Vous êtes sur la page 1sur 174

ELECTRICAL ENGINEERING & DESIGN

Relay settings

Plant : Xuan Thanh

Type : Protection relay settings, MV- & LV-switch gear.

Order No. : 14-45344 Equipment No. :

Reg. No. : 80040412 Version No. : 1.0

Issued by : CB
Date : 12.11.16
Approved by : CBC

Q:\Orders\X\Xuan Thanh 14-45344\05 Electrical Engineering\09 Power Distribution System\Relay settings\Report\Setting report.doc Page 1
Reg. no. 80040412
Relay settings Version no. 1.0
Plant : Xuan Thanh, 14-45344 Date: 12.11.16

Table of contents

1.0 General remarks. ..................................................................................................................................3

2.0 Network configuration. ........................................................................................................................3

3.0 Single Line Diagram.............................................................................................................................3

4.0 Protection & selectivity. .......................................................................................................................3

5.0 Medium voltage switch gear. ...............................................................................................................3


5.1 Definite Time (DT) delay settings on the pick-up currents. ...............................................................3
5.2 Maximum pick-up levels for the over current & earth fault protection. .............................................4
5.3 Protection relays. ................................................................................................................................4
6.0 Low voltage switch gear. ......................................................................................................................4
6.1 Time delay settings on the pick-up currents. ......................................................................................4
6.2 Maximum pick-up levels for the over current protection. ..................................................................4
6.3 Circuit breaker protection relay. .........................................................................................................5
7.0 Relay settings & selectivity curves. ......................................................................................................5

Q:\Orders\X\Xuan Thanh 14-45344\05 Electrical Engineering\09 Power Distribution System\Relay settings\Report\Setting report.doc Page 2
Reg. no. 80040412
Relay settings Version no. 1.0
Plant : Xuan Thanh, 14-45344 Date: 12.11.16

1.0 General remarks.

This document specifies the proper protective settings of relays in the switch gear supplied for distribution at
Xuan Thanh Cement plant.

2.0 Network configuration.

The plant network is designed as a single bus bar radial isolated network, for details see single line diagrams.
The switch gear is of fuse less design.
Protection is achieved by microprocessor controlled relays forming an integrated part of the LV-
compartment in the MV feeder panels and the incoming feeder in the LV switch gears.

3.0 Single Line Diagrams.

Please refer to FLS-drawings: 10373820 & 10374396 ver. 4.0.

4.0 Protection & selectivity.

Fault protection against, the contract specified, electrical fault situations must be set in protection relay
parameters.
An electrical fault in the network must trip the upstream circuit breaker nearest the fault location and clear
the fault within acceptable time.
The setting level of each protection function must ensure that the protection is dependable and secure.
This protection must be fully dependable and secure at high as well as low short circuit levels in the network.

Full selectivity must be achieved by Definite Time settings in all protection relays.

5.0 Medium voltage switch gear.

5.1 Definite Time (DT) delay settings on the pick-up currents.

The different feeder types are regarding trip delay on the phase time over current protection (50/51) to be
set as:

SR-motor feeders: 3 steps, instantaneous, 2000 ms and 50 s.


SC-motor feeders: 3 steps, instantaneous, start-up time + 1000 ms and 50 s.
Transformer feeders: 3 steps, instantaneous, 200 ms and 50 s.

Trip delay on the directional earth fault (67N) to be set as:

Motor feeders: 1 step, 10 s.


Transformer feeders: 1 step, 10 s.

Q:\Orders\X\Xuan Thanh 14-45344\05 Electrical Engineering\09 Power Distribution System\Relay settings\Report\Setting report.doc Page 3
Reg. no. 80040412
Relay settings Version no. 1.0
Plant : Xuan Thanh, 14-45344 Date: 12.11.16

5.2 Maximum allowed pick-up levels for the over current protection.

To obtain pick-up in all fault situations a maximum allowed pick-up current must be selected.

In ETAP (document 80040177) short circuit calculations have been made on the respective switchgears.

The lowest fault current value calculated is a 2-phased fault on switchgear 402MV300 of 16.2 kA.

This however is a theoretical value (bolted short circuit).

In case of short circuit an arc will arise and dampen the current at fault place, in "worst case" down to 40% of
the bolted value.
This must be taken into consideration.

The fault current can be limited to 0.4 x 16.2 = 6.5 kA.

As additional safety margin the maximum pick-up value that will be used in the settings is 5 kA.

Distribution on Xuan Thanh is designed as an isolated network so earth faults cant be considered as
overcurrent faults it is capacitive leakage currents, protection form 67N is used for detection and tripping.

The capacitive leakage currents are calculated in 80040177

1.5 A is used for pick-up on 67N.

5.3 Protection relays.

The relay(s) used for fault protection in the 6.3 kV feeders is of make: Schneider, type: VAMP 300
and in the project mainly used for:

- Over current protection.


- Leakage current protection.
- Overload (thermal) protection.
- Motor protection.
- Transformer protection.

For details about the protection relay(s), please refer to manual forming part of the Vendor Documentation
for MV switchgear.

6.0 Low voltage switch gear.

6.1 Time delay settings on the pick-up currents.

The incoming feeder in each low voltage switch gear must obtain selectivity to the upstream MV circuit
breaker.
The delay time on the pick-up for the short circuit protection is set at 100 ms.
In case of incoming feeders with possible in feed from utility or generator stand-by supply, the circuit
breaker for the generator in feed must be set with a delay time of 300 ms.

6.2 Maximum pick-up levels for the over current protection.

The pick-up level for the over current protection is set at 2.5 times the rated current of the circuit breaker.
Separate for the generator in feed circuit breaker, the pick-up is set at 1.5 times the rated current.
Q:\Orders\X\Xuan Thanh 14-45344\05 Electrical Engineering\09 Power Distribution System\Relay settings\Report\Setting report.doc Page 4
Reg. no. 80040412
Relay settings Version no. 1.0
Plant : Xuan Thanh, 14-45344 Date: 12.11.16

The pick-up level for the over current protection is set at the rated current in all circuit breakers.

6.3 Circuit breaker protection relay.

The protection relay integrated in circuit breaker is of the type ABB SACE, PR 122/P. For details, about the
protection relay please refer to the manual forming part of the Vendor Documentation for LV Switchgear.

7.0 Relay settings & selectivity curves.

The switch gear panels have, based upon the needed protection functions, been designed in 3 different types.

Protection type 1: For motor feeders.


Protection type 2: For transformer feeders.
Protection type 5: For LV incoming feeders.

Relay settings and selectivity curves:

MV relay settings

101MV100 page 6 - 21
101MV200 page 22 - 31
301MV100 page 32 - 56
302MV100 page 57 - 70
401MV100 page 71 - 110
401MV200 page 111 - 131
401MV300 page 132 - 144
402MV300 page 145 - 154
502MV100 page 155 - 163

LV relay settings

101LV100 401LV220 page 164

Phase time over current selectivity curves

101MV100 page 165


101MV200 page 166
301MV100 page 167
302MV100 page 168
401MV100 page 169 - 170
401MV200 page 171
401MV300 page 172
402MV300 page 173
502MV100 page 174

Q:\Orders\X\Xuan Thanh 14-45344\05 Electrical Engineering\09 Power Distribution System\Relay settings\Report\Setting report.doc Page 5
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 101MV100 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A01

Limestone crusher, 111HC100M01, 2000 kW

Functions Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Motor nom current 1 - xxxx A Imot, comp 201 A
CT Primary 1 - xxxx A 300 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

46, Unbalance Load protection, negative phase sequence

PROTECTION > UNBALANCE I2>


Enable for I2> ON / OFF ON
Parameters
Pick-up setting K2 2 - 70 %In 15 % 30,2 A
Operation delay 1 - 600 s 5s

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 1 x Imot 201,0 A
Alarm setting 60 - 99 %  % 191,0 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 4,5 x tau 144,0 min
Max overload at +40 C 70 - 120 %In 100 % 201,0 A
Max overload at +70 C 50 - 100 %In 65 % 130,7 A
Ambient temperature "-55 - 125 C" 42 C

Page6
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 101MV100 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A01

Limestone crusher, 111HC100M01, 2000 kW

Functions Setting Range Prefix Setting value Actual value

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1,1 x Imot 221,1 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 22 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2 x Imot 402,0 A
Operation delay 0.04 - 300 s 2s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 5 x Imot 1.005,0 A
Operation delay 0.04 - 300 s 0.04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

Page7
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 101MV100 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A01

Limestone crusher, 111HC100M01, 2000 kW

Functions Setting Range Prefix Setting value Actual value

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

48, Stall protection

PROTECTION > STALL PROTECTION Ist>


Enable for Ist> ON/OFF ON
Parameters
Motor start detection current 1.3-10 1,3 xImot 261 A
Nom motor start current 1.5 - 10 1,6 xImot 322 A
Delay type DT / INV INV
Operation Delay 1 - 300 s 22 s

