DESIGN CALCULATIONS OF HVAC SYSTEM


00 28/05/2013 SATECH

01 13/08/2013 SATECH

CONSTRUCTION OF 132/13.8KV SUBSTATION #8521 IN


BY

SHAQRA UNIVERSITY
DATE
NO.

REVISIONS
DRAWN

BY SAS
DATE 13/08/2013
CHECKED

BY SAS
DATE 13/08/2013
OPRG. DEPT.

BY ___________
DATE

ENG`G DEPT.

BY ___________
DATE _______
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 01 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

CERT`D APR`D

SVR

SVR
DRAWING COMPLETION CERTIFICATE (DCC)

AN DCC NO. _____________ DATE: ______________

AN

CONTENTS
CHK'D

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
SAS

SAS

SL.# DESCRIPTION PAGE.NO


1 Scope 3
2 Applicable Codes, Standards and Reference Documents 3
3 HVAC System Description & Scope of Work 4
INCORPORATED SEC COMMENTS

3.1 HVAC System Operation Description 5


ISSUED FOR BASE DESIGN

4 HVAC System Sequence of Operation 9


5 Load Estimation for HVAC System 10
5.1 Design Parameter 11
DESCRIPTION

5.2 Co-efficients of Transmission (U-Value) 12


5.2.1 Roof with False ceiling (U value), Roof without False ceiling (U value) 12
5.2.2 Floor (U value) 13
5.2.3 Outside Wall (U value) 13
5.2.4 Partition (U value) 14
5.2.5 Metal Door (U value) 14
5.3 Internal Load Data 15
5.3.1 Lighting 15
5.3.2 People 16
5.3.3 Equipment 17
JOB ORDER

5.4 HVAC Data Gathering Sheet 18


NO.
109

109

5.5 Ventilation, Exhaust and Pressurization calculation 19


5.5.1 Ventilation & Pressurization calculation for Group-1 zones 19
00 28/05/2013 SATECH

01 13/08/2013 SATECH

5.5.2 Ventilation & Pressurization calculation for Group-2 zones 24


BY

5.5.3 Ventilation & Pressurization calculation for Group-3 zones 29


5.5.4 Battery Room Exhaust Calculation 34
DATE

5.5.5 Toilet Room Exhaust Calculation 34


5.6 Summary of Cooling Load 36
NO.

6 Smoke Purge Fan sizing 38


REVISIONS 7 Sand Trap Louver sizing 39
DRAWN

ATTACHEMENTS
BY SAS
DATE 13/08/2013 APPENDIX-1 a. Heat dissipation values reference sheets
CHECKED b. U value reference sheets

BY SAS APPENDIX-2 a. Computer generated load calculation (using ELITE CHVAC software)
DATE 13/08/2013
OPRG. DEPT. APPENDIX-3 Reference Drawings
1 CA-317116 Sheet 01 of 02
BY ___________ 2 CA-317117 Sheet 01 of 01
DATE 3 CA-317118 Sheet 01 of 02
ENG`G DEPT. 4 CA-317120 Sheet 01 of 02
5 CA-317120 Sheet 02 of 02
BY ___________ 6 CA-317118 Sheet 02 of 02
DATE _______ 7 CA-317122 Sheet 01 of 03
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.

DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 02 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
NG-E (2012/01)
http://boilersinfo.com/

CERT`D APR`D

SVR

SVR
DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
SCOPE:
CHK'D

SAS

SAS

The design criteria established, herein, for the mechanical HVAC system of the construction of
SHAQRA132KV/13.8KV SUBSTATION #8521, located in Riyadh area, KSA. The system
should be designed for minimum maintenance, efficient operation and reliability as well.
INCORPORATED SEC COMMENTS

During design procedures, coordination has been taken place with other engineering
ISSUED FOR BASE DESIGN

disciplines for the HVAC project. Furthermore, the report, herein, intends to define, discuss,
and conclude the design of the mechanical HVAC system for the substation and shall
DESCRIPTION

represent this strategy by the following means:

Define the essential guidelines, codes, standards and references that will be followed
during the preparation of the design works as well as drawings documents.

Written brief description of design criteria and HVAC system and selection.
Load calculations and demand estimation.

Zoning details.
JOB ORDER
NO.
109

109

HVAC design drawing layouts.


00 28/05/2013 SATECH

01 13/08/2013 SATECH
BY
DATE
NO.

2.0 APPLICABLE CODES, STANDARDS AND REFERENCE DOCUMENTS:


REVISIONS
DRAWN 2.1 ARI-210: Unitary Air Conditioning Equipment
2.2 ARI-360: Commercial and Industrial Unitary Air Conditioning Equipment
BY SAS 2.3 NFPA-70: Terminal Lugs.
DATE 13/08/2013 2.4 ASHRAE American Soceity of Heating Refrigeration and Air conditioning
CHECKED Engineers
2.5 SMACNA Sheet Metal and Air conditioning Contractors National Association
BY SAS 2.6 NFPA National Fire Protection Code
DATE 13/08/2013 2.7 UL Underwriters Laboratories
OPRG. DEPT. 2.8 IBC International Building code
2.9 73-TMSS-01 Material Standard Specification of Air Conditioning Units,
BY ___________ 2.10 73-TMSS-05 Material Standard Specification of Centrifugal Exhaust fan
DATE 2.11 TES-K-100.01 Heating Ventilation and Air conditioning Design
ENG`G DEPT. 2.12 TCS-K-100.01 Construction Standard for HVAC System
2.13 ASTM American Soceity of Testing and Materials
BY ___________ 2.14 ANSI / ASME B16.22: Fittings
DATE _______
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 03 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

CERT`D APR`D.

SVR

SVR
DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
3 HVAC SYSTEM DESCRIPTION AND SCOPE OF WORK
CHK'D

SAS

SAS

The scope of work includes designing, engineering, procurement of material, manufacturing,


delivery, installation, testing and commissioning of the HVAC system for the SHAQRA
132Kv/13.8Kv Substation #8521, located in Riyadh area, KSA. The scope of work is limited to
the scope of work mentioned in the SEC 4.2 of PTS#11CN129.
INCORPORATED SEC COMMENTS
ISSUED FOR BASE DESIGN

Scope of work includes the provision of HVAC system for the following spaces within the
DESCRIPTION

substation building and which described, hereinafter, as :

1 132KV G.I.S ROOM (Ground Floor) Group-01


2 132KV G.I.S ROOM (Basement Floor) PACU 01A,01B
3 Stair-1

4 13.8KV SWGR A Room (Ground Floor) GROUND +


5 13.8KV SWGR B Room (Ground Floor) BASEMENT
JOB ORDER

6 13.8KV SWGR C Room (Ground Floor)


NO.
109

109

7 Fm200 Room Group-02


8 Toilet PACU 02A,02B
00 28/05/2013 SATECH

01 13/08/2013 SATECH

9 13.8KV SWGR A Room (Basement Floor)


BY

10 13.8KV SWGR B Room (Basement Floor)


11 13.8KV SWGR C Room (Basement Floor)
DATE

12 Stair-2
13 Battery Room
NO.

REVISIONS 14 Control Room Group-03 GROUND


DRAWN 15 Telecom Room PACU 03A,03B FLOOR

BY SAS
DATE 13/08/2013
CHECKED

BY SAS
DATE 13/08/2013
OPRG. DEPT.

BY ___________
DATE

ENG`G DEPT.

BY ___________
DATE _______
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 04 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

CERT`D APR`D.

SVR

SVR
DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
The HVAC system to be designed, herein, is to serve the 132KV/13.8KV Substation.
CHK'D

SAS

SAS

The HVAC system shall covers all the items indicated above; which consists of the
different spaces of the Building in both the ground floor as well as basement. Where,
HVAC system is designed, herein, in order to ensure the desired indoor environment for
optimum operation of equipment performance within the substation.
INCORPORATED SEC COMMENTS
ISSUED FOR BASE DESIGN

The system shall be designed, herein, for each group to be provided with two independent
set of direct expansion packaged type; roof mounted air conditioning units suitable for
DESCRIPTION

outdoor installation. Complete with 100% redundancy; (one unit duty plus one standby)
which works for alternate cyclic operation or otherwise in case of failure.

Each unit of the pair runs independently of the other and can fulfill the concerned zone
requirements as per the load demands/variation. For each set of packaged units there is
one smoke purging fan, which can be operated manually in case of smoke existence or
fire case.

3.1 HVAC System Operation Description

Air conditioning system for substation is divided into three groups. Each group comprises
JOB ORDER

two roof mounted Packaged Units (l00%Duty & 100% stand by). (PACU-1A /1B,
NO.
109

109

PACU-2A / 2B and PACU-3A / 3B)


00 28/05/2013 SATECH

01 13/08/2013 SATECH

HVAC PACU system includes Compressors, Condenser coils & Fans, Evaporator coil &
BY

fans, fresh air filter, pre-filter, bag filter, and controls. PACU has motorized on/off type
isolation damper, supplying conditioned air at design temperature and humidity to the
DATE

respective area. Three (3) hour fire rated motorized fire/smoke dampers are provided on
the main supply and return air duct.
NO.

REVISIONS 2. Operation:
DRAWN The unit is operated from the HVAC control panel through the relevant hand,off,auto
selector switch which gives the following selections:
BY SAS Hand mode: The unit is energized manually from the control Panel
DATE 13/08/2013 Off mode: The unit is de-energized.
CHECKED Auto mode: The duty/stand by unit is automatically selected by the DDC controller

BY SAS The selected duty unit is energized and de-energized automatically according to the
DATE 13/08/2013 times, as programmed. DDC controller alternates the duty/standby units according to
OPRG. DEPT. running hours limits (200 hours) or as required. DDC controller operates the standby
unit automatically upon failure of the duty unit due to:
BY ___________
DATE 1. Evaporator fan trip 5. Compressor high pressure
ENG`G DEPT. 2. Evaporator fan belt failure 6. Compressor low pressure
3. Cond. Fan trip 7. Compressor oil pressure
BY ___________ 4. Compressor trip 8. Power failure.
DATE _______
APPROVAR/CERTF. When the opening of the damper is proved by the end switch, the fan starts.
INFORMATION The motorized volume damper of the standby unit will remain closed.
DCC NO. _______
REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 05 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

CERT`D APR`D.

SVR

SVR
DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
Local user interface:
CHK'D

SAS

SAS

Removable pot unit is provided on the panel door. The unit is connected to the DDC
via communication cable. Removable pot unit provides operation and monitoring of the
system.
INCORPORATED SEC COMMENTS

Smoke detection:
ISSUED FOR BASE DESIGN

Smoke conditions are detected by the smoke detectors and connected to fire alarm panel.
Upon smoke detection, the system is de-energized and the fire/smoke dampers will be
DESCRIPTION

closed. The dampers will open first when the system is restarted. A visual and audible
indication for smoke alarm is provided on the hvac control panel.

Temperature control:
(a) Cooling:
Space conditions are measured by a room mounted digital thermostat and the temperature
measured values are transmitted to the DDC (mec) controller via analog input module
which compares the actual values with the required set point If the temperature is higher
than the set point, the DDC controller energizes the lead compressor via digital output
module. When further cooling is required, the second compressor will be energized as
well both the compressors will run until the set point is achieved. The temperature set
JOB ORDER

point selection is done on the local user interface (pot) provided on the HVAC control panel.
NO.
109

109

(b) Dehumidification Control:


00 28/05/2013 SATECH

01 13/08/2013 SATECH

Space air humidity conditions are measured by a room mounted temperature/humidity


BY

detector and the measured humidity values are transmitted to the DDC (mec) controller
via analog Module.
DATE

The controller compares the actual values with required Humidity values (50%) and if
the humidity is higher, the controller overrides the temperature control process and
NO.

operates the compressors to dehumidify the air to maintain the set point (adjustable
REVISIONS 0-100%). As selected on the local user interface on the HVAC control panel .
DRAWN

Air filter dirty:


BY SAS Dirty filter conditions are detected by the differential pressure switches installed
DATE 13/08/2013 across the filters are transmitted to the DDC controller via digital input module. If the
CHECKED Differential pressure setting is reached; the led is illuminated ON the digital input
module/monitoring on the local interface user. As well as visual alarm on the HVAC
BY SAS control panel to indicate that the filter is dirty.
DATE 13/08/2013
OPRG. DEPT. No Airflow / Fan belt failure:
Airflow failure due to broken fan belt is detected by the Differential pressure switches
BY ___________ installed across each Fan and the signal is transmitted to the DDC controller via
DATE Digital input module. In the event of no air flow. The duty unit will be de-energized, lts
ENG`G DEPT. isolation damper will be closed and the isolation damper of the standby unit will open
to run the unit automatically. A pilot lamp is illuminated on the control panel as well
BY ___________ as a led on the digital input module / operation module to indicate air flow failure of
DATE _______ the duty unit.
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 06 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

CERT`D APR`D.

SVR

SVR
DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
Fire Alarm:
CHK'D

SAS

SAS

Upon receipt of the fire signal from the central fire alarm panel. The system will be
de-energized.

Control power supply:


INCORPORATED SEC COMMENTS

Control power to the panel and field mounted controls requires 24 vac operating
ISSUED FOR BASE DESIGN

voltage is supplied by a low voltage control transformer.


DESCRIPTION

Local monitoring:
The following status of each PACU is indicated on the HVAC control panel.

1. Evaporator fan run


2. Evaporator fan trip.
3. Isolation damper open
4. Isolation damper close.
5. Fan belt fail
6. Air filter dirty
7. Compressor run.
8. Compressor fault
JOB ORDER

9. Compressor low pressure.


NO.
109

109

10. Compressor high pressure.


11. Compressor oil pressure.
00 28/05/2013 SATECH

01 13/08/2013 SATECH

12. Power fail


BY

13. Condenser fan run.


14. Condenser fan trip
DATE

15. Room high temperature


NO.

Local common monitoring:


REVISIONS 1. Fire indication- (signal from fire alarm panel)
DRAWN 2. Supply air fire / smoke (mf/sd) damper open
3. Supply air fire / smoke (mf/sd) damper close
BY SAS 4. Return air fire / smoke (mf/sd) damper open
DATE 13/08/2013 5. Return air fire / smoke (mf/sd) damper close.
CHECKED

Temperature/Humidity Indications:
BY SAS 1. Temperature / humidity room sensor (electronic type) for measuring of temperature
DATE 13/08/2013 and relative humidity for all sensitive areas shall be provided as indicated. "High
OPRG. DEPT. temperature" indication shall be displayed in the portable operator terminal.
2. Duct temperature sensor, one in supply and one in return duct shall be provided
BY ___________ to monitor operating air temperature via portable operator terminal
DATE

ENG`G DEPT. Remote monitoring:


The dry contacts are provided in the control panel for remote monitoring at central
BY ___________ control room and to interface with SCADA system for the following
DATE _______ 1. PACU- DUTY, common fault/trouble.
APPROVAR/CERTF. 2. PACU-STANDBY, common fault/trouble.
INFORMATION 3. Room high temperature.
DCC NO. _______
REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 07 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

CERT`D APR`D.

SVR

SVR
DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
The type of fault/ trouble can be checked which is indicated by the pilot lamp on the
CHK'D

SAS

SAS

HVAC control panel for the following:


1. Evaporator fan trip.
2. Evaporator fan belt fail
3. Filter dirty
INCORPORATED SEC COMMENTS

4. Compressor fault.
ISSUED FOR BASE DESIGN

5. Compressor low pressure.


6. Compressor high pressure.
DESCRIPTION

7. Compressor oil pressure.


8. Power fail
9. Fire.
10. Smoke.
11. Condenser fan trip

Visual and audible alarm indications:


The following faults are indicated via pilot lamps and a common alarm is sounded on
the HVAC control panel. A push button is provided to silence the audible alarm but
the visual indication shall persist until the fault is rectified:
1. Evaporator fan trip.
JOB ORDER

2. Evaporator fan belt fail


NO.
109

109

In Case of Fire:
00 28/05/2013 SATECH

01 13/08/2013 SATECH

If presence of smoke is detected by duct mounted smoke detector the FACP will
BY

send signal to HVAC Control panel to:


1- Shut down the PACU's.
DATE

2- Close the combination motorized fire and smoke dampers (MF/SD's) and
motorized volume dampers (MVD's)
NO.

A time delay relay will be provided, so that MF/SD's and MVD's will be fully
REVISIONS opened before the HVAC System is re-started.
DRAWN Resetting the fire alarm system in case of fire alarm activation shall automatically re-start
the HVAC system.
BY SAS
DATE 13/08/2013 In the event of smoke purging operation:
CHECKED After fire is extinguished, the smoke purging fans (SPF's) can be manually operated
through a remote switch located outside the building to exhaust smoke and gas out
BY SAS of the protected spaces.
DATE 13/08/2013
OPRG. DEPT. SPF's are manually operated either on the HVAC panel or through a remote switch
located outdoor. Operation of MF/SD's and MVD's are interlocked with SPFs.
BY ___________
DATE All MF/SD's and MVD's shall remain close. After the SPF's switch is manually
ENG`G DEPT. depressed; the MVD for purging fan shall swing open. MF/SD's and MVD's in the
supply air duct shall be at 100% fully closed position while in the return duct, the
BY ___________ MF/SD's is opened and the MVD remains close,freshair intake MVD also remain closed.
DATE _______ Interlocking and time delay device shall be provided to ensure that all selected dampers
APPROVAR/CERTF. are in open/close position before SPF's are energized. SPF's can be energized only
INFORMATION when PACUs are not in operation.
DCC NO. _______
REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 08 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

CERT`D APR`D.

SVR

SVR
DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
4. HVAC SYSTEM SEQUENCE OF OPERATION
CHK'D

SAS

SAS

4.1 NORMAL MODE


Each packaged unit is equipped with supply air, return / recirculated air and smoke
purge / exhaust air dampers, along with outdoor air dampers. These dampers control
and regulate the airflow rates under various load conditions.
INCORPORATED SEC COMMENTS
ISSUED FOR BASE DESIGN

Each packaged unit of the pair has individual supply and return air dampers while
exhaust air damper is common. Separate ducting from each unit of the pair combines
DESCRIPTION

into one common header (sized for 100% of supply air from a single unit).

For the duty unit, the supply & return dampers are fully opened and SPF's exhaust air
damper is fully closed; while outdoor air damper is set to minimum open position to
provide firesh air as per the requirement.

The duty & standby units will operate on shift basis. The changeover from duty to
standby unit or viceversa can be either automatic or manual.

The temperature controller (or Thermostat) will decide whether cooling is required or
not, by comparing the set point with actual space temperature, if cooling is required
JOB ORDER

then DX cooling stages have to be activated/deactivated based on the cooling demand.


NO.
109

109

The temperature controls shall be provided as part of the AC unit by the control panel
00 28/05/2013 SATECH

01 13/08/2013 SATECH

Supplier/Installer. The thermostat shall be cooling type with minimum of 2 stage of


BY

mechanical cooling. The thermostat shall be mounted on the return air stream @ 1.5m.
DATE

4.2 SMOKE PURGE MODE


In case the smoke detector detects smoke, FACP sends signal to HVAC control panel
NO.

indicating the smoke presence, then the duty packaged unit shall be automatically
REVISIONS de-energized and all temperature control function shall stop.
DRAWN

During the smoke purge operation all PACUs (Duty and Standby) isolation dampers
BY SAS (supply, return and outdoor air) will be closed and MF/SDs for return duct is set to open
DATE 13/08/2013 position and smoke purging fan shall be activated to clear the smoke and products of
CHECKED combustion from the concerned zone (s).

BY SAS Smoke purging fan is to operate to exhaust smoke from the zones in the event of fire or
DATE 13/08/2013 heavy smoke conditions. It should be possible to manually run the smoke purge fan
OPRG. DEPT. either from the HVAC control panel or from smoke purge fan isolating switch.

BY ___________ After the smoke purging operation ends, it should be possible to restart the air
DATE conditioning unit by resetting the HVAC control panel.
ENG`G DEPT.

BY ___________
DATE _______
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 09 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

CERT`D APR`D.

SVR

SVR
DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
5. LOAD ESTIMATION FOR HVAC SYSTEM
CHK'D

SAS

SAS

Load calculations shall be carried out for cooling/heating seasons. During calculation
procedures, the following items which represent the main sources of heat gain and/or
loss in order to reach a proper sizing of the A/C units shall be considered. Some of these
items are:
INCORPORATED SEC COMMENTS

Solar heat gain


ISSUED FOR BASE DESIGN

Transmission load through different building construction


Equipment & lighting heat gain
DESCRIPTION

Human occupancy heat gain


Fresh air load
JOB ORDER
NO.
109

109
00 28/05/2013 SATECH

01 13/08/2013 SATECH
BY
DATE
NO.

REVISIONS Cooling load calculations will be performed based on ASHRAE cooling load calculation
DRAWN method (CLTDs) and Elite international software program shall be used to compute the
above requirements.
BY SAS
DATE 13/08/2013
CHECKED

BY SAS
DATE 13/08/2013
OPRG. DEPT.

BY ___________
DATE

ENG`G DEPT.

BY ___________
DATE _______
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 10 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

CERT`D APR`D.

SVR

SVR
DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS

5.1 DESIGN PARAMETER

5.1.1 SITE CONDITION


INCORPORATED SEC COMMENTS
ISSUED FOR BASE DESIGN

5.1.1.a Site Location RIYADH


5.1.1.b Site Elevation 635.5 m (above mean sea level)

5.1.2 DESIGN CONDITION


Outdoor Temperature During Summer
5.1.2.a Design ambient Dry bulb temperature 48 8C (118.4 8F)
5.1.2.b Design ambient Wet bulb temperature 24.4 8C (76 8F)
5.1.2.c Daily Range 15.7 8C (60.26 8F)
Design Month and Time August (4 pm)

Outdoor Temperature During Winther


JOB ORDER

5.1.2.d Design ambient Dry bulb temperature 5.1 8C (41.18 8F)


NO.
109

109

5.1.2.e Noise level @2M distance in open air 60 dB(A)


00 28/05/2013 SATECH

01 13/08/2013 SATECH
BY

Indoor Conditions
5.1.2.f Design Temprature 25 8C (77 8F)
DATE

5.1.2.g Relative Humidity 50 %RH


5.1.2.h Equipment Operation 24 Hrs
NO.

5.1.2.i Noise Level 45 dB(A)


REVISIONS
DRAWN 5.1.2.j Maximum wind speed 17 kmph (11 MPH) (NE)
5.1.2.k Over pressurization 0.2 in of wg (50 Pa)
BY SAS
DATE 13/08/2013
CHECKED

BY SAS
DATE 13/08/2013
OPRG. DEPT.

BY ___________
DATE
ENG`G DEPT.

BY ___________
DATE _______
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 11 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

CERT`D APR`D.

SVR

SVR
DRAWING COMPLETION CERTIFICATE (DCC)

AN DCC NO. _____________ DATE: ______________

AN
CHK'D

SAS

SAS

5.2
CO-EFFICIENT OF TRANSMISSION ( U-VALUE)

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OFNational Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
The resistance values are taken from ASHRAE Fundamentals Table 1 & 4 cooling and
heating load manual, unless otherwise specified.
INCORPORATED SEC COMMENTS
ISSUED FOR BASE DESIGN
DESCRIPTION

5.2.1 Roof with suspended ceiling (U Value)


Material R-value 8F- Ref.Document
Construction Detail Material Specification
Thickness ft-h/Btu) ASHRAE Table

1.Outside Air Film-Moving 15 mph 0.17 ASHRAE,CH-25,TB-1


2.Washed Gravel 50 mm 0.2 ASHRAE,CH-25,TB-1
3.Geo Textile 2 mm Negligible
7. Polystrene Rigid 100 mm 19.68 From vendor
5.Structural Screed 50 mm 0.22 ASHRAE,CH-25,TB-4
6.PVC Water Proofing 1.5 mm 0.12 ASHRAE,CH-25,TB-4
7.Concrete Core Slab 300 mm 1.126 ASHRAE,CH-25,TB-4
8. Ceiling air space 1 ASHRAE,CH-25,TB-4
9. Accoustic False Ceiling 20 mm 1.98 ASHRAE,CH-25,TB-4
JOB ORDER

10. Inside Still Air 0.92 ASHRAE,CH-25,TB-4


NO.
109

109

TOTAL R- VALUE 25.42


00 25/05/2013 SATECH

01 25/05/2013 SATECH

U-FACTOR-1/R 0.039 Btu / h-ft-8F


BY

Ref. Architectural drawing No:CA-317120 sheet 02 of 02


Note: U value for the roof is .039 Btu / h-ft-F, that is less than 0.06 Btu / h-ft-F (maximum value
DATE

according to TES-K-100) so 0.06 Btu / h-ft-F is used for calculation as it's more safer.
NO.

5.2.1 Roof without suspended ceiling (U Value)


REVISIONS Material R-value 8F- Ref.Document
Construction Detail Material Specification
DRAWN Thickness ft-h/Btu) ASHRAE Table

BY SAS 1.Outside Air Film-Moving 15 mph 0.17 ASHRAE,CH-25,TB-1


DATE ######## 2.Washed Gravel 50 mm 0.2 ASHRAE,CH-25,TB-4
CHECKED 3.Polypropylene Fabric 2 mm Negligible
7. Polystyrene Rigid 100 mm 19.68 From vendor
BY SAS 5.Structural Screed 50 mm 0.22 ASHRAE,CH-25,TB-4
DATE ######## 6.PVC Water Proofing 1.5 mm 0.12 ASHRAE,CH-25,TB-4
OPRG. DEPT. 7.Concrete Core Slab 300 mm 1.126 ASHRAE,CH-25,TB-4
8. Inside Still Air 0.92 ASHRAE,CH-25,TB-4
BY ___________
DATE TOTAL R- VALUE 22.44
ENG`G DEPT. U-FACTOR-1/R 0.045 Btu / h-ft-8F
Ref. Architectural drawing No:CA-317120 sheet 02 of 02
BY ___________ Note: U value for the roof is .039 Btu / h-ft-F, that is less than 0.06 Btu / h-ft-F (maximum value
DATE _______ according to TES-K-100) so 0.06 Btu / h-ft-F is used for calculation as it's more safer.
APPROVAR/CERTF.
INFORMATION * Refer Appendix 1
DCC NO. _______
REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.

DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION #8521 IN B C279 CE-316495 12 OF 43 01
CERTIFIED AND SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APR`D.

SVR

SVR
CERT`D DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS
INCORPORATED SEC COMMENTS
ISSUED FOR BASE DESIGN

5.2.2 Floor ( U Value)


Material R-value 8F- Ref.Document
Construction Detail Material Specification
Thickness ASHRAE Table
DESCRIPTION

ft-h/Btu)
1.Inside Air Film 0.68 ASHRAE,CH-25,TB-1
2.Concrete Slab 200 mm 2.1 ASHRAE,CH-25,TB-4
3. Inside Still Air 0.92 ASHRAE,CH-25,TB-1

TOTAL R- VALUE 3.70


U-FACTOR-1/R 0.270 Btu / h-ft-8F

But as per NGSA recommendation 0.4 Btu/hr ft F will be used in calculation.


JOB ORDER NO.

109

109
00 28/05/2013 SATECH

01 13/08/2013 SATECH
BY

5.2.3 Outside Wall ( U Value )


Material R-value 8F- Ref.Document
Construction Detail Material Specification
DATE

Thickness ft-h/Btu) ASHRAE Table


1.Outside Air Film 0.17 ASHRAE,CH-25,TB-1
NO.

2. External Wall Block 150 mm 0.6 ASHRAE,CH-25,TB-4


REVISIONS 3. Insulation 50 mm 9.84 ASHRAE,CH-25,TB-4
DRAWN 7. Internal Wall Block 100 mm 0.4 ASHRAE,CH-25,TB-4
5. Inside Air Film 0.68 ASHRAE,CH-25,TB-1
BY SAS
DATE 13/08/2013
CHECKED

TOTAL R- VALUE 11.69


BY SAS U-FACTOR-1/R 0.086 Btu / h-ft-8F
DATE 13/08/2013
OPRG. DEPT.

Ref. Architectural drawing No:CA-317120 sheet 02 of 02


BY ___________ Note: U value for the wall is .086 Btu / h-ft-F, that is less than 0.1 Btu / h-ft-F (maximum value
DATE according to TES-K-100) so 0.1 Btu / h-ft-F will be selected.
ENG`G DEPT.

BY ___________
DATE _______
APPROVAR/CERTF. * Refer Appendix 1
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 13 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APR`D.

SVR

SVR
CERT`D DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS

5.2.4 Partition Wall ( U Value )


Material R-value Ref.Document
Construction Detail Material Specification
Thickness (8F-ft- ASHRAE Table
INCORPORATED SEC COMMENTS

1.Inside Air Film 0.68 ASHRAE,CH-25,TB-1


ISSUED FOR BASE DESIGN

2.Block Wall 200 mm 1.23 ASHRAE,CH-25,TB-4


3. Inside Still Air 0.68 ASHRAE,CH-25,TB-1
DESCRIPTION

TOTAL R- VALUE 2.59


U-FACTOR-1/R 0.386 Btu / h-ft-8F

But as per NGSA recommendation 0.463 Btu/hr ft F will be used in calculation.


JOB ORDER NO.

109

109

5.2.5 Metal Door ( U Value )


Material R-value Ref.Document
Construction Detail Material Specification
00 28/05/2013 SATECH

01 13/08/2013 SATECH

Thickness (8F-ft- ASHRAE Table


BY

1. Outside Air Film 15 mph 0.17 ASHRAE,CH-25,TB-1


2. Outside frame steel - Negligible ASHRAE,CH-25,TB-4
DATE

3. Fiberglass insulation 38 mm 5.98 ASHRAE,CH-25,TB-4


7. Inside, frame steel - Negligible ASHRAE,CH-25,TB-4
NO.

5. Inside Air Film 0.68 ASHRAE,CH-25,TB-1


REVISIONS
DRAWN

BY SAS TOTAL R- VALUE 6.83


DATE 13/08/2013 U-FACTOR-1/R 0.146 Btu / h-ft-8F
CHECKED

But as per NGSA recommendation 0.282 Btu/hr ft F will be used in calculation.


BY SAS
DATE 13/08/2013
OPRG. DEPT.

BY ___________
DATE

ENG`G DEPT.

* Refer Appendix 1
BY ___________
DATE _______
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 14 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APPR`D.

SVR

SVR
CERT`D DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS

5.3 INTERNAL LOAD DATA


Internal load data involves components of cooling loads which arises from
sources internal to the conditioned space. The following components shall be
dealt with in the proceeding items.
INCORPORATED SEC COMMENTS
ISSUED FOR BASE DESIGN

5.3.1 LIGHTING:
The details of the lighting loads in each room is taken from actual lighting load
DESCRIPTION

calculation.
The summary of lighting load is enclosed for reference.

Formula Qs = 3.41 * qw * Fu * Fs * CLF

Where,
Qs = Sensible cooling load in BTU /hr
qw = Total lighting wattage (As shown in the detailed calculation enclosed)
Fu = Usage Factor (%)
JOB ORDER NO.

= Wattage in use * 100


109

109

Total Installed Wattage


Fs = Special Ballast allowance 1.2 (for suspended ceiling rooms),
00 28/05/2013 SATECH

01 13/08/2013 SATECH

refer to Table4.1 ASHRAE GRP-158


BY

CLF = 1, Since lights will be turned on more than 16 Hrs per day.
DATE

Summary of lighting load is as below


NO.

S.No Zone Name Lighting Watts


REVISIONS
DRAWN 1 132KV G.I.S GROUND (2.5 w/ ft) 11990
2 132KV BASEMENT-Floor (1 w/ ft) 4796
BY SAS 3 13.8 KV SWGR RM A Ground (1.5 w/ ft) 1308
DATE 13/08/2013 4 13.8 KV SWGR RM B Ground (1.5 w/ ft) 1360
CHECKED 5 13.8 KV SWGR RM C Ground (1.5 w/ ft) 1425
6 FM200 ROOM (1.5 w/ ft) 348
BY SAS 7 TOILET (1.0 w/ ft) 118
DATE 13/08/2013 8 STAIR-2 (1.5 w/ ft) 117
OPRG. DEPT. 9 13.8 KV SWGR RM A Basement (1 w/ ft) 875
10 13.8 KV SWGR RM B Basement (1 w/ ft) 907
BY ___________ 11 13.8 KV SWGR RM C Basement (1 w/ ft) 953
DATE 12 CONTROL ROOM (1.5 w/ ft) 3257
ENG`G DEPT. 13 TELECOM RM (1.5 w/ ft) 828
14 BATTERY RM-1 (1.5 w/ ft) 408
BY ___________ 15 STAIR-1 (1.5 w/ ft) 99
DATE _______ TOTAL 28790
APPROVAR/CERTF.
INFORMATION * Refer Appendix 1
DCC NO. _______
REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 15 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APPR`D.

SVR

SVR
CERT`D DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS

5.3.2 PEOPLE:

Sensible Heat gain from people (Qs) :


INCORPORATED SEC COMMENTS

Qs = qs x No. of people x CLF


ISSUED FOR BASE DESIGN

Where,
DESCRIPTION

qs = Sensible heat gain per person


CLF = Cooling Load Factor
= Table 4.6 ASHRAE GRP -158

Number of people considered in each room are as below:


No.of. Sen.Heat / Latent CLF ( for
S.NO Zone Name
people person heat / Qs only)
1 132KV G.I.S GROUND 2 375 625 0.25
2 BASEMENT FLOOR 2 375 625 0.25
JOB ORDER NO.

3 13.8 KV SWGR RM A GROUND 2 375 625 0.25


109

109

4 13.8 KV SWGR RM B GROUND 2 375 625 0.25


5 13.8 KV SWGR RM C GROUND 2 375 625 0.25
00 28/05/2013 SATECH

01 13/08/2013 SATECH

6 E.GAS ROOM 2 375 625 0.25


BY

7 TOILET 1 375 625 0.25


8 STAIR-2 _ _ _ _
DATE

9 13.8 KV SWGR RM A BASEMENT 2 375 625 0.25


10 13.8 KV SWGR RM B BASEMENT 2 375 625 0.25
NO.

11 13.8 KV SWGR RM C BASEMENT 2 375 625 0.25


REVISIONS 12 CONTROL ROOM 2 375 625 0.25
DRAWN 13 TELECOM RM 2 375 625 0.25
14 BATTERY RM-1 2 375 625 0.25
BY SAS 15 STAIR-1 _ _ _ _
DATE 13/08/2013 Latent Heat gain from people (QL) :
CHECKED

QL = qL x No of people
BY SAS
DATE 13/08/2013 where,
OPRG. DEPT.

qL = Latent heat gain per person


BY ___________ = Table 4.5 ASHRAE GRP -158
DATE

ENG`G DEPT. Number of people in each room will be the same as indicated above.

BY ___________
DATE _______ * Refer Appendix 1
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 16 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

CERT`D APR`D.

SVR

SVR
DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS

5.3.3 EQUIPMENT HEAT GAIN

The heat gain is due to the heat, dissipated by the equipment inside the building.
The actual load dissipation from each panel is taken from the each equipment
INCORPORATED SEC COMMENTS

manufacturer.
ISSUED FOR BASE DESIGN
DESCRIPTION

The Summary of Equipment loads are as follows,

Heat dissipation
S.NO Zone Name
(watts)
1 132KV G.I.S GROUND 32773
2 132KV G.I.S BASEMENT FLOOR 10000
3 13.8 KV SWGR RM A GROUND 6570
4 13.8 KV SWGR RM B GROUND 6570
5 13.8 KV SWGR RM C GROUND 6570
JOB ORDER NO.

6 13.8 KV SWGR RM A BASEMENT 3000


109

109

7 13.8 KV SWGR RM B BASEMENT 3000


8 13.8 KV SWGR RM C BASEMENT 3000
00 28/05/2013 SATECH

01 13/08/2013 SATECH

9 E.GAS ROOM __
BY

10 TOILET __
11 STAIR-2 __
DATE

12 CONTROL ROOM 15938


13 TELECOM RM 8000
NO.

14 BATTERY RM-1 3170


REVISIONS 15 STAIR-1 __
DRAWN TOTAL 98591

BY SAS
DATE 13/08/2013
CHECKED

BY SAS
DATE 13/08/2013
OPRG. DEPT.

BY ___________
DATE

ENG`G DEPT.

