net Contents 1
Moeller SK1230-1177GB

Circuit-breakers LZM1, 2, 3, 4

Circuit-breakers, switch-disconnectors
and switch-disconnectors LN1, 2, 3, 4 Circuit-breakers, switch-disconnectors
from 15 to 1600 A
up to 1600 A

up to 1600 A
Page Page Page

System overview Rotary handles with door interlock 57 Technical data


Reliably and safely controlling, switching Main switch assembly kit 58
Circuit-breaker 86
Circuit-breakers, switch-disconnectors 2
and managing power, in industry, in buildings Accessories 60
Switch-disconnectors 90
and in machine construction. Enabled by Technical overview 4 Mechanical interlock 62
Temperature influence 91
innovative protection concepts. Ordering Multi-function device adapter 63
Effective power loss 93
Accessories 64
Circuit-breaker thermo-magnetic 6 Terminal capacities 94
release, 3-pole Insulated enclosures 66
Auxiliary contact 96
Circuit-breaker, fixed overload releases, 8 Residual-current release frequency 68
response Equipping with auxiliary contacts, time 97
3 pole differences
Circuit-breaker, electronic releases, 10 Engineering
Undervoltage release, shunt release, 98
3 pole
Selectivity: incoming circuit-breaker, 70 Remote operator, capacitor units 99
Circuit-breaker thermo-magnetic 12 outgoing circuit-breaker
release, 4-pole Residual current relay 100
MCB, backup protection 74
Circuit-breaker, fixed overload releases, 14 Residual current release 102
4 pole Direction of blow-out, minimum 75
clearances, tube cable lugs Dimensions
Circuit-breaker series LZM1 to LZM4, Circuit-breakers, electronic releases, 16
4 pole Auxiliary switches, 76 Size 1: basic units 104
switch-disconnectors LN1 to LN4 trip-indicating auxiliary contacts
- just 4 compact frame sizes Switch-disconnectors, 3 pole 18 Size 1: accessories 105
Mechanical interlock 77
- available as 3 and 4-pole device Switch-disconnectors, 4 pole 18 for (door-coupling) rotary handle Size 2: basic units 113
- now also up to 1600 A
Connection types 20 Mechanical interlock for remote 78 Size 2: accessories 114
- flexible mounting using modular function groups
Standard/trip-indicating auxiliary contact from - full rated current at 50 C ambient temperature Plug-in units 40 operator, residual-current relay
Size 3: basic units 125
the Titan range - switch suitable for world-wide use
Withdrawable units 41 Sizes 1, 2: tripping characteristics 79
Size 3: accessories 126
- reduced number of variants and stockholding requirement Page 6, page 18 Size 3: tripping characteristics 80
Auxiliary contact with screw terminals 42 Size 4: basic units 135
- simple front installation at the same position
- simple clip-on feature saves mounting costs Door coupling rotary handles Undervoltage release with screw 44 Size 4: tripping characteristics 81
Size 4: accessories 136
- attractively priced identical parts from the control circuit - identical drilling template for all terminals Sizes 1, 2, 3: let-through characteristics 82
device range variants Undervoltage release, off-delayed 49 Size 2: residual-current release 84
Page 42 - innovative automatic centring frequency response
Shunt release with screw terminals 50
- axis support for long-term reliable
operation Door coupling rotary handles 54
- side-wall operation ensuring space-
Rotary handles 56
saving main switch installation
Page 54

Remote operators
- common functional concept of all
variants
- low closing delays 60 ms to 100 ms
- locking and sealing features provide
security
Page 64
2 System overview
Circuit-breakers, switch-disconnectors
LZM Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

5
7

4 6
8

25 9
10

3
2

24

11

13 12

14

23

19
20 16
15
21
17

18
System overview 3
Circuit-breakers, switch-disconnectors
http://catalog.moeller.net Moeller SK1230-1177GB LZM

Circuit-breakers, switch-disconnectors
Basic units Add-on functions Mounting accessories

Circuit-breaker 1 Standard auxiliary contact (HIN) 13 Control circuit terminal 8


Rated uninterrupted current up to 1600 A Switching with the main contacts. Used for For two terminals at top or bottom
Switching capacity 16, 25, 36, 50 kA indication and interlock functions. LZM1 a page 23
at 415 V a page 42 LZM2 a page 27
Adjustable releases for overload and short- LZM3 a page 31
circuit Trip-indicating auxiliary contact (HIA) 13
General trip indication '+', when tripped by LZM4 a page 39
Adjustable time selectivity
voltage release, overload release or short-
Earth-fault protection Tunnel terminals for Al and Cu cable 6
circuit release
Protection of systems, cables, motors, Standard with control circuit terminal
a page 42
generators LZM1 a page 21
3 and 4 pole versions,IEC/EN 60947 Early-make auxiliary contacts 24 LZM2 a page 25
a page 6 For interlocking and load shedding circuits, as LZM3 a page 31
well as for early make of the undervoltage LZM4 a page 37
Switch-disconnector 1 release in main switch/Emergency-stop
Rated uninterrupted current up to 1600 A applications Box terminals 7
Remotely tripped switch-disconnector with a page 42 Standard version of frame size 1 assembled
undervoltage or shunt release within the circuit-breaker enclosure
3 and 4 pole versions, IEC/EN 60947 Voltage release 24
LZM1 a page 21
a page 18 Undervoltage release
Non-delayed LZM2 a page 25
OFF-delayed LZM3 a page 29
Shunt release
Terminal cover 4
a page 44
Protection against direct contact where cable
lugs, busbars or tunnel terminals are used
Delay unit for undervoltage release 25
LZM1 a page 23
a page 49
LZM2 a page 27
Rear drive 14 LZM3 a page 32
a page 60 LZM4 a page 39

Door coupling rotary handle 16, Terminal cover, knockout 3


Lockable 18 LZM1 a page 23
With door interlock LZM2 a page 27
a page 54 LZM3 a page 32
LZM4 a page 39
Main switch rotary handle for side panel 15
mounting Clip plate 10
a page 58 NZM1-XC35 for 35 mm top-hat rail
Extension shaft 17 NZM2-XC75 for 75 mm top-hat rail
Can be cut to required length. a page 61
a page 54 Rear connection 11
LZM1 a page 21
Rotary handle 19
LZM2 a page 25
Lockable
LZM3 a page 31
a page 56
LZM4 a page 37
Remote operator 22
Plug-in and withdrawable unit 9
For remote switching of circuit-breakers and
switch-disconnectors a page 40
a page 64 Insulating surround 21
For use with toggle lever, rotary drive and
Toggle lever interlock device 23
remote operator protruding from the enclosure
a page 61
a page 61
External warning plate/designation label 20
a page 60
Spacer 12
a page 61
IP2X protection 2
against contact with a finger
For box terminals
LZM1 a page 23
LZM2 a page 27
LZM3 a page 32
IP2X protection 5
against contact with a finger
For barrier
LZM1 a page 23
LZM2 a page 27
LZM3 a page 32
4 Technical overview Technical overview 5
Circuit-breaker, switch-disconnector, 3/4-pole Circuit-breaker, switch-disconnector, 3/4-pole
LZM1, LZM2, LZM3, LZM4 Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM1, LZM2, LZM3, LZM4
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Circuit-breaker
With main switch characteristics to IEC/EN 60204
and isolating characteristics to IEC/EN 60947

Rated uninterrupted current Iu = Rated current In Thermomagnetic releases Electronic releases