Page8
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 101MV100 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A01

Limestone crusher, 111HC100M01, 2000 kW

Functions Setting Range Prefix Setting value Actual value

66, Number of starts

PROTECTION > FREQUENT START PROTECTION N>


Enable for N> ON/OFF ON
Parameters
Max motor starts/hour 1 - 20 2 starts/hour
Min time between motor starts 1 - 100 20 min

Page9
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 101MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A03

Limestone crushing department, 800 kVA

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 73 A
CT Primary 1 - xxxx A In 75 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 0,97 In 72,8 A
Alarm setting 60 - 99 %  % 69,1 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 50,0 min
Max overload at +40 C 70 - 120 %In 100 % 72,8 A
Max overload at +70 C 50 - 100 %In 65 % 47,3 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1,05 x In 78,8 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page10
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 101MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A03

Limestone crushing department, 800 kVA

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,43 x In 182,3 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 9,8 x In 735,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page11
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 101MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A03

Limestone crushing department, 800 kVA

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page12
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 101MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A04

Coal intake department, 630 kVA

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 58 A
CT Primary 1 - xxxx A In 75 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 0,77 In 57,8 A
Alarm setting 60 - 99 %  % 54,9 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 50,0 min
Max overload at +40 C 70 - 120 %In 100 % 57,8 A
Max overload at +70 C 50 - 100 %In 65 % 37,5 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 0,85 x In 63,8 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page13
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 101MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A04

Coal intake department, 630 kVA

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 1,93 x In 144,8 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 9,8 x In 735,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page14
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 101MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A04

Coal intake department, 630 kVA

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page15
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 101MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A05

Clinker loading department, 1000 kVA.

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 92 A
CT Primary 1 - xxxx A In 100 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 0,92 In 92,0 A
Alarm setting 60 - 99 %  % 87,4 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 50,0 min
Max overload at +40 C 70 - 120 %In 100 % 92,0 A
Max overload at +70 C 50 - 100 %In 65 % 59,8 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1 x In 100,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page16
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 101MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A05

Clinker loading department, 1000 kVA.

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,3 x In 230,0 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 9,8 x In 980,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page17
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 101MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A05

Clinker loading department, 1000 kVA.

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page18
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 101MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A06

Spare feeder

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 0A
CT Primary 1 - xxxx A In 150 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In In 0,0 A
Alarm setting 60 - 99 % % 0,0 A
Time constant tau 2 - 180 min min
Rel. Cooling time contant 1 - 10 x tau x tau 0,0 min
Max overload at +40 C 70 - 120 %In % 0,0 A
Max overload at +70 C 50 - 100 %In % 0,0 A
Ambient temperature "-55 - 125 C" C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In x In 0,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s s
Include Harmonics ON / OFF ON

Page19
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 101MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A06

Spare feeder

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In x In 0,0 A
Operation delay 0.04 - 300 s s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 9,8 x In 1.470,0 A
Operation delay 0.04 - 300 s 1,5 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.3 - 300 s s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page20
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 101MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A06

Spare feeder

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page21
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 101MV200 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A01

Additive crusher, 212SB100M01, 1400 kW

Functions Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Motor nom current 1 - xxxx A Imot, comp 142 A
CT Primary 1 - xxxx A 200 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

46, Unbalance Load protection, negative phase sequence

PROTECTION > UNBALANCE I2>


Enable for I2> ON / OFF ON
Parameters
Pick-up setting K2 2 - 70 %In 15 % 21,3 A
Operation delay 1 - 600 s 5s

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF
Parameters
Maximum continous current 0.1 - 2.40 x In 1 x Imot 142,0 A
Alarm setting 60 - 99 %  % 134,9 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 150,0 min
Max overload at +40 C 70 - 120 %In 100 % 142,0 A
Max overload at +70 C 50 - 100 %In 65 % 92,3 A
Ambient temperature "-55 - 125 C" 42 C

Page22
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 101MV200 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A01

Additive crusher, 212SB100M01, 1400 kW

Functions Setting Range Prefix Setting value Actual value

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1,1 x Imot 156,2 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 22 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2 x Imot 284,0 A
Operation delay 0.04 - 300 s 2s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 5 x Imot 710,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

Page23
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 101MV200 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A01

Additive crusher, 212SB100M01, 1400 kW

Functions Setting Range Prefix Setting value Actual value

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

48, Stall protection

PROTECTION > STALL PROTECTION Ist>


Enable for Ist> ON/OFF ON
Parameters
Motor start detection current 1.3-10 1,3 xImot 185 A
Nom motor start current 1.5 - 10 1,6 xImot 227 A
Delay type DT / INV INV
Operation Delay 1 - 300 s 22 s

Page24
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 101MV200 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A01

Additive crusher, 212SB100M01, 1400 kW

Functions Setting Range Prefix Setting value Actual value

66, Number of starts

PROTECTION > FREQUENT START PROTECTION N>


Enable for N> ON/OFF ON
Parameters
Max motor starts/hour 1 - 20 2 starts/hour
Min time between motor starts 1 - 100 20 min

Page25
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 101MV200 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A03
12
Clay & additive crushing department, 1250 kVA

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 115 A
CT Primary 1 - xxxx A In 125 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 0,92 In 115,0 A
Alarm setting 60 - 99 %  % 109,3 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 50,0 min
Max overload at +40 C 70 - 120 %In 100 % 115,0 A
Max overload at +70 C 50 - 100 %In 65 % 74,8 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1 x In 125,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page26
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 101MV200 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A03
12
Clay & additive crushing department, 1250 kVA

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,3 x In 287,5 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 9,8 x In 1.225,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page27
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 101MV200 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A03
12
Clay & additive crushing department, 1250 kVA

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page28
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 101MV200 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A04

Spare feeder

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 0A
CT Primary 1 - xxxx A In 150 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In In 0,0 A
Alarm setting 60 - 99 % % 0,0 A
Time constant tau 2 - 180 min min
Rel. Cooling time contant 1 - 10 x tau x tau 0,0 min
Max overload at +40 C 70 - 120 %In % 0,0 A
Max overload at +70 C 50 - 100 %In % 0,0 A
Ambient temperature "-55 - 125 C" C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In x In 0,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s s
Include Harmonics ON / OFF ON

Page29
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 101MV200 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A04

Spare feeder

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In x In 0,0 A
Operation delay 0.04 - 300 s s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 9,8 x In 1.470,0 A
Operation delay 0.04 - 300 s 1,5 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page30
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 101MV200 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A04

Spare feeder

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page31
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A01

Raw Mill 1, 321MD140M01, 3800 kW

Functions Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Motor nom current 1 - xxxx A Imot,comp 378 A
CT Primary 1 - xxxx A 500 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

46, Unbalance Load protection, negative phase sequence

PROTECTION > UNBALANCE I2>


Enable for I2> ON / OFF ON
Parameters
Pick-up setting K2 2 - 70 %In 15 % 56,7 A
Operation delay 1 - 600 s 5s

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF
Parameters
Maximum continous current 0.1 - 2.40 x In 1 x Imot 378,0 A
Alarm setting 60 - 99 %  % 359,1 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 4 x tau 180,0 min
Max overload at +40 C 70 - 120 %In 100 % 378,0 A
Max overload at +70 C 50 - 100 %In 65 % 245,7 A
Ambient temperature "-55 - 125 C" 42 C

Page32
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A01

Raw Mill 1, 321MD140M01, 3800 kW

Functions Setting Range Prefix Setting value Actual value

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1,1 x Imot 415,8 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 22 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2 x Imot 756,0 A
Operation delay 0.04 - 300 s 2s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 5 x Imot 1.890,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

Page33
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A01

Raw Mill 1, 321MD140M01, 3800 kW

Functions Setting Range Prefix Setting value Actual value

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

48, Stall protection

PROTECTION > STALL PROTECTION Ist>


Enable for Ist> ON/OFF ON
Parameters
Motor start detection current 1.3-10 1,3 xImot 491 A
Nom motor start current 1.5 - 10 1,6 xImot 605 A
Delay type DT / INV INV
Operation Delay 1 - 300 s 22 s

Page34
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A01

Raw Mill 1, 321MD140M01, 3800 kW

Functions Setting Range Prefix Setting value Actual value

66, Number of starts

PROTECTION > FREQUENT START PROTECTION N>


Enable for N> ON/OFF ON
Parameters
Max motor starts/hour 1 - 20 2 starts/hour
Min time between motor starts 1 - 100 20 min

Page35
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A02

Raw mill fan 1, 321FN400M01, 4120 kW.

