Vous êtes sur la page 1sur 8

Evaporator Water Storage NOTES:

Evaporator Water NPS Pipe Size 1. Dimensional Tolerance +/- 6 mm


10 in 107 Gals (405 Liters)
Connection Size 2. Evaporator and Condenser Entering Fluid
(250 mm)
Connection is the Bottom Connection.
Condenser Water Condenser Water Storage Evaporator and Condenser Leaving Fluid
8 in NPS Pipe Size
Connection Size 61 Gals (231 Liters) Connection is the Top Connection.
(203.2 mm)
Short Circuit Withstand
Rating (RMS Symmetrical AMPS) 10000

TOPSS Dimension Drawing


PLAN VIEW ISOMETRIC VIEW

ALL WEIGHTS AND DIMENSIONS ARE APPROXIMATE.


HSS CORPORATE PLAZA TOWER PROJECT

LEFT END VIEW FRONT VIEW RIGHT END VIEW

Page: 1
Items: CH-04

1/23/2016 1:00:40 AM
Water-Cooled Series R(TM) RTHD

Qty: 1 Tags: CH-04


HSS CORPORATE PLAZA TOWER PROJECT Water-Cooled Series R(TM) RTHD
Items: CH-04
Qty: 1 Tags: CH-04
1/23/2016 1:00:40 AM

FRONT VIEW
3200 mm

TOPSS Dimension Drawing


ALL WEIGHTS AND DIMENSIONS ARE APPROXIMATE. Page: 2
2997 mm

151 mm 201 mm

(1) 1 1/4" NPT


124 mm Pressure Relief Valve
(2) 1 1/4" NPT
Pressure Relief Valve

25 mm NPT
PRESSURE
RELIEF
VALVE

TOPSS Dimension Drawing


173 mmX308 mm
ELECTRIC CONNECTION TOP

ALL WEIGHTS AND DIMENSIONS ARE APPROXIMATE.


25 mm NPT
HSS CORPORATE PLAZA TOWER PROJECT

PRESSURE
RELIEF
VALVE

4 mm

218 mm 276 mm

1060 mm

PLAN VIEW

Page: 3
Items: CH-04

1/23/2016 1:00:40 AM
Water-Cooled Series R(TM) RTHD

Qty: 1 Tags: CH-04


HSS CORPORATE PLAZA TOWER PROJECT Water-Cooled Series R(TM) RTHD
Items: CH-04
Qty: 1 Tags: CH-04
1/23/2016 1:00:40 AM

107 mm
INLET CONNECTION IS THE BOTTOM CONNECTION
OUTLET CONNECTION IS THE TOP CONNECTION

LEFT END VIEW


1732 mm
WHERE APPLICABLE:

1934 mm

TOPSS Dimension Drawing


ALL WEIGHTS AND DIMENSIONS ARE APPROXIMATE. Page: 4
HSS CORPORATE PLAZA TOWER PROJECT Water-Cooled Series R(TM) RTHD
Items: CH-04
Qty: 1 Tags: CH-04
1/23/2016 1:00:41 AM

657 mm

359 mm
INLET CONNECTION IS THE BOTTOM CONNECTION
OUTLET CONNECTION IS THE TOP CONNECTION

RIGHT END VIEW


1307 mm
WHERE APPLICABLE:

411 mm
318 mm
692 mm

TOPSS Dimension Drawing


ALL WEIGHTS AND DIMENSIONS ARE APPROXIMATE. Page: 5
HSS CORPORATE PLAZA TOWER PROJECT Water-Cooled Series R(TM) RTHD
Items: CH-04
Qty: 1 Tags: CH-04
1/23/2016 1:00:41 AM

ISOMETRIC VIEW
EVAP
COND

TOPSS Dimension Drawing


ALL WEIGHTS AND DIMENSIONS ARE APPROXIMATE. Page: 6
3353 mm
3658 mm
BEAM LENGTH

ANTI-ROLLING CABLE
EYELET OR M16 (CHAIN OR SLING) 610 mm
INTERNAL THREAD

44 mm
LIFTING HOLES

LEFT END VIEW FRONT VIEW RIGHT END VIEW

NOTES: LIFTING OPERATING WEIGHT


1. DO NOT USE CABLES (CHAINS OR SLINGS) WEIGHT (LB) WITH WATER (LB)
EXCEPT AS SHOWN. OTHER LIFTING
ARRANGEMENTS MAY CAUSE EQUIPMENT
7334 kg 7965 kg
DAMAGE OR SERIOUS PERSONAL INJURY.
2. EACH OF THE CABLES (CHAINS OR SLINGS) 914 mm

TOPSS Dimension Drawing


USED TO LIFT UNIT MUST BE CAPABLE OF
SUPPORTING THE ENTIRE WEIGHT OF THE
UNIT.
3. LIFTING CABLES (CHAINS OR SLINGS) MAY

ALL WEIGHTS AND DIMENSIONS ARE APPROXIMATE.


