Vous êtes sur la page 1sur 7

International Conference on Electrical, Electronics, and Optimization Techniques (ICEEOT) - 2016

Reduction of Inrush Current for Transformer Using


Sequential Switching Method

Ketan Gohil Jatinkumar Patel Chirag Parekh


Department of electrical engineering Department of electrical engineering Plant coordinator
G.H.Patel college of engineering G.H.Patel college of engineering Atlanta electricals Pvt. Ltd.
Anand, India Anand, India Anand, India
gohilketan369@gmail.com jatinpatel@gcet.ac.in chirag.parekh@atlantaelectricals.com

Abstract- Nowadays, solar power becomes one of the most


suitable renewable energy source for power generation. In practice,
inrush current is produced in grid connected transformer(s) during
routine switching process of solar power plant. This inrush current
effects to winding of transformer as well as produces harmonics
and power quality issues. In this paper the calculation of inrush
current and its effect on power system network is elaborated.
Possible cost effective solution for reduction of inrush current by
suitable techniques is discussed in this paper. In sequential
switching technique, better suppression of inrush current and
harmonics is obtained.

Index termsModelling, Matlab, Transformer, Inrush current,


solar power plant, switching method.

I. INTRODUCTION
Fig.1. pattern of inrush current
A demand of electric power is increasing due to industrial and
mankind growth rapidly. Therefore to fulfill the requirement of Electrical power is unable to generate during night time. As a
Electric power, apart from the conventional source of energy, the result, solar power plant auxiliaries draw the certain amount of
renewable source of energy is being more popular compared to current and solar plant behaves like a load. Therefore, in
other renewable sources of energy. Growth of solar power uninstructed manner, plant(s) have been disconnected from main
installation has been linearly increased and became key player grid by power plant operators. Next day when plant is connected
for produce of electricity. Total installed capacity of solar power to grid through transformer high amount of magnetizing current
in India 5130 MW and Gujarat state is 1024.15 MW up to the till (Im) drawn by the transformer due to residual flux of transformer.
date [1]. As a result, grid tied transformer of solar plant experiences the
Solar power plants are switched off at night due to some heavy amount of inrush current which becomes daily practice for
problems such as reverse power flow and reactive power solar power generation. To prevent from such an undesirable
compensation problem. Next day, at early morning, when solar phenomenon, certain techniques has been developed, however
plant is switched on in case of grid tide, due to switching effect, rigorous research is required in this area. To reduce inrush
high value of inrush current is drawn by transformer due to current, different techniques such as series compensation
instantaneous switching effects. Also transformer draws high techniques, virtual air gap techniques, asymmetric winding, pre
amount of current when it converts its state from de-energized to fluxing, optimal losing, point on wave switching, ultra-low
energized state which measured as inrush current which should power frequency power source, bridge type inrush current
be mitigate effectively to overcome the power quality issues. limiter, grounding resistance at neutral point and sequential
Amount of inrush current is 8 to 10 times higher than rated switching method are discussed in this paper. From above
current [2]. discussed methods, Sequential switching method is adopted to
During starting, amount of high inrush current for several reduce the inrush current.
cycles has been fed to grid. But it slowly decreases and finally
reaches at normal rated current which is shown in Fig. 1.

