Short Circuit Currents and Their Impact on Electrical Equipment and SCCR
June 2017
PUBLIC
Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 1
What is SCCR?
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 2
100, Short Circuit Current Rating
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 3
100, Short Circuit Current Rating
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 4
100, Short Circuit Current Rating
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 5
Short Circuit Current Rating (SCCR)
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 6
Short-Circuit Current Ratings
Definitions:
Transformer Short circuit An electrical current across an unintended path, often resulting in very large current with
potential to harm personnel or damage to equipment.
Short-circuit current the amount of current able to be delivered during a short-circuit event. Also known
as available fault current.
Conductors
SCCR: The ability of equipment to safely withstand a short-
Machinery/equipment 5,000 amps
circuit is defined by its Short-Circuit Current Rating,
or SCCR.
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 8
Current Limitation
Ipeak Fault current that would flow with A Current Limiting
overcurrent protective device
Reduced Peak Let-Thru
Current
Peak Let-Thru
of Fuse
Tc
Total Clearing Time
of Fuse
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 9
Current Limitation
Example 1
45,000 sym rms amps available, 500V
26,000A
Approximate short-circuit current flow
X (due to conductor impedance)
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 10
Current Limitation
Approximately 26,000A Short-Circuit: 90 ft 2/0 AWG
Non-Current Limiting (1 cycle clearing)
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 11
Current Limitation
45,000 sym rms amps available, 500V
Example 2
LPS-RK-200SPI
200A Class RK1 fuse
26,000A
Approximate short-circuit current flow possible
X (due to conductor impedance)
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 12
Current Limitation
200A Low-Peak Fuse 90 ft 2/0 AWG
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 13
Current Limitation
Example 1 Results 1 cycle clearing
IP let-thru = 48.1 kA
I2t = 15,700,000 A2sec
Conductor whip results because of the mechanical forces due to magnetic effect of fault current.
The maximum mechanical force is directly proportion to the instantaneous peak current (IP). Test
5 illustrates the reduction in mechanical forces versus that of Test 4. The reduction in force by
use of the 200A current-limiting fuse is (10.2/48.1)2; which is approximately 1/25.
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 14
SCCR Application Problem
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 15
SCCR Application Problem
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 16
SCCR Application Problem
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 17
SCCR And The NEC
Requirements where marking SCCR on equipment is mandatory
409.110(4) Industrial Control Panels
430.8 Motor Controllers
430.98 Motor Control Centers
440.4(B) Air Conditioning & Refrigeration Equipment
620.16(A) Elevator Control Panel
670.3(A)(4) Industrial Machinery
700.5(E) Transfer Equipment for Emergency Systems
701.5(D) Transfer Equipment for Legally Required and Standby Systems
702.5 Transfer Equipment for Optional Standby Ssytems
708.24(E) Transfer Equipment for Critical Operations Power Systems
1
Know the range of potential fault currents where your equipment may be installed.
2
Design equipment for worst case or with an alternate BOM to address worst-case SCCR.
3
Use available tools to assist in calculation, addressing weak spots, and documenting
SCCR.
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 21
Success Story: Wafer Grinding Machine
Pharmacy Retail
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 22
Case Study - Major Pharmacy Retail
Store
SCCR: 5,000
amps
Inadequate SCCR on installation of new refrigeration equipment required significant effort to resolve, resulting in delays
and larger project costs.
No requirement in equipment spec.
Standard equipment was rated 5 kA.
Actual fault current calculated was 35.5 kA.
Inspector failed installation inspection.
Raising SCCR required changing out most components.
OEM elected to install isolation transformer to lower fault current.
Inadequate SCCR resulted in larger project costs, a delayed opening of the store and subsequent lost revenue.
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 23
Success Story: Wafer Grinding Machine
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 24
Success Story: Wafer Grinding Machine
Challenge: Wafer grinding machine design rated at 5 kA SCCR. Application fault currents range from 5 kA to 65 kA. Customer needed a
solution that met the full range of application needs with minimal impact to the existing design, including space requirements and cost.
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 25
Success Story: Wafer Grinding Machine
Analysis:
Panel A qualified for a 65 kA rating. SCCR SYM: 65kA
Panel B contained servo drives with 5 kA SCCR and miniature 65kASCCR
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 26
Success Story: Wafer Grinding Machine
Analysis:
Servo drives rated 18 kA with specified fuse. SCCR SYM: 65kA
Miniature circuit breakers replaced with Compact Circuit
Protectors containing Class CC or CF fuses.
Panel rating raised to 18 kA SCCR.
Still not adequate for full range of fault currents.
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 27
Success Story: Wafer Grinding Machine
Analysis:
The 60 A circuit breaker in the feeder (Panel A) is
SCCR SYM: 65kA
not current-limiting.
A current-limiting device can be substituted to
achieve a higher SCCR:
60 A Class J fuse with let-through of 10 kA
at a fault current of 100 kA. Applying
SB4.3.3 and SB4.3.4, the servo drives
raised from 18 kA to 100 kA.
SCCR SYM: 65 kA when fed by 60 A Type
Current-limiting type EGC 60 A circuit
EGC circuit breaker
breaker let-through of 17 kA at a fault
current of 65 kA. Applying SB4.3.2 and
SB4.3.4, the servo drives raised from 18 kA
to 65 kA.
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 28
Success Story: Wafer Grinding Machine
Solution: Customer developed the option to offer three different SCCR solutions to their customers
with minimal changes to components and no additional space requirements.
