Vous êtes sur la page 1sur 16

Worldwide

www.tyco-fire.com
Contacts

Model PRV-1 Pressure Reducing Valve


Pilot Operated, Globe and Angle Body Styles

General NOTICE
The TYCO Model PRV-1 Pressure
Description Reducing Valves described herein must
be installed and maintained in compli-
The TYCO Model PRV-1 Pressure ance with this document and with the
Reducing Valves, 2 through 8 Inch applicable standards of the National
(DN50 through DN200), are factory- Fire Protection Association, in addi-
assembled and fully trimmed valve tion to the standards of any authorities
arrangements for pressure control. having jurisdiction. Failure to do so
They are used on water filled pipe may impair the performance of these
where it is necessary to reduce a devices.
higher inlet pressure to a lower delivery
pressure under static and/or residual Owners are responsible for maintaining
flowing conditions. The Model PRV-1 their fire protection system and devices
Valve is intended to automatically main- in proper operating condition. Contact
tain the outlet set pressure (static and the installing contractor or sprinkler
residual) within a close range, regard- manufacturer with any questions.
less of fluctuations in the higher pres- Due to the flow regulating characteris-
sure inlet line or varying flow rates. tic of this device, its impact on system
The Model PRV-1 Valve is provided with hydraulics should be carefully consid-
a factory outlet set pressure of 125 ered, especially when retrofitted into
psi (8,6 bar); however, it may be field existing systems.
set to a nominal outlet set pressure
of 80 to 225 psi (5,5 to 15,5 bar) per its WARNING
FM Approval or 80 to 150 psi (5,5 to Adjustment of the Needle Valve is
10,3 bar) per its UL Listing. factory set and must not be altered.
Typical applications
Within the main header (Ref. Figure 1)
supplying wet pipe, dry pipe, deluge,
Technical
or preaction system risers, and/or a
standpipe system supplying hose
Data
Approvals
connections UL and C-UL Listed
As part of a sectional floor control FM Approved
assembly (Ref. Figure 2) supply- Maximum Inlet Pressure
The UL Listing is based on:
ing sprinkler systems, and/or hose 250 psi (17,2 bar)
stations Installation requirements referenced in Factory Outlet Set Pressure
the Standard for Installation of Sprinkler 125 psi (8,6 bar)
Features Systems, NFPA 13, or the Standard
Can be installed in vertical or hori- for Installation of Standpipe and Hose Field Outlet Set Pressure Range
zontal orientation Valves, NFPA 14, as applicable. 80 to 225 psi (5,5 to 15,5 bar) per FM
Approval, or 80 to 150 psi (5,5 to 10,3 bar)
Eliminates any required bleeding Inspection, testing, and maintenance per UL Listing
of trapped air from the diaphragm requirements referenced in the
chamber during installation Standard for Inspection, Testing, and Pressure Loss With Inlet Pressure
Maintenance of Water-Based Fire Above Set Pressure
Globe or angle pattern Protection Systems, NFPA 25. The inlet pressure minus the outlet set
Accurate pressure control pressure equals pressure loss. For
Filed-setting of the Model PRV-1 Valve example, assuming that the inlet flowing
RILSAN Red coated internal and to provide required outlet pressures and pressure is 225 psi (15,5 bar) and the field
external flows for the given application. outlet set pressure is 130 psi (9,0 bar),
Testing of the Model PRV-1 Valve after the pressure loss is 95 psi (6,5 bar).
One piece, one moving par t
installation in accordance with NFPA 13 Pressure Loss with Inlet Pressure
diaphragm
and/or NFPA 14 as applicable. Below Set Pressure
In-line service Testing the Model PRV-1 Valve tested Refer to Graphs A through E. (These
One pilot valve sub-assembly pro- periodically thereafter in accordance graphs are a requirement of UL and
vides for any outlet set pressure, with NFPA 25. should be used as reference only.)
that is, 80 to 225 psi (5,5 to 15,5 bar)

Page 1 of 16 FEBRUARY 2017 TFP1580


TFP1580
Page 2 of 16

Rated Flowing Range WET PIPE DRY PIPE


2 inch 0 to 250 GPM
SPRINKLER SPRINKLER
(DN50) (0 to 946 LPM) RISER RISER
3 inch 0 to 550 GPM
MAIN MAIN
(DN80) . . . . . . . . . . . . . . . (0 to 2080 LPM)
DRAIN DRAIN
4 inch 0 to 1000 GPM
(DN100) . . . . . . . . . . . . . . (0 to 3785 LPM) MAIN
PRV-1 CONTROL MAIN
6 inch 0 to 2200 GPM VALVE RELIEF HOSE
CONTROL
(DN150) . . . . . . . . . . . . . . (0 to 8325 LPM) MAIN VALVE STATIONS
VALVE
8 inch 0 to 4000 GPM HEADER
(DN200) . . . . . . . . . . . . . (0 to 15140 LPM)
End Connections
Threaded end connections are avail- PRV-1
able as NPT threaded or threaded
per ISO 7-1.
Flanged end connections are avail- FIGURE 1
able as drilled per Table C. TYPICAL MAIN HEADER APPLICATION
Grooved end connections fol-
low industr y standard groove
specifications.

Materials of RELIEF VALVE

Construction
(Refer to Figure 3) PRV-1
The Body is RILSAN polyamide 11 SPRINKLERS
coated, ductile iron per ASTM A 536- SECTIONAL CHECK
77, Grade 65-45-12. FLOOR VALVE RISER
The Diaphragm Cover is RILSAN CONTROL
MANIFOLD
polyamide 11 coated, ductile iron SECTIONAL
HOSE CONTROL OR
per ASTM A 536-77, Grade 65-45-12. ZONE
VALVE VALVE
The Diaphragm is nylon fabric-rein- CHECK
forced, natural rubber per ASTM
D2000. Diaphragm Cover Fasteners
are galvanized carbon steel. RELIEF VALVE
The Pilot Valve is brass and stain-
less steel with nylon fabric-rein- Z
forced, natural rubber per ASTM D
2000 diaphragm. PRV-1
SPRINKLERS
The Strainer is brass and stainless
steel. SECTIONAL CHECK
FLOOR VALVE
Pressure Gauges have a 2-1/2 inch CONTROL
(65 mm) diameter, stainless steel SECTIONAL
case, and 0 to 350 psi (25 bar) pres- HOSE CONTROL
sure rating. VALVE VALVE
Tube, Fittings, and Needle Valve are
copper, brass, and stainless steel.

