Sinamics

G130 / G150
Technical data

Siemens AG 2007 Subject to change without prior notice


Topics

System
overview

Technical data
 Modular cabinet system

Power block
 Power ratings
Mechanical
system
 Product features
Motors

Options  Overload capability


General control
 Derating
Closed-loop
control

Tools Comiss.  Efficiency


Communication
Diagnostics  EMC-conformity
Application
Siemens AG 2007 Subject to change without prior notice
Stand: 18.11.2008 sin-g150-4-02-e.ppt I DT LD
Modular cabinet system (RITTAL)
800 1000 1200 1600 2400 - 3200
System
overview

Technical data

Power block

Mechanical
system
Type output at 400 V: 110 ... 900 kW
Motors 110 kW 200 kW 315 kW 560 kW To 900 kW (parallel)
132 kW 250 kW 400 kW
160 kW 450 kW
Options
Type output at 500 V: 110 ... 1000 kW
General control 110 kW 250 kW 500 kW
132 kW 315 kW 560 kW To 1000 kW (parallel)
Closed-loop 160 kW 400 kW
control 200 kW
Type output at 690 V: 75 ... 1500 kW
Tools Comiss.
75 kW 400 kW 710 kW
90 kW 450 kW 800 kW To 1500 kW (parallel)
Communication
110 kW 560 kW
Diagnostics 132 kW
160 kW
Application 200 kW
250 kW Sinamics G150, Version A
315 kW Cabinet height: 2000 mm (degree of prot. IP20)AG
Siemens + 2007
400 mm (degree
Subject of prot.
to change IP23/IP43/IP54)
without prior notice
Stand: 18.11.2008
Cabinet depth: 600 mmsin-g150-4-02-e.ppt I DT LD
Power ratings and physical dimensions
D = 600 mm
System W = 800 1000 600 + 600 600 + 1000 2400 - 3200
overview
H = 2000

Technical data

Version A
Power block

Mechanical
system

Motors 110 200 315 560


132 250 400
160 450
Options P [kW]
100 200 300 400 500 600
110, 132, 160 315, 400
General control 200, 250 450 560

Closed-loop
control

Version C
H = 2000

Tools Comiss.
Communication
Diagnostics
Application Sinamics G150
B = 400 600 1000
Siemens AG 2007 Subject to change without prior notice
Stand: 18.11.2008 380 - 480 V
sin-g150-4-02-e.ppt I DT LD
Power ratings and physical dimensions
D = 600 mm
System W = 800 600 + 600 600 + 1000 2400 - 3200
overview
H = 2000

Version A
Technical data

Power block

Mechanical
system

Motors 110, 132, 250, 315 500


160, 200 400 560
Options P [kW]
100 200 300 400 500 600
110, 132, 315, 400
General control 160, 200 450 560

Closed-loop
control

Version C
H = 2000

Tools Comiss.
Communication
Sinamics G150
Diagnostics
Application
B = 400 600 1000
Siemens AG 2007 Subject to change without prior notice
500 - 600 V
Stand: 18.11.2008 sin-g150-4-02-e.ppt I DT LD
Power ratings and physical dimensions
D = 600 mm
System W = 800 600 + 600 600 + 1000 2400 - 3200
overview
H = 2000

Version A
Technical data

Power block

Mechanical
system
75, 90, 400
Motors 110, 132, 160, 710, 800
450
200, 250, 315 560
Options P [kW]
100 200 300 400 500 600 700 800
75, 90, 110, 132,
160, 200, 250, 400, 450, 710
General control 560
315 800
Closed-loop
control

Version C
H = 2000

Tools Comiss.
Communication
Diagnostics
Application
Sinamics G150
B = 400 600 1000
Siemens AG 2007 Subject to change without prior notice
Stand: 18.11.2008 660 - 690 V
sin-g150-4-02-e.ppt I DT LD
Technical data
Modular cabinet system from RITTAL

