GeneralSpecificationforHighVoltage
metalenclosedcubiclesfrom1to24
kV
Thisisthecommonarticletouseformainlyprescription
andtenderingpurposes.
Contentofit;
Generalcondition,
Standards,
Ratedvalues,
Mainsystemparameters,
Generalacceptationparameters,
Type&routinetests,
Lastupdate:20150616
1
SpecificationforTender 364842365.doc
Tableofcontents:
1.Generalconditions..............................p.3
2.Standards.p.3
3.Ratedcurrent&voltageandshorttimewithstandcurrentandInternalArc.............p.3
4.Systemparameters..............p.4
4.1Mainelectricalcharacteristics.................................p.4
4.2Generalcharacteristics....................p.45
5.Generalrequirementsrelativetothedesignandmanufactureoftheswitchgear.............p.6
5.1Introduction.........................................p.6
5.2Switchboards..................................p.6
5.3Normaloperatingconditions..............................p.7
5.4Earthingofmetallicparts..............................p.8
5.5Earthingofthepowercircuit..........p.8
5.6Switches..................................................p.8
5.7Circuitbreakers...............................p.9
5.8Contactors................................p.10
5.9Busbars...............................................p.10
5.10Connections.p.10
5.11Operatingmechanisms....................p.10
5.12LVcabinet..........................................................p.11
5.13Currenttransformers.............p.11
5.14LowPowerCurrenttransformers(LPCT)............................p.11
5.15Voltagetransformers.................................p.12
5.16LVauxiliaries............................................p.12
5.17Controlandmonitoring......p.12
5.18Voltageindicatorandphasecomparators..p.12
5.19FaultPassageIndicators.p.12
5.20Safetyofpeople..p.13
5.21AutomaticTransferSystem..p.13
6.Typetestsandroutinetests........................................................p.13
7.Quality..................................p.14
Lastupdate:20150616
2
SpecificationforTender 364842365.doc
1.Generalconditions
Thefollowingspecificationsapplytomodularindoorswitchboardscomprisingfactorybuilt,metalenclosed
switchgearassembles.
Theequipmenttobesuppliedshallconsistofmodularcubiclessatisfyingthefollowingcriteria:
openendeddesign,
easytoinstall,
safeandeasytooperate,
compactdesign,
reducedmaintenance.
safetyofoperator.
ThesuppliermustbeabletoproveitsextensivepossessexperienceinthefieldofMVswitchgear,andhas
alreadysuppliedequipmentofthesametype&productionprocess,inwhichhasbeeninoperationforat
leastthreeyears.
2.Standards
TheswitchgearshallcomplywiththelatestissuesofthefollowingIECstandards:
62271200 HighvoltageswitchgearandcontrolgearPart200:ACmetalenclosedswitchgearand
controlgearforratedvoltageabove1kVanduptoandincluding52kV
622711 HighvoltageswitchgearandcontrolgearPart1:Commonspecifications
62271103 Highvoltageswitchesforratedvoltagesabove1kVandlessorequalto52kV
62271105 Highvoltagealternatingcurrentswitchfusecombinations
60255 Electricalrelays
62271100 Highvoltagealternatingcurrentcircuitbreakers
62271102 Highvoltagealternatingcurrentdisconnectorsandearthingswitches
618692 InstrumenttransformersPart1:currenttransformers
618693 InstrumenttransformersPart2:voltagetransformers
600448 InstrumenttransformersPart8:lowpowercurrenttransducers
62271206 HighvoltageprefabricatedswitchgearandcontrolgearassembliesVoltagepresence
indicatingsystems
IEE6932005IEEERecommendedPracticeforSeismicDesignofSubstations
EN600068331993EnvironmentaltestingPart3:guidance,Seismictestmethodsforequipments
3.Ratedcurrent&voltageandshorttimewithstandcurrentandInternalArc
3.1Theswitchgearshallbesuitableforthreephasesystemsoperatinguptoandincluding24kV,
and50/60Hz.
3.2Theratedvoltageshallbe7,2kV12kV17,5kV24kV.
