Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1 Issued: 2016-05-20
Revision: L
ABB 3
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Lockout relay
HMI
Time
Authorization
2 - Web HMI
I2> 3I>>> 3I>/Io>BF I
AND
ESC Clear
3I 46 50P/51P 51BF/51NBF
O R
L
OR
2
3I> 3I>> 3I2f> 3dI>L
51P-1 51P-2 68 87L
CONDITION MONITORING COMMUNICATION
AND SUPERVISION
I Protocols:
Io IEC 61850-8-1
PHIZ MCS 3I OPTS Modbus
HIZ MCS 3I OPTM IEC 60870-5-103
DNP3
Interfaces:
2 Ethernet: TX (RJ45), FX (LC)
BST PCS TCS Serial: Serial glass ber (ST),
BST PCS TCM RS-485, RS-232
Redundant protocols:
HSR
PRP
18 RSTP
MAP SOTF
MAP SOTF
- I, Io
Object Ctrl 2) Ind 3)
- Limit value supervision
CB 1 - - Load prole record
- Symmetrical components
DC 2 3
ES 1 2
1)
Check availability of binary inputs/outputs
Analog interface types 1)
REMARKS
Optional 3 No. of Calculated OR Alternative
function instances value function to be
Io/Uo dened when
Sum of phase ordering
currents
3I I
RED615
AT REMOTE
END
GUID-78F52211-9D37-4A2F-9527-CD61BDEA68A2 V2 EN
4 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Uo
Lockout relay
HMI
Time
Authorization
2 - Web HMI
I2> I2/I1> 3Ith>F I
AND
ESC Clear
3I 46 46PD 49F
O R
L
OR
3Ith>T/G/C 3I>>>
49T/G/C 50P/51P
CONDITION MONITORING COMMUNICATION
AND SUPERVISION
Protocols:
3I>/Io>BF 3I>
IEC 61850-8-1
51BF/51NBF 51P-1
Modbus
IEC 60870-5-103
2 DNP3
3I>> 3I2f> 3dI>L CBCM MCS 3I OPTS Interfaces:
51P-2 68 87L CBCM MCS 3I OPTM Ethernet: TX (RJ45), FX (LC)
Serial: Serial glass ber (ST),
RS-485, RS-232
Io Redundant protocols:
2 HSR
BST PCS TCS PRP
BST PCS TCM RSTP
Io
3 18
Uo> MAP SOTF OI
59G MAP SOTF 79
REMARKS
Optional 3 No. of Calculated OR Alternative
function instances value function to be
Io/Uo dened when
3I ordering
RED615
AT REMOTE
END
GUID-6AB801FF-A43F-40D6-8D70-D27EF2F402B0 V2 EN
ABB 5
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Lockout relay
HMI
Time
Authorization
2 - Web HMI
I2> I2/I1> 3Ith>F I
AND
ESC Clear
3I 46 46PD 49F
O R
L
OR
3Ith>T/G/C 3I>>>
49T/G/C 50P/51P
CONDITION MONITORING COMMUNICATION
AND SUPERVISION
3I>/Io>BF 3I> Io Protocols:
IEC 61850-8-1
51BF/51NBF 51P-1
Modbus
IEC 60870-5-103
2 DNP3
3I>> 3I2f> 3dI>L CBCM MCS 3I OPTS Interfaces:
51P-2 68 87L CBCM MCS 3I OPTM Ethernet: TX (RJ45), FX (LC)
Serial: Serial glass ber (ST),
RS-485, RS-232
Redundant protocols:
2 HSR
BST PCS TCS PRP
BST PCS TCM RSTP
Io
OI
79
REMARKS
Optional 3 No. of Calculated OR Alternative
function instances value function to be
Io/Uo dened when
3I ordering
RED615
AT REMOTE
END
GUID-C4999021-E1FE-4D55-AB91-FC7C6963501B V2 EN
6 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
UL1UL2UL3
Uo
Lockout relay
HMI
Time
Authorization
2 - Web HMI
I2> I2/I1> 3Ith>F I ESC Clear
AND
3I 46 46PD 49F
O R
L
OR
3Ith>T/G/C 3I>>>
49T/G/C 50P/51P
CONDITION MONITORING COMMUNICATION
AND SUPERVISION
2
Protocols:
3I>/Io>BF 3I> 3I>>
IEC 61850-8-1/-9-2LE
51BF/51NBF 67-1 67-2
Modbus
IEC 60870-5-103
DNP3
3I2f> 3dI>L 3I FUSEF CBCM MCS 3I Interfaces:
68 87L 60 CBCM MCS 3I Ethernet: TX (RJ45), FX (LC)
U12 Serial: Serial glass ber (ST),
RS-485, RS-232
Redundant protocols:
Io 2 HSR
BST OPTS PCS TCS PRP
BST OPTM PCS TCM RSTP
Io
3 3
3U< U2> U1< 3U> SYNC OI PQM3I PQM3U PQMU
27 47O- 47U+ 59 25 79 PQM3I PQM3V PQMV
U12
UL1UL2UL3 3 4
Uo> f>/f<, PQUUB
df/dt PQVUB
59G
81
REMARKS
18 Optional 3 No. of Calculated OR Alternative
2xRTD
1xmA
FLOC MAP SOTF function instances value function to be
21FL MAP SOTF Io/Uo dened when
3I ordering
RED615
AT REMOTE
END
GUID-F76822E6-DDB6-44F2-8704-5A5B3035BAFD V2 EN
ABB 7
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Lockout relay
HMI
Time
Authorization
2 - Web HMI
I2> I2/I1> 3Ith>F I ESC Clear
AND
3I 46 46PD 49F
O R
L
OR
3Ith>T/G/C 3I>>>
49T/G/C 50P/51P
CONDITION MONITORING COMMUNICATION
AND SUPERVISION
2 Protocols:
3I>/Io>BF 3I> 3I>>
IEC 61850-8-1
51BF/51NBF 67-1 67-2
IEC 61850-9-2LE
UL1UL2UL3 Io Modbus
IEC 60870-5-103
3I2f> 3dI>L 3I FUSEF CBCM MCS 3I DNP3
68 87L 60 CBCM MCS 3I Interfaces:
Ethernet: TX (RJ45), FX (LC)
Serial: Serial glass ber (ST),
RS-485, RS-232
2 2 Redundant protocols:
Io Io> Io>> BST OPTS PCS TCS HSR
67N-1 67N-2 BST OPTM PCS TCM PRP
RSTP
1)
Combi sensor inputs with conventional
primary object
Io input
3 3
3U< U2> U1< 3U> SYNC OI PQM3I PQM3U PQMU
27 47O- 47U+ 59 25 79 PQM3I PQM3V PQMV
UL1
3 4
Uo> f>/f<, PQUUB
df/dt
59G PQVUB
81
18
FLOC MAP SOTF REMARKS
21FL MAP SOTF Optional 3 No. of Calculated OR Alternative
function instances value function to be
Io/Uo dened when
3I ordering
RED615
AT REMOTE
END
GUID-D0C7BD80-3FC0-448D-ACD4-D6123319339C V2 EN
8 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Line differential protection with directional earth-fault protection and circuit-breaker condition monitoring B
Line differential protection with non-directional earth-fault protection and circuit-breaker condition monitoring C
Line differential protection with directional overcurrent and earth-fault protection, voltage and frequency based protection and
D
measurements, synchro-check and circuit-breaker condition monitoring (RTD option, optional power quality and fault locator)