FIGURE 2
TYPICAL SECTIONAL FLOOR CONTROL APPLICATION
TFP1580
Page 3 of 12

Nominal Valve Size


Body End
Style Connection 2 Inch 3 Inch 4 Inch 6 Inch 8 Inch
(DN50) (DN80) (DN100) (DN150) (DN200)

Thread x Thread N/A N/A N/A N/A

Globe Groove x Groove

Flange x Flange N/A N/A

= Available N/A = Not Available


TABLE A
AVAILABLE SIZES AND CONFIGURATIONS
NORTH AMERICA

Nominal Valve Size


Body End
Style Connection 2 Inch 3 Inch 4 Inch 6 Inch 8 Inch
(DN50) (DN80) (DN100) (DN150) (DN200)

Thread x Thread N/A N/A N/A

Globe Groove x Groove N/A

Flange x Flange N/A

Thread x Thread N/A N/A N/A

Angle Groove x Groove N/A

Flange x Flange N/A N/A

= Available N/A = Not Available


TABLE B
AVAILABLE SIZES AND CONFIGURATIONS
SOUTH AND CENTRAL AMERICA AND EASTERN HEMISPHERE

Nominal Flange Drilling Specification


Valve Nominal Installation Dimensions in Inches and (mm)
Size ANSI B16.11a ISO 7005-2 ISO 7005-2 JIS B 2210 AS 2129
Inches (Class 125) (PN10)2 b (PN16)3c (10K) (Table E) Dim. A
(DN) Bolt Circle
A B N A B N A B N A B N A B N
Diameter
3 6.00 0.75 4 6.30 0.75 8 5.90 0.59 8 5.75 0.71 4
(DN80) (152,4) (19,0) (160,0) (19,0) (150,0) (15,0) (146,0) (18,0)
USE Dim. B
4 7.50 0.75 7.09 0.75 6.89 0.60 7.00 0.71 Bolt Hole
(DN100) (190,5) (19,0) 8 ISO 7005-2 (180,0) (19,0) 8 (175,0) (15,0) 8 178,0) (18,0) 8
(PN16) Diameter
6 9.50 0.88 9.45 0.91 9.45 0.75 9.25 0.87
(DN150) (241,3) (22,2) 8 (240,0) (23,0) 8 (240,0) (19,0) 8 (235) (22,0) 8
Qty. N
8 11.75 0.88 11.61 0.91 11.61 0.91 12 11.42 0.75 12 11.50 0.87 Number of
(DN200) (298,5) (22,2) 8 (295,0) (23,0) 8 (295,0) 8
(23,0) (290,0) (19,0) (292,0) (22,0) Bolt Holes
Notes:
a. Same drilling as for ANSI B16.5 (Class 150) and ANSI B16.42 (Class 150)
b. Same drilling as for BS 4504 Section 3.2 (PN10) and DIN 2532 (PN10)
c. Same drilling as for BS 4504 Section 3.2 (PN16) and DIN 2532 (PN16)

TABLE C
DIMENSIONAL SPECIFICATION FOR SELECTION OF FLANGE DRILLING
TFP1580
Page 4 of 16

VALVE PARTS
DIAPHRAGM
NO. DESCRIPTION QTY. KIT 7 11 12 3 2
CHAMBER
1 Valve Body . . . . . . . . . . . 1 NR
2 Diaphragm . . . . . . . . . . . 1 (a) OUTLET
3 Diaphragm Cover. . . . . . . 1 NR PRESSURE
4, 5, 6
4 Flat Washer, GAUGE
2 Inch Valve, M12 . . . . . . 4 CH
3 & 4 Inch Valves, M16 . . 4 CH
6 & 8 Inch Valves, M16 . . 8 CH
5 Hex Bolt,
2 Inch Valve, M12 x 35 . . 4 CH 8
3 & 4 Inch Valves,
M16 x 55 . . . . . . . . . . . . . 4 CH
6 Inch Valve, M16 x 45 . . 8 CH
8 Inch Valve, M16 x 55 . . 8 CH DOWNSTREAM UPSTREAM
6 Hex Nut, M16, OUTLET INLET
4 Inch Valve Only . . . . . . . 4 CH CAVITY CAVITY
7 Pilot Valve . . . . . . . . . . . . 1 (b)
8 Water Pressure Gauge . . 2 (c)
9 Strainer . . . . . . . . . . . . . . 1 (d) 8
10 Pressure Sensor Insert . . 1 (e)
11 Tubing and Fittings . . . . . 1 (f) INLET
12 Needle Valve . . . . . . . . . . 1 (g) PRESSURE
REPLACEMENT PART KITS
GAUGE
PRESSURE STRAINER
KIT DESCRIPTION P/N SENSOR INSERT (SEE DETAIL)
1
(a) Diaphragm, (SEE DETAIL)
Fits Either Body Style, GLOBE BODY STYLE
Includes Item 2 only:
2 Inch Valves . . . . . . . . . . . . . 92-570-2-011 OUTLET CAVITY INLET CAVITY
3 Inch Valves . . . . . . . . . . . . . 92-570-2-012 INTERIOR 1 11 INTERIOR 1 11
4 Inch Valves . . . . . . . . . . . . . 92-570-2-013
6 Inch Valves . . . . . . . . . . . . . 92-570-2-014 SENSOR
8 Inch Valves . . . . . . . . . . . . . 92-570-2-015 INLET FACES
(b) Pilot Valve . . . . . . . . . . . . . . . 92-570-2-200 DOWNSTREAM
(c) Water Pressure Gauge . . . . . 92-570-2-211 9
10 PRESSURE SENSOR STRAINER
(d) Strainer:
2, 3, & 4 Inch Valves . . . . . . . 92-570-2-202 INSERT DETAIL DETAIL
6 & 8 Inch Valves . . . . . . . . . . 92-570-2-209
(e) Pressure Sensor Insert:
2 Inch Valve . . . . . . . . . . . . . . 92-570-2-203 DIAPHRAGM
7 11 12 3 2
3 Inch Valve . . . . . . . . . . . . . . 92-570-2-204 CHAMBER
4 Inch Valve . . . . . . . . . . . . . . 92-570-2-205 OUTLET
6 Inch Valve . . . . . . . . . . . . . . 92-570-2-206 PRESSURE
8 Inch Valve . . . . . . . . . . . . . . 92-570-2-207 GAUGE 4, 5, 6
(f) Tubing and Fitting Kit,
Excludes Items 7, 8, 9, 10 and 12
Globe Style Valve:
2 Inch Valve . . . . . . . . . . . . . . 92-570-3-001
3 Inch Valve . . . . . . . . . . . . . . 92-570-3-002
4 Inch Valve . . . . . . . . . . . . . . 92-570-3-003 8
6 Inch Valve . . . . . . . . . . . . . . 92-570-3-004
8 Inch Valve . . . . . . . . . . . . . . 92-570-3-005
Angle Style Valve:
2 Inch Valve . . . . . . . . . . . . . . 92-571-3-001
3 Inch Valve . . . . . . . . . . . . . . 92-571-3-002 DOWNSTREAM
INLET
4 Inch Valve . . . . . . . . . . . . . . 92-571-3-003 OUTLET
6 Inch Valve . . . . . . . . . . . . . . 92-571-3-004 PRESSURE
CAVITY
(g) Needle Valve . . . . . . . . . . . . . 92-570-2-212 GAUGE

