Vous êtes sur la page 1sur 10

Project:

ETAP Page: 1
12.6.0H
Location: Date: 22-08-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: yrtyry Config.: Normal

Electrical Transient Analyzer Program

Short-Circuit Analysis

IEC 60909 Standard


3-Phase Fault Currents

Swing V-Control Load Total


Number of Buses: 1 0 2 3

XFMR2 XFMR3 Reactor Line/Cable Impedance Tie PD Total


Number of Branches: 1 0 0 0 0 1 2

Synchronous Power Synchronous Induction Lumped


Generator Grid Motor Machines Load Total
Number of Machines: 0 1 0 0 0 1

System Frequency: 50.00 Hz

Unit System: Metric

Project Filename: yrtyry

Output Filename: C:\ETAP 1260\yrtyry\Untitled.SI1


Project:
ETAP Page: 2
12.6.0H
Location: Date: 22-08-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: yrtyry Config.: Normal

Adjustments

Apply Individual
Tolerance Adjustments /Global Percent

Transformer Impedance: Yes Individual

Reactor Impedance: Yes Individual

Overload Heater Resistance: No

Transmission Line Length: No

Cable Length: No

Apply Individual
Temperature Correction Adjustments /Global Degree C

Transmission Line Resistance: Yes Individual

Cable Resistance: Yes Individual


Project:
ETAP Page: 3
12.6.0H
Location: Date: 22-08-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: yrtyry Config.: Normal

Bus Input Data

Bus Initial Voltage


ID Type Nom. kV Base kV Sub-sys %Mag. Ang.

Bus1 SWNG 11.000 11.000 1 100.00 0.00

Bus2 Load 0.400 0.400 1 100.00 0.00

Bus3 Load 0.400 0.400 1 100.00 0.00

3 Buses Total

All voltages reported by ETAP are in % of bus Nominal kV.


Base kV values of buses are calculated and used internally by ETAP .
Project:
ETAP Page: 4
12.6.0H
Location: Date: 22-08-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: yrtyry Config.: Normal

2-Winding Transformer Input Data

Transformer Rating Z Variation % Tap Setting Adjusted


ID MVA Prim. kV Sec. kV %Z X/R + 5% - 5% % Tol. Prim. Sec. %Z

T1 3.500 11.000 0.400 7.15 8.50 0 0 0 0 0 7.1500


Project:
ETAP Page: 5
12.6.0H
Location: Date: 22-08-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: yrtyry Config.: Normal

Branch Connections

CKT/Branch Connected Bus ID % Impedance, Pos. Seq., 100 MVAb


ID Type From Bus To Bus R X Z Y

T1 2W XFMR Bus1 Bus3 22.84 194.11 195.45

CB1 Tie Breaker Bus3 Bus2


Project:
ETAP Page: 6
12.6.0H
Location: Date: 22-08-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: yrtyry Config.: Normal

Power Grid Input Data

% Impedance
Power Grid Connected Bus Rating 100 MVA Base
ID ID MVASC kV R X" R/X

U1 Bus1 500.000 11.000 3.28798 19.72788 0.17

Total Connected Power Grids ( = 1 ): 500.000 MVA


Project:
ETAP Page: 7
12.6.0H
Location: Date: 22-08-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: yrtyry Config.: Normal

SHORT-CIRCUIT REPORT

3-Phase fault at bus: Bus1

Nominal kV = 11.000
Voltage c Factor = 1.10 (User-Defined)
Peak Value = 59.916 kA Method C
Steady State = 26.243 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude
Bus1 Total 0.00 4.314 -25.886 6.0 26.243

Bus3 Bus1 0.00 0.000 0.000 999.9 0.000

U1 Bus1 100.00 4.314 -25.886 6.0 26.243

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 26.243 34.235 21.985

0.02 26.243 29.297 13.024

0.03 26.243 27.354 7.715

0.04 26.243 26.638 4.570

0.05 26.243 26.382 2.707

0.06 26.243 26.292 1.604

0.07 26.243 26.260 0.950

0.08 26.243 26.249 0.563

0.09 26.243 26.245 0.333

0.10 26.243 26.244 0.198

0.15 26.243 26.243 0.014

0.20 26.243 26.243 0.001

0.25 26.243 26.243 0.000

0.30 26.243 26.243 0.000


Project:
ETAP Page: 8
12.6.0H
Location: Date: 22-08-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: yrtyry Config.: Normal

3-Phase fault at bus: Bus2

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 167.428 kA Method C
Steady State = 69.704 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude
Bus2 Total 0.00 8.481 -69.186 8.2 69.704

Bus1 Bus3 89.89 8.481 -69.186 8.2 69.704

U1 Bus1 100.00 0.308 -2.516 8.2 2.535

Bus3 Bus2 0.00 8.481 -69.186 8.2 69.704

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 69.704 96.733 67.071

0.02 69.704 83.314 45.635

0.03 69.704 76.307 31.049

0.04 69.704 72.835 21.126

0.05 69.704 71.171 14.374

0.06 69.704 70.387 9.780

0.07 69.704 70.021 6.654

0.08 69.704 69.851 4.527

0.09 69.704 69.772 3.080

0.10 69.704 69.736 2.096

0.15 69.704 69.705 0.306

0.20 69.704 69.704 0.045

0.25 69.704 69.704 0.006

0.30 69.704 69.704 0.001


Project:
ETAP Page: 9
12.6.0H
Location: Date: 22-08-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: yrtyry Config.: Normal

3-Phase fault at bus: Bus3

Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 167.428 kA Method C
Steady State = 69.704 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude
Bus3 Total 0.00 8.481 -69.186 8.2 69.704

Bus1 Bus3 89.89 8.481 -69.186 8.2 69.704

U1 Bus1 100.00 0.308 -2.516 8.2 2.535

Bus3 Bus2 0.00 0.000 0.000 9999.0 0.000

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 69.704 96.733 67.071

0.02 69.704 83.314 45.635

0.03 69.704 76.307 31.049

0.04 69.704 72.835 21.126

0.05 69.704 71.171 14.374

0.06 69.704 70.387 9.780

0.07 69.704 70.021 6.654

0.08 69.704 69.851 4.527

0.09 69.704 69.772 3.080

0.10 69.704 69.736 2.096

0.15 69.704 69.705 0.306

0.20 69.704 69.704 0.045

0.25 69.704 69.704 0.006

0.30 69.704 69.704 0.001


Project:
ETAP Page: 10
12.6.0H
Location: Date: 22-08-2017
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: yrtyry Config.: Normal

Short-Circuit Summary Report

3-Phase Fault Currents

Device Capacity (kA)


Bus Device Short-Circuit Current (kA)
Making
ID kV ID Type Peak Ib sym Ib asym Idc I"k ip Ib sym Ib asym Idc Ik
Bus1 11.000 Bus1 Bus 26.243 59.916 26.243

Bus2 0.400 Bus2 Bus 69.704 167.428 69.704

Bus3 0.400 Bus3 Bus 69.704 167.428 69.704

ip is calculated using method C


Ib does not include decay of non-terminal faulted indunction motors
Ik is the maximum steady state fault current
Idc is based on X/R from Method C and Ib as specified above

LV CB duty determined based on service rating.


Total through current is used for device duty.
* Indicates a device with calculated duty exceeding the device capability.
# Indicates a device with calculated duty exceeding the device marginal limit . ( 95 % times device capability)