Adjustable overload release Ir System and cable protection Systems, cable, selectivity and generator protection
Adjustable short-circuit release Ii
Delayed short-circuit release Isd Iu Iu Ir Ii Iu Iu Ir Isd Ii
A A A A A A A A A

Ambient temperature at 100% Iu 20 0.8 1 x In 350 0.5 1 x In 2 10 x Ir 2 12 x In


min./max. -25/+50 C 25
32
40 8 10 x In
50 6 10 x In
63
80
100
125
160 160 LZM1: 8x In
200 6 10 x In
250
300 320
400 400
500
630
800
1000
1250
1600
Economic switching capacity LZME1-A
400/415 V kA/cos v 18 0.25
Basic switching capacity LZMB1-A LZMB2-A
400/415 V kA/cos v 25 0.25 25 0.25
Comfort switching capacity LZMC1-A LZMC2-A LZMC3-A LZMC3-E
400/415 V kA/cos v 36 0.25 36 0.25 36 0.25 36 0.25
Normal switching capacity LZMN3-A LZMN3-E LZMN4-E
400/415 V kA/cos v 50 0.25 50 0.25 50 0.25

Notes The stated switching capacity values are rated ultimate short-circuit breaking capacities (Icu)

Switch-disconnector
With main switch characteristics to IEC/EN 60204
and VDE 0113 isolating characteristics to IEC/EN 60947,
VDE 0660 without overload and short-circuit release

Rated uninterrupted current Iu = rated current In


63 160 160 250 400 630 630 1600
Type N can be triggered with U/A voltage release LN1- LN2- LN3- LN4-
Rated short-circuit making capacity Icm kA 2.8 5.5 25 53
Rated short-time withstand current Icw (1s-Ieff) kA 2 3.5 12 25
6 Ordering Ordering 7
Circuit-breaker, thermo-magnetic release, 3 pole Circuit-breaker, thermo-magnetic release, 3 pole
LZM...1, LZM...2, LZM...3 Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM....1, LZM...2,LZM...3
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Economic switching capacity Basic switching capacity Comfort switching capacity Normal switching capacity
18 kA at 415 V 50/60 Hz 25 kA at 415 V 50/60 Hz 36 kA at 415 V 50/60 Hz 50 kA at 415 V 50/60 Hz
Rated current = rated Setting range Part no. Price Part no. Price Part no. Price Part no. Price Std. pack Notes
uninterrupted current Article no. see price Article no. see price Article no. see price Article no. see price
list list list list
Overload releases Short-circuit
releases
In = Iu Ir Ii
A A A
I

Protection of systems and cables


3 pole
Terminals standard, terminal screws as accessories
20 1520 350 LZME1-A20-I LZMB1-A20-I LZMC1-A20-I 1 off IEC/EN 60947-2
111808 111848 111888 Adjustable overload releases Ir
25 2025 350 LZME1-A25-I LZMB1-A25-I LZMC1-A25-I 0.8 1 x In (ex-works 0.8 x In)
111809 111849 111889 Adjustable short-circuit releases Ii
6 10 x In (ex-works 6 x In)
32 2532 350 LZME1-A32-I LZMB1-A32-I LZMC1-A32-I LZM...-A40-I: 8 10 x In (ex-works 8 x In)
111810 111850 111890 Fixed short-circuit release Ii
40 3240 320400 LZME1-A40-I LZMB1-A40-I LZMC1-A40-I 350 A at In = 20 32 A
111811 111851 111891 1280 A at In = 160 A (LZM1)
50 4050 300500 LZME1-A50-I LZMB1-A50-I LZMC1-A50-I
111812 111852 111892
63 5063 380630 LZME1-A63-I LZMB1-A63-I LZMC1-A63-I
111813 111853 111893
80 6380 480800 LZME1-A80-I LZMB1-A80-I LZMC1-A80-I
111814 111854 111894
100 80100 6001000 LZME1-A100-I LZMB1-A100-I LZMC1-A100-I
111815 111855 111895
125 100125 7501250 LZME1-A125-I LZMB1-A125-I LZMC1-A125-I
111816 111856 111896
160 125160 1280 LZME1-A160-I LZMB1-A160-I LZMC1-A160-I
111817 111857 111897
Terminal screws standard, terminals as accessories
160 125160 9601600 LZMB2-A160-I LZMC2-A160-I 1 off
111922 111938
200 160200 12002000 LZMB2-A200-I LZMC2-A200-I
111923 111939
250 200250 15002500 LZMB2-A250-I LZMC2-A250-I
111924 111940
300 240300 15002500 LZMB2-A300-I LZMC2-A300-I
111925 111941
Terminal screws standard, terminals as accessories
320 250320 19203200 LZMC3-A320-I LZMN3-A320-I 1 off
111954 111966
400 320400 24004000 LZMC3-A400-I LZMN3-A400-I
111955 111967
500 400500 30005000 LZMC3-A500-I LZMN3-A500-I
111956 111968

Notes Notes for terminals a 21


8 Ordering Ordering 9
Circuit-breaker, fixed overload releases, 3 pole Circuit-breaker, fixed overload releases, 3 pole
LZM...1, LZM...2 Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM...1, LZM...2
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Economic switching capacity Basic switching capacity Comfort switching capacity
18 kA at 415 V 50/60 Hz 25 kA at 415 V 50/60 Hz 36 kA at 415 V 50/60 Hz
Rated current = rated Setting range Part no. Price Part no. Price Part no. Price Std. pack Notes
uninterrupted current Article no. see price Article no. see price Article no. see price
list list list
Overload releases Short-circuit
releases
In = Iu Ir Ii
A A A
I

Protection of systems and cables


3 pole
Terminals standard, terminal screws as accessories
20 1520 350 LZME1-ASF20-I LZMB1-ASF20-I LZMC1-ASF20-I 1 off IEC/EN 60947-2
111678 111838 111878 Adjustable overload releases Ir
25 2025 350 LZME1-ASF25-I LZMB1-ASF25-I LZMC1-ASF25-I 0.8 1 x In (ex-works 0.8 x In)
111679 111839 111879 Fixed short-circuit release Ii
10 x In
32 2532 350 LZME1-ASF32-I LZMB1-ASF32-I LZMC1-ASF32-I 350 A at In = 20/25/32 A (LZM1)
111800 111840 111880 1280 A at In = 160 A (LZM1)
40 3240 400 LZME1-ASF40-I LZMB1-ASF40-I LZMC1-ASF40-I 2500 A at In = 300 A (LZM2)
111801 111841 111881
50 4050 500 LZME1-ASF50-I LZMB1-ASF50-I LZMC1-ASF50-I
111802 111842 111882
63 5063 630 LZME1-ASF63-I LZMB1-ASF63-I LZMC1-ASF63-I
111803 111843 111883
80 6380 800 LZME1-ASF80-I LZMB1-ASF80-I LZMC1-ASF80-I
111804 111844 111884
100 80100 1000 LZME1-ASF100-I LZMB1-ASF100-I LZMC1-ASF100-I
111805 111845 111885
125 100125 1250 LZME1-ASF125-I LZMB1-ASF125-I LZMC1-ASF125-I
111806 111846 111886
160 125160 1280 LZME1-ASF160-I LZMB1-ASF160-I LZMC1-ASF160-I
111807 111847 111887
Terminal screws standard, terminals as accessories
160 125160 1600 LZMB2-ASF160-I LZMC2-ASF160-I 1 off
111918 111934
200 160200 2000 LZMB2-ASF200-I LZMC2-ASF200-I
111919 111935
250 200250 2500 LZMB2-ASF250-I LZMC2-ASF250-I
111920 111936
300 240300 2500 LZMB2-ASF300-I LZMC2-ASF300-I
111921 111937

