Control Systems 10ES43

CONTROL SYSTEMS
(Common to EC/TC/EE/IT/BM/ML)
Sub Code: 10ES43 IA Marks : 25
Hrs/ Week: 04 Exam Hours : 03
Total Hrs: 52 Marks : 100

UNIT 1:
Modeling of Systems: Introduction to Control Systems, Types of Control Systems, Effect of
Feedback Systems, Differential equation of Physical Systems -Mechanical systems, Friction,
Translational systems (Mechanical accelerometer, systems excluded), Rotational systems, Gear
trains, Electrical systems, Analogous systems. 7 Hrs

UNIT 2:
Block diagrams and signal flow graphs: Transfer functions, Block diagram algebra, Signal
Flow graphs (State variable formulation excluded), 6 Hrs

UNIT 3:
Time Response of feedback control systems: Standard test signals, Unit step response of First
and second order systems, Time response specifications, Time response specifications of second
order systems, steady123 state errors and error constants. Introduction to PID Controllers
(excluding design) 7 Hrs

UNIT 4:
Stability analysis: Concepts of stability, Necessary conditions for Stability, Routh- stability
criterion, Relative stability analysis; more on the Routh stability criterion. 6 Hrs

UNIT 5:
RootLocus Techniques: Introduction, The root locus concepts,Construction of root loci 6 Hrs

UNIT 6:
Frequency domain analysis: Correlation between time and frequency response, Bode plots,
Experimental determination of transfer functions, Assessment of relative stability using Bode
Plots. Introduction to lead, lag and lead-lag compensating networks (excluding design). 7 Hrs
UNIT 7:
Stability in the frequency domain: Introduction to Polar Plots, (Inverse Polar Plots excluded)
Mathematical preliminaries, Nyquist Stability criterion, Assessment of relative stability using
Nyquist criterion, (Systems with transportation lag excluded). 7 Hrs

UNIT 8:
Introduction to State variable analysis: Concepts of state, state variable and state models for
electrical systems, Solution of state equations. 6 Hrs

ECE/SJBIT Page 1
Control Systems 10ES43

TEXT BOOK :

1. J. Nagarath and M.Gopal, Control Systems Engineering, New Age


International (P) Limited, Publishers, Fourth edition 2005
REFERENCE BOOKS:
1. Modern Control Engineering , K. Ogata, Pearson Education Asia/
PHI, 4th Edition, 2002.
2. Automatic Control Systems, Benjamin C. Kuo, John Wiley India
Pvt. Ltd., 8th Edition, 2008.
3. Feedback and Control System, Joseph J Distefano III et al.,
Schaums Outlines, TMH, 2nd Edition 2007.

ECE/SJBIT Page 2
Control Systems 10ES43

INDEX SHEET

PAGE
SL.NO TOPIC
No.
I UNIT 1:Modeling of Systems 5-26
1.1 Introduction to Control Systems, Types of Control Systems
1.2 Effect of Feedback Systems
1.3 Differential equation of Physical Systems -Mechanical systems, Friction
1.4 Translational systems (Mechanical accelerometer, systems excluded)
1.5 Rotational systems , Gear trains
1.6 Electrical systems, Analogous systems
II UNIT2 : Block diagrams and signal flow graphs 27-47
2.1 Transfer functions
2.2 Block diagram algebra
2.3 Signal Flow graphs (State variable formulation excluded)
III UNIT 3 :Time Response of feedback control systems 48-90
3.1 Standard test signals
3.2 Unit step response of first order systems
3.3 Unit step response of second order systems
3.4 Time response specifications
3.5 Time response specifications of second order systems
3.6 steady23 state errors and error constants)
3.7 Introduction to PID Controllers (excluding design)
IV UNIT 4 : Stability analysis 91-116
4.1 Concepts of stability, Necessary conditions for Stability
4.2 Routh- stability criterion
4.3 Relative stability analysis; More on the Routh stability criterion.
V UNIT 5 : RootLocus Techniques 117-139
5.1 Introduction, The root locus concepts
5.2 Construction of root loci (problems)
VI UNIT 6 : Frequency domain analysis 140-175
6.1 Correlation between time and frequency response
6.2 Bode plots
6.3 Experimental determination of transfer functions
6.4 Assessment of relative stability using Bode Plots
Introduction to lead, lag and lead-lag compensating networks (excluding
6.5
design)
176-188
VII UNIT 7 : Stability in the frequency domain
7.1 Introduction to Polar Plots,(Inverse Polar Plots excluded)
ECE/SJBIT Page 3
Control Systems 10ES43

7.2 Mathematical preliminaries


7.3 Nyquist Stability criterion
Assessment of relative stability using Nyquist criterion, (Systems with
7.4
transportation lag excluded)
VIII UNIT 8 : Introduction to State variable analysis 189-208
8.1 Concepts of state, state variable
8.2 Concepts of state models for electrical systems
8.3 Solution of state equations

ECE/SJBIT Page 4
Control Systems 10ES43

UNIT-1

A control system is an arrangement of physical components connected or related in such a


manner as to command, direct, or regulate itself or another system, or is that means by which any
quantity of interest in a system is maintained or altered in accordance with a desired manner.

Any control system consists of three essential components namely input, system and output. The
input is the stimulus or excitation applied to a system from an external energy source. A system
is the arrangement of physical components and output is the actual response obtained from the
system. The control system may be one of the following type.
1) man made
2) natural and / or biological and
3) hybrid consisting of man made and natural or biological.

Examples:
1) An electric switch is man made control system, controlling flow of electricity.
input : flipping the switch on/off
system : electric switch
output : flow or no flow of current
2) Pointing a finger at an object is a biological control system.
input : direction of the object with respect to some direction
system : consists of eyes, arm, hand, finger and brain of a man
output : actual pointed direction with respect to same direction
3) Man driving an automobile is a hybrid system.
input : direction or lane
system : drivers hand, eyes, brain and vehicle
output : heading of the automobile.

Classification of Control Systems

Control systems are classified into two general categories based upon the control action which is
responsible to activate the system to produce the output viz.
1) Open loop control system in which the control action is independent of the out put.

2) Closed loop control system in which the control action is some how dependent upon the
output and are generally called as feedback control systems.

Open Loop System is a system in which control action is independent of output. To each
reference input there is a corresponding output which depends upon the system and its operating
conditions. The accuracy of the system depends on the calibration of the system. In the presence
of noise or disturbances open loop control will not perform satisfactorily.

ECE/SJBIT Page 5
Control Systems 10ES43

input Actuating signal output


nput
Controller System

EXAMPLE - 1 Rotational Generator


The input to rotational generator is the speed of the prime mover ( e.g steam turbine) in r.p.m.
Assuming the generator is on no load the output may be induced voltage at the output terminals.
Speed of the Induced Voltage
Prime mover
Inputs Rotational Generator
Output

Fig 1-2 Rotational Generator


EXAMPLE 2 Washing machine
Most ( but not all ) washing machines are operated in the following manner. After the clothes to
be washed have been put into the machine, the soap or detergent, bleach and water are entered in
proper amounts as specified by the manufacturer. The washing time is then set on a timer and the
washer is energized. When the cycle is completed, the machine shuts itself off. In this example
washing time forms input and cleanliness of the clothes is identified as output.
Cleanliness of clothes
Time Washing Machine

Fig 1-3 Washing Machine


EXAMPLE 3 WATER TANK LEVEL CONTROL
To understand the concept further it is useful to consider an example let it be desired to maintain
the actual water level 'c ' in the tank as close as possible to a desired level ' r '. The desired level
will be called the system input, and the actual level the controlled variable or system output.
Water flows from the tank via a valve Vo , and enters the tank from a supply via a control valve
Vc. The control valve is adjustable manually.
Valve VC
Actual
Water level c
Desired Water
Water in level r WATER
TANK
Valve VO

C Water Fig 1-4 b) Open loop control


out
Fig 1.4 a) Water level control

ECE/SJBIT Page 6
Control Systems 10ES43

A closed loop control system is one in which the control action depends on the output. In
closed loop control system the actuating error signal, which is the difference between the input
signal and the feed back signal (out put signal or its function) is fed to the controller.

Error Forward path Controlled


Reference detector Actuating output
/ error
input
signal Control System /
elements Plant
controller

Feed back elements


Feed back signal
Fig 1.5: Closed loop control system
EXAMPLE 1 THERMAL SYSTEM
To illustrate the concept of closed loop control system, consider the thermal system shown in fig-
6 Here human being acts as a controller. He wants to maintain the temperature of the hot water at
a given value ro C. the thermometer installed in the hot water outlet measures the actual
temperature C0 C. This temperature is the output of the system. If the operator watches the
thermometer and finds that the temperature is higher than the desired value, then he reduce the
amount of steam supply in order to lower the temperature. It is quite possible that that if the
temperature becomes lower than the desired value it becomes necessary to increase the amount
of steam supply. This control action is based on closed loop operation which involves human
being, hand muscle, eyes, thermometer such a system may be called manual feed back system.

Human operator
Thermometer Brain of
Actual
operator (r-c)
Desired hot Water temp
Steam Co C
water. temp Muscles
+ C
Steam Hot water ro c + and Valve

Cold water Thermometer


Drain

Fig 1-6 a) Manual feedback thermal system b) Block diagram


EXAMPLE 2 HOME HEATING SYSTEM
The thermostatic temperature control in hour homes and public buildings is a familiar example.
An electronic thermostat or temperature sensor is placed in a central location usually on inside
ECE/SJBIT Page 7
Control Systems 10ES43

wall about 5 feet from the floor. A person selects and adjusts the desired room temperature ( r )
say 250 C and adjusts the temperature setting on the thermostat. A bimetallic coil in the
thermostat is affected by the actual room temperature ( c ). If the room temperature is lower than
the desired temperature the coil strip alters the shape and causes a mercury switch to operate a
relay, which in turn activates the furnace fire when the temperature in the furnace air duct system
reaches reference level ' r ' a blower fan is activated by another relay to force the warm air
throughout the building. When the room temperature ' C ' reaches the desired temperature ' r '
the shape of the coil strip in the thermostat alters so that Mercury switch opens. This deactivates
the relay and in turn turns off furnace fire, which in turn the blower.

Outdoor temp change


(disturbance) Actual
Temp.
Relay Co C
Furnace Blower House
o
Desired temp. r c
+ switch

Fig 1-7 Block diagram of Home Heating system.

A change in out door temperature is a disturbance to the home heating system. If the out side
temperature falls, the room temperature will likewise tend to decrease.

CLOSED- LOOP VERSUS OPEN LOOP CONTROL SYSTEMS

An advantage of the closed loop control system is the fact that the use of feedback makes the
system response relatively insensitive to external disturbances and internal variations in systems
parameters. It is thus possible to use relatively inaccurate and inexpensive components to obtain
the accurate control of the given plant, whereas doing so is impossible in the open-loop case.
From the point of view of stability, the open loop control system is easier to build
because system stability is not a major problem. On the other hand, stability is a major problem
in the closed loop control system, which may tend to overcorrect errors that can cause
oscillations of constant or changing amplitude.
It should be emphasized that for systems in which the inputs are known ahead of time and in
which there are no disturbances it is advisable to use open-loop control. closed loop control
systems have advantages only when unpredictable disturbances it is advisable to use open-loop
control. Closed loop control systems have advantages only when unpredictable disturbances and
/ or unpredictable variations in system components used in a closed loop control system is more
than that for a corresponding open loop control system. Thus the closed loop control system is
generally higher in cost.

ECE/SJBIT Page 8
Control Systems 10ES43

Definitions:
Systems: A system is a combination of components that act together and perform a certain
objective. The system may be physical, biological, economical, etc.
Control system: It is an arrangement of physical components connected or related in a manner
to command, direct or regulate itself or another system.
Open loop: An open loop system control system is one in which the control action is
independent of the output.
Closed loop: A closed loop control system is one in which the control action is somehow
dependent on the output.
Plants: A plant is equipment the purpose of which is to perform a particular operation. Any
physical object to be controlled is called a plant.
Processes: Processes is a natural or artificial or voluntary operation that consists of a series of
controlled actions, directed towards a result.
Input: The input is the excitation applied to a control system from an external energy source.
The inputs are also known as actuating signals.
Output: The output is the response obtained from a control system or known as controlled
variable.
Block diagram: A block diagram is a short hand, pictorial representation of cause and effect
relationship between the input and the output of a physical system. It characterizes the functional
relationship amongst the components of a control system.
Control elements: These are also called controller which are the components required to
generate the appropriate control signal applied to the plant.
Plant: Plant is the control system body process or machine of which a particular quantity or
condition is to be controlled.
Feedback control: feedback control is an operation in which the difference between the output
of the system and the reference input by comparing these using the difference as a means of
control.
Feedback elements: These are the components required to establish the functional relationship
between primary feedback signal and the controlled output.
Actuating signal: also called the error or control action. It is the algebraic sum consisting of
reference input and primary feedback.
Manipulated variable: it that quantity or condition which the control elements apply to the
controlled system.
Feedback signal: it is a signal which is function of controlled output
Disturbance: It is an undesired input signal which affects the output.
Forward path: It is a transmission path from the actuating signal to controlled output
Feedback path: The feed back path is the transmission path from the controlled output to the
primary feedback signal.
Servomechanism: Servomechanism is a feedback control system in which output is some
mechanical position, velocity or acceleration.
Regulator: Regulator is a feedback system in which the input is constant for long time.
Transducer: Transducer is a device which converts one energy form into other
Tachometer: Tachometer is a device whose output is directly proportional to time rate of change
of input.
Synchros: Synchros is an AC machine used for transmission of angular position synchro motor-
receiver, synchro generator- transmitter.
ECE/SJBIT Page 9
Control Systems 10ES43

Block diagram: A block diagram is a short hand, pictorial representation of cause and effect
relationship between the input and the output of a physical system. It characterizes the functional
relationship amongst the components of a control system.
Summing point: It represents an operation of addition and / or subtraction.
Negative feedback: Summing point is a subtractor.
Positive feedback: Summing point is an adder.
Stimulus: It is an externally introduced input signal affecting the controlled output.
Take off point: In order to employ the same signal or variable as an input to more than block or
summing point, take off point is used. This permits the signal to proceed unaltered along several
different paths to several destinations.
Time response: It is the output of a system as a function of time following the application of a
prescribed input under specified operating conditions.

ECE/SJBIT Page 10
Control Systems 10ES43

DIFFERENTIAL EQUATIONS OF PHYSICAL SYSTEMS


The term mechanical translation is used to describe motion with a single degree of freedom or
motion in a straight line. The basis for all translational motion analysis is Newtons second law
of motion which states that the Net force F acting on a body is related to its mass M and
acceleration a by the equation F = Ma
Ma is called reactive force and it acts in a direction opposite to that of acceleration. The
summation of the forces must of course be algebraic and thus considerable care must be taken in
writing the equation so that proper signs prefix the forces.

The three basic elements used in linear mechanical translational systems are ( i ) Masses (ii)
springs iii) dashpot or viscous friction units. The graphical and symbolic notations for all three
are shown in fig 1-8

Fig 1-8 a) Mass Fig 1-8 b) Spring Fig 1-8 c) Dashpot

The spring provides a restoring a force when a force F is applied to deform a coiled spring a
reaction force is produced, which to bring it back to its freelength. As long as deformation is
small, the spring behaves as a linear element. The reaction force is equal to the product of the
stiffness k and the amount of deformation.

Whenever there is motion or tendency of motion between two elements, frictional forces exist.
The frictional forces encountered in physical systems are usually of nonlinear nature. The
characteristics of the frictional forces between two contacting surfaces often depend on the
composition of the surfaces. The pressure between surfaces, their relative velocity and others.
The friction encountered in physical systems may be of many types
( coulomb friction, static friction, viscous friction ) but in control problems viscous friction,
predominates. Viscous friction represents a retarding force i.e. it acts in a direction opposite to
the velocity and it is linear relationship between applied force and velocity. The mathematical
expression of viscous friction F=BV where B is viscous frictional co-efficient. It should be
realized that friction is not always undesirable in physical systems. Sometimes it may be
necessary to introduce friction intentionally to improve dynamic response of the system. Friction
may be introduced intentionally in a system by use of dashpot as shown in fig 1-9. In
automobiles shock absorber is nothing but dashpot.

ECE/SJBIT Page 11
Control Systems 10ES43

a b
Applied force
F
Piston

The basic operation of a dashpot, in which the housing is filled with oil. If a force f is applied to
the shaft, the piston presses against oil increasing the pressure on side b and decreasing
pressure side a As a result the oil flows from side b to side a through the wall clearance. The
friction coefficient B depends on the dimensions and the type of oil used.

Outline of the procedure


For writing differential equations
1. Assume that the system originally is in equilibrium in this way the often-troublesome
effect of gravity is eliminated.
2. Assume then that the system is given some arbitrary displacement if no distributing force
is present.
3. Draw a freebody diagram of the forces exerted on each mass in the system. There should
be a separate diagram for each mass.
4. Apply Newtons law of motion to each diagram using the convention that any force
acting in the direction of the assumed displacement is positive is positive.
5. Rearrange the equation in suitable form to solve by any convenient mathematical means.
Lever
Lever is a device which consists of rigid bar which tends to rotate about a fixed point
called fulcrum the two arms are called effort arm and Load arm respectively. The lever
bears analogy with transformer

F2 Load
L1 L2

Fulcrum
effort F
1

ECE/SJBIT Page 12
Control Systems 10ES43

It is also called mechanical transformer


Equating the moments of the force
F1 L1 = F2 L 2
F2 = F1 L1
L2

Rotational mechanical system


The rotational motion of a body may be defined as motion about a fixed axis. The variables
generally used to describe the motion of rotation are torque, angular displacement , angular
velocity () and angular acceleration()
The three basic rotational mechanical components are 1) Moment of inertia J
2 ) Torsional spring 3) Viscous friction.
Moment of inertia J is considered as an indication of the property of an element, which stores the
kinetic energy of rotational motion. The moment of inertia of a given element depends on
geometric composition about the axis of rotation and its density. When a body is rotating a
reactive torque is produced which is equal to the product of its moment
of inertia (J) and angular acceleration and is given by T= J = J d2
d t2
A well known example of a torsional spring is a shaft which gets twisted when a torque is
applied to it. Ts = K, is angle of twist and K is torsional stiffness.

There is viscous friction whenever a body rotates in viscous contact with another body. This
torque acts in opposite direction so that angular velocity is given by
T = f = f d2 Where = relative angular velocity between two bodies.
2
dt f = co efficient of viscous friction.

Newtons II law of motion states


T = J d2 .
d t2

Gear wheel

ECE/SJBIT Page 13
Control Systems 10ES43

In almost every control system which involves rotational motion gears are necessary. It is often
necessary to match the motor to the load it is driving. A motor which usually runs at high speed
and low torque output may be required to drive a load at low speed and high torque.

Driving wheel
N1

N2
Driven wheel

Analogous Systems
Consider the mechanical system shown in fig A and the electrical system shown in fig B

The differential equation for mechanical system is


d2x dx
M + + B + K X = f (t) ---------- 1
dt2 dt

The differential equation for electrical system is

d2q d2q q
L + +R + = e ---------- 2
dt2 dt2 c
Comparing equations (1) and (2) we see that for the two systems the differential equations are of
identical form such systems are called analogous systems and the terms which occupy the
corresponding positions in differential equations are analogous quantities

The analogy is here is called force voltage analogy


Table for conversion for force voltage analogy

Mechanical System Electrical System

Force (torque) Voltage

Mass (Moment of inertia) Inductance

ECE/SJBIT Page 14
Control Systems 10ES43

Viscous friction coefficient Resistance

Spring constant Capacitance

Displacement Charge

Velocity Current.

Force Current Analogy


Another useful analogy between electrical systems and mechanical systems is based on force
current analogy. Consider electrical and mechanical systems shown in fig.

For mechanical system the differential equation is given by


d2x dx
M + +B + K X = f (t) ---------- 1
2
dt dt

For electrical system


C d2x
+
1
+
d +
= I(t)
dt 2 R dt2 L
Comparing equations (1) and (2) we find that the two systems are analogous systems. The
analogy here is called force current analogy. The analogous quantities are listed.

Table of conversion for force current analogy


Mechanical System Electrical System

Force( torque) Current

Mass( Moment of inertia) Capacitance

Viscous friction coefficient Conductance

Spring constant Inductance

Displacement Flux
( angular)
Velocity (angular) Voltage

ECE/SJBIT Page 15
Control Systems 10ES43

Illustration 1:For a two DOF spring mass damper system obtain the mathematical model where

F is the input x1 and x2 are responses.

k2 b2 (Damper)
Draw the free body diagram for mass
m1 and m2 separately as shown in figure
m2 x2 (Response) 1.10 (b)

Apply NSL for both the masses


k1 b1 separately and get equations as given in
(a) and (b)

m1 x1 (Response)

F
Figure 1.10 (a)

k2 x2 b2 x2
. k2 x2 b2 x2
.
m2 m2
x2
k1 x2 k1 x1
.
b x b1
.
x
.
1 1 2

. ..
k1 (x1-x2) b1 (x1-x2)
k1 x2 k1 x1 b x 1 1 b1 x 2

m1
x1 m1
F
F
Figure 1.10 (b)

From NSL F= ma

For mass m1
.. . .
ECE/SJBIT Page 16
Control Systems 10ES43

m1x1 = F - b1 (x1-x2) - k1 (x1-x2) --- (a)

For mass m2
.. . . .
m2 x2 = b1 (x2-x1) + k1 (x2-x1) - b2 x2 - k2 x2 --- (b)

Illustration 2: For the system shown in figure 2.16 (a) obtain the mathematical model if x1 and

x2 are initial displacements.

Let an initial displacement x1 be given to mass m1 and x2 to mass m2.

K1

m1
X1
K2

m2

K3 X2

Figure 1.11 (a)

ECE/SJBIT Page 17
Control Systems 10ES43

K1 X1
K1 X1

m1
m1
X1
X1
K2 X2 K2 X1 K2 (X2 X1)
K2 X2 K2 X1
K2 (X2 X1)
m2
m2
X2
K3 X2 X2
K3 X2
Figure 2.16 (b)
Based on Newtons second law of motion: F = ma
For mass m1
..
m1x1 = - K1x1 + K2 (x2-x1)
..
m1x1 + K1x1 K2 x2 + K2x1 = 0
..
m1x1 + x1 (K1 + K2) = K2x2 ----- (1)

For mass m2
..
m2x2 = - K3x2 K2 (x2 x1)
..
m2x2 + K3 x2 + K2 x2 K2 x1
..
m2 x2 + x2 (K2 + K3) = K2x1 ----- (2)

ECE/SJBIT Page 18
Control Systems 10ES43

Mathematical models are:

..
m1x1 + x1 (K1 + K2) = K2x2 ----- (1)
..
m2x2 + x2 (K2 + K3) = K2x1 ----- (2)

1.Write the differential equation relating to motion X of the mass M to the force input u(t)

X
(output)
K1 K2
M U(t)
(input)

2. Write the force equation for the mechanical system shown in figure

X (output)
X1
K B2 F(t)
(input)
M
3. Write the differential equations for the mechanical system shown in figure.
B1
X1 X2
K1 f12
M1 M2
f(t) f1 f2
ECE/SJBIT Page 19
Control Systems 10ES43

4. Write the modeling equations for the mechanical systems shown in figure.

Xi K
X

M M
force f(t)
Xo
B

5. For the systems shown in figure write the differential equations and obtain the transfer
functions indicated.

Yk
K F

Xi Xo Xi Xo C

6. Write the differential equation describing the system. Assume the bar through which
force is applied is not flexible, has no mass or moment of inertia, and all
displacements are small.

f(t) b
K
X

a M

ECE/SJBIT Page 20
Control Systems 10ES43

7. Write the equations of motion in terms of given mechanical quantities.

X2
Force f K1
a b
M1 M2

B1
K2
X1
8. Write the force equations for the mechanical systems shown in figure.

B1
J1
T(t)
9. Write the force equation for the mechanical system shown in figure.

K
T(t) J1 J2

1 2
10. Write the force equation for the mechanical system shown in figure.

1 K 2 K 3 K
1 2 3
ECE/SJBIT J1 J2 J3 Page 21
Torque T
B1 B2 B3
Control Systems 10ES43

11. Torque T(t) is applied to a small cylinder with moment of inertia J1 which rotates with in a
larger cylinder with moment of inertia J2. The two cylinders are coupled by viscous friction B1.
The outer cylinder has viscous friction B2 between it and the reference frame and is restrained by
a torsion spring k. write the describing differential equations.

J2 K

J1
B2
Torque T1, 1 B1

12. The polarized relay shown exerts a force f(t) = K i. i(t) upon the pivoted bar. Assume the relay
coil has constant inductance L. The left end of the pivot bar is connected to the reference frame
through a viscous damper B1 to retard rapid motion of the bar. Assume the bar has negligible
mass and moment of inertia and also that all displacements are small. Write the describing
differential equations. Note that the relay coil is not free to move.