65 kA SCCR Solution using a current limiting
5 kA SCCR Solution Panel A 18 kA SCCR Solution Panel A feeder Panel A
Standard design Changes: Changes:
Compact Circuit Type EGC current-
Protector with Class limiting circuit
CC or CF fuse breaker
Compact Circuit
Protector with Class
CC or CF fuse
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 29
Success Story: Wafer Grinding Machine
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 30
Case Study Vertical Seal Machine
An OEM approached Bussmann by Eaton for assistance with determining
the SCCR of their vertical form fill seal machine, and suggestions on how it
could be raised to 65 kA.
The Bussmann series product Application Engineering team provided a free
SCCR analysis.
The team performed an SCCR analysis and determined the panels design
possessed just a 5 kA SCCR.
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 31
Case Study Vertical Seal Machine
The team applied the component SCCRs based on the circuit protective
devices used, as well as the impact of the current limiting devices in the
circuit. The analysis revealed the following, identifying which components
must be addressed to achieve the desired 65 kA equipment SCCR value:
1) The miniature circuit breakers/supplementary protectors, rated at 10 kA
must be replaced with overcurrent protective devices having an interrupting
rating not less than 65 kA and with comparable dimensions.
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 32
Case Study Vertical Seal Machine
Power Circuit
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 33
Case Study Vertical Seal Machine
Power Circuit
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 36
Case Study Vertical Seal Machine
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 37
Case Study Vertical Seal Machine
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 38
Case Study Vertical Seal Machine
The team applied the component SCCRs based on the circuit protective
devices used, as well as the impact of the current limiting devices in the
circuit. The analysis revealed the following, identifying which components
must be addressed to achieve the desired 65 kA equipment SCCR value :
3) Although the power circuit components downstream of the power
transformer had SCCRs less than 65 kA, the presence of the 10 kVA power
transformer helped achieve the desired 65 kA equipment SCCR.
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 39
Case Study Vertical Seal Machine
The Bussmann series product Application Engineering team researched
design solutions to address the weak links limiting the panels SCCR below
65 kA, starting with the miniature circuit breakers/supplementary protectors.
Considering the size, functionality and costs of these existing components,
the Bussmann series Compact Circuit Protector (CCP) solution, with KTK-R
Class CC fuses, provided the best solution when compared with a molded
case circuit breaker or a fuse and fuse block solution. This component
substitution not only raised the interrupting rating to 200 kA, it did so without
any significant impact on costs or the panel layout
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 40
How is SCCR Determined?
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 41
Assembly SCCR
UL508A Supplement SB (SPD pg. 82-101)
Sweep 1
Each power circuit component is analyzed
Ex. PDBs, Busbars, Disconnects
Sweep 2
Each power circuit OCPD is analyzed
Ex. Fuses, Circuit Breakers
Lowest Rated device or component will be the panel SCCR
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 42
Assembly SCCR
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 43
Default SCCR
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 44
Combination SCCR
The maximum short circuit current a component can withstand safely when
protected by an overcurrent protective device
Higher SCCR can be achieved by using a current limiting fuse in
combination
Ex. PDBs, Starters, Contactors
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 45
Application Example 1
Application calls for a power distribution block to be rated to the
available short circuit current of 50kA where it is connected to the
system
Problem: The PDBFS204 is only rated to 10kA by itself
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 46
Application Example 1 cont.
Solution: Apply a current limiting fuse upstream from the PDBFS204
to achieve a 200kA combination SCCR
Tested combination ratings located on data sheet #1049 or pg. 325 of
FLC:
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 47
Application Example 2
Customer has a receptacle installed in their industrial control panel
that is limiting the assembly SCCR to below the 35kA panel rating that
is needed. How can we achieve a higher SCCR for the panel?
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 48
Application Example 2 cont.
Solution:
Control transformer is 5kVA or less with 120V secondary voltage and
the lowest SCCR component of this circuit is 2kA (SPD pg.85)
Therefore, the transformer primary OCPD can be applied as the sub-
feeds overall SCCR. 14kA.
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 49
Application Example 2 cont.
Final Solution:
Substitute a current limiting fuse in place of the primary circuit
breaker to achieve a final branch SCCR of 200kA
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 50
Equipment with Marked SCCR Rotary
Disconnect Switches
Open and enclosed disconnects are readily available in
fused and non-fused solutions Leverage flexibility and
Fused: 30-800A
convenience to make point-
Non-Fused: 16-1200A
of-use configuration easy
When using enclosed disconnects understand NEMA
enclosure ratings (1, 3R, 12, 4, 4X Stainless, and 4X
Plastic)
Most disconnect switches can be operated with a front, side,
flange or direct handle
Modular accessories are important for flexible design
solutions and consistency
Branch Circuit Disconnects must be UL 98 or UL 489 Listed
for UL 508 Listed for Motor Disconnect Applications
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 51
Equipment with Marked SCCR
Terminal Blocks & Power Distribution Blocks
Terminal Blocks
UL & IEC
High SCCR
Branch Circuit Spacings Even terminal blocks and power distribution blocks
Had to be reviewed and modified.
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 52
Equipment with Marked SCCR
Class J Power Distribution Fuse Block
PUBLIC Rockwell Automation TechED 2017 @ROKTechED #ROKTechED Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 53
SCCR tools and resources
How much SCCR do I need?
Which components have SCCR?
FC2 Available Fault Current Calculator
Calculates fault current SCCR Protection Suite
FREE in app store for iPhone or Android Locates components with desired SCCR
Narrow results by setting part preferences
FREE go to sccr.eaton.com