Académique Documents
Professionnel Documents
Culture Documents
Page 41 / 153
3.OVER CURRENT RELAYS
fig 3.1
Page 42 / 153
2
3.OVER CURRENT RELAYS
fig 3.2
Calculate the maximum and minimum load currents bus. Provide
current transformers of ratio as per system load requirements. Set the
relay with an equivalent primary current well above the maximum load
current. The relay setting must be well below the minimum fault current.
Complete the datas in a table as given below:
Table 3.1
loc Total Fault Total CT. Relay
ati impedance current in load Ratio current
on in ohms Amps current setting
Min Max Max Min per prima
cen ry
t curre
nt
A 0.81 1.62 7840 3920 500 400/5 150 600
B 1.41 2.22 4504 2860 350 400/5 125 500
C 2.36 3.17 2694 2003 175 200/5 100 200
D 4.56 5.37 1393 1183 75 100/3 100 100
Page 43 / 153
3
3.OVER CURRENT RELAYS
Page 44 / 153
4
3.OVER CURRENT RELAYS
Relay setting
PSM Tc TMS Ta
Relay at D Fault at D 13.93 2.6 0.05 0.13
Relay at C Fault at D 6.965 3.6 0.175 0.13 + 0.5 = 0.63
Relay at C Fault at C 13.45 2.6 0.175 0.455
Relay at B Fault at C 5.382 4.1 0.233 0.455 + 0.5 = 0.955
Relay at B Fault at B 9 3.15 0.233 0.734
Relay at A Fault at B 7.5 3.45 0.358 0.734 + 0.5 = 1.234
Relay at A Fault at A 13.06 2.65 0.358 0.95
Tc :- Relay operating time from standard curve for the given PSM
Ta :- relay actual operating time
Page 45 / 153
5
3.OVER CURRENT RELAYS
fig 3.2(a)
After having made the template the values of the current (in
amps) are plotted on a log -log paper along the X - axis and the time of
operating of the relay ( in seconds) along the Y - axis.
For plotting the characteristic of the relay - D in the above
illustration, the origin of the template is kept at 100 amps and 0.05 secs
and the curve of the template is transferred on the log - log paper.
Similarly for plotting the characteristic of the relay - C the orgin of the
template should be kept at 200 amps and 0.175 secs and the transfered to
the log - log paper. Repeat the procedure for B and A relays with the
origin of the of template kept at ( 500A, 0.233 s ) and ( 600A, 0.358 s )
respectively.
Illustration 2 :-
fig 3
It is necessary to convert all the system imped ance to a
common base.
Common base used :10 MVA
Page 46 / 153
6
3.OVER CURRENT RELAYS
Base MVA
Percentage impedance of 132KV source = x 100
Fault MVA
10
= x 100 =0.29%
3500
Table 1
Page 47 / 153
7
3.OVER CURRENT RELAYS
R Total impedance in Fault current in Total CT. CT. Ratio Relay current
el Z pu Amps at 3.3KV base load Ratio to the setting
ay current base of
lo at 33kv
ca 3.3KV
ti base
on
Min Max Max Min perc primary
ent current
at 3.3kv
base
D 0.1013 0.2795 17268 6257 700 250/5 833/5 100 833
C 0.0815 0.1013 21466 17268 1500 500/5 1666.6/5 100 1666.6
B 0.0065 0.0815 269160 21466 6000 150/1 6000/1 100 6000
A 0.0029 0.0065 603292 269160 20000 500/1 20000/1 100 20000
Table 2
PSM Tc TMS TC
Relay at D Fault at D 20.7 0.2 0.05 0.1
Relay at C Fault at D 10.36 0.8 0.625 0.1 + 0.4 = 0.5
Relay at C Fault at C 12.88 0.47 0.625 0.29
Relay at B Fault at C 3.58 6 0.115 0.29 + 0.4 = 0.69
Relay at B fault at B 44.8 0.2 0.115 0.023
Relay at A Fault at B 13.458 0.43 1 0.023 + 0.4 =0.423
Relay at A Fault at A 30.1 0.2 1 0.2
Page 48 / 153
8
3.OVER CURRENT RELAYS
10
=
0.175+0.0033+0.0198+0.075+0.0036+0.0029
10
= = 35.76 MVA
0.2796
Fault MVA 35.76
Fault current = =
3 x base KV 3 x 3.3
= 6257Amps at 3.3KV
or 35.76
= = 1877Amps at 11KV
3 x 11
10
Fault level close to bus D =
0.0198+0.075+0.0036+0.0029
10
= = 98.7 MVA
0.1013
98.7MVA
Full load current at 3.3KV base = = 1.7268KAmps
3 x3.3KV
4MVA
Maximum load current at 3.3Kv base = = 0.7KA
3 x3.3KV
CT ratio adopted 250/5A
corresponding CT ratio to the base of 3.3KV = 250 x (11/3.3) / 5
=833.3/5A
So a relay of 100% P.S (plug setting) corresponds to a current
of 833.3Amps(3.3KV base).
