Vous êtes sur la page 1sur 7

1060 IEEE Transactions on Power Delivery, Vol. PWRD-2, No.

4, October 1987

SCALE MODEL STUDIES OF GROUNDING GRIDS IN NON-UNIFORM SOILS


B.Thapar S.L. Goyal
IEEE Senior Member Non-Member
Dept. of Electrical Engineering Punjab State Electricity Board
Montana State University Chandigarh
Bozeman, MT
Abstract Two layer soil Model
A new improved scale model to study the To conduct model studies of station ground-
behaviour of grounding systems in non-uniform ing grids in two layer soil the model should be
(two layer) soils has been developed.Construc- a true replica of the original as faras poss-
tional details and instrumentation has been ible. When all the physical dimensions of the
discussed.To verify the accuracy of the results grounding system including conductor diameter,
obtained from the tests conducted on the model, depth at which the grid is buried, the depth
they have been compared with the data available of the upper medium etc. are reduced in size by
in the literature.The results giving the poten- the same scale factor, the pattern of the
tial profile, grounding resistance, mesh and current flow and the shape of the equipoten-
step potentials for a number of grids in two tial surfaces are unaltered. To get correct
layer soils are presented. results the model should satisfy the following
requirements.
Introduction
1. The two mediums representing the upper
With the increase in the number, size and layer and the lower layer should be stable
complexity of a.c. substations, it has become mix with each other.It should be possible
necessary to develop accurate design procedures to change the resistivity of the two mediums
for installing grounding systems which are independently.
economic and provide the required degree of 2. In order to (a) facilitate measurements
protection. Analytical techniques with sim- of potentials, (b) replace and modify
plifying assumptions have been used to develop the delicate models representing the
computer programs.The technique of using scale grid and vertical rods and (c) have
models in an electrolytic tank to determine proper contact with the thin wires of
potentials developed during groun,d fault has the model, both the mediums should be
been presented by Koch(l),ArmstxoPg 2),Thapar(3), liquids.
Keil(4), Mukhedkar(5),Caldecott(6) etc.Most of 3. At the boundary of the two mediums a point
the studies on scale models presented so far in the upper medium should be at the same
assume the soil to be uniform. potential as a point immediately below it
in the lower medium.
The soil at most substation sites is non- 4. The size of the electrolytic tank should
uniform. It is practically always possible to be big enough to eliminate the boundary
find an equivalent two layer soil for the effects.
actual soil structure(7). The two layer soil
is characterized by its upper layer of resist- To meet the above mentioned requirements
ivity pi, and height h, and the bottom layer of two tanks made of G.I. sheets and measuring
resistivity P2 and infinite depth.The reflec- 85.5 cm x 85.5 cm x 47.0 cm and 84 cm x 84 cm
tion factor K is defined as(P2-Pi)/(P1+P2). x 40 cm respectively were used.Arrangement was
made to keep the bigger tank on the floor and
The scale model studies for two layer soils support the smaller tank in it is so that the
have been reported by Mukhedkar(5) and Caldecott(6) bottom of the upper tank was about 7 cm below
In both the model studies water was used to the top of the lower tank. The base of the
represent the top layer.Cement concrete wasused lower tank was of the same material as the
by Mukhedkar to represent the bottom layer whereas sides whereas the base of the upper tank was
Caldecott used agar.Both the models suffered made of acrylic sheet. Copper pins made of 16
from the disadvantage that the resistivity of SWG (1.62 mm dia) wire and of length 15 mm
the two mediums could not be closely controlled were fixed in the acrylic sheet at a spacing
and maintained for a long time.The new model of 10 mm and perpendicular to the surface of
described in this paper does not have this the plate so that the pins projected 6 mm on
disadvantage.It uses tap water or salt water each side of the acrlyic sheet.Both the tanks
to representboth the mediums and anacrylic sheet were made leak proof. Water in the two tanks
fitted with conducting pins keeps the two mediums was used to represent the two layers of soil.
distinct and separate & conducts the electric The resistivity of water in each tank could be
current as required. changed independently by adding common salt
(NaCl) and any value of K between + 1 and -1
could be obtained.
87 WT4 189-4 A paper recommended and approved The acrylic sheet forming the base of the
by the IEEE Substations Committee of the IEEE upper tank did not allow the electrolytes to
Power Engineerinp, Society for presentation at the mix with each other and at the same time the
IEEE/PES 1987 Winter Meeting, New Orleans, copper pins allowed the passage of electric
Louisiana, February 1 - 6, 1987. Manuscript current almost in the same manner as it would
submitted January 30, 1985; made available for flow in the absence of the acrylic sheet and
printing November 14, 1986. the two mediums in contact with each other.
To minimize the effect of finite dimensions
of the tanks the size of the model of the
grounding system should be less than 1/5 times the
size of the tank.In order to study grounding
0885-8977/87/1000-1060$01 .00 1987 IEEE
1061

