bracket 130396 130397

Email: firesafety@chubb.com.au
Telephone: 13 15 98

Chubb Fire & Security Pty Ltd. ABN 4700 006 7541
We reserve the right to alter specifications at any time in accordance with our policy of
continuous development. Information in this brochure is correct as at March 2011.