978-1-4673-9939-5/16/$31.00 2016 IEEE


A. Effects of inrush current. TABLE II. VALUE OF THE FLUX AT DIFFERENT SWITCHING INSTANT
1. Voltage distortion: when transformer impedance, smaller
than the source impedance during energization of it, consider Switching Angle Value of flux
voltage drop will occurs due to inrush current event. Voltage
= 0 = 3m
distortion (0.1 pu to 0.9 pu) will affect the some sensitive load,
industrial costumer, medical equipment etc. [3] [4]. = 45 = 2.12m
2. Harmonics: Due to inrush current, harmonics are generated = 90 = m
with different orders and its magnitude indicated in Table I.
Second order harmonics are dominant because its quarter wave
symmetric in nature. Inrush current star in either positive 2. Residual flux density: Transformer is made from
direction or negative direction. [i.e. For supply of 50Hz ferromagnetic material. Hence, always residual flux will be
frequency, freq. of second harmonics will be 50 x 2 = 100Hz.] present in it due to hysteresis effect which is the main cause of
[5]. inrush current in windings. Which depends upon core material
characteristics. Its extreme value considered for cold rolled
TABLE I. HARMONICS CONTENT OF INRUSH CURRENT
and hot rolled material are 80% and 60% respectively of the core
Harmonic order Magnitude (%) saturation value [10]. Value of residual flux in transformer is
Fundamental 100% measured by de-energization instant of transformer. Residual
DC 40 to 60% flux measurement is used for calculate of suitable instant for
2nd 30 to 70%
energization of transformer [11]. Table III. shows residual flux
3rd 30 to 50%
in different rating of transformer.
3. Stress on transformer winding: During inrush current in TABLE III. RESIDUAL FLUX OF DIFFERENT RATING OF TRANSFORMER
transformer, two main forces acts on winding.
Radial force. Transformer capacity 300 kVA 800 kVA 50 MVA 300 MVA
Residual flux 0.33 Wb 0.38 Wb 13 Wb 83 Wb
Axial force.
Radial force occurs during inrush current, which cause the
increase the diameter of winding. It also forces during short 3. Series resistance: Line resistance between the sources and
circuit occurrence which is more damaging compared to inrush transformer is another factor of inrush current generation. Due to
current. The axial force drives the winding towards ground damping effect, series resistance between transformer and
which changes the dimensions and also able to damage the sources, not only decreases maximum preliminary inrush current
transformer winding [6] [7]. but also increase its decay rate. Transformer near to generator
4. Malfunctioning of protective relay: In actually to compute usually have high inrush current because of the line resistance
the highest value of inrush current should be very affected between generator side transformers and generator is minimum
parameter in designing and to determine the setting of over [10].
current relay used in power transformer maloperation of relay is 4. Inrush under load: If transformer is energize with
occurred. Due to malfunctioning of relays, circuit breakers connected load, some value of load power factor affected by
operates for tripping which is undesirable [8]. inrush current in transformer. If under heavy load and at unit
power factor transformer is switched on, the maximum value of
B. Factors for inrush current inrush current is low. Inrush current peak value is high for
1. Switching angle: If applied voltage is zero value at that reduction of power factor [9].
instant inrush current is maximum. Because if voltage is zero 5. Source impedance: Inrush current is also defined by
value at that time flux is maximum and hence, inrush current is impedance of source of power system. If transformer primary
maximum. Flux in transformer is given by following equation winding and source impedance is same or impedance of source
[9]. is more than impedance of transformer primary winding inrush
current in that situation is maximum. The transformer inrush
= (r + m) cos() m cos(t + ) (1) current causes momentary voltage sag due to the impedance
between the energized transformer and the source [12].
The flux value at different instant of switching is calculated 6. Size of transformer: The size of the transformer reproduces
using (1) and presented in Table II. Table. II seen that inrush the inner transformer impedance of winding. The small
current depends on two factors; residual flux and switching transformer (< 1000 kVA) generates high inrush current for
angle of voltage. If =90; =2m, for = 0; =3m. Therefore, small duration (100 ms.). The high rated transformer (>1000
voltage at zero crossing inrush current is maximum. kVA) generates low inrush current for long duration in range of
seconds [13].
Above factors are responsible for causes the inrush current.
Main factors for reducing the inrush current are switching angle
() and residual flux (res) after designing of transformer. Inrush
current value is high as compare to normal rated current, transformer, power-on angle of circuit breaker and calculation of
therefore harmonics at that instant is also high. Harmonics residual flux. Inverter based series compensator using a current-
contents in inrush current waveform shown in Table I. mode control for reducing the inrush current during energization
of transformer [17]. By using asymmetric winding the inrush
II. METHODS FOR MITIGATE THE INRUSH CURRENT current was minimizes based on increasing the inrush equivalent
inductance by changing the value of internal film and external
Several methods has been proposed by various authors to film in coil winding. [18]. In this method all three phases of
reduce inrush current in transformer in articles [14-29]. The transformer is energized at proper instant. If each phase of
methods elaborated here are developed in time frame transformer is energized in sequential manner at suitable instant
chronologically which has shown in Fig.2. Most of the methods inrush current is reduce. In this method not required the residual
are able to mitigate inrush current effectively however sequential flux calculation. Inrush current reduce by this method by using
switching method is able to provide most effective solution of zero crossing detector and knowledge about closing time of
compared to others which is simulated for power transformer circuit breaker [19]. By using this method reduce the residual
used for distributed generator at large. flux in core of transformer by applying voltage across tertiary
winding before energization of transformer [20] [21]. In this
method use the diode bridge technique for reduce the inrush
current in primary grounded transformers. The advantages of
Virtual air gap method
this method are its simple circuit, easily implement to
transformer [22]. By using sequential phase energization method
each phase is energized in sequential manner with uses of
Optimal closing method neutral grounding resistance [24] [25]. In prefluxing inrush
current reduction scheme reduce the remaining residual flux
which remaining in transformer core at startup instant of
Series compensation method transformer. Prefluxing equipment consist of capacitor, diode,
and fuse. This method does not need measuring of the residual
flux [26-29].
Asymmetrical winding
III. SIMULATION FOR INRUSH CURRENT INDICES