NOTES: 8
1. NR - Not Replaceable ORIENT
2. CH - Common Hardware DIAPHRAGM TAB
3. Install Item 8 in field UPSTREAM
PERPENDICULAR
INLET
TO OUTLET
CAVITY

1
OUTLET OUTLET PRESSURE
SENSOR INSERT STRAINER
(SEE DETAIL) (SEE DETAIL)
GLOBE ANGLE ANGLE BODY STYLE
FIGURE 3
MODEL PRV-1 PRESSURE REDUCING VALVE
ASSEMBLY
TFP1580
Page 5 of 12

TAMPER NOTES:
CAP 1. SOME PARTS SHOWN IN
PILOT ALTERED POSITIONS AND
VALVE ADJUSTING ORIENTATIONS TO
SCREW NEEDLE VALVE CLARIFY FUNCTION
OUTLET (FACTORY SET,
DO NOT READJUST) 2. ELBOW AND TEE FITTINGS
PRESSURE LOCKNUT
VARY BY VALVE SIZE AND
GAUGE BODY TYPE
REGULATING COMPRESSION
SPRING EXIT FITTING
FLOW
SUPPLY
DIAPHRAGM LINE
CHAMBER
COMPRESSION
PILOT FITTING
VALVE SYSTEM
DIAPHRAGM WATER INLET
WATERFLOW SUPPLY PRESSURE
PILOT TO SYSTEM PRESSURE GAUGE
VALVE
SEAT

SENSING
LINE
PRESSURE STRAINER
SENSOR
INSERT SUPPLY COMPRESSION
PRESSURE
LINE FITTING
SENSOR INSERT PRV-1
(INLET FACES VALVE SEAT VALVE
DOWNSTREAM) BODY PRV-1 BODY
DIAPHRAGM

DOWNSTREAM UPSTREAM
OUTLET CAVITY INLET CAVITY
OUTLET CAVITY SENSING INLET CAVITY
INTERIOR LINE INTERIOR STRAINER GAUGE
FIGURE 4
MODEL PRV-1 PRESSURE REDUCING VALVE
OPERATION

Operation pressure falls below the set pressure


of the spring, exit flow from the Dia-
As the flow demand continues down-
stream of the Model PRV-1 Valve and
phragm Chamber through the Pilot the set pressure is met, the Pilot
With reference to Figure 4, the system
Valve to the Model PRV-1 Valve outlet Valve Seat closes. As the Pilot Valve
water supply pressure from the inlet
cavity resumes and pressure in the Dia- Seat closes to reduce the opening,
cavity of the Model PRV-1 Valve enters
phragm Chamber decreases. pressure is trapped in the Diaphragm
the Diaphragm Chamber through
Chamber at a point that allows the
a Strainer and Needle Valve. The The regulated flow through the Pilot
Diaphragm to remain lifted from the
factory set Needle Valve provides the Valve decreases and increases the
Model PRV-1 Valve Seat to retain the
required orifice size for the supply line pressure in the diaphragm chamber to
downstream set pressure.
to the Diaphragm Chamber to optimize sufficiently open and close the Model
performance. PRV-1 Valve, as required, to regulate Should the downstream pressure
the downstream set pressure. start to fall below the set pressure,
Exit flow from the Diaphragm Chamber
the Pilot Valve Seat re-opens to allow
through the Pilot Valve is controlled by The operation sequence is as follows:
for a decrease in pressure in the Dia-
a regulating spring that is factory set, When there is no flow demand down- phragm Chamber to allow the Model
and subsequently field adjustable, to stream of the Model PRV-1 Valve, the PRV-1 Valve to open further and then
the desired downstream set pressure Seat is closed and the Pilot Valve once again establish the downstream
that is to be maintained. A sensing line Seat is closed. With the Pilot Valve set pressure.
connects the outlet of the Pilot Valve to Seat closed, pressure is trapped in
the system piping downstream of the When the downstream pressure is
the Diaphragm Chamber to seat the
Model PRV-1 Valve via the Pressure at or above the set pressure and
Diaphragm and the Model PRV-1
Sensor Insert in the outlet cavity. assuming there is a flow demand
Valve remains closed.
downstream of the Model PRV-1
When the downstream pressure rises When there is a flow demand down- Valve, the Pilot Valve Seat is closed
above the set pressure of the spring, stream of the Model PRV-1 Valve and to trap a sufficient pressure in the
exit flow from the Diaphragm Chamber the outlet pressure drops below the Diaphragm Chamber to allow the
through the Pilot Valve to the Model set pressure, the Pilot Valve Seat Model PRV-1 Valve to remain open
PRV-1 Valve outlet cavity is stopped opens to relieve pressure from the to provide the set pressure.
and pressure increases in the Dia- Diaphragm Chamber allowing the
phragm Chamber. When downstream Model PRV-1 Valve to open.
TFP1580
Page 6 of 16