3.3Theshorttimewithstandcurrent(Ik/tk)shallbe25kA/1suptoandincluding24kV.(Please,consultus
for2sand3s)
3.4Theratedcurrentshallbe400A630A1250A.
Lastupdate:20150616
3
SpecificationforTender 364842365.doc
3.5TheswitchgearshallhaveInternalArcperformanceas12,5kA/1s&16kA/1sand20kA/1sonthree
compartments(1busbar&2switching/disconnecting,and3cableconnection)asIAC:AFLandAFLRup
toandincluding24kVat630A&1250Aratedcurrents.
Allswitchgearshallbecapableofwithstandingtheaboveconditionswithoutprovokingdamage(exclude
internalarc),inaccordancewithparagraphs4.5,4.6and4.7ofIEC622711¶graph4.5andAnnexAA
ofIEC62271200standards.
4.Systemparameters
TheinsulationleveloftheswitchgearshallcomplywithIECstandardsandthevaluesindicatedinthe
followingtable.
4.1Mainelectricalcharacteristics
Thehereundervaluesareforworkingtemperaturesfrom5Cupto+40Candforasettingupatan
altitudebelow1000m.
(Please,consultusforoutofrangetemperaturesandover1000mapplication)
insulationlevel
50/60Hz/1mnUdinsulation 20 28 38 50
(kVrms)Ud isolation 23 32 45 60
transformeroffload(A) 16
cablesoffload(A) 31.5
okshorttimewithstandcurrentat25 6301250A
asthreephases 20 6301250A
Ik/tk(kA/1s) 16 6301250A
(Please,consultusfor2sand3s)12.5 4006301250A
makingcapacityat62.5 630A
Ima(kA) 50 630A
40 630A
31.25 400630A
ratedcurrent(A)Ir 400A630A1250A
4.2Generalcharacteristics
Maximumbreakingcapacity(Isc)
Lastupdate:20150616
4
SpecificationforTender 364842365.doc
switchunit(A) 630800
fuseswitchunit(kA) 25 25 20 20
Contactorunitwithfuses(kA) 25 25
Circuitbreakerunit(kA) 25 25 25 25
Lastupdate:20150616
5
SpecificationforTender 364842365.doc
Endurance
(*)asperIEC62271105standard,threebreakingatpf=0,2forfuseswitchunit
1730A/12kV
1400A/24kV
2600A/5,5kV
5.Generalrequirementsregardingthedesignandmanufactureoftheswitchgear
5.1Introduction
Theequipmentshallsatisfythecriteriaforindoor,metalenclosedswitchgearclassLSC2&ClassPI
partitioninginaccordancewithparagraph3.131.1;3.109.2&8.103.3of201110editionofIEC62271200
standard.
Thecubiclesshallbedesignedwiththreecompartmentshousedinasingleenclosureatleast30yearslife
spanundernormaloperatingconditions:
busbarcompartment,
switching/disconnectingcompartment,
connectioncompartmentforcablesandCB/contactor/fuse/CTs/VTs,(shallbeinterlockcontrolled
accessible)
5.2Switchboards
Lastupdate:20150616
6
SpecificationforTender 364842365.doc
Theswitchboardsshallbemadeupofseparatefactorybuiltcubicleshousingtheswitchgear(switch
disconnectorandswitchenclosuresshallbemountedhorizontallyinthecubiclesandthecircuitbreakershall
bedisconnectable/withdrawableandmountedvertically).Thecubiclesthereforeformacompartmented
distributionswitchboardthatcanbeextendedifnecessary.
ThecubiclesshallmeettherequirementsofdegreeofprotectionindexIP3X.
Thegalvanizedandelectrogalvanizedsheetmetalandmetalfittingsshallbepaintedtoprovideprotection
againstcorrosion.Theepoxybasedpaintshallhaveathicknessofatleast50micronsmeterandshallbe
appliedtobothsidesofallsheetmetal.ThecolorshallcorrespondtotheRALcolorrangeproposed.
