Académique Documents
Professionnel Documents
Culture Documents
. - ---
Authorized licensed use limited to: G H Patel College of Eng & Technology. Downloaded on November 19, 2009 at 01:02 from IEEE Xplore. Restrictions apply.
that are vital to the adaptive relaying concept: their reliability that relates to the degree that the relay or relay
functions are determined through software, and they system will operate correctly. Security is that facet o f
have a communication capability which can be used to reliability that relates to the degree that a relay or relay
alter the software in response to higher level super- system will not operate incorrectly. Even the most vocal
visory software, or under commands from a remote advocates of adaptive relaying address the issue of
control center. It is, of course necessary to recognize reliability and responsibility with much concern.
that any relay or communication system may fail at Adaptive proposals always include the possibility of
some time, and appropriate fallback positions and failure of the computational hardware, or software, or
safety checks must be built into the relays. the communication links. Checkbacks, safety checks,
fallback positions, and other reliability designs must
Why Adaptive Relaying? be an integral part of any adaptive relaying scheme.
Before describing some adaptive relaying pos- With proper design, an adaptive relaying scheme can
sibilities, we should examine the reasons why the con- be a s safe as any conventional relaying scheme and
cept is attracting such attention from the point of view provides a better match between the current state of
of modern power system practices. As we know, the a power system and its protection system.
power industry is undergoing fundamental changes
that seriously affect its ability t o perform its function Some Examples of Adaptive Relaying
properly. Economic and environmental issues and con- All relay settings are a compromise. In every phase
cerns are creating difficulties in obtaining transmission of the development of a systems protection, a balance
right-of-way or generation siting and are causing defer- must be struck between economy and performance,
rals of new power plants or transmission lines. The dependability and security, complexity and simplicity,
effect of this is t o decrease significantly the margins speed and accuracy, credible vs. conceivable. The
for loading and stability, and to force operation of the objective of providing adaptive relay settings is t o
power systems in ways and at levels that may not have minimize compromises and allow relays to respond to
been considered in its original plans. Consequently, actual system conditions.
criteria for traditional protection and control perfor- Load Effect
mance are being challenged. Operating margins, relay The ability to detect low grade faults is limited by
applications and settings and tripping or reclosing the necessity of not tripping during emergency load
schemes that were commonplace are no longer accept- conditions. On subtransmission and distribution sys-
able. Unusual circumstances can encroach on all of the tems, overcurrent relays must be set sufficiently above
relaying conservatism, and render the transmission load and below fault currents to allow for both depend-
system vulnerable to prolonged or cascading outages. ability and security. On higher voltage systems, dis-
tance relays must not encompass load impedance.
Is Adaptive Relaying Safe? The traditional solution is t o add voltage restraint,
Opposition to adaptive relaying is centered on of directionality, blinders, or t o compromise the setting.
reliability. Based on years of conservatism, there is an In an adaptive environment, the load can be monitored
understandable reluctance on the part of relay en- continuously and when a fault occurs, a s indicated by
gineers to contemplate reducing their control over the a fault detector or a transient monitor, the load can be
fundamental mechanism of system protection. Tradi- removed from the fault calculation.
tionally, applications and settings have been the Cold Load Pickup
province of a small group of experts entrusted with this Similarly, when a distribution circuit has been out of
responsibility. If relays are allowed to change their service for a long time, t h e inrush current upon
characteristics automatically, who is responsible for restoration is extremely high. This is known a s cold
assuring that the setting is appropriate? If many relays load pickup and is caused by the loss of diversity of all
change their settings, will they still coordinate with heating, cooling and other industrial and household
each other? Will such systems trip when they should, equipment. Usually, the instantaneous overcurrent
and refrain from tripping when they should not? In relays will trip on this cold load inrush. The relay will
other words, are adaptive relays reliable? then be blocked and the circuit allowed to reclose.
It is important at this point to remind the reader that Assuming there actually is no fault, the circuit is re-
reliability a s defined by the IEEE Standard Dictionary stored after the second attempt. If there is a fault, a
of Electrical and Electronic Terms (ANSIJEEE loo), time-delay relay will trip, but after a period of heavy
specifically pertaining t o power system protection, fault current and low voltage. Since the cold-load
encompasses two components: dependability and phenomenon follows a logical sequence of events of
security. Reliability denotes certainty o f correct opera- outage plus time plus restoration, it is amenable to a
tion with assurance against incorrect operation from all computer derived calculation and subsequent adjust-
extraneous causes. Dependability is that facet o f ment of the instantaneous relay setting.