Design When reducing pressure for a sprin-


kler system, means shall be provided
For the purposes of the following
instruction, the opening of a flow test
Considerations downstream of the Model PRV-1
Valve to facilitate a flow test at the
valve simulates either the sprinkler
demand or hose stream demand, as
sprinkler system demand. applicable. The sprinkler demand or
The following items must be consid-
hose stream demand must be at least
Installation
ered and applied accordingly for an
installation that will be using the Model 50 GPM (190 LPM) for 2 to 6 inch (DN50
PRV-1 Pressure Reducing Valve: to DN150) valves and at least 100 GPM
The TYCO Model PRV-1 Pressure (380 LPM) for 8 inch (DN200) valves.
The Model PRV-1 Valve may be Reducing Valve must be installed with
installed vertically or horizontally and There is no need to vent any trapped air
the flow arrow located on the Dia- from the Diaphragm Chamber.
in any orientation without affecting its phragm Cover pointing in the intended
operating efficiency. When planning direction of flow. Installation dimen- Filling the System
the positioning of the Model PRV-1 sions are provided in Figures 5 and 6. Step 1. Install gauges at the Pilot Valve
Valve, it is recommended that con- and inlet Sensing Line. Apply thread-
sideration be given to the viewing of Before the Model PRV-1 Valve is
installed, pipe lines should be flushed sealant to the male end of the threads.
the pressure gauges. Consideration Ensure the pips on the pressure gauges
should also be given to positioning of all chips, scale and foreign matter.
Care must be exercised to assure are in the upright position.
the Model PRV-1 Valve so that the
diaphragm cover is facing up. With that the trim is not damaged during Step 2. Verify that downstream drain
the cover facing up, internal access installation. valves are closed and that there are no
is more easily achieved. leaks.
NOTICE Step 3. Partially open a valve or valves
The Model PRV-1 Valve must be in
an area that is easily accessible for Do not lift the valve by its trim. Oth- at the end of the system (such as, an
maintenance purposes, not subject erwise, the trim may be damaged and inspectors test connection on a wet
to freezing temperatures, and not impair system operation. The inlet pipe system) to allow trapped air to
subject to physical damage. and outlet connections must be made escape when filling the system.
based on the direction of flow arrow
The valve is designed for fresh water provided on the Diaphragm Cover. Step 4. Slowly and partially open the
service. When corrosive atmo- The valve cannot operate if connected water supply control valve feeding the
spheres and/or contaminated water backwards. Model PRV-1 Valve.
supplies are present, it is the owners Step 5. After the system fills with water,
responsibility to verify compatibility Do not alter the trim. Altering the trim
may render the valve ineffective and close the valve or valves that had been
with the pressure reducing valve, partially opened in Step 2.
pilot valve, and trim. impair the system operation.
Step 6. Completely open the main
The difference between the water
supply pressure and the desired Placing the water supply control valve feeding the
Model PRV-1 Valve.
outlet (downstream) pressure must
be 25 psi (1,7 bar) or greater per its
FM Approval or 50 psi (3,4 bar) or
Valve Adjusting Downstream Pressure
greater per its UL Listing. The differ-
ential maintains accuracy control of
in Service NOTICE
After any downstream pressure adjust-
the discharging pressure over the full Perform the following 13 Steps when ment, the following items are to be
rated flowing range. placing the TYCO Model PRV-1 Pres- recorded on a tag attached to the valve:
sure Reducing Valve in service.
Cavitation may occur when the inlet Valve installation location
pressure is greater than twice the
set pressure. For this case, the WARNING Inlet static pressure
pressure should be reduced in two Downstream pressure adjustment is Outlet static pressure
steps by using two Model PRV-1 only to be performed by experienced
Valves in series. personnel who understand the impact Inlet residual pressure
When reducing pressure for a sprin- of adjusting the downstream pressure Outlet residual pressure
kler system, a 1/2 inch (DN15) or and who take full responsibility of the
readjustment from the factory setting. Intended outlet flow
larger relief valve shall be located
downstream of the Model PRV-1 The Pilot Valve is provided with a The tag is not to be removed until after
Valve. The relief valve shall be set at Tamper Cap, which upon removal will the system has been accepted by the
a pressure equal to the lowest pres- allow for field adjustment by using the authority having jurisdiction. It is rec-
sure rated component downstream Adjusting Screw. ommended that the tag not be removed
of the Model PRV-1 Valve. even after acceptance by the author-
Adjustment of the Needle Valve is ity having jurisdiction unless another
Note: FM Approval is based on the factory set and must not be altered. means of record keeping is maintained.
use of the 1/2 inch Watts Regulator, Per the requirements of NFPA 13, a Step 1. Remove the Tamper Cap from
Series 530C Pressure Relief Valve. means shall be provided downstream the Pilot Valve by first loosening its set
When reducing pressure for a sprin- of the Model PRV-1 Valve to simulate screw and then unscrewing the Tamper
kler system, a listed indicating valve the sprinkler system demand. In the Cap.
shall be provided on the inlet side of case of hose stations, the opening of a
the Model PRV-1 Valve. hose valve or multiple hose valves, as Step 2. Open the flow test valve to
required, will be necessary to simulate simulate either the desired sprinkler
hose stream demand. demand or hose stream demand.
TFP1580
Page 7 of 12

