Vous êtes sur la page 1sur 5

Adaptive Relaying

A. G.Phadke' and S.H.Horowitz2


Attending national o r international forums on of the time. To meet all possible contingencies, the
protection and control in recent years, one must be relay setting may be made so insensitive that it is not
impressed with the fact that adaptive relaying is a sensitive enough t o cover adequately the protection of
recurring topic on every agenda. It is not only ubiqui- any one state of the power system. These ideas force
tous, it is controversial. Is adaptive relaying really a us to conclude that, under certain conditions, and with
r e v o l u t i o n a r y c o n c e p t n e v e r a t t e m p t e d o r ac- appropriate safeguards, it may be desirable to make
complished before or is it simply the familiar, accepted relays adapt to changing conditions. Of course, not all
and expected versatility of existing protection and features of all relays must be adaptive. Adaptive ele-
control? Is the attention it is now receiving simply due ments are present in many of our existing elect-
t o its appearance in computer based devices and romechanical and solid-state relays. For instance, by
sporting a glamorous label to go along with its new look adjusting its speed of operations automatically to its
or is there a fundamental protection philosophy in the operating current, an induction disc, time-delay, over-
making? Is adaptive relaying safe? Is it beneficial? current relay is adapting to changing fault locations.
What is adaptive relaying? Perhaps in a less obvious fashion, adaptive relaying
and control can be seen in the complex circuitry
associated with many circuit breaker bypass schemes.
What Is Adaptive Relaying?
Adaptive relaying accepts that relays which protect Current transformer and tripping circuits are recon-
a power network may need to change their charac- figured using auxiliary switches to make the measuring
teristics to suit the prevailing power system condi- and tripping circuits compatible at each stage of the
tions. Normally, a protective system responds t o faults switching procedure. Such examples support the view
or abnormal events in a fixed predetermined manner. that we have, indeed, been enjoying adaptive protec-
This predetermined manner, embodied in the charac- tion and control, but they d o not encompass t h e
teristics of the relays, is based upon certain assump- present excitement about the full range of possibilities
tions made about the power system. Thus, one may of adaptive relaying. Existing practices represent per-
have assumed a level of load current which cannot be manent provisions for wellconsidered scenarios or
exceeded at the place where the relay is located. For hard-wired solutions to a variety (albeit limited in num-
ber) of operating states of the power system.
the moment one of the characteristics of t h e relay-its
pickup setting-may thus be defined to lie above the To describe completely the present concept of
adaptive relaying, it is necessary t o include t h e
maximum load current. However, in time, if this load
current level is exceeded by the actual load, then the possibility that the protection systems will permit
making automatic changes to be made within the
pickup setting of the relay is inappropriate, and the
relay may misoperate during heavy loading conditions. protection system itself as the power system under-
Examples of this kind are fairly common in modern goes normal and abnormal changes during its course
power system operations, and will be discussed fur- of operation. With this concept of adaptive relaying,
ther. One could generalize by saying that it is not therefore, it is not necessary to anticipate all contin-
gencies for which the relaying must perform correctly,
possible to foresee all possible operating states of the
power system in a practical power network and conse- nor is it necessary to accept compromises in setting
relays. Thus, adaptive protection is CI protection
quently it is riot possible to ensure that all relay set-
philosophy which permits and seeks to make adjust-
tings will remain appropriate as the power system
evolves in time.
ments in various protection functions automatically in
Even if one could foresee all contingencies and order to make them more attuned to prevailing power
define boundaries of required performance for a relay,
system conditions. Other definitions of adaptive relay-
ing will be found in the technical literature, but their
one must often make an inferior choice for the relay
setting in order to embrace these boundaries. It is sense is contained in the above defintion.
often necessary to make a setting which covers a great
many conditions, and consequently, is not the best for Computer Relaying and Adaptive Relaying
the riorrrial conditions which the relay would face most The adaptive relaying philosophy can be made fully
' Virginia Polytechnic Institute effective only with digital computer based relays.
These relays, which are becoming more common on
Consulting Engineer- Columbus, Ohio
many power systems, contain two important features
0895-0156/90/0700-0047$1 00 0 1990 IEEE July 1.990 47