B = 400 + 1000 400 + 1200 600 + 1200 600 + 400 + 600 + 600 600 + 600 + 800 + 800

H = 2000, T = 600
System
overview

Technical data

Power block

Mechanical
system Rated power at 400 V : 110 .. 800 kW

Motors
110 kW 160 kW 200 kW 315 kW 560 kW
132 kW 250 kW 400 kW 710 kW
450 kW 800 kW
Options
Rated power at 690 V : 75 .. 1200 kW
General control
75 kW 160 kW 400 kW 710 kW
Closed-loop 90 kW 200 kW 450 kW 800 kW
control 110 kW 250 kW 560 kW 900 kW
132 kW 315 kW 1000 kW
Tools Comiss. 1200 kW
Communication Frame size for Active Interface Module / Active Line Module and Motor Modules
FI/FX GI/GX GI/GX HI/HX JI/JX
Diagnostics
Application
SINAMICS S150 - Wide range of power ratings in a modular cabinet system.
Siemens AG 2007 Subject to change without prior notice
Stand: 18.11.2008 sin-g150-4-02-e.ppt I DT LD
Power ratings

System
Power module and Control Unit are individual components
overview 75 kW bis 800 kW
660 .. 690 V
Technical data
0 100 200 300 400 500 600 700 800
Sinamics G130
110 kW bis 560 kW
Power block
500 .. 600 V
Mechanical 0 100 200 300 400 500
system
110 kW bis 560 kW
Motors
380 .. 480 V
0 100 200 300 400 500
Options

General control

Closed-loop
control

Tools Comiss.
Communication
Diagnostics
Application

FS F/G Siemens AG 2007 Subject to change without


FSprior
H/Jnotice
Stand: 18.11.2008 sin-g150-4-02-e.ppt I DT LD
Power ratings / Product features
110 ... 900 kW
System Parallel-
380 ... 480 V
schaltung
overview
0 100 200 300 400 500 600 700 800 900
Technical data
110 ... 1000 kW
Parallel-
Power block 500 ... 600 V
schaltung

0 100 200 300 400 500 600 700 800 900 1000
Sinamics G150
Mechanical
system
75 ... 1500 kW
Motors Parallel-
660 ... 690 V
schaltung

0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
Options

General control

Closed-loop Cabinet Degree of Cabinet


protection IP20
control Version Version
Tools Comiss.
A C

Communication
Diagnostics
Application
Siemens AG 2007 Subject to change without prior notice
Stand: 18.11.2008 sin-g150-4-02-e.ppt I DT LD
Technical data
Power/voltage ranges

Vline supply VDC link =1.5 x Vline supply

400 (380 .. 480) V


400 V 600 V
System 110 .. .. 800 kW
overview 690 V 1035 V
0 100 200 300 400 500 600 700 800
Technical data 690 (660 .. 690) V
75 .. .. 1200 kW
Power block 0 100 200 300 400 500 600 700 800 900 1000 1100 1200

Mechanical
system

Motors

Options

General control

Closed-loop
control

Tools Comiss.
Communication
Fig.: 380..480 V 200..250 kW
Diagnostics
Application The Active Line Module stabilizes the DC link voltage to an adjustable value of 150% of
the rated line supply voltage.
Siemens AG 2007 Subject to change without prior notice
Stand: 18.11.2008 sin-g150-4-02-e.ppt I DT LD
Technical data
Comparison to Masterdrives

System
overview

Technical data

Power block Fig.:


400V, 250kW
Mechanical
system

Motors Examples Masterdrives 6SE71..-5BA0 SINAMICS S150

Options
400V / 400 kW B = 3000 B = 2200
General control

Closed-loop 690V / 1200 kW B = 3600 B = 2800


control

Tools Comiss. The cabinet width and weight have been able to be significantly reduced with SINAMICS
S150.
Communication Distributed over the product range, the average reduction is as follows:
Diagnostics Width: approx. 79 % (SINAMICS S150 to Masterdrives)
Application
Weight: approx. 91 %
Current consumption: approx. 98 %
Siemens AG 2007 Subject to change without prior notice
Stand: 18.11.2008 sin-g150-4-02-e.ppt I DT LD
Technical data
Overview (catalog)

Further technical data Sinamics G150

System
overview

Technical data

Power block

Mechanical
system

Motors

Options

General control

Closed-loop
control

Tools Comiss.
Communication
Diagnostics
Application
Siemens AG 2007 Subject to change without prior notice
Stand: 18.11.2008 sin-g150-4-02-e.ppt I DT LD
Technical data
Overview (catalog)

Further technical data Sinamics S150

System
overview

Technical data

Power block

Mechanical
system

Motors

Options

General control

Closed-loop
control

Tools Comiss.
Communication
Diagnostics
Application
Siemens AG 2007 Subject to change without prior notice
Stand: 18.11.2008 sin-g150-4-02-e.ppt I DT LD
Technical data
Overload currents
SINAMICS S150 provide an overload reserve in order, for example, to overcome
breakaway torques. If higher surge loads occur, then this must be taken into account
when engineering the particular drive.
System For drives with overload requirements, then the appropriate base load current must be
overview used as basis for the load demanded.

