Vous êtes sur la page 1sur 7

PRACTICAL

GUIDE
The following article was published in ASHRAE Journal, April 1999. Copyright 1999 American Society of Heating, Refrigerating and Air-
Conditioning Engineers, Inc. It is presented for educational purposes only. This article may not be copied and/or distributed electronically or in paper
form without permission of ASHRAE.

AIR DISTRIBUTION
FOR LARGE SPACES
By Dan Int-Hout
Member ASHRAE
and
Leon Kloostra
Member ASHRAE

A
ir distribution for large spaces has both good A downward jet of cold air will travel further than isothermal air.
A downward jet of hot air will not travel as far as isothermal air.
and bad news. The good news is that because
Figure 1 shows this effect. This chart can be used several ways:
the spaces are so large, air distribution is
1. If the outlet discharge velocity and flow rate are known,
spread out over a large area. Localized problems are the chart can be used to estimate the downward vertical
therefore unlikely. The bad news is that because the projection of a jet to 50 fpm (0.25 m/s) terminal velocity
(T 50), for various temperature differences between the
spaces are large, diffusers cannot be located everywhere.
discharge jet and the ambient or room temperature. For
example, for an isothermal 1,000 cfm (470 L/s) jet with a
Most of the selection process for large spaces involves experi- 1,000 fpm (5 m/s) discharge velocity, the distance to 50
ence and jet mapping. The standard commercial office axioms fpm (0.25 m/s) will be about 28 ft (9 m).
based on ADPI and diffuser throw vs. spacing are not appli-
2. Because the buoyancy effect is a function only of tempera-
cable. Rather, jet projections are analyzed and diffusers selected
ture, the chart can also be used to predict upward jet projec-
accordingly.
tion by switching the T values. For a given air quantity and
discharge velocity, the upward projection of a warm air jet at
Basic Principles
20F (11C) temperature difference is the same as the down-
There are a couple of basic principles in analyzing airflows
ward projection of a cold air jet at a 20F (11C) tempera-
in any space. The first basic rule is Newtons gravitational ob-
ture difference.
servations: Hot air rises and cold air falls. The question is, of
course, how much? The second rule is that the air follows basic 3. If isothermal throw is known (from standard grille per-
rules of jet theory. Air in a free jet, as opposed to one that is formance charts), the right side of the chart can be used
constrained along a surface, acts pretty much independent of the to estimate the effect of temperature difference on
supply outlet isovel (or air pattern). Once those two principles 50 fpm (0.4 m/s) terminal velocity. Enter the chart at
are understood, predictions of airflow can be made with a high the isothermal throw and move across to the tempera-
degree of confidence. ture difference of interest. For example, if a grille has
an (isothermal) catalog rating of 50 ft (16 m) to a
Vertical Jet Temperature Effects 50 fpm (0.25 m/s) terminal velocity, the jet will travel
Temperature effects are very predictable. Hot air rises and about 72 ft (23m) if it is 20F (11C) cooler than the
cold air falls. Momentum and velocity temper this effect. The ambient air. It will travel only 20 ft (6.5m) if it is 50F
slower the air, the greater the buoyancy effect. Generally speak- (11C) degrees warmer than the surrounding air.
ing, air velocities above 150 fpm (0.76 m/s) are not affected by 4. Figure 1 assumes that the jet aspect ratio (width to depth)
temperature differences. A simple rule of thumb for slower jets is near 1. Long linear slots may produce slightly shorter
is that the throw to a terminal velocity of 75 fpm (0.4 m/s) changes throws than shown in Figure 1. This difference is due to
about 1% /F (2% /C) temperature difference. (Throw is the their increased surface area and subsequent higher entrain-
distance for a jet to reach a stated terminal velocity.) ment ratios.

April 1999 ASHRAE Journal 51


Practical Guide
Horizontal Jets
Horizontal jets are more complex, as
they may be affected by adjacent surfaces
and grille discharge or blade angle in
addition to temperature difference. In
most cases, grilles supply cool air. The
major concern in these situations is the
drop of cold air into the occupied zone
and resulting cold drafts. Following are
several examples, based on experimen-
tal data, for an airfoil blade, sidewall
grille with a discharge temperature 20F
(11C) below ambient. These graphs
show data to a terminal velocity of 50
fpm (0.25 m/s). The shaded area on the
far right of each graph indicates an NC
equal to or greater than 30.
Figure 2 can be used to predict the
drop of the jet, in units of feet, as well
as the throw, of a sidewall grille with a
20 upward deflection located slightly
below a ceiling. Entering with the jet
discharge velocity and the flow rate, a
300 cfm (140 L/s) jet with a 600 fpm
(3 m/s) discharge velocity (0.5 ft 2
[0.05 m 2] free area), the example above
shows a drop of about 3 ft (0.9m) be-
low the grille location and a throw of
27 ft (8.7 m). The adjacent ceiling pro- Figure 1: Vertical jet projection, effect of T. T50 throw distance.
vides some coanda effect, increasing
the throw beyond what would be found with no ceiling, as jacent ceiling keep the drop to 3 ft (0.9 m) or less. The com-
in the next example.
ASHRAE JOURNAL
bination of vertical deflection and spread also increases the
In Figure 3, with the same grille but no adjacent ceiling, the 1791area of theCircle
Tullie NC>30N.E. band, on the right.
jet does not travel nearly as far, only 23 ft (7.4 m), before it Atlanta, If there is no30329-2305
Georgia ceiling nearby, the throw is shortened signifi-
drops to 3 ft (0.9 m) below the grille height. When there is no 404-636-8400
cantly, to less
FAX 404-321-5478
than 15 ft (4.8 m), as shown in Figure 7, where
adjacent ceiling, the jet has more surface area, entrains more air ASHRAE
only spread
Home is employed.
Page In this case, the ceiling is too far away
and loses momentum faster. There is no ceiling for the jet to www.ashrae.org
for the airstream to attach to the ceiling.
cling to, so the jet drops faster. The goal in most designs is to cover all areas without exces-
In Figure 4, the grille is located close to an adjacent ceiling sive drafts. The examples show that both grille adjustment and
and is set with no upward deflection. Our example here has location have a significant effect on the resultant patterns. Throw
Publisher
about the same throw as the first example (27 ft or 8.7 m) but W. canStephen
be extended and drop reduced by locating grilles closer to a
Comstock
drops more than 5 ft (1.6 m) below the grille. This is a result of ceiling. Vertical deflection (aiming the jet upward) can make a
the natural vertical spread of the jet. Note that the actual drop EDITORIAL
grille several feet from the ceiling act like one that is closer to the
below the ceiling is similar to Figure 2 (the grille is closer to the Editor
ceiling. Horizontal deflection (spread) reduces throw without
Fred Turner
ceiling in this example). increasing drop.
fturner@ashrae.org
If there is no ceiling and the grille has no deflection, then the Managing
Table 1 summarizes
Editor the examples in Figures 2 through 7.
drop is more pronounced, 7 ft (2.3 m), and the throw is slightly Sarah Foster
Distributing from Overhead
less (25 ft or 8.1 m). This scenario also would approximate an sfoster@ashrae.org
Assistant Editor
open-ended duct with no grille (see Figure 5). Location, Location, Location. Just as with real estate,
Tanja Mushenko
If a grille has vertical bars, some spread can be applied to de- supply outlet location can make all the difference. Diffusers
tmushenko@ashrae.org
crease the throw. In Figure 6, the same grille is shown with the in open spaces
Washington can provide horizontal, vertical or a mix of
Bureau
adjacent ceiling and the vertical blades adjusted to give about 45 of patterns. There
J.E. Cox, P.E., Ph.D.are some typical diffuser characteristics that
Charles R. Mir
spread. The horizontal blades are set to direct the jet 20 upward. need to be understood.
washofc@ashrae.org
As seen in Figure 6, the throw is shorter, less than 20 ft Senior Ceiling
Editor
diffusers have different airflow patterns from
(6.5 m), and the upward projection coupled with the ad- sidewall William R.outlets.
Coker Except for linear diffusers, ceiling diffusers

52 ASHRAE Journal April 1999


Museums &
Renovation

Figure 2: Throw and drop for outlet 2 to 4 ft (0.6 to 1.3 m) below Figure 3: Throw and drop for outlet without ceiling. 20 vertical
ceiling. 20 upward vertical deflection, 0 spread. deflection, 0 spread.

Figure 4: Throw and drop for outlet 1 ft below ceiling. 0 deflec- Figure 5: Throw and drop for outlet with no ceiling. 0 deflection,
tion, 0 spread. 0 spread.

Figure 6: Throw and drop for outlet 1.5 ft below ceiling. 20 Figure 7: Throw and drop for outlet 2 to 4 ft below ceiling.
vertical, 45 spread. 0 vertical deflection, 45 spread.

typically exhibit flow in one of two patterns: circular or cross reinduced into the primary air. This action reduces dumping and
flow. Figure 8 shows the main differences between circular keeps the cool air near the ceiling, resulting in uniform tem-
and cross flow patterns. peratures throughout the space. On the other hand, cross flow
Comparing the plan views of the circular and cross flow ceil- jet projection continues after the low terminal velocity just like
ing diffusers, the circular pattern has a much shorter throw than the airflow from side wall registers at 0 deflection. During cool-
the cross flow for a given flow rate. With the circular pattern, the ing, the circular recirculating airflow results in less drop than
discharge velocity is equal in all directions, while the cross flow with cross flow jets.
has four higher velocity jets. Throw is a function of velocity. Cross flow patterns with longer throw and individual side
The elevation views indicate that the circular supply jet at the jets are similar to side wall jets. Near the end of the throw,
end of its trajectory has a tendency to return to the diffuser being during cooling, cross flow patterns continue in the direction

April 1999 ASHRAE Journal 53


Practical Guide
away from the diffuser. The drop can
also depend only on the airflow from
each diffuser side. Both patterns are
usually centered in equal spaces in large
open areas.
The wide spreading 45 deflection
from the side wall grilles is similar to
half the circular pattern. The 0 deflec-
tion grille is a pattern that all single non-
spreading patterns follow. The horizon-
tal projection from diffusers and grilles
has been used extensively in commer-
cial applications. Perimeter heating may
need special treatment over the conven-
tional horizontal air discharge at the
ceiling level.
Linear diffusers have a tendency to fold
back like the circular pattern. This reac-
tion results in less drop than expected
during cooling from the linear diffusers as
the airflow is reduced.
During cooling, the air will often
drop to the floor. A stratification zone
can be formed near the ceiling, which
may result in non-uniform temperatures
below the stratification layer. The size
of the stratification zone will vary, de-
pending on the primary air and the natu-
ral heat sources in the space. With a con-
stant heat source, a VAV system that
reduces flow will allow a larger strati-
fication zone to form. This type of distri- Figure 8: Specific airflow characteristics at high and low airflow rates.
bution allows high level stratification
even when air must be introduced from the ceiling. Return forms above the diffuser. The higher pressure in the room to
intakes can be located between supply sources. push the air up in a manner similar to the effect is often called
Applications of this type of cooling can be used to maintain the coanda effect. (True coanda effect relies on attraction
constant temperatures around machinery by projection to the to a surface.) Some of these diffusers can adjust the air pat-
floor near the machines with return over the machines. For ex- tern so that air can come down in a variety of vertical pat-
ample, a high-speed printing press may be handled this way. terns.
Projection may be obtained at low jet velocities with the ma- In some applications, it may be advantageous to locate a cir-
chines located in a near equal temperature. Projecting more or cular pattern diffuser upside down on top of an exposed duct. If
less air to the floor level, providing more air to floor if the main near a ceiling, entrainment may be achieved. With no ceiling
heat source is at the floor level, can control heat loss over the nearby, the diffuser will tend to dump without the adverse effects
machines. of dumping.
During heating, the warm supply air demonstrates less pro- Cross flow pattern diffusers set for a horizontal pattern
jection, spreading out, rising toward the ceiling. The floor level cannot cause airflow to go upward because the air pressure
becomes cooler and a stratification layer and zone can form at between the jets is equal to the air pressure in the room. There-
some level above the floor. Heat sources near the floor or supply fore, no low pressure is developed above the diffusers.
air projected all the way to the floor help push the stratification On the other hand, a cross flow pattern diffuser generally
layer interface closer to the floor. Return intakes located at the produces a better intermediate vertical projection than circu-
floor in stratification zones will help. lar pattern diffusers. With properly designed and installed
Some diffusers (check with the manufacturer) can provide diffusers, the velocities can be spread out almost uniformly
a good horizontal circular pattern when located below the from the center to the outside edges of these jets. The result
ceiling. In these designs, the jet projects upward toward the is a good spread with a drop proportional to the distance
ceiling. This action is caused by a low-pressure region that from the diffuser to the ceiling.

54 ASHRAE Journal April 1999


Museums &
Renovation

Figure 9: Circular ceiling pattern diffuser. Figure 10: Cross-flow pattern diffuser.

Stratifying a High Space Spreading horizontal projection at floor level permits consid-
As a general rule, one should avoid conditioning spaces where erable stratification at high levels during cooling while maintain-
there are no occupants, so stratification is often a useful strategy ing uniform temperatures in the occupied zone. Although high
in large spaces. To stratify a space, the diffusers must be located velocities in the occupied zone may preclude use of this type of
so the diffuser jets do not break up the desired stratification layer. distribution for comfort cooling, application to situations with
This is often a problem in very large spaces, such as atria, where high internal loads or where occupant comfort is not of primary
the required ducts are preferred not to be seen. Sidewall grilles or concern could be considered.
slots are often employed, at around 15 ft (4.5 m) above the floor, Figure 12 matches the actual definition given for displace-
projecting over the occupied areas. Careful consideration of the ment ventilation. Defined as a low velocity, low temperature dif-
previous grille jet parameters must be employed to avoid drafts in ferential air distribution across the floor level, displacement ven-
the occupied space. Heating is seldom a practical application of tilation utilizes natural convection currents within the space to
this technique, because the warm air tends to rise and may not cause air to rise and form a neutral zone above a stratification
penetrate down to the occupied level. On the other hand, cold air level. The stratification level usually occurs at a level where the
will usually make it to the floor, regardless of where it is supplied. room load and air loading match.
Figure 11 shows heating and cooling from a spreading hori- Displacement ventilation has a limited ability to handle high
zontal projection at floor level. This performance compares to cooling or heating loads. The range of supply air temperatures
previous outlet types and locations with heating and cooling loads. and discharge velocities are limited to avoid discomfort, as the
Today a displacement system will use larger air quantities at low jet is located in the occupied zone. European office designs of-
temperature differentials and low discharge velocities. These ten use chilled ceilings or heated floors to overcome this limita-
applications can be used under seats in theaters, around walls to tion. Chilled ceilings, at least, are seldom an option in large
form a ring of air around a space with people, or internal loads open spaces, because of the distance from the occupant and tem-
forming the rising plume up to the ceiling returns. It should be perature limits to avoid condensation.
remembered that temperatures and velocities would be relatively
low and uniform in occupied zones. Return Air Locations
This distribution system has been used extensively in In most cases, the location of a return in offices is of little
Europe and is being promoted on the basis of the reduced concern. In large spaces, however, returns can assist in control-
energy consumption realized by the availability of economizer ling stratification. Returns should be placed in the occupied zone,
in that climate. These may be an option for some large spaces, if stratification is desired. Warm air rises, so return air sent
but few actually have been used except in some theater back to the HVAC system is cooler, saving energy and creating a
situations. more uniform environment in the occupied zone. See the later

FIGURE DISTANCE FROM CEILING VERTICAL DEFLECTION HORIZONTAL DEFLECTION THROW DROP
2 2 to 4 ft (0.6 to 1.3 m) 20 up 0 27 ft (8.7 m) 3 ft (0.9 m)
3 no ceiling 20 up 0 23 ft (7.4 m) 3 ft (0.9 m)
4 1 ft (0.3 m) 0 0 27 ft (8.7 m) 5 ft (1.6 m)
5 no ceiling 0 0 25 ft (8.1 m) 7 ft (2.3 m)
6 1.5 ft (0.5 m) 20 up 45 20 ft (6.5 m) 3 ft (0.9 m)
7 2 to 4 ft (0.6 to 1.3 m) 0 45 15 ft (4.8 m) 3 ft (0.9 m)
Table 1: Summarizes Figures 2 through 7.

April 1999 ASHRAE Journal 55


Practical Guide
comments on return grille acoustics.
The influence of the return air device
on air movement is very subtle. A num-
ber of CFD analyses show many arrows
pointing toward the return opening from
great distances away. Those researchers
need to get another model. In the real
world, air movement toward return open-
ings is imperceptible except within a few
inches of the opening.

Air Distribution Noise


Recommendations
And How to Meet Them
Sound is much less critical in many
large spaces than in offices, where the noise
source is very close to the occupants. There
are obvious exceptions, such as museums,
where air-conditioning noise may be ob- Figure 11: Spreading horizontal projection.
jectionable. Libraries, however, while tra-
ditionally very quiet, can benefit from a consistent background ARI Standard 885) NC ratings can provide an excellent means of
sound level, which may provide a level of speech privacy, and determining the suitability of these devices in a given application.
actually enhance the experience. In stadiums, air-conditioning Air terminals typically cause the NC to be determined in the lower
noise is probably of minimum concern. frequencies, with the result that the NC value is useful in room sound
In many cases, the acoustical consultant will request octave analysis only at the lower frequencies.
band data in order to perform a detailed analysis when design- Diffusers, on the other hand, typically peak in the mid fre-
ing auditoriums, concert halls, theaters, etc. Octave band data quencies, and NC values are typically in the speech interference
on most grilles is not available, but a close approximation can be regions. In most cases, NC values from diffusers and terminals
determined using the following analysis method: cannot, therefore, be considered to be additive. In large spaces
1. The sound power in the 5 octave band
th VAV terminal noise is seldom a problem, except that there is a
(1000 Hz) = NC + 10 dB. tendency to use very large sizes, where generated sound levels
2. The sound power in the 4 octave band
th may be surprisingly high. Manufacturers catalogs (or computer
(500 Hz) = 5 band + 3 dB.
th programs) can provide guidance. Be sure that all the assump-
tions stated in determining NC levels are understood.
3. The sound power in the 6th octave band While RC ratings may be an excellent tool for evaluating all
(2000 Hz) = 5th band 5 dB. sound in a space, they are less practical as a means of rating air
NC is a convenient tool, used industry wide, for providing a terminals. (For diffusers, RC ratings usually result in a value
single number rating of terminal units and diffusers. If reasonable identical to the determined NC value.) When a terminal is rated
attenuation assumptions are employed, (such as those provided in against RC requirements, a low numerical value, with an R

Figure 12: Displacement ventilation.

56 ASHRAE Journal April 1999


Museums &
Renovation
rating usually results. The numerical value that results (the aver- Summary
age of the 500, 1000 and 2000 frequency bands) is typically so As with most HVAC designs common sense rules. Air dis-
low that it has no impact on sound quality in the space. The tribution in large spaces can be summed up with a few simple
resulting R rating, gives no discrimination between units. axioms:
Therefore, RC is not recommended or practical as a single num- Cold air falls; hot air rises. The effect is about 1%/F
ber rating for an air terminal. (2%/C) temperature difference for 75 fpm (0.4 m/s)
Large spaces are often very reverberant due to hard surfaces, terminal velocity.
geometry etc., so an acoustical consultant should be employed. Use stratification to avoid conditioning spaces without
The manufacturers traditional assumption that the room will occupants.
absorb 10 dB, is usually over conservative. Most large spaces Return air is just as noisy as supply air.
will have more attenuation than that. More importantly, large You cannot suck out a match. Returns have little direct
spaces seldom experience near field sounds. More often, sound influence on air patterns.
is in a reverberant field, and calculations can be convoluted. Noise is not always bad. Libraries and other spaces can
ARI-885 suggests the use of the Shultz equation to deter- benefit from constant background noise.
mine room effect. Unfortunately, this equation assumes some
sound absorption resulting from ceiling tile, furniture or some
other absorbing elements. Often, in large spaces, these are not
present. For this reason, the Shultz equation is not a recom-
mended method in large spaces. Dan Int-Hout, Member ASHRAE, is with Carrier
Finally, the return air path is often overlooked as a source of Corporation.
noise in a space. The quantity of air returned is always nearly
the same as that being supplied, but usually through many fewer Leon Kloostra is chief engineer, technical sales, for
air devices and shorter duct runs. TITUS. =

Advertisement in the print edition formerly in this space.

April 1999 ASHRAE Journal 57

Vous aimerez peut-être aussi