CODE COMPLIANCE CHECKLIST FP-CCC 12/2006

THE STATE EDUCATION DEPARTMENT / THE UNIVERSITY OF THE STATE OF NEW YORK / Albany, NY 12234
Office of Facilities Planning, Room 1060 Education Building Annex
Tel. (518) 474-3906 Fax (518) 486-5918
www.emsc.nysed.gov/facplan/

General Information PAGES 1, 2, AND 3 ARE REQUIRED FOR ALL PROJECTS SUBMITTED FOR REVIEW.
Note: Fill in every line.
Note: The Excel version of this form has comments embedded for guidance in filling out many areas of the form. Comments are
accessible by placing the cursor over the red triangle, right click and hit edit to read or copy the comment.

SED Control Number


SED Project Number
8 digit district BEDS Code 4 digit building number 3 digit project number

District / Building Name:


Project Type: New Building Existing Building Site Work Only Other

Project Description:

Architect / Engineer firm:


name phone number & e-mail

Project Contact Person:


name title phone number & e-mail

District Contact Person:


name title phone number & e-mail

SED Project Control Number located on all Contract Documents, forms, and correspondence. Yes

Required Bidding information is located in the contract documents on page or drawing numbers and are paperclipped:
Equivalency Clause Non-Collusion Certification Wage Rates

Required Uniform Safety Standards and TEM information is located on page or drawing numbers and are paperclipped:
C of O statement Exiting Plan Off-Gassing
Safety & Security Ventilation Separation Asbestos Isolation
Separation of Const. Noise Control Testing Lead & Asb.
Cleaning Occupied Area Fume Control TEM & Code Rule 56

Required 155.7 items on the Evaluation of Existing Building Form. Non-conformances are addressed in the documents:
Yes No, District addressing separately No, Addressed in SED project # NA (Big 5 only)
No non-conformances exist list SED project number
Per 155.8 (e) (3) A certificate of Occupancy, a temporary certificate or a building permit may be denied or revoked for violation of health or
safety standards, imposed by law or regulation, which indicate that a building is not suitable for occupancy or intended use.

Page 2 CODE REVIEW CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes


Page 3 STRUCTURAL RESPONSIBILITY CHECKLIST and CERTIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes
Page 4 ARCHITECTURAL REVIEW CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes NA
Page 5 STRUCTURAL DESIGN CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes NA
Page 6 ENERGY CONSERVATION CODE CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes NA
Page 7 FIRE & ELECTRIC CODE REVIEW CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes NA

Page 8 MECHANICAL REVIEW CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes NA

Page 9 PLUMBING & GAS REVIEW CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes NA

It is not necessary to provide pages noted as "NA". If the page does apply and is erroneously not provided, the project will
not be reviewed until the page is provided with an addendum.
FP-CCC 12/2006 CODE REVIEW CHECKLIST page 2 of 9

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
SED Control Number
SED Project Number
District BEDS Code Building Identification # Project number

0
District Name Building Name

Building Information:
Use and Occupancy Classifications: (check all that apply) E B I-4 S-1 R-2 U
A- M S-2 Other -

For Existing Buildings check all that apply: NA Change of Occupancy Relocation Historic-K10 report required
( * check the definitions in Appendix K) Repair* Renovation* Alteration* Reconstruction* Addition*
* Provide Key Plans demonstrating distinct work areas
list drawing numbers
Type of Construction: (check all that apply)
Existing bldg: I-A I-B II-A II-B III-A III-B IV V-A V-B
New building(s): I-A I-B II-A II-B III-A III-B IV V-A V-B

Building Height and Area for New Buildings and Additions: (If additional space needed, provide on Code Compliance Drawings.) NA
Permitted: Height in feet: Number of stories: Square feet / floor*

Actual: Height in feet: Number of stories: Square feet / floor*


Provide calculations on a Code Compliance Drawing.