Line differential protection with directional overcurrent and earth-fault protection, voltage and frequency based protection and
measurements, and circuit-breaker condition monitoring (sensor inputs, optional power quality, fault locator and synchro-check E
with IEC 61850-9-2 LE)
ABB 9
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
10 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
ABB 11
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
12 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Protection
communication
A
A
U12 0. 0 kV
U12 0. 0 kV
P 0.00 kW
P 0.00 kW
Q 0.00 kVAr
Q 0.00 kVAr
IL2 0 A
IL2 0 A
O
I ESC Clear
R
3I 3I I ESC Clear
L O R
L
I I
RED615 RED615
Std. conf. A Std. conf. A
ANSI IEC ANSI IEC
46 I2> 46 I2>
50P/51P 3I>>> 50P/51P 3I>>>
51BF/51NBF 3I>/Io>BF 51BF/51NBF 3I>/Io>BF
51P-1/51P-2 3I>/3I>> 51P-1/51P-2 3I>/3I>>
87L 3I> 87L 3I>
BST BST BST BST
MCS 3I MCS 3I MCS 3I MCS 3I
GUID-28763BDA-8E54-4716-9CDD-F2A208E79E25 V1 EN
Figure 6. Line differential protection for an interconnecting feeder between two primary distribution substations using standard configuration
A
Figure 6 illustrates line differential protection for an protection is offered for a in-zone power transformer, when
interconnecting feeder between two primary distribution available and located in the protection zone.
substations using standard configuration A. Additionally,
3U Uo RED615
A
Std. conf. D
U12 0. 0 kV
P 0.00 kW
ANSI IEC
Q 0.00 kVAr
IL2 0 A
3I I ESC Clear
46 I2>
O R
L
47O-/59 U2>/3U>
47U+/27 U1</3U<
Io 50P/51P 3I>>>
51BF/51NBF 3I>/Io>BF
67N-1/67N-2 Io>/Io>>
Protection
communication 87L 3I>
BST BST
Io MCS 3I MCS 3I
RED615
3I
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
A
I ESC Clear
ANSI IEC
O R
L
46 I2>
49F/49T 3Ith>F/3Ith>T
50P/51P 3I>>>
51BF/51NBF 3I>/Io>BF
51N Io>
87L 3I>
BST BST
MCS 3I MCS 3I
GUID-3084D6C6-6067-4827-AA10-DAC1A772077C V1 EN
Figure 7. Line differential protection of a feeder using the standard configurations D and B or C
Line differential protection of a feeder using the standard protection is offered for an in-zone power transformer, when
configurations D and B or C is shown in Figure 7. Additionally, available and located in the protection zone.
ABB 13
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
A
RED615
3I I ESC Clear
Std. conf. E
O R
L
ANSI IEC
3U
46 I2>
47O-/59 U2>/3U>
47U+/27 U1</3U<
50P/51P 3I>>>
Io
51BF/51NBF 3I>/Io>BF
67N-1/67N-2 Io>/Io>>
Protection 87L 3I>
communication BST BST
Io
RED615
Std. conf. E
ANSI IEC
3U
46 I2>
3I A
47O-/59 U2>/3U>
U12 0. 0 kV
P 0.00 kW
47U+/27 U1</3U<
Q 0.00 kVAr
IL2 0 A
I ESC Clear
O R
L
50P/51P 3I>>>
51BF/51NBF 3I>/Io>BF
67N-1/67N-2 Io>/Io>>
87L 3I>
BST BST
GUID-6802EC2A-DC22-44E6-8BD2-DF7DCEAAEBA0 V1 EN
Figure 8 illustrates line differential protection of a feeder using Standard configurations D and E are not designed for using all
the standard configuration E, in which current sensors the available functionality content in one relay at the same time.
(Rogowski coil) and voltage sensors (voltage divider) are used Frequency protection functions and third instances of voltage
for the measurements. Additionally, protection is offered for an protection functions must be added with the Application
in-zone power transformer, when available and located in the Configuration tool. To ensure the performance of the relay, the
protection zone. The standard configuration E has been pre- user-specific configuration load is verified with the Application
configured especially for ABB switchgears, for example, Configuration tool in PCM600.
UniGear Digital. However, the use of this configuration is not
restricted for this purpose only.
is especially useful when 615 series relays without the optional using calculations based on both real-time and historical
single-line diagram feature are used. The Web HMI of values. A better understanding of the process dynamics is
COM600S also provides an overview of the whole substation, achieved by combining time-based process measurements
including relay-specific single-line diagrams, which makes with production and maintenance events.
information easily accessible. Substation devices and
processes can also be remotely accessed through the Web COM600S can also function as a gateway and provide
HMI, which improves personnel safety. seamless connectivity between the substation devices and
network-level control and management systems, such as
In addition, COM600S can be used as a local data warehouse MicroSCADA Pro and System 800xA.
for the substation's technical documentation and for the
network data collected by the devices. The collected network GOOSE Analyzer interface in COM600S enables the following
data facilitates extensive reporting and analyzing of network and analyzing the horizontal IEC 61850 application during
fault situations by using the data historian and event handling commissioning and operation at station level. It logs all GOOSE
features of COM600S. The historical data can be used for events during substation operation to enable improved system
accurate monitoring of process and equipment performance, supervision.