Step 3. If surging flow occurs, attempt Automatic sprinkler systems are rec- Strainer Maintenance
to bleed trapped air from the system via ommended to be inspected, tested, Prior to performing strainer mainte-
the inspectors test valve and any other and maintained by a qualified Inspec- nance, the Model PRV-1 Valve must
valve that can vent trapped air. tion Service in accordance with local be taken out of service and completely
Step 4. Loosen the locknut on the requirements and/or national code. drained. Be prepared for small amounts
adjusting screw of the Pilot Valve. of residual liquid when disconnecting
The Model PRV-1 Pressure Reducing
any trim part. Refer to Figure 4 to iden-
Step 5. Turn the adjusting screw clock- Valve requires no lubrication, packing
tify parts and key features.
wise to increase outlet pressure or or preventative maintenance; however,
counterclockwise to decrease outlet replacement of the diaphragm every Step 1. Loosen compression fitting on
pressure. five years is recommended. supply line at needle valve inlet trim.
Step 6. After achieving the desired per- Flow Tests Step 2. Disconnect compression fitting
formance, tighten the locknut on the Flow tests per NFPA are required every on supply line at strainer outlet and
adjusting screw. five years, at which point the outlet swing supply line away for access.
pressure is compared to previous tests. Step 3. Remove inlet pressure gauge
Step 7. Close the flow test valve. If necessary the Model PRV-1 Valve can
Observe the outlet pressure gauge and and trim as sub-assembly from strainer
be readjusted following the Placing the outlet.
compare to the required set pressure. Valve in Service section. If the desired
If the required set pressure is not pressure cannot be achieved, the Dia- Note: When removing, do not grip gauge
achieved, repeat Step 8 and proceed itself, loosen sub-assembly by wrench on
phragm and/or Pilot Valve should be
accordingly. fitting closest to strainer only.
replaced.
Replace the Tamper Cap and tighten Step. 4 Remove strainer from valve
its set screw. Diaphragm Replacement
Prior to replacing the Diaphragm, the body.
The pressure reducing valve is now set Model PRV-1 Valve must be taken out Step 5. Disassemble strainer for clean-
for service. of service and completely drained. ing. Remove end lock washer and slide
Due to the spring tolerance within the With reference to Figure 3, the Dia- screen off strainer body. Clean screen
Pilot Valve, it may be necessary to phragm Tab is oriented perpendicu- and body.
alternate back and forth between resid- lar to the outlet flow. When reinstalling
the Diaphragm Cover, the Diaphragm Step 6. Reassemble screen onto body
ual and static conditions to achieve the and secure with lock washer.
desired set pressure for both residual Cover Fasteners must be uniformly
and static conditions. and securely tightened using a cross- Note: Prior to installing strainer and gauge
draw sequence. After tightening, and trim sub-assembly, clean all exposed
Care and double check to make certain that all
of the Diaphragm Cover fasteners are
male NPT pipe threads and apply TEFLON
pipe thread sealant as required. Do not
Maintenance securely tightened.
Pilot Valve Replacement
apply sealant to male threads of separated
compression fitting. Do not contaminate
The TYCO Model PRV-1 Pressure Prior to removing the Pilot Valve, the strainer screen.
Reducing Valve must be maintained Model PRV-1 Valve must be taken out Step 7. Install strainer into valve body.
and serviced in accordance with this of service and completely drained. Install gauge and trim sub-assembly
section. When installing the replacement Pilot into strainer outlet.
Before closing a fire protection system Valve, the trim components must be
replaced exactly as they were. After Step 8. Reconnect supply line com-
main control valve for maintenance pression fitting to strainer outlet trim
work on the fire protection system reinstalling the Pilot Valve and before
returning the Model PRV-1 Valve into and tighten compression fitting on
that it controls, obtain permission to supply line at needle valve inlet trim.
shut down the affected fire protection service, completely unscrew the
system from the proper authorities Adjusting Screw of the replacement Refer to Placing the Valve in Service
and notify all personnel who may be Pilot Valve so as to obtain a minimum section to place the Model PRV-1 Valve
affected by this action. outlet set pressure. Then proceed to in service.
use the instructions under Placing The
Valve In Service section to place the
NOTICE Model PRV-1 Valve in service.
Inspection, testing, and maintenance
must be performed in accordance NOTICE
with the requirements of the NFPA, and
any impairment must be immediately The Pilot Valve is not field repairable.
corrected. Attempting to repair the Pilot Valve may
render the valve ineffective and impair
Responsibility lies with sprinkler owners the system operation.
for the inspection, testing, and mainte-
nance of their fire protection system Completely unscrewing the Adjusting
and devices in compliance with this Screw of the replacement Pilot Valve
document, as well as with the appli- will help to avoid an accidental over
cable standards of the National Fire pressurization of the system piping
Protection Association (for example, prior to achieving the desired set
NFPA 25), in addition to the standards pressure.
of any other authorities having juris-
diction. Contact the installing contrac-
tor or product manufacturer with any
questions.
TFP1580
Page 8 of 16

Thread x Thread End Connections

Nominal
Nominal Installation Dimensions in Inches and (mm) Approx.
Valve Weight
Sizes lbs
Inches A B C D E F (kg)
(DN)
2 7.51 1.34 7.32 6.41 8.18 1.34 16.5
(50) (191) (34) (186) (163) (208) (34) (7,5)
3 11.42 1.97 8.19 7.48 9.25 1.97 30.6
(80) (290) (50) (208) (190) (235) (50) (13,9)

Groove x Groove End Connections

Nominal
Nominal Installation Dimensions in Inches and (mm) Approx. F
Valve Weight
Sizes lbs
Inches A B C D E F (kg)
(DN)
2 7.71 1.18 7.32 6.41 8.18 1.18 15.2 E
(50) (196) (30) (186) (163) (208) (30) (6,9)
3 11.42 1.77 8.19 7.48 9.25 1.77 30.6
(80) (290) (45) (208) (190) (235) (45) (13,9) D
4 13.62 2.24 8.70 7.91 9.68 2.24 40.6
(100) (346) (57) (221) (201) (246) (57) (18,4) C

