Mr. Michael Colombo


Senior Project Manager
Walbridge Joint Venture
Detroit, Michigan

RE: Limited Hazardous Material & Asbestos Survey Report for the Former Lewis Cass
Technical High School Located at 2421 Second Avenue in Detroit, Michigan
ATC Project No.: 39.33581.1009

Dear Mr. Colombo:


Between May 11, 2010 and May 27, 2010, ATC representatives Mr. Michael Hauswirth and Mr.
Anthony G. Rich, surveyed the former Lewis Cass Technical High School Building located at 2421
Second Avenue in Detroit, Michigan for potential hazardous materials/equipment that may require
special handling and disposal prior to demolition of the building. The scope of work for this survey
included the identification, locations, and quantities of the following materials: asbestos-containing
building materials (ACMs), potential polychlorinated biphenyl (PCB) containing electrical
equipment, regulated potential construction wastes (mercury vapor lamps, batteries, emergency
lights, smoke detectors, fluorescent light ballasts, mercury switches, and self-illuminating exit
signs).

Outlined below are the materials/equipment that were identified by ATC during the building survey.
ATC has provided a general recommendation for removal/disposal for use by an environmental
contractor for cost projection purposes. The contractor performing the removal/disposal of these
materials is responsible for determining the correct disposal requirements according to applicable
City of Detroit, State of Michigan, and federal regulations for hazardous material disposal.

1.0 Potential Hazardous Materials Identified


1.1 Asbestos Survey
An asbestos building survey was performed at the former Cass Tech High School building
in May of 2010 by ATC personnel that are properly trained, certified and accredited State of
Michigan asbestos building inspectors. The survey involved the original, seven-story school
building with a mechanical penthouse, and a basement. Some concealed materials, such as
inside wall cavities, were accessed and assessed using minimal destructive methods. The
following list is a summary of materials at the original structure that contain asbestos at
concentrations greater than 1% as reported by laboratory sample analyses: straight pipe
insulation (white, chalky, fibrous); straight pipe insulation (lt. beige corrugated layers);
straight pipe insulation (with wood felt inner liner); pipe fitting insulation; transite panels,
laboratory table tops, tar paper, shelf panels, green chalkboards, white auditorium fire
curtain, rope seals and gaskets, 9” x 9” brown floor tile and mastic, 12” x 12”rock pattern
floor tile (mastic negative), 12” x 12” Beige floor tile (mastic negative), 9” x 9” green
spot floor tile (mastic negative), 9” x 9” tan splotch floor tile (mastic negative), mastic on
12” x 12” brown with tan splotch floor tile (tile negative), 9” x 9” tan with red spot floor
tile and mastic, 9” x 9” Beige floor tile (mastic negative), 9” x 9” beige with brown streak
floor tile (mastic negative), 9” x 9” beige with brown spot floor tile and mastic, 9” x 9”
gray with cream streak floor tile and mastic, 9” x 9” brown with cream streak floor tile
(mastic negative), 9” x 9” white with black streak floor (mastic negative), 9” x 9” gray
marble pattern floor tile and mastic, 12” x 12” brown self adhesive floor tile, transite
oven interior, transite tile (auditorium), lighting electrical wrap (auditorium), electrical
panel insulation (library), floor coating (2nd floor auditorium entrance), fire door
insulation (south basement), oven gasket (room 213), duct insulation, tank insulation,
electrical transite panels, electrical cable wrap, electrical panel backer, 1’ x 1’ smooth
ceiling tile glue pod ( 7th floor northeast rooms), 1’ x 1’ ceiling tile glue pod (7 ½ floor-
south room) and the wood sub-floor layer (room 548 and storage room).

Bulk samples of plaster were collected from various locations within the original building
and lab analyses indicated the presence of low concentrations of asbestos in these
materials. Consequently, ATC requested point count analyses for each of the plaster
samples and the point count analyses indicated asbestos concentrations of 1% or less.
Point-counting is a detailed and more labor-intensive technique for estimating asbestos in
a building material when low asbestos concentration in a building material is suspected or
detected and is less subjective than a visual estimate. Samples near or at 1% were
subsequently analyzed using TEM (Transmission Electron Microscopy) and found to be
0.2% Chrysotile.
.
In the western addition, the following materials were found to contain asbestos at
concentrations greater than 1%. Transite panels (1st floor Receiving), and mastic on 12”
x 12” beige splotch floor tile (tile negative).

It should be noted that vandals had damaged or stripped many pipes of their insulation and
appeared to disperse asbestos-containing pipe insulation throughout many areas of the
original structure. Suspect asbestos pipe insulation and other suspect ACMs were also
observed intermixed with other debris that is present throughout the building’s interior.

Due to the identification of “intact” pipe insulation within concealed areas throughout the
structure, including, but not limited to: within wall cavities, above fixed ceiling systems, in
and around air-handling equipment, etc., ATC recommends that asbestos abatement
personnel carefully locate all ACMs using cautious survey methods and selective demolition
techniques where applicable.

The asbestos bulk samples were labeled, catalogued, and submitted to APEX Research
Laboratory (APEX) in Whitmore Lake, Michigan, an accredited laboratory by the National
Voluntary Laboratory Accreditation Program (NVLAP) for the identification of asbestos by
polarized-light microscopy method (PLM). PLM is a laboratory analytical method
approved by the US-EPA for bulk asbestos analyses. A summary of data for the materials
sampled, sampling locations, and their respective asbestos content in the original building is
provided in Table 1. A summary of data for the materials sampled, sampling locations, and
their respective asbestos content in the western addition is provided in Table 1A. Laboratory
reports and chain-of-custody forms for the sampled materials are provided in Appendix A.

1.2 Polychlorinated Biphenyl (PCB) Containing Electrical Equipment


Fluorescent light ballasts manufactured prior to 1979 may contain polychlorinated
biphenyls. PCB’s are considered hazardous and are regulated by the Environmental
Protection Agency. Ballasts manufactured after 1979 contain the less hazardous chemical,
DEHP (2-ethylhexyl) phthalate. Under federal law, DEHP is also regulated by the USEPA
under the Resource Conservation and Recovery Act (RCRA). DEHP is listed as a
hazardous substance and should be disposed according to applicable local, state and federal
regulations.

Visual observations for potential PCB-containing electrical equipment were performed


during the building survey and included observations for: fluorescent light ballasts, electrical
switches and transformers. During the site survey, ATC observed the presence of a small,
dry-type electrical transformer within a storage room in the main office suite. Generally,
this ventilated, dry-type of electrical transformer equipment typically contained no liquid
at all and offered a practical alternative to oil-cooled equipment, which were sometimes
prone to high maintenance, leakage, and potential PCB hazards for many users. ATC did
not observe suspect staining or residue associated with the transformer, however the
cover was not removed to assess the interior components for safety purposes. ATC
recommends that additional assessment of the transformer unit be conducted once
electrical service has been officially verified to be disconnected.

Pertaining to fluorescent light fixture ballasts, it was observed that the fixtures contained
either one or sometimes more ballasts per fixture. Therefore, based on the quantity of light
fixtures observed within the former Cass Tech School Building, ATC estimates that there
are approximately 6,174 fluorescent light ballasts in the building. Approximately two-thirds
of the randomly selected ballasts evaluated were labeled as “non-PCB-containing”, while
the remainder had no markings regarding the PCB content of the ballasts.

The fluorescent light ballasts should be removed from their fixtures carefully, inspected for
the presence of PCB’s, and placed into steel drums for disposal at a facility that accepts
hazardous waste regardless of the presence of PCB’s.

In addition to the fluorescent light ballasts, various oil-filled electrical equipment was
observed in the mechanical areas of the structure. This electrical equipment may contain
PCB oils that will require special handling and disposal methods.

1.3 Mercury Vapor Lamps


Fluorescent lamps and certain high-intensity discharge (HID) lamps are the two most
common types of lamps that utilize mercury. Approximately 11,990 fluorescent light
bulbs of various configurations were observed throughout the structure. There were
approximately 613 - 8’ fluorescent bulbs, 11,266 – 4’ bulbs, 3 - 8’ “U”-shaped bulbs, 17 –
4’ “U” shaped bulbs, 41 – 2’ bulbs, 20 compact fluorescent bulbs, and 30 – 6’ bulbs.
Fluorescent light bulbs are considered hazardous waste (“Universal Waste”) and cannot be
disposed in dumpsters or household waste landfills. Additionally, ATC observed
approximately 56 HID lamps (gym, pool & auditorium), which can also include mercury-
vapor. Due to the mercury content in fluorescent, mercury vapor and other lamps and lamp
fragments, the United States Environmental Protection Agency (EPA) recommends
recycling of lamps and lamp components.

The fluorescent and HID lamps should be removed from their fixtures carefully, placed into
fiber drums or adequately protective boxes, and disposed at a facility that accepts hazardous
waste or sent to a specialized reclamation facility for recycling.

1.4 Mercury-Containing Equipment, Switches, and Thermostats


Equipment control switches and thermostats containing ampoules of elemental mercury are
common in older buildings. ATC personnel documented the presence of equipment control
switches and thermostats in the building. Numerous thermostats were observed within the
former Cass Tech building. The thermostats may or may not contain mercury switches, as
the covers were not removed from all of the observed units to determine the type of switches
that are present within each thermostat. However, none of the randomly-selected
thermostats that were evaluated had mercury-containing ampoules inside the thermostats.

ATC inspectors noted the presence of “Mercoid” switches in the northeast basement
mechanical area, as well as some small mercury thermometers (Room 311) and urinometers
(Room 313). ATC observed a small graduated cylinder of elemental mercury and a piece of
laboratory equipment containing metallic mercury. Each of these mercury-containing
devices was staged in the southwest fourth floor science storage room.

1.5 Self-Illuminating Exit Signs and Emergency Lighting


ATC observed no (0) self-illuminating exit signs within the building. The limited number
exit signs that were observed appeared to be electrically sourced. Based on the visual
survey, it appears that the signs have either high-efficiency light-emitting diodes (LEDs)
or compact fluorescent lamps. Compact fluorescent lamps contain mercury and lead and
are best handled by recycling at end of life (to capture their recoverable metal content)
through a licensed hazardous waste handler. Emergency exit signs are also required by
law to have rechargeable batteries or other backup systems in case of a power outage.
Many rechargeable batteries used in exit signs contain cadmium, lead, or other metals
that can make the batteries hazardous waste, and may be recycled through qualified firms
such as the Rechargeable Battery Recycling Corp. A total of eight (8) exit signs with
battery backup were observed in various locations of the structure. These types of exit
signs should be removed and disposed at a facility that accepts hazardous waste as
necessary.

Emergency lighting devices are also designed with rechargeable battery systems in the
event of a power outage or other similar building emergency. The types of rechargeable
batteries utilized in emergency lighting equipment often contain sealed, lead-acid power
units that result in the batteries being classified as hazardous waste and require
specialized handling, transport, and reclamation/disposal. No self-illuminating signs and
eight exit signs attached to battery backup devices were observed at the time of the
survey; however, more may be discovered during remediation of the site. ATC
recommends that any emergency lighting batteries identified at the site be removed
through a licensed hazardous waste handler for proper disposal or recycling as necessary.

1.6 Smoke Detectors


ATC observed no smoke detectors within the building. The most common type of smoke
detector is an ionization detector, which contains a small amount (2 micro-Curies) of
Americium-241, a synthetic isotope which emits both alpha and gamma rays. Although
no smoke detectors were observed in the building, it is possible that smoke detectors may
be discovered during abatement of the facility and if radioactive smoke detectors are
found, ATC recommends that these units, where identified, be removed and disposed as
hazardous waste at a facility that accepts radioactive waste.

2.0 Other
In addition to the materials/equipment noted above, other potentially hazardous miscellaneous
materials were observed in the former school buildings. It should be noted that debris piles were
observed throughout the building interior and some of the potentially hazardous materials were
intermingled with the debris. These debris piles were not disturbed to determine their specific
content, but some of the miscellaneous materials observed in the debris piles included: computer
monitors and circuit boards, televisions, empty chemical containers, aerosol paints, paint and
thinner cans, chewing gum and graffiti remover, fire extinguishers, refrigerators, lubricants and
grease, art supplies (glues, paints & inks), soaps and detergents, and copier toner. In addition,
small quantities of laboratory chemicals and mercury containing devices were found in various
locations of the building.

LIMITATIONS
This report is prepared for the express use and benefit of DPS, its agents and employees. The
information in this report or portions thereof may be required to be included in notifications to
employees, contractors or other visitors to the buildings. This report is not intended to be used by
the owner or its agents as a specification or work plan for any of the work suggested or
recommended in the report. This report is based upon conditions observed at the property and
information made available to the surveyor on the above-mentioned dates. This report does not
intend to identify all hazards, or to indicate that other hazards do not exist at the premises. ATC
made their best effort to determine the location of inaccessible ACBMs and other potentially
hazardous materials. ATC shall not be responsible for identifying all ACBMs or other hazardous
materials located in inaccessible building locations, including but not limited to areas limited by
excessive accumulated obstructions, structurally unsafe, etc. If material is found during the
course of demolition that is not listed in this report, the material should be assumed as asbestos-
containing or hazardous until it can be sampled and analyzed at an accredited laboratory.
TABLES
Table 1
Bulk Asbestos Sample Summary Table
Former Lewis Cass Technical High School Building
2421 Second Avenue, Detroit, MI
Approximate
Sample HA Material
HA Locations Total Results
Designation # Description
Quantity
“Mag” pipe
insulation straight
40% Chrysotile
1-PI-A, B, C 1 Throughout Building (white, fibrous) 21,360 LF
10% Amosite
(includes pipe
fittings)
Throughout Building “Air Cell” pipe
insulation straight
2-PI-A, B, C 2 4,100 LF 50% Chrysotile
(includes pipe
fittings)
Throughout Building “Duplex” pipe
insulation straight
3-PI-A, B, C 3 3,600 LF NAD
(includes pipe
fittings)
Throughout Building Cork pipe insulation
4-PI-A, B, C 4 Undetermined NAD
straight
Throughout Building Wool felt pipe
insulation straight
98-PI-A, B, C 98 4,200 LF NAD-20% Chrysotile
(includes pipe
fittings)
7th Floor north mechanical
5-GK-A, B, C 5 Gasket material Undetermined NAD
room
Mechanical
7th floor, north mechanical
6-MI-A, B, C 6 insulation (air Undetermined NAD
room
handler)
Spray-applied
7-SM-A, B, C 7 Rooms 449, 231, 343 Undetermined NAD
fireproofing
Rooms 111, 211, 213, 311,
Transite panels in
8-TP-A, B, C 8 313, 323, 423, 427, 523, 533, 870 SF 40% Chrysotile
fume hoods
546,627
Rooms 111, 133, 211, 213, Laboratory table
9-TT-A, B, C 9 223, 227, 311, 313, 323, 427, tops (specific 1, 947 SF 30% Chrysotile
527, 622, 627 rooms)
10-TTP-A, B, Rooms 211 and 213 (under
10 Tarpaper 60 SF 10% Chrysotile
C stainless steel table tops)