BY ___________
DATE _______ * Refer Appendix 1
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 17 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

National Grid SA
5.4.HVAC DATA GATHERING SHEET ( CONSTRUCTION OF AL SHAQRA 132 / 13.8 KV SUBSTATION # 8521)
Floor AREA L EXPOSURE AREAS ( ft)
x W = Area NE NW SE SW
HEIGHT ROOF PARTITION AREA ft LIGHTING EQUP
S.No ROOM.REF People
AREA IN (ft) AREA(ft) watts LOAD
L (ft) W (ft) WALL DOOR WALL DOOR WALL DOOR WALL DOOR
(ft)
Wd (ft) Ht (ft) Area (ft) Wd (ft) Ht (ft) Qty Area (ft) Wd (ft) Ht (ft) Area (ft) Wd (ft) Ht (ft) Qty Area (ft) Wd (ft) Ht (ft) Area (ft) Wd (ft) Ht (ft) Qty Area (ft) Wd (ft) Ht (ft) Area (ft) Wd (ft) Ht (ft) Qty Area (ft) wall ceiling Floor
30.8 32.3 995 13.12 16.4 1 215.17
132KV G.I.S
1 117.09 40.96 4796.0 32.3 117.1 32.3 3783 40.96 13.4 548 12.13 9.84 119 3.936 7.22 1 28.40 118.6 32.3 3829.8 4796 773.7 __ __ 11990 32773 2
GROUND

2 BASEMENT 117.09 40.96 4796.0 9.51 __ __ 4796 10000 2

3 13.8KV SWGR RM-A 39.11 22.30 872.2 17.56 23.6 17.6 414.42 7.216 10 1 72.16 41 17.6 719.96 872 691.2 __ __ 1308 6570 2

7.216 10 1 72.16
4 13.8KV SWGR RM-B 40.67 22.30 906.9 17.56 29.13 17.6 511.52 907 720.0 __ __ 1360 6570 2

5 13.8KV SWGR RM-C 42.60 22.30 950.0 17.56 22.96 17.6 403.18 7.216 10 1 72.16 950 748.1 __ __ 1425 6570 2

3.6 7.22 1 25.978


6 TOILET 9.84 11.97 117.8 17.56 12.95 17.6 227.4 11.81 17.6 207.35 12.95 17.6 227.4 118 __ 118 __ 1

7.216 10 1 72.16
7 FM200.ROOM 18.86 12.30 232.0 17.56 13.61 17.6 239.0 20.17 17.6 354.19 232 __ 348 __ 2

13.8KV SWGR RM-A


8
Basement
39.26 22.30 875.5 9.51 __ __ 875 3000 2

13.8KV SWGR RM-B


9
Basement
40.63 22.30 906.0 9.51 __ __ 906 3000 2

13.8KV SWGR RM-


10 42.74 22.30 953.1 9.51 __ __ 953 3000 2
C Basement

3.94 7.22 1 28.431


11 STAIR-2 19.02 4.10 78.0 19.02 4.92 8.69 42.755 4.92 8.69 42.755 20.33 8.69 176.67 78 __ __ __ 78 __ __

7.216 9.18 1 66.272


12 CONTROL ROOM 98.10 22.14 2172 17.56 56.48 17.6 991.79 23.05 17.6 404.76 2172 288.0 __ 3258 15938 2

7.216 10 1 72.16
13 TELECOM RM 24.93 22.14 552 17.56 23.05 17.6 404.76 26.24 17.6 460.77 552 438.3 __ 828 8000 2

14 BATTERY RM-1 22.14 12.30 272 17.56 23.45 17.6 411.78 13.61 8.2 111.6 272 __ 408 3170 2

2.788 10 1 27.88
15 STAIR-1 19.84 5.00 99.2 19.02 6.46 8.69 56.14 9.18 8.69 79.774 21.32 8.69 185.3 6.46 8.69 56.14 149 __ __ 149 __ __

* Reference Appendix 3

Page No:18
http://boilersinfo.com/

APPR`D.

SVR

SVR
CERT`D DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
5.5 VENTILATION, EXHAUST AND PRESSURIZATION CALCULATION
CHK'D

SAS

SAS

5.5.1 VENTILATION & PRESSURIZATION CALCULATION FOR GROUP-1 ZONES

Group-1 includes the following zones


INCORPORATED SEC COMMENTS

1 132KV G.I.S Room ( Ground Floor)


ISSUED FOR BASE DESIGN

2 132KV G.I.S room (Basement Floor)


DESCRIPTION

The design of the system is in such a way that a positive pressurization can be
achieved. Introduction of outdoor air into the system through a fresh air / grilles
into the machine room will eventually produce heat of both sensible and latent in
nature.

Qs = 1.1 x (To Tr) x cfm ----------------------- (1)

QL = 4840 x (Wo Wi) x cfm ------------------ (2)


JOB ORDER NO.

109

109

Where,
00 28/05/2013 SATECH

01 13/08/2013 SATECH
BY

Qs = Sensible heat gain, BTU / hr.


QL = Latent heat gain, BTU / hr.
DATE

To = Design outdoor ambient temperature - 118.48F


Tr = Room design temperature - 77 8F
NO.

Wo = Outside air humidity ratio


REVISIONS Wi = Room air humidity ratio
DRAWN cfm = Ventilation rate requirement

BY SAS Please refer to the computer generated calculation sheets enclosed with this
DATE 13/08/2013 document for the details.
CHECKED

BY SAS
DATE 13/08/2013
OPRG. DEPT.

BY ___________
DATE

ENG`G DEPT.

BY ___________
DATE _______
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 19 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APPR`D.

SVR

SVR
CERT`D DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS

5.5.1 PRESSURIZATION

a. Site Condition
Outside temperature : 118 8F
INCORPORATED SEC COMMENTS
ISSUED FOR BASE DESIGN

Wind Speed : 11 mph


Building pressure : 0.2 in wg
DESCRIPTION

b. Wind pressure ( Ref. ASHRAE Fundamental 1997 Chapter 25)

Wind Static pressure Pv = 1/2 (C1*C2*r*V)- Equation No.6 Chapter No 23 of


ASHRAE Fundamental
Where,

Pv = Surface pressure relative to static pressure in


undistributed flow (in of water)
C1 = 0.0129 Unit conversion factor
C2 = 1 wind surface pressure coefficient for undistributed area
JOB ORDER NO.

109

109

r = 0.07 Air density in lb/ft at 118.4 8F


V = 11 Wind speed in MPH (Taken from TES-K-100)
00 28/05/2013 SATECH

01 13/08/2013 SATECH
BY

Hence,
Pv = 1/2 * (0.0129 * 1 * .07 * 11)
DATE

= 0.06 in of w.g
NO.

REVISIONS c. Ex-filtration shall be calculated as below:


DRAWN

Qp = Qexh +Po / Pi Qexh + Po / Pi Qx +Qx


BY SAS
DATE 13/08/2013 Where:
CHECKED Qexh = Exhaust air in cfm
Qx = Ex-filtration in cfm
BY SAS
DATE 13/08/2013 Po = Pv = outside Static Pressure on building wall
OPRG. DEPT. = 0.06 ( Refer to the above calculation)

BY ___________ Pi = Inside Static pressure of the space


DATE = Po+0.2 in w.g
ENG`G DEPT. = 0.055 + 0.2 in w.g
= 0.26 in w.g
BY ___________
DATE _______ Qexh = 0 cfm
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR DESIGN CALCULATIONS OF HVAC SYSTEM
CONSTRUCTION OR
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 20 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APPR`D.

SVR

SVR
CERT`D DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS

d. Exfiltration Air (Qx)

Ex-filtration in cfm Qx = Qx/L x AL

((A x DT) + (B x V))1/2


INCORPORATED SEC COMMENTS

Stack co-efficient, (cfm)(Sq. in)- mph- Qx/L =


ISSUED FOR BASE DESIGN

Stack co- efficient A = 0.0156 ( Ref ASHRAE


fundamentals 1997 chapter 25,
DESCRIPTION

Indoor temp - Outdoor temp. DT = 77-118.4 = -41.48F


Wind co- efficient, (cfm) (Sq.in)-2(mph)-2 B = 0.0119 (shielding class-1)
ASHRAE fundamentals 1997
Wind speed V = 11 mph

Qx/L = ((.0156*(-41.4))+(0.0119*11))^1/2
cfm/in
= (-.6458+1.4399)^1/2
= 0.89 cfm/in
JOB ORDER NO.

Door Area, (ft)


109

109

Double Door Ad = 215 (ft)


Single Door Ad = 29.1 (ft)
00 28/05/2013 SATECH

01 13/08/2013 SATECH

Use 0.12 in/ft for (Double door & single door weather stripped Ref. ASHRAE fundamentals.
BY

Leakage Area AL = Leakage Area


in
DATE

= 0.12 x Ad
NO.

Door Area Leakage


Door Leakage Area
REVISIONS Room Name (Ad) Air (Qx)
Designation (AL), (in)
DRAWN (ft) cfm
132KV G.I.S Rm 1Dd 209.76 25.17 22.40
BY SAS 132KV G.I.S Rm 1 Sd 26.04 3.12 2.78
DATE 13/08/2013
CHECKED

BY SAS Total 235.8 28.30 25


DATE 13/08/2013
OPRG. DEPT.
Note: Sd - Single Door
BY ___________ Dd - Double Door
DATE

ENG`G DEPT.

BY ___________
DATE _______
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 21 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APPR`D.

SVR

SVR
CERT`D DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS

Make-up air required to pressurize the conditioned space.

Qp = Qexh + Po / Pi Qexh + Po / Pi Qx + Qx
Where,
INCORPORATED SEC COMMENTS

Qp = Air required to pressurize the space to required static pressure in cfm


ISSUED FOR BASE DESIGN

Qex = Exhaust air by powered Exhaust fan - in cfm


Po = Outside static pressure acting on wall in -in of w.g
Pi = Inside static pressure of the conditioned space in- in of w.g
DESCRIPTION

Qx = Ex-filtration of the air from the space in cfm

e. Assumptions:
In this design, for the purpose of analysis, following assumptions are made:
Design static pressure inside the conditioned space to be positive relative to atmosphere.
As per TES-K-100 the required pressure inside the conditioned space shall be
maintained at 0.2 in of w.g (50 Pa)
Surface pressure relative to the static pressure is equivalent to the static pressure
acting on the building wall i.e
JOB ORDER NO.

Po = Pi = 0.06 in of W.G
109

109

Qexh = 0 cfm
Qx = 25 cfm
00 28/05/2013 SATECH

01 13/08/2013 SATECH

Qp = (0+.055 / 0.255 x 0+25x.055/.255 + 25)


BY

Qp = 30 cfm
DATE

Note:
NO.

As per TES-K-100, Sec.10, minimum of 10% of supply air required for fresh air make
REVISIONS up. From air balancing table enclosed, required make up is greater than the Qp
DRAWN indicated above.
Hence adopt OA from air balancing as make up, which is 1346 cfm
BY SAS
DATE 13/08/2013
CHECKED

BY SAS
DATE 13/08/2013
OPRG. DEPT.

BY ___________
DATE

ENG`G DEPT.

BY ___________
DATE _______
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 22 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APPR`D.

SVR

SVR
CERT`D DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS

Summary is as below
Tot.Supply Tot.Outside Exhaust
S.No Area %O.A % Pressurization
Air cfm Air cfm Air cfm
1 Group-1 13459 1346 0 10.0 10.0
INCORPORATED SEC COMMENTS
ISSUED FOR BASE DESIGN

Percent of outside air = Outside air x 100


DESCRIPTION

Supply air

Percent of Press air = (Outside air- Exhaust air) x 100


Supply air

AIR BALANCING:
Supply Return Air Pressurization Exf.Air Exhaust
S.No Zone Name
Air cfm cfm Air cfm cfm Air cfm
1 132KV G.I.S (GF) 10588 9529 1034 25 0
JOB ORDER NO.

2 Basement 2762 2486 276 0 0


109

109

3 Stair-1 109 98 11 0 0
00 28/05/2013 SATECH

01 13/08/2013 SATECH
BY

13459 12113 1321 25 0


DATE

Total supply air = 13459 cfm


Return Air = 12113 cfm
NO.

Exhaust. Air = 0 cfm


REVISIONS Pressurization Air = 1321 cfm
DRAWN Ex-filtration Air = 25.18 cfm
Outside Air (O.A.) = Exhaust air + Pressurization air + Ex-filtration air
BY SAS = 1346 cfm
DATE 13/08/2013
CHECKED Adopted outside air = 1346 cfm
Supply air = Return air + Outside air
BY SAS = 13459 cfm
DATE 13/08/2013
OPRG. DEPT.

BY ___________ Required fresh Air by considering the following:


DATE 1. O.A. = 5% of Supply Air + Exhaust + Exfiltration ( as per TES-K-100 clause10.2)
ENG`G DEPT. = 673+0+25
= 698 cfm
BY ___________ 2. O.A. = Pressurization Air + Exhaust Air + Exfiltration Air
DATE _______ = 1328+0+25 = 1346 cfm
APPROVAR/CERTF. 3. O.A. = 10% Supply Air
INFORMATION = 1346 cfm
DCC NO. _______ Hence 1346 cfm is selected
REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 23 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APPR`D.

SVR

SVR
CERT`D DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS

5.5.2 VENTILATION & PRESSURIZATION CALCULATION FOR GROUP-2 ZONES


INCORPORATED SEC COMMENTS

Group-2 includes the following zones


ISSUED FOR BASE DESIGN

1 13.8KV SWGR Room-A( Ground Floor)


2 13.8KV SWGR Room-B( Ground Floor)
3 13.8KV SWGR Room-C( Ground Floor)
DESCRIPTION

4 FM200 Room
5 Toilet
6 Stair-2
7 13.8KV SWGR Room-A( Basement Floor)
8 13.8KV SWGR Room-B( Basement Floor)
9 13.8KV SWGR Room-C( Basement Floor)
JOB ORDER NO.

109

109

The design of the system is in such a way that a positive pressurization can be
achieved. Introduction of outdoor air into the system through a fresh air / grilles
into the machine room will eventually produce heat of both sensible and latent in
00 28/05/2013 SATECH

01 13/08/2013 SATECH
BY

nature.
DATE

Qs = 1.1 x (To Tr) x cfm ----------------------- (1)

QL = 4840 x (Wo Wi) x cfm ------------------ (2)


NO.

REVISIONS
DRAWN

Where,
BY SAS
DATE 13/08/2013 Qs = Sensible heat gain, BTU / hr.
CHECKED QL = Latent heat gain, BTU / hr.
To = Design outdoor ambient temperature - 118.48F
BY SAS Tr = Room design temperature - 77 8F
DATE 13/08/2013 Wo = Outside air humidity ratio
OPRG. DEPT. Wi = Room air humidity ratio
cfm = Ventilation rate requirement
BY ___________
DATE Please refer to the computer generated calculation sheets enclosed with this
ENG`G DEPT. document for the details.

BY ___________
DATE _______
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 24 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APPR`D.

SVR

SVR
CERT`D
DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS

5.5.2 PRESSURIZATION

a. Site Condition
Outside temperature : 118 8F 8C)
INCORPORATED SEC COMMENTS
ISSUED FOR BASE DESIGN

Wind Speed : 11 mph


Building pressure : 50 Pa
DESCRIPTION

b. Wind pressure ( Ref. ASHRAE Fundamental 1997 Chapter 25)

Wind Static pressure Pv = 1/2 (C1*C2*r*V)- Equation No.6 Chapter No 23 of


ASHRAE Fundamental
Where,

Pv = Surface pressure relative to static pressure in


undistributed flow (in of water)
C1 = 0.0129 Unit conversion factor
C2 = 1 wind surface pressure coefficient for undistributed area
JOB ORDER NO.

109

109

r = 0.07 Air density in lb/ft at 118.4 8F


V = 11 Wind speed in MPH (Taken from TES-K-100)
00 28/05/2013 SATECH

01 13/08/2013 SATECH
BY

Hence,
Pv = 1/2 * (0.0129 * 1 * .07 * 11)
DATE

= 0.06 in of w.g
NO.

REVISIONS c. Ex-filtration shall be calculated as shown below:


DRAWN

Qp = Qexh +Po / Pi Qexh + Po / Pi Qx +Qx


BY SAS
DATE 13/08/2013 Where:
CHECKED Qexh = Exhaust air in cfm
Qx = Ex-filtration in cfm
BY SAS
DATE 13/08/2013 Po = Pv = outside Static Pressure on building wall
OPRG. DEPT. = 0.06 ( Refer to the above calculation)

BY ___________ Pi = Inside Static pressure of the space


DATE = Po+0.2 in w.g
ENG`G DEPT. = .055 + 0.2 in w.g
= 0.26 in w.g
BY ___________
DATE _______ Qexh = 1301 cfm
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 25 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APPR`D.

SVR

SVR
CERT`D DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS

d. Exfiltration Air (Qx)

Ex-filtration in cfm Qx = Qx/L x AL

((A x DT) + (B x V))1/2


INCORPORATED SEC COMMENTS

Stack co-efficient, (cfm)(Sq. in)- mph- Qx/L =


ISSUED FOR BASE DESIGN

Stack co- efficient A = 0.0156 ( Ref ASHRAE


fundamentals 1997 chapter 25,
DESCRIPTION

Indoor temp - Outdoor temp. DT = 77-118.4 = -41.48F


Wind co- efficient, (CFm) (Sq.in)-2(mph)-2 B = 0.0119 (shielding class-1)
ASHRAE fundamentals 1997
Wind speed V = 11 mph

Qx/L = ((.0156*(-41.4))+(0.0119*11))^1/2
cfm/in
= (-.6458+1.4399)^1/2
= 0.89 cfm/in
JOB ORDER NO.

Door Area, m (ft)


109

109

Double Door Ad = 72.2 (ft)


Double Door Ad = 67.5 (ft)
00 28/05/2013 SATECH

01 13/08/2013 SATECH

Single Door Ad = 26.6 (ft)


BY

Single Door Ad = 29.1 (ft)


DATE

Use 0.12 in/ft for (Double door & single door weather stripped Ref. ASHRAE fundamentals).

Leakage Area AL = Leakage Area


in
NO.

REVISIONS = 0.12 x Ad
DRAWN

BY SAS
DATE 13/08/2013 Door Door Area (Ad) Leakage Leakage Air
Room Name
CHECKED Designation (ft) Area (AL), (Qx) cfm
13.8KV SWGR SEC-A 1Dd 67.69 8.12 7.2
BY 13.8KV SWGR SEC-B SAS 1Dd 67.69 8.12 7.2
DATE 13/08/2013 13.8KV SWGR SEC-C 1Dd 67.69 8.12 7.2
OPRG. DEPT. EGAS RM 1Dd 63.18 7.58 6.7
Stair-2 1Sd 26.03 3.12 2.8
BY ___________ TOTAL 292.28 35 31.2
DATE

ENG`G DEPT.

BY ___________ Note: Sd - Single Door


DATE _______ Dd - Double Door
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 26 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APPR`D.

SVR

SVR
CERT`D
DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS

Make-up air required to pressurize the conditioned space.

Qp = Qexh + Po / Pi Qexh + Po / Pi Qx + Qx
Where,
INCORPORATED SEC COMMENTS

Qp = Air required to pressurize the space to required static pressure in cfm


ISSUED FOR BASE DESIGN

Qex = Exhaust air by powered Exhaust fan - in cfm


Po = Outside static pressure acting on wall in -in of w.g
Pi = Inside static pressure of the conditioned space in- in of w.g
DESCRIPTION

Qx = Ex-filtration of the air from the space in cfm

e. Assumptions:
In this design, for the purpose of analysis, following assumptions are made:
Design static pressure inside the conditioned space to be positive relative to
atmosphere.

As per TES-K-100 the required pressure inside the conditioned space shall be
maintained at 0.2 in of w.g (50 Pa)
Surface pressure relative to the static pressure is equivalent to the static
JOB ORDER NO.

pressure acting on the building wall i.e


109

109

Po=Pi = 0.055 in of W.G


00 28/05/2013 SATECH

01 13/08/2013 SATECH

Qexh = 1301 cfm


BY

Qx = 31 cfm
Qp = (1301+.055 / 0.255 x 1301+31x.055/.255 + 31)
DATE

Qp = 1619 cfm
NO.

REVISIONS
DRAWN

BY SAS
DATE 13/08/2013
CHECKED

BY SAS Note:
DATE 13/08/2013
As per TES-K-100, Sec.10, minimum of 10% of supply air required for fresh air
OPRG. DEPT.
make up. From air balancing table enclosed, required make up is greater than
BY ___________
the Qp indicated above.
DATE

ENG`G DEPT. Hence adopt OA from air balancing as make up, which is 2148 cfm

BY ___________
DATE _______
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 27 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APPR`D.

SVR

SVR
DRAWING COMPLETION CERTIFICATE (DCC)
CERT`D

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS

Summary is as below
Tot.Supply Tot.Outsid Exhaust Air
S.No Area %O.A % Pressurization
Air cfm e Air cfm cfm
Group-2 9768 2148 1301 13.0 9.63
INCORPORATED SEC COMMENTS
ISSUED FOR BASE DESIGN

Percent of outside air = Outside air x 100


Supply air
DESCRIPTION

Percent of Press air = (Outside air- Exhaust air) x 100


Supply air
AIR BALANCING:
Supply Air Return Air Pressurizati Exhaust
S.No Zone Name Exf.A cfm
cfm cfm on Air cfm Air cfm
1 13.82KV SWGR SEC-A (GF) 1962 1766 189 7
2 13.82KV SWGR SEC-B (GF) 1920 1728 185 7
3 13.82KV SWGR SEC-C (GF) 1934 1741 186 7
4 FM200 Room 280 252 21 7
JOB ORDER NO.

5 Toilet 345 345


109

109

6 Battery Room 956 956


7 13.82KV SWGR SEC-A (BF) 753 678 75 0
00 28/05/2013 SATECH

01 13/08/2013 SATECH

8 13.82KV SWGR SEC-B (BF) 759 683 76 0


BY

9 13.82KV SWGR SEC-C (BF) 768 691 77 0


10 STAIR-2 91 82 6 3
DATE

9768 7620 815 31 1301.0


NO.

Total supply air = 9768 cfm


REVISIONS Return Air = 7620 cfm
DRAWN Exhaust. Air = 1301 cfm
Pressurization Air = 815 cfm
BY SAS Ex-filtration Air = 31 cfm
DATE 13/08/2013 Outside Air (O.A.) = Exhaust air + Pressurization air + Ex-filtration air
CHECKED = 2148 cfm

BY SAS Adopted outside air = 2148 cfm


DATE 13/08/2013 Supply air = Return air + Outside air
OPRG. DEPT. = 9768 cfm

BY ___________ Required fresh Air by considering the following:


DATE 1. O.A. = 5% of Supply Air + Exhaust + Exfiltration ( as per TES-K-100 clause10.2)
ENG`G DEPT. = 488+1301+31
= 1820 cfm
BY ___________ 2. O.A. = Pressurization Air + Exhaust Air + Exfiltration Air
DATE _______ = 815+1301+31 = 2147 cfm
APPROVAR/CERTF. 3. O.A. = 10% Supply Air
INFORMATION = 977 cfm
DCC NO. _______ Hence 2147 cfm is selected
REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.

DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 28 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APPR`D.

SVR

SVR
CERT`D DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS

5.5.3 VENTILATION & PRESSURIZATION CALCULATION FOR GROUP-3 ZONES

Group-3 includes the following zones


INCORPORATED SEC COMMENTS

1 Control Room
ISSUED FOR BASE DESIGN

2 Telecom Room
DESCRIPTION

The design of the system is in such a way that a positive pressurization can be
achieved. Introduction of outdoor air into the system through a fresh air / grilles
into the machine room will eventually produce heat of both sensible and latent in
nature.

Qs = 1.1 x (To Tr) x cfm ----------------------- (1)


JOB ORDER NO.

109

109

QL = 4840 x (Wo Wi) x cfm ------------------ (2)


00 28/05/2013 SATECH

01 13/08/2013 SATECH
BY

Where,
DATE

Qs = Sensible heat gain, BTU / hr.


QL = Latent heat gain, BTU / hr.
NO.

To = Design outdoor ambient temperature - 118.48F


REVISIONS Tr = Room design Temperature - 77 8F
DRAWN Wo = Outside air humidity ratio
Wi = Room air humidity ratio
BY SAS cfm = Ventilation rate requirement
DATE 13/08/2013
CHECKED Please refer to the computer generated calculation sheets enclosed with this document
for the details.
BY SAS
DATE 13/08/2013
OPRG. DEPT.

BY ___________
DATE

ENG`G DEPT.

BY ___________
DATE _______
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 29 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APPR`D.

SVR

SVR
CERT`D
DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS

5.5.3 PRESSURIZATION

a. Site Condition
Outside temperature : 118 8F
INCORPORATED SEC COMMENTS
ISSUED FOR BASE DESIGN

Wind Speed : 11 mph


Building pressure : 0.2 in w.g
DESCRIPTION

b. Wind pressure ( Ref. ASHRAE Fundamental 1997 Chapter 25)

Wind Static pressure Pv = 1/2 (C1*C2*r*V)- Equation No.6 Chapter No 23 of


ASHRAE Fundamental
Where,

Pv = Surface pressure relative to static pressure in


undistributed flow (in of water)
C1 = 0.0129 Unit conversion factor
C2 = 1 wind surface pressure coefficient for undistributed area
JOB ORDER NO.

109

109

r = 0.07 Air density in lb/ft at 118.4 8F


V = 11 Wind speed in MPH (Taken from TES-K-100)
00 28/05/2013 SATECH

01 13/08/2013 SATECH
BY

Hence,
Pv = 1/2 * (0.0129 * 1 * .07 * 11)
DATE

= 0.06 in of w.g
NO.

REVISIONS c. Ex-filtration shall be calculated as shown below:


DRAWN

Qp = Qexh +Po / Pi Qexh + Po / Pi Qx +Qx


BY SAS
DATE 13/08/2013 Where:
CHECKED Qexh = Exhaust air in cfm
Qx = Ex-filtration in cfm
BY SAS
DATE 13/08/2013 Po = Pv = outside Static Pressure on building wall
OPRG. DEPT. = 0.06 ( Refer to the above calculation)

BY ___________ Pi = Inside Static pressure of the space


DATE = Po+0.2 in w.g
ENG`G DEPT. = .055 + 0.2 in w.g
= 0.26 in w.g
BY ___________
DATE _______ Qexh = 0 cfm
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 30 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APPR`D.

SVR

SVR
CERT`D DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS

d. Exfiltration Air (Qx)

Ex-filtration in cfm Qx = Qx/L x AL

((A x DT) + (B x V))1/2


INCORPORATED SEC COMMENTS

Stack co-efficient, (cfm)(Sq. in)- mph- Qx/L =


ISSUED FOR BASE DESIGN

Stack co- efficient A = 0.0156 ( Ref ASHRAE


fundamentals 1997 chapter 25,
DESCRIPTION

Indoor temp - Outdoor temp. DT = 77-118.4 = -41.48F


Wind co- efficient, (cfm) (Sq.in)-2(mph)-2 B = 0.0119 (shielding class-1)
ASHRAE fundamentals 1997
Wind speed V = 11 mph

Qx/L = ((.0156*(-41.4))+(0.0119*11))^1/2
cfm/in
= (-.6458+1.4399)^1/2
= 0.89 cfm/in
JOB ORDER NO.

Door Area, m (ft)


109

109

Double Door Ad = 67.5 ft


Single Door Ad = 26.6 ft
00 28/05/2013 SATECH

01 13/08/2013 SATECH
BY
DATE

Use 0.12 in/ft for (Double door & single door weather stripped Ref. ASHRAE fundamentals.
NO.

REVISIONS Leakage Area AL = Leakage Area in


DRAWN = 0.12 x Ad

BY SAS
DATE 13/08/2013 Door Door Area (Ad) Leakage
Room Name Leakage Air (Qx) cfm
CHECKED Designation (ft) Area (AL),
CONTROL ROOM 1Dd 63.18 7.58 6.75
BY SAS TELECOM ROOM 1Dd 63.18 7.58 6.75
DATE 13/08/2013 STAIR-1 1Dd 63.18 7.58 6.75
OPRG. DEPT. STAIR-1 1Sd 23.66 2.84 2.53

BY ___________
DATE TOTAL 213.2 25.58 23
ENG`G DEPT.

BY ___________ Note: Sd - Single Door


DATE _______ Dd - Double Door
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.

DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 31 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APPR`D.

SVR

SVR
CERT`D DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS

Make-up air required to pressurize the conditioned space.

Qp = Qexh + Po / Pi Qexh + Po / Pi Qx + Qx
Where,
INCORPORATED SEC COMMENTS

Qp = Air required to pressurize the space to required static pressure in cfm


ISSUED FOR BASE DESIGN

Qex = Exhaust air by powered Exhaust fan - in cfm


Po = Outside static pressure acting on wall in -in of w.g
Pi = Inside static pressure of the conditioned space in- in of w.g
DESCRIPTION

Qx = Ex-filtration of the air from the space in cfm

e. Assumptions:
In this design, for the purpose of analysis, following assumptions are made:
Design static pressure inside the conditioned space to be positive relative to
atmosphere.

As per TES-K-100 the required pressure inside the conditioned space shall be
maintained at 0.2 in of w.g (50 Pa)
Surface pressure relative to the static pressure is equivalent to the static pressure
JOB ORDER NO.

acting on the building wall i.e


109

109

Po=Pi = 0.055 in of W.G


00 28/05/2013 SATECH

01 13/08/2013 SATECH

Qexh = 0 cfm
BY

Qx = 22.77 cfm
Qp = (0x0.055/.255+0+23x.055/.255 + 23)
DATE

Qp = 28 cfm
NO.

REVISIONS
DRAWN

BY SAS
DATE 13/08/2013
CHECKED

BY SAS
DATE 13/08/2013
OPRG. DEPT.

Note:
BY ___________ As per TES-K-100, Sec.10, minimum of 10% of supply air required for fresh air make
DATE up. From air balancing table enclosed, required make up is greater than the Qp
ENG`G DEPT. Hence adopt OA from air balancing as make up, which is 615 cfm

BY ___________
DATE _______
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 32 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APPR`D.

SVR

SVR
DRAWING COMPLETION CERTIFICATE (DCC)
CERT`D

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS

Summary is as below
Tot.Supply Tot.Outsid Exhaust Air
S.No Area %O.A % Pressurization
Air cfm e Air cfm cfm
Group-3 6152 615 0 25.5 8.25
INCORPORATED SEC COMMENTS
ISSUED FOR BASE DESIGN

Percent of outside air = Outside air x 100


Supply air
DESCRIPTION

Percent of Press air = (Outside air- Exhaust air) x 100


Supply air
AIR BALANCING:
Supply Air Return Air Pressurizati Exhaust
S.No Zone Name Exf.A cfm
cfm cfm on Air cfm Air cfm
1 CONTROL ROOM 4150 3735 408 7 0
2 TELECOM ROOM 2002 1802 193 7 0
JOB ORDER NO.

6152 5537 602 13 0.0


109

109
00 28/05/2013 SATECH

01 13/08/2013 SATECH
BY
DATE

Total supply air = 6152 cfm


Return Air = 5537 cfm
NO.

Exhaust. Air = 0 cfm


REVISIONS Pressurization Air = 602 cfm
DRAWN Ex-filtration Air = 13.5 cfm
Outside Air (O.A.) = Exhaust air + Pressurization air + Ex-filtration air
BY SAS = 615 cfm
DATE 13/08/2013
CHECKED Adopted outside air = 615 cfm
Supply air = Return air + Outside air
BY SAS = 6152 cfm
DATE 13/08/2013
OPRG. DEPT.

BY ___________ Required fresh Air by considering the following:


DATE 1. O.A. = 5% of Supply Air + Exhaust + Exfiltration ( as per TES-K-100 clause10.2)
ENG`G DEPT. = 308+0+13
= 321 cfm
BY ___________ 2. O.A. = Pressurization Air + Exhaust Air + Exfiltration Air
DATE _______ = 602+0+13 = 615 cfm
APPROVAR/CERTF. 3. O.A. = 10% Supply Air
INFORMATION = 615 cfm
DCC NO. _______ Hence 615 cfm is selected
REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.

DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 33 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APPR`D.

SVR

SVR
DRAWING COMPLETION CERTIFICATE (DCC)
CERT`D

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS

5.5.4 Battery Room Exhaust Calculation

DATA
INCORPORATED SEC COMMENTS

Battery Room Length = 22.1 ft


ISSUED FOR BASE DESIGN

Battery Room Width = 12 ft


Battery Room Height = 17.6 ft
DESCRIPTION

Volume = 4782 ft3

Air changes / Hour = 12


= 956 cfm

* Note:
Minimum exhaust air required is 956 cfm (12 ACH) , comparing with the
JOB ORDER NO.

cooling load calculation supply air flow, the minimun required airflow is higher,
so 956 cfm is selected.
109

109
00 28/05/2013 SATECH

01 13/08/2013 SATECH

5.5.5 Toilet Room Exhaust Calculation


BY

DATA
DATE

Toilet Length = 9.84 ft


Toilet Width = 12 ft
NO.

Toilet Height = 17.6 ft


REVISIONS
DRAWN Volume = 2068 ft3

BY SAS Air changes / Hour = 10


DATE 13/08/2013 345 cfm
CHECKED

BY SAS
DATE 13/08/2013
OPRG. DEPT. * Note:
Minimum exhaust air required is 345 cfm (12 ACH) , comparing with the
BY ___________ cooling load calculation supply air flow, the minimun required airflow is higher,
DATE so 345 cfm is selected.
ENG`G DEPT.

BY ___________
DATE _______
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 34 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APPR`D.

SVR

SVR
DRAWING COMPLETION CERTIFICATE (DCC)
CERT`D

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS

Summary of Ventilation, Exhaust, Pressurization Airbalancing Tables:

Group-1 (PACU 01A & 01B)


INCORPORATED SEC COMMENTS

Supply Air Return Air Exhaust Air Press.Air


S.No Zone Name Ex.Air cfm
ISSUED FOR BASE DESIGN

cfm cfm cfm cfm


1 132 kv G.I.S (GF) 10588 9529 _ 1034 25
2 BASEMENT FLOOR 2762 2486 _ 276 _
DESCRIPTION

2 BASEMENT FLOOR 109 98 _ 11 _


Total 13459 12113 _ 1321 25

Group-2 (PACU 02A & 02B)


Supply Air Return Air Exhaust Air Press.Air
S.No Zone Name Ex.Air cfm
cfm cfm cfm cfm
1 13.8kv SWGR Rm-A (GF) 1962 1766 _ 189 7
2 13.8kv SWGR Rm-B (GF) 1920 1728 _ 185 7
3 13.8kv SWGR Rm-C (GF) 1934 1741 _ 186 7
4 E.GAS ROOM 280 252 _ 21 7
JOB ORDER NO.

5 TOILET 345 0 345 0 0


109

109

6 BATTERY ROOM 956 0 956 0 0


7 13.8kv SWGR Rm-A (BF) 753 678 _ 75 0
00 28/05/2013 SATECH

01 13/08/2013 SATECH

8 13.8kv SWGR Rm-B (BF) 759 683 _ 76 0


BY

9 13.8kv SWGR Rm-C (BF) 768 691 _ 77 0


10 STAIR-2 91 82 _ 6 3
DATE

Total 9768 7620 1301 815 31


NO.

REVISIONS
DRAWN

BY SAS Group-3 (PACU 03A & 03B)


DATE 13/08/2013 Supply Air Return Air Exhaust Air Press.Air
S.No Zone Name Ex.Air cfm
CHECKED cfm cfm cfm cfm
1 CONTROL ROOM 4150 3735 _ 408 7
BY SAS 2 TELECOM ROOM 2002 1802 _ 193 7
DATE 13/08/2013
OPRG. DEPT.

Total 6152 5537 0 602 13


BY ___________
DATE

ENG`G DEPT.

BY ___________
DATE _______
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.

DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 35 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APPR`D.

SVR

SVR
DRAWING COMPLETION CERTIFICATE (DCC)
CERT`D

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS

5.6 SUMMARY OF COOLING LOAD:

Group-1
Location of service: 132KV G.I.S Building
INCORPORATED SEC COMMENTS

Unit Reference PACU 01A & 01B


ISSUED FOR BASE DESIGN

Outdoor Temperature
Summer
DESCRIPTION

Dry bulb temperature 118 8F


Wet bulb temperature 76 8F
Winter
Dry bulb temperature 41 8F
Cooling Load
Total capacity 337.9 MBH = 28.16 ton
Sensible Capacity 331 MBH
Supply Air Flow 13459 cfm
Outdoor Air flow 1346 cfm
JOB ORDER NO.

Entering air condition:


109

109

Entering Dry bulb temp 81.2 8F


Entering Wet bulb temp 65.3 8F
00 28/05/2013 SATECH

01 13/08/2013 SATECH

Leaving air condition:


BY

Leaving Dry bulb temp 57.0 8F


Leaving Wet bulb temp 56.9 8F
DATE

ESP for Supply fan 2.38 in of w.c


NO.

10%safety factor 0.24 in of w.c


REVISIONS Total ESP for Fan 2.62 in of w.c
DRAWN

Power supply 380-420 / 3 ph / 60 hz


BY SAS
DATE 13/08/2013 Group-2
CHECKED Location of service: 13.8KV SWGR Building
Unit Reference PACU 02A & 02B
BY SAS
DATE 13/08/2013 Outdoor Temperature
OPRG. DEPT. Summer
Dry bulb temperature 118 8F
BY ___________ Wet bulb temperature 76 8F
DATE Winter
ENG`G DEPT. Dry bulb temperature 41 8F
Cooling Load
BY ___________ Total capacity 307.9 MBH = 25.7 ton
DATE _______ Sensible Capacity 292.2 MBH
APPROVAR/CERTF. Supply Air Flow 9769 cfm
INFORMATION Outdoor Air flow 2147 cfm
DCC NO. _______
REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 36 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APPR`D.

SVR

SVR
DRAWING COMPLETION CERTIFICATE (DCC)
CERT`D

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
5.6 SUMMARY OF COOLING LOAD:
CHK'D

SAS

SAS

Entering air condition:


Entering Dry bulb temp 86.21 8F
INCORPORATED SEC COMMENTS

Entering Wet bulb temp 66.89 8F


ISSUED FOR BASE DESIGN

Leaving air condition:


Leaving Dry bulb temp 57 8F
Leaving Wet bulb temp 56.00 8F
DESCRIPTION

ESP for Supply fan 2.33 in of w.c


10%safety factor 0.23 in of w.c
Total ESP for Fan 2.56 in of w.c

Power supply 380-420 / 3 ph / 60 hz

Group-3
Location of service: Control room Building
Unit Reference: PACU 03A & 03B
JOB ORDER NO.

109

109

Outdoor Temperature
Summer
00 28/05/2013 SATECH

01 13/08/2013 SATECH

Dry bulb temperature 118 8F


BY

Wet bulb temperature 76 8F


Winter
DATE

Dry bulb temperature 41 8F


Cooling Load
NO.

