without
N Layout Building Zone Split qty Floor split type
ventilation only
running(W)
25 Central control building 26751 2 Floor Standing Unit MFX60CSHNAW / MKX60CSSHIW
5970 1 Floor Standing Unit 2.0 Tr- ZT024ZXCV1
1
14126 2 Floor Standing Unit 2.0 Tr- ZT024ZXCV1
2614 1 Floor Standing Unit 2.0 Tr- ZT024ZXCV1
3 12565 1 Floor Standing Unit MFX60CSHNAW / MKX60CSSHIW
39 Elctrical room WTP 15216 3 Floor Standing Unit 2.0 Tr- ZT024ZXCV1
2
10156 1 Floor Standing Unit MFX48CSHNAW / MKX48CSSHIW
14 Electrical room compressed gas 33312 3 Floor Standing Unit MFX48CSHNAW / MKX48CSSHIW
1 50309 4 Floor Standing Unit MFX48CSHNAW / MKX48CSSHIW
25303 2 Floor Standing Unit MFX60CSHNAW / MKX60CSSHIW
9A Gas turbine 12200 1 Floor Standing Unit MFX60CSHNAW / MKX60CSSHIW
73215 6 Floor Standing Unit MFX60CSHNAW / MKX60CSSHIW
1
51771 4 Floor Standing Unit MFX60CSHNAW / MKX60CSSHIW
1163 1 Floor Standing Unit 2.0 Tr- ZT024ZXCV1
2 17337 3 Floor Standing Unit 2.0 Tr- ZT024ZXCV1
26 Common electrical building 11467 1 Floor Standing Unit MFX48CSHNAW / MKX48CSSHIW
1 4591 1 Floor Standing Unit 2.0 Tr- ZT024ZXCV1
48415 4 Floor Standing Unit MFX60CSHNAW / MKX60CSSHIW
13092 1 Floor Standing Unit MFX60CSHNAW / MKX60CSSHIW
2
12659 1 Floor Standing Unit MFX60CSHNAW / MKX60CSSHIW
58A ASL Electrical Building 10648 1 Floor Standing Unit MFX48CSHNAW / MKX48CSSHIW
1
45698 4 Floor Standing Unit MFX48CSHNAW / MKX48CSSHIW
12 BSDG Electrical building 35709 3 Floor Standing Unit MFX48CSHNAW / MKX48CSSHIW
1
2172 1 Floor Standing Unit 2.0 Tr- ZT024ZXCV1
21 Nitrogen generation and storage 1 72654 6 Floor Standing Unit MFX48CSHNAW / MKX48CSSHIW
59B Unloading pump electrical building 12657 1 Floor Standing Unit MFX60CSHNAW / MKX60CSSHIW
1
7037 1 Floor Standing Unit 2.0 Tr- ZT024ZXCV1
67 ASL Treatment Shelter 1 45100 4 Floor Standing Unit MFX48CSHNAW / MKX48CSSHIW
56 Fuel unloading gate house 1 4982 1 Floor Standing Unit 2.0 Tr- ZT024ZXCV1
* The necessary pressures have been included for the impulsion and return fans of 16 Floor Standing Unit 2.0 Tr- ZT024ZXCV1
Note: ASAP: Pending revision by the engineering department 27 Floor Standing Unit MFX48CSHNAW / MKX48CSSHIW
22 Floor Standing Unit MFX60CSHNAW / MKX60CSSHIW
N Layout Building Zone
3
39 Elctrical room WTP
2
9A Gas turbine
2
26 Common electrical building
1
* The necessary pressures have been included for the impulsion and return fans of
Note: ASAP: Pending revision by the engineering department
N Layout Building Zone
3
39 Elctrical room WTP
2
9A Gas turbine
2
26 Common electrical building
1
* The necessary pressures have been included for the impulsion and return fans of
Note: ASAP: Pending revision by the engineering department
Ambient
N Layout Building ID
extraction
* According to GEMSS-M-33
** According to GEMSS-M-27, Include a special motor driven valve for releasing the dust out of
Temperature qty Unit
Redunda
Filters type service tempo capacity
ncy
(C) ral* (m/h)
lve for releasing the dust out of the collector and a collecting drum with a minimum volume of 1m3, Inertial
BAG Filter box BAG Filter box
Sound Pressure
section air section air
power necesary ATEX VFD
fresh unit fresh unit
(dBA) (Pa)
- 98 x No 775x675
- 98 x No 775x675
- 311 - No 1690x1385
- 150 - No 4450x3830
- 150 - No 3520x2910
ume of 1m3, Inertial type sand filters, permanent metal panel washable type, Secondary air filters on low te
Fans
Qty Qty
m3/h
4 4500 8
3 17000 6
1 55000 11
2 70000 8
1 140000 9
3
1
10
8
9
Secondary air filters on low temperature systems shall be replaceable bag filter 90% efficiency
% efficiency