PowerLogic Ethernet Gateway EGX100

User Guide

63230-319-204B1
08/2012
Safety information

Important information
Read these instructions carefully and look at the equipment to become familiar with
the device before trying to install, operate, service or maintain it. The following
special messages may appear throughout this bulletin or on the equipment to warn
of potential hazards or to call attention to information that clarifies or simplifies a
procedure.

The addition of either symbol to a Danger or Warning safety label indicates that
an electrical hazard exists which will result in personal injury if the instructions are
not followed.

This is the safety alert symbol. It is used to alert you to potential personal injury
hazards. Obey all safety messages that follow this symbol to avoid possible injury
or death.

DANGER indicates an imminently hazardous situation which, if not avoided, will result in
death or serious injury.

WARNING indicates a potentially hazardous situation which, if not avoided, can result in
death or serious injury.

CAUTION indicates a potentially hazardous situation which, if not avoided, can result in
minor or moderate injury.

NOTICE is used to address practices not related to physical injury. The safety alert symbol
shall not be used with this signal word.

Please note
Electrical equipment should be installed, operated, serviced, and maintained only
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.

A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.
Notices

FCC Part 15 notice


This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates, uses, and can
radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his
own expense. The Ringer Equivalence Number (REN) for the Meter_variable
optional internal modem is 0.6. Connection to the Meter_variable internal modem
should be made via an FCC Part 68 compliant telephone cord (not supplied). The
Meter_variable cannot be used on a public coin phone service or party line
services.This Class A digital apparatus complies with Canadian ICES-003.
63230-319-204B1 PowerLogic Ethernet Gateway EGX100
08/2012 Table of Contents

Table of Contents
Introduction .................................................................................................................... 1
Supported Ethernet Protocols .......................................................................................... 1
Hardware .......................................................................................................................... 1
Additional Resources ....................................................................................................... 2
Accessing the EGX Over a Network ............................................................................. 2
Logging in to the EGX ...................................................................................................... 2
Logging Out ...................................................................................................................... 2
EGX User Interface Overview ........................................................................................ 3
Setup ............................................................................................................................... 3
Ethernet and TCP/IP Settings .......................................................................................... 3
Duplicate IP Address Detection .................................................................................... 4
Serial Port ......................................................................................................................... 5
Device List ........................................................................................................................ 6
Master Mode Device List Setup .................................................................................... 6
Slave Mode Device List Setup ...................................................................................... 7
User Accounts .................................................................................................................. 8
Web Page Access ............................................................................................................ 8
Modbus TCP/IP Filtering .................................................................................................. 9
SNMP Parameters ......................................................................................................... 10
System Access Point ...................................................................................................... 11
Diagnostics ................................................................................................................... 12
Statistics ......................................................................................................................... 12
Interpreting Statistics .................................................................................................. 13
Read Device Registers ................................................................................................... 14
Firmware ....................................................................................................................... 15
Finding the Firmware Version ........................................................................................ 15
Getting New Firmware .................................................................................................... 15
Updating the Firmware File ............................................................................................ 16
Index ............................................................................................................................... 17

2006-2012 Schneider Electric All Rights Reserved i


PowerLogic Ethernet Gateway EGX100 63230-319-204B1
Table of Contents 08/2012

ii 2006-2012 Schneider Electric All Rights Reserved


63230-319-204B1 PowerLogic Ethernet Gateway EGX100
08/2012 Introduction

Introduction
This manual is to be used with a PowerLogic EGX100 with firmware version 3.0 or higher.
For installation information, see the installation guide.
The EGX100 is a communications device that provides connectivity between Ethernet
(Modbus TCP/IP) and serial line devices, allowing Modbus TCP/IP clients to access
information from serial slave devices. It also allows serial master devices to access
information from slave devices distributed across an Ethernet network.

Supported Ethernet Protocols


The EGX supports the following Ethernet protocols:
Modbus TCP/IP: Modbus TCP/IP is a combination of the Modbus protocol, which
provides master-slave communication between devices, and TCP/IP, which provides
communications over an Ethernet connection. Modbus TCP/IP is used to exchange data
between the EGX and other compatible Modbus TCP/IP devices via TCP port 502.
Hypertext Transfer Protocol (HTTP): HTTP is a network protocol that handles the
delivery of files and data on the World Wide Web. It provides web server functionality via
TCP port 80. Remote configuration of the EGX and the viewing of diagnostic data is
possible using a web browser.
File Transfer Protocol (FTP): FTP is a network protocol that provides the ability to
transfer files over the Internet from one computer to another. FTP is used to transfer
firmware updates to the EGX via TCP port 21.
Simple Network Management Protocol (SNMP): Based on MIB2 format, SNMP
provides the ability to store and send identifying and diagnostic information used for
network management purposes via UDP port 161.
Address Resolution Protocol (ARP): ARP is used to convert IP addresses to Ethernet
addresses. ARP requests are sent by the EGX to determine if its address is a duplicate
IP address (see Duplicate IP Address Detection on page 4).

Hardware

RJ45 Ethernet port

Control power

Power and
Status LED

RS485 serial port

LEDs for Ethernet


and serial
communications

Bias, termination,
Reset and 2-wire/4-wire
button jumper switches

RS232 serial port


(RJ45 connector)

1
2006-2012 Schneider Electric. All Rights Reserved.
PowerLogic Ethernet Gateway EGX100 63230-319-204B1
Accessing the EGX Over a Network 08/2012

Additional Resources
Documentation: Go to www.powerlogic.com and select your country. Select Library >
PowerLogic Products > Communications > EGX100 Gateway, and then click the document
you want to download.
NOTE: If you selected a country other than the United States, follow the country-specific
website navigation to get the EGX documentation.
Firmware: See Firmware on page 15 to learn where to download firmware updates and
how to install new firmware.

Accessing the EGX Over a Network


After you set up the Ethernet parameters (see the installation guide), you can access the
EGX over an Ethernet LAN using Internet Explorer 6.0 or higher.

Logging in to the EGX

Action Result
1. Launch Internet Explorer 6.0 or higher. Opens Internet Explorer.
2. In the Address text box, type the address of your Opens the Login dialog box.
EGX (169.254.0.10 is the default), then press Enter.
3. Type your user name (Administrator is the default) Enters the user name and password, then opens the EGX
and password (Gateway is the default) into the text home page.
boxes, then click OK.
4. Click Setup to access the EGX setup page, or click Opens the Setup or Diagnostics pages.
Diagnostics to access the EGX diagnostics page.

Figure 1: EGX Home Page

Menu
bar

Logging Out
We recommend logging out whenever you do not need access to the EGX.
To log out of the EGX configuration session, click Logout to end your session.

2006-2012 Schneider Electric. All Rights Reserved.


2
63230-319-204B1 PowerLogic Ethernet Gateway EGX100
08/2012 EGX User Interface Overview

EGX User Interface Overview


The EGX ships with eight pre-installed web pages used for EGX setup and configuration.
See Table 1 for a description of each web page.

Table 1: EGX static web pages

See
EGX Web Page Description
Page
Setup

Ethernet & TCP/IP Configure Ethernet and TCP/IP communication settings. 3


Serial Port Set up or change serial communication parameters. 5
Device List Identify serial devices on the daisy chain. 6
User Accounts1 Create and edit groups and users. 8
Web Page Access1 Select web page access rights for each user group. 8
Modbus TCP/IP Filtering1 Set up which IP addresses can access the EGX through Modbus TCP/IP. 9
SNMP Parameters1 Enable and configure the Simple Network Management Protocol (SNMP), 10
which allows the EGX to identify itself to network devices requesting SNMP
data.
System Access Point1 Allow the EGX100 to multicast its existence to any EGX300 connected to the 11
network.

Diagnostics

Statistics Displays diagnostic data used to troubleshoot network problems. This page 12
also contains information about your specific EGX, including the serial
number, manufacturing date, and Media Access Control (MAC) address.
Read Device Registers Allows EGX administrators to read register data from a serial device 14
connected to the EGX.
1
Accessible by administrator only

Setup
To access the Setup web page links, click Setup on the EGX menu bar.

Ethernet and TCP/IP Settings

Action Result
1. From the Setup page, click Ethernet & TCP/IP. Opens the Ethernet & TCP/IP page.
2. Select your frame format and media type. Contact Selects the frame format and media type.
your network administrator if you do not know.
3. Enter your IP address, subnet mask, and default Enters the Ethernet parameters for the EGX.
gateway address assigned to your EGX by your NOTE: If you enter an IP address that is used by another
network administrator. device, you will be prompted to select a new IP address.
See Duplicate IP Address Detection on page 4.
4. Click Apply. Updates the EGX Ethernet and TCP/IP settings.
* See Table 2 on page 4 for a list of options.

NOTE: After making changes to the Ethernet parameters and clicking Apply, the EGX will
reboot.

3
2006-2012 Schneider Electric. All Rights Reserved.
PowerLogic Ethernet Gateway EGX100 63230-319-204B1
Setup 08/2012

Figure 2: Ethernet & TCP/IP Page

Table 2: EGX Ethernet and TCP/IP Settings

Option Description Setting


Frame Format Used to select the format for data sent over an Ethernet II, 802.3 SNAP
Ethernet connection. Default: Ethernet II
Media Type Used to define the physical Ethernet connection or 10T/100Tx Auto
media type. 10BaseT-HD
10BaseT-FD
100BaseTX-HD
100BaseTX-FD
Default: 10T/100Tx Auto
IP Address Used to enter the static IP address of the EGX. Default: 169.254.0.10
Subnet Mask Used to enter the Ethernet IP subnet mask address of Default: 255.255.0.0
your network.
Default Gateway Used to enter the gateway (router) IP address used Default: 0.0.0.0
for wide area network (WAN) communications.

Duplicate IP Address Detection


While connected to your network, the EGX publishes its IP address. To avoid any duplicate
IP address conflicts, the EGX uses the Address Resolution Protocol (ARP) to see if any
other device on your network is using the same IP address. Table 3 below explains how the
EGX handles a duplicate IP address when it is detected.

Table 3: Duplicate IP Detection Scenarios

Scenario Duplicate IP Detected Power/Status LED

Boot Process / Power Restore Reverts to the default EGX IP address, subnet Four blinks, pause pattern
mask, and gateway address. ARP requests
Ethernet Link Detected
are sent every 15 seconds until the IP address
is available. When the IP address becomes
available, the EGX will use it.
Manual Address Change EGX keeps its previous IP address and
displays a message indicating that the IP
address is already in use by another device.
Receives an ARP request Reverts to the default EGX IP address, subnet Four blinks, pause pattern
mask, and gateway address if a connected
device sends four ARP requests for the EGXs
IP address. The EGX will send ARP requests
every 15 seconds until the IP address is
available again. When the IP address
becomes available, the EGX will use it.

2006-2012 Schneider Electric. All Rights Reserved.


4
63230-319-204B1 PowerLogic Ethernet Gateway EGX100
08/2012 Setup

Serial Port

Action Result
1. From the Setup page, click Serial Port. Opens the Serial Port page.
2. Select your mode, physical interface, transmission Selects the serial port options.
mode, baud rate, parity, and response timeout (see
Table 4 on page 5).
3. If you select Slave mode, enter the IP addresses for Enters the IP addresses of the remote devices.
the remotely connected devices (see Table 4 on page
5).
4. Click Apply. Updates the EGX Serial Port settings.

Figure 3: Serial Port Page

Table 4: Serial Port Settings

Option Description Setting


Mode Used to select how the COM port on the EGX is Master, Slave
utilized (master or slave). Default: Master
NOTE: When the Mode is changed, the EGX
reboots.
Physical Interface Used to select how the EGX serial port is physically RS485 4-wire, RS485 2-wire, or
wired. RS232
Default: RS485 2-wire
Transmission Mode Used to select how data is transmitted over a serial Master mode: Automatic, Modbus
connection. ASCII
Slave mode: Modbus RTU, Modbus
ASCII
Default:
Master mode: Automatic
Slave mode: Modbus RTU

NOTE: Automatic mode allows you to


communicate to Modbus RTU, Jbus,
and PowerLogic (SY/MAX) slave
devices on the same daisy chain.
Baud Rate Used to select the data transmission speed over a 2400, 4800, 9600, 19200, 38400,
serial connection. 56000*, 57600*
Default: 19200
Parity Used to select if data is checked for accuracy using a Even, Odd, None
parity bit. Default: Even
Response Timeout Used to select how long the EGX will wait to receive 0.1 to 10 seconds
a response from a serial device. Default: 3 seconds
Remote Modbus Used to define a list of Modbus TCP/IP addresses for
TCP/IP Connections the EGX to use during slave mode communications.
(Slave mode only)
* Available only if the physical interface and transmission mode is RS232/Modbus ASCII.

5
2006-2012 Schneider Electric. All Rights Reserved.
PowerLogic Ethernet Gateway EGX100 63230-319-204B1
Setup 08/2012

Device List
Before you begin, keep in mind the following:
For master mode usage of the COM port:
Modbus RTU/Jbus devices do not have to be defined in the Device List, but it helps you
manage your system.
PowerLogic protocol (SY/MAX) devices must be defined in the Device List.
NOTE: Do not use serial slave addresses 1 or 16 in Automatic transmission mode on a daisy
chain with mixed protocols (for example, a single daisy chain with some devices using
PowerLogic protocol and others using Modbus RTU/Jbus protocol).

Master Mode Device List Setup


Figure 4: Master Mode Topology

Ethernet
Connection

EGX in
master
mode
RS485 connection Up to 128 serial
slave devices
using repeaters

Serial Slave Devices

If you selected Master mode on the Serial Port page, follow the steps below to set up the
device list:

Action Result
1. From the Setup page, click Device List. Opens the Device List page.
2. Select the number of viewable devices (1 to 128), Selects the number of viewable locations that can be used
then click Apply. to define serial slave devices connected to the EGX.
3. In the Local ID text box, type the local ID (address) of Enters the local address of the device.
the serial slave device.
4. Select the Protocol. Selects the protocol of the connected device.
5. Repeat steps 3 and 4 until all of the devices are Enters all of the connected devices.
entered.
6. Click Apply. Updates the Device List settings.

Figure 5: Device List Page in Master Mode

2006-2012 Schneider Electric. All Rights Reserved.


6
63230-319-204B1 PowerLogic Ethernet Gateway EGX100
08/2012 Setup

Slave Mode Device List Setup


Serial port slave mode allows serial Modbus master devices to access information from
serial slave devices across a TCP/IP network. Figure 6 below illustrates how the devices are
connected using the device list settings in Figure 7.

Figure 6: Slave Mode Topology


Ethernet
Connection Up to 16 remote IP connections
with up to 128 serial slave devices
are possible
EGX in
slave mode
EGX in EGX in
master mode master mode
IP address: IP address:
169.254.0.28 169.254.0.75

RS232 or RS485
RS485 RS485 connection
connection connection

2 5 2 3 4 5 6 7
Serial Slave Devices Serial Slave Devices

If you selected Slave mode on the Serial Port page, follow the steps below to set up the
device list:

Action Result
1. From the Setup page, click Device List. Opens the Device List page.
2. Select the number of viewable devices (1 to 128), Selects the number of viewable locations that can be used
then click Apply. to define remote Modbus TCP/IP devices.
3. Select the Connection. Selects the Modbus TCP/IP address to associate with the
remote ID.
4. In the Local ID text box, type the local ID (address) of Enters the address of the device that the local Modbus
the serial slave device. master device will use to access the remote device.
5. In the Remote ID text box, type the remote ID Enters the serial slave address of the remotely connected
(address) of the serial slave device. device.

6. Repeat steps 3 through 5 until all of the devices are Enters all of the mapping information for the EGX to
entered. communicate to the remote devices.
7. Click Apply. Updates the Device List settings.

Figure 7: Device List Page in Slave Mode

7
2006-2012 Schneider Electric. All Rights Reserved.
PowerLogic Ethernet Gateway EGX100 63230-319-204B1
Setup 08/2012

User Accounts
EGX users are assigned user names and passwords. Each user belongs to a group, and
each group has access rights to the EGX Web pages assigned by the EGX administrator.
NOTE: There are two default user accounts: Administrator (password is Gateway) and
Guest (password is Guest).

Action Result
1. From the Setup page, click User Accounts. Opens the User Accounts page.
2. If you want to change a group name, type a new Enters a new group name.
name in one of the Groups text boxes (the
Administrator group name cannot be changed).
3. In the Users section, enter a Name (1 to 24 Enters the name and password for a user.
characters) and Password (0 to 12 characters) for a
new user.
NOTE: User names and passwords are
case-sensitive and can contain only alphanumeric
characters.
4. Select a group and the default language for the new Selects the group and language for a user.
user.
5. Repeat steps 3 and 4 for each additional user you Continues adding users.
want to add.
6. Click Apply. Saves all of the user account settings.

Table 5: EGX accounts and passwords

Account Default Password


Administrator Gateway
Guest Guest
User-defined accounts (up to 11 accounts possible) No default Password is user-defined

Figure 8: User Accounts Page

Web Page Access

Action Result
1. From the Setup page, click Web Page Access. Opens the Web Page Access page.
2. In the Ethernet & TCP/IP row, select the access level See Table 6 below for an explanation of access levels for
(None, Read-only, or Full) that each user group has each group.
for the Ethernet & TCP/IP web page.

2006-2012 Schneider Electric. All Rights Reserved.


8
63230-319-204B1 PowerLogic Ethernet Gateway EGX100
08/2012 Setup

Action Result
3. To allow Guest access to the web page, select Read- Allows the default Guest group to access the web page.
only under the Guest column.
NOTE: If the Guest group is Read-only, other groups
may only be set to Read-only or Full.
4. Repeat steps 2 and 3 for the Serial Port, Device List, Selects the access level for each web page.
Statistics, and Read Device Registers rows.
5. Click Apply. Saves the password settings.

Table 6: Group Access

Group Access
Administrator Full access to all web pages
NOTE: We recommend that you change the default administrator password for system
security the first time you log in.
Guest Read-only access to selected web pages.
Three user-defined Choosing from the following options, the administrator assigns web page access for each
groups group. Access levels are as follows:
None: a group has no access to selected web page
Read-only: password grants a group read-only access to the selected web page
Full: a group has the same access as the Administrator group to the selected web page

Figure 9: Web Page Access Page

Modbus TCP/IP Filtering


This function allows the administrator to specify Modbus TCP/IP client devices that have or
do not have access to serial slave devices connected to the EGX.
NOTE: There is an anonymous Modbus TCP/IP address (***.***.***.***) that can be set to
Read-only or None. Setting it to Read-only allows any Modbus TCP/IP client not in the
filtered list to access serial slave devices with read-only access. Setting it to None blocks all
Modbus TCP/IP clients not in the filtered list.

Action Result
1. From the Setup page, click Modbus TCP/IP Opens the Modbus TCP/IP Filtering page.
Filtering.
2. Check Enable Filtering. Activates filtering.
3. In the IP address column, enter the Modbus TCP/IP Enters an IP address for a Modbus TCP/IP client that will
client address have access to the serial devices connected to the EGX.
4. In the Access Level column, select Read-only or Selects the access level for the corresponding IP address.
Full. When set to Read-only, only the following Modbus TCP/IP
function codes are allowed:
Decimal: 1, 2, 3, 4, 7, 8, 11, 12, 17, 20, 24, 43, 100
Hexadecimal: 01, 02, 03, 04, 07, 08, 0B, 0C, 11, 14, 18,
2B, 64
5. Repeat steps 3 and 4 to add more IP addresses. Continues adding IP addresses for filtering.
6. Click Apply. Saves the Modbus TCP/IP address filtering list.

9
2006-2012 Schneider Electric. All Rights Reserved.
PowerLogic Ethernet Gateway EGX100 63230-319-204B1
Setup 08/2012

Figure 10: Modbus TCP/IP Filtering Page

SNMP Parameters
The EGX supports SNMP, allowing a network administrator to remotely access an EGX with
an SNMP manager and view the networking status and diagnostics in the MIB2 format.

Action Result
1. From the Setup page, click SNMP Parameters. Opens the SNMP Parameters page.
2. Check Enable SNMP to turn ON the simple network Activates SNMP.
management protocol.
NOTE: If you uncheck Enable SNMP and click Apply,
the EGX will reboot and SNMP functionality will be
turned OFF.
3. Enter the system contact, system name, system Enters the SNMP system information and community
location, read-only community name, and the read- access names.
write community name.
4. Click Apply. Saves the SNMP settings.

Figure 11: SNMP Parameters Page

2006-2012 Schneider Electric. All Rights Reserved.


10
63230-319-204B1 PowerLogic Ethernet Gateway EGX100
08/2012 Setup

System Access Point


The System Access Point allows the EGX100 to multicast its existence to any EGX300
connected to the network. This feature is configured to run by default, with no need for
additional configuration.
Use the setup screen in Figure 12 on page 11 to enter the group IP address and related
information.

Action Result
1. From the Setup menu, click System Access Point. Opens the System Access Point window.
2. Select UDP port, group IP address, hello time, hold Selects the system access point settings.
time, multicast time-to-live and community. See
Table 7 for setting descriptions.
3. Click Apply. Applies settings to the EGX100.
NOTE: To return to default settings, click Default,
then Apply

Table 7: System Access Point Settings

Option Description Setting


Enabled When enabled, EGX300s can discover EGX100s with the Enabled, disabled
same group IP address. Default: Enabled
UDP Port Allows you to set the port number for the UDP port used by 1 to 65535
the System Access Point discovery. Default: 59
Group IP Address This field supports multicast or unicast addresses. Default: 224.0.1.2
Hello Time This is the period of time between Hello messages 1 to 65534 seconds
emitted by this EGX100 announcing its presence to other Default: 300 seconds
Schneider Electric System Access devices on the network.
Hold TIme This is the period of time that Hello messages sent by this 2 to 65535 seconds
EGX100 should be held by recipients before considering Default: 600 seconds
this EGX100 unavailable.
Multicast Time-to-Live Allows you to control how wide an area of the network will 1 to 255 router hops
be included to discover other devices. This is controlled by Default: 1
the number of times that the multicast is allowed to be
forwarded to others.
Community Devices in a group can be divided into communities. 0 to 65535
EGX300s can discover EGX100s with the same group IP Default: 0
address and community number.

