Project name-UNDP
Disclaimer: - "Lighting Design is based on 0.85 Maintenance factor considering 15 % deprecation of life of light
fixture"
The nominal values shown in the calculation report are the result of precision calculations, based upon
precisely positioned luminaires in a fixed relationship to each other and to the area under examination. In
practice the values may vary due to tolerances on luminaires, luminaire position reflection properties, electric
supply etc. Declared lumen output of luminaire are nominal values which are subject to +/- 10% variation as per
IS. Thus accordingly lux level will also vary. There could be tolerance of +/- 5% due to various reasons. Lighting
calculation done for open area without any obstruction. Tolerance in Supply voltage. Luminaire ambient
temperature. Luminaire dirt depreciation.
Date: 15.08.2017
Operator: Pulkit Gandhi
Lighting Design & Calculations Report
15.08.2017
Table of contents
Page 2
Lighting Design & Calculations Report
15.08.2017
Height of Room: 2.700 m, Mounting Height: 2.700 m, Light loss factor: Values in Lux, Scale 1:48
0.85
Workplane:
Height: 0.000 m
Grid: 9 x 7 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.664, Ceiling / Working Plane: 0.201.
No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Philips DN 395B LED20S-6500 PSD WH
1 8 2221 2220 22.0
Diffused /6500K (1.000)
Total: 17764 Total: 17760 175.9
Specific connected load: 8.54 W/m = 2.39 W/m/100 lx (Ground area: 20.61 m)
Page 3
Lighting Design & Calculations Report
15.08.2017
WORKSTATIONS1 / Summary
Height of Room: 2.700 m, Mounting Height: 2.700 m, Light loss factor: Values in Lux, Scale 1:275
0.85
Workplane:
Height: 0.000 m
Grid: 27 x 13 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.628, Ceiling / Working Plane: 0.196.
No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Philips DN 392B LED10S-6500 PSU WH
1 41 1082 1080 10.6
Diffused /6500K (1.000)
Philips DN 395B LED20S-6500 PSD WH
2 46 2221 2220 22.0
Diffused /6500K (1.000)
Total: 146504 Total: 146400 1447.0
Specific connected load: 6.76 W/m = 1.87 W/m/100 lx (Ground area: 213.99 m)
Page 4
Lighting Design & Calculations Report
15.08.2017
Height of Room: 2.700 m, Mounting Height: 2.700 m, Light loss factor: Values in Lux, Scale 1:44
0.85
Workplane:
Height: 0.000 m
Grid: 6 x 4 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.780, Ceiling / Working Plane: 0.235.
No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Philips DN 395B LED20S-6500 PSD WH
1 4 2221 2220 22.0
Diffused /6500K (1.000)
Total: 8882 Total: 8880 88.0
Specific connected load: 10.22 W/m = 3.40 W/m/100 lx (Ground area: 8.61 m)
Page 5
Lighting Design & Calculations Report
15.08.2017
Height of Room: 2.700 m, Mounting Height: 2.700 m, Light loss factor: Values in Lux, Scale 1:44
0.85
Workplane:
Height: 0.000 m
Grid: 5 x 4 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.780, Ceiling / Working Plane: 0.235.
No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Philips DN 395B LED20S-6500 PSD WH
1 4 2221 2220 22.0
Diffused /6500K (1.000)
Total: 8882 Total: 8880 88.0
Specific connected load: 10.22 W/m = 3.40 W/m/100 lx (Ground area: 8.61 m)
Page 6
Lighting Design & Calculations Report
15.08.2017
Height of Room: 2.700 m, Mounting Height: 2.700 m, Light loss factor: Values in Lux, Scale 1:44
0.85
Workplane:
Height: 0.000 m
Grid: 9 x 7 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.789, Ceiling / Working Plane: 0.239.
No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Philips DN 395B LED20S-6500 PSD WH
1 4 2221 2220 22.0
Diffused /6500K (1.000)
Total: 8882 Total: 8880 88.0
Specific connected load: 10.59 W/m = 3.54 W/m/100 lx (Ground area: 8.31 m)
Page 7
Lighting Design & Calculations Report
15.08.2017
Height of Room: 2.700 m, Mounting Height: 2.700 m, Light loss factor: Values in Lux, Scale 1:32
0.85
Workplane:
Height: 0.000 m
Grid: 9 x 7 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.775, Ceiling / Working Plane: 0.233.
No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Philips DN 395B LED20S-6500 PSD WH
1 4 2221 2220 22.0
Diffused /6500K (1.000)
Total: 8882 Total: 8880 88.0
Specific connected load: 10.59 W/m = 3.49 W/m/100 lx (Ground area: 8.31 m)
Page 8