Point on wave switching method Transformer inrush currents are generates high magnitude
amount harmonic rich currents at the instant of transformer
energization. Inrush currents are categorized in three types [30].
Ultra low frequency power source Table IV shows the rating of transformer specially used for solar
power plant.

Bridge type Inrush current limiter TABLE IV. PARAMETERS OF TRANSFORMER

Transformer Primary Secondary Rating of Freq.


winding winding transformer
Grounding resistance at neutral point
voltage
Star-Star 11 kV 66 kV 20 MVA 50
Prefluxing method (Step up) Hz

Fig. 2. Methods of inrush current reduction 1. Energization inrush current: During Energization of
A concept of virtual air gap method is use of virtual air gap transformer, energized inrush current is result of re-energized
which equal thickness differs in function of controllable limits transformer due to residual flux is can be zero or depending on
changed to the alignment of magnetic circuit and the related de-energization time of transformer.
control system. The AGW (air gap windings) current is either set 2. Recovery inrush current: Recovery inrush current is flow
to a definite value using a current sensor or external source, in through transformer when supply voltage is restored after having
the main magnetization winding of the magnetic circuit [14]. By been reduced by system disturbances.
using controlled switching or optimal closing method required 3. Sympathetic inrush current: Sympathetic inrush current
the calculation of residual flux in core of transformer at de- occurs in transformer when multiple transformers are connected
energization instant. In this method to minimize the inrush in system and one of them is energized.
current not required the independent pole circuit breaker but it
required the calculation of residual flux of transformer [15] [16]. Power transformer of 11/66 kV, 20MVA has been simulated for
Series compensator technique is an inverter-based series the given switching instant, normal inrush, recovery inrush and
compensator which is comprised of a single-phase inverter and sympathetic inrush current difference has been achieved by
series transformer. This technique is easy to implement because suitable modelling in Matlab/ Simulink environment which are
it does not requires information about the parameters of
shown in Fig. 3(a), 3(b) and 3(c).
Simulated results which reflects the difference between By analyzing the simulated result of energization inrush
normal inrush current, recovery inrush current and sympathetic current in Fig. 4(a) show the inrush current peak is more than
inrush currents of transformer are as shown in Fig. 4(a), 4(b) and 1500A. Harmonics content and THD generated due to
4(c). energization inrush current shown in Table V.