NOT BE THE SAME LENGTH. ADJUST AS 914 mm
NECESSARY FOR EVEN LEVEL LIFT.
HSS CORPORATE PLAZA TOWER PROJECT

4. ADJUST AS NECESSARY USING SINGLE


POINT LIFT. TO PREVENT UNIT FROM
ROLLING, ATTACH CABLE (CHAIN OR SLING)
WITHOUT ANY TENSION AS SHOWN.
5. DO NOT USE FORKLIFT TO MOVE OR
LIFT UNIT.
6. IF UNIT IS DISASSEMBLED, SEE SERVICE
BULLETIN RTHC-SB-2 FOR LIFTING AND 1626 mm
RIGGING OF COMPONENTS.

NOTE:
ALLOW 914 mm OF CLEARANCE ABOVE
THE STARTER ELECTRICAL CONNECTION DOOR.

1092 mm

5588 mm
7595 mm

PLAN VIEW

Page: 7
Items: CH-04

1/23/2016 1:00:41 AM
Water-Cooled Series R(TM) RTHD

Qty: 1 Tags: CH-04


HSS CORPORATE PLAZA TOWER PROJECT Water-Cooled Series R(TM) RTHD
Items: CH-04
Qty: 1 Tags: CH-04
1/23/2016 1:00:41 AM

WARNING
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POW ER
INCLUDING REMOTE DISCONNECTS AND
FOLLOW LOCK OUT AND TAG PROCEDURES
RTHD CONTROL PANEL BEFORE SERVICING. INSURE THAT ALL
MOTOR CAPACITORS HAVE DISCHARGED
STORED VOLTAGE. UNITS WITH VARIABLE
SPEED DRIVE, REFER TO DRIVE
INSTRUCTIONS FOR CAPACITOR DISCHARGE.
FAILURE TO DO THE ABOVE BEFORE
SERVICING COULD RESULT IN DEATH OR
SERIOUS INJURY.
6 20
1A12 5K22
4
AUTO/EMERGENCY W2 EMERGENCY STOP
STOP 3 5 20
5K21

J11
2
15 W1 AUTO STOP
1
J1

J2
L1 L2 L3
ATTACH
GROUND
3

10

12

13
1A14
EXTERNAL CHILLED CUSTOMER PROVIDED
6

EXTERNAL CURRENT W ATER SETPOINT INPUT CLASS II CONTROL


5

LIMIT & EXTERNAL 2-10VDC OR 4-20mA W IRING


CHILLED WATER
4

EXTERNAL CURRENT LIMIT TOP KNOCKOUTS


SETPOINT IN RIGHT SIDE OF
3

4 SETPOINT INPUT
J11

2-10VDC OR 4-20mA CONTROL BOX.


2

(OPTIONAL)
J2 1
J1

STARTER PANEL CONNECTION SELECT RLA LUG SIZE L1-L3 (EACH PHASE)

000-598 (2) #4-500MCM


TERMINAL BLOCK
599-779 N/A

000-200 (1) 3/0-350MCM

201-476 (2) 2/0-500MCM


MAIN CIRCUIT BREAKER
477-640 (3) 3/0-500MCM
1A15 5K13
EXTERNAL EXTERNAL BASE 25 20 641-779 (4) 3/0-500MCM
1 2 3 4

BASE LOAD COMMAND LOAD COMMAND


(OPTIONAL)
J11

4 000-277 (1) #1-600MCM


J1

J2

278-397 (2) 2/0-500MCM


NON-FUSED
DISCONNECT SWITCH
398-598 (3) 3/0-500MCM

599-779 (4) 3/0-500MCM

CAUTION
USE COPPER CONDUCTORS ONLY!
UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT
OTHER TYPES OF CONDUCTORS.
FAILURE TO DO SO MAY CAUSE DAMAGE TO THE
EQUIPMENT.