systems of large dimensions only quarter space


may be considered for systems which are symmet-
rical about two horizontal axis passing through
the centre of the system.In such a system no
current will flow across the vertical planes
passing through the two horizontal axis of symmetry.
To achieve this the two adjacent walls of both
the tanks were insulated by fixing bakelite,
polythene sheets on them. Figure 1 shows both
the tanks.

Figure 2.Frame for model grid


Probe Carriage
For measurement of potential, probes made
of 0.1 mm dia copper wires were used.Ten wires
at a spacing of 5 mm were fixed in a straight
line in a small bakelite strip which was attached
to a vertical pipe, about 1 cm dia, so that the
tips of all the ten probes werein a horizontal
plane. A ten core flexible shielded cable connect-
ed the ten probes to ten sockets on the carriage
for making measurements of potentials. Arrangement
was made to move the strip containing the probes
in two perpendicular directions parallel to the
sides of the tank and to adjust its position so
that the tips of the probes barely dipped
below the surface of the water. With this
arrangement it was possible tomake,measurement
Figure 1. Electrolytic tanks of potential at 10 points in a straight line
4.5 cm. long and then move the probes in any
Frame for the model arid direction for making further measurements.
For suspending the model of the grounding Scale Factor
grid in the upper tank a frame of backelite
strip strengthened with an aluminium strip was The maximum limit of the scale factor is
used. Small holes and grooves were made in the normally determined by conductor size. Typical
bakelite to accommodate model of quarterof the grid conductors used in practice have equiv-
grid having 1, 9, 25 and 49 meshes.It is very alent diameter of 1.5 cm. The minimum size of
difficult to use conventional soldering tech- the wire that can be conveniently used on the
nique on wires having less than 0.2 mm dia. To frame used is 0.1 mm. This gives 150 as the
study larger grids it was necessary to make the maximum value of scale factor that can be
models with wire having diameter less than 0.2 adopted. However, the size of wire does not
mm. Soldering of the thin wires used was make any significant difference in the ground-
avoided by making the model of the grid with a ing resistance and surface potentials.As such
continuous super enamelled insulated copper a scale factor of 300 with minimum size ofwire
wire passing through holes and grooves on the for the model as 0.1 mm may be used without
frame. After securing the wire properly on the introducing much error.
frame, the insulation from the part of the
wire depicting the actual grid conductor was If the size of the model of the grid is
removed by burning it with a candle flame and limited to less than 1/5 times the size of the
then cleaning with rough cloth.Figure 2 shows tank the maximum size of the quarter model
the frame supporting a quarter of meshes square grid that can be adopted is about 15 cm x 15cm.
grounding grid. On a scale factor of 300 , this would represent
an actual complete grid of 90 m x 90 m.
The presence of thin insulated enamelled
wire and the edge of the curved portion of the Instrumentation
frame in the electrolyte had no noticeable
effect on the flow pattern of the current in Figure 3 shows the complete set up of the
the electrolyte. model and Figure 4 shows the principal elec-
trical connections.50 Hz power supply was used
The frame with the model of the grid was as the source. Isolating transformer was used
hung at the corner of the tank with strings so for personnel safety and to avoid leakage
that the two straight strips of the frame currents flowing into the ground. The system
touched the two insulated walls of the tank was usually operated at a current of 50 ma.
respectively.The depth of the grid was adjusted by The capacitor was used to avoid any flow of
adjusting the length of the strings. Two ends d.c. current due to use of dissimilar metals
of the super enamelled wire forming the grid (copper for the grid and zinc coating on the
were used for feeding the current in the grid. tank) and subsequent polarization.A voltmeter
1062

with an impedance of atleast 10 mega ohms was group of pins in the acrlyic sheet behave like
used to measure the potential of the probes. a plate for collection or dissipation of current
Both the G.I. tanks were used as collecting in the medium.
electrodes.
TABLE I
RESISTANCE BETWEEN PINS AND PLATES