Setting the community number to '0' allows an EGX300 to


discover all EGX100s with the same group IP address
without regard to the community setting.

Figure 12: System Access Point

11
2006-2012 Schneider Electric. All Rights Reserved.
PowerLogic Ethernet Gateway EGX100 63230-319-204B1
Diagnostics 08/2012

Diagnostics
To access the Diagnostics web page links, click Diagnostics on the EGX menu bar.

Statistics

Action Result
1. From the Diagnostics page, click Statistics. Opens the Statistics page (see Figure 13).
NOTE: The Statistics page displays data based on the
mode selected in Serial Port on page 5.
2. View the data. See Interpreting Statistics on page 13.
3. Click Reset. Resets the EGX cumulative diagnostic data to 0.

NOTE: This page will show accumulated readings since the EGX was last activated. If power
to the EGX is lost, all cumulative values reset to zero.

Figure 13: Statistics Page


Reading with Serial Port in MASTER MODE Reading with Serial Port in SLAVE MODE

2006-2012 Schneider Electric. All Rights Reserved.


12
63230-319-204B1 PowerLogic Ethernet Gateway EGX100
08/2012 Diagnostics

Interpreting Statistics

Statistic Description
Ethernet

Link Status A status string that represents the speed and duplex setting being used to
communicate with the linking partner.
Frames Transmitted OK A counter that increments each time a frame is successfully transmitted.
Collisions A counter that increments each time a frame is retransmitted due to collision
detection.
Excessive Collisions A counter that increments each time a frame is not able to be sent due to
reaching the maximum collision status based on the Truncated Binary
Exponential Backoff algorithm.
Frames Received OK A counter that increments each time a frame is successfully received.
CRC Errors A counter that increments each time a frame is received that has a
checksum/CRC that does not match what is calculated.
Alignment Errors A counter that increments each time a frame is received that has a
checksum/CRC error and does not end on an 8-bit frame boundary.
Frames Too Long A counter that increments each time a frame is received that is larger than the
allowed maximum size defined in the standards (frames larger than 1518
bytes).
Frames Too Short A counter that increments each time a frame is received that is smaller than
the allowed minimum size defined in the standards (frames smaller than 64
bytes).

Modbus TCP/IP

Frames Sent A counter that increments each time a frame is sent.


Frames Received A counter that increments each time a frame is received.
Protocol Errors A counter that increments each time an ill-formed message is received.
Active Connections1 A status value that represents the number of connections that are active at
the moment the diagnostics page is refreshed. A maximum of 32 connections
are supported. Clicking Active Connections opens a new window with a list of
all of the active client connections.
Accumulative Connections1 A counter that increments each time a connection is made to the EGX.
Maximum Connections1 A status value that represents the maximum number of connections that were
active at any given moment.
Inbound Read Messages1 A counter that increments each time a read request message is received.
Outbound Read Messages2 A counter that increments each time a read request message is sent.
Inbound Write Messages1 A counter that increments each time a write request message is received.
Outbound Write Messages2 A counter that increments each time a write request message is sent.
Inbound Reply Messages2 A counter that increments each time a reply message is received.
Outbound Reply Messages1 A counter that increments each time a reply message is sent.

Serial Port

Frames Sent A counter that increments each time a frame is sent.


Frames Received A counter that increments each time a frame is received.
CRC Errors A counter that increments each time a message is received that has a CRC
that does not match what is calculated. Typically the result of wiring issues.
Protocol Errors A counter that increments each time an ill-formed message is received.
Timeouts A counter that increments each time a request message is sent without
receiving a corresponding response message within the allowed time.
Timeouts are typically the result of configuration errors or a non-responsive
device.
Inbound Read Messages2 A counter that increments each time a read request message is received.
Outbound Read Messages1 A counter that increments each time a read request message is sent.
Inbound Write Messages2 A counter that increments each time a write request message is received.
Outbound Write Messages1 A counter that increments each time a write request message is sent.
1 Available when the serial port is in Master mode.
2
Available when the serial port is in Slave mode

13
2006-2012 Schneider Electric. All Rights Reserved.
PowerLogic Ethernet Gateway EGX100 63230-319-204B1
Diagnostics 08/2012

Statistic Description
Gateway Information

Firmware Version The firmware version that is installed on the EGX.


System Idle Time A percentage from 0% to 100% indicating the average processor time that is
not being used.
MAC Address The unique Ethernet hardware address of an EGX.
Serial Number The serial number of the EGX.
Model Number The EGX model number (100).
Hardware Version EGX hardware version.
Manufacture Date Date the EGX was manufactured.
1
Available when the serial port is in Master mode.
2
Available when the serial port is in Slave mode

Read Device Registers

Action Result
1. From the Diagnostics page, click Read Device Opens the Read Device Registers page.
Registers.
2. Enter the device ID, starting register number, and the Enters the values to begin reading registers for the
number of registers to read. specified device.
3. Select a data type. Selects the data type to display.
4. To change how the data is displayed in the Value Selects how the data values are displayed.
column, select Decimal, Hexadecimal, Binary, or
ASCII.
5. Click Read. Displays the requested data.

Table 8: EGX Read Device Register Settings

Option Description Default


Device ID The address of the device that registers are read. 1
Starting Register The first register to read. 1000
Number of Registers The number of registers to read (1 to 10). 10
Register column Lists the register numbers
Value column Lists the data stored for a register. Values retrieved depend
on the device connected to the EGX. Refer to the
documentation for the connected device for more information
about stored register values.
Data Type Select Holding Registers, Input Registers, Output Coils, Holding Registers
Input Coils, or Device ID to specify the values retrieved.
Decimal, Hexadecimal, Select an option to specify how the Value column data is Decimal
Binary, or ASCII options displayed.

2006-2012 Schneider Electric. All Rights Reserved.


14
63230-319-204B1 PowerLogic Ethernet Gateway EGX100
08/2012 Firmware

Figure 14: Read Device Registers Page

Firmware
Firmware on the EGX can be updated using File Transfer Protocol (FTP). Check
www.powerlogic.com or with your local sales representative for the latest firmware update.

Finding the Firmware Version

Action Result
1. Log into the EGX. Opens the EGX home page.
2. Locate the firmware version on the bottom-left corner Determines the firmware version of the EGX.
of the page.
NOTE: If you recently updated your firmware, press
F5 to refresh the web page and update the displayed
firmware number.
3. Alternatively, you can select Diagnostics > Also determines the firmware version of the EGX.
Statistics to find the firmware version in the Gateway
Information section.

Getting New Firmware

Action Result
1. Launch Internet Explorer, type www.powerlogic.com Opens the PowerLogic website.
in the Address Bar, then press Enter.
2. Select your country, then click Go. Opens the PowerLogic website for your country.
NOTE: If you selected the United States, continue to
Step 3. Otherwise, follow the country-specific website
navigation to get the EGX firmware.
3. Click Firmware Downloads > Products > Displays available EGX100 downloads.
PowerLogic Communications > EGX100.
4. Click the EGX100 Firmware link. Opens the EGX100 Firmware instructions page.
5. Click the Files tab, then the firmware file link Displays the file names, then opens the File Download
(eg#####.bin, where ##### is the firmware number). dialog box.
NOTE: You must log in to download firmware files. If
you do not have a user name and password, follow
the instructions on the website.
6. Click Save. Saves the firmware file.

15
2006-2012 Schneider Electric. All Rights Reserved.
PowerLogic Ethernet Gateway EGX100 63230-319-204B1
Firmware 08/2012

Updating the Firmware File

Action Result
1. Launch Internet Explorer, type ftp:// and the IP Opens the Log On As dialog box.
address of the EGX in the Address text box (for
example, ftp://169.254.0.10), then press Enter.
2. Type the user name Administrator and the Opens an FTP session with the EGX.
administrator password in the text boxes, then click
Log On.
3. Locate the saved firmware file on your computer, Copies the firmware file to the clipboard.
right-click on it it, then click Copy.
4. Right-click in the Internet Explorer window, then click Copies the firmware to the EGX, and the EGX reboots.
Paste.
NOTE: Instead of copying and pasting the firmware
file, you can drag-and-drop the firmware file into
Internet Explorer.
5. Click the Close button on the Internet Explorer Closes Internet Explorer and ends the FTP connection to
window. the EGX.
6. To verify that the firmware version was updated Verifies the updated firmware version.
successfully, follow the steps in Finding the Firmware
Version on page 15.

2006-2012 Schneider Electric. All Rights Reserved.


16
63230-319-204B1 PowerLogic Ethernet Gateway EGX100
08/2012 Index

Index

A setup 10
accessing the EGX over a network 2 U
additional resources 2
user accounts
D setup 8
user interface 3
device list
setup 6 W
master mode 6
web page access
slave mode 7
setup 8
device registers 14
reading 14
diagnostics 11
duplicate IP address detection 4

E
EGX
login 2
setup 3
user interface 3
Ethernet and TCP/IP settings 3
Ethernet protocols 1

F
firmware 15
finding the version 15
getting new 15
updating 15

H
hardware 1

I
introduction 1

L
logging in to the EGX 2
logging out 2

M
master mode device list setup 6
Modbus TCP/IP filtering
setup 9

N
network
accessing via 2

S
serial port
setup 5
slave mode device list setup 7
SNMP parameters
setup 10
statistics 12
interpreting 12
supported Ethernet protocols 1
system access point

2006-2012 Schneider Electric All Rights Reserved 17


PowerLogic Ethernet Gateway EGX100 63230-319-204B1
Index 08/2012

18 2006-2012 Schneider Electric All Rights Reserved


PowerLogic Ethernet Gateway EGX100
User Guide

PowerLogic is a trademark of Schneider Electric in France, the USA and other


countries. Other trademarks are the property of their respective owners.
Schneider Electric
35 rue Joseph Monier 63230-319-204B1 08/2012
92500 Rueil-Malmaison, France Replaces 63230-319-204A2 12/2008
www.schneider-electric.com 2006-2012 Schneider Electric All Rights Reserved.
Pasarela Ethernet EGX100 de PowerLogic
Manual del usuario

63230-319-204B1
08/2012
Informacin sobre seguridad

Informacin importante
Lea estas instrucciones atentamente y examine el equipo para familiarizarse con el
dispositivo antes de instalarlo, manipularlo, revisarlo o realizar el mantenimiento de
este. Los siguientes mensajes especiales pueden aparecer a lo largo de este
manual o en el equipo para advertir de posibles riesgos o remitirle a otras
informaciones que le ayudarn a aclarar o simplificar los procedimientos.

La adicin de uno de estos dos smbolos a una etiqueta de seguridad del tipo
Peligro o Advertencia indica la existencia de un riesgo de descarga elctrica
que ocasionar lesiones si no se siguen las instrucciones.

Este es el smbolo de alerta de seguridad. Sirve para alertar de posibles riesgos de


lesiones. Siga las recomendaciones de todos los mensajes de seguridad
precedidos por este smbolo para evitar posibles lesiones e incluso la muerte.

PELIGRO indica una situacin de riesgo inmediato que, si no se evita, causar la muerte
o lesiones graves.

ADVERTENCIA indica una situacin de riesgo potencial que, si no se evita, puede causar
la muerte o lesiones graves.

PRECAUCIN indica una situacin de riesgo potencial que, si no se evita, puede causar
lesiones moderadas o leves.

AVISO se emplea en la descripcin de prcticas que no pueden ocasionar lesiones. El


smbolo de alerta de seguridad no se utilizar con este trmino de advertencia.

Por favor, tenga en cuenta lo siguiente


Slo el personal cualificado puede instalar, manipular y revisar el equipo
electrnico as como realizar el mantenimiento de este. Schneider Electric
no asume ninguna responsabilidad de las consecuencias que se deriven de la
utilizacin de este manual.

Por cualificado se entiende la persona que cuenta con conocimientos y experiencia


relacionados con la fabricacin, la instalacin y el funcionamiento de equipos
elctricos y que, adems, ha recibido formacin en materia de seguridad al objeto
de reconocer y evitar cualquier riesgo.
Avisos

Aviso sobre la seccin 15 de la normativa de la FCC


Este equipo ha sido probado y cumple los lmites establecidos para los dispositivos
digitales Clase A, segn la seccin 15 de la normativa de la FCC (Comisin federal
de comunicaciones de los EE. UU.). Estos lmites se establecen para proporcionar
la proteccin adecuada contra interferencias que puedan daar el equipo cuando
este se utiliza en un entorno comercial. Este equipo genera, utiliza y puede emitir
energa de radiofrecuencia y, si no se instala y utiliza siguiendo las indicaciones del
manual de instrucciones, puede provocar interferencias que afecten a las radioco-
municaciones. Si se utiliza en una zona residencial, las interferencias podran
causar daos. En tal caso, el usuario es el responsable de corregir dichas
interferencias por su propia cuenta y riesgo. Este aparato digital Clase A cumple con
la normativa canadiense ICES-003 sobre equipos generadores de interferencias.
63230-319-204B1 Pasarela Ethernet EGX100 de PowerLogic
08/2012 ndice

ndice
Introduccin .................................................................................................................... 1
Protocolos de Ethernet compatibles ................................................................................. 1
Equipo fsico ..................................................................................................................... 1
Otros recursos .................................................................................................................. 2
Acceso a la EGX a travs de una red ........................................................................... 2
Inicio de sesin en la EGX ............................................................................................... 2
Desconexin del sistema ................................................................................................. 2
Descripcin general de la interfaz de usuario de la EGX ........................................... 3
Configuracin ................................................................................................................. 3
Configuracin de Ethernet y TCP/IP ................................................................................ 3
Deteccin de direcciones IP duplicadas ....................................................................... 4
Puerto serie ...................................................................................................................... 5
Lista de dispositivos de la EGX ........................................................................................ 6
Configuracin de la lista de dispositivos en modo Maestro .......................................... 6
Configuracin de la lista de dispositivos en modo Esclavo .......................................... 7
Cuentas de usuario .......................................................................................................... 8
Acceso a pginas web ..................................................................................................... 8
Filtrado de Modbus TCP/IP .............................................................................................. 9
Parmetros del SNMP .................................................................................................... 10
Punto de acceso del sistema ......................................................................................... 11
Diagnsticos ................................................................................................................. 12
Estadsticas .................................................................................................................... 12
Interpretacin de las estadsticas ............................................................................... 13
Lectura de registros de dispositivo ................................................................................. 14
Firmware ....................................................................................................................... 15
Identificacin de la versin del firmware ........................................................................ 15
Obtencin de firmware nuevo ........................................................................................ 15
Actualizacin del archivo de firmware ............................................................................ 16
ndice alfabtico ............................................................................................................ 17

2006-2012 Schneider Electric. Reservados todos los i


Pasarela Ethernet EGX100 de PowerLogic 63230-319-204B1
ndice 08/2012

ii 2006-2012 Schneider Electric. Reservados todos los derechos.


63230-319-204B1 Pasarela Ethernet EGX100 de PowerLogic
08/2012 Introduccin

Introduccin
Este manual debe utilizarse con una PowerLogic EGX100 que cuente con la versin del
firmware 3.0 o superior. Consulte el manual de instalacin para obtener informacin sobre
esta.
La pasarela EGX100 es un dispositivo de comunicacin que ofrece conectividad entre
Ethernet (Modbus TCP/IP) y dispositivos en lnea serie, con lo cual permite que los clientes
Modbus TCP/IP accedan a la informacin desde dispositivos esclavos en serie. Tambin
permite que los dispositivos maestros serie accedan a informacin desde dispositivos
esclavos distribuidos en una red Ethernet.

Protocolos de Ethernet compatibles


La EGX acepta los siguientes protocolos Ethernet:
Modbus TCP/IP: Se trata de una combinacin del protocolo Modbus, que proporciona
comunicacin maestro-esclavo entre dispositivos, y TCP/IP, que proporciona
comunicacin a travs de una conexin Ethernet. Sirve para intercambiar datos entre
la EGX y otros dispositivos compatibles con Modbus TCP/IP a travs del
puerto TCP 502.
Protocolo de transferencia de hipertexto (HTTP): Protocolo de red que realiza los
envos de archivos y datos en Internet Proporciona funcionalidad de servidor web por
medio del puerto TCP 80. Mediante un explorador web es posible configurar la EGX de
manera remota y visualizar los datos de diagnstico.
Protocolo de transferencia de archivos (FTP): Protocolo de red que ofrece la
capacidad de transferir archivos por Internet de un ordenador a otro. Sirve para transferir
las actualizaciones del firmware a la EGX por medio del puerto TCP 21.
Protocolo simple de administracin de redes (SNMP): Se basa en el formato MIB-II y
proporciona la capacidad de almacenar y enviar informacin de identificacin y
diagnstico utilizada en la red por razones de administracin por medio del
puerto UDP 161.
Protocolo de resolucin de direccin (ARP): Sirve para convertir las direcciones IP en
direcciones Ethernet. Las solicitudes de ARP se envan a travs de la EGX para
determinar si su direccin es el duplicado de una direccin IP (consulte Deteccin de
direcciones IP duplicadas en la pgina 4).
Equipo fsico
Puerto Ethernet RJ45

Alimentacin

LED de
alimentacin
y estado
Puerto serie RS485

LED para Ethernet


y comunicaciones
en serie
Interruptores
de puentes para
polaridad,
resistencia
Botn de de final de lnea
restablecim. y 2 hilos/4 hilos
Puerto
serie RS232
(conector RJ45)

2006-2012 Schneider Electric. Reservados todos los derechos. 1


Pasarela Ethernet EGX100 de PowerLogic 63230-319-204B1
Acceso a la EGX a travs de una red 08/2012

Otros recursos
Documentacin: Visite www.powerlogic.com y seleccione su pas. Seleccione Library >
PowerLogic Products > Communications > EGX100 Gateway (Biblioteca > Productos
PowerLogic > Comunicaciones > Pasarela EGX100) y haga clic en el documento que quiere
descargar.
NOTA: Si ha seleccionado un pas que no sea Estados Unidos, siga la navegacin del sitio
web especfico del pas para obtener la documentacin de la EGX.
Firmware: Consulte Firmware en la pgina 15 para saber de dnde bajar las
actualizaciones del firmware y cmo instalar el nuevo firmware.

Acceso a la EGX a travs de una red


Una vez que haya configurado los parmetros de Ethernet (consulte el manual de
instalacin), podr acceder a la EGX a travs de una LAN de Ethernet con Internet
Explorer 6.0 o superior.

Inicio de sesin en la EGX

Accin Resultado
1. Inicie Internet Explorer 6.0 o superior. Abre Internet Explorer.
2. En la barra de direcciones, escriba la direccin de Abre el cuadro de dilogo Iniciar sesin.
la EGX (la direccin predeterminada
es 169.254.0.10) y, a continuacin, pulse Intro.
3. Escriba su nombre de usuario (Administrator es el Introduce el nombre de usuario y la contrasea y, a
valor predeterminado) y la contrasea (Gateway es la continuacin, abre la pgina de inicio de la EGX.
predeterminada) en los cuadros de texto y despus
haga clic en Aceptar.
4. Haga clic en Configuracin o en Diagnsticos para Abre las pginas de configuracin o diagnstico.
acceder a la pgina de configuracin o de diagnstico
respectivamente de la EGX.

Figura 1: Pgina de inicio de la EGX

Barra de
mens

Desconexin del sistema


Le aconsejamos que se desconecte cuando no necesite acceder a la EGX.
Para salir de la sesin de configuracin de la EGX, haga clic en Desconexin y se cerrar
la sesin.

2 2006-2012 Schneider Electric. Reservados todos los


63230-319-204B1 Pasarela Ethernet EGX100 de PowerLogic
08/2012 Descripcin general de la interfaz de usuario de la EGX

Descripcin general de la interfaz de usuario de la EGX


La EGX se enva con 8 pginas web preinstaladas que se utilizan para la preparacin y
configuracin de la EGX. Consulte la Tabla 1 para ver una descripcin de cada pgina web.

Tabla 1: Pginas web estticas de la EGX

Pgina web de Consulte


Descripcin
la EGX la pgina
Configuracin

Ethernet y TCP/IP Configure los parmetros de las comunicaciones Ethernet y TCP/IP. 3


Puerto serie Configure o cambie los parmetros de las comunicaciones serie. 5
Lista de dispositivos de Identifique los dispositivos conectados en el bus de comunicaciones serie. 6
la EGX
Cuentas de usuario1 Cree y modifique grupos y usuarios. 8
Acceso a pgina Web1 Seleccione los derechos de acceso a las pginas web para cada grupo de 8
usuarios.
Filtrado de Configure las direcciones IP que podrn acceder a la EGX a travs de 9
Modbus TCP/IP1 Modbus TCP/IP.
Parmetros del SNMP1 Habilite y configure el Protocolo simple de administracin de redes (SNMP), 10
que permite que la EGX se identifique a otros dispositivos de red que solicitan
datos SNMP.
Punto de acceso del Permite que la EGX100 difunda su existencia a todas las pasarelas EGX300 11
sistema1 que estn conectadas a la red.

Diagnsticos

Estadsticas Muestra datos de diagnstico que se utilizan para resolver problemas de la 12


red. Esta pgina contiene tambin informacin acerca de la EGX especfica
del usuario, incluido el nmero de serie, la fecha de fabricacin y la direccin
de control de acceso de medios (MAC).
Lectura de registros de Permite que los administradores de la EGX lean datos de registro 14
dispositivo procedentes de dispositivos serie conectado a esta
1
Slo el administrador tiene acceso.

Configuracin
Para acceder a los vnculos de la pgina web Configuracin, haga clic en Configuracin en
la barra de mens de la EGX.

Configuracin de Ethernet y TCP/IP

Accin Resultado
1. En la pgina Configuracin, haga clic en Ethernet y Abre la pgina Ethernet y TCP/IP.
TCP/IP.
2. Seleccione el formato de trama y el tipo de medio. Si Selecciona el formato de trama y el tipo de medio.
no los conoce, pngase en contacto con el
administrador de la red.
3. Introduzca su direccin IP, la mscara de subred y la Introduce los parmetros de Ethernet para la EGX.
direccin predeter-minada de la pasarela asignadas a NOTA: Si introduce una direccin IP que ya est siendo
la EGX por el administrador de la red. utilizada por otro dispositivo, se le pedir que seleccione
una direccin IP diferente. Consulte Deteccin de
direcciones IP duplicadas en la pgina 4.
4. Haga clic en Aplicar. Actualiza la configuracin de Ethernet y TCP/IP de
la EGX.
* Consulte la Tabla 2 en la pgina 4 para ver una lista de opciones.