ECE/SJBIT Page 22
Control Systems 10ES43

13. Figure shows a control scheme for controlling the azimuth angle of an armature controlled
dc. Motion with dc generator used as an amplifier. Determine transfer function
L (s)
. The parameters of the plant are given below.
u (s)

Motor torque constant = KT in N.M /amp


Motor back emf constant = KB in V/ rad / Sec
Generator gain constant = KG in v/ amp
Motor to load gear ratio = N2
N1
Resistance of the circuit = R in ohms.

Inductance of the circuit = L in Henry

Moment of inertia of motor = J

Viscous friction coefficient = B

Field resistance = Rf

Field inductance = Lf

ECE/SJBIT Page 23
Control Systems 10ES43

14. The schematic diagram of a dc motor control system is shown in figure where K s is error
detector gain in volt/rad, k is the amplifier gain, Kb back emf constant, Kt is torque

constant, n is the gear train ratio = 2 = Tm Bm = motion friction constant


1 T2
Jm = motor inertia, KL = Torsional spring constant JL = load inertia.

15. Obtain a transfer function C(s) /R(s) for the positional servomechanism shown in figure.
Assume that the input to the system is the reference shaft position (R) and the system output is
the output shaft position ( C ). Assume the following constants.
Gain of the potentiometer (error detector ) K1 in V/rad
Amplifier gain Kp in V / V
Motor torque constant KT in V/ rad
Gear ratio N1 N2
Moment of inertia of load J

ECE/SJBIT Page 24
Control Systems 10ES43

Viscous friction coefficient f

16. Find the transfer function E0 (s) / I(s)

C1
I E0
C2 R Output
input

ECE/SJBIT Page 25
Control Systems 10ES43

Recommended Questions :

1. Name three applications of control systems.


2. Name three reasons for using feedback control systems and at least one reason for not
using them.
3. Give three examples of open- loop systems.
4. Functionally, how do closed loop systems differ from open loop systems.
5. State one condition under which the error signal of a feedback control system would not
be the difference between the input and output.
6. Name two advantages of having a computer in the loop.
7. Name the three major design criteria for control systems.
8. Name the two parts of a systems response.
9. Physically, what happens to a system that is unstable?
10. Instability is attributable to what part of the total response.
11. What mathematical model permits easy interconnection of physical systems?
12. To what classification of systems can the transfer function be best applied?
13. What transformation turns the solution of differential equations into algebraic
manipulations ?
14. Define the transfer function.
15. What assumption is made concerning initial conditions when dealing with transfer
functions?
16. What do we call the mechanical equations written in order to evaluate the transfer
function ?
17. Why do transfer functions for mechanical networks look identical to transfer functions
for electrical networks?
18. What function do gears and levers perform.
19. What are the component parts of the mechanical constants of a motors transfer function?

ECE/SJBIT Page 26
Control Systems 10ES43

UNIT-2

Block Diagram:

A control system may consist of a number of components. In order to show the functions
performed by each component in control engineering, we commonly use a diagram called the
Block Diagram.

A block diagram of a system is a pictorial representation of the function performed by


each component and of the flow of signals. Such a diagram depicts the inter-relationships which
exists between the various components. A block diagram has the advantage of indicating more
realistically the signal flows of the actual system.
In a block diagram all system variables are linked to each other through functional
blocks. The Functional Block or simply Block is a symbol for the mathematical operation on
the input signal to the block which produces the output. The transfer functions of the components
are usually entered in the corresponding blocks, which are connected by arrows to indicate the
direction of flow of signals. Note that signal can pass only in the direction of arrows. Thus a
block diagram of a control system explicitly shows a unilateral property.

Fig 2.1 shows an element of the block diagram. The arrow head pointing towards the block
indicates the input and the arrow head away from the block represents the output. Such arrows
are entered as signals.

X(s)
G(s Y(s)
)
Fig 2.1
The advantages of the block diagram representation of a system lie in the fact that it is
easy to form the over all block diagram for the entire system by merely connecting the blocks of
the components according to the signal flow and thus it is possible to evaluate the contribution of
each component to the overall performance of the system. A block diagram contains information
concerning dynamic behavior but does not contain any information concerning the physical
construction of the system. Thus many dissimilar and unrelated system can be represented by the
same block diagram.

ECE/SJBIT Page 27
Control Systems 10ES43

It should be noted that in a block diagram the main source of energy is not explicitly
shown and also that a block diagram of a given system is not unique. A number of a different
block diagram may be drawn for a system depending upon the view point of analysis.

Error detector : The error detector produces a signal which is the difference between the
reference input and the feed back signal of the control system. Choice of the error detector is
quite important and must be carefully decided. This is because any imperfections in the error
detector will affect the performance of the entire system. The block diagram representation of
the error detector is shown in fig2.2

+
R(s) C(s)
-

C(s)
Fig2.2

Note that a circle with a cross is the symbol which indicates a summing operation. The plus or
minus sign at each arrow head indicates whether the signal is to be added or subtracted. Note
that the quantities to be added or subtracted should have the same dimensions and the same units.

Block diagram of a closed loop system .

Fig2.3 shows an example of a block diagram of a closed system


Summing point

Branch point
R(s) C(s)
+
G(s)
-

Fig. 2.3

The output C(s) is fed back to the summing point, where it is compared with reference input
R(s). The closed loop nature is indicated in fig1.3. Any linear system may be represented by a
block diagram consisting of blocks, summing points and branch points. A branch is the point
from which the output signal from a block diagram goes concurrently to other blocks or
summing points.

ECE/SJBIT Page 28
Control Systems 10ES43

When the output is fed back to the summing point for comparison with the input, it is
necessary to convert the form of output signal to that of he input signal. This conversion is
followed by the feed back element whose transfer function is H(s) as shown in fig 1.4. Another
important role of the feed back element is to modify the output before it is compared with the
input.

B(s)
R(s) + C(s) C(s)
G(s
- )
B(s)
H(s
)
Fig 2.4

The ratio of the feed back signal B(s) to the actuating error signal E(s) is called the open
loop transfer function.
open loop transfer function = B(s)/E(s) = G(s)H(s)
The ratio of the output C(s) to the actuating error signal E(s) is called the feed forward
transfer function .
Feed forward transfer function = C(s)/E(s) = G(s)
If the feed back transfer function is unity, then the open loop and feed forward transfer
function are the same. For the system shown in Fig1.4, the output C(s) and input R(s) are related
as follows.
C(s) = G(s) E(s)
E(s) = R(s) - B(s)
= R(s) - H(s) C(s) but B(s) = H(s)C(s)
Eliminating E(s) from these equations
C(s) = G(s) [R(s) - H(s) C(s)]
C(s) + G(s) [H(s) C(s)] = G(s) R(s)
C(s)[1 + G(s)H(s)] = G(s)R(s)

ECE/SJBIT Page 29
Control Systems 10ES43

C(s) G(s)
=
R(s) 1 + G(s) H(s)
C(s)/R(s) is called the closed loop transfer function.

The output of the closed loop system clearly depends on both the closed loop transfer
function and the nature of the input. If the feed back signal is positive, then
C(s) G(s)
=
R(s) 1 - G(s) H(s)

Closed loop system subjected to a disturbance

Fig2.5 shows a closed loop system subjected to a disturbance. When two inputs are present in
a linear system, each input can be treated independently of the other and the outputs
corresponding to each input alone can be added to give the complete output. The way in
which each input is introduced into the system is shown at the summing point by either a plus
or minus sign.

Disturbance
N(s)

R(s) +
+ +
G1(s) G2(s) C(s)
-

H(s
) Fig2.5
Fig2.5 closed loop system subjected to a disturbance.

Consider the system shown in fig 2.5. We assume that the system is at rest initially with
zero error. Calculate the response CN(s) to the disturbance only. Response is
CN(s) G2(s)
=
R(s) 1 + G1(s)G2(s)H(s)
On the other hand, in considering the response to the reference input R(s), we may
assume that the disturbance is zero. Then the response CR(s) to the reference input R(s)is

ECE/SJBIT Page 30
Control Systems 10ES43

CR(s) G1(s)G2(s)
=
R(s) 1 + G1(s)G2(s)H(s).

The response C(s) due to the simultaneous application of the reference input R(s) and the
disturbance N(s) is given by
C(s) = CR(s) + CN(s)
G2(s)
C(s) = [G1(s)R(s) + N(s)]
1 + G1(s)G2(s)H(s)

Procedure for drawing block diagram :

To draw the block diagram for a system, first write the equation which describes the dynamic
behaviour of each components. Take the laplace transform of these equations, assuming zero
initial conditions and represent each laplace transformed equation individually in the form of
block. Finally assemble the elements into a complete block diagram.

As an example consider the Rc circuit shown in fig2.6 (a). The equations for the circuit
shown are
R

ei i eo
C

Fig. 2.6a

ei = iR + 1/c idt -----------(1)


And
eo = 1/c idt ---------(2)

Equation (1) becomes

ei = iR + eo
ei - eo
=i --------------(3)
R

ECE/SJBIT Page 31
Control Systems 10ES43

Laplace transforms of equations (2) & (3) are

Eo(s) = 1/CsI(s) -----------(4)


Ei(s) - Eo(s)
= I(s) -------- (5)
R

Equation (5) represents a summing operation and the corresponding diagram is shown in fig1.6
(b). Equation (4) represents the block as shown in fig2.6(c). Assembling these two elements, the
overall block diagram for the system shown in fig2.6(d) is obtained.

I(s) Eo(S)
Ei(s) + I(s) 1/C
1/R S
_ Fig2.6(c)
Eo(s)
Eo(s) + I(s) Eo(s)
1/R 1/C
Fig2.6(b) _ S

Fig2.6(d)

SIGNAL FLOW GRAPHS

An alternate to block diagram is the signal flow graph due to S. J. Mason. A signal flow graph is
a diagram that represents a set of simultaneous linear algebraic equations. Each signal flow graph
consists of a network in which nodes are connected by directed branches. Each node represents a
system variable, and each branch acts as a signal multiplier. The signal flows in the direction
indicated by the arrow.

Definitions:
Node: A node is a point representing a variable or signal.
Branch: A branch is a directed line segment joining two nodes.
Transmittance: It is the gain between two nodes.
Input node: A node that has only outgoing branche(s). It is also, called as source and
corresponds to independent variable.

ECE/SJBIT Page 32
Control Systems 10ES43

Output node: A node that has only incoming branches. This is also called as sink and
corresponds to dependent variable.
Mixed node: A node that has incoming and out going branches.
Path: A path is a traversal of connected branches in the direction of branch arrow.
Loop: A loop is a closed path.
Self loop: It is a feedback loop consisting of single branch.
Loop gain: The loop gain is the product of branch transmittances of the loop.
Nontouching loops: Loops that do not posses a common node.
Forward path: A path from source to sink without traversing an node more than once.
Feedback path: A path which originates and terminates at the same node.
Forward path gain: Product of branch transmittances of a forward path.
Properties of Signal Flow Graphs:
1) Signal flow applies only to linear systems.
2) The equations based on which a signal flow graph is drawn must be algebraic equations
in the form of effects as a function of causes.
Nodes are used to represent variables. Normally the nodes are arranged left to right,
following a succession of causes and effects through the system.
3) Signals travel along the branches only in the direction described by the arrows of the
branches.
4) The branch directing from node Xk to Xj represents dependence of the variable Xj on Xk
but not the reverse.
5) The signal traveling along the branch Xk and Xj is multiplied by branch gain akj and
signal akjXk is delivered at node Xj.

Guidelines to Construct the Signal Flow Graphs:

The signal flow graph of a system is constructed from its describing equations, or by direct
reference to block diagram of the system. Each variable of the block diagram becomes a node
and each block becomes a branch. The general procedure is

1) Arrange the input to output nodes from left to right.


2) Connect the nodes by appropriate branches.
3) If the desired output node has outgoing branches, add a dummy node and a unity gain
branch.
4) Rearrange the nodes and/or loops in the graph to achieve pictorial clarity.

ECE/SJBIT Page 33
Control Systems 10ES43

Signal Flow Graph Algebra

Addtion rule
The value of the variable designated by a node is equal to the sum of all signals entering the
node.
Transmission rule
The value of the variable designated by a node is transmitted on every branch leaving the node.
Multiplication rule
A cascaded connection of n-1 branches with transmission functions can be replaced by a single
branch with new transmission function equal to the product of the old ones.

Masons Gain Formula

The relationship between an input variable and an output variable of a signal flow graph is given
by the net gain between input and output nodes and is known as overall gain of the system.
Masons gain formula is used to obtain the over all gain (transfer function) of signal flow graphs.

Gain P is given by
1
P Pk k
k
Where, Pk is gain of kth forward path,
is determinant of graph

=1-(sum of all individual loop gains)+(sum of gain products of all possible combinations of
two nontouching loops sum of gain products of all possible combination of three
nontouching loops) +

k is cofactor of kth forward path determinant of graph with loops touching k th forward path. It is
obtained from by removing the loops touching the path P k.

Example1
Draw the signal flow graph of the block diagram shown in Fig.2.7

H2

X1 X2 X3 X4 X5 X6 C
R
G1 G2 G3

H1

Figure 2.7 Multiple loop system

ECE/SJBIT Page 34
Control Systems 10ES43

Choose the nodes to represent the variables say X1 .. X6 as shown in the block diagram..
Connect the nodes with appropriate gain along the branch. The signal flow graph is shown in
Fig. 2.7

-H2

R X1 X2 X3 C
1 1 G1 1 G2 G3 1

X4
X5 X6
H1

-1

Figure 1.8 Signal flow graph of the system shown in Fig. 2.7

Example 2.9

Draw the signal flow graph of the block diagram shown in Fig.2.9.

G1
X1 X2
R C




G2

G3

X3

G4

Figure 2.9 Block diagram feedback system

ECE/SJBIT Page 35
Control Systems 10ES43

The nodal variables are X1, X2, X3.


The signal flow graph is shown in Fig. 2.10.
G1

R G2 1
X2 1 X3 C

X1
-G3

G4

Figure 2.10 Signal flow graph of example 2

Example 3
Draw the signal flow graph of the system of equations.

X 1 a11 X 1 a12 X 2 a13 X 3 b1u1


X 2 a 21 X 1 a 22 X 2 a 23 X 3 b2 u 2
X 3 a31 X 1 a32 X 2 a33 X 3

The variables are X1, X2, X3, u1 and u2 choose five nodes representing the variables.
Connect the various nodes choosing appropriate branch gain in accordance with the equations.
The signal flow graph is shown in Fig. 2.11.

ECE/SJBIT Page 36
Control Systems 10ES43

a13
a12
u2

b2
a33
a11 X2
u1 b1 a21 a32

X1
X3
a22

a23

a31

Figure 2.11 Signal flow graph of example 2

Example 4
LRC net work is shown in Fig. 2.12. Draw its signal flow graph.

R L

ec(t)
e(t) i(t)
C

Figure 2.12 LRC network


The governing differential equations are
L Ri idt et 1
di 1
dt C
or

L Ri ec et 2
di
dt
de
C c i t 3
dt

Taking Laplace transform of Eqn.1 and Eqn.2 and dividing Eqn.2 by L and Eqn.3 by C

ECE/SJBIT Page 37
Control Systems 10ES43


sI s i 0
R
L
I S E c s E s 4
1
L
1
L

sEc s ec 0 I s 5
C
1

Eqn.4 and Eqn.5 are used to draw the signal flow graph shown in Fig.7.

i(0+)
ec(0+)
1
1 sR L 1

LsR
L
1 s
Cs Ec(s)
I(s)
E(s) -1

LsR
L

Figure 2.12 Signal flow graph of LRC system

ECE/SJBIT Page 38
Control Systems 10ES43

SIGNAL FLOW GRAPHS

The relationship between an input variable and an output variable of a signal flow graph is given
by the net gain between input and output nodes and is known as overall gain of the system.
Masons gain formula is used to obtain the over all gain (transfer function) of signal flow graphs.

Masons Gain Formula

Gain P is given by
1
P Pk k
k

Where, Pk is gain of kth forward path,


is determinant of graph

=1-(sum of all individual loop gains) + (sum of gain products of all possible combinations of
two nontouching loops sum of gain products of all possible combination of three
nontouching loops) +

k is cofactor of kth forward path determinant of graph with loops touching k th forward path. It is
obtained from by removing the loops touching the path P k.

Example 1
Obtain the transfer function of C/R of the system whose signal flow graph is shown in Fig.2.13

G1

R
G2 1 1 C

-G3
G4

Figure 2.13 Signal flow graph of example 1

There are two forward paths:


Gain of path 1 : P1=G1
Gain of path 2 : P2=G2

ECE/SJBIT Page 39
Control Systems 10ES43

There are four loops with loop gains:


L1=-G1G3, L2=G1G4, L3= -G2G3, L4= G2G4
There are no non-touching loops.
= 1+G1G3-G1G4+G2G3-G2G4
Forward paths 1 and 2 touch all the loops. Therefore, 1= 1, 2= 1

C s P11 P2 2 G1 G2
The transfer function T =
Rs 1 G1G3 G1G4 G2 G3 G2 G4

Example 2
Obtain the transfer function of C(s)/R(s) of the system whose signal flow graph is shown in
Fig.2.14.

-H2
R(s) G2 C(s)
1 1 G1 G3 1

H1
-1

Figure 2.14 Signal flow graph of example 2

There is one forward path, whose gain is: P1=G1G2G3


There are three loops with loop gains:
L1=-G1G2H1, L2=G2G3H2, L3= -G1G2G3
There are no non-touching loops.
= 1-G1G2H1+G2G3H2+G1G2G3
Forward path 1 touches all the loops. Therefore, 1= 1.
C s P11 G1G2 G3
The transfer function T =
Rs 1 G1G2 H 1 G1G3 H 2 G1G2 G3

Example 3
Obtain the transfer function of C(s)/R(s) of the system whose signal flow graph is shown in
Fig.2.15.

ECE/SJBIT Page 40
Control Systems 10ES43

G6 G7

R(s) G1 C(s)
G2 G3 G4 G5 1

X1 X2 X3 X4
X5
-H1
-H2

Figure 2.15 Signal flow graph of example 3

There are three forward paths.


The gains of the forward path are: P1=G1G2G3G4G5
P2=G1G6G4G5
P3= G1G2G7
There are four loops with loop gains:
L1=-G4H1, L2=-G2G7H2, L3= -G6G4G5H2, L4=-G2G3G4G5H2
There is one combination of Loops L1 and L2 which are nontouching with loop gain product
L1L2=G2G7H2G4H1
= 1+G4H1+G2G7H2+G6G4G5H2+G2G3G4G5H2+ G2G7H2G4H1
Forward path 1 and 2 touch all the four loops. Therefore 1= 1, 2= 1.
Forward path 3 is not in touch with loop1. Hence, 3= 1+G4H1.

The transfer function

T= C(s) / R(s)

C s P11 P2 2 P3 3 G1G2 G3G4 G5 G1G4 G5G6 G1G2 G7 1 G4 H 1



Rs 1 G4 H 1 G2 G7 H 2 G6 G4 G5 H 2 G2 G3G4 G5 H 2 G2 G4 G7 H 1 H 2

ECE/SJBIT Page 41
Control Systems 10ES43

Example 4

X6 X5 X3
Find the gains , , for the signal flow graph shown in Fig.2.16.
X1 X 2 X1

b -h

X1 a d X5 f X6
c e
X2 X3 X4

-g
-i

Figure 2.16 Signal flow graph of MIMO system

X6
Case 1:
X1

There are two forward paths.


The gain of the forward path are: P1=acdef
P2=abef
There are four loops with loop gains:
L1=-cg, L2=-eh, L3= -cdei, L4=-bei
There is one combination of Loops L1 and L2 which are nontouching with loop gain product
L1L2=cgeh
= 1+cg+eh+cdei+bei+cgeh
Forward path 1 and 2 touch all the four loops. Therefore 1= 1, 2= 1.
X 6 P11 P2 2 cdef abef
The transfer function T =
X1 1 cg eh cdei bei cgeh

ECE/SJBIT Page 42
Control Systems 10ES43

X5
Case 2:
X2
The modified signal flow graph for case 2 is shown in Fig.2.17.

b -h

X2 X5 X5
1 d e 1
c
X2 X3 X4

-g

-i

Figure 2.17 Signal flow graph of example 4 case 2

The transfer function can directly manipulated from case 1 as branches a and f are removed
which do not form the loops. Hence,

X 5 P11 P2 2 cde be
The transfer function T=
X2 1 cg eh cdei bei cgeh

X3
Case 3:
X1
The signal flow graph is redrawn to obtain the clarity of the functional relation as shown in
Fig.2.18. -h

c
X1 a X2 b e X5 f 1 X3

X4 X3
-i d

-g

Figure 2.18 Signal flow graph of example 4 case 3

ECE/SJBIT Page 43
Control Systems 10ES43

There are two forward paths.


The gain of the forward path are: P1=abcd
P2=ac
There are five loops with loop gains:
L1=-eh, L2=-cg, L3= -bei, L4=edf, L5=-befg
There is one combination of Loops L1 and L2 which are nontouching with loop gain product
L1L2=ehcg
= 1+eh+cg+bei+efd+befg+ehcg
Forward path 1 touches all the five loops. Therefore 1= 1.
Forward path 2 does not touch loop L1. Hence, 2= 1+ eh

X 3 P11 P2 2 abef ac1 eh


The transfer function T =
X1 1 eh cg bei efd befg ehcg

Example 5

For the system represented by the following equations find the transfer function X(s)/U(s) using
signal flow graph technique.
X X 1 3u

X 1 a1 X 1 X 2 2 u

X 2 a 2 X 1 1u

Taking Laplace transform with zero initial conditions


X s X 1 s 3U s
sX 1 s a1 X 1 s X 2 s 2U s
sX 2 s a 2 X 1 s 1U s

Rearrange the above equation


X s X 1 s 3U s
a1
X 1 s X 1 s X 2 s 2 U s
1
s s s
a2
X 2 s X 1 s 1 U s
s s

The signal flow graph is shown in Fig.2.19.

ECE/SJBIT Page 44
Control Systems 10ES43

1
s
a1
2 a2
X1 s X
s s X
X2
U 1
s 1

Figure 2.19 Signal flow grapgh of example 5

There are three forward paths.


The gain of the forward path are: P1=3
P2=1/ s2
P3=2/ s

There are two loops with loop gains:


a1
L1
s
a
L2 2 2
s
L1=-eh, L2=-cg, L3= -bei, L4=edf, L5=-befg

There are no combination two Loops which are nontouching.


a a
1 1 22
s s

Forward path 1 does not touch loops L1 and L2. Therefore


a a
1 1 1 22
s s

Forward path 2 path 3 touch the two loops. Hence, 2= 1, 2= 1.

The transfer function T =



X 3 P11 P2 2 P3 3 3 s 2 a1 s a2 2 s 1
X1 s 2 a1 s a2

ECE/SJBIT Page 45
Control Systems 10ES43

Recommended Questions:

1. Define block diagram & depict the block diagram of closed loop system.
2. Write the procedure to draw the block diagram.

3. Define signal flow graph and its parameters

4. Explain briefly Masons Gain formula


5. Draw the signal flow graph of the block diagram shown in Fig below.

H2

X1 X2 X3 X4 X5 X6 C
R
G1 G2 G3

H1

6. Draw the signal flow graph of the block diagram shown in Fig below

G1
X1 X2
R C




G2

G3

X3

G4

ECE/SJBIT Page 46
Control Systems 10ES43

7. For the LRC net work is shown in Fig Draw its signal flow graph.

R L

ec(t)
e(t) i(t)
C

Figure

8. Obtain the transfer function of C(s)/R(s) of the system whose signal flow graph is shown in
Fig.

G6 G7

R(s) G1 C(s)
G2 G3 G4 G5 1
X1 X X3 X4 X5
2 -H1
-H2

Q.9 For the system represented by the following equations find the transfer function X(s)/U(s)
using signal flow graph technique.
X X 1 3u

X 1 a1 X 1 X 2 2u

X 2 a2 X 1 1u

ECE/SJBIT Page 47
Control Systems 10ES43

UNIT- 3

Time response analysis of control systems:

Introduction:
Time is used as an independent variable in most of the control systems. It is important to
analyze the response given by the system for the applied excitation, which is function of time.
Analysis of response means to see the variation of out put with respect to time. The output
behavior with respect to time should be within these specified limits to have satisfactory
performance of the systems. The stability analysis lies in the time response analysis that is when
the system is stable out put is finite

The system stability, system accuracy and complete evaluation is based on the time
response analysis on corresponding results.

DEFINITION AND CLASSIFICATION OF TIME RESPONSE

Time Response:
The response given by the system which is function of the time, to the applied excitation is
called time response of a control system.
Practically, output of the system takes some finite time to reach to its final value.
This time varies from system to system and is dependent on different factors.
The factors like friction mass or inertia of moving elements some nonlinearities present etc.
Example: Measuring instruments like Voltmeter, Ammeter.

Classification:

The time response of a control system is divided into two parts.


1 Transient response ct(t)
2 Steady state response css(t)
. . . c(t)=ct(t) +cSS(t)
Where c (t) = Time Response
Total Response=Zero State Response +Zero Input Response

Transient Response:
It is defined as the part of the response that goes to zero as time becomes very large. i,e,
Lim ct(t) = 0
t

A system in which the transient response do not decay as time progresses is an Unstable
system.