Notes Notes for terminals a 21


10 Ordering Ordering 11
Circuit-breaker, electronic releases, 3 pole Circuit-breaker, electronic releases, 3 pole
LZM...2, LZM...3, LZM...4 Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM...2, LZM...3, LZM...4
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Comfort switching capacity Normal switching capacity
36 kA at 415 V 50/60 Hz 50 kA at 415 V 50/60 Hz
Rated current = rated Setting range Part no. Price Part no. Price Std. pack Notes
uninterrupted current Article no. see price list Article no. see price list
Overload Short-circuit releases
releases
Non-delayed Delayed short-
circuit release
In = Iu Ir Ii Isd
A A A A
I I

Protection of systems and cables


3 pole
Terminal screws standard, terminals as accessories
630 315630 12605040 LZMC3-AE630-I LZMN3-AE630-I 1 off IEC/EN 60947-2
111957 111969
800 400800 16009600 LZMN4-AE800-I Adjustable overload releases Ir
111978 0.5 1 x In (ex-works 0.8 x In)
1000 5001000 200012000 LZMN4-AE1000-I R.m.s. value measurement and thermal memory
111979
1250 6301250 250015000 LZMN4-AE1250-I Adjustable short-circuit releases Ii
111980 LZM...3-AE250/400-I: 2 11 x In (ex-works 6 x In)
LZM...3-AE630-I: 2 8 x In (ex-works 6 x In)
1600 8001600 320019200 LZMN4-AE1600-I
LZM...4-AE...-I: 2 12 x In (ex-works 6 x In)
111981

Systems and cable protection, selectivity and generator protection


3 pole
Terminal screws standard, terminals as accessories
160 LZMC2-VE160-I
111942
250 LZMC2-VE250-I
111943

400 LZMC3-VE400-I LZMN3-VE400-I 1 off IEC/EN 60947-2


111958 111970
630 315630 12605040 4724410 LZMC3-VE630-I LZMN3-VE630-I Adjustable overload releases Ir
111959 111971 0.5 1 x In (ex-works 0.8 x In)

R.m.s. value measurement and thermal memory

Adjustable time delay setting to overcome current peaks tr


800 400800 16009600 8008000 LZMN4-VE800-I 2 20 s with 6 x Ir as well as infinity (without overload release) (ex-factory 10 s)
111982
1000 5001000 200012000 100010000 LZMN4-VE1000-I Adjustable delayed short-circuit releases Isd
111983 2 10 x Ir (ex-works 6 x Ir)
1250 6301250 250015000 125012500 LZMN4-VE1250-I LZM3-VE630-I: 1.5 7 x Ir (ex-works 6 x Ir)
111984
Adjustable delay time tsd
1600 8001600 320019200 160016000 LZMN4-VE1600-I Steps: 0, 20, 60, 100, 200, 300, 500, 750, 1000 ms (ex-works 0 ms)
111985
Adjustable non-delayed short-circuit releases Ii
LZM2 fixed 12 x In
LZM3-VE400-I: 2 11 x In (ex-works 6 x In)
LZM3-VE630-I: 2 8 x In (ex-works 6 x In)
LZM4-VE-I: 2 12 x In (ex-works 12 x In)
i2t constant function
LZM3, LZM4 switched (ex-works OFF)

Notes Notes for terminals a 29


12 Ordering Ordering 13
Circuit-breaker, thermomagnetic release, 4 pole Circuit-breaker, thermomagnetic release, 4 pole
LZM...1, LZM...2, LZM...3 Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM...1, LZM...2, LZM...3
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Ecconomic switching capacity Basic switching capacity Comfort switching capacity Normal switching capacity
18 kA at 415 V 50/60 Hz 25 kA at 415 V 50/60 Hz 36 kA at 415 V 50/60 Hz 50 kA at 415 V 50/60 Hz
Rated current = Setting range Part no. Price Part no. Price Part no. Price Part no. Price Std. pack Notes
rated Overload Neutral Short-circuit Article no. see price Article no. see price Article no. see price Article no. see price
uninterrupted releases conductor releases list list list list
current
In = Iu Ir Ir Ii
A A A A
I

Protection of systems and cables


4 pole
Terminals standard, terminal screws as accessories
20 1520 1520 350 LZME1-4-A20-I LZMB1-4-A20-I LZMC1-4-A20-I 1 off IEC/EN 60947-2
111828 111868 111908
25 2025 2025 350 LZME1-4-A25-I LZMB1-4-A25-I LZMC1-4-A25-I Adjustable overload releases Ir
111829 111869 111909 0.8 1 x In (ex-works 0.8 x In)
32 2532 2532 350 LZME1-4-A32-I LZMB1-4-A32-I LZMC1-4-A32-I Setting on neutral pole implemented via the main pole setting Ir of the main pole.
111830 111870 111910
40 3240 3240 320400 LZME1-4-A40-I LZMB1-4-A40-I LZMC1-4-A40-I Adjustable short-circuit releases Ii
111831 111871 111911 6 10 x In (ex-works 6 x In)
50 4050 4050 300500 LZME1-4-A50-I LZMB1-4-A50-I LZMC1-4-A50-I LZM-A40-I: 8 10 x In (ex-works 8 x In)
111832 111872 111912
Fixed short-circuit release Ii
63 5063 5063 380630 LZME1-4-A63-I LZMB1-4-A63-I LZMC1-4-A63-I 350 A at In = 20 32 A
111833 111873 111913 1280 A at In = 160 A (LZM1)
80 6380 6380 480800 LZME1-4-A80-I LZMB1-4-A80-I LZMC1-4-A80-I
111834 111874 111914 LZM..1-4-A
With 100 % overload and short-circuit protection in 4th pole
100 80100 80100 6001000 LZME1-4-A100-I LZMB1-4-A100-I LZMC1-4-A100-I LZM..2-4-A
111835 111875 111915 With 60 % overload and short-circuit protection in 4th pole
125 100125 100125 7501250 LZME1-4-A125-I LZMB1-4-A125-I LZMC1-4-A125-I
111836 111876 111916
160 125160 125160 1280 LZME1-4-A160-I LZMB1-4-A160-I LZMC1-4-A160-I
111837 111877 111917
Terminal screws standard, terminals as accessories
160 125160 80100 9601600 LZMB2-4-A160/100-I LZMC2-4-A160/100-I 1 off
111930 111948
200 160200 100125 12002000 LZMB2-4-A200/125-I LZMC2-4-A200/125-I
111931 111949
250 200250 125160 15002500 LZMB2-4-A250/160-I LZMC2-4-A250/160-I
111932 111950
300 240300 160200 15002500 LZMB2-4-A300/200-I LZMC2-4-A300/200-I
111933 111951
Terminal screws standard, terminals as accessories
320 250320 200250 19203200 LZMC3-4-A320/200-I LZMN3-4-A320/200-I 1 off
111960 111974
400 320400 240300 24004000 LZMC3-4-A400/250-I LZMN3-4-A400/250-I
111961 111975
500 400500 250320 30005000 LZMC3-4-A500/320-I LZMN3-4-A500/320-I
111962 111976

Notes Notes for terminals a 21


14 Ordering Ordering 15
Circuit-breaker, fixed overload releases, 4 pole Circuit-breaker, fixed overload releases, 4 pole
LZM1, LZM2 Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM1, LZM2
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Economic switching capacity Basic switching capacity Comfort switching capacity
18 kA at 415 V 50/60 Hz 25 kA at 415 V 50/60 Hz 36 kA at 415 V 50/60 Hz
Rated current = Setting range Part no. Price Part no. Price Part no. Price Std. Notes
rated Overload Neutral Short-circuit Article no. see price Article no. see price Article no. see price pack
uninterrupted releases conductor releases list list list
current
In = Iu Ir Ir Ii
A A A A
I