NOTA: Tras introducir los cambios en los parmetros de Ethernet y hacer clic en Aplicar,
la EGX se reiniciar.

2006-2012 Schneider Electric. Reservados todos los derechos. 3


Pasarela Ethernet EGX100 de PowerLogic 63230-319-204B1
Configuracin 08/2012

Figura 2: Pgina Ethernet y TCP/IP

Tabla 2: Configuracin de Ethernet y TCP/IP de la EGX

Opcin Descripcin Valor


Formato de trama Permite seleccionar el formato en el que se envan los Ethernet II, 802.3 SNAP
datos a travs de una conexin Ethernet. Predeterminado: Ethernet II
Tipo de medio Sirve para definir la conexin fsica a Ethernet o el 10T/100Tx Auto
tipo de medio. 10BaseT-HD
10BaseT-FD
100BaseTX-HD
100BaseTX-FD
Predeterminado: 10T/100Tx Auto
Direccin IP Sirve para introducir la direccin IP esttica de Valor predeterminado: 169.254.0.10
la EGX.
Mscara de subred Permite introducir la direccin de la mscara de Valor predeterminado: 255.255.0.0
subred de la red.
Pasarela Sirve para introducir la direccin IP de la pasarela Valor predeterminado: 0.0.0.0
predeterminada (router) que se usa en las comunicaciones con la red
de rea extendida (WAN).

Deteccin de direcciones IP duplicadas


Mientras est conectada a la red, la EGX publica su direccin IP. Para evitar conflictos de
direcciones IP duplicadas, la EGX utiliza el protocolo de resolucin de direcciones (ARP) al
objeto de determinar si algn otro dispositivo de la red utiliza la misma direccin IP. En la
Tabla 3 a continuacin se explica cmo trata la EGX las direcciones duplicadas al
detectarlas.

Tabla 3: Situaciones de deteccin de IP duplicadas

Situacin IP duplicada detectada LED de alimentacin/estado

Proceso de inicio/restableci- Vuelve a la direccin IP, la mscara de Patrn de 4 parpadeos y pausa


miento de alimentacin subred y la direccin de la pasarela
predeterminadas de la EGX. Las
Enlace de Ethernet detectado
solicitudes ARP se envan cada 15 segundos
hasta que la direccin IP queda disponible.
Cuando la direccin IP quede disponible,
la EGX la utilizar.
Cambio manual de la direccin La EGX mantiene su direccin IP anterior y
muestra un mensaje que indica que otro
dispositivo ya est empleando la direccin IP.
Recibe una solicitud ARP Vuelve a la direccin IP, la mscara de Patrn de 4 parpadeos y pausa
subred y la direccin de la pasarela
predeterminadas de la EGX si un dispositivo
conectado enva cuatro solicitudes ARP de la
direccin IP de la EGX. La EGX enviar
solicitudes ARP cada 15 segundos hasta que
la direccin IP vuelva a quedar disponible.
Cuando la direccin IP quede disponible,
la EGX la utilizar.

4 2006-2012 Schneider Electric. Reservados todos los


63230-319-204B1 Pasarela Ethernet EGX100 de PowerLogic
08/2012 Configuracin

Puerto serie

Accin Resultado
1. En la pgina Configuracin, haga clic en Puerto Abre la pgina Puerto serie.
serie.
2. Seleccione el modo, la interfaz fsica, el modo de Selecciona las opciones del puerto serie.
transmisin, la velocidad en baudios, la paridad y el
tiempo de espera de respuesta (consulte la Tabla 4
en la pgina 5).
3. Si selecciona el modo Esclavo, introduzca las Introduce las direcciones IP de los dispositivos remotos.
direcciones IP correspondientes a los dispositivos de
conexin remota (consulte la Tabla 4 en la pgina 5).
4. Haga clic en Aplicar. Actualiza la configuracin del puerto serie de la EGX.

Figura 3: Pgina Puerto serie

Tabla 4: Configuracin del puerto serie

Opcin Descripcin Valor


Modo Sirve para seleccionar el modo de uso del Maestro, Esclavo
puerto COM de la EGX (Maestro o Esclavo). Valor predeterminado: Maestro
NOTA: Cuando se cambia el valor de Modo, se
reinicia la EGX.
Interfaz fsica Sirve para seleccionar el modo de cableado fsico del RS485 4 hilos, RS485 2 hilos
puerto serie de la EGX. o RS232
Valor predeterminado:
RS485 2 hilos
Modo de transmisin Permite seleccionar el modo de transmitir datos en Modo Maestro: Automtico, Modbus
una conexin serie. ASCII
Modo Esclavo: Modbus RTU,
Modbus ASCII
Valor predeterminado:
Modo Maestro: Automtico
Modo Esclavo: Modbus RTU

NOTA: El modo Automtico le permite


comunicarse con dispositivos
esclavos Modbus RTU, Jbus y
PowerLogic (SY/MAX) en el mismo
bus de comunicaciones serie.

Velocidad en baudios Sirve para seleccionar la velocidad de transmisin de 2400, 4800, 9600, 19200, 38400,
datos en una conexin serie. 56000*, 57600*
Valor predeterminado: 19200
Paridad Sirve para seleccionar si se comprueba la precisin Par, Impar o Ninguna
de los datos con un bit de paridad. Valor predeterminado: Par
Tiempo de espera de Permite seleccionar el tiempo que esperar la EGX 0,1 a 10 segundos
respuesta para recibir respuesta de un dispositivo serie. Predeterminado: 3 segundos
Conexiones Define una lista de direcciones Modbus TCP/IP que
Modbus TCP/IP utilizar la EGX durante la comunicacin en modo
remotas (slo modo Esclavo.
Esclavo)
* Slo est disponible si la interfaz fsica y el modo de transmisin son RS232 y Modbus ASCII respectivamente.

2006-2012 Schneider Electric. Reservados todos los derechos. 5


Pasarela Ethernet EGX100 de PowerLogic 63230-319-204B1
Configuracin 08/2012

Lista de dispositivos de la EGX


Antes de comenzar, tenga en cuenta las consideraciones siguientes:
En relacin con el uso del modo Maestro del puerto COM:
No es obligatorio definir los dispositivos RTU/Jbus en la lista de dispositivos, pero le
ayudar a gestionar el sistema.
Los dispositivos con protocolo PowerLogic (SY/MAX) se deben definir en la lista de
dispositivos.
NOTA: No utilice las direcciones serie esclavas 1 o 16 en el modo de transmisin
Automtico en un bus de comunicaciones serie con protocolos mixtos (por ejemplo, una sola
conexin en bus de comunicaciones serie con algunos dispositivos que usen el protocolo
PowerLogic y otros que usen el protocolo Modbus RTU/Jbus).

Configuracin de la lista de dispositivos en modo Maestro


Figura 4: Topologa del modo Maestro

Conexin Ethernet

EGX en
modo
Maestro Hasta
Conexin RS485 128 dispositivos
esclavos en serie
con repetidores

Dispositivos esclavos en serie

Si seleccion el modo Maestro en la pgina Puerto serie, siga los pasos descritos a
continuacin para configurar la lista de dispositivos:

Accin Resultado
1. En la pgina Configuracin, haga clic en Lista de Abre la pgina Lista de dispositivos.
dispositivos.
2. Seleccione el nmero de dispositivos visualizables (1 a 128) Selecciona el nmero de ubicaciones visualizables
y, a continuacin, haga clic en Aplicar. que utilizar para definir los dispositivos esclavos
en serie conectados a la EGX.
3. En el cuadro de texto ID local, escriba el identificador local Introduce la direccin local del dispositivo.
(direccin) del dispositivo esclavo en serie.
4. Seleccione el protocolo. Selecciona el protocolo correspondiente al
dispositivo conectado.
5. Repita los pasos 3 y 4 hasta introducir todos los dispositivos. Introduce todos los dispositivos conectados.
6. Haga clic en Aplicar. Actualiza los valores de Lista de dispositivos.

Figura 5: Pgina Lista de dispositivos en modo Maestro

6 2006-2012 Schneider Electric. Reservados todos los


63230-319-204B1 Pasarela Ethernet EGX100 de PowerLogic
08/2012 Configuracin

Configuracin de la lista de dispositivos en modo Esclavo


El modo Esclavo del puerto serie permite que los dispositivos Modbus maestros en serie
accedan a la informacin de los dispositivos esclavos en serie en una red TCP/IP. La
Figura 6 a continuacin ilustra cmo se conectan los dispositivos a travs de los valores de
la lista de dispositivos de la Figura 7.
Figura 6: Topologa del modo Esclavo
Conexin Ethernet
Son posibles hasta 16 conexiones IP
remotas con un mximo de
128 dispositivos esclavos en serie.
EGX en modo
Esclavo
EGX en modo EGX en
Maestro modo
Maestro
Direccin IP:
169.254.0.28 Direccin IP:
169.254.0.75
Conexin RS232
Conexin RS485 Conexin RS485 o RS485

2 5 2 3 4 5 6 7
Dispositivos esclavos en serie Dispositivos esclavos en serie

Si seleccion el modo Esclavo en la pgina Puerto serie, siga los pasos descritos a
continuacin para configurar la lista de dispositivos:

Accin Resultado
1. En la pgina Configuracin, haga clic en Lista de Abre la pgina Lista de dispositivos.
dispositivos.
2. Seleccione el nmero de dispositivos visualizables Selecciona el nmero de ubicaciones visualizables que se
(1 a 128) y, a continuacin, haga clic en Aplicar. puede utilizar para definir los dispositivos Modbus TCP/IP
remotos.
3. Seleccione la conexin. Selecciona la direccin Modbus TCP/IP que se asocia
con el identificador remoto.
4. En el cuadro de texto ID local, escriba el identificador Introduce la direccin del dispositivo que utilizar el
local (direccin) del dispositivo esclavo en serie. dispositivo Modbus maestro local para acceder al
dispositivo remoto.
5. En el cuadro de texto ID remoto, escriba el Introduce la direccin esclava en serie del dispositivo de
identificador remoto (direccin) del dispositivo conexin remota.
esclavo en serie.
6. Repita los pasos 3 a 5 hasta introducir todos los Introduce toda la informacin de asignaciones de modo
dispositivos. que la EGX se comunique con los dispositivos remotos.
7. Haga clic en Aplicar. Actualiza los valores de Lista de dispositivos.

Figura 7: Pgina Lista de dispositivos en modo Esclavo

2006-2012 Schneider Electric. Reservados todos los derechos. 7


Pasarela Ethernet EGX100 de PowerLogic 63230-319-204B1
Configuracin 08/2012

Cuentas de usuario
A los usuarios de la EGX se les asignan nombres de usuario y contraseas. Cada usuario
pertenece a un grupo, cuyos derechos de acceso a las pginas web de la EGX los asigna el
administrador de la EGX.
NOTA: Existen dos cuentas de usuario predeterminadas: Administrator (Administrador),
cuya contrasea es Gateway, y Guest (Invitado), cuya contrasea es Guest.

Accin Resultado
1. En la pgina Configuracin, haga clic en Cuentas de Abre la pgina Cuentas de usuario.
usuario.
2. Si desea cambiar el nombre de un grupo, escriba el Introduce un nuevo nombre de grupo.
nuevo nombre en uno de los cuadros de texto
Grupos (no se puede cambiar el nombre del grupo
Administradores).
3. En la seccin Usuarios, introduzca un nombre Introduce el nombre y la contrasea de un usuario.
(1 a 24 caracteres) y contrasea (0 a 12 caracteres)
para el nuevo usuario.
NOTA: Los nombres de usuario y las contraseas
respetan maysculas y minsculas y slo pueden
contener caracteres alfanumricos.
4. Seleccione un grupo y el idioma predeterminado Selecciona el grupo y el idioma para un usuario.
aplicables al nuevo usuario.
5. Repita los pasos 3 y 4 por cada usuario adicional que Contina aadiendo usuarios.
desee agregar.
6. Haga clic en Aplicar. Guarda toda la configuracin de las cuentas de usuario.

Tabla 5: Cuentas y contraseas de la EGX

Cuenta Contrasea predeterminada


Administrator Gateway
Guest Guest
Cuentas definidas por el usuario (hasta 11 cuentas) Sin valor predeterminado. La contrasea la define
el usuario.

Figura 8: Pgina Cuentas de usuario

Acceso a pginas web


Accin Resultado
1. En la pgina Configuracin, haga clic en Acceso a pgina Web. Abre la pgina Acceso a pgina Web.
2. En la fila Ethernet y TCP/IP, seleccione el nivel de acceso Consulte la Tabla 6 a continuacin para ver
(Ninguna, Slo lectura o Completo) que tiene cada grupo de una explicacin de los niveles de acceso
usuarios para la pgina web Ethernet y TCP/IP. correspondientes a cada grupo.

8 2006-2012 Schneider Electric. Reservados todos los


63230-319-204B1 Pasarela Ethernet EGX100 de PowerLogic
08/2012 Configuracin

Accin Resultado
3. Para permitir el acceso de invitados a la pgina web, seleccione Permite que el grupo Guest predeterminado
Slo lectura en la columna Guest. acceda a la pgina web.
NOTA: Si el grupo Guest es de slo lectura, otros grupos se
pueden configurar como Slo lectura o Completo.
4. Repita los pasos 2 y 3 para las filas Puerto serie, Lista de Selecciona el nivel de acceso para cada
dispositivos, Estadsticas y Lectura de registros de dispositivo. pgina web.
5. Haga clic en Aplicar. Guarda los valores de las contraseas.

Tabla 6: Acceso de grupo

Grupo Acceso
Administrator Acceso completo a todas las pginas web.
NOTA: Para garantizar la seguridad del sistema, le recomendamos que cambie la
contrasea predeterminada del administrador la primera vez que se conecte al sistema.
Guest Acceso de slo lectura a las pginas web seleccionadas.
Tres grupos definidos Al elegir entre las siguientes opciones, el administrador asigna el acceso a las pginas web
por el usuario para cada grupo. Los niveles de acceso son los siguientes:
Ninguna: el grupo no tiene acceso a la pgina web seleccionada.
Slo lectura: la contrasea le concede al grupo acceso de slo lectura a la pgina web
seleccionada.
Completo: el grupo tiene el mismo acceso que el grupo de administradores a la pgina
web seleccionada.

Figura 9: Pgina Acceso a pgina Web

Filtrado de Modbus TCP/IP


Esta funcin permite al administrador asignar o denegar el acceso que los clientes
Modbus TCP/IP tienen a los dispositivos esclavos en serie conectados a la EGX.
NOTA: Existe una direccin Modbus TCP/IP annima (***.***.***.***) que se puede
configurar como Slo lectura o Ninguna. Si la configura como Slo lectura, permitir que
cualquier cliente Modbus TCP/IP que no est en la lista de filtrado acceda a los dispositivos
esclavos en serie con acceso de slo lectura. Si la configura como Ninguna, bloquear a
todos los clientes Modbus TCP/IP que no estn en la lista de filtrado.

Accin Resultado
1. En la pgina Configuracin, haga clic en Filtrado Abre la pgina Filtrado de Modbus TCP/IP.
de Modbus TCP/IP.
2. Marque la casilla de verificacin Activar filtrado. Activa el filtrado.
3. En la columna Direccin IP, introduzca la Introduce la direccin IP de un cliente Modbus TCP/IP que
direccin del cliente Modbus TCP/IP. tendr acceso a los dispositivos serie conectados a la EGX.
4. En la columna Nivel de acceso, seleccione Slo Selecciona el nivel de acceso para la correspondiente
lectura o Completo. direccin IP. Cuando se establece como Slo lectura, slo se
permiten los siguientes cdigos de funcin Modbus TCP/IP:
Decimal: 1, 2, 3, 4, 7, 8, 11, 12, 17, 20, 24, 43, 100
Hexadecimal: 01, 02, 03, 04, 07, 08, 0B, 0C, 11, 14, 18, 2B, 64
5. Repita los pasos 3 y 4 para agregar ms Contina aadiendo direcciones IP para el filtrado.
direcciones IP.
6. Haga clic en Aplicar. Guarda la lista de filtrado de direcciones Modbus TCP/IP.

2006-2012 Schneider Electric. Reservados todos los derechos. 9


Pasarela Ethernet EGX100 de PowerLogic 63230-319-204B1
Configuracin 08/2012

Figura 10: Pgina Filtrado de Modbus TCP/IP

Parmetros del SNMP


La EGX es compatible con el protocolo SNMP, lo cual permite que un administrador de red
acceda de manera remota a una EGX mediante un gestor de SNMP y visualice el estado de
la conexin y los diagnsticos en formato MIB-II.

Accin Resultado
1. En la pgina Configuracin, haga clic en Parmetros Abre la pgina Parmetros del SNMP.
del SNMP.
2. Marque la casilla de verificacin Activar SNMP para Activa el protocolo SNMP.
habilitar el protocolo simple de administracin de
redes.
NOTA: Si quita la marca de Activar SNMP y hace clic
en Aplicar, se reiniciar la EGX y se desactivar la
funcionalidad SNMP.
3. Introduzca el contacto del sistema, el nombre del Introduce la informacin del sistema SNMP y los nombres
sistema, su ubicacin, el nombre de la comunidad de de acceso de las comunidades.
slo lectura y el nombre de la comunidad de lectura y
escritura.
4. Haga clic en Aplicar. Guarda los valores del protocolo SNMP.

Figura 11: Pgina Parmetros del SNMP

10 2006-2012 Schneider Electric. Reservados todos los


63230-319-204B1 Pasarela Ethernet EGX100 de PowerLogic
08/2012 Configuracin

Punto de acceso del sistema


El punto de acceso del sistema permite que la EGX100 difunda su existencia a todas las
pasarelas EGX300 que estn conectadas a la red. Esta funcin est configurada para su
ejecucin de manera predeterminada, por lo que no es necesario configurar ningn
parmetro adicional.
La pantalla de configuracin de la Figura 12 de la pgina 11 le permitir introducir la
direccin IP del grupo y su informacin asociada.

Accin Resultado
1. En el men Configuracin, haga clic en Punto de acceso del Abre la ventana Punto de acceso del sistema.
sistema.
2. Seleccione el puerto UDP, la direccin IP del grupo, el intervalo Selecciona la configuracin del punto de acceso
de introduccin, el tiempo de espera, el perodo de vida de del sistema.
multidifusin y la comunidad. Consulte la Tabla 7 para ver las
descripciones de los parmetros.
3. Haga clic en Aplicar. Aplica la configuracin a la EGX100.
NOTA: Para volver a la configuracin predeterminada, haga clic
en Predeterminados y, a continuacin, en Aplicar.

Tabla 7: Configuracin del punto de acceso del sistema

Opcin Descripcin Valor


Activado Cuando se marca esta casilla, las pasarelas EGX300 podrn Activado, desactivado
detectar las EGX100 que tengan la misma direccin IP de Predeterminado: Activado
grupo.
Puerto UDP Le permite establecer el nmero de puerto del puerto UDP De 1 a 65535
empleado por la deteccin de la funcin Punto de acceso del Valor predeterminado: 59
sistema.
Direccin IP del grupo Este campo admite direcciones de unidifusin o multidifusin. Valor predeterminado:
224.0.1.2
Intervalo de introduccin Periodo de tiempo transcurrido entre mensajes de bienvenida De 1 a 65534 segundos
emitidos por esta EGX100 con que se anuncia su presencia a Predeterminado:
otros dispositivos de punto de acceso del sistema de 300 segundos
Schneider Electric que se encuentren en red.
Tiempo de espera Periodo de tiempo durante el cual los mensajes de bienvenida De 2 a 65535 segundos
que emite esta EGX100 deberan ser retenidos por los Predeterminado:
destinatarios antes de considerar que esta no est disponible. 600 segundos
Perodo de vida de Le permite controlar la amplitud del rea de la red para De 1 a 255 saltos de router
multidifusin detectar otros dispositivos. Se controla mediante el nmero de Valor predeterminado: 1
veces que se permite el reenvo de la multidifusin a otros.
Comunidad Los dispositivos de un grupo pueden dividirse en De 0 a 65535
comunidades. Las pasarelas EGX300 son capaces de detectar Valor predeterminado: 0
las EGX100 que tengan la misma direccin IP del grupo y el
mismo nmero de comunidad.

Si se configura el nmero de comunidad como 0, ello


permitir que una EGX300 detecte todas las EGX100 con la
misma direccin IP de grupo independientemente del valor del
parmetro de comunidad.

Figura 12: Punto de acceso del sistema

2006-2012 Schneider Electric. Reservados todos los derechos. 11


Pasarela Ethernet EGX100 de PowerLogic 63230-319-204B1
Diagnsticos 08/2012

Diagnsticos
Para acceder a los vnculos de la pgina web Diagnsticos, haga clic en Diagnsticos en la
barra de mens de la EGX.

Estadsticas
Accin Resultado
1. En la pgina Diagnsticos, haga clic Abre la pgina Estadsticas (consulte la Figura 13).
en Estadsticas.
NOTA: La pgina Estadsticas muestra los datos basados en el modo
seleccionado en Puerto serie en la pgina 5.
2. Visualice los datos. Consulte Interpretacin de las estadsticas en la pgina 13.
3. Haga clic en Restablecer. Restablece los datos de diagnstico acumulativos de la EGX a 0.

NOTA: Esta pgina ilustra las lecturas acumuladas desde la ltima vez que se activ
la EGX. Si la EGX pierde alimentacin, todos los valores acumulativos volvern a cero.

