Académique Documents
Professionnel Documents
Culture Documents
ELECTRICAL WORKS
PARTICAL SPECIFICATIONS
FOR
SUPERMARKET
Waterfront Mall, Deira, Dubai
OWNER: CONSULTANTS:
Fairway Continente Hypermarket, LLC. Capital Engineering Consultancy, LLC.
2604, Saba 1, Jumeirah Lakes Towers GYM Building, Mezzanine Floor, Office No. M16
PO Box: 336336, Dubai, UAE Port Saeed St., PO Box: 92301,
Deira, Dubai, UAE
May 2016
CONTENTS PAGES
1.1 GENERAL
3.1 GEENRAL
4.1 GENERAL
5.1 GENERAL
A. All electrical equipment, accessories and fitting shall be designed
and manufactured to operate continuously in the electricity supply
system having the following characteristics.
Frequency 50 Hz + 4%
6.1 GENERAL
7.1 GENERAL
8.1 GENERAL
A. The Contractor shall ensure that all equipment included in his offer
can be accommodated in the position shown on the drawings
without structural alterations. The Engineer will not consider any
claims for additional payments resulting from modifications arising
from equipment of unsuitable dimensions being provided.
9.1 GENERAL
10.1 GENERAL
B. The results of the tests shall be not less than the requirements
stipulate in DCD/ DEWA and all other Authorities Regulations.
On satisfactory completion of the above testing, the Contractor shall submit the
necessary Test Forms duly completed; along with amount sets of As Built
Drawings, to DCD/ DEWA and all other Authorities for their inspection and
testing. The test forms and drawings shall be submitted at least 45 days
before the date
required for power supply. All tools, instruments and labour required for the
above testing and inspection shall be provided by the Contractor.
No portion of the work shall be accepted and taken over before the connection of
power supply. After the power supply connection the Contractor shall
commission all his equipment to the satisfaction o the Engineer.
SECTION EL-02
PART 1 GENERAL
1.1 SUMMARY
B. Related Sections:
1.2 REFERENCES
A. Grounding systems use the following elements as grounding electrodes cupper tape
and all other accessories as shown in article 1.1 A
B. Anchor and fasten electrical products to building elements and finishes as follows:
1. Steel Structural Elements: Provide beam clamps and spring steel clips.
3. Wire marker for each conductor at panelboard, pull boxes, outlet and junction boxes,
and each load connection.
A. Select materials, sizes, and types of anchors, fasteners, and supports to carry loads
of equipment and raceway, including weight of wire and cable in raceway.
1.5 SUBMITTALS
C. Samples: Submit one nameplates, 100 x 100 mm in size illustrating materials and
engraving quality.
D. Test Reports: Indicate overall resistance to ground and resistance of each electrode.
1.7 QUALIFICATIONS
2.1 EXAMINATION
B. Verify final backfill and compaction has been completed before driving rod
electrodes.
2.2 INSTALLATION
2. Install grounding well pipe with cover at each rod location as indicated on
Drawings. Install well pipe top flush with finished grade as per Engineer
requirement.
4. Install bonding meeting to meet DCD / DEWA and other local Authorities
requirements.
5. Bond together metal siding not attached to grounded structure; bond to ground.
6. Bond together reinforcing steel and metal accessories in pool and fount ain
structures.
B. Supports:
1. Fabricate supports from structural steel or formed steel members. Rigidly weld
members or install hexagon head bolts to present neat appearance with
adequate strength and rigidity. Install spring lock washers under nuts.
2. Install surface mounted cabinets and panel boards with minimum of four
anchors.
3. In wet and damp locations install steel channel supports to stand cabinets and
panel boards 25 mm off wall.
4. Install sheet metal channel to bridge studs above and below cabinets and panel
boards recessed in hollow partitions.
6. Identify underground conduits using one underground warning tape for each
trench at 75 mm below finished grade.
D. Raceway Painting: Identify conduit using field painting in accordance with Section
09900.
1 Color:
B. Inspect and test in accordance with NETA, B.S, DEWA/ DCD and other Local
Authorities.
C. Grounding and Bonding: Perform inspections and tests listed in NETA ATS, Section
7.13 and as DEWA/ DCD and other Authorities requirement.
PART 1 GENERAL
1.1 SUMMARY
A. Section includes building wire and cable; nonmetallic-sheathed cable; direct burial
cable; service entrance cable; armored cable; metal clad cable; and wiring connectors
and connections.
1.2 REFERENCES
1.5 SUBMITTALS
Product Data: Submit for building wire and each cable assembly.
C. Samples:
D. Design Data: Indicate voltage drop and ampacity calculations for aluminum conductors
substituted for copper conductors.
1.7 QUALIFICATIONS
1.9 COORDINATION
B. Where wire and cable destination is indicated and routing is not shown, determine
routing and lengths required.
PART 2 PRODUCTS
A. Manufacturers:
1. Riyadh Cable
2. Oman Cable
3. Pirelli, (UK)
4. Crompton, England
Or equal approved by the Engineer.
B. Wire shall be continuous from outlet to outlet and no splice shall be made. A separate
neutral wire shall be provided for each circuit. Wires shall be left sufficiently long permit
making final connections. The colour of insulation shall be as specified in IEE
regulations for different phases, neutral and earth wires.
A. PVC/PVC cables: PVC insulated PVC sheathed cables shall be 600/1000 V, single or
multi-core conforming to BS 6346 with high conductivity plain annealed stranded
copper conductors to BS 6360, PVC insulated with an extruded layer of PVC bedding
and a final outer extruded PVC sheath. The insulation and sheath shall be BS 6746
with insulation coloured to identify phases and neutral in accordance with BS 6746 C.
A. PVC/SWA/PVC cables: PVC insulated single wire armoured and PVC sheathed cables
shall be 600/1000 V, multi-core conforming to BS 6346 with high conductivity plain
annealed stranded copper conductors to BS 6360, PVC insulated with an extruded
layer of PVC bedding having a single layer of galvanised steel wires armoured for
multi-core cables and aluminium wires or tape for single core cables and a final outer
extruded PVC sheath. The insulation and sheath shall be to BS 6746 with insulation
coloured to identify phases and neural in accordance with BS 6746 C.
A. XLPE/SWA/PVC and XLPE/PVC cables: XLPE insulated single wire armoured and
PVC sheathed cables shall be single core or multi-core cables, 600/1000 V conforming
to BS 5467 with high conductivity plain annealed stranded copper conductors to BS
6360 to BS 6790 for aluminium conductors, insulated with cross linked polyet hylene
(XLPE) to BS 5468 applied.
A. Flexible silicon rubber shall be two or three core silicon rubber insulated, glass fibre
braided 300/500 volt conforming to BS 6500. Conductors shall be stranded tinned
annealed copper. Insulation shall be heat resistant 85 oC flexible Type 4 insulation
compound is used.
PART 3 EXECUTION
3.1 EXAMINATION
C. Verify mechanical work likely to damage wire and cable has been completed.
3.2 PREPARATION
3.3 INSTALLATION
C. Neatly train and lace wiring inside boxes, equipment, and panel boards.
D. Identify and color code wire and cable under provisions of Section 16050. Identify
each conductor with its circuit number or other designation indicated.
2. Support cables above accessible ceiling, using spring metal clips or metal
cable ties to support cables from structure. Do not rest cable on ceiling panels.
1. Trench and backfill for direct burial cable installation. Refer to Sections 02320
and 02324. Install warning tape along entire length of direct burial cable, within
75 mm grade.
2. Make splices, taps, and terminations to carry full ampacity of conductors with
no perceptible temperature rise.
3. Tape uninsulated conductors and connectors with electrical tape to 150 percent
of insulation rating of conductor.
4. Install split bolt connectors for copper conductor splices and taps, 10 mm 2 and
larger.
6. Install insulated spring wire connectors with plastic caps for copper conductor
splices and taps, 4 mm2 and smaller.
7. Install solid conductor for feeders and branch circuits as indicated on the
drawings.
SECTION EL-04
PART 1 GENERAL
1.1 SUMMARY
A. Section includes conduit and tubing, surface raceways, wireways, outlet boxes, pull
and junction boxes, and handholes.
B. Related Sections:
1. - Cable Trays.
1.2 REFERENCES
16130/1
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical Specification -Raceway and Boxes
F. NEMA RN 1 (National Electrical Manufacturers Association) - Polyvinyl Chloride (PVC)
Externally Coated Galvanized Rigid Steel Conduit and Intermediate Metal Conduit.
G. NEMA TC 3 (National Electrical Manufacturers Association) - PVC Fittings for Use with
Rigid PVC Conduit and Tubing.
A. Raceway and boxes located as indicated on Drawings, and at other locations required
for splices, taps, wire pulling, equipment connections, and compliance with regulatory
requirements. Raceway and boxes are shown in approximate locations unless
dimensioned. Provide raceway to complete wiring system.
B. Outdoor Locations, Above Grade: Provide rigid steel conduit, cast metal or
nonmetallic outlet, pull, and junction boxes.
16130/2
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical Specification -Raceway and Boxes
C. In Slab Above Grade: Provide rigid steel conduit. Provide nonmetallic boxes.
D. Wet and Damp Locations: Provide thick wall nonmetallic conduit and nonmetallic
tubing. Provide nonmetallic outlet, junction, and pull boxes. Provide flush mounting
outlet box in finished areas.
E. Concealed Dry Locations: Provide thick wall nonmetallic conduit and nonmetallic
tubing. Provide flush mounting outlet box in finished areas. Provide hinged enclosure
for large pull boxes.
1.5 SUBMITTALS
16130/3
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical Specification -Raceway and Boxes
1.7 DELIVERY, STORAGE, AND HANDLING
B. Protect conduit from corrosion and entrance of debris by storing above grade. Provide
appropriate covering.
1.8 COORDINATION
PART 2 PRODUCTS
A. Manufacturers:
1. Marushi, Japan
2. Barton, England
3. Mitsubishi, Japan
(any equivalents are not allowed)
A. Metallic conduits shall be steel heavy gauge to BS 4568 Part I, and CEE Publication
23, hot-dip galvanised inside and outside with screwed ends. Conduit fittings shall be
malleable iron, galvanised, with threaded spouts suitable for the number and
arrangement of conduits connecting to them.
B. Couplers, unions, saddles, hangers, straps, etc. shall be employed for connection and
fixing of conduit in a permanent and rigid manner and these shall be all galvani sed
steel, to BS 4568 Part 2.
C. Use of inspection type elbows, bends, tees and manufactured bends shall be avoided
wherever possible. Where impracticable to set conduit, normal factory made bends
may be used where approved by the Engineer.
D. Steel conduits shall be continuous from outlet to outlet to distribution boards, junction
or pull boxes and secured to all boxes so that each system is electrically continuous
from service to outlet. Conduits shall be screwed tightly into couplings and fittings and
connected to unspouted accessories such as distribution boards, switch and socket
boxes by couplers and male brass bushes to ensure earth continuity.
16130/4
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical Specification -Raceway and Boxes
E. Steel conduit ends shall be cut square and reamed to remove burrs and sharp edges.
No more screw threads shall be exposed than necessary and all exposed threads shall
be coated with Galvanite paint immediately after erection. Bends in conduits shall be
neatly made with proper bending machine and so formed that there is no cross
sectional distortion of conduits. Conduits shall be fixed surfaces by distance saddles
spaced at even intervals not exceeding the distance stated below:
Meter
Upto 25 mm 0.60
32 and 38 mm 0.90
50 mm 1.00
F. All conduit expansion couplings used shall be fabricated from material equal or
equivalent to that of the conduit with which the coupling is to be used, having factory
installed packing ring and pressure ring to prevent entrance of moisture. All expansion
couplings shall be equipped with earthing ring or earthing conductor.
G. All conduit runs shall be fixed using spacer bar pattern saddles giving not less than 3
mm clearance between the conduit and the surface to which it is fixed. Saddles shall
have finish to match the conduit and saddle clips shall be secured to bar by means of
brass screws.
A. Flexible steel conduit shall consist of flexible corrosion resistant steel core with a
watertight, synthetic jacket extruded over the conduit and a continu ous copper earth
tape under the jacket.
A. Manufacturers:
B. Product Description: NEMA RN 1; rigid steel conduit with external PVC coating, 0.1
mm.
C. Fittings and Conduit Bodies: NEMA FB 1; steel fittings with external PVC coating to
match conduit.
16130/5
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical Specification -Raceway and Boxes
2.5 PVC CONDUIT
A. Manufacturers
1. MK (UK)
2. CLIPSAL (AUS.)
3. EGA Tube, England
4. Marshall Tufflex, Germany
any equivalents are not allowed).
B. The sizes of conduits shall be in accordance with the number and sizes of wires to be
drawn inside then as indicted in IEE or latest ADDC Regulations but no conduit smaller
than 20 mm shall be used. A pull wire or tape shall be provided in all empty conduits
with no less than 200 mm of slack left at each end.