Theswitchboardshallbesuitableformountingabovecabletrenchesrespectingcivilengineeringdefinition.
Eachcubicleshallcarryasuitablydimensionalidentificationlabelclearlyindicatingthefunctionsand
electricalcharacteristicsofthecubicleinaccordancewithchapter5.10ofIEC62271200.
Theswitchgearandtheswitchboardsshallbedesignedinsuchawaythatthepositionsofthevarious
switchgeardevicesshallbevisiblebytheoperatorfromthefrontoftheswitchboard.Itshallalsobepossible
tooperatetheswitchgearfromthefrontofit.
Theswitchgearshallcomplywiththeseismicrequirement.ItshallconformtotheSeismicrequirementas
perIEEE6932005recommendedpracticeSeismicdesignofsubstationsupto0.5ghorizontaland0.4g
vertical.Class2.
Theswitchgearshallhavearcdetectionsystemifrequired,referringtoIEC622712008.104.3
ThecivilworksspecificationsshallbeuniqueforallcubiclesmakinguptheMVswitchboard.Thecubicle
widthsshallbe375mm,500mm,625mmand750mm.Inparticular,thecivilworksforthecircuitbreaker
cubiclesshallbeidenticaltothecivilworksfortheswitchcubicles.
Themanufacturershallprovideaninstallationdrawingtoserveasaguideforthecivilworks.
Inaccordancewithapplicablestandards,theswitchboardsshallbedesignedtopreventaccesstoallliveparts
wheninoperationaswellasduringmaintenancework.
5.3Normaloperatingconditions
Ambientairtemperature:
lessthanorequalto40C,
lessthanorequalto35Conaverageover24hours,
greaterorequalto5C.
Altitude:
lessthanorequalto1000m,
above1000m,aderatingcoefficientisapplied(pleaseconsultus).
Solarradiation:
nosolarradiationinfluenceispermitted,
Ambientairpollution:
nosignificantpollutionbydust,smoke,corrosiveand/orflammablegases,vapoursorsalt.
Humidity:
averagerelativehumidityovera24hourperiod,lessthanorequalto95%,
averagerelativehumidityovera1monthperiod,lessthanorequalto90%,
Lastupdate:20150616
7
SpecificationforTender 364842365.doc
averagevaporpressureovera24hourperiod,lessthanorequalto2.2kPa,
averagevaporpressureovera1monthperiod,lessthanorequalto1.8kPa.
Fortheseconditions,condensationmayoccasionallyoccur.Condensationcanbeexpectedwheresudden
temperaturechangesoccurinperiodsofhighhumidity.
Themanufacturershallprovideanalternativebusbarinstallationtowithstandsevereenvironmentcondition
asoption.
Towithstandtheeffectsofhighhumidityandcondensation,suchasbreakdownofinsulation,pleasepay
attentiononCivilEngineeringrecommendationsfordesignofthebuildingorhousing,bysuitable
ventilationandinstallation.
5.4Earthingofmetallicparts
Theearthingbarsofeachofthecubiclesmakinguptheswitchboardshallbeinterconnectedbyasetof
busbars,whichshallbeconnectableoutsidetheswitchboardandextendoveritsfullwidth.
Thecrosssectionofthebusbarsshallbedeterminedsoastowithstandtheratedshortcircuitcurrentofthe
switchgearinaccordancewithIEC62271200standard.
Theearthingbarshallbedesignedforconnectiontothemainearthingbarofthesubstationwithout
dismantlinganyofthebars.
5.5Earthingofthepowercircuit
Cableearthingshallbecarriedoutbyanearthingswitchwithashortcircuitmakingcapacity,inaccordance
withIEC62271102standard.Itshallbepossibletooperatetheearthingswitchwhentheswitchor
disconnectorisopen.
Apadlockingsystemshallbeprovidedtolocktheearthingswitchineitheropenorclosedposition.The
positionoftheearthingswitchshallbeclearlyvisiblefromthefrontofthecubicle.
Mechanicalinterlocking(padlocking)systemsshallbeprovidedtopreventincorrectoperationssuchasthe
closingoftheearthingswitchwiththeswitchordisconnectorinclosedposition.