Figura 13: Pgina Estadsticas


Lectura con puerto serie en MODO MAESTRO Lectura con puerto serie en MODO ESCLAVO

12 2006-2012 Schneider Electric. Reservados todos los


63230-319-204B1 Pasarela Ethernet EGX100 de PowerLogic
08/2012 Diagnsticos

Interpretacin de las estadsticas


Estadstica Descripcin
Ethernet
Estado de conexin Cadena de estado que representa la velocidad y la configuracin bidireccional que
se utiliza para comunicarse con el dispositivo conectado.
Tramas transmitidas Contador que aumenta cada vez que se enva una trama correctamente.
satisfactoriamente
Colisiones Contador que aumenta cada vez que se reenva una trama debido a deteccin de
colisiones.
Colisiones excesivas Contador que aumenta cada vez que no se puede enviar una trama porque ha
alcanzado el estado de colisin mxima basado en el algoritmo de retroceso
exponencial binario truncado.
Tramas recibidas Contador que aumenta cada vez que se recibe una trama correctamente.
satisfactoriamente
Errores de CRC de tramas Contador que aumenta cada vez que se recibe una trama que contiene una suma
de verificacin/CRC que no coincide con la calculada.
Errores de alineacin Contador que aumenta cada vez que se recibe una trama que contiene un error de
suma de verificacin/CRC y que no termina en un borde de trama de 8 bits.
Tramas demasiado largas Contador que aumenta cada vez que se recibe una trama que excede el tamao
mximo definido en las normas (tramas de ms de 1518 bytes).
Tramas demasiado cortas Contador que aumenta cada vez que se recibe una trama que no alcanza el
tamao mnimo definido en las normas (tramas de menos de 64 bytes).
Modbus TCP/IP
Tramas enviadas Contador que aumenta cada vez que se enva una trama.
Tramas recibidas Contador que aumenta cada vez que se recibe una trama.
Errores de protocolo Contador que aumenta cada vez que se recibe un mensaje mal formado.
Conexiones activas1 Valor de estado que representa el nmero de conexiones activas en el momento
de actualizacin de la pgina de diagnsticos. Se admite un mximo de
32 conexiones. Al hacer clic en Conexiones activas, se abre una ventana nueva
con una lista de todas las conexiones clientes activas.
Conexiones acumuladas1 Contador que aumenta cada vez que se realiza una conexin a la EGX.
Mximo de conexiones1 Valor de estado que representa el nmero mximo de conexiones que pueden
estar activas en un momento dado.
Mensajes entrantes de lectura1 Contador que aumenta cada vez que se recibe un mensaje de solicitud de lectura.
Mensajes salientes de lectura2 Contador que aumenta cada vez que se enva un mensaje de solicitud de lectura.
Mensajes entrantes de escritura1 Contador que aumenta cada vez que se recibe un mensaje de solicitud de
escritura.
Mensajes salientes de escritura2 Contador que aumenta cada vez que se enva un mensaje de solicitud de
escritura.
Mensajes entrantes de respuesta2 Contador que aumenta cada vez que se recibe un mensaje de respuesta.
Mensajes salientes de respuesta1 Contador que aumenta cada vez que se enva un mensaje de respuesta.
Puerto serie
Tramas enviadas Contador que aumenta cada vez que se enva una trama.
Tramas recibidas Contador que aumenta cada vez que se recibe una trama.
Errores de CRC de tramas Contador que aumenta cada vez que se recibe un mensaje que contiene una CRC
que no coincide con la calculada. Suele ser el resultado de problemas de
cableado.
Errores de protocolo Contador que aumenta cada vez que se recibe un mensaje mal formado.
Tiempos de espera Contador que aumenta cada vez que se enva un mensaje de solicitud sin recibir
el mensaje de respuesta correspondiente durante el tiempo permitido. Los
tiempos de espera de respuesta suelen ser el resultado de errores de
configuracin o un dispositivo que no responde.
Mensajes entrantes de lectura2 Contador que aumenta cada vez que se recibe un mensaje de solicitud de lectura.
Mensajes salientes de lectura1 Contador que aumenta cada vez que se enva un mensaje de solicitud de lectura.
Mensajes entrantes de escritura2 Contador que aumenta cada vez que se recibe un mensaje de solicitud de
escritura.
Mensajes salientes de escritura1 Contador que aumenta cada vez que se enva un mensaje de solicitud de
escritura.
1 Disponible cuando el puerto serie est en modo Maestro.
2
Disponible cuando el puerto serie est en modo Esclavo.

2006-2012 Schneider Electric. Reservados todos los derechos. 13


Pasarela Ethernet EGX100 de PowerLogic 63230-319-204B1
Diagnsticos 08/2012

Estadstica Descripcin
Informacin de pasarela
Versin del firmware Versin del firmware que est instalada en la EGX.
Tiempo de inactividad del sistema Porcentaje del 0% al 100% que indica el tiempo medio de procesador que no se
utiliza.
Direccin MAC Direccin exclusiva del hardware Ethernet de una EGX.
Nmero de serie Nmero de serie de la EGX.
Nmero de modelo Nmero de modelo de la EGX (100).
Versin del hardware Versin del hardware de la EGX.
Fecha de fabricacin Fecha de fabricacin de la EGX.

Lectura de registros de dispositivo

Accin Resultado
1. En la pgina Diagnsticos, haga clic en Lectura de Abre la pgina Lectura de registros de dispositivo.
registros de dispositivo.
2. Introduzca el identificador del dispositivo, el nmero de Introduce los valores con los que empezar a leer
registro de inicio y el nmero de registros que desea leer. los registros del dispositivo especificado.
3. Seleccione un tipo de datos. Selecciona el tipo de datos que visualizar.
4. Para modificar la visualizacin de los datos de la columna Selecciona el modo de visualizacin de los valores
Valor, seleccione Decimal, Hexadecimal, Binario o ASCII. de los datos.
5. Haga clic en Lectura. Muestra los datos solicitados.

Tabla 8: Parmetros de lectura de registros de dispositivo de la EGX

Opcin Descripcin Predet.


ID de dispositivo Direccin del dispositivo cuyos registros se leen. 1
Registro de inicio Primer registro para leer. 1000
Nmero de registros Nmero de registros para leer (1 a 10). 10
Columna Registro Muestra una lista con los nmeros de los registros.
Columna Valor Muestra una lista de los datos almacenados en un registro. Los
valores recuperados dependen del dispositivo conectado a la EGX.
Consulte la documentacin correspondiente al dispositivo conectado
para obtener ms informacin acerca de los valores de los registros
almacenados.
Tipo de datos Seleccione Registros de retencin, Registros de entrada, Bobinas de Registros de
salida, Bobinas de entrada o ID de dispositivo para especificar los retencin
valores recuperados.
Opciones Decimal, Seleccione una opcin para especificar el modo de visualizacin de Decimal
Hexadecimal, Binario o ASCII los datos de la columna Valor.

14 2006-2012 Schneider Electric. Reservados todos los


63230-319-204B1 Pasarela Ethernet EGX100 de PowerLogic
08/2012 Firmware

Figura 14: Pgina Lectura de registros de dispositivo

Firmware
El firmware de la EGX se puede actualizar utilizando el protocolo de transferencia de
archivos (FTP). Consulte el sitio www.powerlogic.com o a su distribuidor local para obtener
la ltima actualizacin del firmware.

Identificacin de la versin del firmware

Accin Resultado
1. Conctese a la EGX. Abre la pgina de inicio de la EGX.
2. Localice la versin del firmware en la parte inferior izquierda Seala la versin del firmware de la EGX.
de la pgina.
NOTA: Si ha actualizado el firmware recientemente,
pulse F5 para actualizar la pgina web y actualizar el
nmero de firmware que aparece en ella.
3. Tambin puede seleccionar Diagnsticos > Estadsticas Tambin seala la versin del firmware de la EGX.
para ver la versin del firmware en la seccin Informacin
de pasarela.

Obtencin de firmware nuevo

Accin Resultado
1. Inicie Internet Explorer, escriba www.powerlogic.com en la Abre el sitio web de PowerLogic.
barra de direcciones y luego pulse Intro.
2. Seleccione su pas y luego haga clic en Go (Ir). Abre el sitio web de PowerLogic de su pas.
NOTA: Si ha seleccionado Estados Unidos, vaya al paso 3.
De lo contrario, siga la navegacin del sitio web especfico
del pas para obtener el firmware de la EGX.
3. Seleccione Firmware Downloads > Products > Muestra las descargas disponibles para
PowerLogic Communications > EGX100 (Descargas de la EGX100.
firmware > Productos > Comunicaciones de PowerLogic >
EGX100).
4. Haga clic en el vnculo EGX100 Firmware (Firmware de Abre la pgina de instrucciones del firmware de
la EGX100). la EGX100.

2006-2012 Schneider Electric. Reservados todos los derechos. 15


Pasarela Ethernet EGX100 de PowerLogic 63230-319-204B1
Firmware 08/2012

Accin Resultado
5. Haga clic en la ficha Files (Archivos) y, a continuacin, en Muestra los nombres de archivo y, a continuacin,
el vnculo del archivo de firmware (eg#####.bin, donde abre el cuadro de dilogo Descarga de archivos.
##### es el nmero del firmware).
NOTA: Debe iniciar sesin para descargar los archivos del
firmware. Si no tiene un nombre de usuario ni una
contrasea, siga las instrucciones del sitio web.
6. Haga clic en Guardar. Guarda el archivo de firmware.

Actualizacin del archivo de firmware

Accin Resultado
1. Inicie Internet Explorer, escriba ftp:// y la direccin IP de Abre el cuadro de dilogo Iniciar sesin como.
la EGX en la barra de direcciones (por ejemplo,
ftp://169.254.0.10), y luego pulse Intro.
2. Escriba el nombre de usuario Administrator y la contrasea Abre una sesin de FTP con la EGX.
de administrador en los cuadros de texto, y luego haga clic
en Iniciar sesin.
3. Localice el archivo de firmware guardado en el equipo, haga Copia el archivo de firmware en el portapapeles.
clic con el botn derecho en el archivo y luego haga clic en
Copiar.
4. Haga clic con el botn derecho en la ventana de Internet Copia el firmware en la EGX y esta se reinicia.
Explorer y seguidamente haga clic en Pegar.
NOTA: En vez de copiar y pegar el nombre de archivo del
firmware, puede arrastrarlo y soltarlo en Internet Explorer.
5. Haga clic en el botn Cerrar en la ventana de Internet Cierra Internet Explorer y termina la conexin FTP
Explorer. con la EGX.
6. Para verificar que se ha actualizado correctamente la Verifica la versin actualizada del firmware.
versin del firmware, siga los pasos de Identificacin de la
versin del firmware en la pgina 15.

16 2006-2012 Schneider Electric. Reservados todos los


63230-319-204B1 Pasarela Ethernet EGX100 de PowerLogic
08/2012 ndice alfabtico

ndice alfabtico

A punto de acceso del sistema


configuracin 11
acceso a la EGX a travs de una red 2
acceso a pginas web R
configuracin 8
registros de dispositivo 14
C lectura 14
configuracin U
de Ethernet y TCP/IP 3
una red
de la lista de dispositivos en modo
acceso a travs de 2
Esclavo 7
de la lista de dispositivos en modo
Maestro 6
cuentas de usuario
configuracin 8

D
desconectar 2
deteccin de direcciones IP duplicadas 4
diagnsticos 12

E
EGX
configuracin 3
inicio de sesin 2
interfaz de usuario 3
equipo fsico 1
estadsticas 12
interpretacin 13

F
filtrado de Modbus TCP/IP
configuracin 9
firmware 15
actualizacin 15
identificacin de la versin 15
obtencin de nuevo 15

I
inicio de sesin en la EGX 2
interfaz de usuario 3
introduccin 1

L
lista de dispositivos
configuracin 6
modo Esclavo 7
modo Maestro 6

O
otros recursos 2

P
parmetros del SNMP
configuracin 10
protocolos Ethernet 1
compatibles 1
puerto serie
configuracin 5

2006-2012 Schneider Electric. Reservados todos los 17


Pasarela Ethernet EGX100 de PowerLogic 63230-319-204B1
ndice alfabtico 08/2012

18 2006-2012 Schneider Electric. Reservados todos los


Pasarela Ethernet EGX100 de PowerLogic
Manual del usuario

PowerLogic es una marca comercial de Schneider Electric en EE. UU., Francia y


otros pases. Las dems marcas comerciales son propiedad de sus respectivos
propietarios.

Schneider Electric.
35 rue Joseph Monier 63230-319-204B1 08/2012
92500 Rueil-Malmaison, France Sustituye a 63230-319-204A2 con fecha de 12/2008.
www.schneider-electric.com. 2006-2012 Schneider Electric. Reservados todos los derechos.
Passerelle Ethernet PowerLogic EGX100
Manuel de lutilisateur

63230-319-204B1
08/2012
Informations sur la scurit

Informations importantes
Lisez attentivement ces directives et examinez lquipement afin de vous
familiariser avec lui avant linstallation, lutilisation ou lentretien. Les messages
spciaux qui suivent peuvent apparatre dans ce document ou sur lappareillage. Ils
vous avertissent de dangers potentiels ou attirent votre attention sur des
renseignements pouvant claircir ou simplifier une procdure.

Lajout de lun ou lautre des symboles une tiquette de scurit Danger


ou Avertissement vous indique quun danger lectrique existe et quil pourra
y avoir des blessures corporelles si les directives ne sont pas suivies.

Ceci est le symbole dune alerte de scurit. Il sert vous avertir dun danger
potentiel de blessures corporelles. Respectez toutes les consignes de scurit
accompagnant ce symbole pour viter tout risque potentiel de blessure ou de mort.

DANGER indique une situation de danger imminent qui, si elle nest pas vite, entranera
la mort ou des blessures graves.

AVERTISSEMENT indique une situation de danger potentiel qui, si elle nest pas vite,
peut entraner la mort ou des blessures graves.

ATTENTION indique une situation de danger potentiel qui, si elle nest pas vite, peut
entraner des blessures mineures ou modres.

AVIS est utilis pour les applications sans risque de dommages corporels. Le symbole
dalerte de scurit ne peut tre utilis avec ce terme.

Veuillez noter
Seul un personnel qualifi doit effectuer linstallation, lutilisation, lentretien et la
maintenance du matriel lectrique. Schneider Electric dcline toute responsabilit
quant aux consquences ventuelles dcoulant de lutilisation de ce matriel.

Par personne qualifie, on entend un technicien comptent en matire de


construction, dinstallation et dutilisation de ce type dinstallation lectrique et
form aux procdures de scurit, donc capable de dtecter et dviter les risques
associs.
Avis

Avis FCC section 15


Cet appareil a subi des essais et a t reconnu conforme aux limites imposes aux
appareils numriques de classe A, selon le paragraphe 15 de la rglementation
FCC (Commission fdrale des communications des tats-Unis). Ces limites sont
conues pour fournir une protection raisonnable contre les interfrences nuisibles
lorsquun appareil est employ dans un environnement commercial. Cet appareil
produit, utilise et peut mettre de lnergie radiofrquence et, sil nest pas install
ou utilis conformment au mode demploi, il peut provoquer des interfrences
nuisibles aux communications radio. Le fonctionnement de cet appareil dans une
zone rsidentielle est susceptible de provoquer des interfrences nuisibles, auquel
cas lutilisateur devra corriger les interfrences ses propres frais. Cet appareil
numrique appartient la Classe A et est conforme la norme ICES-003 du
Canada.
63230-319-204B1 PowerLogic Ethernet Gateway EGX100
08/2012 Table des matires

Table des matires


Introduction .................................................................................................................... 1
Protocoles Ethernet pris en charge .................................................................................. 1
Matriel ............................................................................................................................. 1
Ressources supplmentaires ........................................................................................... 2
Accs la passerelle EGX via un rseau ..................................................................... 2
Connexion la passerelle EGX ....................................................................................... 2
Dconnexion .................................................................................................................... 2
Prsentation de linterface utilisateur EGX .................................................................. 3
Configuration .................................................................................................................. 3
Paramtres Ethernet et TCP/IP ........................................................................................ 3
Dtection des adresses IP identiques........................................................................... 4
Port srie .......................................................................................................................... 5
Liste des appareils ........................................................................................................... 6
Configuration de la liste des appareils en mode Matre................................................ 6
Configuration de la liste des appareils en mode Esclave ............................................. 7
Comptes utilisateur ........................................................................................................... 8
Accs aux pages Web ...................................................................................................... 8
Filtrage Modbus TCP/IP ................................................................................................... 9
Paramtres SNMP ......................................................................................................... 10
Point daccs systme .................................................................................................... 11
Diagnostics ................................................................................................................... 12
Statistiques ..................................................................................................................... 12
Interprtation des statistiques ..................................................................................... 13
Lecture de registres dappareils ..................................................................................... 14
Logiciel embarqu (firmware) ..................................................................................... 15
Recherche de la version du logiciel embarqu .............................................................. 15
Obtention du dernier logiciel embarqu ......................................................................... 15
Mise jour du logiciel embarqu .................................................................................... 16
Index ............................................................................................................................... 17

2006-2012 Schneider Electric. Tous droits rservs. i


PowerLogic Ethernet Gateway EGX100 63230-319-204B1
Table des matires 08/2012

ii 2006-2012 Schneider Electric. Tous droits rservs.


63230-319-204B1 Passerelle Ethernet PowerLogic EGX100
08/2012 Introduction

Introduction
Ce manuel doit tre utilis avec une passerelle PowerLogic EGX100 quipe de la
version 3.0 ou ultrieure du logiciel embarqu (firmware). Pour des informations concernant
linstallation, consultez le manuel dinstallation.
La passerelle EGX100 est un appareil de communication qui assure la connectivit entre
des appareils Ethernet (Modbus TCP/IP) et srie. Elle permet des clients Modbus TCP/IP
daccder aux informations dappareils esclaves en srie. Elle permet aussi des appareils
srie matres daccder aux informations dappareils esclaves rpartis sur un rseau
Ethernet.

Protocoles Ethernet pris en charge


La passerelle EGX prend en charge les protocoles Ethernet suivants :
Modbus TCP/IP : Modbus TCP/IP est une combinaison du protocole Modbus qui permet
les communications matre/esclave entre appareils et du protocole TCP/IP qui permet de
communiquer par le biais dune connexion Ethernet. Modbus TCP/IP permet dchanger
des donnes entre la passerelle EGX et dautres appareils compatibles Modbus TCP/IP
via le port TCP 502.
Hypertext Transfer Protocol (HTTP) : HTTP est un protocole rseau qui gre la remise
de fichiers et de donnes sur le Web. Il fournit les fonctionnalits de serveur Web via le
port TCP 80. La configuration distance de la passerelle EGX et laffichage des
diagnostics sont possibles en utilisant un navigateur Web.
File Transfer Protocol (FTP) : FTP est un protocole rseau qui permet de transfrer des
fichiers dun ordinateur un autre sur Internet. Le protocole FTP sutilise pour transfrer
les mises jour dans la passerelle EGX via le port TCP 21.
Simple Network Management Protocol (SNMP) : Bas sur le format MIB2, SNMP
permet denregistrer et didentifier des informations de diagnostic utilises pour la gestion
du rseau via le port UDP 161.
ARP (Address Resolution Protocol) : ARP convertit des adresses IP en adresses
Ethernet. La passerelle EGX envoie des requtes ARP pour vrifier si son adresse IP est
dj utilise (voir Dtection des adresses IP identiques , page 4).

Matriel

Port Ethernet RJ-45

Alimentation

Voyant LED
dalimentation
et dtat
Port srie RS-485
Voyant LED pour
les communications
Ethernet et srie

Cavaliers de polarit,
de terminaison et 2/4
Bouton de fils
rinitialisation Port srie RS-232
(connecteur RJ-45)

2006-2012 Schneider Electric. Tous droits rservs. 1


Passerelle Ethernet PowerLogic EGX100 63230-319-204B1
Accs la passerelle EGX via un rseau 08/2012

Ressources supplmentaires
Documentation : Rendez-vous sur le site www.powerlogic.com et slectionnez votre pays.
Slectionnez Library (bibliothque) > PowerLogic Products (produits PowerLogic) >
Communications > EGX100 Gateway (passerelle EGX100), puis cliquez sur le document
que vous souhaitez tlcharger.
REMARQUE : Si vous avez slectionn un pays autre que les tats-Unis, suivez les tapes
spcifiques chaque pays pour obtenir la documentation EGX.
Logiciel embarqu (firmware) : la section Logiciel embarqu (firmware) , page 15
explique comment tlcharger et installer les mises jour du logiciel embarqu.

Accs la passerelle EGX via un rseau


Aprs avoir configur les paramtres Ethernet (voir le manuel dinstallation), vous pouvez
accder la passerelle EGX sur un rseau local Ethernet au moyen dInternet Explorer 6.0
(ou dune version ultrieure).

Connexion la passerelle EGX

Action Rsultat
1. Lancez Internet Explorer 6.0 (ou version ultrieure). Ouvre Internet Explorer.
2. Dans la zone Adresse, tapez ladresse IP de la Ouvre la bote de dialogue de connexion.
passerelle EGX (169.254.0.10 par dfaut), puis
appuyez sur Entre.
3. Tapez votre nom dutilisateur (Administrator par Saisit le nom dutilisateur et le mot de passe, puis ouvre la
dfaut) et votre mot de passe (Gateway par dfaut) page daccueil EGX.
dans les zones appropries, puis cliquez sur OK.
4. Cliquez sur Configuration pour accder la page de Ouvre la page Configuration ou Diagnostics.
configuration EGX ou cliquez sur Diagnostics pour
accder la page de diagnostic EGX.

Figure 1 : Page daccueil EGX

Barre de
menus

Dconnexion
Nous vous recommandons de vous dconnecter ds que vous navez plus besoin daccder
la passerelle EGX.
Pour fermer la session de configuration EGX en cours, cliquez sur Dconnexion.

2 2006-2012 Schneider Electric. Tous droits rservs.


63230-319-204B1 Passerelle Ethernet PowerLogic EGX100
08/2012 Prsentation de linterface utilisateur EGX

Prsentation de linterface utilisateur EGX


La passerelle EGX est livre avec huit pages Web prinstalles utilises pour la
configuration. Voir le Tableau 1 pour la description de chaque page.