Product Version
ABB 15
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
ABB
MicroSCADA Pro/
System 800xA
COM600S COM600S
Web HMI Web HMI
GUID-4D002AA0-E35D-4D3F-A157-01F1A3044DDB V4 EN
Figure 9. ABB power system example using Relion relays, COM600S and MicroSCADA Pro/System 800xA
16 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
The voltage unbalance and voltage variation functions are used The sequence-of-events information can be accessed either via
for measuring short-duration voltage variations and monitoring local HMI or remotely via the communication interface of the
voltage unbalance conditions in power transmission and relay. The information can also be accessed locally or remotely
distribution networks. using the Web HMI.
ABB 17
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
events
WHMI
DNP3
LHMI
(FIFO) 1024
Fault
records
(FIFO) 128
BASIC FUNCTIONS
Fault summary;
Trip timestamp, Function, Currents, Voltages, etc.
Audit
trail
events
(FIFO) 2048
n100
Load profile
record
...7 yrs Historical load data captured at a periodical
time interval (Demand interval 1...180min)
GUID-CDF1DC16-AF90-406F-B21B-EF6C7F60BCCA V1 EN
13. Condition monitoring In addition, the relay includes a runtime counter for monitoring
The condition monitoring functions of the relay constantly of how many hours a protected device has been in operation
monitor the performance and the condition of the circuit thus enabling scheduling of time-based preventive
breaker. The monitoring comprises the spring charging time, maintenance of the device.
SF6 gas pressure, the travel time and the inactivity time of the
circuit breaker.
14. Trip-circuit supervision
The monitoring functions provide operational circuit breaker The trip-circuit supervision continuously monitors the
history data, which can be used for scheduling preventive availability and operability of the trip circuit. It provides open-
circuit breaker maintenance. circuit monitoring both when the circuit breaker is in its closed
and in its open position. It also detects loss of circuit-breaker
control voltage.
18 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
A permanent relay fault blocks the protection functions to The pilot wire link supports the same protection and
prevent incorrect operation. communication functionality as the fiber optic link. The quality
of service (QoS) is indicated by the modems and the
communication link is continuously supervised by the relay. The
16. Current circuit supervision
RPW600 modem offers a 5 kV (RMS) level of isolation between
The relay includes current circuit supervision. Current circuit
the pilot wire terminals and ground. The RPW600 modems
supervision is used for detecting faults in the current
(master and follower) are galvanically connected to either end of
transformer secondary circuits. On detecting of a fault the
the pilot wire and optically connected to the relays using short
current circuit supervision function activates an alarm LED and
optical single-mode cables. Using 0.8 mm2 twisted pair cables
blocks the line differential protection and negative-sequence
pilot wire link distances up to 8 km are typically supported.
overcurrent protection functions to avoid unintended operation.
However, twisted pair pilot wire cables in good conditions may
The current circuit supervision function calculates the sum of
support even longer distances to be covered. The length of the
the phase currents from the protection cores and compares the
supported pilot wire link also depends on the noise environment
sum with the measured single reference current from a core
in the installation. Should the need arise to replace the pilot wire
balance current transformer or from separate cores in the
cables with fiber optic cables, the single mode fiber optic LC
phase current transformers
connectors of the relays can be utilized for direct connection of
the fiber optic communication link.
17. Protection communication and supervision
The communication between the relays is enabled by means of Apart from the continued protection communication, the
a dedicated fiber optic communication channel. 1310 nm multi- communication channel can also be used for binary signal
mode or single-mode fibers with LC connectors are used for transfer (BST) that is, transferring of user configurable binary
line differential communication. The channel is used for information between the relays. There are a total of eight BST
transferring the phase segregated current value data between signals available for user definable purposes. The BST signals
the relays. The current phasors from the two relays, can originate from the relays binary inputs or internal logics,
geographically located apart from each other, must be time and be assigned to the remote relays binary outputs or internal
coordinated so that the current differential algorithm can be logics.
executed correctly. The so called echo method is used for time
The protection communication supervision continuously
synchronization. No external devices such as GPS clocks are
monitors the protection communication link. The relay
thereby needed for the line differential protection
immediately blocks the line differential protection function in
communication.
case that severe interference in the communication link, risking
As an option to the fiber optic communication link a galvanic the correct operation of the function, is detected. An alarm
connection over a pilot wire link composed of a twisted pair signal will eventually be issued if the interference, indicating
cable and RPW600 link-end communication modems can be permanent failure in the protection communication, persists.
established. The optional pilot wire communication link is also The two high-set stages of the overcurrent protection are
an ideal and cost efficient retrofit solution for electromechanical further by default released.
line differential protection installations. Compared to
ABB 19
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
RED615 RED615
GUID-8CE71CC9-F0EA-4BE9-B693-173CAEA9FA58 V2 EN
RED615 RED615
GUID-12C57326-6CB9-4FA9-B9F4-3D8F21015DCF V2 EN
18. Access control Furthermore, the adapters also enable the use of sensors with
To protect the relay from unauthorized access and to maintain Twin-BNC connectors.
information integrity, the relay is provided with a four-level, role-
based authentication system with administrator-programmable The phase-current inputs are rated 1/5 A. Two optional
individual passwords for the viewer, operator, engineer and residual-current inputs are available, that is, 1/5 A or 0.2/1 A.
administrator levels. The access control applies to the local The 0.2/1 A input is normally used in applications requiring
HMI, the Web HMI and PCM600. sensitive earth-fault protection and featuring core-balance
current transformers. The residual-voltage input covers the
rated voltages 60...210 V.