Theuseofkeyorelectriclockstoactuatetheabovementionedinterlockingsystemshallnotbeaccepted.
5.6Switches
TheswitchesshalluselowpressureSF6gasforcurrentinterruptionandshallrequirenomaintenance.The
switchenclosureshallbemountedhorizontallywithinthecubicleandthepositionofthemainandearthing
contactsshallbeclearlyvisiblefromthefrontofthecubicle.Thepositionindicatorshallbeplaced
directlyonthecontactoperatingshaft.
Theopenandearthedpositionsofthemainmovingcontactshallbevisible(inspectionwindows)fromthe
frontofthecubicleuponthecustomerrequest.
Lastupdate:20150616
8
SpecificationforTender 364842365.doc
Theswitchenclosuresshallbemadeofcastepoxyresinthatshallbecapableofbearingformechanical
strength,aswellaselectromagneticforces.
Theswitchesshallbeofthehighoperatingfrequencytypeinaccordancewithparagraph3.104ofIEC
602651standard.Theyshallhavethreepositions(closed,openandearthed)andshallbefully
assembledandtestedbeforeleavingthefactory.
TherelativepressureoftheSF6gasinsidetheenclosureshallnotexceed0.4bars(400hPa).
Thepoleunitenclosuresshallbeofthesealedpressuresystemtypeasdefinedby
IEC62271200,chapter3.118.2standard.
Leakagerateshallnotbeover0.1%forlifespanthatisatleast30years.Norefillingofthegasshallbe
requiredoverthisperiod.
Switchunitsrequiringmaintenanceorgasrefillingwillnotbeaccepted.
Switchunitswouldbeequippedwithanalogorpressureswitch.Bothofthemshallbetemperature
compensated.Pressureswitchshallprovide2levelofindicationthatarelowlevelandcriticallevel.
Themechanicalenduranceoftheswitchoperatingmechanismsshallensureatleast1000operations.
5.7Circuitbreakers
5.7.1SF6
Thecircuitbreakersshallbemountedvertically&laterally,andshallbedisconnectable/withdrawable.It
shalluseSF6gasasthecurrentinterruptionmedium.Theyshallrequireonlyminimummaintenanceand
shallprovideahighlevelofelectricalendurance.Thepositionofthecircuitbreakershallbeclearlyvisible.
Furthermore,thecircuitbreakersshallbemechanicallyinterlockedwiththepowercircuitdisconnector.
Thepoleunitsshallbemadeofcastepoxyresinandshallbefullyassembledandtestedbeforeleavingthe
factory.TherelativepressureoftheSF6gasshallnotexceed2bars(2000hPa).Thepoleunitsshallbeofthe
sealedpressuresystemtypeasdefinedbyIEC62271100,withaservicelifeofatleast30years.
Norefillingofthegasshallberequiredoverthisperiod.
Circuitbreakerpoleunitsrequiringmaintenance,inspectionorgasrefillingwillnotbeaccepted.
Themechanicalandelectricalenduranceshallensureatleast10,000operations.
Cubiclewidthshallnotbebiggerthan750mmwiththistypeofCBthatincludesdisconector,CTs,VTsand
downstreamearthingswitch.
Thecircuitbreakersshallbecoveredwithtestreportsthatareissuedbyarecognizedorganizationaffiliated
withaninternationalorganization.
5.7.2.1Vacuum
Thecircuitbreakersshallbemountedvertically&frontallyorlaterally,andshallbedisconnectable.Itshall
usevacuumasthecurrentinterruptionmedium.Theyshallrequireonlyminimummaintenanceandshall
provideahighlevelofelectricalendurance.Thepositionofthecircuitbreakershallbeclearlyvisible.
Furthermore,thecircuitbreakersshallbemechanicallyinterlockedwiththepowercircuitdisconnector.
Lastupdate:20150616
9
SpecificationforTender 364842365.doc
Thepoleunitsshallbefullyassembledandtestedbeforeleavingthefactory.Thepoleunitsshallbeofthe
sealedpressuresystemtypeasdefinedbyIEC62271100,withaservicelifeofatleast30years.