TABLE. V. HARMONICS CONTENT AND THD OF ENERGIZATION INRUSH CURRENT


Phase THD 2nd harmonics 3rd harmonics
Phase R 90.92% 63.93% 31.32%
Phase Y 111.69% 72.98% 52.85%
Phase B 110.75% 73.49% 53.53%

Fig. 3 (a). Matlab/Simulink based model of energization inrush current

Fig. 4(a). Energization inrush current

Recovery inrush current for 20MVA transformer are


elaborated in 4(b). During starting (0 to 0.6 sec) is
characterization of energization inrush current. For single phase
fault (0.9 to 1.2 sec) has been achieved for rated power
transformer. After recover the fault recovery inrush current is
drawn by transformer after 1.2 sec as shown.

Fig. 3(b). Matlab/Simulink based model of recovery inrush current

Fig. 4(b). Recovery inrush current


Fig.3(c). Matlab/Simulink based model of sympathetic inrush current
Figure 4(c) indicates the waveform of transformer T1 current
having energization inrush current and sympathetic inrush
current (1 to 2 sec.) due to transformer T2 is energized. When
transformer T2 is energized after 1 sec. it is observed that a TABLE. VI. PEAK VOLTAGE INSTANT OF PHASE AT DIFFERENT FREQUENCY
value of sympathetic inrush is low as compare to energization Frequency Peak voltage Peak voltage Peak voltage
inrush current in terms of magnitude. (Hz) instant of Phase instant of Phase instant of Phase
R (msec.) Y (msec.) B (msec.)
48.5 5.150 12.016 18.883
49.0 5.100 11.900 18.700
49.5 5.050 11.783 18.516
50.0 5.000 11.666 18.333
50.5 4.950 11.550 18.150
51.0 4.900 11.433 18.700
51.5 4.854 11.326 17.798

In Fig. 5 show that the Matlab/Simulink model of sequential


switching method and in Fig. 6 show the waveform of current in
transformer using sequential switching method. Simulation is
carried out for 50Hz frequency and its phase R, Y, and B phase
switching instant is 5 msec. 11.666 msec. and 18.333 msec.
respectively.

