Vous êtes sur la page 1sur 3

PRICED SCHEDULE FOR INTERNAL WIRING FOR CONTROL ROOM BUILDING (EXISTING &

EXTENSION PORTION) AT KUSHMANDI 33/11KV SUB-STATION UNDER DAKSHIN DINAJPUR (D)


DIVISION
PART B: Electrical Works
Sl.No. Description of Items Quantity Unit Rate Amount(Rs.)
1 SUPPLYING, FITTING & FIXING OF 13mm
bore 3mm thickness Polythene pipe complete
with accessories as required for Main to D.B. 280.00 Mtr. Mtr. 18.00 5040.00
2 Main wiring with 2x2.5 sq.mm. PVC insulated
unsheathed copper wire from Panel Board to D.
Boards 280.00 Mtr. Mtr. 25.00 7000.00
3 Dist. Wiring with 2x1.5 sq.mm. PVC insulated
unsheathed copper wire in 1 casing capping
complete with all accessories embedded in wall
to light/ fan points with Piano Key type switches
fixed on wooden box board with Bakelite top
cover 45 No. Point 562.00 25290.00
4 Dist. Wiring with 2x1.5 sq.mm. PVC insulated
unsheathed copper wire to 250V, 5 Amp. 3 pin
plug socket without top including supplying,
fitting and fixing 1 no. 22 SWG G.I. earth
continuity wire to G.S.
14 No. Point 231.00 3234.00
5 Dist. Wiring with 2x2.5 sq.mm. PVC insulated
and unsheathed copper wire to 250V- 15 Amp.
Plug point/ exhaust Fan point in 1 casing
capping complete with all accessories embedded
in wall. 80.00 Mtr. Mtr. 60.00 4800.00
6 Supplying, fitting and fixing of bulk head light
fittings on wall with all fittings and necessary
connection 4 Nos. Each 115.00 460.00
7 Supplying, fitting and fixing composite flush
type 250V 3 Pin 15 Amps plug socket with 15
Amps. Piano key type switch on double
w3ooden Board on wall. 15 Nos. Each 150.00 2250.00
8 Fixing outdoor type S.V. light fittings complete
with all accessories to be fixed/ projected from
the wall of the building including making holes/
providing clamping arrangement and necessary
G.I. Reducer as required supplying, fitting and
fixing of 40 mm. Suitable bend supplying and
fitting necessary length of PVC wire and making
connection as required and mending good
damages to wall including painting etc. 5 Nos. Each 535.00 2675.00
9 Fixing outdoor type S.V. light fittings on Rail
Pole of Yard light including supplying, fitting
and fixing of 40mm dia x 1.68 mtrs. Long G.I.
Pipe with 50mm x 6 mm M.S. Clamp and
providing wiring with 1x1.5 sq.mm. PVC
insulated and sheathed wire from loop box at the
base of pole to light fittings and through pole
and bracket including making connection and
painting. 8 Nos. Each 960.00 7680.00
10 Supplying, fitting and fixing water proof looping
cable box having one 250V 15 Amps. Kit Kat
fuse unit one N.L. on porcelain insulator and
fixing of P.P. and painting as to G.S. 7 Nos. Each 720.00 5040.00
11 Laying one no. 2-core 16 sq.mm. PVC
Armoured copper cable through underground
trench 460mm wide x 760mm average depth
with brick protection on the top of the cable with
8 nos. Brick per mtr. Including fitting the space
between brick and cable and also the trench with
shifted soil, levelling up and restoring surface
duly rammed (cable supplied by tenderer.) 280.00 Mtr. Mtr. 72.00 20160.00
12 Earthing complete for A/C panel and D/C panel
with G.I. Pipe and 1x6 SWG G.I. Flat 13mm dia
x 80mm long G.I. nut bolts double washer
including supplying and fitting 15 mm dia G.I.
pipe protection partly under the ground level and
partly above ground level driven to an average
depth of 3 mtrs. Below the ground level and
restoring the surface duly rammed in soft soil. 4 Nos. Each 920.00 3680.00
13 Fixing only single/ double fluorescent light
fittings complete with tube lamp directly on wall
as required. 28 Nos. Each 78.00 2184.00
14 Fixing only ceiling Fan complete with blades,
regulator, canopy, fork, rubber bush etc.
Including supplying, fitting and fixing 2x1.5
sq.mm. PVC wire for down rod up to 30 cm and
making necessary connection as required 4 Nos. Each 34.00 136.00
15 Fixing of Exhaust Fan after making hole on wall
and making good damages and smooth cement
finish etc. As practicable as possible and
providing 2x1.5 sq.mm. PVC insulated and
sheathed wire and making connection for
Exhaust Fan of 23 cm dia 2 Nos. Each 140.00 280.00
16 Laying of 50 sq.mm. 3 core PVC cable from
Power Transformer to A/C panel Board through
underground trench as mentioned Sl.No.11
supplied by tenderer. 65.00 Mtr. Mtr. 78.00 5070.00
17 Making and fixing of Glow sign Board size : Each
6.5 x 3x8. 1 Item Item 4000.00 4000.00
18 Installation of L.T. A.C and D.C. Control Panel
and necessary connection 1 Nos. Each 5000.00 5000.00

TOTAL COST Rs.1,03,979.00


Add @1% cess on labour=Rs.1039.79
Total Estimated cost = Rs.1,05,018.79
Say Rs.1,05,019.00

SUPPLY PART:-
19 Supply of Fluorescent double (2x40 watt.) tube L.S
light fittings with 2 nos. 40 Watt lamp. 23 Set 1950.00 44850.00
20 Installation of L.T. A.C and D.C. Control Panel
and necessary connection 5 Nos. Each 980.00 4900.00
21 Supply of Exhaust Fan 23 cm dia 2 Nos. Each 3000.00 6000.00
22 Supply of Ceiling Fan (120cm dia) 60 Watt. 7 Nos. Each 1800.00 12600.00
23 Supply of L.T. A.C. and D.C. Control Panel 1 Nos. Each 52000.00 52000.00
24 Supply only 250V 250W Sodium Vapour

(Philips make) light fittings with 250 Watt lamp. 10 Nos. Each 5500.00 55000.00
25 Supply 16 sq.mm. 2-core armoured cable of
Aluminium conductor 280.00 Mtr. Mtr. 101.60 28448.00
26 Supply 50 sq.mm. 4-core armoured cable of
aluminium conductor 70.00 Mtr. Mtr. 214.93 15045.10

Total Estimated cost = Rs.2,18,843.10


Say Rs.2,18,843.00
Total Estimated cost-"B"(Electrical WORKS) =(Rs.1,05,019.00+Rs.2,18,843.00)= Rs.3,23,862.00