Protection of systems and cables


4 pole
Terminal standard, terminals screws as accessories
20 1520 1520 350 LZME1-4-ASF20-I LZMB1-4-ASF20-I LZMC1-4-ASF20-I 1 off IEC/EN 60947-2
111818 111858 111898
25 2025 2025 350 LZME1-4-ASF25-I LZMB1-4-ASF25-I LZMC1-4-ASF25-I Adjustable overload releases Ir
111819 111859 111899 0.8 1 x In (ex-works 0.8 x In)
32 2532 2532 350 LZME1-4-ASF32-I LZMB1-4-ASF32-I LZMC1-4-ASF32-I Setting on neutral pole implemented via the main pole setting Ir of the main pole.
111820 111860 111900
40 3240 3240 400 LZME1-4-ASF40-I LZMB1-4-ASF40-I LZMC1-4-ASF40-I Fixed short-circuit release Ii
111821 111861 111901 10 x In
50 4050 4050 500 LZME1-4-ASF50-I LZMB1-4-ASF50-I LZMC1-4-ASF50-I 350 A at In = 20/25/32 A (LZM1)
111822 111862 111902 1280 A at In = 160 A (LZM1)
2500 A at In = 300 A (LZM2)
63 5063 5063 630 LZME1-4-ASF63-I LZMB1-4-ASF63-I LZMC1-4-ASF63-I
111823 111863 111903 LZM..1-4-A
80 6380 6380 800 LZME1-4-ASF80-I LZMB1-4-ASF80-I LZMC1-4-ASF80-I With 100 % overload and short-circuit protection in 4th pole
111824 111864 111904 LZM..2-4-A
With 60 % overload and short-circuit protection in 4th pole
100 80100 80100 1000 LZME1-4-ASF100-I LZMB1-4-ASF100-I LZMC1-4-ASF100-I
111825 111865 111905
125 100125 100125 1250 LZME1-4-ASF125-I LZMB1-4-ASF125-I LZMC1-4-ASF125-I
111826 111866 111906
160 125160 125160 1280 LZME1-4-ASF160-I LZMB1-4-ASF160-I LZMC1-4-ASF160-I
111827 111867 111907
Terminal screws standard, terminals as accessories
160 125160 80100 1600 LZMB2-4-ASF160/100-I LZMC2-4-ASF160/100-I 1 off
111926 111944
200 160200 100125 2000 LZMB2-4-ASF200/125-I LZMC2-4-ASF200/125-I
111927 111945
250 200250 125160 2500 LZMB2-4-ASF250/160-I LZMC2-4-ASF250/160-I
111928 111946
300 240300 160200 2500 LZMB2-4-ASF300/200-I LZMC2-4-ASF300/200-I
111929 111947

Notes Notes for terminals a 25


16 Ordering Ordering 17
Circuit-breakers, electronic releases, 4 pole Circuit-breakers, electronic releases, 4 pole
LZM2, LZM3, LZM4 Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM2, LZM3, LZM4
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Comfort switching capacity Normal switching capacity
36 kA at 415 V 50/60 Hz 50 kA at 415 V 50/60 Hz
Rated current = rated Setting range Part no. Price Part no. Price Std. pack Notes
uninterrupted current Overload releases Short-circuit Delayed Article no. see price Article no. see price
releases short-circuit list list
Non-delayed release
In = Iu Ir Ii Isd
A A A A
I I

Protection of systems and cables


4 pole
Terminal screws standard, terminals as accessories
630 315630 12605040 LZMC3-4-AE630/400-I LZMN3-4-AE630/400-I 1 off IEC/EN 60947-2
111963 111977 Adjustable overload releases Ir
0.5 1 x In (ex-works 0.8 x In)
Setting on neutral pole implemented via the main pole setting Ir of the main pole.
R.m.s. value measurement and thermal memory

Adjustable short-circuit releases Ii


LZM...3-AE630-I: 2 8 x In (ex-works 6 x In)
800 400800 16009600 LZMN4-4-AE800/500-I LZM...4-4-AE...-I: 2 12 x In (ex-works 6 x In)
111986
1000 5001000 200012000 LZMN4-4-AE1000/630-I LZM...-4-AE.../...-I
111987 With 60 % overload and short-circuit protection in 4th pole
1250 6301250 250015000 LZMN4-4-AE1250/800-I
111988
1600 8001600 320019200 LZMN4-4-AE1600/1000-I
111989

Systems and cable protection, selectivity and generator protection


4 pole
Terminal screws standard, terminals as accessories
160 80160 1920 1601600 LZMC2-4-VE160/100-I 1 off IEC/EN 60947-2
111952 Adjustable overload releases Ir
250 125250 3000 2502500 LZMC2-4-VE250/160-I 0.5 1 x In (ex-works 0.8 x In)
111953 Setting on neutral pole implemented via the main pole setting Ir of the main pole.
R.m.s. value measurement and thermal memory
400 200400 8004400 4004000 LZMC3-4-VE400/250-I LZMN3-4-VE400/250-I Adjustable delayed short-circuit releases Isd
111964 111972 2 10 x Ir (ex-works 6 x Ir)
LZM3-VE630-I: 1.5 7 x Ir (ex-works 6 x Ir)
630 315630 12605040 4724410 LZMC3-4-VE630/400-I LZMN3-4-VE630/400-I
111965 111973
Adjustable delay time tsd
Steps: 0, 20, 60, 100, 200, 300, 500, 750, 1000 ms (ex-works 0 ms)

Adjustable short-circuit releases Ii


800 400800 16009600 8008000 LZMN4-4-VE800/500-I LZM2: fixed 12 x In
111990 LZM...3-4-VE400-I: 2 11 x In (ex-works 6 x In)
1000 5001000 200012000 100010000 LZMN4-4-VE1000/630-I LZM...3-4-VE630-I: 2 8 x In (ex-works 6 x In)
111991 LZM...4-4-VE...-I: 2 12 x In (ex-works 12 x In)
1250 6301250 250015000 125012500 LZMN4-4-VE1250/800-I i2t constant function (ex-works OFF)
111992 LZM2 fixed OFF
1600 8001600 320019200 160016000 LZMN4-4-VE1600/1000-I LZM3, LZM4 switched (ex-works OFF)
111993
LZM...-4-AE.../...-I
With 60 % overload and short-circuit protection in 4th pole

Notes Notes for terminals a 29


18 Ordering
Switch-disconnectors 3 pole, 4 pole
LN1, LN2, LN3, LN4 Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

3 switch positions I, +, 0;
can be tripped remotely with shunt/undervoltage release
3 pole 4 pole
Rated current = Short-circuit Part no. Price Part no. Price Std. pack
rated uninterrupted protection max. fuse Article no. see price Article no. see price
current gL-characteristic list list
In = Iu
A A gL

Switch-disconnectors
Terminals standard, terminal screws as accessories
63 125 LN1-63-I LN1-4-63-I 1 off
111994 111998
100 125 LN1-100-I LN1-4-100-I
111995 111999
125 125 LN1-125-I LN1-4-125-I
111996 112000
160 160 LN1-160-I LN1-4-160-I
111997 112001
Terminal screws standard, terminals as accessories
160 250 LN2-160-I LN2-4-160-I 1 off
112002 112005
200 250 LN2-200-I LN2-4-200-I
112003 112006
250 250 LN2-250-I LN2-4-250-I
112004 112007