6 17.80 3.30 9.88 6.73 11.49 3.30 75.6


(150) (452) (84) (251) (171) (292) (84) (34,3)
8 18.50 6.30 11.14 9.25 12.55 6.69 110.0
(200) (470) (160) (283) (235) (319) (170) (49,9)

B
Flange x Flange End Connections
A
Nominal
Nominal Installation Dimensions in Inches and (mm) Approx.
Valve Weight
Sizes lbs
Inches A B C D E F (kg)
(DN)
3 11.14 3.93 8.19 7.48 9.25 3.93 46.3
(80) (283) (100) (208) (190) (235) (100) (21,0)
4 12.00 4.37 8.70 7.91 9.68 4.37 57.3
(100) (305) (111) (221) (201) (246) (111) (26,0)
6 15.98 5.59 9.88 6.73 11.49 5.60 112.4
(150) (406) (142) (251) (171) (292) (142) (51,0)
8 18.50 6.30 11.14 7.16 12.55 6.69 149.9
(200) (470) (160) (283) (182) (319) (170) (68,0)

FIGURE 5
MODEL PRV-1 PRESSURE REDUCING VALVE
GLOVE STYLE INSTALLATION DIMENSIONS
TFP1580
Page 9 of 12

Thread x Thread End Connections

Nominal
Nominal Installation Dimensions in Inches and (mm) Approx.
Valve Weight
Sizes lbs
Inches A B C D E F (kg)
(DN)
2 3.62 3.23 7.32 6.41 8.18 2.40 16.5
(50) (92) (83) (186) (163) (208) (61) (7,5)
3 5.91 4.21 8.19 7.48 9.25 3.93 30.6
(80) (150) (107) (208) (190) (235) (100) (13,9)

Groove x Groove End Connections F


Nominal
Nominal Installation Dimensions in Inches and (mm) Approx.
Valve Weight
Sizes E
lbs
Inches A B C D E F (kg)
(DN)
2 3.62 3.23 7.32 6.41 8.18 2.40 15.2
(50) (92) (83) (186) (163) (208) (61) (6,9) D G
3 5.91 4.21 8.19 7.48 9.25 3.93 33.5
(80) (150) (107) (208) (190) (235) (100) (15,2) C

4 6.42 4.57 8.70 7.91 9.68 4.52 42.8


(100) (163) (116) (221) (201) (246) (115) (19,4)
6 8.9 6.69 9.88 6.73 11.49 5.90 83.8
(150) (226) (170) (251) (171) (292) (150) (38,0)

B
Flange x Flange End Connections
A
Nominal
Nominal Installation Dimensions in Inches and (mm) Approx.
Valve Weight
Sizes lbs
Inches A B C D E F (kg)
(DN)
3 6.26 4.53 8.19 7.48 9.25 3.93 48.5
(80) (159) (115) (208) (190) (235) (100) (22)
4 6.85 4.65 8.70 7.91 9.68 4.52 61.1
(100) (174) (118) (221) (201) (246) (115) (27,7)
6 7.99 5.83 9.88 6.73 11.49 5.90 110.2
(150) (203) (148) (251) (171) (292) (150) (50)

FIGURE 6
MODEL PRV-1 PRESSURE REDUCING VALVE
ANGLE STYLE INSTALLATION DIMENSIONS
TFP1580
Page 10 of 16

1 PSI = 0,06895 BAR 1 GPM = 3,785 LPM


140

130 A = 70 PSI INLET PRESSURE


OUTLET PRESSURE IN POUNDS PER SQUARE INCH (PSI)

B = 50 PSI INLET PRESSURE


120

110

100

90

80

70
A
60

50

40 B

30

20

10

0
0 25 50 75 100 125 150 175 200 225 250
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH A-1
2 INCH (DN50) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)

1 PSI = 0,06895 BAR 1 GPM = 3,785 LPM


140

130 A = 140 PSI INLET PRESSURE


OUTLET PRESSURE IN POUNDS PER SQUARE INCH (PSI)

B = 100 PSI INLET PRESSURE


A
120 C = 50 PSI INLET PRESSURE
110

100
B
90

80

70

60

50

40
C
30

20

10

0
0 25 50 75 100 125 150 175 200 225 250
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH A-2
2 INCH (DN50) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)
TFP1580
Page 11 of 12

1 PSI = 0,06895 BAR 1 GPM = 3,785 LPM


140

130 A = 70 PSI INLET PRESSURE


OUTLET PRESSURE IN POUNDS PER SQUARE INCH (PSI)

B = 50 PSI INLET PRESSURE


120

110

100

90

80

70

60
A
50

40
B
30

20

10

0
0 50 100 150 200 250 300 350 400 450 500 550
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH B-1
3 INCH (DN80) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)

1 PSI = 0,06895 BAR 1 GPM = 3,785 LPM


140

130 A = 140 PSI INLET PRESSURE


OUTLET PRESSURE IN POUNDS PER SQUARE INCH (PSI)

A B = 100 PSI INLET PRESSURE


120 C = 50 PSI INLET PRESSURE
110

100

90 B

80

70

60

50

40
C
30

20

10

0
0 50 100 150 200 250 300 350 400 450 500 550
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH B-2
3 INCH (DN80) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)
TFP1580
Page 12 of 16

1 PSI = 0,06895 BAR 1 GPM = 3,785 LPM


140

130 A = 70 PSI INLET PRESSURE


OUTLET PRESSURE IN POUNDS PER SQUARE INCH (PSI)

B = 50 PSI INLET PRESSURE


120

110

100

90

80

70
A
60

50

40 B

30

20

10

0
0 100 200 300 400 500 600 700 800 900 1000
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH C-1
4 INCH (DN100) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)