C. All plastic PVC conduits and associated fittings shall be Class A high impact quality
constructed of self extinguishing PVC material and shall comply with the requirements
of BS 4607 suitable for use in temperature upto 85oC.
D. Conduits shall not less than 20 mm diameter size, and shall be complete with all
necessary conduit fittings of the same manufacturer, class and colour as the conduit to
which they are fitted.
E. All conduit boxes from which fittings are suspended shall have external metal fixing
lugs riveted to the threaded inserts in the box.
G. All conduit saddle fixings shall be spacer bar saddles giving not less than 3 mm
clearance between the conduit and the surface to which it is fixed, and shall be of the
same colour as the conduit which they secure. The saddle clip shall be secured to the
bar by pass screws. Self tapping screws will not be permitted.
H. All conduit expansion couplings used shall be of the, same manufacture as the
conduits to which they are fitted, and shall be of the same class and colour.
2.6 BOXES
A. Manufacturers:
1. Marushi, Japan
2. Hubbell Wiring Devices, USA
3. Mitsubishi, Japan
any equivalents are not allowed).
16130/6
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical Specification -Raceway and Boxes
2.7 OUTLET BOXES
C. Cast Boxes: NEMA FB 1, Type FD, cast feralloy. Furnish gasketed cover by box
manufacturer.
C. Surface Mounted Cast Metal Box: NEMA 250, Type 4 flat-flanged, surface mounted
junction box:
Cover: Furnish with ground flange, neoprene gasket, and stainless steel cover
screws.
D. In-Ground Cast Metal Box: NEMA 250, Type 6, outside flanged, recessed cover box
for flush mounting:
2. Cover: Smooth cover with neoprene gasket and stainless steel cover screws.
16130/7
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical Specification -Raceway and Boxes
PART 3 EXECUTION
3.1 EXAMINATION
B. Verify outlet locations and routing and termination locations of raceway prior to rough -
in.
3.2 INSTALLATION
A. Install Work in accordance with DCD / DEWA local Authorities Standard and NECA.
B. Ground and bond raceway and boxes in accordance with Section 16050.
C. Fasten raceway and box supports to structure and finishes in accordance with Section
16050.
E. Arrange raceway and boxes to maintain headroom and present neat appearance.
D. Support raceway using coated steel or malleable iron straps, lay-in adjustable
hangers, clevis hangers, and split hangers.
E. Group related raceway; support using conduit rack. Construct rack using steel
channel , provide space on each for 25 percent additional raceways].
F. Do not support raceway with wire or perforated pipe straps. Remove wire used for
temporary supports
J. Route raceway installed above accessible ceilings parallel and perpendicular to walls.
16130/8
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical Specification -Raceway and Boxes
L. Maintain clearance between raceway and piping for maintenance purposes.
Q. Install no more than equivalent of three 90 degree bends between boxes. Install
conduit bodies to make sharp changes in direction, as around beams. Install factory
elbows for bends in metal conduit larger than 50 mm size.
R. Avoid moisture traps; install junction box with drain fitting at low points in conduit
system.
T. Install suitable pull string or cord in each empty raceway except sleeves and nipples.
U. Install suitable caps to protect installed conduit against entrance of dirt and moisture.
V. Surface Raceway: Install flat-head screws, clips, and straps to fasten raceway channel
to surfaces; mount plumb and level. Install insulating bushings and inserts at
connections to outlets and corner fittings.
C. Install pull boxes and junction boxes above accessible ceilings and in unfinished areas
only.
D. Inaccessible Ceiling Areas: Install outlet and junction boxes no more than 150 mm
from ceiling access panel or from removable recessed luminaire.
E. Locate flush mounting box in masonry wall to require cutting of masonry unit corner
only. Coordinate masonry cutting to achieve neat opening.
F. Do not install flush mounting box back-to-back in walls; install with minimum 150 mm
separation.
16130/9
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical Specification -Raceway and Boxes
G. Secure flush mounting box to interior wall and partition studs. Accurately position to
allow for surface finish thickness.
H. Install stamped steel bridges to fasten flush mounting outlet box between studs.
I. Install flush mounting box without damaging wall insulation or reducing its
effectiveness.
J. Install adjustable steel channel fasteners for hung ceiling outlet box.
M. Install gang box where more than one device is mounted together. Do not use
sectional box.
N. Install gang box with plaster ring for single device outlets.
A. Install conduit to preserve fire resistance rating of partitions and other elements, using
materials and methods .
B. Route conduit through roof openings for piping and ductwork or through suitable roof
jack with pitch pocket. Coordinate location with roofing installation.
D. Align adjacent wall mounted outlet boxes for switches, thermostats, and similar
devices.
3.6 ADJUSTING
B. Adjust flush-mounting outlets to make front flush with finished wall material.
3.7 CLEANING
CABLE TRAYS
PART 1 GENERAL
1.1 SUMMARY
1.2 REFERENCES
B. ASTM A525 - General Requirements for Steel Sheet, Zinc-Coated Galvanized by the
Hot-Dip Process.
1.3 SUBMITTALS
B. Shop Drawings: Indicate tray type, dimensions, support points, and finishes.
B. Project Record Documents: Record actual routing of cable tray and locations of
supports.
1.5 QUALIFICATIONS
PART 2 PRODUCTS
A. NEMA VE 1 Class designation, indicated in the following specifications for metal cable
tray, is support span in meters plus working load designation.
B. Manufacturers
1. Davis, UK
2. Barton, UK
3. Wibe, Sweden
(any equivalents are not allowed)
B. Material: Steel.
C. Finish: ASTM A123, hot dipped galvanized after fabrication Painted with gray epoxy.
B. Material: Steel.
3.1 INSTALLATION
C. Support trays and fasten to structure and finishes in accordance with Section 16050.
Install supports at each connection point, at end of each run, and at other points to
maintain spacing between supports of 2000 mm maximum.
E. Install fire stopping in accordance with Section 07840, 16050 to sustain ratings when
passing cable tray through fire-rated elements.
F. Ground and bond metal cable tray in accordance with Section 16050.
G. Install warning signs at 1500 mm centers along cable tray, located to be visible.
WIRING DEVICES
PART 1 GENERAL
1.1 SUMMARY
A. Section includes wall switches; wall dimmers; receptacles; multioutlet assembly; and
device plates and decorative box covers.
B. Related Sections:
1.2 REFERENCES
1.3 SUBMITTALS
C. Samples: Submit two samples of each wiring device and wall plate illustrating materials,
construction, color, and finish.
A. Manufacturers
1. M.K., England
2. Siemens, Germany
3. Legrand, France
(any equivalents are not allowed).
A. Lighting Accessories
Provide complete lighting control system including direct switching control, control and
contactor control all as detailed and indicated on the drawings and specified hereinafter.
B. Direct Switching
1. Locally installed on/off switches controlling the lighting for a particular room by
means of direct connection/disconnection of lighting circuits.
2. Switches shall be 20A, 250V, AC inductive load rated to their full rated capacity
to BS 3676.
3. Switches shall be flush mounted in walls inside galvanised stamped steel boxes
at a height of 1200mm above finished floor level, unless otherwise indicated on
the Drawings. Switches shall be of white moulded cover plates as approved by
the Engineer. Terminals shall be of the screw type of solder-less pressure type
having suitable conductor release arrangement. Where two or more switches are
located in the same position and same phase, they shall be installed in one box
and covered by a multi-gang cover plate.
C. Contactor Control
2. The manual mode of the contactor shall be controlled by local push button
stations at the floor lighting control panel.
A. Socket shall be 250 V, three pin, 13A switched type to BS 1363. Safety shutters shall
cover pin holes to prevent accidental contact. Contact arrangement shall be such that
contact is made on two sides of the rectangular pins of plugs.
B. Sockets shall be fixed inside galvanised stamped steel boxes which shall be flush
mounted in walls, and it shall be single or duplex as indicated on the drawings.
A. All weatherproof (splash proof) socket outlets shall comply with BS 5420, IP 44.
B. Outlets shall single phase 250 volt, three pin, 13A one (1) pair of phase, neutral and
earth terminals each pair suitable for two (2) 2.5 m sq. hard wiring conductors.
2.4 JUNCTION BOXES
A. Junction boxes shall be fused type and complete with one (1) pair of phase, neutral and
earth terminals each pair suitable for two (2) 2.5 mm sq. hard wiring conductors.
B. All boxes shall incorporate an internal grip for securing the flexible cord or cable.
3.1 EXAMINATION
C. Verify wall openings are neatly cut and completely covered by wall plates.
D. Verify branch circuit wiring installation is completed, tested, and ready for connection to
wiring devices.
3.2 PREPARATION
3.3 INSTALLATION
D. Install wall dimmers to achieve full rating specified and indicated after derating for
ganging as instructed by manufacturer.
G. Connect wiring device grounding terminal to outlet box with bonding jumper and branch
circuit equipment grounding conductor.
H. Install decorative plates on switch, receptacle, and blank outlets in finished areas.
I. Connect wiring devices by wrapping solid conductor around screw terminal. Install
stranded conductor for branch circuits 10 AWG and smaller. When stranded conductors
are used in lieu of solid, use crimp on fork terminals for device terminations. Do not
place bare stranded conductors directly under device screws.
K. Install galvanized steel plates on outlet boxes and junction boxes in unfinished areas,
above accessible ceilings, and on surface mounted outlets.
C. Operate each wall switch with circuit energized and verify proper operation.
3.6 ADJUSTING
3.7 CLEANING
WIRING CONNECTIONS
PART 1 GENERAL
1.1 SUMMARY
B. Related Sections:
1.2 REFERENCES
1.3 SUBMITTALS
1.5 COORDINATION
B. Obtain and review shop drawings, product data, manufacturers wiring diagrams, and
manufacturer's instructions for equipment furnished under other sections.
A. Manufacturers:
D. Cord Construction: Type SJO multi conductor flexible cord with identified equipment
grounding conductor, suitable for use in damp locations.
E. Size: Suitable for connected load of equipment, length of cord, and rating of branch
circuit over current protection.
3.1 EXAMINATION
B. Verify equipment is ready for electrical connection, for wiring, and to be energized.
3.2 INSTALLATION
B. Make conduit connections to equipment using flexible conduit. Use liquid tight flexible
conduit with watertight connectors in damp or wet locations.
C. Connect heat producing equipment using wire and cable with insulation suitable for
temperatures encountered.
F. Install suitable strain-relief clamps and fittings for cord connections at outlet boxes and
equipment connection boxes.
I. Install interconnecting conduit and wiring between devices and equipment to complete
equipment wiring requirements.
3.3 ADJUSTING
B. Cooperate with utilization equipment installers and field service personnel during
checkout and starting of equipment to allow testing and balancing and other startup
operations. Provide personnel to operate electrical system and checkout wiring
connection components and configurations.
PART 1 GENERAL
C. Bonding connection.
1.2 REFERENCES
C. DCD/DEWA
Regulation. D. IEE
Requirements.
B. Concrete-encased electrode.
C. Rod electrode.
A. Provide complete earth system in strict accordance with DCD/DEWA and IEE
requirements.
Generally, all non-current-carrying, metal components of the electrical installation and
of power-consuming equipment shall be connected to the earthing system.
B. The contractor shall not connect the system neutrals to earth at any point.
1.5 SUBMITTALS
1.7 QUALIFICATIONS
NOT USED.
PART 2 PRODUCTS
A. Manufacturers
1. Furse, England
2. E.F. International, Switzerland
3. Wallis, England
(any equivalents are not allowed).
A. Earth rods shall be steel/copper of not less than 16 mm diameter, three metres long,
driven full length into the earth. The copper clad earth rods shall be manufactured by
fusion weld process resulting in an electrolytic copper sheath nomogeneously welded
to an inner steel core. The thickness of the copper sheath shall be approximately 10%
of the overall rod diameter. Copper electroplated steel is not acceptable.
B. One end of the rod shall be pointed without application of heat and with driving head at
other end. The sectional rods shall be coupled with strong bronze couplers. The
coupler shall be threaded to fit the rod section. For driving the rod into the ground
threaded steel shall be used.
2.2 MATERIALS
A. The main earth bars shall be constructed of high conductivity copper, drilled, mounted
on insulators and fixed as detailed on the drawings.
B. Unless specified otherwise, the cross sectional area of protective conductors shall be
in accordance with the relevant IEC and BSI standards and DCD /DEWA regulations.
A. A brass clamp of suitable size shall be provided for clamping the earth copper tape to
earth rod. The rod shall be driven into the earth by means of a power hammer. The top
of the earth electrode shall be concrete housing with removable concrete cover for
periodical testing of the electrode.
B. Exothemic connections for connection of foundation steel bar and earthing wires (tape)
and between earthing wires.