19. Inputs and outputs
Depending on the standard configuration selected, the relay is The phase-current input 1 A or 5 A, the residual-current input 1
equipped with three phase-current inputs and one residual- A or 5 A, alternatively 0.2 A or 1 A, and the rated voltage of the
current input for non-directional earth-fault protection and residual voltage input are selected in the relay software. In
current circuit supervision, or three phase-current inputs, one addition, the binary input thresholds 16176 V DC are selected
residual-current input and one residual voltage input for by adjusting the relays parameter settings.
directional earth-fault protection and current circuit
supervision. All binary inputs and outputs contacts are freely configurable
with the signal matrix or application configuration functionality
The standard configuration E includes one conventional of PCM600.
residual current (Io 0.2/1 A) input and three sensor inputs for the
direct connection of three combi-sensors with RJ-45 See the Input/output overview table and the terminal diagrams
connectors. As an alternative to combi-sensors, separate for more information about the inputs and outputs.
current and voltage sensors can be utilized using adapters.
20 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
AD 4 - - 12 4 PO + 6 SO - -
A AC
AF 4 - - 18 4 PO + 9 SO - -
AC 4 1 - 11 4 PO + 6 SO - -
B AA / AB
AE 4 1 - 17 4 PO + 9 SO - -
AD 4 - - 12 4 PO + 6 SO - -
C AC
AF 4 - - 18 4 PO + 9 SO - -
FE / FF AD 4 5 - 12 4 PO + 6 SO 2 1
D
AE / AF AG 4 5 - 16 4 PO + 6 SO - -
E DA AH 1 - 3 8 4 PO + 6 SO - -
20. Station communication protection schemes. The relay meets the GOOSE performance
The relay supports a range of communication protocols requirements for tripping applications in distribution
including IEC 61850 Edition 2, IEC 61850-9-2 LE, IEC substations, as defined by the IEC 61850 standard (<10 ms
60870-5-103, Modbus and DNP3. Profibus DPV1 data exchange between the devices). The relay also supports
communication protocol is supported with using the protocol the sending and receiving of analog values using GOOSE
converter SPA-ZC 302. Operational information and controls messaging. Analog GOOSE messaging enables easy transfer of
are available through these protocols. However, some analog measurement values over the station bus, thus
communication functionality, for example, horizontal facilitating for example the sending of measurement values
communication between the relays, is only enabled by the IEC between the relays when controlling parallel running
61850 communication protocol. transformers.
The IEC 61850 protocol is a core part of the relay as the The relay also supports IEC 61850 process bus by sending
protection and control application is fully based on standard sampled values of analog currents and voltages and by
modelling. The relay supports Edition 2 and Edition 1 versions receiving sampled values of voltages. With this functionality the
of the standard. With Edition 2 support, the relay has the latest galvanic interpanel wiring can be replaced with Ethernet
functionality modelling for substation applications and the best communication. The measured values are transferred as
interoperability for modern substations. It incorporates also the sampled values using IEC 61850-9-2 LE protocol. The intended
full support of standard device mode functionality supporting application for sampled values shares the voltages to other 615
different test applications. Control applications can utilize the series relays, having voltage based functions and 9-2 support.
new safe and advanced station control authority feature. 615 relays with process bus based applications use IEEE 1588
for high accuracy time synchronization.
The IEC 61850 communication implementation supports
monitoring and control functions. Additionally, parameter For redundant Ethernet communication, the relay offers two
settings, disturbance recordings and fault records can be optical Ethernet network interfaces. Ethernet network
accessed using the IEC 61850 protocol. Disturbance redundancy can be achieved using the high-availability
recordings are available to any Ethernet-based application in seamless redundancy (HSR) protocol or the parallel
the standard COMTRADE file format. The relay supports redundancy protocol (PRP) or a with self-healing ring using
simultaneous event reporting to five different clients on the RSTP in managed switches. Ethernet redundancy can be
station bus. The relay can exchange data with other devices applied to Ethernet-based IEC 61850, Modbus and DNP3
using the IEC 61850 protocol. protocols.
The relay can send binary and analog signals to other devices All communication card variants support self-healing ring based
using the IEC 61850-8-1 GOOSE (Generic Object Oriented Ethernet redundancy. Communication card variants with two
Substation Event) profile. Binary GOOSE messaging can, for optical interfaces for station bus communication have support
example, be employed for protection and interlocking-based for HSR and PRP redundancy protocols. These variants include
also support for IEEE 1588 based time synchronization.
ABB 21
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
The IEC 61850 standard specifies network redundancy which switches fail, thus fulfilling all the stringent real-time
improves the system availability for the substation requirements of substation automation.
communication. The network redundancy is based on two
complementary protocols defined in the IEC 62439-3 standard: In PRP, each network node is attached to two independent
PRP and HSR protocols. Both the protocols are able to networks operated in parallel. The networks are completely
overcome a failure of a link or switch with a zero switch-over separated to ensure failure independence and can have
time. In both the protocols, each network node has two different topologies. The networks operate in parallel, thus
identical Ethernet ports dedicated for one network connection. providing zero-time recovery and continuous checking of
The protocols rely on the duplication of all transmitted redundancy to avoid failures.
information and provide a zero switch-over time if the links or
COM600
SCADA
HSR applies the PRP principle of parallel operation to a single sender node discards the frame to avoid loops. The HSR ring
ring. For each message sent, the node sends two frames, one with 615 series relays supports the connection of up to 30
through each port. Both the frames circulate in opposite relays. If more than 30 relays are to be connected, it is
directions over the ring. Every node forwards the frames it recommended to split the network into several rings to
receives from one port to another to reach the next node. When guarantee the performance for real-time applications.
the originating sender node receives the frame it sent, the
22 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
COM600
Devices not supporting HSR
SCADA
Ethernet switch
The choice between the HSR and PRP redundancy protocols solution supports the connection of up to 30 615 series relays.
depends on the required functionality, cost and complexity. If more than 30 relays are to be connected, it is recommended
to split the network into several rings. The self-healing Ethernet
The self-healing Ethernet ring solution enables a cost-efficient ring solution avoids single point of failure concerns and
communication ring controlled by a managed switch with improves the reliability of the communication.
standard Rapid Spanning Tree Protocol (RSTP) support. The
managed switch controls the consistency of the loop, routes The self-healing Ethernet ring solution avoids single point of
the data and corrects the data flow in case of a communication failure concerns and improves the reliability of the
switch-over. The relays in the ring topology act as unmanaged communication. The solution can be applied for the Ethernet-
switches forwarding unrelated data traffic. The Ethernet ring based IEC 61850, Modbus and DNP3 protocols.