. - ---

Authorized licensed use limited to: G H Patel College of Eng & Technology. Downloaded on November 19, 2009 at 01:02 from IEEE Xplore. Restrictions apply.
that are vital to the adaptive relaying concept: their reliability that relates to the degree that the relay or relay
functions are determined through software, and they system will operate correctly. Security is that facet o f
have a communication capability which can be used to reliability that relates to the degree that a relay or relay
alter the software in response to higher level super- system will not operate incorrectly. Even the most vocal
visory software, or under commands from a remote advocates of adaptive relaying address the issue of
control center. It is, of course necessary to recognize reliability and responsibility with much concern.
that any relay or communication system may fail at Adaptive proposals always include the possibility of
some time, and appropriate fallback positions and failure of the computational hardware, or software, or
safety checks must be built into the relays. the communication links. Checkbacks, safety checks,
fallback positions, and other reliability designs must
Why Adaptive Relaying? be an integral part of any adaptive relaying scheme.
Before describing some adaptive relaying pos- With proper design, an adaptive relaying scheme can
sibilities, we should examine the reasons why the con- be a s safe as any conventional relaying scheme and
cept is attracting such attention from the point of view provides a better match between the current state of
of modern power system practices. As we know, the a power system and its protection system.
power industry is undergoing fundamental changes
that seriously affect its ability t o perform its function Some Examples of Adaptive Relaying
properly. Economic and environmental issues and con- All relay settings are a compromise. In every phase
cerns are creating difficulties in obtaining transmission of the development of a systems protection, a balance
right-of-way or generation siting and are causing defer- must be struck between economy and performance,
rals of new power plants or transmission lines. The dependability and security, complexity and simplicity,
effect of this is t o decrease significantly the margins speed and accuracy, credible vs. conceivable. The
for loading and stability, and to force operation of the objective of providing adaptive relay settings is t o
power systems in ways and at levels that may not have minimize compromises and allow relays to respond to
been considered in its original plans. Consequently, actual system conditions.
criteria for traditional protection and control perfor- Load Effect
mance are being challenged. Operating margins, relay The ability to detect low grade faults is limited by
applications and settings and tripping or reclosing the necessity of not tripping during emergency load
schemes that were commonplace are no longer accept- conditions. On subtransmission and distribution sys-
able. Unusual circumstances can encroach on all of the tems, overcurrent relays must be set sufficiently above
relaying conservatism, and render the transmission load and below fault currents to allow for both depend-
system vulnerable to prolonged or cascading outages. ability and security. On higher voltage systems, dis-
tance relays must not encompass load impedance.
Is Adaptive Relaying Safe? The traditional solution is t o add voltage restraint,
Opposition to adaptive relaying is centered on of directionality, blinders, or t o compromise the setting.
reliability. Based on years of conservatism, there is an In an adaptive environment, the load can be monitored
understandable reluctance on the part of relay en- continuously and when a fault occurs, a s indicated by
gineers to contemplate reducing their control over the a fault detector or a transient monitor, the load can be
fundamental mechanism of system protection. Tradi- removed from the fault calculation.
tionally, applications and settings have been the Cold Load Pickup
province of a small group of experts entrusted with this Similarly, when a distribution circuit has been out of
responsibility. If relays are allowed to change their service for a long time, t h e inrush current upon
characteristics automatically, who is responsible for restoration is extremely high. This is known a s cold
assuring that the setting is appropriate? If many relays load pickup and is caused by the loss of diversity of all
change their settings, will they still coordinate with heating, cooling and other industrial and household
each other? Will such systems trip when they should, equipment. Usually, the instantaneous overcurrent
and refrain from tripping when they should not? In relays will trip on this cold load inrush. The relay will
other words, are adaptive relays reliable? then be blocked and the circuit allowed to reclose.
It is important at this point to remind the reader that Assuming there actually is no fault, the circuit is re-
reliability a s defined by the IEEE Standard Dictionary stored after the second attempt. If there is a fault, a
of Electrical and Electronic Terms (ANSIJEEE loo), time-delay relay will trip, but after a period of heavy
specifically pertaining t o power system protection, fault current and low voltage. Since the cold-load
encompasses two components: dependability and phenomenon follows a logical sequence of events of
security. Reliability denotes certainty o f correct opera- outage plus time plus restoration, it is amenable to a
tion with assurance against incorrect operation from all computer derived calculation and subsequent adjust-
extraneous causes. Dependability is that facet o f ment of the instantaneous relay setting.
48 IEEE ComputerApplications in Power