400 630 LN3-400-I LN3-4-400-I


112008 112010
630 630 LN3-630-I LN3-4-630-I
112009 112011
800 1600 LN4-800-I LN4-4-800-I
112012 112016

1000 1600 LN4-1000-I LN4-4-1000-I


112013 112017
1250 1600 LN4-1250-I LN4-4-1250-I
112014 112018
1600 1600 LN4-1600-I LN4-4-1600-I
112015 112019

Notes Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113
Isolating characteristics to IEC/EN 60947-3 and VDE 0660
Protection against accidental contact according to IEC 100
Notes for terminals a 21
Notes 19

http://catalog.moeller.net Moeller SK1230-1177GB

Circuit-breakers, switch-disconnectors
20 Ordering Ordering 21
Connection types Connection types
LZM1 Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM1
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Part no. Price
Max. cable connection For use with Terminal capacities Terminal capacities Article no. when see price Std. pack Notes
area ordered separately list
Type of conductor AWG/kcmil Cu strip (number of segments Copper busbar width x
x width x segment thickness
thickness)

mm2 mm mm

Box terminal
Standard equipment
LZM1(-4) Three- and four-pole Cu cable 1 x 10 701) 1 x 8 2/0 2 x 9 x 0.8 NZM1-XKC 1 off Standard connection with all switches LZM1 and LN1.
LN1(-4) 2 x 6 25 2x94 9 x 9 x 0.8 260015 Conversion kit for circuit-breaker with screw connection.
10

Type contains parts for a 3 or 4-pole switch side.


NZM1-4-XKC 1 off Fitted within the switch housing
12 267075

Screw connection
LZM1(-4) Three- and four-pole Copper cable lugs 1 x 10 70 1 x 8 2/0 min. 12 x 5 NZM1-XKS 1 off Type contains parts for a terminal located at top or
LN1(-4) 2 x 6 25 2x94 max. 16 x 5 260019 bottom for 3 or 4-pole circuit-breakers.
Aluminium cable lug 1 x 10 35 1x82 min. 12 x 5 NZM1-4-XKS 1 off Fitted outside the switch housing
2 x 10 35 2x82 max. 16 x 5 266725 Mounting of the cover NZM1(-4)-XKSA obligatory
o 6.5 (supplied).
7

16

Tunnel terminal
LZM1(-4) Three- and four-pole Copper cable 1 x 16 95 1 x 6 3/0 NZM1-XKA 1 off Type contains parts for a terminal located at top or
LN1(-4) Al cable 266730 bottom for 3 or 4-pole circuit-breakers.
NZM1-4-XKA 1 off A standard with control circuit terminal for
14.5 266731 1 x 0.75 2.5 mm2 (18 14 AWG) or
2 x 0.75 1.5 mm2 (18 14 AWG) copper conductors.
Fitted outside the switch housing
Use with flexible and highly flexible conductors ferrules.
Maximum specified cross-section can only be connected
when stranded and without ferrules.
Mounting of the cover NZM1(-4)-XKSA obligatory
(supplied).

Connection on rear
LZM1(-4) Three- and four-pole Copper cable lugs 1 x 2.5 25 F 12 x 5 NZM1-XKR 1 off Type contains parts for a terminal located at top or
LN1(-4) 2 x 2.5 25 F 16 x 5 266734 bottom for 3 or 4-pole circuit-breakers.
Aluminium cable lug 1 x 10 35 NZM1-4-XKR 1 off
2 x 10 35 266737

Notes 1) Up to 240 mmB can be connected depending on the cable manufacturer.


22 Ordering Ordering 23
Connection types Connection types
LZM1 Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM1
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Part no. Price
Max. cable connection For use with Terminal capacities Article no. when see price Std. pack Notes
area ordered separately list
Type of conductor AWG/kcmil

mm2

Control circuit terminal


LZM1(-4) Three- and four-pole Screw connection 1 x 0.75 2.5 1 x 18 14 NZM1-XSTS 1 off Type contains parts for two terminal locations located at top or bottom for 3 or 4-pole circuit-breakers.
LN1(-4) 2 x 0.75 1.5 2 x 18 16 260150 Included as standard with tunnel terminal
Degree of protection IP1X
Box terminal NZM-XSTK 1 off NZM-XSTK cannot be combined with NZM1(-4)-XIPK IP2X protection against contact with a finger.
266739 Height or thickness of the control terminals:
NZM-XSTK = 2 mm
NZM-XSTS = 2 mm

Cover
LZM1(-4) 3 pole NZM1-XKSA 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
LN1(-4) 260021 Protection against direct contact where cable lugs, busbars or tunnel terminals are used
4 pole NZM1-4-XKSA 1 off Contained in kit with tunnel terminals or screw connection terminals.
266741 Degree of protection IP1X on the connection side when using insulated conductor material.

Terminal cover, knockout


For box terminals
LZM1 3-pole NZM1-XKSFA 1 off Type contains parts for a terminal located at top or bottom for 3 or 4 pole circuit-breakers.
LN1 100780 Enhancement of the protection against direct contact (simple finger protection).
LZM1-4 4 pole NZM1-4-XKSFA 1 off
LN1-4 100781

IP2X protection against contact with a finger


For box terminals
LZM1 3 pole NZM1-XIPK 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
LN1 266744 Enhancement of the protection against direct contact to IP2X.
LZM1-4 4 pole NZM1-4-XIPK 1 off Protection when reaching into the cable connection area with the connection of cables in the box terminal.
LN1-4 266745 Cannot be combined with NZM-XSTK control circuit terminal.

For cover NZM1(-4)-XKSA


LZM1 3 pole NZM1-XIPA 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
LN1 266748 Enhancement of the protection against direct contact to IP2X.
LZM1-4 4 pole NZM1-4-XIPA 1 off
LN1-4 266749
24 Ordering Ordering 25
Connection types Connection types
LZM2 Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM2
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Max. cable For use with Terminal capacities Terminal capacities Part no. Price Part no. Price Std. Notes
connection area Type of Terminal AWG/kcmil Cu strip (number of Copper busbar Article no. when ordered see price Article no. when ordered see price pack
conductor capacities segments x width x width x with basic unit list separately list
segment thickness) thickness

mm2 mm mm

Box terminal
LZM2(-4) Three- Copper 1 x 4 185 1 x 11 350 f 2 x 9 x 0.8 +NZM2-160-XKCO NZM2-160-XKC 1 off Type suffix and type contain parts for a circuit-breaker
LN2(-4) and four- conductors 2 x 4 70 2 x 12 2/0 262218 262240 side at top or bottom for 3 or 4 pole circuit-breakers.
pole Cu cable +NZM2-160-XKCU Conversion kit for circuit-breaker with screw connection.
15

262223 Fitted within the switch housing


O = for fitting at the top
18 +NZM2-250-XKCO NZM2-250-XKC U = for fitting at the bottom
262242 262244 Ue f 525 V AC:
+NZM2-250-XKCU Use cover NZM2(4)-XKSA.
262243 Use ferrules with flexible and highly flexible conductors.
+NZM2-4-160-XKCO NZM2-4-160-XKC Max. cross section shown can only be connected when
266751 266755 flexible and without ferrules.
+NZM2-4-160-XKCU
266753
+NZM2-4-250-XKCO NZM2-4-250-XKC
266752 266756
+NZM2-4-250-XKCU
266754
Screw connection
Standard equipment
LZM2(-4) Three- Copper cable 1 x 4 185 1 x 11 3/0 f 2 x 16 x 0.8 f 16 x 5 NZM2-XKS 1 off Type contains parts for a terminal located at top or
LN2(-4) and four- lugs 2 x 4 70 2 x 12 260030 bottom for 3 or 4 pole circuit-breakers.
pole 1 x 10 50 1 x 8 1/0 Standard connection with all LZM2 circuit-breakers.
Aluminium cable 2 x 10 50 2 x 8 1/0 Conversion kit for circuit-breaker with box terminal.
o 8.5
8

lug Use special cable lug narrow version, a 27


24 NZM2-4-XKS 1 off Fitted within the switch housing
266750 If a busbar is used, insulation (400 mm) e.g sleeving and
a NZM2(-4)-XKSA cover are required.
Ue f 525 V AC:
For all other connection material a NZM2(-4)-XKSA
shroud must be used.

