Académique Documents
Professionnel Documents
Culture Documents
Jayachandra Sakamuri and D. John Yesuraj are with R&D Department, Schematic diagram of the typical 400 kV CVT used in this
Instrument Transformer Division of Crompton Greaves Ltd, Ambad, Nashik, study is shown in Fig. 1. The CVT model composed of
India-422010(e-mail:jayachandra.naidu@cgglobal.com;
johnyesuraj.D@cgglobal.com). capacitive voltage divider (C1 and C2), compensating reactor
(L), intermediate transformer (VT), over voltage protection
978-1-4244-8417-1/11/$26.00 2011
2
Current [A]
Fig. 5. Series RLC Filter.
Fig. 3. Voltage Vs Current characteristics of MOV
frequency. Therefore, this filter has no loading effect on the also damps the dangerous high voltage oscillations due to
CVT under normal operating conditions. ferroresonance within less time compared to other techniques
[10], [11]. As it does not involve any energy storage elements,
( L + M )(1 2C ( L + M )) it wont affect the transient response of the CVT. Moreover,
f2 f f f1 by switching on the electronic device in case of transient
Z ( j ) = R + j M (2)
2 f condition, it can further damp the low voltage oscillations by
1 C f ( L f 1 + L f 2 + 2M f )
bringing the damping resistance across CVT secondary. To
design the FSC, the following points are considered.
At off-nominal frequencies, the impedance of the filter The magnitudes of high voltage oscillations without
gradually approaches to the resistance of the damping resistor. any FSC are approximately 2.5 p.u. and the CVT
The variation of impedance, active power load with frequency should withstand (a voltage of 1.5 p.u). for about 30s
is shown in Fig. 8. But this filter impacts the transient according to IEC 60044-5 [12]. Hence the FSC can
response [3]. The filter is designed at 50 Hz frequency be turned on if the voltage exceeds 1.5 p.u so that it
connected at 63.5 V using the method given in [9], and the will not affect the normal CVT operation.
values are The switch can be made ON for a specified duration
until fault is cleared.
M f = 0.1146H , C f = 19.7F , R f = 7.5 In case of fault, the damping burden should be
L f 1 = 0.2292H , L f 2 = 0.0573H connected in both positive and negative half cycles
hence switch should be selected accordingly
The switch can also be turned on if the RMS value of
the CVT voltage falls below certain low value to
suppress the low transient oscillations.
Fig. 7. (a) Power frequency Filter (b) Digital model of the filter
Impedance [], Power [W]
inductor and capacitor, and the VA rating of the VT has to be above 1.6 p.u. The enlarged view of currents through RLC
increased to meet the specified accuracy requirements. series filter and MOV is shown in Fig. 12.
Fig. 11. CVT secondary instantaneous voltage in presence of MOV, RMS Fig. 13. CVT secondary voltage, its RMS value, current through the filter
voltage, and current through the RLC filter (ILC) and metal oxide varistor (IPBF) and MOV (Ivar), with power frequency blocking filter as an FSC
(Ivar).
Simulation results with the addition of MOV are shown in C. Performance of Electronic Switch
Fig. 11. In this case the damping time is reduced to 0.3s as the The electronic switch FSC is connected at 200 V with a
MOV conducts immediately when the fault voltage exceeds damping resistance R. Once the fault is detected, the switch is
5
ON for a fixed duration (say 80ms). After this time, if the fault of a primary short circuit to the peak value of the secondary
still exists then the switch is continued to be ON until the fault voltage before application of short circuit [12]. The CVT
is completely cleared .The MOV is also included in the circuit
to damp the oscillations more effectively. The simulation
results with a damping resistance of R = 80 is given in Fig.