Technical data Load duty cycle over 300 sec:


ohne IL_kurz IL_lang IH_kurz IH_lang
Power block Low overload, High overload,
berlast 150% 110% 160% 150%
for base load current IL for base
I_G, A load
330 current
320 IH 320 280 280
Mechanical 150 % for 10 sec and 110 % for 60 sec 160 % for 10 sec and 150 % for 60 sec240
Zeit_2, s 300 290 240 290
system Example: I_Max, A 0 480 352 448 420
(500A) Zeit_1, s 0 10 60 10 60
Motors I L*150% ohne G1_kurz G1_lang G2_kurz G2_lang I H*160%
I_N, A 330 327 327 287 313
berlast 150% 110% 170% 150%
I_G, A 330 320 320 280 280
Options Zeit_2, s 300 290 240 290 240 I H*150%
(400A)
I_Max, A 0 480 352 476 420
Zeit_1, s 0 10 60 10 60
General control I LI_N,
*110%
A 330 327 327 289 313
I N_eff
Closed-loop (300A) IL
control IH
300 s 300 s
Tools Comiss.
0 10 60 300 0 10 60 300 T, sec.
Communication
Diagnostics
Application Depending on the application, a lower or higher overload can be selected but it can
also vary within these limits.
Siemens AG 2007 Subject to change without prior notice
Stand: 18.11.2008 sin-g150-4-02-e.ppt I DT LD
Overload currents / Overload capability
Sinamics G150 offer an overload capability to overcome i.e. starting torque requirements.
System
The handling of large steps of torque has to be considered by design.
overview
When designing drives for overload operation the maximum load required has to be
Technical data related to the respective base load current.

Power block Load cycle of 300 sec:


Mechanical ohne IL_kurz IL_lang IH_kurz IH_lang
Small overload, High overload,
berlast 150% 110% 160% 150%
system
at base load current IL at base
I_G, A load
330 current I
320 H 320 280 280
Motors 150 % for 10 sec rsp. 110 % for 60 sec 160 % for 10 sec rsp. 150 % for 60 sec240
Zeit_2, s 300 290 240 290
Example: I_Max, A 0 480 352 448 420
(500A) Zeit_1, s 0 10 60 10 60
Options I L*150% ohne G1_kurz G1_lang G2_kurz G2_lang I H*160%
I_N, A 330 327 327 287 313
berlast 150% 110% 170% 150%
I_G, A 330 320 320 280 280
General control Zeit_2, s 300 290 240 290 240 I H*150%
(400A)
I_Max, A 0 480 352 476 420
Closed-loop Zeit_1, s 0 10 60 10 60
control I LI_N,
*110%
A 330 327 327 289 313
I N_eff
Tools Comiss. (300A) IL
IH
Communication 300 s 300 s
Diagnostics 0 10 60 300 0 10 60 300 T, sek.
Application
Depending on the application, the selection can be based on small or high overload; if
Siemens AG 2007 Subject to change without prior notice
required it can be varied between
Stand: 18.11.2008 these limits.
sin-g150-4-02-e.ppt I DT LD
Selection criteria and ordering data

System
Sinamics G150
overview Type crossover
Small overload High overload
Technical data Output Rated input Rated Base load Output Base load
Order No.
at current output current current
400 V, 50Hz current
Power block A IN IL
1)
to IH IH
2)

A
Mechanical kW A kW A
system Supply voltage 380 480 V, 50 Hz
6SL3710-1GE32-1_A0 110 239 210 205 90 178
Motors
6SL3710-1GE32-6_A0 132 294 260 250 110 233
6SL3710-1GE33-1_A0 160 348 310 302 132 277
Options 6SL3710-1GE33-8_A0 200 405 380 370 160 340
6SL3710-1GE35-0_A0 250 519 490 477 200 438
General control 6SL3710-1GE36-1_A0 315 639 605 590 250 460
6SL3710-1GE37-5_A0 400 785 745 725 315 570
Closed-loop 6SL3710-1GE38-4_A0 450 883 840 820 400 700
control 6SL3710-1GE41-0_A0 560 1034 985 960 450 860