Total capacity 156.91 MBH = 13.1 ton


REVISIONS Sensible Capacity 152.97 MBH
DRAWN Supply Air Flow 6152 cfm
Outdoor Air flow 615 cfm
BY SAS
DATE 13/08/2013 Entering air condition:
CHECKED Entering Dry bulb temp 81.3 8F
Entering Wet bulb temp 65.3 8F
BY SAS Leaving air condition:
DATE 13/08/2013 Leaving Dry bulb temp 57.0 8F
OPRG. DEPT. Leaving Wet bulb temp 56.81 8F

BY ___________ ESP for Supply fan 1.73 in of w.c


DATE 10%safety factor 0.17 in of w.c
ENG`G DEPT. Total ESP for Fan 1.90 in of w.c

BY ___________
DATE _______ Power supply 380-420 / 3 ph / 60 hz
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION #8521 B C279 CE-316495 37 OF 43 01
CERTIFIED AND IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APPR`D.

SVR

SVR
CERT`D
DRAWING COMPLETION CERTIFICATE (DCC)

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
6. Smoke Purge Fans Sizing:
CHK'D

SAS

SAS

For sizing of smoke purge fan, we take the building air changes to be at (4.6 ACH)
so that smoke laden air without any drought can be exhausted.
INCORPORATED SEC COMMENTS

Sample Calculations
ISSUED FOR BASE DESIGN

Volume of conditioned space = 47497 ft


No. of Air changes / hour = 4.6 ACH
Exhaust cfm = Volume of space X Air changes / hr
DESCRIPTION

60
= 47497X 4.6
.
= 3641 cfm
Table summary
From HVAC Data Gathering sheet,
Exhaust
FAN VOLUME TIME R.Q.D IN
S.NO ROOM REF ACH Air Flow
REF.NO IN ft sec
(cfm)
SYSTEM-01
JOB ORDER NO.

132 KV G.I.S RM-


109

109

154911 4.6 11877


Ground Flr
1 SPF-01 783
132kv G.I.S Basement
47497 4.6 3641
00 28/05/2013 SATECH

01 13/08/2013 SATECH

Floor
BY

TOTAL EXHAUST FLOW cfm 15518


SYSTEM-02
DATE

13.8KV SWGR RM-A


15315 4.6 1174
Ground Flr
NO.

13.8KV SWGR RM-B


15926 4.6 1221
REVISIONS Ground Flr
DRAWN 13.8KV SWGR RM-C
16682 4.6 1279
Ground Flr
BY SAS 13.8KV SWGR RM-A
1 SPF-02 8326 4.6 783 638
DATE 13/08/2013 Basement Flr
CHECKED 13.8KV SWGR RM-B
8621 4.6 661
Basement Flr
BY SAS 13.8KV SWGR RM-C
9066 4.6 695
DATE 13/08/2013 Basement Flr
OPRG. DEPT. E.Gas Room 4074 4.6 312
STAIR-2 1483 4.6 114
BY ___________ TOTAL EXHAUST FLOW cfm 6094
DATE

ENG`G DEPT. SYSTEM-03


Control Room 38128 4.6 2923
BY ___________ 3 SPF-03 Telecom Room 9692 4.6 783 743
DATE _______ 0
APPROVAR/CERTF. TOTAL EXHAUST FLOW cfm 3666
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 38 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APPR`D.

SVR

SVR
DRAWING COMPLETION CERTIFICATE (DCC)
CERT`D

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
7. SAND TRAP LOUVER SIZING
CHK'D

SAS

SAS

GROUP-01 (PACU 01 & 02 )

DATA
INCORPORATED SEC COMMENTS

* From calculations
ISSUED FOR BASE DESIGN

Fresh Air requirement at normal operation Q = 1309 cfm

recommended face velocity v = 100 fpm


DESCRIPTION

Q = 0.33 x W(in) x H(in) x face velocity (fpm)


144
Standard free area ratio

A (in) = _______Q x 144________


0.33 x face velocity (fpm)

= _______1309 x 144________ = 5712


0.33 x100
JOB ORDER NO.

A = 5712 in
109

109

= 39.7 ft
assuming width as W = 5.9 ft
00 28/05/2013 SATECH

01 13/08/2013 SATECH

height will be H = 6.72 ft


BY
DATE

GROUP-02 (PACU 03 & 04 )


NO.

DATA
REVISIONS
DRAWN * From calculations
Fresh Air requirement at normal operation Q = 2127 cfm
BY SAS
DATE 13/08/2013 recommended face velocity v = 100 fpm
CHECKED

Q = 0.33 x W(in) x H(in) x face velocity (fpm)


BY SAS 144
DATE 13/08/2013 Standard free area ratio
OPRG. DEPT.

A (in) = _______Q x 144________


BY ___________ 0.33 x face velocity (fpm)
DATE

ENG`G DEPT. = _______2127 x 144________ = 9281


0.33 x100
BY ___________ A = 4711 in
DATE _______ = 32.7 ft
APPROVAR/CERTF. assuming width as W = 5.9 ft
INFORMATION height will be H = 5.55 ft
DCC NO. _______
REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 39 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APPR`D.

SVR

SVR
DRAWING COMPLETION CERTIFICATE (DCC)
CERT`D

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
7.SAND TRAP LOUVER SIZING
CHK'D

SAS

SAS

GROUP-03 ( PACU 05 & 06 )

DATA
INCORPORATED SEC COMMENTS

* From calculations
ISSUED FOR BASE DESIGN

Fresh Air requirement at normal operation Q = 602 cfm

recommended face velocity v = 100 fpm


DESCRIPTION

Q = 0.33 x W(in) x H(in) x face velocity (fpm)


144
Standard free area ratio

A (in) = _______Q x 144________


0.33 x face velocity (fpm)

= _______602 x 144________
0.33 x100
JOB ORDER NO.

A = 2627 in
109

109

= 18.2 ft
assuming width as W = 5.9 ft
00 28/05/2013 SATECH

01 13/08/2013 SATECH

height will be H = 3.09 ft


BY
DATE
NO.

REVISIONS
DRAWN

BY SAS
DATE 13/08/2013
CHECKED

BY SAS
DATE 13/08/2013
OPRG. DEPT.

BY ___________
DATE

ENG`G DEPT.

BY ___________
DATE _______
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 40 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

APPR`D.

SVR

SVR
DRAWING COMPLETION CERTIFICATE (DCC)
CERT`D

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS
INCORPORATED SEC COMMENTS
ISSUED FOR BASE DESIGN
DESCRIPTION
JOB ORDER NO.

109

109
00 28/05/2013 SATECH

01 13/08/2013 SATECH

APPENDIX-1
BY
DATE
NO.

* Heat Dissipation Values Reference Sheets


REVISIONS
DRAWN * U value Reference Sheets

BY SAS
DATE 13/08/2013
CHECKED

BY SAS
DATE 13/08/2013
OPRG. DEPT.

BY ___________
DATE

ENG`G DEPT.

BY ___________
DATE _______
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 41 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

SEC-COA CONSTRUCTION OF 8521 132kV GIS 01-TMSS-01, Rev.1


Rev.No. 00
CONTRACT No. : - 32-TMSS-02, Rev.0

2) HEAT DISSIPATION DATA SHEET


1. INPUT DATA
1.1 Project Name : SEC-COA CONSTRUCTION OF 8521 132/13.8 kV S/S
1.2 Item : 132kV 40kA 2000/1200/800A GIS
1.3 T/L Feeder Current (If) 1200 A
-. Conductor Resistance (Rfc): 2.07E-05 ohm/m
-. Tank Resistance (Rft) : 1.44E-05 ohm/m
1.4 T/R Feeder Current (If) 800 A
-. Conductor Resistance (Rfc): 2.07E-05 ohm/m
-. Tank Resistance (Rft) : 1.44E-05 ohm/m
1.5 MainBus Current (Im) : 2000 A
-. Conductor Resistance (Rmc): 2.07E-05 ohm/m
-. Tank Resistance (Rmt) : 1.44E-05 ohm/m
1.6 Enclosure type (Nc) 1 enclosure per bay
1.7 LCC quantity : 14 EA
1.8 Tank induced current is 10% of main current

2. Heat dissipation of 3-phase conductor and tank


2.1 T/L Feeder
2
2.1.1 Conductor loss = 8.94E+01 W/m ( = 3 * If * Rfc )
2.1.2 Tank loss due to induced current of magnetic flux components for 3phase
2
= 0.21 W/m ( = Nc * (0.1If) * Rft )
3.1 T/R Feeder
2
3.1.1 Conductor loss = 3.97E+01 W/m ( = 3 * Im * Rmc )
3.1.2 Tank loss due to induced current of magnetic flux components for 3phase
2
= 0.09 W/m ( = Nc * (0.1Im) * Rmt )
4.1 Main Bus
2
4.1.1 Conductor loss = 2.48E+02 W/m ( = 3 * Im * Rmc )
4.1.2 Tank loss due to induced current of magnetic flux components for 3phase
2
= 0.58 W/m ( = Nc * (0.1Im) * Rmt )
http://boilersinfo.com/

SEC-COA CONSTRUCTION OF 8521 132kV GIS 01-TMSS-01, Rev.1


Rev.No. 00
CONTRACT No. : - 32-TMSS-02, Rev.0

5. Heat dissipation of LCC (general type gas density meter)


5.1 Average heat dissipation per LCC: 148.7W
5.2 The # of LCC 14 EA
5.3 Total Heat dissipation 2081.8 W

6. The Calculation of Heat dissipation (INDOOR)

Heat dissipation of
Length GIS [W] # of Total Heat
Bay Name
[M] Feeder [W]
Conductor Tank

T/L Feeder(1200A) 11 89.39 0.21 6 5,913.19

T/L Feeder with Bushing(1200A) 25 89.39 0.21 2 4,479.69

T/R Feeder(800A) 22 39.73 0.09 3 2,628.08

Bus section(2000A) 16 248.30 0.58 1 3,981.94

Bus coupler(2000A) 9 248.30 0.58 2 4,479.69

Main Bus(2000A) 37 248.30 0.58 1 9,208.25

LCC - 148.7 14 2081.8

.
* TOTAL HEAT DISSIPATION : 32,772.64 W
http://boilersinfo.com/

S
PROJECT : CONSTRUCTION OF NEW 132/13.8kV S/S # 8521
TITLE : 13.8kV SWGR HEAT DISSIPATION DETAILS

HEAT
SERIAL NUMBER OF
DESCRIPTION DISSIPATED TOTAL
No. PANELS / SS
(watts)

13.8kV SWGR Incomer Panels

1.0 3150A Branch Busbar 3 1200 3,600.00 watts


3150A Main Busbar
AD3 WITH LF3-3600A Breaker

13.8kV SWGR Metered Feeder Panels

2.0 2000A(max load current) Branch Busbar 2 1100 2,200.00 watts


3150A Main Busbar
AD3 WITH LF3-2000A Breaker

13.8kV SWGR Plain O/G Feeder Panels

3.0 400A(max load current) Branch Busbar 18 510 9,180.00 watts


3150A Main Busbar
AD2 WITH LF2-630A Breaker

13.8kV SWGR Plain Capacitor Feeder Panels


400A(max load current) Branch Busbar
4.0 3 510 1,530.00 watts
3150A Main Busbar
AD2 WITH LF2-630A Breaker

13.8kV SWGR Bus Riser/VT/Earthing Panels


5.0 3 200 600.00 watts
3150A Main Busbar

13.8kV SWGR Bus Tie Panel

6.0 3150A Branch Busbar 2 1300 2,600.00 watts


3150A Main Busbar
AD3 WITH LF3-3150A Breaker

TOTAL HEAT DISSIPATED BY THE 13.8kV SWGR PANELS > > > > > > 19,710.00 watts
http://boilersinfo.com/

SHAQRASUBSTATION#8521
CONTROLROOMHEATDISSIPATION

S.NO PANELDESCRIPTION QTY WATTS/PANEL TOALWATTS


1 PROTECTIONPANEL 29 200 5800
2 SASPANEL 13 _ 3938
OTHERPANELS(HVAC,Lighting,
3 31 200 6200
etc.,)
TOTAL 15938
http://boilersinfo.com/

3) HEAT DISSIPATION ESTIMATION

S.No DESCRIPTION QTY WATT/CUBICLE TOTAL REMARK

1 RELAY PANEL 29 200.00 5800.00 MAXIMUM

TOTAL HEAT DISSIPATION 5800.00 WATTS

Based on PTS Customer Doc PTS#09CN168 Prepared 11-10-2011 GP Title AC/DC Load Calculation & Doc kind Base Design Plant No. C279
- - - - - Approved 11-10-2011 AK Heat Dissipation Estimation Division PSAC Rev Ind. 00
- - - - - Project National Grid, SA - Central Operating Area Protection & Control Panels Resp Dept Engineering Language EN
00 For Approval GP 13 06 SS 8521 - 132/13.8KV in Al-Shaqra University Protection & Substation Automation Sheet 19
Rev Revision note Name Year Week 00000000/00 ABB ABB Automation, Saudi Arabia Doc No CE-317261 No. Sheets 20
http://boilersinfo.com/
http://boilersinfo.com/
http://boilersinfo.com/
http://boilersinfo.com/
http://boilersinfo.com/

APPR`D.

SVR

SVR
DRAWING COMPLETION CERTIFICATE (DCC)
CERT`D

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS
INCORPORATED SEC COMMENTS
ISSUED FOR BASE DESIGN
DESCRIPTION
JOB ORDER NO.

109

109
00 28/05/2013 SATECH

01 13/08/2013 SATECH

APPENDIX-2
BY
DATE
NO.

* Computer Generated Load Calculation ( Using ELITE CHVAC Software)


REVISIONS
DRAWN

BY SAS
DATE 13/08/2013
CHECKED

BY SAS
DATE 13/08/2013
OPRG. DEPT.

BY ___________
DATE

ENG`G DEPT.

BY ___________
DATE _______
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 42 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/

132KV G.I.S BLDG, SHAQRA #8521


HVAC Load Analysis
for

NGSA (Central Region)


(Saudi Electricity Company)
Riyadh,ksa

Prepared By:

Satech
Al-khobar

Tuesday, August 13, 2013


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 132KV G.I.S BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 2

Air Handler Input


Air Handler Number 1 Input Data
Name: Pacu-01A & 01B
Terminal type: Constant Volume
Method for CV Sum of Peaks
Supply fan type: Package fan
Calculations performed: Both heating and cooling loads
Excess supply air: Reserve
Occurrences: 1
People profile number: 1
Lighting profile number: 2
Equipment profile number: 3
Exhaust may not exceed supply air: Yes
Leaving heating coil temp (deg.F): 90.0
Leaving cooling coil temp (deg.F): 57.0
Cooling coil CFM 0
Misc. Btuh gain - supply side: 0
Misc. Btuh gain - return side: 0
Combined fan & motor efficiency: 85
Static pressure across fan (in.wg.): 0.50
Summer supply duct temp rise (deg.F): 1.000
Summer return duct temp rise (deg.F): 0.250
Winter supply duct temp drop (deg.F): 2.000
Winter return duct temp drop (deg.F): 1.000
Chilled water temp difference (deg.F): 0.000
Hot water temp difference (deg.F): 0.000
Cooling ventilation: 0 Direct
Cooling infiltration: 0 AC/Hr
Heating ventilation: 0 Direct
Heating infiltration: 0 Direct
Pretreated outside air: none
Pretreated air Summer DB (deg.F): 0
Pretreated air Summer WB (deg.F): 0
Pretreated air Winter DB (deg.F): 0

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
August 123 76 50% 77 -4.63 9
Winter 41 77

D:\ ...\SUBSTATION SHAQRA-132KV G.I.S ROOM.CH8 Tuesday, August 13, 2013, 01:26 PM
http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 132KV G.I.S BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 3

Zone Input
Zone 1: 132kv Gis Room (ground) (4796.006 sq.ft) (Group 1)
Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 117.09 Zone width (feet): 40.96
Lighting Watts: 11,990 Equipment Watts: 32,773
Number of people in zone: 2 People profile number: 1
Lighting profile number: 2 Equipment profile number: 3
Ceiling height (feet): 32.30 Heating safety factor (%): 0
Sensible safety factor (%): 5 Latent safety factor (%): 5
Sensible heat per person (Btuh): 375 Latent heat per person (Btuh): 625
Cooling ventilation method: Direct Cooling ventilation value: 1,059.000
Cooling infiltration method: AC/Hr Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 1,059.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 4,796 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 2 8 0.060 No 117.09 40.96 4,796.0 No

Part Type U-Factor Cool TD Heat TD Height Width Area


6 1 0.463 10.000 15.000 18.89 40.96 773.7

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 A 0.100 D 32.30 117.09 3,782.0 NE
2 1 A 0.100 D 13.12 42.64 559.4 NW
3 1 A 0.100 D 32.30 118.57 3,829.8 SW
4 1 A 0.100 D 32.30 30.79 994.5 SE
5 1 A 0.100 D 9.84 12.13 119.4 SE
7 2 G 0.282 D 16.40 13.12 215.2 SE
8 2 G 0.282 D 7.22 3.94 28.4 SE

Zone 2: STAIR-1 (99.2 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 19.84 Zone width (feet): 5.00
Lighting Watts: 149 Equipment Watts: 0
Number of people in zone: 0 People profile number: 1
Lighting profile number: 2 Equipment profile number: 3
Ceiling height (feet): 19.02 Heating safety factor (%): 0
Sensible safety factor (%): 5 Latent safety factor (%): 5
Sensible heat per person (Btuh): 375 Latent heat per person (Btuh): 625
Cooling ventilation method: Direct Cooling ventilation value: 11.000
Cooling infiltration method: AC/Hr Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 11.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 99 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 2 8 0.060 No 19.84 5.00 99.2 No

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 A 0.100 D 8.69 6.47 56.2 NE
2 1 A 0.100 D 8.69 9.18 79.8 NW
3 1 A 0.100 D 8.69 21.32 185.3 SE
4 1 A 0.100 D 8.69 6.47 56.2 SW
5 2 G 0.282 D 7.22 3.94 28.4 NE

D:\ ...\SUBSTATION SHAQRA-132KV G.I.S ROOM.CH8 Tuesday, August 13, 2013, 01:26 PM
http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 132KV G.I.S BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 4

Zone Input (cont'd)


Zone 2: STAIR-1 (99.2 sq.ft) (Group 1)

Zone 3: 132 Basement (4796.006 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 117.09 Zone width (feet): 40.96
Lighting Watts: 4,796 Equipment Watts: 10,000
Number of people in zone: 2 People profile number: 1
Lighting profile number: 3 Equipment profile number: 3
Ceiling height (feet): 9.51 Heating safety factor (%): 0
Sensible safety factor (%): 5 Latent safety factor (%): 5
Sensible heat per person (Btuh): 375 Latent heat per person (Btuh): 625
Cooling ventilation method: Direct Cooling ventilation value: 276.000
Cooling infiltration method: AC/Hr Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 276.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 4,796 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

D:\ ...\SUBSTATION SHAQRA-132KV G.I.S ROOM.CH8 Tuesday, August 13, 2013, 01:26 PM
http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 132KV G.I.S BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 5

Building Summary Loads


Building peaks in August at 5pm.
Bldg Load Area Sen %Tot Lat Sen Net %Net
Descriptions Quan Loss Loss Gain Gain Gain Gain
Roof 4,895 10,574 9.05 0 9,809 9,809 2.90
Wall 9,935 37,547 32.13 0 29,879 29,879 8.84
Glass 0 0 0.00 0 0 0 0.00
Floor Slab 0 0 0.00 0 0 0 0.00
Skin Loads 48,121 41.18 0 39,689 39,689 11.75
Lighting 16,935 0 0.00 0 60,674 60,674 17.96
Equipment 42,773 0 0.00 0 153,245 153,245 45.35
Pool Latent 0 0 0.00 0 0 0 0.00
People 4 0 0.00 2,625 1,575 4,200 1.24
Partition 774 5,374 4.60 0 3,762 3,762 1.11
Cool. Pret. 0 0 0.00 0 0 0 0.00
Heat. Pret. 0 0 0.00 0 0 0 0.00
Cool. Vent. 1,346 0 0.00 4,254 55,191 59,445 17.59
Heat. Vent. 1,346 48,769 41.74 0 0 0 0.00
Cool. Infil. 0 0 0.00 0 0 0 0.00
Heat. Infil. 0 0 0.00 0 0 0 0.00
Draw-Thru Fan 0 0 0.00 0 0 0 0.00
Blow-Thru Fan 0 0 0.00 0 0 0 0.00
Reserve Cap. 0 0 0.00 0 0 0 0.00
Reheat Cap. 0 0 0.00 0 0 0 0.00
Supply Duct 0 9,726 8.32 0 13,797 13,797 4.08
Return Duct 0 4,863 4.16 0 3,104 3,104 0.92
Misc. Supply 0 0 0.00 0 0 0 0.00
Misc. Return 0 0 0.00 0 0 0 0.00
Building Totals 116,853 100.00 6,879 331,036 337,915 100.00

Building Sen %Tot Lat Sen Net %Net


Summary Loss Loss Gain Gain Gain Gain
Ventilation 48,769 41.74 4,254 55,191 59,445 17.59
Infiltration 0 0.00 0 0 0 0.00
Pretreated Air 0 0.00 0 0 0 0.00
Zone Loads 53,495 45.78 2,625 258,944 261,569 77.41
Plenum Loads 0 0.00 0 0 0 0.00
Fan/Duct/Misc Loads 14,589 12.49 0 16,901 16,901 5.00
Building Totals 116,853 100.00 6,879 331,036 337,915 100.00

Check Figures
Total Building Supply Air (based on a 20 TD): 13,459 CFM
Total Building Vent. Air (10.00% of Supply): 1,346 CFM
Total Conditioned Air Space: 9,691 Sq.ft
Supply Air Per Unit Area: 1.3888 CFM/Sq.ft
Area Per Cooling Capacity: 344.2 Sq.ft/Ton
Cooling Capacity Per Area: 0.0029 Tons/Sq.ft
Heating Capacity Per Area: 12.06 Btuh/Sq.ft
Total Heating Required With Outside Air: 116,853 Btuh
Total Cooling Required With Outside Air: 28.16 Tons

D:\ ...\SUBSTATION SHAQRA-132KV G.I.S ROOM.CH8 Tuesday, August 13, 2013, 01:26 PM
http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 132KV G.I.S BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 6

Air Handler #1 - Pacu-01A & 01B - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
132kv Gis Room
4,796 51,633 206,226 1,313 Direct Direct
1 (ground)
2 4,664 10,588 0 1,059 1,059
9pm August
154,911 0.97 2.21 0 1,299 1,059

2 STAIR-1 99 1,862 2,128 0 Direct Direct


8pm August 0 168 109 0 11 11
1,887 1.70 1.10 0 47 11

3 132 Basement 4,796 0 53,798 1,313 Direct Direct


12am August 2 0 2,762 0 276 276
45,610 0.00 0.58 0 0 276
Zone Peak Totals: 9,691 53,495 262,152 2,625
Total Zones: 3 4 4,832 13,460 0 1,346 1,346
Unique Zones: 3 202,408 0.50 1.39 0 1,346 1,346
Main trunk duct size: 54 in. dia, Velocity: 846.3 ft/min, Pressure drop: 0.014 in.wg./100ft

D:\ ...\SUBSTATION SHAQRA-132KV G.I.S ROOM.CH8 Tuesday, August 13, 2013, 01:26 PM
http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 132KV G.I.S BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 7

Air Handler #1 - Pacu-01A & 01B - Total Load Summary


Air Handler Description: Pacu-01A & 01B Constant Volume - Sum of Peaks
Sensible Heat Ratio: 0.99 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in August.
Outdoor Conditions: Clg: 117 DB, 76 WB, 79.32 grains, Htg: 41 DB
Indoor Conditions: Clg: 77 DB, 50% RH, Htg: 77 DB
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 53,495 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 48,769 Btuh 1,346 CFM
Supply Duct sensible loss: 9,726 Btuh
Return Duct sensible loss: 4,863 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 116,853 Btuh
Heating Supply Air: 63,221 / (.932 X 1.08 X 13) = 4,832 CFM
Winter Vent Outside Air (27.9% of supply) = 1,346 CFM
Zone space sensible gain: 258,944 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 13,797 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 272,741 Btuh
Cooling Supply Air: 275,941 / (.932 X 1.1 X 20) = 13,459 CFM
Summer Vent Outside Air (10.0% of supply) = 1,346 CFM
Return duct sensible gain: 3,104 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 55,191 Btuh 1,346 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 58,295 Btuh
Total sensible gain on air handling system: 331,036 Btuh
Zone space latent gain: 2,625 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 4,254 Btuh
Total latent gain on air handling system: 6,879 Btuh
Total system sensible and latent gain: 337,915 Btuh

Check Figures
Total Air Handler Supply Air (based on a 20 TD): 13,459 CFM
Total Air Handler Vent. Air (10.00% of Supply): 1,346 CFM
Total Conditioned Air Space: 9,691 Sq.ft
Supply Air Per Unit Area: 1.3888 CFM/Sq.ft
Area Per Cooling Capacity: 344.2 Sq.ft/Ton
Cooling Capacity Per Area: 0.0029 Tons/Sq.ft
Heating Capacity Per Area: 12.06 Btuh/Sq.ft
Total Heating Required With Outside Air: 116,853 Btuh
Total Cooling Required With Outside Air: 28.16 Tons

D:\ ...\SUBSTATION SHAQRA-132KV G.I.S ROOM.CH8 Tuesday, August 13, 2013, 01:26 PM
http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 132KV G.I.S BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 8

Air Handler #1 - Pacu-01A & 01B - Summary Loads for Groups (G)
Gr Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Group Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
1 Group 1 9,691 53,495 262,144 2,625 n/a n/a
9pm August 4 4,832 13,459 0 1,346 1,346
202,408 0.50 1.39 0 1,346 1,346
Group Peak Totals: 9,691 53,495 262,144 2,625
Total Groups: 1 4 4,832 13,459 0 1,346 1,346
202,408 0.50 1.39 0 1,346 1,346
Main trunk duct size: 54 in. dia, Velocity: 846.3 ft/min, Pressure drop: 0.014 in.wg./100ft

D:\ ...\SUBSTATION SHAQRA-132KV G.I.S ROOM.CH8 Tuesday, August 13, 2013, 01:26 PM
http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 132KV G.I.S BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 9

Air Handler #1 - Pacu-01A & 01B - Summary Loads for Zones (G)
Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Group Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
132kv Gis Room
4,796 51,633 206,226 1,313 Direct Direct
1 (ground)
2 4,664 10,588 0 1,059 1,059
9pm August
154,911 0.97 2.21 0 1,299 1,059

2 STAIR-1 99 1,862 2,120 0 Direct Direct


9pm August 0 168 109 0 11 11
1,887 1.70 1.10 0 47 11

3 132 Basement 4,796 0 53,798 1,313 Direct Direct


9pm August 2 0 2,762 0 276 276
45,610 0.00 0.58 0 0 276
Zone Peak Totals: 9,691 53,495 262,144 2,625
Total Zones: 3 4 4,832 13,459 0 1,346 1,346
202,408 0.50 1.39 0 1,346 1,346
Main trunk duct size: 54 in. dia, Velocity: 846.3 ft/min, Pressure drop: 0.014 in.wg./100ft

D:\ ...\SUBSTATION SHAQRA-132KV G.I.S ROOM.CH8 Tuesday, August 13, 2013, 01:26 PM
http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 132KV G.I.S BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 10

Air Handler #1 - Pacu-01A & 01B - Total Load Summary (G)


Air Handler Description: Pacu-01A & 01B Constant Volume - Sum of Peaks
Sensible Heat Ratio: 0.99 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in August.
Outdoor Conditions: Clg: 117 DB, 76 WB, 79.32 grains, Htg: 41 DB
Indoor Conditions: Clg: 77 DB, 50% RH, Htg: 77 DB
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 53,495 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 48,769 Btuh 1,346 CFM
Supply Duct sensible loss: 9,726 Btuh
Return Duct sensible loss: 4,863 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 116,853 Btuh
Heating Supply Air: 63,221 / (.932 X 1.08 X 13) = 4,832 CFM
Winter Vent Outside Air (27.9% of supply) = 1,346 CFM
Zone space sensible gain: 258,944 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 13,797 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 272,741 Btuh
Cooling Supply Air: 275,941 / (.932 X 1.1 X 20) = 13,459 CFM
Summer Vent Outside Air (10.0% of supply) = 1,346 CFM
Return duct sensible gain: 3,104 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 55,191 Btuh 1,346 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 58,295 Btuh
Total sensible gain on air handling system: 331,036 Btuh
Zone space latent gain: 2,625 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 4,254 Btuh
Total latent gain on air handling system: 6,879 Btuh
Total system sensible and latent gain: 337,915 Btuh

Check Figures
Total Air Handler Supply Air (based on a 20 TD): 13,459 CFM
Total Air Handler Vent. Air (10.00% of Supply): 1,346 CFM
Total Conditioned Air Space: 9,691 Sq.ft
Supply Air Per Unit Area: 1.3888 CFM/Sq.ft
Area Per Cooling Capacity: 344.2 Sq.ft/Ton
Cooling Capacity Per Area: 0.0029 Tons/Sq.ft
Heating Capacity Per Area: 12.06 Btuh/Sq.ft
Total Heating Required With Outside Air: 116,853 Btuh
Total Cooling Required With Outside Air: 28.16 Tons

D:\ ...\SUBSTATION SHAQRA-132KV G.I.S ROOM.CH8 Tuesday, August 13, 2013, 01:26 PM
http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 132KV G.I.S BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 11

Group Detailed Loads (At Group Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 1-132kv Gis Room (ground) - Air Handler 1 (Pacu-01A & 01B), Group 1 peaks (sensible)
in August at 9pm.
Roof-1-8-No.Clg-L 4,796 0.50 35.3 0.060 10,160 2.160 10,359
Wall-1-NE-A-D 3,782 1 28.7 0.100 10,871 3.600 13,615
Wall-2-NW-A-D 559 1 26.7 0.100 1,496 3.600 2,014
Wall-3-SW-A-D 3,830 1 31.0 0.100 11,871 3.600 13,787
Wall-4-SE-A-D 995 1 32.0 0.100 3,182 3.600 3,580
Wall-5-SE-A-D 119 1 32.0 0.100 382 3.600 430
Wall-7-SE-G-D 215 1 20.0 0.282 1,213 10.152 2,184
Wall-8-SE-G-D 28 1 20.0 0.282 160 10.152 289
Partition-6-1 773.7344 10/15 0.463 3,582 6.945 5,374
Lights-Prof=2 11,990 1.000 40,912
Equipment-Prof=3 32,773 1.000 111,826 0
People-Prof=1 2.0 1.000 750 1,250
Sub-total 196,406 1,250 51,633
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 206,226 1,313 51,633

Zone 2-STAIR-1 - Air Handler 1 (Pacu-01A & 01B), Group 1 peaks (sensible) in August at 9pm.
Roof-1-8-No.Clg-L 99 0.50 35.3 0.060 210 2.160 214
Wall-1-NE-A-D 56 1 28.7 0.100 162 3.600 202
Wall-2-NW-A-D 80 1 26.7 0.100 213 3.600 287
Wall-3-SE-A-D 185 1 32.0 0.100 593 3.600 667
Wall-4-SW-A-D 56 1 31.0 0.100 174 3.600 202
Wall-5-NE-G-D 28 1 19.7 0.282 158 10.152 289
Lights-Prof=2 149 1.000 508
Sub-total 2,019 0 1,862
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 2,120 0 1,862

Zone 3-132 Basement - Air Handler 1 (Pacu-01A & 01B), Group 1 peaks (sensible) in August at
9pm.
Lights-Prof=3 4,796 1.000 16,365
Equipment-Prof=3 10,000 1.000 34,121 0
People-Prof=1 2.0 1.000 750 1,250
Sub-total 51,236 1,250 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 53,798 1,313 0

D:\ ...\SUBSTATION SHAQRA-132KV G.I.S ROOM.CH8 Tuesday, August 13, 2013, 01:26 PM
http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 132KV G.I.S BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 12

Zone Detailed Loads (At Zone Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 1-132kv Gis Room (ground) peaks (sensible) in August at 9pm, Air Handler 1 (Pacu-01A &
01B), Group 1, 117.1 x 41.0, Construction Type: 10 (Medium)
Roof-1-8-No.Clg-L 4,796 0.50 35.3 0.060 10,160 2.160 10,359
Wall-1-NE-A-D 3,782 1 28.7 0.100 10,871 3.600 13,615
Wall-2-NW-A-D 559 1 26.7 0.100 1,496 3.600 2,014
Wall-3-SW-A-D 3,830 1 31.0 0.100 11,871 3.600 13,787
Wall-4-SE-A-D 995 1 32.0 0.100 3,182 3.600 3,580
Wall-5-SE-A-D 119 1 32.0 0.100 382 3.600 430
Wall-7-SE-G-D 215 1 20.0 0.282 1,213 10.152 2,184
Wall-8-SE-G-D 28 1 20.0 0.282 160 10.152 289
Partition-6-1 773.7344 10/15 0.463 3,582 6.945 5,374
Lights-Prof=2 11,990 1.000 40,912
Equipment-Prof=3 32,773 1.000 111,826 0
People-Prof=1 2.0 1.000 750 1,250
Sub-total 196,406 1,250 51,633
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 206,226 1,313 51,633

Zone 2-STAIR-1 peaks (sensible) in August at 8pm, Air Handler 1 (Pacu-01A & 01B), Group 1,
19.8 x 5.0, Construction Type: 10 (Medium)
Roof-1-8-No.Clg-L 99 0.50 35.8 0.060 213 2.160 214
Wall-1-NE-A-D 56 1 27.7 0.100 156 3.600 202
Wall-2-NW-A-D 80 1 25.7 0.100 205 3.600 287
Wall-3-SE-A-D 185 1 32.0 0.100 593 3.600 667
Wall-4-SW-A-D 56 1 30.0 0.100 169 3.600 202
Wall-5-NE-G-D 28 1 22.7 0.282 182 10.152 289
Lights-Prof=2 149 1.000 508
Sub-total 2,027 0 1,862
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 2,128 0 1,862

Zone 3-132 Basement peaks (sensible) in August at 12am, Air Handler 1 (Pacu-01A & 01B),
Group 1, 117.1 x 41.0, Construction Type: 10 (Medium)
Lights-Prof=3 4,796 1.000 16,365
Equipment-Prof=3 10,000 1.000 34,121 0
People-Prof=1 2.0 1.000 750 1,250
Sub-total 51,236 1,250 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 53,798 1,313 0

D:\ ...\SUBSTATION SHAQRA-132KV G.I.S ROOM.CH8 Tuesday, August 13, 2013, 01:26 PM
http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 132KV G.I.S BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 13

Air System #1 (Pacu-01A & 01B) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 73.972 57.000
Draw-Thru Fan 0 0.000 0
Misc Load on Supply Side 0 0.000 0 0.000 0
Supply Air Duct 13,797 1.000 673
Zone Loads 2,625 0.308 262,144 19.000 12,786
Sensible Reserve 0 0.000 0
Zone Condition 2,625 74.279 275,941 77.000 13,459
Return Air Duct 3,104 0.250
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000 0 0.000
Vent Air 1,346 CFM 4,254 0.500 55,191 3.975
Blow-Thru Fan 0 0.000
Entering Coil Condition 6,879 74.780 334,236 81.225 13,459

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.932 x 1.10 x 13,459 x( 81.2 - 57.0 )= 334,237 Btuh


TLH = 0.932 x 0.68 x 13,459 x( 74.8 - 74.0 )= 6,893 Btuh
----------
SUM = 341,130 Btuh
GTH = 0.932 x 4.50 x 13,459 x( 31.2 - 25.2 )= 341,725 Btuh
Total System Load = 337,915 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 341,725 / ( 0.00 x 500 ) = 0.0 GPM
Heating GPM = 116,853 / ( 0.00 x 500 ) = 0.0 GPM
Steam Req. = 116,853 / 970 = 120.5 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 81.23 Dry bulb temperature: 66.25
Wet bulb temperature: 65.32
Relative humidity: 43.80
Enthalpy: 31.22 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 57.00 Dry bulb temperature: 90.00
Wet bulb temperature: 56.90
Relative humidity: 99.41
Enthalpy: 25.16 Btu/lbm

D:\ ...\SUBSTATION SHAQRA-132KV G.I.S ROOM.CH8 Tuesday, August 13, 2013, 01:26 PM
http://boilersinfo.com/

13.8KV SWGR BLDG, SHAQRA #8521


HVAC Load Analysis
for

NGSA (Central Region)


(Saudi Electricity Company)
Riyadh,ksa

Prepared By:

Satech
Al-khobar

Tuesday, August 13, 2013


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 13.8KV SWGR BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 2

Air Handler Input


Air Handler Number 2 Input Data
Name: Pacu-02A & 02B
Terminal type: Constant Volume
Method for CV Sum of Peaks
Supply fan type: Package fan
Calculations performed: Both heating and cooling loads
Excess supply air: Reserve
Occurrences: 1
People profile number: 1
Lighting profile number: 2
Equipment profile number: 3
Exhaust may not exceed supply air: Yes
Leaving heating coil temp (deg.F): 90.0
Leaving cooling coil temp (deg.F): 57.0
Cooling coil CFM 0
Misc. Btuh gain - supply side: 0
Misc. Btuh gain - return side: 0
Combined fan & motor efficiency: 85
Static pressure across fan (in.wg.): 0.50
Summer supply duct temp rise (deg.F): 1.000
Summer return duct temp rise (deg.F): 0.250
Winter supply duct temp drop (deg.F): 2.000
Winter return duct temp drop (deg.F): 1.000
Chilled water temp difference (deg.F): 0.000
Hot water temp difference (deg.F): 0.000
Cooling ventilation: 0 Direct
Cooling infiltration: 0 AC/Hr
Heating ventilation: 0 Direct
Heating infiltration: 0 Direct
Pretreated outside air: none
Pretreated air Summer DB (deg.F): 0
Pretreated air Summer WB (deg.F): 0
Pretreated air Winter DB (deg.F): 0