Circuitbreakerpoleunitsrequiringmaintenance,inspectionwillnotbeaccepted.
Themechanicalandelectricalenduranceshallensureatleast10,000operations.
Cubiclewidthshallnotbebiggerthan625mmwithfrontallyinstalledtypeCBthatincludes
disconnector/switch,CTs,VTsanddownstreamearthingswitch.And,cubiclewidthshallnotbebiggerthan
750mmwithlaterallyinstalledtypeCBthatincludesdisconnector,CTs,VTsanddownstreamearthing
switch.
Thecircuitbreakersshallbecoveredwithtestreportsthatareissuedbyarecognizedorganizationaffiliated
withaninternationalorganization.
5.8Contactor
TheVacuumcontactorshallbemountedvertically&laterally,andshallbedisconnectable.Itshalluse
vacuumasthecurrentinterruptionmedium.Itshallrequireonlyminimummaintenanceandshallprovidea
highlevelofelectricalendurance.Thepositionofthecontactorshallbeclearlyvisible.
Furthermore,thecontactorshallbemechanicallyinterlockedwiththepowercircuitdisconnector.
Thepoleunitsshallbefullyassembledandtestedbeforeleavingthefactory.Thepoleunitsshallbeofthe
sealedpressuresystemtypeasdefinedbyIEC60470,withaservicelifeofatleast30years.
Contactorpoleunitsrequiringmaintenance,inspectionwillnotbeaccepted.
Thecontactorshallbecoveredwithtestreportsthatareissuedbyarecognizedorganizationaffiliatedwith
aninternationalorganization.
5.9Busbars
Thebusbarcompartmentshallbelocatedatthetopofthecubicle.
Itshallincludethreeparallelmountedbarswithoutphaseseparatingmeans.Connectionsshallbemadeto
thetoppadsoftheswitchordisconnectorenclosures.Accesstothebusbarsshallonlybepossibleafter
removingasingleaccesspanelcarryingasymbolwarningofthedangerofelectricalshock.Nootherbusbar
accesssystemwillbeaccepted.
5.10Connections
TheHVcableconnectionpadsshallbedesignedtoacceptsimplifiedterminationsfordrytypecables.
Accesstotheconnectioncompartment,shallbeinterlockcontrolledaccessible,andshallonlybepossible
afterclosingtheearthingswitch.Nootheraccessmodewillbeaccepted.
5.11Operatingmechanisms
Theoperatingmechanismsshallprovideinfrontallthenecessarymeansforoperatingtheswitches,
disconnectorandcircuitbreakers&contactor.
Lastupdate:20150616
10
SpecificationforTender 364842365.doc
5.11.1Loadbreakswitch
Theoperatingmechanismboxshallincludeaswitchandearthingswitchpositionindicatorfixeddirectlyto
theshaftofthemovingpole,therebysatisfyingthepositivebreakcriteria.
Thisboxshallalsohousethevoltageindicatorsandthemechanicalfuseblownindicatorforfuseswitch
combinationunits.
Theboxshallbeaccessiblewiththecablesandbusbarslive,withoutisolatingtheentireswitchboard,
andshallbedesignedforeasyinstallationofpadlocks,keylocks,auxiliarycontacts,releasesandthe
usualLVaccessories.
Thefrontcoveroftheoperatingmechanismshallbesuitablefortheapplicationofallsymbols,mimic
diagrams,nameplatesandpadlockingfixturesrequiredbythefunctionimplemented.
Thefrontoveroftheoperatingmechanismshallprovidevisibilityofmaincontactwhentheswitchis
openedorearthedpositioning.
Allswitchandearthingswitchoperationsshallbecarriedoutwithanantireflexleverandshallbe
independentoftheactionoftheoperatorafterchargingtheoperatingmechanismsprings.