Tools Comiss.
Communication 1)
The base load current IL is based on a duty cycle of 110 % for 60 sec or 150 % for 10 sec with a
Diagnostics duration of 300 sec.
2)
The base load current IH is based on a duty cycle of 150 % for 60 sec or 160 % for 10 sec with a
Application duration of 300 sec.
Siemens AG 2007 Subject to change without prior notice
Stand: 18.11.2008 sin-g150-4-02-e.ppt I DT LD
Technical data
Selection and ordering data

Type jump

System
overview

Technical data

Power block

Mechanical
system

Motors

Options

General control

Closed-loop
control

Tools Comiss.
Communication
Diagnostics
Application
Siemens AG 2007 Subject to change without prior notice
Stand: 18.11.2008 sin-g150-4-02-e.ppt I DT LD
Current-derating depending on installation altitude, temperature,
degree of protection
Installation altitude Ambient temperature of C
System above sea level m 20 25 30 35 40 45 50
overview
0-2000 95.0% 87.0%
Technical data 2001-2500 100% 96.3% 91.4% 83.7%
2501-3000 96.2% 92.5% 87.9% 80.5%
Power block 3001-3500 96.7% 92.3% 88.8% 84.3% 77.3%
3501-4000 97.8% 92.7% 88.4% 85.0% 80.8% 74.0%
Mechanical
system SINAMICS G150 Cabinet units with degree of protection IP20, IP21, IP23 and IP43 and
SINAMICS G130 Chassis units with degree of protection IP20 or IP00
Motors
With increasing altitude and/or
Example: IN = 490 A
Options increasing ambient temperature or
higher degree of protection, H = 2500 m, t = 45C: K = 87.9%
the maximum rated output current must be IN* = 0.879 x 490 A = 431 A
General control
reduced.
Closed-loop
control Installation altitude Ambient temperature of C
above sea level m 20 25 30 35 40 45 50
Tools Comiss. 0-2000 95.0% 87.5% 80.0%
Communication 2001-2500 100 % 96.3% 91.4% 84.2% 77.0%

Diagnostics 2501-3000 96.2% 92.5% 87.9% 81.0% 74.1%


3001-3500 96.7% 92.3% 88.8% 84.3% 77.7% 71.1%
Application
3501-4000 97.8% 92.7% 88.4% 85.0% 80.8% 74.7% 68.0%
Siemens AG 2007 Subject to change without prior notice
SINAMICS
Stand: G150 Cabinet unitssin-g150-4-02-e.ppt
18.11.2008 with degree of protection IP54 I DT LD
Technical data:
Voltage and current de-rating
Installation altitude Voltage de-rating Voltage de-rating
above sea level for a rated input voltage of for a rated input voltage

System
overview

Technical data

Power block

Mechanical
system

Motors Current de-rating for a temperature of


Installation altitude
above sea level IP20 .. IP23
Options IP54

General control to
to
Closed-loop
to
control
to
Tools Comiss.
Communication Example: IN = 490 A, Vline supply= 400V
With increasing altitude and ambient
H = 2700m, t = 50C: temperature, the maximum rated output
Diagnostics
 K=83.3% current must be reduced.
Application IN* = 0,833 * 490 A = 408 A This de-rating is somewhat higher for
VN*= 400 A * 100% = 400 V IP54.
Siemens AG 2007 Subject to change without prior notice
Stand: 18.11.2008 sin-g150-4-02-e.ppt I DT LD
Voltage derating for altitudes >2000m

Lower insulation Voltage


System
overview derating
Altitude
Technical data Lower air density

Power block Higher cooling


air temp. Lower heat
Mechanical
dissipation Current
system derating
Motors Lower
IP54 with filter airflow
Options
Installation Drive converter rated input voltate
altitude above Max. input 380 V 400 V 420 V 440 V 460 V 480 V Max. input 660 V 690 V
General control sea level voltage in V voltage in V
in m
Closed-loop 0 - 2000 480 690 100%
control 2001-2250 461 96% 660 96%
2251-2500 451 98% 94% 648 98% 94%
Tools Comiss. 2501-2750 432 100% 99% 94% 90% 621 95% 90%
2751-3000 422 95% 91% 88% 607 92% 88%
Communication 3001-3250 408 97% 93% 89% 85% 586 89% 85%
3251-3500 394 98% 93% 89% 85% 82% 565 85% 82%
Diagnostics
3501-3750 380 95% 91% 87% 83% 79% 545 83% 79%
Application 3751-4000 365 96% 92% 87% 90% 80% 76% 524 80% 76%