48 IEEE ComputerApplications in Power
Authorized licensed use limited to: G H Patel College of Eng & Technology. Downloaded on November 19, 2009 at 01:02 from IEEE Xplore. Restrictions apply.
End-of-line Protection
Instantaneous overcurrent relays and Zone 1 imped-
ance relays must not overreach into the next line sec-
tion. Overcurrent relays are therefore set above the
maximum current that will exist when all circuit
breakers are closed. Zone 1 relays are set at 80-90%of
the total line length. Time delay overcurrent relays Figure 1. Underreaching and overreaching protection with
and Zone 2 elements are used to cover the portion of overcurrent and impedance relays for 100% protection of
the line that is not covered by the instantaneous relays. transmission lines.
This is shown in Figure 1. For overcurrent relays, when
mismatch and variable power transformer tap set-
the remote breaker opens, the current will change. In
tings. Harmonic restraint is provided in the relay to
the non-adaptive case, the instantaneous relay must be
prevent its operation during magnetizing inrush or
set for the worst case currents, i.e, the system con-
current transformer saturation on external faults.
figuration that provides the maximum fault current.
Since all these variables may change depending on
For any other system configuration, the current may
system conditions, the transformer relay settings must
be less and the instananeous relay may not pick up.
assume some normal condition upon which pickup
With adaptive relaying, the system configuration can
and slope can be based. The effect is to reduce the
be communicated to all terminals and the resulting
fraction of the transformer winding being protected by
current change when the remote breaker opens can be
the relay. Since many of these variables are known
determined and the relay setting changed accordingly.
during the pre-fault state, adaptive relays can be ad-
In case of impedance relays, the opening of the breaker
justed without the need to accommodate any variable
at the remote end can be communicated to the relays,
parameters. The power transformer tap setting can be
and Zone1 setting of the relay can be made t o over-
determined by limit switches or by voltage measure-
reach the remote end. Since these are steady-state
ment. The current transformer ratios and calibration
system configuration changes, there is no need for a
curves can be stored in the relay and the pickup ad-
high-speed communication channel. The information
justed accordingly. Magnetizing inrush accompanies
can be sent off-line between stations or from a central
energizing of the transformer or recovery from a fault.
control point.
Both conditions can be determined by breaker posi-
Probably one of the best known relay problems is
tion, and voltage measurements and the harmonic
the multi-terminal transmission line and the com-
restraint provided to prevent relay operation from
promise settings associated with the presence or ab-
inrush can be enabled or disabled as required.
s e n c e of infeed. As discussed a b o v e , Zone-1
protection at A, B and C (see Figure 2) must always
underreach any remote terminal. It must always, there- Automatic Reclosing
fore, be set assuming no infeed from any of the other Adaptive control of automatic reclosing of circuit
lines. When infeed is present, i.e., all terminals con- breakers has attracted considerable attention recent-
tributing to the fault, the relay reach is further reduced. ly. Although it is not usually thought of in such terms,
This is not particularly desirable, but it is safe. Zone2 the use of dead-line or check-synchronizing in reclos-
protection must always overreach the complete line. ing relays is adaptive in nature. Also adaptive are the
In this case, the setting is determined with all infeeds interlocks which may be used with high speed reclos-
present. By continuously transmitting the system con- ing t o govern its use, e.g., to allow reclosing after single
figuration, i.e., circuit breaker status, to all terminals,
the presence or absence of infeed is known and the A B
relays set accordingly. This transmission is done
A
during steady-state operation and can b e accom- fault
modated by a slow speed channel. A more sophisti-
cated adaptive scheme makes use of a high speed
communication channel over which the actual ter-
minal currents are transmitted and the exact apparent
impedance seen by the relays can be calculated.
Transformer Protection ~
Setting the pickup and slope of the differential relays Figure 2. A multi-terminal transmission line protection prob-
for power transformer protection is another well lem. Setting of the distance relay at A (similarly at B and C)
is complicated by the presence of the third terminal and its
known compromise. The slope and pickup settings
contribution to the fault.
must be selected to account for current transformer
July 1990 49
Authorized licensed use limited to: G H Patel College of Eng & Technology. Downloaded on November 19, 2009 at 01:02 from IEEE Xplore. Restrictions apply.
