Secondary Air Damper Control in


Boiler
PRINT REFERENCE THIS

Published: 23rd March, 2015 Last Edited: 6th July, 2017

This essay has been submitted by a student. This is not an example of the work written by
our professional essay writers.

Keywords: furnace to windbox differential pressure, windbox to furnace

In this proposed work, design and development of controlling Secondary air dampers in a draft
system of a power plant which is presently working on DCS technique has been accomplished by
using high computing software ARDUINO and results has been shown with suitable simulation in
VISUAL BASICS. The goal of this work is to control the air dampers in a different way according to
the unit load thereby increasing the boiler efficiency and to reduce the pollution. A set of six
interlock conditions were provided for this purpose. Since DCS is applicable only for big system
not less than 5000 input and output but this is costly. It consists of separate server, processor and
computers where as ARDUINO does not require a separate processor, no workstation, no
operator station here directly connect interfacing card with computer itself.

Keywords- Secondary air dampers, Draft


system, ARDUINO, Power plant (TTPS),
Software control.
I. INTRODUCTION

https://www.ukessays.com/essays/engineering/automatic-control-of-secondary-air-damper... 9/13/2017
Secondary Air Damper Control in Boiler Page 2 of 10

In power plant boilers, the draft is obtained by means of fans namely Forced draft and Induced
3
UK ESSAYS (/)
draft fan. The FD and ID fans develop enough draft to move the tremendous volume of air and
gases through the flue gas ducts and stack to atmosphere maintaining a balanced draft in the
furnace. The secondary air for combustion primarily enters into the windbox. The wind box
assembly is a tall structure divided in its height into thirteen compartments which houses 6 no. of
Coal nozzles and 5 auxiliary air nozzles alternatively at different elevations from top to bottom.
Louvre dampers named as secondary air dampers each of which is operated by an individual
damper drive cylinder located at the side of the wind box. The coal nozzle elevations are
designated as A,B,C,D,E,F elevation from bottom to top, the bottom end air and top end air
elevations as AA and FF respectively. The auxiliary air nozzles in between coal elevations are
designated as elevations AB,BC,CD,DE,EF. The furnace corners are designated as corner 1, 2, 3 and
4 in clockwise direction. The heat released in the furnace is received by the

Water/steam/air to the maximum extent to have boiler efficiency of the order of 86%.

II. OPERATIONAL PROCEDURE OF SECONDARY AIR


The operation of the auxiliary and fuel air dampers in the windbox assemblies are affected by the
FSSS.

A. Auxiliary air dampers:

During the furnace purge period and initial operations up to 30% boiler loading all elevations of
auxiliary and end air dampers modulate to maintain a predetermined (approx. 40 mmWC) set
point differential pressure between windbox to furnace. 30 to 40% of total air flow to have an air
rich furnace will be supplied during the above period to avoid unhealthy furnace conditions.

When the unit load exceeds 30% MCR, the differential pressure set point is changed and ramps to
a higher setting (approx. 100 mmWC). Simultaneously, the auxillary air dampers associated with
coal or oil elevations not in service close in timed sequence starting with the upper elevation of
dampers and progressing to the lowest elevation.

When the unit loading is reduced below 30% loading, the auxillary air dampers open in a timed
sequence starting with the lowest elevation of dampers. Simultaneously, the differential set point
changes to its lowest setting.

All the auxillary air dampers maintain the status quotient upon a boiler trip and will open fully
when both the FD fans are off. The bottom end air damper is normally kept open to a fixed
predetermined position to reduce unburnt coal dust fall out.

B. Fuel (oil) air dampers:

Elevation AB, CD and EF dampers modulate according to the oil header pressure when heavy oil is
being fired. Otherwise they open and close with the rest of the aux air dampers. Elevation AB
dampers are kept at a fixed opening when light oil is being fired.

C. Fuel (coal) air dampers:

Their operations are independent of Boiler load. All coal

https://www.ukessays.com/essays/engineering/automatic-control-of-secondary-air-damper... 9/13/2017
Secondary Air Damper Control in Boiler Page 3 of 10

air dampers are normally closed. They open fifty seconds after the associated feeder is started,
3
UK ESSAYS (/)
and modulate as a function of feeder speed. Fifty seconds after the coal feeders are removed
from service, the associated fuel air dampers close. The fuel (coal) air dampers open fully, when
both FD fans are off or when the boiler trips on master fuel trip.

Importance of secondary air:

Protect Boiler Equipments


Control the Pollution
Improve the Efficiency of the Boiler

III.METHODOLOGY
This project is to automatically control the air inlets that are termed as dampers which are
operated using pneumatic valves. The pneumatic valves are controlled by sensors depending on
the windbox to furnace differential pressure. Thus this project controls dampers based on arduino
coding

And its visually displayed in visual basics. This forms the basic methodology for this project.

A. Hardware Description:

The hardware components consist of 4potentiometers of range 10kâ. These are assumed
to be the coal mills/diesel input i.e. inputs for coal. Secondary air dampers are present near all
coal and diesel elevations.