11-SP-A, B, C 11 Room 213 storage room Shelf panels 12 SF 40% Chrysotile

12-GCB-A, B,
12 Rooms 227, 311, 313 Green chalkboards 180 SF 30% Chrysotile
C
13-BCB-A, B,
13 Classrooms Black chalkboards Undetermined NAD
C
Black glue pods on
14-GP-A, B, C 14 Rooms 662 and 664 Undetermined NAD
chalkboards
6th floor east hallway, Rooms Tan glue pods on
15-GP-A, B, C 15 Undetermined NAD
241, 242, 243, 245, and 331 chalkboards
Table 1
Bulk Asbestos Sample Summary Table
Former Lewis Cass Technical High School Building
2421 Second Avenue, Detroit, MI
Approximate
Sample HA Material
HA Locations Total Results
Designation # Description
Quantity
16-WF-A, B, Wood flooring in
16 Classrooms Undetermined NAD
C classrooms
17-WF-A, B, Wood flooring in old
17 Old gym Undetermined NAD
C gym
18-WF-A, B, Wood flooring in 7th
18 7th floor gym Undetermined NAD
C floor gym
19-WF-A, B, Flooring paper (under
19 Room 243 Undetermined NAD
C wood floor)
Room 101restroom, rooms Brown flooring
20-FS-A, B, C 20 Undetermined NAD
623-646 sheeting
4” black baseboard
Rooms 101, 131, 241,
21-BB-A, B, C 21 molding and Undetermined NAD/NAD
“Attendance Center”
adhesive
Main office, rooms 123, 231,
243, 246, 245, 247, 248, 331, 6” Brown baseboard
22-BB-A, B,C 22 Undetermined NAD/NAD
341, 343, 347, 348, 715, 712, molding and adhesive
719, 723
6” Black baseboard
23-BB-A, B, C 23 Room 219 Undetermined NAD/NAD
molding and adhesive
6” Brown baseboard
24-BB-A, B, C 24 Room 601 Undetermined NAD/NAD
molding and adhesive
Blue baseboard molding
25-BB-A, B, C 25 Room 725 Undetermined NAD/NAD
and adhesive
White fire curtain
26-FC-A, B, C 26 Auditorium 1, 000 SF 60% Chrysotile
(auditorium)
Red fire curtain
27-FC-A, B, C 27 Auditorium Undetermined NAD
(auditorium)
Black fire curtain
28-FC-A, B, C 28 Auditorium Undetermined NAD
(auditorium)
29-WC-A, B, Rooms 246, 346, and 7 th floor Interior window
29 Undetermined NAD
C old kitchen caulk
30-WL-A, B,
30 Rooms 246, 327, and 407 “Slate” window ledge Undetermined NAD
C
31-EW-A, B, 2nd, 3rd, and 6th floor hallways, Electrical wiring
31 Undetermined NAD
C room 641 insulation
32-TWP-A, B, Rooms 715, 717, 719, 723,
32 Textured paint Undetermined NAD
C 725, and 7 ½ floor
Pink sink
33-SU-A, B, C 33 Rooms 113, 123, and 311 Undetermined NAD
undercoating
Rooms 113, 123, 219, 248,
331A, 356, 601, 715, 719,
Drywall systems
723, 725, “Attendance
34-DS-A, B, C 34 (wallboard, tape, Undetermined NAD (all layers)
Center”, men’s and women’s
joint compound)
restrooms, 2nd floor south
hallway
35-PL-A, B, Plaster ceiling NAD –skim coat
35 Throughout original structure Undetermined
C, D, E, F, G (multiple layers) TEM - 0.02%
Table 1
Bulk Asbestos Sample Summary Table
Former Lewis Cass Technical High School Building
2421 Second Avenue, Detroit, MI
Approximate
Sample HA Material
HA Locations Total Results
Designation # Description
Quantity
36-PL-A, B, Plaster walls NAD-Skim coat
36 Throughout original structure Undetermined
C, D, E, F, G (multiple layers) TEM 0.02%-Basecoat
Decorative plaster
37-PL-A, B,
37 Auditorium (multiple layers in Undetermined NAD (all layers)
C, D, E
auditorium)
38-SCM-A, B,
38 Room 147 Mezzanine Stucco ceiling Undetermined NAD
C
39-PB-A, B, Throughout old building in
39 “Pyroblock” Undetermined NAD
C, D, E wall cavities
40-FBM-A, B, Fireplace brick
40 Room 113 Undetermined NAD
C mortar
41-WI-A, B, C 41 Main Office Wall insulation Undetermined NAD
Drain pipe fitting
42-PJ-A, B, C 42 Room 431 60 LF NAD-20% Chrysotile
insulation
Paper Fire door
43-FD-A, B, C 43 Room 227 Undetermined NAD
insulation
44-CG-A, B, C 44 Rooms 231, 243, and 247 Carpet glue Undetermined NAD
45-UM-A, B, Underlayment
45 Room 349 Undetermined NAD
C material (in bucket)
46-PP-A, B, C 46 Room 621 Patching plaster Undetermined NAD
Rope, packings, and
47-RGK-A, B,
47 Basement gaskets (in boxes 100 LF 50% Chrysotile
C
and equipment)
2’ x 4’ heavy fissure
48-CP-A, B, C 48 Rooms 113 and 245 Undetermined NAD
pattern ceiling panels
Rooms 101, 103, 107, 113,
123, 131, 133, 2 nd floor south
2’ x 4’ fissure pattern
49-CP-A, B, C 49 hallway, 3rd floor hallway, 7th Undetermined NAD
ceiling panels
floor northeast room,
“Attendance Center”
12” x 12” large hole
NAD-Tiles
50-CT-A, B, C 50 Room 101 pattern ceiling tiles and Undetermined
NAD-Glue pods
glue pods
2’ x 4’ large fissure
51-CP-A, B, C 51 Room 101 Undetermined NAD
pattern ceiling panels
2’ x 2’ fissure pattern
52-CP-A, B, C 52 Main office Undetermined NAD
ceiling panels
12” x 12” Small
NAD-tiles
53-CT-A, B, C 53 Main office groove pattern ceiling Undetermined
NAD-Glue pods
tiles and glue pods
2’ x 4’ slash/gash
54-CP-A, B, C 54 Security office Undetermined NAD
pattern ceiling panels
2’ x 2’ slash/gash
55-CP-A, B, C 55 Drafting room Undetermined NAD
pattern ceiling panels
2’ x 2’
56-CP-A, B, C 56 1st floor hallway Fissure/pinhole Undetermined NAD
pattern ceiling panels
Table 1
Bulk Asbestos Sample Summary Table
Former Lewis Cass Technical High School Building
2421 Second Avenue, Detroit, MI
Approximate
Sample HA Material
HA Locations Total Results
Designation # Description
Quantity
2’ x 4’ Pinhole
57-CP-A, B, C 57 Rooms 227 and 242 Undetermined NAD
pattern ceiling panels
Rooms 231, 241, 242, 243,
2’ x 2’ heavy fissure
58-CP-A, B, C 58 246, 248, 331, 342, 343, 346, Undetermined NAD
pattern ceiling panels
347, and 348
2’ x 2’ slash/gash
East, west and north 2nd floor
59-CP-A, B, C 59 with pinhole pattern Undetermined NAD
hallways
ceiling panels
2’ x 2’ Rough surface
60-CP-A, B, C 60 Room 341 Undetermined NAD
ceiling panels
2’ x 2’ Slash and
61-CP-A, B, C 61 3rd floor north hallway pinhole pattern Undetermined NAD
ceiling panels
12” x 12” slash/gash
NAD-Tile
62-CT-A, B, C 62 6th floor hallways pattern ceiling tiles Undetermined
NAD-Glue pods
and glue pods
12” x 12” smooth NAD-Tile
63-CT-A, B,
63 7th floor –northeast rooms surface ceiling tiles 3, 000 SF Glue pods-10%
C
and glue pods Chrysotile
7th Floor, northeast corner 2’ x 4’ Fissure ceiling
64-CP-A, B, C 64 Undetermined NAD
room-old building panels
12” x 12”
Pinhole/slash pattern NAD-Tile
65-CT-A, B, C 65 7th Floor hallways Undetermined
ceiling tiles and glue NAD-Glue pods
pods
2’ x 2’ Pinhole/slash
66-CP-A, B, C 66 7th Floor, East hallway Undetermined NAD
pattern ceiling panels
Rooms 111, 113, 123, 213, 12” x 12” Beige
NAD-Tile
67-FT-A, B, C 67 223, 225, and 644, Security splotch floor tile and Undetermined
NAD-Mastic
Office, Tech Office mastic
12” x 12” Blue floor NAD-Tile
68-FT-A, B, C 68 Room 111 Undetermined
tile and mastic NAD-Mastic
9” x 9” Brown floor 5% Chrysotile-Tile
69-FT-A, B, C 69 Room 111 85 SF
tile and mastic 2% Chrysotile-Mastic
12” x 12” Rock pattern 2% Chrysotile-Tile
70-FT-A, B, C 70 Room 101 432 SF
floor tile and mastic NAD-Mastic
nd
Room 101, 2 floor south 12” x 12” Beige 2% Chrysotile-Tile
71-FT-A, B, C 71 695 SF
hall floor tile and mastic NAD-Mastic
9” x 9” Green spot 10% Chrysotile-Tile
72-FT-A, B, C 72 Area under auditorium 800 SF
floor tile and mastic NAD-Mastic
9” x 9” Tan splotch 10% Chrysotile-Tile
73-FT-A, B, C 73 Area under auditorium 160 SF
floor tile and mastic NAD-Mastic
12” x 12” Green floor NAD-Tile
74-FT-A, B, C 74 Main Office Undetermined
tile and mastic NAD-Mastic
12” x 12” Green
Security Office, rooms 323, NAD-Tile
75-FT-A, B, C 75 splotch floor tile and Undetermined
627, and 643 NAD-Mastic
mastic
Table 1
Bulk Asbestos Sample Summary Table
Former Lewis Cass Technical High School Building
2421 Second Avenue, Detroit, MI
Approximate
Sample HA Material
HA Locations Total Results
Designation # Description
Quantity
Rooms 131, 356, 425, 501,
527, 531, 7 th floor print 12” x 12” Brown
NAD-Tile
76-FT-A, B, C 76 room, 833 and rooms at with tan splotch 3, 634 SF
2% Chrysotile-Mastic
north auditorium stairs 2 nd floor tile and mastic
floor
9” x 9” Tan with red
2% Chrysotile-Tile
77-FT-A, B, C 77 Room 131 and 133 spot floor tile and 1,240 SF
2% Chrysotile-Mastic
mastic
12” x 12” Gray
NAD-Tile
78-FT-A, B, C 78 Drafting room, 227, and 627 splotch floor tile and Undetermined
NAD-Mastic
mastic
12” x 12” Black floor NAD-Tile
79-FT-A, B, C 79 Drafting room, 241 Undetermined
tile and mastic NAD-Mastic
Drafting room, Rooms 211,
9” x 9” Beige floor 5% Chrysotile-Tile
80-FT-A, B, C 80 213, 311,423, 427, 523, 527 7, 221 SF
tile and mastic NAD-Mastic
and 533
9” x 9” Beige with
2% Chrysotile-Tile
81-FT-A, B, C 81 Room above pool, Room 627 brown streak floor 344 SF
NAD-Mastic
tile and mastic
9” x 9” Beige with
5% Chrysotile-Tile
82-FT-A, B, C 82 Room 223 and 323 brown spot floor tile 170 SF
5% Chrysotile-Mastic
and mastic
12” x 12” Light beige
Rooms 242, 246, 248, 323, NAD-Tile
83-FT-A, B, C 83 splotch floor tile and Undetermined
343, 348, and 643 NAD-Mastic
mastic
9” x 9” Gray with
5% Chrysotile-Tile
84-FT-A, B, C 84 Room 311 and 313 cream streak floor 1,016 SF
5% Chrysotile-Mastic
tile and mastic
85-FT-A, B, C 85 Room 315-Library Brown linoleum Undetermined NAD
86-FT-A, B, C 86 Room 315 office Gray Linoleum Undetermined NAD
12” x 12” Beige with
Rooms 715, 717, 719, 723 and NAD-Tile
87-FT-A, B, C 87 brown streak floor Undetermined
727 NAD-Mastic
tile and mastic
12” x 12” Beige with
NAD-Tile
88-FT-A, B, C 88 Room behind room 202 brown streak floor Undetermined
NAD-Mastic
tile and mastic
9” x 9” Brown with
North auditorium stairs 5% Chrysotile-Tile
89-FT-A, B, C 89 cream streak floor tile 160 SF
(room off 2 nd floor) NAD-Mastic
and mastic
12” x 12” Blue
NAD-Tile
90-FT-A, B, C 90 2nd floor “Attendance Center” splotch floor tile and Undetermined
NAD-Mastic
mastic
9” x 9” White with
5% Chrysotile-Tile
91-FT-A, B, C 91 Room 413 shelf black streak floor 50 SF
NAD-Mastic
tile and mastic
9” x 9” Gray marble
5% Chrysotile-Tile
92-FT-A, B, C 92 Room 458 pattern floor tile 200 SF
5% Chrysotile-Mastic
and mastic
Table 1
Bulk Asbestos Sample Summary Table
Former Lewis Cass Technical High School Building
2421 Second Avenue, Detroit, MI
Approximate
Sample HA Material
HA Locations Total Results
Designation # Description
Quantity
12” x 12” Brown
93-FT-A B, C 93 Room 561 self adhesive floor 120 SF 2% Chrysotile-Tile
tile
7th Floor southeast storage Floor leveling
94-FT-A, B, C 94 Undetermined NAD
room material
Black acoustical tile NAD-Tile
95-CT-A, B, C 95 Room 500 Undetermined
and adhesive NAD-Adhesive
NAD-Tile
96-CT-A, B, 12” x 12” Ceiling
96 7 ½ floor- south room 1, 600 SF 10 % Chrysotile-
C tile and adhesive
Adhesive
Gray lab table top
97-TT-A, B, C 97 Room 627 Undetermined NAD
and sink
99-FB-A, B, C 99 Auditorium Fire blanket Undetermined NAD
100-TRO-A, Transite oven
100 Room 546 6 SF 40% Chrysotile
B, C material
101-TRT-A,
101 Room 546 Transite tile 30 SF 40% Chrysotile
B, C
102-HVA, B, South mechanical rooms (2nd, HVAC vibration
102 Undetermined NAD
C 3rd, 4th floors) dampener fabric
103-PB-A, B,
103 Room 226 Pegboard Undetermined NAD
C
104-CP-A, B, Panels above drop
104 Room 241 Undetermined NAD
C ceiling panels
105-FS-A, B,
105 Old gym Track flooring Undetermined NAD
C
106-CM-A, B,
106 Old gym Tar paper on ceiling Undetermined NAD
C
107-FS-A, B,
107 6th floor south, room 646 Dark brown flooring Undetermined NAD
C
Throughout old building in
108-BM-A, B,
108 wall cavities in rooms and Pyroblock mortar Undetermined NAD
C, D, E
hallways
109-EW-A, B, Lighting electrical
109 Area under auditorium 6 lights 70% Chrysotile
C wrap
110-EI-A, B, Electrical panel
110 Library 12 SF 50% Chrysotile
C insulation debris
111-TNK-A,
111 8th floor tank room Water tank insulation Undetermined NAD
B, C
112-FC-A, B, 2nd floor Auditorium
112 Floor coating 100 SF 2% Chrysotile
C entrance
113-DS-A, B,
113 2nd floor mechanical room Duct sealant Undetermined NAD
C
114-WGL-A, Interior window
114 Rooms 556 and 559 Undetermined NAD
B, C glazing (partition)
115-FD-A, B,
115 Southeast basement Fire door insulation 5 doors (105 SF) 30% Chrysotile
C
Table 1
Bulk Asbestos Sample Summary Table
Former Lewis Cass Technical High School Building
2421 Second Avenue, Detroit, MI
Approximate
Sample HA Material
HA Locations Total Results
Designation # Description
Quantity
2nd floor NW stairs, 1 st floor
116-MRM-A,
116 east main entrance, 5th floor Marble mortar Undetermined NAD
B, C
south-central stairs
117-OGK-A,
117 Room 213 mezzanine level Oven gasket 2 SF 70% Chrysotile
B, C
118-PPI-A, B, Plenum pipe
118 Basement hot and cold decks 8,000 LF 70% Chrysotile
C insulation
119-DI-A, B,
119 South, central basement Duct insulation 600 SF 70% Chrysotile
C
120-TI-A, B,
120 North portion of basement Tank Insulation 300 SF 40% Chrysotile
C
121-TI-A, B, North, central portion of Tank Insulation
121 Undetermined NAD-Both layers
C basement (cork)
122-ETR-A, Throughout basement, 3rd
122 Electrical transite 200 SF 40% Chrysotile
B, C floor, east main hallway
123-CWR-A, Basement Transformer Electrical cable
123 30 SF 60% Chrysotile
B, C rooms wrap insulation
Northeast and southeast
124-EPB-A, Electrical panel
124 basement and 3rd floor 50 CF 20% Chrysotile
B, C backer
debris
125-AUC-A, Auditorium ceiling
125 Auditorium Undetermined NAD
B, C cloth
NAD-Adhesive
126-WFL-A, Wood floor adhesive
126 Room 548 and storage room 550 SF 5% Chrysotile-
B, C and sublayers
Sublayers
127-CBI-A, B, Ceiling batt
127 Auditorium Undetermined NAD
C insulation
NAD-Skim coat
128-PL-A, B, Auditorium balcony ceiling, Wall and Ceiling
128 28,800 SF Trace -0.2% Chrysotile-
C, D, E, F, G north, south, east walls plaster (2 layers)
Basecoat
12” x 12” Beige with
129-FT-A, B, NAD-Tile
129 Central basement brown streak floor Undetermined
C NAD-Mastic
tile and mastic
130 130 NA NA Undetermined No Samples submitted
131-WT-A, B,
131 Rooms 662 and 664 Cork wall tiles Undetermined NAD
C
Table 1A
Bulk Asbestos Sample Summary Table
Former Lewis Cass Technical High School Building Addition
2421 Second Avenue, Detroit, MI
Approximate
Sample HA Material
HA Locations Total Results
Designation # Description
Quantity
A1-CP-A, B, 2’ x 4’ 2 size pinhole
A1 Kitchen (New) Undetermined NAD
C pattern ceiling panels
A2-CP-A, B, 2’ x 2’ Rough surface
A2 Cafeteria (New) Undetermined NAD
C ceiling panels
A3-CP-A, B, 2’ x 2’ fissure pattern
A3 Pool Area Undetermined NAD
C ceiling panels
A4-CP-A, B, 2’ x 4’ fissure pattern
A4 Locker room office Undetermined NAD
C ceiling panels
12” x 12” Light gray NAD-Tile
A5-FT-A, B, C A5 Hallways, cafeteria Undetermined
floor tile and mastic NAD-Mastic
12” x 12” Dark gray NAD-Tile
A6-FT-A, B, C A6 1st floor hallway Undetermined
floor tile and mastic NAD-Mastic
12” x 12” Beige
A7-FT-A, B, NAD-Tile
A7 7th floor hallway splotch floor tile and 200 SF
C 5% Chrysotile-Mastic
mastic
Brown with tan speck NAD-Tile
A8-FS-A, B, C A8 Stairway Undetermined
sheet flooring NAD-Mastic
Stair tread covering NAD-Stair tread
A9-ST-A, B, C A9 Stairway Undetermined
and adhesive NAD-Adhesive
A10-SR-A, B, Stair riser covering <1% Chrysotile-Riser
A10 Stairway Undetermined
C and adhesive NAD-Adhesive
A11-FS-A, B,
A11 Stage hallway Brown sheet flooring Undetermined NAD
C
A12-FT-A, B, 12” x 12” Green floor NAD-Tile
A12 Elevator Undetermined
C tile and mastic NAD-Mastic
A13-CG-A, B,
A13 Classrooms, music room Carpet glue Undetermined NAD
C
A14-WF-A, B,
A14 Gym, dance studio Wood flooring Undetermined NAD
C
A15-BB-A, B, Black baseboard NAD-Baseboard
A15 Room 087 Undetermined
C molding and adhesive NAD-Adhesive
A16-CB-A, B,
A16 Classrooms, music area Black chalkboard Undetermined NAD
C
A17-GP-A, B,
A17 Classrooms, music area Chalkboard glue pods Undetermined NAD
C
A18-FC-A, B,
A18 Music stage Black fire curtain Undetermined NAD
C
A19-FC-A, B,
A19 Music stage Orange fire curtain Undetermined NAD
C
A20-DS-A, B,
A20 Hallways, locker rooms Wallboard system Undetermined NAD
C
A21-PL-A, B,
A21 Locker room, shower area Plaster ceiling Undetermined NAD
C
A22-PJ-A, B, Basement mechanical room,
A22 Pipe fitting insulation Undetermined NAD
C 8th floor mechanical room
A23-TP-A, B, 1st floor Receiving area
A23 Transite panels 200 SF 35% Chrysotile
C above transformer room
Table 1A
Bulk Asbestos Sample Summary Table
Former Lewis Cass Technical High School Building Addition
2421 Second Avenue, Detroit, MI
Approximate
Sample HA Material
HA Locations Total Results
Designation # Description
Quantity
A24-DI-A, B, Textured duct
A24 7th floor mechanical room Undetermined NAD
C insulation coating
A25-DI-A, B,
A25 8th floor mechanical room Duct insulation Undetermined NAD
C
A26-DM-A,
A26 Room 455 Duct mastic Undetermined NAD
B, C
A27-SFP-A, Spray-applied
A27 Basement through 8 th floors Undetermined NAD
B, C fireproofing
A28-EPL-A,
A28 Exterior entrance Plaster overhang Undetermined NAD (both layers)
B, C
A29-WG-A, Basement room 087 showcase,
A29 Window glazing Undetermined NAD
B, C cafeteria
A30-FT-A, B, Dark brown splotch NAD-Tile
A30 Child Care room Undetermined
C floor tile and mastic NAD-Mastic
TABLE 2
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL BUILDING (ORIGINAL BUILDING)
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
1 LIT Basement Southern basement 4' 16 each FL Bulbs Mercury vapors
2 Ballasts Basement Southern basement NA 8 each FL Ballasts PCBs
3 Chem Basement Southern basement 1 gallon 2 gallons Oil Chemicals
4 Chem Basement Southern basement Small 1 cyl Unidentified gas cylinder Chemicals
5 Chem Basement Freight elevator area 15 gallon 1 gallons Compressor oil Chemicals
6 Chem Basement Southern basement NA 1 NA Mercury gauge Chemicals
7 Paint Basement Southern basement 1 gallon 1 gallons Urethane finish Chemicals
8 LIT Basement Southern basement 4' 24 each FL Bulbs Mercury vapors
9 Ballasts Basement Southern basement NA 12 each FL Ballasts PCBs
10 Paint Basement Southern basement 1 gallon 2.5 gallons Misc paints Chemicals
11 Chem Basement Southern basement 1 gallon 2.5 gallons Degreaser Chemicals
12 Freezer Basement Southern basement NA 1 each Freezer Freon, oils
13 Chem Basement South boiler room 1 gallon 3 each Hydrochloric acid Chemicals
14 Chem Basement South boiler room 1 gallon 1 each Oil Chemicals
15 Chem Basement South boiler room 1 gallon 1 each Paint Chemicals
Basement bulb and ballast
16 LIT Basement storage room 4' 150 each FL bulbs Mercury vapors
Basement bulb and ballast
17 Ballasts Basement storage room NA 100 each FL Ballasts PCBs
Basement bulb and ballast
18 Chem Basement storage room 55 gallon 6 drums Unlabeled chemicals Undetermined
Basement bulb and ballast
19 LIT Basement storage room 4' 20 each FL Bulbs Mercury vapors
20 LIT Basement Engineer's office 4' 4 each FL Bulbs Mercury vapors
21 Ballasts Basement Engineer's office NA 2 each FL Ballasts PCBs
22 Monitors Basement Engineer's office NA 3 each TV/Computer monitors Metals
23 Aerosol can Basement Engineer's office 15 oz. 1 each Aerosol can Chemicals
24 Paint Basement Basement storage room 1 quart 10 each Various paints Chemicals
25 Aerosol can Basement Basement storage room 15 oz. 2 each Aerosol can Chemicals
Basement chemical storage
26 Paint Basement room 1 gallon 50 Cans Various paints Chemicals
Basement chemical storage
27 Chem Basement room 5 gallon 4 buckets Oil cans (buckets) Chemicals
Basement chemical storage
28 Chem Basement room Box 20 boxes Soda acid Chemicals
Basement chemical storage
29 Chem Basement room 5 gallon 1 buckets Iodine sanitizer Chemicals
30 LIT Basement Basement break room 4' 3 each FL Bulbs Mercury vapor
31 Ballasts Basement Basement break room NA 3 each FL Ballasts PCBs