1 PSI = 0,06895 BAR 1 GPM = 3,785 LPM


140
A
130
OUTLET PRESSURE IN POUNDS PER SQUARE INCH (PSI)

120

110 A = 140 PSI INLET PRESSURE


B = 100 PSI INLET PRESSURE
100 C = 50 PSI INLET PRESSURE
B
90

80

70

60

50
C
40

30

20

10

0
0 100 200 300 400 500 600 700 800 900 1000
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH C-2
4 INCH (DN100) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)
TFP1580
Page 13 of 12

1 PSI = 0,06895 BAR 1 GPM = 3,785 LPM


140

130 A = 70 PSI INLET PRESSURE


OUTLET PRESSURE IN POUNDS PER SQUARE INCH (PSI)

B = 50 PSI INLET PRESSURE


120

110

100

90

80

70

60
A
50

40
B
30

20

10

0
0 250 500 750 1000 1250 1500 1750 2000 2250 2500
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH D-1
6 INCH (DN150) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)

1 PSI = 0,06895 BAR 1 GPM = 3,785 LPM


140

130 A = 140 PSI INLET PRESSURE


OUTLET PRESSURE IN POUNDS PER SQUARE INCH (PSI)

A B = 100 PSI INLET PRESSURE


120 C = 50 PSI INLET PRESSURE
110

100
B
90

80

70

60

50

40
C
30

20

10

0
0 250 500 750 1000 1250 1500 1750 2000 2250 2500
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH D-2
6 INCH (DN150) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)
TFP1580
Page 14 of 16

1 PSI = 0,06895 BAR 1 GPM = 3,785 LPM


140

130 A = 70 PSI INLET PRESSURE


OUTLET PRESSURE IN POUNDS PER SQUARE INCH (PSI)

B = 50 PSI INLET PRESSURE


120

110

100

90

80

70
A
60

50

40 B

30

20

10

0
0 500 1000 1500 2000 2500 3000 3500 4000
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH E-1
8 INCH (DN200) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)

1 PSI = 0,06895 BAR 1 GPM = 3,785 LPM


140
A A = 140 PSI INLET PRESSURE
130
OUTLET PRESSURE IN POUNDS PER SQUARE INCH (PSI)

B = 100 PSI INLET PRESSURE


120 C = 50 PSI INLET PRESSURE
110

100
B
90

80

70

60

50

40 C

30

20

10

0
0 500 1000 1500 2000 2500 3000 3500 4000
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH E-2
8 INCH (DN200) MODEL PRV-1 PRESSURE REDUCING VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI
(THIS GRAPH IS A REQUIREMENT OF UL AND SHOULD BE USED AS REFERENCE ONLY)
TFP1580
Page 15 of 12

Limited For grooved, specify 6 Inch F x F


O.D. Pipe Size AS Flange. . . . . . . . . . . . . . . . . . 52-570-8-525

Warranty
8 Inch G X G
2 inch (DN50): 8.62 Inch (219,1mm)
2.88 inch (60,3 mm) O.D. Groove O.D. . . . . . . . . . . . . . . . . 52-570-8-926
For warranty terms and conditions, visit 3 inch (DN80): 8 Inch F x F
www.tyco-fire.com. 3.50 inch (88,9 mm) O.D.
ANSI Flange. . . . . . . . . . . . . . . . 52-570-8-026
8 Inch F x F

Ordering 4 inch (DN100):


4.50 inch (114,3 mm) O.D.
ISO (PN10) Flange . . . . . . . . . .
8 Inch F x F
52-570-8-116