The calculations for the remaining relay locations are
proceeded in similar way as illustrated above and tabulated
Calculations were made for all the relay locations for the TMS
(time lever setting) in the same way as explained in the previous
example and tabulated in Table 2
Page 49 / 153
9
3.OVER CURRENT RELAYS
The discriminating curves were plotted for all the relays at sub
stations A, B, C, D &E on a log-log sheet (fig).
ILLUSTRAT ION 3
Coordination of over current relays for an industrial system :-
fig 3.4
The relays used for protection are :
i) for motor protection (relay G) a thermal relay with high set unit for
instantaneous over current element
ii) for transformer protection (relay H) over current relay with very
inverse characteristic and high over current element
iii) for feeder protection (relay J) a normal inverse characteristic
iv) for generator a voltage controlled normal inverse characteristic
with dual characteristic
Page 50 / 153
10
3.OVER CURRENT RELAYS
fig 3.5
Fuse characteristic :- The operating characteristic of the fuse should be
plotted on a log-log sheet with a suitable scale for maximum fault levels
on a common base voltage of 6.6KV.
Table 1
Operating current at Operating Time
415V Base 6.6KV Base
795 50 40
955 60 13
1160 70 6
1270 80 3
1590 100 0.9
2700 170 0.1
Induction motor :-
Rating of the motor =100KW.
Full load current =139 Amps at 415V base
ie =8.75 Amps at 6.6KV base
Motor starting current ( 6 times full load current) =6 x 139 = 834 Amps
ie 52.48 Amps at 6.6KV base
Starting time = 10 secs
The relay may be set for 100% setting corresponding to 9.43Amps at
6.6KV base ie. 13% overload.
The thermal characteristic of the relay is
Table 2
Page 51 / 153
11
3.OVER CURRENT RELAYS
Transformer protection:
10 x 106
Max fault level = = 874.7 Amp
3 x 6.6 x103
Relay PSM = 847.7/75 = 11.6
Relay operating time at 11.6 times plug setting and 1.0 TMS is
1.41secs. The grading margin between relay and fuse will be
t = 0.4t + 0.15 sec
were t = nominal operating time.
So the grading margin = 0.4 x 0.01 + 0.15 =0.154 (say 0.16)
Page 52 / 153
12
3.OVER CURRENT RELAYS
Feeder protection:
Generator :
Relay used . The relay used is with a duel characteristic
which changes its pick-up value to 40% of its nominal plug setting and
Page 53 / 153
13
3.OVER CURRENT RELAYS
Page 54 / 153
14
3.OVER CURRENT RELAYS
fig 3.6
Instead of three separate CTs one open core CT (Core Balance
CT) can be used in networks three cable (Fig 3.7).
fig 3.7
Page 55 / 153
15
3.OVER CURRENT RELAYS
Page 56 / 153
16
3.OVER CURRENT RELAYS
fig 3.12
Page 57 / 153
17