ATC Associates Inc. 6


TABLE 2
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL BUILDING (ORIGINAL BUILDING)
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
32 Chem Basement Northeast basement NA 4 each Mercury switches (Mercoid) Chemicals
33 LIT Basement Power distribution room 8' 4 each FL Bulbs Mercury vapors
34 LIT Basement Southeast telephone room 8' 7 each FL Bulbs Mercury vapors
35 Ballasts Basement Southeast telephone room NA 2 each FL Ballasts PCBs
36 LIT Basement Southeast hallway 8' 14 each FL Bulbs Mercury vapors
37 Ballasts Basement Southeast hallway NA 9 each FL Ballasts PCBs
38 Chem Basement Southeast hallway NA 2 each Mercury thermometers Elemental mercury
39 Chem Basement Southeast hallway 5 gallon 7 gallons Waste oil Chemicals
40 Transformer Basement Southeast hallway NA 1 each Transformer Chemicals
41 Transformer Basement South Transformer room NA 4 each Old transformers Chemicals
42 Transformer Basement South Transformer room NA 6 each New transformers Chemicals
South transformer room
43 Ballasts Basement storage NA 106 each FL Ballasts PCBs
South transformer room
44 LIT Basement storage 8' 30 each FL Bulbs Mercury vapors
45 LIT Basement Southwest storage room 8' 100 each FL Bulbs Mercury vapors
46 Ballasts Basement Southwest storage room NA 40 each FL Ballasts PCBs
47 Chem Basement Plumbing-Maintenance room 5 gallon 1 each Waste oil Chemicals
48 Chem Basement Basement stairwell cyl 1 each Oxygen cylinder Compressed gas
49 LIT Basement Basement stairwell 8' 1 each FL Bulbs Mercury vapors
50 Chem Basement Steel storage-machine shop 5 gallon 2 each Spindle oil Chemicals
51 Chem Basement West hallway 5 gallon 2 each Dust Away Chemicals
52 Chem Basement West hallway 5g 1 each 150 wt oil Chemicals
53 LIT Basement West hallway 4' 10 each FL Bulbs Mercury vapors
54 Chem Basement West hallway 1 gallon 2 each State 999 #20748 Chemicals
55 Chem Basement West hallway 1 gallon 2 each Paint Chemicals
56 Chem Basement West hallway 5 gallon 1 each Paint (urethane) Chemicals
57 LIT Basement West hallway 4' "U-shape" 10 each FL Bulbs Mercury vapors
58 LIT Basement West hallway 6' 30 each FL Bulbs Mercury vapors
59 LIT 1 1st floor east stairwell 4' 65 each FL Bulbs Mercury vapor
60 Ballasts 1 1st floor east stairwell NA 32 each FL Ballasts PCBs
61 LIT 1 1st floor southeast entrance 4' 8 each FL Bulbs Mercury vapor
62 Ballasts 1 1st floor southeast entrance NA 4 each FL Ballasts PCBs
63 LIT 1 North hallway 4' 52 each FL Bulbs Mercury Vapor
64 Ballasts 1 North hallway NA 26 each FL Ballasts PCBs
65 LIT 1 East hallway 4' 132 each FL Bulbs Mercury Vapor
66 Ballasts 1 East hallway NA 66 each FL Ballasts PCBs

ATC Associates Inc. 7


TABLE 2
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL BUILDING (ORIGINAL BUILDING)
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
67 LIT 1 South hallway 4' 68 each FL Bulbs Mercury Vapor
68 Ballasts 1 South hallway NA 34 each FL Ballasts PCBs
69 LIT 1 1st floor main entrance 4' 4 each FL Bulbs Mercury Vapor
70 Ballasts 1 1st floor main entrance NA 2 each FL Ballasts PCBs
71 LIT 1 1st floor entrance B Compact 1 each Compact FL bulb Mercury Vapor
72 LIT 1 1st floor entrance B1 Compact 2 each Compact FL bulb Mercury Vapor
73 LIT 1 1st floor entrance F1 Compact 1 each Compact FL bulb Mercury Vapor
74 Paint 1 Stairwell off F1 1 gallon 10 gallons Paint Chemicals
75 Chem 1 Stairwell off F1 1 qt. 2 quart Rubber cement Chemicals
76 Chem 1 Stairwell off F1 5 gal. 5 gallons Gym floor finish Chemicals
77 Chem 1 Stairwell off F1 5 gal. 10 gallons Acoustic tile mastic Chemicals
1st floor northwest corner
78 LIT 1 stairwell 4' 28 each FL Bulbs Mercury Vapor
1st floor northwest corner
79 Ballasts 1 stairwell NA 14 each FL Ballasts PCBs

