Vous êtes sur la page 1sur 9

Banyan OTS MSB Voltage Absorbed load (kW) Load rating

Tag Load description


WBH Panel 1 400 3.5 3.5
WBH Panel 2 400 3.5 3.5
WBH Panel 3 400 3.5 3.5
L&SP DB 400 6.454287 9.22041
DB-AC-01 Metering DB 400 9.8287 10.92078
Motor Hoist 400 0.9 1.5
63A XP SSO 400 3.491814 34.91814
16A XP SSO 230 0.368 3.68
16A XP SSO 230 0.368 3.68
16A XP SSO 230 0.368 3.68
DB-UPSRM UPS Room DB 400 41.30086 45.88985
DB-AC-02 Spare DB 400 1.5 7.5
Spare 1 400 - -
Spare 2 400 - -
Spare 3 230 - -
Spare 4 230 - -
Spare 5 230 - -
Spare 6 230 - -
- -
- -
- -

L&SP DB Voltage Absorbed load (kW) Load rating


Tag Load description
7 No. 2x36W XP FLUOR (OTS) 230 0.5313 0.5313
7 No. 2x36W XP FLUOR (OTS) 230 0.5313 0.5313
2 No. 400W XP Flood light (OTS) 230 0.92 0.92
3 No. 2x36W FLUOR & 1 No. E ligt (SWRM) 230 0.3036 0.3036
6 No. 2x36W XP FLUOR (FILTER) 230 0.4554 0.4554
6 No. 2x36W XP FLUOR (WBH) 230 0.4554 0.4554
9 No. 2x36W XP FLUOR (PIG) 230 0.6831 0.6831
2 No. 2x36W XP FLUOR (MOV) 230 0.1518 0.1518
6 No. 2x36W XP FLUOR (WBH) 230 0.4554 0.4554
1 No. 2x8W Exit light (SWRM) 230 0.016 0.016
2 No. 2x36W E (XP)FLUOR (OTS) 230 0.1518 0.1518
2 No. 13A XP SSO (OTS) 230 5.98 5.98
2 No. 13A Twin SSO (SWRM) 230 11.96 11.96
7 No. CCTV SSO 230 0.0395 0.0395
3 No. 500W CCTV Halogen spotlight 230 1.5 1.5
3 No. 500W CCTV Halogen spotlight 230 1.5 1.5
5 No. 400W floodlight 230 2.3 2.3
5 No. 400W floodlight 230 2.3 2.3
7 No. 250W st light 230 2.898 2.898
6 No. 250W st light 230 2.484 2.484
Spare1 230
Spare2 230
Spare3 230
Spare4 230
Spare5 230
Spare6 230
Spare7 230

Metering DB Voltage Absorbed load (kW) Load rating


Tag Load description
SCADA RTU 230 0.69 0.69
SCADA RTU 230 0.69 0.69
Security RTU 230 0.46 0.46
CCTV system panel (DVR) 230 0.09 0.09
CP transducer 230 0.07 0.07
Battery charger unit 230 1.1 1.1
Fire alarm panel 230 0.45 0.5
FIDS 230 0.063 0.07
Air conditioner 1 230 2.24 5.6
Air conditioner 2 230 2.96 7.4
DB-DC-01 230 0.43 0.43
DB-DC-01 230 1.1 1.1
Spare1 230 0 0
Spare2 230 0 0
Spare3 230 0 0
Spare4 230 0 0

Spare DB Voltage Absorbed load (kW) Load rating


Tag Load description
UPS 400 24.29259 40.48765
DB-UPSRM UPS Room L&SP DB 400 27.53391 45.88985

