Académique Documents
Professionnel Documents
Culture Documents
Department of Electrical and Computer Engineering McCleer Power, Inc. Oak Ridge National Laboratory
University of Wisconsin Madison Jackson, MI USA Oak Ridge, TN USA
Madison, WI USA
6000
5000
Pout [Watts]
4000
3000
2000
1000
0
0 1000 2000 3000 4000 5000 6000 7000
Speed [rpm]
Figure 2: Calculated power vs. speed envelope of the prototype Figure 3: One cycle of the predicted SPM machine
SPM machine cogging torque
Updated analytical predictions for the prototype machine
with the measured inductance (see Sec. VI) indicate that the
required constant power level of 6 kW can still be achieved by
increasing the dc bus voltage from 126 V to 195 V as shown
in the calculated power vs. speed envelope curve in Fig. 2.
This will be confirmed by experimental results later in this
paper. The important observation is that this prototype
machine continues to offer the opportunity to confirm that a
wide constant-power speed range can be achieved despite its
non-optimal characteristic current value.
C. Cogging Torque
Figure 4: Overlaid analytical and FEA predicted phase back-emf
Figure 3 shows one cycle of the predicted cogging torque voltage waveforms at 600 r/min
for the prototype 36s/30p SPM machine. The predicted peak-
to-peak cogging torque amplitude is less than 1% of the rated Torque at 600 rpm
torque. This result is consistent with results presented 80
elsewhere in the literature [1,11-13] showing that cogging 70
60
Torque [Nm]
Figure 4 shows overlaid versions of the phase back-emf 0 50 100 150 200 250 300 350 400
Angle [elect. degrees]
waveform at 600 r/min using both closed-form analysis and
FEA. The excellent match between these two waveforms Figure 5: FEA predicted machine output torque at
builds confidence in the accuracy of the analytical model. 600 r/min under sinusoidal current excitation.
Although the phase back-emf waveform contains significant
harmonic components, the triplen harmonics dominate so that Torque at 6000 rpm
little ripple torque is generated with three-phase sinusoidal 14
current excitation. The line-to-line back-emf waveform is 12
Torque [Nm]
110
No Segmetation
90
Power Loss [Watts]
Segmented_2Pieces
70
50
30
10
-10 1 3 5 7 9 11 13 15 17 19 21 23 25
Spacial Harmonic Order
70 100
60 Experimental
80
Analytical
Efficiency [%]
Torque [Nm]
50 Experimental
60
40 Analytical
30 40
20
20
10
0 0
0 2000 4000 6000 8000 0 1000 2000 3000 4000 5000 6000 7000
Figure 24: Comparison of the measured and calculated machine Figure 26: Comparison of the measured and calculated machine
torque vs. speed envelopes efficiency vs. speed envelopes
7000 100
6000
80
Efficiency [%]
5000
Pout [Watts]
4000 60
Experimental
3000 40
Analytical
2000
20
1000
0 0
0 1000 2000 3000 4000 5000 6000 7000 0 1000 2000 3000 4000 5000
Speed [rpm] Speed [rpm]
Figure 25: Comparison of the measured and predicted machine Figure 27: Measured machine-plus-inverter system efficiency vs.
power-speed envelopes speed envelope
result of the higher-than-expected phase inductance. This
Converter Efficiency vs Speed
higher bus voltage makes it possible to demonstrate that the
machine can achieve a wide speed range of constant-power 120
operation at the 6 kW level. 100
Efficiency [%]
For the test results reported here, the bus voltage was raised 80 Experimental
to a somewhat higher value than the minimum required value 60 Analytical
of 195V, and the tests were conducted with the machine 40
operating continuously in PWM mode in order to simplify the 20
control issues. The torque/power envelope tests were carried 0
out by adjusting the synchronous-frame id and iq current 0 1000 2000 3000 4000 5000 6000 7000
values to develop the desired torque/power within the targeted Speed [rpm]
phase voltage limit of 87.8 Vrms (fundamental). This phase
voltage corresponds to a dc link bus voltage of 195V (ignoring Figure 28: Comparison of the measured and calculated inverter
switch voltage drops) with six-step voltage excitation (i.e., efficiency vs. speed envelopes
195 2 = 87.8 Vrms).
available evidence suggests that the machine will be able to
Comparisons of the measured and updated analytical demonstrate higher CPSR values before testing is completed.
machine torque vs. speed envelopes and the corresponding
The results in Fig. 24 show that the measured torque is
power vs. speed envelopes are shown in Figs. 24 and 25,
slightly higher than predicted at lower speeds for the same
respectively. . The envelope curves in Figs. 24 and 25 show
stator current. This is consistent with the higher value of
that there is a very good match between the measured and
magnet Br in the prototype machine, as previously discussed.
analytical results up to the maximum test speed of 4000 r/min.
These results are very significant since they confirm that the C. Machine and Inverter Efficiency vs. Speed Envelopes
prototype machine has achieved a wide speed range of Figure 26 shows a comparison of the measured and
constant-power operation (approx. 5:1, to date). calculated machine efficiency vs. speed along the maximum
At the time of this writing, no tests have been carried out torque/power envelope. Updated analytical predictions and
above 4000 r/min in order to complete testing at lower speeds measured results agree very closely over the entire tested
before exposing the rotor to higher structural stresses. All