80 LIT 1 1st floor main center stairwell 4' 42 each FL Bulbs Mercury Vapor

81 Ballasts 1 1st floor main center stairwell NA 21 each FL Ballasts PCBs


82 LIT 1 1st floor southeast stairwell 4' 42 each FL Bulbs Mercury Vapor
83 Ballasts 1 1st floor southeast stairwell NA 21 each FL Ballasts PCBs

84 LIT 1 1st floor north auditorium stairs 4' 7 each FL Bulbs Mercury Vapor

85 Chem 1 1st floor north auditorium stairs 1/2 gal 1/2 gal gallons Wood stain Chemicals

86 LIT 1 1st floor north men's restroom 4' 6 each FL Bulbs Mercury Vapor

87 Ballasts 1 1st floor north men's restroom NA 3 each FL Ballasts PCBs


88 LIT 1 Room 101 4' 24 each FL Bulbs Mercury Vapor
89 Ballasts 1 Room 101 NA 12 each FL Ballasts PCBs
90 LIT 1 Room 103 4' 32 each FL Bulbs Mercury Vapor
91 Ballasts 1 Room 103 NA 16 each FL Ballasts PCBs
92 Monitors 1 Room 103 NA 1 each TV/Computer monitors Metals
93 LIT 1 Room 107 4' 32 each FL Bulbs Mercury Vapor
94 Ballasts 1 Room 107 NA 16 each FL Ballasts PCBs
95 Monitors 1 Room 107 NA 1 each TV/Computer monitors Metals
96 LIT 1 Room 109 4' 32 each FL Bulbs Mercury Vapor

ATC Associates Inc. 8


TABLE 2
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL BUILDING (ORIGINAL BUILDING)
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
97 Ballasts 1 Room 109 NA 16 each FL Ballasts PCBs
98 LIT 1 Room 111 4' 88 each FL Bulbs Mercury Vapor
99 Ballasts 1 Room 111 NA 44 each FL Ballasts PCBs
100 Monitors 1 Room 111 NA 1 each TV/Computer monitors Metals
101 LIT 1 Room 113 4' 16 each FL Bulbs Mercury Vapor
102 Ballasts 1 Room 113 NA 8 each FL Ballasts PCBs
103 Monitors 1 Room 113 NA 5 each TV/Computer monitors Metals
104 Chem 1 Room 113 1 qt. 1 quart Paint thinner Chemicals
105 LIT 1 Room 113 8' 18 each FL Bulbs Mercury Vapor
106 Ballasts 1 Room 113 NA 9 each FL Ballasts PCBs
107 Printers 1 Room 113 NA 4 each Printers Metals
108 Computers 1 Room 113 NA 6 each Computers Metals
109 LIT 1 Main office 4' 120 each FL Bulbs Mercury Vapor
110 Ballasts 1 Main office NA 60 each FL Ballasts PCBs
111 Monitors 1 Main office NA 6 each TV/Computer monitors Metals
112 Computers 1 Main office NA 4 each Computers Metals
113 Printers 1 Main office NA 3 each Printers Metals
114 Chem 1 Main office NA 1 each Window air conditioner unit Freon, oils
115 LIT 1 Room 123 4' 74 each FL Bulbs Mercury Vapor
116 Ballasts 1 Room 123 NA 37 each FL Ballasts PCBs
117 Printers 1 Room 123 NA 4 each Printers Metals
118 Computers 1 Room 123 NA 2 each Computers Metals
119 Monitors 1 Room 123 NA 4 each TV/Computer monitors Metals
120 LIT 1 1st floor east hallway 4' 18 each FL Bulbs Mercury Vapor
121 Ballasts 1 1st floor east hallway NA 9 each FL Ballasts PCBs
122 LIT 1 1st floor east custodial closet Compact 1 each Compact FL bulb Mercury Vapor
123 Chem 1 1st floor east custodial closet 5 gal. 5 gallons Mop treatment Chemicals

124 Chem 1 1st floor east custodial closet 5 gal. 5 gallons Glass cleaner Chemicals
125 LIT 1 1st floor east hall security 4' 6 each FL Bulbs Mercury Vapor
126 Ballasts 1 1st floor east hall security NA 3 each FL Ballasts PCBs
127 LIT 1 Room 127 4' 40 each FL Bulbs Mercury Vapor
128 Ballasts 1 Room 127 NA 20 each FL Ballasts PCBs
129 Monitors 1 Room 127 NA 1 each TV/Computer monitors Metals
130 LIT 1 Room 131 4' 44 each FL Bulbs Mercury Vapor
131 Ballasts 1 Room 131 NA 22 each FL Ballasts PCBs
132 Monitors 1 Room 131 NA 2 each TV/Computer monitors Metals

ATC Associates Inc. 9


TABLE 2
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL BUILDING (ORIGINAL BUILDING)
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
133 Computers 1 Room 131 NA 1 each Computers Metals
134 LIT 1 Room 133 4' 48 each FL Bulbs Mercury Vapor
135 Ballasts 1 Room 133 NA 24 each FL Ballasts PCBs
136 Monitors 1 Room 133 NA 1 each TV/Computer monitors Metals
137 LIT 1 1st floor drafting room 4' 120 each FL Bulbs Mercury Vapor
138 Ballasts 1 1st floor drafting room NA 60 each FL Ballasts PCBs
139 Monitors 1 1st floor drafting room NA 7 each TV/Computer monitors Metals
140 Computers 1 1st floor drafting room NA 6 each Computers Metals
141 Printers 1 1st floor drafting room NA 2 each Printers Metals
142 LIT 1 1st floor south janitor closet 4' 18 each FL Bulbs Mercury Vapor
143 Ballasts 1 1st floor south janitor closet NA 9 each FL Ballasts PCBs
144 LIT 1 1st floor storage room Compact 1 each Compact FL bulb Mercury Vapor
145 Copier 1 1st floor storage room NA 1 each Copier Metals
146 Paint 1 Room 147 1 gallon 50 gallons Misc. paint Chemicals
147 Aerosol cans 1 Room 147 Various 20 each Spray paints Chemicals
148 LIT 1 Auditorium stage NA 12 each HID lamps Metals

149 LIT 1 1st floor "Attendance Center" 4' 104 each FL Bulbs Mercury Vapor

150 Ballasts 1 1st floor "Attendance Center" NA 52 each FL Ballasts PCBs

151 Monitors 1 1st floor "Attendance Center" NA 2 each TV/Computer monitors Metals

152 Copiers 1 1st floor "Attendance Center" NA 1 each Copier Metals

153 Computers 1 1st floor "Attendance Center" NA 1 each Computers Metals

154 Chem 1 1st floor "Attendance Center" 15 oz. 2 each Aerosol cans Chemicals
155 LIT 2 2nd floor men's restroom compact 1 each Compact FL bulbs Mercury Vapor
156 LIT 2 Room 201 4' 32 each FL Bulbs Mercury Vapor
157 LIT 2 Room 201 compact 2 each Compact FL bulbs Mercury Vapor
158 Ballasts 2 Room 201 NA 16 each FL Ballasts PCBs
159 Monitors 2 Room 201 NA 3 each TV/Computer Monitors Metals
160 Computers 3 Room 201 NA 3 each Computers Metals
161 LIT 2 Room 203 4' 16 each FL Bulbs Mercury Vapor
162 Ballasts 2 Room 203 NA 8 each FL Ballasts PCBs
163 Monitors 2 Room 203 NA 1 each TV Metals

ATC Associates Inc. 10


TABLE 2
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL BUILDING (ORIGINAL BUILDING)
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
164 LIT 2 Room 205 4' 22 each FL Bulbs Mercury Vapor
165 Ballasts 2 Room 205 NA 11 each FL Ballasts PCBs
166 Monitors 2 Room 205 NA 1 each TV Metals
167 LIT 2 Room 207 4' 16 each FL Bulbs Mercury Vapor
168 Ballasts 2 Room 207 NA 8 each FL Ballasts PCBs
169 Monitors 2 Room 207 NA 1 each TV Metals
170 LIT 2 Room 209 4' 16 each FL Bulbs Mercury Vapor
171 Ballasts 2 Room 209 NA 8 each FL Ballasts PCBs
172 LIT 2 Room 211 4' 102 each FL Bulbs Mercury Vapor
173 Ballasts 2 Room 211 NA 51 each FL Ballasts PCBs
174 LIT 2 Room 211 2' 2 each FL Bulbs Mercury Vapor
175 Ballasts 2 Room 211 NA 1 each FL Ballasts PCBs
176 Refrigerators 2 Room 211 NA 1 each Refrigerator freon, oils
177 LIT 2 Room 213 4' 58 each FL Bulbs Mercury Vapor
178 Ballasts 2 Room 213 NA 26 each FL Ballasts PCBs
179 LIT 2 Room 213 2' 2 each FL Bulbs Mercury Vapor
180 Computers 2 Room 213 NA 1 each Computers Metals
181 Refrigerators 2 Room 213 NA 2 each Refrigerators Oils, freon
182 Pine oil 2 Room 213 1 gallon 1 each Pine oil Oil
183 Monitors 2 Room 213 NA 2 each TV/computer monitors Metals
184 LIT 2 Room 215 4' 48 each FL Bulbs Mercury Vapor
185 Ballasts 2 Room 215 NA 24 each FL Ballasts PCBs
186 Monitors 2 Room 215 NA 1 each Computer monitor Metals
187 LIT 2 Room 217 4' 32 each FL Bulbs Mercury Vapor
188 Ballasts 2 Room 217 NA 16 each FL Ballasts PCBs
189 Monitors 2 Room 217 NA 1 each TV/Computer Monitors Metals
190 LIT 2 Room 219 4' 48 each FL Bulbs Mercury Vapor
191 Ballasts 2 Room 219 NA 24 each FL Ballasts PCBs
192 Monitors 2 Room 219 NA 1 each TV/Computer Monitors Metals
193 LIT 2 2nd Floor women's restroom 4' 16 each FL Bulbs Mercury Vapor
194 Ballasts 2 2nd Floor women's restroom NA 8 each FL Ballasts PCBs
195 Chem 2 2nd Floor women's restroom 5 gal 2 Gal Floor stripper Chemicals
196 LIT 2 Room 223 4' 78 each FL Bulbs Mercury Vapor
197 Ballasts 2 Room 223 NA 39 each FL Ballasts PCBs
198 Monitors 2 Room 223 NA 1 each TV/Computer Monitors Metals
199 Chem 2 Room 223 2 1 cubic ft Helium lecture bottle Compressed gas

ATC Associates Inc. 11


TABLE 2
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL BUILDING (ORIGINAL BUILDING)
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN

200 LIT 2 2nd floor east custodial closet compact 1 each Compact FL bulbs Mercury Vapor

201 Chem 2 2nd floor east custodial closet 2.5 1 Gal Dust mop treatment Chemicals

202 Paint 2 2nd floor east custodial closet 5 1 Gal Lustre enamel paint Chemicals
203 LIT 2 Room 226 8' 2 each FL Bulbs Mercury Vapor
204 LIT 2 Room 226 4' 4 each FL Bulbs Mercury Vapor
205 Ballasts 2 Room 226 NA 4 each FL Ballasts PCBs
206 Computers 2 Room 226 NA 1 each Computers Metals
207 Printer 2 Room 226 NA 1 each Printer Metals
208 LIT 2 Room 225 4' 32 each FL Bulbs Mercury Vapor
209 Ballasts 2 Room 225 NA 16 each FL Ballasts PCBs
210 Monitors 2 Room 225 NA 2 each TV/Computer Monitors Metals
211 LIT 2 Room 227 4' 66 each FL Bulbs Mercury Vapor
212 Ballasts 2 Room 227 NA 33 each FL Ballasts PCBs
213 LIT 2 Room 231 4' 84 each FL Bulbs Mercury Vapor
214 Ballasts 2 Room 231 NA 42 each FL Ballasts PCBs
215 Monitors 2 Room 231 NA 1 each TV/Computer Monitors Metals
216 LIT 2 Room 241 4' 92 each FL Bulbs Mercury Vapor
217 Ballasts 2 Room 241 NA 46 each FL Ballasts PCBs
218 Computers 2 Room 241 NA 25 each Computers Metals
219 Monitors 2 Room 241 NA 36 each TV/Computer Monitors Metals
220 Printers 2 Room 241 NA 4 each Printer Metals

221 Aerosol paint 2 2nd floor south custodial closet 15 oz. 3 each Spray paint Chemicals

222 LIT 2 2nd floor south custodial closet 4' 2 each FL Bulbs Mercury Vapor

223 Ballasts 2 2nd floor south custodial closet NA 1 each FL Ballasts PCBs

224 Chem 2 2nd floor south custodial closet 1/2 gal 1 Gal Furniture polish Chemicals
225 LIT 2 2nd floor south men's room 4' 16 each FL Bulbs Mercury Vapor
226 Ballasts 2 2nd floor south men's room NA 8 each FL Ballasts PCBs
227 LIT 2 Room 243 4' 76 each FL Bulbs Mercury Vapor
228 Ballasts 2 Room 243 NA 38 each FL Ballasts PCBs
229 LIT 2 Room 242 4' 60 each FL Bulbs Mercury Vapor