1A9
6 H CUSTOMER PROVIDED
19 CONDENSER
CHILLER 5 5K1 CHILLED WATER PUMP 115V 60HZ
WATER PUMP 4 N OR 220V 50HZ
STARTER 3
5K2
J11

2 CONDENSER W ATER PUMP


1
J1

J2

CHILLED W ATER
1A7 21 5S1
J3

5K1 AUX
W ATER FLOW 2
SW ITCH AND 1
INTERLOCKS CONDENSER W ATER
17 21 5S2
J2
J11

5K2 AUX
2

1
J1

24 1X6
26 1

CUSTOMER PROVIDED
CLASS I CONTROL
11 WIRING
BOTTOM KNOCKOUTS
1A10 16 IN RIGHT SIDE OF
H CUSTOMER PROVIDED
8 9 10 11 12
C

CONTROL BOX.
115V 60HZ POW ER
NO NC

5K4 19
MAX FUSE SIZE
UNIT OPERATING N IS 15 AMPS
NO NC C

STATUS 5K5 COMPRESSOR RUN RELAY


4
(OPTIONAL)
16
5 6 7

5K6
NO NC C

22

5K7 ALARM RELAY


4
NO NC C
2 3
J11

5K8
1
J1

J2

5K9 CHILLER LIMIT MODE RELAY

5K10

5K11 HEAD PRESSURE RELIEF REQUEST

15 THE CONTACTS FOR THESE FEATURES ARE JUMPERED AT THE FACTORY BY JUMPERS W1 & W2 TO ENABLE UNIT OPERATION. IF REMOTE
GENERAL NOTES: CONTROL IS DESIRED REMOVE THE JUMPERS AND CONNECT TO THE DESIRED CONTROL CIRCUIT.

16 FIELD PROVIDED 115 VOLT 60HZ OR 220 VOLT 50HZ CONTROL POWER SUPPLIES ARE REQUIRED. THE MAX FUSE SIZE FOR ALL FIELD
1. CAUTION-DO NOT ENERGIZE THE UNIT UNTIL CHECK OUT AND STARTUP PROCEDURES HAVE BEEN COMPLETED. PROVIDED WIRING IS 15 AMPS. GROUND ALL CUSTOMER PROVIDED POWER SUPPLIES AS REQUIRED BY CODE. GREEN GROUND SCREWS
2. ARE PROVIDED IN UNIT CONTROL PANEL.
COMPRESSOR MOTOR IS PROTECTED FROM PRIMARY SINGLE PHASE FAILURE.
17 CHILLED/CONDENSER WATER PUMP STARTER AUXILIARY CONTACTS TO BE WIRED IN SERIES WITH FLOW SWITCHES.
3 ALL UNIT POWER WIRING MUST BE COPPER CONDUCTORS ONLY AND HAVE A MINIMUM TEMPERATURE INSULATION RATING OF
75 DEGREE C (MRLA = 0-598) OR 90 DEGREE C (MRLA = 779). SEE UNIT NAMEPLATE FOR MINIMUM CIRCUIT AMPACITY
AND MAXIMUM FUSE SIZE REQUIREMENTS. USE 600 VOLT COPPER CONDUCTORS ONLY. 200 TO 600 VOLT CIRCUIT, PROVIDE
AN EQUIPMENT GROUND IN ACCORDANCE WITH APPLICABLE ELECTRIC CODES.

444 THESE FEATURES ARE OPTIONAL AND MAY OR MAY NOT BE PROVIDED. CUSTOMER PROVIDED WIRING FOR ALL STANDARD
FEATURES AND OPTIONS IS SHOWN ON THIS DIAGRAM. OPTIONAL FEATURES ARE SO NOTED.
CONTACT RATINGS AND REQUIREMENTS
5 OPENING THE EXTERNAL AUTO-STOP CONTACT WILL INITATE A SHUT DOWN SEQUENCE OF THE CHILLER. CLOSURE OF THE
CONTACT WILL ALLOW THE CHILLER TO RETURN TO NORMAL AUTOMATIC OPERATION. 19 UNIT PROVIDED DRY CONTACTS FOR THE CONDENSER/CHILLED WATER PUMP CONTROL. THE UNIT OPERATING STATUS RELAYS AND ICE
MAKING STATUS RELAY ARE RATED FOR 7.2 AMPS RESISTIVE, 2.88 AMPS PILOT DUTY, OR 1/3 HP, 7.2 FLA AT 120 VOLTS 60 HZ,
6 AN OPENING OF THE EMERGENCY STOP CONTACT WILL SHUT THE CHILLER DOWN IMMEDIATELY AND TRIGGER AN EMERGENCY CONTACTS ARE RATED FOR 5 AMPS GENERAL PURPOSE DUTY AT 240 VOLTS.
STOP INPUT DIAGNOSTIC. CLOSURE OF THE CONTACT AND A MANUAL RESET OF THE UNIT CONTROL DIAGNOSTIC WILL ALLOW
THE CHILLER TO RETURN TO NORMAL OPERATION. 20 CUSTOMER SUPPLIED CONTACTS FOR ALL LOW VOLTAGE CONNECTIONS MUST BE COMPATABLE WITH DRY CIRCUIT 24 VOLTS DC
FOR A 12 MA RESISTIVE LOAD. SILVER OR GOLD PLATED CONTACTS ARE RECOMMENDED.
21 FLOW SWITCH AND INTERLOCK CONTACTS MUST BE ACCEPTABLE FOR USE IN A 120 VOLT 1mA CIRCUIT. OR A 220 VOLT 2mA CIRCUIT.