Functions Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Motor nom current 1 - xxxx A Imot,comp 415 A
CT Primary 1 - xxxx A 500 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

46, Unbalance Load protection, negative phase sequence

PROTECTION > UNBALANCE I2>


Enable for I2> ON / OFF ON
Parameters
Pick-up setting K2 2 - 70 %In 15 % 62,3 A
Operation delay 1 - 600 s 5s

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF
Parameters
Maximum continous current 0.1 - 2.40 x In 1 x Imot 415,0 A
Alarm setting 60 - 99 %  % 394,3 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 4 x tau 152,0 min
Max overload at +40 C 70 - 120 %In 100 % 415,0 A
Max overload at +70 C 50 - 100 %In 65 % 269,8 A
Ambient temperature "-55 - 125 C" 42 C

Page36
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A02

Raw mill fan 1, 321FN400M01, 4120 kW.

Functions Setting Range Prefix Setting value Actual value

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1,1 x Imot 456,5 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 32 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2 x Imot 830,0 A
Operation delay 0.04 - 300 s 2s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 5 x Imot 2.075,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

Page37
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A02

Raw mill fan 1, 321FN400M01, 4120 kW.

Functions Setting Range Prefix Setting value Actual value

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

48, Stall protection

PROTECTION > STALL PROTECTION Ist>


Enable for Ist> ON/OFF ON
Parameters
Motor start detection current 1.3-10 1,3 xImot 540 A
Nom motor start current 1.5 - 10 1,6 xImot 664 A
Delay type DT / INV INV
Operation Delay 1 - 300 s 32 s

Page38
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A02

Raw mill fan 1, 321FN400M01, 4120 kW.

Functions Setting Range Prefix Setting value Actual value

66, Number of starts

PROTECTION > FREQUENT START PROTECTION N>


Enable for N> ON/OFF ON
Parameters
Max motor starts/hour 1 - 20 2 starts/hour
Min time between motor starts 1 - 100 20 min

Page39
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A04

Raw mill 1 department, 1250 kVA.

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 115 A
CT Primary 1 - xxxx A In 125 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 0,92 In 115,0 A
Alarm setting 60 - 99 %  % 109,3 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 50,0 min
Max overload at +40 C 70 - 120 %In 100 % 115,0 A
Max overload at +70 C 50 - 100 %In 65 % 74,8 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1 x In 125,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page40
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A04

Raw mill 1 department, 1250 kVA.

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,3 x In 287,5 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 9,8 x In 1.225,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page41
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A04

Raw mill 1 department, 1250 kVA.

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page42
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A05

Compressor 1 department, 1250 kVA.

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 115 A
CT Primary 1 - xxxx A In 125 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 0,92 In 115,0 A
Alarm setting 60 - 99 %  % 109,3 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 50,0 min
Max overload at +40 C 70 - 120 %In 100 % 115,0 A
Max overload at +70 C 50 - 100 %In 65 % 74,8 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1 x In 125,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page43
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A05

Compressor 1 department, 1250 kVA.

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,3 x In 287,5 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 9,8 x In 1.225,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page44
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A05

Compressor 1 department, 1250 kVA.

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page45
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A06

Limestone storage, 1250 kVA

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 115 A
CT Primary 1 - xxxx A In 125 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 0,92 In 115,0 A
Alarm setting 60 - 99 %  % 109,3 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 50,0 min
Max overload at +40 C 70 - 120 %In 100 % 115,0 A
Max overload at +70 C 50 - 100 %In 65 % 74,8 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1 x In 125,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page46
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A06

Limestone storage, 1250 kVA

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,3 x In 287,5 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 9,8 x In 1.225,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page47
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A06

Limestone storage, 1250 kVA

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page48
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV41 Panel name: A07

Bucket elevator, 341BE050M01, 315 kW.

Functions Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Motor nom current 1 - xxxx A Imot 37 A
CT Primary 1 - xxxx A 50 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

46, Unbalance Load protection, negative phase sequence

PROTECTION > UNBALANCE I2>


Enable for I2> ON / OFF ON
Parameters
Pick-up setting K2 2 - 70 %In 15 % 5,6 A
Operation delay 1 - 600 s 5s

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 1 x Imot 37,0 A
Alarm setting 60 - 99 %  % 35,2 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 4 x tau 220,0 min
Max overload at +40 C 70 - 120 %In 100 % 37,0 A
Max overload at +70 C 50 - 100 %In 65 % 24,1 A
Ambient temperature "-55 - 125 C" 42 C

Page49
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV41 Panel name: A07

Bucket elevator, 341BE050M01, 315 kW.

Functions Setting Range Prefix Setting value Actual value

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1,1 x Imot 40,7 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 1,5 x Imot 55,5 A
Operation delay 0.04 - 300 s 10 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 10 x Imot 370,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

Page50
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV41 Panel name: A07

Bucket elevator, 341BE050M01, 315 kW.

Functions Setting Range Prefix Setting value Actual value

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

48, Stall protection

PROTECTION > STALL PROTECTION Ist>


Enable for Ist> ON/OFF ON
Parameters
Motor start detection current 1.3-10 2 xImot 74 A
Nom motor start current 1.5 - 10 5 xImot 185 A
Delay type DT / INV DT
Operation Delay 1 - 300 s 10 s

Page51
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV41 Panel name: A07

Bucket elevator, 341BE050M01, 315 kW.

Functions Setting Range Prefix Setting value Actual value

66, Number of starts

PROTECTION > FREQUENT START PROTECTION N>


Enable for N> ON/OFF ON
Parameters
Max motor starts/hour 1 - 20 2 starts/hour
Min time between motor starts 1 - 100 20 min

Page52
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV41 Panel name: A08

Bucket elevator, 341BE050M02, 315 kW.

Functions Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Motor nom current 1 - xxxx A Imot 37 A
CT Primary 1 - xxxx A 50 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

46, Unbalance Load protection, negative phase sequence

PROTECTION > UNBALANCE I2>


Enable for I2> ON / OFF ON
Parameters
Pick-up setting K2 2 - 70 %In 15 % 5,6 A
Operation delay 1 - 600 s 5s

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 1 x Imot 37,0 A
Alarm setting 60 - 99 %  % 35,2 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 4 x tau 220,0 min
Max overload at +40 C 70 - 120 %In 100 % 37,0 A
Max overload at +70 C 50 - 100 %In 65 % 24,1 A
Ambient temperature "-55 - 125 C" 42 C

Page53
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV41 Panel name: A08

Bucket elevator, 341BE050M02, 315 kW.

Functions Setting Range Prefix Setting value Actual value

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1,1 x Imot 40,7 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 1,5 x Imot 55,5 A
Operation delay 0.04 - 300 s 10 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 10 x Imot 370,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

Page54
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV41 Panel name: A08

Bucket elevator, 341BE050M02, 315 kW.

Functions Setting Range Prefix Setting value Actual value

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

48, Stall protection

PROTECTION > STALL PROTECTION Ist>


Enable for Ist> ON/OFF ON
Parameters
Motor start detection current 1.3-10 2 xImot 74 A
Nom motor start current 1.5 - 10 5 xImot 185 A
Delay type DT / INV DT
Operation Delay 1 - 300 s 10 s

Page55
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 301MV100 Date: 12.11.16
Relay: VAMP 300 MV41 Panel name: A08

Bucket elevator, 341BE050M02, 315 kW.

Functions Setting Range Prefix Setting value Actual value

66, Number of starts

PROTECTION > FREQUENT START PROTECTION N>


Enable for N> ON/OFF ON
Parameters
Max motor starts/hour 1 - 20 2 starts/hour
Min time between motor starts 1 - 100 20 min

Page56
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 302MV100 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A01

Raw mill 2, 322MD140M01, 3800 kW.

Functions Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Motor nom current 1 - xxxx A Imot,comp 378 A
CT Primary 1 - xxxx A 500 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

46, Unbalance Load protection, negative phase sequence

PROTECTION > UNBALANCE I2>


Enable for I2> ON / OFF ON
Parameters
Pick-up setting K2 2 - 70 %In 15 % 56,7 A
Operation delay 1 - 600 s 5s

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 1 x Imot 378,0 A
Alarm setting 60 - 99 %  % 359,1 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 4 x tau 152,0 min
Max overload at +40 C 70 - 120 %In 100 % 378,0 A
Max overload at +70 C 50 - 100 %In 65 % 245,7 A
Ambient temperature "-55 - 125 C" 42 C

Page57
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 302MV100 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A01

Raw mill 2, 322MD140M01, 3800 kW.

Functions Setting Range Prefix Setting value Actual value

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1,1 x Imot 415,8 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 22 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2 x Imot 756,0 A
Operation delay 0.04 - 300 s 2s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 5 x Imot 1.890,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

Page58
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 302MV100 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A01

Raw mill 2, 322MD140M01, 3800 kW.

Functions Setting Range Prefix Setting value Actual value

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

48, Stall protection

PROTECTION > STALL PROTECTION Ist>


Enable for Ist> ON/OFF ON
Parameters
Motor start detection current 1.3-10 1,3 xImot 491 A
Nom motor start current 1.5 - 10 1,6 xImot 605 A
Delay type DT / INV INV
Operation Delay 1 - 300 s 22 s

Page59
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 302MV100 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A01

Raw mill 2, 322MD140M01, 3800 kW.

Functions Setting Range Prefix Setting value Actual value

66, Number of starts

PROTECTION > FREQUENT START PROTECTION N>


Enable for N> ON/OFF ON
Parameters
Max motor starts/hour 1 - 20 2 starts/hour
Min time between motor starts 1 - 100 20 min

Page60
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 302MV100 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A03

Raw mill fan 2, 322FN400M01, 4120 kW.

Functions Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Motor nom current 1 - xxxx A Imot,comp 415 A
CT Primary 1 - xxxx A 500 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

46, Unbalance Load protection, negative phase sequence

PROTECTION > UNBALANCE I2>


Enable for I2> ON / OFF ON
Parameters
Pick-up setting K2 2 - 70 %In 15 % 62,3 A
Operation delay 1 - 600 s 5s

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 1 x Imot 415,0 A
Alarm setting 60 - 99 %  % 394,3 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 4 x tau 152,0 min
Max overload at +40 C 70 - 120 %In 100 % 415,0 A
Max overload at +70 C 50 - 100 %In 65 % 269,8 A
Ambient temperature "-55 - 125 C" 42 C

Page61
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 302MV100 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A03

Raw mill fan 2, 322FN400M01, 4120 kW.

Functions Setting Range Prefix Setting value Actual value

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1,1 x Imot 456,5 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 32 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2 x Imot 830,0 A
Operation delay 0.04 - 300 s 2s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 5 x Imot 2.075,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

Page62
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 302MV100 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A03

Raw mill fan 2, 322FN400M01, 4120 kW.

Functions Setting Range Prefix Setting value Actual value

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

48, Stall protection

PROTECTION > STALL PROTECTION Ist>


Enable for Ist> ON/OFF ON
Parameters
Motor start detection current 1.3-10 1,3 xImot 540 A
Nom motor start current 1.5 - 10 1,6 xImot 664 A
Delay type DT / INV INV
Operation Delay 1 - 300 s 22 s

Page63
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 302MV100 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A03

Raw mill fan 2, 322FN400M01, 4120 kW.

Functions Setting Range Prefix Setting value Actual value

66, Number of starts

PROTECTION > FREQUENT START PROTECTION N>


Enable for N> ON/OFF ON
Parameters
Max motor starts/hour 1 - 20 2 starts/hour
Min time between motor starts 1 - 100 20 min

Page64
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 302MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A04

Raw mill 2 department, 1000 kVA.

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 92 A
CT Primary 1 - xxxx A In 100 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 0,92 In 92,0 A
Alarm setting 60 - 99 %  % 87,4 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 50,0 min
Max overload at +40 C 70 - 120 %In 100 % 92,0 A
Max overload at +70 C 50 - 100 %In 65 % 59,8 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1 x In 100,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page65
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 302MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A04

Raw mill 2 department, 1000 kVA.

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,3 x In 230,0 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 9,8 x In 980,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page66
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 302MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A04

Raw mill 2 department, 1000 kVA.

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page67
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 302MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A05

Spare feeder.

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 0A
CT Primary 1 - xxxx A In 250 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In In 0,0 A
Alarm setting 60 - 99 % % 0,0 A
Time constant tau 2 - 180 min min
Rel. Cooling time contant 1 - 10 x tau x tau 0,0 min
Max overload at +40 C 70 - 120 %In % 0,0 A
Max overload at +70 C 50 - 100 %In % 0,0 A
Ambient temperature "-55 - 125 C" C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In x In 0,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s s
Include Harmonics ON / OFF ON

Page68
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 302MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A05

Spare feeder.

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In x In 0,0 A
Operation delay 0.04 - 300 s s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 9,8 x In 2.450,0 A
Operation delay 0.04 - 300 s 1,5 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.3 - 300 s s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s
Intermittent time 0.00 - 5.00s s

Page69
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 302MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A05

Spare feeder.

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Communication Settings for ProfiBus

Page70
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV64 Panel name: A01

Kiln drive, 431MD140M01 & M02, 2 x 1025 kW (VFD).

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 250 A
CT Primary 1 - xxxx A In 300 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 0,83 In 249,0 A
Alarm setting 60 - 99 %  % 236,6 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 100,0 min
Max overload at +40 C 70 - 120 %In 100 % 249,0 A
Max overload at +70 C 50 - 100 %In 65 % 161,9 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 0,92 x In 276,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page71
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV64 Panel name: A01

Kiln drive, 431MD140M01 & M02, 2 x 1025 kW (VFD).

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,08 x In 624,0 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 5,8 x In 1.740,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page72
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV64 Panel name: A01

Kiln drive, 431MD140M01 & M02, 2 x 1025 kW (VFD).

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page73
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV62 Panel name: A02

Kiln ID-fan 1, 331FN110M01, 2900 kW (VFD).

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A In 355 A
CT Primary 1 - xxxx A 400 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 1 In 355,0 A
Alarm setting 60 - 99 %  % 337,3 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 100,0 min
Max overload at +40 C 70 - 120 %In 100 % 355,0 A
Max overload at +70 C 50 - 100 %In 65 % 230,8 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1,1 x In 390,5 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page74
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV62 Panel name: A02

Kiln ID-fan 1, 331FN110M01, 2900 kW (VFD).

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,5 x In 887,5 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 7 x In 2.485,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page75
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV62 Panel name: A02

Kiln ID-fan 1, 331FN110M01, 2900 kW (VFD).

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page76
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV62 Panel name: A03

Kiln ID-fan 2, 331FN120M01, 2900 kW (VFD).

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A In 355 A
CT Primary 1 - xxxx A 400 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 1 In 355,0 A
Alarm setting 60 - 99 %  % 337,3 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 100,0 min
Max overload at +40 C 70 - 120 %In 100 % 355,0 A
Max overload at +70 C 50 - 100 %In 65 % 230,8 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1,1 x In 390,5 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page77
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV62 Panel name: A03

Kiln ID-fan 2, 331FN120M01, 2900 kW (VFD).

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,5 x In 887,5 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 7 x In 2.485,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page78
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV62 Panel name: A03

Kiln ID-fan 2, 331FN120M01, 2900 kW (VFD).

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page79
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV62 Panel name: A05

Filter fan, 331FN400M01, 2550 kW (VFD).

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A In 312 A
CT Primary 1 - xxxx A 350 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 1 In 312,0 A
Alarm setting 60 - 99 %  % 296,4 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 100,0 min
Max overload at +40 C 70 - 120 %In 100 % 312,0 A
Max overload at +70 C 50 - 100 %In 65 % 202,8 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1,1 x In 343,2 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page80
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV62 Panel name: A05

Filter fan, 331FN400M01, 2550 kW (VFD).

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,5 x In 780,0 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 7 x In 2.184,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page81
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV62 Panel name: A05

Filter fan, 331FN400M01, 2550 kW (VFD).

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page82
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV41 Panel name: A06

Bucket elevator, 351BE04M01, 355 kW.

Functions Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Motor nom current 1 - xxxx A Imot 40 A
CT Primary 1 - xxxx A 50 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

46, Unbalance Load protection, negative phase sequence

PROTECTION > UNBALANCE I2>


Enable for I2> ON / OFF ON
Parameters
Pick-up setting K2 2 - 70 %In 15 % 6,0 A
Operation delay 1 - 600 s 5s

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 1 x Imot 40,0 A
Alarm setting 60 - 99 %  % 38,0 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 4 x tau 240,0 min
Max overload at +40 C 70 - 120 %In 100 % 40,0 A
Max overload at +70 C 50 - 100 %In 65 % 26,0 A
Ambient temperature "-55 - 125 C" 42 C

Page83
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV41 Panel name: A06

Bucket elevator, 351BE04M01, 355 kW.

Functions Setting Range Prefix Setting value Actual value

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1,1 x Imot 44,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2 x Imot 80,0 A
Operation delay 0.04 - 300 s 10 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 10 x Imot 400,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

Page84
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV41 Panel name: A06

Bucket elevator, 351BE04M01, 355 kW.

Functions Setting Range Prefix Setting value Actual value

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

48, Stall protection

PROTECTION > STALL PROTECTION Ist>


Enable for Ist> ON/OFF ON
Parameters
Motor start detection current 1.3-10 2 xImot 80 A
Nom motor start current 1.5 - 10 5 xImot 200 A
Delay type DT / INV DT
Operation Delay 1 - 300 s 10 s

Page85
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV41 Panel name: A06

Bucket elevator, 351BE04M01, 355 kW.

Functions Setting Range Prefix Setting value Actual value

66, Number of starts

PROTECTION > FREQUENT START PROTECTION N>


Enable for N> ON/OFF ON
Parameters
Max motor starts/hour 1 - 20 2 starts/hour
Min time between motor starts 1 - 100 20 min

Page86
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV41 Panel name: A07

Bucket elevator, 351BE04M02, 355 kW.