ATC Associates Inc. 12


TABLE 2
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL BUILDING (ORIGINAL BUILDING)
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
230 Ballasts 2 Room 242 NA 30 each FL Ballasts PCBs
231 Monitors 2 Room 242 NA 1 each TV/Computer Monitors Metals
232 LIT 2 Room 246 4' 62 each FL Bulbs Mercury Vapor
233 Ballasts 2 Room 246 NA 31 each FL Ballasts PCBs
234 Monitors 2 Room 246 NA 1 each TV/Computer Monitors Metals
235 LIT 2 Room 245 4' 48 each FL Bulbs Mercury Vapor
236 Ballasts 2 Room 245 NA 24 each FL Ballasts PCBs
237 Monitors 2 Room 245 NA 1 each TV/Computer Monitors Metals
238 LIT 2 Room 247 4' 48 each FL Bulbs Mercury Vapor
239 Ballasts 2 Room 247 NA 24 each FL Ballasts PCBs
240 Monitors 2 Room 247 NA 1 each TV/Computer Monitors Metals
241 LIT 2 Room 248 4' 96 each FL Bulbs Mercury Vapor
242 Ballasts 2 Room 248 NA 48 each FL Ballasts PCBs
243 Monitors 2 Room 248 NA 1 each TV/Computer Monitors Metals
244 Chem 2 Room 248 1 gallon 1 each Bleach Chemicals
245 LIT 2 Room 249-mechanical 4' 4 each FL Bulbs Mercury Vapor
246 Ballasts 2 Room 249-mechanical NA 2 each FL Ballasts PCBs
247 LIT 2 2nd floor central hallway 4' 52 each FL Bulbs Mercury Vapor
248 Ballasts 2 2nd floor central hallway NA 26 each FL Ballasts PCBs
249 LIT 2 2nd floor west hallway 4' 36 each FL Bulbs Mercury Vapor
250 Ballasts 2 2nd floor west hallway NA 18 each FL Ballasts PCBs
251 LIT 2 2nd floor north hallway 4' 52 each FL Bulbs Mercury Vapor
252 Ballasts 2 2nd floor north hallway NA 26 each FL Ballasts PCBs
253 LIT 2 2nd floor east hallway 4' 112 each FL Bulbs Mercury Vapor
254 Ballasts 2 2nd floor east hallway NA 56 each FL Ballasts PCBs
255 LIT 2 2nd floor south hallway 4' 76 each FL Bulbs Mercury Vapor
256 Ballasts 2 2nd floor south hallway NA 38 each FL Ballasts PCBs
3rd floor north women's
257 LIT 3 restroom compact 3 each Compact FL bulbs Mercury Vapor
257 LIT 3 Room 301 4' 36 each FL Bulbs Mercury Vapor
258 Ballasts 3 Room 301 NA 18 each FL Ballasts PCBs
259 Monitors 3 Room 301 NA 1 each TV/Computer Monitors Metals
260 Printer 3 Room 301 NA 1 each Printer Metals
261 LIT 3 Room 305 4' 32 each FL Bulbs Mercury Vapor
262 LIT 3 Room 302 4' 16 each FL Bulbs Mercury Vapor
263 Ballasts 3 Room 302 NA 8 each FL Ballasts PCBs
264 Monitors 3 Room 302 NA 1 each TV/computer monitors Metals

ATC Associates Inc. 13


TABLE 2
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL BUILDING (ORIGINAL BUILDING)
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
265 Ballasts 3 Room 305 NA 16 each FL Ballasts PCBs
266 Monitors 3 Room 305 NA 1 each TV/Computer Monitors Metals
267 LIT 3 Room 309 4' 32 each FL Bulbs Mercury Vapor
268 Ballasts 3 Room 309 NA 16 each FL Ballasts PCBs
269 Monitors 3 Room 309 NA 1 each TV/computer monitors Metals
270 Printer 3 Room 309 NA 1 each Printer Metals
271 LIT 3 Room 311 4' 58 each FL Bulbs Mercury Vapor
272 Ballasts 3 Room 311 NA 29 each FL Ballasts PCBs
273 Printer 3 Room 311 NA 1 each Printer Metals
274 Chem 3 Room 311 NA 15 each Small mercury thermometers Mercury
275 LIT 3 Room 311 2' 2 each FL Bulbs Mercury Vapor
276 Ballasts 3 Room 311 NA 1 each FL Ballasts PCBs
277 Monitors 3 Room 311 NA 1 each TV/computer monitors Metals
278 Printer 3 Room 311 NA 1 each Printer Metals
279 LIT 3 Room 313 4' 60 each FL Bulbs Mercury Vapor
280 Ballasts 3 Room 313 NA 30 each FL Ballasts PCBs
281 LIT 3 Room 313 2' 2 each FL Bulbs Mercury Vapor
282 Ballasts 3 Room 313 NA 1 each FL Ballasts PCBs
383 Chem 3 Room 313 NA 4 each Mercury urinometers Mercury
294 LIT 3 Room 315-Library 4' 72 each FL Bulbs Mercury Vapor
285 Ballasts 3 Room 315-Library NA 36 each FL Ballasts PCBs
286 Monitors 3 Room 315-Library NA 23 each TV/computer monitors Metals
287 Computers 3 Room 315-Library NA 10 each Computers Metals
3rd floor east women's
288 LIT 3 restroom 4' 18 each FL Bulbs Mercury Vapor
3rd floor east women's
289 Ballasts 3 restroom NA 9 each FL Ballasts PCBs
3rd floor east women's
290 Chem 3 restroom 1 liter 1 each Paint thinner Chemicals
3rd floor east women's
291 LIT 3 restroom 4' 4 each FL Bulbs Mercury Vapor
292 LIT 3 Room 323 4' 92 each FL Bulbs Mercury Vapor
293 Ballasts 3 Room 323 NA 46 each FL Ballasts PCBs
294 LIT 3 Room 323 2' 4 each FL Bulbs Mercury Vapor
295 Ballasts 3 Room 323 NA 2 each FL Ballasts PCBs
296 LIT 3 Room 323 8' (U-shape) 3 each FL Bulbs Mercury Vapor
297 Monitors 3 Room 323 NA 2 each TV/Computer Monitors Metals

ATC Associates Inc. 14


TABLE 2
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL BUILDING (ORIGINAL BUILDING)
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
298 Paint 3 Room 323 1 gallon 3 gal Paint Chemicals

299 Aerosol paint 3 3rd floor east custodial closet 15 oz. 1 each Spray paint Chemicals
300 LIT 3 Room 325 4' 24 each FL Bulbs Mercury Vapor
301 Ballasts 3 Room 325 NA 12 each FL Ballasts PCBs
302 Monitors 3 Room 325 NA 1 each TV/Computer Monitors Metals
303 LIT 3 Room 327 4' 36 each FL Bulbs Mercury Vapor
304 Ballasts 3 Room 327 NA 18 each FL Ballasts PCBs
305 Copiers 3 Room 327 NA 3 each Copiers Metals
306 Computers 3 Room 327 NA 13 each Computers Metals
307 Monitors 3 Room 327 NA 12 each TV/Computer Monitors Metals
308 LIT 3 Room 331 4' 72 each FL Bulbs Mercury Vapor
309 Ballasts 3 Room 331 NA 36 each FL Ballasts PCBs
310 Aerosol paint 3 Room 331 15 oz. 3 each Spray paint Chemicals
311 Monitors 3 Room 331 NA 2 each TV/Computer Monitors Metals
312 Computers 3 Room 331 NA 1 each Computers Metals
313 Printer 3 Room 331 NA 1 each Printer Metals
314 LIT 3 Room 341 4' 96 each FL Bulbs Mercury Vapor
315 Ballasts 3 Room 341 NA 48 each FL Ballasts PCBs
316 Monitors 3 Room 341 NA 30 each TV/Computer Monitors Metals
317 Computers 3 Room 341 NA 30 each Computers Metals
318 Printers 3 Room 341 NA 4 each Printer Metals
319 Chem 3 Room 341 14.1 oz. 1 cyl Propane fuel Chemicals

320 LIT 3 3rd floor south custodial closet 4' 2 each FL Bulbs Mercury Vapor

321 Ballasts 3 3rd floor south custodial closet NA 1 each FL Ballasts PCBs

322 LIT 3 3rd floor south men's restroom 4' 18 each FL Bulbs Mercury Vapor

323 Ballasts 3 3rd floor south men's restroom NA 9 each FL Ballasts PCBs
324 LIT 3 Room 343 4' 112 each FL Bulbs Mercury Vapor
325 Ballasts 3 Room 343 NA 56 each FL Ballasts PCBs
326 Monitors 3 Room 343 NA 6 each TV/Computer Monitors Metals
327 Printers 3 Room 343 NA 2 each Printer Metals
328 LIT 3 Room 347 4' 60 each FL Bulbs Mercury Vapor
329 Ballasts 3 Room 347 NA 30 each FL Ballasts PCBs

ATC Associates Inc. 15


TABLE 2
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL BUILDING (ORIGINAL BUILDING)
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
330 Copiers 3 Room 347 NA 1 each Copiers Metals
331 Printer 3 Room 347 NA 1 each Printer Metals
332 Refrigerators 3 Room 347 NA 1 each Refrigerator compressor Oil
333 LIT 3 Room 345C 4' 8 each FL Bulbs Mercury Vapor
334 Ballasts 3 Room 345C NA 4 each FL Ballasts PCBs
335 LIT 3 Room 349-mechanical 4' 10 each FL Bulbs Mercury Vapor
336 Ballasts 3 Room 349-mechanical NA 5 each FL Ballasts PCBs
337 LIT 3 Room 348 4' 56 each FL Bulbs Mercury Vapor
338 Ballasts 3 Room 348 NA 28 each FL Ballasts PCBs
339 Computers 3 Room 348 NA 17 each Computers Metals
340 Printers 3 Room 348 NA 5 each Printer Metals
341 Monitors 3 Room 348 NA 13 each TV/Computer Monitors Metals
342 LIT 3 Room 348A 4' 16 each FL Bulbs Mercury Vapor
343 Ballasts 3 Room 348A NA 8 each FL Ballasts PCBs
344 Printers 3 Room 348A NA 1 each Printer Metals
345 Computers 3 Room 348A NA 2 each Computers Metals
346 Monitors 3 Room 348A NA 2 each TV/Computer Monitors Metals
347 LIT 3 Room 346 4' 52 each FL Bulbs Mercury Vapor
348 Ballasts 3 Room 346 NA 26 each FL Ballasts PCBs
349 Monitors 3 Room 346 NA 10 each TV/Computer Monitors Metals
350 Computers 3 Room 346 NA 15 each Computers Metals
351 Copiers 3 Room 346 NA 1 each Copiers Metals
352 LIT 3 Room 342 4' 64 each FL Bulbs Mercury Vapor
353 Ballasts 3 Room 342 NA 32 each FL Ballasts PCBs
354 Monitors 3 Room 342 NA 45 each TV/Computer Monitors Metals
355 Computers 3 Room 342 NA 40 each Computers Metals
356 LIT 3 Room 354 4' 40 each FL Bulbs Mercury Vapor
357 Ballasts 3 Room 354 NA 20 each FL Ballasts PCBs
358 Copiers 3 Room 354 NA 1 each Copiers Metals
359 LIT 3 Room 350 4' 32 each FL Bulbs Mercury Vapor
360 Ballasts 3 Room 350 NA 16 each FL Ballasts PCBs
361 Monitors 3 Room 350 NA 1 each TV/Computer Monitors Metals
362 LIT 3 3rd floor north hallway 4' 56 each FL Bulbs Mercury Vapor
363 Ballasts 3 3rd floor north hallway NA 28 each FL Ballasts PCBs
364 LIT 3 3rd floor east hallway 4' 124 each FL Bulbs Mercury Vapor
365 Ballasts 3 3rd floor east hallway NA 62 each FL Ballasts PCBs

ATC Associates Inc. 16


TABLE 2
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL BUILDING (ORIGINAL BUILDING)
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
366 LIT 3 3rd floor south hallway 4' 76 each FL Bulbs Mercury Vapor
367 Ballasts 3 3rd floor south hallway NA 38 each FL Ballasts PCBs
368 LIT 3 3rd floor center hallway 4' 52 each FL Bulbs Mercury Vapor
369 Ballasts 3 3rd floor center hallway NA 26 each FL Ballasts PCBs
370 LIT 3 3rd floor west hallway 4' 50 each FL Bulbs Mercury Vapor
371 Ballasts 3 3rd floor west hallway NA 25 each FL Ballasts PCBs
372 LIT 4 Room 401 4' 32 each FL Bulbs Mercury Vapor
373 Ballasts 4 Room 401 NA 16 each FL Ballasts PCBs
374 Monitors 4 Room 401 NA 1 each TV/computer monitors Metals
375 LIT 4 Room 403 4' 32 each FL Bulbs Mercury Vapor
376 Ballasts 4 Room 403 NA 16 each FL Ballasts PCBs
377 Monitors 4 Room 403 NA 1 each TV/computer monitors Metals
378 LIT 4 Room 405 4' 32 each FL Bulbs Mercury Vapor
379 Ballasts 4 Room 405 NA 16 each FL Ballasts PCBs
380 Monitors 4 Room 405 NA 1 each TV/computer monitors Metals
381 LIT 4 North women's restroom Compact 2 each Compact FL bulbs Mercury vapors
382 LIT 4 Room 407 4' 32 each FL Bulbs Mercury Vapor
383 Ballasts 4 Room 407 NA 16 each FL Ballasts PCBs
384 Monitors 4 Room 407 NA 1 each TV/computer monitors Metals
385 LIT 4 Room 409 4' 8 each FL Bulbs Mercury Vapor
386 Ballasts 4 Room 409 NA 8 each FL Ballasts PCBs
387 Monitors 4 Room 409 NA 5 each TV/computer monitors Metals
388 Refrigerators 4 Room 409 NA 1 each Refrigerator freon, oils
389 LIT 4 Room 411 4' 48 each FL Bulbs Mercury Vapor
390 Ballasts 4 Room 411 NA 24 each FL Ballasts PCBs
391 Monitors 4 Room 411 NA 1 each TV/Computer Monitors Metals
392 LIT 4 Room 413 4' 32 each FL Bulbs Mercury Vapor
393 Ballasts 4 Room 413 NA 16 each FL Ballasts PCBs
394 Monitors 4 Room 413 NA 1 each TV/Computer Monitors Metals
395 Refrigerators 4 Room 413 NA 1 each Refrigerator freon, oils
396 LIT 4 Room 417 8' 24 each FL Bulbs Mercury Vapor
397 Ballasts 4 Room 417 NA 24 each FL Ballasts PCBs
398 Monitors 4 Room 417 NA 1 each TV/Computer Monitors Metals
399 LIT 4 Room 421 4' 64 each FL Bulbs Mercury Vapor
400 Ballasts 4 Room 421 NA 32 each FL Ballasts PCBs
401 Monitors 4 Room 421 NA 1 each TV/Computer Monitors Metals