Tableau 1 : EGX Pages Web statiques

Voir
Page Web EGX Description
page
Configuration

Ethernet et TCP/IP Configure les paramtres des communications Ethernet et TCP/IP. 3


Port srie Dfinit ou modifie les paramtres des communications srie. 5
Liste des appareils Identifie les appareils srie raccords la guirlande. 6
Comptes utilisateur1 Permet de crer ou modifier les noms de groupe. 8
Accs aux pages Web1 Slectionne les droits daccs aux pages Web pour chaque groupe 8
dutilisateurs.
Filtrage Modbus TCP/IP1 Configure les adresses IP qui peuvent accder la passerelle EGX via le 9
protocole Modbus TCP/IP.
Paramtres SNMP1 Permet dactiver et de configurer le protocole SNMP (Simple Network 10
Management Protocol), qui permet la passerelle EGX de sidentifier auprs
des appareils rseau qui demandent des donnes SNMP.
Point daccs systme1 Permet la passerelle EGX100 de multidiffuser sa prsence toutes les 11
passerelles EGX300 connectes au rseau.

Diagnostics

Statistiques Affiche les donnes de diagnostic utilises pour rechercher des problmes sur 12
le rseau. Cette page contient galement des informations sur votre
passerelle EGX, notamment le numro de srie, la date de fabrication et
ladresse MAC (Media Access Control contrle daccs au support).
Lecture de registres Permet aux administrateurs EGX de lire les donnes de registres dun 14
dappareils appareil srie connect la passerelle EGX.
1
Uniquement accessible par un administrateur

Configuration
Pour accder aux liens de la page Configuration, cliquez sur Configuration dans la barre
de menus de la passerelle EGX.

Paramtres Ethernet et TCP/IP

Action Rsultat
1. la page Configuration, cliquez sur Ethernet et Ouvre la page Ethernet et TCP/IP.
TCP/IP.
2. Slectionnez le format de trame et le type de support. Slectionne le format de trame et le type de support.
Contactez votre administrateur rseau si vous ne
connaissez pas ces informations.
3. Entrez ladresse IP, le masque de sous-rseau et Configure les paramtres Ethernet de la passerelle EGX.
ladresse de passerelle attribus la passerelle EGX REMARQUE : Si vous saisissez une adresse IP dj
par votre administrateur rseau. utilise par un autre appareil, le systme vous demande
den saisir une autre. Voir Dtection des adresses IP
identiques , page 4.
4. Cliquez sur Appliquer. Met jour les paramtres Ethernet et TCP/IP de la
passerelle EGX.
* Voir le Tableau 2, page 4 pour la liste des options.

REMARQUE : Aprs avoir effectu les modifications et cliqu sur Appliquer, la passerelle
EGX redmarre.

2006-2012 Schneider Electric. Tous droits rservs. 3


Passerelle Ethernet PowerLogic EGX100 63230-319-204B1
Configuration 08/2012

Figure 2 : Page Ethernet et TCP/IP

Tableau 2 : Paramtres Ethernet et TCP/IP de la passerelle EGX

Option Description Valeur


Format de trame Slection du format des donnes envoyes travers une Ethernet II, 802.3 SNAP
connexion Ethernet. Par dfaut : Ethernet II
Type de support Dfinition de la connexion Ethernet physique ou du type de 10T/100Tx Auto
support. 10BaseT-HD
10BaseT-FD
100BaseTx-HD
100BaseTx-FD
Par dfaut : 10T/100Tx Auto
Adresse IP Saisie de ladresse IP statique de la passerelle EGX. Par dfaut : 169.254.0.10
Masque de sous-rseau Saisie de ladresse IP Ethernet du masque de sous-rseau. Par dfaut : 255.255.0.0
Passerelle par dfaut Saisie de ladresse IP de la passerelle (routeur) utilise Par dfaut : 0.0.0.0
pour les communications sur rseau tendu.

Dtection des adresses IP identiques


Lorsquelle est connecte au rseau, la passerelle EGX publie son adresse IP. Afin dviter
les conflits dadresses IP identiques, la passerelle EGX utilise le protocole ARP (Address
Resolution Protocol) pour vrifier si un autre appareil du rseau utilise la mme adresse IP.
Le Tableau 3 ci-dessous explique comment la passerelle EGX gre une adresse IP en
double quelle dtecte.

Tableau 3 : Scnarios de dtection des adresses IP identiques

Voyant LED dalimentation et


Scnario Adresse IP en double dtecte
dtat

Redmarrage / Rtablissement Rtablit ladresse IP, le masque de sous- Quatre clignotements, pause
de lalimentation rseau et ladresse par dfaut de la passerelle
EGX. Les demandes ARP sont envoyes
Liaison Ethernet dtecte
toutes les 15 secondes jusqu ce que
ladresse IP soit disponible. Lorsque ladresse
est disponible, la passerelle EGX lutilise.
Modification manuelle des La passerelle EGX conserve son adresse IP
adresses prcdente et affiche un message qui indique
que ladresse IP est dj utilise par un autre
appareil.
Rception dune demande ARP Rtablit ladresse IP, le masque de sous- Quatre clignotements, pause
rseau et ladresse par dfaut de la passerelle
EGX si un appareil connect envoie quatre
demandes ARP pour ladresse IP de la
passerelle EGX. La passerelle EGX envoie
des demandes ARP toutes les 15 secondes
jusqu ce que ladresse IP soit nouveau
disponible. Lorsque ladresse est disponible,
la passerelle EGX lutilise.

4 2006-2012 Schneider Electric. Tous droits rservs.


63230-319-204B1 Passerelle Ethernet PowerLogic EGX100
08/2012 Configuration

Port srie

Action Rsultat
1. la page Configuration, cliquez sur Port srie. Ouvre la page Port srie.
2. Slectionnez le mode, linterface physique, le mode et Slectionne les options de port srie.
la vitesse de transmission, la parit et la
temporisation (voir Tableau 4, page 5).
3. Si vous slectionnez le mode Esclave, saisissez les Configure les adresses IP des appareils distants.
adresses IP des appareils connects distance (voir
Tableau 4, page 5).
4. Cliquez sur Appliquer. Met jour les paramtres du port srie de la passerelle
EGX.

Figure 3 : Page Port srie

Tableau 4 : Paramtres de port srie

Option Description Valeur


Mode Permet de slectionner lutilisation du port COM de la Matre, Esclave
passerelle EGX (matre ou esclave). Par dfaut : Matre
REMARQUE : Lorsque le Mode est modifi, la
passerelle EGX redmarre.
Interface physique Permet de slectionner le cblage physique du port RS-485 4 fils, RS-485 2 fils ou RS-
srie de la passerelle EGX. 232
Par dfaut : RS-485 2 fils
Mode de transmission Permet de dterminer comment les donnes sont Mode Matre : Automatique, Modbus
transmises travers une connexion srie. ASCII
Mode Esclave : Modbus RTU,
Modbus ASCII
Par dfaut :
Mode Matre : Automatique
Mode Esclave : Modbus RTU

REMARQUE : Le mode automatique


permet simultanment de
communiquer avec les appareils
esclaves Modbus RTU, PowerLogic
(SY/MAX) et Jbus sur la mme
guirlande.

Vitesse de Permet de slectionner la vitesse de transmission 2400, 4800, 9600, 19200, 38400,
transmission travers une connexion srie. 56000*, 57600*
Par dfaut : 19200
Parit Spcifie si la prcision des donnes est vrifie au Paire, Impaire, Aucune
moyen dun bit de parit. Par dfaut : Paire
Dlai dattente de Permet de slectionner le temps pendant lequel la 0,1-10 secondes
rponse passerelle EGX attend une rponse dun appareil Par dfaut : 3 secondes
srie.
Connexions Modbus Dfinit une liste dadresses Modbus TCP/IP que la
TCP/IP distance passerelle EGX utilisera pendant les communications
(mode Esclave en mode Esclave.
uniquement)
* Disponible uniquement si linterface physique et le mode de transmission sont RS-232/Modbus ASCII.

2006-2012 Schneider Electric. Tous droits rservs. 5


Passerelle Ethernet PowerLogic EGX100 63230-319-204B1
Configuration 08/2012

Liste des appareils


Avant de commencer, tenez compte des points suivants :
Pour lutilisation du port COM en mode Matre :
Il nest pas obligatoire de dfinir les appareils RTU/Jbus dans la liste des appareils, mais
cela peut faciliter la gestion du systme.
Les appareils protocole PowerLogic (SY/MAX) doivent tre dfinis dans la liste des
appareils.
REMARQUE : Nutilisez pas les adresses esclaves en srie 1 16 en mode de transmission
automatique sur une guirlande utilisant plusieurs protocoles (ex. une guirlande qui comporte
des appareils utilisant le protocole PowerLogic et dautres utilisant le protocole
Modbus/Jbus).

Configuration de la liste des appareils en mode Matre


Figure 4 : Topologie du mode Matre

Connexion Ethernet

EGX en
mode
Matre
Connexion RS-485 Jusqu 128
appareils
esclaves en
srie utilisant
des rpteurs
Appareils esclaves srie

Si vous avez slectionn le mode Matre la page Port srie, procdez comme suit pour
configurer la liste des appareils :

Action Rsultat
1. la page Configuration, cliquez sur Liste des appareils. Ouvre la page Liste des appareils.
2. Slectionnez le nombre dappareils quil est possible Slectionne le nombre demplacements affichables
dafficher (1 128) et cliquez sur Appliquer. qui peuvent servir dfinir des appareils esclaves
en srie connects la passerelle EGX.
3. Dans la zone de texte Identification locale, tapez Configure ladresse locale de lappareil.
lidentification locale (adresse) de lappareil esclave en srie.
4. Slectionnez le Protocole. Slectionne le protocole de lappareil connect.
5. Recommencez les tapes 3 et 4 jusqu ce que tous les Saisit tous les appareils connects.
appareils soient configurs.
6. Cliquez sur Appliquer. Actualise la liste des appareils.

Figure 5 : Page Liste des appareils en mode Matre

6 2006-2012 Schneider Electric. Tous droits rservs.


63230-319-204B1 Passerelle Ethernet PowerLogic EGX100
08/2012 Configuration

Configuration de la liste des appareils en mode Esclave


Le mode Esclave en srie permet aux appareils Modbus matres en srie daccder aux
informations des appareils esclaves en srie travers un rseau TCP/IP. La Figure 6 illustre
la connexion des appareils en utilisant les paramtres de la liste des appareils de la Figure 7.

Figure 6 : Topologie du mode Esclave


Connexion Ethernet
Jusqu 16 connexions IP
distantes avec 128 appareils
esclaves en srie sont possibles.
EGX en mode
Esclave
EGX en mode EGX en mode
Matre Matre
Adresse IP : Adresse IP :
169.254.0.28 169.254.0.75

Connexion RS-232
Connexion RS-485 Connexion RS-485 ou RS-485

2 5 2 3 4 5 6 7
Appareils esclaves srie Appareils esclaves srie

Si vous avez slectionn le mode Esclave la page Port srie, procdez comme suit pour
configurer la liste des appareils :

Action Rsultat
1. la page Configuration, cliquez sur Liste des Ouvre la page Liste des appareils.
appareils.
2. Slectionnez le nombre dappareils quil est possible Slectionne le nombre demplacements quil est possible
dafficher (1 128) et cliquez sur Appliquer. dafficher utilisables pour dfinir des appareils Modbus
TCP/IP distants.
3. Slectionnez la Connexion. Slectionne ladresse Modbus TCP/IP associer
lidentification distante.
4. Dans la zone de texte Identification locale, tapez Saisit ladresse de lappareil que lappareil Modbus matre
lidentification locale (adresse) de lappareil esclave utilisera pour accder lappareil distant.
en srie.
5. Dans la zone de texte Identification distante, tapez Saisit ladresse esclave en srie de lappareil connect
lidentification distante (adresse) de lappareil esclave distance.
en srie.
6. Recommencez les tapes 3 5 jusqu ce que tous Saisit les informations de correspondance de faon que la
les appareils soient configurs. passerelle EGX communique avec les appareils distants.
7. Cliquez sur Appliquer. Actualise la liste des appareils.

Figure 7 : Page Liste des appareils en mode Esclave

2006-2012 Schneider Electric. Tous droits rservs. 7


Passerelle Ethernet PowerLogic EGX100 63230-319-204B1
Configuration 08/2012

Comptes utilisateur
Les utilisateurs de la passerelle EGX reoivent un nom dutilisateur et un mot de passe.
Chaque utilisateur appartient un groupe et chaque groupe a des droits daccs aux pages
Web EGX qui lui sont attribus par ladministrateur EGX.
REMARQUE : Il existe par dfaut deux comptes utilisateur : Administrator (Administrateur)
(mot de passe : Gateway) et Guest (Invit) (mot de passe : Guest).

Action Rsultat
1. la page Configuration, cliquez sur Comptes utilisateur. Ouvre la page Comptes utilisateur.
2. Si vous voulez modifier le nom dun groupe, tapez le Entrez le nom du nouveau groupe.
nouveau nom dans lune des zones de texte de la zone
Groupes (vous ne pouvez pas modifier le nom du groupe
Administrator).
3. Dans la zone Utilisateurs, saisissez le nom (1 24 Dfinit le nom et le mot de passe dun utilisateur.
caractres) et le mot de passe (0 12 caractres) du
nouvel utilisateur.
REMARQUE : Les noms et les mots de passe des
utilisateurs distinguent les majuscules et les minuscules ;
ils peuvent contenir uniquement des caractres
alphanumriques.
4. Slectionnez le groupe ainsi que la langue par dfaut du Slectionne le nom et la langue de lutilisateur.
nouvel utilisateur.
5. Recommencez les oprations 3 et 4 pour chaque Ajoute dautres utilisateurs.
utilisateur que vous voulez ajouter.
6. Cliquez sur Appliquer. Enregistre tous les paramtres dun compte utilisateur.

Tableau 5 : Comptes et mots de passe EGX

Compte Mot de passe par dfaut


Administrator Gateway
Guest Guest
Comptes personnaliss (jusqu 11 comptes) Aucune valeur par dfaut Le mot de passe
personnalis est dfini par lutilisateur.

Figure 8 : Page Comptes utilisateur

Accs aux pages Web

Action Rsultat
1. la page Configuration, cliquez sur Accs aux pages Web. Ouvre la page Accs aux pages Web.
2. Dans la ligne Ethernet et TCP/IP, slectionnez le niveau daccs Voir le Tableau 6 pour une explication des
(Aucun, Lecture seule ou Complet) de chaque utilisateur de la niveaux daccs de chaque groupe.
page Web Ethernet et TCP/IP.

8 2006-2012 Schneider Electric. Tous droits rservs.


63230-319-204B1 Passerelle Ethernet PowerLogic EGX100
08/2012 Configuration

Action Rsultat
3. Pour autoriser le compte Guest accder la page Web, Permet au groupe par dfaut Guest daccder
slectionnez Lecture seule sous la colonne Guest. la page Web.
REMARQUE : Si le groupe Guest est en lecture seule, les autres
groupes peuvent tre configurs uniquement en Lecture seule ou
en accs Complet.
4. Recommencez les tapes 2 et 3 pour les lignes Port srie, Liste Slectionne le niveau daccs chaque page
des appareils, Statistiques et Lecture de registres dappareils. Web.
5. Cliquez sur Appliquer. Enregistre la configuration des mots de passe.

Tableau 6 : Accs des groupes

Groupe Accs
Administrator Accs complet toutes les pages Web.
REMARQUE : Il est recommand de changer le mot de passe par dfaut du compte
Administrateur lors de la premire connexion.
Guest Accs en lecture seule aux pages Web slectionnes.
Trois groupes En choisissant parmi les options ci-dessous, ladministrateur attribue des niveaux daccs
personnaliss dfinis par aux pages Web pour chaque groupe. Les niveaux daccs sont les suivants :
lutilisateur
Aucun : Le groupe ne peut pas accder la page Web slectionne.
Lecture seule : Le mot de passe autorise laccs en lecture seule du groupe la page
Web slectionne.
Complet : Le groupe a le mme droit daccs que le groupe Administrator la page
Web slectionne.

Figure 9 : Page Accs aux pages Web

Filtrage Modbus TCP/IP


Cette fonction permet ladministrateur de spcifier les appareils clients Modbus TCP/IP qui
ont accs ou non aux appareils esclaves en srie connects la passerelle EGX.
REMARQUE : Il existe une adresse anonyme Modbus TCP/IP (***.***.***.***) quil est
possible de configurer en lecture seule ou sans droit daccs. La configuration en Lecture
seule permet nimporte quel client Modbus TCP/IP ne figurant pas dans la liste filtre
daccder en lecture seule aux appareils srie esclave. La configuration sans droit daccs
(Aucun) bloque tous les clients Modbus TCP/IP qui ne figurent pas dans la liste filtre.

Action Rsultat
1. la page Configuration, cliquez sur Ouvre la page Filtrage Modbus TCP/IP.
Filtrage Modbus TCP/IP.
2. Slectionnez loption Activer le filtrage. Active le filtrage.
3. Dans la colonne Adresse IP, saisissez Saisit ladresse IP dun client Modbus TCP/IP qui accdera aux
ladresse client Modbus TCP/IP. appareils srie connects la passerelle EGX.
4. Dans la colonne Niveau daccs, Slectionne le niveau daccs pour chaque adresse IP
slectionnez Lecture seule ou Complet. correspondante. En Lecture seule, seuls les codes de fonctions
Modbus TCP/IP suivants sont autoriss :
Dcimal : 1, 2, 3, 4, 7, 8, 11, 12, 17, 20, 24, 43, 100
Hexadcimal : 01, 02, 03, 04, 07, 08, 0B, 0C, 11, 14, 18, 2B, 64
5. Recommencez les tapes 3 et 4 pour Ajoute dautres adresses IP filtrer.
ajouter dautres adresses IP.
6. Cliquez sur Appliquer. Enregistre la liste de filtrage des adresses Modbus TCP/IP.

2006-2012 Schneider Electric. Tous droits rservs. 9


Passerelle Ethernet PowerLogic EGX100 63230-319-204B1
Configuration 08/2012

Figure 10 : Page Filtrage Modbus TCP/IP

Paramtres SNMP
Ladministrateur rseau peut utiliser un gestionnaire SNMP pour accder distance la
passerelle EGX et consulter ltat et les diagnostics rseau au format MIB2.

Action Rsultat
1. la page Configuration, cliquez sur Paramtres Ouvre la page Paramtres SNMP.
SNMP.
2. Slectionnez loption Activer SNMP pour activer le Active le protocole SNMP.
protocole SNMP.
REMARQUE : Si vous ne cochez pas cette case et
cliquez sur Appliquer, la passerelle EGX redmarre et
la fonctionnalit SNMP est dsactive.
3. Saisissez le contact systme, le nom et Saisit les informations SNMP du systme et les noms
lemplacement du systme, le nom de la communaut daccs des communauts.
en lecture seule et le nom de la communaut en
lecture/criture.
4. Cliquez sur Appliquer. Enregistre la configuration SNMP.

Figure 11 : Page Paramtres SNMP

10 2006-2012 Schneider Electric. Tous droits rservs.


63230-319-204B1 Passerelle Ethernet PowerLogic EGX100
08/2012 Configuration

Point daccs systme


La fonction Point daccs systme permet la passerelle EGX100 de multidiffuser sa
prsence toutes les passerelles EGX300 connectes au rseau. Cette fonction est active
par dfaut et ne ncessite pas dautre configuration.
Utilisez lcran de configuration de la Figure 12, page 11 pour saisir ladresse IP de groupe
et dautres informations connexes.

Action Rsultat
1. Dans le menu Configuration, cliquez sur Point Affiche la fentre Point daccs systme.
daccs systme.
2. Spcifiez les paramtres Port UDP, Adresse IP de Slectionne les paramtres Point daccs systme.
groupe, Intervalle Hello, Temps de retenue, Dure de
vie pour multidiffusion et Communaut. Consultez le
Tableau 7 pour la description de ces paramtres.
3. Cliquez sur Appliquer. Applique les paramtres la passerelle EGX100.
REMARQUE : Pour rtablir les paramtres par
dfaut, cliquez sur Valeurs par dfaut, puis sur
Appliquer.

Tableau 7 : Paramtres Point daccs systme

Option Description Valeur


Activ Lorsque cette option est active, les passerelles EGX300 Activ, dsactiv
peuvent dtecter les passerelles EGX100 qui utilisent la Par dfaut : Activ
mme adresse IP de groupe.
Port UDP Permet de dfinir le numro du port UDP utilis pour la 1 65535
dtection par le Point daccs systme. Par dfaut : 59
Adresse IP de groupe Vous pouvez entrer dans ce champ une adresse pour Par dfaut : 224.0.1.2
multidiffusion ou monodiffusion.
Intervalle Hello Intervalle entre deux messages Hello envoys par cette 1 65534 secondes
passerelle EGX100 pour annoncer sa prsence aux autres Par dfaut : 300 secondes
appareils Schneider Electric dtects par le Point daccs
systme sur le rseau.
Temps de retenue Dlai dattente maximum aprs le dernier message Hello 2 65535 secondes
envoy par cette EGX100 avant que les autres appareils ne Par dfaut : 600 secondes
la considrent comme indisponible.
Dure de vie pour Permet de spcifier la portion du rseau sur laquelle 1 255 sauts de routeur
multidiffusion portera la dtection des autres appareils. Cette valeur est Par dfaut : 1
dtermine par le nombre de fois que la multidiffusion peut
tre rexpdie aux autres appareils.
Communaut Les appareils dun groupe peuvent tre rpartis en 0 65535
communauts. Les passerelles EGX300 peuvent dtecter Par dfaut : 0
les passerelles EGX100 qui utilisent la mme adresse IP de
groupe et le mme numro de communaut.

Si vous rglez le numro de communaut sur 0, la


passerelle pourra dtecter toutes les autres passerelles
EGX100 ayant la mme adresse IP, quel que soit le
paramtre de communaut.

Figure 12 : Point daccs systme

2006-2012 Schneider Electric. Tous droits rservs. 11


Passerelle Ethernet PowerLogic EGX100 63230-319-204B1
Diagnostics 08/2012

Diagnostics
Pour accder aux liens de la page Web Diagnostics, cliquez sur Diagnostics dans la barre
de menus EGX.

Statistiques
Action Rsultat
1. la page Diagnostics, cliquez sur Statistiques. Ouvre la page Statistiques (voir Figure 13).
REMARQUE : La page Statistiques affiche des donnes
bases sur le mode slectionn dans Port srie , page 5.
2. Affichez les donnes. Voir Interprtation des statistiques , page 13.
3. Cliquez sur Rinitialiser. Remet zro les donnes de diagnostic de la passerelle EGX.