Functions Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Motor nom current 1 - xxxx A Imot 40 A
CT Primary 1 - xxxx A 50 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

46, Unbalance Load protection, negative phase sequence

PROTECTION > UNBALANCE I2>


Enable for I2> ON / OFF ON
Parameters
Pick-up setting K2 2 - 70 %In 15 % 6,0 A
Operation delay 1 - 600 s 5s

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 1 x Imot 40,0 A
Alarm setting 60 - 99 %  % 38,0 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 4 x tau 240,0 min
Max overload at +40 C 70 - 120 %In 100 % 40,0 A
Max overload at +70 C 50 - 100 %In 65 % 26,0 A
Ambient temperature "-55 - 125 C" 42 C

Page87
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV41 Panel name: A07

Bucket elevator, 351BE04M02, 355 kW.

Functions Setting Range Prefix Setting value Actual value

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1,1 x Imot 44,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2 x Imot 80,0 A
Operation delay 0.04 - 300 s 10 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 10 x Imot 400,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

Page88
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV41 Panel name: A07

Bucket elevator, 351BE04M02, 355 kW.

Functions Setting Range Prefix Setting value Actual value

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

48, Stall protection

PROTECTION > STALL PROTECTION Ist>


Enable for Ist> ON/OFF ON
Parameters
Motor start detection current 1.3-10 2 xImot 80 A
Nom motor start current 1.5 - 10 5 xImot 200 A
Delay type DT / INV DT
Operation Delay 1 - 300 s 10 s

Page89
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV41 Panel name: A07

Bucket elevator, 351BE04M02, 355 kW.

Functions Setting Range Prefix Setting value Actual value

66, Number of starts

PROTECTION > FREQUENT START PROTECTION N>


Enable for N> ON/OFF ON
Parameters
Max motor starts/hour 1 - 20 2 starts/hour
Min time between motor starts 1 - 100 20 min

Page90
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV41 Panel name: A08

Bucket elevator, 351BE340M01, 315 kW.

Functions Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Motor nom current 1 - xxxx A Imot 37 A
CT Primary 1 - xxxx A 50 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

46, Unbalance Load protection, negative phase sequence

PROTECTION > UNBALANCE I2>


Enable for I2> ON / OFF ON
Parameters
Pick-up setting K2 2 - 70 %In 15 % 5,6 A
Operation delay 1 - 600 s 5s

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 1 x Imot 37,0 A
Alarm setting 60 - 99 %  % 35,2 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 4 x tau 220,0 min
Max overload at +40 C 70 - 120 %In 100 % 37,0 A
Max overload at +70 C 50 - 100 %In 65 % 24,1 A
Ambient temperature "-55 - 125 C" 42 C

Page91
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV41 Panel name: A08

Bucket elevator, 351BE340M01, 315 kW.

Functions Setting Range Prefix Setting value Actual value

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1,1 x Imot 40,7 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2 x Imot 74,0 A
Operation delay 0.04 - 300 s 10 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 10 x Imot 370,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

Page92
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV41 Panel name: A08

Bucket elevator, 351BE340M01, 315 kW.

Functions Setting Range Prefix Setting value Actual value

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

48, Stall protection

PROTECTION > STALL PROTECTION Ist>


Enable for Ist> ON/OFF ON
Parameters
Motor start detection current 1.3-10 2 xImot 74 A
Nom motor start current 1.5 - 10 5 xImot 185 A
Delay type DT / INV DT
Operation Delay 1 - 300 s 10 s

Page93
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV41 Panel name: A08

Bucket elevator, 351BE340M01, 315 kW.

Functions Setting Range Prefix Setting value Actual value

66, Number of starts

PROTECTION > FREQUENT START PROTECTION N>


Enable for N> ON/OFF ON
Parameters
Max motor starts/hour 1 - 20 2 starts/hour
Min time between motor starts 1 - 100 20 min

Page94
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 Panel name: A09

Bucket elevator, 351BE340M02, 315 kW.

Functions Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Motor nom current 1 - xxxx A Imot 37 A
CT Primary 1 - xxxx A 50 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

46, Unbalance Load protection, negative phase sequence

PROTECTION > UNBALANCE I2>


Enable for I2> ON / OFF ON
Parameters
Pick-up setting K2 2 - 70 %In 15 % 5,6 A
Operation delay 1 - 600 s 5s

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 1 x Imot 37,0 A
Alarm setting 60 - 99 %  % 35,2 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 4 x tau 220,0 min
Max overload at +40 C 70 - 120 %In 100 % 37,0 A
Max overload at +70 C 50 - 100 %In 65 % 24,1 A
Ambient temperature "-55 - 125 C" 42 C

Page95
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 Panel name: A09

Bucket elevator, 351BE340M02, 315 kW.

Functions Setting Range Prefix Setting value Actual value

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1,1 x Imot 40,7 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2 x Imot 74,0 A
Operation delay 0.04 - 300 s 10 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 10 x Imot 370,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

Page96
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 Panel name: A09

Bucket elevator, 351BE340M02, 315 kW.

Functions Setting Range Prefix Setting value Actual value

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

48, Stall protection

PROTECTION > STALL PROTECTION Ist>


Enable for Ist> ON/OFF ON
Parameters
Motor start detection current 1.3-10 2 xImot 74 A
Nom motor start current 1.5 - 10 5 xImot 185 A
Delay type DT / INV DT
Operation Delay 1 - 300 s 10 s

Page97
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 Panel name: A09

Bucket elevator, 351BE340M02, 315 kW.

Functions Setting Range Prefix Setting value Actual value

66, Number of starts

PROTECTION > FREQUENT START PROTECTION N>


Enable for N> ON/OFF ON
Parameters
Max motor starts/hour 1 - 20 2 starts/hour
Min time between motor starts 1 - 100 20 min

Page98
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A10

Kiln department, 1600 kVA.

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 147 A
CT Primary 1 - xxxx A In 150 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 0,98 In 147,0 A
Alarm setting 60 - 99 %  % 139,7 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 50,0 min
Max overload at +40 C 70 - 120 %In 100 % 147,0 A
Max overload at +70 C 50 - 100 %In 65 % 95,6 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1,08 x In 162,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page99
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A10

Kiln department, 1600 kVA.

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,45 x In 367,5 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 9,8 x In 1.470,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page100
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A10

Kiln department, 1600 kVA.

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page101
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A11

Stand-by diesel generator, 1250 kVA.

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 115 A
CT Primary 1 - xxxx A In 125 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 1 In 125,0 A
Alarm setting 60 - 99 %  % 118,8 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 50,0 min
Max overload at +40 C 70 - 120 %In 100 % 125,0 A
Max overload at +70 C 50 - 100 %In 65 % 81,3 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 0,92 x In 115,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page102
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A11

Stand-by diesel generator, 1250 kVA.

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,3 x In 287,5 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 9,8 x In 1.225,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page103
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A11

Stand-by diesel generator, 1250 kVA.

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page104
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A12

Exhaust gas conditioning department, 2000 kVA

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 183 A
CT Primary 1 - xxxx A In 200 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 0,92 In 184,0 A
Alarm setting 60 - 99 %  % 174,8 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 50,0 min
Max overload at +40 C 70 - 120 %In 100 % 184,0 A
Max overload at +70 C 50 - 100 %In 65 % 119,6 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1 x In 200,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page105
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A12

Exhaust gas conditioning department, 2000 kVA

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,3 x In 460,0 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 9,15 x In 1.830,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page106
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A12

Exhaust gas conditioning department, 2000 kVA

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page107
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A13

Spare feeder

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 0A
CT Primary 1 - xxxx A In 250 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF
Parameters
Maximum continous current 0.1 - 2.40 x In In 0,0 A
Alarm setting 60 - 99 % % 0,0 A
Time constant tau 2 - 180 min min
Rel. Cooling time contant 1 - 10 x tau x tau 0,0 min
Max overload at +40 C 70 - 120 %In % 0,0 A
Max overload at +70 C 50 - 100 %In % 0,0 A
Ambient temperature "-55 - 125 C" C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In x In 0,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s s
Include Harmonics ON / OFF ON

Page108
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A13

Spare feeder

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In x In 0,0 A
Operation delay 0.04 - 300 s s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 9,8 x In 2.450,0 A
Operation delay 0.04 - 300 s 1,5 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.3 - 300 s s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s
Intermittent time 0.00 - 5.00s s

Page109
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A13

Spare feeder

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page110
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV200 Date: 12.11.16
Relay: VAMP 300 MV22 Panel name: A01

Cooler fans, 5080 kVA (VFD)

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 441 A
CT Primary 1 - xxxx A In 500 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF
Parameters
Maximum continous current 0.1 - 2.40 x In 0,88 In 440,0 A
Alarm setting 60 - 99 %  % 418,0 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 100,0 min
Max overload at +40 C 70 - 120 %In 100 % 440,0 A
Max overload at +70 C 50 - 100 %In 65 % 286,0 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 0,97 x In 485,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page111
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV200 Date: 12.11.16
Relay: VAMP 300 MV22 Panel name: A01

Cooler fans, 5080 kVA (VFD)

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,2 x In 1.100,0 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 6,2 x In 3.100,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page112
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV200 Date: 12.11.16
Relay: VAMP 300 MV22 Panel name: A01

Cooler fans, 5080 kVA (VFD)

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page113
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV200 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A03

Spare feeder

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 0A
CT Primary 1 - xxxx A In 150 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF
Parameters
Maximum continous current 0.1 - 2.40 x In In 0,0 A
Alarm setting 60 - 99 % % 0,0 A
Time constant tau 2 - 180 min min
Rel. Cooling time contant 1 - 10 x tau x tau 0,0 min
Max overload at +40 C 70 - 120 %In % 0,0 A
Max overload at +70 C 50 - 100 %In % 0,0 A
Ambient temperature "-55 - 125 C" C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In x In 0,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s s
Include Harmonics ON / OFF ON

Page114
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV200 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A03

Spare feeder

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In x In 0,0 A
Operation delay 0.04 - 300 s s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 9,8 x In 1.470,0 A
Operation delay 0.04 - 300 s 1,5 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.3 - 300 s s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s
Intermittent time 0.00 - 5.00s s

Page115
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV200 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A03

Spare feeder

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page116
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV200 Date: 12.11.16
Relay: VAMP 300 MV63 Panel name: A04

Cooler excess air fan, 441FN590M01, 845 kW (VFD).

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 105 A
CT Primary 1 - xxxx A In 125 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 0,84 In 105,0 A
Alarm setting 60 - 99 %  % 99,8 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 100,0 min
Max overload at +40 C 70 - 120 %In 100 % 105,0 A
Max overload at +70 C 50 - 100 %In 65 % 68,3 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 0,92 x In 115,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page117
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV200 Date: 12.11.16
Relay: VAMP 300 MV63 Panel name: A04

Cooler excess air fan, 441FN590M01, 845 kW (VFD).

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,1 x In 262,5 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 5,9 x In 737,5 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page118
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV200 Date: 12.11.16
Relay: VAMP 300 MV63 Panel name: A04

Cooler excess air fan, 441FN590M01, 845 kW (VFD).

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page119
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV200 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A05

Cooler department, 1600 kVA.

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 147 A
CT Primary 1 - xxxx A In 150 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 0,98 In 147,0 A
Alarm setting 60 - 99 %  % 139,7 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 50,0 min
Max overload at +40 C 70 - 120 %In 100 % 147,0 A
Max overload at +70 C 50 - 100 %In 65 % 95,6 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1,08 x In 162,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page120
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV200 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A05

Cooler department, 1600 kVA.

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,45 x In 367,5 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 9,4 x In 1.410,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page121
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV200 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A05

Cooler department, 1600 kVA.

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page122
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV200 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A06

Stand-by diesel generator, 1250 kVA.

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 115 A
CT Primary 1 - xxxx A In 125 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 0,92 In 115,0 A
Alarm setting 60 - 99 %  % 109,3 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 50,0 min
Max overload at +40 C 70 - 120 %In 100 % 115,0 A
Max overload at +70 C 50 - 100 %In 65 % 74,8 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1 x In 125,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page123
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV200 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A06

Stand-by diesel generator, 1250 kVA.

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,3 x In 287,5 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 9,2 x In 1.150,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page124
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV200 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A06

Stand-by diesel generator, 1250 kVA.

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page125
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV200 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A07

Cooler hydraulic system, 1250 kVA.

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 115 A
CT Primary 1 - xxxx A In 125 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 0,92 In 115,0 A
Alarm setting 60 - 99 %  % 109,3 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 50,0 min
Max overload at +40 C 70 - 120 %In 100 % 115,0 A
Max overload at +70 C 50 - 100 %In 65 % 74,8 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1 x In 125,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page126
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV200 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A07

Cooler hydraulic system, 1250 kVA.

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,3 x In 287,5 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 9,2 x In 1.150,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page127
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV200 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A07

Cooler hydraulic system, 1250 kVA.

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page128
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV200 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A08

Water treatment department. 630 kVA

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 58 A
CT Primary 1 - xxxx A In 75 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 0,77 In 57,8 A
Alarm setting 60 - 99 %  % 54,9 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 50,0 min
Max overload at +40 C 70 - 120 %In 80 % 46,2 A
Max overload at +70 C 50 - 100 %In 100 % 57,8 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 0,85 x In 63,8 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page129
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV200 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A08

Water treatment department. 630 kVA

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 1,93 x In 144,8 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 7,7 x In 577,5 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page130
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV200 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A08

Water treatment department. 630 kVA

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page131
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV300 Date: 12.11.16
Relay: VAMP 300 MV63 Panel name: A01

Coal Mill 1, 461MD140M01, 1130 kW (VFD).

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 141 A
CT Primary 1 - xxxx A In 150 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 0,94 In 141,0 A
Alarm setting 60 - 99 %  % 134,0 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 100,0 min
Max overload at +40 C 70 - 120 %In 100 % 141,0 A
Max overload at +70 C 50 - 100 %In 65 % 91,7 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1 x In 150,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page132
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV300 Date: 12.11.16
Relay: VAMP 300 MV63 Panel name: A01

Coal Mill 1, 461MD140M01, 1130 kW (VFD).

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,35 x In 352,5 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 6,58 x In 987,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page133
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV300 Date: 12.11.16
Relay: VAMP 300 MV63 Panel name: A01

Coal Mill 1, 461MD140M01, 1130 kW (VFD).

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page134
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 401MV300 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A02

Coal Mill Fan 1, 461FN400M01, 1180 kW.

Functions Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Motor nom current 1 - xxxx A Imot 137 A
CT Primary 1 - xxxx A 150 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

46, Unbalance Load protection, negative phase sequence

PROTECTION > UNBALANCE I2>


Enable for I2> ON / OFF ON
Parameters
Pick-up setting K2 2 - 70 %In 15 % 20,6 A
Operation delay 1 - 600 s 5s

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 1 x Imot 137,0 A
Alarm setting 60 - 99 %  % 130,2 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 125,0 min
Max overload at +40 C 70 - 120 %In 100 % 137,0 A
Max overload at +70 C 50 - 100 %In 65 % 89,1 A
Ambient temperature "-55 - 125 C" 42 C

Page135
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 401MV300 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A02

Coal Mill Fan 1, 461FN400M01, 1180 kW.

Functions Setting Range Prefix Setting value Actual value

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1,1 x Imot 150,7 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 32 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2 x Imot 274,0 A
Operation delay 0.04 - 300 s 2s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 5 x Imot 685,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

Page136
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 401MV300 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A02

Coal Mill Fan 1, 461FN400M01, 1180 kW.

Functions Setting Range Prefix Setting value Actual value

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

48, Stall protection

PROTECTION > STALL PROTECTION Ist>


Enable for Ist> ON/OFF ON
Parameters
Motor start detection current 1.3-10 1,3 xImot 178 A
Nom motor start current 1.5 - 10 1,6 xImot 219 A
Delay type DT / INV INV
Operation Delay 1 - 300 s 32 s

Page137
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 401MV300 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A02

Coal Mill Fan 1, 461FN400M01, 1180 kW.

Functions Setting Range Prefix Setting value Actual value

66, Number of starts

PROTECTION > FREQUENT START PROTECTION N>


Enable for N> ON/OFF ON
Parameters
Max motor starts/hour 1 - 20 2 starts/hour
Min time between motor starts 1 - 100 20 min

Page138
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV300 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A04

Coal Mill department, 1250 kVA.

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 115 A
CT Primary 1 - xxxx A In 125 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 0,92 In 115,0 A
Alarm setting 60 - 99 %  % 109,3 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 50,0 min
Max overload at +40 C 70 - 120 %In 100 % 115,0 A
Max overload at +70 C 50 - 100 %In 65 % 74,8 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1 x In 125,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page139
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV300 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A04

Coal Mill department, 1250 kVA.

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,3 x In 287,5 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 9,2 x In 1.150,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page140
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV300 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A04

Coal Mill department, 1250 kVA.

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page141
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV300 Date: 12.11.16
Relay: VAMP 300 MV63 Panel name: A05

Hot gas Booster Fan, 461FN450M01, 700 kW (VFD).

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 87 A
CT Primary 1 - xxxx A In 100 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 0,87 In 87,0 A
Alarm setting 60 - 99 %  % 82,7 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 100,0 min
Max overload at +40 C 70 - 120 %In 100 % 87,0 A
Max overload at +70 C 50 - 100 %In 65 % 56,6 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 0,96 x In 96,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page142
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV300 Date: 12.11.16
Relay: VAMP 300 MV63 Panel name: A05

Hot gas Booster Fan, 461FN450M01, 700 kW (VFD).