2.4 WIRE
A. Material: Copper.
B. Size to meet IEE, DCD/DEWA and other Authorities requirements and as indicated
on the drawings.
B. Material - concrete.
PART 3 EXECUTION
3.1 EXAMINATION
A. Verify that final backfill and compaction has been completed before driving rod
electrodes.
3.2 INSTALLATION
C. Provide earthing pit with cover at rod locations where indicated. Install earthing top
flush with finished grade.
D. Install 75 mm2 bare copper wire or (tape) in foundation footing where indicated.
E. Provide bonding to meet DCD/ DEWA, other local Authorities & IEE
requirements.
G. Bond together reinforcing steel and metal accessories in pool and fountain structures.
H. All metallic equipment enclosures, steel conduit system, cable trays, trunkings, lighting
fixtures, earthing pins of socket, all non-current carrying metal parts of the electrical
systems and any other equipment or system components required by DCD/ DEWA,
IEE and other local Authorities regulations shall be earthed in an approved manner.
I. All earth connections shall terminate finally at the main low tension switchboard earth
bus extended from there to earth electrodes as specified hereinafter.
J. The earthing system of the building shall be an independent system connected to the
earth bus on the main switchboard. The neutral shall not be used for earthing and shall
be connected to the earth only at the main low tension switchboard.
K. The conduit system shall be considered as continuous for earthing purposes only if the
conduit is rigid heavy gauge steel with threaded connections and lock nuts at all boxes
and all connections of the conduit system shall be checked for good electrical
continuity. Where flexible connections are made to equipment, earthing jumpers shall
be provided.
L. In all other cases, a separate earth in additional to the circuit wiring shall be included.
The earth conductor shall installed in the same conduit with the phase and neutral
conductors and shall be sized in accordance with DCD/ DEWA regulations.
M. The earth wires shall be covered with PVC and distinguished by green colour.
N. All electrical equipment in mechanical rooms areas shall be earthed to earth tape fixed
to walls as shown on the Drawings. The earth tape shall be high conductivity copper
conductor neatly and firmly secured to the walls maintaining 12mm clearance
therefrom and sizes as shown on the Drawings.
Q. All distribution boards, switch fuses and isolators shall be provided with an earth bus or
earth terminal and these shall be connected to the earth bus in the main switchboard
by earth conductors included with the feeders.
R. On cable trays and in electrical riser shafts an earthing copper tape of 25 x 3 mm shall
be provided for earthing all distribution boards, isolators and equipment.
A. Connection between earth bars and equipment frames and stranded cables shall be
made with appropriate compression lugs, bolts, nuts and lock washers. Contact
surfaces shall be thoroughly cleaned and tinned.
B. Lugs, bolts, nuts, washers, screws, clamps, cleats and other items which come into
direct contact with copper earth bars, tapes, cables etc. shall be non -ferrous
and manufactured from brass, bronze or other suitable conducting material which will
not cause electrolytic corrosion. Connection between copper and galvanized
structures shall additionally be tinned.
D. The earth bus in the main switchboard shall be connected to the panel room earth bus.
The panel room earth bus shall be connected to the earthing points.
E. The maximum earth resistance as measured at the earth bus shall be in accordance
with ADDC regulations. If this resistance cannot be obtained with two earth rods,
additional earth rods or sectional earth rods shall be used to obtain the required
resistance. Parallel connected earth rods shall be spaced at a distance of not less
than the rod lengths and connected by 25 x 3 mm copper tape. If approved by the
Engineer, earth plates or other earthing means may be used instead of the additional
earth rods.
F. Measurement of earth resistance shall not be made within 48 hours after rainfall. The
panel room earth bus may be connection to the metallic water service of the building
provided this is approved by DCD/DEWA, the Ministry of Electricity and Water.
G. The connection between earth conductors and earth rods shall be made by means of
high strength corrosion resistant copper alloy connector clamps.
H. The tops of the electrodes shall be protected from any damage and shall be easily
accessible being enclosed in pits equipped with covers. The presence of the
electrode shall be indicated in English and Arabic.
3.4 FIELD QUALITY CONTROL
A. Inspect grounding and bonding system conductors and connections for tightness
and proper installation.
SECTION EL-09
GENERAL
1.01 SUMMARY
1.02 SUBMITTALS
A. Product Data: Include data on features, components, ratings, and performance for
each uninterruptible power supply component indicated.
D. Field Test Reports: Indicate test results compared with specified performance
requirements and provide justification and resolution of differences if values do not
agree.
C. Source Limitations: Obtain the UPS and associated components specified in this
Section from a single manufacturer with responsibility for entire UPS installation.
1.05 WARRANTY
A. Warranties, General: Special warranties specified in this Article shall not deprive
Owner of other rights Owner may have under other provisions of the Contract
Documents and shall be in addition to, and run concurrent with, other warranties
made by Contractor under requirements of the Contract Documents.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents. Deliver extra materials to Owner.
1. Fuses: One for every 10 of each type and rating, but not less than 1 of each.
2. Cabinet Ventilation Filters: One complete set.
3. One spare circuit board for each critical circuit.
PART 2 PRODUCTS
2.01 MANUFACTURERS
A. UPS shall perform as specified in this Article while supplying rated full-load current,
composed of any combination of linear and nonlinear load, up to 100 percent
nonlinear load with a load crest factor of 3.0, under the following conditions or
combinations of the following conditions:
1. Inverter is switched to battery source.
2. Steady-state ac input voltage deviates up to plus or minus 10 percent from
nominal voltage.
3. Steady-state input frequency deviates up to plus or minus 5 percent from
nominal frequency.
4. THD of input voltage is 15 percent or more with a minimum crest factor of
3.0, and the largest single harmonic component is a minimum of 5 percent of
the fundamental value.
5. Choice of alternative performance figure in subparagraph below affects ability
of UPS.
D. Overall UPS Efficiency: Equal to or greater than 95 percent at 100 percent load.
J. Maximum Output-Voltage Transient Excursions from Rated Value: For the following
instantaneous load changes, stated as percentages of rated full UPS load, voltage
shall remain within stated percentages of rated value and recover to, and remain
within, plus or minus 2 percent of that value within 100 ms:
1. 50 Percent: Plus or minus 8 percent.
100 Percent: Plus or minus 10 percent.
Loss of AC Input Power: Plus or minus 5 percent.
Restoration of AC Input Power: Plus or minus 5 percent.
K. Input Power Factor: A minimum of 0.9 lagging when supply voltage and current are
at nominal rated values and UPS is supplying rated full-load current.
L. EMI Emissions: Comply with FCC Rules and Regulations, 47 CFR 15 for Class A
equipment.
Surge Suppression: Protect internal UPS components from surges that enter at
each ac power input connection including main disconnect, static bypass transfer
switch, and maintenance bypass/isolation switch. Protect rectifier-charger, inverter,
controls, and output components.
Use factory-installed surge suppressors tested according to IEEE C62.41.
Additional Surge Protection: Protect internal UPS components from low
frequency, high-energy voltage surges described in IEEE C62.41. Design
the circuits connecting with external power sources and select circuit
elements, conductors, conventional surge suppressors, and rectifier
components and controls so input assemblies will have adequate
mechanical strength and thermal and current-carrying capacity to
withstand stresses imposed by 40-Hz, 180 percent voltage surges
described in IEEE C62.41.
Output Circuit Neutral Bus, Conductor, and Terminal Amp city: Rated phase current
times a multiple of 1.73, minimum.
2.06 RECTIFIER-CHARGER
A. Capacity: Adequate to supply the inverter during full-rated output load conditions
and simultaneously recharge the battery from fully discharged condition to 95
percent of full charge within 10 times the rated discharge time for duration of supply
under battery power at full load.
B. Output Ripple: Limited by output filtration to less than 0.5 percent of rated current,
peak to peak.
2.07 INVERTER
B. Switch Rating: minimum Continuous duty at the rated full-load current of the UPS.
2.09 BATTERY
A. Description: Sealed Acid type, ABS Container, mounted on steel impact racks.
Battery circuit breaker to be provided.
B. Minimum displays, indicating devices, and controls include those in lists below.
Provide sensors, transducers, terminals, relays, and wiring required to support
listed items. Alarms include an audible signal and a visual display.
D. Dry-form "C" contacts shall be available for remote indication of the following
conditions:
1. UPS on battery.
2. UPS on-line.
3. UPS load-on bypass.
4. UPS in alarm condition.
UPS off (maintenance bypass closed).
PART 3 EXECUTION
3.01 INSTALLATION
3.02 GROUNDING
3.03 IDENTIFICATION
3.05 DEMONSTRATION
SECTION EL-10
ENCLOSED SWITCHES
PART 1 GENERAL
1.1 SUMMARY
B. Related Sections:
1.2 REFERENCES
1.3 SUBMITTALS
B. Project Record Documents: Record actual locations of enclosed switches and ratings
of installed fuses.
1.5 QUALIFICATIONS
A. Manufacturers:
1. GE Electrical, USA
2. Merlin Gerin Co., France
3. Westinghouse Electric Corp., USA
4. Siemens Co., Germany
Or equal approved by the Engineer.
D. Service Entrance: Switches identified for use as service equipment are to be labeled
for this application. Furnish solid neutral assembly and equipment ground bar.
C. Service Entrance: Switches identified for use as service equipment are to be labeled
for this application. Furnish solid neutral assembly and equipment ground bar.
B. Short Circuit Current Rating: As DCD/ DEWA and other Authorities regulation.
3.1 INSTALLATION
B. Install enclosed switches plumb. Provide supports in accordance with Section 16050. C.
F. Apply adhesive tag on inside door of each fused switch indicating NEMA fuse class
and size installed.
SWITCH BOARDS
PART 1 GENERAL
1.1 SUMMARY
A. Section includes specification for, Isolator & Switch fuses, main distribution boards, Sub
main distribution boards, meters, meter selector switches, KWH meter, CTs and
Capacitor Bank.
B. Related Sections:
2. - Fuses.
1.2 REFERENCES
The switchboards shall comply with the following standards as appropriate. Where no regulation
/ standards are mentioned, latest IEC standards shall be applicable.
1.3 SUBMITTALS
A. - Submittal Procedures.
B. Shop Drawings: Indicate front and side views of enclosures with overall dimensions
shown; conduit entrance locations and requirements; nameplate legends; size and
number of bus bars for each phase, neutral, and ground; and switchboard instrument
details.
C. Product Data: Submit electrical characteristics including voltage, frame size and trip
ratings, fault current withstand ratings, and time-current curves of equipment and
components.
D. The switchboards shall be factory assembled and tested. Where any equipment need to
be assembled at site, a prior approval of the engineer would be necessary
H. All switchboards and component shall be from the same manufacture to maintain the
best cost/performance ratio between continuity of supply and safety, to ensure
discrimination, proper protection, full co-ordinations and easy substitution.
C. Operation and Maintenance Data: Submit spare parts data listing; source and current
prices of replacement parts and supplies; and recommended maintenance procedures
and intervals.
1.5 QUALIFICATIONS
B. All low voltage switchboards shall offer a dedicated section when required in order to
allow the installation in an electrical room corner. Bus bar shall be sized so that the main
bus bar forms a constant rating from one side to opposite one. The manufacturer shall
make evidence that this solution is part of its standard offer.
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical Specification Switchboard 16441/3
C. All low-voltage electrical switchboard should have the capability to withstand seismic
conditions. When the switchboard is to be used in a seismic area, the manufacturer
should determine the switchboard configuration according to seismic information
provided by customer, which is appropriate to the stresses involved. The seismic test
should be done in compliance with the UBC (Uniform Building Code) and CBC
(California Building Code) regulations. The manufacturer shall be able to provide
information on seismic zone (1 to 4) and installation level which the equipment is
conforming to. Test report shall be made available.
A. Deliver in shipping splits, individually wrapped for protection and mounted on shipping
skids.
C. Store in clean, dry space. Maintain factory wrapping or provide additional canvas or
plastic cover to protect units from dirt, water, construction debris, and traffic.
1.8 SEQUENCING
B. Sequence Work to avoid interferences with building finishes and installation of other
products.
C. Furnish two set of hard copy and a soft copy of complete as built drawings.
A. General: Furnish extra materials, matching products installed (as described below).
packaging with protective covering for storage, and identifying with labels clearly
describing contents.
B. Miniature circuit breakers : Furnish quantity equal to 5 percent of the number breaker
installed, but not less than 5.
C. Fuses: Furnish quantity equal to 10 percent of number of fuses installed of each rating
but not less than 10.
D. Molded case circuit breakers : Furnish quantity equal to 10 percent of the number of
breakers installed of each frame rating, but not less than one.
