Transformer Damage These observations led us to conclude that

Curve Made Easy in order to draw a damage curve correctly for


a protective device, we must shift the damage
Plotting transformer damage curves is
curve horizontally by the ratio r=(max protective
childs play in DistriView V7, thanks to a
device current in primary amps)/(max trans-
new algorithm we just developed. A similar
former winding current on the side of the
feature will appear in the next major release
protective device). The following example with
of OneLiner.
a wye-delta transformer demonstrates how
this method works.
The first case is a single-line-to-ground
fault on phase a on the low side of the
transformer (Fig. 2). The fault currents

Fig. 3: Three-phase fault.

except we shift the damage curve horizontally


to the right by 1.73 as the final step.
So far we have been plotting the fuse curve
and the transformer damage curve as a function
Fig. 1: Dialog box for damage curve.
of the high-side current. It is a common industry
The new automatic damage-curve feature practice to plot these curves on the basis of the
requires the user to simply associate the damage low-side current. DistriView does this by first
curve with a fuse, recloser or relay that is computing the fuse curve and the transformer
protecting a transformer. (See Fig. 1) The curve for the high side as described above, and
program does the rest. The old method of then shifting both curves to the right by the ratio
specifying the transformer rating, impedance of (low-side fault current)/(fuse current). This
and base current is still there. It is now called shifting preserves the separation between the
Fig. 2: Single-line-to-ground fault.
the manual method. Gone is the old link fuse curve and the transformer damage curve.
damage curve to relay curve feature. In fact, if on the high side are confined to the delta The strength of our method is that it is
you had selected this link option in a previous winding between phases a and c. This is based on physical principles, and it does
version, you will get the new automatic option a special case in which the fuse current not rely on any standard table lookup. We
when you open the file with DistriView V7. is exactly the same as the maximum winding
To understand the new damage-curve I N T H I S I S S U E
current. The ratio r is equal to 1, which
algorithm, it is important to note that trans- implies that we can draw the damage curve Transformer Damage Curve
former damage curves are designed to work simply by using the transformer MVA rating Made Easy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cover
New Features in Relay Database
with the maximum winding current, and that and impedance, and the one-per-unit base
Web Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
the winding current does not always equal current on the high side. Relay Database Security Improved . . . . . . . . . . . 2
the current sensed by the protective device. In the second case, a three-phase fault Upcoming Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
For example, for a fuse on the delta side of is applied to the low side bus (Fig. 3). The New Users . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
a wye-delta transformer, the fuse senses a fault currents are balanced on both sides of
phase current that enters the transformer the transformer. In this case, the fuse current
bushing. This current is generally not the is higher than the delta winding current by a ASPEN
34 North San Mateo Dr., San Mateo, CA 94401
same as any of the winding currents that ratio r of 1.73. To draw the damage curve for Phone: (650)347-3997 FAX: (650)347-0233
info@aspeninc.com www.aspeninc.com
flow through the delta windings. this case, we use the same method as before,
Relay Database
Security Improved
In the latest version of the ASPEN Relay
Database (V8), the user passwords are one-way
encrypted. One-way encryption ensures that
no one can decrypt the passwords both
practically and theoretically even if one has
access to the user-information table.
Also, since version 8.6, the administrator
of the Client/Server Version can enable
the High Security options that enforce
complex password, password length, password
expiration, limit on login attempts, and time-
out after failure. These options substantially
comply with mandates from the U.S. Homeland
Security Department for databases maintained
by government agencies.

New Users
OneLiner
Allgeier, Martin & Associates, Joplin, MO
Fig. 2: Web Interface read/write settings page.
Empresa Nacional de Electricidade,
Luanda, Angola
have found from extensive testing that the will gradually make more and more forms
GE Wind Energy, Schenectady, NY
method works for single or parallel trans- write-enabled, until the entire Web Interface
Stanley Consultants, Muscatine, IA
formers of any winding configuration, under is read/write.
City of Saskatoon, SK, Canada
classical or simultaneous faults. It works for We are working to add the SQL Builder to
KEMA TDC, Raleigh, NC
fuses and recloser. It also works for relays the Web Interface. This tool will help Web
Platte River Power Authority,
that sense phase currents and transformer Interface users query the database quickly Fort Collins, CO
neutral currents, as well as those that sense and easily, without having to learn the SQL Reedy Creek Improvement District,
Io, 3Io, I2 or 3I2. database language. The SQL Builder should Lake Buena Vista, FL.
appear in a maintenance update of the software
New Features in in October.
Power Flow
GE Wind Energy, Schenectady, NY
Relay Database Web Interface
Write-enabled data forms appeared in the
Upcoming Events DistriView
Hydro Ottawa, Ottawa, ON, Canada
latest ASPEN Relay Database Web Interface OneLiner Users Group Meeting:
Unisource Energy Services, Tucson, AZ
Morning of Monday, October 18, 2004,
for the first time. Users of the Relay Database Baccari & Associates, Sheridan, WY
in Spokane, WA.
should have received this new Web Interface TriAxis Engineering, Corvallis, OR
Relay Database Seminar:
with their V8.6 update in late August. Afternoon of Monday, October 18, 2004, Line Constants Program
Many users have told us that they want in Spokane, WA. Chelan County PUD, Wenatchee, WA
the capability of editing setting and test data Hospitality Suite: Saudi Consolidate Electricity Co.
through the Web Interface. For this reason, October 18-20 in Spokane, WA, -Southern Region, Abha, Saudi Arabia
the first forms we made write-enabled were during the Western Protective Relay Seattle City Light, WA
Conference.
the setting list form, the test list form, the KEMA TDC, Raleigh, NC
More information on these events are in
settings form, and the test form. (See Fig. 4 MSE Power Systems, Albany, NY
the News | Events page of our web site.
for a sample settings form.) Over time, we Ulteig Engineers, Minneapolis, MN

ASPEN Leaflet Editor: Sherman Chan. Readers are encouraged to submit articles to Editor, ASPEN Leaflet, 34 North San Mateo Dr., San Mateo, CA 94401.