ABB 23
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Client A Client B
Network A
Network B
GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V4 EN
All communication connectors, except for the front port 615 series supports Profibus DPV1 with support of SPA-ZC
connector, are placed on integrated optional communication 302 Profibus adapter. If Profibus is required the relay must be
modules. The relay can be connected to Ethernet-based ordered with Modbus serial options. Modbus implementation
communication systems via the RJ-45 connector (100Base-TX) includes SPA-protocol emulation functionality. This
or the fiber optic LC connector (100Base-FX). functionality enables connection to SPA-ZC 302.
Modbus implementation supports RTU, ASCII and TCP modes. When the relay uses the RS-485 bus for the serial
Besides standard Modbus functionality, the relay supports communication, both two- and four wire connections are
retrieval of time-stamped events, changing the active setting supported. Termination and pull-up/down resistors can be
group and uploading of the latest fault records. If a Modbus configured with jumpers on the communication card so external
TCP connection is used, five clients can be connected to the resistors are not needed.
relay simultaneously. Further, Modbus serial and Modbus TCP
can be used in parallel, and if required both IEC 61850 and The relay supports the following time synchronization methods
Modbus protocols can be run simultaneously. with a time-stamping resolution of 1 ms.
24 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
The relay supports the following high accuracy time Layer 2 mapping
synchronization method with a time-stamping resolution of 4 s Peer to peer delay calculation
required especially in process bus applications. Multicast operation
PTP (IEEE 1588) v2 with Power Profile
Required accuracy of grandmaster clock is +/-1 s. The relay
can work as a master clock per BMC algorithm if the external
The IEEE 1588 support is included in all variants having a grandmaster clock is not available for short term.
redundant Ethernet communication module.
The IEEE 1588 support is included in all variants having a
IEEE 1588 v2 features redundant Ethernet communication module.
Ordinary Clock with Best Master Clock algorithm
One-step Transparent Clock for Ethernet ring topology In addition, the relay supports time synchronization via
1588 v2 Power Profile Modbus, DNP3 and IEC 60870-5-103 serial communication
Receive (slave): 1-step/2-step protocols.
Transmit (master): 1-step
IEC 61850-8-1 - -
IEC 61850-9-2 LE -
MODBUS RTU/ASCII - -
MODBUS TCP/IP - -
DNP3 (serial) - -
DNP3 TCP/IP - -
IEC 60870-5-103 - -
= Supported
ABB 25
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Table 6. Dimensions
Description Value
Case 164 mm
Case 160 mm
Nominal auxiliary voltage Un 100, 110, 120, 220, 240 V AC, 50 and 60 Hz 24, 30, 48, 60 V DC
Burden of auxiliary voltage supply under DC <13.0 W (nominal)/<18.0 W (max.) DC <13.0 W (nominal)/<18.0 W (max.)
quiescent (Pq)/operating condition AC <16.0 W (nominal)/<21.0 W (max.)
Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)
Description Value
Continuously 4A 20 A
Voltage withstand:
Continuous 240 V AC
For 10 s 360 V AC
26 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Description Value
Current sensor input Rated current voltage (in secondary 75 mV...9000 mV1)
side)
Description Value
Description Value
RTD inputs Supported RTD sensors 100 platinum TCR 0.00385 (DIN 43760)
250 platinum TCR 0.00385
100 nickel TCR 0.00618 (DIN 43760)
120 nickel TCR 0.00618
250 nickel TCR 0.00618
10 copper TCR 0.00427
2.0% or 1 1C
10 copper: 2C
ABB 27
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Description Value
Breaking capacity when the control-circuit time constant L/R<40 ms 1 A/0.25 A/0.15 A
Description Value
Breaking capacity when the control-circuit time constant L/R<40 ms, at 1 A/0.25 A/0.15 A
48/110/220 V DC
Description Value
Breaking capacity when the control-circuit time constant L/R<40 ms, at 5 A/3 A/1 A
48/110/220 V DC (two contacts connected in series)
Description Value
Breaking capacity when the control-circuit time constant L/R<40 ms, at 5 A/3 A/1 A
48/110/220 V DC
28 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Description Value
Breaking capacity when the control-circuit time constant L/R <40 ms, at 5 A/3 A/1 A
48/110/220 V DC
Front TCP/IP protocol Standard Ethernet CAT 5 cable with RJ-45 connector 10 MBits/s
Connector Fibre type Wave length Typical max. Permitted path attenuation2)
length1)
1) Maximum length depends on the cable attenuation and quality, the amount of splices and connectors in the path.
2) Maximum allowed attenuation caused by connectors and cable altogether
3) Use single-mode fiber with recommended minimum length of 3 m to connect RED615 to the pilot wire modem RPW600.