ATC Associates Inc. 17


TABLE 2
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL BUILDING (ORIGINAL BUILDING)
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
402 LIT 4 Room 423 2' 25 each FL Bulbs Mercury vapors
403 Ballasts 4 Room 423 NA 25 each FL Ballasts PCBs
404 LIT 4 Room 423 8' 68 each FL Bulbs Mercury vapors
405 Ballasts 4 Room 423 NA 68 each FL Ballasts PCBs
406 Monitors 4 Room 423 NA 1 each TV/Computer Monitors Metals
407 LIT 4 Room 425 4' 48 each FL Bulbs Mercury vapors
408 Ballasts 4 Room 425 NA 24 each FL Ballasts PCBs
409 Monitors 4 Room 425 NA 1 each TV/Computer Monitors Metals
410 Chem 4 Room 425 1 pint 1 each Ethanol Chemicals
411 Chem 4 Room 425 1 quart 2 each Sulfuric acid Chemicals
412 LIT 4 Room 426 4' 8 each FL Bulbs Mercury vapors
413 Ballasts 4 Room 426 NA 4 each FL Ballasts PCBs
414 LIT 4 Room 427 4' 60 each FL Bulbs Mercury vapors
415 Ballasts 4 Room 427 NA 30 each FL Ballasts PCBs
416 Monitors 4 Room 427 NA 1 each TV/Computer Monitors Metals
417 Chem 4 Room 427 NA 1 each Mercury barometer Elemental mercury
418 LIT 4 4th floor east hallway 4' 120 each FL Bulbs Mercury vapors
419 Ballasts 4 4th floor east hallway NA 60 each FL Ballasts PCBs
420 LIT 4 Room 431 4' 74 each FL Bulbs Mercury vapors
421 Ballasts 4 Room 431 NA 36 each FL Ballasts PCBs
422 Chem 4 Room 431 NA 1 each Ni-Cd battery in emergency light Metals
423 Monitors 4 Room 431 NA 15 each TV/Computer Monitors Metals
424 LIT 4 Room 431 4' 88 each FL Bulbs Mercury vapors
425 Ballasts 4 Room 431 NA 44 each FL Ballasts PCBs
426 LIT 4 4th floor men's restroom 4' 16 each FL Bulbs Mercury vapors
427 Ballasts 4 4th floor men's restroom NA 16 each FL Ballasts PCBs
428 LIT 4 Room 443 4' 74 each FL Bulbs Mercury vapors
429 Ballasts 4 Room 443 NA 38 each FL Ballasts PCBs
430 Monitors 4 Room 443 NA 16 each TV/Computer Monitors Metals
431 LIT 4 Room 445 4' 48 each FL Bulbs Mercury vapors
432 Ballasts 4 Room 445 NA 24 each FL Ballasts PCBs
433 LIT 4 Room 447 4' 48 each FL Bulbs Mercury vapors
434 Ballasts 4 Room 447 NA 24 each FL Ballasts PCBs
435 LIT 4 4th floor south hallway 4' 64 each FL Bulbs Mercury vapors
436 Ballasts 4 4th floor south hallway NA 32 each FL Ballasts PCBs
437 LIT 4 Room 449 4' 10 each FL Bulbs Mercury vapors

ATC Associates Inc. 18


TABLE 2
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL BUILDING (ORIGINAL BUILDING)
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
438 Ballasts 4 Room 449 NA 8 each FL Ballasts PCBs
439 Transformer 4 Room 449 NA 1 each Transformer Oil
440 LIT 4 Room 450 4' 32 each FL Bulbs Mercury vapors
441 Ballasts 4 Room 450 NA 16 each FL Ballasts PCBs
442 Monitors 4 Room 450 NA 1 each TV/Computer Monitors Metals
443 LIT 4 Room 452 4' 16 each FL Bulbs Mercury vapors
444 Ballasts 4 Room 452 NA 8 each FL Ballasts PCBs
445 Monitors 4 Room 452 NA 1 each TV/Computer Monitors Metals
446 LIT 4 Room 454 4' 16 each FL Bulbs Mercury vapors
447 Ballasts 4 Room 454 NA 8 each FL Ballasts PCBs
448 Monitors 4 Room 454 NA 1 each TV/Computer Monitors Metals
449 LIT 4 Room 456 4' 16 each FL Bulbs Mercury vapors
450 Ballasts 4 Room 456 NA 8 each FL Ballasts PCBs
451 Monitors 4 Room 456 NA 1 each TV/Computer Monitors Metals
452 LIT 4 Room 458 4' 12 each FL Bulbs Mercury vapors
453 Ballasts 4 Room 458 NA 6 each FL Ballasts PCBs
454 LIT 5 Room 500 8' 6 each FL Bulbs Mercury vapors
455 Ballasts 5 Room 500 NA 6 each FL Ballasts PCBs
456 Chem 5 Room 500 1 liter 8 each Pro Beam lens cleaner Chemicals
457 LIT 5 Room 501 4' 36 each FL Bulbs Mercury vapors
458 Ballasts 5 Room 501 NA 8 each FL Ballasts PCBs
459 LIT 5 Room 503 8' 8 each FL Bulbs Limited access - Mercury vapors
460 Ballasts 5 Room 503 NA 8 each FL Ballasts PCBs
461 LIT 5 Room 505 8' 8 each FL Bulbs Mercury vapors
462 Ballasts 5 Room 505 NA 12 each FL Ballasts PCBs
463 Monitors 5 Room 505 NA 1 each TV/Computer monitors Metals
464 LIT 5 Room 507 8' 8 each FL Bulbs Mercury vapors
465 Ballasts 5 Room 507 NA 12 each FL Ballasts PCBs
466 Monitors 5 Room 507 NA 1 each TV/Computer monitors Metals
467 LIT 5 Room 509 8' 8 each FL Bulbs Mercury vapors
468 Ballasts 5 Room 509 NA 8 each FL Ballasts PCBs
469 Monitors 5 Room 509 NA 1 each TV/Computer monitors Metals
470 LIT 5 Room 511 4' 48 each FL Bulbs Mercury vapors
471 Ballasts 5 Room 511 NA 24 each FL Ballasts PCBs
472 Monitors 5 Room 511 NA 1 each TV/Computer monitors Metals
473 LIT 5 Room 513 8' 28 each FL Bulbs Mercury vapors

ATC Associates Inc. 19


TABLE 2
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL BUILDING (ORIGINAL BUILDING)
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
474 Ballasts 5 Room 513 NA 28 each FL Ballasts PCBs
475 Monitors 5 Room 513 NA 23 each TV/Computer monitors Metals
476 Chem 5 Room 513 storage 1 gallon 2 each Paint Chemicals
477 LIT 5 Room 515 8' 24 each FL Bulbs Mercury vapors
478 Ballasts 5 Room 515 NA 24 each FL Ballasts PCBs
479 Monitors 5 Room 515 NA 1 each TV/Computer monitors Metals
480 LIT 5 Room 519 8' 24 each FL Bulbs Mercury vapors
481 Ballasts 5 Room 519 NA 24 each FL Ballasts PCBs
482 Monitors 5 Room 519 NA 1 each TV/Computer monitors Metals
483 LIT 5 Room 521 4' 64 each FL Bulbs Mercury vapors
484 Ballasts 5 Room 521 NA 32 each FL Ballasts PCBs
485 Monitors 5 Room 521 NA 2 each TV/Computer monitors Metals
486 LIT 5 Room 525 4' 50 each FL Bulbs Mercury vapors
487 Ballasts 5 Room 525 NA 27 each FL Ballasts PCBs
488 Monitors 5 Room 525 NA 2 each TV/Computer monitors Metals
489 Chem 5 Room 525 1 quart 1 each Fehling's solution Chemicals
490 Chem 5 Room 525 1 quart 1 each Bromine solution Chemicals
491 Chem 5 Room 525 1 quart 1 each Cupric Sulfate solution Chemicals
492 Chem 5 Room 525 1 quart 3 each Unknown liquids Chemicals
493 LIT 5 Room 527 4' 48 each FL Bulbs Mercury vapors
494 Ballasts 5 Room 527 NA 48 each FL Ballasts PCBs
495 Monitors 5 Room 527 NA 1 each TV/Computer monitors Metals
496 LIT 5 Room 531 8' 16 each FL Bulbs Mercury vapors
497 Ballasts 5 Room 531 NA 16 each FL Ballasts PCBs
498 Monitors 5 Room 531 NA 1 each TV/Computer monitors Metals
499 Chem 5 Room 531 1 gallon 2 each Paint Chemicals
500 LIT 5 Room 544 8' 32 each FL Bulbs Mercury vapors
501 Ballasts 5 Room 544 NA 32 each FL Ballasts PCBs
502 Monitors 5 Room 544 NA 30 each TV/Computer monitors Metals
503 Chem 5 Room 544 NA 30 each Capacitors Chemicals
504 Chem 5 Room 544 1 gallon 2 each Paint Chemicals
505 Monitors 5 Room 544B NA 5 each TV/Computer monitors Metals
506 LIT 5 Room 544B 8' 16 each FL Bulbs Mercury vapors
507 Ballasts 5 Room 544B NA 16 each FL Ballasts PCBs
508 LIT 5 Room 541 4' 36 each FL Bulbs Mercury vapors
509 Ballasts 5 Room 541 NA 16 each FL Ballasts PCBs

ATC Associates Inc. 20


TABLE 2
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL BUILDING (ORIGINAL BUILDING)
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
510 Monitors 5 Room 541 NA 3 each TV/Computer monitors Metals
511 LIT 5 Room 541 8' 18 each FL Bulbs Mercury vapors
513 Ballasts 5 Room 541 NA 13 each FL Ballasts PCBs
514 LIT 5 Room 543 4' 60 each FL Bulbs Mercury vapors
515 Ballasts 5 Room 543 NA 30 each FL Ballasts PCBs
516 Monitors 5 Room 543 NA 1 each TV/Computer monitors Metals
517 Chem 5 Room 543 1 gallon 1 each Paint Chemicals
518 LIT 5 Room 545 4' 42 each FL Bulbs Mercury vapors
519 Ballasts 5 Room 545 NA 26 each FL Ballasts PCBs
520 LIT 5 Room 546 8' 28 each FL Bulbs Mercury vapors
521 Ballasts 5 Room 546 NA 28 each FL Ballasts PCBs
522 Monitors 5 Room 546 NA 1 each TV/Computer monitors Metals
523 LIT 5 Room 547 4' 99 each FL Bulbs Mercury vapors
524 Ballasts 5 Room 547 NA 81 each FL Ballasts PCBs
525 Monitors 5 Room 547 NA 1 each TV/Computer monitors Metals
526 LIT 5 Science storage room 4' 16 each FL Bulbs Mercury vapors
527 Chem 5 Science storage room NA 1 each Cenco Darimeter Elemental mercury
528 Chem 5 Science storage room 20 ml 1 each Metallic mercury Graduated cylinder of elemental Mercury
529 LIT 5 Southwest corner 8' 8 each FL Bulbs Mercury vapors
530 LIT 5 Room 550 4' 32 each FL Bulbs Mercury vapors
531 Ballasts 5 Room 550 NA 16 each FL Ballasts PCBs
532 Monitors 5 Room 550 NA 1 each TV/Computer monitors Metals
533 LIT 5 Room 552 8' 8 each FL Bulbs Mercury vapors
534 Ballasts 5 Room 552 NA 8 each FL Ballasts PCBs
535 Monitors 5 Room 552 NA 1 each TV/Computer monitors Metals
536 LIT 5 Room 554 4' 24 each FL Bulbs Mercury vapors
537 Ballasts 5 Room 554 NA 12 each FL Ballasts PCBs
538 Monitors 5 Room 554 NA 1 each TV/Computer monitors Metals
539 LIT 5 Room 556 4' 44 each FL Bulbs Mercury vapors
540 LIT 5 5th floor center hallway 4' 44 each FL Bulbs Mercury vapors
541 Ballasts 5 5th floor center hallway NA 22 each FL Ballasts PCBs
542 LIT 5 5th floor hallways 4' 112 each FL Bulbs Mercury vapors
543 Ballasts 5 5th floor hallways NA 56 each FL Ballasts PCBs
544 Monitors 5 Room 558 NA 1 each TV/Computer monitors Metals
545 Chem 5 Room 561 1 gallon 3 each Duoclean solution Chemicals
546 Chem 5 Room 561 1 gallon 4 each All purpose cleaner Chemicals

ATC Associates Inc. 21


TABLE 2
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL BUILDING (ORIGINAL BUILDING)
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
Arrow Aro-Neu all purpose
547 Chem 5 Room 561 1 gallon 3 each cleaner Chemicals
548 Chem 5 Room 561 1 gallon 3 each Spartan glass cleaner Chemicals
549 Chem 5 Room 561 1 gallon 1 each Iodine cleaner sanitizer Chemicals
550 Chem 5 Room 561 1 gallon 5 each Windshield washer solution Chemicals
551 Chem 5 Room 561 1 gallon 1 each Wallglide cleaner Chemicals
552 LIT 6 6th floor women's restroom compact 3 each Compact FL bulbs Mercury vapor
553 LIT 6 Room 601 4' 31 each FL bulbs Mercury vapor
554 Ballasts 6 Room 601 NA 15 each FL ballasts PCBs
555 Monitor 6 Room 601 NA 1 each TV/Computer monitors Metals
556 LIT 6 Room 601 8' 10 each FL bulbs Mercury vapor
557 Computers 6 Room 601 NA 1 each Computers Metals
558 Refrigerator 6 Room 601 NA 1 each Refrigerator Freons, oils
559 LIT 6 Room 603 4' 48 each FL bulbs Mercury vapor
560 Monitor 6 Room 603 NA 1 each TV/Computer monitors Metals
561 Ballasts 6 Room 603 NA 24 each FL ballasts PCBs
562 LIT 6 Room 607 4' 24 each FL bulbs Mercury vapor
563 Ballasts 6 Room 607 NA 12 each FL ballasts PCBs
564 Monitor 6 Room 607 NA 1 each TV/Computer monitors Metals
565 LIT 6 Room 609 4' 36 each FL bulbs Mercury vapor
566 Ballasts 6 Room 609 NA 18 each FL ballasts PCBs
567 Monitor 6 Room 609 NA 1 each TV/Computer monitors Metals
568 LIT 6 Room 611 4' 48 each FL bulbs Mercury vapor
569 Ballasts 6 Room 611 NA 24 each FL ballasts PCBs
570 Monitor 6 Room 611 NA 1 each TV/Computer monitors Metals
571 LIT 6 Room 612 4' 24 each FL bulbs Mercury vapor
572 Ballasts 6 Room 612 NA 12 each FL ballasts PCBs
573 Monitor 6 Room 612 NA 1 each TV/Computer monitors Metals
574 LIT 6 Room 613 4' 40 each FL bulbs Mercury vapor
575 Ballasts 6 Room 613 NA 20 each FL ballasts PCBs
576 Monitor 6 Room 613 NA 2 each TV/Computer monitors Metals
577 Refrigerator 6 Room 613 NA 1 each Refrigerator Freons, oils
578 Chem 6 Room 613 15 oz. 3 each Aerosol cans Chemicals
579 Chem 6 Room 613 1/2 quart 1 each Ammonia Chemicals
580 LIT 6 Room 614 4' 24 each FL bulbs Mercury vapor
581 Ballasts 6 Room 614 NA 12 each FL ballasts PCBs
582 Monitor 6 Room 614 NA 1 each TV/Computer monitors Metals