S.No. h cm Resistance between


Two plates Plate and pins
ohms ohms
1 1 17.5 17.6
2 2 27.0 28.1
3 3 41.5 42.5

Shape and size of tank


The limited size of the tank is expected to
introduce some error in measurements. In order
to estimate the order of the error consider the
r.Lyure J. rluue.l ZmL up
tank to be a hemisphere of radius R and the
CAPACITOR model of the grid being studied to be a circ-
ular plate of radius r placed horizontally on
the surface of the water at the centre of the
tank.
Accuracy, A, can be defined as
A = (R -Rt)/Rp
Where Rp = Grounding resistance of the plate
PP/(4r)
R = Grounding resistance of the hemi-
sphere of the tank
= p/(2iTR)
p = resistivity of the medium
Figure 4. Connection diagram
When both the tanks are used and the
Accuracy of the Model quarter space is considered, the radius of
the equivalent hemisphere may be about 70 cm.
The following two important sources of When r is 10 cm A will be 0.91.
error neen investigation.
Figure 5 gives the equipotentials at the
(a) Presence of the pinned acrylic separal tor surface of the water for a quarter of 9 mesh
between the two tanks.
(b) Shape and finite size of the tank.
Pinned acrylic separator
The following simple experiment was performed:
(a) Two square aluminium plates each measuring
13 cm x 13 cm were placed parallel to each
other with h as the separation distance in
water. The water extended a distance ofat least
10 h from the edge of the plates. Resistance
between the two plates was determined by simple
voltmeter ammeter method.
(b) A group of 14 x 14 pins on the acrlyic sheet
forming a 13 cm x 13 cm square was short circ-
uited and an aluminium plate measuringl1 cm x
13 cm was placed parallel to the plane formed by
the tips of the pins. The distance between
the tips of the pins and the plate was kept
as h. The medium between the plate & the pins
was water having the same resistivity and
extended to the same distance as in (a). The
resistance between the plate and the group of
the pins was measured by simple voltmeter and
ammeter method.
The results of the measurements are given
in Table 1 from where it is indicated that the Figure 5. Equipotentials
1063

grid placed at the insulated corner of the tank. 2. To study asymmetric grids full half space
As the tank walls are approached the potential is to be used and the model of the grid will
gradient in the medium becomes negligibly have to be placed at the centre of the tank
small. The shape of the tank therefore becomes with all the walls of the tank conducting.
unimportant. In this case the maximum size of the grid
that can be studied is about 25m x 25m.
The error in measuring the grounding resist- 3. While analysing the error due to the finite
ance because of the acrlyic sheet is positive size of the tank in the previous section only
and because of the limited size of the tank it homogeneous soil(K = 0) was considered. It
is negative. The two errors wil compensate each is an established fact that the error because
other to some extent. of the finite size of the tank increases
when K is positive and it decreases when K
Grounding resistance of an 8 cm x 8 cm grid is negative.Therefore,the model will give
made of 0.26 mm dia copper wire having four good results only in cases where the top
equal meshes was measured first by using only layer of the soil is having higher resist-
the lower tank filled with tap water upto the ivity as compared to that of the lower layer.
top and then using both the tanks with the
lower tank full of tap water & the upper tank 4. The minimum depth of the upper layer that
having the tap water to a depth of 3 cm. The can be considered in the model is 2.5 cm.
resistivity of the water was 17.9 ohm-m. The A lesser value brings the grid conductor too
results are given in table II. The calculated close to the pins of the acrylicsheet and
value of the grounding resistance of the grid the position of the conductor relative to
was obtained with the help of formula developed the pins will affect the measurements.
by Schwarz(8). The results show that measured First three limitations listed above can
value of the grounding resistance of the grid be overcome by increasing the size of the tanks
when placed in the upper tank is very close to whereas to overcome the fourth limitation the
the calculated value. spacing between the pins and the diameter of
the pins will have to be reduced.
TABLE II
Tests Conducted
GROUNDING RESISTANCE OF GRID
Tests were conducted on grids of various
S.No. Depth of Measured Grounding Calculated sizes and the value of K varying fromO to-0.9.
grid cm resistance ohm grounding Results of the studies made with the following
Lower tank Upper tank resistance parameters are reported.
ohm
Grid size 30 cm x 30 cm
No. of meshes 1, 9, 25, 49
1 0.5 105 109 107 Size of conductor 0.26 mm
2 1.0 99 103 103 P1 20 ohm-m (normalised)
K 0, - 0.9
3 1.5 90 101 101 depth of upper 2.5 cm, 5.0 cm, 12.5 cm.
layer, h
depth of burial 0.5 cm
The model is therefore, expected to be of the grid
reasonably accurate for measurement of grounding
resistance, potential profiles and maximum value Table III gives the grounding resistance,
to touch and step potentials. mesh & step potential for the various values of
these parameters. For K = 0 both the tanks
Capabilities of the model were used. The model of the grid was placed in
Following are the capabilities of the model: the upper tank and the depth of water in the
tank was kept 15 cm.
1. Limited by the size of theconductor to make
the model,the maximum size of the symmetrical Figure 6 and 7 shows the potential profile
grid that can be studied is about 90 m x 90 m. on the surface along a lineparallel to the side