Description Value
Modulation Unmodulated
Description Value
Front side IP 54
ABB 29
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Description Value
Altitude Up to 2000 m
1) Degradation in MTBF and HMI performance outside the temperature range of -25...+55 C
2) For relays with an LC communication interface the maximum operating temperature is +70 C
30 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Contact discharge 8 kV
Air discharge 15 kV
All ports 4 kV
2s 100 A/m
ABB 31
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Conducted
Radiated
32 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
1) For relays with an LC communication interface the maximum operating temperature is +70o C
Description Reference
LV directive 2006/95/EC
Description Reference
Description
ABB 33
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Protection functions
Characteristic Value
PHIPTOC:
IFault = 2 set Start value 16 ms 19 ms 23 ms
IFault = 10 set Start value
11 ms 12 ms 14 ms
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
Operate time accuracy in inverse time mode 5.0% of the theoretical value or 20 ms 3)
1) Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 In, fn = 50 Hz, fault current in one phase
with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Includes the delay of the heavy-duty output contact
PHIPTOC 20...200000 ms 10
34 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Characteristic Value
DPHLPDOC Current:
1.5% of the set value or 0.002 In
Voltage:
1.5% of the set value or 0.002 Un
Phase angle: 2
DPHHPDOC Current:
1.5% of the set value or 0.002 In
(at currents in the range of 0.110 In)
5.0% of the set value
(at currents in the range of 1040 In)
Voltage:
1.5% of the set value or 0.002 Un
Phase angle: 2
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
Operate time accuracy in inverse time mode 5.0% of the theoretical value or 20 ms3)
1) Measurement mode and Pol quantity = default, current before fault = 0.0 In, voltage before fault = 1.0 Un, fn = 50 Hz, fault current in one phase with nominal frequency injected from
random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 In, Start value multiples in range of 1.5...20
ABB 35
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Characteristic Value
EFIPTOC:
IFault = 2 set Start value 16 ms 19 ms 23 ms
IFault = 10 set Start value 11 ms 12 ms 14 ms
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
Operate time accuracy in inverse time mode 5.0% of the theoretical value or 20 ms 3)
1) Measurement mode = default (depends on stage), current before fault = 0.0 In, fn = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 In, Start value multiples in range of 1.5...20
EFIPTOC 20...200000 ms 10
36 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Characteristic Value
DEFLPDEF Current:
1.5% of the set value or 0.002 In
Voltage
1.5% of the set value or 0.002 Un
Phase angle:
2
DEFHPDEF Current:
1.5% of the set value or 0.002 In
(at currents in the range of 0.110 In)
5.0% of the set value
(at currents in the range of 1040 In)
Voltage:
1.5% of the set value or 0.002 Un
Phase angle:
2
DEFHPDEF
IFault = 2 set Start value 42 ms 46 ms 49 ms
DEFLPDEF 58 ms 62 ms 66 ms
IFault = 2 set Start value
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
Operate time accuracy in inverse time mode 5.0% of the theoretical value or 20 ms 3)
1) Set Operate delay time = 0.06 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 In , fn = 50 Hz, earth-fault current with
nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 In, Start value multiples in range of 1.5...20
ABB 37
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
DEFHPDEF 40...200000 ms 10
Characteristic Value
1.0% or 0.01 mS
(In range of 0.5...100 mS)
56 ms 60 ms 64 ms
Reset time 40 ms
1) Uo = 1.0 Un
2) Includes the delay of the signal output contact, results based on statistical distribution of 1000 measurements
38 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Characteristic Value
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
1) Io varied during the test, Uo = 1.0 Un = phase to earth voltage during earth fault in compensated or un-earthed network, the residual power value before fault = 0.0 pu, fn = 50 Hz, results
based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
ABB 39
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Characteristic Value
Operation accuracy (Uo criteria with transient protection) Depending on the frequency of the measured current: fn 2 Hz
40 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Characteristic Value
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
-3 dB at f = 13 fn
1) Fundamental frequency current = 1.0 I n , harmonics current before fault = 0.0 In , harmonics fault current 2.0 Start value, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 In, Start value multiples in range of 2...20
Characteristic Value
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
Operate time accuracy in inverse time mode 5.0% of the theoretical value or 20 ms 3)
1) Negative sequence current before fault = 0.0, fn = 50 Hz, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 In, Start value multiples in range of 1.5...20
ABB 41
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Characteristic Value
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
Characteristic Value
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
1) Residual voltage before fault = 0.0 Un , fn = 50 Hz, residual voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact
42 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Characteristic Value
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
Operate time accuracy in inverse time mode 5.0% of the theoretical value or 20 ms3)
1) Start value = 1.0 Un, Voltage before fault = 1.1 Un, fn = 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Minimum Start value = 0.50, Start value multiples in range of 0.90...0.20
ABB 43
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Characteristic Value
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
Operate time accuracy in inverse time mode 5.0% of the theoretical value or 20 ms3)
1) Start value = 1.0 Un, Voltage before fault = 0.9 Un, fn = 50 Hz, overvoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 1.20 Un, Start value multiples in range of 1.10...2.00
Characteristic Value
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
1) Start value = 1.0 Un, positive-sequence voltage before fault = 1.1 Un, fn = 50 Hz, positive sequence undervoltage with nominal frequency injected from random phase angle, results based
on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
44 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Characteristic Value
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
1) Negative-sequence voltage before fault = 0.0 Un, fn = 50 Hz, negative-sequence overvoltage with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Includes the delay of the signal output contact
Characteristic Value
df/dt <120 ms
ABB 45
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Table 61. Three-phase thermal protection for feeders, cables and distribution transformers (T1PTTR)
Characteristic Value
Table 62. Three-phase thermal protection for feeders, cables and distribution transformers (T1PTTR) main settings
Table 63. Three-phase thermal overload protection, two time constants (T2PTTR)
Characteristic Value
46 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Table 64. Three-phase thermal overload protection, two time constants (T2PTTR) main settings
Operation T2PTTR 1 = on -
5 = off
Characteristic Value
Characteristic Value
ABB 47
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Characteristic Value
Current measurement:
1.5% of the set value or 0.002 In
Ratio I2f/I1f measurement:
5.0% of the set value
Characteristic Value
Characteristic Value
48 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Characteristic Value
Impedance:
2.5% or 0.25
Distance:
2.5% or 0.16 km/0.1 mile
XC0F_CALC:
2.5% or 50
IFLT_PER_ILD:
5% or 0.05
Table 76. Line differential protection with in-zone power transformer (LNPLDF)
Characteristics Value
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
Operate time accuracy in inverse time mode 5.0% of the set value or 20 ms 4)
1) With the symmetrical communication channel (as when using dedicated fiber optic).
2) Without additional delay in the communication channel (as when using dedicated fiber optic).
3) Including the delay of the output contact. When differential current = 2 High operate value and fn = 50 Hz with galvanic pilot wire link + 5 ms.
4) Low operate value multiples in range of 1.5...20.