Special Features: (check all that apply) Parapet Mezzanine Stage Catwalk Courtyard

For All Projects* Provide Code Compliance Drawings: NA*


(*excludes site, roof, district-wide and energy performance projects) list drawing numbers

Is a Sprinkler System provided? No Yes, full Yes, partial Yes, in new construction only

Building Information: Egress Information:


Occupancy Classification Yes NA Room Use Designations Yes NA
Construction Classification - Existing Yes NA Room Square Footages Yes NA
Construction Classification - New Yes NA Room Occupancy Loads Yes NA
Key Plan with building sides accessible Yes NA Room Exit & Corridor exit width Calculations Yes NA
Building Areas Yes NA Exit Travel Distances incl. Common Path Yes NA
(Provide numbered Building Areas (existing and new), construction types, Stair & Exit Door exit width Calculations Yes NA
number of stories, number of sides accessible, allowable fire areas and
Accessibility for Exist and New Yes NA
actual fire areas with calculations. Show locations of fire walls and fire
barriers.) Corridor/Exit Enclosures Smoke only Fire rated

Accessory Assembly Areas: (If additional space needed, provide on Code Compliance Drawings.) NA

Code requirements:
Gymnasium: area in sq. ft. Occupant load Required E.W. Provided E.W.
Auditorium: area in sq. ft. Occupant load Required E.W. Provided E.W.
Cafeteria: area in sq. ft. Occupant load Required E.W. Provided E.W.
Library: area in sq. ft. Occupant load Required E.W. Provided E.W.
Other: area in sq. ft. Occupant load Required E.W. Provided E.W.

SED (MPS) requirements: Reminder: Exit unit = 22", half units are permitted at 12" per half unit.
Gymnasium: area in sq. ft. / 600 sq. ft added
Req'd exit units Provided exit units
Gymnasium: bleacher sq. ft. / 250 sq. ft equals
Auditorium: area in sq. ft. / 600 sq. ft equals Req'd exit units Provided exit units
Stage/Platform area in sq. ft. / 1200 sq. ft equals Req'd exit units Provided exit units
Cafeteria: area in sq. ft. / 600 sq. ft equals Req'd exit units Provided exit units
Natatorium: bleacher sq. ft / 250 sq. ft added
Req'd exit units Provided exit units
remaining area including / 1500 sq. ft. equals
the pool in sq. ft.
STRUCTURAL RESPONSIBILITY
FP-CCC 12/2006 CHECKLIST and CERTIFICATION page 3 of 9

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
SED Control Number
SED Project Number
District BEDS Code Building Identification Number Project number

0
District Name Building Name
The architect/engineer for each project which requires approval by the Commissioner, shall complete and sign this form and submit it together with the final plans
and specifications for the project.
A. STRUCTURAL ELEMENTS
Are there any structural elements involved with this project Yes No
a. If no, go to Section D and sign the Certification.
b. If yes, complete Sections B, C, and D, seal and sign the Certification
B. STRUCTURAL LOADING
Structural loading shall meet at least the requirements of the Uniform Fire Prevention Yes No
and Building Code. Page 5, the Structural Design Checklist, is appropriately filled in and attached
C. STRUCTURAL DESIGN
IMPORTANT: IMPORTANT:
Check who is responsible Check applicable
for the design of each element for each element
ARCH ENGR Present Not Present
STRUCTURAL ELEMENT In Work In Work
1. Foundation
a. Footings
b. Walls
c. Piles (type)
2. Floor Framing Systems
a. Mechanical/Special Framing
3. Columns
4. Walls
a. Exterior Bearing
1. lintels
2. veneer attachment
3. reinforcing
b. Exterior Nonbearing
1. lintels
2. veneer attachment
3. reinforcing
c. Interior Bearing
1. lintels
2. reinforcing
d. Interior Nonbearing
1. lintels
2. reinforcing
5. Roof Framing Systems
a. Mechanical/Special Framing
6. Stairs and Stairways
7. Bridges
8. Catwalks
9. Railings
10. Bleachers/Grandstands
11. Retaining Walls
12. Chimney Stacks
13. Parapet Walls
14. Other

D. CERTIFICATION

I, the undersigned, do hereby certify that: (Check appropriate box)

There are no structural elements involved in the project, or

I have designed the structural elements of this project, as


noted above, in accordance with at least the criteria listed in the
New York State Uniform Fire Prevention and Building Code.