ECE/SJBIT Page 48
Control Systems 10ES43

C(t)
Ct(t) Css(t)
Step
ess
= study state
error

O Time The transient response may be experimental


Transient time Study state
or oscillatory in nature.
Time

2. Steady State Response:


It is defined the part of the response which remains after complete transient response
vanishes from the system output.
. i,e, Lim ct(t)=css(t)
t

The time domain analysis essentially involves the evaluation of the transient and
Steady state response of the control system.

Standard Test Input Signals:

For the analysis point of view, the signals, which are most commonly used as reference
inputs, are defined as standard test inputs.

The performance of a system can be evaluated with respect to these test signals.
Based on the information obtained the design of control system is carried out.
The commonly used test signals are
1. Step Input signal.
2. Ramp Input Signals.
3. Parabolic Input Signal.
4. Impulse input signal.

Details of standard test signals

1. Step input signal (position function)


It is the sudden application of the input at a specified time as usual in the figure or
instant any us change in the reference input
Example :-
a. If the input is an angular position of a mechanical shaft a step input represent
the sudden rotation of a shaft.
b. Switching on a constant voltage in an electrical circuit.
ECE/SJBIT Page 49
Control Systems 10ES43

c. Sudden opening or closing a valve.

r(t)

O t
When, A = 1, r(t) = u(t) = 1

The step is a signal whos value changes from 1 value (usually 0) to another level A in
Zero time.
In the Laplace Transform form R(s) = A / S
Mathematically r(t) = u(t)
= 1 for t > 0
= 0 for t < 0

2. Ramp Input Signal (Velocity Functions):

It is constant rate of change in input that is gradual application of input as shown


in fig (2 b). r(t)
Ex:- Altitude Control
of a Missile
Slope = A

t
O

The ramp is a signal, which starts at a value of zero and increases linearly with
time.
Mathematically r (t) = A t for t 0
= 0 for t 0.

In LT form R(S) = A
S2
If A=1, it is called Unit Ramp Input

Mathematically
r(t) = t u(t)
{
In LT form R(S) = A = 1 t for t 0
S2 S2 =
0 for t 0

ECE/SJBIT Page 50
Control Systems 10ES43

3. Parabolic Input Signal (Acceleration function):


The input which is one degree faster than a ramp type of input as shown in fig (2 c) or
it is an integral of a ramp.
Mathematically a parabolic signal of magnitude

A is given by r(t) = A t 2 u(t)


2 Slope = At
r(t) 2
At for t 0
= 2
0 for t 0
t

In LT form R(S) = A
S3
If A = 1, a unit parabolic function is defined as r(t) = t2 u(t)
2
ie., r(t)
{
In LT for R(S) = 1 t2 for t 0
= 2
S3
0 for t 0
4. Impulse Input Signal :

It is the input applied instantaneously (for short duration of time) of very high amplitude
as shown in fig 2(d)
Eg: Sudden shocks i e, HV due lightening or short circuit.
It is the pulse whose magnitude is infinite while its width tends to zero.
r(t)
ie., t 0 (zero) applied
momentarily
A

O t
t 0

Area of impulse = its magnitude


If area is unity, it is called Unit Impulse Input denoted as (t)
Mathematically it can be expressed as
r(t) = A for t = 0
= 0 for t 0

ECE/SJBIT Page 51
Control Systems 10ES43

In LT form R(S) = 1 if A = 1

Standard test Input Signals and its Laplace Transforms.

r(t) R(S)
Unit Step 1/S
Unit ramp 1/S2
Unit Parabolic 1/S3
Unit Impulse 1

First order system:-

The 1st order system is represent by the differential Eq:- a1dc(t )+ao c (t) = bo r(t)------ (1)
dt

Where, e (t) = out put , r(t) = input, a0, a1 & b0 are constants.

Dividing Eq:- (1) by a0, then a1. d c(t ) + c(t) = bo.r (t)
a0 dt ao

T . d c(t ) + c(t) = Kr (t) ---------------------- (2)


dt

Where, T=time const, has the dimensions of time = a1 & K= static sensitivity = b0
a0 a0

Taking for L.T. for the above Eq:- [ TS+1] C(S) = K.R(S)

T.F. of a 1st order system is ; G(S) = C(S ) = K .


R(S) 1+TS

If K=1, Then G(S) = 1 . [ Its a dimensionless T.F.]


1+TS I

This system represent RC ckt. A simplified block diagram is as shown.;

R(S)+ 1 C(S)
TS
-

ECE/SJBIT Page 52
Control Systems 10ES43

Unit step response of 1st order system:-

Let a unit step i\p u(t) be applied to a 1st order system,


Then, r (t) = u (t) & R(S) = 1 . ---------------(1)
S
W.K.T. C(S) = G(S). R(S)
C(S) = 1 . 1 . = 1 . T . ----------------- (2)
1+TS S S TS+1

Taking inverse L.T. for the above Eq:-

then, C(t)=u (t) e t/T ; t.>0.------------- (3) slope = 1 .


T
At t=T, then the value of c(t)= 1- e 1 = 0.632. c (t)

The smaller the time const. T. the


faster the system response. 0.632 1 e t/T

The slope of the tangent line at at t= 0 is 1/T.


t/T
Since dc = 1 .e - = 1 . at t .=0. ------------- (4)
dt T T t
T
From Eq:- (4) , We see that the slope of the response curve c(t) decreases monotonically from 1
. at t=0 to zero. At t=
T

Second order system:-

The 2nd order system is defined as,


a2 d2 c(t) + a1 dc(t) + a0 c(t) = b0 .r(t)-----------------(1)
dt2 dt

Where c(t) = o/p & r(t) = I/p


-- ing (1) by a0,

a2 d2 c(t) + a1 . dc (t) + c(t) = b0 . r(t).


a0 dt2 a0 dt a0

a2 d2 c(t) + 2a1 . a2 . dc (t) + c(t) = b0 . r(t).


a0 dt2 2a0 a0 . a2 dt a0

3) The open loop T.F. of a unity feed back system is given by G(S) = K . where,
S(1+ST)
ECE/SJBIT Page 53
Control Systems 10ES43

T&K are constants having + ve values. By what factor (1) the amplitude gain be reduced so
that (a) The peak overshoot of unity step response of the system is reduced from 75% to 25%
(b) The damping ratio increases from 0.1 to 0.6.

Solution: G(S) = K .
S(1+ST)

Let the value of damping ratio is, when peak overshoot is 75% & when peak
overshoot is 25%

Mp =
e 1- 2

ln 0. 75 = . 0.0916 = .
1- 2 1- 2

1 = 0.091 (0.0084) (1-2) = 2


2 = 0.4037 (1.0084 2) = 0.0084
= 0.091

K/( S + S2T ) .
w.k.t. T.F. = G(S) = 1+ K . .= K
1+ G(S) . H(S) ( S + S2 T ) S + S2T+K

T.F. = K/T .
S2 + S + K .
T T

Comparing with std Eq :-

Wn = K . , 2 Wn = 1 .
T T

Let the value of K = K1 When = 1 & K = K2 When = 2.


Since 2 Wn = 1 . , = 1 . = 1 .
T 2TWn 2 KT
1 .
1 . = 2 K1T = K2 .
2 1 K1
2 K2T

ECE/SJBIT Page 54
Control Systems 10ES43

0.091 = K2 . K2 . = 0.0508
0.4037 K1 K1

K2 = 0.0508 K1

a) The amplitude K has to be reduced by a factor = 1 . = 20


0.0508
b) Let = 0.1 Where gain is K1 and
= 0.6 Where gain is K2
0.1 = K2 . K2 . = 0.027 K2 = 0.027 K1
0.6 K1 K1

The amplitude gain should be reduced by 1 . = 36


0.027

4) Find all the time domain specification for a unity feed back control system whose open loop
T.F. is given by

G(S) = 25 .
S(S+6)

Solution:
25 .
G(S) = 25 . G(S) . = S(S+6) .
S(S+6) 1 + G(S) .H(S) 1 + 25 .
S(S+6)
= 25 .
S2 + ( 6S+25 )

W2n = 25 , Wn = 5, 2 Wn = 6 = 6 . = 0.6
2x5
Wd = Wn 1- = 5 1- (0.6) = 4
2 2

tr = - , = tan-1 Wd = Wn = 0.6 x 5 = 3
Wd

= tan-1 ( 4/3 ) = 0.927 rad.

tp = . = 3.14 = 0.785 sec.


Wd 4

MP = = - 0.6 . x3.4 = 9.5%


e 1- 2 e 1- 0.62

ECE/SJBIT Page 55
Control Systems 10ES43

ts = 4 . for 2% = 4 . = 1.3 3sec.


Wn 0.6 x 5

5) The closed loop T.F. of a unity feed back control system is given by

C(S) = 5 . Determine (1) Damping ratio (2) Natural


R(S) 2
S + 4S +5 undamped response frequency Wn. (3) Percent
peak over shoot Mp (4) Expression for error
resoponse.

Solution:

C(S) = 5 . , Wn2 = 5 Wn = 5 = 2.236


R(S) S2 + 4S +5

2Wn = 4 = 4 . = 0.894. Wd = 1.0018


2 x 2.236

MP = = 0.894 . X 3.14 = 0.19%


e 1- 2 e
1-(0.894)2

W. K.T. C(t) = e-Wnt Cos Wdtr + . sin wdtr


1-2

= e-0.894x2.236t Cos 1.0018t + 0.894 . sin 1.0018t


1-(0.894)2

6) A servo mechanism is represent by the Eq:-

d2 + 10 d = 150E , E = R- is the actuating signal calculate the


dt2 dt value of damping ratio, undamped and damped
frequency of ascillation.

Soutions:- d2 + 10 d = 15 ( r - ) , = 150r 150.


dt2 dt

Taking L.T., [S2 + 10S + 150] (S) = 150 R (S).

ECE/SJBIT Page 56
Control Systems 10ES43

(S) = 150 .
2
R(S) S + 10S + 15O

Wn2 = 150 Wn = 12.25. .rad sec .1

2Wn = 10 = 10 . = 0.408.
2 x 12.25

Wd = Wn 1 - 2 = 12.25 1- (0.408)2 = 11.18. rad 1sec.

7) Fig shows a mechanical system and the response when 10N of force is applied to the system.
Determine the values of M, F, K,.

x(t)inmt
K
f(t) 0.00193
The T.F. of the mechanical system is ,
0.02
X(S) = 1 .
M F(S) 2
MS + FS = K
f(t) = Md2X + F dX + KX
F x dt2 dt
F(S) = (MS2 + FS + K) x (S)
1 2 3 4 5

Given :- F(S) = 10
S.
X(S) = 10 .
S(MS2 + FS + K)
SX (S) = 10 .
MS2 + FS + K

The steady state value of X is By applying final value theorem,

lt. SX(S) = 10 . = 10 = 0.02 ( Given from Fig.)


S O M(0) + F (0) + K K. ( K = 500.)

MP = 0.00193 = 0.0965 = 9.62%


0.02

Mp =
e 1- 2

ECE/SJBIT Page 57
Control Systems 10ES43

0.744 = . 0.5539 = 2 .
1 - 2 1 - 2

0.5539 0.5539 2 = 2
= 0.597 = 0.6
tp = = .
Wd Wn 1 2

3 = . Wn = 1.31 rad / Sec.


2
Wn (1 (0.6) )

S x(S) = 10/ M .
2
(S + F S + K )
M M

Comparing with the std. 2nd order Eq :-, then,

Wn2 = K Wn = K (1.31)2 = 500 . M = 291.36 kg.


M M M

F = 2Wn F = 2 x 0.6 x 291 x 1.31


M F = 458.7 N/M/ Sec.

8) Measurements conducted on sever me mechanism show the system response to be c(t) =


1+0.2e-60t 1.2e-10t , When subjected to a unit step i/p. Obtain the expression for closed
loop T.F the damping ratio and undamped natural frequency of oscillation .

Solution:
C(t) = 1+0.2e-60t 1.2e-10t
Taking L.T., C(S) = 1 . + 0.2 . 1.2 .
S S+60 S+10

C(S) . = 600 / S .
S2 + 70S + + 600

Given that :- Unit step i/p r(t) = 1 R(S) = 1 .

C(S) . = 600 / S .
2
R(S) S + 70S + + 600

ECE/SJBIT Page 58
Control Systems 10ES43

Comparing, Wn2 = 600, 24.4 ..rad / Sec

2 Wn =
70, = 70 . = 1.428
2 x 24.4

10) A feed back system employing o/p damping is as shown in fig.


1) Find the value of K1 & K2 so that closed loop system resembles a 2 nd order system with
= 0.5 & frequency of damped oscillation 9.5 rad / Sec.
2) With the above value of K1 & K2 find the % overshoot when i/p is step i/p
3) What is the % overshoot when i/p is step i/p, the settling time for 2% tolerance?

K1 1 . R + C
S(1+S)
__
K2S

C . = K1 .
R S2 + ( 1 + K2 ) S + K1

Wn2 = K1 Wn = K1
2Wn = 1 + K2 = 1 + K2
2 K1
Wd = Wn 1 - 2 Wn = 9.5 . 10.96 rad/Sec
1 0.52

K1 = (10.96)2 = 120.34
2Wn = 1 + K2 , K2 = 9.97

Mp =
e 1- 2

ECE/SJBIT Page 59
Control Systems 10ES43

Mp = 16.3%

Ts = 4 . = 4 . = 0.729 sec
Wn 0.5 x 10.97

Steady state Error :-


Steady state errors constitute an extremely important aspect of system
performance. The state error is a measure of system accuracy. These errors arise from the nature
of i/ps type of system and from non-linearties of the system components. The steady state
performance of a stable control system is generally judged by its steady state error to step, ramp
and parabolic i/p.

Consider the system shown in the fig.

G(S)
R(S) E(S) C(S)

H(S)

C(S) = G(S) . (1)


R(S) 1+G(S) . H(S)

The closed loop T.F is given by (1). The T.F. b/w the actuating error signal e(t) and the
i/p signal r(t) is,

E(S) = R(S) C(S) H(S) = 1 C(S) . H(S)


R(S) R(S) R(S)

= 1 G(S) . H(S) . = 1 + G(S) . H(S) G(S)H(S)


1 + G(S) . H(S) 1+G(S) . H(S)

= 1 .
1 + G(S) . H(S)

Where e(t) = Difference b/w the i/p signal and the feed back signal

ECE/SJBIT Page 60
Control Systems 10ES43

E(S) = 1 . .R(S) .(1)


1 + G(S) . H(S)
The steady state error ess may be found by the use of final value theorem
and is as follows;

ess = lt e(t) = lt SE(S)


t S O

Substituting (1), ess = lt S.R(S) . .(2)


S O 1+G(S) . H(S)

Eq :- (2) Shows that the steady state error depends upon the i/p R(S) and the forward T.F.
G(S) and loop T.F G(S) . H(S).
The expression for steady state errors for various types of standard test signals are
derived below;
1) Steady state error due to step i/p or position error constant (Kp):-

The steady state error for the step i/p is


I/P r(t) = u(t). Taking L.T., R(S) = 1/S.
From Eq:- (2), ess = lt S. R(s) . = 1 .
S O 1 +G(S). H.S 1 + lt G(S). H(S)
SO

lt G(S) . H(S) = Kp
(S O )
Where Kp = proportional error constant or position error const.
ess = 1 .
1 + Kp
(1 + Kp) ess = 1 Kp = 1 - ess
ess

Note :- ess = R . for non-unit step i/p


1 + Kp

2) Steady state error due to ramp i/p or static velocity error co-efficient (Kv) :-
The ess of the system with a unit ramp i/p or unit velocity i/p is given by,

r ( t) = t. u(t) , Taking L -T, R(S) = 1/S2

Substituting this to ess Eq:-


ess = lt S . . 1 . = lt 1 .
S O 1 + G(S) . H(s) S2 S O S +S G(S) H(s)S

lt = SG(S) . H(S) = Kv = velocity co-efficient then

ECE/SJBIT Page 61
Control Systems 10ES43

S O

ess = lt 1 . ess = 1 .
S O (S + Kv) Kv

Velocity error is not an error in velocity , but it is an error in position error due to a ramp
i/p

3) Steady state error due to parabolic i/p or static acceleration co-efficient (Ka) :-

The steady state actuating error of the system with a unit parabolic i/p (acceleration i/p)
which is defined by r(t) + 1 . t2 Taking L.T. R(S)= 1 .
2 S3

ess = lt S . 1 . lt 1 .
S O 1 + G(S) . H(S) S 3
S O S + S2 G(S) . H(S)
2

2
lt S G(S) . H(S) = Ka.
S O

ess = lt 1 . = 1 .
S O 2
S + Ka Ka

Note :- ess = R . for non unit parabolic.


Ka

Types of feed back control system :-

The open loop T.F. of a unity feed back system can be written in two std, forms;

1) Time constant form and 2) Pole Zero form,


G(S) = K(TaS +1) (TbS +1)..
Sn(T1 S+1) (T2S + 1).

Where K = open loop gain.


Above Eq:- involves the term Sn in denominator which corresponds to no, of
integrations in the system. A system is called Type O, Type1, Type2,.. if n = 0, 1,
2, .. Respectively. The Type no., determines the value of error co-efficients. As
the type no., is increased, accuracy is improved; however increasing the type no.,
aggregates the stability error. A term in the denominator represents the poles at the origin
in complex S plane. Hence Index n denotes the multiplicity of the poles at the origin.
The steady state errors co-efficient for a given type have definite values. This is
illustration as follows.

ECE/SJBIT Page 62
Control Systems 10ES43

1) Type O system :- If, n = 0, the system is called type 0, system. The


steady state error are as follows;
. .
Let, G(S) = K . [ . H(s) = 1]
S+1

ess (Position) = 1 . = 1 .= 1 .
1 + G(O) . H(O) 1+K 1 + Kp
. .
. Kp = lt G(S) . H(S) = lt K . = K
S 0 S 0 S+1

ess (Velocity) = 1 . = 1 .=
Kv 0

Kv = lt G(S) . H(S) = lt S K . = 0.
S0 S 0 S + 1

ess (acceleration) = 1 . = 1 .=
Ka 0

Ka = lt S2 G(S) . H(S) = lt S2 K . =0
S0 S 0 S+1

2) Type 1 System :- If, n = 1, the ess to various std, i/p, G(S) = K .


S (S + 1)

ess (Position) = 1 . = O
1+

Kp = lt G(S) . H(S) = lt K . =
S O
S 0 S( S + 1)

Kv = lt
S K . = K
S 0
S(S+1)
ess (Velocity) = 1 .
K

ess (acceleration) = 1 . =
0

ECE/SJBIT Page 63
Control Systems 10ES43

Ka = lt S2 K . = 0.
S0 S (S + 1)

3) Type 2 System :- If, n = 2, the ess to various std, i/p, are , G(S) = K .
2
S (S + 1)
Kp = lt K .=
S 0 S2 (S + 1)
.
. . ess (Position) = 1 . = 0

Kv = lt S K .=
S0 S2 (S + 1)
.
. . ess (Velocity) = 1 . = 0

2
Ka = lt S K . = K.
S0 S2 (S + 1)
.
. . ess (acceleration) = 1 .
K

3) Type 3 System :- Gives Kp = Kv = Ka = & ess = 0.


(Onwards)

The error co-efficient Kp, Kv, & Ka describes the ability of the system to eliminate the steady
state error therefore they are indicative of steady state performance. It is generally described to
increase the error co-efficient while maintaining the transient response within an acceptable
limit.

PROBLEMS;

1. The unit step response of a system is given by

C (t) = 5/2 +5t 5/2 e-2t. Find the T. F of the system.

T/P = r(t) = U (t). Taking L.T, R(s) = 1/S.

Response C(t) = 5/2+5t-5/2 e-2t


1 + 2 - 1
S S2 S+2

ECE/SJBIT Page 64
Control Systems 10ES43

Taking L.T, C(s) = 5 1 +5 1 5 1 = 5


2 S S2 2 (S+2) 2

C(s) = 5 S(S+2)+2(S+2)-
S2 = 5 S2+2S+2S+4
s2 S2 (S+2) 2 S2(S+2)
2

= 10 (S+1)
S2 (S+2)

T.F = C (S) = 10 (S+1) S = 10 (S+1)


R (S) S2(S+2) S(S+2)

2. The open loop T F of a unity food back system is G(s) = 100


S (S+10)
Find the static error constant and the steady state error of the system when subjected to an i/p
given by the polynomial

R(t) = Po + p1t + P2 t2
2
G(s) = 100 position error co-efficient
S (S+10)

KP = lt G(s) = lt 100 =
S 0 S 0 S (S+10)

Similarly KV = lt SG(s) = lt 100 x s = 100 = 10


S 0 S 0 S (S+10)
10

lt 100 x s2 = 0
S 0 S 0 S (S+10) Ka = lt S2 G(S)

ECE/SJBIT Page 65
Control Systems 10ES43

Given :- r(t) = Po+P1t +P2 t2


2
R1 R2 R3
Therefore steady state error ess + +
1+Kp Kv Ka

R1 R2
R3+ P0 P1
ess =
+ P2
1+ 10 0 + +
1+ 10 0

Ess = 0+0.1 P1 + =

3. Determine the error co-efficeint and static error for G(s) = 1


And H(s) = (S+2) S(S+1) (S+10)

The error constants for a non unity feed back system is as follows
Kp = lt G(S) H(S) = (0+2)
lt (S+2) =
S 0 G(S).H(S) =S 0(0+1) (0+10)
0 S(S+1) (S+10)

Kv = lt G(S) H(S) = (0+2)


lt = 1/5 = 0.2
S 0 S 0(0+1) (0+10)
0
Ka = 0

Static Error:-

Steady state error for unit step i/p = 0


1 1
Unit ramp i/p
= =5
Kv 0.2

Unit parabolic i/p = 1/0 =

ECE/SJBIT Page 66
Control Systems 10ES43

4. A feed back C.S is described as G(S) = 50


H(S)=1/s.
S (S+2) (S+5)
For unit step i/p,cal steady state error constant and errors.

Kp = lt G(S) H(S) = 50
S 0 S 0
=
2
S (S+2) (S+5)

Kv = lt G(S) H(S) = lt 50 x S
S 0 S =
0 S2 (S+2) (S+5)

Ka = lt G(S) H(S) = lt S2 x 50 50
S 0 S = = 5
0 S2 (S+2) (S+5) 10

Ess = lt S. 1/S Lt S2 (S+2) (S+5)


The steady state error
S 0 1+50
S 0 S2 (S+2) (S+5) + 50
2
S (S+2)(S+5)
= 0/50 = 0
K
H(S) = 1
5. A certain feed back C.S is described by following C.S G(S) = S2 (S+20) (S+30)

Determine steady state error co-efficient and also determine the


value of K to limit the steady to 10 units due to i/p r(t) = 1 + 10 + t 20/2 t2.

Kp = lt G(S) H(S) = lt 50
S 0 S 0 =
2
S (S+20) (S+30)

ECE/SJBIT Page 67
Control Systems 10ES43

Kv = lt S K
S 0 S2 (S+20) (S+30) =

Ka = lt S2 K K
S 0 S2 (S+20) (S+30) 600

Steady state error:-


1 1
Error due to unit step i/p + =0
1+Kp 1+

Error due o r(t) ramp i/p


10 10
+ =0
Kv

20 40 20 x 600 12000
Error due to para i/p, = = =
, Ka 2Ka K K

r (t) = (0+0 12000 )/K= 10 = K = 1200

First order system:-

The 1st order system is represent by the differential Eq:- a1dc(t )+aoc (t) = bor(t)------ (1)
dt

Where, e (t) = out put , r(t) = input, a0, a1 & b0 are constants.

Dividing Eq:- (1) by a0, then a1. d c(t ) + c(t) = bo.r (t)
a0 dt ao

T . d c(t ) + c(t) = Kr (t) ---------------------- (2)


dt

ECE/SJBIT Page 68
Control Systems 10ES43

Where, T=time const, has the dimensions of time = a1 & K= static sensitivity = b0
a0 a0

Taking for L.T. for the above Eq:- [ TS+1] C(S) = K.R(S)

T.F. of a 1st order system is ; G(S) = C(S ) = K .


R(S) 1+TS

If K=1, Then G(S) = 1 . [ Its a dimensionless T.F.]