ABB 49
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Table 77. Line differential protection with in-zone power transformer (LNPLDF) main settings
50 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Characteristic Value
Characteristic Value
Operation VSQVUB 1 = on -
5 = off
ABB 51
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Control functions
Characteristic Value
Characteristic Value
Voltage:
3.0% of the set value or 0.01 Un
Frequency:
10 mHz
Phase angle:
3
Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
52 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Characteristic Value
Characteristic Value
Characteristic Value
Operate time1) NPS function UFault = 1.1 set Neg Seq voltage <33 ms
Lev
UFault = 5.0 set Neg Seq voltage <18 ms
Lev
1) Includes the delay of the signal output contact, fn = 50 Hz, fault voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
Description Value
ABB 53
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Measurement functions
Characteristic Value
0.5% or 0.002 In
(at currents in the range of 0.01...4.00 In)
Characteristic Value
1.0% or 0.002 In
at currents in the range of 0.01...4.00 In
Characteristic Value
0.5% or 0.002 In
at currents in the range of 0.01...4.00 In
Characteristic Value
0.5% or 0.002 Un
Characteristic Value
0.5% or 0.002 Un
54 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Characteristic Value
1.0% or 0.002 Un
Characteristic Value
Description Value
RTD inputs Supported RTD sensors 100 platinum TCR 0.00385 (DIN 43760)
250 platinum TCR 0.00385
100 nickel TCR 0.00618 (DIN 43760)
120 nickel TCR 0.00618
250 nickel TCR 0.00618
10 copper TCR 0.00427
2.0% or 1 1C
10 copper: 2C
Characteristic Value
ABB 55
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Other functions
Characteristic Value
Characteristic Value
Characteristic Value
56 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
22. Local HMI default single line diagram. The SLD view can also be accessed
The relay is available with two optional displays, a large one and using the Web browser-based user interface. The default SLD
a small one. The large display is suited for relay installations can be modified according to user requirements by using the
where the front panel user interface is frequently used and a Graphical Display Editor in PCM600. The user can create up to
single line diagram is required. The small display is suited for 10 SLD pages.
remotely controlled substations where the relay is only
occasionally accessed locally via the front panel user interface. The local HMI includes a push button (L/R) for local/remote
operation of the relay. When the relay is in the local mode, it can
Both LCD displays offer front-panel user interface functionality be operated only by using the local front panel user interface.
with menu navigation and menu views. However, the large When the relay is in the remote mode, it can execute
display offers increased front-panel usability with less menu commands sent from a remote location. The relay supports the
scrolling and improved information overview. In addition, the remote selection of local/remote mode via a binary input. This
large display includes a user-configurable single line diagram feature facilitates, for example, the use of an external switch at
(SLD) with position indication for the associated primary the substation to ensure that all relays are in the local mode
equipment. Depending on the chosen standard configuration, during maintenance work and that the circuit breakers cannot
the relay displays the related measuring values, apart from the be operated remotely from the network control center.
IECA070904 V3 EN IECA070901 V3 EN
ABB 57
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
190
6
18
164
177
25
160
160
177
177
230
98
107
48
1 53 133
103
Figure 18. Flush mounting Figure 19. Semi-flush mounting Figure 20. Semi-flush mounting in a 25 tilt
24. Relay case and plug-in unit 25. Selection and ordering data
The relay cases are assigned to a certain type of plug-in unit. Use ABB Library to access the selection and ordering
For safety reasons, the relay cases for current measuring relays information and to generate the order number.
are provided with automatically operating contacts for short-
circuiting the CT secondary circuits when a relay unit is Product Selection Tool (PST), a Next-Generation Order Number
withdrawn from its case. The relay case is further provided with Tool, supports order code creation for ABB Distribution
a mechanical coding system preventing the current measuring Automation IEC products with emphasis on but not exclusively
relay units from being inserted into relay cases intended for for the Relion product family. PST is an easy to use, online tool
voltage measuring relay units. always containing the latest product information. The complete
order code can be created with detailed specification and the
result can be printed and mailed. Registration is required.
58 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Pilot Wire communication package including two Pilot Wire modems: RPW600AM (master) and RPW600AF RPW600AMF
(follower)
Diagnostics kit including the RPW-diagnostic tool, a diagnostic cable and a CD with necessary drivers and RPW600ADP
information
3.0 meter LC-LC single-mode fiber-optic patch cable for connecting one Pilot Wire modem to the RED615 relay1) 1MRS120547-3
1) Two patch cables are required for connecting the Pilot Wire communication package (RPW600AMF).
Mounting bracket for one relay with test switch RTXP in 4U Combiflex (RHGT 19 variant C) 2RCA022642P0001
19 rack mounting kit for one relay and one RTXP18 test switch (the test switch is not included in the delivery) 2RCA021952A0003
19 rack mounting kit for one relay and one RTXP24 test switch (the test switch is not included in the delivery) 2RCA022561A0003
Replacement kit for a Strmberg SP_J40 series relay (cut-out in the center of the installation plate) 2RCA027871A0001
Replacement kit for a Strmberg SP_J40 series relay (cut-out on the left or the right of the installation plate) 2RCA027874A0001
19 rack replacement kit for Strmberg SP_J3/J6 series relays (one cut-out) 2RCA027894A0001
19 rack replacement kit for Strmberg SP_J3/J6 series relays (two cut-outs) 2RCA027897A0001
1) Cannot be used when the protection relay is mounted with the Combiflex 19" equipment frame (2RCA032826A0001)
connectivity packages reduce the risk of errors in system additional local HMI language to the protection relay. The
integration, minimizing device configuration and setup times. update tool is activated using PCM600, and it enables multiple
Further, the connectivity packages for protection relays of this updates of the additional HMI language, thus offering flexible
product series include a flexible update tool for adding one means for possible future language updates.
Description Version
Signal monitoring
Application configuration -
Event viewing
Online monitoring -
= Supported
28. Cyber security and Web HMI use TLS encryption with a minimum of 128 bit key
The relay supports role based user authentication and length protecting the data in transit. In this case the used
authorization. It can store 2048 audit trail events to a non- communication protocols are FTPS and HTTPS. All rear
volatile memory. The non-volatile memory is based on a communication ports and optional protocol services can be
memory type which does not need battery backup or regular deactivated according to the required system setup.