Seal of R. A. licensed in New York State Seal of P. E. licensed in New York State

Signature - Architect Date Signature - Engineer Date


FP-CCC 12/2006 ARCHITECTURAL REVIEW CHECKLIST page 4 of 9

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
SED Control Number
SED Project Number
District BEDS Code Building Identification Number Project number

0
District Name Building Name
LOCATION in Documents

Dead End Corridors less than 1 1/2 times the width, max 20 ft. . Yes not applicable
Smoke Zone Exiting all student spaces over 500 sq. ft. . . . Yes not applicable
Rescue Windows located on Construction Documents . . . Yes not applicable
Rescue Window Clear Opening Size on Construction Document(s) . Yes not applicable
Class A finishes in Corridors and Assembly Spaces . . . Yes not applicable
Assembly Area Maximum Occupancy Sign . . . . . Yes not applicable
Electrically Powered Moveable Partition Sign . . . . . Yes not applicable
Fire Extinguishers . . . . . Yes not applicable
Safety Glazing in Doors, Exterior Corridor Windows, and Stair Windows Yes not applicable
Partition/Wall Fireproofing Design Number of Rated Partitions/Assemblies Yes not applicable
Corridor enclosure . . . . . . . . . Yes not applicable
Rated interior Corridor Windows . . . . . . . . Yes not applicable
Elevator Equipment Room enclosure 2 hour . . . . . Yes not applicable

Stairways, riser and tread sizes are indicated . . . . . Yes not applicable
Classroom Ceiling height 9'-0" . . . . . . . . Yes not applicable
Secure Exam Storage . . . . . . . . . Yes not applicable
Fire Blankets in Laboratory Rooms . . . . . . . Yes not applicable
Door Schedules . . . . . . . . . Yes not applicable
Hardware Schedule . . . . . . . . . Yes not applicable
Window Schedules . . . . . . . . . Yes not applicable
Roof System UL Class A or FM Class 1 . . . . . . Yes not applicable
Carpet, Radiant Floor Panel Test Class 1 . . . . . . Yes not applicable
Assembly Area Seating meets NFPA 701 . . . . . . Yes not applicable
Truss/Joist Identification Signs . . . . . . Yes not applicable
Site and floor plans showing separations during construction . . . Yes not applicable

Accessibility Yes NA PENC


Parking . . . . . . . . . Yes NA PENC
Exterior Accessible Route . . . . . . . . Yes NA PENC
Signage . . . . . . . . . Yes NA PENC
Accessible Exits / Entrances . . . . . . . . Yes NA PENC
Accessible Toilets . . . . . . . . Yes NA PENC
Accessible Work Stations in all classrooms . . . . . Yes NA PENC
Door Approach Clearances . . . . . . . . Yes NA PENC
Interior Accessible Route to major spaces . . . . . . Yes NA PENC
Door Hardware . . . . . . . . . Yes NA PENC
Wheelchair Viewing Spaces in assembly spaces . . . . Yes NA PENC
Auditorium ambulatory seats . . . . . . . . Yes NA PENC
Assistive Listening Devices . . . . . . . . Yes NA PENC
Public Telephones . . . . . . . . . Yes NA PENC
Elevator . . . . . . . . . Yes NA PENC
Elevator Signage . . . . . . . . . Yes NA PENC
Interior Accessibility Signage . . . . . . . . Yes NA PENC
All Program Spaces are Accessible . . . . . . . Yes No
There is an Accessible Toilet Room on Every Floor . . . . Yes No
FP-CCC 12/2006 STRUCTURAL DESIGN CHECKLIST page 5 of 9

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
SED Control Number
SED Project Number
District BEDS Code Building Identification Number Project number

0
District Name Building Name

1604.5 Prior to structural design, the District / BOCES has been consulted to determine if this facility is currently or will be
considered for use as an emergency shelter facility? Yes Will this building be used as an emergency Shelter? Yes

The New York State Uniform Fire Prevention and Building Code Section 1603 requires, "The design loads and other information
pertinent to the structural design required by Sections 1603.1.1 through 1603.1.8 shall be clearly indicated on the
construction documents for parts of the building or structure."

Conventional light-frame construction: NA


Floor and roof live loads
list drawing numbers

Ground snow load


list drawing numbers

Basic wind speed (3-second gust), miles per hour and wind exposure
list drawing numbers

Seismic Design Category and Site Class


list drawing numbers

1603.1.1 Floor live load


list drawing numbers

1603.1.2 Roof live load Exceeds 10 pounds / sq. ft.


list drawing numbers

1603.1.3 Roof snow load


list drawing numbers

1603.1.4 Wind load


list drawing numbers

1603.1.5 Earthquake design data


list drawing numbers

1603.1.6 Flood load Not in flood hazard area per Section 1612.3
Flood certification provided per Section 1612.5 list drawing numbers