1+TS I

This system represent RC ckt. A simplified bloc diagram is as shown.;

R(S)+ 1 C(S)
TS
-

Unit step response of 1st order system:-

Let a unit step i\p u(t) be applied to a 1st order system,


Then, r (t)=u (t) & R(S) = 1 . ---------------(1)
S
W.K.T. C(S) = G(S). R(S)

C(S) = 1 . 1. = 1 . T . ----------------- (2)


1+TS S S TS+1

Taking inverse L.T. for the above Eq:-


then, C(t)=u (t) e t/T ; t.>0.------------- (3) slope = 1 .
T
At t=T, then the value of c(t)= 1- e 1 = 0.632. c (t)

The smaller the time const. T. the


faster the system response. 0.632 1 e t/T
The slope of the tangent line at at t= 0 is 1/T.
t/T
Since dc = 1 .e - = 1 . at t .=0. ------------- (4)
dt T T t
T
From Eq:- (4) , We see that the slope of the response curve c(t) decreases monotonically from 1
. at t=0 to zero. At t=
ECE/SJBIT Page 69
Control Systems 10ES43

Second order system:-

The 2nd order system is defined as,


a2 d2 c(t) + a1 dc(t) + a0 c(t) = b0 .r(t)-----------------(1)
dt2 dt

Where c(t) = o/p & r(t) = I/p


-- ing (1) by a0,

a2 d2 c(t) + a1 . dc (t) + c(t) = b0 . r(t).


a0 dt2 a0 dt a0

a2 d2 c(t) + 2a1 . a2 . dc (t) + c(t) = b0 . r(t).


a0 dt2 2a0 a0 . a2 dt a0

Step response of 2nd order system:

The T.F. = C(s) = Wn2 Based on value


R(s) 32+2 WnS+ Wn2

The system may be,


2) Under damped system (0< <1)
3) Critically damped system (=1)
4) Over damped system (>1)

1) Under damped system :- (0< <1)


In this case C(s) can be written as
R(s)

C(s) = Wn2
R(s) (S+ wn + jwd ) (S+ wn - jwd )

1-
2
Where wd = wn The Freq. wd is called damped
natural frequency

For a unit step i/p :- [ R(t)= 1 R(S) = 1/S]

ECE/SJBIT Page 70
Control Systems 10ES43

C(S) = Wn2 . X R (S) = Wn2 . = 1 .


(S2+2 Wn S+ Wn2) (S2+2 WnS+ Wn2) S

C(S) = 1 . S+2Wn .
S S +2 WnS+ Wn
2 2

= 1 . S+Wn . __ Wn . --------------- (5)


S (S+ Wn) + Wd
2 2
(S+ Wn + Wd )
2 2

C(S) = 1 . S+Wn . __ . Wd .
S (S+ Wn) 2 + Wd2 1- 2 (S+ Wn) 2 + Wd2

Taking ILT, C(t) = 1-e-Wnt COS Wdt + . Sin Wdt ------------ (6)
1- 2

The error signal for this system is the difference b/w the I/p & o/p.

e(t) = r(t) c(t) .


= 1 c(t)

= e-Wnt COS Wdt + . Sin Wdt --------------------- (7)


1- 2 t > o.

At t = , error exists b/w the i/p & o/p.

If the damping ratio = O, the response becomes undamped & oscillations continues
indefinitely.
The response C(t) for the zero damping case is ,
c(t) =1-1(COS wnt) =1- COS wnt ; t > O --------------------- (8)

From Eq:- (8) , we see that the Wn represents the undamped natural frequency of the system. If
the linear system has any amount of damping the undamped natural frequency cannot be
observed experimentally. The frequency, which may be observed, is the damped natural
frequency.
Wd =wn 1 2 This frequency is always lower than the undamped natural frequency. An
increase in would reduce the damped natural frequency Wd . If is increased beyond unity,
the response over damped & will not oscillate.

Critically damped case:- ( =1).

ECE/SJBIT Page 71
Control Systems 10ES43

If the two poles of C(S) are nearly equal, the system may be approximated by a
R(S)
Critically damped one.

For a step I/p R(S) = 1/S

C(S) = Wn2 . 1 .
S2+2 Wn S+ Wn2 S

= 1 . 1 . Wn .
2
S (S + Wn) ( S+ Wn)

= 1 . Wn2 .
S ( S + Wn )2S
Taking I.L.T.,

C(t) = 1 e -Wnt (1+wnt)

Over damped system :- ( > 1)

If this case, the two poles of C(S) are negative, real and unequal.
R(S)
For a unit step I/p R(S) = 1/S , then,

C(S) = Wn2 .
(S+ Wn + Wn 2 - 1 ) ( S+ Wn - Wn 2 1)

Taking ILT, C(t) = 1+ 1 . e ( + 2 1) Wn t.


S 1 (+ 1)
2 2

1 . e ( + (2 1)) Wn t.
S (2 1 )[(+ (2 1)]

C(t) = 1+ Wn . e-S1t . - e-S2t . ;t>O


S 2 1 S1 S2

Where S1 = ( + 2 1) Wn

S2 = ( - 2 1) Wn

Time response (Transient ) Specification (Time domain) Performance :-

ECE/SJBIT Page 72
Control Systems 10ES43

The performance characteristics of a controlled system are specified in terms of the


transient response to a unit step i/p since it is easy to generate & is sufficiently drastic.
MP
The transient response of a practical C.S often exhibits damped oscillations before
reaching steady state. In specifying the transient response characteristic of a C.S to unit step
i/p, it is common to specify the following terms.

1) Delay time (td)


2) Rise time (tr)

Response curve
3) Peak time (tp)
4) Max over shoot (Mp)
5) Settling time (ts)

1) Delay time :- (td)


It is the time required for the response to reach 50% of its final value for the 1 st
time.

2) Rise time :- (tr)


It is the time required for the response to rise from 10% and 90% or 0% to
100% of its final value. For under damped system, second order system the 0 to 100% rise
time is commonly used. For over damped system, the 10 to 90% rise time is commonly used.

3) Peak time :- (tp)


It is the time required for the response to reach the 1 st of peak of the overshoot.

ECE/SJBIT Page 73
Control Systems 10ES43

4) Maximum over shoot :- (MP)


It is the maximum peak value of the response curve measured from unity. The amount
of max over shoot directly indicates the relative stability of the system.

5) Settling time :- (ts)


It is the time required for the response curve to reach & stay with in a range about the
final value of size specified by absolute percentage of the final value (usually 5% to 2%).
The settling time is related to the largest time const., of C.S.
Transient response specifications of second order system :-

W. K.T. for the second order system,

T.F. = C(S) = Wn2 . ------------------------------(1)


R(S) S +2 WnS+ Wn
2 2

Assuming the system is to be underdamped (< 1)


Rise time tr
W. K.T. C(t r) = 1- e-Wnt Cos Wdtr + . sin wdtr
1-2

Let C(tr) = 1, i.e., substituting t r for t in the above Eq:

Then, C(tr) = 1 = 1- e-Wntr Cos wdtr + . sin wdtr


1-2

Cos wdtr + . sin wdtr = tan wdtr = - 1-2 = wd .


1-2

jW

Thus, the rise time t r is , jWd

tr =1 . tan-1 - w d = - secs Wn 1-2 Wn


Wd wd
When must be in radians. -
Wn

S- Plane

Peak time :- (tp)

ECE/SJBIT Page 74
Control Systems 10ES43

Peak time can be obtained by differentiating C(t) W.r.t. t and equating that
derivative to zero.
dc = O = Sin Wdtp Wn . e-Wntp
dt t = t p 1-2
Since the peak time corresponds to the 1st peak over shoot.
Wdtp = = tp = .
Wd

The peak time tp corresponds to one half cycle of the frequency of damped oscillation.

Maximum overshoot :- (MP)

The max over shoot occurs at the peak time.


i.e. At t = tp = .
Wd
(/ Wd)
Mp = e or e ( / 1-2)

Settling time :- (ts)


An approximate value of ts can be obtained for the system O < <1 by using the
envelope of the damped sinusoidal waveform.

Time constant of a system = T = 1 .


Wn
Setting time ts = 4x Time constant.
= 4x 1 . for a tolerance band of +/- 2% steady state.
Wn

Delay time :- (td)


The easier way to find the delay time is to plot Wn td VS . Then approximate
the curve for the range O<< 1 , then the Eq. becomes,
Wn td = 1+0.7
td = 1+0.7
Wn

PROBLEMS:

(1) Consider the 2 nd order control system, where = 0.6 & Wn = 5 rad / sec, obtain the
rise time tr, peak time tp, max overshoot Mp and settling time ts When the system is subject
to a unit step i/p.,

Given :- = 0.6, Wn = 5rad /sec, tr = ?, tp = ?, Mp = ?, ts = ?

ECE/SJBIT Page 75
Control Systems 10ES43

Wd = Wn 1- 2 = 5 1-(0.6) 2 = 4

= Wn = 0.6 x 5 = 3.

tr = -, = tan-1 Wd = tan-1 4 = 0.927 rad


Wd 3

tr = 3.14 0.927 = 0.55sec.


4

tp = = 3.14 = 0.785 sec.


Wd 4
/ Wd
. = e
MP = e 1- 2

MP = e (3/4) x 3.14
= 0.094 x 100 = 9.4%

ts :- For the 2% criteria.,


ts = 4 . = 4 . = 1.33 sec.
Wn 0.6x5

For the 5% criteria.,


ts = 3 = 3 = 1 sec
3
EXERCISE:

(2) A unity feed back system has on open loop T.F. G(S) = K .
S ( S+10)
Determine the value of K so that the system has a damping factors of 0.5 For this value of K
determine settling time, peak over shoot & time for peak over shoot for unit step i/p

LCS

The error co-efficient Kp, Kv, & Ka describes the ability of the system to eliminate the steady
state error therefore they are indicative of steady state performance. It is generally described to
increase the error co-efficient while maintaining the transient response within an acceptable
limit.

PROBLEMS;

ECE/SJBIT Page 76
Control Systems 10ES43

2. The unit step response of a system is given by

C (t) = 5/2 +5t 5/2 e-2t. Find the T. F of the system.

T/P = r(t) = U (t). Taking L.T, R(s) = 1/S.

Response C(t) = 5/2+5t-5/2 e-2t


1 + 2 - 1
S S2 S+2 Taking
L.T, C(s)
=5 1 + 5 1 - 5 1 = 5
2 S S2 2 (S+2) 2

C(s) = 5 S(S+2)+2(S+2)-
S 2
= 5 S2+2S+2S+4
s2 S2 (S+2) 3 S2(S+2)
2

= 10 (S+1)
S2 (S+2)

T.F = C (S) = 10 (S+1) S = 10 (S+1)


R (S) S2(S+2) S(S+2)

2. The open loop T F of a unity food back system is G(s) = 100


S (S+10)

Find the static error constant and the steady state error of the system when subjected to an i/p
given by the polynomial

R(t) = Po + p1t + P2 t2
2
G(s) = 100 position error co-efficient
S (S+10)

KP = lt G(s) = lt 100 =
S 0 S 0 S (S+10)

ECE/SJBIT Page 77
Control Systems 10ES43

Similarly KV = lt SG(s) = lt 100 x s = 100 = 10


S 0 S 0 S (S+10)
10

lt 100 x s2 = 0
S 0 S 0 S (S+10) Ka = lt S2 G(S)

Given :- r(t) = Po+P1t +P2 t2


2
R1 R2 R3
Therefore steady state error ess + +
1+Kp Kv Ka

R1 R2 R3
+ + P0 P1 P2
ess = +
1+ 10 0 +
1+ 10 0

Ess = 0+0.1 P1 + =

3. Determine the error co-efficeint and static error for G(s) = 1


And H(s) = (S+2) S(S+1) (S+10)

The error constants for a non unity feed back system is as follows

(S+2)
G(S).H(S) =
S(S+1) (S+10)

Kp = lt G(S) H(S) = lt (0+2)


S 0 S 0 =
ECE/SJBIT 0(0+1) (0+10) Page 78
Control Systems 10ES43

Kv = lt G(S) H(S) = (0+2)


lt = 1/5 = 0.2
S 0 0(0+1) (0+10)

Ka = 0

Static Error:-

Steady state error for unit step i/p = 0


1 1
Unit ramp i/p
= =5
Kv 0.2

Unit parabolic i/p = 1/0 =

50
4. A feed back C.S is described as G(S) =
H(S)=1/s. S (S+2) (S+5)

For unit step i/p,calculate steady state error constant and errors.

Kp = lt G(S) H(S) = 50
lt =
S 0 S S2 (S+2) (S+5)
0
Kv = lt G(S) H(S) = 50 x S
lt =
2
S 0 S S (S+2) (S+5)
0

Ka = lt G(S) H(S) = lt S2 x 50 50
S
ECE/SJBIT 0 S = = 5 Page 79
0 S2 (S+2) (S+5) 10
Control Systems 10ES43

Ess = lt S. 1/S Lt S2 (S+2) (S+5)


The steady state error
S 0 1+50
S 0 S2 (S+2) (S+5) + 50
2
S (S+2)(S+5)
= 0/50 = 0
K
5. A certain feed back C.S is described by following C.S G(S) H(S) = 1
2
= S (S+20) (S+30)

Determine steady state error co-efficient and also determine the value of K to limit the steady to
10 units due to i/p r(t) = 1 + 10 + t 20/2 t2.

Kp = lt G(S) H(S) = lt 50
S 0 S =
0 S2 (S+20) (S+30)

Kv = lt S K
S 0 2
S (S+20) (S+30) =

Ka = lt S2 K K
S 0 S2 (S+20) (S+30) 600

Steady state error:-


1 1
Error due to unit step i/p + =0
1+Kp 1+

Error due o r(t) ramp i/p 10 10


+ =0
Kv

20 40 20 x 600 12000
Error due to para i/p, = = =
Ka 2Ka K K
ECE/SJBIT Page 80
Control Systems 10ES43

r (t) = 0+0 12000 = 10 = K = 1200


K

3) The open loop T.F. of a unity feed back system is given by G(S) = K . where,
S(1+ST)
T&K are constants having + Ve values.By what factor (1) the amplitude gain be reduced so
that (a) The peak overshoot of unity step response of the system is reduced from 75% to 25%
(b) The damping ratio increases from 0.1 to 0.6.

Solution: G(S) = K .
S(1+ST)

Let the value of damping ratio is, when peak overshoot is 75% & when peak
overshoot is 25%

Mp = .
e 1- 2

ln 0. 75 = . 0.0916 = .
1- 2 1- 2

1 = 0.091 (0.0084) (1-2) = 2


2 = 0.4037 (1.0084 2) = 0.0084
= 0.091

k .
2
S+S T .
w.k.t. T.F. = G(S) = 1+ K . = K .
2 2
1+ G(S) . H(S) S+S T S + S T+K

T.F. = K/T .
2
S + S+ K.
T T

Comparing with std Eq :-

Wn = K . , 2 Wn = 1 .

ECE/SJBIT Page 81
Control Systems 10ES43

T T
Let the value of K = K1 When = 1 & K = K2 When = 2.
Since 2 Wn = 1 . , = 1 . = 1 .
T 2TWn 2 KT
1 .
1 . = 2 K1T = K2 .
2 1 K1
2 K2T

0.091 = K2 . K2 . = 0.0508
0.4037 K1 K1

K2 = 0.0508 K1

a) The amplitude K has to be reduced by a factor = 1 . = 20


0.0508
b) Let = 0.1 Where gain is K1 and
= 0.6 Where gain is K2
0.1 = K2 . K2 . = 0.027 K2 = 0.027 K1
0.6 K1 K1

The amplitude gain should be reduced by 1 . = 36


0.027

4) Find all the time domain specification for a unity feed back control system whose open loop
T.F. is given by

G(S) = 25 .
S(S+6)

Solution:
25 .
G(S) = 25 . G(S) . = S(S+6) .
S(S+6) 1 + G(S) .H(S) 1 + 25 .
S(S+6)
= 25 .
S2 + ( 6S+25 )

W2n = 25 , Wn = 5, 2 Wn = 6 = 6 . = 0.6
2x5
Wd = Wn 1- = 5 1- (0.6) = 4
2 2

tr = - , = tan-1 Wd = Wn = 0.6 x 5 = 3
Wd

ECE/SJBIT Page 82
Control Systems 10ES43

= tan-1 ( 4/3 ) = 0.927 rad.

tp = . = 3.14 = 0.785 sec.


Wd 4

MP = . = 0.6 . x3.4 = 9.5%


e 1- 2 e 1- 0.6 2

ts = 4 . for 2% = 4 . = 1.3 3sec.


Wn 0.6 x 5

5) The closed loop T.F. of a unity feed back control system is given by

C(S) = 5 . Determine (1) Damping ratio (2) Natural


R(S) S2 + 4S +5 undamped response frequency Wn. (3) Percent
peak over shoot Mp (4) Expression for error
resoponse.

Solution:

C(S) = 5 . , Wn2 = 5 Wn = 5 = 2.236


2
R(S) S + 4S +5

2Wn = 4 = 4 . = 0.894. Wd = 1.0018


2 x 2.236

MP = . = 0.894 . X 3.14 = 0.19%


e 1- 2 e 1-(0.894)2

W. K.T. C(t) = e-Wnt Cos Wdtr + . sin wdtr


1-2

= e-0.894x2.236t Cos 1.0018t + 0.894 . sin 1.0018t


1-(0.894)2

6) A servo mechanism is represent by the Eq:-

d2 + 10 d = 150E , E = R- is the actuating signal calculate the

ECE/SJBIT Page 83
Control Systems 10ES43

dt2 dt value of damping ratio, undamped and damped


frequency of ascillation.

Soutions:- d2 + 10 d = 15 ( r - ) , = 150r 150.


dt2 dt

Taking L.T., [S2 + 10S + 150] (S) = 150 R (S).


(S) = 150 .
R(S) S2 + 10S + 15O

Wn2 = 150 Wn = 12.25. .rad sec .1

2Wn = 10 = 10 . = 0.408.
2 x 12.25

Wd = Wn 1 - 2 = 12.25 1- (0.408)2 = 11.18. rad 1sec.

7) Fig shows a mechanical system and the response when 10N of force is applied to the system.
Determine the values of M, F, K,.

x(t)inmt
K
f(t) 0.00193
The T.F. of the mechanical system is ,
0.02
X(S) = 1 .
M F(S) MS2 + FS = K
f(t) = Md2X + F dX + KX
F x dt2 dt
2
F(S) = (MS + FS + K) x (S)
1 2 3 4 5

Given :- F(S) = 10
S.
X(S) = 10 .
S(MS2 + FS + K)
SX (S) = 10 .
2
MS + FS + K

The steady state value of X is By applying final value theorem,

lt. SX(S) = 10 . = 10 = 0.02 ( Given from Fig.)

ECE/SJBIT Page 84
Control Systems 10ES43

S O M(0) + F (0) + K K. ( K = 500.)

MP = 0.00193 = 0.0965 = 9.62%


0.02

0.744 = . 0.5539 = 2 .
1 - 2 1 - 2

0.5539 0.5539 2 = 2

= 0.597 = 0.6

tp = = .
Wd Wn( 1 )
2

3 = . Wn = 1.31 rad / Sec.


Wn 1 (0.6)2

Sx(S) = 10/ M .
(S2 + F S + K )
M M

Comparing with the std. 2nd order Eq :-, then,

Wn2 = K Wn = K (1.31)2 = 500 . M = 291.36 kg.


M M M

F = 2Wn F = 2 x 0.6 x 291 x 1.31


M F = 458.7 N/M/ Sec.

9) Measurements conducted on sever me mechanism show the system response to be c(t) =


1+0.2e-60t 1.2e-10t , When subjected to a unit step i/p. Obtain the expression for closed
loop T.F the damping ratio and undamped natural frequency of oscillation .

Solution:
C(t) = 1+0.2e-60t 1.2e-10t
Taking L.T., C(S) = 1 . + 0.2 . 1.2 .
S S+60 S+10

C(S) . = 600 / S .
S2 + 70S + + 600

ECE/SJBIT Page 85
Control Systems 10ES43

Given that :- Unit step i/p r(t) = 1 R(S) = 1 .


S

C(S) . = 600 / S .
R(S) S2 + 70S + + 600

Comparing, Wn2 = 600, 24.4 ..rad / Sec

2 Wn = 70, = 70 . = 1.428
2 x 24.4

10) The C.S. shown in the fig employs proportional plus error rate control. Determine the

value of error rate const. Ke, so the damping ratio is 0.6 . Determine the value of settling

time, max overshoot and steady state error, if the i/p is unit ramp, what will be the value

of steady state

10) A feed back system employing o/p damping is as shown in fig.


4) Find the value of K1 & K2 so that closed loop system resembles a 2 nd order system with
= 0.5 & frequency of damped oscillation 9.5 rad / Sec.
5) With the above value of K1 & K2 find the % overshoot when i/p is step i/p
6) What is the % overshoot when i/p is step i/p, the settling time for 2% tolerance?

K1 1 . + C
S(1+S)
__
K2S

C . = K1 .
2
R S + ( 1 + K2 ) S + K1

Wn2 = K1 Wn = K1

2Wn = 1 + K2 = 1 + K2

ECE/SJBIT Page 86
Control Systems 10ES43

2 K1
Wd = Wn (1 - ) 2
Wn = 9.5 . = 10.96 rad/Sec
(1 0.52)

K1 = (10.96)2 = 120.34

2Wn = 1 + K2 , K2 = 9.97

MP = . = 16.3%
e (1 - 2)

ts = 4 . = 4 . = 0.729 sec
Wn 0.5 x 10.97

Types of feed back control system :-

The open loop T.F. of a unity feed back system can be written in two std, forms;

1) Time constant form and 2) Pole Zero form,


G(S) = K(TaS +1) (TbS +1)..
Sn(T1 S+1) (T2S + 1).

Where K = open loop gain.


Above Eq:- involves the term Sn in denominator which corresponds to no, of
integrations in the system. A system is called Type O, Type1, Type2,.. if n = 0, 1,
2, .. Respectively. The Type no., determines the value of error co-efficients. As
the type no., is increased, accuracy is improved; however increasing the type no.,
aggregates the stability error. A term in the denominator represents the poles at the origin
in complex S plane. Hence Index n denotes the multiplicity of the poles at the origin.
The steady state errors co-efficient for a given type have definite values. This is
illustration as follows.

2) Type O system :- If, n = 0, the system is called type 0, system. The


steady state error are as follows;
. .
Let, G(S) = K . [ . H(s) = 1]
S+1

ess (Position) = 1 . = 1 .= 1 .
1 + G(O) . H(O) 1+K 1 + Kp

. .
. Kp = lt G(S) . H(S) = lt K . = K
S 0 S 0 S+1

ECE/SJBIT Page 87
Control Systems 10ES43

ess (Velocity) = 1 . = 1 .=
Kv 0

Kv = lt G(S) . H(S) = lt S K . =0
S0 S0 S+1

ess (acceleration) = 1 . = 1 .=
Ka 0

Ka = lt S2 G(S) . H(S) = lt S2 K . = 0.
S0
S 0 S+1

2) Type 1 System :- If, n = 1, the ess to various std, i/p, G(S) = K .


S (S + 1)

ess (Position) = 1 . = 0
1+

Kp = lt G(S) . H(S) = lt K . =
S 0 S 0 S( S + 1)

Kv = lt S K . = K
S 0 S(S+1)

ess (Velocity) = 1 .
K

ess (acceleration) = 1 . = 1 . =
0 0

Ka = lt S2 K . = O.
S0 S (S + 1)

3) Type 2 System :- If, n = 2, the ess to various std, i/p, are , G(S) = K .
S2 (S + 1)
Kp = lt K .=

ECE/SJBIT Page 88
Control Systems 10ES43

SO S2 (S + 1)
.
. . ess (Position) = 1 . = O

Kv = lt S K .=
S O S2 (S + 1)
.
. . ess (Velocity) = 1 . = O

Ka = lt S2 K . = K.
S O S2 (S + 1)
.
. . ess (acceleration) = 1 .
K

3) Type 3 System :- Gives Kp = Kv = Ka = & ess = O.


(Onwards)

Recommended Questions
1. Define and classify time response of a system.
2. Mention the Standard Test Input Signals and its Laplace transform
3. The open loop T.F. of a unity feed back system is given by G(S) = K . Where,
S(1+ST)
T&K are constants having + Ve values.By what factor (1) the amplitude gain be reduced so that
(a) The peak overshoot of unity step response of the system is reduced from 75% to 25% (b)
The damping ratio increases from 0.1 to 0.6.

4. Find all the time domain specification for a unity feed back control system whose open loop
T.F. is given by

G(S) = 25 .
S(S+6)
5. The closed loop T.F. of a unity feed back control system is given by

C(S) = 5 . Determine (1) Damping ratio (2) Natural


R(S) 2
S + 4S +5 undamped response frequency Wn. (3) Percent
peak over shoot Mp (4) Expression for error
resoponse.

6. A servo mechanism is represent by the Eq:-

d2 + 10 d = 150E , E = R- is the actuating signal calculate the


dt2 dt value of damping ratio, undamped and damped
frequency of ascillation.

ECE/SJBIT Page 89
Control Systems 10ES43

7. Measurements conducted on sever me mechanism show the system response to be c (t) =


1+0.2e-60t 1.2e-10t , When subjected to a unit step i/p. Obtain the expression for closed loop T.F
the damping ratio and undamped natural frequency of oscillation .

8. A feed back system employing o/p damping is as shown in fig.


1) Find the value of K1 & K2 so that closed loop system resembles a 2 nd order system with =
0.5 & frequency of damped oscillation 9.5 rad / Sec.
2) With the above value of K1 & K2 find the % overshoot when i/p is step i/p
3) What is the % overshoot when i/p is step i/p, the settling time for 2% tolerance?