phase faults, and block it after three phase faults. This Adaptive Control of Defective Relays
concept can be carried much further. Sympathy trips One of the earliest advantages recognized with com-
are incorrect trips, usually at one end only, that occur puter relays was their ability to monitor themselves
when some event other than an internal fault occurs. and to report their condition to a central location. This
Two common causes are loss of a blocking signal or ability has been taken several steps beyond this simple
loss of directionality. With adaptive relays, t h e approach. It was at first considered sufficient that a
presence (indeed the exact location) of a fault, is defective relay should alarm and remove itself from
known to a degree not possible with conventional service. In this way no damage could result and
relays. Coupling this knowledge into the reclosing maintenance could be scheduled immediately. Since
circuits will allow an incorrectly tripped breaker to there was always a redundant protection system, this
reclose immediately without the usual delays required action appeared justified. As the digital relay and
for fault clearing and synchronizing interlocks. This adaptive schemes were studied in greater detail, other
will significantly mitigate the effect of the incorrect solutions to the problem of defective relays became
trip. attractive. For instance, the ability to share data is one
Another reclosing concept that has been recently of the major advantages of computers connected in
introduced in several forums is the idea of preventing s o m e c o m m u n i c a t i o n n e t w o r k . With t o d a y s
reclosing into any fault other than a line-to-ground or microprocessors it is possible to load all of the algo-
line-to-line fault. This is done by closing one phase at rithms in all of the microprocessors, activating, under
one end and measuring all of the resulting phase volt- normal conditions, only the appropriate algorithm. If
age on the unenergized phases. The impressed and a relay detects that it can no longer function properly,
coupled voltages can then be analyzed, and reclosing a defective relay could transfer its function t o a healthy
permitted or aborted as appropriate (see Figure 3). relay, invoking the required algorithm and settings and,
using the shared data, maintain the integrity of the
Security and Dependability Balance protective system. Of course, if a relay can analyze its
If we allow our imagination a little more freedom we own failure it can d o many other things t o continue
can, with adaptive protection and control, address a operating in a somewhat degraded, but acceptable,
far more fundamental issue: the conflict referred to manner. For instance, if Zone-1 element is defective,
earlier between dependability and security of protec- Zone2 can now assume a new setting for an instanta-
tion. This is a dilemma that must be resolved very neous trip and revert to its normal time delay for
early in the engineering phase of an installation and backup. The reverse is also true: Zone-1 can extend its
cannot be altered without much expense and time. setting to the Zone-2 reach and add a time delay. These
Dependability is generally achieved through redun- are software changes actuated either automatically or
dant relaying, and a degree of security is achieved by command from a central location.
through a complex arrangement of interlocks. The
resulting protection system is invariably biased Other Adaptive Relaying Possibilities
toward greater dependability at t h e expense of Several other adaptive relaying ideas will be found
security or toward greater security at the expense of in the literature. Among these is the idea of adaptive
dependability. For mature HV or EHV systems the bias out-of -step relaying. This falls under the general prob-
is generally toward dependability. This is because the lem of trying to predict the instability of a power
power system itself is redundant and it is vital that swing as it is developing. With accurate synchronized
faults be cleared with certainty-even if, on occasion,
there may be some false trips. On the other hand,
distribution circuits are not redundant, and here
security is the most important consideration. Even for v
mature HV and EHV systems, however, during major
outages or upon restoration following a cascading
series of outages, one may wish to revise this philoso-
phy of protection which is biased towards depend-
ability at the expense of security. In conventional
relaying technology, this adaptive shift of balance be-
tween dependability and security would be almost
impossible to achieve. With computer relays, this type
of change can be accomplished with ease. Figure 4
shows a conceptual adaptive relaying scheme to ac-
complish such a change.
Authorized licensed use limited to: G H Patel College of Eng & Technology. Downloaded on November 19, 2009 at 01:02 from IEEE Xplore. Restrictions apply.
Redundant Supervisory
Protection I Control continuously a power network as well as t h e protective
relays, and to adjust the protection performance a s t h e
network conditions change. We have shown that t h e
concept is not totally new, but the advent of computer
Protection #1 relaying will permit applications not previously pos-
sible. Certainly, the changes will not occur suddenly.
Protection #2 c They will be introduced as computer relays justify
Trip themselves, and will allow the engineering fraternity
Protection #3 time to adjust to the inherent advantages of this new
technology, and become familiar with t h e possibilities
Figure 4. Adaptive adjustment of dependability and security it offers. We believe the relaying community will accept
of protecitve relays. Depending upon the condition of the this challenge, and embrace a protection philosophy
power system, the redundant protection systems are used suited t o t h e new and demanding environment of the
in an AND, OR, TWO OUT OF THREE scheme to determine electric power transmission networks.
whether a trip should be issued.
July 1990 51
Authorized licensed use limited to: G H Patel College of Eng & Technology. Downloaded on November 19, 2009 at 01:02 from IEEE Xplore. Restrictions apply.