Door Mounting type HEX080PB series

Dimension drawing













 
 





  

 


 

Internal External

Benefit for customer

* Low power consumption Main feature Unit Specification

* "One touch" dry run test and dust cleaning Dimension (H x W x D) mm 850 x 500 x 160

* Optional communication function design Cooling capacity*Note W/K 60 70

* Easy installation and maintenance from Rated voltage Vdc 48 (TYP.)

internal side Operating voltage range Vdc 40 ~ 60

* Simply LED status indicator Rated current A 1.8 max.

* High efficiency and reliable fan selection Power consumption W 87 max.

Operating temperature range C -10 ~ +65

Competitive Design Internal airflow CFM 180 230

* Air to air circulation of heat exchange External airflow CFM 140 170

* Door mounted 1.5M sound pressure noise dB-A 65.0 68.0

* Lightweight Weight Kg 14.0

* Rated voltage at 48V * Note : The cooling capacity (W/K OR W/C) is defi ned as Q/ (TI-TA)

* IP55 waterproof at external side Q : Heat dissipation (W) from inside of cabinet

* Drainage hole in the bottom TI : Return temperature of internal air circuit (K OR C)

* Safety approval TA : Ambient temperature of external air circuit (K OR C)