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
August 124 76 50% 77 -6.23 10
Winter 41 77

D:\ ...\SUBSTATION SHAQRA-13.8kv SWGR.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 13.8KV SWGR BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 3

Zone Input
Zone 1: 13.8kv SWGR RM-A (872.153 sq.ft) (Group 2)
Air Handler number: 2 Zone occurrences: 1
Zone length: (feet) 39.11 Zone width (feet): 22.30
Lighting Watts: 1,308 Equipment Watts: 6,570
Number of people in zone: 2 People profile number: 1
Lighting profile number: 2 Equipment profile number: 3
Ceiling height (feet): 17.56 Heating safety factor (%): 0
Sensible safety factor (%): 5 Latent safety factor (%): 5
Sensible heat per person (Btuh): 375 Latent heat per person (Btuh): 625
Cooling ventilation method: Direct Cooling ventilation value: 196.000
Cooling infiltration method: AC/Hr Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 196.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 872 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 2 8 0.060 No 39.11 22.30 872.2 No

Part Type U-Factor Cool TD Heat TD Height Width Area


4 1 0.463 10.000 15.000 17.56 39.42 692.2

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 A 0.100 D 17.56 23.60 414.4 NE
2 1 A 0.100 D 17.56 41.06 721.0 NW
3 2 G 0.282 D 10.00 7.22 72.2 NE

Zone 2: 13.8kv SWGR RM-B (906.9409 sq.ft) (Group 2)


Air Handler number: 2 Zone occurrences: 1
Zone length: (feet) 40.67 Zone width (feet): 22.30
Lighting Watts: 1,360 Equipment Watts: 6,570
Number of people in zone: 2 People profile number: 1
Lighting profile number: 2 Equipment profile number: 3
Ceiling height (feet): 17.56 Heating safety factor (%): 0
Sensible safety factor (%): 5 Latent safety factor (%): 5
Sensible heat per person (Btuh): 375 Latent heat per person (Btuh): 625
Cooling ventilation method: Direct Cooling ventilation value: 192.000
Cooling infiltration method: AC/Hr Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 92.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 907 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 2 8 0.060 No 40.67 22.30 906.9 No

Part Type U-Factor Cool TD Heat TD Height Width Area


3 1 0.463 10.000 15.000 17.56 41.00 720.0

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 A 0.100 D 17.56 29.12 511.3 NW
2 2 G 0.282 D 10.00 7.22 72.2 NW

Zone 3: 13.8kv SWGR RM-C (949.9799 sq.ft) (Group 2)


Air Handler number: 2 Zone occurrences: 1

D:\ ...\SUBSTATION SHAQRA-13.8kv SWGR.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 13.8KV SWGR BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 4

Zone Input (cont'd)


Zone 3: 13.8kv SWGR RM-C (949.9799 sq.ft) (Group 2)
Zone length: (feet) 42.60 Zone width (feet): 22.30
Lighting Watts: 1,425 Equipment Watts: 6,570
Number of people in zone: 2 People profile number: 1
Lighting profile number: 2 Equipment profile number: 3
Ceiling height (feet): 17.56 Heating safety factor (%): 0
Sensible safety factor (%): 5 Latent safety factor (%): 5
Sensible heat per person (Btuh): 375 Latent heat per person (Btuh): 625
Cooling ventilation method: Direct Cooling ventilation value: 193.000
Cooling infiltration method: AC/Hr Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 193.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 950 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 2 8 0.060 No 42.60 22.30 950.0 No

Part Type U-Factor Cool TD Heat TD Height Width Area


4 1 0.463 10.000 15.000 17.56 42.64 748.8

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 A 0.100 D 17.56 22.96 403.2 SW
3 2 G 0.282 D 10.00 7.22 72.2 SW

Zone 4: 13.8kv SWGR RM-A ( BF) (875.4979 sq.ft) (Group 2)


Air Handler number: 2 Zone occurrences: 1
Zone length: (feet) 39.26 Zone width (feet): 22.30
Lighting Watts: 875 Equipment Watts: 3,000
Number of people in zone: 2 People profile number: 1
Lighting profile number: 2 Equipment profile number: 3
Ceiling height (feet): 9.51 Heating safety factor (%): 0
Sensible safety factor (%): 5 Latent safety factor (%): 5
Sensible heat per person (Btuh): 375 Latent heat per person (Btuh): 625
Cooling ventilation method: Direct Cooling ventilation value: 75.000
Cooling infiltration method: AC/Hr Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 75.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 875 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Zone 5: 13.8kv SWGR RM-B ( BF) (906.495 sq.ft) (Group 2)


Air Handler number: 2 Zone occurrences: 1
Zone length: (feet) 40.65 Zone width (feet): 22.30
Lighting Watts: 907 Equipment Watts: 3,000
Number of people in zone: 2 People profile number: 1
Lighting profile number: 2 Equipment profile number: 3
Ceiling height (feet): 9.51 Heating safety factor (%): 0
Sensible safety factor (%): 5 Latent safety factor (%): 5
Sensible heat per person (Btuh): 375 Latent heat per person (Btuh): 625
Cooling ventilation method: Direct Cooling ventilation value: 76.000
Cooling infiltration method: AC/Hr Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 76.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0

D:\ ...\SUBSTATION SHAQRA-13.8kv SWGR.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 13.8KV SWGR BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 5

Zone Input (cont'd)


Zone 5: 13.8kv SWGR RM-B ( BF) (906.495 sq.ft) (Group 2)
Ceil. exposed to plenum (sq.ft): 906 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Zone 6: 13.8kv SWGR RM-C ( BF) (953.325 sq.ft) (Group 2)


Air Handler number: 2 Zone occurrences: 1
Zone length: (feet) 42.75 Zone width (feet): 22.30
Lighting Watts: 953 Equipment Watts: 3,000
Number of people in zone: 2 People profile number: 1
Lighting profile number: 2 Equipment profile number: 3
Ceiling height (feet): 9.51 Heating safety factor (%): 0
Sensible safety factor (%): 5 Latent safety factor (%): 5
Sensible heat per person (Btuh): 375 Latent heat per person (Btuh): 625
Cooling ventilation method: Direct Cooling ventilation value: 77.000
Cooling infiltration method: AC/Hr Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 77.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 953 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Zone 7: Fm200 ROOM (231.978 sq.ft) (Group 2)


Air Handler number: 2 Zone occurrences: 1
Zone length: (feet) 18.86 Zone width (feet): 12.30
Lighting Watts: 348 Equipment Watts: 0
Number of people in zone: 2 People profile number: 1
Lighting profile number: 2 Equipment profile number: 3
Ceiling height (feet): 17.56 Heating safety factor (%): 0
Sensible safety factor (%): 5 Latent safety factor (%): 5
Sensible heat per person (Btuh): 375 Latent heat per person (Btuh): 625
Cooling ventilation method: Direct Cooling ventilation value: 28.000
Cooling infiltration method: AC/Hr Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 28.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 232 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 8 0.060 No 18.86 12.30 232.0 Yes

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 A 0.100 D 17.56 13.61 239.0 NE
2 2 G 0.282 D 10.00 7.22 72.2 NW
3 1 A 0.100 D 17.56 20.17 354.2 NW

Zone 8: STAIR-2 (77.982 sq.ft) (Group 2)


Air Handler number: 2 Zone occurrences: 1
Zone length: (feet) 19.02 Zone width (feet): 4.10
Lighting Watts: 78 Equipment Watts: 0
Number of people in zone: 0 People profile number: 1
Lighting profile number: 2 Equipment profile number: 3
Ceiling height (feet): 19.02 Heating safety factor (%): 0
Sensible safety factor (%): 5 Latent safety factor (%): 5
Sensible heat per person (Btuh): 375 Latent heat per person (Btuh): 625
Cooling ventilation method: Direct Cooling ventilation value: 9.000
Cooling infiltration method: AC/Hr Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 9.000

D:\ ...\SUBSTATION SHAQRA-13.8kv SWGR.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 13.8KV SWGR BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 6

Zone Input (cont'd)


Zone 8: STAIR-2 (77.982 sq.ft) (Group 2)
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 78 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 2 8 0.060 No 19.02 4.10 78.0 No

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 A 0.100 D 8.69 20.33 176.7 SW
2 1 A 0.100 D 8.69 4.92 42.8 SE
3 1 A 0.100 D 8.69 4.92 42.8 NW
4 2 G 0.282 D 7.22 3.94 28.4 NW

Zone 9: BATTERY ROOM-1 (272.322 sq.ft) (Group 2)


Air Handler number: 2 Zone occurrences: 1
Zone length: (feet) 22.14 Zone width (feet): 12.30
Lighting Watts: 408 Equipment Watts: 3,170
Number of people in zone: 2 People profile number: 1
Lighting profile number: 2 Equipment profile number: 3
Ceiling height (feet): 17.56 Heating safety factor (%): 0
Sensible safety factor (%): 5 Latent safety factor (%): 5
Sensible heat per person (Btuh): 375 Latent heat per person (Btuh): 625
Cooling ventilation method: Direct Cooling ventilation value: 956.000
Cooling infiltration method: AC/Hr Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 956.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 953 Summer exhaust air CFM: 956
Minimum supply CFM: 956 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 272 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 8 0.060 No 22.14 12.30 272.3 Yes

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 A 0.100 D 17.56 23.45 411.8 NW
2 2 G 0.282 D 9.18 7.22 66.3 NW
3 1 A 0.100 D 17.56 13.61 239.0 SW

Zone 10: TOILET (117.7848 sq.ft) (Group 2)


Air Handler number: 2 Zone occurrences: 1
Zone length: (feet) 9.84 Zone width (feet): 11.97
Lighting Watts: 118 Equipment Watts: 0
Number of people in zone: 1 People profile number: 1
Lighting profile number: 2 Equipment profile number: 3
Ceiling height (feet): 17.56 Heating safety factor (%): 0
Sensible safety factor (%): 5 Latent safety factor (%): 5
Sensible heat per person (Btuh): 375 Latent heat per person (Btuh): 625
Cooling ventilation method: Direct Cooling ventilation value: 345.000
Cooling infiltration method: AC/Hr Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 345.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 345 Summer exhaust air CFM: 345
Minimum supply CFM: 345 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 118 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

D:\ ...\SUBSTATION SHAQRA-13.8kv SWGR.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 13.8KV SWGR BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 7

Zone Input (cont'd)


Zone 10: TOILET (117.7848 sq.ft) (Group 2)
Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil
1 1 8 0.060 No 9.84 11.97 117.8 Yes

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 A 0.100 D 17.56 12.95 227.4 NE
2 1 A 0.100 D 17.56 12.95 227.4 SW
3 2 G 0.282 D 7.22 3.60 26.0 NW
4 1 A 0.100 D 17.56 11.80 207.2 NW

D:\ ...\SUBSTATION SHAQRA-13.8kv SWGR.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 13.8KV SWGR BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 8

Building Summary Loads


Building peaks in August at 5pm.
Bldg Load Area Sen %Tot Lat Sen Net %Net
Descriptions Quan Loss Loss Gain Gain Gain Gain
Roof 3,429 7,407 5.82 0 6,852 6,852 2.23
Wall 4,628 19,343 15.19 0 18,834 18,834 6.12
Glass 0 0 0.00 0 0 0 0.00
Floor Slab 0 0 0.00 0 0 0 0.00
Skin Loads 26,750 21.01 0 25,686 25,686 8.34
Lighting 7,780 0 0.00 0 27,874 27,874 9.05
Equipment 31,880 0 0.00 0 114,218 114,218 37.09
Pool Latent 0 0 0.00 0 0 0 0.00
People 17 0 0.00 11,156 6,694 17,850 5.80
Partition 2,161 15,008 11.79 0 10,505 10,505 3.41
Cool. Pret. 0 0 0.00 0 0 0 0.00
Heat. Pret. 0 0 0.00 0 0 0 0.00
Cool. Vent. 2,147 0 0.00 4,602 90,235 94,838 30.80
Heat. Vent. 2,047 74,167 58.26 0 0 0 0.00
Cool. Infil. 0 0 0.00 0 0 0 0.00
Heat. Infil. 0 0 0.00 0 0 0 0.00
Draw-Thru Fan 0 0 0.00 0 0 0 0.00
Blow-Thru Fan 0 0 0.00 0 0 0 0.00
Reserve Cap. 0 0 0.00 0 5,003 5,003 1.62
Reheat Cap. 0 0 0.00 0 0 0 0.00
Supply Duct 0 7,592 5.96 0 10,014 10,014 3.25
Return Duct 0 3,796 2.98 0 1,953 1,953 0.63
Misc. Supply 0 0 0.00 0 0 0 0.00
Misc. Return 0 0 0.00 0 0 0 0.00
Building Totals 127,313 100.00 15,759 292,183 307,942 100.00

Building Sen %Tot Lat Sen Net %Net


Summary Loss Loss Gain Gain Gain Gain
Ventilation 74,167 58.26 4,602 90,235 94,838 30.80
Infiltration 0 0.00 0 0 0 0.00
Pretreated Air 0 0.00 0 0 0 0.00
Zone Loads 41,757 32.80 11,156 189,980 201,137 65.32
Plenum Loads 0 0.00 0 0 0 0.00
Fan/Duct/Misc Loads 11,388 8.95 0 11,968 11,968 3.89
Building Totals 127,313 100.00 15,759 292,183 307,942 100.00

Check Figures
Total Building Supply Air (based on a 20 TD): 9,769 CFM
Total Building Vent. Air (21.98% of Supply): 2,147 CFM
Total Conditioned Air Space: 6,164 Sq.ft
Supply Air Per Unit Area: 1.5848 CFM/Sq.ft
Area Per Cooling Capacity: 240.2 Sq.ft/Ton
Cooling Capacity Per Area: 0.0042 Tons/Sq.ft
Heating Capacity Per Area: 20.65 Btuh/Sq.ft
Total Heating Required With Outside Air: 127,313 Btuh
Total Cooling Required With Outside Air: 25.66 Tons

D:\ ...\SUBSTATION SHAQRA-13.8kv SWGR.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 13.8KV SWGR BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 9

Air Handler #2 - Pacu-02A & 02B - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
1 13.8kv SWGR RM-A 872 11,512 38,211 1,313 Direct Direct
9pm August 2 1,040 1,962 0 196 196
15,315 1.19 2.25 0 564 431

2 13.8kv SWGR RM-B 907 9,533 37,400 1,313 Direct Direct


6pm August 2 861 1,920 0 92 192
15,926 0.95 2.12 0 467 422

3 13.8kv SWGR RM-C 950 9,436 37,674 1,313 Direct Direct


5pm August 2 852 1,934 0 193 193
16,682 0.90 2.04 0 463 425

13.8kv SWGR RM-A (


875 0 14,671 1,313 Direct Direct
4 BF)
2 0 753 0 75 75
12am August
8,326 0.00 0.86 0 0 166

13.8kv SWGR RM-B (


906 0 14,785 1,313 Direct Direct
5 BF)
2 0 759 0 76 76
12am August
8,621 0.00 0.84 0 0 167

13.8kv SWGR RM-C (


953 0 14,950 1,313 Direct Direct
6 BF)
2 0 768 0 77 77
12am August
9,066 0.00 0.81 0 0 169

7 Fm200 ROOM 232 3,369 5,456 1,313 Direct Direct


6pm August 2 304 280 0 28 28
4,074 1.31 1.21 0 165 62

8 STAIR-2 78 1,401 1,770 0 Direct Direct


6pm August 0 127 91 0 9 9
1,483 1.62 1.17 0 69 20

9 BATTERY ROOM-1 272 3,604 17,144 1,313 Direct Direct


6pm August 2 326 956 956 956 956
4,782 1.20 3.51 953 177 210

10 TOILET 118 2,902 3,398 656 Direct Direct


6pm August 1 262 345 345 345 345
2,068 2.23 2.93 345 142 76
Zone Peak Totals: 6,164 41,757 185,459 11,156
Total Zones: 10 17 3,772 9,769 1,301 2,047 2,147
Unique Zones: 10 86,342 0.61 1.58 1,298 2,047 2,147
Main trunk duct size: 40 in. h x 40in. w, Velocity: 879.2 ft/min, Pressure drop: 0.021 in.wg./100ft

D:\ ...\SUBSTATION SHAQRA-13.8kv SWGR.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 13.8KV SWGR BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 10

Air Handler #2 - Pacu-02A & 02B - Total Load Summary


Air Handler Description: Pacu-02A & 02B Constant Volume - Sum of Peaks
Sensible Heat Ratio: 0.95 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in August.
Outdoor Conditions: Clg: 118 DB, 76 WB, 77.72 grains, Htg: 41 DB
Indoor Conditions: Clg: 77 DB, 50% RH, Htg: 77 DB
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 41,757 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 74,167 Btuh 2,047 CFM
Supply Duct sensible loss: 7,592 Btuh
Return Duct sensible loss: 3,796 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 127,313 Btuh
Heating Supply Air: 49,349 / (.932 X 1.08 X 13) = 3,772 CFM
Winter Vent Outside Air (54.3% of supply) = 2,047 CFM
Zone space sensible gain: 184,977 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 10,014 Btuh
Reserve sensible gain: 5,003 Btuh
Total sensible gain on supply side of coil: 199,995 Btuh
Cooling Supply Air: 200,284 / (.932 X 1.1 X 20) = 9,769 CFM
Summer Vent Outside Air (22.0% of supply) = 2,147 CFM
Return duct sensible gain: 1,953 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 90,235 Btuh 2,147 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 92,189 Btuh
Total sensible gain on air handling system: 292,183 Btuh
Zone space latent gain: 11,156 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 4,602 Btuh
Total latent gain on air handling system: 15,759 Btuh
Total system sensible and latent gain: 307,942 Btuh

Check Figures
Total Air Handler Supply Air (based on a 20 TD): 9,769 CFM
Total Air Handler Vent. Air (21.98% of Supply): 2,147 CFM
Total Conditioned Air Space: 6,164 Sq.ft
Supply Air Per Unit Area: 1.5848 CFM/Sq.ft
Area Per Cooling Capacity: 240.2 Sq.ft/Ton
Cooling Capacity Per Area: 0.0042 Tons/Sq.ft
Heating Capacity Per Area: 20.65 Btuh/Sq.ft
Total Heating Required With Outside Air: 127,313 Btuh
Total Cooling Required With Outside Air: 25.66 Tons

D:\ ...\SUBSTATION SHAQRA-13.8kv SWGR.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 13.8KV SWGR BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 11

Air Handler #2 - Pacu-02A & 02B - Summary Loads for Groups (G)
Gr Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Group Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
2 Group 2 6,164 41,757 185,267 11,156 n/a n/a
6pm August 17 3,772 9,512 1,301 2,047 2,147
86,342 0.61 1.54 1,298 2,047 2,147
Group Peak Totals: 6,164 41,757 185,267 11,156
Total Groups: 1 17 3,772 9,512 1,301 2,047 2,147
86,342 0.61 1.54 1,298 2,047 2,147
Main trunk duct size: 40 in. h x 40in. w, Velocity: 856.1 ft/min, Pressure drop: 0.020 in.wg./100ft

D:\ ...\SUBSTATION SHAQRA-13.8kv SWGR.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 13.8KV SWGR BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 12

Air Handler #2 - Pacu-02A & 02B - Summary Loads for Zones (G)
Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Group Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
1 13.8kv SWGR RM-A 872 11,512 38,049 1,313 Direct Direct
6pm August 2 1,040 1,954 0 196 196
15,315 1.19 2.24 0 564 441

2 13.8kv SWGR RM-B 907 9,533 37,400 1,313 Direct Direct


6pm August 2 861 1,920 0 92 192
15,926 0.95 2.12 0 467 433

3 13.8kv SWGR RM-C 950 9,436 37,644 1,313 Direct Direct


6pm August 2 852 1,933 0 193 193
16,682 0.90 2.03 0 463 436

13.8kv SWGR RM-A (


875 0 14,671 1,313 Direct Direct
4 BF)
2 0 753 0 75 75
6pm August
8,326 0.00 0.86 0 0 170

13.8kv SWGR RM-B (


906 0 14,785 1,313 Direct Direct
5 BF)
2 0 759 0 76 76
6pm August
8,621 0.00 0.84 0 0 171

13.8kv SWGR RM-C (


953 0 14,950 1,313 Direct Direct
6 BF)
2 0 768 0 77 77
6pm August
9,066 0.00 0.81 0 0 173

7 Fm200 ROOM 232 3,369 5,456 1,313 Direct Direct


6pm August 2 304 280 0 28 28
4,074 1.31 1.21 0 165 63

8 STAIR-2 78 1,401 1,770 0 Direct Direct


6pm August 0 127 91 0 9 9
1,483 1.62 1.17 0 69 21

9 BATTERY ROOM-1 272 3,604 17,144 1,313 Direct Direct


6pm August 2 326 880 956 956 956
4,782 1.20 3.23 953 177 199

10 TOILET 118 2,902 3,398 656 Direct Direct


6pm August 1 262 174 345 345 345
2,068 2.23 1.48 345 142 39
Zone Peak Totals: 6,164 41,757 185,267 11,156
Total Zones: 10 17 3,772 9,512 1,301 2,047 2,147
86,342 0.61 1.54 1,298 2,047 2,147
Main trunk duct size: 40 in. h x 40in. w, Velocity: 856.1 ft/min, Pressure drop: 0.020 in.wg./100ft

D:\ ...\SUBSTATION SHAQRA-13.8kv SWGR.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 13.8KV SWGR BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 13

Air Handler #2 - Pacu-02A & 02B - Total Load Summary (G)


Air Handler Description: Pacu-02A & 02B Constant Volume - Sum of Peaks
Sensible Heat Ratio: 0.94 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in August.
Outdoor Conditions: Clg: 118 DB, 76 WB, 77.72 grains, Htg: 41 DB
Indoor Conditions: Clg: 77 DB, 50% RH, Htg: 77 DB
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 41,757 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 74,167 Btuh 2,047 CFM
Supply Duct sensible loss: 7,592 Btuh
Return Duct sensible loss: 3,796 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 127,313 Btuh
Heating Supply Air: 49,349 / (.932 X 1.08 X 13) = 3,772 CFM
Winter Vent Outside Air (54.3% of supply) = 2,047 CFM
Zone space sensible gain: 184,977 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 9,751 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 194,728 Btuh
Cooling Supply Air: 195,018 / (.932 X 1.1 X 20) = 9,512 CFM
Summer Vent Outside Air (22.6% of supply) = 2,147 CFM
Return duct sensible gain: 1,888 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 90,235 Btuh 2,147 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 92,123 Btuh
Total sensible gain on air handling system: 286,851 Btuh
Zone space latent gain: 11,156 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 4,602 Btuh
Total latent gain on air handling system: 15,759 Btuh
Total system sensible and latent gain: 302,610 Btuh

Check Figures
Total Air Handler Supply Air (based on a 20 TD): 9,512 CFM
Total Air Handler Vent. Air (22.57% of Supply): 2,147 CFM
Total Conditioned Air Space: 6,164 Sq.ft
Supply Air Per Unit Area: 1.5431 CFM/Sq.ft
Area Per Cooling Capacity: 244.5 Sq.ft/Ton
Cooling Capacity Per Area: 0.0041 Tons/Sq.ft
Heating Capacity Per Area: 20.65 Btuh/Sq.ft
Total Heating Required With Outside Air: 127,313 Btuh
Total Cooling Required With Outside Air: 25.22 Tons

D:\ ...\SUBSTATION SHAQRA-13.8kv SWGR.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 13.8KV SWGR BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 14

Group Detailed Loads (At Group Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 1-13.8kv SWGR RM-A - Air Handler 2 (Pacu-02A & 02B), Group 2 peaks (sensible) in
August at 6pm.
Roof-1-8-No.Clg-L 872 0.50 34.8 0.060 1,821 2.160 1,884
Wall-1-NE-A-D 414 1 27.7 0.100 1,150 3.600 1,492
Wall-2-NW-A-D 721 1 24.7 0.100 1,784 3.600 2,596
Wall-3-NE-G-D 72 1 31.7 0.282 646 10.152 733
Partition-4-1 692.2151 10/15 0.463 3,205 6.945 4,807
Lights-Prof=2 1,308 1.000 4,463
Equipment-Prof=3 6,570 1.000 22,418 0
People-Prof=1 2.0 1.000 750 1,250
Sub-total 36,238 1,250 11,512
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 38,049 1,313 11,512

Zone 2-13.8kv SWGR RM-B - Air Handler 2 (Pacu-02A & 02B), Group 2 peaks (sensible) in
August at 6pm.
Roof-1-8-No.Clg-L 907 0.50 34.8 0.060 1,894 2.160 1,959
Wall-1-NW-A-D 511 1 24.7 0.100 1,265 3.600 1,841
Wall-2-NW-G-D 72 1 64.7 0.282 1,318 10.152 733
Partition-3-1 719.96 10/15 0.463 3,333 6.945 5,000
Lights-Prof=2 1,360 1.000 4,641
Equipment-Prof=3 6,570 1.000 22,418 0
People-Prof=1 2.0 1.000 750 1,250
Sub-total 35,619 1,250 9,533
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 37,400 1,313 9,533

Zone 3-13.8kv SWGR RM-C - Air Handler 2 (Pacu-02A & 02B), Group 2 peaks (sensible) in
August at 6pm.
Roof-1-8-No.Clg-L 950 0.50 34.8 0.060 1,984 2.160 2,052
Wall-1-SW-A-D 403 1 28.0 0.100 1,129 3.600 1,451
Wall-3-SW-G-D 72 1 61.0 0.282 1,242 10.152 733
Partition-4-1 748.7584 10/15 0.463 3,467 6.945 5,200
Lights-Prof=2 1,425 1.000 4,862
Equipment-Prof=3 6,570 1.000 22,418 0
People-Prof=1 2.0 1.000 750 1,250
Sub-total 35,851 1,250 9,436
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 37,644 1,313 9,436

Zone 4-13.8kv SWGR RM-A ( BF) - Air Handler 2 (Pacu-02A & 02B), Group 2 peaks (sensible)
in August at 6pm.
Lights-Prof=2 875 1.000 2,986
Equipment-Prof=3 3,000 1.000 10,236 0
People-Prof=1 2.0 1.000 750 1,250
Sub-total 13,972 1,250 0
Safety factors: +5% +5% +0%
--------- --------- ---------

D:\ ...\SUBSTATION SHAQRA-13.8kv SWGR.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 13.8KV SWGR BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 15

Group Detailed Loads (At Group Peak Times) (cont'd)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Total w/ safety factors: 14,671 1,313 0

Zone 5-13.8kv SWGR RM-B ( BF) - Air Handler 2 (Pacu-02A & 02B), Group 2 peaks (sensible)
in August at 6pm.
Lights-Prof=2 907 1.000 3,095
Equipment-Prof=3 3,000 1.000 10,236 0
People-Prof=1 2.0 1.000 750 1,250
Sub-total 14,081 1,250 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 14,785 1,313 0

Zone 6-13.8kv SWGR RM-C ( BF) - Air Handler 2 (Pacu-02A & 02B), Group 2 peaks (sensible)
in August at 6pm.
Lights-Prof=2 953 1.000 3,252
Equipment-Prof=3 3,000 1.000 10,236 0
People-Prof=1 2.0 1.000 750 1,250
Sub-total 14,238 1,250 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 14,950 1,313 0

Zone 7-Fm200 ROOM - Air Handler 2 (Pacu-02A & 02B), Group 2 peaks (sensible) in August at
6pm.
Roof-1-8-Susp.C-L 232 0.50 28.8 0.060 401 2.160 501
Wall-1-NE-A-D 239 1 27.7 0.100 663 3.600 860
Wall-2-NW-G-D 72 1 64.7 0.282 1,318 10.152 733
Wall-3-NW-A-D 354 1 24.7 0.100 876 3.600 1,275
Lights-Prof=2 348 1.000 1,187
People-Prof=1 2.0 1.000 750 1,250
Sub-total 5,196 1,250 3,369
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 5,456 1,313 3,369

Zone 8-STAIR-2 - Air Handler 2 (Pacu-02A & 02B), Group 2 peaks (sensible) in August at 6pm.
Roof-1-8-No.Clg-L 78 0.50 34.8 0.060 163 2.160 168
Wall-1-SW-A-D 177 1 28.0 0.100 495 3.600 636
Wall-2-SE-A-D 43 1 32.0 0.100 137 3.600 154
Wall-3-NW-A-D 43 1 24.7 0.100 106 3.600 154
Wall-4-NW-G-D 28 1 64.7 0.282 519 10.152 289
Lights-Prof=2 78 1.000 266
Sub-total 1,686 0 1,401
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 1,770 0 1,401

D:\ ...\SUBSTATION SHAQRA-13.8kv SWGR.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 13.8KV SWGR BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 16

Group Detailed Loads (At Group Peak Times) (cont'd)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 9-BATTERY ROOM-1 - Air Handler 2 (Pacu-02A & 02B), Group 2 peaks (sensible) in
August at 6pm.
Roof-1-8-Susp.C-L 272 0.50 28.8 0.060 471 2.160 588
Wall-1-NW-A-D 412 1 24.7 0.100 1,019 3.600 1,482
Wall-2-NW-G-D 66 1 64.7 0.282 1,210 10.152 673
Wall-3-SW-A-D 239 1 28.0 0.100 669 3.600 860
Lights-Prof=2 408 1.000 1,392
Equipment-Prof=3 3,170 1.000 10,816 0
People-Prof=1 2.0 1.000 750 1,250
Sub-total 16,327 1,250 3,604
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 17,144 1,313 3,604

Zone 10-TOILET - Air Handler 2 (Pacu-02A & 02B), Group 2 peaks (sensible) in August at 6pm.
Roof-1-8-Susp.C-L 118 0.50 28.8 0.060 204 2.160 254
Wall-1-NE-A-D 227 1 27.7 0.100 631 3.600 819
Wall-2-SW-A-D 227 1 28.0 0.100 637 3.600 819
Wall-3-NW-G-D 26 1 64.7 0.282 475 10.152 264
Wall-4-NW-A-D 207 1 24.7 0.100 513 3.600 746
Lights-Prof=2 118 1.000 403
People-Prof=1 1.0 1.000 375 625
Sub-total 3,236 625 2,902
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 3,398 656 2,902

D:\ ...\SUBSTATION SHAQRA-13.8kv SWGR.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 13.8KV SWGR BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 17

Zone Detailed Loads (At Zone Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 1-13.8kv SWGR RM-A peaks (sensible) in August at 9pm, Air Handler 2 (Pacu-02A &
02B), Group 2, 39.1 x 22.3, Construction Type: 10 (Medium)
Roof-1-8-No.Clg-L 872 0.50 36.3 0.060 1,900 2.160 1,884
Wall-1-NE-A-D 414 1 29.7 0.100 1,233 3.600 1,492
Wall-2-NW-A-D 721 1 27.7 0.100 2,000 3.600 2,596
Wall-3-NE-G-D 72 1 20.7 0.282 422 10.152 733
Partition-4-1 692.2151 10/15 0.463 3,205 6.945 4,807
Lights-Prof=2 1,308 1.000 4,463
Equipment-Prof=3 6,570 1.000 22,418 0
People-Prof=1 2.0 1.000 750 1,250
Sub-total 36,391 1,250 11,512
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 38,211 1,313 11,512

Zone 2-13.8kv SWGR RM-B peaks (sensible) in August at 6pm, Air Handler 2 (Pacu-02A &
02B), Group 2, 40.7 x 22.3, Construction Type: 10 (Medium)
Roof-1-8-No.Clg-L 907 0.50 34.8 0.060 1,894 2.160 1,959
Wall-1-NW-A-D 511 1 24.7 0.100 1,265 3.600 1,841
Wall-2-NW-G-D 72 1 64.7 0.282 1,318 10.152 733
Partition-3-1 719.96 10/15 0.463 3,333 6.945 5,000
Lights-Prof=2 1,360 1.000 4,641
Equipment-Prof=3 6,570 1.000 22,418 0
People-Prof=1 2.0 1.000 750 1,250
Sub-total 35,619 1,250 9,533
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 37,400 1,313 9,533

Zone 3-13.8kv SWGR RM-C peaks (sensible) in August at 5pm, Air Handler 2 (Pacu-02A &
02B), Group 2, 42.6 x 22.3, Construction Type: 10 (Medium)
Roof-1-8-No.Clg-L 950 0.50 32.8 0.060 1,870 2.160 2,052
Wall-1-SW-A-D 403 1 27.0 0.100 1,088 3.600 1,451
Wall-3-SW-G-D 72 1 70.0 0.282 1,425 10.152 733
Partition-4-1 748.7584 10/15 0.463 3,467 6.945 5,200
Lights-Prof=2 1,425 1.000 4,862
Equipment-Prof=3 6,570 1.000 22,418 0
People-Prof=1 2.0 1.000 750 1,250
Sub-total 35,880 1,250 9,436
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 37,674 1,313 9,436

Zone 4-13.8kv SWGR RM-A ( BF) peaks (sensible) in August at 12am, Air Handler 2 (Pacu-02A
& 02B), Group 2, 39.3 x 22.3, Construction Type: 10 (Medium)
Lights-Prof=2 875 1.000 2,986
Equipment-Prof=3 3,000 1.000 10,236 0
People-Prof=1 2.0 1.000 750 1,250
Sub-total 13,972 1,250 0
Safety factors: +5% +5% +0%
--------- --------- ---------

D:\ ...\SUBSTATION SHAQRA-13.8kv SWGR.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 13.8KV SWGR BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 18

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Total w/ safety factors: 14,671 1,313 0

Zone 5-13.8kv SWGR RM-B ( BF) peaks (sensible) in August at 12am, Air Handler 2 (Pacu-02A
& 02B), Group 2, 40.7 x 22.3, Construction Type: 10 (Medium)
Lights-Prof=2 907 1.000 3,095
Equipment-Prof=3 3,000 1.000 10,236 0
People-Prof=1 2.0 1.000 750 1,250
Sub-total 14,081 1,250 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 14,785 1,313 0

Zone 6-13.8kv SWGR RM-C ( BF) peaks (sensible) in August at 12am, Air Handler 2 (Pacu-02A
& 02B), Group 2, 42.8 x 22.3, Construction Type: 10 (Medium)
Lights-Prof=2 953 1.000 3,252
Equipment-Prof=3 3,000 1.000 10,236 0
People-Prof=1 2.0 1.000 750 1,250
Sub-total 14,238 1,250 0
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 14,950 1,313 0

Zone 7-Fm200 ROOM peaks (sensible) in August at 6pm, Air Handler 2 (Pacu-02A & 02B),
Group 2, 18.9 x 12.3, Construction Type: 10 (Medium)
Roof-1-8-Susp.C-L 232 0.50 28.8 0.060 401 2.160 501
Wall-1-NE-A-D 239 1 27.7 0.100 663 3.600 860
Wall-2-NW-G-D 72 1 64.7 0.282 1,318 10.152 733
Wall-3-NW-A-D 354 1 24.7 0.100 876 3.600 1,275
Lights-Prof=2 348 1.000 1,187
People-Prof=1 2.0 1.000 750 1,250
Sub-total 5,196 1,250 3,369
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 5,456 1,313 3,369

Zone 8-STAIR-2 peaks (sensible) in August at 6pm, Air Handler 2 (Pacu-02A & 02B), Group 2,
19.0 x 4.1, Construction Type: 10 (Medium)
Roof-1-8-No.Clg-L 78 0.50 34.8 0.060 163 2.160 168
Wall-1-SW-A-D 177 1 28.0 0.100 495 3.600 636
Wall-2-SE-A-D 43 1 32.0 0.100 137 3.600 154
Wall-3-NW-A-D 43 1 24.7 0.100 106 3.600 154
Wall-4-NW-G-D 28 1 64.7 0.282 519 10.152 289
Lights-Prof=2 78 1.000 266
Sub-total 1,686 0 1,401
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 1,770 0 1,401

D:\ ...\SUBSTATION SHAQRA-13.8kv SWGR.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 13.8KV SWGR BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 19

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 9-BATTERY ROOM-1 peaks (sensible) in August at 6pm, Air Handler 2 (Pacu-02A &
02B), Group 2, 22.1 x 12.3, Construction Type: 10 (Medium)
Roof-1-8-Susp.C-L 272 0.50 28.8 0.060 471 2.160 588
Wall-1-NW-A-D 412 1 24.7 0.100 1,019 3.600 1,482
Wall-2-NW-G-D 66 1 64.7 0.282 1,210 10.152 673
Wall-3-SW-A-D 239 1 28.0 0.100 669 3.600 860
Lights-Prof=2 408 1.000 1,392
Equipment-Prof=3 3,170 1.000 10,816 0
People-Prof=1 2.0 1.000 750 1,250
Sub-total 16,327 1,250 3,604
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 17,144 1,313 3,604

Zone 10-TOILET peaks (sensible) in August at 6pm, Air Handler 2 (Pacu-02A & 02B), Group 2,
9.8 x 12.0, Construction Type: 10 (Medium)
Roof-1-8-Susp.C-L 118 0.50 28.8 0.060 204 2.160 254
Wall-1-NE-A-D 227 1 27.7 0.100 631 3.600 819
Wall-2-SW-A-D 227 1 28.0 0.100 637 3.600 819
Wall-3-NW-G-D 26 1 64.7 0.282 475 10.152 264
Wall-4-NW-A-D 207 1 24.7 0.100 513 3.600 746
Lights-Prof=2 118 1.000 403
People-Prof=1 1.0 1.000 375 625
Sub-total 3,236 625 2,902
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 3,398 656 2,902