1603.1.7 Special loads Not applicable


applicable code sections list drawing numbers

1603.1.8 System and components requiring special


inspections for seismic resistance Not applicable
list drawing numbers
Soils
1802.6 Soil classification & design load bearing capacity
list drawing numbers list specification numbers
Soil investigation report Available Not applicable

1621.2 and 1621.3 have been reviewed and coordinated with architect and engineers Yes

1704 Special Inspection requirements, where are they located in the documents?
list drawing or specification numbers

Print name:

Signature:

Date: Telephone:
Seal of P. E. or R. A. licensed in New York State
FP-CCC 12/2006 ENERGY CONSERVATION CODE CHECKLIST page 6 of 9

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
SED Control Number
SED Project Number
District BEDS Code Building Identification Number Project number

0
District Name Building Name

The 2002 Energy Conservation Code of New York State Section 104.2 states "Compliance with specific provisions of this code shall be
determined through the use of computer software, worksheets, compliance manuals and other similar materials when they have met
the intent of this code." (www.eren.doe.gov/buildings/tools_directory/software/comcheckez.htm)
Section 104.3 requires " Construction documents shall be of sufficient clarity to indicate the location, nature and extent of the work
proposed and show in sufficient detail pertinent data and features of the building and the equipment and the systems as herein
governed, including, but not limited to, design criteria, exterior envelope component materials, U-factors of the envelope systems, U-
factors of fenestration products, R-values of insulating materials, size and type of apparatus and equipment, equipment and systems
controls and other pertinent data to indicate conformance with the requirements of this code and relevant laws, ordinances, rules and
regulations."

Applicability: New Building Substantial alterations Change in occupancy


(check the definitions) Additions Historic Building

Exempt Building: Low Energy Usage Building Unconditioned Building

Thermal Design Parameters:


Outdoor design temperature Per ASHRAE Handbook of Fundamentals
Degree days (heating / cooling) Per ASHRAE Handbook of Fundamentals

Climate Zone: 4 5 6 14A

Glazing percentage: 10% or less between 10% and 25% between 25% and 40% between 40% and 50%

Design Approach: Chapter 7 - Prescriptive Chapter 8 - Acceptable Practice DOE software used
Chapter 7 - System
Chapter 7 - Energy Cost Budget

802 Building Envelope Requirements: In compliance Worksheets available Not applicable

U-factors of the envelope systems or


list drawing numbers list specification sections
U-factors of fenestration products or
list drawing numbers list specification sections
R-values of insulating materials or
list drawing numbers list specification sections

803 Building Mechanical Systems: 803.2 Applicable 803.3 Applicable Not applicable
Design Load
list drawing number
804 Service Water Heating: Applicable Not applicable

805 Lighting and Power Systems: Applicable Not applicable


Interior lighting power Entire building method Portion of building method

806 Design By Total Building Performance: Applicable Not applicable


Provide a full detailed analysis of the entire building and all systems.
list drawing number or specification section
FP-CCC 12/2006 FIRE & ELECTRIC CODE REVIEW CHECKLIST page 7 of 9

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
SED Control Number
SED Project Number
District BEDS Code Building Identification Number Project number

0
District Name Building Name

NA = Not Applicable = LOCATION in Construction Documents

FIRE SERVICE NA MEANS OF EGRESS NA


Access Roads . . Yes NA New Buildings
Access Openings . . Yes NA Corridor Plenum . . Yes NA
Stairway Identification . . Yes NA Exit Enclosure Ventilation . Yes NA
Premises ID . . Yes NA Exit Signs . . . . Yes NA
Hazards Firefighters . . Yes NA Egress Illumination . . Yes NA
Water Supplies . . Yes NA Emergency Power . . Yes NA
Fire Hydrants . . Yes NA Area of Refuge . . . Yes NA
Fire Command Center . . Yes NA Boiler/Furnace/Refrig. Rms Yes NA

BUILDING SYSTEMS NA Fire Code Section 1010 NA


Emergency Power . . Yes NA Renovations, alterations, reconstructions,
Electrical Eqpt, Wiring & Hazards. Yes NA additions, and changes of occupancy
Mechanical Refrigeration . . Yes NA Exit Signs . . . . Yes NA
Elevator Recall . . Yes NA Egress Illumination . . Yes NA
Battery Systems . . Yes NA Emergency power . . Yes NA