Theoperatingmechanismsshallbesoconstructedthatcancomeoutoftheirneitheropennorclosed
positionsbyforcesarisingfromgravity,vibration,reasonableshocksoraccidentaltouchingoftheleverof
theiroperatingdevices,orbyelectromagneticforces.
Itshallbepossibletoadd,onsite,amotormechanismforelectricalchargingoftheoperatingmechanismas
wellasthenecessaryaccessories.
5.12LVcabinet
TheLVcabinetshallbeincludedintheoverallvolumeofthecubicle.Itshallbedesignedtohousethe
variousLVelementsrequiredfortheoperationofthemotormechanismandauxiliaryequipment.
Forspecificneeds,itshallbepossibletoenlargeorextendtheLVboxbyaddinganenclosurewithadoorto
thetopofthecubicle.Theoverallheightofthecubiclesshallnotexceed2050mm.
Inallcases,thesevolumesshallbeaccessiblewiththecablesandbusbarslive,withoutisolatingtheentire
switchboard.LVcabinetnotsatisfyingthesecriteriawillnotbeaccepted.
5.13Currenttransformers
Thecurrenttransformersshallhavethesameshorttimewithstandcurrentandratedvoltageasthe
switchgear.
Lastupdate:20150616
11
SpecificationforTender 364842365.doc
ItshallbeinaccordancetoIEC618692,andbemadeofcastepoxyresinandmustbelabeledindividually.
Themanufacturershallbeinapositiontoprovidetypetestreportscertifiedbyanapprovedlaboratory
affiliatedwithinternationalorganizations.
Currenttransformersnotsatisfyingthesecriteriawillnotbeaccepted.
5.14LowPowerCurrenttransformers(LPCT)
TheLPCTisamagneticsensorinwhichprovidesavoltageoutputthatrepresentstheprimarycurrent,and
shallmeetthecharacteristicofswitchgear.
ItshallbeinaccordancetoIEC600448,andshallhavetwotypeofapplicationinwhichmediumvoltage
LPCTthatshallbemadeofcastepoxyresinprotection,andlowvoltageLPCTthatshallbemadeofplastic
protection.And,bothmustbelabeledindividually.
Itshallbeeasilyinstalled,andshallbedirectconnection(plugging)toprotectionrelay.
LPCTnotsatisfyingthesecriteriawillnotbeaccepted.
5.15Voltagetransformers
Thevoltagetransformersshallbemadeofcastepoxyresinandmustbelabeledindividually,anditshallbe
inaccordancetoIEC618693standard.
Dependingontheneeds,theyshallbeofthephasetophaseorphasetoearthtype.Theyshallbeprotected
byMVfusesorbycircuitbreakersonthepowercircuit.
Themanufacturershallbeinapositiontoprovidetypetestreportscertifiedbyanapprovedlaboratory
affiliatedwithinternationalorganizations.
Voltagetransformersnotsatisfyingthesecriteriawillnotbeaccepted.
5.16LVauxiliaries
Auxiliaryequipmentshallsatisfysection5.4ofIEC62271200standard.
TheLVcablesshallbeclass2typewitha2000Vinsulationlevel.
Theyshallbemarkedateachendforeasyverificationduringmaintenanceorservicingwork.
Thecablecrosssectionsshallnotbelessthan2.5sqmmforcircuitscarryinghighcurrents,or1sqmmfor
othercircuits.
5.17Controlandmonitoring
Alltherelays,instrumentsandmetersshallbeincorporatedintheLVboxlocatedatthetopofthecubicle.
Therelaysshallbeoftheintegratedunittype,meetingallprotectionandautomaticcontrolneeds.
TheyshallcomplywithIEC60801.4and50263standardsconcerningelectromagneticcompatibility.
Ifnecessary,theyshallbeabletocommunicate:
usingstandardizedprotocols,
adaptingtoawiderangeofpowersupplyvoltages,
withthepossibilityofbeingdisconnectedwhilelivewithoutanydangertoinstallation,
Lastupdate:20150616
12
SpecificationforTender 364842365.doc
storingtheinformationinmemoryintheeventofanauxiliarypowerfailure.