The percentage opening of a damper depends on the amount of coal/diesel input. Therefore
variation of potentiometers indicate amount of coal/diesel input. The damper opening depends
on the variable point of the potentiometers.

4 potentiometers are so connected for explanation and they are connected to the A/D convertor
pins of AT MEGA 8.0 controller.

Then the freeduino board in which the AT MEGA 8.0 is fixed is connected to PC and arduino coding
is uploaded in the controller. Then VB shows graphical representation of percentage of damper
opening and all other factors.

B. Software Description:

The software coding was developed based on several conditions on which the secondary air
damper openings depend. These form the base for developing a program. These conditions are
based on some fixed values and formulas. As already mentioned the percentages of secondary air
damper opening depend on the amount of fuel input to the furnace. The algorithm for visual
basics coding are as below.

1) Operation Of Coal Elevation Dampers: (A, B, C, D, E, F)

The coal dampers at elevations A, B, C, D, E and F will be fed with coal depending on the load of
the power plant. Feeding (30 tonnes per hour) any three of these coal elevations is sufficient
enough to supply the predetermined full load (210 MW) of the unit. All dampers always have a
minimum opening of 30%. In general,less than 20% of the secondary air to the fireball will

https://www.ukessays.com/essays/engineering/automatic-control-of-secondary-air-damper... 9/13/2017
Secondary Air Damper Control in Boiler Page 4 of 10

maintain substoichiometric combustion which limits the flame temperature of the fireball 3 and
UK ESSAYS (/)
provides the curtain of secondary air over the walls. The curtain of secondary air militates against
the formation of slag on the furnace walls. All this proportioning of the air requires tools of
adjustment available to the furnace operator.

The dampers modulate according to coal input in three different ways as:

When coal is fed into a particular(own) elevation ,the corresponding air damper starts modulating
based on the fuel input to let the secondary air required for the combustion of given input.

Rather when coal is fed into an (auxillary) elevation adjacent to a particular damper, the damper
modulates to maintain the windbox to furnace differential pressure, thereby controlling the
constant negative pressure essential to create swirling fireballs of combustion in tangentially fired
boilers.

When the condition of tripping the whole unit arises, all the six coal elevation dampers are opened
to100 % (maximum).

When there is no fuel input in any of the above elevations then the dampers will be in minimum
opening position. (0%)

2) Operation of oil elevation dampers

(AB, BC, CD, DE, EF):

Oil is used as fuel input during startup and during scarcity of coal. Each pair of coal nozzle
elevations is served by one elevation of oil burners (4 nos. /elevation) located in the auxiliary air
nozzle. Thus 12 oil guns, non retractable type, are accommodated in the three elevations AB, CD
and EF. Heavy fuel oil can be fired at the oil guns of all these three elevations, whereas light fuel oil
(High speed diesel oil) can also be fired at AB elevation. Each oil gun is associated with a
retractable high energy arc (HEA) igniter, arranged at the side of the oil gun in the auxiliary air
compartment and they directly light up the oil guns.

The dampers modulate according to oil input in three different ways as:

When oil is fed into a particular(own) elevation ,the corresponding air damper starts modulating
based on the fuel input to let the secondary air required for the combustion of given input.

When steam input is higher than 30% with adjacent elevation opened then windbox to furnace
differential pressure is maintained.

Rather when oil is fed into an (auxillary) elevation adjacent to a particular damper, the damper
modulates to maintain the windbox to furnace differential pressure, thereby controlling the
constant negative pressure essential to create swirling fireballs of combustion in tangentially fired
boilers.

When the condition of tripping the whole unit arises, all the oil elevation dampers are opened to
100 % (maximum).

When there is no fuel input in any of the above elevations then the dampers will be in minimum
opening position. (0%)

https://www.ukessays.com/essays/engineering/automatic-control-of-secondary-air-damper... 9/13/2017
Secondary Air Damper Control in Boiler Page 5 of 10

3
UKESSAYS (/)
3) Operation of AA, FF elevation dampers:

The AA elevation of air damper is always fully (100%) opened and the FF elevation is always closed
to enhance combustion.

Thus the coding for the project is developed based onthe conditions of the coal and oil inputs.

IV. SEQUENCE OF OPERATION


The opening of dampers depends on the load and coal input. The above table I illustrate the
percentage of coal input in each mill for given percentage of load. Here 30 Tonnes/Hr of coal is the
100% input and 10 Kg/cm2 of oil is the 100% input of oil.

When unit load is 50%, then coal mills A, B are in full operation and C mill operates 10% with AB
elevation having oil.

For a load of 60%, coal mills A, B, C will operate till 30% and mill D has 10% input. AB oil elevation
is fed with full percentage of oil.

If the load is 70%, then there is no need for oil but coal mills A, B, C, and D are fed with maximum
input.

For 90% ,there is no need for oil but the coal mills

A, B, C, D is fed with maximum input and E with 20% of fuel input.

For 100% load, all the coal elevations are fed with maximum input.