FIRE PROTECTION SYSTEMS . NA Combustible Dust . . Yes NA


Automatic Sprinkler System . Yes NA Fire Safety During Construction Yes NA
Alternative System . . Yes NA Flammable Finishes . Yes NA
Hood Fire Suppression . . Yes NA Service Stn. & Repair Garage Yes NA
Standpipe System . . Yes NA
Fire Extinguishers . . Yes NA
Fire Alarm . . Yes NA GENERAL - FIRE
Automatic Detection System . Yes NA Acceptance Testing/Inspection Yes NA
Emergency Alarm System . Yes NA Training . . . . Yes NA
Smoke Control System . . Yes NA Equipment Listed/Labeled . Yes NA
Smoke & Heat Vent . . Yes NA Fire Stopping . . . Yes NA
Municipal FA Station . . Yes NA Identification . . . Yes NA
Explosion Control . . Yes NA Equipment Location . . Yes NA
Fire Dept. Connections . . Yes NA
Fire Pumps . . Yes NA
AH Units & Fans shutdown w/ FA Yes NA

ELECTRICAL NA GENERAL - ELECTRIC


Telephone . . Yes NA Acceptance Testing/Inspection Yes NA
NEC (NFPA 70) Electric Work . Yes NA Training . . . . Yes NA
Panel/Circuits Identified . . Yes NA Equipment Listed/Labeled . Yes NA
Artificial Light . . Yes NA Fire Stopping . . . Yes NA
Explosion Proof Equipment . Yes NA Equipment Location . . Yes NA
Shop Emergency Shunts . . Yes NA Access/Clearances . . Yes NA
Dust Proof Shop Outlets . . Yes NA Identification Lines/Mtl./Eqpt. Yes NA
Shielded Shop Light Fixtures . Yes NA Instruction Manual / Video Yes NA
Closed Elec. Htg. Elements & UL Yes NA Material/Eqpt Reuse . Yes NA
Underground Electric Service . Yes NA Unsafe System Rehab/Rmvl. Yes NA
Elevator Code A17.1 . . Yes NA .
Electric Operated Partition . Yes NA
Plenum Cable . . Yes NA
HID Self Extinguishing . . Yes NA
Other ________________ . Yes NA
FP-CCC 12/2006 MECHANICAL REVIEW CHECKLIST page 8 of 9

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
SED Control Number
SED Project Number
District BEDS Code Building Identification Number Project number

0
District Name Building Name
NA = Not Applicable = LOCATION in Construction Documents

BOILER ROOM NA Duct Systems NA


Fuel: Oil Gas Electric Other Plenum . . . . Yes NA
Other Construction . . . Yes NA
Low Water Cutoff . . Yes NA Insulation . . . Yes NA
Combustion Air . . Yes NA Filters . . . . Yes NA
Clearance . . Yes NA Smoke Detection Systems Yes NA
Safety Burner Switch . . Yes NA Fire Dampers . . Yes NA
Chimney/Vent . . Yes NA Smoke Dampers . . Yes NA
Standards . . Yes NA Appliances NA
Electronic Flame Safeguards . Yes NA Cooling Towers . . Yes NA
Safety Valves & Controls . . Yes NA Forced Air Furnace . . Yes NA
12NYCRR4 (Ind. Code Rule 4) . Yes NA Engine/Turbine . . Yes NA
Remote Burner Shutoff Valves . Yes NA Other ______________ . Yes NA
Fuel Train Standards . . Yes NA Other ______________ . Yes NA
Scald Protection Domestic HW Yes NA Refrigeration NA
ASME Vessel . . Yes NA ASHRAE 15 . . . Yes NA
MECHANICAL NA Refrigerant type . . Yes NA
Ventilation NA Machinery Room . Yes NA
Intake Openings & Protections . Yes NA Piping . . . . Yes NA
Ventilation Rate . . Yes NA Hydronic piping NA
Common System . . Yes NA Material . . . . Yes NA
Balancing . . Yes NA Insulation . . . . Yes NA
Uninhabited Spaces . . Yes NA Valves . . . . Yes NA
Exhaust . . NA Installation requirements Yes NA
Independent Systems . . Yes NA Fuel Oil NA
Toilet/Locker/Janitor Closets . Yes NA Materials . . . . Yes NA
Hazardous Areas . . Yes NA Piping . . . . Yes NA
Laboratories . . Yes NA Storage . . . . Yes NA
Shops . . Yes NA Valves . . . . Yes NA
Kitchen Domestic . . Yes NA Solar Systems . Yes NA
Kitchen Commercial . . Yes NA
Kitchen Commercial Makeup . Yes NA
Mechanical Equipment Rooms . Yes NA
Elevator Equipment Rooms . Yes NA
Other ________________ . Yes NA
Subslab . . Yes NA