UPS Voltage Absorbed load (kW) Load rating


Tag Load description
S25-50 DN700 L120-190 U/G MOV near gate 400 4.112 5.14
S25-50A DN300IQ20 bypass 400 0.648 0.81
S25-51 DN700 L120-190 PIG MOV 400 4.112 5.14
S25-51A DN300IQ20 bypass PIG MOV 400 0.648 0.81
S25-73 DN600 IQ 40 WBH MOV 400 2.352 2.94
S25-75 DN600 IQ 40 WBH MOV 400 2.352 2.94
S25-77 DN600 IQ 40 WBH MOV 400 2.352 2.94
S25-1 DN600 IQ40F25B4 TJ MOV 400 2.592 3.24
S25-1A DN300 IQ20F14B4 bypass TJ MOV 400 0.648 0.81
S25-86 DN700 IQ40F25B4 Interlink MOV 400 2.592 3.24
S25-86A DN300 IQ20F14B4 bypass interlink 400 0.648 0.81
S25-85 DN700 IQ40F25B4 U/G MOV 400 2.592 3.24
S25-85A DN300 IQ20F14B4 bypass U/G MOV 400 0.648 0.81
S25-96 DN700 IQ40F25B4 U/G MOV 400 2.592 3.24
S25-96A DN300 IQ20F14B4 bypass U/G MOV 400 0.648 0.81
S25-97 DN600 IQ40F25B4 U/G Interlink MOV 400 2.592 3.24
SCADA RTU 400 0.69 0.69
DC DB panel 400 1.5 1.5
Fire alarm panel 400 0.5 0.5

DB-UPSRM-01 Voltage Absorbed load (kW) Load rating


Tag Load description
UPS 400 24.29259 40.48765
Air-cond1 400 6.3 7
Air-cond2 400 7 7
Battery ventilation fan1 400 0.2 0.2
Battery ventilation fan2 400 0.2 0.2
3 no. 13A Twin SSO 230 3.588 17.94
3 no. 2x36W FLUOR (UPS RM) + 1 no. E L 230 0.3036 0.3036
3 no. 2x36W FLUOR (BATT RM) + 1 no. E L 230 0.3036 0.3036
2 No. 2x8W Exit light (UPS + BATT RM) 230 0.032 0.032
g (kW) Load/diversity factor Efficiency PF Consumed load
kW kVA
1 1 0.9 3.5 3.888889
1 1 0.9 3.5 3.888889
1 1 0.9 3.5 3.888889
0.7 0.9 0.8 7.17143 8.964288
0.9 0.9 0.9 10.92078 12.1342
0.6 0.9 0.8 1 1.25
0.1 0.9 0.8 3.879794 4.849742 63
0.1 0.9 0.8 0.408889 0.511111 16
0.1 0.9 0.8 0.408889 0.511111 16
0.1 0.9 0.8 0.408889 0.511111 16
0.9 0.9 0.8 45.88985 57.36231
0.2 0.9 0.8 1.666667 2.083333
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
Total 82.25518 99.84387 ( 144.1122

Main incoming MCCB AT 150 A

g (kW) Load/diversity factor Efficiency PF Consumed load


kW kVA A
1 1 0.9 0.5313 0.590333 0.33
1 1 0.9 0.5313 0.590333 0.33
1 1 0.9 0.92 1.022222 2
1 1 0.9 0.3036 0.337333 0.33
1 1 0.9 0.4554 0.506 0.33
1 1 0.9 0.4554 0.506 0.33
1 1 0.9 0.6831 0.759 0.33
1 1 0.9 0.1518 0.168667 0.33
1 1 0.9 0.4554 0.506 0.33
1 1 0.9 0.016 0.017778
1 1 0.9 0.1518 0.168667 0.33
1 1 0.9 5.98 6.644444 13
1 1 0.9 11.96 13.28889 26
1 1 0.9 0.0395 0.043889
1 1 0.9 1.5 1.666667
1 1 0.9 1.5 1.666667
1 1 0.9 2.3 2.555556 2
1 1 0.9 2.3 2.555556 2
1 1 0.9 2.898 3.22 1.8
1 1 0.9 2.484 2.76 1.8