A. Manufacturers
1. Dorman Smith, UK
2. Merlin Gerin, France
3. ABB, Europ
4. Eaton, USA
5. Sennider, Europ
B. Service Conditions:
1. Temperature: 55 degrees C.
C. The components such as panel boards, busbar system, switchgear etc. used in different
switchboards mainly MLTBs, MSBs, SMSBs, MCCs, DBs and Control Panels shall be
from one manufacturer to maintain the best cost/performance ratio between continuity of
supply and safety, to ensure discrimination, proper protection, full co-ordinations and
easy substitution.
D. All switchboards shall have been type tested per IEC 61439-1 & 2 and passed all test
stipulated in the standard. Temperature rise test shall have been performed at 55 deg C
to suit UAE climatic conditions. Complete type test report shall be made available along
with submittal for approval. The type-test certificates shall be originated by a worldwide
known third-party certification organization such as ASTA, KEMA, ACAE, CESI, ASEFA,
PEHLA, CEBEC, SEMKO. Certificates from Laboratories not certified under LOVAG will
not be acceptable.
E. All switchboards shall be made of folded EGI (Electro galvanized iron (EGI) epoxy
polyester painted (CR or Black steel material will not be accepted) sheet metal of atleast
2.0mm thickness. The sheet metal shall be treated by several steps of chemical process
to protect against corrosion. It shall be gray finish RAL 9002 over a rust -inhibiting primer
on phosphatizing-treated metal surfaces.
F. Bus isolation barriers shall be arranged to isolate line bus from load bus at each main
and tie circuit breaker. Fabricate enclosure with removable rear cover panels to allow
access to rear interior of switchgear.
G. Each vertical structure (or section) shall contain main horizontal bus bar on the top or at
the bottom vertical distribution bus bar to feed the different functional units (fixed or
withdrawable) containing ACB, MCCB, compartment for auxiliary components
(instruments, measurement, control.).
H. The section construction shall be so designed that sheet steel barriers shall be provided
between each vertical sections, breaker compartments, control and power
compartments. Each compartment sheet walls shall provide protection against direct
contacts with live parts and guarantee a degree of protection IP2X. The sections shall
be of modular construction with its functional unit having its own door, mounting plates,
side partitions, horizontal partitions. This type of functional arrangement ensures the
compartment design / sizing is identical to the type tested configuration. Switchboards
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical Specification Switchboard 16441/5
shall give an access to operators either from front or rear side. Common mounting plates
for different functional units within the same vertical section will not be acceptable.
J. People Safety: All MLTBs should be equipped with an efficient and reliable arc detection
system designed according to IEC 61508 with a safety integrity level meeting at least
SIL 2 claim. The system shall consist of one or more arc monitoring units and light
detectors. The switchboard shall be designed to minimize the risks of occurrence of an
internal arc, and whenever such an arc occurs it should prevent its effect on operators
and material/equipment surrounding the switchboard.
K. The manufacturer shall provide certificates showing evidence that the switchboard can
withstand an internal arc of 85kA 0.3s. Tests shall be performed on horizontal and
vertical bus bar as well as functional units and fulfill the 5 criteria of IEC 61641 edition 2
standard concerning personal protection. It should also be in conformance with the
requirements of AS 3439-1 for outgoing compartments.
L. All switchboards shall be made of identified free standing vertical structures, suitable for
installation side by side and designed to be connected with bus ducts as well as cables.
The system shall make it possible to implement fixed or withdrawable distribution
sections, which together form an assembly referred to as a low voltage electrical
switchboard
M. The switchboards shall be of IP54 construction in accordance with IEC 60529. All doors
and removable covers or plates shall be provided with suitable neoprene gaskets to
prevent the ingress of dust, vermin and insect.
N. Each unit of the switchboard shall be housed in its own cell fitted with a hinged door
mechanically interlocked in such a manner that the cell door can only be opened when
the switch is in the OFF position. For maintenance purpose, this mechanical door
interlocks shall be defeatable by trained and authorized personnel.
P. Adequate cable ways shall be provided in the switchboards accessible by hinged doors.
The equipment in the switchboards shall be accessible with indicating instruments
mounted not higher than 1.9mt. above switchboard base. The switchboards shall be
properly fixed to the floor with foundation bolts grouted in the floor or bolted to the
channels laid across the cable trench.
Q. The switchboards shall have top or bottom cable entries as required. Main incoming
cables shall be top / bottom entry with necessary cable glands. Provide aluminium gland
plates for single core cables.
T. The low-voltage electrical switchboards shall be compatible with all system earthing
arrangements defined in standard IEC 60984 (IT, TT or TN). The low-voltage electrical
switchboards shall have an earthing circuit of a solid copper bar able to withstand the
rated short circuit level.
U. The installation area shall provide enough space in order to allow Future extension of
the switchgear on both sides, opening of front and/or rear doors and/or covers if any.
Extensions of all electrical switchboard shall be possible on either side (right or left) of
the switchboard and accordingly main busbars shall be predrilled to extend at later stage
with minimum shutdown time.
V. Depending on cable connection way, the following shall be foreseen connection from top
shall provide at least 600mm to allow cable connection, connection from bottom shall
provide at least 600mm on either a trench or a false floor.
W. Busbar:
Y. Line and Load Terminations: Accessible from rear of switchboard, suitable for conductor
materials and sizes as indicated on Drawings.
AA. Future Provisions: Fully equip spaces for future devices with bussing and bus
connections, insulated and braced for short circuit currents. Furnish continuous current
rating as indicated on Drawings.
CC. Switchboard Height: Should not exceed 2200mm and to be approved by the Engineer.
A. The moulded-case circuit breakers shall comply with the general rules of IEC 60947 1
and 2 or standards derived from the latter (VDE 0660; BS4752; UTE 63120). Versions
complying with UL 489 shall also be available.
B. The moulded-case circuit breakers above 630A shall belong to category B as defined
IEC 60947-2. MCCBs including and upto 630A shall be current limiting type and belong
to category A to achieve total co-ordination. Certificates attesting to compliance with
these rules shall be established taking into account the following performance levels for
the test sequences: service breaking capacity (Ics) equal to 100% of the rated ultimate
breaking capacity (Icu) and a rated short-time withstand current (Icw) of 25 kA / 0.5s
C. The rated ultimate breaking capacity (Icu) of each moulded-case circuit breaker shall be
equal to at least the value of the short-circuit current (Isc) at the point of installation on
the electric circuit, unless the upstream circuit breaker makes it possible to ensure total
coordination (as defined in Appendix A of IEC 60947-2); in this case, the coordination
between the two circuit breakers shall be confirmed co-ordination study.
D. The moulded-case circuit breakers shall have a rated operational voltage (Ue) as 690V
AC (50/60Hz), rated insulation voltage (Ui) as 800V AC (50/60Hz). The moulded -case
circuit breakers shall be available in switch-disconnector versions. MCCBs shall be
designed according to Eco-design complying with ISO 14062. Especially MCCBs
materials shall be of halogen free type.
E. MCCBs including and upto 250A shall have thermal magnetic type trip unit with
adjustable thermal protection between 70% to 100% and fixed magnetic setting
including and upto 200A. Magnetic settings shall be adjustable between 5% to 10% the
current rating for thermal magnetic trip units above 200A. All thermal magnetic trip units
shall be calibrated to 50 Deg C.
F. Above 250A, trip units should be electronic type. All electronic trip units shall be fitted
with thermal memory.
G. The moulded-case circuit breakers shall be designed for vertical, horizontal, flat
mounting and reverse feed without any reduction in performance. For a MCCB rating
frame given , MCCBs dimensions shall be the same whatever the ultimate breaking
capacity.
H. All molded-case circuit breakers shall provide double insulation of the front face to allow
on-site installation of auxiliaries without de-energising the installation. It shall be possible
to use the same field installable auxiliary contacts for signalizing different functions, as:
open/ closed position, fault signal, electrical fault (including electrical leakage) signal.
I. All electrical auxiliaries and accessories of MCCBs such as voltage releases, (shunt or
undervoltage type) and auxiliary contacts shall be designed for easy on-site installation.
All electrical auxiliaries shall be equipped with terminal blocks and shall be of the snap -
in type. Auxiliary location and function shall be clearly identified inside the MCCBs.
J. The addition of auxiliaries shall not increase the volume of the circuit breaker. The
addition of a motor mechanism module or a rotary handle, etc., shall not mask or block
device settings.
K. The operating mechanism of the moulded-case circuit breakers shall be of the fast make
and fast break type. Tripping on a fault shall be mechanically independent of the
operating handle. The operating mechanism shall be of stored energy type only and
designed to operate all poles of the circuit breaker simultaneously for making, breaking
and tripping.
L. The moulded-case circuit breakers shall be actuated by a handle that clearly indicates
the three fundamental positions: ON, OFF and TRIPPED.
M. When required, the circuit breaker shall be equipped with a rotary handle, In order to
ensure suitability for isolation complying with IEC 60947- 1 & 2, the operating
mechanism shall be designed in such a way that the position of the operating handle of
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical Specification Switchboard 16441/9
the circuit breaker indicates the real position of the main contacts, even if the circuit
breaker is equipped with a rotary handle.
N. MCCBs shall comprise a device, designed to trip the circuit-breaker in the event of high-
value short-circuit currents. This device shall be independent of the thermal magnetic or
electronic trip unit. The breaking should be carried out in less than 10ms for short-circuit
currents above 25 times rated current.
O. MCCBs shall be designed to prevent access to live parts when the cover is removed. It
shall be equipped with a push to trip button in front to test operation and the opening of
the poles.
P. All MCCBs frame rating higher than 250 A, shall be fitted with metallic filters to reduce
effects perceptible from the outside during current interruption.
Q. Category A MCCBs breaking unit shall be made with a double rotary contact to greatly
limit let through energy on the installation. The electrical durability of MCCBs, as defined
by IEC 60947-2 standard, shall be at least equal to 3 times the minimum required by the
standard.
R. The addition of an add-on earth leakage module shall not change MCCB accessories or
options possibilities.
S. The protection functions shall be provided by a trip unit powered by current transformers
located within the case. For safety reason, In electronic trip units, protection functions
shall be electronically managed independently of measurement and communication
function by a dedicated ASIC. It shall be possible to adjust the long time protection with
a knob without any additional power supply or when the main is off. The operation of the
tripping mechanism shall require no external power source.
T. The trip unit shall be interchangeable at site without removing breaker from panel for
adaptation to changes in the installation. All trip units shall have sealable transparent
cover to avoid any unintentional change to setting.
U. Sensors shall be of the Rogosky type current transformers for accurate current
measurements. The trip unit shall measure the true rms value of the current.
Measurement chain shall be independent from the protection chain.
W. Electronic trip units for category A MCCBs shall have settings and indications as follows:
1. Long-time (LT) protection with an adjustable current setting of 40% to 100%. It
shall be in steps of 10 percent between 40% to 90% and multiple settings
between 90% to 100% for precise setting;
2. Short-time (ST) protection with an adjustable pick-up between 1.5 to 10 times
LT and time delay.
3. Earth-fault protection (where required) with an adjustable pick-up and time
delay shall be provided which will be added to MCCB.
4. From 90% to 105% load (with respect to the long-time setting), an orange LED
shall be illuminated.
5. Above 105%, the orange LED shall flash.
X. Electronic trip units for category B MCCBs shall be same as of ACBs specified in this
section but shall have at least ammeter in-built as standard.
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical Specification Switchboard 16441/10
Y. Wherever other non tariff electrical parameters like Current, Voltage, Frequency, Active
power (kW), active demand power (kWh), reactive power (kVARh), apparent power
(kVAh), minimum & maximum demand values etc, are required, these parameters shall
be provided by the trip unit itself without any external CT. These readings shall be
communicable from the circuit breaker to building management system or other systems
for achieving energy efficiency.
A. Current operated earth leakage relays shall be used either in conjunction with circuit
breakers for tripping the breakers or for giving alarm signal only by an indicator lamp
and alarm bell in cases of earth leakage as shown in drawings.
B. The relays shall comply with IEC 60947-2 annex M or corresponding standards in force
in the IEC member countries (BS EN 60947-2, NF EN 60947-2). The relays shall be of
solid state type. The relays shall be protected against nuisance tripping (transient
currents or overloads caused by switching surges or by lightning surges, especially,
concerning the overvoltage withstand, the sensors shall comply with IEC 60664 -1 for
overvoltage category IV for up to 1000 V electrical network to allow their installation to
be safe on any LV network.
C. Furthermore the relays shall be of class II on front face according to IEC 60664 -1.
Concerning the EMC withstand, the relays shall comply with the IEC 60947 -2 annex M
requirements and be tested for immunity according to the IEC 60000 -4-1 to 4-6
standards.
D. Test certificates shall be provided to validate these tests. The relays shall be insensible
to no dangerous fault currents with harmonics even if these are higher than the setting
threshold. The relay-tripping curve according to the frequency shall comply with the
safety requirements given by the IEC 60479 standard.