Tunnel terminal
LZM2(-4) Three- Copper cable 1 x 16 185 1 x 6 350 NZM2-XKA 1 off Type contains parts for a terminal located at top or
LN2(-4) and four- Al cable 1 x 16 185 271457 bottom for 3 or 4-pole circuit-breakers.
pole A standard with control circuit terminal for
1 x 0.75 2.5 mm2 (18 14 AWG) or
20.5 2 x 0.75 1.5 mm2 (18 16 AWG) copper conductors.
NZM2-4-XKA 1 off Fitted outside the switch housing
271458 Use with flexible and highly flexible conductors ferrules.
Maximum specified cross-section can only be connected
when stranded and without ferrules.
Mounting of the cover NZM2(-4)-XKSA obligatory
(supplied).

Connection on rear
When using cable lugs without NZM3(-4)-XKSA cover, they must be insulated.
LZM2(-4) Three- Copper cable 1 x 4 185 f 2 x 16 x 0.8 f 16 x 5 +NZM2-XKRO NZM2-XKR 1 off Type suffix and type contain parts for a circuit-breaker
LN2(-4) and four- lugs 2 x 4 70 F 6 x 24 x 0.5 F 20 x 5 266763 266765 side at top or bottom for 3 or 4-pole circuit-breakers.
pole 1 x 10 50 +NZM2-XKRU NZM2-4-XKR O = for fitting at the top
Aluminium cable 2 x 10 50 266764 266768 U = for fitting at the bottom
lug
+NZM2-4-XKRO
266766
+NZM2-4-XKRU
266767
Notes 1) Up to 240 mmB can be connected depending on the cable manufacturer.
26 Ordering Ordering 27
Connection types Connection types
LZM2 Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM2
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Max. cable connection For use with Terminal capacities Part no. Price Std. Notes
area Type of conductor Terminal capacities AWG/kcmil Copper busbar Article no. when ordered see price pack
width x separately list
thickness
mm
mm2

Control circuit terminal


LZM2(-4) Three- and four- Screw connection 1 x 0.75 2.5 1 x 18 14 NZM2-XSTS 1 off Type contains parts for two terminal locations located at top or bottom for 3 or 4-pole circuit-
LN2(-4) pole 2 x 0.75 1.5 2 x 18 16 260156 breakers.
Included as standard with tunnel terminal
Degree of protection IP1X
NZM-XSTK cannot be combined with NZM2(-4)-XIPK IP2X protection against contact with a finger.
LZM2(-4) Three- and four- Box terminal 1 x 0.75 2.5 1 x 18 14 NZM-XSTK 1 off Height or thickness of the control circuit terminals:
LN2(-4) pole 2 x 0.75 1.5 2 x 18 16 266739 NZM-XSTK = 2 mm
NZM-XSTS = 2 mm

Cover
LZM2 3 pole NZM2-XKSA 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
LN2 260038 Protection against direct contact where cable lugs, busbars or tunnel terminals are used
LZM2-4 4 pole NZM2-4-XKSA 1 off Degree of protection IP1X on the connection side when using insulated conductor material.
LN2-4 266770

Connection cover, knockout


LZM2 3 pole NZM2-XKSFA 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
LN2 104640 Enhancement of the protection against direct contact (simplified protection against contact with a
finger).
LZM2-4 4 pole NZM2-4-XKSFA 1 off
LN2-4 104641
IP2X protection against contact with a finger
For box terminals
LZM2 3 pole NZM2-XIPK 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
LN2 266773 Enhancement of the protection against direct contact to IP2X.
Protection when reaching into the cable connection area with the connection of cables in the box
LZM2-4 4 pole NZM2-4-XIPK 1 off terminal.
LN2-4 266774 With 2 conductors minimum cross-section 25 mm2.
Cannot be combined with NZM-XSTK control circuit terminal.
For covers NZM2(-4)-XKSA or NZM2(-4)
LZM2 3 pole NZM2-XIPA 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
LN2 266777 Enhancement of the protection against direct contact to IP2X.
LZM2-4 4 pole NZM2-4-XIPA 1 off
LN2-4 266778

Copper cable lug


When using cable lugs without NZM3(-4)-XKSA cover, they must be insulated.
95 mm2 LZM2(-4) Three- and four- KS95-NZM7 3 off Type contains a cable lug for 3-pole or 4-pole switches.
LN2(-4) pole 059775 Special cable lug, narrow style
120 mm2 KS120-NZM7
059776
150 mm2 KS150-NZM7
059777
185 mm2 NZM2-XKS185
260032
28 Ordering Ordering 29
Connection types Connection types
LZM3 Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM3
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Max. cable connection Rated For use with Terminal capacities Terminal capacities Part no. Price Part no. Price Std. pack Notes
area current1) Article no. when see Article no. when see
In Type of Terminal AWG/kcmil Cu strip (number of Copper busbar ordered with price ordered price
conductor capacities segments x width x width x basic unit list separately list
segment thickness) thickness
A mm2 mm mm

Box terminal
max. 500 LZM3(-4) Three- and Copper 1 x 35 240 1 x 2 500 min. 6 x 16 x 0.8 +NZM3-XKCO NZM3-XKC 1 off Type suffix and type contain parts for a circuit-
400 UL/CSA LN3(-4) four-pole conductors 2 x 16 120 max. 20 x 24 x 0.5 262246 260042 breaker side at top or bottom for 3 or 4-pole
Cu cable or +NZM3-XKCU circuit-breakers.
16

max. 11 x 21 x 1 262245 Conversion kit for circuit-breaker with screw


connection.
630 1 x 35 240 1 x 2 500 min. 6 x 16 x 0.8 +NZM3-4-XKCO NZM3-4-XKC Fitted within the switch housing
25
2 x 16 120 max. 20 x 24 x 0.5 266781 266783 O = for fitting at the top
or +NZM3-4-XKCU U = for fitting at the bottom
max. 11 x 21 x 1 266782 Ue f 525 V AC:
Use NZM3(-4)-XKSA cover.
Use with flexible and highly flexible conductors
ferrules, note the max. terminal capacity when
using ferrules.

Screw connection
630 LZM3(-4) Three- and Copper cable 1 x 16 240 1 x 4 350 10 x 32 x 1.0 30 x 10 NZM3-XKS 1 off Type contains parts for a terminal located at top or
LN3(-4) four-pole lugs 2 x 16 240 2 x 350 + 5 x 32 x 1.0 + 30 x 5 260039 bottom for 3 or 4-pole circuit-breakers.
15

max. 400 1 x 10 120 NZM3-4-XKS 1 off Standard connection with all LZM3 circuit-breakers
Aluminium 2 x 10 120 266780 and LN3 switch-disconnectors.
o 10.5 cable lug Conversion kit for circuit-breaker with box
32 terminal.
Use special cable lugs narrow version, a 32
Fitted within the switch housing
When a busbar is used insulation is required
(400 mm) e.g. using heat shrink and a shroud
NZM3(-4)-XKSA.
Ue f 525 V AC:
A shroud NZM3(-4)-XKSA must be used with all
other connection types.

