SEBU7909-05 51
Operation Section
Features and Controls
R448 Adjustments
Wustration 40 901212000,
R446 Voltage Regulator52
Operation Section
Features and Controls
‘SEBU7909-05
PMG excitation
2 a) Yetow
Green
Rags Xt
Se 6.
Exciter field
IMustration 41 cousetete) ustration 44 soneeeott
Connections for shunt excitation Connections for PMG excitation
6 wires
1— 140 V Maximum supply
| 50/60 Hz
1/2 phose 11. 14
5+ ey 6
Exciter field
Mustration 42 900085049,
Connections for shunt excitation
12 wires
Green Aux windings
Black
Exciter field
Illustration 43 (900905005,
Connections for AREP excitation
Use the following procedure to adjust the R448
voltage regulator.
Use the following procedure in order to run the
generator set in parallel operation.
Adjustments for Stand-alone Generators
4. Turn the remote adjustment potentiometer to the
center position, if equipped.
2. Connect an analog voltmeter that is calibrated for
50 VDC on terminal E+ and terminal E-.
3. Connect a voltmeter that is calibrated for 300 VAG.
to 500 VAC or 1000 VAC to the output terminals of
the generator.
4, Make sure that the ST3 wire is positioned on the
desired frequency. Also, the engine speed must
be changed from the factory setting in order to
change the frequency of the generator.
5. Turn potentiometer (P2) to a full counterclockwis
position,
6. Turn stability potentiometer (P3) counterclod
to about 1/3 of the total rotation for the
potentiometer.
7. Start the engine and set the engine speed toa
frequency of 48 Hz for 50 Hz or 58 Hz for 60 Hz‘SEBU7909-05
53
Operation Section
Features and Controls
8. Adjust the output voltage to the correct value
with potentiometer P2. This voltage should be
the rated voltage UN for single operation or
UN plus 2% to 4% for parallel operation with
a current transformer. Use potentiometer P3
to make adjustments if the voltage oscillates.
Adjust potentiometer P3 in both directions while
you observe the voltage between E+ and E-
The voltage between E+ and E- should be
approximately 10 VDC. The best response times
are obtained at the limit of the instability. Try
cutting or replacing the wire ST2 if no stable
position can be obtained.
9. Check the operation of the Load Adjustment
Module (LAM). STS must be closed. The LAM can
be adjusted to 15% or 25% voltage dip by moving
the ST10 jumper wire.
Adjustments for Generators in Parallel
Operation
Note: Make sure that the speed droop is identical for
all of the engines before adjustments are made to
the generator.
1. Preset the unit for parallel operation by connecting
the current transformer to S1 and S2 of the
connector J2. Set potentiometer P1 for quadrature
droop in the center position. Apply the rated load.
The voltage should drop for 2% to 3%. Switch the
positions of the two incoming secondary wires of
the current transformer if the voltage increases.
2. The no-load voltages should be identical for all the
generators that are operating in parallel. Connect
the generators in parallel. Try to obtain a 0 kW
power exchange by adjusting the speed of the
generator. Try to minimize the circulating currents
between generators by altering the voltage setting
with potentiometer P2 or Rhe on one of the
generators.
Note: Do not change the voltage settings after
this step.
3. Apply the available load. The setting is correct
only if a reactive load is available. Equalize the
Kilowatts or divide the rated power of the units
proportionally by altering the speed. Alter the
quadrature droop potentiometer (P1) in order to
equalize the currents or divide the currents.
R448 Adjustment for Maximum
Excitation
Ilustration 45 (901212287
The maximum factory setting corresponds to
an excitation current that is required to obtain a
three-phase short circuit current of 3 X IN at 50 Hz for
industrial power, unless this is specified otherwise.
The maximum level of excitation may be reduced
by a static method. The static method is safer for
the generator and the installation. Use the following
steps to reduce the maximum excitation level.
4. Disconnect the power supply wires X1, X2, Z1
and Z2.
2. Disconnect sensing leads OV, 110V, 220V and
380V on the generator.
3. Connect the main power supply 200V-240V to X1
and X2, as shown
4. Install a 20 Amp DC ammeter in series with the
exciter field.
5. Turn potentiometer P5 to a full counterclockwise
position and activate the power supply. If there
is no output current from the voltage regulator,
turn potentiometer P2 clockwise until the ammeter
indicates a stable current
6. Switch off the power supply. Switch on the power
supply. Turn potentiometer P5 until the required
maximum current is obtained. The maximum.
current must not be greater than 15 Amperes.
Use the following steps in order to check the internal
protection:
4. Open switch D. The excitation current should
increase up to the preset maximum value and
the excitation current should remain at the preset
maximum value for approximately 10 seconds
The current will decrease to less than 1 Amp.54
Operation Section
Features and Controls
‘SEBU7909-05
2. Open switch A in order to reset the internal Table 7
eer Applications B Volts Time
Note: The voltage must be adjusted after the Voltage build up 6 (1A) | 1-2 seconds
maximum excitation current has been set. - aT
De-energized parallel
operation 6 (1A) 1-2 seconds
Special Use —
Standby parallel
- . operation 12 (2A) 5-10 seconde
De-energizing the Field Frequency starting (24 (4A) 5-10 seconds
Voltage that is sustained .
NOTICE Notege | 24 (4a) | 5-10 seconds
Damage will occur to the voltage regulator if the exci-
tation current E+ and E- are left open when the gen-
erator set is operating.
xa AREP / PMG
Zz
x1 fo oy
Z2 Qf.
Et aaa
’
The exciter is switched off by disconnecting the
power supply to the voltage regulator. The rating of
the switch contacts should be at least 16A - 250 VAC.
The connection is identical for resetting the internal
protection for the voltage regulator.
Forcing the Field
(s00V-10.A)44 Diode
Battery
B Volts
a Gen
Exciter field
Mustration 47 goratats9
Use a 12 VDC power source in order to energize the
field, if necessary. Refer to the following table.