E. The relays and sensor shall be able to operate in the presence of fault currents with
pulsating DC components: they shall be of class A according to the IEC 60755 and IEC
60947-2 annex M classification. The earth leakage relays shall consist of a core balance
current transformer and a trip coil.
F. All components shall be enclosed in a casing of moulded plastic. A reset button shall be
G. The manufacturer shall offer as standard ranges of associated sensors that are either
toroidal transformer of closed type with an inside diameter of 30 to 200 ms or toroidal
transformer of the open type of 45 to 110 mm. The sensors shall be in insulated
thermoplastic case. The relays could be also connected to rectangular sensor
specifically designed for measurement on busbars. The relays shall be equipped with
one changeover fail safe output contact without latching for the prealarm setting. The
relays shall be equipped with local indication using LEDs: Green = power supply; red =
prealarm ; red = alarm.
A. Isolators and switch fuses where mounted individually shall be of sheet steel
construction with doors and front operated door interlock handles. The enclosure
fabricated from rust protected sheet steel (EGI), black steel will not approved, in grey
stoved paint finish, with removable top and bottom gland plate and gasketed door. The
interiors of fuse switches shall be porcelian bases fitted with non ferrous conducting
components. Isolators & Switchfuses shall be of quick make and quick break type with
door interlocks and ON/OFF indicators.
B. The Isolators up to 80A TPN rating shall be in metal clad or polycorbonate and above
80A shall be all in metal clad boxes. They shall have a ample space between gland
plate and terminals for easy cable termination, to suit bending radius of cables and an
option for extension boxes to meet bigger cables connections shall be available from the
manufacturer.
C. Disconnect switches and isolators shall comply to IEC 60947-3. Disconnect switch
mechanism shall be of quick make & quick break type rated for AC22A and AC23A.
D. Isolators enclosures shall be IP55 as standard & where fixed in plant room, they shall
have IP65 degree of protection complying to IEC 60529. Isolators shall have rated
operational voltage upto 690V, rated insulation Voltage shall be upto 750V and current
ratings shall be as in BOQ or drawings.
E. Complete enclosed isolator assembly shall be type tested at third party test lab like
ASTA, LOVAG or KEMA.
F. Isolators and switch fuses shall be single or triple pole with n eutral, of ratings as
indicated on the drawings and provided with earth terminals. The switch fuses shall be
suitable for HRC type fuses of class QI to BS88.
A. The main and sub-main distribution boards shall be totally enclosed, dust protected and
factory fabricated same as MLTB but in Form 2b construction. They shall have minimum
IP42 protection and IP54 for those installed in mechanical rooms in accordance with IEC
60529.
B. Main and sub-main distribution boards shall comprise of main incoming isolator,
busbars, moulded case circuit breakers, earth leakage relays, earth bus etc., with
ratings and arrangements as shown on the drawings.
C. The busbars shall be electrolytic high conductivity copper bars type Cu ETP as defined
by standards ISO 1190-1 with ratings as indicated on the Drawings for the three phases
and neutral. The busbars shall be arranged and marked to the approval of the Engineer
in compliance with type tested design according to IEC 61439 1 & 2. It shall be 99.9%
purity HDHC copper.
D. The components (moulded case circuit breakers and earth leakage relays etc.) shall be
as specified herein before. All MCCBs shall have adjustable thermal and adjustable
magnetic trip settings.
E. The earth bus shall have adequate rating, termination bolts and length for connecting
the incoming and outgoing earth cables.
F. The main and sub-main distribution boards shall be complete with all necessary internal
wiring and connections.
G. The arrangement of the boards shall be such that the main incomer and outgoing
breakers can be operated when opening the door but to gain access to the MCCBs
settings, cabling and terminations a second cover should be removed. There shall be
ample clearance, space and cable supports inside the boards for cabling and
terminations. Adequate clearance shall be maintained between phases, non-current
carrying metal and terminals shall be so located that in the final connected positions
there shall be no crowding of wires in close proximity of metal.
H. The boards shall be complete with cable glands for convenient terminations of incoming
and outgoing cables.
A. Ammeters: Complying with IEC 60051; direct-reading, full range, indicating ammeter
with 96 mm square recessed case, white dial with black figures and pointer, x/5A
ampere, 1.5% accuracy including current transformers. Where communication of
electrical data is required, these readings shall be in built in the trip unit of the circuit
breaker with communication module.
B. Voltmeters: Complying with IEC 60051; direct-reading, full range, indicating voltmeter
with 96 mm square recessed case, white dial with black figures and pointer, 500 volt
FSD, 50 Hertz movement, 0.5% accuracy. Where communication of electrical data is
required, these readings shall be in built in the trip unit of the circuit breaker with
communication module.
A. Voltmeter selector Switch: Rotary multistage snap-action type with 600 volt AC silver
plated contacts, engraved escutcheon plate, oval type handle, and seven positions
including OFF.
A. Kilo Watt-hour Meters: KWhr meter for ADDC metering shall be suitable for operation on
415/240V, 3Phase, 4 wire, 50Hz. System. It shall be absolutely dust and vermin proof,
protected from corrosion due to high humidity and compensated against the effect of
temperature upto 55 deg C.
B. The meter shall maintain their accuracy over many years of service under UAE climatic
conditions. The counters shall be of the cycle-meter type with six digits and shall give a
direct reading of power consumption to six figures, the lowest figure being units and not
tenth of units. Pointer type counters are not acceptable. Multiplying factors shall not be
used except for the larger size of CT operated meters, where 10 and 100 may be used.
C. The calibrating adjustments shall be operated by screw driver only. The meter cover and
cases shall be of metal and not plastic. The ratings for direct connected whole current
meters shall be 50, 75 and 125amperes maximum per phase and terminals holes shall
not be less than 6, 9 or 12mm diameter respectively. Higher rating meters shall have not
less than 5mm diameter terminal holes and shall be operated through current
transformer with 5 amperes rating to the secondary side and the counter or the meter
shall be calibrated to read the primary KWh passing through the current transformers.
D. The current transformers shall be of ring or slide on busbar type. Three current
transformers of the following sizes shall be provided for each meter. 200/5, 400/5,
800/5, 1000/5, 1500/5, 2000/5 or to ADDC & other local Authorities approval. All meters
shall be handed over to ADDC for calibration before final erection and connection.
A. Current Transformers: IEC 60044-1, 5A ampere secondary, wound type, with double
secondary winding and secondary shorting device, primary/secondary ratio as indicated
on Drawings, burden and accuracy consistent with connected metering and relay
devices, 50 Hertz.
2.15 ACCESSORIES
A. Circuit Breaker Lifting Device: Floor supported, lifting trolley, shall be provided for
assisting in lifting of draw-out circuit breakers in switchboard.
A. Furnish shop inspection and testing in accordance with IEC 61439 1 & 2.
PART 3 EXECUTION
3.1 EXAMINATION
Certificate for evidence of the complete type test of the switchboard with reference to IEC 61438- 1 &
2 , to be submitted , the type-test certificates shall be originated by a worldwide known third-party
certification organization such as ASTA, KEMA, ACAE, CESI, ASEFA, PEHLA, CEBEC, SEMKO.
Certificates from Laboratories not certified under LOVAG will not be acceptable
3.2 INSTALLATION
B. Tighten accessible bus connections and mechanical fasteners after placing switchboard
to required torque as in manufacturers installation manual. The bolts shall be marked
after checking the torque.
C. Install fuses in each switch and coordinate sizes with connected load.
3.4 ADJUSTING
D. Adjust circuit breaker trip and time delay settings to values as per co-ordination study.
3.5 CLEANING
PANEL BOARDS
PART 1 GENERAL
1.1 SUMMARY
A. Section includes distribution and branch circuit panel boards, electronic grade branch
circuit panel boards, Miniature circuit Breaker, Residual current circuit breaker, RCBO,
surge arrestor, automatic re-closure for breakers and circuit breaker with integrated
operating mechanism.
B. Related Sections:
1.2 REFERENCES
The switchboards shall comply with the following standards as appropriate. Where no
regulation / standards are mentioned, latest IEC standards shall be applicable:
B. IEC 61439-2: LV Switchgear & Control Gear Assemblies Power Switchgear and
Controlgear Assemblies
J. IEC 61008: Residual Current Operated Circuit breakers without integral over current
protection (RCCB).
K. IEC 61009: Residual Current Operated Circuit breakers with integral over current
protection (RCBO)
M. IEC 60269: Specification for Cartridge Fuses for voltage upto and including 1000V
A.C. and 1500V D.C.
1.3 SUBMITTALS
B. Shop Drawings: Indicate outline and support point dimensions, voltage, main bus
ampacity, integrated short circuit ampere rating, circuit breaker and fusible switch
arrangement and sizes.
C. Product Data: Submit catalog data showing specified features of standard products.
A. Project Record Documents: Record actual locations of panel boards and record actual
circuiting arrangements.
B. Operation and Maintenance Data: Submit spare parts listing; source and current prices
of replacement parts and supplies; and recommended maintenance procedures and
intervals.
1.5 QUALIFICATIONS
A. Furnish two set of hard copy and a soft copy of complete as built drawings.
A. General: Furnish extra materials, matching products installed (as described below).
packaging with protective covering for storage, and identifying with labels clearly
describing contents.
B. Miniature circuit breakers / ELCB: Furnish quantity equal to 5 percent of the number
breaker installed , but not less than 5.
C. Others: Furnish quantity equal to 5 percent of the number other components installed
which has long lead delivery time, but not less than 3 each type and rating.
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical Specification Panel Boards
16442/5
PART 2 PRODUCTS
A. Manufacturers
All the switchboards, panel boards and all components shall be from the same
manufacture to maintain the best cost/performance ratio between continuity of
supply and safety, to ensure discrimination, proper protection, full co -ordinations
and easy substitution.
1. ABB , Germany
2. Merlin Gerin , France
3. Schneider Electric, Europe
4. Dorman Smith, UK
5. Marlin Gerin, France
D. Panel boards shall be 3 phase , 4 wires suitable for ratings of main and outgoing
feeders as shown on the drawings and schedules.
E. Enclosures shall provide Class II total insulation as per IEC / BS EN 61439-3, section
7.4.3.2 between outer space and all live components inside. The arrangement of the
enclosure shall be such that the MCBs and RCCB., cannot be operated without
opening the hinged door however, access to the inside of the enclosure for maintenance
purposes or cabling shall be possible by removing the inner dead front / cover..
F. Construction: Dead front construction and separation to IEC-61439-3 . Type tests shall
be certified by an Independent Certification Body / Testing Laboratory (KEMA / DEKRA).
The metal enclosure of the distribution board shall be made of electro galvanized steel
sheet metal thickness of 1.2mm and shall have received an anti-corrosion coating (hot
polymerized polyester/epoxy powder).
G. The complete busbar type distribution boards must have been tested for 50 deg ambient
temperature rise tests with natural ventilation. For enclosures supplying Retail shops or
flats, access to devices shall be protected by a door with sliding type plastic catch locks.
H. Cable entry to enclosures shall be possible for flexible conduits or insulated cables, from
both top and bottom of the enclosure. For cable running in the enclosure, adequate
clearance shall be available on either side of the outgoing breakers (gutter space).
J. The main copper busbar used in the pan assembly must be of high grade copper with
tin plating and the busbar supports must be made of high quality plastic material of ploy
carbonate with 25% fibre content to provide very high strength to with stand higher lever
of short circuit current withstand capabilities. The busbar support plastic materials must
have been type tested as per IEC 61439-2: resistance to corrosion (severity test A
indoor) : verification to resistance of insulating materials to normal heat ( 125 degrees)
and also abnormal heat ( 960 degrees) and fire due to internal electric effects as per
IEC 60695-10-2 standard.
K. Earth and earth/neutral terminal blocks in enclosures shall comply with standard IEC
61439-3. It shall be possible to install the earth and earth/neutral terminal blocks and
distribution devices either at the top or bottom of enclosures, near the incoming cables.
L. Terminal blocks shall be designed to secure cables in compliance with standards IEC
60947-1, section 8.2.4, IEC 60998-1 and IEC 60998-2-1. For cable cross-sections up to
6 mm (rigid or flexible without ferrules), cable connection shall not require tightening by
the installer. Terminal-block extensions, e.g. for installation modifications, must be easy
to add and dependable. The connection between earth and neutral terminal blo cks must
be rigid and removable only using a tool.
M. It must be possible to install flush-mount enclosures without use of mortar. The front
panels shall be perfectly seated, even if the rear part (flush-mount case) is imperfectly
set or if the wall is irregular at the point of installation.
N. The colour of the enclosures shall be RAL9002 mat finished grey and shall be possible
for users to personalize doors without risk of touching live parts (non -transparent,
transparent, images, wall paper, etc.).
P. The boards shall be recess type unless indicated otherwise on the Drawings. Cable
glands shall be provided where required.