GENERAL
Acceptance Testing/Inspection Yes NA Sequence of Operations . Yes NA
Training . . Yes NA Identification Lines/Mtl./Eqpt. Yes NA
Equipment Listed/Labeled . . Yes NA Instruction Manual / Video Yes NA
Fire Stopping . . Yes NA Material/Eqpt Reuse . Yes NA
Equipment Location . . Yes NA Unsafe System Rehab/Rmvl. Yes NA
Access/Clearances . . Yes NA Condensate Disposal . Yes NA
Controls . . Yes NA No Direct Fired Heaters . Yes NA
FP-CCC 12/2006 PLUMBING & GAS REVIEW CHECKLIST page 9 of 9

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
SED Control Number
SED Project Number
District BEDS Code Building Identification Number Project number

0
District Name Building Name
NA = Not Applicable = LOCATION in Construction Documents

PLUMBING NA GAS NA
Rodent proofing . . Yes NA Low pressure 1/2 psig or < Yes NA
Protection plumbing systems . Yes NA No gas lines in corridors . Yes NA
Structural Safety . . Yes NA Master Gas Valve for Outlets Yes NA
Piping Support . . Yes NA Pipe Size/Material . . Yes NA
Floodproofing . . Yes NA Valves . . . . Yes NA
Fixtures/Faucets/Fittings NA Enc. of Pressure Regulation Eq. Yes NA
Fixture Adequacy . . Yes NA PSC Distribution Service . Yes NA
Accessible Facilities . . Yes NA Liq. Petroleum Gas NFPA 58 Yes NA
Emergency Shower/Eyewash . Yes NA Vent/Chimney . . . Yes NA
Drinking Fountains . . Yes NA Appliances Shown . . Yes NA
Sink - Bubbler Separated . Yes NA Other ______________ . Yes NA
Lavatories . . Yes NA Other ______________ . Yes NA
Showers . . Yes NA
Sinks . . Yes NA GENERAL - GAS
Urinals . . Yes NA Acceptance Testing/Inspection Yes NA
Water Closets . . Yes NA Training . . . . Yes NA
Water Saving Fixtures . . Yes NA Equipment Listed/Labeled . Yes NA
Water Heaters NA Fire Stopping . . . Yes NA
DHW Heater ASME Tank . Yes NA Equipment Location . . Yes NA
Location . . Yes NA Access/Clearances . . Yes NA
Controls . . Yes NA Controls . . . . Yes NA
Safety Devices . . Yes NA Sequence of Operations . Yes NA
Insulation . . Yes NA Identification Lines/Mtl./Eqpt. Yes NA
Water Supply and Distribution NA Instruction Manual / Video . Yes NA
Protect Water Quality . . Yes NA Material/Eqpt Reuse . . Yes NA
Size/Material Piping . . Yes NA Unsafe System Rehab/Rmvl. Yes NA
No Lead Solder . . Yes NA Condensate Disposal . Yes NA
Disinfection . . Yes NA No Direct Fired Heaters . Yes NA
Sanitary Drainage NA
Sanitary Discharge Permits . Yes NA
Storm - Sanitary Separated . Yes NA
Size/Material Piping . . Yes NA
Sumps/Ejectors . . Yes NA
Indirect/Special Waste . . Yes NA
Vents . . Yes NA
Traps/Interceptors/Separators Yes NA
Storm Drainage . . Yes NA
Swimming Pool . . Yes NA

GENERAL - PLUMBING
Acceptance Testing/Inspection Yes NA Identification Lines/Mtl./Eqpt. Yes NA
Training . . Yes NA Instruction Manual / Video Yes NA
Equipment Listed/Labeled . . Yes NA Material/Eqpt Reuse . . Yes NA
Fire Stopping . . Yes NA Unsafe System Rehab/Rmvl. Yes NA
Equipment Location . . Yes NA Condensate Disposal . Yes NA
Access/Clearances . . Yes NA