REMARQUE : Cette page affiche les mesures accumules depuis la dernire activation de
la passerelle EGX. En cas de perte de lalimentation de la passerelle, toutes les valeurs
cumules se remettent zro.

Figure 13 : Page Statistiques


Lecture avec un port srie en MODE MATRE Lecture avec un port srie en MODE ESCLAVE

12 2006-2012 Schneider Electric. Tous droits rservs.


63230-319-204B1 Passerelle Ethernet PowerLogic EGX100
08/2012 Diagnostics

Interprtation des statistiques

Statistiques Description
Ethernet
tat de liaison Chane de caractres qui reprsente la vitesse de transmission et le paramtre
duplex utiliss pour communiquer avec un autre appareil.
Trames transmises avec Compteur qui augmente dune unit chaque fois quune trame est envoye sans
succs problme.
Collisions Compteur qui augmente dune unit chaque fois quune trame est retransmise
cause de la dtection dune collision.
Excs de collisions Compteur qui augmente dune unit chaque fois quil est impossible denvoyer une
trame, car le nombre maximal de collisions bas sur lalgorithme de repli exponentiel
binaire par troncature est atteint.
Trames reues avec succs Compteur qui augmente dune unit chaque fois quune trame est reue sans
problme.
Erreurs CRC Compteur qui augmente dune unit chaque rception dune trame dont la somme
de contrle/CRC (contrle par redondance cyclique) ne correspond pas la valeur
calcule.
Erreurs dalignement Compteur qui augmente dune unit chaque rception dune trame dont la somme
de contrle/CRC (contrle par redondance cyclique) est errone et qui ne se termine
pas sur une limite sur 8 bits.
Longueur de trame excessive Compteur qui augmente dune unit chaque rception dune trame suprieure la
taille maximale autorise dfinie dans les normes (trames suprieures 1518
octets).
Longueur de trame insuffisante Compteur qui augmente dune unit chaque rception dune trame infrieure la
taille minimale autorise dfinie dans les normes (trames infrieures 64 octets).
Modbus TCP/IP
Trames envoyes Compteur qui augmente dune unit chaque envoi dune trame.
Trames reues Compteur qui augmente dune unit chaque rception dune trame.
Erreurs de protocole Compteur qui augmente dune unit chaque rception dun message de format
incorrect.
Connexions actives1 Valeur qui indique le nombre de connexions actives lors de la mise jour de la page
de diagnostics. Prise en charge de 32 connexions maximum. Cliquez sur
Connexions actives pour ouvrir une nouvelle fentre qui affiche la liste de toutes les
connexions client actives.
Connexions cumules1 Compteur qui augmente dune unit chaque connexion tablie avec la passerelle
EGX.
Nombre maximal de Valeur qui indique le nombre maximal de connexions qui taient actives un instant
connexions1 donn.
Messages de lecture en Compteur qui augmente dune unit chaque rception dun message de demande
arrive1 de lecture.
Messages de lecture en Compteur qui augmente dune unit chaque envoi dun message de demande de
partance2 lecture.
Messages dcriture en Compteur qui augmente dune unit chaque rception dun message de demande
arrive1 dcriture.
Messages dcriture en Compteur qui augmente dune unit chaque envoi dun message de demande
partance2 dcriture.
Messages de rponse en Compteur qui augmente dune unit chaque rception dun message de rponse.
arrive2
Messages de rponse en Compteur qui augmente dune unit chaque envoi dun message de rponse.
partance1
Port srie
Trames envoyes Compteur qui augmente dune unit chaque envoi dune trame.
Trames reues Compteur qui augmente dune unit chaque rception dune trame.
Erreurs CRC Compteur qui augmente dune unit chaque rception dun message dont le
contrle par redondance cyclique (CRC) ne correspond pas la valeur calcule.
Indique gnralement des problmes de cblage.
Erreurs de protocole Compteur qui augmente dune unit chaque rception dun message de format
incorrect.
1
Disponible lorsque le port srie fonctionne en mode Matre.
2
Disponible lorsque le port srie fonctionne en mode Esclave.

2006-2012 Schneider Electric. Tous droits rservs. 13


Passerelle Ethernet PowerLogic EGX100 63230-319-204B1
Diagnostics 08/2012

Statistiques Description
Dlais dattente Compteur qui augmente dune unit chaque fois quun message ne reoit aucune
rponse dans le temps imparti. Il sagit en gnral de la consquence derreurs de
configuration ou dun appareil dfaillant.
Messages de lecture en Compteur qui augmente dune unit chaque rception dun message de demande
arrive2 de lecture.
Messages de lecture en Compteur qui augmente dune unit chaque envoi dun message de demande de
partance1 lecture.
Messages dcriture en Compteur qui augmente dune unit chaque rception dun message de demande
arrive2 dcriture.
Messages dcriture en Compteur qui augmente dune unit chaque envoi dun message de demande
partance1 dcriture.
Informations sur la passerelle
Version du logiciel embarqu Version du logiciel embarqu install sur la passerelle EGX.
Dlai dinactivit du systme Priode moyenne dinactivit du processeur exprime en pourcentage (0 100 %).
Adresse MAC Adresse matrielle Ethernet dune passerelle EGX.
Numro de srie Numro de srie de la passerelle EGX.
Numro de modle Numro du modle de la passerelle EGX (100).
Version de matriel Version matrielle de la passerelle EGX.
Date de fabrication Date de fabrication de la passerelle EGX.
1
Disponible lorsque le port srie fonctionne en mode Matre.
2 Disponible lorsque le port srie fonctionne en mode Esclave.

Lecture de registres dappareils

Action Rsultat
1. la page Diagnostics, cliquez sur Lecture de registres Ouvre la page Lecture de registres
dappareils. dappareils.
2. Saisissez lidentificateur de lappareil (ID), le numro du registre Saisit les valeurs de dbut de lecture des
de dpart et le nombre de registres lire. registres de lappareil spcifi.
3. Slectionnez un type de donnes. Slectionne le type de donnes afficher.
4. Pour modifier laffichage des donnes dans la colonne Valeur, Slectionne le mode daffichage des valeurs.
slectionnez Dcimal, Hexadcimal, Binaire ou ASCII.
5. Cliquez sur Lecture. Affiche les donnes requises.

Tableau 8 : Paramtres de lecture de registres dappareils EGX

Option Description Valeur par dfaut


Identification de lappareil Adresse de lappareil dans lequel les registres sont lus. 1
Registre de dpart Premier registre lire. 1000
Nombre de registres Nombre de registres lire (1 10). 10
Colonne Registre Liste des numros de registres.
Colonne Valeur Liste des donnes enregistres dans un registre. Les valeurs
rcupres dpendent de lappareil connect la passerelle
EGX. Reportez-vous la documentation de lappareil connect
pour plus dinformations sur les valeurs stockes dans un
registre.
Type de donnes Permet de slectionner les registres de maintien, les registres Registres de
dentre, les bobines de sortie, les bobines dentre ou maintien
lidentification dappareil pour spcifier les valeurs rcupres.
Options Dcimal, Slection dune option pour spcifier laffichage des donnes Dcimal
Hexadcimal, Binaire ou ASCII de la colonne Valeur.

14 2006-2012 Schneider Electric. Tous droits rservs.


63230-319-204B1 Passerelle Ethernet PowerLogic EGX100
08/2012 Logiciel embarqu (firmware)

Figure 14 : Page Lecture de registres dappareils

Logiciel embarqu (firmware)


Vous pouvez mettre niveau le logiciel embarqu (firmware) de la passerelle EGX au
moyen du protocole FTP (File Transfer Protocol). Rendez-vous sur le site
www.powerlogic.com ou consultez votre reprsentant local pour obtenir la dernire mise
jour du logiciel embarqu.

Recherche de la version du logiciel embarqu

Action Rsultat
1. Connectez-vous la passerelle EGX. Ouvre la page daccueil EGX.
2. Recherchez la version du logiciel embarqu en bas Dtermine la version du logiciel embarqu de la
gauche de la page. passerelle EGX.
REMARQUE : Si vous avez rcemment mis jour le
logiciel embarqu, appuyez sur la touche F5 pour
actualiser la page et afficher le nouveau numro de
version.
3. Vous pouvez galement slectionner Diagnostics > Dtermine galement la version du logiciel embarqu de
Statistiques pour rechercher la version du logiciel la passerelle EGX.
embarqu dans la section Informations sur la
passerelle.

Obtention du dernier logiciel embarqu

Action Rsultat
1. Lancez Internet Explorer. Dans la zone Adresse, Ouvre le site Web de PowerLogic.
tapez www.powerlogic.com, puis appuyez sur Entre.
2. Slectionnez votre pays, puis cliquez sur Go Affiche le site PowerLogic de votre pays.
(atteindre).
REMARQUE : Si vous slectionnez les tats-Unis,
allez ltape 3. Dans le cas contraire, suivez les
tapes spcifiques chaque pays pour obtenir le
logiciel embarqu de la passerelle EGX.
3. Cliquez sur Firmware Downloads (tlchargements Affiche les tlchargements EGX100 disponibles.
du logiciel embarqu) > Products (produits) >
PowerLogic Communications > EGX100.

2006-2012 Schneider Electric. Tous droits rservs. 15


Passerelle Ethernet PowerLogic EGX100 63230-319-204B1
Logiciel embarqu (firmware) 08/2012

Action Rsultat
4. Cliquez sur le lien EGX100 Firmware (logiciel Ouvre la page dinstructions pour le logiciel embarqu de
embarqu EGX100). la passerelle EGX100.
5. Cliquez sur longlet Files (fichiers), puis sur le lien Affiche les noms de fichier, puis ouvre la bote de dialogue
vers le fichier du logiciel embarqu (eg#####.bin, de tlchargement de fichier.
o ##### correspond au numro de logiciel
embarqu).
REMARQUE : Vous devez vous identifier pour
tlcharger des fichiers de logiciel embarqu. Si vous
navez pas encore de nom dutilisateur et de mot de
passe, suivez les instructions fournies sur le site.
6. Cliquez sur Enregistrer. Enregistre le fichier de logiciel embarqu.

Mise jour du logiciel embarqu

Action Rsultat
1. Lancez Internet Explorer, tapez ftp:// et ladresse IP Ouvre la bote de dialogue Ouvrir une session en tant
de la passerelle EGX dans la barre dadresse (ex. : que.
ftp://169.254.0.10), puis appuyez sur Entre.
2. Tapez le nom dutilisateur Administrator et le mot de Ouvre une session FTP avec la passerelle EGX.
passe correspondant dans les zones de texte
appropries, puis cliquez sur Connexion.
3. Localisez le fichier du logiciel embarqu sur votre Copie le fichier dans le Presse-papiers.
ordinateur, cliquez avec le bouton droit sur le fichier,
puis cliquez sur Copier.
4. Cliquez avec le bouton droit de la souris dans la Copie le logiciel embarqu dans la passerelle EGX, qui
fentre Internet Explorer, puis cliquez sur Coller. redmarre.
REMARQUE : Au lieu de copier/coller le fichier du
logiciel embarqu, vous pouvez le faire glisser dans
Internet Explorer.
5. Cliquez sur Fermer dans la fentre Internet Explorer. Ferme Internet Explorer et met fin la connexion FTP
avec la passerelle EGX.
6. Pour vrifier que la mise jour a russi, suivez la Vrifie la mise jour du logiciel embarqu.
procdure dcrite la section Recherche de la
version du logiciel embarqu , page 15.

16 2006-2012 Schneider Electric. Tous droits rservs.


63230-319-204B1 PowerLogic Ethernet Gateway EGX100
08/2012 Index

Index

A R
accs la passerelle EGX via un rseau 2 registres dappareils 14
accs aux pages Web lecture 14
configuration 8 rseau
accs via 2
C ressources supplmentaires 2
comptes utilisateurs
configuration 8 S
configuration de la liste des appareils en statistiques 12
mode Esclave 7 interprtation 13
configuration de la liste des appareils en
mode Matre 6
connexion la passerelle EGX 2

D
dconnexion 2
dtection des adresses IP identiques 4
diagnostics 12

E
EGX
configuration 3
connexion 2
interface utilisateur 3

F
filtrage Modbus TCP/IP
configuration 9

I
interface utilisateur 3
introduction 1

L
liste des appareils
configuration 6
mode Esclave 7
mode Matre 6
logiciel embarqu (firmware) 15
mise jour 15
obtention de la dernire version 15
recherche de la version 15

M
matriel 1

P
paramtres Ethernet et TCP/IP 3
paramtres SNMP
configuration 10
point daccs systme
configuration 11
port srie
configuration 5
protocoles Ethernet 1
pris en charge 1

2006-2012 Schneider Electric. Tous droits rservs. 17


PowerLogic Ethernet Gateway EGX100 63230-319-204B1
Index 08/2012

18 2006-2012 Schneider Electric. Tous droits rservs.


Passerelle Ethernet PowerLogic EGX100
Manuel de lutilisateur

PowerLogic est une marque commerciale de Schneider Electric en France, aux


tats-Unis et dans dautres pays. Les autres marques de commerce sont la proprit
de leurs dtenteurs respectifs.
Schneider Electric
35 rue Joseph Monier 63230-319-204B1 08/2012
92500 Rueil-Malmaison, France Remplace le manuel 63230-319-204A2 12/2008
www.schneider-electric.com 2006-2012 Schneider Electric. Tous droits rservs.
PowerLogic Ethernet Gateway EGX100
Benutzerhandbuch

63230-319-204B1
08/2012
Sicherheitshinweise

Wichtige Informationen
Lesen Sie die Anweisungen sorgfltig durch und sehen Sie sich die Ausrstung
genau an, um sich mit dem Gert vor der Installation, dem Betrieb oder der
Wartung vertraut zu machen. In dieser Publikation oder auf dem Gert knnen sich
folgende Hinweise befinden, die vor potenziellen Gefahren warnen oder die
Aufmerksamkeit auf Informationen lenken, die ein Verfahren erklren oder
vereinfachen.

Der Zusatz eines der beiden Symbole zu den Sicherheitshinweisen Gefahr oder
Warnung deutet auf eine elektrische Gefahr hin, die zu schweren Verletzungen
fhren kann, wenn die Anweisungen nicht befolgt werden.

Dieses Symbol steht fr eine Sicherheitswarnung. Es macht auf die potenzielle


Gefahr eines Personenschadens aufmerksam. Beachten Sie alle Sicherheitshin-
weise mit diesem Symbol, um schwere oder tdliche Verletzungen zu vermeiden.

GEFAHR weist auf eine unmittelbar gefhrliche Situation hin, die bei Nichtbeachtung zu
schweren bzw. tdlichen Verletzungen fhrt.

WARNUNG weist auf eine potenziell gefhrliche Situation hin, die bei Nichtbeachtung zu
schweren bzw. tdlichen Verletzungen fhren kann.

ACHTUNG weist auf eine potenziell gefhrliche Situation hin, die bei Nichtbeachtung zu
leichten Verletzungen fhren kann.

HINWEIS bezieht sich auf Vorgehensweisen, die keine Verletzungen verursachen knnen.
Daher wird das Symbol fr Sicherheitswarnungen nicht zusammen mit diesem Signalwort
verwendet.

Bitte beachten
Elektrisches Gert sollte stets von qualifiziertem Personal installiert, betrieben und
gewartet werden. Schneider Electric bernimmt keine Verantwortung fr jegliche
Konsequenzen, die sich aus der Verwendung dieser Publikation ergeben knnen.

Eine qualifizierte Person verfgt ber entsprechende Fhigkeiten und Wissen in


Bezug auf Aufbau, Installation und Betrieb elektrischer Gerte und hat eine
Sicherheitsschulung zur Erkennung und Vermeidung der damit verbundenen
Gefahren absolviert.
Hinweise

Hinweis zum Teil 15 der FCC-Bestimmungen


Dieses Gert wurde getestet und erfllt die Anforderungen fr digitale Gerte der
Klasse A gem Teil 15 der FCC-Bestimmungen. Diese Bestimmungen sollen bei
der gewerblichen Nutzung des Gerts einen angemessenen Schutz gegen
schdliche Funkstrungen sicherstellen. Dieses Gert erzeugt und nutzt Energie
im Funkfrequenzspektrum und kann solche auch abstrahlen. Wird es nicht der
Anleitung entsprechend installiert, kann es schdliche Funkstrungen verursachen.
Die Verwendung dieses Gerts in einem Wohngebiet kann schdliche Funkst-
rungen verursachen. In diesem Fall ist der Benutzer dafr verantwortlich, die
Strungen auf eigene Kosten zu beseitigen. Dieses digitale Gert der Klasse A
erfllt die Anforderungen der kanadischen Norm ICES-003 (Interference-Causing
Equipment Standard).
63230-319-204B1 PowerLogic Ethernet Gateway EGX100
08/2012 Inhaltsverzeichnis

Inhaltsverzeichnis
Einfhrung ...................................................................................................................... 1
Untersttzte Ethernet-Protokolle ...................................................................................... 1
Hardware .......................................................................................................................... 1
Zustzliche Ressourcen ................................................................................................... 2
Zugang zum EGX ber ein Netzwerk ............................................................................ 2
Anmelden beim EGX ........................................................................................................ 2
Abmeldung ....................................................................................................................... 2
EGX-Benutzeroberflche berblick ........................................................................... 3
Setup ............................................................................................................................... 3
Ethernet- und TCP/IP-Einstellungen ................................................................................ 3
Erkennung identischer IP-Adressen ............................................................................. 4
Serielle Schnittstelle ......................................................................................................... 5
Gerteliste ........................................................................................................................ 6
Gerteliste fr Master-Modus einrichten....................................................................... 6
Gerteliste fr Slave-Modus einrichten......................................................................... 7
Benutzerkonten ................................................................................................................ 8
Webseitenzugriff ............................................................................................................... 8
Modbus-TCP/IP-Filter ....................................................................................................... 9
SNMP-Parameter ........................................................................................................... 10
Systemzugangspunkt ..................................................................................................... 11
Diagnose ....................................................................................................................... 12
Statistik ........................................................................................................................... 12
Statistik auswerten...................................................................................................... 13
Gerteregister lesen ....................................................................................................... 14
Firmware ....................................................................................................................... 15
Firmwareversion feststellen ............................................................................................ 15
Neue Firmware herunterladen ........................................................................................ 15
Firmwaredatei aktualisieren ........................................................................................... 16
Index ............................................................................................................................... 17

2006-2012 Schneider Electric. Alle Rechte vorbehalten. i


PowerLogic Ethernet Gateway EGX100 63230-319-204B1
Inhaltsverzeichnis 08/2012

ii 2006-2012 Schneider Electric. Alle Rechte vorbehalten.


63230-319-204B1 PowerLogic Ethernet Gateway EGX100
08/2012 Einfhrung

Einfhrung
Dieses Handbuch ist mit einem PowerLogic EGX100 mit Firmwareversion 3.0 oder hher
zu benutzen. Informationen zur Installation enthlt das Installationshandbuch.
Das EGX100 ist ein Kommunikationsgert, welches die Vernetzung zwischen Ethernet
(Modbus TCP/IP) und seriellen Gerten ermglicht, indem Modbus-TCP/IP-Clients auf
Informationen von seriellen Slave-Gerten zugreifen knnen. Es ermglicht auch den Zugriff
serieller Master-Gerte auf Informationen von Slave-Gerten, die ber ein Ethernet-
Netzwerk verteilt sind.

Untersttzte Ethernet-Protokolle
Das EGX untersttzt folgende Ethernet-Protokolle:
Modbus-TCP/IP: Modbus TCP/IP ist eine Kombination aus dem Modbus-Protokoll, das
die Master-Slave-Kommunikation zwischen Gerten ermglicht, und TCP/IP, das fr die
Kommunikation ber eine Ethernet-Verbindung sorgt. Modbus TCP/IP wird fr den
Datenaustausch zwischen dem EGX und anderen kompatiblen Modbus-TCP/IP-Gerten
ber TCP-Port 502 verwendet.
Hypertext Transfer Protocol (HTTP): HTTP ist ein Netzwerkprotokoll, das die
bertragung von Dateien und Daten im Internet abwickelt. Es stellt Webserver-
Funktionalitt ber den TCP-Port 80 bereit. Die Fernkonfiguration des EGX und die
Anzeige der Diagnosedaten ist mit einem Webbrowser mglich.
File Transfer Protocol (FTP): FTP ist ein Netzwerkprotokoll, mit dem Dateien ber das
Internet von einem Computer zum anderen bertragen werden knnen. FTP wird ber
den TCP-Port 21 zur bertragung von Firmware-Updates zum EGX benutzt.
Simple Network Management Protocol (SNMP): SNMP basiert auf dem MIB-2-Format
und ermglicht das Speichern und bertragen von Identifikations- und Diagnosedaten,
die fr Netzwerkverwaltungszwecke ber den UDP-Port 161 benutzt werden.
Address Resolution Protocol (ARP): ARP wird zur Konvertierung von IP-Adressen in
Ethernet-Adressen verwendet. ARP-Anfragen werden vom EGX gesendet, um
festzustellen, ob seine IP-Adresse bereits benutzt wird (siehe Erkennung identischer
IP-Adressen auf Seite 4).

Hardware

Ethernet-RJ45-Anschluss

Steuerspannung

Spannungs-
versorgungs-/
Status-LED
Serielle RS485-
Schnittstelle
LEDs fr Ethernet
und serielle
Kommunikations-
schnittstelle
DIP-Schalter zur
Konfiguration von
Vorspannung,
Rcksetz- Leitungsabschluss
taste und 2-/4-Leiter-
Verbindung

Serielle RS232-
Schnittstelle
(RJ45-Anschluss)

2006-2012 Schneider Electric. Alle Rechte vorbehalten. 1


PowerLogic Ethernet Gateway EGX100 63230-319-204B1
Zugang zum EGX ber ein Netzwerk 08/2012

Zustzliche Ressourcen
Unterlagen: Rufen Sie die Website www.powerlogic.com auf und whlen Sie Ihr Land aus.
Whlen Sie Library > PowerLogic Products > Communications > EGX100 Gateway
aus und klicken Sie auf das Dokument, das Sie herunterladen mchten.
HINWEIS: Wenn Sie ein anderes Land als die USA ausgewhlt haben, folgen Sie der
lnderspezifischen Navigation, um die EGX-Dokumentation abzurufen.
Firmware: Siehe Firmware auf Seite 15 fr Informationen zum Herunterladen und
Installieren von neuer Firmware.