Authorized licensed use limited to: G H Patel College of Eng & Technology. Downloaded on November 19, 2009 at 01:02 from IEEE Xplore. Restrictions apply.
End-of-line Protection
Instantaneous overcurrent relays and Zone 1 imped-
ance relays must not overreach into the next line sec-
tion. Overcurrent relays are therefore set above the
maximum current that will exist when all circuit
breakers are closed. Zone 1 relays are set at 80-90%of
the total line length. Time delay overcurrent relays Figure 1. Underreaching and overreaching protection with
and Zone 2 elements are used to cover the portion of overcurrent and impedance relays for 100% protection of
the line that is not covered by the instantaneous relays. transmission lines.
This is shown in Figure 1. For overcurrent relays, when
mismatch and variable power transformer tap set-
the remote breaker opens, the current will change. In
tings. Harmonic restraint is provided in the relay to
the non-adaptive case, the instantaneous relay must be
prevent its operation during magnetizing inrush or
set for the worst case currents, i.e, the system con-
current transformer saturation on external faults.
figuration that provides the maximum fault current.
Since all these variables may change depending on
For any other system configuration, the current may
system conditions, the transformer relay settings must
be less and the instananeous relay may not pick up.
assume some normal condition upon which pickup
With adaptive relaying, the system configuration can
and slope can be based. The effect is to reduce the
be communicated to all terminals and the resulting
fraction of the transformer winding being protected by
current change when the remote breaker opens can be
the relay. Since many of these variables are known
determined and the relay setting changed accordingly.
during the pre-fault state, adaptive relays can be ad-
In case of impedance relays, the opening of the breaker
justed without the need to accommodate any variable
at the remote end can be communicated to the relays,
parameters. The power transformer tap setting can be
and Zone1 setting of the relay can be made t o over-
determined by limit switches or by voltage measure-
reach the remote end. Since these are steady-state
ment. The current transformer ratios and calibration
system configuration changes, there is no need for a
curves can be stored in the relay and the pickup ad-
high-speed communication channel. The information
justed accordingly. Magnetizing inrush accompanies
can be sent off-line between stations or from a central
energizing of the transformer or recovery from a fault.
control point.
Both conditions can be determined by breaker posi-
Probably one of the best known relay problems is
tion, and voltage measurements and the harmonic
the multi-terminal transmission line and the com-
restraint provided to prevent relay operation from
promise settings associated with the presence or ab-
inrush can be enabled or disabled as required.
s e n c e of infeed. As discussed a b o v e , Zone-1
protection at A, B and C (see Figure 2) must always
underreach any remote terminal. It must always, there- Automatic Reclosing
fore, be set assuming no infeed from any of the other Adaptive control of automatic reclosing of circuit
lines. When infeed is present, i.e., all terminals con- breakers has attracted considerable attention recent-
tributing to the fault, the relay reach is further reduced. ly. Although it is not usually thought of in such terms,
This is not particularly desirable, but it is safe. Zone2 the use of dead-line or check-synchronizing in reclos-
protection must always overreach the complete line. ing relays is adaptive in nature. Also adaptive are the
In this case, the setting is determined with all infeeds interlocks which may be used with high speed reclos-
present. By continuously transmitting the system con- ing t o govern its use, e.g., to allow reclosing after single
figuration, i.e., circuit breaker status, to all terminals,
the presence or absence of infeed is known and the A B
relays set accordingly. This transmission is done
A
during steady-state operation and can b e accom- fault
modated by a slow speed channel. A more sophisti-
cated adaptive scheme makes use of a high speed
communication channel over which the actual ter-
minal currents are transmitted and the exact apparent
impedance seen by the relays can be calculated.

