Total loads

without
N Layout Building Zone Split qty Floor split type
ventilation only
running(W)
25 Central control building 26751 2 Floor Standing Unit MFX60CSHNAW / MKX60CSSHIW
5970 1 Floor Standing Unit 2.0 Tr- ZT024ZXCV1
1
14126 2 Floor Standing Unit 2.0 Tr- ZT024ZXCV1
2614 1 Floor Standing Unit 2.0 Tr- ZT024ZXCV1
3 12565 1 Floor Standing Unit MFX60CSHNAW / MKX60CSSHIW
39 Elctrical room WTP 15216 3 Floor Standing Unit 2.0 Tr- ZT024ZXCV1
2
10156 1 Floor Standing Unit MFX48CSHNAW / MKX48CSSHIW
14 Electrical room compressed gas 33312 3 Floor Standing Unit MFX48CSHNAW / MKX48CSSHIW
1 50309 4 Floor Standing Unit MFX48CSHNAW / MKX48CSSHIW
25303 2 Floor Standing Unit MFX60CSHNAW / MKX60CSSHIW
9A Gas turbine 12200 1 Floor Standing Unit MFX60CSHNAW / MKX60CSSHIW
73215 6 Floor Standing Unit MFX60CSHNAW / MKX60CSSHIW
1
51771 4 Floor Standing Unit MFX60CSHNAW / MKX60CSSHIW
1163 1 Floor Standing Unit 2.0 Tr- ZT024ZXCV1
2 17337 3 Floor Standing Unit 2.0 Tr- ZT024ZXCV1
26 Common electrical building 11467 1 Floor Standing Unit MFX48CSHNAW / MKX48CSSHIW
1 4591 1 Floor Standing Unit 2.0 Tr- ZT024ZXCV1
48415 4 Floor Standing Unit MFX60CSHNAW / MKX60CSSHIW
13092 1 Floor Standing Unit MFX60CSHNAW / MKX60CSSHIW
2
12659 1 Floor Standing Unit MFX60CSHNAW / MKX60CSSHIW
58A ASL Electrical Building 10648 1 Floor Standing Unit MFX48CSHNAW / MKX48CSSHIW
1
45698 4 Floor Standing Unit MFX48CSHNAW / MKX48CSSHIW
12 BSDG Electrical building 35709 3 Floor Standing Unit MFX48CSHNAW / MKX48CSSHIW
1
2172 1 Floor Standing Unit 2.0 Tr- ZT024ZXCV1
21 Nitrogen generation and storage 1 72654 6 Floor Standing Unit MFX48CSHNAW / MKX48CSSHIW
59B Unloading pump electrical building 12657 1 Floor Standing Unit MFX60CSHNAW / MKX60CSSHIW
1
7037 1 Floor Standing Unit 2.0 Tr- ZT024ZXCV1
67 ASL Treatment Shelter 1 45100 4 Floor Standing Unit MFX48CSHNAW / MKX48CSSHIW
56 Fuel unloading gate house 1 4982 1 Floor Standing Unit 2.0 Tr- ZT024ZXCV1

* The necessary pressures have been included for the impulsion and return fans of 16 Floor Standing Unit 2.0 Tr- ZT024ZXCV1
Note: ASAP: Pending revision by the engineering department 27 Floor Standing Unit MFX48CSHNAW / MKX48CSSHIW
22 Floor Standing Unit MFX60CSHNAW / MKX60CSSHIW
N Layout Building Zone

25 Central control building

3
39 Elctrical room WTP
2

14 Electrical room compressed gas


1

9A Gas turbine

2
26 Common electrical building
1

58A ASL Electrical Building


1

12 BSDG Electrical building


1

21 Nitrogen generation and storage 1


59B Unloading pump electrical building
1

67 ASL Treatment Shelter 1


56 Fuel unloading gate house 1

* The necessary pressures have been included for the impulsion and return fans of
Note: ASAP: Pending revision by the engineering department
N Layout Building Zone

25 Central control building

3
39 Elctrical room WTP
2

14 Electrical room compressed gas


1

9A Gas turbine

2
26 Common electrical building
1

58A ASL Electrical Building


1

12 BSDG Electrical building


1

21 Nitrogen generation and storage 1


59B Unloading pump electrical building
1

67 ASL Treatment Shelter 1


56 Fuel unloading gate house 1

* The necessary pressures have been included for the impulsion and return fans of
Note: ASAP: Pending revision by the engineering department
Ambient
N Layout Building ID
extraction

