Design calculation sheet

Project name: STORAGE, PARKING Date: 15/03/2015 Sheet no.: 1 of 1 Computed by:
3
Computed by:
Storage Building Plans
Approved by:

Car Park Ventilation


Parking Area 5200 m
Parking Height 5.2 m
Floor Volume 27040 m3
In Normal Mode (Normal Pollution: 30 PPM < Co > 50 PPM) 6 ACH
In Fire mode (High Pollution: CO>50 PPM) 10 ACH

Exhaust Fans Volumetric Flow Rate in Normal Mode (6 ACH) 45067 L/S 7511.1 15915 CFM
Exhaust Fans Volumetric Flow Rate in Fire Mode (10 ACH) 75111 L/S 12519 26525 CFM

Supply Fans Volumetric Flow Rate in Normal Mode (6 ACH) 38307 L/S 9576.7 20292 CFM
Supplyt Fans Volumetric Flow Rate in Fire Mode (10 ACH) 63844 L/S 15961 33820 CFM
Remarks :
* Make up air flow rate preferably at 85% of exhaust flow rate.

Furniture Storage Ventilation (S-104)


Storage Area 1276.1 m
Storage Height 7.7 m
Floor Volume 9825.97 m3
In Normal Mode 6 ACH
In Fire mode 10 ACH

Exhaust Fans Volumetric Flow Rate in Normal Mode (6 ACH) 16377 L/S
Exhaust Fans Volumetric Flow Rate in Fire Mode (10 ACH) 27294 L/S

Supply Fans Volumetric Flow Rate in Normal Mode (6 ACH) 13920 L/S
Supplyt Fans Volumetric Flow Rate in Fire Mode (10 ACH) 23200 L/S

Furniture Storage Ventilation (S-118)


Storage Area 817 m
Storage Height 7.7 m
Floor Volume 6290.9 m3
In Normal Mode 6 ACH
In Fire mode 10 ACH

Exhaust Fans Volumetric Flow Rate in Normal Mode (6 ACH) 10485 L/S
Exhaust Fans Volumetric Flow Rate in Fire Mode (10 ACH) 17475 L/S

Supply Fans Volumetric Flow Rate in Normal Mode (6 ACH) 8912 L/S
Supplyt Fans Volumetric Flow Rate in Fire Mode (10 ACH) 14854 L/S

Archiving Ventilation (S-101)


Storage Area 1636 m
Storage Height 7.7 m
Floor Volume 12597.2 m3
In Fire mode 10 ACH
Design calculation sheet
Project name: STORAGE, PARKING Date: 15/03/2015 Sheet no.: 1 of 1 Computed by:
3
Computed by:
Storage Building Plans
Approved by:

Exhaust Fans Volumetric Flow Rate in Fire Mode (10 ACH) 34992 L/S
Supplyt Fans Volumetric Flow Rate in Fire Mode (10 ACH) 29743 L/S

Storage Goods Ventilation (S-109)


Storage Area 395 m
Storage Height 7.7 m
Floor Volume 3041.5 m3
In Fire mode 10 ACH

Exhaust Fans Volumetric Flow Rate in Fire Mode (10 ACH) 8449 L/S
Supplyt Fans Volumetric Flow Rate in Fire Mode (10 ACH) 7181 L/S

Storage Ventilation (S-112)


Storage Area 168 m
Storage Height 7.7 m
Floor Volume 1293.6 m3
In Fire mode 10 ACH

Exhaust Fans Volumetric Flow Rate in Fire Mode (10 ACH) 3593 L/S
Supplyt Fans Volumetric Flow Rate in Fire Mode (10 ACH) 3054 L/S

Storage Ventilation (S-115)


Storage Area 355 m
Storage Height 7.7 m
Floor Volume 2733.5 m3
In Fire mode 10 ACH

Exhaust Fans Volumetric Flow Rate in Fire Mode (10 ACH) 7593 L/S
Supplyt Fans Volumetric Flow Rate in Fire Mode (10 ACH) 6454 L/S

CAP Washing Machine Ventilation (S-001)


Storage Area 55.6 m
Storage Height 3.05 m
Exhaust Rate 7.5 L/S.m

Supply Fans Volumetric Flow Rate 417 L/S

CAP Machine Ventilation (S-002)


Storage Area 55.6 m
Storage Height 3.05 m
Exhaust Rate 7.5 L/S.m

Supply Fans Volumetric Flow Rate 417 L/S


Design calculation sheet
Project name: STORAGE, PARKING Date: 15/03/2015 Sheet no.: 1 of 1 Computed by:
3
Computed by:
Storage Building Plans
Approved by: