Vous êtes sur la page 1sur 41

1 2 3 4 5 6 7 8

Preconfiguration for open/closed ring feeder

A Analog current input Analog voltage input A

I_SMAI_20_1 U_SMAI_20_2
I1 V1
SMAI_20_1 SMAI_20_2
BLOCK SPFCOUT BLOCK AI3P U3P
AIM_2.CH1 DFTSPFC AI3P I3P AIM_2.CH7 REVROT AI1 UL1
REVROT AI1 IL1 V2 UL1 AI2 UL2
IL1 AI2 IL2 GRP2L1 AI3 UL3
I2
GRP1L1 AI3 IL3 UL2 AI4 U0m
IL2 AI4 I0 GRP2L2 AIN
GRP1L2 AIN AIM_2.CH8 UL3
AIM_2.CH2 IL3 GRP2L3
V3
GRP1L3 U0
I3
I0 GRP2N
B GRP1N B
AIM_2.CH9 O:1|T:10|I:1
AIM_2.CH3 O:1|T:10|I:1

I_SMAI_80_1 U_SMAI_80_2
I1 V1
SMAI_80_1 SMAI_80_2
BLOCK SPFCOUT BLOCK AI3P U3P_80SPC
AIM_2.CH1 DFTSPFC AI3P I3P_80SPC AIM_2.CH7 REVROT
REVROT V2 UL1
IL1 GRP2L1
I2
GRP1L1 UL2
IL2 GRP2L2
GRP1L2 AIM_2.CH8 UL3
C AIM_2.CH2 C
IL3 GRP2L3
V3
GRP1L3 U0
I3
I0 GRP2N
GRP1N
AIM_2.CH9 O:1|T:5|I:1
AIM_2.CH3 O:1|T:5|I:1

Fixed signal

FXDSIGN
OFF FALSE
ON TRUE
D INTZERO INTZERO D
INTONE INTONE
INTALONE INTALONE
REALZERO REALZERO
STRNULL STRNULL
ZEROSMPL ZEROSMPL
GRP_OFF GRP_OFF
O:1000|T:1|I:1

E E

Main Application: Signals, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
1 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
1 2 3 4 5 6 7 8

A A

Bay control

QCCBAY
FALSE BLK_UPD LOC
BLK_CMD REM
O:2200|T:10|I:1

B B

Switch control for circuit breaker

CB1

DAXCBR
CB1 BLOCK XPOS
FALSE BLK_OPEN EXE_OP CB_OPEN_CMD
GNRLCSWI BLK_CLOSE EXE_CL CB_CLOSE_CMD
LR_SWI SUBSTED
C FALSE BLOCK EXE_OP OPEN OP_BLKD C
L_SEL EXE_CL CLOSE CL_BLKD
L_OPEN SELECTED POSOPEN UPD_BLKD
L_CLOSE START_SYN POSCLOSE OPENPOS DAXCBR_OPEN
AU_OPEN POSITION TRUCK_OPEN CLOSEPOS DAXCBR_CLOSE
AU_CLOSE OPENPOS TRUCK_CLOSE TRUCK_POS
RES_EXT INTERMPOS RS_OPR_CNT CNT_VAL
SYN_INPRO CLOSEPOS XIN L_CAUSE
SCILO TRUE SYNC_OK CMD_BLKD O:2301|T:10|I:1
EN_OPEN L_CAUSE
DAXCBR_OPEN POSOPEN EN_OPEN EN_CLOSE XOUT
DAXCBR_CLOSE POSCLOSE EN_CLOSE XPOS
TRUE OPEN_EN O:2251|T:10|I:1
CLOSE_EN
O:2210|T:10|I:1

CB_OP
D D

COM_101.BI1
CB_CL

COM_101.BI2

E E

Main Application: Control, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
2 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
1 2 3 4 5 6 7 8

A A

Switch control for disconnector 1

DC1_OP
B DC1 B
DAXSWI PSM_102.BO4_PO
DC1 FALSE BLOCK XPOS DC1_CL
BLK_OPEN EXE_OP
GNRLCSWI BLK_CLOSE EXE_CL
LR_SWI SUBSTED
FALSE BLOCK EXE_OP OPEN OP_BLKD PSM_102.BO5_PO
L_SEL EXE_CL CLOSE CL_BLKD
L_OPEN SELECTED POSOPEN UPD_BLKD
L_CLOSE START_SYN POSCLOSE OPENPOS DAXDC1_OPEN
AU_OPEN POSITION RS_OPR_CNT CLOSEPOS DAXDC1_CLOSE
AU_CLOSE OPENPOS XIN CNT_VAL
RES_EXT INTERMPOS L_CAUSE
SCILO SYN_INPRO CLOSEPOS
O:2301|T:100|I:1
TRUE SYNC_OK CMD_BLKD
DAXDC1_OPEN POSOPEN EN_OPEN EN_OPEN L_CAUSE
DAXDC1_CLOSE POSCLOSE EN_CLOSE EN_CLOSE XOUT
TRUE OPEN_EN XPOS
CLOSE_EN O:2250|T:100|I:3
C O:2210|T:100|I:3 C

DC1_OP

COM_101.BI3
DC1_CL

COM_101.BI4

D D

E E

Main Application: Control, Page: 2


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
3 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
1 2 3 4 5 6 7 8

A A

Switch control for disconnector 2

DC2_OP
DC2

DAXSWI PSM_102.BO6_PO
DC2 FALSE BLOCK XPOS DC2_CL
BLK_OPEN EXE_OP
GNRLCSWI BLK_CLOSE EXE_CL
LR_SWI SUBSTED
FALSE BLOCK EXE_OP OPEN OP_BLKD BIO_3.BO2_PO
L_SEL EXE_CL CLOSE CL_BLKD
L_OPEN SELECTED POSOPEN UPD_BLKD
B L_CLOSE START_SYN POSCLOSE OPENPOS DAXDC2_OPEN B
AU_OPEN POSITION RS_OPR_CNT CLOSEPOS DAXDC2_CLOSE
AU_CLOSE OPENPOS XIN CNT_VAL
RES_EXT INTERMPOS L_CAUSE
SCILO SYN_INPRO CLOSEPOS
O:2302|T:100|I:2
TRUE SYNC_OK CMD_BLKD
DAXDC2_OPEN POSOPEN EN_OPEN EN_OPEN L_CAUSE
DAXDC2_CLOSE POSCLOSE EN_CLOSE EN_CLOSE XOUT
OPEN_EN XPOS
CLOSE_EN O:2251|T:100|I:4
O:2211|T:100|I:4

DC2_OP

COM_101.BI5
C DC2_CL C

COM_101.BI6

D D

E E

Main Application: Control, Page: 3


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
4 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
1 2 3 4 5 6 7 8

A A

B B
Switch control for earth switch
ES

DAXSWI
ES FALSE BLOCK XPOS
BLK_OPEN EXE_OP ES[3]_EXE_OP
GNRLCSWI BLK_CLOSE EXE_CL ES[3]_EXE_CL
LR_SWI SUBSTED
FALSE BLOCK EXE_OP OPEN OP_BLKD
L_SEL EXE_CL CLOSE CL_BLKD
L_OPEN SELECTED POSOPEN UPD_BLKD
L_CLOSE START_SYN POSCLOSE OPENPOS DAXES_OPEN
AU_OPEN POSITION RS_OPR_CNT CLOSEPOS DAXES_CLOSE
AU_CLOSE OPENPOS XIN CNT_VAL
RES_EXT INTERMPOS L_CAUSE
SCILO SYN_INPRO CLOSEPOS
O:2303|T:100|I:3
TRUE SYNC_OK CMD_BLKD
C DAXES_OPEN POSOPEN EN_OPEN EN_OPEN L_CAUSE C
DAXES_CLOSE POSCLOSE EN_CLOSE EN_CLOSE XOUT
TRUE OPEN_EN XPOS
CLOSE_EN O:2252|T:100|I:5
O:2212|T:100|I:5

ES_OP

COM_101.BI7
ES_CL

COM_101.BI8

D D

E E

Main Application: Control, Page: 4


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
5 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
1 2 3 4 5 6 7 8

A Check for intermittent state of apparatus A

CB_CL AND DC1_CL AND


INPUT1 OUT CB_CLOSE INPUT1 OUT DC1_CLOSE
INPUT2 INPUT2
COM_101.BI2 COM_101.BI4
O:708|T:10|I:65 O:952|T:100|I:158

CB_OP INVERTER DC1_OP INVERTER


INPUT OUT INPUT OUT
COM_101.BI1 O:702|T:10|I:26 COM_101.BI3 O:946|T:100|I:104
B B
CB_OP AND
DC1_OP AND
INPUT1 OUT CB_OPEN
INPUT2 INPUT1 OUT DC1_OPEN
COM_101.BI1 INPUT2
O:716|T:10|I:79 COM_101.BI3
O:936|T:100|I:130
CB_CL INVERTER
DC1_CL INVERTER
INPUT OUT
O:710|T:10|I:40 INPUT OUT
COM_101.BI2
COM_101.BI4 O:930|T:100|I:76

AND
INPUT1 OUT TRUCK_CLOSE AND
ES_OP
INPUT2
O:724|T:100|I:143 INPUT1 OUT ES_OPEN
INPUT2
COM_101.BI7
INVERTER O:928|T:100|I:116
C C
INPUT OUT ES_CL INVERTER
O:718|T:100|I:89
INPUT OUT
COM_101.BI8 O:922|T:100|I:62
AND
INPUT1 OUT TRUCK_OPEN
INPUT2 AND
ES_CL
O:732|T:100|I:157
INPUT1 OUT ES_CLOSE
INVERTER INPUT2
COM_101.BI8
O:944|T:100|I:144
INPUT OUT
O:726|T:100|I:103 ES_OP INVERTER
INPUT OUT
COM_101.BI7 O:938|T:100|I:90