R
K1 1 . + C
S(1+S)
__
K2S

ECE/SJBIT Page 90
Control Systems 10ES43

UNIT-4
Stability Analysis
Every System, for small amount of time has to pass through a transient period. Whether system
will reach its steady state after passing through transients or not. The answer to this question is
whether the system is stable or unstable. This is stability analysis.

For example, we want to go from one station to other. The station we want to reach is
our final steady state. The traveling period is the transient period. Now any thing
may happen during the traveling period due to bad weather, road accident etc, there is a chance
that we may not reach the next station in time. The analysis of wheather the given system can
reach steady state after passing through the transients successfully is called the stability analysis
of the system.

In this chapter, we will steady


1. The stability & the factor on which system stability depends.
2. Stability analysis & location of closed loop poles.
3. Stability analysis using Hurwitz method.
4. Stability analysis using Routh-Hurwitz method.
5. Special cases of Rouths array.
6. Applications of Routh-Hurwitz method.

Concept of stability:
Consider a system i.e a deep container with an object placed inside it as shown in fig(1)
force F

(a) fig(1) (b)

Now, if we apply a force to take out the object, as the depth of container is more, it will oscillate
& settle down again at original position.

Assume that force required to take out the object tends to infinity i.e always object will
oscillate when force is applied & will settle down but will not come out such a system is called
absolutely stable system. No change in parameters, disturbances, changes the output.

ECE/SJBIT Page 91
Control Systems 10ES43

Now consider a container which is pointed one, on which we try to keep a circular object. In this
object will fall down without any external application of force. Such system is called Unstable
system.

(a) fig(2) (b)


While in certain cases the container is shallow then there exsists a critical value of
force for which the object will come out of the container.
F
F F

Fig(3) F<Fcritical F>Fcritical

As long as F<Fcritical object regains its original position but if F>F critical object will come out.
Stability depends on certain conditions of the system, hence system is called conditionally stable
system.

Pendulum where system keeps on oscillating when certain force is applied. Such
systems are neither stable nor unstable & hence called critically stable or marginally stable
systems

Stability of control systems:

The stability of a linear closed loop system can be determined from the locations of closed loop
poles in the S-plane.

If the system has closed loop T.F.


C(s) = 10
R(s) (S+2) (S+4) 1
Output response for unit step input R(s) =
S

ECE/SJBIT Page 92
Control Systems 10ES43

C(s) 10 = A B C
S(S+2) (S+4) S S+2 S+4

Find out partial fractions

1 1 1
C(s) = 8 4 8 10
S S+2 S+4

= 1.25 2.5 1.25


S S+2 S+4

C(s) = 1.25 2.5e-2t+1.25e-4t

=Css + Ct(t)
If the closed loop poles are located in left half of s-plane, Output response contains exponential
terms with negative indices will approach zero & output will be the steady state output.
i.e.
Ct (t) = 0
t
Transient output = 0
Such system are called absolutely stable systems.

Now let us have a system with one closed loop pole located in right half of s- plane
C(s) 10
R(s) S(S-2)(s+4)

A + B + C 10
= S S-2 S+4

C(t) = - 1.25 + 0.833e 2t + 0.416e 4 t


Here there is one exponential term with positive in transient output
Therefore Css = - 1.25

t C(t)
0 0
1 + 4.91
2 + 44.23
4 +2481.88

ECE/SJBIT Page 93
Control Systems 10ES43

From the above table, it is clear that output response instead of approaching to steady state value
as t due to exponential term with positive index, transients go on increasing in amplitude.
So such system is said to be unstable. In such system output is uncontrollable & unbounded one.
Output response of such system is as shown in fig(4).
C(t) C(t)

OR
Steady state
output

t
(a) fig(4) t
(b)
For such unstable systems, if input is removed output may not return to zero. And if the input
power is turned on, output tends to . If no saturation takes place in system & no mechanical
stop is provided then system may get damaged.

If all the closed loop poles or roots of the characteristic equation lies in left of s-plane, then in the
output response contains steady state terms & transient terms. Such transient terms approach to
zero as time advances eventually output reaches to equilibrium & attains steady state value.
Transient terms in such system may give oscillation but the amplitude of such oscillation will
be decreasing with time & finally will vanish. So output response of such system is shown in
fig5 (a) & (b).

C(t) C(t) Damped oscillations


Steady state
----------------------- ---------------------------
OR
Steady state output

t t
(a) fig 5 (b)

BIBO Stability : This is bounded input bounded output stability.

Definition of stable system:


A linear time invariant system is said to be stable if following conditions are satisfied.
1. When system is excited by a bounded input, output is also bounded & controllable.
2. In the absence of input, output must tend to zero irrespective of the initial conditions.
Unstable system:
A linear time invariant system is said to be unstable if,

ECE/SJBIT Page 94
Control Systems 10ES43

1. for a bounded input it produces unbounded output.


2. In the absence of input, output may not be returning to zero. It shows certain output
without input.

Besides these two cases, if one or more pairs simple non repeated roots are located on the
imaginary axis of the s-plane, but there are no roots in the right half of s-plane, the output
response will be undamped sinusoidal oscillations of constant frequency & amplitude. Such
systems are said to be critically or marginally stable systems.

Critically or Marginally stable systems:


A linear time invariant system is said to be critically or marginally stable if for a bounded
input its output oscillates with constant frequency & Amplitude. Such oscillation of output are
called Undamped or Sustained oscillations.

For such system one or more pairs of non repeated roots are located on the imaginary axis as
shown in fig6(a). Output response of such systems is as shown in fig6(b).
C(t)
Constant Amplitude & frequency oscillations
X J2 ------------------------------------
----------------------------- steady state output
X J1 ------------------------------------

X - J1

X - J2
Fig 6(a)
non repeated poles on J axis. t

If there are repeated poles located purely on imaginary axis system is said to be unstable.

C(t)

J1 x x
-----------------------------------------
steady state output
s-plane
J1 x x

ECE/SJBIT Page 95
Control Systems 10ES43

Conditionally Stable:
A linear time invariant system is said to be conditionally stable, if for a certain condition if a
particular parameter of the system, its output is bounded one. Otherwise if that condition is
violated output becomes unbounded system becomes unstable. i.e. Stability of the system
depends the on condition of the parameter of the system. Such system is called conditionally
stable system.

S-plane can be divided into three zones from stability point of view.

J axis

Left half of s-plane Right half of s-plane

Real

Stable Unstable
S-Plane

(repeated)

unstable (non repeated roots)


Marginally stable

ECE/SJBIT Page 96
Control Systems 10ES43

Sl. Nature of closed Location of closed loop Step response Stability condition
No loop poles. poles in s-plane
1. Real negative i.e
in LHS of splane J C(t)

--------------------- Absolutely stable


x x
-02 -01

Real positive in J
RHS of s-plane
2. C(t)
x
a1 ------------------------ Unstable

t
increasing towards

3. Complex C(t)
conjugate with J
negative real x J 1
part
-a1 Absolutely stable.
t
x
-J 2 Damped oscillation

4. Complex Ct
conjugate with
positive real
part J1 x

Unstable.
-J 1 -x

t
oscillations with
increasing amplitude

ECE/SJBIT Page 97
Control Systems 10ES43

5. Non repeated C(t)


pair on J
imaginary axis Marginally or
x J1 critically stable

x -J2 t

OR C(t)

X J2 t

Marginally or
x J1
critically stable

Sustained oscillations
with two frequencies 1 &
x J1
2
x J2

Two non repeated pairs on


imaginary axis.
6. Repeated pair J
on imaginary C(t)
axis
x x J1
------------------------
Unstable

t
x x -J1

oscillation of increasing
amplitude

ECE/SJBIT Page 98
Control Systems 10ES43

Relative Stability:
The system is said to be relatively more stable or unstable on the basis of
settling time. System is said to be more stable if settling time for that system is less than that of
other system.

The settling time of the root or pair of complex conjugate roots is inversely proportional
to the real part of the roots.

Sofar the roots located near the J axis, settling time will be large. As the roots move
away from J axis i.e towards left half of the s-plane settling time becomes lesser or smaller &
system becomes more & more stable. So the relative stability improves.

J C(t)

Stable for P1

x x ----------------------------------
P2 P1
Relatively more stable for P2
t

C(t) stable for 1


x x


2 1 --------------------------------------------------------------

x x

more stable for 2


J axis

Relative stability s-plane


improves

ECE/SJBIT Page 99
Control Systems 10ES43

Routh Hurwitz Criterion :

This represents a method of determining the location of poles of a characteristics equation


with the respect to the left half & right half of the s-plane without actually solving the equation.

The T.F.of any linear closed loop system can be represented as,

C(s) b0 sm + b1 sm-1 +.+ bm


=
R(s) a0 sn + a1 sn-1 + . + an
Where a & b are constants.
To find the closed loop poles we equate F(s) =0. This equation is called as Characteristic
Equation of the system.
F(s) = a0 sn + a1 sn-1 + a2 sn-2 + .. + an = 0.
Thus the roots of the characteristic equation are the closed loop poles of the system which decide
the stability of the system.

Necessary Condition to have all closed loop poles in L.H.S. of s-plane.

In order that the above characteristic equation has no root in right of s-plane, it is necessary
but not sufficient that,
1. All the coefficients off the polynomial have the same sign.
2. Non of the coefficient vanishes i.e. all powers of s must be present in descending order
from n to zero.
These conditions are not sufficient.

Hurwitzs Criterion :

The sufficient condition for having all roots of characteristics equation in left half of s-plane
is given by Hurwitz. It is referred as Hurwitz criterion. It states that:

The necessary & sufficient condition to have all roots of characteristic equation in left half of
s-plane is that the sub-determinants DK, K = 1, 2,n obtained from Hurwitz determinant
H must all be positive.

ECE/SJBIT Page 100


Control Systems 10ES43

Method of forming Hurwitz determinant:

a1 a3 a5 .. a2n-1
a0 a2 a4 .. a2n-2

0 a1 a3 .. a2n-3

0 a0 a2 .. a2n-4
H=
0 0 a1 ... a2n-5

- - ... -

- - - ... -

0 - - . an

The order is n*n where n = order of characteristic equation. In Hurwitz determinant all
coefficients with suffices greater than n or negative suffices must all be replaced by zeros.
From Hurwitz determinant subdeterminants, DK, K= 1, 2, .n must be formed as follows:

a1 a3 a5
D1 = a1 D2 = a1 a3 D3 = a0 a2 a4 DK = H
a0 a2 0 a1 a3

For the system to be stable, all above determinants must be positive.

Determine the stability of the given characteristics equation by Hurwitz,s method.

Ex 1: F(s)= s3 + s2 + s1 + 4 = 0 is characteristic equation.


a0 = 1, a1 = 1, a2 = 1, a3 = 4, n = 3

a1 a3 a5 1 4 0
H= a0 a2 a4 = 1 1 0
0 a1 a3 0 1 4

D1 = 1 =1

1 4
D2 = 1 1 = -3

ECE/SJBIT Page 101


Control Systems 10ES43

1 4 0
D3 = 1 1 0 = 4 16 = -12.
0 1 4

As D2 & D3 are negative, given system is unstable.

Disadvantages of Hurwitzs method :

1. For higher order system, to solve the determinants of higher order is very complicated &
time consuming.
2. Number of roots located in right half of s-plane for unstable system cannot be judged by
this method.
3. Difficult to predict marginal stability of the system.

Due to these limitations, a new method is suggested by the scientist Routh called Rouths
method. It is also called Routh-Hurwitz method.

Rouths Stability Criterion:

It is also called Rouths array method or Routh-Hurwitzs method


Routh suggested a method of tabulating the coefficients of characteristic equation
in a particular way. Tabulation of coefficients gives an array called Rouths array.
Consider the general characteristic equation as,
F(s) = a0 sn + a1 sn-1 + a2 sn-2 + .. + an = 0.

Method of forming an array :

Sn a0 a2 a4 a6 .

Sn-1 a1 a3 a5 a7

Sn-2 b1 b2 b3

Sn-3 c1 c2 c3

- - - -

- - - -

S0 an

Coefficients of first two rows are written directly from characteristics equation.
From these two rows next rows can be obtained as follows.

ECE/SJBIT Page 102


Control Systems 10ES43

a1 a2 a0 a3 a1 a4 a0 a5 a1 a6 a0 a7
b1 = , b2 = , b3 =
a1 a1 a1

From 2nd & 3rd row , 4th row can be obtained as

b1 a3 a1 b2 b1 a5 a1 b3
C1 = , C2 =
b1 b1

This process is to be continued till the coefficient for s0 is obtained which will be a n. From this
array stability of system can be predicted.

Rouths criterion :

The necessary & sufficient condition for system to be stable is All the terms in the first
column of Rouths array must have same sign. There should not be any sign change in first
column of Rouths array.

If there are sign changes existing then,


1. System is unstable.
2. The number of sign changes equals the number of roots lying in the right half of the
s-plane.

Examine the stability of given equation using Rouths method :

Ex.2: s3+6s2 + 11s + 6 =0


Sol: a0 = 1, a1 = 6, a2 =11, a3 = 6, n = 3

S3 1 11

S2 6 6

S1 11 * 6 6 =10 0
6
S0 6

As there is no sign change in the first column, system is stable.

ECE/SJBIT Page 103


Control Systems 10ES43

Ex. 3 s3 + 4s2 + s + 16 = 0
Sol: a0 =1, a1 = 4, a2 = 1, a3 = 16

S3 1 1

S2 +4 16

S1 4 - 16 = -3 0
4
S0 +16

As there are two sign changes, system is unstable.


Number of roots located in the right half of s-plane = number of sign changes = 2.

Special Cases of Rouths criterion :

Special case 1 :

First element of any of the rows of Rouths array is zero & same remaining rows contains at
least one non-zero element.

Effect : The terms in the new row become infinite & Rouths test fails.

e.g. : s5 + 2s4 + 3s3 + 6s2 + 2s + 1 = 0

S5 1 3 2

S4 2 6 1 Special case 1 Rouths array failed

S3 0 1.5 0

S2 .

Following two methods are used to remove above said difficulty.

First method : Substitute a small positive number in place of a zero occurred as a first
element in the row. Complete the array with this number . Then
examine

lim
Sign change by taking . Consider above Example.
0

ECE/SJBIT Page 104


Control Systems 10ES43

S5 1 3 2

S4 2 6 1

S3 1.5 0

S2 6 - 3 1 0

S1 1.5(6 - 3) 0
-

(6 - 3)

S0 1

To examine sign change,


Lim = 6 - 3 = lim 6- 3
0 0
=6-
= - sign is negative.

Lim 1.5(6 3) - 2 = Lim 9 - 4.5 - 2


0 6 -3 0 6 - 3
= 0 4.5 0
0 -3

= + 1.5 sign is positive

ECE/SJBIT Page 105


Control Systems 10ES43

Rouths array is,

S5 1 3 2

S4 2 6 1

S3 + 1.5 0

S2 -
1 0

S1 +1.5 0 0

S0 1 0 0

As there are two sign changes, system is unstable.

Second method : To solve the above difficulty one more method can be used. In this, replace
s by 1/Z in original equation. Taking L.C.M. rearrange characteristic equation in descending
powers of Z. Then complete the Rouths array with this new equation in Z & examine the
stability with this array.

Consider F(s) = s5 + 2s4 + 3s3 + 6s2 + 2s + 1 = 0


Put s=1/Z

1 + 2 + 3 +6 +2 + 1=0
Z5 Z4 Z3 Z2 Z

Z5 + 2Z4+ 6Z3+3Z2+2Z+ 1 = 0

Z5 1 6 2

Z4 2 3 1

Z3 4.5 1.5 0

Z2 2.33 1 0

Z1 - 0.429 0

Z0 1

As there are two sign changes, system is unstable.

ECE/SJBIT Page 106


Control Systems 10ES43

Special case 2 :

All the elements of a row in a Rouths array are zero.


Effect : The terms of the next row can not be determined & Rouths test fails.

S5 a b c

S4 d e f

S3 0 0 0 Row of zeros, special case 2

This indicates no availability of coefficient in that row.

Procedure to eliminate this difficulty :


1. Form an equation by using the coefficients of row which is just above the row of zeros.
Such an equation is called an Auxillary equation denoted as A(s). For above case such
an equation is,
A(s) = ds4 + es2 + f
Note that the coefficients of any row are corresponding to alternate powers of s starting
from the power indicated against it.

So d is coefficient corresponding to s4 so first term is ds4 of A(s).

Next coefficient e is corresponding to alternate power of s from 4 i.e. s 2 Hence the term es
2
& so on.

2. Take the derivative of an auxillary equation with respect to s.


i.e. dA(s)
= 4d s3 + 2e s
ds

3. Replace row of zeros by the coefficients of dA(s)


ds

S5 a b c

S4 d e f

S3 4d 2e 0

ECE/SJBIT Page 107


Control Systems 10ES43

4. Complete the array of zeros by the coefficients.

Importance of auxillary equation :

Auxillary equation is always the part of original characteristic equation. This means the roots of
the auxillary equation are some of the roots of original characteristics equation. Not only this but
roots of auxillary equation are the most dominant roots of the original characteristic equation,
from the stability point of view. The stability can be predicted from the roots of A(s)=0 rather
than the roots of characteristic equation as the roots of A(s) = 0 are the most dominant from the
stability point of view. The remaining roots of the characteristic equation are always in the left
half & they do not play any significant role in the stability analysis.

e.g. Let F(s) = 0 is the original characteristic equation of say order n = 5.


Let A(s) = 0 be the auxillary equation for the system due to occurrence of special case 2
of the order m = 2.

Then out of 5 roots of F(s) = 0, the 2 roots which are most dominant (dominant means very
close to imaginary axis or on the imaginary axis or in the right half of s-plane) from the stability
point of view are the 2roots of A(s) = 0. The remaining 5 2 = 3 roots are not significant from
stability point of view as they will be far away from the imaginary axis in the left half of s-plane.

The roots of auxillary equation may be,


1. A pair of real roots of opposite sign i.e.as shown in the fig. 8.10 (a).

j j
x

x x

x Fig. 8. 10 (b)
Fig 8. 10(a)

2. A pair of roots located on the imaginary axis as shown in the fig. 8.10(b).
3. The non-repeated pairs of roots located on the imaginary axis as shown in the
fig.8.10 (c).
j j

x xx
x

x
x xx

ECE/SJBIT Page 108


Control Systems 10ES43

Fig. 8.10(c) Fig. 8.10(d).

4. The repeated pairs of roots located on the imaginary axis as shown in the Fig.8.10 (d).

Hence total stability can be determined from the roots of A(s) = 0, which can be out of
four types shown above.

Change in criterion of stability in special case 2 :

After replacing a row of zeros by the coefficients of dA(s) , complete the Rouths array.
ds
But now, the criterion that, no sign in 1 st column of array for stability, no longer remains
sufficient but becomes a necessary. This is because though A(s) is a part of original
characteristic equation, dA(s) is not, which is in fact used to complete the array.
ds
So if sign change occurs in first column, system is unstable with number of sign changes
equal to number of roots of characteristics equation located in right half of
s-plane.

But there is no sign changes, system cannot be predicted as stable . And in such case
stability is to be determined by actually solving A(s) = 0 for its roots. And from the location
of roots of A(s) = 0 in the s-plane the system stability must be determined. Because roots
A(s) = 0 are always dominant roots of characteristic equation.

Application of Rouths of criterion :


Relative stability analysis :
If it is required to find relative stability of system about a line s = - . i.e. how many roots
are located in right half of this line s = - , the Rouths method can be used effectively.
To determine this from Rouths array, shift the axis of s plane & then apply Rouths
array i.e. substitute s = s 1 - , ( = constant) in characteristic equation. Write polynomial in
terms of s1. Complete array from this new equation. The number of sign changes in first
column is equal to number of roots those are located to right of the vertical line
s = - .

Imaginary j


- 0

Determining range of values of K :

ECE/SJBIT Page 109


Control Systems 10ES43

In practical system, an amplifier of variable gain K is introduced .


The closed loop transfer function is

C(s) KG(s)
=
R(s) 1+ KG(s) H(s)

Hence the characteristic equation is


F(s) = 1+ KG(s) H(s) = 0
So the roots of above equation are dependent on the proper selection of value of K.
So unknown K appears in the characteristic equation. In such case Rouths array is to be
constructed in terms of K & then the range of values of K can be obtained in such away that it
will not produce any sign change in first column of the Rouths array. Hence it is possible to
obtain the range of values of K for absolute stability of the system using Rouths criterion. Such
a system where stability depends on the condition of parameter K, is called conditionally stable
system.

Advantages of Rouths criterion :


Advantages of rouths array method are :

1. Stability of the system can be judged without actually solving the characteristic equation.
2. No evaluation of determinants, which saves calculation time.
3. For unstable system it gives number of roots of characteristic equation having
positive real part.
4. Relative stability of the system can be easily judged.

5. By using the criterion, critical value of system gain can be determined hence
frequency of sustained oscillations can be determined.
6. It helps in finding out range of values of K for system stability.
7. It helps in finding out intersection points of roots locus with imaginary axis.

Limitation of Rouths criterion :

1. It is valid only for real coefficients of the characteristic equation.


2. It does not provide exact locations of the closed loop poles in left or right half of s-plane.
3. It does not suggest methods of stabilizing an unstable system.
4. Applicable only to linear system.

Ex.1. s6 + 4s5 +3s4 16s2- 64s 48 = 0 Find the number of roots of this equation with positive
real part, zero real part & negative real part

ECE/SJBIT Page 110


Control Systems 10ES43

Sol: S6 1 3 -16 -48

S5 4 0 -64 0

S4 3 0 -48 0

S3 0 0 0

dA
A(s) = 3S4 48 = 0 = 12s3
ds

S6 1 3 -16 -48

S5 4 0 -64 0

S4 3 0 -48 0

S3 12 0 0 0

S2 ( )0 -48 0 0

S1 576 0 0 0

S0 -48

Lim 576
0 = +

Therefore One sign change & system is unstable. Thus there is one root in R.H.S of the s plane
i.e. with positive real part. Now
solve A(s) = 0 for the dominant roots

A(s) = 3s4 48 =0

Put S2 = Y

3Y2 = 48 Y2 =16, Y = 16 = 4

ECE/SJBIT Page 111


Control Systems 10ES43

S2 = + 4 S2 = -4

S = 2 S = 2j

So S = 2j are the two parts on imaginary axis i.e. with zero real part. Root in R.H.S. indicated
by a sign change is S = 2 as obtained by solving A(s) = 0. Total there are 6 roots as n = 6.

Roots with Positive real part = 1


Roots with zero real part =2
Roots with negative real part = 6 2 1 = 3

Ex.2 : For unity feed back system,

k
G(s) = , Find range of values of K, marginal value of K
S(1 + 0.4s) ( 1 + 0.25 s) & frequency of sustained oscillations.

Sol : Characteristic equation, 1 + G (s) H (s) = 0 & H(s) = 1

K
1+ =0
s(1 + 0.4s) ( 1 + 0.25s)

s [ 1 + 0.65s + 0.1s2} + K = 0

0.1s3 + 0.65s2 +s + K = 0

S3 0.1 1 From s0, K>0

S2 0.65 K from s1,

S1 0.65 0.1K 0 0.65 0.1K > 0


0.65 0.65 > 0.1 K
S0 K 6.5 > K

Range of values of K, 0 < K < 6.5

Now marginal value of K is that value of K for which system becomes marginally stable. For
a marginal stable system there must be row of zeros occurring in Rouths array. So value of K
which makes any row of Routh array as row of zeros is called marginal value of K. Now K = 0

ECE/SJBIT Page 112


Control Systems 10ES43

makes row of s0 as row of zeros but K = 0 can not be marginal value because for K = 0, constant
term in characteristic equation becomes zeros ie one coefficient for s 0 vanishes which makes
system unstable instead of marginally stable.

Hence marginal value of K is a value which makes any row other than s 0 as row of zeros.
0.65 0.1 K mar = 0
K mar = 6.5
To find frequency, find out roots of auxiliary equation at marginal value of K

A(s) = 0.65 s2 + K = 0 ;
0.65 s2 + 6.5 = 0 Because K = 6.5
2
s = -10
s = j 3.162
comparing with s = j
= frequency of oscillations = 3.162 rad/ sec.

Ex : 3 For a system with characteristic equation

F(s) = s5 + s4 + 2s3 + 2s2 + 3s +15 = , examine the stability


Solution :
S5 1 2 3

S4 1 2 15

S3 0 -12 0

S2

S1

S0

S5 1 2 3

S4 1 2 15

S3 -12 0

S2 (2 + 12) 15 0

S1 (2 + 12)( -12 ) 15
0
2 + 12

ECE/SJBIT Page 113
Control Systems 10ES43

S0 15
Lim 2 + 12 12
0 =2 + =2+ = +

Lim (2 + 12)( -12 ) 15 Lim -24 - 144 15 2


0 = 0 2 + 12
2 + 12

0 144 - 0
= = - 12
0 + 12
S5 1 2 3

S4 1 2 15

S3 -12 0
There are two sign changes, so
system is unstable.
S2 + 15 0

S1 - 12 0

S0 15

Ex : 4 Using Routh Criterion, investigate the stability of a unity feedback system


whose open loop transfer function is
e -sT
G(s) =
s(s+1)

Sol : The characteristic equation is

1 + G(s) H(s) =0

e -sT
1 + = 0
s(s+1)

s2 + s + e sT =0

Now e sT can be Expressed in the series form as

ECE/SJBIT Page 114


Control Systems 10ES43

s2 T2
sT
e = 1 sT + +
2!