Zugang zum EGX ber ein Netzwerk


Nachdem Sie die Ethernet-Parameter eingerichtet haben (siehe Installationshandbuch)
knnen Sie mit Internet Explorer 6.0 oder hher ber ein Ethernet-LAN auf das EGX
zugreifen.

Anmelden beim EGX

Manahme Ergebnis
1. Starten Sie Internet Explorer 6.0 oder hher. Einblendung des Internet Explorers.
2. Geben Sie in das Textfeld Adresse die Adresse Ihres Einblendung des Anmelde-Dialogfelds.
EGX ein (Werkeinstellung: 169.254.0.10) und
drcken Sie die Eingabetaste.
3. Geben Sie in die Textfelder Ihren Benutzernamen Eingabe des Benutzernamens und des Kennworts sowie
(Werkeinstellung: Administrator) und das Kennwort Einblendung der EGX-Startseite.
(Werkeinstellung: Gateway) ein und klicken Sie auf
OK.
4. Klicken Sie auf Setup, um die EGX-Setup-Seite Einblendung der Setup- oder Diagnoseseite
aufzurufen, oder klicken Sie auf Diagnose, um auf
die EGX-Diagnoseseite zuzugreifen.

Abbildung 1: EGX-Startseite

Menleiste

Abmeldung
Es wird empfohlen, dass Sie sich immer dann abmelden, wenn Sie keinen Zugang zum EGX
bentigen.
Um die EGX-Konfigurationssitzung zu beenden und sich abzumelden, klicken Sie auf
Logout.

2 2006-2012 Schneider Electric. Alle Rechte vorbehalten.


63230-319-204B1 PowerLogic Ethernet Gateway EGX100
08/2012 EGX-Benutzeroberflche berblick

EGX-Benutzeroberflche berblick
Das EGX wird mit acht vorinstallierten Webseiten fr die Einrichtung und Konfiguration des
EGX ausgeliefert. Tabelle 1 enthlt eine Beschreibung jeder Webseite.

Tabelle 1: Statische EGX-Webseiten

Siehe
EGX-Webseite Beschreibung
Seite
Setup

Ethernet & TCP/IP Konfiguration der Ethernet- und TCP/IP-Einstellungen. 3


Serielle Schnittstelle Einrichtung oder nderung von seriellen Kommunikationsparametern. 5
Gerteliste Identifizierung der seriellen Gerte in der Gertekette. 6
Benutzerkonten1 Erstellung und Bearbeitung von Gruppen und Benutzern. 8
Webseitenzugriff1 Auswahl der Webseiten-Zugriffsrechte fr jede Benutzergruppe. 8
Modbus-TCP/IP-Filter1 Einrichtung der IP-Adressen, die ber Modbus-TCP/IP auf das EGX zugreifen 9
knnen.
SNMP-Parameter1 Aktivieren und Konfigurieren des SNMP (Simple Network Management 10
Protocol), mit dem sich das EGX Netzwerkgerten gegenber identifizieren
kann, die SNMP Daten anfordern.
Systemzugangspunkt1 Damit kann das EGX100 seine Existenz jedem mit dem Netzwerk 11
verbundenen EGX300 ber Multicast mitteilen.

Diagnose

Statistik Anzeige von Diagnosedaten zur Fehlersuche und -behebung bei 12


Netzwerkproblemen. Diese Seite enthlt auch spezifische Informationen ber
Ihr EGX, einschlielich Seriennummer, Herstellungsdatum und MAC-Adresse.
Gerteregister lesen Ermglicht EGX-Administratoren das Lesen der Registerdaten von einem mit 14
dem EGX verbundenen seriellen Gert.
1
Nur fr den Administrator zugnglich

Setup
Fr den Zugang zu den Links der Setup-Webseiten klicken Sie auf Setup in der
EGX-Menleiste.

Ethernet- und TCP/IP-Einstellungen

Manahme Ergebnis
1. Klicken Sie auf der Setup-Seite auf Ethernet & Einblendung der Ethernet & TCP/IP-Seite.
TCP/IP.
2. Whlen Sie Ihr Rahmenformat und das bertragungs- Auswahl von Rahmenformat und bertragungsmedium.
medium aus. Falls Sie diese Informationen nicht
haben, wenden Sie sich an Ihren
Netzwerkadministrator.
3. Geben Sie Ihre IP-Adresse, die Subnetzmaske und Eingabe der Ethernet-Parameter fr das EGX.
die dem EGX durch Ihren Netzwerkadministrator HINWEIS: Wenn Sie eine IP-Adresse eingeben, die
zugewiesene Standard-Gateway-Adresse ein. bereits verwendet wird, werden Sie zur Auswahl einer
anderen IP-Adresse aufgefordert. Siehe Erkennung
identischer IP-Adressen auf Seite 4.
4. Klicken Sie auf bernehmen. Aktualisierung der Ethernet- und TCP/IP-Einstellungen
des EGX.
* Tabelle 2 auf Seite 4 enthlt eine Liste der Optionen.

HINWEIS: Nachdem Sie die Ethernet-Parameter gendert und auf bernehmen geklickt
haben, startet das EGX neu.

2006-2012 Schneider Electric. Alle Rechte vorbehalten. 3


PowerLogic Ethernet Gateway EGX100 63230-319-204B1
Setup 08/2012

Abbildung 2: Ethernet & TCP/IP-Seite

Tabelle 2: EGX-Ethernet- und TCP/IP-Einstellungen

Option Beschreibung Einstellung


Rahmenformat Auswahl des Formats, in dem Daten ber eine Ethernet II, 802.3 SNAP
Ethernet-Verbindung gesendet werden. Werkeinstellung: Ethernet II
bertragungsmedium Festlegung der physikalischen Ethernet-Verbindung 10T/100Tx Auto
oder des bertragungsmediums. 10BaseT-HD
10BaseT-FD
100BaseTX-HD
100BaseTX-FD
Werkeinstellung: 10T/100Tx Auto
IP-Adresse Eingabe der statischen IP-Adresse des EGX. Werkeinstellung: 169.254.0.10
Subnetzmaske Eingabe der Ethernet-IP-Subnetzmaskenadresse Werkeinstellung: 255.255.0.0
Ihres Netzwerks.
Standard-Gateway Eingabe der Gateway-IP-Adresse (Router) fr WAN- Werkeinstellung: 0.0.0.0
Kommunikation.

Erkennung identischer IP-Adressen


Whrend das EGX an Ihr Netzwerk angeschlossen ist, verffentlicht es seine IP-Adresse.
Zur Vermeidung von Konflikten aufgrund doppelt vergebener IP-Adressen wird vom EGX
das ARP-Protokoll (Address Resolution Protocol) benutzt. Damit wird festgestellt, ob ein
anderes Gert in Ihrem Netzwerk die gleiche IP-Adresse verwendet. In der nachstehenden
Tabelle 3 wird erlutert, wie das EGX mit einer doppelt vergebenen IP-Adresse umgeht,
sobald es sie erkannt hat.

Tabelle 3: Szenarien fr Erkennung doppelter IP-Adressen

Spannungsversorgungs-/
Szenario Doppelte IP-Adresse erkannt
Status-LED

Boot-Prozess/ Das EGX kehrt zur voreingestellten IP- Muster aus vier Blinkzeichen und
Wiederherstellung der Adresse, Subnetzmaske und Gateway- einer Pause
Spannungsversorgung Adresse zurck. ARP-Anfragen werden alle
15 Sekunden gesendet, bis die IP-Adresse
Ethernet-Verbindung erkannt
verfgbar ist. Sobald die IP-Adresse verfgbar
ist, wird sie vom EGX verwendet.
Manuelle Adressennderung Das EGX behlt die vorherige IP-Adresse bei
und zeigt durch eine Meldung an, dass die IP-
Adresse bereits von einem anderen Gert
verwendet wird.
Empfang einer ARP-Anfrage Das EGX kehrt zur voreingestellten IP- Muster aus vier Blinkzeichen und
Adresse, Subnetzmaske und Gateway- einer Pause
Adresse zurck, wenn ein angeschlossenes
Gert vier ARP-Anfragen bezglich der IP-
Adresse des EGX sendet. Das EGX sendet
alle 15 Sekunden ARP-Anfragen, bis die IP-
Adresse wieder verfgbar ist. Sobald die IP-
Adresse verfgbar ist, wird sie vom EGX
verwendet.

4 2006-2012 Schneider Electric. Alle Rechte vorbehalten.


63230-319-204B1 PowerLogic Ethernet Gateway EGX100
08/2012 Setup

Serielle Schnittstelle
Manahme Ergebnis
1. Klicken Sie auf der Setup-Seite auf Serielle Einblendung der Seite Serielle Schnittstelle.
Schnittstelle.
2. Whlen Sie Ihren Modus, die physikalische Auswahl der Optionen fr die serielle Schnittstelle.
Schnittstelle, den bertragungsmodus, die Baudrate,
die Paritt und die Antwort-Zeitberschreitung aus
(siehe Tabelle 4 auf Seite 5).
3. Wenn Sie den Slave-Modus auswhlen, geben Sie Eingabe der IP-Adressen der entfernten Gerte.
die IP-Adresse fr die angeschlossenen, abgesetzten
Gerte ein (siehe Tabelle 4 auf Seite 5).
4. Klicken Sie auf bernehmen. Aktualisierung der Einstellungen der seriellen EGX-
Schnittstelle.

Abbildung 3: Seite Serielle Schnittstelle

Tabelle 4: Einstellungen der seriellen Schnittstelle


Option Beschreibung Einstellung
Modus Hier wird festgelegt, wie die COM-Schnittstelle am Master, Slave
EGX verwendet wird (Master oder Slave). Werkeinstellung: Master
HINWEIS: Wird der Modus gendert, startet das
EGX neu.
Physikalische Auswahl der physikalischen Verdrahtung der RS485 4-Draht, RS485 2-Draht oder
Schnittstelle seriellen EGX-Schnittstelle. RS232
Werkeinstellung: RS485 2-Draht
bertragungsmodus Hier wird festgelegt, wie Daten ber die serielle Master-Modus: Automatisch,
Verbindung bertragen werden. Modbus ASCII
Slave-Modus: Modbus RTU, Modbus
ASCII
Werkeinstellung:
Master-Modus: Automatisch
Slave-Modus: Modbus RTU

HINWEIS: Im Automatikmodus kann


das Gert mit Modbus-RTU-, Jbus-
und PowerLogic (SY/MAX)-Slave-
Gerten in der gleichen Gertekette
kommunizieren.

Baudrate Hier wird die Geschwindigkeit der Datenbertragung 2400, 4800, 9600, 19200, 38400,
ber die serielle Verbindung festgelegt. 56000*, 57600*
Werkeinstellung: 19200
Paritt Hier wird festgelegt, ob die Daten mit einem Paritts- Gerade, Ungerade, Keine
Bit auf Richtigkeit geprft werden sollen. Werkeinstellung: Gerade
Antwort- Dieser Parameter legt fest, wie lange das EGX auf 0,1 bis 10 Sekunden
Zeitberschreitung den Empfang einer Antwort von einem seriellen Werkeinstellung: 3 Sekunden
Gert wartet.
Remote-Modbus- Damit wird eine Liste mit Modbus-TCP/IP-Adressen
TCP/IP-Verbindungen fr das EGX zur Verwendung whrend der Slave-
(nur Slave-Modus) Modus-Kommunikation festgelegt.
* Nur verfgbar, wenn die physikalische Schnittstelle bzw. der bertragungsmodus auf RS232/Modbus ASCII
eingestellt ist.

2006-2012 Schneider Electric. Alle Rechte vorbehalten. 5


PowerLogic Ethernet Gateway EGX100 63230-319-204B1
Setup 08/2012

Gerteliste
Beachten Sie vor Beginn Folgendes:
Bei Master-Modus fr die COM-Schnittstelle:
Modbus-RTU/Jbus-Gerte mssen nicht in die Gerteliste eingetragen werden, aber ein
Eintrag erleichtert die Verwaltung Ihres Systems.
PowerLogic-Protokollgerte (SY/MAX) mssen in die Gerteliste eingetragen werden.
HINWEIS: Verwenden Sie die seriellen Slave-Adressen 1 bzw. 16 nicht im automatischen
bertragungsmodus in einer Gertekette mit gemischten Protokollen (beispielsweise bei
einer Gertekette mit Gerten, von denen einige das PowerLogic-Protokoll und andere ein
Modbus-RTU/Jbus-Protokoll verwenden).

Gerteliste fr Master-Modus einrichten


Abbildung 4: Master-Modus-Topologie

Ethernet-
Verbindung

EGX im
Master-
Modus
Bis zu
RS485-Verbindung 128 serielle
Slave-Gerte
mit Repeatern

Serielle Slave-Gerte

Wenn Sie auf der Seite Serielle Schnittstelle den Master-Modus ausgewhlt haben, fhren
Sie die nachstehenden Schritte zur Einrichtung der Gerteliste aus:

Manahme Ergebnis
1. Klicken Sie auf der Setup-Seite auf Gerteliste. Einblendung der Seite Gerteliste.
2. Whlen Sie die Anzahl der anzuzeigenden Gerte Auswahl der Anzahl sichtbarer Standorte, die zur
(1 bis 128) aus und klicken Sie auf bernehmen. Definition der an das EGX angeschlossenen seriellen
Slave-Gerte benutzt werden knnen.
3. Geben Sie in das Textfeld Lokale ID die lokale ID Eingabe der lokalen Adresse des Gerts.
(Adresse) des seriellen Slave-Gerts ein.
4. Whlen Sie das Protokoll aus. Auswahl des Protokolls fr das angeschlossene Gert.
5. Wiederholen Sie die Schritte 3 und 4, bis alle Gerte Eingabe aller angeschlossenen Gerte.
eingegeben sind.
6. Klicken Sie auf bernehmen. Aktualisierung der Einstellungen in der Gerteliste.

Abbildung 5: Seite Gerteliste im Master-Modus

6 2006-2012 Schneider Electric. Alle Rechte vorbehalten.


63230-319-204B1 PowerLogic Ethernet Gateway EGX100
08/2012 Setup

Gerteliste fr Slave-Modus einrichten


Der Slave-Modus der seriellen Schnittstelle gestattet seriellen Modbus-Master-Gerten den
Zugriff auf Informationen von seriellen Slave-Gerten ber ein TCP/IP-Netzwerk. Die
nachstehende Abbildung 6 zeigt, wie die Gerte mit den Gertelisteneinstellungen in
Abbildung 7 angeschlossen werden.

Abbildung 6: Slave-Modus-Topologie
Ethernet-
Verbindung Es sind bis zu 16 IP-Fernverbindungen
mit bis zu 128 seriellen Slave-Gerten
mglich.
EGX im Slave-
Modus
EGX im Master- EGX im
Modus Master-
Modus
IP-Adresse:
169.254.0.28 IP-Adresse:
169.254.0.75
RS232- oder RS485-
RS485- RS485- Verbindung
Verbindung Verbindung

2 5 2 3 4 5 6 7
Serielle Slave-Gerte Serielle Slave-Gerte

Wenn Sie auf der Seite Serielle Schnittstelle den Slave-Modus ausgewhlt haben, fhren
Sie die nachstehenden Schritte zur Einrichtung der Gerteliste aus:

Manahme Ergebnis
1. Klicken Sie auf der Setup-Seite auf Gerteliste. Einblendung der Seite Gerteliste.
2. Whlen Sie die Anzahl der anzuzeigenden Gerte Auswahl der Anzahl sichtbarer Standorte, die zur
(1 bis 128) aus und klicken Sie auf bernehmen. Definition von Remote-Modbus-TCP/IP-Gerten benutzt
werden knnen.
3. Whlen Sie die Verbindung aus. Auswahl der Modbus-TCP/IP-Adresse zur Verknpfung
mit der Fern-ID.
4. Geben Sie in das Textfeld Lokale ID die lokale ID Eingabe der Adresse des Gerts, welches das lokale
(Adresse) des seriellen Slave-Gerts ein. Modbus-Master-Gert fr den Zugriff auf das abgesetzte
Gert nutzen soll
5. Geben Sie in das Textfeld Fern-ID die Fern-ID Eingabe der seriellen Slave-Adresse des angeschlos-
(Adresse) des seriellen Slave-Gerts ein. senen abgesetzten Gerts.

6. Wiederholen Sie die Schritte 3 bis 5, bis alle Gerte Eingabe aller Zuordnungsinformationen fr das EGX zur
eingegeben sind. Kommunikation mit abgesetzten Gerten.
7. Klicken Sie auf bernehmen. Aktualisierung der Einstellungen in der Gerteliste.

Abbildung 7: Seite Gerteliste im Slave-Modus

2006-2012 Schneider Electric. Alle Rechte vorbehalten. 7


PowerLogic Ethernet Gateway EGX100 63230-319-204B1
Setup 08/2012

Benutzerkonten
EGX-Benutzern werden Benutzernamen und Kennwrter zugewiesen. Jeder Benutzer
gehrt zu einer Gruppe, und jede Gruppe besitzt Zugriffsrechte auf die EGX-Webseiten, die
vom EGX-Administrator zugewiesen wurden.
HINWEIS: Es gibt zwei Standard-Benutzerkonten: Administrator (Kennwort: Gateway) und
Guest (Kennwort: Guest).

Manahme Ergebnis
1. Klicken Sie auf der Setup-Seite auf Benutzerkonten. Einblendung der Seite Benutzerkonten.
2. Wenn Sie einen Gruppennamen ndern wollen, Eingabe eines neuen Gruppennamens.
geben Sie den neuen Namen in eines der Textfelder
Gruppen ein (der Administrator-Gruppenname kann
nicht gendert werden).
3. Geben Sie im Bereich Benutzer einen Namen (1 bis Eingabe des Namens und des Kennworts fr einen
24 Zeichen) und ein Kennwort (0 bis 12 Zeichen) fr Benutzer.
einen neuen Benutzer ein.
HINWEIS: Benutzernamen und Kennwrter
bercksichtigen Gro- und Kleinschreibung und
knnen nur alphanumerische Zeichen enthalten.
4. Whlen Sie eine Gruppe und die Standardsprache fr Auswahl der Gruppe und der Sprache fr einen Benutzer.
den neuen Benutzer aus.
5. Wiederholen Sie die Schritte 3 und 4 fr jeden Hinzufgen weiterer Benutzer.
zustzlichen Benutzer, den Sie hinzufgen wollen.
6. Klicken Sie auf bernehmen. Speicherung aller Benutzerkonteneinstellungen.

Tabelle 5: EGX-Konten und -Kennwrter

Konto Standardkennwort
Administrator Gateway
Guest Guest
Benutzerdefinierte Konten (bis zu 11 Konten mglich) Keine Werkeinstellung Kennwort ist
benutzerdefiniert

Abbildung 8: Seite Benutzerkonten

Webseitenzugriff
Manahme Ergebnis
1. Klicken Sie auf der Setup-Seite auf Webseitenzugriff. Einblendung der Seite
Webseitenzugriff.
2. Whlen Sie in der Zeile Ethernet u. TCP/IP die Zugriffsberechtigung Fr eine Erluterung der Zugriffsberech-
(Keine, Schreibgeschtzt oder Vollstndig) fr jede Benutzergruppe fr tigungen fr jede Gruppe siehe die
die Webseite Ethernet & TCP/IP aus. nachstehende Tabelle 6.

8 2006-2012 Schneider Electric. Alle Rechte vorbehalten.


63230-319-204B1 PowerLogic Ethernet Gateway EGX100
08/2012 Setup

Manahme Ergebnis
3. Um einem Gast den Zugriff auf die Webseite zu ermglichen, whlen Sie Erlaubt der Standardgruppe Guest den
in der Spalte Guest die Zugriffsberechtigung Schreibgeschtzt aus. Zugriff auf die Webseite.
HINWEIS: Wenn fr die Gruppe Guest die Zugriffsberechtigung
Schreibgeschtzt eingestellt ist, kann als Zugriffsberechtigung fr
andere Gruppen nur Schreibgeschtzt oder Vollstndig ausgewhlt
werden.
4. Wiederholen Sie die Schritte 2 und 3 fr die Zeilen Serielle Auswahl der Zugriffsberechtigung fr
Schnittstelle, Gerteliste, Statistik und Gerteregister lesen. jede Webseite.
5. Klicken Sie auf bernehmen. Speicherung der Kennworteinstellungen.

Tabelle 6: Gruppenzugriff

Gruppe Zugriff
Administrator Vollstndiger Zugriff auf alle Webseiten.
HINWEIS: Aus Systemsicherheitsgrnden wird empfohlen, das Standard-
Administratorkennwort nach der ersten Anmeldung zu ndern.
Guest Schreibgeschtzter Zugriff auf ausgewhlte Webseiten.
Drei benutzerdefinierte Durch Auswahl aus folgenden Optionen weist der Administrator jeder Gruppe bestimmte
Gruppen Webseiten-Zugriffsrechte zu. Es gibt folgende Zugriffsberechtigungen:
Keine: Eine Gruppe hat keinen Zugriff auf die ausgewhlte Webseite.
Schreibgeschtzt: Das Kennwort gewhrt einer Gruppe nur Lesezugriff auf die
ausgewhlte Webseite.
Vollstndig: Eine Gruppe hat die gleichen Zugriffsrechte fr die ausgewhlte Webseite
wie die Administrator-Gruppe.

Abbildung 9: Seite Webseitenzugriff

Modbus-TCP/IP-Filter
Mit dieser Funktion kann der Administrator fr Modbus-TCP/IP-Client-Gerte festlegen, ob
sie Zugriff auf die an das EGX angeschlossenen seriellen Slave-Gerte haben oder nicht.
HINWEIS: Der anonymen Modbus-TCP/IP-Adresse (***.***.***.***) knnen die
Zugriffsberechtigungen Schreibgeschtzt oder Keine zugewiesen werden. Die
Einstellung Schreibgeschtzt erlaubt jedem Modbus-TCP/IP-Client, der nicht in der
Filterliste enthalten ist, den Zugriff auf serielle Slave-Gerte mit der Zugriffsberechtigung
Schreibgeschtzt. Die Einstellung Keine blockiert alle Modbus-TCP/IP-Clients, die nicht in
der Filterliste enthalten sind.