Transformer Protection ~

Setting the pickup and slope of the differential relays Figure 2. A multi-terminal transmission line protection prob-
for power transformer protection is another well lem. Setting of the distance relay at A (similarly at B and C)
is complicated by the presence of the third terminal and its
known compromise. The slope and pickup settings
contribution to the fault.
must be selected to account for current transformer
July 1990 49

Authorized licensed use limited to: G H Patel College of Eng & Technology. Downloaded on November 19, 2009 at 01:02 from IEEE Xplore. Restrictions apply.
phase faults, and block it after three phase faults. This Adaptive Control of Defective Relays
concept can be carried much further. Sympathy trips One of the earliest advantages recognized with com-
are incorrect trips, usually at one end only, that occur puter relays was their ability to monitor themselves
when some event other than an internal fault occurs. and to report their condition to a central location. This
Two common causes are loss of a blocking signal or ability has been taken several steps beyond this simple
loss of directionality. With adaptive relays, t h e approach. It was at first considered sufficient that a
presence (indeed the exact location) of a fault, is defective relay should alarm and remove itself from
known to a degree not possible with conventional service. In this way no damage could result and
relays. Coupling this knowledge into the reclosing maintenance could be scheduled immediately. Since
circuits will allow an incorrectly tripped breaker to there was always a redundant protection system, this
reclose immediately without the usual delays required action appeared justified. As the digital relay and
for fault clearing and synchronizing interlocks. This adaptive schemes were studied in greater detail, other
will significantly mitigate the effect of the incorrect solutions to the problem of defective relays became
trip. attractive. For instance, the ability to share data is one
Another reclosing concept that has been recently of the major advantages of computers connected in
introduced in several forums is the idea of preventing s o m e c o m m u n i c a t i o n n e t w o r k . With t o d a y s
reclosing into any fault other than a line-to-ground or microprocessors it is possible to load all of the algo-
line-to-line fault. This is done by closing one phase at rithms in all of the microprocessors, activating, under
one end and measuring all of the resulting phase volt- normal conditions, only the appropriate algorithm. If
age on the unenergized phases. The impressed and a relay detects that it can no longer function properly,
coupled voltages can then be analyzed, and reclosing a defective relay could transfer its function t o a healthy
permitted or aborted as appropriate (see Figure 3). relay, invoking the required algorithm and settings and,
using the shared data, maintain the integrity of the
Security and Dependability Balance protective system. Of course, if a relay can analyze its
If we allow our imagination a little more freedom we own failure it can d o many other things t o continue
can, with adaptive protection and control, address a operating in a somewhat degraded, but acceptable,
far more fundamental issue: the conflict referred to manner. For instance, if Zone-1 element is defective,
earlier between dependability and security of protec- Zone2 can now assume a new setting for an instanta-
tion. This is a dilemma that must be resolved very neous trip and revert to its normal time delay for
early in the engineering phase of an installation and backup. The reverse is also true: Zone-1 can extend its
cannot be altered without much expense and time. setting to the Zone-2 reach and add a time delay. These
Dependability is generally achieved through redun- are software changes actuated either automatically or
dant relaying, and a degree of security is achieved by command from a central location.
through a complex arrangement of interlocks. The
resulting protection system is invariably biased Other Adaptive Relaying Possibilities
toward greater dependability at t h e expense of Several other adaptive relaying ideas will be found
security or toward greater security at the expense of in the literature. Among these is the idea of adaptive
dependability. For mature HV or EHV systems the bias out-of -step relaying. This falls under the general prob-
is generally toward dependability. This is because the lem of trying to predict the instability of a power
power system itself is redundant and it is vital that swing as it is developing. With accurate synchronized
faults be cleared with certainty-even if, on occasion,
there may be some false trips. On the other hand,
distribution circuits are not redundant, and here
security is the most important consideration. Even for v
mature HV and EHV systems, however, during major
outages or upon restoration following a cascading
series of outages, one may wish to revise this philoso-
phy of protection which is biased towards depend-
ability at the expense of security. In conventional
relaying technology, this adaptive shift of balance be-
tween dependability and security would be almost
impossible to achieve. With computer relays, this type
of change can be accomplished with ease. Figure 4
shows a conceptual adaptive relaying scheme to ac-
complish such a change.

50 IEEE Computer Applications in Power

Authorized licensed use limited to: G H Patel College of Eng & Technology. Downloaded on November 19, 2009 at 01:02 from IEEE Xplore. Restrictions apply.
Redundant Supervisory
Protection I Control continuously a power network as well as t h e protective
relays, and to adjust the protection performance a s t h e
network conditions change. We have shown that t h e
concept is not totally new, but the advent of computer
Protection #1 relaying will permit applications not previously pos-
sible. Certainly, the changes will not occur suddenly.
Protection #2 c They will be introduced as computer relays justify
Trip themselves, and will allow the engineering fraternity
Protection #3 time to adjust to the inherent advantages of this new
technology, and become familiar with t h e possibilities
Figure 4. Adaptive adjustment of dependability and security it offers. We believe the relaying community will accept
of protecitve relays. Depending upon the condition of the this challenge, and embrace a protection philosophy
power system, the redundant protection systems are used suited t o t h e new and demanding environment of the
in an AND, OR, TWO OUT OF THREE scheme to determine electric power transmission networks.
whether a trip should be issued.