V. SIMULATION RESULTS
Visual Basic is a third-generation event-driven programming language and integrated
development environment (IDE) from Microsoft for its COM programming model first released in
1991. Visual Basic was derived from BASIC and enables the rapid application development (RAD)
of graphical user interface (GUI) applications, access to databases using Data Access Objects,
Remote Data Objects, or ActiveX Data Objects, and creation of ActiveX controls and objects. VBA is
effectively the same language as Visual Basic but VBA-code is tied to Microsoft Office and can only
run within that environment. A programmer can put together an application using the
components provided with Visual Basic itself.

The four fuel inputs are received via the potentiometer to the AT MEGA 8 microcontroller. The
variation of potentiometers indicate amount of coal/diesel input. The damper opening depends
on the variable point of the potentiometers.

The controller board is connected to PC and arduino coding is uploaded in the controller. Then VB
is used for graphical representation of damper opening.

The simulation results showing the air dampers status variation according to the various input set
points is as follows:

https://www.ukessays.com/essays/engineering/automatic-control-of-secondary-air-damper... 9/13/2017
Secondary Air Damper Control in Boiler Page 6 of 10

3
UKESSAYS (/)
The amount of coal input given is shown in the above fig 5. This show the percentage of input
given, timer, coal mill that is active, amount of load, steam input set point and steam input in
percentage.

This form shows all the elevation of dampers and denotes the damper that is open and the
percentage of damper opening is also shown. In addition to that reactive power produced for
corresponding load is also calculated.

VI CONCLUSION
Based on the graphical programming language and the data stream operating mode, the software
instead of apparatus, the use of virtual instrument technology has opened up our new field of
control. Compared to the traditional control it has obvious advantages. Programming is simple by
the graphical programming language. A form of visual basics personalizes button design and
layout, with the virtual knobs and switches to struck the friendly human, intuitive control interface
makes vivid, so that the operators are involved in the operation easier to control the process and
results at a glance. The main advantage of controlling secondary air dampers by using arduino is
lesser cost as compared to DCS technique, since the interfacing of inputs and outputs are directly
given to the PC (which works as work station i.e. block panel and operator station i.e. front
panel) .This paper was made in a Coal Based Thermal power plant at tuticorin, TTPS as the existing
is running on DCS system.

VII ABBREVIATIONS:

DCS - Distributed Control System

FSSS - Furnace Safeguard Supervision System

FD fan - Forced Draft Fan

ID fan - Induced Draft Fan

ADC - Analog to Digital converter

PC - Personal Computer

VB - Visual Basic 6.0

Draft - difference of pressure causing flow of air

Elevation -position of dampers

Windbox -secondary air storage compartment between FD fan and furnace.

https://www.ukessays.com/essays/engineering/automatic-control-of-secondary-air-damper... 9/13/2017
Secondary Air Damper Control in Boiler Page 7 of 10

3
UKESSAYS (/)

Video: Discover UK Essays!

Need help with your work?


We provide top quality academic writing to assist with your essay
and help you achieve success!
Take a look at our essay writing service now!
(/services/essay-writing-service.php)

https://www.ukessays.com/essays/engineering/automatic-control-of-secondary-air-damper... 9/13/2017
Secondary Air Damper Control in Boiler Page 8 of 10

3
UKESSAYS (/)

(https://www.scanmyessay.com/?utm_source=ukessays-
essays&utm_medium=banner&utm_content=lg_banner)

Dissertation Writing Service

Our Dissertation Writing service can help with everything from full dissertations to
individual chapters.

(/services/dissertation-writing-services.php)

Marking Service

Our Marking Service will help you pick out the areas of your work that need
improvement.

(/marking/premium-service.php)

https://www.ukessays.com/essays/engineering/automatic-control-of-secondary-air-damper... 9/13/2017
Secondary Air Damper Control in Boiler Page 9 of 10

3
All ServicesUKESSAYS (/)

Fully referenced, delivered on time. Get the extra support you require now.
(/services/)

APA Referencing Tool FREE

Harvard Referencing Tool FREE

Vancouver Referencing Tool FREE

Study Guides FREE

Request Removal
If you are the original writer of this essay and no longer wish to have the essay published on the
UK Essays website then please click on the link below to request removal:

REQUEST THE REMOVAL OF THIS ESSAY

More from UK Essays


Engineering Essay Writing Service

Essays

More Engineering Essays

Examples of Our Work

Engineering Dissertation Examples

https://www.ukessays.com/essays/engineering/automatic-control-of-secondary-air-damper... 9/13/2017
Secondary Air Damper Control in Boiler Page 10 of 10

WEUKCAN HELP WITH YOUR ESSAY


ESSAYS (/)
3

FIND OUT MORE (/SERVICES/ESSAY-WRITING-SERVICE.PHP)

Copyright 2003 - 2017 - UK Essays is a trading name of All Answers Ltd, a company registered in
England and Wales. Company Registration No: 4964706. VAT Registration No: 842417633.
Registered Data Controller No: Z1821391. Registered office: Venture House, Cross Street, Arnold,
Nottingham, Nottinghamshire, NG5 7PJ.

https://www.ukessays.com/essays/engineering/automatic-control-of-secondary-air-damper... 9/13/2017

Vous aimerez peut-être aussi