ATC Associates Inc. 22


TABLE 2
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL BUILDING (ORIGINAL BUILDING)
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
583 LIT 6 Room 616 4' 16 each FL bulbs Mercury vapor
584 Ballasts 6 Room 616 NA 8 each FL ballasts PCBs
585 Monitors 6 Room 616 NA 1 each TV/Computer monitors Metals
586 LIT 6 Room 617 4' 50 each FL bulbs Mercury vapor
587 Ballasts 6 Room 617 NA 25 each FL ballasts PCBs
588 Monitors 6 Room 617 NA 24 each TV/Computer monitors Metals
589 Computers 6 Room 617 NA 6 each Computers Metals
590 LIT 6 Room 618 4' 16 each FL bulbs Mercury vapor
591 Ballasts 6 Room 618 NA 8 each FL ballasts PCBs
592 Monitors 6 Room 618 NA 1 each TV/Computer monitors Metals
593 LIT 6 Room 620 4' 16 each FL bulbs Mercury vapor
594 Ballasts 6 Room 620 NA 8 each FL ballasts PCBs
595 Monitors 6 Room 620 NA 1 each TV/Computer monitors Metals
596 LIT 6 Room 621 4' 52 each FL bulbs Mercury vapor
597 Ballasts 6 Room 621 NA 26 each FL ballasts PCBs
598 Monitors 6 Room 621 NA 2 each TV/Computer monitors Metals
599 Chem 6 Room 621 15 oz. 8 each Aerosol cans Chemicals
600 Chem 6 Room 621 1 pint 1 each Denatured alcohol Chemicals
601 Chem 6 Room 621 1 quart 1 each Rubber cement Chemicals
602 Chem 6 Room 621 1.5 quart 1 each Linseed oil Chemicals
603 LIT 6 Room 622 4' 54 each FL bulbs Mercury vapor
604 Ballasts 6 Room 622 NA 27 each FL ballasts PCBs
605 Monitors 6 Room 622 NA 2 each TV/Computer monitors Metals
6th floor east women's
606 LIT 6 restroom 4' 16 each FL bulbs Mercury vapor
6th floor east women's
607 Ballasts 6 restroom NA 8 each FL ballasts PCBs
6th floor east women's
608 Chem 6 restroom 1/2 gallon 1 each Glass cleaner Chemicals
6th floor east women's
609 Chem 6 restroom 1 gallon 1 each Paint Chemicals
610 LIT 6 Room 623 4' 60 each FL bulbs Mercury vapor
611 Ballasts 6 Room 623 NA 30 each FL ballasts PCBs
612 Monitors 6 Room 623 NA 5 each TV/Computer monitors Metals
613 Computers 6 Room 623 NA 3 each Computers Metals
614 Chem 6 6th floor east janitor closet 1 gallon 1 each Iodine cleanser Chemicals
615 LIT 6 Room 626 4' 8 each FL bulbs Mercury vapor

ATC Associates Inc. 23


TABLE 2
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL BUILDING (ORIGINAL BUILDING)
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
616 Ballasts 6 Room 626 NA 4 each FL ballasts PCBs
617 LIT 6 Room 627 4' 150 each FL bulbs Mercury vapor
618 Ballasts 6 Room 627 NA 75 each FL ballasts PCBs
619 Monitors 6 Room 627 NA 3 each TV/Computer monitors Metals
620 LIT 6 Room 627 2' 4 each FL bulbs Mercury vapor
621 Ballasts 6 Room 627 NA 2 each FL ballasts PCBs
622 LIT 6 Room 631 4' 32 each FL bulbs Mercury vapor
623 Ballasts 6 Room 631 NA 16 each FL ballasts PCBs
624 Monitors 6 Room 631 NA 1 each TV/Computer monitors Metals
625 LIT 6 Room 641 4' 116 each FL bulbs Mercury vapor
626 Ballasts 6 Room 641 NA 58 each FL ballasts PCBs
627 Monitors 6 Room 641 NA 1 each TV/Computer monitors Metals
628 Chem 6 Room 641 1 gallon 2 each Color film developer Chemicals
629 Chem 6 Room 641 1 gallon 1 each Fountain solution concentrate Chemicals
630 Chem 6 Room 641 Various 50 each Printing inks Chemicals
631 LIT 6 Room 643 4' 28 each FL bulbs Mercury vapor
632 Ballasts 6 Room 643 NA 14 each FL ballasts PCBs
633 LIT 6 Room 647 4' 58 each FL bulbs Mercury vapor
634 Ballasts 6 Room 647 NA 29 each FL ballasts PCBs
635 Copiers 6 Room 647 NA 1 each Copier Metals
636 Monitors 6 Room 647 NA 1 each TV/Computer monitors Metals
637 Chem 6 6th floor south storage room 1 gallon 2 each Iodine tincture Chemicals
638 LIT 6 6th floor south janitor closet 8' 7 each FL bulbs Mercury vapor

639 LIT 6 6th floor south men's restroom 4' 16 each FL bulbs Mercury vapor

640 Ballasts 6 6th floor south men's restroom NA 8 each FL ballasts PCBs
6th floor hallway near south
641 Air conditioner 6 men's restroom NA 1 each Air conditioner freon, oils
642 LIT 6 Room 644 4' 56 each FL bulbs Mercury vapor
643 Ballasts 6 Room 644 NA 28 each FL ballasts PCBs
644 Monitors 6 Room 644 NA 12 each TV/Computer monitors Metals
645 Computers 6 Room 644 NA 10 each Computers Metals
646 LIT 6 Room 646 4' 72 each FL bulbs Mercury vapor
647 Ballasts 6 Room 646 NA 36 each FL ballasts PCBs
648 Monitors 6 Room 646 NA 1 each TV/Computer monitors Metals
649 Chem 6 Room 648B 1 gallon 2 each Insecticide Chemicals

ATC Associates Inc. 24


TABLE 2
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL BUILDING (ORIGINAL BUILDING)
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
650 LIT 6 Room 648B Compact 2 each Compact FL bulbs Mercury vapor
651 Chem 6 Room 648B 1 gallon 2 each Oven cleaner Chemicals
652 Chem 6 Room 648B 1 gallon 1 each Cleaning solvent Chemicals
653 Chem 6 Room 648B 1 gallon 10 each Glass cleaner Chemicals
654 Chem 6 Room 648B 1 gallon 2 each Antimicrobial cleaner Chemicals
655 Chem 6 Room 648B 1 gallon 2 each Marble cleaner Chemicals
656 Chem 6 Room 648B 1 gallon 3 each Floor restorer Chemicals
657 LIT 6 Room 650 4' 16 each FL bulbs Mercury vapor
658 Ballasts 6 Room 650 NA 8 each FL ballasts PCBs
659 Monitors 6 Room 650 NA 1 each TV/Computer monitors Metals
660 LIT 6 Room 652 4' 16 each FL bulbs Mercury vapor
661 Ballasts 6 Room 652 NA 8 each FL ballasts PCBs
662 Monitors 6 Room 652 NA 1 each TV/Computer monitors Metals
663 LIT 6 Room 654 4' 16 each FL bulbs Mercury vapor
664 Ballasts 6 Room 654 NA 8 each FL ballasts PCBs
665 Monitors 6 Room 654 NA 2 each TV/Computer monitors Metals
666 LIT 6 Room 656 4' 24 each FL bulbs Mercury vapor
667 Ballasts 6 Room 656 NA 12 each FL ballasts PCBs
668 Monitors 6 Room 656 NA 1 each TV/Computer monitors Metals
669 LIT 6 Room 658 4' 36 each FL bulbs Mercury vapor
670 Ballasts 6 Room 658 NA 18 each FL ballasts PCBs
671 Monitors 6 Room 658 NA 1 each TV/Computer monitors Metals
672 LIT 6 6th floor elevator room 4' 10 each FL bulbs Mercury vapor
673 Ballasts 6 6th floor elevator room NA 2 each FL ballasts PCBs
674 Chem 6 6th floor elevator room 5 gallon 1 each Gym floor finish Chemicals
675 Chem 6 6th floor elevator room 5 gallon 1 each Soluble oil Chemicals
676 Chem 6 6th floor elevator room 1 gallon 1 each Kerosene Chemicals
677 LIT 6 6th floor elevator room 8' 17 each FL bulbs Mercury vapor
678 LIT 6 Old bathroom near room 658 8' 7 each FL bulbs Mercury vapor
679 LIT 6 Old bathroom near room 658 4' 3 each FL bulbs Mercury vapor
680 LIT 6 Room 660 4' 8 each FL bulbs Mercury vapor
681 Ballasts 6 Room 660 NA 4 each FL ballasts PCBs
682 Monitors 6 Room 660 NA 1 each TV/Computer monitors Metals
683 Computers 6 Room 660 NA 1 each Computers Metals
684 LIT 6 Room 662 4' 24 each FL bulbs Mercury vapor
685 Ballasts 6 Room 662 NA 12 each FL ballasts PCBs

ATC Associates Inc. 25


TABLE 2
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL BUILDING (ORIGINAL BUILDING)
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
686 Monitors 6 Room 662 NA 1 each TV/Computer monitors Metals
687 LIT 6 Room 664 4' 24 each FL bulbs Mercury vapor
688 Ballasts 6 Room 664 NA 12 each FL ballasts PCBs
689 Monitors 6 Room 664 NA 1 each TV/Computer monitors Metals
690 LIT 6 6th floor north hallway 8' 13 each FL bulbs Mercury vapor
691 Ballasts 6 6th floor north hallway NA 13 each FL ballasts PCBs
692 LIT 6 6th floor east hallway 8' 35 each FL bulbs Mercury vapor
693 Ballasts 6 6th floor east hallway NA 35 each FL ballasts PCBs
694 LIT 6 6th floor west hallway 8' 16 each FL bulbs Mercury vapor
695 Ballasts 6 6th floor west hallway NA 16 each FL ballasts PCBs
696 LIT 6 6th floor east hallway 4' 70 each FL bulbs Mercury vapor
697 Ballasts 6 6th floor east hallway NA 35 each FL ballasts PCBs
698 Chem 7 7th floor north elevator 1 gallon 2.5 each Oil Chemicals
699 Monitors 7 7th floor northeast corner NA 1 each TV/Computer monitors Metals
700 LIT 7 7th floor northeast corner 4' "U-shape" 7 each FL bulbs Mercury vapor
701 Chem 7 7th floor northeast corner 1 gallon 0.5 gal each Paint Chemicals

702 Chem 7 7th floor east mechanical room 15 oz. 5 each Aerosol cans Chemicals
703 LIT 7 Room 715 4' 36 each FL bulbs Mercury vapor
704 Ballasts 7 Room 715 NA 18 each FL ballasts PCBs
705 LIT 7 Room 717 4' 42 each FL bulbs Mercury vapor
706 Ballasts 7 Room 717 NA 21 each FL ballasts PCBs
707 LIT 7 Room 719 4' 48 each FL bulbs Mercury vapor
708 Ballasts 7 Room 719 NA 24 each FL ballasts PCBs
709 Computers 7 Room 719 NA 1 each Computers Metals
710 Printers 7 Room 719 NA 1 each Printer Metals
711 Monitors 7 Room 719 NA 2 each TV/Computer monitors Metals
712 Chem 7 Room 719 1 gallon 6.5 each Paint Chemicals
713 Chem 7 Room 719 15 oz. 2 each Aerosol cans Chemicals
714 LIT 7 Room 723 4' 44 each FL bulbs Mercury vapor
715 Ballasts 7 Room 723 NA 22 each FL ballasts PCBs
716 LIT 7 Room 725 4' 48 each FL bulbs Mercury vapor
717 Ballasts 7 Room 725 NA 24 each FL ballasts PCBs
718 Monitors 7 Room 725 NA 24 each TV/Computer monitors Metals
719 Computers 7 Room 725 NA 20 each Computers Metals
7th floor former restroom near
720 Chem 7 sealed elevator 5 gallon 1 each Paint Chemicals

ATC Associates Inc. 26


TABLE 2
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL BUILDING (ORIGINAL BUILDING)
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
7th floor former restroom near
721 LIT 7 sealed elevator 4' 21 each FL bulbs Mercury vapor
722 Chem 7 7th floor former kitchen 15 oz. 3 each Aerosol cans Chemicals
723 LIT 7 Room 727 4' 36 each FL bulbs Mercury vapor
724 Ballasts 7 Room 727 NA 18 each FL ballasts PCBs
7th floor east hallway near
725 LIT 7 elevator 4' 8 each FL bulbs Mercury vapor
7th floor east hallway near
726 Ballasts 7 elevator NA 4 each FL ballasts PCBs
727 LIT 7 7th floor east hallway 4' 80 each FL bulbs Mercury vapor
728 Ballasts 7 7th floor east hallway NA 40 each FL ballasts PCBs
729 Chem 7 7th floor east hallway 1 gallon 2 each Paint Chemicals
730 LIT 7 7th floor south hallway 4' 52 each FL bulbs Mercury vapor
731 Ballasts 7 7th floor south hallway NA 26 each FL ballasts PCBs

732 LIT 7.5 7th floor room north of stairwell 4' 40 each FL bulbs Mercury vapor

733 Ballasts 7.5 7th floor room north of stairwell NA 20 each FL ballasts PCBs
734 Ballasts 8 Room 831 NA 18 each FL ballasts PCBs
735 Chem 8 8th floor elevator room 15 oz. 1 each Aerosol cans Chemicals
736 Chem 8 8th floor elevator room 1 gallon 0.5 gal each Oil Chemicals
737 LIT 8 8th floor elevator room 4' 3 each FL bulbs Mercury vapor
738 Ballasts 8 8th floor elevator room NA 1 each FL ballasts PCBs
739 Chem 8 8th floor mechanical room 1 gallon 3 each Oil Chemicals