Trancating the series & considering only first two terms we get

esT = 1 sT

s2 + s + 1 sT = 0
s2 + s ( 1- T ) + 1 = 0
So rouths array is

S2 1 1

S 1-T 0

S0 1

1 T > 0 for stability


T<1
This is the required condition for stability of the system.

Ex : 5 Determine the location of roots with respect to s = -2 given that

F(s) = s4 + 10 s3 + 36s2 + 70s + 75


Sol : shift the origin with respect to s = -2
s = s1 2

(s 2 ) 4 + 10 (s 2)3 + 36(s 2 )2 + 70 ( s 2) + 75 = 0

s4 + 2s3 + 0s2 + 14s + 15 = 0


S4 1 0 15

S3 2 14 0

S2 -7 15 0

S1 18.28 0 0

S 0 15

ECE/SJBIT Page 115


Control Systems 10ES43

Two sign change, there are two roots to the right of s = -2 & remaining 2 are to the left of
the line s = -2. Hence the system is unstable.
Recommended Questions:

1. Explain briefly how system depends on poles and zeros.

2. Mention the necessary condition to have all closed loop poles in LHS of S-Plane

3. Explain briefly the Hurwitzs Criterion.

4. Explain briefly the Rouths Stability Criterion.

5..Examine the stability of given equation using Rouths method

s3+6s2 + 11s + 6 =0

6. Examine the stability of given equation using Rouths method


s5 + 2s4 + 3s3 + 6s2 + 2s + 1 = 0

7. Using Routh Criterion, investigate the stability of a unity feedback system whose open loop
transfer function is
e -sT
G(s) =
s(s+1)

ECE/SJBIT Page 116


Control Systems 10ES43

UNIT-5
RootLocus Techniques

The characteristics of the transient response of a closed loop control system are related to
location of the closed loop poles. If the system has a variable loop gain, then the location of the
closed loop poles depends on the value of the loop gain chosen. It is important, that the designer
knows how the closed loop poles move in the s-plane as the loop gain is varied. W. R. Evans
introduced a graphical method for finding the roots of the characteristic equation known as root
locus method. The root locus is used to study the location of the poles of the closed loop transfer
function of a given linear system as a function of its parameters, usually a loop gain, given its
open loop transfer function. The roots corresponding to a particular value of the system
parameter can then be located on the locus or the value of the parameter for a desired root
location can be determined from the locus. It is a powerful technique, as an approximate root
locus sketch can be made quickly and the designer can visualize the effects of varying system
parameters on root locations or vice versa. It is applicable for single loop as well as multiple loop
system.

ROOT LOCUS CONCEPT

To understand the concepts underlying the root locus technique, consider the second
order system shown in Fig. 1.

R(s) E(s) K C(s)



s(s a)

Fig. 3 Second order control system

The open loop transfer function of this system is


K
G(s) (1)
s(s a)
Where, K and a are constants. The open loop transfer function has two poles one at origin s = 0
and the other at s = -a. The closed loop transfer function of the system shown in Fig.1 is

C(s) G(s) K
2 (2)
R(s) 1 G(s)H(s) s as K

The characteristic equation for the closed loop system is obtained by setting the
denominator of the right hand side of Eqn.(2) equal to zero. That is,

ECE/SJBIT Page 117


Control Systems 10ES43

1 G(s)H(s) s 2 as K 0 (3)

The second order system under consideration is always stable for positive values of a and
K but its dynamic behavior is controlled by the roots of Eqn.(3) and hence, in turn by the
magnitudes of a and K, since the roots are given by

a (a 2 4K) a a 2
s1 , s 2 K (4)
2 2a 2 2

From Eqn.(4), it is seen that as the system parameters a or K varies, the roots change.
Consider a to be constant and gain K to be variable. As K is varied from zero to infinity, the two
roots s1 and s2 describe loci in the s-plane. Root locations for various ranges of K are:

1) K= 0, the two roots are real and coincide with open loop poles of the system s 1 =
0, s2 = -a.
2) 0 K < a2/4, the roots are real and distinct.
3) K= a2/4, roots are real and equal.
4) a2/4 < K < , the rots are complex conjugates.

The root locus plot is shown in Fig.2

Fig. 4 Root loci of s2+as+K as a function of K

Figure 2 has been drawn by the direct solution of the characteristic equation. This
procedure becomes tedious. Evans graphical procedure helps in sketching the root locus quickly.
The characteristic equation of any system is given by

(s) 0 (5)
Where, (s) is the determinant of the signal flow graph of the system given by Eqn.(5).

ECE/SJBIT Page 118


Control Systems 10ES43

=1-(sum of all individual loop gains)+(sum of gain products of all possible combinations of
two nontouching loops sum of gain products of all possible combination of three
nontouching loops) +
Or
(s) 1 Pm1 Pm2 Pm3 (6)
m m m
Where, Pmr is gain product of mth possible combination of r nontouching loops of the graph.

The characteristic equation can be written in the form

1 P(s) 0
KA(s)
1 0 (7)
B(s)

For single loop system shown in Fig.3

P(s) G(s)H(s) (8)

Where, G(s)H(s) is open loop transfer function in block diagram terminology or transmittance in
signal flow graph terminology.

R(s) E(s) C(s)


G(s)

H(s)

Fig. 5 Single loop feedback system

From Eqn.(7) it can be seen that the roots of the characteristic equation (closed loop
poles)occur only for those values of s where

P(s) 1 (9)

Since, s is a complex variable, Eqn.(9) can be converted into the two Evans conditions
given below.

P(s) 1 (10)
P(s) 180 (2q 1); q 0,1,2 (11)

Roots of 1+P(s) = 0 are those values of s at which the magnitude and angle condition
given by Eqn.(10) and Eqn.(11). A plot of points in the complex plane satisfying the angle

ECE/SJBIT Page 119


Control Systems 10ES43

criterion is the root locus. The value of gain corresponding to a root can be determined from the
magnitude criterion.

To make the root locus sketching certain rules have been developed which helps in
visualizing the effects of variation of system gain K ( K > 0 corresponds to the negative feed
back and K < 0 corresponds to positive feedback control system) and the effects of shifting
pole-zero locations and adding in anew set of poles and zeros.

GENERAL RULES FOR CONSTRUCTING ROOT LOCUS

1) The root locus is symmetrical about real axis. The roots of the characteristic equation are
either real or complex conjugate or combination of both. Therefore their locus must be
symmetrical about the real axis.

2) As K increases from zero to infinity, each branch of the root locus originates from an
open loop pole (n nos.) with K= 0 and terminates either on an open loop zero (m nos.)
with K = along the asymptotes or on infinity (zero at ). The number of branches
terminating on infinity is equal to (n m).

3) Determine the root locus on the real axis. Root loci on the real axis are determined by
open loop poles and zeros lying on it. In constructing the root loci on the real axis choose
a test point on it. If the total number of real poles and real zeros to the right of this point
is odd, then the point lies on root locus. The complex conjugate poles and zeros of the
open loop transfer function have no effect on the location of the root loci on the real axis.

ECE/SJBIT Page 120


Control Systems 10ES43

4) Determine the asymptotes of root loci. The root loci for very large values of s must be
asymptotic to straight lines whose angles are given by

180 (2q 1)
Angle of asymptotes A ; q 0,1,2, n m - 1 (12)
nm

5) All the asymptotes intersect on the real axis. It is denoted by a , given by

sum of poles sum of zeros


a
nm
(p1 p 2 p n ) (z1 z 2 z m )
(13)
nm

6) Find breakaway and breakin points. The breakaway and breakin points either lie on the
real axis or occur in complex conjugate pairs. On real axis, breakaway points exist
between two adjacent poles and breakin in points exist between two adjacent zeros. To
dK
calculate these polynomial 0 must be solved. The resulting roots are the breakaway
ds
/ breakin points. The characteristic equation given by Eqn.(7), can be rearranged as

B(s) KA(s) 0 (14)


where, B(s) (s p1 )(s p 2 ) (s p n ) and
A(s) K(s z1 )(s z 2 ) (s z m )
The breakaway and breakin points are given by

dK d d
A B A B 0 (15)
ds ds ds

Note that the breakaway points and breakin points must be the roots of Eqn.(15), but
not all roots of Eqn.(15) are breakaway or breakin points. If the root is not on the root
locus portion of the real axis, then this root neither corresponds to breakaway or breakin
point. If the roots of Eqn.(15) are complex conjugate pair, to ascertain that they lie on
root loci, check the corresponding K value. If K is positive, then root is a breakaway or
breakin point.

7) Determine the angle of departure of the root locus from a complex pole

Angle of departure from a complex p 180


(sum of angles of vectors to a complex pole in question from other poles)
(sum of angles of vectors to a complex pole in question from other zeros) (16)

8) Determine the angle of arrival of the root locus at a complex zero


ECE/SJBIT Page 121
Control Systems 10ES43

Angle of arrival at complex zero 180


(sum of angles of vectors to a complex zero in question from other zeros)
(sum of angles of vectors to a complex zero in question from other poles) (17)

9) Find the points where the root loci may cross the imaginary axis. The points where the
root loci intersect the j axis can be found by
a) use of Rouths stability criterion or
b) letting s = j in the characteristic equation , equating both the real part and
imaginary part to zero, and solving for and K. The values of thus found give
the frequencies at which root loci cross the imaginary axis. The corresponding K
value is the gain at each crossing frequency.

10) The value of K corresponding to any point s on a root locus can be obtained using the
magnitude condition, or

product of lengths between points to poles


K (18)
product of length between points to zeros

PHASE MARGIN AND GAIN MARGIN OF ROOT LOCUS

Gain Margin

It is a factor by which the design value of the gain can be multiplied before the closed
loop system becomes unstable.

Value of K at imaginary cross over


Gain Margin (19)
Design value of K
The Phase Margin

ECE/SJBIT Page 122


Control Systems 10ES43

Find the point j1 on the imaginary axis for which G j H j 1 for the design value
of K i.e. B j /A j K .
design
The phase margin is

180 argG j1 H(j1 ) (20)

Problem No 1

Sketch the root locus of a unity negative feedback system whose forward path transfer function
K
is G(s) .
s
Solution:

1) Root locus is symmetrical about real axis.

2) There are no open loop zeros(m = 0). Open loop pole is at s = 0 (n = 1). One branch of
root locus starts from the open loop pole when K = 0 and goes to asymptotically when
K.

3) Root locus lies on the entire negative real axis as there is one pole towards right of any
point on the negative real axis.

180 (2q 1)
4) The asymptote angle is A = , q n m 1 0.
nm
Angle of asymptote is A = 180.

(sum of poles) (sum of zeros)


5) Centroid of the asymptote is A
nm
0
0.0
1

6) The root locus does not branch. Hence, there is no need to calculate the break points.

7) The root locus departs at an angle of -180 from the open loop pole at s = 0.

8) The root locus does not cross the imaginary axis. Hence there is no imaginary axis cross
over.

The root locus plot is shown in Fig.1

ECE/SJBIT Page 123


Control Systems 10ES43

Figure 6 Root locus plot of K/s

Comments on stability:

The system is stable for all the values of K > 0. Th system is over damped.

Problem No 2
K(s 2)
The open loop transfer function is G(s) . Sketch the root locus plot
(s 1) 2
Solution:

1) Root locus is symmetrical about real axis.

2) There is one open loop zero at s=-2.0(m=1). There are two open loop poles at
s=-1, -1(n=2). Two branches of root loci start from the open loop pole when
K= 0. One branch goes to open loop zero at s =-2.0 when K and other goes to
(open loop zero) asymptotically when K .

3) Root locus lies on negative real axis for s -2.0 as the number of open loop poles plus
number of open loop zeros to the right of s=-0.2 are odd in number.

180 (2q 1)
4) The asymptote angle is A = , q n m 1 0.
nm
Angle of asymptote is A = 180.

(sum of poles) (sum of zeros)


5) Centroid of the asymptote is A
nm
(1 1) (2)
0.0
1
ECE/SJBIT Page 124
Control Systems 10ES43

6) The root locus has break points.


(s 1) 2
K
(s 2)
dK
Break point is given by 0
ds
2(s 1)(s 2) (s 1) 2
0
(s 2) 2
s1 1, K 0; s 2 3, K 4

The root loci brakesout at the open loop poles at s=-1, when K =0 and breaks in onto the
real axis at s=-3, when K=4. One branch goes to open loop zero at s=-2 and other goes to
along the asymptotically.

7) The branches of the root locus at s=-1, -1 break at K=0 and are tangential to a line s=-
1+j0 hence depart at 90.

8) The locus arrives at open loop zero at 180.

9) The root locus does not cross the imaginary axis, hence there is no need to find the
imaginary axis cross over.

The root locus plot is shown in Fig.2.

Figure 7 Root locus plot of K(s+2)/(s+1)2

ECE/SJBIT Page 125


Control Systems 10ES43

Comments on stability:
System is stable for all values of K > 0. The system is over damped for K > 4. It is critically
damped at K = 0, 4.

Problem No 3
K(s 4)
The open loop transfer function is G(s) . Sketch the root locus.
s(s 2)
Solution:

1) Root locus is symmetrical about real axis.

2) There are is one open loop zero at s=-4(m=1). There are two open loop poles at s=0, -
2(n=2). Two branches of root loci start from the open loop poles when K= 0. One branch
goes to open loop zero when K and other goes to infinity asymptotically when K
.

3) Entire negative real axis except the segment between s=-4 to s=-2 lies on the root locus.
180 (2q 1)
4) The asymptote angle is A = , q 0,1, n m 1 0.
nm
Angle of asymptote are A = 180.

(sum of poles) (sum of zeros)


5) Centroid of the asymptote is A
nm
(2) (4)
2.0
1

6) The brake points are given by dK/ds =0.


s(s 2)
K
(s 4)
dK (2s 2)(s 4) (s 2 2s)
0
ds (s 4) 2
s1 1.172, K 0.343;
s 2 6.828, K 11.7

7) Angle of departure from open loop pole at s =0 is 180. Angle of departure from pole at
s=-2.0 is 0.

8) The angle of arrival at open loop zero at s=-4 is 180

ECE/SJBIT Page 126


Control Systems 10ES43

9) The root locus does not cross the imaginary axis. Hence there is no imaginary cross over.

The root locus plot is shown in fig.3.

Figure 3 Root locus plot of K(s+4)/s(s+2)

Comments on stability:
System is stable for all values of K.
0 > K > 0.343 : > 1 over damped
K = 0.343 : = 1 critically damped
0.343 > K > 11.7 : < 1 under damped
K = 11.7 : = 1 critically damped
K > 11.7 : >1 over damped.

Problem No 4
K(s 0.2)
The open loop transfer function is G(s) . Sketch the root locus.
s 2 (s 3.6)
Solution:

1) Root locus is symmetrical about real axis.

2) There is one open loop zero at s = -0.2(m=1). There are three open loop poles at
s = 0, 0, -3.6(n=3). Three branches of root loci start from the three open loop poles when
K= 0 and one branch goes to open loop zero at s = -0.2 when K and other two go to
asymptotically when K .

ECE/SJBIT Page 127


Control Systems 10ES43

3) Root locus lies on negative real axis between -3.6 to -0.2 as the number of open loop
poles plus open zeros to the right of any point on the real axis in this range is odd.

180 (2q 1)
4) The asymptote angle is A = , q n m 1 0,1
nm
Angle of asymptote are A = 90, 270.

(sum of poles) (sum of zeros)


5) Centroid of the asymptote is A
nm
(3.6) (0.2)
1.7
2

6) The root locus does branch out, which are given by dK/ds =0.

(s 3 3.6s 2 )
K-
s 0.2
dK (3s 2 7.2s)(s 0.2) (s 3 3.6s 2 )

ds (s 0.2) 2
2s 3 4.8s 2 1.44s 0
s 0, 0.432, 1.67 and K 0, 2.55, 3.66 respectively.

The root loci brakeout at the open loop poles at s = 0, when K =0 and breakin onto the
real axis at s=-0.432, when K=2.55 One branch goes to open loop zero at s=-0.2 and
other goes breaksout with the another locus starting from open loop ploe at s= -3.6. The
break point is at s=-1.67 with K=3.66. The loci go to infinity in the complex plane with
constant real part s= -1.67.

7) The branches of the root locus at s=0,0 break at K=0 and are tangential to imaginary axis
or depart at 90. The locus departs from open loop pole at s=-3.6 at 0.

8) The locus arrives at open loop zero at s=-0.2 at 180.

9) The root locus does not cross the imaginary axis, hence there is no imaginary axis cross
over.

The root locus plot is shown in Fig.4.

ECE/SJBIT Page 128


Control Systems 10ES43

Figure 4 Root locus plot of K(s+0.2)/s2(s+3.6)

Comments on stability:
System is stable for all values of K. System is critically damped at K= 2.55, 3.66. It is under
damped for 2.55 > K > 0 and K >3.66. It is over damped for 3.66 > K >2.55.

Problem No 5
K
The open loop transfer function is G(s) . Sketch the root locus.
s(s 6s 25)
Solution:

1) Root locus is symmetrical about real axis.

2) There are no open loop zeros (m=0). There are three open loop poles at s=-0,
-3j4(n=3). Three branches of root loci start from the open loop poles when K= 0 and all
the three branches go asymptotically when K .

3) Entire negative real axis lies on the root locus as there is a single pole at s=0 on the real
axis.

180 (2q 1)
4) The asymptote angle is A = , q 0,1, n m 1 0, 1, 2.
nm
Angle of asymptote are A = 60, 180, 300.

(sum of poles) (sum of zeros)


5) Centroid of the asymptote is A
nm
(3 3)
2.0
3

ECE/SJBIT Page 129


Control Systems 10ES43

6) The brake points are given by dK/ds =0.


K s(s 2 6s 25) (s 3 6s 2 25s)
dK
3s 2 12s 25 0
ds
s1,2 2 j2.0817and
K 1,2 34 j18.04
For a point to be break point, the corresponding value of K is a real number greater than
or equal to zero. Hence, S1,2 are not break points.

7) Angle of departure from the open loop pole at s=0 is 180. Angle of departure from
complex pole s= -3+j4 is
p 180
(sum of the angles of vectors to a complex pole in question from other poles)
(sum of the angles of vectors to a complex pole inquestion from zeros)

4
p 180 (180 tan 1 90 ) 36.87
3
Similarly, Angle of departure from complex pole s= -3-j4 is
p 180 (233.13 270 ) 323.13 or 36.87

8) The root locus does cross the imaginary axis. The cross over point and the gain at the
cross over can be obtained by

Rouths criterion
The characteristic equation is s 3 6s 2 25s K 0 . The Rouths array is
s3 1 25
s2 6 K
1 150 K
s
6
s0 6
For the system to be stable K < 150. At K=150 the auxillary equation is 6s2+150=0.
s = j5.
or
substitute s= j in the characteristic equation. Equate real and imaginary parts to zero. Solve
for and K.
s 3 6s 2 25s K 0
j3 6 j2 25 j K 0

(6 2 K) j 2 25 0
0, j5 K 0, 150

ECE/SJBIT Page 130


Control Systems 10ES43

The plot of root locus is shown in Fig.5.

Figure 5 Root locus plot of K/s(s2+6s+25)

Comments on stability:
System is stable for all values of 150 > K > 0. At K=150, it has sustained oscillation of 5rad/sec.
The system is unstable for K >150.

Problem No 1

Sketch the root locus of a unity negative feedback system whose forward path transfer function
K(s 2)
is G(s)H(s) . Comment on the stability of the system.
(s 1)(s 3 j)(s 3 j)

Solution:

9) Root locus is symmetrical about real axis.

10) There is one open loop zero at s = -2 (m = 1). There are three open loop poles at
s = -1, -3 j (n=3). All the three branches of root locus start from the open loop
poles when K = 0. One locus starting from s = -1 goes to zero at s = -2 when
K , and other two branches go to asymptotically (zeros at ) when K .
11) Root locus lies on the negative real axis in the range s=-1 to s= -2 as there is one pole to
the right of any point s on the real axis in this range.

180 (2q 1)
12) The asymptote angle is A = , q n m 1 0,1.
nm
Angle of asymptote is A = 90, 270.

ECE/SJBIT Page 131


Control Systems 10ES43

(sum of poles) (sum of zeros)


13) Centroid of the asymptote is A
nm
(1 3 3) (2)
2.5
1

14) The root locus does not branch. Hence, there is no need to calculate break points.

15) The angle of departure at real pole at s=-1 is 180. The angle of departure at the complex
pole at s=-3+j is 71.57.

p 180
(sum of the angles of vectors to a complex pole in question from other poles)
(sum of the angles of vectors to a complex pole inquestion from zeros)

1
1 tan 1 26.57 or 153.43
-2
1 atan2(-2,1) 153.43
1 2
tan 1 -45 or 135 , 3 tan 1 90
-1 0
p 180 (153.43 90 ) 135 71.57

The angle of departure at the complex pole at s=-3-j is -71.57.

p 180 (206.57 270 ) 225 71.57


16) The root locus does not cross the imaginary axis. Hence there is no imaginary axis cross
over.

The root locus plot is shown in Fig.1

ECE/SJBIT Page 132


Control Systems 10ES43

Figure 1 Root locus plot of K(s+2)/(s+1)(s+3+j)(s+3-j)

Comments on stability:

The system is stable for all the values of K > 0.

Problem No 2

K
The open loop transfer function is G(s)H(s) Sketch the root locus
s(s 0.5)(s 0.6s 10)
2

plot. Comment on the stability of the system. .

Solution:

10) Root locus is symmetrical about real axis.

11) There are no open loop zeros (m=0). There are four open loop poles (n=4) at s=0,
-0.5, -0.3 j3.1480. Four branches of root loci start from the four open loop poles when
K= 0 and go to (open loop zero at infinity) asymptotically when K .

12) Root locus lies on negative real axis between s = 0 to s = -0.5 as there is one pole to the
right of any point s on the real axis in this range.

180 (2q 1)
13) The asymptote angle is A = , q n m 1 0,1,2,3.
nm
Angle of asymptote is A = 45, 135, 225, 315.

ECE/SJBIT Page 133


Control Systems 10ES43

(sum of poles) (sum of zeros)


14) Centroid of the asymptote is A
nm
(0.5 0.3 0.3)
0.275
4
The value of K at s=-0.275 is 0.6137.

15) The root locus has break points.

K = -s(s+0.5)(s2+0.6s+10) = -(s4+1.1s3+10.3s2+5s)

Break points are given by dK/ds = 0

dK
4s 3 3.3s 2 20.6s 5 0
ds

s= -0.2497, -0.2877 j 2.2189

There is only one break point at -0.2497. Value of K at s = -0.2497 is 0.6195.

16) The angle of departure at real pole at s=0 is 180 and at s=-0.5 is 0. The angle of
departure at the complex pole at s = -0.3 + j3.148 is -91.8
p 180
(sum of the angles of vectors to a complex pole in question from other poles)
(sum of the angles of vectors to a complex pole inquestion from zeros)
3.148
1 tan 1 84.6 or 95.4
- 0.3
3.148 6.296
2 tan 1 86.4 , 3 tan 1 90
0.2 0
The angleof 180 (95.4 86.4 90 ) 91.8
p departure at the complex pole at s = -0.3 - j3.148 is 91.8

p 180 (264.6 273.6 270 ) 91.8

17) The root locus does cross the imaginary axis, The cross over frequency and gain is
obtained from Rouths criterion.

The characteristic equation is

s(s+0.5)(s2+0.6s+10)+K =0 or s4+1.1s3+10.3s2+5s+K=0

ECE/SJBIT Page 134


Control Systems 10ES43

The Rouths array is

s4 1 10.3 K
3
s 1.1 5
2
s 5.75 K
28.75 - 1.1K
s1
5.75
s0 K

The system is stable if 0 < K < 26.13

The auxiliary equation at K 26.13 is 5.75s2+26.13 = 0 which gives s = j2.13 at


imaginary axis crossover.

The root locus plot is shown in Fig.2.

Figure 8 Root locus plot of K/s(s+0.5)(s2+0.6s+10)

Comments on stability:

System is stable for all values of 26.13 >K > 0. The system has sustained oscillation at =
2.13 rad/sec at K=26.13. The system is unstable for K > 26.13.

Problem No 3

K
The open loop transfer function is G(s) . Sketch the root locus.
s(s 4)(s 4s 20)
2

ECE/SJBIT Page 135


Control Systems 10ES43

Solution:

10) Root locus is symmetrical about real axis.

11) There are no open loop zeros (m=0). There are three open loop poles (n=3) at s = -0, -4, -
2 j4. Three branches of root loci start from the three open loop poles when K= 0 and to
infinity asymptotically when K .

12) Root locus lies on negative real axis between s = 0 to s = -4.0 as there is one pole to the
right of any point s on the real axis in this range.

180 (2q 1)
13) The asymptote angle is A = , q n m 1 0, 1, 2, 3
nm
Angle of asymptote are A = 45, 135, 225, 315.