D D

E E

Main Application: Control, Page: 5


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
6 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
1 2 3 4 5 6 7 8

Interlocking for circuit breaker Interlocking for earthswitch


A A

INVERTER
AND
COM_OC_OPERATE INPUT OUT
O:1022|T:10|I:28 DC1_OPEN INPUT1 OUT
CB_CLOSE INPUT2
DC1_CLOSE INPUT3
O:1020|T:100|I:103
OR
AND
INVERTER INPUT1 OUT ES_EN
INPUT1 OUT CB_CLOSE_EN_A CB_OPEN INPUT2
SPR_CHR_ALM INPUT OUT INPUT2 O:1024|T:100|I:183
O:1030|T:10|I:42 INPUT3
O:1120|T:10|I:54

B B
Interlocking for disconnector 2
INVERTER
PRES_LOCKOUT INPUT OUT CB_OPEN_EN
O:922|T:10|I:27

AND
CB_OPEN INPUT1 OUT DC2_EN
DC1_OPEN INPUT2
ES_OPEN INPUT3
O:1984|T:100|I:218

AND
ES_CLOSE
DC1_OPEN
INPUT1
INPUT2
OUT
Interlocking for disconnector 1
C DC1_CLOSE INPUT3 C
CB_CLOSE_EN_A INPUT4
O:1128|T:10|I:68
OR AND
INPUT1 OUT INPUT1 OUT CB_CLOSE_EN AND
INPUT2 INPUT2
O:1140|T:10|I:77 O:1144|T:10|I:96 CB_OPEN INPUT1 OUT DC1_EN
DC1_CLOSE INPUT2
ES_OPEN INPUT3
AND O:1992|T:100|I:232
CB_CLOSE_EN_A INPUT1 OUT TRUCK_CLOSE
ES_OPEN INPUT2
O:1136|T:10|I:82

D D

E E

Main Application: Control, Page: 6


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
7 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
1 2 3 4 5 6 7 8

A A
OR
OP_DOC_H INPUT1 OUT
OP_OC_H1
OP_OC_H2
INPUT2
INPUT3
NOUT Autoreclosure
OP_OC_I INPUT4
OP_EF_L INPUT5
COM_OP_DIST INPUT6
O:1712|T:10|I:64

Circuit breaker monitoring


OR
OP_OC_L INPUT1 OUT
OP_DOC_L1 INPUT2 DARREC
OP_DOC_L2 INPUT3
INIT_1 OPEN_CB
O:1932|T:10|I:65
INIT_2 CLOSE_CB RECLOSE_AR
B INIT_3 CMD_WAIT B
INIT_4 INPRO AR_IN_PRO
OR INIT_5 LOCKED LOCKED_BY_AR
INIT_6 PROT_CRD
OP_EF_H INPUT1 OUT DEL_INIT_2 PROT_DISA
OP_DEF_H INPUT2 DEL_INIT_3 UNSUC_RECL UNSUCC_AR
OP_DEF_L1 INPUT3 DEL_INIT_4 AR_ON
OP_DEF_L2 INPUT4 BLK_RECL_T READY AR_READY CB_OP
O:1720|T:10|I:78 BLK_RCLM_T ACTIVE AR_ZONES SSCBR
BLK_BY_TH BLK_THERM AR_ZONES
CB_OPEN CB_POS I3P I3P TRV_T_OP_ALM TRV_T_OP_ALM
TRUE CB_READY COM_101.BI1 BLOCK TRV_T_CL_ALM TRV_T_CL_ALM
OR INC_SHOTP BLK_ALM SPR_CHR_ALM SPR_CHR_ALM
CB_CL
FALSE INHIBIT_RECL POSOPEN OPR_ALM CBOPR_ALM
OP_NSOC_1 INPUT1 OUT RECL_ON POSCLOSE OPR_LO
OP_NSOC_2 INPUT2 SYNC PRES_ALM_IN IPOW_ALM IPOW_ALM
OP_INTREF INPUT3 COM_101.BI2 PRES_LO_IN IPOW_LO
O:2010|T:10|I:1
OP_PHDIS INPUT4 SPR_CHR_ST CB_LIFE_ALM CB_LIFE_ALM
SF6_LOW
PRES_LOCKOUT INPUT5 SPR_CHR MON_ALM MON_ALM
RST_CB_WEAR PRES_ALM
O:1728|T:10|I:127
RST_IPOW PRES_LO PRES_LOCKOUT
BIO_3.BI2 RST_SPR_T OPENPOS
C C
SPR_CHR_ST RST_TRV_T INVALIDPOS
CLOSEPOS
RCA
O:3101|T:10|I:1

BIO_3.BI5

RCA INVERTER
INPUT OUT SPR_CHR_ST
BIO_3.BI5 O:2922|T:10|I:35

D D

OR
TRV_T_CL_ALM INPUT1 OUT
TRV_T_OP_ALM INPUT2
CB_LIFE_ALM INPUT3
CBOPR_ALM INPUT4
IPOW_ALM INPUT5 OR
MON_ALM INPUT6
O:3720|T:10|I:119 INPUT1 OUT CB_MONITOR_ALARM
PRES_LOCKOUT INPUT2
SPR_CHR_ALM INPUT3
O:3728|T:10|I:343

E E

Main Application: Control, Page: 7


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
8 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
1 2 3 4 5 6 7 8

A A

Fuse failure supervision Current circuit supervision


Inrush protection

SEQRFUF
CCRDIF
INRPHAR I3P I3P FUSEF_3PH
U3P U3P FUSEF_U FUSE_FAILURE I3P I3P FAIL CC_FAILURE
I3P_80SPC I3P BLK2H BLK_BY_INRUSH BLOCK FUSEF_Z BLOCK ALARM
BLOCK BLK2H_A BLK_ON_TR O:1011|T:10|I:1
BLK2H_B CB_CLOSE CB_CLOSED
BLK2H_C DISCON_OPEN
MCB
O:1001|T:5|I:1 MINCB_OPEN
O:1060|T:10|I:1
BIO_3.BI3
B B

Trip circuit supervision


Thermal protection

PSM_102.TCS_BO1 TCSSCBR
TCS_STATE ALARM TC_ALARM_1
BLOCK T1PTTR
FR_TIMER
O:3003|T:10|I:1 I3P I3P OPERATE OP_TH
AMB_TEMP START
BLOCK ALARM ALARM_TH
BLK_OPR BLK_CLOSE BLK_BY_TH
ENA_MULT
C SENSFLT C
RESET
PSM_102.TCS_BO3
TCSSCBR O:1100|T:200|I:1
OR
TCS_STATE ALARM TC_ALARM_2
CB_OPEN INPUT1 OUT BLOCK
COM_OC_OPERATE INPUT2 FR_TIMER
O:2924|T:10|I:55 O:3001|T:10|I:2

Circuit breaker failure protection


PSM_102.TCS_BO2 TCSSCBR
TCS_STATE ALARM TC_ALARM_3
CB_CLOSE BLOCK
FR_TIMER
O:3002|T:10|I:3
D D
CCBRBRF
OR
I3P I3P TRRET CBFP_RETRIP
COM_OC_OPERATE INPUT1 OUT START TRBU CBFP_BUTRIP
INPUT2 CB_CLOSE POSCLOSE CB_FAULT_AL
EXTST_CCBRBRF
O:924|T:10|I:47 BLOCK
CB_FAULT
BIO_3.BI4 O:1250|T:10|I:1
OR BIO_3.BO3_PO
TC_ALARM_1 INPUT1 OUT TC_ALARM
TC_ALARM_2 INPUT2
TC_ALARM_3 INPUT3
O:3704|T:10|I:56

E E

Main Application: Protection, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
9 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
1 2 3 4 5 6 7 8

A A

Directional overcurrent protection

DPHLPDOC
I3P I3P OPERATE OP_DOC_L1
U3P U3P OPR_A
BLOCK OPR_B
BLK_OPR OPR_C
BLK_ST START ST_DOC_L1
FR_TIMER ST_A
BLK_BY_INRUSH ENA_MULT ST_B
ST_C
B FAULT_DIR B
FLT_DIR_A
FLT_DIR_B
FLT_DIR_C
O:1202|T:10|I:1

DPHLPDOC OR
I3P I3P OPERATE OP_DOC_L2 OP_DOC_H INPUT1 OUT COM_OP_DOC
U3P U3P OPR_A OP_DOC_L1 INPUT2
BLOCK OPR_B OP_DOC_L2 INPUT3
BLK_OPR OPR_C
O:1704|T:10|I:50
BLK_ST START ST_DOC_L2
FR_TIMER ST_A
BLK_BY_INRUSH ENA_MULT ST_B
ST_C
FAULT_DIR
C FLT_DIR_A C
FLT_DIR_B
FLT_DIR_C
O:1203|T:10|I:2

OR
ST_DOC_H INPUT1 OUT COM_ST_DOC
ST_DOC_L1 INPUT2
DPHHPDOC ST_DOC_L2 INPUT3
O:1924|T:10|I:51
I3P I3P OPERATE OP_DOC_H
U3P U3P OPR_A
BLOCK OPR_B
BLK_OPR OPR_C
BLK_ST START ST_DOC_H
FR_TIMER ST_A
BLK_BY_INRUSH ENA_MULT ST_B
ST_C
D FAULT_DIR D
FLT_DIR_A
FLT_DIR_B
FLT_DIR_C
O:1204|T:10|I:1

E E

Main Application: Protection, Page: 2


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
10 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
1 2 3 4 5 6 7 8