Manahme Ergebnis
1. Klicken Sie auf der Setup-Seite auf Einblendung der Seite Modbus-TCP/IP-Filter.
Modbus-TCP/IP-Filter.
2. Markieren Sie Filter aktivieren. Aktivierung der Filterfunktion.
3. Geben Sie in der Spalte IP-Adresse die Eingabe einer IP-Adresse fr einen Modbus-TCP/IP-Client, der
Modbus-TCP/IP-Client-Adresse ein. Zugriff auf die an das EGX angeschlossenen seriellen Gerte haben
soll.
4. Whlen Sie in der Spalte Auswahl der Zugriffsberechtigung fr die entsprechende IP-Adresse.
Zugriffsberechtigung entweder Fr die Einstellung Schreibgeschtzt sind nur die folgenden
Schreibgeschtzt oder Vollstndig aus. Modbus-TCP/IP-Funktionscodes zulssig:
Dezimal: 1, 2, 3, 4, 7, 8, 11, 12, 17, 20, 24, 43, 100
Hexadezimal: 01, 02, 03, 04, 07, 08, 0B, 0C, 11, 14, 18, 2B, 64

2006-2012 Schneider Electric. Alle Rechte vorbehalten. 9


PowerLogic Ethernet Gateway EGX100 63230-319-204B1
Setup 08/2012

Manahme Ergebnis
5. Wiederholen Sie die Schritte 3 und 4, um Hinzufgen weiterer IP-Adressen fr den Filter.
weitere IP-Adressen hinzuzufgen.
6. Klicken Sie auf bernehmen. Speicherung der Modbus-TCP/IP-Adressen-Filterliste.

Abbildung 10: Seite Modbus-TCP/IP-Filter

SNMP-Parameter
Da das EGX SNMP untersttzt, knnen Netzwerkadministratoren mit einem SNMP-Manager
auf ein abgesetztes EGX zugreifen und den Netzwerkstatus sowie die Diagnose im MIB-2-
Format anzeigen.

Manahme Ergebnis
1. Klicken Sie auf der Setup-Seite auf SNMP-Parameter. Einblendung der Seite SNMP-
Parameter.
2. Markieren Sie SNMP aktivieren, um SNMP (Simple Network Aktivierung von SNMP.
Management Protocol) einzuschalten.
HINWEIS: Wenn Sie die Markierung des Kontrollkstchens SNMP
aktivieren entfernen und auf bernehmen klicken, startet das EGX
neu und die SNMP-Funktion wird deaktiviert.
3. Geben Sie den Systemverantwortlichen, die Systembezeichnung, den Eingabe der SNMP-Systeminformationen
Systemstandort, den Communitynamen mit Nur-Lese-Zugriff und den und der Community-Zugriffsnamen.
Communitynamen mit Lese- und Schreibzugriff ein.
4. Klicken Sie auf bernehmen. Speicherung der SNMP-Einstellungen.

Abbildung 11: Seite SNMP-Parameter

10 2006-2012 Schneider Electric. Alle Rechte vorbehalten.


63230-319-204B1 PowerLogic Ethernet Gateway EGX100
08/2012 Setup

Systemzugangspunkt
Mit Hilfe des Systemzugangspunkts kann das EGX100 seine Existenz jedem mit dem
Netzwerk verbundenen EGX300 ber Multicast mitteilen. Diese Funktion ist so konfiguriert,
dass sie standardmig ausgefhrt wird und keine weitere Konfiguration bentigt.
Verwenden Sie den Setup-Bildschirm in Abbildung 12 auf Seite 11 fr die Eingabe der
Gruppen-IP-Adresse und zugehriger Informationen.

Manahme Ergebnis
1. Klicken Sie im Setup-Men auf Systemzugangspunkt. Das Fenster Systemzugangspunkt wird angezeigt.
2. Whlen Sie den UDP-Port, die Gruppen-IP-Adresse, das Auswahl der Systemzugangspunkteinstellungen.
Meldungsintervall, die Haltezeit, die Multicast-
Gltigkeitsdauer und die Gemeinschaft aus. Fr eine
Beschreibung der Einstellungen siehe Tabelle 7.
3. Klicken Sie auf bernehmen. bernahme der Einstellungen fr das EGX100.
HINWEIS: Um die Werkeinstellungen wiederherzustellen,
klicken Sie auf Standardwerte und dann auf bernehmen.

Tabelle 7: Einstellungen fr den Systemzugangspunkt

Option Beschreibung Einstellung


Aktiviert Bei aktivierter Option knnen EGX300-Gerte EGX100-Gerte Aktiviert, Deaktiviert
mit der gleichen Gruppen-IP-Adresse erkennen. Werkeinstellung: Aktiviert
UDP-Port Damit kann die Port-Nummer fr den UDP-Port eingestellt 1 bis 65535
werden, der von der Systemzugangspunkt-Erkennung verwendet Werkeinstellung: 59
wird.
Gruppen-IP-Adresse Mit dieser Option werden Multicast- und Unicast-Adressen Werkeinstellung:
untersttzt. 224.0.1.2
Meldungsintervall Das ist die Zeit zwischen den Hallo-Meldungen, die vom 1 bis 65534 Sekunden
EGX100 ausgegeben werden, um anderen Systemzu- Werkeinstellung:
gangsgerten von Schneider Electric seine Anwesenheit im 300 Sekunden
Netzwerk mitzuteilen.
Haltezeit Das ist der Zeitraum, fr den vom jeweiligen EGX100 gesendete 2 bis 65535 Sekunden
Hallo-Meldungen von Empfngern gehalten werden mssen, Werkeinstellung:
bevor dieses EGX100 als nicht verfgbar angesehen wird. 600 Sekunden
Multicast- Damit knnen Sie die Gre des Netzwerkbereichs, der zur 1 bis 255 Routerhops
Gltigkeitsdauer Erkennung von anderen Gerten verwendet wird, festlegen. Dazu Werkeinstellung: 1
wird die zulssige Anzahl der Multicast-Weiterleitungen an
andere Gerte angegeben.
Gemeinschaft Gerte in einer Gruppe knnen in Gemeinschaften unterteilt 0 bis 65535
werden. EGX300-Gerte knnen EGX100-Gerte mit der Werkeinstellung: 0
gleichen IP-Adresse und Gemeinschaftsnummer erkennen.

Durch Einstellen der Gemeinschaftsnummer auf 0 kann ein


EGX300 alle EGX100-Gerte mit derselben Gruppen-IP-Adresse
ohne Bercksichtigung der Gemeinschaftsein-stellung erkennen.

Abbildung 12: Systemzugangspunkt

2006-2012 Schneider Electric. Alle Rechte vorbehalten. 11


PowerLogic Ethernet Gateway EGX100 63230-319-204B1
Diagnose 08/2012

Diagnose
Fr den Zugriff auf die Diagnose-Webseiten-Links klicken Sie in der EGX-Menleiste auf
Diagnose.

Statistik

Manahme Ergebnis
1. Klicken Sie auf der Seite Diagnose Einblendung der Seite Statistik (siehe Abbildung 13).
auf Statistik.
HINWEIS: Die Seite Statistik zeigt Daten auf der Grundlage des unter
Serielle Schnittstelle auf Seite 5 ausgewhlten Modus an.
2. Zeigen Sie die Daten an. Siehe Statistik auswerten auf Seite 13.
3. Klicken Sie auf Rcksetzen. Rcksetzung der kumulativen Diagnosedaten des EGX auf 0.

HINWEIS: Diese Seite zeigt kumulierte Werte seit der letzten Aktivierung des EGX an. Wenn
die Spannungsversorgung zum EGX unterbrochen wird, werden alle kumulierten Werte auf
0 zurckgesetzt.
Abbildung 13: Seite Statistik
Lesen mit serieller Schnittstelle im MASTER-MODUS Lesen mit serieller Schnittstelle im SLAVE-MODUS

12 2006-2012 Schneider Electric. Alle Rechte vorbehalten.


63230-319-204B1 PowerLogic Ethernet Gateway EGX100
08/2012 Diagnose

Statistik auswerten
Statistik Beschreibung
Ethernet
Verbindungsstatus Status-Zeichenkette, die die Geschwindigkeit und die Duplex-Einstellung
darstellt, die zur Kommunikation mit dem Verbindungspartner benutzt werden.
Rahmen ohne Fehler gesendet Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen erfolgreich
gesendet wird.
Kollisionen Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen aufgrund der
Erkennung einer Kollision neu bertragen wird.
Zu hohe Anzahl an Kollisionen Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen aufgrund der
Erreichung des maximalen Kollisionsstatus auf der Basis des Truncated Binary
Exponential Backoff-Algorithmus nicht gesendet werden kann.
Rahmen ohne Fehler empfangen Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen erfolgreich
empfangen wird.
CRC-Fehler Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen empfangen wird,
dessen Prfsumme/CRC nicht mit dem berechneten Wert bereinstimmt.
Synchronisierfehler Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen empfangen wird,
dessen Prfsumme/CRC nicht mit einer 8-Bit-Rahmenbegrenzung endet.
Rahmen zu lang Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen empfangen wird,
der die in den Standardeinstellungen festgelegte maximale Lnge berschreitet
(Rahmen grer als 1518 Byte).
Rahmen zu kurz Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen empfangen wird,
der die in den Standardeinstellungen festgelegte minimale Lnge unterschreitet
(Rahmen kleiner als 64 Byte).
Modbus-TCP/IP
Rahmen gesendet Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen gesendet wird.
Rahmen empfangen Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen empfangen wird.
Protokollfehler Zhler, der sich jedes Mal um eins erhht, wenn eine Nachricht mit einem
falschen Format empfangen wird.
Aktive Verbindungen1 Statuswert, der die Anzahl der Verbindungen darstellt, die zum Zeitpunkt der
Aktualisierung der Diagnoseseite aktiv sind. Es werden maximal 32 Verbindun-
gen untersttzt. Durch Klicken auf Aktive Verbindungen wird ein neues Fenster
mit einer Liste aller aktiven Client-Verbindungen eingeblendet.
Summe der Verbindungen1 Zhler, der sich jedes Mal um eins erhht, wenn eine Verbindung zum EGX
aufgebaut wird.
Maximale Anzahl Verbindungen1 Statuswert, der die maximale Anzahl der aktiven Verbindungen darstellt.
Eingegangene Lesenachrichten1 Zhler, der sich jedes Mal um eins erhht, wenn eine Lesenachricht empfangen
wird.
Abgegangene Lesenachrichten2 Zhler, der sich jedes Mal um eins erhht, wenn eine Lesenachricht gesendet
wird.
Eingegangene Schreibnachrichten1 Zhler, der sich jedes Mal um eins erhht, wenn eine Schreibnachricht
empfangen wird.
Abgegangene Schreibnachrichten2 Zhler, der sich jedes Mal um eins erhht, wenn eine Schreibnachricht gesendet
wird.
Eingegangene Antwortnachrichten2 Zhler, der sich jedes Mal um eins erhht, wenn eine Antwortnachricht
empfangen wird.
Abgegangene Antwortnachrichten1 Zhler, der sich jedes Mal um eins erhht, wenn eine Antwortnachricht gesendet
wird.
Serielle Schnittstelle
Rahmen gesendet Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen gesendet wird.
Rahmen empfangen Zhler, der sich jedes Mal um eins erhht, wenn ein Rahmen empfangen wird.
CRC-Fehler Zhler, der sich jedes Mal um eins erhht, wenn eine Nachricht empfangen wird,
deren CRC nicht mit dem berechneten Wert bereinstimmt. Das ist normaler-
weise die Folge von Verdrahtungsproblemen.
Protokollfehler Zhler, der sich jedes Mal um eins erhht, wenn eine Nachricht mit einem
falschen Format empfangen wird.
Zeitberschreitungen Zhler, der sich jedes Mal um eins erhht, wenn eine Anforderungsnachricht
gesendet wird, ohne dass eine entsprechende Antwortnachricht innerhalb der
zulssigen Zeit empfangen wird. Zeitberschreitungen sind normalerweise das
Ergebnis von Konfigurationsfehlern oder einer fehlenden Reaktion des Gerts.
1 Verfgbar, wenn sich die serielle Schnittstelle im Master-Modus befindet.
2
Verfgbar, wenn sich die serielle Schnittstelle im Slave-Modus befindet.

2006-2012 Schneider Electric. Alle Rechte vorbehalten. 13


PowerLogic Ethernet Gateway EGX100 63230-319-204B1
Diagnose 08/2012

Statistik Beschreibung
Eingegangene Lesenachrichten2 Zhler, der sich jedes Mal um eins erhht, wenn eine Lesenachricht empfangen
wird.
Abgegangene Lesenachrichten1 Zhler, der sich jedes Mal um eins erhht, wenn eine Lesenachricht gesendet
wird.
Eingegangene Schreibnachrichten2 Zhler, der sich jedes Mal um eins erhht, wenn eine Schreibnachricht
empfangen wird.
Abgegangene Schreibnachrichten1 Zhler, der sich jedes Mal um eins erhht, wenn eine Schreibnachricht gesendet
wird.
Gateway-Informationen
Firmwareversion Das ist die Firmwareversion, die im EGX installiert ist.
System-Leerlaufzeit Prozentsatz von 0 % bis 100 %, der die durchschnittliche ungenutzte
Prozessorzeit anzeigt.
MAC-Adresse Unverwechselbare Ethernet-Hardware-Adresse eines EGX.
Seriennummer Seriennummer des EGX.
Modellnummer Modellnummer des EGX (100).
Hardwareversion EGX-Hardwareversion
Herstellungsdatum Datum, an dem das EGX hergestellt wurde.
1
Verfgbar, wenn sich die serielle Schnittstelle im Master-Modus befindet.
2
Verfgbar, wenn sich die serielle Schnittstelle im Slave-Modus befindet.

Gerteregister lesen
Manahme Ergebnis
1. Klicken Sie auf der Seite Diagnose auf Einblendung der Seite Gerteregister lesen.
Gerteregister lesen.
2. Geben Sie die Gerte-ID, das Startregister und die Eingabe der Werte fr Beginn der Registerauslesung fr
Anzahl der zu lesenden Register ein. das angegebene Gert.
3. Whlen Sie einen Datentyp aus. Auswahl des anzuzeigenden Datentyps.
4. Um die Art der Datenanzeige in der Spalte Wert zu Auswahl der Art der Datenanzeige.
ndern, whlen Sie Dezimal, Hexadezimal, Binr
oder ASCII aus.
5. Klicken Sie auf Lesen. Anzeige der angeforderten Daten.

Tabelle 8: Einstellungen des EGX zum Lesen von Gerteregistern


Option Beschreibung Werkeinstellung
Gerte-ID Adresse des Gerts, dessen Register gelesen werden. 1
Startregister Erstes zu lesendes Register. 1000
Anzahl Register Anzahl der zu lesenden Register (1 bis 10). 10
Spalte Register Auflistung der Registernummern.
Spalte Wert Auflistung der fr ein Register gespeicherten Daten. Die
abgerufenen Werte hngen vom Gert ab, das mit dem
EGX verbunden ist. Weitere Informationen ber gespei-
cherte Registerwerte finden Sie in den Unterlagen des
verbundenen Gerts.
Datentyp Auswahl von Halteregistern, Eingangsregistern, Aus- Halteregister
gangsspulen, Eingangsspulen bzw. Gerte-ID fr die
Spezifizierung der abgerufenen Werte.
Optionen Dezimal, Hexadezimal, Legt fest, wie Daten in der Spalte Wert angezeigt werden Dezimal
Binr bzw. ASCII sollen.

14 2006-2012 Schneider Electric. Alle Rechte vorbehalten.


63230-319-204B1 PowerLogic Ethernet Gateway EGX100
08/2012 Firmware

Abbildung 14: Seite Gerteregister lesen

Firmware
Die Firmware der EGX-Gerte kann mit FTP (File Transfer Protocol) aktualisiert werden.
Das neueste Firmware-Update finden Sie unter www.powerlogic.com, oder fragen Sie Ihren
zustndigen Vertriebsmitarbeiter danach.

Firmwareversion feststellen
Manahme Ergebnis
1. Melden Sie sich beim EGX an. Einblendung der EGX-Startseite.
2. Suchen Sie die Firmwareversion in der unteren linken Feststellung der Firmware-Version des EGX.
Ecke der Seite.
HINWEIS: Wenn Sie die Firmware krzlich aktualisiert
haben, drcken Sie F5, um die Webseite und die
angezeigte Firmwarenummer zu aktualisieren.
3. Alternativ knnen Sie auf Diagnose > Statistik klicken, Alternative Feststellung der Firmwareversion des
um die Firmwareversion im Abschnitt Gateway- EGX.
Informationen zu finden.

Neue Firmware herunterladen

Manahme Ergebnis
1. Starten Sie Internet Explorer, geben Sie Einblendung der PowerLogic-Website.
www.powerlogic.com in die Adressenleiste ein und
drcken Sie die Eingabetaste.
2. Whlen Sie Ihr Land aus und klicken Sie auf Go. Einblendung der PowerLogic-Website fr Ihr Land.
HINWEIS: Wenn Sie United States ausgewhlt haben,
fahren Sie mit Schritt 3 fort. Anderenfalls folgen Sie der
lnderspezifischen Navigation zur EGX-Firmware.
3. Klicken Sie auf Firmware Downloads > Products > Anzeige der verfgbaren Downloads fr das EGX100.
PowerLogic Communications > EGX100.
4. Klicken Sie auf den Link EGX100 Firmware. Einblendung der Seite mit Anweisungen fr die
EGX100-Firmware.
5. Klicken Sie auf die Registerkarte Files und dann auf den Anzeige der Dateinamen und ffnen des Dialogfelds
Firmware-Dateilink (eg#####.bin, wobei ##### die File Download.
Firmwarenummer ist).
HINWEIS: Fr das Herunterladen von Firmwaredateien
mssen Sie angemeldet sein. Wenn Sie keinen
Benutzernamen und kein Kennwort haben, befolgen Sie
die Anweisungen auf der Website.
6. Klicken Sie auf Save. Speicherung der Firmwaredatei.

2006-2012 Schneider Electric. Alle Rechte vorbehalten. 15


PowerLogic Ethernet Gateway EGX100 63230-319-204B1
Firmware 08/2012

Firmwaredatei aktualisieren

Manahme Ergebnis
1. Starten Sie Internet Explorer, geben Sie ftp:// sowie die Einblendung des Dialogfelds Anmelden als.
IP-Adresse des EGX in die Adressenleiste ein (z. B.
ftp://169.254.0.10) und drcken Sie die Eingabetaste.
2. Geben Sie in die Textfelder den Benutzernamen Beginn einer FTP-Sitzung mit dem EGX.
Administrator und das Administratorkennwort ein und
klicken Sie auf Anmelden.
3. Suchen Sie die gespeicherte Firmwaredatei auf Ihrem Kopieren der Firmwaredatei in die Zwischenablage.
Computer, rechtsklicken Sie auf die Datei und klicken Sie
dann auf Kopieren.
4. Rechtsklicken Sie in das Internet Explorer-Fenster und Kopieren der Firmware auf das EGX und Neustart des
klicken Sie auf Einfgen. EGX.
HINWEIS: Anstelle des Kopierens und Einfgens der
Firmwaredatei knnen Sie die Firmwaredatei im Internet
Explorer auch ziehen und ablegen (Drag & Drop).
5. Schlieen Sie das Internet Explorer-Fenster. Schlieen von Internet Explorer und Beenden der
FTP-Verbindung zum EGX.
6. Um zu kontrollieren, ob die Firmwareversion erfolgreich berprfung der aktualisierten Firmwareversion.
aktualisiert wurde, fhren Sie die Schritte unter
Firmwareversion feststellen auf Seite 15 aus.

16 2006-2012 Schneider Electric. Alle Rechte vorbehalten.


63230-319-204B1 PowerLogic Ethernet Gateway EGX100
08/2012 Index

Index

A Systemzugangspunkt
Einrichten 11
Abmelden 2
Anmelden beim EGX 2 U
B Untersttzte Ethernet-Protokolle 1
Benutzerkonten W
Einrichten 8
Webseitenzugriff
Benutzeroberflche 3
Einrichten 8
D
Z
Diagnose 12
Zugang zum EGX ber ein Netzwerk 2
E Zustzliche Ressourcen 2
EGX
Anmeldung 2
Benutzeroberflche 3
Einrichten 3
Einfhrung 1
Einrichten
Gerteliste
Master-Modus 6
Slave-Modus 7
Erkennung identischer IP-Adressen 4
Ethernet- und TCP/IP-Einstellungen 3
Ethernet-Protokolle 1

F
Firmware 15
Aktualisieren 15
Neu herunterladen 15
Version feststellen 15

G
Gerteliste
Einrichten 6
Master-Modus 6
Slave-Modus 7
Gerteregister 14
Lesen 14

H
Hardware 1

M
Modbus-TCP/IP-Filter
Einrichten 9

N
Netzwerk
Zugang 2

S
Serielle Schnittstelle
Einrichten 5
SNMP-Parameter
Einrichten 10
Statistik 12
Auswerten 13

2006-2012 Schneider Electric. Alle Rechte vorbehalten. 17


PowerLogic Ethernet Gateway EGX100 63230-319-204B1
Index 08/2012

18 2006-2012 Schneider Electric. Alle Rechte vorbehalten.


PowerLogic Ethernet Gateway EGX100
Benutzerhandbuch

PowerLogic ist eine Marke von Schneider Electric in Frankreich, den USA und
anderen Lndern. Andere Marken sind das Eigentum ihrer entsprechenden Inhaber.
Schneider Electric
35 rue Joseph Monier 63230-319-204B1 08/2012
92500 Rueil-Malmaison, France Ersatz fr 63230-319-204A2 12/2008
www.schneider-electric.com 2006-2012 Schneider Electric. Alle Rechte vorbehalten.