Siemens AG 2007 Subject to change without prior notice


Example 380..480V-Unit; H=2500m: max. Input Voltage: 451V
Stand: 18.11.2008 sin-g150-4-02-e.ppt I DT LD
Ordering data / MLFB (MRPD)

System Cabinet for low voltage


overview Sinamics AC/AC drive converter
Technical data
air cooled Version

Power block

Mechanical
system

Motors 6SL3 710 1GE 32 6 C A0 Z


Options

General control
Output current Options
Closed-loop 3 = factor 100
control 100*2-6: ca. 260A
Tools Comiss. 1 = Non-regulated DFE
Communication
G = G150 = Version:
General Performance Vector A = with many customer options
Diagnostics
Line supply E =380 ... 480 V C = especially space saving
Application H =660 ... 690 V
Siemens AG 2007 Subject to change without prior notice
Stand: 18.11.2008 sin-g150-4-02-e.ppt I DT LD
Ordering data / MLFB (MRPD)

System
Chassis-version for
overview Sinamics Low Voltage AC/AC converter,
1. Generation air cooled
Technical data

Power block

Mechanical
system

Motors 6SL3 310 1GE 32 6 A A0


Options

General control Output current


Closed-loop 3 = factor 100
control 100*2-6: ca. 260A
Tools Comiss. 1 = uncontrolled DFE
Communication G = General Performance Vector
Diagnostics Line E = 380 ... 480 V
Application F = 500 ... 600V
H = 660 ... 690 V
Siemens AG 2007 Subject to change without prior notice
Stand: 18.11.2008 sin-g150-4-02-e.ppt I DT LD
Technical data
Ordering data MRPD [Machine Readable Product Designation]

7 = cabinet for low voltage Version


3 = chassis unit

System
10 = AC/AC drive Options
overview
SINAMICS converter, air-cooled
Technical data

Power block

Mechanical
system
6SL3 710 7LE 36 1 AA0 Z
Motors

Options 7= Active Line Module


1= non-regulated DFE
General control
Output current
Closed-loop
control
3 = factor 100
L = S120, S150 High Performance 100*6- 1 = approx. 610A
Tools Comiss. G = G150/G130 General Performance
Communication
Line supply E =380 ... 480 V
Diagnostics
H =660 ... 690 V
Application
Example: SINAMICS S150, 380..480V, IN=306A (P=315kW), with Z options
Siemens AG 2007 Subject to change without prior notice
Stand: 18.11.2008 sin-g150-4-02-e.ppt I DT LD
Voltage- and current-derating

System Lower insulation Voltage


overview derating
Altitude
Technical data Lower air density

Power block
Higher cooling
Mechanical air temp. Lower heat
dissipation Current
system
derating
Motors
Lower
IP54 with filter airflow
Options

General control

Closed-loop
For installation altitudes >2000 m a voltage-derating has to be taken into
control account.
Tools Comiss. With increasing altitude and/or increasing ambient temperature the
Communication maximum output current has to be reduced.
Diagnostics
Application
For class IP54 a somewhat larger reduction has to be considered!
Siemens AG 2007 Subject to change without prior notice
Stand: 18.11.2008 sin-g150-4-02-e.ppt I DT LD
Technical data:
Sound pressure level and efficiency

System
overview
Using Active Infeed, the
Technical data sound pressure level was
able to be kept low!
Power block
50Hz: 71...78 dB(A)
Mechanical 60 Hz: 73...80 dB(A)
system

Motors

Options

General control
Low-loss IGBT technology in
Closed-loop the Active Infeed Modules
control P1 P2
and Motor Modules keep the
Tools Comiss. efficiency high.
Communication
Power:
Diagnostics
P2
Application Px = 3 U I cos =
P1
Siemens AG 2007 Subject to change without prior notice
Stand: 18.11.2008 sin-g150-4-02-e.ppt I DT LD
Sound pressure level in dB(A)

System
overview 1m
Technical data

Power block

Mechanical 1m
system

Motors

Options 380 ... 480 V


Power rating kW 110 132 160 200 250 315 400 450 560
General control Size F F G G G H H H J
Imms 100 A 210 260 310 380 490 605 745 840 985
Closed-loop
control Sound press.
dB 67 69 69 69 69 70 70 70 72
level 50 Hz IP20
Tools Comiss.
Sound press. level
dB 68 73 73 73 73 73 73 73 75
Communication 60 Hz IP20
Diagnostics
Application
The sound pressure level values can be kept very low!
Siemens AG 2007 Subject to change without prior notice
Stand: 18.11.2008 sin-g150-4-02-e.ppt I DT LD
EMC-directives