phasor measurements from several buses, the goal of


For Further Reading
Study of Adaptive Transmission System Protection and Control:
real-time instability prediction seems achievable. One A.G. Phadke, J.S.Thorp, S.H.Horowitz; ORNL/SUB/85-2205C, U S .
could then foresee t h e use of adaptive out-of-step D e p a r t m e n t of Energy; available from Oak Ridge National
relays, which would change their functions from trip- Laboratory.
ping t o blocking, or vice-versa, a s the power swing Adaptive Power System Transmission Protection: G.D.-
Rockefeller, C.L. Wagner, J.R. Linders, K.L. Hicks, D.T.Rizy; O-
develops. Another idea is to make load-shedding RNL/SUB/85-2201C; U.S. Department of Energy; available from Oak
relays adapt to the condition where the frequency does Ridge National Laboratory.
not deviate much from its nominal value, yet there is a Computer Relaying for Power Systems: (Book) A.G. Phadke, J.S.
shortage (or excess) of generation in the system. This Thorp; John Wiley and Sons, 1988.
may b e assessed by real-time measurements per- Conference Proceedings of the Blacksburg Conferences on Com-
puter Relaying-1987 & 1989, available from Virginia Polytechnic
formed at t h e system boundary, and computing a Institute and State University, Blacksburg, Va.
dynamic Area Control Error. The interested reader is
referred to the literature for a fuller explanation of
these and other ideas on adaptive relaying. Biographies
Arthur G. Phadke received his Ph.D. in electric
Industry Activities power engineering from the University of Wisconsin-
In addition t o the efforts of individual researchers in Madison and his M.S. from the Illinois Institute of Tech-
adaptive relaying, several industry activities address nology, Chicago. Dr. Phadke was a systems engineer
the issues raised by this subject. In 1985, the U.S. with Allis Chalmers, Consulting Engineer at American
Department of Energy authorized studies into the area Electric Power Service Corp., and is presently AEP
of Adaptive Protection. Results of these studies have Professor of Electrical Engineering at Virginia Polytech-
been published. In addition to the reports, several nic Institute and State University, Blacksburg, Va.
technical papers were presented at IEEE and CIGRE Dr. Phadke is a Fellow of IEEE, member of HKN, Tau
annual meetings, and at t h e Blacksburg Conferences on Beta Pi and Sigma Xi. In 1986 he was honored by t h e
Computer Relaying. Very lively discussions ensued, Edison Electric Institute as Power Engineering Profes-
which have been recorded in the proceedings of these sor of the year, and in 1987 received t h e Distinguished
meetings. At present a CIGRk working group is being Service Award from t h e College of Engineering,
formed to study and document the development of University of Wisconsin-Madison.
adaptive relaying. The Power System Relaying Com- Stanley H. Horowitz received his BSEE from t h e City
mittee of IEEE also has formed a working group on this College of New York. He was employed at American
subject, which is beginning its activity by issuing a Electric Power Service Corp for 38 years, retiring
questionnaire to determine relay engineers' percep- recently a s Consulting Electrical Engineer. H e is
tion of what protection and control functions are can- presently a private consultant in Columbus, Ohio.
didates for adaptive treatment. Some references on Mr. Horowitz is a Fellow of IEEE. He was Chairman
the subject article are listed in "For Further Reading". of the Power System Relay Committee of IEEE, Interna-
tional Chairman of ClGRE Study Committee 34-Protec-
Conclusions tion and Control, and member of t h e IEEE Executive
In this article we have described the ambivalence Board. He is author or co-author of numerous techni-
that exists about an emerging protective philosophy- cal papers and was editor of t h e IEEE Press Book
a philosophy that allows digital devices to monitor Protective Reluying for Power Systems.

July 1990 51

Authorized licensed use limited to: G H Patel College of Eng & Technology. Downloaded on November 19, 2009 at 01:02 from IEEE Xplore. Restrictions apply.

Vous aimerez peut-être aussi