22 THE FIELD PROVIDED INDICATORS MAY BE RELAYS, LIGHTS OR AUDIBLE DEVICES. EACH FUNCTION IS ASSOCIATED WITH A SPDT RELAY.
WIRING REQUIREMENTS THE INDICATORS FUNCTIONS MAY BE CONNECTED TO EITHER OR BOTH OF THE NORMALLY OPEN OR NORMALLY CLOSED RELAY CONTACTS
OF EACH OF THE 4 SPDT RELAYS ON THE OPTIONAL UNIT OPERATING STATUS MODULE.
8. RECOMMENDED FIELD WIRING CONNECTIONS ARE SHOWN BY DASHED LINES
THE FUNCTIONS OF THE OPERATING STATUS MODULE RELAYS ARE PROGRAMABLE. SEE IOM FOR DETAILS. DEFAULT FUNCTIONS ARE SHOWN.
9. ALL FIELD WIRING MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE AND STATE AND LOCAL REQUIREMENTS. THE NORMALLY OPEN CONTACTS ON EACH RELAY OPERATE AS FOLLOWS:
EXPORT UNIT WIRING MUST COMPLY WITH LOCAL APPLICABLE CODES.
COMPRESSOR THE NO CONTACTS CLOSE WHEN COMPRESSOR STATUS FROM STARTER MODULE IS EITHER STARTING OR RUNNING.
10 LINE VOLTAGE OPTIONS: RUNNING
UNIT MOUNTED TERMINAL BLOCK, DISCONNECT OR HACR CIRCUIT BREAKER. THE POWER WIRING LUG SIZE PROVIDED ON THE VARIOUS
ALARM RELAY THE NO CONTACTS CLOSE WHEN THERE IS AN DIAGNOSTIC THAT HAS CAUSED A CHILLER SHUTDOWN WITH EITHER
UNITS IS SHOWN IN TABLE 1. A MANUAL RESET REQUIRED OR AN AUTOMATIC RESET POTENTIAL.
11 CLASS I WIRING ,14 AWG, 600 VOLT CONDUCTORS. 115 VOLT CIRCUIT CHILLER LIMIT THE NO CONTACTS CLOSE WHENEVER THE CHILLER HAS BEEN RUNNING IN ONE OF THE UNLOADING TYPES OF
MODE RELAY LIMIT MODES (CONDENSER, EVAPORATOR, CURRENT LIMIT OR PHASE IMBALANCE LIMIT) CONTINUOUSLY FOR THE
12 ALL CUSTOMER CONTROL CIRCUIT WIRING MUST BE COPPER CONDUCTORS ONLY AND HAVE A MINIMUM INSULATION RATING OF 300 VOLTS. LAST 20 MINUTES.
EXCEPT AS NOTED ALL CUSTOMER WIRING CONNECTIONS ARE MADE TO CIRCUIT BOARD MOUNTED BOX LUGS WITH A WIRE RANGE OF 14 HEAD PRESSURE THE NO CONTACTS CLOSE ANYTIME THE CHILLER IS RUNNING IN ONE OF THE FOLLOWING MODES: ICE MAKING
TO 18 AWG. RELIEF REQUEST MODE OR CONDENSER PRESSURE LIMIT CONTROL MODE CONTINUOUSLY FOR THE DURATION SPECIFIED BY THE
CHILLER HEAD RELIEF RELAY FILTER TIME.
13 DO NOT RUN LOW VOLTAGE CONTROL WIRING (30 VOLTS OR LESS) IN CONDUIT WITH 110 VOLT OR HIGHER WIRING. DO NOT EXCEED
THE FOLLOWING MAXIMUM RUN LENGTHS FOR A GIVEN SIZE: 14 AWG, 5000 FT; 16 AWG, 2000 FT; 18 AWG, 1000 FT.

24 THE FIELD WIRING FOR THE 115V HOT LEG IS TERMINATED TO 1X6 TERMINAL BLOCK. SEE INSTRUCTION LABEL IN CONTROL PANEL FOR
WIRE INSERTION INSTRUCTIONS. SPLICE FIELD WIRES TOGETHER AND WIRE TO 1X6.

25 CLOSED CONTACT COMMANDS BASE LOADING OPERATION.

TOPSS Dimension Drawing


ALL WEIGHTS AND DIMENSIONS ARE APPROXIMATE. Page: 8