Académique Documents
Professionnel Documents
Culture Documents
4, October 1987
with an impedance of atleast 10 mega ohms was group of pins in the acrlyic sheet behave like
used to measure the potential of the probes. a plate for collection or dissipation of current
Both the G.I. tanks were used as collecting in the medium.
electrodes.
TABLE I
RESISTANCE BETWEEN PINS AND PLATES
grid placed at the insulated corner of the tank. 2. To study asymmetric grids full half space
As the tank walls are approached the potential is to be used and the model of the grid will
gradient in the medium becomes negligibly have to be placed at the centre of the tank
small. The shape of the tank therefore becomes with all the walls of the tank conducting.
unimportant. In this case the maximum size of the grid
that can be studied is about 25m x 25m.
The error in measuring the grounding resist- 3. While analysing the error due to the finite
ance because of the acrlyic sheet is positive size of the tank in the previous section only
and because of the limited size of the tank it homogeneous soil(K = 0) was considered. It
is negative. The two errors wil compensate each is an established fact that the error because
other to some extent. of the finite size of the tank increases
when K is positive and it decreases when K
Grounding resistance of an 8 cm x 8 cm grid is negative.Therefore,the model will give
made of 0.26 mm dia copper wire having four good results only in cases where the top
equal meshes was measured first by using only layer of the soil is having higher resist-
the lower tank filled with tap water upto the ivity as compared to that of the lower layer.
top and then using both the tanks with the
lower tank full of tap water & the upper tank 4. The minimum depth of the upper layer that
having the tap water to a depth of 3 cm. The can be considered in the model is 2.5 cm.
resistivity of the water was 17.9 ohm-m. The A lesser value brings the grid conductor too
results are given in table II. The calculated close to the pins of the acrylicsheet and
value of the grounding resistance of the grid the position of the conductor relative to
was obtained with the help of formula developed the pins will affect the measurements.
by Schwarz(8). The results show that measured First three limitations listed above can
value of the grounding resistance of the grid be overcome by increasing the size of the tanks
when placed in the upper tank is very close to whereas to overcome the fourth limitation the
the calculated value. spacing between the pins and the diameter of
the pins will have to be reduced.
TABLE II
Tests Conducted
GROUNDING RESISTANCE OF GRID
Tests were conducted on grids of various
S.No. Depth of Measured Grounding Calculated sizes and the value of K varying fromO to-0.9.
grid cm resistance ohm grounding Results of the studies made with the following
Lower tank Upper tank resistance parameters are reported.
ohm
Grid size 30 cm x 30 cm
No. of meshes 1, 9, 25, 49
1 0.5 105 109 107 Size of conductor 0.26 mm
2 1.0 99 103 103 P1 20 ohm-m (normalised)
K 0, - 0.9
3 1.5 90 101 101 depth of upper 2.5 cm, 5.0 cm, 12.5 cm.
layer, h
depth of burial 0.5 cm
The model is therefore, expected to be of the grid
reasonably accurate for measurement of grounding
resistance, potential profiles and maximum value Table III gives the grounding resistance,
to touch and step potentials. mesh & step potential for the various values of
these parameters. For K = 0 both the tanks
Capabilities of the model were used. The model of the grid was placed in
Following are the capabilities of the model: the upper tank and the depth of water in the
tank was kept 15 cm.
1. Limited by the size of theconductor to make
the model,the maximum size of the symmetrical Figure 6 and 7 shows the potential profile
grid that can be studied is about 90 m x 90 m. on the surface along a lineparallel to the side
TABLE III
GROUNDING RESISTANCE, MESH & STEP POTENTIAL
90
L 80 _
80ok z
NO. OF
70 _ MESHES
w 70If- '1
0
I- 0.
z
W
60
-J 60 -
: 1/)
w
a. z wi
l1 50 l;L
z
W 40 :r
0
a.
Ln 4o L 9
h, c m
w 30
Lr 12.5 Z 30r
'A 20 *t50 25
0.O r 49
2^5 0.
0o 0 20; LA 49
(A 25
9
0 --I A ! I-I .I
0 5 10 15 20 25 30
DISTANCE FROM GRID CEtITER LINE- cm
Figure 6. Potential profiles for 30cm x 30 cmy 0E3
25 mesh grid with K 0 and K = -0.9y
=
5
2- 94 4s9
1-5 1-35
w
UI 8 6 4 3 2
r/h
Iz
w
0
soil to that in non-uniform soil having the same
resistivity of the top layer,percentage mesh
and step potentials do not vary appreciably if
w
Figure 7. Potential profiles for 30cm x 30cm (a) The grounding resistance for r/h=7.0 would
grids with K = 0.9,h = 5.0 cm,
-
be about 70% of the grounding resistancein
depth 0.5 cm.
=
uniform soil of Pi resistivity.
of the grid and passing throuch the centre of the grid (b) The percentage mesh potential for rfh=7.0
and 15 cm point is vertically above the outer increases toabout 2 times when compared with
conductor. the value in uniform soil. Since there is
Figure 8 shows the variation of grounding a corresponding decrease in the grounding
resistance, ,ercentage mesh and step potentials resistance the actual increase in the mesh
1065
(Translated and reprinted as Appendix III Material Management of the State Electricity
AIEE-80, 1961). Board. As Deputy Director and presently as
10. Guide for Safety in Alternating Current Sub- Director, directed and carried out investigations
Stations Grounding",IEEE Standard 80,1976. on various research projects in power systems.
11. B. Thapar and 8.K.Arora,"Grounding Systems He has to his credit a number of Research and
in Non-Uniform Soil",Institution of Engineers Technical Publications.Areas of specialisation
and interest are Vibrations and Oscillations
(India), Vol. 58, Pt. EL I, August, 1977, in single and bundle conductor transmission
pp. 23-29.
lines and grounding systems.
12. E.B. Joy, N.Paik, T.E.Brewer, R.E. Wilson, Mr. Goyal is a fellow of Institution of
R.P. Webb, and A.P.Meliopoulos, "Graphical Engineers (India),member CIGRE and member ERA.
Data for Ground Grid Analysis, IEEE Transac-
tions, PAS, Vol. PAS-102,1983,pp.3038-3048.