(sum of poles) (sum of zeros)


14) Centroid of the asymptote is A
nm
(2.0 2.0 4.0)
2.0
4

15) The root locus does branch out, which are given by dK/ds =0.

K s(s 4)(s 2 4s 20)


(s 4 8s 3 36s 2 80s)
dK
Break point is given by 0
ds
4s 3 24s 2 72s 80 0
4s 3 8s 2 16s 2 32s 40s 80 0
(s 2)(4s 2 16s 40)
s1 2.0, K 64;
s 2 2.0 j2.45, K 100

The root loci brakeout at the open loop poles at s = -2.0, when K = 64 and breakin and
breakout at s=-2+j2.45, when K=100

16) The angle of departure at real pole at s=0 is 180 and at s=-4 is 0. The angle of
departure at the complex pole at s = -2 + j4 is -90.

ECE/SJBIT Page 136


Control Systems 10ES43

p 180
(sum of the angles of vectors to a complex pole in question from other poles)
(sum of the angles of vectors to a complex pole inquestion from zeros)

4
1 tan 1 63.4 or 116.6
-2
1 atan2(4,-2) 116.6
4 8
2 tan 1 63.4 , 3 tan 1 90
2 0
p 180 - (116.6 63.4 90 ) 90

The angle of departure at the complex pole at s = -2 j4 is 90

p 180 - (243.4 296.6 270 )


270 90
17) The root locus does cross the imaginary axis, The cross over point and gain at cross over
is obtained by either Rouths array or substitute s= j in the characteristic equation and
solve for and gain K by equating the real and imaginary parts to zero.

Rouths array

The characteristic equation is s 4 8s 3 36s 2 80s K 0


The Rouths array is
s4 1 36 K
s3 8 80
s 2 26 K
2080 8K
s1
26
s0 K

For the system to be stable K > 0 and 2080-8K > 0. The imaginary crossover is given by
2080-8K=0 or K = 260.

At K = 260, the auxiliary equation is 26s2+260 = 0. The imaginary cross over occurs at s=
j10.

or

ECE/SJBIT Page 137


Control Systems 10ES43

s 4 8s 3 36s 2 80s K 0
put s j
j4 8 j3 36 j2 80 j K 0

36 2 K j 83 80 0
4

Equate real and imaginary parts to zero
83 80 0 0, j 10 ; s j 10
4 36 2 K 0 K 260

The root locus plot is shown in Fig.3.

Figure 9 Root locus plot of K/s(s+4)(s2+4s+20)

Comments on stability:
For 260 > K > 0 system is stable
K = 260 system has stained oscillations of 10 rad/sec.
K > 260 system is unstable.

ECE/SJBIT Page 138


Control Systems 10ES43

Recommended Questions:

1. Give the general rules for constructing root locus.

2. Define Phase margin and Gain margin of root locus.

3. Sketch the root locus of a unity negative feedback system whose forward path transfer
K
function is G(s) .
s
K(s 2)
4. The open loop transfer function is G(s) . Sketch the root locus plot.
(s 1) 2
K(s 4)
5. The open loop transfer function is G(s) . Sketch the root locus.
s(s 2)
K
6. The open loop transfer function is G(s) . Sketch the root locus.
s(s 6s 25)
K
7. The open loop transfer function is G(s) . Sketch the root
s(s 4)(s 4s 20)
2

ECE/SJBIT Page 139


Control Systems 10ES43

UNIT: 06
Stability in the frequency domain

Introduction

Frequency response of a control system refers to the steady state response of a system subject to

sinusoidal input of fixed (constant) amplitude but frequency varying over a specific range,

usually from 0 to . For linear systems the frequency of input and output signal remains the

same, while the ratio of magnitude of output signal to the input signal and phase between two

signals may change. Frequency response analysis is a complimentary method to time domain

analysis (step and ramp input analysis). It deals with only steady state and measurements are

taken when transients have disappeared. Hence frequency response tests are not generally carried

out for systems with large time constants.

The frequency response information can be obtained either by analytical methods or by

experimental methods, if the system exits. The concept and procedure is illustrated in Figure 6.1

(a) in which a linear system is subjected to a sinusoidal input. I(t) = a Sin t and the

corresponding output is O(t) = b Sin (t +) as shown in Figure 6.1 (b).

Figure 6.1 (a) Figure 6.1 (b)

The following quantities are very important in frequency response analysis.

M () = b/a = ratio of amplitudes = Magnitude ratio or Magnification factor or gain.

() = = phase shift or phase angle

ECE/SJBIT Page 140


Control Systems 10ES43

These factors when plotted in polar co-ordinates give polar plot, or when plotted in rectangular

co-ordinates give rectangular plot which depict the frequency response characteristics of a

system over entire frequency range in a single plot.

Frequency Response Data

The following procedure can be adopted in obtaining data analytically for frequency response
analysis.

1. Obtain the transfer function of the system

O( S )
F (S ) , Where F (S) is transfer function, O(S) and I(S) are the Laplace transforms
I (S )
of the output and input respectively.

2. Replace S by (j) (As S is a complex number)

O( j )
F ( j )
I ( j )

O( j )
A( ) B( j ) (another complex number)
I ( j )

3. For various values of , ranging from 0 to determine M () and .

O( j )
M ( ) A( ) B( j ) A jB
I ( j )

M A2 B 2

O( j )
A jB
I ( j )

B
tan 1
A

ECE/SJBIT Page 141


Control Systems 10ES43

4. Plot the results from step 3 in polar co-ordinates or rectangular co-ordinates. These plots are

not only convenient means for presenting frequency response data but are also serve as a

basis for analytical and design methods.

Comparison between Time Domain and Frequency Domain Analysis

An interesting and revealing comparison of frequency and time domain approaches is based on

the relative stability studies of feedback systems. The Rouths criterion is a time domain

approach which establishes with relative ease the stability of a system, but its adoption to

determine the relative stability is involved and requires repeated application of the criterion. The

Root Locus method is a very powerful time domain approach as it reveals not only stability but

also the actual time response of the system. On the other hand, the Nyquist criterion (discussed

later in this Chapter) is a powerful frequency domain method of extracting the information

regarding stability as well as relative stability of a system without the need to evaluate roots of

the characteristic equation.

Graphical Methods to Represent Frequency Response Data

Two graphical techniques are used to represent the frequency response data. They are: 1) Polar

plots 2) Rectangular plots.

Polar Plot

The frequency response data namely magnitude ratio M() and phase angle () when

represented in polar co-ordinates polar plots are obtained. The plot is plotted in complex plane

shown in Figure 6.2. It is also called Nyquist plot. As is varied the magnitude and phase angle

change and if the magnitude ratio M is plotted for varying phase angles, the locus obtained gives

ECE/SJBIT Page 142


Control Systems 10ES43

the polar plot. It is easier to construct a polar plot and ready information of magnitude ratio and

phase angle can be obtained.

Img
+90, -270
Positive angles

+180, -180 0, + 360, -360

Real

Negative angles

+270, -90

Figure 6.2: Complex Plane Representation

A typical polar plot is shown in Figure 6.3 in which the magnitude ratio M and phase angle at a

given value of can be readily obtained.

ECE/SJBIT Page 143


Control Systems 10ES43

Figure 6.3: A Typical Polar Plot

Rectangular Plot

The frequency response data namely magnitude ratio M() and phase angle () can also be

presented in rectangular co-ordinates and then the plots are referred as Bode plots which will be

discussed in Chapter 7.

Illustrations on Polar Plots: Following examples illustrate the procedure followed in obtaining
the polar plots.

Illustration 1: A first order mechanical system is subjected to a input x(t). Obtain the polar plot,

if the time constant of the system is 0.1 sec.

x (t) (input)

y (t) (output)

Governing Differential Equation:

dy
C. Ky Kx by K
dt

C dy
. yx
K dt
dy
. y x Take Laplace transform
dt

SY(S) + Y(S) = X(S)

(S+1) Y(S) = X(S)


ECE/SJBIT Page 144
Control Systems 10ES43

Y (S ) 1
Transfer function F(S) =
X ( S ) S 1

Given = 0.1 sec

Y (S ) 1 1

X ( S ) 0.1S 1 1 0.1S

To obtain the polar plot (i.e., frequency response data) replace S by j.

Y ( j ) 1 1

X ( j ) 0.1 j 1 1 j (0.1 )

Y ( j ) 1 1 j (0)
Magnification Factor M =
X ( j ) 1 j (0.1 ) 1 j (0.1 )

1
M
1 (0.1 ) 2

Y ( j )
Phase angle = Y ( j ) Xj 1 j (0) (1 0.1 )
X ( j )

0
tan 1 tan 1 (0.1 )
1

tan 1 (0.1 )

Now obtain the values of M and for different values of ranging from 0 to as given in Table
6.1.

Table 6.1 Frequency Response Data

1 tan 1 (0.1 )
M
1 (0.1 ) 2
0 1.00 0
2 0.98 -11.13
4 0.928 -21.8
5 0.89 -26.6
6 0.86 -30.9

ECE/SJBIT Page 145


Control Systems 10ES43

10 0.707 -45
20 0.45 -63.4
40 0.24 -76
50 0.196 -78.69
100 0.099 -84.29
0 -90

The data from Table 6.1 when plotted on the complex plane with as a parameter polar plot is

obtained as given below.


=6
= 50


= 20

Illustration 2: A second order system has a natural frequency of 10 rad/sec and a damping ratio

of 0.5. Sketch the polar plot for the system.


x (Input)

y (Response)
m

ECE/SJBIT Page 146


Control Systems 10ES43

The transfer function of the system is given by

Y (S ) n 2

2 Given n = 10 rad/sec and = 0.5


X ( S ) S 2 n S n 2

Y (S ) 100
2
X ( S ) S 10S 100

Replace S by j

Y ( j ) 100 100 j (0)


as j 1
X ( j ) ( j ) 10 j 100 10 j 100
2 2

Y ( j ) 100 j (0) 100 2


M
X ( j ) (100 2 ) j (10 ) (100 2 ) 2 (10 ) 2

100
Magnification Factor = M
(100 2 ) 2 (10 ) 2

100 j (0)
Phase angle = 100 j (0) (100 2 ) j (10 )
(100 ) j (10 )
2

0 1 10
tan 1 tan 2
100 100

Now obtain the values of M and for various value of ranging from 0 to as given in the
following Table 6.2.

Table 6.2 Frequency Response Data: Illustration 2

M()
0 1.00 0.0
2 1.02 -11.8
5 1.11 -33.7
8 1.14 -65.8
10 1.00 -90.0
12 0.78 -110.1
15 0.51 -129.8
20 0.28 -146.3
40 0.06 -165.1
70 0.02 -171.7
0.00 -180.0

ECE/SJBIT Page 147


Control Systems 10ES43

The data from Table 6.2 when plotted on the complex plane with as a parameter polar plot is

obtained as given below.

Note: The polar plot intersects the imaginary axis at a frequency equal to the natural frequency of

the system = n = 10 rad/sec.

Illustration 3: Obtain the polar plot for the transfer function

10
F (S ) Replace S by j
( S 1)

10
F ( j )
j 1

10
M ( ) F ( j )
2 1

() = F (j) = 10 - (j+1)


tan 1
1

Table 6.3 Frequency Response Data: Illustration 3

ECE/SJBIT Page 148


Control Systems 10ES43

M()
0 1.00 0
0.2 9.8 -11
0.4 9.3 -21
0.6 8.6 -31
0.8 7.8 -39
2.0 4.5 -63
3.0 3.2 -72
4.0 2.5 -76
5.0 1.9 -79
10 0.99 -84
0.00 -90

=
M() = 0

Polar plot for Illustration 3

Guidelines to Sketch Polar Plots

Polar plots for some typical transfer function can be sketched on the following guidelines.

(a jb )(c jd )
I A jB F ( S ) --- (Transfer function)
(e jf )

a jb c jd a2 b2 * c2 d 2
Magnitude Ratio = M
e jf e2 f 2

ECE/SJBIT Page 149


Control Systems 10ES43

Phase angle:

a jb c jd
(a jb ) (c jd ) (e jf )
e jf

b d f
tan 1 tan 1 tan 1
a c e

II Values of tan functions Img


IQ
IIQ
IQ: tan-1 (b/a) Positive:
(-a+jb) (a+jb)
IIQ: tan (b/-a) Negative: 180 -
-1

IIIQ: tan-1 (-b/-a) Positive: 180 +


Real
(-a-jb) (a-jb)
IVQ: tan-1 (-b/a) Negative: 360 -
IIIQ IVQ

tan-1 (0) = 00 tan-1 (-0) =1800

tan-1 (1) = 450 tan-1 (-1) = 1350

tan-1 () = 900 tan-1 (-) = 2700

III Let K = Constant

= K + j(0)

ECE/SJBIT Page 150


Control Systems 10ES43

Therefore K K 2 0 2 K Applicable for both K>0 and K<0

K = (K+ j0) Img

= tan-1(0/K) Real

-1
= tan (0) = 0, if K>0

-K+j0
K+j0

= tan-1 (-0) = 1800, if K<0

IV: Sn = (j)n = (0+j)n

= (0+j) (0+j) . . . . . . . . . . . . . n times

a. Magnitude

S n ( j ) n (0 j ) (0 j ) . . . . . . . . . . . . . n times

(0 2 ) (0 2 . . . . . . . . . . . . . n times

Therefore Sn = n

b. Angle

S n ( j ) n (0 j ) (0 j ) . . . . . . . . . . . . n times

= tan-1 (/0) + tan-1 (/0)+ . . . . . . . . . . . . n times

= 900 + 900 + . . . . . . . . . . . . n times

ECE/SJBIT Page 151


Control Systems 10ES43

Sn = n * 900

Illustration 4: Sketch the polar plot for the system represented by the following open loop

transfer function.

10
G(S ) H (S ) , obtain M and for different values of
S ( S 10)(S 2)

i) As 0, S 0 S j

10 0.5 0.5
G(S ) H ( S ) S 0
S *10 * 2 S 0

0.5 S

0 900

90 0

ii) As , S

10 10
G ( S ) H ( S ) S 3 0
S ( S )(S ) S

10 S 3

0 3 * 90 270 0

ECE/SJBIT Page 152


Control Systems 10ES43

-270 Img

M() ()

0 -900 -180 = , M = 0 0

0 -2700 Real

= 0, M =
-90

Illustration 5: Sketch the polar plots for the system represented by the following open loop

transfer function.

K
G(S ) H (S )
S ( S 5)
2

i) As 0, S 0 S j

K
G ( S ) H ( S ) S 0 , S is far lesser than 5 and can be neglected
0 S ( S 5)
2

K K /5
2
2
5S S

K /5 K
M ( )
S2 n

K / 5
( ) ( K / 5) S 2 = 0 2*90 = 0 180 = - 1800
S 2

ECE/SJBIT Page 153


Control Systems 10ES43

ii) As , S

K K
G ( S ) H ( S ) S 3
S ( S 5) S
2

K K
M ( ) 3 0
S 3

( ) K S 3

= 0 - 3*90 = - 2700

-270 Img

M() ()

0 -1800

0 -2700 = 0, M = = , M = 0
0
-180
Real

-90

Illustration 6: Sketch the polar plots for the system represented by the following open loop

transfer function.

10
G(S ) H (S )
S ( S 5)( S 8)
2

i) As 0, S 0 S j

ECE/SJBIT Page 154


Control Systems 10ES43

10 1/ 4
G(S ) H (S ) S 0 2
2
0 S .5.8 S

1/ 4 1/ 4 1/ 4
M ( ) 2
S2 0

( ) 1 / 4 S 2

= 0 - 2*90

= - 2*900 = 1800

ii) As , S

10 10
G(S ) H (S ) S 2
4
S .S .S S

10 10
M ( ) 4
S 4

as , M () = 0

( ) 10 S 4

= 0 4*90 = - 3600

ECE/SJBIT Page 155


Control Systems 10ES43

-270 Img

M() ()

0 -1800 = 0, M = 0, -360
= , M = 0
-180
0 -3600 Real

-90

Illustration 7: Sketch the polar plots for the system represented by the following open loop

transfer function.

10( S 2)
G(S ) H (S )
S ( S 4)( S 5)
3

i) As 0, S 0 S j

10( S 2)
G(S ) H (S ) S 0
0 S ( S 4)(S 5)
3

10.2 1
3
3
S .4.5 S

1 1
M ( ) 3
S 3

( ) 1 S 3 = 0 3*90 = - 2700

ii) As , S

10.S 10
G(S ) H (S ) S 3
4
S .S .S ) S

10 10
M ( ) 4 0
S 4

ECE/SJBIT Page 156


Control Systems 10ES43

( ) 10 S 4 = 0 4*90 = -3600

-270 Img
= 0, M =
M() ()

0 -2700

0 -3600 = , M = 0 0, -360
-180
Real

-90

Illustration 8: Sketch the polar plots for the system represented by the following open loop

transfer function.

10
G(S ) H (S )
S ( S 2)(S 4)

i) As 0, S 0 S j

10 10 / 8
G(S ) H (S ) S 0
0 S (2).4 S

10 / 8 10 / 8
M ( )
S

() 10 / 8 S = 1800 - 900 = 900

ii) As , S

10
G(S ) H (S ) S
S3

10 10
M ( ) 0
S 3 3

ECE/SJBIT Page 157


Control Systems 10ES43

( ) 10 S 3 = 0 3*900 = - 2700
Img
-270
+90 = 0, M =

M() ()

= , M = 0 0, -360
0 900 +180
-180 Real
0 -270 0

+270
-90

Illustration 9: Sketch the polar plot for the system represented by the following transfer function.

Y (S ) 100
2
X ( S ) S 10S 100

i) As 0, S 0 S j

M ( ) 1 1 , for both K positive and negative

( ) 1 180 0

ii) As , S

100 100 100


M ( ) S 0, ( ) = 0 2* = - 900*2 = -1800
S2 S2 S2

M() ()

0 1 1800

ECE/SJBIT Page 158


Control Systems 10ES43

0 -1800 -270
Img
+90

= , M = 0
+180 0, -360
= 0, M = 1
-180 Real

+270
Experimental determination of Frequency Response -90

Many a times the transfer function of a physical system may not be available in such
circumstances it is necessary to obtain frequency response information experimentally. Such data
may then be used to establish the transfer function. This method requires the actual system.

SYSTEM ANALYSIS USING POLAR PLOTS: NYQUIST CRITERION

System Analysis using Polar Plots: Nyquist Criterion

Polar plots can be used to predict feed back control system stability by the application of Nyquist

Criterion, and therefore are also referred as Nyquist Plots. It is a labor saving technique in the

analysis of dynamic behaviour of control systems in which the need for finding roots of

characteristic equation of the system is eliminated.

Consider a typical closed loop control system which may be represented by the simplified block

diagram as shown in Figure 6.4

C(S)
R(S) +
- G(S)

H(S)

Figure 6.4 Simplified System Block Diagram

ECE/SJBIT Page 159


Control Systems 10ES43

The closed-loop transfer function or the relationship between the output and input of the system

is given by

C (S ) G(S )

R( S ) 1 G ( S ) H ( S )

The open-loop transfer function is G(S) H(S) (the transfer function with the feedback loop

broken at the summing point).

1+ G(S) H(S) is called Characteristic Function which when equated to zero gives the

Characteristic Equation of the system.

1 + G(S) H(S) = 0 Characteristic Equation

The characteristic function F(S) = 1 + G(S) H(S) can be expressed as the ratio of two factored

polynomials.

K ( S Z1 )(S Z 2 ).............(S Z n )
Let F ( S ) 1 G( S ) H ( S )
S ( S P1 )(S P2 )(S P3 )..........( S Z n )
k

The Characteristic equation in general can be represented as

F(S) = K (S+Z1) (S+Z2) (S+Z3) . (S+Zn) = 0

Then:

Z1, -Z2, -Z3 . Zn are the roots of the characteristic equation

at S= -Z1, S= -Z2, S= -Z3, 1+ G(S) H(S) becomes zero.

These values of S are termed as Zeros of F(S)

Similarly:

at S= -P1, S= -P2, S= -P3 . Etc. 1+ G (S) H (S) becomes infinity.

These values are called Poles of F (S).

ECE/SJBIT Page 160


Control Systems 10ES43

Condition for Stability

For stable operation of control system all the roots of characteristic equation must be

negative real numbers or complex numbers with negative real parts. Therefore, for a system

to be stable all the Zeros of characteristic equation (function) should be either negative real

numbers or complex numbers with negative real parts. These roots can be plotted on a complex-

plane or S-plane in which the imaginary axis divides the complex plane in to two parts: right half

plane and left half plane. Negative real numbers or complex numbers with negative real parts lie

on the left of S-plane as shown Figure 6.5.

Left half Img Right half


of S Plane of S Plane
-3+j2

2+j1

Real

2-j1

-3-j2

Figure 6.5 Two halves of Complex Plane

Therefore the roots which are positive real numbers or complex numbers with positive real parts

lie on the right-half of S-plane.

In view of this, the condition for stability can be stated as For a system to be stable all the

zeros of characteristic equation should lie on the left half of S-plane.

Therefore, the procedure for investigating system stability is to search for Zeros on the right

half of S-plane, which would lead the system to instability, if present. However, it is

impracticable to investigate every point on S-plane as to which half of S-plane it belongs to and

ECE/SJBIT Page 161


Control Systems 10ES43

so it is necessary to have a short-cut method. Such a procedure for searching the right half of S-

plane for the presence of Zeros and interpretation of this procedure on the Polar plot is given by

the Nyquist Criterion.

Nyquist Criterion: Cauchys Principle of Argument:

In order to investigate stability on the Polar plot, it is first necessary to correlate the region of

instability on the S-plane with identification of instability on the polar plot, or 1+GH plane. The

1+GH plane is frequently the name given to the plane where 1+G(S) H(S) is plotted in complex

coordinates with S replaced by j. Likewise, the plot of G(S) H(S) with S replaced by j is often

termed as GH plane. This terminology is adopted in the remainder of this discussion.

The Nyquist Criterion is based on the Cauchys principle of argument of complex variable

theory. Consider [F(S) = 1+G(S) H(S)] be a single valued rational function which is analytic

everywhere in a specified region except at a finite number of points in S-plane. (A function F(S)

is said to be analytic if the function and all its derivatives exist). The points where the function

and its derivatives does not exist are called singular points. The poles of a point are singular

points.

Let CS be a closed path chosen in S-plane as shown Figure 6.6 (a) such that the function F(S) is

analytic at all points on it. For each point on CS represented on S-plane there is a corresponding

mapping point in F(S) plane. Thus when mapping is made on F(S) plane, the curve C G mapped

by the function F(S) plane is also a closed path as shown in Figure 6.6 (b). The direction of

traverse of CG in F(S) plane may be clockwise or counter clockwise, depending upon the

particular function F(S).

ECE/SJBIT Page 162


Control Systems 10ES43

Then the Cauchy principle of argument states that: The mapping made on F(S) plane will

encircle its origin as many number of times as the difference between the number of Zeros

and Poles of F(S) enclosed by the S-plane locus CS in the S-plane.

F(S) = 1+G(S) H(S) plane


S-plane
+j +j
GS5
S1
GS4
GS1
S5 S2

- - (0+j)
GS3
CS
S3 CG GS2
S4

-j
-j
Figure 6.6 (a) Figure 6.6 (b)

Figure 6.6 Mapping on S-plane and F(S) plane

Thus N=ZP

N0+j0 = Z P

Where N0+j0: Number of encirclements made by F(S) plane plot (CG) about its origin.

Z and P: Number of Zeros and Poles of F(S) respectively enclosed by the locus C S in the S-

plane.

Illustration: Consider a function F(S)

K ( S 1)(S 2 j 2)(S 2 j 2)
F( S )
S ( S 3)(S 5)(S 5 j 2)(S 5 j 2)

Zeros: -1, (-2-j2), (-2+j2) indicated by O (dots) in the S-plane

Poles: 0, -3, -5, (-5 j2), (-5 +j2) indicated by X (Cross) in S-plane: As shown in Figure 6.6 (c)

ECE/SJBIT Page 163


Control Systems 10ES43

+j S-plane F(S) = 1+G(S) H(S) plane


+j
CS2
CS1

CG2 CG1
- CS1 - (0+j0)
CG2
CG2
O: ZEROS
X: POLES

CS2 -j
-j
Figure 6.6 (c) Figure 6.6 (d)

Now consider path CS1 (CCW) on S-plane for which:

Z: 2, P =1

Consider another path CS2 (CCW) in the same S plane for which:

Z = 1, P = 4

CG1 and CG2 are the corresponding paths on F(S) plane [Figure 6.6 (d)].

Considering CG1 [plot corresponding to CS1 on F (S) plane]

N0+j0 = Z P = 2-1 = +1

CG1 will encircle the origin once in the same direction of C S1 (CCW)

Similarly for the path CG2

N0+j0 = Z P = 1 4 = - 3

CG2 will encircle the origin 3 times in the opposite direction of C S2 (CCW)

Note: The mapping on F(S) plane will encircle its origin as many number of times as the

difference between the number of Zeros and Poles of F(S) enclosed by the S-plane locus.