D:\ ...\SUBSTATION SHAQRA-13.8kv SWGR.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr 13.8KV SWGR BLDG, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 20

Air System #2 (Pacu-02A & 02B) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 72.493 57.000
Draw-Thru Fan 0 0.000 0
Misc Load on Supply Side 0 0.000 0 0.000 0
Supply Air Duct 10,014 1.000 488
Zone Loads 11,156 1.802 185,267 18.500 9,037
Sensible Reserve 5,003 0.500 244
Zone Condition 11,156 74.295 200,284 77.000 9,769
Return Air Duct 1,953 0.250
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000 0 0.000
Vent Air 2,147 CFM 4,602 0.744 90,235 8.956
Blow-Thru Fan 0 0.000
Entering Coil Condition 15,759 75.039 292,473 86.206 9,769

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.932 x 1.10 x 9,769 x( 86.2 - 57.0 )= 292,474 Btuh


TLH = 0.932 x 0.68 x 9,769 x( 75.0 - 72.5 )= 15,759 Btuh
----------
SUM = 308,233 Btuh
GTH = 0.932 x 4.50 x 9,769 x( 32.5 - 24.9 )= 309,038 Btuh
Total System Load = 307,942 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 309,038 / ( 0.00 x 500 ) = 0.0 GPM
Heating GPM = 127,313 / ( 0.00 x 500 ) = 0.0 GPM
Steam Req. = 127,313 / 970 = 131.3 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 86.21 Dry bulb temperature: 57.01
Wet bulb temperature: 66.89
Relative humidity: 37.44
Enthalpy: 32.48 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 57.00 Dry bulb temperature: 90.00
Wet bulb temperature: 56.55
Relative humidity: 97.45
Enthalpy: 24.93 Btu/lbm

D:\ ...\SUBSTATION SHAQRA-13.8kv SWGR.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Control Bldg, SHAQRA #8521


HVAC Load Analysis
for

NGSA(Central Region)
(Saudi Electricity Company)
Riyadh,ksa

Prepared By:

Satech
Al-khobar

Tuesday, August 13, 2013


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr Control Bldg, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 2

Air Handler Input


Air Handler Number 3 Input Data
Name: Pacu-03A & 03B
Terminal type: Constant Volume
Method for CV Sum of Peaks
Supply fan type: Package fan
Calculations performed: Both heating and cooling loads
Excess supply air: Reserve
Occurrences: 1
People profile number: 1
Lighting profile number: 2
Equipment profile number: 3
Exhaust may not exceed supply air: Yes
Leaving heating coil temp (deg.F): 90.0
Leaving cooling coil temp (deg.F): 57.0
Cooling coil CFM 0
Misc. Btuh gain - supply side: 0
Misc. Btuh gain - return side: 0
Combined fan & motor efficiency: 85
Static pressure across fan (in.wg.): 0.50
Summer supply duct temp rise (deg.F): 1.000
Summer return duct temp rise (deg.F): 0.250
Winter supply duct temp drop (deg.F): 2.000
Winter return duct temp drop (deg.F): 1.000
Chilled water temp difference (deg.F): 0.000
Hot water temp difference (deg.F): 0.000
Cooling ventilation: 0 Direct
Cooling infiltration: 0 AC/Hr
Heating ventilation: 0 Direct
Heating infiltration: 0 Direct
Pretreated outside air: none
Pretreated air Summer DB (deg.F): 0
Pretreated air Summer WB (deg.F): 0
Pretreated air Winter DB (deg.F): 0

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
August 124 76 50% 77 -6.23 10
Winter 41 77

D:\ ...\SUBSTATION SHAQRA-control room.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr Control Bldg, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 3

Zone Input
Zone 1: CONTROL ROOM (2171.27 sq.ft) (Group 3)
Air Handler number: 3 Zone occurrences: 1
Zone length: (feet) 98.07 Zone width (feet): 22.14
Lighting Watts: 3,257 Equipment Watts: 15,938
Number of people in zone: 2 People profile number: 1
Lighting profile number: 2 Equipment profile number: 3
Ceiling height (feet): 17.56 Heating safety factor (%): 0
Sensible safety factor (%): 5 Latent safety factor (%): 5
Sensible heat per person (Btuh): 375 Latent heat per person (Btuh): 625
Cooling ventilation method: Direct Cooling ventilation value: 415.000
Cooling infiltration method: AC/Hr Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 415.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 2,171 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 8 0.060 No 98.07 22.14 2,171.3 Yes

Part Type U-Factor Cool TD Heat TD Height Width Area


4 1 0.463 10.000 15.000 17.56 16.40 288.0

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 A 0.100 D 17.56 56.48 991.8 SE
2 2 G 0.282 D 10.00 7.22 72.2 SW
3 1 A 0.100 D 17.56 23.05 404.8 SW

Zone 2: TELECOM ROOM (551.9502 sq.ft) (Group 3)


Air Handler number: 3 Zone occurrences: 1
Zone length: (feet) 24.93 Zone width (feet): 22.14
Lighting Watts: 828 Equipment Watts: 8,000
Number of people in zone: 2 People profile number: 1
Lighting profile number: 2 Equipment profile number: 3
Ceiling height (feet): 17.56 Heating safety factor (%): 0
Sensible safety factor (%): 5 Latent safety factor (%): 5
Sensible heat per person (Btuh): 375 Latent heat per person (Btuh): 625
Cooling ventilation method: Direct Cooling ventilation value: 200.000
Cooling infiltration method: AC/Hr Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 200.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 552 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 8 0.060 No 24.93 22.14 552.0 Yes

Part Type U-Factor Cool TD Heat TD Height Width Area


3 1 0.463 10.000 15.000 17.56 24.93 437.8

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 A 0.100 D 17.56 23.05 404.8 NE
2 2 G 0.282 D 10.00 7.22 72.2 NE
4 1 A 0.100 D 17.56 26.24 460.8 SE

D:\ ...\SUBSTATION SHAQRA-control room.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr Control Bldg, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 4

Building Summary Loads


Building peaks in August at 5pm.
Bldg Load Area Sen %Tot Lat Sen Net %Net
Descriptions Quan Loss Loss Gain Gain Gain Gain
Roof 2,723 5,882 12.15 0 4,599 4,599 2.93
Wall 2,406 9,609 19.85 0 9,293 9,293 5.92
Glass 0 0 0.00 0 0 0 0.00
Floor Slab 0 0 0.00 0 0 0 0.00
Skin Loads 15,492 32.00 0 13,892 13,892 8.85
Lighting 4,085 0 0.00 0 14,636 14,636 9.33
Equipment 23,938 0 0.00 0 85,764 85,764 54.66
Pool Latent 0 0 0.00 0 0 0 0.00
People 4 0 0.00 2,625 1,575 4,200 2.68
Partition 726 5,040 10.41 0 3,528 3,528 2.25
Cool. Pret. 0 0 0.00 0 0 0 0.00
Heat. Pret. 0 0 0.00 0 0 0 0.00
Cool. Vent. 615 0 0.00 1,318 25,848 27,166 17.31
Heat. Vent. 615 22,283 46.03 0 0 0 0.00
Cool. Infil. 0 0 0.00 0 0 0 0.00
Heat. Infil. 0 0 0.00 0 0 0 0.00
Draw-Thru Fan 0 0 0.00 0 0 0 0.00
Blow-Thru Fan 0 0 0.00 0 0 0 0.00
Reserve Cap. 0 0 0.00 0 0 0 0.00
Reheat Cap. 0 0 0.00 0 0 0 0.00
Supply Duct 0 3,733 7.71 0 6,307 6,307 4.02
Return Duct 0 1,867 3.86 0 1,419 1,419 0.90
Misc. Supply 0 0 0.00 0 0 0 0.00
Misc. Return 0 0 0.00 0 0 0 0.00
Building Totals 48,414 100.00 3,943 152,968 156,912 100.00

Building Sen %Tot Lat Sen Net %Net


Summary Loss Loss Gain Gain Gain Gain
Ventilation 22,283 46.03 1,318 25,848 27,166 17.31
Infiltration 0 0.00 0 0 0 0.00
Pretreated Air 0 0.00 0 0 0 0.00
Zone Loads 20,532 42.41 2,625 119,395 122,020 77.76
Plenum Loads 0 0.00 0 0 0 0.00
Fan/Duct/Misc Loads 5,600 11.57 0 7,726 7,726 4.92
Building Totals 48,414 100.00 3,943 152,968 156,912 100.00

Check Figures
Total Building Supply Air (based on a 20 TD): 6,153 CFM
Total Building Vent. Air (10.00% of Supply): 615 CFM
Total Conditioned Air Space: 2,723 Sq.ft
Supply Air Per Unit Area: 2.2593 CFM/Sq.ft
Area Per Cooling Capacity: 208.3 Sq.ft/Ton
Cooling Capacity Per Area: 0.0048 Tons/Sq.ft
Heating Capacity Per Area: 17.78 Btuh/Sq.ft
Total Heating Required With Outside Air: 48,414 Btuh
Total Cooling Required With Outside Air: 13.08 Tons

D:\ ...\SUBSTATION SHAQRA-control room.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr Control Bldg, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 5

Air Handler #3 - Pacu-03A & 03B - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
1 CONTROL ROOM 2,171 12,451 80,836 1,313 Direct Direct
8pm August 2 1,125 4,150 0 415 415
38,128 0.52 1.91 0 373 415

2 TELECOM ROOM 552 8,081 38,993 1,313 Direct Direct


8pm August 2 730 2,002 0 200 200
9,692 1.32 3.63 0 242 200
Zone Peak Totals: 2,723 20,532 119,830 2,625
Total Zones: 2 4 1,855 6,152 0 615 615
Unique Zones: 2 47,820 0.68 2.26 0 615 615
Main trunk duct size: 32 in. h x 32in. w, Velocity: 865.2 ft/min, Pressure drop: 0.027 in.wg./100ft

D:\ ...\SUBSTATION SHAQRA-control room.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr Control Bldg, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 6

Air Handler #3 - Pacu-03A & 03B - Total Load Summary


Air Handler Description: Pacu-03A & 03B Constant Volume - Sum of Peaks
Sensible Heat Ratio: 0.98 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in August.
Outdoor Conditions: Clg: 118 DB, 76 WB, 77.72 grains, Htg: 41 DB
Indoor Conditions: Clg: 77 DB, 50% RH, Htg: 77 DB
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 20,532 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 22,283 Btuh 615 CFM
Supply Duct sensible loss: 3,733 Btuh
Return Duct sensible loss: 1,867 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 48,414 Btuh
Heating Supply Air: 24,265 / (.932 X 1.08 X 13) = 1,855 CFM
Winter Vent Outside Air (33.2% of supply) = 615 CFM
Zone space sensible gain: 119,395 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 6,307 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 125,702 Btuh
Cooling Supply Air: 126,137 / (.932 X 1.1 X 20) = 6,153 CFM
Summer Vent Outside Air (10.0% of supply) = 615 CFM
Return duct sensible gain: 1,419 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 25,848 Btuh 615 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 27,267 Btuh
Total sensible gain on air handling system: 152,968 Btuh
Zone space latent gain: 2,625 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 1,318 Btuh
Total latent gain on air handling system: 3,943 Btuh
Total system sensible and latent gain: 156,912 Btuh

Check Figures
Total Air Handler Supply Air (based on a 20 TD): 6,153 CFM
Total Air Handler Vent. Air (10.00% of Supply): 615 CFM
Total Conditioned Air Space: 2,723 Sq.ft
Supply Air Per Unit Area: 2.2593 CFM/Sq.ft
Area Per Cooling Capacity: 208.3 Sq.ft/Ton
Cooling Capacity Per Area: 0.0048 Tons/Sq.ft
Heating Capacity Per Area: 17.78 Btuh/Sq.ft
Total Heating Required With Outside Air: 48,414 Btuh
Total Cooling Required With Outside Air: 13.08 Tons

D:\ ...\SUBSTATION SHAQRA-control room.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr Control Bldg, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 7

Air Handler #3 - Pacu-03A & 03B - Summary Loads for Groups (G)
Gr Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Group Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
3 Group 3 2,723 20,532 119,830 2,625 n/a n/a
8pm August 4 1,855 6,152 0 615 615
47,820 0.68 2.26 0 615 615
Group Peak Totals: 2,723 20,532 119,830 2,625
Total Groups: 1 4 1,855 6,152 0 615 615
47,820 0.68 2.26 0 615 615
Main trunk duct size: 32 in. h x 32in. w, Velocity: 865.2 ft/min, Pressure drop: 0.027 in.wg./100ft

D:\ ...\SUBSTATION SHAQRA-control room.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr Control Bldg, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 8

Air Handler #3 - Pacu-03A & 03B - Summary Loads for Zones (G)
Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Group Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
1 CONTROL ROOM 2,171 12,451 80,836 1,313 Direct Direct
8pm August 2 1,125 4,150 0 415 415
38,128 0.52 1.91 0 373 415

2 TELECOM ROOM 552 8,081 38,993 1,313 Direct Direct


8pm August 2 730 2,002 0 200 200
9,692 1.32 3.63 0 242 200
Zone Peak Totals: 2,723 20,532 119,830 2,625
Total Zones: 2 4 1,855 6,152 0 615 615
47,820 0.68 2.26 0 615 615
Main trunk duct size: 32 in. h x 32in. w, Velocity: 865.2 ft/min, Pressure drop: 0.027 in.wg./100ft

D:\ ...\SUBSTATION SHAQRA-control room.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr Control Bldg, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 9

Air Handler #3 - Pacu-03A & 03B - Total Load Summary (G)


Air Handler Description: Pacu-03A & 03B Constant Volume - Sum of Peaks
Sensible Heat Ratio: 0.98 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in August.
Outdoor Conditions: Clg: 118 DB, 76 WB, 77.72 grains, Htg: 41 DB
Indoor Conditions: Clg: 77 DB, 50% RH, Htg: 77 DB
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 20,532 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 22,283 Btuh 615 CFM
Supply Duct sensible loss: 3,733 Btuh
Return Duct sensible loss: 1,867 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 48,414 Btuh
Heating Supply Air: 24,265 / (.932 X 1.08 X 13) = 1,855 CFM
Winter Vent Outside Air (33.2% of supply) = 615 CFM
Zone space sensible gain: 119,395 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 6,307 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 125,702 Btuh
Cooling Supply Air: 126,137 / (.932 X 1.1 X 20) = 6,153 CFM
Summer Vent Outside Air (10.0% of supply) = 615 CFM
Return duct sensible gain: 1,419 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 25,848 Btuh 615 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 27,267 Btuh
Total sensible gain on air handling system: 152,968 Btuh
Zone space latent gain: 2,625 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 1,318 Btuh
Total latent gain on air handling system: 3,943 Btuh
Total system sensible and latent gain: 156,912 Btuh

Check Figures
Total Air Handler Supply Air (based on a 20 TD): 6,153 CFM
Total Air Handler Vent. Air (10.00% of Supply): 615 CFM
Total Conditioned Air Space: 2,723 Sq.ft
Supply Air Per Unit Area: 2.2593 CFM/Sq.ft
Area Per Cooling Capacity: 208.3 Sq.ft/Ton
Cooling Capacity Per Area: 0.0048 Tons/Sq.ft
Heating Capacity Per Area: 17.78 Btuh/Sq.ft
Total Heating Required With Outside Air: 48,414 Btuh
Total Cooling Required With Outside Air: 13.08 Tons

D:\ ...\SUBSTATION SHAQRA-control room.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr Control Bldg, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 10

Group Detailed Loads (At Group Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 1-CONTROL ROOM - Air Handler 3 (Pacu-03A & 03B), Group 3 peaks (sensible) in
August at 8pm.
Roof-1-8-Susp.C-L 2,171 0.50 32.3 0.060 4,209 2.160 4,690
Wall-1-SE-A-D 992 1 33.0 0.100 3,272 3.600 3,570
Wall-2-SW-G-D 72 1 33.0 0.282 672 10.152 733
Wall-3-SW-A-D 405 1 31.0 0.100 1,255 3.600 1,457
Partition-4-1 287.984 10/15 0.463 1,333 6.945 2,000
Lights-Prof=2 3,257 1.000 11,113
Equipment-Prof=3 15,938 1.000 54,383 0
People-Prof=1 2.0 1.000 750 1,250
Sub-total 76,987 1,250 12,451
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 80,836 1,313 12,451

Zone 2-TELECOM ROOM - Air Handler 3 (Pacu-03A & 03B), Group 3 peaks (sensible) in
August at 8pm.
Roof-1-8-Susp.C-L 552 0.50 32.3 0.060 1,070 2.160 1,192
Wall-1-NE-A-D 405 1 28.7 0.100 1,163 3.600 1,457
Wall-2-NE-G-D 72 1 23.7 0.282 483 10.152 733
Wall-4-SE-A-D 461 1 33.0 0.100 1,520 3.600 1,659
Partition-3-1 437.7708 10/15 0.463 2,027 6.945 3,040
Lights-Prof=2 828 1.000 2,825
Equipment-Prof=3 8,000 1.000 27,297 0
People-Prof=1 2.0 1.000 750 1,250
Sub-total 37,136 1,250 8,081
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 38,993 1,313 8,081

D:\ ...\SUBSTATION SHAQRA-control room.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr Control Bldg, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 11

Zone Detailed Loads (At Zone Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 1-CONTROL ROOM peaks (sensible) in August at 8pm, Air Handler 3 (Pacu-03A & 03B),
Group 3, 98.1 x 22.1, Construction Type: 10 (Medium)
Roof-1-8-Susp.C-L 2,171 0.50 32.3 0.060 4,209 2.160 4,690
Wall-1-SE-A-D 992 1 33.0 0.100 3,272 3.600 3,570
Wall-2-SW-G-D 72 1 33.0 0.282 672 10.152 733
Wall-3-SW-A-D 405 1 31.0 0.100 1,255 3.600 1,457
Partition-4-1 287.984 10/15 0.463 1,333 6.945 2,000
Lights-Prof=2 3,257 1.000 11,113
Equipment-Prof=3 15,938 1.000 54,383 0
People-Prof=1 2.0 1.000 750 1,250
Sub-total 76,987 1,250 12,451
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 80,836 1,313 12,451

Zone 2-TELECOM ROOM peaks (sensible) in August at 8pm, Air Handler 3 (Pacu-03A & 03B),
Group 3, 24.9 x 22.1, Construction Type: 10 (Medium)
Roof-1-8-Susp.C-L 552 0.50 32.3 0.060 1,070 2.160 1,192
Wall-1-NE-A-D 405 1 28.7 0.100 1,163 3.600 1,457
Wall-2-NE-G-D 72 1 23.7 0.282 483 10.152 733
Wall-4-SE-A-D 461 1 33.0 0.100 1,520 3.600 1,659
Partition-3-1 437.7708 10/15 0.463 2,027 6.945 3,040
Lights-Prof=2 828 1.000 2,825
Equipment-Prof=3 8,000 1.000 27,297 0
People-Prof=1 2.0 1.000 750 1,250
Sub-total 37,136 1,250 8,081
Safety factors: +5% +5% +0%
--------- --------- ---------
Total w/ safety factors: 38,993 1,313 8,081

D:\ ...\SUBSTATION SHAQRA-control room.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Saudi Technologists Cons Engr Control Bldg, SHAQRA #8521
Al-Khobar, Saudi Arabia, 31952 Page 12

Air System #3 (Pacu-03A & 03B) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 73.587 57.000
Draw-Thru Fan 0 0.000 0
Misc Load on Supply Side 0 0.000 0 0.000 0
Supply Air Duct 6,307 1.000 308
Zone Loads 2,625 0.673 119,830 19.000 5,845
Sensible Reserve 0 0.000 0
Zone Condition 2,625 74.260 126,137 77.000 6,153
Return Air Duct 1,419 0.250
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000 0 0.000
Vent Air 615 CFM 1,318 0.342 25,848 4.073
Blow-Thru Fan 0 0.000
Entering Coil Condition 3,943 74.602 153,403 81.323 6,153

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.932 x 1.10 x 6,153 x( 81.3 - 57.0 )= 153,404 Btuh


TLH = 0.932 x 0.68 x 6,153 x( 74.6 - 73.6 )= 3,957 Btuh
----------
SUM = 157,361 Btuh
GTH = 0.932 x 4.50 x 6,153 x( 31.2 - 25.1 )= 157,649 Btuh
Total System Load = 156,912 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 157,649 / ( 0.00 x 500 ) = 0.0 GPM
Heating GPM = 48,414 / ( 0.00 x 500 ) = 0.0 GPM
Steam Req. = 48,414 / 970 = 49.9 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 81.32 Dry bulb temperature: 64.39
Wet bulb temperature: 65.31
Relative humidity: 43.56
Enthalpy: 31.21 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 57.00 Dry bulb temperature: 90.00
Wet bulb temperature: 56.81
Relative humidity: 98.90
Enthalpy: 25.10 Btu/lbm

D:\ ...\SUBSTATION SHAQRA-control room.CH8 Tuesday, August 13, 2013, 01:27 PM


http://boilersinfo.com/

Al Shaqra 132/13.8kv Ss#8521


HVAC Duct Sizing
for

132kv G.i.s Building


Saudi Electricity Company
Riyadh,ksa

Prepared By:

William
Satech
Al-khobar

Tuesday, August 13, 2013


http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 2

General Project Data Input


General Project Information
Project file name: C:\Elite\Ductw\132kv gis duct sizing.dsw
Project title: Al Shaqra 132/13.8kv Ss#8521
Designed by: Siddique
Project date: Saturday, August 04, 2012
Client name: 132kv G.i.s Building
Client address: Saudi Electricity Company
Client city: Riyadh,ksa
Company name: Satech
Company representative: William
Company address: Al-khobar

D:\ ...\132kv gis duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 3

System 1 "PACU 01 & 02" - Input Data - Supply


Project & Default Data Trunks Runouts
Maximum desired velocity (FPM): 1,650 500
Material Reference: Galv Rect Galv Rect
Height constraint (in): 0 0
Width constraint (in): 0 0
Diameter constraint (in): 0 0
R-Value of insulation (Sq.ft.F/Btuh): 4.00 2.00
Duct shape: Round Rect.
Sizing method: EF EF
NC criteria: N/A 30

Duct System Data


Maximum system velocity (FPM): 1,650
Minimum system velocity (FPM): 500
Minimum trunk diameter (in): 0.0
Orifice opening interval (in): 1.000
Temperature of air leaving coil (F): 55
Design room temperature (F): 77
Temperature of duct installation space (F): 80
Altitude (ft): 2,000
Density (lb/cu.ft): 0.072
Friction loss per 100 ft. (in.wg): 0.080
Est. st. press. loss of central equip. (in.wg): 0.000
Maximum % supply air increase: 0
Allow increasing downstream diameters: No
Show diversified trunk flows: No
Duct diameter interval (in): 0.0
Whole number dimensions: Yes

Fan Data
Fan description: CENT-BACKWARD 36 in and
over
Fan static pressure (in.wg): 0.000
Fan CFM: 12,076
Fan efficiency: 85
Fan RPM: 0
Number of blades: 0
Fan blast width (in): 44
Fan blast height (in): 24
Length to first fitting (ft): 1.0

D:\ ...\132kv gis duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 4

System 1 "PACU 01 & 02" - Input Data - Return


Project & Default Data Trunks Runouts
Maximum desired velocity (FPM): 1,650 500
Material Reference: Galv Rect Galv Rect
Height constraint (in): 0 0
Width constraint (in): 0 0
Diameter constraint (in): 0 0
R-Value of insulation (Sq.ft.F/Btuh): 4.00 2.00
Duct shape: Round Rect.
Sizing method: EF EF
NC criteria: N/A 30

Duct System Data


Maximum system velocity (FPM): 1,650
Minimum system velocity (FPM): 500
Minimum trunk diameter (in): 0.0
Orifice opening interval (in): 1.000
Temperature of air leaving coil (F): 55
Design room temperature (F): 77
Temperature of duct installation space (F): 80
Altitude (ft): 2,000
Density (lb/cu.ft): 0.072
Friction loss per 100 ft. (in.wg): 0.080
Est. st. press. loss of central equip. (in.wg): 0.000
Maximum % supply air increase: 0
Allow increasing downstream diameters: No
Show diversified trunk flows: No
Duct diameter interval (in): 0.0
Whole number dimensions: Yes

Fan Data
Fan description: CENT-BACKWARD 36 in and
over
Fan static pressure (in.wg): 0.000
Fan CFM: 12,076
Fan efficiency: 85
Fan RPM: 0
Number of blades: 0
Fan blast width (in): 78
Fan blast height (in): 65
Length to first fitting (ft): 1.0

D:\ ...\132kv gis duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 5

System 1 "PACU 01 & 02" - Trunk Input Data - Supply


Trunk Dia Length Fit 1 #Fit Shape Active Material Ref.
Ups. Hei Max.Vel Fit 2 #Fit Add.Loss Take Off Roughness
SM Wid Junc fit #Fit R-Value Per.Div
ST1-1 0.0 50.00 CR3-1 4 Rect. Yes Galv Rect
FAN 0.0 1,650 CR9-5 1 0.00 0 0.00050
EF 0.0 SR5-12 1 4.00 0
Fit 3 CR9-4 2

ST1-2 0.0 8.85 SD4-2 1 Round Yes Galv Round


ST1-1 0.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SD5-10 1 4.00 0

ST1-3 0.0 10.65 ---- Round Yes Galv Round


ST1-2 0.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SD5-10 1 4.00 0

ST1-4 0.0 10.65 ---- Round Yes Galv Round


ST1-3 0.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SD5-10 1 4.00 0

ST1-5 0.0 10.65 ---- 1 Round Yes Galv Round


ST1-4 0.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SD5-10 1 4.00 0

ST1-6 0.0 10.65 ---- Round Yes Galv Round


ST1-5 0.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SD5-10 1 4.00 0

ST1-7 0.0 10.65 ---- Round Yes Galv Rect


ST1-6 0.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SD5-10 1 4.00 0

ST1-8 0.0 10.65 ---- Round Yes Galv Rect


ST1-7 0.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SD5-10 1 4.00 0

ST1-9 0.0 10.65 ---- Round Yes Galv Rect


ST1-8 0.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SD5-10 1 4.00 0

ST1-10 0.0 10.65 ---- Round Yes Galv Rect


ST1-9 0.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SD5-10 1 4.00 0

ST1-11 0.0 11.00 ---- Round Yes Galv Rect


ST1-10 0.0 1,650 ---- 0.00 0 0.00050
EF 0.0 1 4.00 0

ST1-12 0.0 37.00 CR3-1 1 Rect. Yes Galv Rect


ST1-1 0.0 1,650 CR9-4 1 0.00 90 0.00050
EF 0.0 SR5-5 1 4.00 0
Fit 3 CR9-5 1

ST1-13 0.0 16.73 ---- Rect. Yes Galv Rect


ST1-12 0.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SR5-5 1 4.00 0

ST1-14 0.0 16.73 ---- Rect. Yes Galv Rect


ST1-13 0.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SR5-5 1 4.00 0

ST1-15 0.0 16.73 ---- Rect. Yes Galv Rect


ST1-14 0.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SR5-5 1 4.00 0

D:\ ...\132kv gis duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 6

System 1 "PACU 01 & 02" - Trunk Input Data - Supply (cont'd)


Trunk Dia Length Fit 1 #Fit Shape Active Material Ref.
Ups. Hei Max.Vel Fit 2 #Fit Add.Loss Take Off Roughness
SM Wid Junc fit #Fit R-Value Per.Div
ST1-16 0.0 16.73 ---- Rect. Yes Galv Rect
ST1-15 0.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SR5-5 1 4.00 0

D:\ ...\132kv gis duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 7

System 1 "PACU 01 & 02" - Trunk Input Data - Return


Trunk Dia Length Fit 1 #Fit Shape Active Material Ref.
Ups. Hei Max.Vel Fit 2 #Fit Add.Loss Take Off Roughness
SM Wid Junc fit #Fit R-Value Per.Div
RT1-3 0.0 25.60 CR9-4 1 Rect. Yes Galv Rect
FAN 0.0 1,650 CR3-1 2 0.00 0 0.00050
EF 0.0 ER5-4 1 4.00 0
Fit 3 CR9-5 1

RT1-2 0.0 36.11 CR3-1 2 Rect. Yes Galv Rect


RT1-3 0.0 1,650 CR9-4 2 0.00 90 0.00050
EF 0.0 ER5-3 1 4.00 0

RT1-1 0.0 25.15 CR3-1 2 Rect. Yes Galv Rect


RT1-2 0.0 1,650 CR9-4 1 0.00 90 0.00050
EF 0.0 1 4.00 0
Fit 3 CR9-5 1

D:\ ...\132kv gis duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 8

System 1 "PACU 01 & 02" - Runout Input Data - Supply


Runout Dia Length Fit 1 #Fit Shape Active Material Ref.
Ups. Hei Max.Vel Fit 2 #Fit Add.Loss Take Off Roughness
SM Wid Fit 3 #Fit R-Value NC Level Dif.Loss
SAG1-1 0.0 2.00 SR4-3 1 Rect. Yes Galv Rect
ST1-2 0.0 500 CR9-4 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SAG1-2 0.0 2.00 SR4-3 1 Rect. Yes Galv Rect


ST1-3 0.0 500 CR9-4 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SAG1-3 0.0 2.00 SR4-3 1 Rect. Yes Galv Rect


ST1-4 0.0 500 CR9-4 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SAG1-4 0.0 2.00 SR4-3 1 Rect. Yes Galv Rect


ST1-5 0.0 500 CR9-4 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SAG1-5 0.0 2.00 SR4-3 1 Rect. Yes Galv Rect


ST1-6 0.0 500 CR9-4 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SAG1-6 0.0 2.00 SR4-3 1 Rect. Yes Galv Rect


ST1-7 0.0 500 CR9-4 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SAG1-7 0.0 2.00 SR4-3 1 Rect. Yes Galv Rect


ST1-8 0.0 500 CR9-4 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SAG1-8 0.0 2.00 SR4-3 1 Rect. Yes Galv Rect


ST1-9 0.0 500 CR9-4 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SAG1-9 0.0 2.00 SR4-3 1 Rect. Yes Galv Rect


ST1-10 0.0 500 CR9-4 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SAG1-10 0.0 2.00 SR4-3 1 Rect. Yes Galv Rect


ST1-11 0.0 500 CR9-4 1 0.00 0 0.00050
EF 0.0 ---- 2.00 30 0.080

SAG1-11 0.0 2.00 ---- Rect. Yes Galv Rect


ST1-12 0.0 500 CR9-4 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SAG1-12 0.0 2.00 ---- Rect. Yes Galv Rect


ST1-13 0.0 500 CR9-4 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SAG1-13 0.0 2.00 ---- Rect. Yes Galv Rect


ST1-14 0.0 500 CR9-4 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SAG1-14 0.0 2.00 ---- Rect. Yes Galv Rect


ST1-15 0.0 500 CR9-4 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SAG1-15 0.0 2.00 ---- Rect. Yes Galv Rect


ST1-16 0.0 500 CR9-4 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SAG1-16 0.0 2.00 SR4-3 1 Rect. Yes Galv Rect

D:\ ...\132kv gis duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 9

System 1 "PACU 01 & 02" - Runout Input Data - Supply (cont'd)


Runout Dia Length Fit 1 #Fit Shape Active Material Ref.
Ups. Hei Max.Vel Fit 2 #Fit Add.Loss Take Off Roughness
SM Wid Fit 3 #Fit R-Value NC Level Dif.Loss
ST1-16 0.0 500 CR9-4 1 0.00 0 0.00050
EF 0.0 ---- 2.00 30 0.080

D:\ ...\132kv gis duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 10

System 1 "PACU 01 & 02" - Runout Input Data - Return


Runout Dia Length Fit 1 #Fit Shape Active Material Ref.
Ups. Hei Max.Vel Fit 2 #Fit Add.Loss Take Off Roughness
SM Wid Fit 3 #Fit R-Value NC Level Grille.Loss
RAG1-1 0.0 2.00 CR9-4 1 Rect. Yes Galv Rect
RT1-2 0.0 600 ---- 0.00 0 0.00050
EF 0.0 ---- 2.00 30 0.080

RAG1-2 0.0 2.00 CR3-1 1 Rect. Yes Galv Rect


RT1-1 0.0 600 CR9-4 1 0.00 0 0.00050
EF 0.0 ---- 2.00 30 0.080

FAD-1 0.0 27.35 CR9-4 2 Rect. Yes Galv Rect


RT1-3 0.0 500 ---- 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

D:\ ...\132kv gis duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 11

System 1 "PACU 01 & 02" - Trunk Output Data - Supply


Fit Sect1 Sect2 Cumul Press
------ ------ ------ ------ ------
Trunk Dia SM L/100 Shape Ups.Sh Equip Dynam Vel.P Veloc
Upstr Hei TOA Reg Fit.1 Qty Coef Loss Add.L Fric Stat Stat
Vel Wid Gau Fit.2 Qty Coef Loss F.Tot Total Total Total
CFM Len Ref Mat Ups.Junc Coef Loss Dynam
ST1-1 40.4 EF 0.060 Rect N/A 0.000 1.890 0.000 0.137
FAN 36.0 0 0.000 *CR3-1 4 1.203 0.145 0.000 0.030 1.920 0.325
1,512 38.0 20 CR9-5 1 0.460 0.055 1.890 1.920 1.920 0.462
13,460 50.0 Galv Rect 1.890
Fit.3: CR9-4 2 0.520 0.063

ST1-2 35.0 EF 0.080 Rnd Rect 0.000 0.006 -0.013 0.150


ST1-1 32.0 0 -0.020 SD4-2 1 0.041 0.006 0.000 0.007 1.947 0.299
1,585 32.0 20 ---- 0.006 0.013 1.934 0.449
10,588 8.9 Galv Round *SR5-12-MN 0.006

ST1-3 34.0 EF 0.075 Rnd Rnd 0.000 0.018 0.000 0.137


ST1-2 31.1 0 -0.004 ---- 0.000 0.008 1.959 0.287
1,511 31.1 20 ---- 0.018 0.026 1.959 0.423
9,529 10.7 Galv Round *SD5-10-MN 0.130 0.018 0.018

ST1-4 32.0 EF 0.080 Rnd Rnd 0.000 0.018 -0.001 0.138


ST1-3 29.3 0 -0.019 ---- 0.000 0.009 1.987 0.259
1,517 29.2 20 ---- 0.018 0.027 1.986 0.397
8,470 10.7 Galv Round SD5-10-MN 0.132 0.018 0.018

ST1-5 30.0 EF 0.085 Rnd Rnd 0.000 0.018 0.000 0.137


ST1-4 27.4 0 -0.017 ---- 1 0.000 0.009 2.013 0.233
1,510 27.4 22 ---- 0.018 0.027 2.014 0.369
7,411 10.7 Galv Round SD5-10-MN 0.134 0.018 0.018

ST1-6 28.0 EF 0.090 Rnd Rnd 0.000 0.018 0.005 0.132


ST1-5 25.6 0 -0.013 ---- 0.000 0.010 2.036 0.209
1,486 25.7 22 ---- 0.018 0.028 2.041 0.342
6,352 10.7 Galv Round SD5-10-MN 0.135 0.018 0.018

ST1-7 27.3 EF 0.075 Rnd Rnd 0.000 0.014 0.035 0.102


ST1-6 24.0 0 0.017 ---- 0.000 0.008 2.027 0.218
1,302 26.0 22 ---- 0.014 0.022 2.063 0.320
5,293 10.7 Galv Rect *SD5-10-MN 0.137 0.014 0.014

ST1-8 25.1 EF 0.075 Rnd Rnd 0.000 0.012 0.046 0.091


ST1-7 22.0 0 -0.002 ---- 0.000 0.008 2.037 0.209
1,232 24.0 22 ---- 0.012 0.020 2.083 0.300
4,234 10.7 Galv Rect SD5-10-MN 0.135 0.012 0.012

ST1-9 21.9 EF 0.085 Rnd Rnd 0.000 0.012 0.049 0.088


ST1-8 20.0 0 -0.009 ---- 0.000 0.009 2.055 0.191
1,214 20.0 22 ---- 0.012 0.021 2.103 0.279
3,175 10.7 Galv Rect SD5-10-MN 0.134 0.012 0.012

ST1-10 18.5 EF 0.090 Rnd Rnd 0.000 0.010 0.060 0.077


ST1-9 16.0 0 0.001 ---- 0.000 0.010 2.063 0.182
1,134 18.0 24 ---- 0.010 0.020 2.123 0.259
2,116 10.7 Galv Rect SD5-10-MN 0.133 0.010 0.010

ST1-11 15.3 EF 0.065 Rnd Rnd 0.000 0.006 0.096 0.041


ST1-10 14.0 0 0.029 ---- 0.000 0.007 2.041 0.205
829 14.0 24 ---- 0.006 0.013 2.137 0.246
1,058 11.0 Galv Rect SD5-10-MN 0.157 0.006 0.006

ST1-12 21.9 EF 0.070 Rect Rect 0.000 0.252 0.065 0.072


ST1-1 20.0 90 -0.187 *CR3-1 1 1.180 0.076 0.000 0.026 2.134 0.112

D:\ ...\132kv gis duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 12

System 1 "PACU 01 & 02" - Trunk Output Data - Supply (cont'd)


Fit Sect1 Sect2 Cumul Press
------ ------ ------ ------ ------
Trunk Dia SM L/100 Shape Ups.Sh Equip Dynam Vel.P Veloc
Upstr Hei TOA Reg Fit.1 Qty Coef Loss Add.L Fric Stat Stat
Vel Wid Gau Fit.2 Qty Coef Loss F.Tot Total Total Total
CFM Len Ref Mat Ups.Junc Coef Loss Dynam
1,098 20.0 22 CR9-4 1 0.520 0.033 0.252 0.278 2.198 0.184
2,872 37.0 Galv Rect SR5-12-BR 1.779 0.114 0.252
Fit.3: CR9-5 1 0.460 0.029

ST1-13 19.7 EF 0.085 Rect Rect 0.000 0.002 0.060 0.077


ST1-12 18.0 0 -0.006 ---- 0.000 0.014 2.154 0.092
1,131 18.0 24 ---- 0.002 0.016 2.214 0.169
2,394 16.7 Galv Rect SR5-5-MN 0.025 0.002 0.002

ST1-14 18.5 EF 0.075 Rect Rect 0.000 0.002 0.074 0.063


ST1-13 16.0 0 0.012 ---- 0.000 0.013 2.154 0.091
1,026 18.0 24 ---- 0.002 0.014 2.228 0.155
1,916 16.7 Galv Rect SR5-5-MN 0.030 0.002 0.002

ST1-15 16.4 EF 0.080 Rect Rect 0.000 0.003 0.079 0.057


ST1-14 14.0 0 0.002 ---- 0.000 0.013 2.165 0.080
980 16.0 24 ---- 0.003 0.017 2.245 0.138
1,437 16.7 Galv Rect SR5-5-MN 0.065 0.003 0.003

ST1-16 14.2 EF 0.075 Rect Rect 0.000 0.005 0.091 0.045


ST1-15 12.0 0 0.007 ---- 0.000 0.013 2.171 0.075
871 14.0 24 ---- 0.005 0.018 2.263 0.120
958 16.7 Galv Rect SR5-5-MN 0.123 0.005 0.005

* Loss coefficient for indicated fitting is from the boundary of the table since one or more of the parameters used to
look up the coefficient was outside the range of the table.
Explanation of Values in Rightmost Five Columns Above
Column Description
"Fit": "Loss" = Static pressure loss through the indicated fitting.
"Sect1": "Equip" = User-entered loss through central equipment (supply main trunk only).
"Add.L" = User entered additional static pressure loss.
"F.Tot" = Total of all the fitting static pressure losses. For supply main trunk, also includes loss through
central equipment and any loss carried from return system.
"Dynam" = Total of all the dynamic losses, which includes everything but the frictional loss.
"Sect2": "Dynam" = Total of the dynamic losses, carried from bottom of previous column.
"Fric" = Static pressure loss due to the inside surface roughness (friction).
"Total" = Total of the dynamic and friction losses.
"Cumul": "Vel.P" = Cumulative loss in velocity pressure. For return, velocity pressure of downstream runout with
highest static pressure minus that of this trunk. For supply, main trunk velocity pressure minus that of
this trunk.
"Stat" = Cumulative loss of static pressure. For return, sum of the loss of all ducts in route starting with
downstream runout with highest static pressure through this trunk. For supply, sum of all upstream trunk
losses plus this trunk's loss.
"Total" = Cumulative velocity pressure loss plus cumulative static pressure loss.
"Press": "Veloc" = Velocity pressure.
"Stat" = Static pressure available. For return, at entrance of duct. For supply, at exit.
"Total" = Velocity pressure plus static pressure available.