A A

Nondirectional overcurrent protection

PHHPTOC
I3P_80SPC I3P OPERATE OP_OC_H1
BLOCK OPR_A
BLK_OPR OPR_B
BLK_ST OPR_C
FR_TIMER START ST_OC_H1
BLK_BY_INRUSH ENA_MULT ST_A
ST_B
B ST_C B
O:1202|T:5|I:1

OR
PHHPTOC
OP_OC_H1 INPUT1 OUT COM_OP_OC
I3P_80SPC I3P OPERATE OP_OC_H2 OP_OC_H2 INPUT2
BLOCK OPR_A OP_OC_I INPUT3
BLK_OPR OPR_B OP_OC_L INPUT4
BLK_ST OPR_C O:1712|T:5|I:149
FR_TIMER START ST_OC_H2
BLK_BY_INRUSH ENA_MULT ST_A
ST_B
ST_C
O:1203|T:5|I:2

PHIPTOC
C C
I3P_80SPC I3P OPERATE OP_OC_I
BLOCK OPR_A
BLK_OPR OPR_B OR
BLK_ST OPR_C
FR_TIMER START ST_OC_I ST_OC_H1 INPUT1 OUT COM_ST_OC
BLK_BY_INRUSH ENA_MULT ST_A ST_OC_H2 INPUT2
ST_B ST_OC_I INPUT3
ST_C ST_OC_L INPUT4
O:1101|T:5|I:1 O:1704|T:5|I:135

PHLPTOC
I3P I3P OPERATE OP_OC_L
BLOCK OPR_A
BLK_OPR OPR_B
BLK_ST OPR_C
FR_TIMER START ST_OC_L
BLK_BY_INRUSH ENA_MULT ST_A
D ST_B D
ST_C
O:1201|T:10|I:1

E E

Main Application: Protection, Page: 3


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
11 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
1 2 3 4 5 6 7 8

A A
Directional earthfault protection

DEFHPDEF
I3P I3P OPERATE OP_DEF_H
U3P U3P START ST_DEF_H
BLK_BY_INTREF BLOCK FAULT_DIR
BLK_OPR
BLK_ST
FR_TIMER
RCA
ENA_MULT
RCA_CTL
BIO_3.BI5 O:1211|T:10|I:1

B B
OR
DEFLPDEF OP_DEF_H INPUT1 OUT COM_OP_DEF
OP_DEF_L1 INPUT2
I3P I3P OPERATE OP_DEF_L1 OP_DEF_L2 INPUT3
U3P U3P START ST_DEF_L1 O:1940|T:10|I:79
BLK_BY_INTREF BLOCK FAULT_DIR
BLK_OPR
BLK_ST
FR_TIMER
RCA
ENA_MULT
RCA_CTL
BIO_3.BI5 O:1209|T:10|I:1

C C
DEFLPDEF
OR
I3P I3P OPERATE OP_DEF_L2
U3P U3P START ST_DEF_L2 ST_DEF_H INPUT1 OUT COM_ST_DEF
BLK_BY_INTREF BLOCK FAULT_DIR ST_DEF_L1 INPUT2
BLK_OPR ST_DEF_L2 INPUT3
BLK_ST
O:2024|T:10|I:52
FR_TIMER
RCA
ENA_MULT
RCA_CTL
BIO_3.BI5 O:1210|T:10|I:2

D D

E E

Main Application: Protection, Page: 4


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
12 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
1 2 3 4 5 6 7 8

A A

Negative sequence overcurrent protection

NSPTOC
B I3P I3P OPERATE OP_NSOC_1 B
BLOCK START ST_NSOC_1 OR
BLK_OPR
BLK_ST OP_NSOC_1 INPUT1 OUT COM_OP_NSOC
FR_TIMER OP_NSOC_2 INPUT2
ENA_MULT O:1948|T:10|I:128
O:1205|T:10|I:1

NSPTOC
C C
I3P I3P OPERATE OP_NSOC_2 OR
BLOCK START ST_NSOC_2
BLK_OPR ST_NSOC_1 INPUT1 OUT COM_ST_NSOC
BLK_ST ST_NSOC_2 INPUT2
FR_TIMER O:2032|T:10|I:66
ENA_MULT
O:1206|T:10|I:2

D
Phase discontinuity protection D

PDNSPTOC
I3P I3P OPERATE OP_PHDIS
BLOCK START ST_PHDIS
BLK_OPR
BLK_ST
FR_TIMER
O:1207|T:10|I:1

E E

Main Application: Protection, Page: 5


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
13 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
1 2 3 4 5 6 7 8

Distance protection
A DSTPDIS A
I3P I3P OPERATE_GFC OP_GFC
GRP_OFF I3P_PAR START_GFC ST_GFC
I3P_REF STARTS_GFC
U3P U3P RELEASE_PE AND OR
FUSE_FAILURE BLOCK RELEASE_PP
SYS_EARTHING EARTH_FLT INPUT1 OUT OP_EARTH_Z1 OP_Z1 INPUT1 OUT COM_OP_DIST
TRIGG_REC XC_FLT OP_Z1 INPUT2 OP_Z2 INPUT2
AR_ZONES AR_ZONES DIR_E_FLT O:700|T:5|I:1 OP_Z3 INPUT3
BLOCK_GFC OPERATE_Z1 OP_Z1 OP_Z4 INPUT4
BLK_OP_GFC START_Z1 ST_Z1 OP_Z5 INPUT5
BLK_ST_GFC STARTS_Z1
O:704|T:5|I:131
FR_T_GFC OPERATE_Z2 OP_Z2
BLOCK_Z1 START_Z2 ST_Z2
BLK_OP_Z1 STARTS_Z2
BLK_ST_Z1 OPERATE_Z3 OP_Z3
FR_T_PE_Z1 START_Z3 ST_Z3 GRP2_LED1
FR_T_PP_Z1 STARTS_Z3
BLOCK_Z2 OPERATE_ZAR1 OP_Z4 OP_Z1 HM2L01R
BLK_OP_Z2 START_ZAR1 ST_Z4 ST_Z1 HM2L01Y
B BLK_ST_Z2 STARTS_ZAR1 HM2L01G B
FR_T_PE_Z2 OPERATE_ZAR2 OP_Z5 O:4500|T:10|I:1
FR_T_PP_Z2 START_ZAR2 ST_Z5
BLOCK_Z3 STARTS_ZAR2
BLK_OP_Z3 DIRECTION DIRECTION
BLK_ST_Z3 DIR_LOOP_R DIR_LOOP_R
FR_T_PE_Z3 DIR_LOOP_X DIR_LOOP_X
FR_T_PP_Z3 FLTLOOP_RFST FLTLOOP_RFST GRP2_LED2
BLOCK_ZAR1 FLTLOOP_XFST FLTLOOP_XFST
BLK_OP_ZAR1 FLTLOOP_RSND FLTLOOP_RSND OP_Z2 HM2L02R
BLK_ST_ZAR1 FLTLOOP_XSND FLTLOOP_XSND ST_Z2 HM2L02Y
FR_T_PE_ZAR1 FLTLOOP_RPP FLTLOOP_RPP HM2L02G
FR_T_PP_ZAR1 FLTLOOP_XPP FLTLOOP_XPP O:4500|T:10|I:1
BLOCK_ZAR2
BLK_OP_ZAR2
BLK_ST_ZAR2
FR_T_PE_ZAR2
FR_T_PP_ZAR2
RESET GRP2_LED3
O:1253|T:10|I:1
OP_Z3 HM2L03R
C ST_Z3 HM2L03Y C
HM2L03G
O:4500|T:10|I:1

GRP2_LED4
SCEFRFLO OP_Z4 HM2L04R
ST_Z4 HM2L04Y
I3P I3P ALARM ALARM HM2L04G
U3P U3P EF_VALIDITY EF_VALIDITY O:4500|T:10|I:1
BLOCK FAULT_LOOP FAULT_LOOP
TRIGG_FLOC TRIGG TRIGG_OUT TRIGG_OUT
TRIGG_XC0F FLT_DISTANCE FLT_DISTANCE
RESET IFLT_PER_ILD IFLT_PER_ILD
RF RF GRP2_LED5
RFLOOP RFLOOP
D XFLOOP XFLOOP OP_Z5 HM2L05R D
S_CALC S_CALC ST_Z5 HM2L05Y
XC0F_CALC XC0F_CALC HM2L05G
O:1300|T:10|I:1 O:4500|T:10|I:1

OR
COM_OP_DIST INPUT1 OUT TRIGG_FLOC
COM_OP_EF INPUT2
O:1024|T:5|I:133

E E

Main Application: Protection, Page: 6


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
14 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
1 2 3 4 5 6 7 8

A A

Nondirectional earth fault protection

EFIPTOC EFHPTOC EFLPTOC


I3P_80SPC I3P OPERATE OP_EF_I I3P_80SPC I3P OPERATE OP_EF_H I3P I3P OPERATE OP_EF_L
BLOCK START ST_EF_I BLOCK START ST_EF_H BLOCK START ST_EF_L
BLK_OPR BLK_OPR BLK_OPR
BLK_ST BLK_ST BLK_ST
FR_TIMER FR_TIMER FR_TIMER
ENA_MULT ENA_MULT ENA_MULT
O:1102|T:5|I:1 O:1201|T:5|I:1 O:1208|T:10|I:1

B B

OR OR
OP_EF_I INPUT1 OUT COM_OP_EF ST_EF_I INPUT1 OUT COM_ST_EF
OP_EF_H INPUT2 ST_EF_H INPUT2
OP_EF_L INPUT3 ST_EF_L INPUT3
OP_INTREF INPUT4 ST_INTREF INPUT4
O:1720|T:5|I:163 O:1728|T:5|I:177

Intermittent earth fault protection

INTRPTEF
C C
I3P_80SPC I3P OPERATE OP_INTREF
U3P_80SPC U3P START ST_INTREF
BLOCK FAULT_DIR
BLK_OPR BLK_EF BLK_BY_INTREF
BLK_ST
FR_TIMER
O:1002|T:5|I:1

D D

E E

Main Application: Protection, Page: 7


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
15 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
1 2 3 4 5 6 7 8

A A
Common alarm signals

OR OR
COM_OP_DOC INPUT1 OUT OC/DOC_OP_ALARM COM_ST_DOC INPUT1 OUT UPSTM_OC/DOC_BLK
COM_OP_OC INPUT2 COM_ST_OC INPUT2
O:1924|T:5|I:136 O:2140|T:5|I:166

B B

OC_GENERAL
OR OR
COM_OP_EF INPUT1 OUT EF/DEF_OP_ALARM OC/DOC_OP_ALARM INPUT1 OUT COM_OC_OPERATE
OP_DEF_H INPUT2 EF/DEF_OP_ALARM INPUT2
OP_DEF_L1 INPUT3 OP_PHDIS INPUT3
OP_DEF_L2 INPUT4 OP_TH INPUT4
O:1932|T:5|I:150 OP_NSOC_1 INPUT5
OP_NSOC_2 INPUT6
C O:1940|T:5|I:164 C

OR
COM_ST_DEF INPUT1 OUT COM_START
COM_ST_DOC INPUT2 OR
COM_ST_EF INPUT3
D COM_ST_NSOC INPUT4 TC_ALARM INPUT1 OUT SUPERVISION_ALM D
COM_ST_OC INPUT5 CC_FAILURE INPUT2
ST_PHDIS INPUT6 FUSE_FAILURE INPUT3
O:2704|T:5|I:139 CB_MONITOR_ALARM INPUT4
O:3924|T:10|I:57

E E

Main Application: Protection, Page: 8


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
16 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
1 2 3 4 5 6 7 8

Voltage Protection

A A
PHPTOV OR
U3P U3P OPERATE OP_OV OP_OV INPUT1 OUT COM_OP_VP
BLOCK OPR_A OP_UV INPUT2
BLK_OPR OPR_B OP_ROV INPUT3
BLK_ST OPR_C
O:924|T:5|I:132
FR_TIMER START ST_OV
ST_A
ST_B
ST_C
O:1215|T:10|I:1

PHPTUV ROVPTOV
B B
U3P U3P OPERATE OP_UV U3P U3P OPERATE OP_ROV
BLOCK OPR_A BLOCK START ST_ROV
BLK_OPR OPR_B BLK_OPR
BLK_ST OPR_C BLK_ST
FR_TIMER START ST_UV FR_TIMER
ST_A
O:1214|T:10|I:1
ST_B
ST_C
O:1218|T:10|I:1

Frecuency Protection

C C

DAPTOF OR
U3P U3P OPERATE OP_O_FREC OP_O_FREC INPUT1 OUT OP_FREC
BLOCK START ST_O_FREC OP_U_FREC INPUT2
LOWAMPL_BLKD O:2024|T:5|I:137
O:1234|T:10|I:1

DAPTUF
U3P U3P OPERATE OP_U_FREC
BLK_UF BLOCK START ST_U_FREC
BLK_REST RESTORE
D LOWAMPL_BLKD D
O:1239|T:10|I:1

E E

Main Application: Protection, Page: 9


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
17 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
1 2 3 4 5 6 7 8

A
Alarm signals connected to binary outputs A

OR OR
OC/DOC_OP_ALARM INPUT1 OUT COM_OC_OPERATE INPUT1 OUT
B INPUT2 INPUT2 B
O:4932|T:5|I:158 O:4924|T:5|I:144
PULSETIMER
PULSETIMER
INPUT OUT
O:4798|T:5|I:45 INPUT OUT
O:3798|T:5|I:44

OR OR
EF/DEF_OP_ALARM INPUT1 OUT CB_MONITOR_ALARM INPUT1 OUT
INPUT2 INPUT2
O:4948|T:5|I:356 O:4924|T:10|I:59

PULSETIMER
PULSETIMER
INPUT OUT
C INPUT OUT O:4785|T:5|I:5 C
O:2785|T:5|I:3

OR OR
COM_START INPUT1 OUT SUPERVISION_ALM INPUT1 OUT
INPUT2 INPUT2
O:4940|T:5|I:172 O:4932|T:10|I:73

PULSETIMER PULSETIMER
INPUT OUT INPUT OUT
O:2798|T:5|I:43 O:4785|T:10|I:15

OR
UPSTM_OC/DOC_BLK INPUT1 OUT
D INPUT2 D
O:4704|T:5|I:143

PULSETIMER
INPUT OUT
O:3785|T:5|I:4

E E

Main Application: Protection, Page: 10


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
18 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
1 2 3 4 5 6 7 8

A A

Master trip and close logic

OR CB_OP
CB_OPEN_CMD
INPUT1 OUT
INPUT2
PSM_102.BO1_PO_TCS
O:2948|T:5|I:352
B OR TRPPTRC TRIP #2 B
COM_OC_OPERATE INPUT1 OUT OPERATE TRIP
INPUT2 BLOCK CL_LKOUT
FALSE INPUT3 RST_LKOUT PSM_102.BO3_PO_TCS
FALSE INPUT4 O:2001|T:5|I:1
FALSE INPUT5
O:1948|T:5|I:178

OR CB_CL
CB_CLOSE_CMD INPUT1 OUT
C RECLOSE_AR INPUT2 C
PSM_102.BO2_PO_TCS
O:4728|T:5|I:355

D D

E E

Main Application: Protection, Page: 11


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
19 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
1 2 3 4 5 6 7 8

Phase Voltage Phase current measurement Power monitoring with frequency


A A
CMMXU PWRMMXU
VPHMMXU
I3P I3P I_INST_A I3P I3P S_INST S_INST
U3P U3P U_INST_A IL1 U3P U3P S_DB
UL1 I_DB_A S_RANGE
U_DB_A IL1 angle P_INST P_INST
UL1 angle I_ANGL_A P_DB
U_ANGL_A I_RANGE_A P_RANGE
U_RANGE_A U_RANGE_A I_INST_B Q_INST Q_INST
U_INST_B IL2 Q_DB
UL2 I_DB_B Q_RANGE
U_DB_B IL2 angle PF_DB PF_DB
UL2 angle I_ANGL_B PF_RANGE
U_ANGL_B I_RANGE_B ILAG ILAG
U_RANGE_B U_RANGE_B I_INST_C ILEAD ILEAD
U_INST_C IL3 F_DB F_DB
UL3 I_DB_C F_RANGE F_RANGE
U_DB_C IL3 angle
I_ANGL_C O:3030|T:100|I:1
UL3 angle
U_ANGL_C I_RANGE_C
B U_RANGE_C U_RANGE_C O:3001|T:100|I:1 B
O:3020|T:100|I:1

UL1
Residual current measurement
MVEXP
RESCMMXU U_RANGE_A RANGE HIGHHIGH
HIGH
I3P I3P I0_INST NORMAL
VPPMMXU I0 RESCMMXU_I0 LOW
I0_DB LOWLOW
U3P U3P U_INST_AB I0 angle
I0_ANGL O:4003|T:100|I:18
U12
U_DB_AB I0_RANGE
U12 angle O:3004|T:100|I:1
U_ANGL_AB UL2
U_RANGE_AB
U_INST_BC
U23
Residual voltage measurement MVEXP
U_DB_BC U_RANGE_B RANGE HIGHHIGH OR
C U23 angle RESVMMXU HIGH C
U_ANGL_BC NORMAL INPUT1 OUT BLK_UF
U_RANGE_BC U3P U3P U0_RMS_INST LOW INPUT2
U_INST_CA U0 RESVMMXU_U0 LOWLOW INPUT3
U31 U0_RMS_DB
O:4001|T:100|I:16 O:1124|T:5|I:134
U_DB_CA U0_RMS_RANGE
U31 angle U0_MAG_INST
U_ANGL_CA U0_MAG_DB
U_RANGE_CA U0_MAG_RANGE
O:3021|T:100|I:1 U0 angle UL3
U0_ANGL_INST
O:3022|T:100|I:1 MVEXP
U_RANGE_C RANGE HIGHHIGH
HIGH
Sequence current measurement NORMAL
LOW
LOWLOW
CSMSQI O:4002|T:100|I:17
I3P I3P I1_INST I1_INST
D I1_DB D
I1_RANGE
I2_INST I2_INST
I2_DB
I2_RANGE
O:3007|T:100|I:1

Sequence voltage measurement


VSMSQI
U3P U3P U1_INST
U1_DB
U1 RANGE
U2_INST
U2_DB
U2_RANGE
E O:3023|T:100|I:1 E

Main Application: Meas_Rec, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
20 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
1 2 3 4 5 6 7 8