Connection width extension


630 LZM3(-4) Three- and Copper cable 2 x 300 2 x 500 (2 x) 10 x 50 x 1.0 (2 x) 10 x 50 NZM3-XKV70 1 off Type contains parts for a terminal located at top or
LN3(-4) four-pole lugs 100514 bottom for 3 or 4 pole circuit-breakers.
NZM3-4-XKV70 1 off Central drill holes, e.g. for up to 2 cable lugs per
Aluminium 100515 phase.
cable lug Can be fitted to circuit-breaker with screw
termination
Phase isolator supplied.
Distance between pole centres with
NZM3(-4)-XKV70: 70 mm
Drill hole available for control cable.
Connection terminals NZM3(-4)-XK300 and
NZM3(-4)-XK22X21 can be installed.

Notes 1) The following applies for the rated current: The values have been determined conform
to IEC/EN 60947 (switchgear standard) and generally relate to the max. defined cross-
sections and are intended for the purpose of orientation.
30 Ordering Ordering 31
Connection types Connection types
LZM3 Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM3
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Max. cable Rated For use with Terminal capacities Terminal capacities Part no. Price Part no. Price Std. Notes
connection area current1) Article no. when see Article no. when see pack
Type of Terminal AWG/kcmil Cu strip (number of Copper ordered with price ordered price
conductor capacities segments x width x busbar width basic unit list separately list
In segment thickness) x thickness
A mm2 mm mm

Terminals for connection width extension


max. 500 LZM3, LN3 3 pole Cu cable 1 x 120 300 NZM3-XK300 1 off Type contains parts for a terminal located at
100782 top or bottom for 3 or 4-pole circuit-breakers.
LZM3-4, LN3-4 4 pole NZM3-4-XK300 1 off Only in conjunction with connection width
100783 extension NZM3(-4)-XKV70.
Use with flexible and highly flexible conductors
630 LZM3, LN3 3 pole (2 x) 11 x 21 x 1.0 NZM3-XK22X21 1 off ferrules.
100784 Standard with control circuit terminal for
LZM3-4, LN3-4 4 pole (2 x) 11 x 21 x 1.0 NZM3-4- 1 off 1 x 0.75 2.5 mm2 or 2 x 0.75 1.5 mm2
XK22X21 copper conductors.
100785
Tunnel terminal
max. 350 LZM3(-4) Three- and four- Copper 1 x 16 1852) 1 x 6 350 NZM3-XKA1 1 off Type contains parts for a terminal located at
LN3(-4) pole conductors 271459 top or bottom for 3 or 4-pole circuit-breakers.
Cu cable NZM3-4-XKA1 1 off A standard with control circuit terminal for
Al 271460 1 x 0.75 2.5 mm2 (18 14 AWG) or
conductors 2 x 0.75 1.5 mm2 (18 16 AWG)
Al cable copper conductors.
20.5 Fitted outside the switch housing
Use with flexible and highly flexible conductors
ferrules. Maximum specified cross-section can only
max. 630 1 x 50 240 1 x 0 500 NZM3-XKA2 1 off be connected when stranded and without ferrules.
2 x 50 240 2 x 0 500 271461 Mounting of the cover NZM3(-4)-XKSA obligatory
(supplied).
NZM3-4-XKA2 1 off
271462

22.5

Connection on rear
not UL/CSA approved
max. 630 LZM3(-4) Three- and four- Copper 1 x 16 240 +NZM3-XKRO NZM3-XKR 1 off Type suffix and type contain parts for a circuit-
LN3(-4) pole cables 2 x 16 240 266790 266792 breaker side at top or bottom for 3 or 4-pole circuit-
Cu cable +NZM3-XKRU NZM3-4-XKR 1 off breakers.
266791 266795 O = for fitting at the top
U = for fitting at the bottom
+NZM3-4-XKRO
266793
+NZM3-4-XKRU
266794
max. 500 1 x 10 120 min.6 x 16 x 0.8 Min. 20 x 5
2 x 10 120 Max. 10 x 32 x 1.0 Max. 30 x 10
Control circuit terminal
LZM3(-4) Three- and four- Screw 1 x 0.75 2.5 1 x 18 14 NZM3/4-XSTS 1 off Type contains parts for two terminal locations
LN3(-4) pole connection 2 x 0.75 1.5 2 x 18 16 266797 located at top or bottom for 3 or 4 pole circuit-
breakers.
Included as standard with tunnel terminal
Degree of protection IP1X
LZM3(-4) Box NZM-XSTK 1 off Height or thickness of the control circuit terminals
LN3(-4) terminal 266739 NZM-XSTS = 2 mm

Notes 1) The following applies for the rated current: The values have been determined conform to
IEC/EN 60947 (switchgear standard) and generally relate to the max. defined cross-sections
and are intended for the purpose of orientation.
The engineering standards which apply in each case must be observed.
32 Ordering Ordering 33
Connection types Connection types
LZM3 Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM3
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Max. cable connection For use with Part no. Price Std. pack Notes
area Article no. when see price
ordered separately list

Cover
LZM3(-4) 3 pole NZM3-XKSA 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
LN3(-4) 260045 Insulation/protection against direct contact where cable lugs, busbars or tunnel terminals are used.
4 pole NZM3-4-XKSA 1 off Included in set with tunnel terminals
266801 Degree of protection IP1X on the connection side when using insulated conductor material.

Phase isolator
LZM3(-4) 3 pole NZM3-XKP 1 off Type contains parts for a terminal located at top or bottom for 3 or 4 pole circuit-breakers.
LN3(-4) 100512 Included with the connection width extension.
4 pole NZM3-4-XKP 1 off Cannot be combined with the NZM3(-4)-XKA tunnel terminal, NZM3(-4)-XKR connection on rear.
100513 Insulation protection with connection of cable lugs, busbars or braid.

Connection cover, knockout


LZM3(-4) 3 pole NZM3-XKSFA 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
LN3(-4) 104642 Enhancement of the protection against direct contact to (simplified protection against contact with a finger).
4 pole NZM3-4-XKSFA 1 off
104643
IP2X protection against contact with a finger
LZM3(-4) 3 pole NZM3-XIPK 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
LN3(-4) 266804 Enhancement of the protection against direct contact to IP2X.
4 pole NZM3-4-XIPK 1 off Protection when reaching into the cable connection area with the connection of cables in the box terminal.
266805 With 2 conductors minimum cross-section 70 mm2.
Cannot be combined with NZM-XSTK control circuit terminal.