D:\ ...\132kv gis duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 13

System 1 "PACU 01 & 02" - Trunk Output Data - Return


Fit Sect1 Sect2 Cumul Press
------ ------ ------ ------ ------
Trunk Dia SM L/100 Shape Ups.Sh Equip Dynam Vel.P Veloc
Dnstr Hei TOA Reg Fit.1 Qty Coef Loss Add.L Fric Stat Stat
Vel Wid Gau Fit.2 Qty Coef Loss F.Tot Total Total Total
CFM Len Ref Mat Ups.Junc Coef Loss Dynam
RT1-3 40.4 EF 0.060 Rect N/A 0.000 0.407 -0.064 0.137
FAN 36.0 0 0.000 CR9-4 1 0.520 0.063 0.000 0.016 1.131 -0.709
1,512 38.0 20 *CR3-1 2 1.203 0.145 0.407 0.423 1.068 -0.572
13,459 25.6 Galv Rect 0.407
Fit.3: CR9-5 1 0.460 0.055

RT1-2 37.2 EF 0.075 Rect Rect 0.000 0.500 -0.081 0.154


RT1-3 34.0 90 -0.517 *CR3-1 2 1.180 0.161 0.000 0.027 0.691 -0.165
1,605 34.0 20 CR9-4 2 0.520 0.071 0.500 0.527 0.610 -0.010
12,113 36.1 Galv Rect ER5-4-BR 0.265 0.036 0.500

RT1-1 20.7 EF 0.075 Rect Rect 0.000 0.034 0.000 0.073


RT1-2 18.0 90 0.047 *CR3-1 2 1.224 0.078 0.000 0.019 0.246 -0.193
1,106 20.0 24 CR9-4 1 0.520 0.033 0.034 0.053 0.246 -0.120
2,584 25.2 Galv Rect ER5-3-BR -2.902 -0.186 0.034
Fit.3: CR9-5 1 0.460 0.029

* Loss coefficient for indicated fitting is from the boundary of the table since one or more of the parameters used to
look up the coefficient was outside the range of the table.
Explanation of Values in Rightmost Five Columns Above
Column Description
"Fit": "Loss" = Static pressure loss through the indicated fitting.
"Sect1": "Equip" = User-entered loss through central equipment (supply main trunk only).
"Add.L" = User entered additional static pressure loss.
"F.Tot" = Total of all the fitting static pressure losses. For supply main trunk, also includes loss through
central equipment and any loss carried from return system.
"Dynam" = Total of all the dynamic losses, which includes everything but the frictional loss.
"Sect2": "Dynam" = Total of the dynamic losses, carried from bottom of previous column.
"Fric" = Static pressure loss due to the inside surface roughness (friction).
"Total" = Total of the dynamic and friction losses.
"Cumul": "Vel.P" = Cumulative loss in velocity pressure. For return, velocity pressure of downstream runout with
highest static pressure minus that of this trunk. For supply, main trunk velocity pressure minus that of
this trunk.
"Stat" = Cumulative loss of static pressure. For return, sum of the loss of all ducts in route starting with
downstream runout with highest static pressure through this trunk. For supply, sum of all upstream trunk
losses plus this trunk's loss.
"Total" = Cumulative velocity pressure loss plus cumulative static pressure loss.
"Press": "Veloc" = Velocity pressure.
"Stat" = Static pressure available. For return, at entrance of duct. For supply, at exit.
"Total" = Velocity pressure plus static pressure available.

D:\ ...\132kv gis duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 14

System 1 "PACU 01 & 02" - Runout Output Data - Supply


Fit Sect1 Sect2 Cumul Press
Runout Dia SM L/100 Shape Ups.Sh ------ ------ ------ ------ ------
Conn Hei TOA Reg Fit1 Qty Coef Loss Diff. Dynam Vel.P Veloc
Vel Wid Gau Fit2 Qty Coef Loss Add.L Fric Stat Stat
CFM Len Ref Mat Fit3 Qty Coef Loss F.Tot Total Total Total
Orif R.NC Act.NC Ups.Junc Qty Coef Loss Dynam
SAG1-1 20.7 EF 0.015 Rect Rnd 0.080 0.216 0.125 0.012
ST1-2 18.0 90 -0.078 SR4-3 1 0.067 0.001 0.000 0.000 2.025 0.220
453 20.0 24 CR9-4 1 0.520 0.006 0.136 0.216 2.150 0.233
1,059 2.0 Galv Rect ---- 0.216
13.70 30 35 SD5-10-BR 1 10.555 0.130

SAG1-2 20.7 EF 0.015 Rect Rnd 0.080 0.220 0.125 0.012


ST1-3 18.0 90 -0.095 SR4-3 1 0.066 0.001 0.000 0.000 2.055 0.191
453 20.0 24 CR9-4 1 0.520 0.006 0.140 0.220 2.179 0.203
1,059 2.0 Galv Rect ---- 0.220
13.70 30 30 SD5-10-BR 1 10.858 0.134

SAG1-3 20.7 EF 0.015 Rect Rnd 0.080 0.238 0.125 0.012


ST1-4 18.0 90 -0.113 SR4-3 1 0.062 0.001 0.000 0.000 2.100 0.146
453 20.0 24 CR9-4 1 0.520 0.006 0.158 0.238 2.224 0.158
1,059 2.0 Galv Rect ---- 0.238
14.70 30 30 SD5-10-BR 1 12.336 0.152

SAG1-4 20.7 EF 0.015 Rect Rnd 0.080 0.252 0.125 0.012


ST1-5 18.0 90 -0.128 SR4-3 1 0.060 0.001 0.000 0.000 2.141 0.105
453 20.0 24 CR9-4 1 0.520 0.006 0.172 0.252 2.266 0.117
1,059 2.0 Galv Rect ---- 0.252
15.70 30 30 SD5-10-BR 1 13.457 0.165

SAG1-5 20.7 EF 0.015 Rect Rnd 0.080 0.247 0.125 0.012


ST1-6 18.0 90 -0.127 SR4-3 1 0.051 0.001 0.000 0.000 2.164 0.082
453 20.0 24 CR9-4 1 0.520 0.006 0.167 0.247 2.288 0.095
1,059 2.0 Galv Rect ---- 0.247
16.70 30 30 SD5-10-BR 1 13.067 0.161

SAG1-6 20.7 EF 0.015 Rect Rnd 0.080 0.169 0.125 0.012


ST1-7 18.0 90 -0.080 SR4-3 1 0.046 0.000 0.000 0.000 2.107 0.138
453 20.0 24 CR9-4 1 0.520 0.006 0.089 0.169 2.232 0.151
1,059 2.0 Galv Rect ---- 0.169
14.70 30 30 SD5-10-BR 1 6.745 0.083

SAG1-7 20.7 EF 0.015 Rect Rnd 0.080 0.170 0.125 0.012


ST1-8 18.0 90 -0.092 SR4-3 1 0.045 0.000 0.000 0.000 2.129 0.117
453 20.0 24 CR9-4 1 0.520 0.006 0.090 0.170 2.253 0.129
1,059 2.0 Galv Rect ---- 0.170
15.70 30 30 SD5-10-BR 1 6.842 0.084

SAG1-8 20.7 EF 0.015 Rect Rnd 0.080 0.161 0.125 0.012


ST1-9 18.0 90 -0.085 *SR4-3 1 0.012 0.000 0.000 0.000 2.140 0.106
453 20.0 24 CR9-4 1 0.520 0.006 0.081 0.161 2.264 0.118
1,059 2.0 Galv Rect ---- 0.161
15.70 30 30 SD5-10-BR 1 6.099 0.075

SAG1-9 18.5 EF 0.025 Rect Rnd 0.080 0.134 0.118 0.019


ST1-10 16.0 90 -0.076 *SR4-3 1 0.000 0.001 2.140 0.106
567 18.0 24 CR9-4 1 0.520 0.009 0.054 0.134 2.258 0.125
1,058 2.0 Galv Rect ---- 0.134
15.50 30 30 *SD5-10-BR 1 2.350 0.045

SAG1-10 15.3 EF 0.065 Rect Rnd 0.080 0.099 0.096 0.041


ST1-11 14.0 0 -0.099 *SR4-3 1 0.000 0.001 2.141 0.105
829 14.0 24 CR9-4 1 0.520 0.019 0.019 0.100 2.237 0.146
1,058 2.0 Galv Rect ---- 0.099

D:\ ...\132kv gis duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 15

System 1 "PACU 01 & 02" - Runout Output Data - Supply (cont'd)


Fit Sect1 Sect2 Cumul Press
Runout Dia SM L/100 Shape Ups.Sh ------ ------ ------ ------ ------
Conn Hei TOA Reg Fit1 Qty Coef Loss Diff. Dynam Vel.P Veloc
Vel Wid Gau Fit2 Qty Coef Loss Add.L Fric Stat Stat
CFM Len Ref Mat Fit3 Qty Coef Loss F.Tot Total Total Total
Orif R.NC Act.NC Ups.Junc Qty Coef Loss Dynam
14.30 30 30 1

SAG1-11 14.2 EF 0.020 Rect Rect 0.080 0.176 0.126 0.011


ST1-12 12.0 90 -0.115 ---- 0.000 0.000 2.249 -0.003
435 14.0 24 CR9-4 1 0.520 0.005 0.096 0.176 2.375 0.008
478 2.0 Galv Rect ---- 0.176
14.20 30 30 SR5-5-BR 1 9.037 0.091

SAG1-12 14.2 EF 0.020 Rect Rect 0.080 0.154 0.126 0.011


ST1-13 12.0 90 -0.089 ---- 0.000 0.000 2.243 0.003
435 14.0 24 CR9-4 1 0.520 0.005 0.074 0.154 2.368 0.015
478 2.0 Galv Rect ---- 0.154
14.20 30 30 SR5-5-BR 1 6.823 0.069

SAG1-13 14.2 EF 0.020 Rect Rect 0.080 0.147 0.126 0.011


ST1-14 12.0 90 -0.095 ---- 0.000 0.000 2.250 -0.004
436 14.0 24 CR9-4 1 0.520 0.005 0.067 0.147 2.375 0.007
479 2.0 Galv Rect ---- 0.147
14.20 30 30 SR5-5-BR 1 6.099 0.062

SAG1-14 14.2 EF 0.020 Rect Rect 0.080 0.136 0.126 0.011


ST1-15 12.0 90 -0.090 ---- 0.000 0.000 2.256 -0.010
436 14.0 24 CR9-4 1 0.520 0.005 0.056 0.136 2.381 0.001
479 2.0 Galv Rect ---- 0.136
14.20 30 30 SR5-5-BR 1 5.023 0.051

SAG1-15 14.2 EF 0.020 Rect Rect 0.080 0.110 0.126 0.011


ST1-16 12.0 90 -0.075 ---- 0.000 0.000 2.247 -0.001
436 14.0 24 CR9-4 1 0.520 0.005 0.030 0.110 2.373 0.010
479 2.0 Galv Rect ---- 0.110
14.20 30 30 *SR5-5-BR 1 2.410 0.024

SAG1-16 14.2 EF 0.020 Rect Rect 0.080 0.089 0.126 0.011


ST1-16 12.0 0 -0.055 *SR4-3 1 0.000 0.000 2.227 0.019
436 14.0 24 CR9-4 1 0.520 0.005 0.009 0.090 2.352 0.030
479 2.0 Galv Rect ---- 0.089
13.20 30 30 SR5-5-MN 1 0.400 0.004

* Loss coefficient for indicated fitting is from the boundary of the table since one or more of the parameters used to
look up the coefficient was outside the range of the table.
Explanation of Values in Rightmost Five Columns Above
Column Description
"Fit": "Loss" = Static pressure loss through the indicated fitting.
"Sect1": "Dif" = User-entered static pressure loss due to the diffuser.
"Add.L" = User entered additional static pressure loss.
"F.Tot" = Total of all the fitting static pressure losses.
"Dynam" = Total of all the dynamic losses, which includes everything but the frictional loss.
"Sect2": "Dynam" = Total of the dynamic losses, carried from bottom of previous column.
"Fric" = Static pressure loss due to the inside surface roughness (friction).
"Total" = Total of the dynamic and friction losses.
"Cumul": "Vel.P" = Cumulative loss in velocity pressure. For return, zero for each runout. For supply, velocity
pressure of main trunk minus that of this duct.
"Stat" = Cumulative loss of static pressure. For return, this runout's loss. For supply, sum of all upstream
trunk losses plus this runout's loss.
"Total" = Cumulative velocity pressure loss plus cumulative static pressure loss.

D:\ ...\132kv gis duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 16

System 1 "PACU 01 & 02" - Runout Output Data - Supply (cont'd)


Column Description
"Press": "Veloc" = Velocity pressure.
"Stat" = Static pressure available. For return, at entrance of duct. For supply, at exit.
"Total" = Velocity pressure plus static pressure available.

D:\ ...\132kv gis duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 17

System 1 "PACU 01 & 02" - Runout Output Data - Return


Fit Sect1 Sect2 Cumul Press
Runout Dia SM L/100 Shape Ups.Sh ------ ------ ------ ------ ------
Conn Hei TOA Reg Fit1 Qty Coef Loss Diff. Dynam Vel.P Veloc
Vel Wid Gau Fit2 Qty Coef Loss Add.L Fric Stat Stat
CFM Len Ref Mat Fit3 Qty Coef Loss F.Tot Total Total Total
Orif R.NC Act.NC Ups.Junc Qty Coef Loss Dynam
RAG1-1 37.2 EF 0.050 Rect Rect 0.080 0.160 0.000 0.095
RT1-2 34.0 0 -0.101 CR9-4 1 0.520 0.044 0.000 0.001 0.161 -0.062
1,263 34.0 20 ---- 0.080 0.161 0.161 0.033
9,529 2.0 Galv Rect ---- 0.160
37.20 30 35 ER5-3-MN 1 0.431 0.036

RAG1-2 20.7 EF 0.075 Rect Rect 0.080 0.192 0.000 0.073


RT1-1 18.0 0 -0.192 *CR3-1 1 1.224 0.078 0.000 0.002 0.193 0.000
1,106 20.0 24 CR9-4 1 0.520 0.033 0.112 0.193 0.193 0.073
2,584 2.0 Galv Rect ---- 0.192
20.70 30 30 1

FAD-1 22.9 EF 0.015 Rect Rect 0.080 0.095 0.000 0.013


RT1-3 20.0 90 0.029 CR9-4 2 0.520 0.006 0.000 0.004 0.099 -0.734
471 22.0 22 ---- 0.015 0.099 0.099 -0.721
1,346 27.4 Galv Rect ---- 0.095
11.90 30 40 *ER5-4-BR 1 0.230 0.003

* Loss coefficient for indicated fitting is from the boundary of the table since one or more of the parameters used to
look up the coefficient was outside the range of the table.
Explanation of Values in Rightmost Five Columns Above
Column Description
"Fit": "Loss" = Static pressure loss through the indicated fitting.
"Sect1": "Dif" = User-entered static pressure loss due to the diffuser.
"Add.L" = User entered additional static pressure loss.
"F.Tot" = Total of all the fitting static pressure losses.
"Dynam" = Total of all the dynamic losses, which includes everything but the frictional loss.
"Sect2": "Dynam" = Total of the dynamic losses, carried from bottom of previous column.
"Fric" = Static pressure loss due to the inside surface roughness (friction).
"Total" = Total of the dynamic and friction losses.
"Cumul": "Vel.P" = Cumulative loss in velocity pressure. For return, zero for each runout. For supply, velocity
pressure of main trunk minus that of this duct.
"Stat" = Cumulative loss of static pressure. For return, this runout's loss. For supply, sum of all upstream
trunk losses plus this runout's loss.
"Total" = Cumulative velocity pressure loss plus cumulative static pressure loss.
"Press": "Veloc" = Velocity pressure.
"Stat" = Static pressure available. For return, at entrance of duct. For supply, at exit.
"Total" = Velocity pressure plus static pressure available.

D:\ ...\132kv gis duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 18

System 1 "PACU 01 & 02" - Output Summary - Supply


Number of active trunks: 16
Number of active runouts: 16
Total system weight (lb.) minus fittings: 2,950.87
Total outlet flow 13,460
Total outlet flow after heat gain 13,460
Size of largest trunk: 40.4
Size of smallest trunk: 14.2
Size of largest runout: 20.7
Size of smallest runout: 14.2

Maximum static pressure loss occurs in route to runout: SAG1-14


Cumulative static pressure loss at above runout: 2.256

Isolate Return From Supply Option: No


Return SP Loss Added to 1st Trunk of Supply: 1.131
Available static pressure at above runout: -0.010
Fan static pressure: 2.246
Fan velocity pressure: 0.137
Fan total pressure: 2.383

D:\ ...\132kv gis duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 19

System 1 "PACU 01 & 02" - Output Summary - Return


Number of active trunks: 3
Number of active runouts: 3
Total system weight (lb.) minus fittings: 1,707.08
Total outlet flow 13,459
Total outlet flow after heat gain 13,459
Size of largest trunk: 40.4
Size of smallest trunk: 20.7
Size of largest runout: 37.2
Size of smallest runout: 20.7

Maximum SP loss occurs in route from runout: RAG1-2


Total SP loss of route starting from above runout: 1.131

Isolate Return From Supply Option: No


Return SP Loss Added to 1st Trunk of Supply: 1.131
Available static pressure at above runout: 0.000
Fan static pressure: -1.131
Fan velocity pressure: 0.137
Fan total pressure: -0.994

D:\ ...\132kv gis duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 20

System 1 "PACU 01 & 02" - Pressure Changes Graph

Pressure Changes Through Route with Highest Static Pressure Loss

1.4

1.2
F

1.0

0.8

0.6

0.4
G
Pressure, in.wg

0.2
H I J K
A
0.0
L

-0.2 C
B

-0.4

-0.6

D
-0.8

-1.0

E
-1.2

Static Pressure Available


Total Pressure Available
Note: Return side point values are at entrance of duct, while supply side points are at exit. When a return system is
present, an additional return side point named [Fan Entrance] is drawn in the graph to show the static pressure
available at the entrance of the fan. When a supply system is present, and an additional supply side point named [Fan
Exit] is drawn to show the static pressure available at the exit of the fan.
Point Name Static Pressure Available Total Pressure Available
A RAG1-2 0.000 0.073
B RT1-1 -0.193 -0.120
C RT1-2 -0.165 -0.010
D RT1-3 -0.709 -0.572
E [Fan Entrance] -1.131 -0.994
F [Fan Exit] 1.115 1.251
G ST1-1 0.325 0.462
H ST1-12 0.112 0.184
I ST1-13 0.092 0.169
J ST1-14 0.091 0.155
K ST1-15 0.080 0.138
L SAG1-14 -0.010 0.001

D:\ ...\132kv gis duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 21

System 1 "PACU 01 & 02" - Runout Sound Data - Supply


Runout
63 125 250 500 1000 2000 4000 8000 NC
Name
SAG1-1 Required Attenuation 29 35 41 45 48 45 38 34 30
Actual Attenuation 40 40 40 49 77 80 69 78 35
Additional Attenuation 0 0 1 0 0 0 0 0

SAG1-2 Required Attenuation 29 35 41 45 48 45 38 34 30


Actual Attenuation 40 42 44 57 88 87 75 83 30
Additional Attenuation 0 0 0 0 0 0 0 0

SAG1-3 Required Attenuation 29 35 41 45 48 45 38 34 30


Actual Attenuation 41 44 49 66 99 95 80 89 30
Additional Attenuation 0 0 0 0 0 0 0 0

SAG1-4 Required Attenuation 29 35 41 45 48 45 38 34 30


Actual Attenuation 42 46 53 74 109 102 85 94 30
Additional Attenuation 0 0 0 0 0 0 0 0

SAG1-5 Required Attenuation 29 35 41 45 48 45 38 34 30


Actual Attenuation 43 48 57 83 120 110 91 99 30
Additional Attenuation 0 0 0 0 0 0 0 0

SAG1-6 Required Attenuation 29 35 41 45 48 45 38 34 30


Actual Attenuation 43 50 61 91 131 117 96 105 30
Additional Attenuation 0 0 0 0 0 0 0 0

SAG1-7 Required Attenuation 29 35 41 45 48 45 38 34 30


Actual Attenuation 44 53 66 100 141 124 101 110 30
Additional Attenuation 0 0 0 0 0 0 0 0

SAG1-8 Required Attenuation 29 35 41 45 48 45 38 34 30


Actual Attenuation 45 58 72 110 159 134 107 115 30
Additional Attenuation 0 0 0 0 0 0 0 0

SAG1-9 Required Attenuation 29 35 41 45 48 45 38 34 30


Actual Attenuation 48 65 79 121 177 144 112 121 30
Additional Attenuation 0 0 0 0 0 0 0 0

SAG1-10 Required Attenuation 29 35 41 45 48 45 38 34 30


Actual Attenuation 50 72 88 130 201 166 119 125 30
Additional Attenuation 0 0 0 0 0 0 0 0

SAG1-11 Required Attenuation 29 35 41 45 48 45 38 34 30


Actual Attenuation 51 50 47 55 83 112 104 112 30
Additional Attenuation 0 0 0 0 0 0 0 0

SAG1-12 Required Attenuation 29 35 41 45 48 45 38 34 30


Actual Attenuation 53 51 48 55 84 119 110 119 30
Additional Attenuation 0 0 0 0 0 0 0 0

SAG1-13 Required Attenuation 29 35 41 45 48 45 38 34 30


Actual Attenuation 56 53 49 56 85 126 117 126 30
Additional Attenuation 0 0 0 0 0 0 0 0

SAG1-14 Required Attenuation 29 35 41 45 48 45 38 34 30


Actual Attenuation 58 55 49 57 85 132 124 132 30
Additional Attenuation 0 0 0 0 0 0 0 0

SAG1-15 Required Attenuation 29 35 41 45 48 45 38 34 30


Actual Attenuation 60 56 50 58 86 133 131 139 30
Additional Attenuation 0 0 0 0 0 0 0 0

SAG1-16 Required Attenuation 29 35 41 45 48 45 38 34 30


Actual Attenuation 60 55 48 54 80 125 121 129 30

D:\ ...\132kv gis duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 22

System 1 "PACU 01 & 02" - Runout Sound Data - Supply (cont'd)


Runout
63 125 250 500 1000 2000 4000 8000 NC
Name
Additional Attenuation 0 0 0 0 0 0 0 0

D:\ ...\132kv gis duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 23

System 1 "PACU 01 & 02" - Runout Sound Data - Return


Runout
63 125 250 500 1000 2000 4000 8000 NC
Name
RAG1-1 Required Attenuation 23 29 35 39 42 39 32 28 30
Actual Attenuation 35 35 34 39 68 73 61 71 35
Additional Attenuation 0 0 1 0 0 0 0 0

RAG1-2 Required Attenuation 23 29 35 39 42 39 32 28 30


Actual Attenuation 47 49 50 64 104 127 125 135 30
Additional Attenuation 0 0 0 0 0 0 0 0

FAD-1 Required Attenuation 23 29 35 39 42 39 32 28 30


Actual Attenuation 37 33 30 32 46 60 57 61 40
Additional Attenuation 0 0 5 7 0 0 0 0

D:\ ...\132kv gis duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 24

Duct Connection Tree Diagram - System 1 - PACU 01 & 02


System 1 - PACU 01 & 02
Supply
ST1-1, EF, Rect, 50 ft, SR5-12, 38"x36",
ST1-2, EF, Rnd, 8.85 ft, SD5-10, 35",
SAG1-1, EF, Rect, 2 ft, 1059 CFM, 20"x18",
ST1-3, EF, Rnd, 10.65 ft, SD5-10, 34",
SAG1-2, EF, Rect, 2 ft, 1059 CFM, 20"x18",
ST1-4, EF, Rnd, 10.65 ft, SD5-10, 32",
SAG1-3, EF, Rect, 2 ft, 1059 CFM, 20"x18",
ST1-5, EF, Rnd, 10.65 ft, SD5-10, 30",
SAG1-4, EF, Rect, 2 ft, 1059 CFM, 20"x18",
ST1-6, EF, Rnd, 10.65 ft, SD5-10, 28",
SAG1-5, EF, Rect, 2 ft, 1059 CFM, 20"x18",
ST1-7, EF, Rnd, 10.65 ft, SD5-10, 27.3",
SAG1-6, EF, Rect, 2 ft, 1059 CFM, 20"x18",
ST1-8, EF, Rnd, 10.65 ft, SD5-10, 25.1",
SAG1-7, EF, Rect, 2 ft, 1059 CFM, 20"x18",
ST1-9, EF, Rnd, 10.65 ft, SD5-10, 21.9",
SAG1-8, EF, Rect, 2 ft, 1059 CFM, 20"x18",
ST1-10, EF, Rnd, 10.65 ft, SD5-10, 18.5",
SAG1-9, EF, Rect, 2 ft, 1058 CFM, 18"x16",
ST1-11, EF, Rnd, 11 ft, (none), 15.3",
SAG1-10, EF, Rect, 2 ft, 1058 CFM, 14"x14",
ST1-12, EF, Rect, 37 ft, SR5-5, 20"x20",
SAG1-11, EF, Rect, 2 ft, 478 CFM, 14"x12",
ST1-13, EF, Rect, 16.73 ft, SR5-5, 18"x18",
SAG1-12, EF, Rect, 2 ft, 478 CFM, 14"x12",
ST1-14, EF, Rect, 16.73 ft, SR5-5, 18"x16",
SAG1-13, EF, Rect, 2 ft, 479 CFM, 14"x12",
ST1-15, EF, Rect, 16.73 ft, SR5-5, 16"x14",
SAG1-14, EF, Rect, 2 ft, 479 CFM, 14"x12",
ST1-16, EF, Rect, 16.73 ft, SR5-5, 14"x12",
SAG1-15, EF, Rect, 2 ft, 479 CFM, 14"x12",
SAG1-16, EF, Rect, 2 ft, 479 CFM, 14"x12",
Return
RT1-3, EF, Rect, 25.6 ft, ER5-4, 38"x36",
FAD-1, EF, Rect, 27.35 ft, 1346 CFM, 22"x20",
RT1-2, EF, Rect, 36.11 ft, ER5-3, 34"x34",
RAG1-1, EF, Rect, 2 ft, 9529 CFM, 34"x34",
RT1-1, EF, Rect, 25.15 ft, (none), 20"x18",
RAG1-2, EF, Rect, 2 ft, 2584 CFM, 20"x18",

D:\ ...\132kv gis duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Al Shaqra 132/13.8kv Ss#8521


HVAC Duct Sizing
for

13.8KV SWGR Building


Saudi Electricity Company
Riyadh,ksa

Prepared By:

William
Satech
Al-khobar

Tuesday, August 13, 2013


http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 2

General Project Data Input


General Project Information
Project file name: C:\Elite\Ductw\13.8kv swgr duct sizing.dsw
Project title: Al Shaqra 132/13.8kv Ss#8521
Designed by: Siddique
Project date: Saturday, August 04, 2012
Client name: 13.8KV SWGR Building
Client address: Saudi Electricity Company
Client city: Riyadh,ksa
Company name: Satech
Company representative: William
Company address: Al-khobar

D:\ ...\13.8kv swgr duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 3

System 1 "PACU 02A & 02B" - Input Data - Supply


Project & Default Data Trunks Runouts
Maximum desired velocity (FPM): 1,650 500
Material Reference: Galv Rect Galv Rect
Height constraint (in): 30 0
Width constraint (in): 0 0
Diameter constraint (in): 0 0
R-Value of insulation (Sq.ft.F/Btuh): 4.00 2.00
Duct shape: Round Rect.
Sizing method: EF EF
NC criteria: N/A 30

Duct System Data


Maximum system velocity (FPM): 1,650
Minimum system velocity (FPM): 500
Minimum trunk diameter (in): 0.0
Orifice opening interval (in): 1.000
Temperature of air leaving coil (F): 55
Design room temperature (F): 77
Temperature of duct installation space (F): 80
Altitude (ft): 2,000
Density (lb/cu.ft): 0.072
Friction loss per 100 ft. (in.wg): 0.080
Est. st. press. loss of central equip. (in.wg): 0.000
Maximum % supply air increase: 0
Allow increasing downstream diameters: No
Show diversified trunk flows: No
Duct diameter interval (in): 0.0
Whole number dimensions: Yes

Fan Data
Fan description: CENT-BACKWARD 36 in and
over
Fan static pressure (in.wg): 0.000
Fan CFM: 10,679
Fan efficiency: 85
Fan RPM: 0
Number of blades: 0
Fan blast width (in): 44
Fan blast height (in): 24
Length to first fitting (ft): 1.0

D:\ ...\13.8kv swgr duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 4

System 1 "PACU 02A & 02B" - Input Data - Return


Project & Default Data Trunks Runouts
Maximum desired velocity (FPM): 1,650 500
Material Reference: Galv Rect Galv Rect
Height constraint (in): 30 0
Width constraint (in): 0 0
Diameter constraint (in): 0 0
R-Value of insulation (Sq.ft.F/Btuh): 4.00 2.00
Duct shape: Round Rect.
Sizing method: EF EF
NC criteria: N/A 30

Duct System Data


Maximum system velocity (FPM): 1,650
Minimum system velocity (FPM): 500
Minimum trunk diameter (in): 0.0
Orifice opening interval (in): 1.000
Temperature of air leaving coil (F): 55
Design room temperature (F): 77
Temperature of duct installation space (F): 80
Altitude (ft): 2,000
Density (lb/cu.ft): 0.072
Friction loss per 100 ft. (in.wg): 0.080
Est. st. press. loss of central equip. (in.wg): 0.000
Maximum % supply air increase: 0
Allow increasing downstream diameters: No
Show diversified trunk flows: No
Duct diameter interval (in): 0.0
Whole number dimensions: Yes

Fan Data
Fan description: CENT-BACKWARD 36 in and
over
Fan static pressure (in.wg): 0.000
Fan CFM: 0
Fan efficiency: 0
Fan RPM: 0
Number of blades: 0
Fan blast width (in): 0
Fan blast height (in): 0
Length to first fitting (ft): 1.0

D:\ ...\13.8kv swgr duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 5

System 1 "PACU 02A & 02B" - Trunk Input Data - Supply


Trunk Dia Length Fit 1 #Fit Shape Active Material Ref.
Ups. Hei Max.Vel Fit 2 #Fit Add.Loss Take Off Roughness
SM Wid Junc fit #Fit R-Value Per.Div
ST2-1 0.0 21.97 CR3-1 4 Rect. Yes Galv Rect
FAN 30.0 1,650 CR9-5 1 0.00 0 0.00050
EF 0.0 SR5-13 1 4.00 0
Fit 3 CR9-4 1

ST2-2 0.0 7.51 ---- Rect. Yes Galv Rect


ST2-1 30.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SR5-5 1 4.00 0

ST2-3 0.0 19.43 ---- Rect. Yes Galv Rect


ST2-2 30.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SR5-5 1 4.00 0

ST2-4 0.0 16.33 ---- Rect. Yes Galv Rect


ST2-3 30.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SR5-5 1 4.00 0

ST2-5 0.0 4.00 ---- 1 Rect. Yes Galv Rect


ST2-4 30.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SR5-5 1 4.00 0

ST2-6 0.0 20.99 ---- Rect. Yes Galv Rect


ST2-5 30.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SR5-5 1 4.00 0

ST2-7 0.0 14.63 ---- Rect. Yes Galv Rect


ST2-6 30.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SR5-5 1 4.00 0

ST2-8 0.0 5.70 ---- Rect. Yes Galv Rect


ST2-7 30.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SR5-5 1 4.00 0

ST2-9 0.0 17.15 ---- Rect. Yes Galv Rect


ST2-8 30.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SR5-5 1 4.00 0

ST2-10 0.0 17.24 CR9-4 1 Rect. Yes Galv Rect


ST2-9 30.0 1,650 CR9-5 1 0.00 10 0.00050
EF 0.0 1 4.00 0

ST2-11 0.0 32.80 CR3-1 1 Rect. Yes Galv Rect


ST2-1 30.0 1,650 CR9-5 1 0.00 90 0.00050
EF 0.0 SR5-5 1 4.00 0

ST2-12 0.0 39.75 ---- Rect. Yes Galv Rect


ST2-11 30.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SR5-5 1 4.00 0

D:\ ...\13.8kv swgr duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 6

System 1 "PACU 02A & 02B" - Trunk Input Data - Return


Trunk Dia Length Fit 1 #Fit Shape Active Material Ref.
Ups. Hei Max.Vel Fit 2 #Fit Add.Loss Take Off Roughness
SM Wid Junc fit #Fit R-Value Per.Div
RT2-10 0.0 12.16 CR3-1 1 Rect. Yes Galv Rect
FAN 30.0 1,650 CR9-4 2 0.00 0 0.00050
EF 0.0 ER5-5 1 4.00 0

RT2-9 0.0 45.09 CR3-1 1 Rect. Yes Galv Rect


RT2-10 30.0 1,650 CR9-5 1 0.00 90 0.00050
EF 0.0 ER5-3 1 4.00 0

RT2-8 0.0 12.13 ---- Rect. Yes Galv Rect


RT2-9 30.0 1,650 ---- 0.00 0 0.00050
EF 0.0 ER5-3 1 4.00 0

RT2-7 0.0 10.61 ---- Rect. Yes Galv Rect


RT2-8 30.0 1,650 ---- 0.00 0 0.00050
EF 0.0 ER5-3 1 4.00 0

RT2-6 0.0 15.94 CR9-4 1 Rect. Yes Galv Rect


RT2-7 30.0 1,650 ---- 0.00 0 0.00050
EF 0.0 ER5-3 1 4.00 0

RT2-5 0.0 12.12 ---- Rect. Yes Galv Rect


RT2-6 30.0 1,650 ---- 0.00 0 0.00050
EF 0.0 ER5-3 1 4.00 0

RT2-4 0.0 11.48 ---- Rect. Yes Galv Rect


RT2-5 30.0 1,650 ---- 0.00 0 0.00050
EF 0.0 ER5-3 1 4.00 0

RT2-3 0.0 3.94 ---- Rect. Yes Galv Rect


RT2-4 30.0 1,650 ---- 0.00 0 0.00050
EF 0.0 ER5-3 1 4.00 0

RT2-2 0.0 11.92 ---- Rect. Yes Galv Rect


RT2-3 30.0 1,650 ---- 0.00 0 0.00050
EF 0.0 ER5-3 1 4.00 0

RT2-1 0.0 13.12 ---- Rect. Yes Galv Rect


RT2-2 30.0 1,650 ---- 0.00 0 0.00050
EF 0.0 1 4.00 0

D:\ ...\13.8kv swgr duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 7

System 1 "PACU 02A & 02B" - Runout Input Data - Supply


Runout Dia Length Fit 1 #Fit Shape Active Material Ref.
Ups. Hei Max.Vel Fit 2 #Fit Add.Loss Take Off Roughness
SM Wid Fit 3 #Fit R-Value NC Level Dif.Loss
SCD2-1 0.0 6.56 ---- Rect. Yes Galv Rect
ST2-4 0.0 500 CR9-4 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SAG2-1 0.0 2.00 ---- Rect. Yes Galv Rect