Procedure
ISO (PN16) Flange . . . . . . . . . . 52-570-8-126
6 inch (DN150):
8 Inch F x F
6.62 inch (168,3 mm) O.D. or JIS Flange. . . . . . . . . . . . . . . . . . 52-570-8-726
North America 6.50 inch (165,1 mm) O.D. 8 Inch F x F
8 inch (DN200): AS Flange. . . . . . . . . . . . . . . . . . 52-570-8-526
Pressure Reducing Valve
Specify: Globe Type, (specify size), 8.62 inch (219,1 mm) O.D. Angle Body Style
125 psi Outlet Set Pressure with For flanged, specify 2 Inch T x T
(T x T, G x G, or F x F) Connection, flange drilling per NPT. . . . . . . . . . . . . . . . . . . . . . . 52-571-8-060
P/N (specify from below). 2 Inch T x T
2 Inch T x T ANSI B16-1 (Class 125) ISO . . . . . . . . . . . . . . . . . . . . . . . 52-571-8-160
NPT. . . . . . . . . . . . . . . . . . . . . . . 52-570-8-060 ISO 7005-2 (PN16) 2 Inch G x G
2 Inch G x G 2.37 inch (60,3 mm)
2.37 inch (60,3 mm) ISO 7005-2 (PN10), Groove O.D. . . . . . . . . . . . . . . . . 52-571-8-920
Groove O.D. . . . . . . . . . . . . . . . . 52-570-8-920 8 inch valve only 3 Inch T x T
3 Inch G x G NPT. . . . . . . . . . . . . . . . . . . . . . . 52-571-8-062
3.50 inch (88,9 mm)
JIS B2210 (10K) 3 Inch T x T
Groove O.D. . . . . . . . . . . . . . . . . 52-570-8-922 AS 2129 (Table E) ISO . . . . . . . . . . . . . . . . . . . . . . . 52-571-8-162
4 Inch G x G 3 Inch G x G
4.50 inch (114,3 mm) Refer to Table C for flange drilling 3.50 inch (88,9 mm)
Groove O.D. . . . . . . . . . . . . . . . . 52-570-8-923 dimensional specifications. Groove O.D. . . . . . . . . . . . . . . . . 52-571-8-922
4 Inch F x F Globe Body Style 3 Inch F x F
ANSI Flange. . . . . . . . . . . . . . . . 52-570-8-023 ANSI Flange. . . . . . . . . . . . . . . . 52-571-8-022
2 Inch T x T
6 Inch G x G NPT. . . . . . . . . . . . . . . . . . . . . . . 52-570-8-060 3 Inch F x F
6.62 inch (168,3 mm) ISO (PN16) Flange . . . . . . . . . . .52-571-8-112
Groove O.D. . . . . . . . . . . . . . . . . 52-570-8-925 2 Inch T x T
ISO . . . . . . . . . . . . . . . . . . . . . . . 52-570-8-160 3 Inch F x F
6 Inch F x F JIS Flange. . . . . . . . . . . . . . . . . . 52-571-8-722
ANSI Flange.. . . . . . . . . . . . . . . . 52-570-8-025 2 Inch G x G
2.37 inch (60,3 mm) 3 Inch F x F
8 Inch G X G Groove O.D. . . . . . . . . . . . . . . . . 52-570-8-920 AS Flange. . . . . . . . . . . . . . . . . . 52-571-8-522
8.62 Inch (219,1mm) 4 Inch G x G
Groove O.D. . . . . . . . . . . . . . . . . 52-570-8-926 3 Inch T x T 4.50 inch (114,3 mm)
NPT. . . . . . . . . . . . . . . . . . . . . . . 52-570-8-062 Groove O.D. . . . . . . . . . . . . . . . . 52-571-8-923
8 Inch F x F
ANSI Flange. . . . . . . . . . . . . . . . 52-570-8-026 3 Inch T x T 4 Inch F x F
ISO . . . . . . . . . . . . . . . . . . . . . . . 52-570-8-162 ANSI Flange. . . . . . . . . . . . . . . . 52-571-8-023
Pressure Relief Valve 3 Inch G x G 4 Inch F x F
Specify: 1/2 inch (DN15) Watts Regula- 3.50 inch (88,9 mm) ISO (PN16) Flange . . . . . . . . . . .52-571-8-113
tor, Series 530C Pressure Relief Valve Groove O.D. . . . . . . . . . . . . . . . . 52-570-8-922 4 Inch F x F
for use downstream of a Model PRV-1 3 Inch F x F JIS Flange. . . . . . . . . . . . . . . . . . 52-571-8-723
Valve being used for reducing pressure ANSI Flange. . . . . . . . . . . . . . . . 52-570-8-022 4 Inch F x F
in sprinkler system, P/N 20608 3 Inch F x F AS Flange. . . . . . . . . . . . . . . . . . 52-571-8-523
ISO (PN16) Flange . . . . . . . . . . .52-570-8-112 6 Inch G x G
Replacement Valve Parts 3 Inch F x F
6.62 inch (168,3 mm)
Specify: (description) for use with Groove O.D. . . . . . . . . . . . . . . . . 52-571-8-925
JIS Flange. . . . . . . . . . . . . . . . . . 52-570-8-722
6 Inch G x G
(specify) size Model PRV-1 Pressure 3 Inch F x F 6.50 inch (165,1 mm)
Reducing Valve, P/N (see Figure 3) AS Flange. . . . . . . . . . . . . . . . . . 52-570-8-522 Groove O.D. . . . . . . . . . . . . . . . . 52-571-8-945
4 Inch G x G 6 Inch F x F
South America, Central 4.50 inch (114,3 mm) ANSI Flange. . . . . . . . . . . . . . . . 52-571-8-025
America and Eastern Groove O.D. . . . . . . . . . . . . . . . . 52-570-8-923 6 Inch F x F
Hemisphere 4 Inch F x F ISO (PN16) Flange . . . . . . . . . . .52-571-8-115
ANSI Flange. . . . . . . . . . . . . . . . 52-570-8-023 6 Inch F x F
Pressure Reducing Valve 4 Inch F x F JIS Flange. . . . . . . . . . . . . . . . . . 52-571-8-725
Specify: (Globe or Angle) Type, (specify ISO (PN16) Flange . . . . . . . . . . .52-570-8-113 6 Inch F x F
size), 125 psi Outlet Set Pressure with 4 Inch F x F AS Flange. . . . . . . . . . . . . . . . . . 52-571-8-525
(specify) Connection (and for flanged JIS Flange. . . . . . . . . . . . . . . . . . 52-570-8-723
valves specify flange drilling), P/N 4 Inch F x F Pressure Relief Valve
(specify from complete listing on Page AS Flange. . . . . . . . . . . . . . . . . . 52-570-8-523 Specify: Size (specify) Watts Regula-
16). 6 Inch G x G tor, Series 530C Pressure Relief Valve
6.62 inch (168,3 mm) for use downstream of a Model PRV-1
Valve Type & Size Groove O.D. . . . . . . . . . . . . . . . . 52-570-8-925 Valve being used for reducing pressure
(Globe, 2, 3, 4, 6, or 8 Inch) 6 Inch G x G in sprinkler system, P/N (Specify):
6.50 inch (165,1 mm)
(Angle, 2, 3, 4, or 6 Inch Groove O.D. . . . . . . . . . . . . . . . . 52-570-8-945 South America and Central America
125 psi Outlet Set Pressure Pressure 1/2 Inch (DN15) . . . . . . . . . . . . . . . . . . . . . 20608
6 Inch F x F
Connection Type (Threaded, Grooved, ANSI Flange. . . . . . . . . . . . . . . . 52-570-8-025 Eastern Hemisphere
6 Inch F x F 1/2 inch (DN15). . . . . . . . . . . . . . . . 92-570-2-208
Flanged)
ISO (PN16) Flange . . . . . . . . . . .52-570-8-115
For threaded, specify
6 Inch F x F
Replacement Valve Parts
NPT or ISO JIS Flange. . . . . . . . . . . . . . . . . . 52-570-8-725 Specify: (description) for use with
(specify) size Model PRV-1 Pressure
Reducing Valve, P/N (see Figure 3)
TFP1580
Page 16 of 16

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


Copyright 2017 Tyco Fire Products, LP. All rights reserved.
RILSAN is a registered trademark of Arkema, Inc.

Vous aimerez peut-être aussi