A. All Protective devices (Main incoming switches or incoming circuit breakers, Surge
arresters , Residual current device and Miniature circuit breakers) shall be of the
modular type (DIN profile). Plug on type will not be acceptable.
B. ELCBs and MCBs must be capable of heavy-duty operation and to that end, the
manufacturer shall guarantee the following performance levels, defined by IEC / EN
60947-2 standards.
1. suitability for isolation (section 7.2.7)
2. rated insulation voltage (section 4.3.1.2) : 500 V
3. pollution degree (Part 1, section 6.1.3.2) : 3
4. rated impulse-withstand voltage (section 4.3.1.3) : 6 kV
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical Specification Panel Boards
16442/7
C. To ensure the longest possible service life, switching mechanisms shall be designed to
make the contact-closing speed totally independent of the operators action.
D. Contact positions shall be clearly indicated on the front of devices and marked. "I - ON",
standing for device contacts closed, circuit energized, "O - OFF" with a green
background , standing for device contacts open, circuit disconnected and shall provide a
differentiated indication, enabling to identify the reason for an OFF position : manual
operation or fault-driven trip
E. For safety of non-skilled users, accessible parts of the devices, when in a suitable
enclosure, shall feature insulation class II as per IEC 60364 and degree of protection
IP40 as per IEC 60529.
A. Miniature Circuit breakers shall comply with international standards IEC 60898 and IEC
60947-2 / European standard EN 60898 and EN 60947-2. Compliance with these
standards shall be certified by the VDE organization and its quality mark shall be visible
on the devices.
B. MCB shall provide circuits against short circuit and over load currents. It shall be
suitable for isolation according to IEC 60947-2 and have fault trip indication by a red
mechanical indicator on the front face. It shall have various add on electrical
accessories like shunt trip, under voltage relay, auxiliary contact for signaling the status
of breaker. These accessories shall be common for the complete range of products.
C. Where required, MCBs shall be possible to be pad locked. There shall be large circuit
labeling area for identification and terminals shall be IP20 to IEC 60529.
D. For each device, the characteristics shall be indicated on the single-line diagram or
schedule. The specified values of breaking capacity shall be also be valid in case of
short circuit between phase and protective earth (Icn1). If not specified on the diagram,
the breaking capacity shall be 10kA minimum as per IEC 60497-2 at 240Vac (Phase to
neutral) or 415 Vac (Phase to Phase).
E. All MCBs shall be calibrated to 50 Deg C without derating of the thermal protection
current rating. MCB dollies shall be of the trip free pattern to prevent closing the breaker
on a fault
F. MCBs should be available from 0.5 to 125A, in B, C and D curves and in 1,2,3 and 4
pole version. Where not specified the breaker shall be of C curve.
G. MCBs shall be so arranged in the board that it shall be possible to replace a triple pole
M.C.B. with three adjacent single pole MCBs or vice versa.
A. RCCBs shall comply with international standard IEC 61008 / European standard EN
61008. Compliance with the standard shall be certified by the VDE organization and its
quality mark shall be visible on the devices.
D. The rated conditional short-circuit currents (Inc et Ic, sections 5.4.2 and 5.4.3) shall be
greater than or equal to the prospective short-circuit current at the point of installation
(Isc as per IEC 60364). The manufacturer shall guarantee these values do not differ
from the rated breaking capacity of the circuit breaker providing short-circuit protection
of the RCCB.
E. RCCBs located upstream of the following loads shall have a reinforced level of
performance to restrict power outages to the strict minimum required for user safety:
1. sets of fluorescent lighting, halogen lighting supplied with LV or ELV power
2. groups of PCs and work stations,
3. motors driven by single-phase variable-speed drives, etc.
F. The reinforcement in performance means that the RCCB shall not trip in the following
situations:
1. continuous 1 kHz leakage current, 8 times higher than the rated tripping
threshold (as per IEC 60479-1)
2. leakage currents and transient overvoltages due to lightning strikes, switching,
decoupling capacitance discharges, etc.:
5 kV peak voltage for a 1.2/50 s wave (IEC/EN 61000-4-5),
5 k leakage current for an 8/20 s wave (IEC/EN 61008),
400 leakage current for a damped sinusoidal 0.5 s / 100 kHz ring
wave (IEC/EN 61008),
residual current equal to 5 times the rated residual operating current for a
duration less than or equal to 10 ms,
very high-frequency inducted or conducted disturbances (starting at 150
kHz).
G. The RCCBs must trip for fault currents with a DC component as per type A as per IEC
60755. The same is required of residual current devices located downstream of UPSs.
RCCBs protecting three-phase variable-speed drives shall be type B as per IEC 60755.
2.5 RCBO
A. The modular RCBOs shall be of the type that snap onto 35 mm symmetrical rails, but
shall also provide the option of surface mounting. The snap-on system shall be of the
bistable type to allow the modular RCBO to be mounted and removed using an ordinary
screw driver. The RCBO casing shall be made of self-extinguishing, tropicalized
material.
B. RCBOs shall be suitable for use at frequencies of 50/60 Hz. A toggle shall be used for
manual opening and closing. It shall be equipped with a free tripping mechanisms. The
devices shall include a mechanical device that guarantees contact closing speed that is
independent of operator speed. Each auxiliary function may be added to the modular
RCBO by simply snapping it on mechanically
C. RCBOs shall be delivered with the screw terminals opened to the maximum. RCBO and
auxiliary functions shall form a self-contained unit held on the 35 mm symmetrical rail by
the modular RCBO bistable snap-on system.
E. RCBOs shall be self contained residual current device carries out complete protection
for final circuits. It shall protect against short circuit, overload and protection against
electric shock depending on the sensitivity selected. The phase pole shall be protected
against overloads by a bimetal strip mechanism. The modular RCBOs shall have a high
limiting capacity (class 3) so as to reduce thermal stress on to the protected cables. The
modular RCBOs shall be of the "voltage-dependant" type in compliance with the IEC
61009-1 standard. It should incorporate an additional power supply between the phase
and the PE conductor for additional safety in use.
F. The electrical and mechanical endurance of the modular RCBOs shall be higher than
those stipulated in the standard. The breaking capacity of the modular RCBOs shall be
no less than 10kA and greater than or equal to the prospective fault level at the location
in the distribution system in which the RCBO is installed. By design, the manufacturer's
range of modular RCBOs shall meet the requirements for cascading of modular RCBO s
according to an explicit chart in order to optimize the cost of the installation.
G. RCBO shall be available in 1P & 2P versions with various current ratings upto 45A.
Sensitivities available shall be 10mA, 30mA & 100mA. The sensitivity thresholds shall
be of the non user-adjustable type by construction. The breaking capacity Im shall be
75% of rated breaking capacity (Icn).
H. The RCBOs shall be suitable for use between 50V and 253V AC. The test button shall
also be suitable for such voltages. It shall be protected against nuisance tripping by a
protective device, limiting such tripping to a peak value of 250A according to the 8/20
wave for all the range.
I. RCBOs shall be of the positive contact indication type. Indication shall be provided by
the toggle of RCBO. When the device is in the "Open" position, a green zone appears. It
shall provide a differentiated indication, enabling to identify the reason for an open
position : manual operation or fault-driven trip.
J. Under loss of neutral supply conditions the residual current element of the device will
continue to provide earth-leakage protection. With these conditions and upon detection
of an earth-leakage current, the rcbo should operate within its normal characteristics.
Under loss of both the neutral supply and the PE conductor connection, the device shall
automatically trip as earth-leakage protection is no longer provided. Under reverse
polarity conditions, the modular rcbos shall automatically trip as automatic tripping of
the phase conductor in case of fault is no longer provided.
B. Therefore, final distribution switchboard shall embed a surge arrester compliant with IEC
61643-1 / EN 61643-11 standard. Compliance shall be proved by NF quality label
printed on the device.
C. The surge arrester, type 2 according to IEC 61643-1 / EN 61643-11 will limit voltage to
never exceed:
1. 1,4 kV live to earth
2. 1,0 kV phase to neutral.
F. The surge arrester shall be associated with a dedicated disconnector, the opening of
which will not disturb or turn off power supply to any downstream located load. This
disconnector will be made of a circuit-breaker, compliant with IEC 60898 standard.
Coordination between circuit-breaker and surge arrester, according to 6.2.7. of above
standard, will have be certified by the breaker manufacturer.
G. Disconnecting circuit-breaker shall be integrated with the surge arrester: in case of trip,
it will be possible to reset it only once all required cartridges have been replaced.
A. Compliance standards:
Number Title Use
EN 50557 Automatic reclosing devices Standard for reclosing devices
EN /IEC 61131- Programmable controllers
2 Equipment requirements and tests
EN /IEC 60947 Protection in industrial Degree of pollution 3
environments
EN /IEC 60068 Environmental tests Salt mist resistance
IEC/EN 61000 Electromagnetic compatibility Immunity tests:
(EMC)
4 - 2: electrostatic discharges
4 -3: radiated electromagnetic
fields
4 4: fast transient/burst
4 -5: surges
4 6: conducted magnetic fields
4 8: power frequency magnetic
fields
4 9: pulse magnetic fields
4 11: voltage dips
4 13: harmonics
4 28: variations of power
frequency
IEC 60695 2 10 (and 11): Fire resistance
IEC 60721 Resistance to corrosive
environments
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical Specification Panel Boards
16442/11
B. Provide automatic reclosing device which improves the availability of installations that
are unsupervised, isolated and/or difficult to access and need to be restarted without
any action by personnel when transient or permanent faults occur where indicated.
C. The protection devices MCBs or MCBs along with vigi add on RCD shall be equipped
with automatic recloser auxiliaries to reset the circuits following such faults (e.g.
lightning strike, temporary leakage current due to humidity, etc.).
D. Technical Characteristics:
1. The reclosing device shall be an auxiliary available for 1P, 1P+N 2P, 3P or 4P
circuit breakers, equipped or not with an earth leakage protection auxiliary and
2P or 4P RCCBs.
2. Supply voltage: 230 V AC (50 Hz),
3. Control voltage: 230 V AC (50 Hz),
4. Insulation voltage: 400 V AC (50Hz)
5. Degree of pollution: 3
6. Impulse withstand voltage: 6 kV
7. Operation at ambient temperature: -25C to +60C
8. Tropicalization: treatment 2 for 40C, 93% relative humidity
E. The operator can choose between several possible predefined reclosing programs
which reconcile installation safety and availability. Each program defines
1. Authorized number of reclosing operations
2. Wait time before reclosing
3. Control time after reclosing.
F. The maximum number of automatic reclosing operations shall be between 1 and 5 for
circuit breakers with Vigi module and Between 1 and 15 for RCCBs. Similarly, There is a
minimum time between protection device tripping and the automatic reclosing attempt
which shall be 1 minute for circuit breakers with Vigi and 20 seconds for RCCBs.
G. For transient faults, the recloser auxiliary will automatically reset the circuit breaker.
After the authorized maximum number of reclosing operations, if the fault is still present,
the device will be disabled. A final remote reset operation is then permitted. If the final
remote reset attempt fails, on-site intervention by an operator will be necessary to reset
the device.
H. In the event of a permanent fault on a circuit breaker protection device, the circuit
breaker will immediately trip after the automatic reset attempt. The auxiliary will
immediately be disabled regardless of the remaining number of authorized reclosing
operations. When this is the case, final remote reclosing should not be authorized.
I. Protection devices with automatic reclosing shall be equipped with indicators that signal
operating status:
1. Normal operation
2. reclosing cycle in progress
3. cycle completed and fault still present, product locked out
4. product disabled manually
The last two statuses (locked out and disabled) may also be indicated remotely by
means of a dry contact
J. They shall include a contact that can remotely indicate, at any time, the status of the
circuit protection device (open/closed and may also be equipped with a remote
indication auxiliary that makes a distinction between tripping and manual opening.
M. Production site organization shall comply with the requirements of the ISO 9002 and
ISO 14001 standards. Protection devices with automatic resetting shall be designed
according to the eco-design principles defined by ISO 14062. IN particular, they shall
not include first-generation halogenated flame retardants. They shall be delivered in
recyclable packaging compliant with European directives; the manufacturer shall
implement non-polluting manufacturing processes; no use of chloro/fluorocarbons or ink
chlorinated hydrocarbons for package marking. The automatic recloser auxiliary shall
come with an environmental profile data sheet explaining end-of-life management.
A. Where indicated, provide circuit breaker with integrated operating mechanism shall
include the following main functions in a single device.
1. Circuit protection against short-circuit current
2. Circuit protection against overload current
3. Isolation in the tertiary and industrial sectors
4. A remote control mechanism for remote opening and closing of circuits.
B. The circuit breaker will be manually reset after tripping by means of the device toggle.
The device shall enable the circuit to be secured by padlocking.
C. Compliance standards: The circuit breaker with integrated operating mechanism shall
comply with the following standards and have successfully passed the tests stipulated
therein
D.