ST2-2 0.0 500 CR9-4 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SAG2-2 0.0 2.00 ---- Rect. Yes Galv Rect


ST2-3 0.0 500 CR9-4 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SCD2-2 0.0 7.18 CR9-4 1 Rect. Yes Galv Rect


ST2-7 0.0 500 ---- 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.000

SAG2-3 0.0 2.00 ---- Rect. Yes Galv Rect


ST2-5 0.0 500 CR9-4 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SAG2-4 0.0 2.00 ---- Rect. Yes Galv Rect


ST2-6 0.0 500 CR9-4 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SAG2-07 0.0 6.97 ---- Rect. Yes Galv Rect


ST2-10 0.0 500 CR9-4 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SAG2-5 0.0 2.00 ---- Rect. Yes Galv Rect


ST2-8 0.0 500 CR9-4 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SAG2-6 0.0 2.00 ---- Rect. Yes Galv Rect


ST2-9 0.0 500 CR9-4 1 0.00 0 0.00050
EF 0.0 ---- 2.00 30 0.080

SAG2-7 0.0 2.00 ---- Rect. Yes Galv Rect


ST2-11 0.0 500 CR9-4 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SAG2-8 0.0 2.00 ---- Rect. Yes Galv Rect


ST2-12 0.0 500 CR9-4 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SAG2-9 0.0 2.00 ---- Rect. Yes Galv Rect


ST2-12 0.0 500 CR9-4 1 0.00 0 0.00050
EF 0.0 ---- 2.00 30 0.080

D:\ ...\13.8kv swgr duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 8

System 1 "PACU 02A & 02B" - Runout Input Data - Return


Runout Dia Length Fit 1 #Fit Shape Active Material Ref.
Ups. Hei Max.Vel Fit 2 #Fit Add.Loss Take Off Roughness
SM Wid Fit 3 #Fit R-Value NC Level Grille.Loss
RAG2-1 0.0 14.76 CR9-4 1 Rect. Yes Galv Rect
RT2-9 0.0 500 ---- 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

RAG2-2 0.0 2.00 CR9-4 1 Rect. Yes Galv Rect


RT2-8 0.0 500 ---- 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

RAG2-3 0.0 2.00 CR9-4 1 Rect. Yes Galv Rect


RT2-6 0.0 500 ---- 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.000

RAG2-4 0.0 2.00 CR9-4 1 Rect. Yes Galv Rect


RT2-5 0.0 500 ---- 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.000

RAG2-5 0.0 2.00 CR9-4 1 Rect. Yes Galv Rect


RT2-2 0.0 500 ---- 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

RAG2-6 0.0 10.69 ---- Rect. Yes Galv Rect


RT2-1 0.0 500 CR9-4 1 0.00 0 0.00050
EF 0.0 ---- 2.00 30 0.080

RAG2-7 0.0 11.48 CR9-4 1 Rect. Yes Galv Rect


RT2-7 0.0 500 CR9-5 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

RAG2-8 0.0 11.48 CR9-4 1 Rect. Yes Galv Rect


RT2-4 0.0 500 CR9-5 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

RAG2-9 0.0 11.48 CR9-4 1 Rect. Yes Galv Rect


RT2-3 0.0 500 CR9-5 1 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.000

FAD-1 0.0 21.54 CR9-4 2 Rect. Yes Galv Rect


RT2-10 0.0 500 ---- 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

D:\ ...\13.8kv swgr duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 9

System 1 "PACU 02A & 02B" - Trunk Output Data - Supply


Fit Sect1 Sect2 Cumul Press
------ ------ ------ ------ ------
Trunk Dia SM L/100 Shape Ups.Sh Equip Dynam Vel.P Veloc
Upstr Hei TOA Reg Fit.1 Qty Coef Loss Add.L Fric Stat Stat
Vel Wid Gau Fit.2 Qty Coef Loss F.Tot Total Total Total
CFM Len Ref Mat Ups.Junc Coef Loss Dynam
ST2-1 33.9 EF 0.080 Rect N/A 0.000 1.908 0.000 0.145
FAN 30.0 0 0.000 *CR3-1 4 1.208 0.155 0.000 0.017 1.926 0.264
1,558 32.0 20 CR9-5 1 0.460 0.059 1.908 1.926 1.926 0.409
9,768 22.0 Galv Rect 1.908
Fit.3: CR9-4 1 0.520 0.067

ST2-2 30.6 EF 0.080 Rect Rect 0.000 0.007 0.020 0.126


ST2-1 28.0 0 0.013 ---- 0.000 0.006 1.919 0.271
1,448 28.0 22 ---- 0.007 0.013 1.939 0.396
7,397 7.5 Galv Rect SR5-13-MN 0.065 0.007 0.007

ST2-3 29.4 EF 0.075 Rect Rect 0.000 0.002 0.035 0.111


ST2-2 26.0 0 0.013 ---- 0.000 0.014 1.920 0.269
1,361 28.0 22 ---- 0.002 0.016 1.955 0.380
6,416 19.4 Galv Rect SR5-5-MN 0.020 0.002 0.002

ST2-4 27.3 EF 0.075 Rect Rect 0.000 0.002 0.038 0.107


ST2-3 24.0 0 0.002 ---- 0.000 0.013 1.931 0.259
1,337 26.0 22 ---- 0.002 0.015 1.969 0.366
5,435 16.3 Galv Rect SR5-5-MN 0.023 0.002 0.002

ST2-5 26.2 EF 0.085 Rect Rect 0.000 0.001 0.035 0.111


ST2-4 24.0 0 -0.005 ---- 1 0.000 0.003 1.939 0.251
1,360 24.0 22 ---- 0.001 0.004 1.974 0.361
5,090 4.0 Galv Rect SR5-5-MN 0.010 0.001 0.001

ST2-6 25.1 EF 0.070 Rect Rect 0.000 0.002 0.059 0.087


ST2-5 22.0 0 0.022 ---- 0.000 0.015 1.931 0.258
1,202 24.0 22 ---- 0.002 0.017 1.990 0.345
4,130 21.0 Galv Rect SR5-5-MN 0.028 0.002 0.002

ST2-7 21.9 EF 0.085 Rect Rect 0.000 0.004 0.057 0.088


ST2-6 20.0 0 -0.006 ---- 0.000 0.012 1.949 0.240
1,212 20.0 22 ---- 0.004 0.016 2.007 0.328
3,170 14.6 Galv Rect SR5-5-MN 0.053 0.004 0.004

ST2-8 21.9 EF 0.070 Rect Rect 0.000 0.001 0.072 0.073


ST2-7 20.0 0 0.014 ---- 0.000 0.004 1.939 0.250
1,105 20.0 22 ---- 0.001 0.005 2.012 0.323
2,890 5.7 Galv Rect SR5-5-MN 0.013 0.001 0.001

ST2-9 18.5 EF 0.075 Rect Rect 0.000 0.007 0.082 0.064


ST2-8 16.0 0 0.003 ---- 0.000 0.013 1.950 0.240
1,030 18.0 24 ---- 0.007 0.020 2.031 0.303
1,923 17.2 Galv Rect SR5-5-MN 0.124 0.007 0.007

ST2-10 14.2 EF 0.075 Rect Rect 0.000 0.104 0.100 0.045


ST2-9 12.0 10 -0.086 CR9-4 1 0.520 0.021 0.000 0.013 2.049 0.141
869 14.0 24 CR9-5 1 0.460 0.018 0.104 0.117 2.149 0.186
956 17.2 Galv Rect SR5-5-BR 1.613 0.065 0.104

ST2-11 19.7 EF 0.080 Rect Rect 0.000 0.219 0.070 0.075


ST2-1 18.0 90 -0.149 *CR3-1 1 1.180 0.078 0.000 0.027 2.101 0.088
1,120 18.0 24 CR9-5 1 0.460 0.031 0.219 0.246 2.172 0.163
2,371 32.8 Galv Rect SR5-13-BR 1.656 0.110 0.219

ST2-12 17.5 EF 0.070 Rect Rect 0.000 0.006 0.089 0.056


ST2-11 16.0 0 0.013 ---- 0.000 0.029 2.117 0.073

D:\ ...\13.8kv swgr duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 10

System 1 "PACU 02A & 02B" - Trunk Output Data - Supply (cont'd)
Fit Sect1 Sect2 Cumul Press
------ ------ ------ ------ ------
Trunk Dia SM L/100 Shape Ups.Sh Equip Dynam Vel.P Veloc
Upstr Hei TOA Reg Fit.1 Qty Coef Loss Add.L Fric Stat Stat
Vel Wid Gau Fit.2 Qty Coef Loss F.Tot Total Total Total
CFM Len Ref Mat Ups.Junc Coef Loss Dynam
969 16.0 24 ---- 0.006 0.034 2.206 0.129
1,618 39.8 Galv Rect SR5-5-MN 0.112 0.006 0.006

* Loss coefficient for indicated fitting is from the boundary of the table since one or more of the parameters used to
look up the coefficient was outside the range of the table.
Explanation of Values in Rightmost Five Columns Above
Column Description
"Fit": "Loss" = Static pressure loss through the indicated fitting.
"Sect1": "Equip" = User-entered loss through central equipment (supply main trunk only).
"Add.L" = User entered additional static pressure loss.
"F.Tot" = Total of all the fitting static pressure losses. For supply main trunk, also includes loss through
central equipment and any loss carried from return system.
"Dynam" = Total of all the dynamic losses, which includes everything but the frictional loss.
"Sect2": "Dynam" = Total of the dynamic losses, carried from bottom of previous column.
"Fric" = Static pressure loss due to the inside surface roughness (friction).
"Total" = Total of the dynamic and friction losses.
"Cumul": "Vel.P" = Cumulative loss in velocity pressure. For return, velocity pressure of downstream runout with
highest static pressure minus that of this trunk. For supply, main trunk velocity pressure minus that of
this trunk.
"Stat" = Cumulative loss of static pressure. For return, sum of the loss of all ducts in route starting with
downstream runout with highest static pressure through this trunk. For supply, sum of all upstream trunk
losses plus this trunk's loss.
"Total" = Cumulative velocity pressure loss plus cumulative static pressure loss.
"Press": "Veloc" = Velocity pressure.
"Stat" = Static pressure available. For return, at entrance of duct. For supply, at exit.
"Total" = Velocity pressure plus static pressure available.

D:\ ...\13.8kv swgr duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 11

System 1 "PACU 02A & 02B" - Trunk Output Data - Return


Fit Sect1 Sect2 Cumul Press
------ ------ ------ ------ ------
Trunk Dia SM L/100 Shape Ups.Sh Equip Dynam Vel.P Veloc
Dnstr Hei TOA Reg Fit.1 Qty Coef Loss Add.L Fric Stat Stat
Vel Wid Gau Fit.2 Qty Coef Loss F.Tot Total Total Total
CFM Len Ref Mat Ups.Junc Coef Loss Dynam
RT2-10 33.9 EF 0.080 Rect N/A 0.000 0.289 -0.096 0.145
FAN 30.0 0 0.000 *CR3-1 1 1.208 0.155 0.000 0.010 1.161 -0.862
1,559 32.0 20 CR9-4 2 0.520 0.067 0.289 0.299 1.065 -0.717
9,769 12.2 Galv Rect 0.289

RT2-9 30.6 EF 0.085 Rect Rect 0.000 0.419 -0.084 0.133


RT2-10 28.0 90 -0.407 *CR3-1 1 1.180 0.138 0.000 0.037 0.875 -0.419
1,492 28.0 22 CR9-5 1 0.460 0.054 0.419 0.456 0.790 -0.285
7,622 45.1 Galv Rect ER5-5-BR 1.928 0.226 0.419

RT2-8 29.4 EF 0.080 Rect Rect 0.000 0.015 -0.073 0.122


RT2-9 26.0 0 -0.004 ---- 0.000 0.010 0.430 -0.404
1,429 28.0 22 ---- 0.015 0.025 0.356 -0.282
6,739 12.1 Galv Rect ER5-3-MN 0.144 0.015 0.015

RT2-7 28.4 EF 0.075 Rect Rect 0.000 0.017 -0.057 0.106


RT2-8 26.0 0 -0.001 ---- 0.000 0.008 0.421 -0.396
1,331 26.0 22 ---- 0.017 0.025 0.364 -0.289
5,856 10.6 Galv Rect ER5-3-MN 0.187 0.017 0.017

RT2-6 26.2 EF 0.085 Rect Rect 0.000 0.067 -0.065 0.115


RT2-7 24.0 0 -0.075 CR9-4 1 0.520 0.052 0.000 0.014 0.387 -0.307
1,383 24.0 22 ---- 0.067 0.080 0.322 -0.192
5,178 15.9 Galv Rect ER5-3-MN 0.144 0.014 0.067

RT2-5 25.1 EF 0.075 Rect Rect 0.000 0.024 -0.045 0.094


RT2-6 22.0 0 -0.004 ---- 0.000 0.009 0.327 -0.294
1,255 24.0 22 ---- 0.024 0.033 0.282 -0.200
4,314 12.1 Galv Rect ER5-3-MN 0.287 0.024 0.024

RT2-4 22.9 EF 0.080 Rect Rect 0.000 0.029 -0.038 0.087


RT2-5 20.0 0 -0.022 ---- 0.000 0.009 0.301 -0.263
1,206 22.0 22 ---- 0.029 0.038 0.263 -0.176
3,450 11.5 Galv Rect ER5-3-MN 0.381 0.029 0.029

RT2-3 20.7 EF 0.085 Rect Rect 0.000 0.027 -0.035 0.084


RT2-4 18.0 0 -0.024 ---- 0.000 0.003 0.266 -0.235
1,184 20.0 24 ---- 0.027 0.031 0.232 -0.151
2,767 3.9 Galv Rect ER5-3-MN 0.374 0.027 0.027

RT2-2 18.5 EF 0.080 Rect Rect 0.000 0.041 -0.019 0.068


RT2-3 16.0 0 -0.025 ---- 0.000 0.010 0.251 -0.201
1,068 18.0 24 ---- 0.041 0.050 0.232 -0.132
1,994 11.9 Galv Rect ER5-3-MN 0.682 0.041 0.041

RT2-1 14.2 EF 0.085 Rect Rect 0.000 0.098 0.000 0.049


RT2-2 12.0 0 -0.078 ---- 0.000 0.011 0.220 -0.112
907 14.0 24 ---- 0.098 0.108 0.220 -0.062
997 13.1 Galv Rect ER5-3-MN 2.230 0.098 0.098

* Loss coefficient for indicated fitting is from the boundary of the table since one or more of the parameters used to
look up the coefficient was outside the range of the table.
Explanation of Values in Rightmost Five Columns Above
Column Description
"Fit": "Loss" = Static pressure loss through the indicated fitting.

D:\ ...\13.8kv swgr duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 12

System 1 "PACU 02A & 02B" - Trunk Output Data - Return (cont'd)
Column Description
"Sect1": "Equip" = User-entered loss through central equipment (supply main trunk only).
"Add.L" = User entered additional static pressure loss.
"F.Tot" = Total of all the fitting static pressure losses. For supply main trunk, also includes loss through
central equipment and any loss carried from return system.
"Dynam" = Total of all the dynamic losses, which includes everything but the frictional loss.
"Sect2": "Dynam" = Total of the dynamic losses, carried from bottom of previous column.
"Fric" = Static pressure loss due to the inside surface roughness (friction).
"Total" = Total of the dynamic and friction losses.
"Cumul": "Vel.P" = Cumulative loss in velocity pressure. For return, velocity pressure of downstream runout with
highest static pressure minus that of this trunk. For supply, main trunk velocity pressure minus that of
this trunk.
"Stat" = Cumulative loss of static pressure. For return, sum of the loss of all ducts in route starting with
downstream runout with highest static pressure through this trunk. For supply, sum of all upstream trunk
losses plus this trunk's loss.
"Total" = Cumulative velocity pressure loss plus cumulative static pressure loss.
"Press": "Veloc" = Velocity pressure.
"Stat" = Static pressure available. For return, at entrance of duct. For supply, at exit.
"Total" = Velocity pressure plus static pressure available.

D:\ ...\13.8kv swgr duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 13

System 1 "PACU 02A & 02B" - Runout Output Data - Supply


Fit Sect1 Sect2 Cumul Press
Runout Dia SM L/100 Shape Ups.Sh ------ ------ ------ ------ ------
Conn Hei TOA Reg Fit1 Qty Coef Loss Diff. Dynam Vel.P Veloc
Vel Wid Gau Fit2 Qty Coef Loss Add.L Fric Stat Stat
CFM Len Ref Mat Fit3 Qty Coef Loss F.Tot Total Total Total
Orif R.NC Act.NC Ups.Junc Qty Coef Loss Dynam
SCD2-1 12.0 EF 0.025 Rect Rect 0.080 0.136 0.134 0.012
ST2-4 10.0 90 -0.040 ---- 0.000 0.002 1.973 0.216
439 12.0 24 CR9-4 1 0.520 0.005 0.056 0.138 2.107 0.228
345 6.6 Galv Rect ---- 0.136
8.00 30 30 *SR5-5-BR 1 4.922 0.051

SAG2-1 19.7 EF 0.015 Rect Rect 0.080 0.233 0.133 0.013


ST2-2 18.0 90 -0.120 ---- 0.000 0.000 2.039 0.150
463 18.0 24 CR9-4 1 0.520 0.006 0.153 0.233 2.172 0.163
981 2.0 Galv Rect ---- 0.233
13.70 30 35 SR5-5-BR 1 12.931 0.147

SAG2-2 19.7 EF 0.015 Rect Rect 0.080 0.223 0.133 0.013


ST2-3 18.0 90 -0.125 ---- 0.000 0.000 2.045 0.144
463 18.0 24 CR9-4 1 0.520 0.006 0.143 0.223 2.178 0.157
981 2.0 Galv Rect ---- 0.223
13.70 30 35 SR5-5-BR 1 12.017 0.137

SCD2-2 10.9 EF 0.030 Rect Rect 0.000 0.080 0.134 0.011


ST2-7 10.0 90 -0.003 CR9-4 1 0.520 0.005 0.000 0.002 1.955 0.235
432 10.0 26 ---- 0.080 0.082 2.089 0.246
280 7.2 Galv Rect ---- 0.080
6.90 30 30 *SR5-5-BR 1 7.710 0.075

SAG2-3 19.7 EF 0.015 Rect Rect 0.080 0.199 0.133 0.012


ST2-5 18.0 90 -0.101 ---- 0.000 0.000 2.040 0.149
454 18.0 24 CR9-4 1 0.520 0.006 0.119 0.200 2.173 0.162
960 2.0 Galv Rect ---- 0.199
13.70 30 30 SR5-5-BR 1 10.429 0.114

SAG2-4 19.7 EF 0.015 Rect Rect 0.080 0.168 0.133 0.012


ST2-6 18.0 90 -0.093 ---- 0.000 0.000 2.025 0.164
454 18.0 24 CR9-4 1 0.520 0.006 0.088 0.168 2.158 0.177
960 2.0 Galv Rect ---- 0.168
12.70 30 30 SR5-5-BR 1 7.514 0.082

SAG2-07 14.2 EF 0.075 Rect Rect 0.080 0.101 0.100 0.045


ST2-10 12.0 90 -0.101 ---- 0.000 0.005 2.155 0.035
869 14.0 24 CR9-4 1 0.520 0.021 0.021 0.106 2.255 0.080
956 7.0 Galv Rect ---- 0.101
14.20 30 30 1

SAG2-5 19.7 EF 0.015 Rect Rect 0.080 0.147 0.133 0.012


ST2-8 18.0 90 -0.087 ---- 0.000 0.000 2.026 0.163
457 18.0 24 CR9-4 1 0.520 0.006 0.067 0.148 2.159 0.176
967 2.0 Galv Rect ---- 0.147
12.70 30 30 *SR5-5-BR 1 5.564 0.062

SAG2-6 18.5 EF 0.020 Rect Rect 0.080 0.093 0.129 0.016


ST2-9 16.0 0 -0.045 ---- 0.000 0.000 1.995 0.194
518 18.0 24 CR9-4 1 0.520 0.007 0.013 0.093 2.125 0.210
967 2.0 Galv Rect ---- 0.093
12.50 30 30 SR5-5-MN 1 0.393 0.006

SAG2-7 17.5 EF 0.020 Rect Rect 0.080 0.149 0.133 0.012


ST2-11 16.0 90 -0.086 ---- 0.000 0.000 2.188 0.002
451 16.0 24 CR9-4 1 0.520 0.006 0.069 0.150 2.321 0.014
753 2.0 Galv Rect ---- 0.149

D:\ ...\13.8kv swgr duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 14

System 1 "PACU 02A & 02B" - Runout Output Data - Supply (cont'd)
Fit Sect1 Sect2 Cumul Press
Runout Dia SM L/100 Shape Ups.Sh ------ ------ ------ ------ ------
Conn Hei TOA Reg Fit1 Qty Coef Loss Diff. Dynam Vel.P Veloc
Vel Wid Gau Fit2 Qty Coef Loss Add.L Fric Stat Stat
CFM Len Ref Mat Fit3 Qty Coef Loss F.Tot Total Total Total
Orif R.NC Act.NC Ups.Junc Qty Coef Loss Dynam
17.50 30 30 SR5-5-BR 1 5.920 0.064

SAG2-8 17.5 EF 0.020 Rect Rect 0.080 0.116 0.133 0.012


ST2-12 16.0 90 -0.073 ---- 0.000 0.000 2.190 0.000
454 16.0 24 CR9-4 1 0.520 0.006 0.036 0.117 2.323 0.012
759 2.0 Galv Rect ---- 0.116
17.50 30 30 *SR5-5-BR 1 2.815 0.031

SAG2-9 17.5 EF 0.025 Rect Rect 0.080 0.092 0.130 0.016


ST2-12 16.0 0 -0.052 ---- 0.000 0.000 2.169 0.021
514 16.0 24 CR9-4 1 0.520 0.007 0.012 0.092 2.298 0.037
859 2.0 Galv Rect ---- 0.092
16.50 30 30 SR5-5-MN 1 0.329 0.005

* Loss coefficient for indicated fitting is from the boundary of the table since one or more of the parameters used to
look up the coefficient was outside the range of the table.
Explanation of Values in Rightmost Five Columns Above
Column Description
"Fit": "Loss" = Static pressure loss through the indicated fitting.
"Sect1": "Dif" = User-entered static pressure loss due to the diffuser.
"Add.L" = User entered additional static pressure loss.
"F.Tot" = Total of all the fitting static pressure losses.
"Dynam" = Total of all the dynamic losses, which includes everything but the frictional loss.
"Sect2": "Dynam" = Total of the dynamic losses, carried from bottom of previous column.
"Fric" = Static pressure loss due to the inside surface roughness (friction).
"Total" = Total of the dynamic and friction losses.
"Cumul": "Vel.P" = Cumulative loss in velocity pressure. For return, zero for each runout. For supply, velocity
pressure of main trunk minus that of this duct.
"Stat" = Cumulative loss of static pressure. For return, this runout's loss. For supply, sum of all upstream
trunk losses plus this runout's loss.
"Total" = Cumulative velocity pressure loss plus cumulative static pressure loss.
"Press": "Veloc" = Velocity pressure.
"Stat" = Static pressure available. For return, at entrance of duct. For supply, at exit.
"Total" = Velocity pressure plus static pressure available.

D:\ ...\13.8kv swgr duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 15

System 1 "PACU 02A & 02B" - Runout Output Data - Return


Fit Sect1 Sect2 Cumul Press
Runout Dia SM L/100 Shape Ups.Sh ------ ------ ------ ------ ------
Conn Hei TOA Reg Fit1 Qty Coef Loss Diff. Dynam Vel.P Veloc
Vel Wid Gau Fit2 Qty Coef Loss Add.L Fric Stat Stat
CFM Len Ref Mat Fit3 Qty Coef Loss F.Tot Total Total Total
Orif R.NC Act.NC Ups.Junc Qty Coef Loss Dynam
RAG2-1 18.5 EF 0.020 Rect Rect 0.080 -0.097 0.000 0.013
RT2-9 16.0 90 0.217 CR9-4 1 0.520 0.006 0.000 0.003 -0.094 -0.633
473 18.0 24 ---- -0.177 -0.094 -0.094 -0.619
883 14.8 Galv Rect ---- -0.097
9.50 30 35 ER5-3-BR 1 -15.662 -0.183

RAG2-2 18.5 EF 0.020 Rect Rect 0.080 -0.071 0.000 0.013


RT2-8 16.0 90 0.180 CR9-4 1 0.520 0.006 0.000 0.000 -0.070 -0.584
473 18.0 24 ---- -0.151 -0.070 -0.070 -0.570
883 2.0 Galv Rect ---- -0.071
9.50 30 35 ER5-3-BR 1 -13.423 -0.157

RAG2-3 18.5 EF 0.020 Rect Rect 0.000 -0.085 0.000 0.013


RT2-6 16.0 90 0.187 CR9-4 1 0.520 0.006 0.000 0.000 -0.085 -0.493
463 18.0 24 ---- -0.085 -0.085 -0.085 -0.480
864 2.0 Galv Rect ---- -0.085
10.50 30 30 ER5-3-BR 1 -8.138 -0.091

RAG2-4 18.5 EF 0.020 Rect Rect 0.000 -0.030 0.000 0.013


RT2-5 16.0 90 0.112 CR9-4 1 0.520 0.006 0.000 0.000 -0.030 -0.406
463 18.0 24 ---- -0.030 -0.030 -0.030 -0.393
864 2.0 Galv Rect ---- -0.030
10.50 30 30 ER5-3-BR 1 -3.243 -0.036

RAG2-5 18.5 EF 0.025 Rect Rect 0.080 0.099 0.000 0.017


RT2-2 16.0 90 -0.048 CR9-4 1 0.520 0.008 0.000 0.000 0.099 -0.153
534 18.0 24 ---- 0.019 0.099 0.099 -0.135
997 2.0 Galv Rect ---- 0.099
13.50 30 30 ER5-3-BR 1 0.760 0.011

RAG2-6 14.2 EF 0.085 Rect Rect 0.080 0.103 0.000 0.049


RT2-1 12.0 0 -0.103 ---- 0.000 0.009 0.112 0.000
907 14.0 24 CR9-4 1 0.520 0.023 0.023 0.112 0.112 0.049
997 10.7 Galv Rect ---- 0.103
14.20 30 30 1

RAG2-7 16.4 EF 0.020 Rect Rect 0.080 -0.087 0.000 0.013


RT2-7 14.0 90 0.180 CR9-4 1 0.520 0.006 0.000 0.002 -0.085 -0.574
462 16.0 24 CR9-5 1 0.460 0.005 -0.167 -0.085 -0.085 -0.561
678 11.5 Galv Rect ---- -0.087
8.40 30 30 ER5-3-BR 1 -15.673 -0.178

RAG2-8 16.4 EF 0.020 Rect Rect 0.080 0.050 0.000 0.013


RT2-4 14.0 90 0.024 CR9-4 1 0.520 0.006 0.000 0.002 0.053 -0.285
466 16.0 24 CR9-5 1 0.460 0.005 -0.030 0.053 0.053 -0.272
683 11.5 Galv Rect ---- 0.050
10.40 30 30 ER5-3-BR 1 -3.549 -0.041

RAG2-9 17.5 EF 0.020 Rect Rect 0.000 -0.002 0.000 0.013


RT2-3 16.0 90 0.073 CR9-4 1 0.520 0.006 0.000 0.002 0.000 -0.307
463 16.0 24 CR9-5 1 0.460 0.005 -0.002 0.000 0.000 -0.294
773 11.5 Galv Rect ---- -0.002
10.50 30 30 ER5-3-BR 1 -1.179 -0.013

FAD-1 29.4 EF 0.010 Rect Rect 0.080 0.351 0.000 0.012


RT2-10 26.0 90 -0.218 CR9-4 2 0.520 0.006 0.000 0.002 0.353 -0.643
455 28.0 22 ---- 0.271 0.353 0.353 -0.630
2,147 21.5 Galv Rect ---- 0.351

D:\ ...\13.8kv swgr duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 16

System 1 "PACU 02A & 02B" - Runout Output Data - Return (cont'd)
Fit Sect1 Sect2 Cumul Press
Runout Dia SM L/100 Shape Ups.Sh ------ ------ ------ ------ ------
Conn Hei TOA Reg Fit1 Qty Coef Loss Diff. Dynam Vel.P Veloc
Vel Wid Gau Fit2 Qty Coef Loss Add.L Fric Stat Stat
CFM Len Ref Mat Fit3 Qty Coef Loss F.Tot Total Total Total
Orif R.NC Act.NC Ups.Junc Qty Coef Loss Dynam
14.40 30 50 ER5-5-BR 1 24.039 0.260

Explanation of Values in Rightmost Five Columns Above


Column Description
"Fit": "Loss" = Static pressure loss through the indicated fitting.
"Sect1": "Dif" = User-entered static pressure loss due to the diffuser.
"Add.L" = User entered additional static pressure loss.
"F.Tot" = Total of all the fitting static pressure losses.
"Dynam" = Total of all the dynamic losses, which includes everything but the frictional loss.
"Sect2": "Dynam" = Total of the dynamic losses, carried from bottom of previous column.
"Fric" = Static pressure loss due to the inside surface roughness (friction).
"Total" = Total of the dynamic and friction losses.
"Cumul": "Vel.P" = Cumulative loss in velocity pressure. For return, zero for each runout. For supply, velocity
pressure of main trunk minus that of this duct.
"Stat" = Cumulative loss of static pressure. For return, this runout's loss. For supply, sum of all upstream
trunk losses plus this runout's loss.
"Total" = Cumulative velocity pressure loss plus cumulative static pressure loss.
"Press": "Veloc" = Velocity pressure.
"Stat" = Static pressure available. For return, at entrance of duct. For supply, at exit.
"Total" = Velocity pressure plus static pressure available.

D:\ ...\13.8kv swgr duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 17

System 1 "PACU 02A & 02B" - Output Summary - Supply


Number of active trunks: 12
Number of active runouts: 12
Total system weight (lb.) minus fittings: 2,159.32
Total outlet flow 9,768
Total outlet flow after heat gain 9,768
Size of largest trunk: 33.9
Size of smallest trunk: 14.2
Size of largest runout: 19.7
Size of smallest runout: 10.9

Maximum static pressure loss occurs in route to runout: SAG2-8


Cumulative static pressure loss at above runout: 2.190

Isolate Return From Supply Option: No


Return SP Loss Added to 1st Trunk of Supply: 1.161
Available static pressure at above runout: 0.000
Fan static pressure: 2.190
Fan velocity pressure: 0.145
Fan total pressure: 2.335

D:\ ...\13.8kv swgr duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 18

System 1 "PACU 02A & 02B" - Output Summary - Return


Number of active trunks: 10
Number of active runouts: 10
Total system weight (lb.) minus fittings: 2,305.34
Total outlet flow 9,769
Total outlet flow after heat gain 9,769
Size of largest trunk: 33.9
Size of smallest trunk: 14.2
Size of largest runout: 29.4
Size of smallest runout: 14.2

Maximum SP loss occurs in route from runout: RAG2-6


Total SP loss of route starting from above runout: 1.161

Isolate Return From Supply Option: No


Return SP Loss Added to 1st Trunk of Supply: 1.161
Available static pressure at above runout: 0.000
Fan static pressure: -1.161
Fan velocity pressure: 0.145
Fan total pressure: -1.016

D:\ ...\13.8kv swgr duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 19

System 1 "PACU 02A & 02B" - Pressure Changes Graph

Pressure Changes Through Route with Highest Static Pressure Loss

1.2

M
1.0

0.8

0.6

0.4
N

0.2
Pressure, in.wg

O P
A
0.0
Q

B
-0.2
C
D
E
F G
-0.4
H I J

-0.6

-0.8
K
-1.0

-1.2 L

Static Pressure Available


Total Pressure Available
Note: Return side point values are at entrance of duct, while supply side points are at exit. When a return system is
present, an additional return side point named [Fan Entrance] is drawn in the graph to show the static pressure
available at the entrance of the fan. When a supply system is present, and an additional supply side point named [Fan
Exit] is drawn to show the static pressure available at the exit of the fan.
Point Name Static Pressure Available Total Pressure Available
A RAG2-6 0.000 0.049
B RT2-1 -0.112 -0.062
C RT2-2 -0.201 -0.132
D RT2-3 -0.235 -0.151
E RT2-4 -0.263 -0.176
F RT2-5 -0.294 -0.200
G RT2-6 -0.307 -0.192
H RT2-7 -0.396 -0.289
I RT2-8 -0.404 -0.282
J RT2-9 -0.419 -0.285
K RT2-10 -0.862 -0.717
L [Fan Entrance] -1.161 -1.016
M [Fan Exit] 1.028 1.174
N ST2-1 0.264 0.409
O ST2-11 0.088 0.163

D:\ ...\13.8kv swgr duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 20

System 1 "PACU 02A & 02B" - Pressure Changes Graph (cont'd)


Point Name Static Pressure Available Total Pressure Available
P ST2-12 0.073 0.129
Q SAG2-8 0.000 0.012

D:\ ...\13.8kv swgr duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 21

System 1 "PACU 02A & 02B" - Runout Sound Data - Supply


Runout
63 125 250 500 1000 2000 4000 8000 NC
Name
SCD2-1 Required Attenuation 28 34 40 44 47 44 37 33 30
Actual Attenuation 49 47 46 54 84 110 86 96 30
Additional Attenuation 0 0 0 0 0 0 0 0

SAG2-1 Required Attenuation 28 34 40 44 47 44 37 33 30


Actual Attenuation 35 36 37 45 66 70 68 77 35
Additional Attenuation 0 0 3 0 0 0 0 0

SAG2-2 Required Attenuation 28 34 40 44 47 44 37 33 30


Actual Attenuation 39 38 38 46 74 78 69 78 35
Additional Attenuation 0 0 2 0 0 0 0 0

SCD2-2 Required Attenuation 28 34 40 44 47 44 37 33 30


Actual Attenuation 56 53 55 70 116 147 110 121 30
Additional Attenuation 0 0 0 0 0 0 0 0

SAG2-3 Required Attenuation 28 34 40 44 47 44 37 33 30


Actual Attenuation 42 41 41 50 81 90 79 87 30
Additional Attenuation 0 0 0 0 0 0 0 0

SAG2-4 Required Attenuation 28 34 40 44 47 44 37 33 30


Actual Attenuation 46 44 42 51 82 98 87 96 30
Additional Attenuation 0 0 0 0 0 0 0 0

SAG2-07 Required Attenuation 28 34 40 44 47 44 37 33 30


Actual Attenuation 60 58 60 79 133 170 139 148 30
Additional Attenuation 0 0 0 0 0 0 0 0

SAG2-5 Required Attenuation 28 34 40 44 47 44 37 33 30


Actual Attenuation 50 48 50 67 114 127 103 112 30
Additional Attenuation 0 0 0 0 0 0 0 0

SAG2-6 Required Attenuation 28 34 40 44 47 44 37 33 30


Actual Attenuation 55 50 50 64 109 125 100 109 30
Additional Attenuation 0 0 0 0 0 0 0 0

SAG2-7 Required Attenuation 28 34 40 44 47 44 37 33 30


Actual Attenuation 43 44 44 53 74 94 100 108 30
Additional Attenuation 0 0 0 0 0 0 0 0

SAG2-8 Required Attenuation 28 34 40 44 47 44 37 33 30


Actual Attenuation 49 48 46 55 75 110 116 124 30
Additional Attenuation 0 0 0 0 0 0 0 0

SAG2-9 Required Attenuation 28 34 40 44 47 44 37 33 30


Actual Attenuation 46 44 41 48 66 99 103 111 30
Additional Attenuation 0 0 0 0 0 0 0 0

D:\ ...\13.8kv swgr duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 22

System 1 "PACU 02A & 02B" - Runout Sound Data - Return


Runout
63 125 250 500 1000 2000 4000 8000 NC
Name
RAG2-1 Required Attenuation 34 40 46 50 53 50 43 39 30
Actual Attenuation 44 43 44 57 102 97 77 83 35
Additional Attenuation 0 0 2 0 0 0 0 0

RAG2-2 Required Attenuation 34 40 46 50 53 50 43 39 30


Actual Attenuation 44 42 41 52 91 90 71 78 35
Additional Attenuation 0 0 5 0 0 0 0 0

RAG2-3 Required Attenuation 34 40 46 50 53 50 43 39 30


Actual Attenuation 49 46 46 59 104 107 84 91 30
Additional Attenuation 0 0 0 0 0 0 0 0

RAG2-4 Required Attenuation 34 40 46 50 53 50 43 39 30


Actual Attenuation 51 49 50 69 123 124 94 100 30
Additional Attenuation 0 0 0 0 0 0 0 0

RAG2-5 Required Attenuation 34 40 46 50 53 50 43 39 30


Actual Attenuation 57 55 63 94 174 164 119 125 30
Additional Attenuation 0 0 0 0 0 0 0 0

RAG2-6 Required Attenuation 34 40 46 50 53 50 43 39 30


Actual Attenuation 63 63 76 115 216 260 154 161 30
Additional Attenuation 0 0 0 0 0 0 0 0