System Noise immunity


overview
= insensitive to low-frequency and high-frequency noise and
Technical data
disturbances
Power block  Line harmonics and line dissymmetry
Mechanical  Transient voltage spikes
system
 Electrostatic discharge
Motors  Electromagnetic fields
Options
Noise emission
General control
 Components/devices such as IGBTs and microprocessors are
Closed-loop
control some of the causes
Tools Comiss.
 This noise is propagated as follows
Communication - Cable-borne (noise voltage)
Diagnostics - Non cable-borne (radiation)
Application
Siemens AG 2007 Subject to change without prior notice
Stand: 18.11.2008 sin-g150-4-02-e.ppt I DT LD
Technical data
EMC Directive

Electromagnetic compatibility (EMC)


System  The ability of electrical or electronic devices/equipment to operate
overview disturbance-free in an electromagnetic environment.
Technical data
 It is not permissible that these devices/equipment simultaneously
Power block disturb or influence other installations or systems at the place of
Mechanical installation.
system

Motors
N o is e im m u n ity

Options
L im it va lu e , n o is e
im m u n ity
General control C o m p a tib ilty ra n g e
L im it va lu e , n o is e
Closed-loop
e m is s io n
control

Tools Comiss.
N o is e le ve l
Communication
Diagnostics
Application F re q u e n c y
Siemens AG 2007 Subject to change without prior notice
Stand: 18.11.2008 sin-g150-4-02-e.ppt I DT LD
Product standard EN 61800-3

The Product Standard EN 61800-3 defines the EMC requirements relating to variable-
System
overview speed drive systems
Noise immunity and noise level depend on the installation location
Technical data
Medium-voltage line supply
Power block
Cable-borne
Mechanical
noise
system
Public low-voltage Industrial low-voltage
Motors
line supply line supply
Options
Test point for
cable-borne
General control noise/disturbances

Closed-loop
control
First Second
Tools Comiss. environment environment
Communication
Diagnostics Installation limit

10m
Application
Equipment Drive
(effected by the noise) Test point
Siemens AG for (noise
2007 Subject to change without source)
prior notice
Stand: 18.11.2008 radiated
sin-g150-4-02-e.ppt noise/disturbances I DT LD
Product standard EN 61800-3

System
Depending on where the drive system is installed, different environments and
overview categories are defined:
Industrial areas supplied from
Technical data Residential building or connected the medium-voltage line supply
to the low-voltage line supply without through a companys own
Power block a transformer transformer.

Mechanical Category C1: C1 Category C3:


system Rated voltages <1000V Rated voltages <1000V
unrestricted use in the first First
C2 Second exclusively used in the
Motors environment. environment environment second environment.
C3
Options Category C2: C4 Category C4:
Fixed, stationary drive Rated voltages > 1000V
General control systems rated voltages <1000V or for rated currents >400A
for use in the second environment. in complex systems in
Closed-loop When used in the first environment must the second environment.
control be sold and installed by specialist
personnel. Carefully note the
Tools Comiss. manufacturers data!
Communication Sinamics G150 S150 are almost exclusively used in the 2nd environment (C3, C4).
Diagnostics Limiting the noise emission:
 EMC radio interference suppression filter as standard, Category C3
Application
 Optional filter (L00) for use in the first environment (Category C2)
Sinamics G150 S150 fulfills the requirements regarding
Siemens AG noise immunity
2007 Subject for the
to change 1st +prior
without 2nd notice
Stand: 18.11.2008
environments. sin-g150-4-02-e.ppt I DT LD
Product standard EN 61800-3 / Definition PDS

System Installation or part of installation


overview
Power Drive System (PDS) OEM, ..
Technical data
CDM (Complete Drive Module)
Power block
System control and
Mechanical sequencing
system
BDM (Basic Drive Module)
Motors Control
Converter SIEMENS
Options Protection factory
General control Feeding section
Field supplay
Closed-loop Dynamic bracing
control Auxiliaries, ...
Tools Comiss.
Communication
Motor and sensors SIEMENS
Diagnostics factory
Application
Driven equipment
Siemens AG 2007 Subject to change without prior notice
Stand: 18.11.2008 sin-g150-4-02-e.ppt I DT LD