Themanufacturershallprovideproofthathehasalreadysuppliedequipmentofthesametypeandsame
makeandthatthisequipmenthasbeeninoperationforatleastthreeyears.
5.18Voltageindicatorsandphasecomparators
Functionshallbeabletobeequippedwithavoltageindicatorboxonthefrontofthedevicetoindicate
whetherornotthereisvoltageinthecables.Thecapacitivedividerswillsupplylowvoltagepowertothe
lamps.
Threeinletscanbeusedtocheckthesynchronizationofphases.
ThisdeviceshallbeincompliancewithIEC62271206standard.
5.19FaultPassageIndicators
Loadbreakswitchfunctionshallbeequippedwithafaultpassageindicator(FPI),inordertodetectand
localizeeasilythefaultypartofthenetwork.
ThelatterFPIshallsegregatetheshortcircuitandearthfaults,shallindicatepermanentlythephaseper
phaseloadcurrents,andshalleasilyactuatearemoteindicationlamp.
TheFPIfaultdetectioncorefunctionshallbeselfpoweredwithouthelpexternalpowersupplyorbuiltin
batteries.
5.20Safetyofpeople
Anyaccidentaloverpressureduetointernalarcinoneofthree(1busbar&2switching/disconnecting,and
3cableconnection)compartmentsofthefunctionsshallberesist,andgasshallbeexhausttothecable
trenchesorupwardtunneltoletoutofelectricalroomthroughexhaustchamberatrearofeachcubicleat
switchboard.
Noadditionalreinforcementshallbenecessaryatelectricalroom.
ManufacturershallprovidetypetestreporttoprovecompliancewithIEC62271200AnnexAfortwo
differentInternalArcperformance;
IAC:AFLandAFLRat12.5kA/1swithdownstreamexhaust,
IAC:AFLandAFLRat16kA/1swithdownstream,andupstreamexhausts.
IAC:AFLandAFLRat20kA/1swithupstreamexhaust,
5.21AutomaticTransferSystem(ATS)
ATSswitchgearshallgiveautomaticcontrolandmanagementofsourcesinthemediumvoltagewithusing
switchunits.
Theminimumtimetoswitchfromonesourcetosecondsourceshallbebetween(minimum)0.34sto2.24s
thatwouldbeadjustable.
Switchgearshallbeequippedwithmechanicalandelectricalinterlacingtoavoidanywrongoperation.
Switchgearshallguaranteeparallelsoperationbymechanicalandelectricalsynchronization.
Lastupdate:20150616
13
SpecificationforTender 364842365.doc
6.Typetestsandroutinetests
Dependingonswitchboard,typetestcertificatesmayberequiredfortheequipment,includingtheswitches
andthecircuitbreakers.
impulsedielectrictests,
powerfrequencydielectrictests,
temperaturerisetests,
shorttimewithstandcurrenttests,
mechanicaloperatingtests,
verificationofthedegreeofprotection,
internalarcwithstand
Inaddition,fortheswitchesandcircuitbreakers,theratedmakingandbreakingcapacitiesshallbe
substantiatedbyatestreport.
Fortheearthingswitch,themakingcapacity,theshorttimewithstandcurrentandthecorrespondingpeak
valueshallbesubstantiatedbyatestreport.
Theroutinetestscarriedoutbythemanufacturershallbesubstantiatedbyatestreportsignedbythe
manufacturer'squalitycontroldepartment.
Thereportshallcoverthefollowingaspects:
conformitywithdrawingsanddiagrams,
powerfrequencytests,
manualoperatingmechanismtests,
functionaltestsofLVauxiliariesandrelays.
7.Quality
Ifrequestedbytheclient,thesuppliershallprovideproofofapplicationofaqualityprocedurecomplying
withstandards.Thismeans:
useofaqualitymanualapprovedandsignedbyamanagementrepresentative,
regularupdatingofthismanualsothatitreflectsthemostrecentapplicablequalitycontrolprocedures,
ISO9002;9001certificationandalsoISO14001.
ProductEnvironmentalProfile(PEP)file
Lastupdate:20150616
14