FEATURES

System total capacity up to


12KW output for
DUMW-48/50H.
DUMW
Suitable for outdoor
application with various
48/50H System
protection measures.

Wide AC input range 90V to


300V.

PFC technique features the


system high efficiency,
energy-saving and up to
0.99 power factor.
Intelligent fan-cooling
technique brings good
cooling performance, low
failure rate and high
reliability.

Fast on-line expansion of


rectifier modules enabled INTRODUCTION
by hot-swap.
DUMW-48/50H outdoor power system is compact and intelligent power
N+1 rectifier module system containing max.4 rectifier modules, controller module, LLVD, BLVD,AC
redundancy. and DC distributions. Special protection measures ensure it could be applied
in outdoor environment.
Automatic management of
battery charging and
temperature
compensation function

RS232 communication PPLICATIONS


interface. Fiber optic network
Broadband and network access
Dust-proof design : Bilayer Transmission equipment
filter, double shielding, easy Mobile communication/2G, 3G,4G base station
to maintain and replace Satellite communication ground station
Audible alarm : the sound is
up to 100dB. Automatic off
after 2 minutes.

Battery compartment
anti-theft : Double room Switch Mode Power System Distribution Cabinet Inverter
design for Anti-theft Remote Monitoring System DC/DC Converter UPS/EPS
Renewable Energy Solution Hybrid Power System HVDC UPS
Door lock anti-theft : Increase
door lock protective box to
realize double anti-theft.
Beijing Dynamic Power Co.,Ltd.
www.dpc.com.cn
installation LED light and
NO.8 Xinghuo Road, Science City, Fengtai District, Beijing, P. R. China
thermometer, smart fan
control.
SPECIFICATIONS
AC Input Monitoring and Control
Nominal:186-285Vac, 1phase Monitoring unit DKD48
AC supply Tolerance:90-300 VAC, 1phase Local Menu driven software via keypads
1 phase three wires input operation and LCD or PC (PowerSuite)
Frequency 45-65Hz
Remote
Power Factor 0.99 RS232
operation
Voltage wave LCD system status
<5%
distortion Visual Green LED System ON
Current Distortion 5% @50~100% load indications Yellow LED Minor alarm(s)
Soft start Red LED Major alarm(s)
Surge protection (SPD: Class B or C) Alarm relays 8 relays
Protection
Internal fuses (L & N)
4 to 8 options (for monitoring of external
Over voltage protection Digital inputs
equipment), Custom options available
AC Distribution Options Current Battery current
AC input 1*100A/2P for MCB, one set of SPD measurements Rectifier current
AC output 1*AC 10A/220V socket ,1*10A/1p MCB AC failure alarm
DC Output Rectifier failure alarm
Voltage -48VDC (-42--58VDC adjustable) Load fuse alarm
Battery fuse alarm
Current 200A ultimate capacity (48/50H) LVD operated
Voltage Low output voltage alarms
1%
regulation Alarms High output voltage alarms
Current Symmetry alarm
5% Fan fail
Sharing
Door
Efficiency Typical: 94%; (DZY-48/50H) Water
Smoke
Ripple and
200mV p-p Infrared
Noise
Psophometric Other Specifications
2mVrms
noise
Over/under voltage shutdown Cooling Air cooling
Protection Short circuit proof
High temperature protection
Protection level IP55
DC Distribution Options
Operating temp -40 to +75C (-40 to +167F)
No.of Load MCB:7*16A/1P; 9*32A/1P
Fuse Custom options available Temp range
-40 to +50C)
(when full load)
No.of Battery
MCB:2*100A Storage temp -40 to +85C (-40 to +185F)
Fuse
LLVD :4*16A /1P MCB,9*32A/1P MCB Operating: 95% non-condensing
LVD Humidity
BLVD:3*16A/1P MCB Storage: 99% non-condensing
Rectifier Dimensions 800W*650D*2000H(mm)
Type DZY-48/50H Weight 110kg excl. rectifiers

Beijing Dynamic Power Co.,Ltd.


www.dpc.com.cn
NO.8 Xinghuo Road, Science City, Fengtai District, Beijing, P. R. China