LED indication

GRP1_LED1 GRP1_LED11
A A
COM_OP_DOC HM1L01R CBFP_RETRIP HM1L11R
COM_ST_DOC HM1L01Y
O:4500|T:10|I:1
O:4500|T:10|I:1

GRP1_LED2
GRP1_LED12
COM_OP_OC HM1L02R
COM_ST_OC HM1L02Y CB_MONITOR_ALARM HM1L12R
O:4500|T:10|I:1 O:4500|T:10|I:1

GRP1_LED3
GRP1_LED13
COM_OP_NSOC HM1L03R
COM_ST_NSOC HM1L03Y FUSE_FAILURE HM1L13R
O:4500|T:10|I:1 O:4500|T:10|I:1
B B

GRP1_LED4
COM_OP_EF HM1L04R GRP1_LED14
COM_ST_EF HM1L04Y
O:4500|T:10|I:1 CC_FAILURE HM1L14R
O:4500|T:10|I:1

GRP1_LED5
GRP1_LED15
COM_OP_DEF HM1L05R
COM_ST_DEF HM1L05Y HM1L15R
O:4500|T:10|I:1 HM1L15Y
HM1L15G
O:4500|T:10|I:1

GRP1_LED6
C C
OP_PHDIS HM1L06R GRP2_LED6
ST_PHDIS HM1L06Y
O:4500|T:10|I:1 OP_OV HM2L06R
ST_OV HM2L06Y
O:4500|T:10|I:1

GRP1_LED7
OP_TH HM1L07R GRP2_LED7
ALARM_TH HM1L07Y
O:4500|T:10|I:1 OP_UV HM2L07R
ST_UV HM2L07Y
O:4500|T:10|I:1

GRP1_LED8
LOCKED_BY_AR HM1L08R GRP2_LED8
AR_IN_PRO HM1L08Y
AR_READY HM1L08G OP_O_FREC HM2L08R
D O:4500|T:10|I:1 ST_O_FREC HM2L08Y D
HM2L08G
O:4500|T:10|I:1

GRP1_LED9
TC_ALARM HM1L09R GRP2_LED9
O:4500|T:10|I:1
OP_U_FREC HM2L09R
ST_U_FREC HM2L09Y
HM2L09G
GRP1_LED10 O:4500|T:10|I:1
CBFP_BUTRIP HM1L10R
O:4500|T:10|I:1

GRP2_LED10
OP_ROV HM2L10R
ST_ROV HM2L10Y
HM2L10G
E O:4500|T:10|I:1 E

Main Application: Meas_Rec, Page: 2


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
21 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
1 2 3 4 5 6 7 8

Binary recorders
CB_CL
A A

COM_101.BI2
B1RBDR B2RBDR CB_OP B3RBDR B4RBDR
BLK_BY_INRUSH BLK_BY_INRUSH ST_NSOC_1 ST_NSOC_1 CB_CLOSE OP_ROV OP_ROV
INPUT1 INPUT17 INPUT33 INPUT49
ST_DOC_H ST_DOC_H OP_NSOC_1 OP_NSOC_1 COM_101.BI1 CB_OPEN ST_ROV ST_ROV
INPUT2 INPUT18 INPUT34 INPUT50
OP_DOC_H OP_DOC_H ST_NSOC_2 ST_NSOC_2 UNSUCC_AR UNSUCC_AR ST_O_FREC ST_O_FREC
INPUT3 INPUT19 INPUT35 INPUT51
ST_DOC_L1 ST_DOC_L1 OP_NSOC_2 OP_NSOC_2 LOCKED_BY_AR LOCKED_BY_AR ST_U_FREC ST_U_FREC
INPUT4 INPUT20 INPUT36 INPUT52
OP_DOC_L1 OP_DOC_L1 ST_DEF_H ST_DEF_H RECLOSE_AR RECLOSE_AR ST_Z1 Z1_START
INPUT5 INPUT21 INPUT37 INPUT53
ST_DOC_L2 ST_DOC_L2 OP_DEF_H OP_DEF_H OP_U_FREC OP_U_FREC ST_Z2 Z2_START
INPUT6 INPUT22 INPUT38 INPUT54
OP_DOC_L2 OP_DOC_L2 ST_DEF_L1 ST_DEF_L1 OP_O_FREC OP_O_FREC ST_Z3 Z3_START
INPUT7 INPUT23 INPUT39 INPUT55
ST_OC_H1 ST_OC_H1 OP_DEF_L1 OP_DEF_L1 TC_ALARM TC_ALARM_1 ST_Z4 Z4_START
INPUT8 INPUT24 INPUT40 INPUT56
B B
OP_OC_H1 OP_OC_H1 ST_DEF_L2 ST_DEF_L2 OP_EF_I OP_EF_I ST_Z5 Z5_START
INPUT9 INPUT25 INPUT41 INPUT57
ST_OC_H2 ST_OC_H2 OP_DEF_L2 OP_DEF_L2 ST_EF_I ST_EF_I OP_Z1 Z1_OP
INPUT10 INPUT26 INPUT42 INPUT58
OP_OC_H2 OP_OC_H2 ST_EF_L ST_EF_L CC_FAILURE CC_FAILURE OP_Z2 Z2_OP
INPUT11 INPUT27 INPUT43 INPUT59
ST_OC_I ST_OC_I OP_EF_L OP_EF_L FUSE_FAILURE FUSE_FAILURE OP_Z3 Z3_OP
INPUT12 INPUT28 INPUT44 INPUT60
OP_OC_I OP_OC_I ST_INTREF ST_INTREF OP_EF_H OP_EF_H OP_Z4 Z4_OP
INPUT13 INPUT29 INPUT45 INPUT61
ST_OC_L ST_OC_L OP_INTREF OP_INTREF ST_EF_H ST_EF_H OP_Z5 Z5_OP
INPUT14 INPUT30 INPUT46 INPUT62
OP_OC_L OP_OC_L ST_UV ST_UV SPR_CHR_ALM SPR_CHR_ALM OP_UV OP_UV
INPUT15 INPUT31 INPUT47 INPUT63
OP_TH OP_TH ST_OV ST_OV CB_LIFE_ALM CB_LIFE_ALM OP_OV OP_OV
INPUT16 INPUT32 INPUT48 INPUT64
O:4051|T:10|I:1 O:4052|T:10|I:1 O:4053|T:10|I:1 O:4057|T:10|I:1
ST_PHDIS

C OP_PHDIS C

Analog recorders

A1RADR
A2RADR A3RADR A4RADR
IL1 IL1
GRPINPUT1 OPEN_DELTA_VT U12 DIR_LOOP_R DIR_LOOP_R
IL2 IL2 GRPINPUT11 INPUT21 INPUT31
GRPINPUT2 GRPINPUT12 U23 DIR_LOOP_X DIR_LOOP_X
IL3 IL3 GRPINPUT13 INPUT22 INPUT32
GRPINPUT3 GRPINPUT14 U31 FLTLOOP_RFST FLTLOOP_RFST
I0 I0 GRPINPUT15 INPUT23 INPUT33
GRPINPUT4 GRPINPUT16 I1_INST I_POS_SEQ FLTLOOP_RPP FLTLOOP_RPP
UL1 UL1 GRPINPUT17 INPUT24 INPUT34
D GRPINPUT5 GRPINPUT18 I2_INST I_NEG_SEQ FLTLOOP_RSND FLTLOOP_RSND D
UL2 UL2 GRPINPUT19 INPUT25 INPUT35
GRPINPUT6 GRPINPUT20 P_INST P_INST FLTLOOP_XFST FLTLOOP_XFST
UL3 UL3 INPUT26 INPUT36
O:4102|T:10|I:1
GRPINPUT7 Q_INST Q_INST FLTLOOP_XPP FLTLOOP_XPP
U0m U0m INPUT27 INPUT37
GRPINPUT8 S_INST S_INST FLTLOOP_XSND FLTLOOP_XSND
INPUT28 INPUT38
O:4101|T:10|I:1
O:4103|T:10|I:1 FLT_DISTANCE FLT_DISTANCE
INPUT39
RF FAULT RES.
INPUT40
O:4104|T:10|I:1

E E

Main Application: Meas_Rec, Page: 3


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
22 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
1 2 3 4 5 6 7 8

FK_RESET TRIP & START LEDS


A A

FNKEYMD1 LHMICTRL
OR
LEDCTL1 FKEYOUT1 CLRLEDS HMI-ON
RED-S INPUT1 OUT
O:4001|T:10|I:1
YELLOW-S INPUT2
YELLOW-F O:704|T:10|I:46
CLRPULSE
LEDSCLRD
O:10|T:100|I:1

LEDGEN
B B
BLOCK NEWIND
RESET ACK
O:4500|T:10|I:1

Short Cut - MEAS

FNKEYMD2
LEDCTL2 FKEYOUT2
O:4002|T:10|I:1

C C

D D

E E

Main Application: Meas_Rec, Page: 4


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
23 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
Output Variable Information Present in Signals Page 1
Name Page Partner Location Partner Page
I3P 1 Control 7
Protection 1
Protection 1
Protection 1
Protection 1
Protection 2
Protection 2
Protection 2
Protection 3
Protection 4
Protection 4
Protection 4
Protection 5
Protection 5
Protection 5
Protection 6
Protection 6
Protection 7
Meas_Rec 1
Meas_Rec 1
Meas_Rec 1
Meas_Rec 1
IL1 1 Meas_Rec 3
IL2 1 Meas_Rec 3
IL3 1 Meas_Rec 3
I0 1 Meas_Rec 3
I3P_80SPC 1 Protection 1
Protection 3
Protection 3
Protection 3
Protection 7
Protection 7
Protection 7
U3P_80SPC 1 Protection 7
U3P 1 Protection 1
Protection 2
Protection 2
Protection 2
Protection 4
Protection 4
Protection 4
Protection 6
Protection 6
Protection 9
Protection 9
Protection 9
Protection 9
Protection 9
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
24 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
Name Page Partner Location Partner Page
Meas_Rec 1
Meas_Rec 1
Meas_Rec 1
Meas_Rec 1
Meas_Rec 1
UL1 1 Meas_Rec 3
UL2 1 Meas_Rec 3
UL3 1 Meas_Rec 3
U0m 1 Meas_Rec 3
FALSE 1 Control 1
Control 1
Control 1
Control 2
Control 2
Control 3
Control 3
Control 4
Control 4
Control 7
Protection 11
Protection 11
Protection 11
TRUE 1 Control 1
Control 1
Control 2
Control 2
Control 3
Control 4
Control 4
Control 7
GRP_OFF 1 Protection 6
INTZERO 1
INTONE 1
INTALONE 1
REALZERO 1
STRNULL 1
ZEROSMPL 1
Input Variable Information Present in Control Page 1
Name Page Partner Location Partner Page
FALSE 1 Signals 1
DAXCBR_OPEN 1 Control 1
DAXCBR_CLOSE 1 Control 1
FALSE 1 Signals 1
TRUE 1 Signals 1
FALSE 1 Signals 1
TRUE 1 Signals 1
Output Variable Information Present in Control Page 1
Name Page Partner Location Partner Page
CB_OPEN_CMD 1 Protection 11
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
25 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
Name Page Partner Location Partner Page
CB_CLOSE_CMD 1 Protection 11
DAXCBR_OPEN 1 Control 1
DAXCBR_CLOSE 1 Control 1
Input Variable Information Present in Control Page 2
Name Page Partner Location Partner Page
FALSE 2 Signals 1
FALSE 2 Signals 1
DAXDC1_OPEN 2 Control 2
DAXDC1_CLOSE 2 Control 2
TRUE 2 Signals 1
TRUE 2 Signals 1
Output Variable Information Present in Control Page 2
Name Page Partner Location Partner Page
DAXDC1_OPEN 2 Control 2
DAXDC1_CLOSE 2 Control 2
Input Variable Information Present in Control Page 3
Name Page Partner Location Partner Page
FALSE 3 Signals 1
FALSE 3 Signals 1
DAXDC2_OPEN 3 Control 3
DAXDC2_CLOSE 3 Control 3
TRUE 3 Signals 1
Output Variable Information Present in Control Page 3
Name Page Partner Location Partner Page
DAXDC2_OPEN 3 Control 3
DAXDC2_CLOSE 3 Control 3
Input Variable Information Present in Control Page 4
Name Page Partner Location Partner Page
FALSE 4 Signals 1
FALSE 4 Signals 1
DAXES_OPEN 4 Control 4
DAXES_CLOSE 4 Control 4
TRUE 4 Signals 1
TRUE 4 Signals 1
Output Variable Information Present in Control Page 4
Name Page Partner Location Partner Page
DAXES_OPEN 4 Control 4
DAXES_CLOSE 4 Control 4
ES[3]_EXE_OP 4
ES[3]_EXE_CL 4
Output Variable Information Present in Control Page 5
Name Page Partner Location Partner Page
CB_CLOSE 5 Control 6
Protection 1
Protection 1
Protection 1
CB_OPEN 5 Control 6
Control 6
Control 6
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
26 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
Name Page Partner Location Partner Page
Control 7
Protection 1
TRUCK_CLOSE 5 Control 6
TRUCK_OPEN 5
DC1_CLOSE 5 Control 6
Control 6
Control 6
DC1_OPEN 5 Control 6
Control 6
Control 6
ES_OPEN 5 Control 6
Control 6
Control 6
ES_CLOSE 5 Control 6
Input Variable Information Present in Control Page 6
Name Page Partner Location Partner Page
CB_OPEN 6 Control 5
CB_OPEN 6 Control 5
DC1_OPEN 6 Control 5
ES_OPEN 6 Control 5
CB_OPEN 6 Control 5
DC1_CLOSE 6 Control 5
ES_OPEN 6 Control 5
DC1_OPEN 6 Control 5
CB_CLOSE 6 Control 5
DC1_CLOSE 6 Control 5
TRUCK_CLOSE 6 Control 5
ES_CLOSE 6 Control 5
DC1_OPEN 6 Control 5
DC1_CLOSE 6 Control 5
CB_CLOSE_EN_A 6 Control 6
CB_CLOSE_EN_A 6 Control 6
ES_OPEN 6 Control 5
PRES_LOCKOUT 6 Control 7
SPR_CHR_ALM 6 Control 7
COM_OC_OPERATE 6 Protection 8
Output Variable Information Present in Control Page 6
Name Page Partner Location Partner Page
CB_CLOSE_EN_A 6 Control 6
Control 6
CB_OPEN_EN 6
ES_EN 6
DC2_EN 6
DC1_EN 6
CB_CLOSE_EN 6
Input Variable Information Present in Control Page 7
Name Page Partner Location Partner Page
BLK_BY_TH 7 Protection 1
CB_OPEN 7 Control 5
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
27 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
Name Page Partner Location Partner Page
I3P 7 Signals 1
SPR_CHR_ST 7 Control 7
TRV_T_CL_ALM 7 Control 7
TRV_T_OP_ALM 7 Control 7
CB_LIFE_ALM 7 Control 7
CBOPR_ALM 7 Control 7
IPOW_ALM 7 Control 7
MON_ALM 7 Control 7
PRES_LOCKOUT 7 Control 7
SPR_CHR_ALM 7 Control 7
OP_DOC_H 7 Protection 2
OP_OC_H1 7 Protection 3
OP_OC_H2 7 Protection 3
OP_OC_I 7 Protection 3
OP_OC_L 7 Protection 3
OP_DOC_L1 7 Protection 2
OP_DOC_L2 7 Protection 2
OP_EF_H 7 Protection 7
OP_DEF_H 7 Protection 4
OP_DEF_L1 7 Protection 4
OP_DEF_L2 7 Protection 4
OP_NSOC_1 7 Protection 5
OP_NSOC_2 7 Protection 5
OP_INTREF 7 Protection 7
OP_PHDIS 7 Protection 5
PRES_LOCKOUT 7 Control 7
OP_EF_L 7 Protection 7
COM_OP_DIST 7 Protection 6
TRUE 7 Signals 1
FALSE 7 Signals 1
Output Variable Information Present in Control Page 7
Name Page Partner Location Partner Page
TRV_T_OP_ALM 7 Control 7
TRV_T_CL_ALM 7 Control 7
SPR_CHR_ALM 7 Control 6
Control 7
Meas_Rec 3
CBOPR_ALM 7 Control 7
IPOW_ALM 7 Control 7
CB_LIFE_ALM 7 Control 7
Meas_Rec 3
MON_ALM 7 Control 7
PRES_LOCKOUT 7 Control 6
Control 7
Control 7
SPR_CHR_ST 7 Control 7
CB_MONITOR_ALARM 7 Protection 8
Protection 10
Meas_Rec 2
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
28 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
Name Page Partner Location Partner Page
RECLOSE_AR 7 Protection 11
Meas_Rec 3
AR_IN_PRO 7 Meas_Rec 2
UNSUCC_AR 7 Meas_Rec 3
AR_READY 7 Meas_Rec 2
LOCKED_BY_AR 7 Meas_Rec 2
Meas_Rec 3
AR_ZONES 7 Protection 6
Input Variable Information Present in Protection Page 1
Name Page Partner Location Partner Page
I3P_80SPC 1 Signals 1
TC_ALARM_1 1 Protection 1
TC_ALARM_2 1 Protection 1
TC_ALARM_3 1 Protection 1
I3P 1 Signals 1
I3P 1 Signals 1
I3P 1 Signals 1
U3P 1 Signals 1
I3P 1 Signals 1
CB_CLOSE 1 Control 5
CB_CLOSE 1 Control 5
COM_OC_OPERATE 1 Protection 8
CB_OPEN 1 Control 5
COM_OC_OPERATE 1 Protection 8
CB_CLOSE 1 Control 5
Output Variable Information Present in Protection Page 1
Name Page Partner Location Partner Page
BLK_BY_INRUSH 1 Protection 2
Protection 2
Protection 2
Protection 3
Protection 3
Protection 3
Protection 3
Meas_Rec 3
TC_ALARM_1 1 Protection 1
TC_ALARM_2 1 Protection 1
TC_ALARM_3 1 Protection 1
TC_ALARM 1 Protection 8
Meas_Rec 2
Meas_Rec 3
CC_FAILURE 1 Protection 8
Meas_Rec 2
Meas_Rec 3
OP_TH 1 Protection 8
Meas_Rec 2
Meas_Rec 3
ALARM_TH 1 Meas_Rec 2
BLK_BY_TH 1 Control 7
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
29 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
Name Page Partner Location Partner Page
FUSE_FAILURE 1 Protection 6
Protection 8
Meas_Rec 2
Meas_Rec 3
CBFP_RETRIP 1 Meas_Rec 2
CBFP_BUTRIP 1 Meas_Rec 2
Input Variable Information Present in Protection Page 2
Name Page Partner Location Partner Page
I3P 2 Signals 1
U3P 2 Signals 1
I3P 2 Signals 1
U3P 2 Signals 1
I3P 2 Signals 1
U3P 2 Signals 1
BLK_BY_INRUSH 2 Protection 1
BLK_BY_INRUSH 2 Protection 1
BLK_BY_INRUSH 2 Protection 1
OP_DOC_H 2 Protection 2
OP_DOC_L1 2 Protection 2
OP_DOC_L2 2 Protection 2
ST_DOC_H 2 Protection 2
ST_DOC_L1 2 Protection 2
ST_DOC_L2 2 Protection 2
Output Variable Information Present in Protection Page 2
Name Page Partner Location Partner Page
OP_DOC_L1 2 Control 7
Protection 2
Meas_Rec 3
ST_DOC_L1 2 Protection 2
Meas_Rec 3
OP_DOC_L2 2 Control 7
Protection 2
Meas_Rec 3
ST_DOC_L2 2 Protection 2
Meas_Rec 3
OP_DOC_H 2 Control 7
Protection 2
Meas_Rec 3
ST_DOC_H 2 Protection 2
Meas_Rec 3
COM_OP_DOC 2 Protection 8
Meas_Rec 2
COM_ST_DOC 2 Protection 8
Protection 8
Meas_Rec 2
Input Variable Information Present in Protection Page 3
Name Page Partner Location Partner Page
I3P 3 Signals 1
I3P_80SPC 3 Signals 1
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
30 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
Name Page Partner Location Partner Page
I3P_80SPC 3 Signals 1
I3P_80SPC 3 Signals 1
OP_OC_H1 3 Protection 3
OP_OC_H2 3 Protection 3
OP_OC_I 3 Protection 3
OP_OC_L 3 Protection 3
ST_OC_H1 3 Protection 3
ST_OC_H2 3 Protection 3
ST_OC_I 3 Protection 3
ST_OC_L 3 Protection 3
BLK_BY_INRUSH 3 Protection 1
BLK_BY_INRUSH 3 Protection 1
BLK_BY_INRUSH 3 Protection 1
BLK_BY_INRUSH 3 Protection 1
Output Variable Information Present in Protection Page 3
Name Page Partner Location Partner Page
OP_OC_H1 3 Control 7
Protection 3
Meas_Rec 3
ST_OC_H1 3 Protection 3
Meas_Rec 3
OP_OC_H2 3 Control 7
Protection 3
Meas_Rec 3
ST_OC_H2 3 Protection 3
Meas_Rec 3
OP_OC_I 3 Control 7
Protection 3
Meas_Rec 3
ST_OC_I 3 Protection 3
Meas_Rec 3
OP_OC_L 3 Control 7
Protection 3
Meas_Rec 3
ST_OC_L 3 Protection 3
Meas_Rec 3
COM_OP_OC 3 Protection 8
Meas_Rec 2
COM_ST_OC 3 Protection 8
Protection 8
Meas_Rec 2
Input Variable Information Present in Protection Page 4
Name Page Partner Location Partner Page
I3P 4 Signals 1
I3P 4 Signals 1
I3P 4 Signals 1
OP_DEF_H 4 Protection 4
OP_DEF_L1 4 Protection 4
OP_DEF_L2 4 Protection 4
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
31 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
Name Page Partner Location Partner Page
ST_DEF_H 4 Protection 4
ST_DEF_L1 4 Protection 4
ST_DEF_L2 4 Protection 4
BLK_BY_INTREF 4 Protection 7
BLK_BY_INTREF 4 Protection 7
BLK_BY_INTREF 4 Protection 7
U3P 4 Signals 1
U3P 4 Signals 1
U3P 4 Signals 1
Output Variable Information Present in Protection Page 4
Name Page Partner Location Partner Page
OP_DEF_H 4 Control 7
Protection 4
Protection 8
Meas_Rec 3
ST_DEF_H 4 Protection 4
Meas_Rec 3
OP_DEF_L1 4 Control 7
Protection 4
Protection 8
Meas_Rec 3
ST_DEF_L1 4 Protection 4
Meas_Rec 3
OP_DEF_L2 4 Control 7
Protection 4
Protection 8
Meas_Rec 3
ST_DEF_L2 4 Protection 4
Meas_Rec 3
COM_OP_DEF 4 Meas_Rec 2
COM_ST_DEF 4 Protection 8
Meas_Rec 2
Input Variable Information Present in Protection Page 5
Name Page Partner Location Partner Page
I3P 5 Signals 1
I3P 5 Signals 1
I3P 5 Signals 1
OP_NSOC_1 5 Protection 5
OP_NSOC_2 5 Protection 5
ST_NSOC_1 5 Protection 5
ST_NSOC_2 5 Protection 5
Output Variable Information Present in Protection Page 5
Name Page Partner Location Partner Page
OP_NSOC_1 5 Control 7
Protection 5
Protection 8
Meas_Rec 3
ST_NSOC_1 5 Protection 5
Meas_Rec 3
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
32 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
Name Page Partner Location Partner Page
OP_NSOC_2 5 Control 7
Protection 5
Protection 8
Meas_Rec 3
ST_NSOC_2 5 Protection 5
Meas_Rec 3
OP_PHDIS 5 Control 7
Protection 8
Meas_Rec 2
Meas_Rec 3
ST_PHDIS 5 Protection 8
Meas_Rec 2
Meas_Rec 3
COM_OP_NSOC 5 Meas_Rec 2
COM_ST_NSOC 5 Protection 8
Meas_Rec 2
Input Variable Information Present in Protection Page 6
Name Page Partner Location Partner Page
I3P 6 Signals 1
GRP_OFF 6 Signals 1
U3P 6 Signals 1
FUSE_FAILURE 6 Protection 1
OP_Z1 6 Protection 6
OP_Z1 6 Protection 6
OP_Z2 6 Protection 6
OP_Z3 6 Protection 6
AR_ZONES 6 Control 7
OP_Z4 6 Protection 6
OP_Z5 6 Protection 6
ST_Z1 6 Protection 6
OP_Z1 6 Protection 6
OP_Z2 6 Protection 6
OP_Z3 6 Protection 6
OP_Z4 6 Protection 6
OP_Z5 6 Protection 6
ST_Z2 6 Protection 6
ST_Z3 6 Protection 6
ST_Z4 6 Protection 6
ST_Z5 6 Protection 6
I3P 6 Signals 1
U3P 6 Signals 1
COM_OP_DIST 6 Protection 6
COM_OP_EF 6 Protection 7
TRIGG_FLOC 6 Protection 6
Output Variable Information Present in Protection Page 6
Name Page Partner Location Partner Page
OP_GFC 6
ST_GFC 6
OP_Z1 6 Protection 6
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
33 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
Name Page Partner Location Partner Page
Protection 6
Protection 6
Meas_Rec 3
ST_Z1 6 Protection 6
Meas_Rec 3
OP_Z2 6 Protection 6
Protection 6
Meas_Rec 3
ST_Z2 6 Protection 6
Meas_Rec 3
OP_Z3 6 Protection 6
Protection 6
Meas_Rec 3
ST_Z3 6 Protection 6
Meas_Rec 3
OP_Z4 6 Protection 6
Protection 6
Meas_Rec 3
ST_Z4 6 Protection 6
Meas_Rec 3
OP_Z5 6 Protection 6
Protection 6
Meas_Rec 3
ST_Z5 6 Protection 6
Meas_Rec 3
FLTLOOP_RFST 6 Meas_Rec 3
FLTLOOP_XFST 6 Meas_Rec 3
FLTLOOP_RSND 6 Meas_Rec 3
FLTLOOP_XSND 6 Meas_Rec 3
FLTLOOP_RPP 6 Meas_Rec 3
FLTLOOP_XPP 6 Meas_Rec 3
OP_EARTH_Z1 6
COM_OP_DIST 6 Control 7
Protection 6
DIRECTION 6
DIR_LOOP_R 6 Meas_Rec 3
DIR_LOOP_X 6 Meas_Rec 3
ALARM 6
EF_VALIDITY 6
FAULT_LOOP 6
TRIGG_OUT 6
FLT_DISTANCE 6 Meas_Rec 3
IFLT_PER_ILD 6
RF 6 Meas_Rec 3
XFLOOP 6
RFLOOP 6
S_CALC 6
XC0F_CALC 6
TRIGG_FLOC 6 Protection 6
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
34 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
Input Variable Information Present in Protection Page 7
Name Page Partner Location Partner Page
U3P_80SPC 7 Signals 1
I3P_80SPC 7 Signals 1
I3P_80SPC 7 Signals 1
OP_EF_H 7 Protection 7
OP_INTREF 7 Protection 7
ST_EF_H 7 Protection 7
ST_INTREF 7 Protection 7
I3P 7 Signals 1
OP_EF_L 7 Protection 7
I3P_80SPC 7 Signals 1
OP_EF_I 7 Protection 7
ST_EF_I 7 Protection 7
ST_EF_L 7 Protection 7
Output Variable Information Present in Protection Page 7
Name Page Partner Location Partner Page
OP_EF_H 7 Control 7
Protection 7
Meas_Rec 3
ST_EF_H 7 Protection 7
Meas_Rec 3
OP_INTREF 7 Control 7
Protection 7
Meas_Rec 3
ST_INTREF 7 Protection 7
Meas_Rec 3
BLK_BY_INTREF 7 Protection 4
Protection 4
Protection 4
COM_OP_EF 7 Protection 6
Protection 8
Meas_Rec 2
COM_ST_EF 7 Protection 8
Meas_Rec 2
OP_EF_L 7 Control 7
Protection 7
Meas_Rec 3
ST_EF_L 7 Protection 7
Meas_Rec 3
OP_EF_I 7 Protection 7
Meas_Rec 3
ST_EF_I 7 Protection 7
Meas_Rec 3
Input Variable Information Present in Protection Page 8
Name Page Partner Location Partner Page
COM_OP_DOC 8 Protection 2
COM_OP_OC 8 Protection 3
COM_ST_DEF 8 Protection 4
COM_ST_DOC 8 Protection 2
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
35 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
Name Page Partner Location Partner Page
COM_ST_EF 8 Protection 7
COM_ST_NSOC 8 Protection 5
COM_ST_OC 8 Protection 3
ST_PHDIS 8 Protection 5
TC_ALARM 8 Protection 1
CC_FAILURE 8 Protection 1
FUSE_FAILURE 8 Protection 1
CB_MONITOR_ALARM 8 Control 7
OC/DOC_OP_ALARM 8 Protection 8
EF/DEF_OP_ALARM 8 Protection 8
OP_PHDIS 8 Protection 5
OP_TH 8 Protection 1
OP_NSOC_1 8 Protection 5
OP_NSOC_2 8 Protection 5
COM_ST_DOC 8 Protection 2
COM_ST_OC 8 Protection 3
OP_DEF_H 8 Protection 4
OP_DEF_L1 8 Protection 4
OP_DEF_L2 8 Protection 4
COM_OP_EF 8 Protection 7
Output Variable Information Present in Protection Page 8
Name Page Partner Location Partner Page
OC/DOC_OP_ALARM 8 Protection 8
Protection 10
EF/DEF_OP_ALARM 8 Protection 8
Protection 10
COM_START 8 Protection 10
UPSTM_OC/DOC_BLK 8 Protection 10
COM_OC_OPERATE 8 Control 6
Protection 1
Protection 1
Protection 10
Protection 11
SUPERVISION_ALM 8 Protection 10
Input Variable Information Present in Protection Page 9
Name Page Partner Location Partner Page
OP_OV 9 Protection 9
OP_UV 9 Protection 9
U3P 9 Signals 1
U3P 9 Signals 1
U3P 9 Signals 1
U3P 9 Signals 1
U3P 9 Signals 1
OP_ROV 9 Protection 9
BLK_UF 9 Meas_Rec 1
OP_O_FREC 9 Protection 9
OP_U_FREC 9 Protection 9