Fig. 4(c). Sympathetic inrush current

IV. INRUSH CURRENT REDUCE BY SEQUENTIAL SWITCHING


METHOD
In this paper to reduce of transformer inrush current by using
sequential switching method is described. In this method
transformer each phase is energized at peak value of supply
voltage of each phase. An instant of Peak value of supply
voltage for each phase is different. For 50 Hz supply frequency
switching instant of phase R, Y, B is calculated as follows,
Therefore, 10 msec. time is required for half cycle (180
degree). 5 msec. is for 90 degree. For circuit breaker of phase Fig.5. Matlab simulation mode of sequential switching method
RYB closing instant is, firstly assume that we supply phase R
voltage at 90 (maximum) in 5 msec. Next phase Y is connected Figure 6 show that inrush current is reduce by effectively by
at 120 apart from phase R that means 90 + 120 = 210. Time using sequential switching method for 11/66 kV, 20 MVA
required for 0 to 210 is 11.666666 msec. After energization of transformer.
phase Y next phase B is energized at 120 apart from phase Y.
time required for 210+120=330. Time duration for 0 to 330
is 18.3333333 msec. [19]. But in actual supply frequency is not
remaining 50 Hz constant. For different frequency peak instant
of voltage is different. Some different value of frequency and
their switching instants are shown in Table VI.
Table VI show that the peak voltage instant of three phase for
different frequency. In proposed method, transformer must be
energized at peak value of phase voltage. In actual it is possible
by zero crossing detector such as IC TCA 785 and other zero
crossing detector. But the limitation of zero crossing detector
only use for particular value of frequency. Because, for different
value of frequency peak instant of voltage is different. For
example from Table V for 50 Hz frequency peak voltage instant
of phase R, Y and B phase is 5 msec. , 11.666 msec. and 18.333
msec. respectively.
Fig. 6: Inrush current reduce by sequential switching method
From Table VII show that the harmonics content after
implementation of sequential switching method.
TABLE VII. HARMONICS CONTENT AND THD AFTER IMPLEMENT OF SEQUENTIAL [11] Goran Petrovi, Tomislav Kili, Stanko Milun Remanent flux
SWITCHING METHOD measurement and optimal energization instant determination of power
transformer XVII IMEKO World Congress Metrology in the 3rd
Phase THD (%) 2nd order 3rd order Reduction
harmonics harmonics of Millennium, Dubrovnik, Croatia, June 22 27, 2003.
(%) (%) harmonics [12] Lin, C.E., Cheng, C.L., Huang, C.L., and Yeh, J.C. Investigation of
(%) magnetizing inrush current in transformers- Part I: Numerical
14.21 3.34 3.35 70.76 simulation IEEE Transactions on Power Delivery, Vol. 8, No. 1, pp.
R
246254, January 1993.
Y 24.92 6.35 2.11 86.77
[13] Al-Khalifah A. K. and Al-Saadany E. F. "Investigation of
B 37.52 2.99 2.92 73.23
magnetizing inrush current in a single-phase transformer" IEEE
Conference on Power Engineering, 2006 Large Engineering Systems,
pp. 165-171, July 26-28, 2006.
[14] V. Molcrette , J. L. Kotony, J. P. Swan and J. F. Brudny, "Reduction
V. CONCLUSION
of inrush current insingle-phase transformer using virtual air gap
During switching of solar plant, produces inrush current in technique" IEEE Trans.Magn. , vol. 34, pp.1192 -1194, 1998.
transformer effects the transformer winding, generates the [15] J. Brunke, K. Frohlich, Elimination of Transformer Inrush Currents
harmonics and power quality issues. Different techniques to by Controlled Switching-Part I: Theoretical considerations IEEE
reduce the inrush current are discussed in this paper. Sequential Transactions on Power Delivery vol 16 no.2 April 2001.
switching method is used because it does not required [16] J. Brunke, and K. Frohlich, Elimination of Transformer Inrush
calculation of residual flux and easy to implement in system. Currents by Controlled Switching Part II: Application and
From simulation and analysis of inrush current it conclude that performance considerations IEEE Transactions on Power Delivery
vol 16 no.2 April 2001.
harmonics reduce in R, Y, and B phase are 71%, 87%, and 73%
respectively
[17] Juei - Lung Shyu ," A Novel Control Strategy to Reduce Transformer
Inrush Currents by Series Compensator ", IEEE PEDS 2005.
References
[18] J. Chhen, T. Liang, C. Cheng, S. Chen, R. Lin and W. Yang,
[1] http://pib.nic.in/newsite/PrintRelease.aspx?relid=134497. Asymmetrical winding configuration to reduce inrush current with
appropriate short-circuit current in transformer IEE Proc.-Electr.
[2] Hemchandra Madhusudan Shertukde distributed photovoltaic grid Power Appl., Vol.152, No.3, May 2005.
transformer CRC publication book, 2014.
[3] Seo, HC & Kim, CH 2008, The analysis of power quality effects [19] F. Ali Asghar and K. P. Basu, "Reduction of three phase transformer
from the transformer inrush current: A case study of the Jeju power magnetizing inrush current by use of point on wave switching ", IEEE
station, Koria, Power and energy society general meeting-conversion Student Conference on Research and Development, Malaysia, pp-
and delivery of electrical energy in the 21st century 2008, IEEE, PA
368-370, Nov. 16-18 2009.
Pittsburgh, pp. 1-6, 20-24 July 2008.
[20] B. Kovan, F. de Leon, D. Czarkowski, Z. Zabar, and L. Birenbaum,
[4] M. Nagpal, T. G. Martinich, A. Moshref, K. Morison, and P. Mitigation of inrush currents in network transformers by reducing
Kundur,"Assessing and limiting impact of transformer inrush current the residual flux with an ultra-low-frequency power source, IEEE
on power quality," IEEE Transactions on Power Delivery, vol. 21, pp.
Trans. Power Del., vol. 26, no. 3, pp. 15631570, Jul. 2011.
890-896, 2006.
[5] Al-Khalifah A. K. and Al-Saadany E. F. "Investigation of [21] D. P. Balachandran, K. R. Sreerama and V. P. Shimnamol,
magnetizing inrush current in a single-phase transformer" IEEE "Transformer Inrush Current Redution by Power Frequency Low
Conference on Power Engineering, 2006 Large Engineering Systems, Voltage Signal Injection to the Tertiary Winding" IEEE conf
pp. 165-171, July 26-28, 2006. Powertech 07, pp.1953 -1958, 2007.