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,18 x In 218,0 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 6,1 x In 610,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page143
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 401MV300 Date: 12.11.16
Relay: VAMP 300 MV63 Panel name: A05

Hot gas Booster Fan, 461FN450M01, 700 kW (VFD).

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page144
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 402MV300 Date: 12.11.16
Relay: VAMP 300 MV63 Panel name: A01

Coal Mill 2, 462MD140M01, 1130 kW, (VFD).

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 141 A
CT Primary 1 - xxxx A In 150 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 0,94 In 141,0 A
Alarm setting 60 - 99 %  % 134,0 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 100,0 min
Max overload at +40 C 70 - 120 %In 100 % 141,0 A
Max overload at +70 C 50 - 100 %In 65 % 91,7 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1 x In 150,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page145
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 402MV300 Date: 12.11.16
Relay: VAMP 300 MV63 Panel name: A01

Coal Mill 2, 462MD140M01, 1130 kW, (VFD).

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,35 x In 352,5 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 6,6 x In 990,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page146
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 402MV300 Date: 12.11.16
Relay: VAMP 300 MV63 Panel name: A01

Coal Mill 2, 462MD140M01, 1130 kW, (VFD).

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page147
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 402MV300 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A02

Coal Mill Fan 2, 462FN400M01, 1180 kW.

Functions Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Motor nom current 1 - xxxx A Imot 137 A
CT Primary 1 - xxxx A 150 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

46, Unbalance Load protection, negative phase sequence

PROTECTION > UNBALANCE I2>


Enable for I2> ON / OFF ON
Parameters
Pick-up setting K2 2 - 70 %In 15 % 20,6 A
Operation delay 1 - 600 s 5s

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 1 x Imot 137,0 A
Alarm setting 60 - 99 %  % 130,2 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 125,0 min
Max overload at +40 C 70 - 120 %In 100 % 137,0 A
Max overload at +70 C 50 - 100 %In 65 % 89,1 A
Ambient temperature "-55 - 125 C" 42 C

Page148
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 402MV300 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A02

Coal Mill Fan 2, 462FN400M01, 1180 kW.

Functions Setting Range Prefix Setting value Actual value

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1,1 x Imot 150,7 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 32 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2 x Imot 274,0 A
Operation delay 0.04 - 300 s 2s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 5 x Imot 685,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

Page149
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 402MV300 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A02

Coal Mill Fan 2, 462FN400M01, 1180 kW.

Functions Setting Range Prefix Setting value Actual value

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

48, Stall protection

PROTECTION > STALL PROTECTION Ist>


Enable for Ist> ON/OFF ON
Parameters
Motor start detection current 1.3-10 1,3 xImot 178 A
Nom motor start current 1.5 - 10 1,6 xImot 219 A
Delay type DT / INV INV
Operation Delay 1 - 300 s 32 s

Page150
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 1 Switchgear: 402MV300 Date: 12.11.16
Relay: VAMP 300 MV42 Panel name: A02

Coal Mill Fan 2, 462FN400M01, 1180 kW.

Functions Setting Range Prefix Setting value Actual value

66, Number of starts

PROTECTION > FREQUENT START PROTECTION N>


Enable for N> ON/OFF ON
Parameters
Max motor starts/hour 1 - 20 2 starts/hour
Min time between motor starts 1 - 100 20 min

Page151
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 402MV300 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A04

Coal Mill 2 department, 800 kVA

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 73 A
CT Primary 1 - xxxx A In 100 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 0,73 In 73,0 A
Alarm setting 60 - 99 %  % 69,4 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 50,0 min
Max overload at +40 C 70 - 120 %In 100 % 73,0 A
Max overload at +70 C 50 - 100 %In 65 % 47,5 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 0,8 x In 80,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page152
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 402MV300 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A04

Coal Mill 2 department, 800 kVA

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 1,83 x In 183,0 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 7,3 x In 730,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page153
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 402MV300 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A04

Coal Mill 2 department, 800 kVA

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page154
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 502MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A01

Additive storage department, 1600 kVA

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 147 A
CT Primary 1 - xxxx A In 150 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 0,98 In 147,0 A
Alarm setting 60 - 99 %  % 139,7 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 50,0 min
Max overload at +40 C 70 - 120 %In 100 % 147,0 A
Max overload at +70 C 50 - 100 %In 65 % 95,6 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1 x In 150,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page155
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 502MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A01

Additive storage department, 1600 kVA

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,4 x In 360,0 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 9,8 x In 1.470,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page156
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 502MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A01

Additive storage department, 1600 kVA

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page157
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 502MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A02

Clinker extraction department, 1600 kVA

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 147 A
CT Primary 1 - xxxx A In 150 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 0,98 In 147,0 A
Alarm setting 60 - 99 %  % 139,7 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 50,0 min
Max overload at +40 C 70 - 120 %In 100 % 147,0 A
Max overload at +70 C 50 - 100 %In 65 % 95,6 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1 x In 150,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page158
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 502MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A02

Clinker extraction department, 1600 kVA

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,4 x In 360,0 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 9,8 x In 1.470,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page159
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 502MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A02

Clinker extraction department, 1600 kVA

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Communication Settings for ProfiBus

Page160
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 502MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A04

Compressor 2 department, 1250 kVA

Description Setting Range Prefix Setting value Actual value

Analog inputs

GENERAL > SCALING > CT


Nominal Primary 1 - xxxx A 115 A
CT Primary 1 - xxxx A In 125 A
CT Secondary 1-5A 1A
GENERAL > SCALING > VT
VT Primary 1 - xxxx V 6300 V
VT Secondary 1 - 400 V 110 V
Vty Secondary 1 - 400 V -- V
GENERAL > SCALING > Meas Mode
Voltage Meas. Mode 3LN / 3LN+Uo 3LN
Frequency Adaptation mode Auto / Manual / Fixed Auto
Adapted Frequency 50 - 60 Hz 50 Hz
GENERAL > SCALING > CT Residuals
Io1 CT Primary 1 - 500 A 50 A
Io1 CT Secondary 1-5A 1 A
Io2 CT Primary 1 - 500 A -- A
Io2 CT Secondary 1-5A -- A

Protection functions

49, Thermal Overload protection

PROTECTION > OVERLOAD STAGE T>


Enable for T> ON / OFF ON
Parameters
Maximum continous current 0.1 - 2.40 x In 0,92 In 115,0 A
Alarm setting 60 - 99 %  % 109,3 A
Time constant tau 2 - 180 min  min
Rel. Cooling time contant 1 - 10 x tau 5 x tau 50,0 min
Max overload at +40 C 70 - 120 %In 100 % 115,0 A
Max overload at +70 C 50 - 100 %In 65 % 74,8 A
Ambient temperature "-55 - 125 C" 42 C

50/51, Overcurrent protection (Definite Time)

PROTECTION > OVERCURRENT STAGE I>


Enable for I> ON / OFF ON
Parameters
Pick-up setting 0.1 - 5.0 x In 1 x In 125,0 A
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation delay 0.04 - 300 s 50 s
Include Harmonics ON / OFF ON

Page161
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 502MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A04

Compressor 2 department, 1250 kVA

Description Setting Range Prefix Setting value Actual value

PROTECTION > OVERCURRENT STAGE I>>


Enable for I>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 2,3 x In 287,5 A
Operation delay 0.04 - 300 s 0,2 s
Include Harmonics ON / OFF ON

PROTECTION > OVERCURRENT STAGE I>>>


Enable for I>>> ON / OFF ON
Parameters
Pick-up setting 0.1 - 20 x In 9,2 x In 1.150,0 A
Operation delay 0.04 - 300 s 0,04 s

59N, Residual voltage (ground fault protection).

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>


Enable for Uo> ON / OFF ON
Parameters
Pick.up setting 1 - 60 % Uon 15 %
Operation delay 0.3 - 300 s 3s

PROTECTION > ZERO SEQ. VOLTAGE STAGE Uo>>


Enable for Uo>> ON / OFF OFF
Parameters
Pick.up setting 1 - 60 % Uon %
Operation delay 0.06 - 300 s s

67 N Directional earth fault protection

PROTECTION > DIRECTIONAL E/F Io M>


Enable for IoM> ON / OFF ON
Io input Io1 / Io2 / IoCalc Io1
Parameters
Direction mode Sector / UnDir / ResCap ResCap
Char ctrl. In ResCap mode Res / Cap Cap
Pickup setting 0.005-20 pu 0,03 pu
U0 setting for IoDir> stage "-88 - +88 %" 10 %
Angle offset "-180 - +179 " 0
Pick up sector size "-180 - +179 " +/- 85
Delay curve family DT / IEC / IEEE DT
Delay type DT DT
Operation Delay 0.04 -300 s 10 s
Intermittent time 0.00 - 5.00s 0 s

Page162
Reg. No.: 80040412
Xuan Thanh, Relay settings Version No.: 1.0
Protection type 2 Switchgear: 502MV100 Date: 12.11.16
Relay: VAMP 300 MV21 Panel name: A04

Compressor 2 department, 1250 kVA

Description Setting Range Prefix Setting value Actual value

PROTECTION > DIRECTIONAL E/F Io M>>


Enable for IoM>> ON / OFF OFF
Io input Io1 / Io2 / IoCalc
Parameters
Direction mode Sector / UnDir / ResCap
Char ctrl. In ResCap mode Res / Cap
Pickup setting 0.005-20 pu pu
U0 setting for IoDir> stage "-88 - +88 %" %
Angle offset "-180 - +179 "
Pick up sector size "-180 - +179 "
Delay curve family DT / IEC / IEEE
Delay type DT
Operation Delay 0.04 -300 s s

26, Oil temperature Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

63, Pressure Protection in form of potential free trip contacts on the transformer
hard wired into trip circuit of the circuit breaker.

Page163
Reg no.: 80040412
Relay settings for incoming breaker in LV switch gear
Version no.: 1.0
Project: Xuan Thanh Date: 12.11.17
Contract no.: 14-45344 Engineer: CB
Suplier: ABB, SACE. Page no.: 164
MDC/MCC Feeder Tag. No. Protection relay L S I G U
101LV100 Incoming 101LV100Q01 PR 122/P 1.0 x In, 10 s 2.5 x In, 0.1 s 10 x In N.A. N.A.
101LV110 Incoming 101LV110Q01 PR 122/P 1.0 x In, 10 s 2.5 x In, 0.1 s 10 x In N.A. N.A.
101LV200 Incoming 101LV200Q01 PR 122/P 1.0 x In, 10 s 2.5 x In, 0.1 s 10 x In N.A. N.A.
101LV400 Incoming 101LV400Q01 PR 122/P 1.0 x In, 10 s 2.5 x In, 0.1 s 10 x In N.A. N.A.
101LV500 Incoming 101LV500Q01 PR 122/P 1.0 x In, 10 s 2.5 x In, 0.1 s 10 x In N.A. N.A.
101LV600 Incoming 101LV600Q01 PR 122/P 1.0 x In, 10 s 2.5 x In, 0.1 s 10 x In N.A. N.A.
101LV700 Incoming 101LV700Q01 PR 122/P 1.0 x In, 10 s 2.5 x In, 0.1 s 10 x In N.A. N.A.
301LV100 Incoming 301LV100Q01 PR 122/P 1.0 x In, 10 s 2.5 x In, 0.1 s 10 x In N.A. N.A.
302LV100 Incoming 302LV100Q01 PR 122/P 1.0 x In, 10 s 2.5 x In, 0.1 s 10 x In N.A. N.A.
404LV100 Incoming 404LV100Q01 PR 122/P 1.0 x In, 10 s 2.5 x In, 0.1 s 10 x In N.A. N.A.
404LV110 Incoming 404LV110Q01 PR 122/P 1.0 x In, 10 s 2.5 x In, 0.1 s 10 x In N.A. N.A.
401LV200 Incoming 401LV200Q01 PR 122/P 1.0 x In, 10 s 2.5 x In, 0.1 s 10 x In N.A. N.A.
401LV210 Incoming 401LV210Q01 PR 122/P 1.0 x In, 10 s 2.5 x In, 0.1 s 10 x In N.A. N.A.
401LV220 Incoming 401LV220Q01 PR 122/P 1.0 x In, 10 s 2.5 x In, 0.1 s 10 x In N.A. N.A.

L=Overload, inverse time delay , S=Short circuit, adjustable delay , I=short circuit, instantaneous , G=Earth fault, adjustable delay , U=Phase unbalance
Selectivity curves Reg no: 80040412
50/51 Phase time overcurrent (definite time) Version: 1.0
Project: Xuan Thanh, 14-45344 Date: 12.11.16
Protective relay: VAMP 300 CB
MV-DB: 101MV100 Voltage level: 6.3 kV Page: 165

1000

100

10
Time [sec]

0,1

0,01
0,01 0,1 1 10 100

Current [kA]

Upstream breaker (Client) 101MV100A01

101MV100A03 101MV100A04

101MV100A05
Selectivity curves Reg no: 80040412
50/51 Phase time overcurrent (definite time) Version: 1.0
Project: Xuan Thanh, 14-45344 Date: 12.11.16
Protective relay: VAMP 300 CB
MV-DB: 101MV200 Voltage level: 6.3 kV Page: 166

1000

100

10
Time [sec]

0,1

0,01
0,01 0,1 1 10 100

Current [kA]

Upstream breaker (Client) 101MV200A01

101MV200A03
Selectivity curves Reg no: 80040412
50/51 Phase time overcurrent (definite time) Version: 1.0
Project: Xuan Thanh, 14-45344 Date: 12.11.16
Protective relay: VAMP 300 CB
MV-DB: 301MV100 Voltage level: 6.3 kV Page: 167

1000

100

10
Time [sec]

0,1

0,01
0,01 0,1 1 10 100

Current [kA]
Upstream breaker (Client)
301MV100A01
301MV100A02
301MV100A04 301MV100A05 301MV100A06
301MV100A07 301MV100A08
Selectivity curves Reg no: 80040412
50/51 Phase time overcurrent (definite time) Version: 1.0
Project: Xuan Thanh, 14-45344 Date: 12.11.16
Protective relay: VAMP 300 CB
MV-DB: 302MV100 Voltage level: 6.3 kV Page: 168

1000

100

10
Time [sec]

0,1

0,01
0,01 0,1 1 10 100

Current [kA]
Upstream breaker (Client) 302MV100A01

302MV100A03 302MV100A04
Selectivity curves Reg no: 80040412
50/51 Phase time overcurrent (definite time) Version: 1.0
Project: Xuan Thanh, 14-45344 Date: 12.11.16
Protective relay: VAMP 300 CB
MV-DB: 401MV100 Voltage level: 6.3 kV Page: 169

1000

100

10
Time [sec]

0,1

0,01
0,01 0,1 1 10 100

Current [kA]
Upstream breaker (Client) 401MV100A01

401MV100A02 401MV100A03 401MV100A05

401MV100A06 401MV100A07 401MV100A08, 401MV100A09


Selectivity curves Reg no: 80040412
50/51 Phase time overcurrent (definite time) Version: 1.0
Project: Xuan Thanh, 14-45344 Date: 12.11.16
Protective relay: VAMP 300 CB
MV-DB: 401MV100 Voltage level: 6.3 kV Page: 170

1000

100

10
Time [sec]

0,1

0,01
0,01 0,1 1 10 100

Current [kA]
Upstream breaker (Client) 401MV100A10

401MV100A11 401MV100A12
Selectivity curves Reg no: 80040412
50/51 Phase time overcurrent (definite time) Version: 1.0
Project: Xuan Thanh, 14-45344 Date: 12.11.16
Protective relay: VAMP 300 CB
MV-DB: 401MV200 Voltage level: 6.3 kV Page: 171

1000

100

10
Time [sec]

0,1

0,01
0,01 0,1 1 10 100

Current [kA]
Upstream breaker (Client) 401MV200A01

401MV200A04 401MV200A05

401MV100A06 401MV100A07 401MV200A08


Selectivity curves Reg no: 80040412
50/51 Phase time overcurrent (definite time) Version: 1.0
Project: Xuan Thanh, 14-45344 Date: 12.11.16
Protective relay: VAMP 300 CB
MV-DB: 401MV300 Voltage level: 6.3 kV Page: 172

1000

100

10
Time [sec]

0,1

0,01
0,01 0,1 1 10 100

Current [kA]
Upstream breaker (Client) 401MV300A01

401MV300A02 401MV300A04

401MV300A05
Selectivity curves Reg no: 80040412
50/51 Phase time overcurrent (definite time) Version: 1.0
Project: Xuan Thanh, 14-45344 Date: 12.11.16
Protective relay: VAMP 300 CB
MV-DB: 402MV300 Voltage level: 6.3 kV Page: 173

1000

100

10
Time [sec]

0,1

0,01
0,01 0,1 1 10 100

Current [kA]
Upstream breaker (Client) 402MV300A01

402MV300A02 402MV300A04
Selectivity curves Reg no: 80040412
50/51 Phase time overcurrent (definite time) Version: 1.0
Project: Xuan Thanh, 14-45344 Date: 12.11.16
Protective relay: VAMP 300 CB
MV-DB: 502MV100 Voltage level: 6.3 kV Page: 174

1000

100

10
Time [sec]

0,1

0,01
0,01 0,1 1 10 100

Current [kA]
Upstream breaker (Client) 502MV100A01 502MV100A02

502MV100A04