14.The zoomed view of currents through thyristor switch and
MOV are given in Fig 15 and from which one can see that the
MOV is ON if the voltage goes beyond 1.6 p.u and thus it will
limit the fault level. The thyristor switch is ON for duration of
80 ms once it detects the fault voltage above the set value (1.6
p.u) thereby it suppresses the oscillations completely. The
performance of this FSC for different damping resistance
values is shown in Fig. 16. With lower resistance,
ferroresonance is more effectively damped out. However,
there is an optimum resistance, which depends on circuit
configuration, by which the best suppression is obtained. With
R=80, ferroresonance is suppressed within 0.1s
Fig. 16. CVT RMS output voltages with damping resistances of R = 160,
100, 40, and 20 with electronic switch FSC
Characteristics of the transient response of the CVT is the The transient response of the CVT without any suppression
ratio of secondary voltage at a specified time after application device but with 50 VA burden at 0.8 pf with fault applied at
primary voltage zero crossing is shown in Fig. 17. Here the
6
secondary voltage of CVT oscillates at sub harmonic FSC on transient response with fault applied at primary zero
frequency and takes more time (more 0.3s) to get suppressed. crossing is shown in Fig. 19. Only CVT secondary voltage is
The corresponding CVT primary and secondary voltage when shown here for better visibility of the results. The peak voltage
the fault applied at primary crest voltage point is shown in Fig. is 20 V and it is taking more than 200 ms to suppress the
18. As seen from this Fig., at crest fault initiation, the oscillations and hence it can meet only 3PT1 of IEC 60044-5
discharge is a ringing high frequency oscillations caused by [12].
the parasitic capacitance of the compensating reactor and
intermediate voltage transformer and due to lower VT burden.
But after 25 ms of fault initiation, these oscillations were
suppressed.
Fig. 19 Transient Response of CVT with Series RLC FSC and 300 W
Permanent Burden with a fault applied at primary voltage zero crossing
Fig. 21 (a) Thyristor FSC with 50 burden Fig. 23 Transient Response of CVT with Electronic switch FSC with reduced
VT magnetizing current
VI. APPENDIX
Table I Typical 420 kV CVT Technical Data
Parameter Value Description
Vp 231 kV Rated primary voltage of CVT (Ph-n)
magnetizing current considered for CVT discussed so far is Lm 2596 H Magnetization inductance of VT
12mA at rated voltage. If the magnetizing current is reduced
to 4 mA, then the transient response is studied with both series Rm 5.12 M Core loss resistance of VT
RLC FSC and Thyristor FSC. Fig. 22 shows the transient
response results of a typical 400 kV CVT with reduced VII. CONCLUSIONS
magnetizing current with series RLC filter as FSC. The
transient response is better compared to higher magnetizing This paper has presented the detailed model for transient
current shown in Fig. 17. The test results using Thyristor FSC studies and investigation of ferroresonance behaviour of
is shown in Fig. 23. This is the best result among all. The typical 420 kV CVT with PSCAD/EMTDC. Various
result shows that the CVT is meeting all the transient response ferroresonance suppression circuits have been reviewed and
classes such as 3PT1, 3PT2, and 3PT3 of IEC 60044-5 [12]. their performance has been investigated for ferroresonance
and transient response test conditions. The ferroresonance
damping time using series RLC filter is more (0.5s) and it also
affects the transient response and accuracy of the CVT due to
low power factor permanent burden imposed by this filter. The
performance of power frequency blocking filter for the
ferroresonance (time =0.15s) and transient response conditions
is better than the series RLC filter. But it still affects the
accuracy and transient response due to its energy storage
elements.
performance is better with series RLC filter. With Electronic D. John Yesuraj received his M.Tech in High
FSC and with reduced VT magnetizing current, the transient Voltage Engineering from Anna University
Chennai, India. He is presently working as Dy.
response is much better and meeting all the classes, 3PT1 , General Manager (R&D), Instrument Transformers
3Pt2 and 3PT3 of IEC 60044-5. This technique also leads to Division, Crompton Greaves Ltd, Nashik, India. He
improved accuracy compared to the other FSCs. With all the has vast experinece in design and development of
three FSCs, adding a metal oxide varistor can limit HV and UHV instrument tarnsformers and lightning
arresters. His research interests include power
overvoltage in the first cycle and significantly reduce the system transient studies, dielctric evaluation ,
damping time. Although the existing FSCs (series RLC, and condition monitoring of power system components.
power frequency blocking filter) perform well for damping
ferroresonance, they cant improve the transient response due
to their energy storage elements. Hence, with the electronic
switch FSC, the ferroresonance can be damped within five
cycles as well as transient response can be improved by
properly sensing the fault situation and controlling it
accordingly.
VIII. REFERENCES