[6] Neves, W, Fernandes, D, Baltar, F, Rosentino, A, Saraiva, E, Delaiba, [22] Seyed Majid Madania, Mehrdad Rostamia, G.B. Gharehpetianb, Reza
A, Guimaraes, R, Lynce, M & de Oliveira, J 2011, A comparative Hagh Maram Improved bridge type inrush current limiter for
investigation of electromechanical stress on transformers caused by primary grounded transformers Electric Power Systems Research ,
inrush and short-circuited currents, International conference on vol.95, pp. 1 8, feb.2013.
electrical power quality and utilisation (EPQU), 2011, Libson, 17-19 [23] Yu Cui, Sami G. Abdulsalam, Shiuming Chen, Wilsun Xu, A
October 2011. Sequential Phase Energization Technique for Transformer Inrush
[7] Faiz, J., Ebrahimi, B.M., Abu-Elhaija, W. Computation of static and Current Reduction Part I: Simulation and Experimental Results
dynamic axial and radial forces on power transformer windings due to IEEE transactions on power delivery, vol. 20, no. 2, April 2005.
inrush and short circuit currents Applied Electrical Engineering and [24] Yu Cui, Sami G. Abdulsalam, Shiuming Chen, Wilsun Xu, A
Computing Technologies (AEECT), 2011 IEEE Conference, Jordan, Sequential Phase Energization Technique for Transformer Inrush
2011. Current ReductionPart II: Theoretical Analysis and Design Guide
[8] Fahrudin Mekic, Ramsis Girgis, Zoran Gajic, Ed teNyenhuis Power IEEE transactions on power delivery, vol. 20, no. 2, April 2005.
Transformer Characteristics and Their Effect on Protective Relays [25] D.I.Taylor, N.Fischer, J. D. Law, and B. K. Johnson, Using Lab-
33rd Western Protective Relay Conference, October 17-19, 2006. VIEW to measure transformer residual flux for inrush current
[9] Y.G. paithankar and S.R. bhide fundamental of power system reduction, presented at the North Amer. Power Symp., Starkville,
protection PHI Pvt. Ltd, 2003. MS, Oct. 46, 2009.

[10] S.V.kulkarni and S.A.kharpade Transformer engineering design and [26] Douglas I. Taylor, Joseph D. Law, Brian K. Johnson, and Normann
practice MARCEL DEKKER, INC. 2004. Fischer, Single phase transformer inrush current reduction using
prefluxing IEEE Transactions On Power Delivery, Vol. 27, No. 1,
January 2012.
[27] Douglos I. taylor system apparatus, and method for reducing inrush
current in a three phase transformer united states patent, patent no.
US 8,878,391 B2, date: nov, 4, 2014.
[28] V. Oiring de Castro Cezar, L-L. Rouve, J-L. Coulomb, F-X.
Zgainski, O. Chadebec, and B. Caillault Elimination of inrush
current using a new prefluxing method. Application to a single-phase
transformerIEEE, 2014.
[29] Vaddeboina, V, Taylor, G & Proudfoot, C 2012, Switching large
transformers on weak transmission netroks A real time case study,
Universities power engineering conference 2012, 47th international
conference, , IEEE, London, pp. 1-6, 4-7 September 2012.
[30] Patel Jatinkumar, Gupta, S.P. and Singh, S.P Comparison of Control
Techniques for rotor current control of Line-Excited Slip-ring IG for
WECS International Conference on Computational Intelligence and
Communication Networks, IEEE, 2010.

Vous aimerez peut-être aussi