(Limitation of DDM)

1 . There should be minimum three spans in each direction

2 . Panels must be rectangular with the ratio of longer to shorter span c/c of
supports within a panel not greater than 2.0

3 . The successive span lengths c/c of support in each direction do not differ by
more than one third of the longer span.
4 . Columns are not offset more than 10% of all the span in the direction of
offset.
a. 10% of the longer span is (25 x 12) 10% = 30 and column width in
this direction is 16 which is less than 30
b. 10% of the shorter span is (20 x 12) x 10% = 24" and column width in
this direction is 12" which is less than 24"

5 . The load is due to gravity only and is uniformly distributed over an entire
panel and the service LL does not exceed two times the service DL.

1 2 2 2
6 . The relative stiffness ratio of to must lie between 0.2 and 5.0 where
1 2
is the ratio of the flexure stiffness of the included beam to that of the slab.

252
Panel 1, = = 53.72
.5 (14.59+8.68)
53.72
= .60
222 89.05
= = 89.05
.5 (6.81+4.06)

252
Panel 2, = = 53.72
.5 (14.59+8.68)
53.72
= 0.45
119.21
222
= = 119.21
.5 (4.06+4.06)

252
Panel 3, = = 72 72
.5 (8.68+8.68)
= .81
89.05
222
= = 89.05
.5 (6.81+4.06)

252
Panel 4, = = 72
.5 (8.68+8.68)
72
= .60
119.21
222
= = 119.21
.5 (4.06+4.06)