14 Electrical room compressed gas F3 normal


9A Gas turbine F4 normal
59B Oil unloading pumps shelter F3 normal
26 Common electrical building F6 normal
58A ASL Electrical Building F2 normal
12 BSDG Electrical building F2 normal
21 Nitrogen generation and storage F1 normal
52 Maintenance and Workshop Building F1 normal
F1 normal
Warehouse Building & Offices (Phase 1)
71B F2 normal
Warehouse Building & Offices (Phase 2) F2 normal
40 Fire Pump House F1 normal
12 Black start diesel generator building F1 normal
35 Compressed Air Building F1 normal
59A Oil unloading pumps shelter F1 normal
66 ASL Forwarding pumps shelter F1 normal
67 ASL Treatment shelter F2 normal
ASL pit B1 chemical

DFO pit B1 chemical

12 BSDG compressors building F1 normal


F1 normal
73 GT & ST building
F2 normal

* According to GEMSS-M-33
** According to GEMSS-M-27, Include a special motor driven valve for releasing the dust out of
Temperature qty Unit
Redunda
Filters type service tempo capacity
ncy
(C) ral* (m/h)

Inertial filters with bleed fan, bag filter * 50 1 N+1 1200.00


Inertial filters with bleed fan, bag filter * 50 1 N+1 1800.06
Inertial filters with bleed fan, bag filter * 50 1 N+1 1059.48
Inertial filters with bleed fan, bag filter * 50 1 N+1 12083.00
Inertial filters with bleed fan, bag filter * 50 1 N+1 3979.00
Inertial filters with bleed fan, bag filter * 50 1 N+1 3168.00
Inertial filters with bleed fan, bag filter * 50 1 N+1 6400.00
Inertial filters with bleed fan, bag filter * 50 1 N+1 51582
Inertial filters with bleed fan, bag filter * 50 2 N+1 47484
Inertial filters with bleed fan, bag filter * 50 3 N+1 49567
Inertial filters with bleed fan, bag filter * 50 3 N+1 49184
Inertial filters with bleed fan, bag filter * 50 1 N+1 47,940
Inertial filters with bleed fan, bag filter * 50 1 N+1 31,589
Inertial filters with bleed fan, bag filter * 50 1 N+1 15,900
Inertial filters with bleed fan, bag filter * 50 1 N+1 11,024
Inertial filters with bleed fan, bag filter * 50 1 N+1 15,493
Inertial filters with bleed fan, bag filter * 50 1 N+1 4,414
Discharges shall be fitted with separators
50 1 N+1 2,220
Inertial filters with bleed fan and bag filter *
Discharges shall be fitted with separators
50 1 N+1 2,220
Inertial filters with bleed fan and bag filter *
Inertial filters with bleed fan, bag filter * 50 1 2x100% 16683
Inertial filters with bleed fan, bag filter * 50 9 140000
N+1
Inertial filters with bleed fan, bag filter * 50 8 70000

lve for releasing the dust out of the collector and a collecting drum with a minimum volume of 1m3, Inertial
BAG Filter box BAG Filter box
Sound Pressure
section air section air
power necesary ATEX VFD
fresh unit fresh unit
(dBA) (Pa)

- 285.96 - No 775x675 775x675


- 200.77 No 775x675 980x775
- 158 No 1385x1080 1080x1080
- 107 No 1385x1385 1385x1080
- 203 No 980x775 1385x1385
- 144 No 980x775 1690x1385
- 83.474 No 1080x1080 1995x1995
- 300 - No 2605x2605 2605x2605
- 300 - No 2605x2605 3520x2910
- 300 - No 2605x2605 4450x3830
- 300 - No 2605x2605
- 296 - Yes 2605x2605
- 268 - No 1995x1995
- 271 - No 1690x1385
- 280 - No 1385x1080
- 278 - No 1690x1385
- 261 - No 980x775

- 98 x No 775x675

- 98 x No 775x675
- 311 - No 1690x1385
- 150 - No 4450x3830
- 150 - No 3520x2910

ume of 1m3, Inertial type sand filters, permanent metal panel washable type, Secondary air filters on low te
Fans
Qty Qty
m3/h

4 4500 8
3 17000 6
1 55000 11
2 70000 8
1 140000 9
3
1
10
8
9

Secondary air filters on low temperature systems shall be replaceable bag filter 90% efficiency
% efficiency