From the above it can be observed that

ECE/SJBIT Page 164


Control Systems 10ES43

In the expression

N= Z - P,

N can be positive when: Z>P

N = 0 when: Z=P

N can be negative when: Z<P

When N is positive the map CG encircles the origin N times in the same direction as that of

CS

When N = 0, No encirclements

N is negative the map CG encircles the origin N times in the opposite direction as that of CS

Nyquist Path and Nyquist Plot

The above Cauchys principle of argument can be used to investigate the stability of control

systems. We have seen that if the Zeros of characteristic function lie on the right half of S-plane

it will lead to system instability. Now, to encircle the entire right half of S-plane, select a closed

path as shown in Figure 6.6 (e) such that all the Zeros lying on the right-half of S-plane will lie

inside this path. This path in S-plane is known as Nyquist path. Nyquist path is generally taken

in CCW direction. This path consists of the imaginary axis of the S-plane (S = 0+j, - < < )

and a closing semicircle of infinite radius. If the system being tested has poles of F(S) on the

imaginary axis, it is customary to modify the contour as shown Figure 6.6 (f) excluding these

poles from the path.

ECE/SJBIT Page 165


Control Systems 10ES43

+j S-plane
+j
+j

r=
0+j0 r=
- S=+j0
0-j0 - S= -j0
r0

-j
S= -j
-j -j

Figure 6.6 (e): Nyquist Path Figure 6.6 (f)

Corresponding to the Nyquist path a plot can be mapped on F(S) = 1+G(S) H(S) plane as shown

in Figure 6.6 (g) and the number of encirclements made by this F(S) plot about its origin can be

counted.
1+ G(S) H(S) plane
Img

0+j0
Real Real

Img

Figure 6.6 (g)

Now from the principle of argument

N0+j0 = Z-P

N0+j0 = number of encirclements made by F(S) plane plot

Z, P: Zeros and Poles lying on right half of S-plane

ECE/SJBIT Page 166


Control Systems 10ES43

For the system to be stable: Z = 0

N0+j0 = - P Condition for Stability

Apart from this, the Nyquist path can also be mapped on G(S) H(S) plane (Open-loop transfer

function plane) as shown in Figure 6.6 (h).

Now consider

F(S) = 1+ G(S) H(S) for which the origin is (0+j0) as shown in Figure 6.6 (g).

Therefore G(S) H(S) = F(S) 1

= (0+j0) 1 = (-1+j0) Coordinates for origin on G(S) H(S) plane as shown in

Figure 6.6(h)
G(S) H(S) plane
Img

0+j0
(-1+j0)
Origin of the plot
for G(S) H(S)

Figure 6.6 (h)

Thus a path on 1+ G(S) H(S) plane can be easily converted to a path on G(S) H(S) plane or open

loop transfer function plane. This path will be identical to that of 1+G(S) H(S) path except that

the origin is now shifted to the left by one as shown in Figure 6.6 (h).

This concept can be made use of by making the plot in G(S) H(S) plane instead of 1+ G(S) H(S)

plane. The plot made on G(S) H(S) plane is termed as the Niquist Plot and its net encirclements

about (-1+j0) (known as critical point) will be the same as the number of net encirclements made

by F(S) plot in the F(S) = 1+G(S) H(S) plane about the origin.

Now, the principle of argument now can be re-written as

ECE/SJBIT Page 167


Control Systems 10ES43

N-1+j0 = Z-P

Where N-1+j0 = Number of net encirclements made by the G(S) H(S) plot (Nyquist Plot) in the

G(S) H(S) plane about -1+j0

For a system to be stable Z = 0

N-1+j0 = -P

Thus the Nyquist Criterion for a stable system can be stated as The number of net

encirclements made by the Nyquist plot in the G(S) H(S) plane about the critical point

(-1+j0) is equal to the number of poles of F(S) lying in right half of S-plane. [Encirclements

if any will be in the opposite direction. Poles of F(S) are the same as the poles of G(S) H(S)].

Thus the stability of closed-loop control system is determined from its open-loop transfer

function.

System Analysis using Nyquist Criterion: Illustrations

Illustration 1: Sketch the Nyquist plot for the system represented by the open loop transfer

function and comment on its stability.

K
G(S ) H (S ) K 0, a 0 Poles: S = 0 (on imaginary axis) and S = -a
S ( S a)

Step 1: Define Nyquist path. Let the Nyquist path be defined as given below.

ECE/SJBIT Page 168


Control Systems 10ES43

+j
S= +j

S=+j0 r=
- S= -j0
r0

Nyquist Path
S= -j

-j

Section I: S = +j to S = +j0; Section II: S = +j0 to S = -j0

Section III: S = -j0 to S = -j; Section IV: S = -j to S = +j

2. Corresponding to different sections namely I, II, III, and IV Obtain polar plots on G(S) H(S)

plane, which are nothing but Nyquist Plots.

Nyquist Plot for Section I: In S-plane section I runs from S= + j to S = +j0

To obtain polar plot in G(S) H(S) plane:

K
G(S ) H (S ) K 0, a 0
S ( S a)

K
(i) G( S ) H ( S ) S j ,
S2

K
G(S ) H (S ) 0
S2

K
G( S ) H ( S ) 2
K S 2
S

= 0 2*900 = - 1800
S= -j

ECE/SJBIT Page 169


Control Systems 10ES43

K
K K1
(ii) G ( S ) H ( S ) S j0 a ,
S .a S S

G(S) H(S) = K/a S = 0 - 900 = - 900

Img G(S) H(S) Plane


S M() ()

S 0 -1800

S 0 -900 S=j
-1800 Real

Section I

S=j0
-900

Nyquist Plot for Section II: In S-plane section II runs from S= + j0 to S = -j0

In this region S 0

In S-plane section II is a semicircle from S = + j0 to S = -j0 of radius r 00, covering an angle of


1800 in clockwise direction

K K1
G(S ) H (S ) where K1 = K/a
S( a ) S

But S = re+j equation of a circle in exponential form

K1
G(S ) H (S ) j
Re j , where R
K1
re r
K1
G(S) H(S) = R.e-j R (as r is very small)
r

ECE/SJBIT Page 170


Control Systems 10ES43

This shows that G(S) H(S) plot of section II of Nyquist path is a circle of radius = starting
from S = +j0 and ending at a point S = -j0 covering an angle of 1800 in opposite direction of
section II of Nyquist path (CCW direction i.e., negative sign)

K1
In general if G (S) H (S) =
Sn

K1
G(S ) H (S ) n jn
R.e jn
r e

K1
Where R = Img
rn G(S) H(S) Plane
S= -j0

R= Section II

Real

S=j0
The G (S) H (S) plot will be a portion circle (part) of radius R , starting at a point S = +j
and ending at a point S = -j covering an angle of (n*1800) in the opposite direction (CCW)
(since sign is negative)

Nyquist Plot for Section III: In S-plane section III runs from S= -j0 to S = j

K K
G(S ) H (S ) S j 0 K1 / S where Kl = (K/a)
S( S a ) S .a

G( S ) H ( S ) K 1 / S

G(S) H(S) = Kl S, Kl is negative

= -Kl S

G(S) H(S) = 1800 900 = 900

K
G( S ) H ( S ) S j S j = K/S2
S ( S a)

ECE/SJBIT Page 171


Control Systems 10ES43

K
G(S ) H (S ) 0
S2
G(S) H(S) = K - S2 = 0 2 (-900) = 1800 ; (S is negative)

Img
+900 S= -j0 G(S) H(S) Plane

Section III

+1800 S= -j

Real

This Section III is the mirror image of section of the Section I.

Nyquist Plot for Section IV: In S-plane section IV runs from S= -j to S = j

In this region S

In the S-plane it is a semicircle of radius R from S = - j to S = + j covering an angle of


1800 in the counter clockwise direction.

In the G(S) H(S) plane

K
G( S ) H ( S ) S
S2
But S = R e+j Equation in circle in exponential form

K K
G(S ) H (S ) r.e j 2 where r 0
R .e j 2
2
R2

Thus G(S) H(S) plot for section IV is also a circle of radius r 0 starting at S = - j and
ending at S = + j covering an angle of 2* 1800 (2) in the opposite direction (CW).

ECE/SJBIT Page 172


Control Systems 10ES43

Img
G(S) H(S) Plane

S= -j r0
S= +j Real
Section IV

Now assemble the Nyquist plots of all the sections as given below to get the overall Nyquist
plot Img
-j0 G(S) H(S) Plane

-j

Real
(-1+j0) j

j0
From Nyquist Criterion:

No. of encirclements made by Nyquist plot about ( 1 +j0) = N-1+j0 = Z P

P = No. of poles lying in the right half of S plane

ECE/SJBIT Page 173


Control Systems 10ES43

K
For the function G( S ) H ( S ) , the Poles are: S = 0, S = - a = 0, which lie on the left half
S ( S a)
of S-plane

Therefore P = 0: Number of poles on the right half of S-plane

N-1+j=0 = 0 as counted from the Nyquist plot

N-1+j0 = Z P

0=Z0

Therefore Z = 0

Number of zeros lying on the right half of S-plane is 0 and hence the system is stable

Illustration 2: Obtain the Nyquist diagram for the system represented by the block diagram given
below and comment on its stability

C (S)
R (S) + K
S (S 1)
2

K
G(S )
S (S 1)
2

H (S ) S

K K
G(S ) H (S ) *S , Poles are S = 0, -1/ P = 0
S (S 1)
2
S (S 1)

ECE/SJBIT Page 174


Control Systems 10ES43

Recommended Questions:

1. Explain briefly the different Graphical Methods to Represent Frequency Response Data .

2. A second order system has a natural frequency of 10 rad/sec and a damping ratio of 0.5.

Sketch the polar plot for the system.

3. Obtain the polar plot for the transfer function

4. Sketch the polar plots for the system represented by the following open loop transfer function.

K
G(S ) H (S )
S ( S 5)
2

5. Sketch the polar plots for the system represented by the following open loop transfer function.

10
G(S ) H (S )
S ( S 5)( S 8)
2

6. Sketch the polar plots for the system represented by the following open loop transfer function.

10
G(S ) H (S )
S ( S 2)(S 4)

7. Draw Nyquist path for the function F(s)


K ( S 1)(S 2 j 2)(S 2 j 2)
F( S )
S ( S 3)(S 5)(S 5 j 2)(S 5 j 2)

ECE/SJBIT Page 175


Control Systems 10ES43

UNIT-7

Frequency domain analysis

Frequency response of a control system refers to the steady state response of a system subject to

sinusoidal input of fixed (constant) amplitude but frequency varying over a specific range,

usually from 0 to . For linear systems the frequency of input and output signal remains the

same, while the ratio of magnitude of output signal to the input signal and phase between two

signals may change. Frequency response analysis is a complimentary method to time domain

analysis (step and ramp input analysis). It deals with only steady state and measurements are

taken when transients have disappeared. Hence frequency response tests are not generally carried

out for systems with large time constants.

The frequency response information can be obtained either by analytical methods or by

experimental methods, if the system exits. The concept and procedure is illustrated in Figure 7.1

(a) in which a linear system is subjected to a sinusoidal input. I(t) = a Sin t and the

corresponding output is O(t) = b Sin (t +) as shown in Figure 6.1 (b).

Figure 7.1 (a) Figure 7.1 (b)

The following quantities are very important in frequency response analysis.

M () = b/a = ratio of amplitudes = Magnitude ratio or Magnification factor or gain.

() = = phase shift or phase angle

ECE/SJBIT Page 176


Control Systems 10ES43

These factors when plotted in polar co-ordinates give polar plot, or when plotted in rectangular

co-ordinates give rectangular plot which depict the frequency response characteristics of a

system over entire frequency range in a single plot.

Frequency Response Data

The following procedure can be adopted in obtaining data analytically for frequency response
analysis.

5. Obtain the transfer function of the system

O( S )
F (S ) , Where F (S) is transfer function, O(S) and I(S) are the Laplace transforms
I (S )
of the output and input respectively.

6. Replace S by (j) (As S is a complex number)

O( j )
F ( j )
I ( j )

O( j )
A( ) B( j ) (another complex number)
I ( j )

7. For various values of , ranging from 0 to determine M () and .

O( j )
M ( ) A( ) B( j ) A jB
I ( j )

M A2 B 2

O( j )
A jB
I ( j )

B
tan 1
A

ECE/SJBIT Page 177


Control Systems 10ES43

8. Plot the results from step 3 in polar co-ordinates or rectangular co-ordinates. These plots are

not only convenient means for presenting frequency response data but are also serve as a

basis for analytical and design methods.

Comparison between Time Domain and Frequency Domain Analysis

An interesting and revealing comparison of frequency and time domain approaches is based on

the relative stability studies of feedback systems. The Rouths criterion is a time domain

approach which establishes with relative ease the stability of a system, but its adoption to

determine the relative stability is involved and requires repeated application of the criterion. The

Root Locus method is a very powerful time domain approach as it reveals not only stability but

also the actual time response of the system.

It was pointed out earlier that the performance of a feedback control system is more
preferably measured by its time domain response characteristics. This is in contrast to the
analysis & design of systems in the communication field, where the frequency response is of
more importance, since in this case most of the signals to be processed are either sinusoidal or
periodic in nature. However analytically, the time response of a control system is usually
difficult to determine, especially in the case of high order systems. In the design aspects, there
are no unified ways of arriving at a designed system given the time-domain specifications, such
as peak overshoot, rise time , delay time & setting time. On the other hand, there is a wealth of
graphical methods available in the frequency-domain analysis, all suitable for the analysis &
design of linear feedback control systems once the analysis & design are carried out in the
frequency domain, time domain behavior of the system can be interpreted based on the
relationships that exist between the time-domain & the frequency-domain properties. Therefore,
we may consider that the main purpose of conducting control systems analysis & design in
frequency domain is merely to use the techniques as a convenient vehicle toward the same
objectives as with time-domain methods.
The starting point in frequency-domain analysis is the transfer function.
For a single loop feed back system, the closed loop transfer function is written

ECE/SJBIT Page 178


Control Systems 10ES43

C(s) G(s)
M(s) = = (1)
R(s) 1+ G(s) H(s)

Under the sinusoidal steady-state, we get s = j; then equation(1.0) becomes,

C(j) G(j)
M(j) = = (1.1)
R(j) 1+ G(j) H(j)

The sinusoidal steady-state transfer relation M(j), which is a complex function of , may be
expressed in terms of a real & an imaginary part; that is,

M((j) = Re [ M (j)] + j Im [ M(j)] (1.2)

Or , M(j) can be expressed in terms of its magnitude & phase as

M(j) = M () m() (1.3)


Where
G(j)
M(() = (1.4)
1 + G(j) H(j)
And
G(j)
m() =
1 + G(j) H(j)
(1.5)

= G(j) - 1 + G(j) H(j)

ECE/SJBIT Page 179


Control Systems 10ES43

since the analysis is now in the frequency domain, some of the terminology used in
communication system may be applied to the present control system characterization. For
instance, M() of Eq. (1.4) may be regarded as the magnification of the feed back control system
is similar to the gain or amplification of an electronic amplifier. In an audio amplifier, for
instance, an ideal design criterion is that the amplifier must have a flat gain for all frequencies.
Of course, realistically, the design criterion becomes that of having a flat gain in the audio
frequency range. In control system the ideal design criterion is similar. If it is desirable to keep
the output C(j) identical to the input R(j) at all frequencies, M(j) must be unity for all
frequencies. However, from Eq. (1.1) it is apparent that M(j) can be unity only when G(j) is
infinite, while H(j) is finite & nonzero. An infinite magnitude for g(j) is, of course,
impossible to achieve in practice, nor would it be desirable, since most control system become
unstable when its loop gain becomes very high. Further more, all control system are subject
noise. Thus in addition to responding to the input signal, the system should be able to reject &
suppress noise & unwanted signals. This means that the frequency response of a control system
should have a cutoff characteristic in general, & sometimes even a band-pass characteristic.
The phase characteristics of the frequency response are also of importance. The ideal situation
is that the phase must be a linear function of frequency within the frequency range of interest.
Figure 1.1 shows the gain & phase characteristics of an ideal low-pass filter, which is impossible
to realize physically. Typical gain & phase characteristics of a feedback control system are
shown in Fig. 1.2. The fact is that the great majority of control systems have the characteristics
of a low-pass filter, so the gain decreases as the frequency increases.
M() 0

1
m()

0 c Deg
Fig. 1.1. Gain-phase characteristics of an ideal low-pass filter.

ECE/SJBIT Page 180


Control Systems 10ES43

M() Mp
m()
1 Deg

0
Fig.1.2. Typical gain & phase characteristics of a feedback control system.

Frequency-Domain characteristics:
If a control system is to be designed or analyzed using frequency-domain techniques, we need
a set of specification to describe the system performance. The following frequency-domain
specifications are often used in practice.

Peak response Mp :
The peak response Mp is defined as the maximum value of M() that is given in
Eq.(1.4). In general, the magnitude of Mp gives an indication of the relative stability of a feed
back control system. Normally, a large M p corresponds to a large peak overshoot in the step
response. For most design problems it is generally accepted that an optimum value Mp of should
be somewhere between 1.1 & 1.5.
Resonant frequency p :
The resonant frequency p is defined as the frequency at which the peak resonance Mp occurs.
Bandwidth :
The bandwidth , BW, is defined as the frequency at which the magnitude of M(j), M(),
drops at 70.7 percent of its zero-frequency level, or 3 dB down from the zero-frequency gain. In
general, the bandwidth of a control system indicates the noise-filtering characteristics of the
system. Also, bandwidth gives a measure of the transient response properties, in that a large
bandwidth corresponds to a faster rise time, since higher-frequency signals are passed on to the

ECE/SJBIT Page 181


Control Systems 10ES43

outputs. Conversely, if the bandwidth is small, only signals of relatively low frequencies are
passed, & the time response will generally be slow & sluggish.
Cutoff rate :
Often, bandwidth alone is inadequate in the indication of the characteristics of the system in
distinguishing signals from noise. Sometimes it may be necessary to specify the cutoff rate of the
frequency response at the higher frequencies. However, in general, a steep cutoff characteristics
may be accompanied by a large Mp, which corresponds to a system with a low stability margin.
The performance criteria defined above for the frequency-domain analysis are illustrated on
the closed-loop frequency response, as shown in Fig. 1.3.
There are other criteria defined that may be used to specify the relative stability &
performance of a feedback control system. These are defined in the ensuring sections of this
chapter.
M()

Mp

1 Bandwidth
0
p BW

Fig.1.3. Typical magnification curve of a feedback control system.

Mp, , p & the bandwidth of a second-order system:


For a second-order feedback control system, the peak resonance Mp, the resonant frequency p,
& the bandwidth are all uniquely related to the damping ratio & the natural undamped
frequency n of the system. Consider the second-order sinusoidal steady-state transfer function
of a closed-loop system,
C(j) 2 n
M(j) = = (1.6)
R(j) (j)2 + 2 n (j) + 2 n

ECE/SJBIT Page 182


Control Systems 10ES43

1
=
1 + j 2 (/n) - (/n)2

We may simplify the last expression by letter u = / n. The Eq. (1.6) becomes

1
M(ju) = ( 1.7)
1 + j2 u - u2

The magnitude & phase of M (j) are


1
M(ju) = M(u) = (1.8)
[( 1 u2 )2 + ( 2 u)2]
And
2 u
M(ju) = m(u) = - tan -1 (1.9)
1 u2

The resonant frequency is determined first by taking the derivative of M(u) with respect to u &
setting it equal to zero. Thus

dM(u) 1
=- [( 1 u2 )2 + ( 2 u)2] 3/2 ( 4 u3 4u + 8u2) = 0 ( 1.10)
du 2
from which
4u3 4u + 8u2 = 0 ( 1.11)

The root of Eq. (1.11) are


up = 0 (1.12)

ECE/SJBIT Page 183


Control Systems 10ES43

and
up = 1 - 22 ( 1.13)

The solution Eq. (1.12) merely indicates that the slope of the M() versus curve is zero at
= 0; it is not true maximum. The solution of eq. (1.13) gives the resonant frequency,
p = n 1 - 22 (1.14)
Since frequency is a real quantity, Eq. (1.14) is valid only for 1 22 or 0.707. This means
simply that for all values of greater than 0.707, the solution of p = 0 becomes the valid one, &
Mp = 1.
Substituting Eq. (1.13) into Eq. (1.8) & simplifying, we get
1
Mp = (1.15)
2 1 - 2
It is important to note that Mp is a function of only, whereas p is a function of & n
5

3
Mp

0
0.5 0.707 1.0 1.5 2.0
Damping ratio
1
Fig.1.4 Mp versus-damping ratio for a second order system, Mp =
2 1 - 2
ECE/SJBIT Page 184
Control Systems 10ES43

1.0

0.8

up = p /n
0.6

0.4

0.2

0
0.5 0.707 1.0
Damping ratio

Fig 1.5. Normalized resonant frequency- versus-damping ratio for a second order system,
Up = 1 - 2 .
Fig.1.4 & 1.5 illustrate the relationship between Mp & , & u = p / n & ,
respectively.
Bandwidth :
Bandwidth BW of a system is a frequency at which M() drops to 70.7% of its zero
frequency level or 3 dB down from the zero frequency gain. Equating the Eq.
1
M(u) = = 0.707
[( 1 u2)2 + ( 2u)2]

1
= [( 1 u2)2 + ( 2u)2] =
0.707

= 2.

ECE/SJBIT Page 185


Control Systems 10ES43

Squaring both sides


( 1 u2)2 + 42u2 = 2

1 + u4 2u2 + 42u2 = 2
Let u2 = x

1 + x2 2x + 42 x = 2

x2 2x + 42 x = 1
x2 x ( 2 - 42 ) =1
x2 x ( 2 - 42 ) 1 = 0
a = 1, b = - ( 2 - 42 ) , c = -1
-b b2 4ac
x=
2a
(2 42 ) (2 42 )2 + 4
=
2
(2 42 ) (4 + 164 16 2 + 4
=
2
(2 42 ) 16 4 16 2 + 8
=
2
2 (1 22 ) 4 + 164 16 2 + 4
=
2
2 (1 22 ) 22 + 44 42
=
2

ECE/SJBIT Page 186


Control Systems 10ES43

2 (1 22 ) 22 + 44 42
=
2

2 [(1 22 ) 2 + 44 42]
=
2
u2 = x = (1 22 ) 2 + 44 4 2
/ n = u = [(1 22 ) (2 + 44 4 2 ] 1/2
BW = n [ ( 1 22 ) + 44 - 42 +2]1/2
For the second order system under consideration, we easily establish some simple relationship
between the time domain response & the frequency-domain response of the system.
1. The maximum over shoot of the unit step response in the time domain depends upon
only.
2. The response peak of the closed - loop frequency response Mp depends upon only.
3. The rise time increases with , & the bandwidth decreases with the increase of , for a
fixed n, therefore, bandwidth & rise time are inversely proportional to each other.
4. Bandwidth is directly proportional to n.
5. Higher bandwidth corresponds to larger Mp.

ECE/SJBIT Page 187


Control Systems 10ES43

Recommended Questions:

1. Give the Comparison between Time Domain and Frequency Domain Analysis

2. For the second order system under consideration, establish some simple relationship between
the time domain response & the frequency-domain response of the system.
3. Define Peak response, resonant frequency, cutoff rate and bandwidth.

ECE/SJBIT Page 188


Control Systems 10ES43

UNIT -8
Introduction to State variable analysis:

ECE/SJBIT Page 189


Control Systems 10ES43

ECE/SJBIT Page 190


Control Systems 10ES43

ECE/SJBIT Page 191


Control Systems 10ES43

ECE/SJBIT Page 192


Control Systems 10ES43

ECE/SJBIT Page 193


Control Systems 10ES43

ECE/SJBIT Page 194


Control Systems 10ES43

ECE/SJBIT Page 195


Control Systems 10ES43

ECE/SJBIT Page 196


Control Systems 10ES43

ECE/SJBIT Page 197


Control Systems 10ES43

ECE/SJBIT Page 198


Control Systems 10ES43

ECE/SJBIT Page 199


Control Systems 10ES43

ECE/SJBIT Page 200


Control Systems 10ES43

ECE/SJBIT Page 201


Control Systems 10ES43

ECE/SJBIT Page 202


Control Systems 10ES43

ECE/SJBIT Page 203


Control Systems 10ES43

ECE/SJBIT Page 204


Control Systems 10ES43

ECE/SJBIT Page 205


Control Systems 10ES43

ECE/SJBIT Page 206


Control Systems 10ES43

ECE/SJBIT Page 207


Control Systems 10ES43

Recommended Questions:

1.Define state equation & write the mathematical form of it.

2. Define output variables & give the matrix form of it for n variables of the system.

3. Explain briefly the state equation based on modeling procedure.

4. Draw a block diagram for the general second-order, single-input single-output system:

5. Find the transfer function and a single first-order differential equation relating the output y(t)
to the input u(t) for a system described by the first-order linear state and output equations:

Q.6 Use the Laplace transform method to derive a single differential equation for the capacitor
voltage vC in the series R-L-C electric circuit shown in Fig below.

ECE/SJBIT Page 208