TABLE III
GROUNDING RESISTANCE, MESH & STEP POTENTIAL

S.No. No.of Meshes Top layer depth cm for k = - 0.9 K = 0


2.5 5.0 12.5
R M S R M S R M S R M S
1 1 25.7 86.0 16.9 27.0 77.0 14.5 31.0 60.0 12.5 38.5 63.9 12.0
2 9 20.9 60.0 17.5 24.0 52.0 16.5 25.5 39.0 15.5 30.5 39.5 12.0
3 25 19.3 45.1 23.1 21.5 35.0 22.0 22.5 32.0 18.7 30.5 20.0 12.0
4 49 18.5 41.0 22.9 20.7 34.0 21.0 21.4 29.0 19.0 29.0 15.0 12.0

R = Grounding resistance for p l= 20 ohm-m


M = Percentage mesh potential
S = Percentage step potential
1064

with depth of the upper layer for different


1001_ number of meshes.

90
L 80 _
80ok z
NO. OF
70 _ MESHES
w 70If- '1
0
I- 0.
z
W
60
-J 60 -
: 1/)
w
a. z wi
l1 50 l;L

z
W 40 :r
0
a.
Ln 4o L 9
h, c m
w 30
Lr 12.5 Z 30r
'A 20 *t50 25
0.O r 49
2^5 0.
0o 0 20; LA 49
(A 25
9
0 --I A ! I-I .I
0 5 10 15 20 25 30
DISTANCE FROM GRID CEtITER LINE- cm
Figure 6. Potential profiles for 30cm x 30 cmy 0E3
25 mesh grid with K 0 and K = -0.9y
=

depth of grid 0.5 cm


=

5
2- 94 4s9

w 0 2-5 5-0 7-5 10.0 12-5


ID
HEIGHT OF UPPER LAYER. cm
z LL1._lI1, s I I l
,,

1-5 1-35
w

UI 8 6 4 3 2
r/h
Iz
w

-i Figure 8. Grounding resistance,mesh and


step potentials
z
The ratio of the grounding resistance in uniform
w
-I-

0
soil to that in non-uniform soil having the same
resistivity of the top layer,percentage mesh
and step potentials do not vary appreciably if
w

rnh is kept constant, r being the radius of


cU) a circular plate having the same area as that
,1 of the grid. Figure 8 also shows scale for
rnh which varies from 1.35 to 6.75. Therefore,
these results can be applied to other sizes of
the grids also.
Results
5 10 15 20 25 The following results in non-uniform soil
DISTANCE FROM GRID CENTER LINE-cm for K -0.9 can be observed.
=

Figure 7. Potential profiles for 30cm x 30cm (a) The grounding resistance for r/h=7.0 would
grids with K = 0.9,h = 5.0 cm,
-
be about 70% of the grounding resistancein
depth 0.5 cm.
=
uniform soil of Pi resistivity.
of the grid and passing throuch the centre of the grid (b) The percentage mesh potential for rfh=7.0
and 15 cm point is vertically above the outer increases toabout 2 times when compared with
conductor. the value in uniform soil. Since there is
Figure 8 shows the variation of grounding a corresponding decrease in the grounding
resistance, ,ercentage mesh and step potentials resistance the actual increase in the mesh
1065

potential is small (not more than 1.5 times). TABLE VII


(c) The percentage step potential for r/h= 7.0 COMPARISON OF GROUNDING RESISTANCE IN NON-UNIFORM
increases to about 1.5 times when compared SOIL
with the value in uniform soil.Because of
the corresponding decrease in the grounding S.No. No.of h cm Grounding Resistance Ohms
resistance the actual change in the step meshes Measured Thapar 3)
potential is negligible.
Verification of Results 1 1 5.0 27.0 30.8
2 9 5.0 24.0 21.6
The measured values of the grounding
resistance, percentage mesh and step potentials 3 25 5.0 21.5 19.0
were compared with the corresponding values 4 49 5.0 20.7 17.1
available in literature. Tables IV to IX
present the comparison. The measured values
obtained from the model studies are quite close TABLE VIII
to the values either calculated or obtained
with th )elp of a dig it 1 computer by Laurent(9), COMPARISON OF MESH POTENTIAL IN NON-UNIFORM
Schwarz ,I 80 O, Thapar (3,1),Dawalibi7' SOIL
Joy(12) and the values obtained from model S.No. No.of
studies by Caldecott and Kasten(6). h cm Percentage Mesh Potential
meshes Measured Dawalibi((7) CaldecottT6)
6
TABLE IV
COMPARISON OF GROUNDING RESISTANCE IN UNIFORM SOIL 1 9 2.5 60.0 65.0** 80.0**
2 9 5.0 52.0 50.0** 59.0**
S.No. No.of Grounding Resistance ohms 3 9 12.5 39.0 40.0** -
meshes Meas-
ured
Lau-
rant(9)
Schwarz(8)Cald Joy(12)
cottT6) ** No. of meshes 16
1 1 38.5 46.2 39.0 - 44.0 TABLE IX
2 9 32.0 37.9 35.1 41.4 38.0 COMPARISON OF STEP POTENTIAL IN NON-UNIFORM
3 25 30.5 35.1 33.3 36.0 36.0 SOIL
4 49 29.0 33.7 32.3 - 34.0 S.No. No.of h cm Percentage Step Potential
meshes Measured Dawalibi (7)

TABLE V 1 9 2.5 17.5 19.0*


COMPARISON OF MESH POTENTIAL IN UNIFORM SOIL 2 9 5.0 16.5 16.0*
S.N o. No.of Percentage Mesh Potential 3 9 12.5 15.5 13.0*
meshes Meas-
IEEE-80 (10) Caldecott (65 Joy (12) 4 25 2.5 23.1 22.0**
ured 5 25 5.0 22.0 20.5**
1 1 63.9 57.6 - 60.0 6 25 12.5 18.7 17.0**
2 9 39.5 32.9 42.0 33.0
* No. of meshes 4
3 25 20.0 18.2 36.0 28.0 ** No. of meshes 16
4 49 15.0 12.7 - 23.0
Conclusions

TABLE VI 1. A new two layer soil model to study the


behaviour of grounding grids in non-uniform
COMPARISON OF STEP POTENTIAL IN UNIFORM SOIL soil has been developed.
S.No. No.of Percentage Step Potential 2. The model has been tested and the values
of grounding resistance,mesh and step potentials
meshes Meas- IEEE-80( 10)Dawalibi (7) y(12) are quite close to those obtained by calculations
ured or with the use of digital computer by other
1 1 12.5 13.8 - 14.5 authors.
2 9 12.0 14.5 10.0* 12.2 3. The model described in the paper has the
following advantages over the models developed
3 25 12.0 13.3 12.0** 12.0 previously (a) The two mediums do not mix and
4 49 12.0 14.6 - 12.0 retain their values of the resistivity for
any time needed to complete the study. (b)
Any value of K can be obtained by using tap
water as one medium and salted tap water as
* No. of meshes 4 the other medium.
** No. of meshes 16 4. The model presented in the paper should
prove to be very good tool to study the
grounding grids in non-uniform soils.
1066