RAG2-7 Required Attenuation 34 40 46 50 53 50 43 39 30


Actual Attenuation 49 48 50 70 123 117 89 96 30
Additional Attenuation 0 0 0 0 0 0 0 0

RAG2-8 Required Attenuation 34 40 46 50 53 50 43 39 30


Actual Attenuation 56 54 61 89 162 156 114 121 30
Additional Attenuation 0 0 0 0 0 0 0 0

RAG2-9 Required Attenuation 34 40 46 50 53 50 43 39 30


Actual Attenuation 56 54 62 91 169 160 116 123 30
Additional Attenuation 0 0 0 0 0 0 0 0

FAD-1 Required Attenuation 34 40 46 50 53 50 43 39 30


Actual Attenuation 29 28 26 33 50 50 42 47 50
Additional Attenuation 5 12 20 17 3 0 1 0

D:\ ...\13.8kv swgr duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 23

Duct Connection Tree Diagram - System 1 - PACU 02A & 02B


System 1 - PACU 02A & 02B
Supply
ST2-1, EF, Rect, 21.97 ft, SR5-13, 32"x30",
ST2-2, EF, Rect, 7.51 ft, SR5-5, 28"x28",
SAG2-1, EF, Rect, 2 ft, 981 CFM, 18"x18",
ST2-3, EF, Rect, 19.43 ft, SR5-5, 28"x26",
SAG2-2, EF, Rect, 2 ft, 981 CFM, 18"x18",
ST2-4, EF, Rect, 16.33 ft, SR5-5, 26"x24",
SCD2-1, EF, Rect, 6.56 ft, 345 CFM, 12"x10",
ST2-5, EF, Rect, 4 ft, SR5-5, 24"x24",
SAG2-3, EF, Rect, 2 ft, 960 CFM, 18"x18",
ST2-6, EF, Rect, 20.99 ft, SR5-5, 24"x22",
SAG2-4, EF, Rect, 2 ft, 960 CFM, 18"x18",
ST2-7, EF, Rect, 14.63 ft, SR5-5, 20"x20",
SCD2-2, EF, Rect, 7.18 ft, 280 CFM, 10"x10",
ST2-8, EF, Rect, 5.7 ft, SR5-5, 20"x20",
SAG2-5, EF, Rect, 2 ft, 967 CFM, 18"x18",
ST2-9, EF, Rect, 17.15 ft, SR5-5, 18"x16",
SAG2-6, EF, Rect, 2 ft, 967 CFM, 18"x16",
ST2-10, EF, Rect, 17.24 ft, (none), 14"x12",
SAG2-07, EF, Rect, 6.97 ft, 956 CFM, 14"x12",
ST2-11, EF, Rect, 32.8 ft, SR5-5, 18"x18",
SAG2-7, EF, Rect, 2 ft, 753 CFM, 16"x16",
ST2-12, EF, Rect, 39.75 ft, SR5-5, 16"x16",
SAG2-8, EF, Rect, 2 ft, 759 CFM, 16"x16",
SAG2-9, EF, Rect, 2 ft, 859 CFM, 16"x16",
Return
RT2-10, EF, Rect, 12.16 ft, ER5-5, 32"x30",
FAD-1, EF, Rect, 21.54 ft, 2147 CFM, 28"x26",
RT2-9, EF, Rect, 45.09 ft, ER5-3, 28"x28",
RAG2-1, EF, Rect, 14.76 ft, 883 CFM, 18"x16",
RT2-8, EF, Rect, 12.13 ft, ER5-3, 28"x26",
RAG2-2, EF, Rect, 2 ft, 883 CFM, 18"x16",
RT2-7, EF, Rect, 10.61 ft, ER5-3, 26"x26",
RAG2-7, EF, Rect, 11.48 ft, 678 CFM, 16"x14",
RT2-6, EF, Rect, 15.94 ft, ER5-3, 24"x24",
RAG2-3, EF, Rect, 2 ft, 864 CFM, 18"x16",
RT2-5, EF, Rect, 12.12 ft, ER5-3, 24"x22",
RAG2-4, EF, Rect, 2 ft, 864 CFM, 18"x16",
RT2-4, EF, Rect, 11.48 ft, ER5-3, 22"x20",
RAG2-8, EF, Rect, 11.48 ft, 683 CFM, 16"x14",
RT2-3, EF, Rect, 3.94 ft, ER5-3, 20"x18",
RAG2-9, EF, Rect, 11.48 ft, 773 CFM, 16"x16",
RT2-2, EF, Rect, 11.92 ft, ER5-3, 18"x16",
RAG2-5, EF, Rect, 2 ft, 997 CFM, 18"x16",
RT2-1, EF, Rect, 13.12 ft, (none), 14"x12",
RAG2-6, EF, Rect, 10.69 ft, 997 CFM, 14"x12",

D:\ ...\13.8kv swgr duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Al Shaqra 132/13.8kv Ss#8521


HVAC Duct Sizing
for

CONTROL BUILDING Building


Saudi Electricity Company
Riyadh,ksa

Prepared By:

William
Satech
Al-khobar

Tuesday, August 13, 2013


http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 2

General Project Data Input


General Project Information
Project file name: C:\Elite\Ductw\CONTROL ROOM duct sizing.dsw
Project title: Al Shaqra 132/13.8kv Ss#8521
Designed by: Siddique
Project date: Saturday, August 04, 2012
Client name: CONTROL BUILDING Building
Client address: Saudi Electricity Company
Client city: Riyadh,ksa
Company name: Satech
Company representative: William
Company address: Al-khobar

D:\ ...\CONTROL ROOM duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 3

System 1 "PACU 05 & 06" - Input Data - Supply


Project & Default Data Trunks Runouts
Maximum desired velocity (FPM): 1,650 500
Material Reference: Galv Rect Galv Rect
Height constraint (in): 22 0
Width constraint (in): 0 0
Diameter constraint (in): 0 0
R-Value of insulation (Sq.ft.F/Btuh): 4.00 2.00
Duct shape: Round Rect.
Sizing method: EF EF
NC criteria: N/A 30

Duct System Data


Maximum system velocity (FPM): 1,650
Minimum system velocity (FPM): 500
Minimum trunk diameter (in): 0.0
Orifice opening interval (in): 1.000
Temperature of air leaving coil (F): 55
Design room temperature (F): 77
Temperature of duct installation space (F): 80
Altitude (ft): 2,000
Density (lb/cu.ft): 0.072
Friction loss per 100 ft. (in.wg): 0.080
Est. st. press. loss of central equip. (in.wg): 0.000
Maximum % supply air increase: 0
Allow increasing downstream diameters: No
Show diversified trunk flows: No
Duct diameter interval (in): 0.0
Whole number dimensions: Yes

Fan Data
Fan description: CENT-BACKWARD 36 in and
over
Fan static pressure (in.wg): 0.000
Fan CFM: 5,849
Fan efficiency: 85
Fan RPM: 0
Number of blades: 0
Fan blast width (in): 44
Fan blast height (in): 24
Length to first fitting (ft): 1.0

D:\ ...\CONTROL ROOM duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 4

System 1 "PACU 05 & 06" - Input Data - Return


Project & Default Data Trunks Runouts
Maximum desired velocity (FPM): 1,650 500
Material Reference: Galv Rect Galv Rect
Height constraint (in): 22 0
Width constraint (in): 0 0
Diameter constraint (in): 0 0
R-Value of insulation (Sq.ft.F/Btuh): 4.00 2.00
Duct shape: Round Rect.
Sizing method: EF EF
NC criteria: N/A 30

Duct System Data


Maximum system velocity (FPM): 1,650
Minimum system velocity (FPM): 500
Minimum trunk diameter (in): 0.0
Orifice opening interval (in): 1.000
Temperature of air leaving coil (F): 55
Design room temperature (F): 77
Temperature of duct installation space (F): 80
Altitude (ft): 2,000
Density (lb/cu.ft): 0.072
Friction loss per 100 ft. (in.wg): 0.080
Est. st. press. loss of central equip. (in.wg): 0.000
Maximum % supply air increase: 0
Allow increasing downstream diameters: No
Show diversified trunk flows: No
Duct diameter interval (in): 0.0
Whole number dimensions: Yes

Fan Data
Fan description: CENT-BACKWARD 36 in and
over
Fan static pressure (in.wg): 0.000
Fan CFM: 0
Fan efficiency: 0
Fan RPM: 0
Number of blades: 0
Fan blast width (in): 0
Fan blast height (in): 0
Length to first fitting (ft): 1.0

D:\ ...\CONTROL ROOM duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 5

System 1 "PACU 05 & 06" - Trunk Input Data - Supply


Trunk Dia Length Fit 1 #Fit Shape Active Material Ref.
Ups. Hei Max.Vel Fit 2 #Fit Add.Loss Take Off Roughness
SM Wid Junc fit #Fit R-Value Per.Div
ST3-1 0.0 67.33 CR3-1 3 Rect. Yes Galv Rect
FAN 22.0 1,650 CR9-5 1 0.00 0 0.00050
EF 0.0 SR5-13 1 4.00 0
Fit 3 CR9-4 1
Fit 4 CR3-6 1

ST3-2 0.0 14.00 CR3-6 1 Rect. Yes Galv Rect


ST3-1 22.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SR5-13 1 4.00 0

ST3-3 0.0 14.00 ---- Rect. Yes Galv Rect


ST3-2 22.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SR5-13 1 4.00 0

ST3-4 0.0 14.00 ---- Rect. Yes Galv Rect


ST3-3 22.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SR5-13 1 4.00 0

ST3-5 0.0 14.00 ---- 1 Rect. Yes Galv Rect


ST3-4 22.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SR5-13 1 4.00 0

ST2-6 0.0 14.00 ---- Rect. Yes Galv Rect


ST3-5 22.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SR5-13 1 4.00 0

ST2-7 0.0 23.00 ---- Rect. Yes Galv Rect


ST2-6 22.0 1,650 ---- 0.00 0 0.00050
EF 0.0 SR5-13 1 4.00 0

ST2-8 0.0 12.62 ---- Rect. Yes Galv Rect


ST2-7 22.0 1,650 ---- 0.00 0 0.00050
EF 0.0 1 4.00 0

D:\ ...\CONTROL ROOM duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 6

System 1 "PACU 05 & 06" - Trunk Input Data - Return


Trunk Dia Length Fit 1 #Fit Shape Active Material Ref.
Ups. Hei Max.Vel Fit 2 #Fit Add.Loss Take Off Roughness
SM Wid Junc fit #Fit R-Value Per.Div
RT3-1 0.0 9.40 CR9-4 1 Rect. Yes Galv Rect
FAN 22.0 1,650 ---- 0.00 0 0.00050
EF 0.0 ER5-3 1 4.00 0

RT3-2 0.0 38.86 CR3-1 5 Rect. Yes Galv Rect


RT3-1 22.0 1,650 CR9-4 1 0.00 0 0.00050
EF 0.0 1 4.00 0
Fit 3 CR9-5 1

D:\ ...\CONTROL ROOM duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 7

System 1 "PACU 05 & 06" - Runout Input Data - Supply


Runout Dia Length Fit 1 #Fit Shape Active Material Ref.
Ups. Hei Max.Vel Fit 2 #Fit Add.Loss Take Off Roughness
SM Wid Fit 3 #Fit R-Value NC Level Dif.Loss
SCD3-1 0.0 1.64 CR9-4 1 Rect. Yes Galv Rect
ST3-1 0.0 500 ---- 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SCD3-2 0.0 12.62 CR9-4 1 Rect. Yes Galv Rect


ST3-2 0.0 500 ---- 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SCD3-3 0.0 1.64 CR9-4 1 Rect. Yes Galv Rect


ST3-3 0.0 500 ---- 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SCD3-4 0.0 12.62 CR9-4 1 Rect. Yes Galv Rect


ST3-4 0.0 500 ---- 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SCD3-5 0.0 1.64 CR9-4 1 Rect. Yes Galv Rect


ST3-5 0.0 500 ---- 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SCD3-6 0.0 12.62 CR9-4 1 Rect. Yes Galv Rect


ST2-6 0.0 500 ---- 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SCD3-7 0.0 1.62 CR9-4 1 Rect. Yes Galv Rect


ST2-7 0.0 500 ---- 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

SCD3-8 0.0 8.20 CR3-1 1 Rect. Yes Galv Rect


ST2-8 0.0 500 CR9-4 1 0.00 0 0.00050
EF 0.0 ---- 2.00 30 0.080

D:\ ...\CONTROL ROOM duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 8

System 1 "PACU 05 & 06" - Runout Input Data - Return


Runout Dia Length Fit 1 #Fit Shape Active Material Ref.
Ups. Hei Max.Vel Fit 2 #Fit Add.Loss Take Off Roughness
SM Wid Fit 3 #Fit R-Value NC Level Grille.Loss
RAG3-1 0.0 19.68 ---- Rect. Yes Galv Rect
RT3-2 0.0 500 CR9-4 0.00 0 0.00050
EF 0.0 ---- 2.00 30 0.080

FAD-1 0.0 4.92 CR9-4 2 Rect. Yes Galv Rect


RT3-1 0.0 500 ---- 0.00 90 0.00050
EF 0.0 ---- 2.00 30 0.080

D:\ ...\CONTROL ROOM duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 9

System 1 "PACU 05 & 06" - Trunk Output Data - Supply


Fit Sect1 Sect2 Cumul Press
------ ------ ------ ------ ------
Trunk Dia SM L/100 Shape Ups.Sh Equip Dynam Vel.P Veloc
Upstr Hei TOA Reg Fit.1 Qty Coef Loss Add.L Fric Stat Stat
Vel Wid Gau Fit.2 Qty Coef Loss F.Tot Total Total Total
CFM Len Ref Mat Ups.Junc Coef Loss Dynam
ST3-1 28.4 EF 0.080 Rect N/A 0.000 1.381 0.000 0.117
FAN 22.0 0 0.000 *CR3-1 3 1.180 0.121 0.000 0.054 1.434 0.180
1,398 32.0 22 CR9-5 1 0.460 0.047 1.381 1.434 1.434 0.297
6,152 67.3 Galv Rect 1.381
Fit.3: CR9-4 1 0.520 0.053
Fit.4: CR3-6 1 0.340 0.035

ST3-2 26.2 EF 0.085 Rect Rect 0.000 0.038 0.004 0.113


ST3-1 22.0 0 -0.034 CR3-6 1 0.340 0.034 0.000 0.012 1.481 0.133
1,376 26.0 22 ---- 0.038 0.050 1.484 0.247
5,151 14.0 Galv Rect SR5-13-MN 0.043 0.004 0.038

ST3-3 25.1 EF 0.070 Rect Rect 0.000 0.005 0.030 0.087


ST3-2 22.0 0 0.021 ---- 0.000 0.010 1.470 0.144
1,208 24.0 22 ---- 0.005 0.015 1.499 0.232
4,150 14.0 Galv Rect *SR5-13-MN 0.068 0.005 0.005

ST3-4 22.9 EF 0.080 Rect Rect 0.000 0.003 0.030 0.088


ST3-3 20.0 0 -0.003 ---- 0.000 0.011 1.484 0.130
1,209 22.0 22 ---- 0.003 0.014 1.513 0.218
3,458 14.0 Galv Rect SR5-13-MN 0.038 0.003 0.003

ST3-5 20.7 EF 0.085 Rect Rect 0.000 0.003 0.033 0.084


ST3-4 18.0 0 0.000 ---- 1 0.000 0.012 1.495 0.119
1,184 20.0 24 ---- 0.003 0.015 1.529 0.203
2,766 14.0 Galv Rect SR5-13-MN 0.046 0.003 0.003

ST2-6 18.5 EF 0.085 Rect Rect 0.000 0.004 0.043 0.074


ST3-5 16.0 0 0.006 ---- 0.000 0.012 1.502 0.113
1,111 18.0 24 ---- 0.004 0.016 1.545 0.186
2,074 14.0 Galv Rect SR5-13-MN 0.060 0.004 0.004

ST2-7 16.4 EF 0.075 Rect Rect 0.000 0.005 0.064 0.053


ST2-6 14.0 0 0.016 ---- 0.000 0.017 1.503 0.111
942 16.0 24 ---- 0.005 0.022 1.567 0.165
1,382 23.0 Galv Rect SR5-13-MN 0.101 0.005 0.005

ST2-8 13.1 EF 0.065 Rect Rect 0.000 0.004 0.084 0.033


ST2-7 12.0 0 0.016 ---- 0.000 0.008 1.494 0.120
738 12.0 24 ---- 0.004 0.012 1.579 0.152
691 12.6 Galv Rect SR5-13-MN 0.156 0.004 0.004

* Loss coefficient for indicated fitting is from the boundary of the table since one or more of the parameters used to
look up the coefficient was outside the range of the table.
Explanation of Values in Rightmost Five Columns Above
Column Description
"Fit": "Loss" = Static pressure loss through the indicated fitting.
"Sect1": "Equip" = User-entered loss through central equipment (supply main trunk only).
"Add.L" = User entered additional static pressure loss.
"F.Tot" = Total of all the fitting static pressure losses. For supply main trunk, also includes loss through
central equipment and any loss carried from return system.
"Dynam" = Total of all the dynamic losses, which includes everything but the frictional loss.
"Sect2": "Dynam" = Total of the dynamic losses, carried from bottom of previous column.
"Fric" = Static pressure loss due to the inside surface roughness (friction).
"Total" = Total of the dynamic and friction losses.

D:\ ...\CONTROL ROOM duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 10

System 1 "PACU 05 & 06" - Trunk Output Data - Supply (cont'd)


Column Description
"Cumul": "Vel.P" = Cumulative loss in velocity pressure. For return, velocity pressure of downstream runout with
highest static pressure minus that of this trunk. For supply, main trunk velocity pressure minus that of
this trunk.
"Stat" = Cumulative loss of static pressure. For return, sum of the loss of all ducts in route starting with
downstream runout with highest static pressure through this trunk. For supply, sum of all upstream trunk
losses plus this trunk's loss.
"Total" = Cumulative velocity pressure loss plus cumulative static pressure loss.
"Press": "Veloc" = Velocity pressure.
"Stat" = Static pressure available. For return, at entrance of duct. For supply, at exit.
"Total" = Velocity pressure plus static pressure available.

D:\ ...\CONTROL ROOM duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 11

System 1 "PACU 05 & 06" - Trunk Output Data - Return


Fit Sect1 Sect2 Cumul Press
------ ------ ------ ------ ------
Trunk Dia SM L/100 Shape Ups.Sh Equip Dynam Vel.P Veloc
Dnstr Hei TOA Reg Fit.1 Qty Coef Loss Add.L Fric Stat Stat
Vel Wid Gau Fit.2 Qty Coef Loss F.Tot Total Total Total
CFM Len Ref Mat Ups.Junc Coef Loss Dynam
RT3-1 28.4 EF 0.080 Rect N/A 0.000 0.053 -0.006 0.117
FAN 22.0 0 0.000 CR9-4 1 0.520 0.053 0.000 0.008 0.881 -0.820
1,398 32.0 22 ---- 0.053 0.061 0.875 -0.703
6,152 9.4 Galv Rect 0.053

RT3-2 27.3 EF 0.080 Rect Rect 0.000 0.699 0.000 0.111


RT3-1 22.0 0 -0.693 *CR3-1 5 1.214 0.119 0.000 0.031 0.826 -0.096
1,362 28.0 22 CR9-4 1 0.520 0.051 0.699 0.730 0.826 0.015
5,537 38.9 Galv Rect *ER5-3-MN 0.100 0.010 0.699
Fit.3: CR9-5 1 0.460 0.045

* Loss coefficient for indicated fitting is from the boundary of the table since one or more of the parameters used to
look up the coefficient was outside the range of the table.
Explanation of Values in Rightmost Five Columns Above
Column Description
"Fit": "Loss" = Static pressure loss through the indicated fitting.
"Sect1": "Equip" = User-entered loss through central equipment (supply main trunk only).
"Add.L" = User entered additional static pressure loss.
"F.Tot" = Total of all the fitting static pressure losses. For supply main trunk, also includes loss through
central equipment and any loss carried from return system.
"Dynam" = Total of all the dynamic losses, which includes everything but the frictional loss.
"Sect2": "Dynam" = Total of the dynamic losses, carried from bottom of previous column.
"Fric" = Static pressure loss due to the inside surface roughness (friction).
"Total" = Total of the dynamic and friction losses.
"Cumul": "Vel.P" = Cumulative loss in velocity pressure. For return, velocity pressure of downstream runout with
highest static pressure minus that of this trunk. For supply, main trunk velocity pressure minus that of
this trunk.
"Stat" = Cumulative loss of static pressure. For return, sum of the loss of all ducts in route starting with
downstream runout with highest static pressure through this trunk. For supply, sum of all upstream trunk
losses plus this trunk's loss.
"Total" = Cumulative velocity pressure loss plus cumulative static pressure loss.
"Press": "Veloc" = Velocity pressure.
"Stat" = Static pressure available. For return, at entrance of duct. For supply, at exit.
"Total" = Velocity pressure plus static pressure available.

D:\ ...\CONTROL ROOM duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 12

System 1 "PACU 05 & 06" - Runout Output Data - Supply


Fit Sect1 Sect2 Cumul Press
Runout Dia SM L/100 Shape Ups.Sh ------ ------ ------ ------ ------
Conn Hei TOA Reg Fit1 Qty Coef Loss Diff. Dynam Vel.P Veloc
Vel Wid Gau Fit2 Qty Coef Loss Add.L Fric Stat Stat
CFM Len Ref Mat Fit3 Qty Coef Loss F.Tot Total Total Total
Orif R.NC Act.NC Ups.Junc Qty Coef Loss Dynam
SCD3-1 19.7 EF 0.015 Rect Rect 0.080 0.214 0.104 0.013
ST3-1 18.0 90 -0.110 CR9-4 1 0.520 0.006 0.000 0.000 1.545 0.069
473 18.0 24 ---- 0.134 0.214 1.649 0.082
1,001 1.6 Galv Rect ---- 0.214
16.70 30 35 SR5-13-BR 1 10.802 0.128

SCD3-2 19.7 EF 0.015 Rect Rect 0.080 0.180 0.104 0.013


ST3-2 18.0 90 -0.080 CR9-4 1 0.520 0.006 0.000 0.002 1.563 0.051
473 18.0 24 ---- 0.100 0.183 1.667 0.064
1,001 12.6 Galv Rect ---- 0.180
17.70 30 30 SR5-13-BR 1 7.955 0.094

SCD3-3 16.4 EF 0.020 Rect Rect 0.080 0.179 0.104 0.013


ST3-3 14.0 90 -0.105 CR9-4 1 0.520 0.006 0.000 0.000 1.575 0.039
472 16.0 24 ---- 0.099 0.179 1.679 0.053
692 1.6 Galv Rect ---- 0.179
16.40 30 30 SR5-13-BR 1 7.814 0.093

SCD3-4 16.4 EF 0.020 Rect Rect 0.080 0.149 0.104 0.013


ST3-4 14.0 90 -0.075 CR9-4 1 0.520 0.006 0.000 0.003 1.561 0.053
472 16.0 24 ---- 0.069 0.152 1.665 0.066
692 12.6 Galv Rect ---- 0.149
14.40 30 30 SR5-13-BR 1 5.305 0.063

SCD3-5 16.4 EF 0.020 Rect Rect 0.080 0.155 0.104 0.013


ST3-5 14.0 90 -0.085 CR9-4 1 0.520 0.006 0.000 0.000 1.580 0.034
472 16.0 24 ---- 0.075 0.155 1.684 0.047
692 1.6 Galv Rect ---- 0.155
16.40 30 30 SR5-13-BR 1 5.814 0.069

SCD3-6 16.4 EF 0.020 Rect Rect 0.080 0.141 0.104 0.013


ST2-6 14.0 90 -0.081 CR9-4 1 0.520 0.006 0.000 0.003 1.585 0.029
472 16.0 24 ---- 0.061 0.144 1.689 0.043
692 12.6 Galv Rect ---- 0.141
16.40 30 30 SR5-13-BR 1 4.651 0.055

SCD3-7 16.4 EF 0.020 Rect Rect 0.080 0.115 0.104 0.013


ST2-7 14.0 90 -0.075 CR9-4 1 0.520 0.006 0.000 0.000 1.578 0.036
471 16.0 24 ---- 0.035 0.116 1.682 0.049
691 1.6 Galv Rect ---- 0.115
16.40 30 30 *SR5-13-BR 1 2.460 0.029

SCD3-8 13.1 EF 0.065 Rect Rect 0.080 0.115 0.084 0.033


ST2-8 12.0 0 -0.115 CR3-1 1 0.687 0.020 0.000 0.005 1.614 0.000
738 12.0 24 CR9-4 1 0.520 0.015 0.035 0.120 1.699 0.033
691 8.2 Galv Rect ---- 0.115
13.10 30 30 1

* Loss coefficient for indicated fitting is from the boundary of the table since one or more of the parameters used to
look up the coefficient was outside the range of the table.
Explanation of Values in Rightmost Five Columns Above
Column Description
"Fit": "Loss" = Static pressure loss through the indicated fitting.

D:\ ...\CONTROL ROOM duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 13

System 1 "PACU 05 & 06" - Runout Output Data - Supply (cont'd)


Column Description
"Sect1": "Dif" = User-entered static pressure loss due to the diffuser.
"Add.L" = User entered additional static pressure loss.
"F.Tot" = Total of all the fitting static pressure losses.
"Dynam" = Total of all the dynamic losses, which includes everything but the frictional loss.
"Sect2": "Dynam" = Total of the dynamic losses, carried from bottom of previous column.
"Fric" = Static pressure loss due to the inside surface roughness (friction).
"Total" = Total of the dynamic and friction losses.
"Cumul": "Vel.P" = Cumulative loss in velocity pressure. For return, zero for each runout. For supply, velocity
pressure of main trunk minus that of this duct.
"Stat" = Cumulative loss of static pressure. For return, this runout's loss. For supply, sum of all upstream
trunk losses plus this runout's loss.
"Total" = Cumulative velocity pressure loss plus cumulative static pressure loss.
"Press": "Veloc" = Velocity pressure.
"Stat" = Static pressure available. For return, at entrance of duct. For supply, at exit.
"Total" = Velocity pressure plus static pressure available.

D:\ ...\CONTROL ROOM duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 14

System 1 "PACU 05 & 06" - Runout Output Data - Return


Fit Sect1 Sect2 Cumul Press
Runout Dia SM L/100 Shape Ups.Sh ------ ------ ------ ------ ------
Conn Hei TOA Reg Fit1 Qty Coef Loss Diff. Dynam Vel.P Veloc
Vel Wid Gau Fit2 Qty Coef Loss Add.L Fric Stat Stat
CFM Len Ref Mat Fit3 Qty Coef Loss F.Tot Total Total Total
Orif R.NC Act.NC Ups.Junc Qty Coef Loss Dynam
RAG3-1 27.3 EF 0.080 Rect Rect 0.080 0.080 0.000 0.111
RT3-2 24.0 0 -0.080 ---- 0.000 0.016 0.096 0.000
1,362 26.0 22 CR9-4 0.000 0.096 0.096 0.111
5,537 19.7 Galv Rect ---- 0.080
27.30 30 35 1

FAD-1 16.4 EF 0.015 Rect Rect 0.080 -0.079 0.000 0.011


RT3-1 14.0 90 0.185 CR9-4 2 0.520 0.005 0.000 0.001 -0.078 -1.004
419 16.0 24 ---- -0.159 -0.078 -0.078 -0.994
615 4.9 Galv Rect ---- -0.079
7.40 30 50 *ER5-3-BR 1 -18.000 -0.168

* Loss coefficient for indicated fitting is from the boundary of the table since one or more of the parameters used to
look up the coefficient was outside the range of the table.
Explanation of Values in Rightmost Five Columns Above
Column Description
"Fit": "Loss" = Static pressure loss through the indicated fitting.
"Sect1": "Dif" = User-entered static pressure loss due to the diffuser.
"Add.L" = User entered additional static pressure loss.
"F.Tot" = Total of all the fitting static pressure losses.
"Dynam" = Total of all the dynamic losses, which includes everything but the frictional loss.
"Sect2": "Dynam" = Total of the dynamic losses, carried from bottom of previous column.
"Fric" = Static pressure loss due to the inside surface roughness (friction).
"Total" = Total of the dynamic and friction losses.
"Cumul": "Vel.P" = Cumulative loss in velocity pressure. For return, zero for each runout. For supply, velocity
pressure of main trunk minus that of this duct.
"Stat" = Cumulative loss of static pressure. For return, this runout's loss. For supply, sum of all upstream
trunk losses plus this runout's loss.
"Total" = Cumulative velocity pressure loss plus cumulative static pressure loss.
"Press": "Veloc" = Velocity pressure.
"Stat" = Static pressure available. For return, at entrance of duct. For supply, at exit.
"Total" = Velocity pressure plus static pressure available.

D:\ ...\CONTROL ROOM duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 15

System 1 "PACU 05 & 06" - Output Summary - Supply


Number of active trunks: 8
Number of active runouts: 8
Total system weight (lb.) minus fittings: 1,974.61
Total outlet flow 6,152
Total outlet flow after heat gain 6,152
Size of largest trunk: 28.4
Size of smallest trunk: 13.1
Size of largest runout: 19.7
Size of smallest runout: 13.1

Maximum static pressure loss occurs in route to runout: SCD3-8


Cumulative static pressure loss at above runout: 1.614

Isolate Return From Supply Option: No


Return SP Loss Added to 1st Trunk of Supply: 0.881
Available static pressure at above runout: 0.000
Fan static pressure: 1.614
Fan velocity pressure: 0.117
Fan total pressure: 1.731

D:\ ...\CONTROL ROOM duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 16

System 1 "PACU 05 & 06" - Output Summary - Return


Number of active trunks: 2
Number of active runouts: 2
Total system weight (lb.) minus fittings: 830.93
Total outlet flow 6,152
Total outlet flow after heat gain 6,152
Size of largest trunk: 28.4
Size of smallest trunk: 27.3
Size of largest runout: 27.3
Size of smallest runout: 16.4

Maximum SP loss occurs in route from runout: RAG3-1


Total SP loss of route starting from above runout: 0.881

Isolate Return From Supply Option: No


Return SP Loss Added to 1st Trunk of Supply: 0.881
Available static pressure at above runout: 0.000
Fan static pressure: -0.881
Fan velocity pressure: 0.117
Fan total pressure: -0.764

D:\ ...\CONTROL ROOM duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 17

System 1 "PACU 05 & 06" - Pressure Changes Graph

Pressure Changes Through Route with Highest Static Pressure Loss

0.9

0.8
E
0.7

0.6

0.5

0.4

0.3

0.2 F
G H I J K L M
Pressure, in.wg

0.1
A
0.0
N
-0.1
B

-0.2

-0.3

-0.4

-0.5

-0.6

-0.7

-0.8
C
-0.9 D

Static Pressure Available


Total Pressure Available
Note: Return side point values are at entrance of duct, while supply side points are at exit. When a return system is
present, an additional return side point named [Fan Entrance] is drawn in the graph to show the static pressure
available at the entrance of the fan. When a supply system is present, and an additional supply side point named [Fan
Exit] is drawn to show the static pressure available at the exit of the fan.
Point Name Static Pressure Available Total Pressure Available
A RAG3-1 0.000 0.111
B RT3-2 -0.096 0.015
C RT3-1 -0.820 -0.703
D [Fan Entrance] -0.881 -0.764
E [Fan Exit] 0.733 0.850
F ST3-1 0.180 0.297
G ST3-2 0.133 0.247
H ST3-3 0.144 0.232
I ST3-4 0.130 0.218
J ST3-5 0.119 0.203
K ST2-6 0.113 0.186
L ST2-7 0.111 0.165
M ST2-8 0.120 0.152
N SCD3-8 0.000 0.033

D:\ ...\CONTROL ROOM duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 18

System 1 "PACU 05 & 06" - Runout Sound Data - Supply


Runout
63 125 250 500 1000 2000 4000 8000 NC
Name
SCD3-1 Required Attenuation 23 29 35 39 42 39 32 28 30
Actual Attenuation 38 36 34 40 47 77 86 95 35
Additional Attenuation 0 0 1 0 0 0 0 0

SCD3-2 Required Attenuation 23 29 35 39 42 39 32 28 30


Actual Attenuation 44 44 48 66 97 119 116 127 30
Additional Attenuation 0 0 0 0 0 0 0 0

SCD3-3 Required Attenuation 23 29 35 39 42 39 32 28 30


Actual Attenuation 48 47 51 68 98 124 118 129 30
Additional Attenuation 0 0 0 0 0 0 0 0

SCD3-4 Required Attenuation 23 29 35 39 42 39 32 28 30


Actual Attenuation 53 52 62 90 143 160 141 152 30
Additional Attenuation 0 0 0 0 0 0 0 0

SCD3-5 Required Attenuation 23 29 35 39 42 39 32 28 30


Actual Attenuation 53 53 63 93 149 165 144 155 30
Additional Attenuation 0 0 0 0 0 0 0 0

SCD3-6 Required Attenuation 23 29 35 39 42 39 32 28 30


Actual Attenuation 58 59 76 118 199 202 169 180 30
Additional Attenuation 0 0 0 0 0 0 0 0

SCD3-7 Required Attenuation 23 29 35 39 42 39 32 28 30


Actual Attenuation 59 59 71 108 178 195 167 178 30
Additional Attenuation 0 0 0 0 0 0 0 0

SCD3-8 Required Attenuation 23 29 35 39 42 39 32 28 30


Actual Attenuation 65 68 87 135 226 294 217 228 30
Additional Attenuation 0 0 0 0 0 0 0 0

D:\ ...\CONTROL ROOM duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 19

System 1 "PACU 05 & 06" - Runout Sound Data - Return


Runout
63 125 250 500 1000 2000 4000 8000 NC
Name
RAG3-1 Required Attenuation 30 36 42 46 49 46 39 35 30
Actual Attenuation 37 36 37 46 58 83 87 98 35
Additional Attenuation 0 0 5 0 0 0 0 0

FAD-1 Required Attenuation 30 36 42 46 49 46 39 35 30


Actual Attenuation 27 26 26 33 47 46 40 41 50
Additional Attenuation 3 10 16 13 2 0 0 0

D:\ ...\CONTROL ROOM duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

Ductsize - HVAC Duct Sizing Elite Software Development, Inc.


pReJkEr Al Shaqra 132/13.8kv Ss#8521
Hell Page 20

Duct Connection Tree Diagram - System 1 - PACU 05 & 06


System 1 - PACU 05 & 06
Supply
ST3-1, EF, Rect, 67.33 ft, SR5-13, 32"x22",
SCD3-1, EF, Rect, 1.64 ft, 1001 CFM, 18"x18",
ST3-2, EF, Rect, 14 ft, SR5-13, 26"x22",
SCD3-2, EF, Rect, 12.62 ft, 1001 CFM, 18"x18",
ST3-3, EF, Rect, 14 ft, SR5-13, 24"x22",
SCD3-3, EF, Rect, 1.64 ft, 692 CFM, 16"x14",
ST3-4, EF, Rect, 14 ft, SR5-13, 22"x20",
SCD3-4, EF, Rect, 12.62 ft, 692 CFM, 16"x14",
ST3-5, EF, Rect, 14 ft, SR5-13, 20"x18",
SCD3-5, EF, Rect, 1.64 ft, 692 CFM, 16"x14",
ST2-6, EF, Rect, 14 ft, SR5-13, 18"x16",
SCD3-6, EF, Rect, 12.62 ft, 692 CFM, 16"x14",
ST2-7, EF, Rect, 23 ft, SR5-13, 16"x14",
SCD3-7, EF, Rect, 1.62 ft, 691 CFM, 16"x14",
ST2-8, EF, Rect, 12.62 ft, (none), 12"x12",
SCD3-8, EF, Rect, 8.2 ft, 691 CFM, 12"x12",
Return
RT3-1, EF, Rect, 9.4 ft, ER5-3, 32"x22",
FAD-1, EF, Rect, 4.92 ft, 615 CFM, 16"x14",
RT3-2, EF, Rect, 38.86 ft, (none), 28"x22",
RAG3-1, EF, Rect, 19.68 ft, 5537 CFM, 26"x24",

D:\ ...\CONTROL ROOM duct sizing.dsw Tuesday, August 13, 2013, 1:29 PM
http://boilersinfo.com/

APPR`D.

SVR

SVR
DRAWING COMPLETION CERTIFICATE (DCC)
CERT`D

DCC NO. _____________ DATE: ______________


AN

AN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF National Grid SA NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D

SAS

SAS
INCORPORATED SEC COMMENTS
ISSUED FOR BASE DESIGN
DESCRIPTION
JOB ORDER NO.

109

109
00 28/05/2013 SATECH

01 13/08/2013 SATECH

APPENDIX-3
BY
DATE
NO.

REVISIONS * Reference Drawings


DRAWN

BY SAS
DATE 13/08/2013
CHECKED

BY SAS
DATE 13/08/2013
OPRG. DEPT.

BY ___________
DATE

ENG`G DEPT.

BY ___________
DATE _______
APPROVAR/CERTF.
INFORMATION

DCC NO. _______


REV. NO. 01 AS BUILT BY _____________ DATE __________ DWG. CONTROL SHT.
DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OR
DESIGN CALCULATIONS OF HVAC SYSTEM
FOR ORDERING
MATERIALS UNTIL
CONSTRUCTION OF 132/13.8KV SUBSTATION B C279 CE-316495 43 OF 43 01
CERTIFIED AND #8521 IN SHAQRA UNIVERSITY
DATED
RIYADH AREA SAUDI ARABIA JOB ORDER NO. 109 CONTRACT NO. 11131153/00
http://boilersinfo.com/
http://boilersinfo.com/
http://boilersinfo.com/
http://boilersinfo.com/

Vous aimerez peut-être aussi