Number Title Use
IEC/EN 60529 Degree of protection Device alone IP20
Control Circuit:
1. Supply voltage (Ue): 230 V AC (50Hz)
2. Control voltage (Uc): 230 V AC/ 24 V DC
3. Minimum control pulse time >= 200 ms
4. Response time <= 200 ms
5. Power consumption <= 1 W
6. Inrush power consumption < 1000 VA
7. Electrical endurance: up to 50 000 cycles.
Power Circuit:
1. Max. operating voltage (Ue): 400 V AC (50Hz)
2. Insulation voltage (Ui): 500V
3. Impulse withstand voltage: 6 kV is disconnected position
4. Magnetic tripping: B, C and D curves
5. Degree of pollution: 3
6. Operation at ambient temperature: -25C to +60C
G. The orders received via the different control points shall be processed as they arrive, in
the order in which they arrive. The circuit breaker with integrated operating mechanism
shall have an operating mode that allows disabling of local pulse-type control. For circuit
breakers with an integrated 24 V DC operating mechanism, the product shall have an
operating mode that allows disabling of centralized latched-type control.
H. The circuit breaker with integrated operating mechanism shall include an auxiliary
contact that can remotely indicate, at any time, the status of the protection circuit
(disconnected/open) and the status of the control circuit (open/closed). It shall be
equipped with an operating status indicator:
1. Circuit disconnected: remote control impossible
2. Circuit open but not disconnected: remote control possible,
3. Circuit closed: remote control possible
I. The circuit breaker with integrated operating mechanism shall be equipped with a circuit
isolation mechanism, capable of being locked out by padlocking. It shall not change
status in the event of a power failure It shall also allow Isolation of the circuit breaker by
the toggle and Local control of the electrical circuit by an open/close button
J. Production site organization shall comply with the requirements of the ISO 9002 and
ISO 14001 standards. The circuit breakers with integrated operating mechanism shall
be designed according to the eco-design principles defined by ISO 14062. They shall
comply with the RoHS and Reach standards. They shall be delivered in recyclable
packaging compliant with European directives; the manufacturer shall implement non -
polluting manufacturing processes; no use of chloro/fluorocarbons or ink chlorinated
hydrocarbons for package marking. It shall come with an environmental profile data
sheet and an end-of-life data sheet.
3.1 INSTALLATION
A. Install panel boards in accordance with IEC 61439 standards and manufacturers
recommendation."
F. Provide typed circuit directory for each branch circuit panel board. Revise directory to
reflect circuiting changes to balance phase loads.
H. Ground and bond panel board enclosure . Connect equipment ground bars of
panels.
3.3 ADJUSTING
B. Measure steady state load currents at each panel board feeder; rearrange circuits in
panel board to balance phase loads to within 10 percent of each other. Maintain proper
phasing for multi-wire branch circuits.
FUSES
PART 1 GENERAL
1.1 SUMMARY
1.2 REFERENCES
1.3 SUBMITTALS
B. Product Data: Submit data sheets showing electrical characteristics, including time -
current curves.
B. Project Record Documents: Record actual sizes, ratings, and locations of fuses.
1.5 QUALIFICATIONS
B. Furnish two spare fuses of each Class, size, and rating installed.
2.1 FUSES
A. Manufacturers:
1. MEM Co.
2. Merlin Gerin Co.
3. Siemens Co., Germany.
Or equal approved
by the Engineer.
PART 3 EXECUTION
3.1 INSTALLATION
A. Install fuse with label oriented so manufacturer, type, and size are
easily read.
TRANSFER SWITCHES
PART 1 - GENERAL
1.01 SUMMARY
A. This Section includes transfer switches rated 600 V and less and the
following items:
2. Bypass/isolation switch.
1.02 SUBMITTALS
F. Field Test Reports: Indicate and interpret test results for compliance
with performance requirements.
D. Standards :
1. Comply with ISO 3046 and relevant IEC standards or equal and the
followings .
2.01 MANUFACTURERS
e. Group Schneider .
b. Group Schneider .
c. ABB.
d. ASCO
2. Units 600 Amperes and larger have current ratings that apply to
mixtures of loads including 30- percent tungsten filament lamp
load .
I. Factory Wiring: Train and bundle factory wiring and label consistent
with Shop Drawings, by color code numbered or lettered wire and
cable tape markers at termination.
It shall be possible to feed the loads from either sources at any time
by programming or manually.
A. Comply with the requirements of IEC 947 and or NFPA 110 for non -
automatic transfer switches.
2. Switch position.
PART 3 - EXECUTION
3.01 INSTALLATION
3.03 CONNECTIONS
B. Field Tests: Give 7 days' advance notice of tests and perform tests
in presence of Owner's representative.
INTERIOR LUMINAIRES
PART 1 GENERAL
1.1 SUMMARY
B. Related Sections:
1. - Luminous Ceiling.
2. - Integrated Ceilings.
1.2 REFERENCES
B. ANSI C82.4 - Ballasts for High-Intensity Discharge and Low Pressure Sodium
Lamps (Multiple Supply Type).
1.3 SUBMITTALS
B. Shop Drawings: Indicate dimensions and components for each luminaire not
standard product of manufacturer.
1.4 QUALIFICATIONS
1.5 MOCK-UP
B. Light fitting : Furnish quantity equal to 5 percent of the number of light fitting
installed , but not less than two for each type .
A. Manufacturers
1. Targetti, Italy
2. Reggiani, Italy
3. Wila, Germany
4. We-Ef , Germany
5. Erco, Germany
6. Thorn, England
7. Sunlux, France
8. Philips holland only
Or as shown on the drawing. (any equivalents are not allowed)
D. Lamps: fluorescent.
G. Test Switch: Transfers unit from external power supply to internal battery supply.
H. Lamps: Fluorescent.
3.1 INSTALLATION
A. Install suspended luminaires using pendants supported from swivel hangers. Install
pendant length required to suspend luminaire at indicated height.
B. Support luminaires larger than 600 x 1200 mm size independent of ceiling framing.
D. Install surface mounted luminaires plumb and adjust to align with building lines and
with each other. Secure to prevent movement.
K. Connect luminaires to branch circuit outlets provided under Section 16130 using
flexible conduit.
L. Make wiring connections to branch circuit using building wire with insulation suitable
for temperature conditions within luminaire.
B. Operate each luminaire after installation and connection. Inspect for proper
connection and operation.
3.3 ADJUSTING
Completion.
Section 16620 / 1
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical W orks Specifications Package Engine Generator Set
SECTION EL-16
PART 1 - GENERAL
1.02 SUMMARY
3. Earthing as in division 16 .
1.03 DEFINITIONS
Section 16620 / 2
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical W orks Specifications Package Engine Generator Set
1.04 SYSTEM DESCRIPTION
1.05 SUBMITTALS
Section 16620 / 3
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical W orks Specifications Package Engine Generator Set
D. Shop Drawings: Detail fabrication, piping, wiring, and installation of
the field-installed portions of the system. Include general
arrangement drawings showing locations of auxiliary components in
relation to the engine generator set and duct, piping, and wiring
connections between the generator set and the auxiliary equipment.
Show connections, mounting, and support provisions and access and
working space requirements. Provide foundation drawings, indicating
size and location of fixing details.
3. Remote Radiator.
4. Load Banks.
Section 16620 / 4
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical W orks Specifications Package Engine Generator Set
M. Design and Guaranteed Performance data : Submit design data for
engine , generator and accessories in standard format including but
not limited to the following :
Section 16620 / 5
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical W orks Specifications Package Engine Generator Set
1.07 DELIVERY, STORAGE, AND HANDLING
1. Fuses: 3 for every 10 of each type and rating, but not less
than 3 of each.
2. Pilot Lights: 2 for every 6 of each type used, but not less than
2 of each.
5. One complete change of lube oil plus one gallon of make -up
lube oil supplied in unopened containers.
B. Provide one set of all special tools that are required for the normal
operation and maintenance of the engine driven generator unit .
Section 16620 / 6
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical W orks Specifications Package Engine Generator Set
PART 2 - PRODUCTS
2.01 MANUFACTURERS
a. Cummens
2. Storage Batteries:
b. Chloride Systems.
c. Exide Corp.
4. Battery Chargers:
b. Exide Corp.
c. SAFT - NIFE .
d. Onan Corp.
Section 16620 / 7
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical W orks Specifications Package Engine Generator Set
2.02 SYSTEM SERVICE CONDITIONS
Section 16620 / 8
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical W orks Specifications Package Engine Generator Set
D. Steady-State Frequency Operational Bandwidth: 0.5 percent of rated
frequency from no load to full load.
K. Starting Time: Maximum total time period for a cold start, with
ambient temperature at the low end of the specified range, is 5
seconds. Time period includes output voltage and frequency
settlement within specified steady-state bands.
Section 16620 / 9
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical W orks Specifications Package Engine Generator Set
2.05 ENGINE GENERATOR SET
2.06 ENGINE
Section 16620 / 10
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical W orks Specifications Package Engine Generator Set
E. Engine Fuel System: Comply with NFPA 30, "Flammable and
Combustible Liquids." System includes:
Section 16620 / 11
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical W orks Specifications Package Engine Generator Set
2. Actuator Design: Normally-open valves to return to open
position when actuator fails.
Section 16620 / 12
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical W orks Specifications Package Engine Generator Set
not shut down the engine generator set.
Section 16620 / 13
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical W orks Specifications Package Engine Generator Set
2.11 STARTING SYSTEM
Section 16620 / 14
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical W orks Specifications Package Engine Generator Set
constant regardless of input voltage variations up to plus
or minus 10 percent.
Section 16620 / 15
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical W orks Specifications Package Engine Generator Set
1. A.C. Voltmeter with 7-position selector switch 64mm face, 0.5
percent accuracy .
Section 16620 / 16
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical W orks Specifications Package Engine Generator Set
6. Low-Lube Oil Pressure Pre-alarm.
8. Over-crank Shutdown.
Section 16620 / 17
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical W orks Specifications Package Engine Generator Set
enclosure .Put isolation transformer and filters shall be provided to
minimize disturbances caused by line harmonics .
Section 16620 / 18
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical W orks Specifications Package Engine Generator Set
emission. Enclosure framing and skid shall be rigid for lifting the
complete unit via four points lifting provisions. Doors shall be full
gasketed to form a weather tight perimeter seal. Hinges shall be
forged stainless steel with stainless steel pins, handle shall be
stainless steel and pad-lockable.
4. Doublex single phase socket out let 16 Amp rated with ground
fault current interrupter.
2.16 FINISHES
Section 16620 / 19
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical W orks Specifications Package Engine Generator Set
4. Complete System Continuous Operation Test: Includes
nonstop operation for a minimum of 8 hours, including at least 1
hour each at 1/2, 3/4, and full load, and 2 hours at 110 percent
of full load. If unit stops during the 8-hour test, repeat the
complete test. Record the following minimum data at the start
and end of each load run, at 15-minute intervals between those
times, and at 15-minute intervals during the balance of the test:
a. Fuel consumption.
b. Exhaust temperature.
PART 3 - EXECUTION
3.01 INSTALLATION
Section 16620 / 21
Continente Supermarket, Waterfront Mall
Deira, Dubai
Electrical W orks Specifications Package Engine Generator Set
not exceeding those specified in IE / BS standards "rotating
equipment" are acceptable.
3.04 CLEANING
PART 1 : GENERAL
1.1 SUMMARY
1. The Contractor shall Modify and Relocate the existing FACP In the Supermarket area to
the new location as indicated in the drawing.
-acting electronic Analogue SAFE (Software Addressed Firmware Encoded)
Addressable Fire Detection System.
2. The Contractor shall do necessary modification by providing additional smoke detectors/
heat detectors as indicated in the drawing .
3. All works shall be executed after obtaining prior approval client and mall management.
4. Contractors shall prepare shop drawing base on design drawing for Fire Alarm system
and get the approval from authorities.
5. Prior to placing order for any equipment, the contractor shall submit
comprehensive document comprising working drawings, catalogues and
descriptive literature of components, maintenance manuals, etc for engineers
study and approval.
6. The contractor shall be required to train and instruct clients personnel in the
correct use, operation and supervision of the system, preferably prior to the
handling over of the project.
1.2 QUALIFICATION
1. The contractor shall ensure that all system components offered shall be
manufactured by one manufacturer who shall also be on the local fire department
list of approved manufacturers and be established in UAE for a minimum of 5
years. The Contractor shall be responsible for all submittals of complete design
information to Dubai Civil Defense and for obtaining all necessary approval
certificates prior to the commencement of the installation and upon completion.
2. In order to ensure whole site integration capability, the fire alarm system shall be
awarded to a single specialist manufacturer who will be responsible for the design,
global operation, management and interfacing of the system.