ATC Associates Inc. 27


TABLE 2A
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL ADDITION
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
740 LIT Basement Basement mechanical room NA 2 each HID bulbs Metals
741 Chem Basement Basement mechanical room 1 Liter 1 each Ortho-tolidine Chemicals
742 Chem Basement Basement mechanical room 1 Liter 1 each Sulfuric Acid Chemicals
743 Air conditioner Basement Basement mechanical room NA 1 each Air conditioner Freon, oils
744 Chem Basement Basement mechanical room NA 30 each Capacitors Chemicals
745 LIT Basement Pool area 4' 8 each FL Bulbs Mercury Vapors
746 Ballasts Basement Pool area NA 4 each FL ballasts PCBs
747 LIT Basement Pool area locker room 4' 100 each FL bulbs Mercury Vapors
748 Ballasts Basement Pool area locker room NA 50 each FL ballasts PCBs
749 LIT Basement Dance studio NA 4 each HID bulbs Metals
750 Monitors Basement Dance studio NA 2 each TV/Computer monitors Metals
751 Copier Basement Dance studio NA 1 each Copier Metals
752 LIT Basement Dance studio 4' 8 each FL bulbs Mercury Vapors
753 Ballasts Basement Dance studio NA 4 each FL ballasts PCBs
754 Chem Basement Dance studio storage room 30 gal drum 30 gallons Floor finish Chemicals
755 LIT Basement Room 087 NA 4 each HID bulbs Mercury Vapors
756 LIT Basement Room 087 4' 6 each FL Bulbs Mercury Vapors
757 Ballasts Basement Room 087 NA 3 each FL ballasts PCBs
758 LIT Basement Basement gym NA 24 each HID bulbs Metals
759 Monitors Basement Basement gym NA 75 each TV/Computer monitors Metals
760 Computers Basement Basement gym NA 50 each Computers Metals
761 LIT Basement Basement gym 4' 8 each FL Bulbs Mercury Vapors
762 Ballasts Basement Basement gym NA 4 each FL ballasts PCBs
763 Refrigerator Basement Basement gym NA 1 each Refrigerator Freon, oils
764 LIT Basement Women's locker room 4' 100 each FL Bulbs Mercury Vapors
765 Ballasts Basement Women's locker room NA 50 each FL ballasts PCBs
766 LIT 1 1st floor new hallway 4' 132 each FL Bulbs Mercury Vapors
767 Ballasts 1 1st floor new hallway NA 66 each FL ballasts PCBs
768 LIT 1 1st floor loading dock-mechanical 4' 62 each FL Bulbs Mercury Vapors
769 Ballasts 1 1st floor loading dock-mechanical NA 31 each FL ballasts PCBs
770 Chem 1 1st floor loading dock-mechanical 15 oz. 1 each Insecticide aerosol Chemicals
771 Computers 1 1st floor loading dock-mechanical NA 1 each Computers Metals
772 Monitors 1 1st floor loading dock-mechanical NA 1 each TV/Computer monitors Metals
773 Copier 1 1st floor loading dock-mechanical NA 1 each Copier Metals
Engineering room near loading
774 LIT 1 dock 4' 70 each FL Bulbs Mercury Vapors
Engineering room near loading
775 Ballasts 1 dock NA 10 each FL ballasts PCBs
Engineering room near loading
776 Computers 1 dock NA 7 each Computers Metals
777 Transformers 1 Transformer room NA 3 each Oil transformers Chemicals
778 LIT 1 Electrical switch room 4' 12 each FL Bulbs Mercury Vapors
779 Ballasts 1 Electrical switch room NA 6 each FL ballasts PCBs

ATC Associates Inc. 1


TABLE 2A
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL ADDITION
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
780 Chem 1 Electrical switch room 1 gallon 2 each Floor sealer Chemicals
781 Chem 1 Electrical switch room 1 gallon 1 each Paint stripper Chemicals
782 Chem 1 Electrical switch room 1 gallon 1 each Disinfectant Chemicals
783 LIT 1 Electrical room 4' 2 each FL Bulbs Mercury Vapors
784 Ballasts 1 Electrical room NA 1 each FL ballasts PCBs
785 LIT 1 1st floor center hallway 4' 42 each FL Bulbs Mercury Vapors
786 Ballasts 1 1st floor center hallway NA 21 each FL ballasts PCBs
787 Refrigerator 1 1st floor center hallway NA 1 each Refrigerator Freon, oils
788 LIT 1 Room 161 4' 86 each FL Bulbs Mercury Vapors
789 Ballasts 1 Room 161 NA 43 each FL ballasts PCBs
790 LIT 1 Room 161 office 4' 16 each FL Bulbs Mercury Vapors
791 Ballasts 1 Room 161 office NA 8 each FL ballasts PCBs
792 LIT 1 Room 165 4' 120 each FL Bulbs Mercury Vapors
793 Ballasts 1 Room 165 NA 60 each FL ballasts PCBs
794 LIT 1 Instrument room 4' 8 each FL Bulbs Mercury Vapors
795 Ballasts 1 Instrument room NA 4 each FL ballasts PCBs
796 LIT 1 New auditorium 4' 6 each FL Bulbs Mercury Vapors
797 Ballasts 1 New auditorium NA 3 each FL ballasts PCBs
798 Monitors 1 New auditorium NA 2 each TV/Computer monitors Metals
799 LIT 1 Room 169 4' 40 each FL Bulbs Mercury Vapors
800 Ballasts 1 Room 169 NA 20 each FL ballasts PCBs
801 LIT 1 Room 173 4' 52 each FL Bulbs Mercury Vapors
802 Ballasts 1 Room 173 NA 26 each FL ballasts PCBs
803 Monitors 1 Room 173 NA 1 each TV/Computer monitors Metals
804 LIT 1 Electrician-Practice hallway 4' 2 each FL Bulbs Mercury Vapors
805 LIT 1 Practice rooms (178-185) 4' 60 each FL Bulbs Mercury Vapors
806 Ballasts 1 Practice rooms (178-185) NA 30 each FL ballasts PCBs
807 LIT 1 Practice hallway 4' 20 each FL Bulbs Mercury Vapors
808 Ballasts 1 Practice hallway NA 10 each FL ballasts PCBs
809 LIT 1 Room 195 4' 52 each FL Bulbs Mercury Vapors
810 Ballasts 1 Room 195 NA 26 each FL ballasts PCBs
811 Monitors 1 Room 195 NA 1 each TV/Computer monitors Metals
812 LIT 1 Piano room 4' 36 each FL Bulbs Mercury Vapors
813 Ballasts 1 Piano room NA 18 each FL ballasts PCBs
814 Monitors 1 Piano room NA 2 each TV/Computer monitors Metals
815 LIT 1 HWP room 4' 36 each FL Bulbs Mercury Vapors
816 Ballasts 1 HWP room NA 18 each FL ballasts PCBs
817 Monitors 1 HWP room NA 1 each TV/Computer monitors Metals
818 LIT 1 Auditorium vestibule 4' 36 each FL Bulbs Mercury Vapors
819 Ballasts 1 Auditorium vestibule NA 18 each FL ballasts PCBs
820 LIT 1 Auditorium vestibule restrooms 4' 4 each FL Bulbs Mercury Vapors
821 Ballasts 1 Auditorium vestibule restrooms NA 2 each FL ballasts PCBs
822 LIT 1 Projection room 4' 16 each FL Bulbs Mercury Vapors

ATC Associates Inc. 2


TABLE 2A
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL ADDITION
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
823 Ballasts 1 Projection room NA 8 each FL ballasts PCBs
824 LIT 1 Projection room storage 4' 8 each FL Bulbs Mercury Vapors
825 Ballasts 1 Projection room storage NA 4 each FL ballasts PCBs
826 LIT 1 M-1 Stairwell 4' 8 each FL Bulbs Mercury Vapors
827 Ballasts 1 M-1 Stairwell NA 4 each FL ballasts PCBs
828 LIT 2 2nd floor hallway 4' 132 each FL Bulbs Mercury Vapors
829 Ballasts 2 2nd floor hallway NA 66 each FL ballasts PCBs
830 LIT 2 Room off 2nd floor cafeteria 4' 40 each FL Bulbs Mercury Vapors
831 Ballasts 2 Room off 2nd floor cafeteria NA 20 each FL ballasts PCBs
832 LIT 2 Men's locker room 4' 6 each FL Bulbs Mercury Vapors
833 Ballasts 2 Men's locker room NA 3 each FL ballasts PCBs
834 LIT 2 Cafeteria tray room 4' 4 each FL Bulbs Mercury Vapors
835 Ballasts 2 Cafeteria tray room NA 2 each FL ballasts PCBs
836 LIT 2 Cafeteria 4' 480 each FL Bulbs Mercury Vapors
837 Ballasts 2 Cafeteria NA 240 each FL ballasts PCBs
838 LIT 2 Kitchen 4' 168 each FL Bulbs Mercury Vapors
839 Ballasts 2 Kitchen NA 84 each FL ballasts PCBs
840 LIT 3 3rd floor hallway 4' 132 each FL Bulbs Mercury Vapors
841 Ballasts 3 3rd floor hallway NA 66 each FL ballasts PCBs
842 LIT 3 3rd floor storage room 4' 4 each FL Bulbs Mercury Vapors
843 Ballasts 3 3rd floor storage room NA 2 each FL ballasts PCBs
844 LIT 3 Room 355 4' 96 each FL Bulbs Mercury Vapors
845 Ballasts 3 Room 355 NA 48 each FL ballasts PCBs
846 Monitors 3 Room 355 NA 2 each TV/Computer monitors Metals
847 LIT 3 3rd floor men's staff restroom 4' 6 each FL Bulbs Mercury Vapors
848 Ballasts 3 3rd floor men's staff restroom NA 3 each FL ballasts PCBs
849 LIT 3 3rd floor women's staff restroom 4' 6 each FL Bulbs Mercury Vapors
850 Ballasts 3 3rd floor women's staff restroom NA 3 each FL ballasts PCBs
851 LIT 3 3rd floor staff lounge 4' 40 each FL Bulbs Mercury Vapors
852 Ballasts 3 3rd floor staff lounge NA 20 each FL ballasts PCBs
853 Computers 3 3rd floor staff lounge NA 6 each Computers Metals
854 Monitors 3 3rd floor staff lounge NA 5 each TV/Computer monitors Metals
855 LIT 4 4th floor hallway 4' 148 each FL Bulbs Mercury Vapors
856 Ballasts 4 4th floor hallway NA 74 each FL ballasts PCBs
857 LIT 4 4th floor classroom 4' 96 each FL Bulbs Mercury Vapors
858 Ballasts 4 4th floor classroom NA 48 each FL ballasts PCBs
859 Monitors 4 4th floor classroom NA 2 each TV/Computer monitors Metals
860 LIT 4 4th floor Records room 4' 2 each FL Bulbs Mercury Vapors
861 Ballasts 4 4th floor Records room NA 1 each FL ballasts PCBs
862 LIT 4 4th floor janitor closet 4' 2 each FL Bulbs Mercury Vapors
863 Ballasts 4 4th floor janitor closet NA 1 each FL ballasts PCBs
864 Monitors 4 4th floor janitor closet NA 3 each TV/Computer monitors Metals
865 LIT 4 4th floor storage room 4' 4 each FL Bulbs Mercury Vapors

ATC Associates Inc. 3


TABLE 2A
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL ADDITION
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
866 Ballasts 4 4th floor storage room NA 2 each FL ballasts PCBs
867 LIT 5 5th floor storage room 4' 4 each FL Bulbs Mercury Vapors
868 Ballasts 5 5th floor storage room NA 2 each FL ballasts PCBs
869 LIT 5 5th floor classroom 4' 96 each FL Bulbs Mercury Vapors
870 Ballasts 5 5th floor classroom NA 48 each FL ballasts PCBs
871 LIT 5 5th floor lecture hall and storage 4' 60 each FL Bulbs Mercury Vapors
872 Ballasts 5 5th floor lecture hall and storage NA 30 each FL ballasts PCBs
873 Monitors 5 5th floor lecture hall and storage NA 6 each TV/Computer monitors Metals
874 Computers 5 5th floor lecture hall and storage NA 4 each Computers Metals
875 LIT 5 5th floor hallway 4' 156 each FL Bulbs Mercury Vapors
876 Ballasts 5 5th floor hallway NA 78 each FL ballasts PCBs
877 LIT 5 5th floor storage room 4' 2 each FL Bulbs Mercury Vapors
878 Ballasts 5 5th floor storage room NA 1 each FL ballasts PCBs
879 LIT 6 6th floor hallway 4' 156 each FL Bulbs Mercury Vapors
880 Ballasts 6 6th floor hallway NA 78 each FL ballasts PCBs
881 Monitors 6 6th floor hallway NA 2 each TV/Computer monitors Metals
882 LIT 7 7th floor storage 4' 6 each FL Bulbs Mercury Vapors
883 Ballasts 7 7th floor storage NA 3 each FL ballasts PCBs
884 LIT 7 Emergency generator room 4' 6 each FL Bulbs Mercury Vapors
885 Ballasts 7 Emergency generator room NA 3 each FL ballasts PCBs
886 Chem 7 Emergency generator room 55 gallon 1 drum Roofing tar Chemicals
887 Chem 7 Emergency generator room NA 6 each Lead acid batteries Chemicals
888 Chem 7 Emergency generator room 5 gallon 2 each Chlorine solution Chemicals
889 LIT 7 7th floor hallway 4' 16 each FL Bulbs Mercury Vapors
890 Ballasts 7 7th floor hallway NA 8 each FL ballasts PCBs
891 LIT 7 7th floor custodial closet 4' 2 each FL Bulbs Mercury Vapors
892 Ballasts 7 7th floor custodial closet NA 1 each FL ballasts PCBs
893 Chem 7 7th floor mechanical room 5 gallon 2 each Cooling water treatment Chemicals
894 LIT 7 7th floor mechanical room NA 10 each HID bulbs Metals
895 Chem 7 7th floor mechanical room NA 30 each Capacitors Chemicals
896 LIT 7 7th floor mechanical room 4' 76 each FL Bulbs Mercury Vapors
897 Ballasts 7 7th floor mechanical room NA 38 each FL ballasts PCBs
898 Chem 7 7th floor mechanical room 55 gallon poly 1 each Unknown liquid Chemicals
899 Chem 7 7th floor mechanical room 55 gallon metal 1 each Unknown liquid Chemicals
890 Chem 7 7th floor mechanical room 1 quart 49 each Pump oil Chemicals
891 LIT 7 7th floor north hallway 4' 24 each FL Bulbs Mercury Vapors
892 Ballasts 7 7th floor north hallway NA 12 each FL ballasts PCBs
893 Computers 7 7th floor north hallway NA 1 each Computers Metals
894 Monitors 7 7th floor north hallway NA 1 each TV/Computer monitors Metals
895 LIT 8 8th floor stairwell 8' 12 each FL Bulbs Mercury Vapors
896 LIT 8 8th floor mechanical room 4' 18 each FL Bulbs Mercury Vapors
897 Ballasts 8 8th floor mechanical room NA 9 each FL ballasts PCBs
898 LIT 1 to 8 South stairwell 4' 42 each FL Bulbs Mercury Vapors

ATC Associates Inc. 4


TABLE 2A
OTHER REGULATED MATERIALS
FORMER CASS TECHNICAL HIGH SCHOOL ADDITION
No ID FLOOR ROOM DESCRIPTION SIZE QUANTITY UNITS COMMENTS DISPOSAL CONCERN
890 Ballasts 1 to 8 South stairwell NA 21 each FL ballasts PCBs
891 LIT 1 to 8 North stairwell 4' 42 each FL Bulbs Mercury Vapors
892 Ballasts 1 to 8 North stairwell NA 21 each FL ballasts PCBs
892 Chem Roof East roof NA 4 each Lead roof vents Lead