References B.Thapar (S'61-M'63-SM' 70 )


was born in Ludhiana,India on
1. Walter Koch, "Grounding Methods of High- Sept.1,1930.He received the
voltage Stations with Grounded Neutrals", B.Sc.degree in Electrical
Elektrotechnische Zeit, Vol. 71, No. 4 Engineering from Banaras
February 1950, pp. 89-91 (Translated and Hindu University, M.S. and
reprinted as Appendix VI of AIEE-80, 1961). Ph.D. degrees in Electrical
Engineering from Illinois
2. H.R. Armstrong and L.J. Simpkin,"Grounding Institute of Technology,
Electrode Potential Gradients from Model Chicago, in 1953, 1960 and
Test", AIEE Transactions, Vol. 78,Part III, 1963 respectively.
1959, pp. 618-622. From 1953 to 1955 he was
3. B.Thapar and E.T.B. Gross,"Grounding Grids with Punjab Public Works Department, Electricity
for High-voltage Stations IV-Resistance of Branch, Chandigarh, India, working in Power
Grounding Grids in Non-Uniform Soil", IEEE System operation section. In 1955 he joined
Transactions, PAS,Vol.PAS-82,1963,pp. 782- the faculty of Punjab Engineering College
788. Chandigarh, and is now a Professor of Electrical
Engineering. He has published a number of
4. R.P.Keil and W.K.Dick,"Substation Grounding Technical papers and is co-author of a book on
-Update of IEEE STANDARD 80", Fourteenth power system transients.
Annual Transmission and Substation Design Dr. Thapar is a member of IEE, fellow of
and Operating Symposium, University of number of
Texas at Arlington, September,1981. IE(India). He is working on a
bodies for the development of electrical educa-
5. D. Mukhedkar, Y. Gervais & 3.P. Dejean, tion and research in electric power systems.
"Modelling of Grounding Electrode", IEEE
Transactions,PAS, Vol. PAS -92, 1973, pp. S.L. Goyal was born in Moga,
295-296. India, on November 1, 1932.
6. Ross Caldecott and Donald G.Kasten, "Scale He graduated in Electrical
Model studies of Station Grounding Grids", Engineering from Rajasthan
IEEE Transactions, PAS, Vol. PAS-102, 1983, University in the year1953.
pp. 558-566. Received M.Sc. Electrical
7. F.Dawalibi and D. Mukhedkar, "Parametric Engineering(Power Systems)
Analysis of Grounding Grids", IEEE Transac-
degree from Panjab University
in 1973.
tions, PAS, Vol.PAS-98,1979,pp.1659-1668. After working at Hirakud
8. S.B. Schwarz, "Analytical Expressions for Dam Project for two years,
Resistance of Grounding Systems", AIEE joined Punjab State Electri-
Transactions,Vol. 73, Part - III B, 1954, city Board in the year 1956.He was responsible
pp. 1011-1016. for the operation and maintenance ofdistribu -
9. P.G. Laurent, "General Fundamentals of tion systems as Assistant Engineer and Executive
Electric Grounding Technique, "Bulletin Engineer. He was assigned the responsibility
for field design,construction and planning of
de la Societe' Grancaisedes Electriciens, first 400 kV (Dehar Panipat)line in the country.
Vol. I Series 7,July, 1951, pp. 368 402
As Superintending Engineer, had a stint at the
-

(Translated and reprinted as Appendix III Material Management of the State Electricity
AIEE-80, 1961). Board. As Deputy Director and presently as
10. Guide for Safety in Alternating Current Sub- Director, directed and carried out investigations
Stations Grounding",IEEE Standard 80,1976. on various research projects in power systems.
11. B. Thapar and 8.K.Arora,"Grounding Systems He has to his credit a number of Research and
in Non-Uniform Soil",Institution of Engineers Technical Publications.Areas of specialisation
and interest are Vibrations and Oscillations
(India), Vol. 58, Pt. EL I, August, 1977, in single and bundle conductor transmission
pp. 23-29.
lines and grounding systems.
12. E.B. Joy, N.Paik, T.E.Brewer, R.E. Wilson, Mr. Goyal is a fellow of Institution of
R.P. Webb, and A.P.Meliopoulos, "Graphical Engineers (India),member CIGRE and member ERA.
Data for Ground Grid Analysis, IEEE Transac-
tions, PAS, Vol. PAS-102,1983,pp.3038-3048.

Vous aimerez peut-être aussi