component exchange to maintain the memory storage. FTP
60 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
GUID-FBFA9940-E37D-4C32-A083-0367AAEDE267 V2 EN
ABB 61
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
GUID-A05D9233-4377-48D7-9F00-4218F0E7D4DC V2 EN
62 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
RED615
X120 X100
1 + 1
BI 1 U aux
2 2
-
3 3
BI 2
IRF
4
4 5
BI 3
PO1
5
BI 4
6 6
7 1/5A 2) 7
IL1
8 N PO2
9 1/5A
IL2 8
10 N 9
11 1/5A 10
IL3 SO1
12 N
1/5A 11
Io 12
14 N 13
SO2
X130 14
1 6) 16
BI 1 PO3
2
17
3 15
BI 2 19
4 TCS1 18
5 20
BI 3 22
6
PO4
7 21
BI 4
8 23
60 - TCS2 24
9 210V
U12B
10 N
60 -
11 210V
U1
12 N
60 -
13 210V
U2
14 N
60 -
15 210V
U3
16 N
60 -
17 210V
Uo
18 N
X110 X110
1 14
BI 1
2 SO1
16
3 15
BI 2
4 17
SO2
5
BI 3 19
6 18
20
BI 4 SO3
7
22
8 21
BI 5 23
9
SO4
BI 6 24
10
11
BI 7
12
BI 8
13
X1
1) 3)
LAN
X2
1) 3)
LAN
X5 1) 4)
1 GND
2 GNDC
3 IRIG-B -
4 IRIG-B + 1) Optional
5 AGND
6 B/- / TX 2) The IED features an automatic short-circuit
7 A/+ mechanism in the CT connector when plug-in
8 B/- unit is detached
9 A/+ / RX 3) 100BaseFx / LC or 100BaseTx / RJ-45
4) RS-485 serial bus
X12 5) Fibre Optic (ST) Serial Bus
1) 5)
RX 6) AIM0006 (5U+4BI)
TX Alternative Module AIM0003 (5U+2RTD+1mA)
X16
Line Differential Protection Communication
GUID-EE704FD2-E4A7-4745-B84D-95033D4DC5AA V2 EN
ABB 63
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
RED615
X130 X100
+ 1
1 0,2/1A
U aux
Io 2
2 N -
3
X131 IRF
4
4 5
IL1
5
7 PO1
U1
8
6
X132 7
4 PO2
IL2
5
8
7 9
U2
8 10
X133 SO1
11
4 12
IL3
5 13
7 SO2
U3
8 14
16
PO3
17
15
19
TCS1 18
20
22
X110 PO4
1 21
BI 1 23
2
TCS2 24
3
BI 2
4
5 X110
BI 3
6 14
SO1
BI 4 16
7 15
8 17
BI 5 SO2
9
19
18
BI 6 20
10
SO3
11 22
BI 7
12 21
23
BI 8 SO4
13 24
X1
1) 3)
LAN
X2
1) 3)
LAN
X5 1) 4)
1 GND
2 GNDC
3 IRIG-B -
4 IRIG-B +
5 AGND
6 B/- / TX
7 A/+
8 B/- 1) Optional
9 A/+ / RX 2) The IED features an automatic short-circuit
mechanism in the CT connector when plug-in
X12 unit is detached
1) 5) 3) 100BaseFx / LC or 100BaseTx / RJ-45
RX
TX 4) RS-485 serial bus
5) Fibre Optic (ST) Serial Bus
X16
Line Differential Protection Communication
GUID-33733308-95B9-4B59-B5DC-E15AFA16E05E V1 EN
64 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
30. Certificates For information regarding the RPW600 modems please refer to
DNV GL has issued an IEC 61850 Edition 2 Certificate Level A1 the RPW600 Users Guide, document id 6621-2260. The
for Relion 615 series. Certificate number: 7410570I-OPE/INC document is available for download on the RED615
15-1136. product page. Scroll down the page to find and download the
related documentation.
DNV GL has issued an IEC 61850 Edition 1 Certificate Level A1
for Relion 615 series. Certificate number: 74105701-OPE/INC
15-1145.
31. References
The www.abb.com/substationautomation portal provides
information on the entire range of distribution automation
products and services.
ABB 65
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Protection
Three-phase non-directional overcurrent protection, low PHLPTOC1 3I> (1) 51P-1 (1)
stage
Three-phase non-directional overcurrent protection, high PHHPTOC1 3I>> (1) 51P-2 (1)
stage
PHHPTOC2 3I>> (2) 51P-2 (2)
Three-phase directional overcurrent protection, low stage DPHLPDOC1 3I> -> (1) 67-1 (1)
Three-phase directional overcurrent protection, high stage DPHHPDOC1 3I>> -> (1) 67-2 (1)
Non-directional earth-fault protection, low stage EFLPTOC1 Io> (1) 51N-1 (1)
Non-directional earth-fault protection, high stage EFHPTOC1 Io>> (1) 51N-2 (1)
Non-directional earth-fault protection, instantaneous stage EFIPTOC1 Io>>> (1) 50N/51N (1)
Directional earth-fault protection, low stage DEFLPDEF1 Io> -> (1) 67N-1 (1)
Directional earth-fault protection, high stage DEFHPDEF1 Io>> -> (1) 67N-2 (1)
Transient/intermittent earth-fault protection INTRPTEF1 Io> -> IEF (1) 67NIEF (1)
Non-directional (cross-country) earth-fault protection, using EFHPTOC1 Io>> (1) 51N-2 (1)
calculated Io
66 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Three-phase thermal protection for feeders, cables and T1PTTR1 3Ith>F (1) 49F (1)
distribution transformers
Three-phase thermal overload protection, two time constants T2PTTR1 3Ith>T/G/C (1) 49T/G/C (1)
Line differential protection with in-zone power transformer LNPLDF1 3Id/I> (1) 87L (1)
ABB 67
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
Power quality
Control
Earthing switch control ESXSWI1 I <-> O ESC (1) I <-> O ESC (1)
Runtime counter for machines and devices MDSOPT1 OPTS (1) OPTM (1)
Measurement
Sequence current measurement CSMSQI1 I1, I2, I0 (1) I1, I2, I0 (1)
Sequence voltage measurement VSMSQI1 U1, U2, U0 (1) V1, V2, V0 (1)
68 ABB
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1
IEC 61850-9-2 LE sampled value receiving (voltage sharing) SMVRCV SMVRCV SMVRCV
Other
Minimum pulse timer (2 pcs, second resolution) TPSGAPC1 TPS (1) TPS (1)
Minimum pulse timer (2 pcs, minute resolution) TPMGAPC1 TPM (1) TPM (1)
Generic control point (16 pcs) SPCGAPC1 SPC (1) SPC (1)
ABB 69
Line Differential Protection and Control 1MRS756500 L
RED615
Product version: 5.0 FP1