2. The system shall be true analogue in operation, with each sensor device providing
signal levels relative to the current operating environment. These analogue
samples shall be transmitted to the control panel in a digital format to reduce
possible corruption. Threshold conditions shall be located using fast -scanning
techniques within a period of 0.5 seconds and 256 data readings shall be taken to
analyse the activity.
3. Addressing of any devices directly connected to the system shall be carried out in
a manner that does not require manual setting of switches in either, the head or the
base. All addressing shall be carried out automatically by the control panel (soft
addressed), additionally the devices can be SAFE addressed (Software Addressed
Firmware Encoded). Each device should incorporate an EE EPROM allowing the
SAFE address to be encoded, this shall be achieved using the control panel SAFE
software function only.
4. All field devices are to be connected to the main control panel directly via 2 wire
loop circuits. Both initiation and annunciation devices to be connected on these
loops in the same manner.
5. The system shall be capable of providing full, fire, fault disablement and
supervisory monitoring facilities.
6. Short or open circuit wiring fault isolation shall be provided via built -in- isolators
every device to protect the system. Field Wiring/Circuit Monitors which
isolate/protect sections of a loop circuit, i.e. a group/zone of field devices are not
acceptable.
2.1 MANUFACTURERS:Existing
2.2.1 GENERAL
1. The control and indicator panel shall be designed to meet the requirements of
BS5839 Part 4 or EN54 Part4.
5. The control panel shall have the capability to be networked with up to 31 panels
in the same network domain via the addition of network cards using industry
standard RS485 and with up to 64 domains using domain bridge cards via
industry standard RS232.
6. All site specific data shall be field programmable and be stored on an integral
RAM card with lithium battery back up. The use of burnt EPROMS to retain
site data in the event of a malfunction shall NOT be permitted.
7. All internal cards shalll be fully monitored, for fault conditions with appropriate
watchdogs to try and assure continuous operation of the system.
8. All relevant information shall be capable of being displayed on the LCD display
and/or printed using the Integral Printer.
16. The system shall operate on the Windows environment. The platform specification
required is an
17. IBM PC compatible with the following minimum specifications.
Pentium Processor
133MHz speed
32MB RAM
500 GB Hard Disk
Minimum 21 super VGA colour screen
Two serial ports and two parallel ports
Real time clock
CD Rom
Microsoft mouse
The combined text and graphics package shall be provided on the same supervisor
1. These devices shall be directly connected to the loop, three variants shall be
available as standard, these being:
3. Loop driven interface devices shall be capable of accepting 4 I/P signals, providing
4 output signals or any combination of either.
4. Dependent upon the specific application I/P signals may be interpreted by the
system as any of the following:-
5. The exact nature of which shall be selected by means of an on -board DIL switch.
For Fire I/P applications a selectable 10 second delay shall be available as
standard for applications such as Sprinkler Flow switches.
7. These devices shall not require any form of external power supply and are fully
maintained under mains failure condition by the main control panels standby
batteries.
8. As with other outstation previously mentioned loop driven interface shall contain its
own local processor to handle all signalling and loop communications.
10. Loop driven interface devices shall be capable of accepting either 1 I/P signals,
providing 1 output signals or any combination of either.
11. Dependent upon the specific application I/P signals may be interpreted by the
system as any of the following:-
12. The exact nature of which shall be selected by means of an on -board DIL switch.
For Fire I/P
13. applications a selectable 10 second delay shall be available as standard for
applications such as
14. Sprinkler Flow switches.
15. These units shall accept and or supply clean contact signals only, whether
normally open or normally
16. closed (configurable). No switched voltage outputs or inputs shall be accepted.
17. These devices shall not require any form of external power supply and are fully
maintained under
18. mains failure condition by the main control panels standby batteries.
19. When used as an output the device shall be provided with single pole change over
contacts for
20. control of plant, door release units etc. The contacts shall be rated at 5amps at a
nominal voltage of
21. 240v AC.
22. As with other outstation previously mentioned loop driven interface shall con tain its
own local
23. processor to handle all signalling and loop communications.
25. These interface units shall require a separate supply of 240V a.c. and integral 24V
1.9AH battery pack.
27. Input channels shall be capable of supporting the specified manufacturers current
range of conventional detectors and manual call points, these being 24V d.c.
operational.
28. These circuits shall be fully monitored for open and short circuit faults providing
that these devices are installed correctly and terminated with the correct E.O.L.
device.
29. Output channels shalll be capable of providing a 24V output in the eve nt of an
alarm. This may be used for driving conventional bells/relays. Providing that these
devices are installed correctly and terminated with an E.O.L. resistor, the output
shall be fully monitored for open and short circuit faults. A total alarm load of
500mA at 24v DC shall be provided from the interface unit in the event of an alarm
condition being initiated.
30. An auxilliary, 24v DC, 500mA, power supply shall be available from the interface
unit for the control of ancilliary services.
31. Within the enclosure provision shall be made for mounting up to 4 octal base relays
for remote signalling along with a suitable voltage barrier.
32. In the event of any of the above faults occurring or a problem developing with the
mains or battery supply, a suitable fault message will be displayed throughout the
system, e.g.
33. Control panel software shall automatically differentiate between extinguishant and
conventional interface devices, thus ensuring that upon operation of Start
Sounders extinguishant is not released. This identification process shall not
require any need to set switches on interface units.
34. Confirmation that loop communications between interface units and main control
panel are being carried out shall be identified by means of an on-board L.E.D.
which shall illuminate upon a communications breakdown. Similarly an indication
will be provided to represent 240V a.c. is being supplied to the unit.
1. All wiring within the system shall be carried out, utilising 2 core 1.5mm( shielded
cable, sheathed with P.V.C. This wiring will not exceed 1km in length for individual
loop circuits and since the system specified employs a complex data transmission
system a continuous earth screen for each loop is required.
2. For any individual loop the maximum inter-core capacitance shall not exceed 0.5(F
and the loop resistance of any single core shall not exceed 13 ohms.
B. Call point Units: Furnish quantity equal to 10 percent of the number of units
installed, but not less than one.
D. Bells: Furnish quantity equal to 2 percent of the number of units of each type size
installed but not less than one of each type.
16950/1
SECTION EL-18
DATA SYSTEM
Scope of Work
A. The contractor shall supply, install, test the Data system (PVC, G.I conduit,
Trunking, Cable Tray, Flexible Conduits, Draw boxes, Box outlets and draw wires
only for Data system )
B. All related works required for the proper performance of a complete raceway
system.
C. The contractor is responsible to make full coordination with the other services &
latest furniture layout to finalized exact location of points and connections.
SECTION EL-
19
PABLIC ADDRESS
SYSTEM
Scope of Work
A. The contractor shall supply, install, test the public address system
(conduit, conduit, boxes, and draw wires only )
B. The conduits routing shall be from each point up to main box
C. The contractor is responsible to make full coordination with the other
services & latest furniture layout to finalized exact location of points and
connections.
16950/2
SECTION EL-20
ELECTRICAL TESTS
PART 1 - GENERAL
1.01 SUMMARY
B. Work Included: The work shall include, but not be limited to, the following:
3. Operational tests.
1.02 DESCRIPTION
A. Testing and testing equipment shall conform to the latest edition of reference
specifications specified herein and to applicable codes and requirements o f local
authorities having jurisdiction.
B. Personnel engaged in the testing of electrical equipment and systems shall have
a minimum of five (5) years of continuous experience in the testing of the
equipment and systems to be tested. Submit evidence of such qualifications to
the Engineer.
16950/3
C. Contractor shall furnish testing equipment as required. Testing equipment,
meters and instruments shall have been properly calibrated and certified within six
(6) months prior to testing and shall be in satisfactory condition to perform its
functions.
F. Electrical equipment and installation shall meet acceptance and operational tests.
Promptly repair or replace defective work and repeat the tests until the particular
system and component parts thereof receive the approval of the Engineer. Any
damages resulting from tests shall be repaired and/or damaged materials
replaced, to the satisfaction of the Engineer.
H. The operation of the electrical installation by the Engineer does not constitute an
acceptance of the electrical installations. Final acceptance will depend on
Contractor's demonstration of compliance with contract documents, completion of
adjustments as specified and required, and submission of required documentation
and certification of approval by governing authorities.
I. Continuity tests shall be performed using direct current and audible bells or
buzzers. Use of telephones is not acceptable.
J. Safety devices such as rubber gloves and blankets, glow detectors, hot sticks,
helmets, eye shields, protective screens and barriers, danger signs, etc. shall be
used to adequately protect and warn personnel in the vicinity of the tests.
1.04 SCHEDULING
1.05 SUBMITTALS
1. Submit two (2) copies of test reports including actual readings and corrected
16950/4
readings after each test period.
2. Submit four (4) bound copies of final approved test reports at the
completion of tests.
3. Test reports shall be signed by the persons performing the tests and the
witnesses to the tests and include, but not be limited to, the following data.
a. Date of test.
c. Description of test.
d. Test results.
PART 3 - EXECUTION
3.01 EXAMINATION
A. Examine conditions at the job site where work of this Section is to be performed
to insure proper arrangement and fit of the work. Start of work implies
acceptance of job site conditions.
3.02 PREPARATION
B. Cooperate in the coordination and scheduling of the work of this Section with the
work of related trades, so as not to delay job progress.
D. Megger and high potential testing shall not be performed during periods of high
relative humidity. A guard shall be stationed at each location where exposed
cables, buswork, connections or other components exist during megger and high
potential testing.
16950/5
E. Equipment shall be thoroughly cleaned prior to testing. Vacuum the interiors of
cubicles and remove foreign material. Insulators, bushings and bus supports
shall be wiped clean with a lint free cloth.
G. Where the equipment or system under test is interrelated with and depends upon
other equipment, systems and/or controls for proper operation, functioning and
performance, the latter shall be operated simultaneously with the equipment or
system under test.
16950/6
insulation valves, the drying method shall be in accordance with the
manufacturer's recommendations.
3.03 APPLICATION
A. Equipment that can be paralleled under any conditions including interlock defeat
shall be tested for proper phasing using hot-phase hot-stick or other approved
methods. This includes, but is not limited to, primary selector switches, automatic
transfer switches, tie breakers and busses, etc. at medium and low voltage levels.
B. Full load currents of feeders serving single phase loads shall be measured to
assure an equal load balance on each phase. Branch circuits shall be
reconnected if necessary to achieve this balance.
3.04 TESTS
1. Wire and cable shall be tested for continuity, freedom from short circuits
and grounds by a1000vdc.Megger to assure adequate insulation
resistances for each conductor.
2. Test Voltages: Megger instrument shall be 1000 volts DC applied for one
minute.
B. Panel boards
1. Equipment shall be tested for continuity, freedom from short circuits, and
grounds and meggered to assure adequate resistances.
D. Grounding System
1. General
16950/7
a. Tests on individual ground rods shall be performed with each rod
isolated from each other and the grounding system.
16950/8
E. Circuit and Motor Disconnects: Upon completion of the installation of electrical
disconnects, energize circuits and demonstrate capability and compliance with
requirements. Except as otherwise indicated, do not test switches by operating
them under load. However, demonstrate switch operation through six
opening/closing cycles with circuit unloaded. Open each switch enclosure for
inspection of interior, mechanical and electrical connections, fuse installation and
for verification of type and rating of fuses installed. Correct deficiencies, then
retest to demonstrate compliance. Remove and replace defective units with new
units and retest.
F. Receptacles
1. Upon completion of wire tests, check receptacles for proper voltages and
phasing, utilizing a receptacle tester for 240 volt 15 and 20 ampere devices
and a voltmeter for other devices.
2. Test three phase receptacles for proper phase rotation using a phase
sequence meter.
4. Test ground fault circuit interrupter receptacles with both local and remote
fault simulations in accordance with the manufacturer's recommendations.
G. Lighting Switches: Test lighting switches for correct operation with special
emphasis on 3- and 4-way switches.
1. Duration of supply.
J. Control Circuits: Test control circuits for proper functioning and fail safe
operation.
16950/9
components, and after circuitry has been energized with the power source, test
television systems to demonstrate capability and compliance with requirements
including, but not limited to, video output signal strength at each television
camera, monitor and receiver location. Where possible, correct malfunctioning
units at site, then retest to demonstrate compliance, otherwise remove and
replace with new units and proceed with retesting.
2. Pre-testing: Upon completing installation of the system, align and adjust the
system and perform pre-testing. Determine, through pre-testing, the
conformance of the system to the requirements of the drawings and
specifications. Correct deficiencies by replacing malfunctioning or damaged
items with new items and retest until satisfactory performance and
conditions are achieved.
3. Testing
16950/1
0
4) Serial numbers, locations by zone and model number for each
installed detector.
e. After completion of the tests and adjustments listed above, submit the
following information to the Engineer:
16950/1
1
END OF SECTION
16950/10