Total 35.6166 39.574 ( 57.12015


9.22041 3.766067 ( 5.435849

Adjusted load 100% 3.0555 3.395 MCCB 40


50% 0.1518 0.168667
30% 4.29525 0.1518
10% 1.71786 0.0506
9.22041 3.766067

g (kW) Load/diversity factor Efficiency PF Consumed load


kW kVA
1 1 0.9 0.69 0.766667
1 1 0.9 0.69 0.766667
1 1 0.9 0.46 0.511111
1 1 0.9 0.09 0.1
1 1 0.9 0.07 0.077778
1 1 0.9 1.1 1.222222
0.9 1 0.9 0.45 0.5
0.9 1 0.9 0.063 0.07
0.4 0.9 0.8 2.488889 3.111111
0.4 0.9 0.8 3.288889 4.111111
1 1 0.9 0.43 0.477778
1 1 0.9 1.1 1.222222
1 1 0.9 0 0
1 1 0.9 0 0
1 1 0.9 0 0
1 1 0.9 0 0
Total 10.92078 12.93667 ( 18.67247
40

g (kW) Load/diversity factor Efficiency PF Consumed load


kW kVA
0.6 0.95 0.8 25.57115 31.96393
0.6 0.95 0.8 28.98306 36.22883
Total 54.55421 68.19276 ( 98.42777
63

g (kW) Load/diversity factor Efficiency PF Consumed load


kW kVA
0.8 0.85 0.85 4.837647 5.691349 6.982542
0.8 0.85 0.85 0.762353 0.896886 1.100362
0.8 0.85 0.85 4.837647 5.691349 6.982542
0.8 0.85 0.85 0.762353 0.896886 1.100362
0.8 0.85 0.85 2.767059 3.255363 3.993905
0.8 0.85 0.85 2.767059 3.255363 3.993905
0.8 0.85 0.85 2.767059 3.255363 3.993905
0.8 0.85 0.85 3.049412 3.587543 4.401447
0.8 0.85 0.85 0.762353 0.896886 1.100362
0.8 0.85 0.85 3.049412 3.587543 4.401447
0.8 0.85 0.85 0.762353 0.896886 1.100362
0.8 0.85 0.85 3.049412 3.587543 4.401447
0.8 0.85 0.85 0.762353 0.896886 1.100362
0.8 0.85 0.85 3.049412 3.587543 4.401447
0.8 0.85 0.85 0.762353 0.896886 1.100362
0.8 0.85 0.85 3.049412 3.587543 4.401447
1 1 0.9 0.69 0.766667
1 1 0.9 1.5 1.666667
1 1 0.9 0.5 0.555556
Total 40.48765 47.45671 ( 68.49786
18.96294 22.13353 ( 31.94699
10.57706 12.26778 ( 17.70702

22.75553 26.56023 ( 38.33639

80
Adjusted load 100% 18.96294 22.13353
50%
30%
10%
18.96294 22.13353

g (kW) Load/diversity factor Efficiency PF Consumed load


kW kVA
0.6 0.95 0.8 25.57115 31.96393
0.9 0.85 0.85 7.411765 8.719723
0.9 0.85 0.85 8.235294 9.688581
1 0.9 0.85 0.222222 0.261438
1 0.9 0.85 0.222222 0.261438
0.2 1 0.9 3.588 3.986667
1 1 0.9 0.3036 0.337333
1 1 0.9 0.3036 0.337333
1 1 0.9 0.032 0.035556
Total 45.88985 55.592 ( 80.24014
80
34.91814
3.68
3.68
3.68

A)

kW
0.0759
0.0759
0.46
0.0759
0.0759
0.0759
0.0759
0.0759
0.0759
0.016
0.0759
2.99
5.98

0.5
0.5
0.46
0.46
0.414
0.414

A)
A)

AT

A)
AT

A)
AT
A) Actual connected
A) Isolation of selected MOVs + I&C
A) Isolation of 2 MOVs + I&C

A) Contingency 20%

AT

A)
AT