Project Responsible department Technical reference Document kind Doc. designation


PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
36 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
Output Variable Information Present in Protection Page 9
Name Page Partner Location Partner Page
OP_OV 9 Protection 9
Meas_Rec 2
Meas_Rec 3
OP_UV 9 Protection 9
Meas_Rec 2
Meas_Rec 3
ST_OV 9 Meas_Rec 2
Meas_Rec 3
ST_UV 9 Meas_Rec 2
Meas_Rec 3
COM_OP_VP 9
OP_O_FREC 9 Protection 9
Meas_Rec 2
Meas_Rec 3
ST_O_FREC 9 Meas_Rec 2
Meas_Rec 3
OP_U_FREC 9 Protection 9
Meas_Rec 2
Meas_Rec 3
ST_U_FREC 9 Meas_Rec 2
Meas_Rec 3
OP_ROV 9 Protection 9
Meas_Rec 2
Meas_Rec 3
ST_ROV 9 Meas_Rec 2
Meas_Rec 3
OP_FREC 9
Input Variable Information Present in Protection Page 10
Name Page Partner Location Partner Page
COM_OC_OPERATE 10 Protection 8
CB_MONITOR_ALARM 10 Control 7
SUPERVISION_ALM 10 Protection 8
OC/DOC_OP_ALARM 10 Protection 8
EF/DEF_OP_ALARM 10 Protection 8
COM_START 10 Protection 8
UPSTM_OC/DOC_BLK 10 Protection 8
Input Variable Information Present in Protection Page 11
Name Page Partner Location Partner Page
COM_OC_OPERATE 11 Protection 8
CB_OPEN_CMD 11 Control 1
CB_CLOSE_CMD 11 Control 1
RECLOSE_AR 11 Control 7
FALSE 11 Signals 1
FALSE 11 Signals 1
FALSE 11 Signals 1
Input Variable Information Present in Meas_Rec Page 1
Name Page Partner Location Partner Page
I3P 1 Signals 1
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
37 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
Name Page Partner Location Partner Page
U3P 1 Signals 1
I3P 1 Signals 1
I3P 1 Signals 1
I3P 1 Signals 1
U3P 1 Signals 1
U3P 1 Signals 1
U_RANGE_A 1 Meas_Rec 1
U_RANGE_B 1 Meas_Rec 1
U_RANGE_C 1 Meas_Rec 1
U3P 1 Signals 1
U3P 1 Signals 1
Output Variable Information Present in Meas_Rec Page 1
Name Page Partner Location Partner Page
I1_INST 1 Meas_Rec 3
I2_INST 1 Meas_Rec 3
S_INST 1 Meas_Rec 3
RESCMMXU_I0 1
RESVMMXU_U0 1
P_INST 1 Meas_Rec 3
Q_INST 1 Meas_Rec 3
PF_DB 1
ILAG 1
ILEAD 1
F_DB 1
F_RANGE 1
U_RANGE_A 1 Meas_Rec 1
U_RANGE_B 1 Meas_Rec 1
U_RANGE_C 1 Meas_Rec 1
BLK_UF 1 Protection 9
Input Variable Information Present in Meas_Rec Page 2
Name Page Partner Location Partner Page
COM_OP_DOC 2 Protection 2
COM_ST_DOC 2 Protection 2
COM_OP_OC 2 Protection 3
COM_ST_OC 2 Protection 3
COM_OP_NSOC 2 Protection 5
COM_ST_NSOC 2 Protection 5
COM_ST_DEF 2 Protection 4
COM_OP_DEF 2 Protection 4
OP_PHDIS 2 Protection 5
ST_PHDIS 2 Protection 5
OP_TH 2 Protection 1
ALARM_TH 2 Protection 1
LOCKED_BY_AR 2 Control 7
AR_IN_PRO 2 Control 7
AR_READY 2 Control 7
TC_ALARM 2 Protection 1
CBFP_BUTRIP 2 Protection 1
CBFP_RETRIP 2 Protection 1
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
38 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
Name Page Partner Location Partner Page
CB_MONITOR_ALARM 2 Control 7
FUSE_FAILURE 2 Protection 1
CC_FAILURE 2 Protection 1
COM_OP_EF 2 Protection 7
COM_ST_EF 2 Protection 7
OP_OV 2 Protection 9
ST_OV 2 Protection 9
OP_UV 2 Protection 9
ST_UV 2 Protection 9
OP_O_FREC 2 Protection 9
ST_O_FREC 2 Protection 9
OP_U_FREC 2 Protection 9
ST_U_FREC 2 Protection 9
OP_ROV 2 Protection 9
ST_ROV 2 Protection 9
Input Variable Information Present in Meas_Rec Page 3
Name Page Partner Location Partner Page
IL1 3 Signals 1
IL2 3 Signals 1
IL3 3 Signals 1
I0 3 Signals 1
UL1 3 Signals 1
UL2 3 Signals 1
UL3 3 Signals 1
U0m 3 Signals 1
BLK_BY_INRUSH 3 Protection 1
ST_DOC_H 3 Protection 2
OP_DOC_H 3 Protection 2
ST_DOC_L1 3 Protection 2
OP_DOC_L1 3 Protection 2
ST_DOC_L2 3 Protection 2
OP_DOC_L2 3 Protection 2
ST_OC_H1 3 Protection 3
OP_OC_H1 3 Protection 3
ST_OC_H2 3 Protection 3
OP_OC_H2 3 Protection 3
ST_OC_I 3 Protection 3
OP_OC_I 3 Protection 3
ST_OC_L 3 Protection 3
OP_OC_L 3 Protection 3
OP_TH 3 Protection 1
ST_NSOC_1 3 Protection 5
OP_NSOC_1 3 Protection 5
ST_NSOC_2 3 Protection 5
OP_NSOC_2 3 Protection 5
ST_DEF_H 3 Protection 4
OP_DEF_H 3 Protection 4
ST_DEF_L1 3 Protection 4
OP_DEF_L1 3 Protection 4
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
39 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
Name Page Partner Location Partner Page
ST_DEF_L2 3 Protection 4
OP_DEF_L2 3 Protection 4
ST_PHDIS 3 Protection 5
OP_PHDIS 3 Protection 5
UNSUCC_AR 3 Control 7
LOCKED_BY_AR 3 Control 7
RECLOSE_AR 3 Control 7
TC_ALARM 3 Protection 1
CC_FAILURE 3 Protection 1
FUSE_FAILURE 3 Protection 1
SPR_CHR_ALM 3 Control 7
CB_LIFE_ALM 3 Control 7
OP_ROV 3 Protection 9
ST_ROV 3 Protection 9
ST_EF_L 3 Protection 7
OP_EF_L 3 Protection 7
ST_INTREF 3 Protection 7
OP_INTREF 3 Protection 7
ST_Z1 3 Protection 6
ST_Z2 3 Protection 6
ST_Z3 3 Protection 6
ST_Z4 3 Protection 6
ST_Z5 3 Protection 6
OP_Z1 3 Protection 6
OP_Z2 3 Protection 6
OP_Z3 3 Protection 6
OP_Z4 3 Protection 6
OP_Z5 3 Protection 6
OP_UV 3 Protection 9
OP_OV 3 Protection 9
ST_UV 3 Protection 9
ST_OV 3 Protection 9
I1_INST 3 Meas_Rec 1
I2_INST 3 Meas_Rec 1
P_INST 3 Meas_Rec 1
Q_INST 3 Meas_Rec 1
S_INST 3 Meas_Rec 1
DIR_LOOP_R 3 Protection 6
DIR_LOOP_X 3 Protection 6
FLTLOOP_RFST 3 Protection 6
FLTLOOP_RPP 3 Protection 6
FLTLOOP_RSND 3 Protection 6
FLTLOOP_XFST 3 Protection 6
FLTLOOP_XPP 3 Protection 6
FLTLOOP_XSND 3 Protection 6
FLT_DISTANCE 3 Protection 6
RF 3 Protection 6
OP_EF_I 3 Protection 7
ST_EF_I 3 Protection 7
Project Responsible department Technical reference Document kind Doc. designation
PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
40 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en
Name Page Partner Location Partner Page
OP_EF_H 3 Protection 7
ST_EF_H 3 Protection 7
OP_U_FREC 3 Protection 9
OP_O_FREC 3 Protection 9
ST_O_FREC 3 Protection 9
ST_U_FREC 3 Protection 9

Project Responsible department Technical reference Document kind Doc. designation


PENINSULA ABB Ltd. Graphical Application Configuration PRI12
Replacing Created by Title Document id.
REF630 PRI11 El Paseo
PENINSULA.Subestacin Carolina Approved by Rev. Rel. date Lang.
41 / 41
Rev. Modification Rel. date Created by Based on 0 04/25/2017 en

Vous aimerez peut-être aussi