For cover NZM3(-4)-XKSA


LZM3(-4), LN3(-4) 3 pole NZM3-XIPA 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
266808 Enhancement of the protection against direct contact to IP2X.
4 pole NZM3-4-XIPA 1 off
266809

Copper cable lug


When using cable lugs without NZM3(-4)-XKSA cover, they must be insulated.
185 mm2 LZM3(-4), LN3(-4) 3 and 4 pole NZM3-XKS185 3 off Type contains a cable lug for 3-pole or 4-pole switches.
LZM4(-4), LN4(-4) 260040 Special cable lug, narrow style

900 mm2 3 and 4 pole NZM3-XKS240 3 off


260041
34 Ordering Ordering 35
Connection types Connection types
LZM4 Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM4
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Max. cable connection area Rated For use with Terminal capacities Terminal capacities Part no. Price Std. pack Notes
current1) Article no. when see price
Type of Terminal AWG/kcmil Cu strip (number of Copper busbar width ordered separately list
conductor capacities segments x width x x thickness
In segment thickness)

A mm2 mm mm

Screw connection
Standard equipment
2-hole max. 1250 LZM4(-4) Three- and Cu cable lugs 1 x 120 185 1 x 250 350 (2 x) 10 x 50 x 1.0 (2 x) 50 x 10 off Double hole fitting for M10 screws with 25 mm clearance.
LN4(-4) four-pole 4 x 50 185 4 x 0 350 Use special cable lug narrow version.

20
Ue f 525 V or cross-section > 185 mm2: Use of shroud NZM4(-4)-
XKSA required.
o10.5 o10.5 1600 off
25
50

Module plate
Single max. 1250 LZM4, LN4 3 pole Copper cable 1 x 120 300 1 x 250 600 (2 x) 10 x 40 x 1.0 (2 x) 40 x 10 NZM4-XKM1 1 off Type contains parts for a terminal located at top or bottom for 3 or
hole lugs 2 x 95 300 2 x 000 600 (2 x) 10 x 50 x 1.0 (2 x) 50 x 10 266814 4-pole circuit-breakers.
LZM4-4 4 pole NZM4-4-XKM1 1 off For M10 screws. Can be enlarged for M12 screws.
LN4-4 266815 Use special cable lug narrow version.
Can be fitted to circuit-breaker with screw termination
Double max. 1400 LZM4, LN4 3 pole Copper cable 2 x 95 185 2 x 000 350 NZM4-XKM2 1 off Insulation through NZM4(-4)-XKSA cover or NZM4(-4)-XKP phase
hole lugs 4 x 35 185 4 x 2 350 266820 separator necessary
LZM4-4 4 pole 4 x 50 NZM4-4-XKM2 1 off
LN4-4 266821
Double max. 1250 LZM4, LN4 3 pole Copper cable 2 x 95 300 2 x 000 600 NZM4-XKM2S- 1 off Type contains parts for a terminal located at top or bottom for 3 or
hole lugs 1250 4-pole circuit-breakers.
284471 Insulation through cover NZM4(-4)-XKSA or phase isolator
LZM4-4 4 pole NZM4-4-XKM2S- 1 off NZM4(4)-XKP necessary.
LN4-4 1250
284472
max. 1600 LZM4, LN4 3 pole Copper cable 2 x 95 300 2 x 000 500 NZM4-XKM2S- 1 off
lugs 1600
284473
LZM4-4 4 pole 2 x 95 300 2 x 000 500 NZM4-4-XKM2S- 1 off
LN4-4 1600
284474
Connection width extension
max. 1600 LZM4, LN4 3 pole Cu cable lugs 4 x 300 4 x 600 min. 10 x 50 x 1.0 max. (2 x) 80 x 10 NZM4-XKV95 1 off Type contains parts for a terminal located at top or bottom for 3 or
6 x 95 240 6 x 000 281591 4-pole circuit-breakers.
500 NZM4-XKV110 1 off Five way holes, e.g. for up to 9 cable lugs per phase.
281593 Can be fitted to circuit-breaker with screw termination
Phase isolator supplied.
LZM4-4 4 pole NZM4-4-XKV95 1 off Distance between pole centres with NZM4(-4)-XKV95: 95 mm
LN4-4 281592 Installation conditions for current transformer up to 130 mm width
NZM4-4-XKV120 1 off with 80 mm busbar width.
281594 Distance between pole centres with NZM4-XKV110: 107.5 mm
Installation conditions for current transformer up to 135 mm width
with 80 mm busbar width.
Distance between pole centres with NZM4-4-XKV120: 122 mm
Installation conditions for current transformer up to 164 mm width
with 80 mm busbar width.
4 mm drilled holes for control circuit terminal available.

Notes 1) Thefollowing applies for the rated current: The values have been determined conform to IEC/EN 60947
(switchgear standard) and generally relate to the max. defined cross-sections and are intended for the
purpose of orientation.
36 Ordering Ordering 37
Connection types Connection types
LZM4 Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM4
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Max. cable connection area Rated For use with Terminal Terminal capacities Part no. Price Std. pack Notes
current1) capacities Article no. when see price
In Type of Terminal AWG/kcmil Cu strip (number of Copper busbar ordered separately list
conductor capacities segments x width x width x
segment thickness) thickness
A mm
mm2 mm

Flat cable terminal


max. 1100 LZM4, LN4 3 pole min.6 x 16 x 0.8 NZM4-XKB 1 off Type contains parts for a terminal located at top or bottom
max. (2 x) 10 x 32 x 1.0 266829 for 3 or 4-pole circuit-breakers.
LZM4-4 4 pole min.6 x 16 x 0.8 NZM4-4-XKB 1 off Conversion kit for circuit-breaker with screw connection.
LN4-4 max. (2 x) 10 x 32 x 1.0 266831 Insulation through cover NZM4(-4)-XKSA or phase isolator
NZM4(4)-XKP necessary.
With switch mpunting on conductive mounting plates use
of the shroud NZM4(-4)-XKSA necessary (supplied item).

Tunnel terminal
max. 1400 LZM4, LN4 3 pole Copper 1 x 50 240 1 x 0 500 NZM4-XKA 1 off Type contains parts for a terminal located at top or bottom
conductors 4 x 50 240 4 x 0 500 266836 for 3 or 4 pole circuit-breakers.
LZM4-4 4 pole Cu cable 1 x 50 240 1 x 0 500 NZM4-4-XKA 1 off A standard with control circuit terminal for
LN4-4 Al 4 x 50 240 4 x 0 500 266837 1 x 0.75 2.5 mm2 (18 14 AWG) or
conductors 2 x 0.75 1.5 mm2 (18 16 AWG) copper conductors.
Al cable Can be fitted to circuit-breaker with screw termination
22.5 Use ferrules with flexible and highly flexible conductors. Max.
cross section shown can only be connected when flexible and
without ferrules.
Use of the NZM4(-4)-XKSA cover obligatory(supplied).

Connection on rear
max. 1250 LZM4(-4) Three- and Copper cable 1 x 120 185 (2 x) 10 x 50 x 1.0 (2 x) 50 x 10 NZM4-XKR 1 off Type contains parts for a terminal located at top or bottom
LN4(-4) four-pole lugs 2 x 95 185 266842 for 3 or 4-pole circuit-breakers.
4 x 35 185 NZM4-4-XKR 1 off Can also be retrofitted:
1 x 185 266843 NZM4...-XKM... module plate or NZM4-...-XKV... connection
Aluminium 2 x 70 185 width extension
cable lug 4 x 50 185
1600 off

Notes 1) The following applies for the rated current: The values have been determined conform to IEC/EN 60947
(switchgear standard) and generally relate to the max. defined cross-sections and are intended for the purpose
of orientation.
38 Ordering Ordering 39
Connection types Connection types
LZM4 Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM4
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Max. cable connection area For use with Terminal capacities Part no. Price Std. pack Notes
Article no. when ordered see price
Type of conductor Terminal AWG/kcmil separately list
capacities

mm2

Control circuit terminal


LZM3(-4) Three- and Screw connection 1 x 0.75 2.5 1 x 18 14 NZM3/4-XSTS 1 off Type contains parts for two terminal locations located at top or bottom for 3 or 4 pole circuit-breakers.
LN3(-4) four-pole 2 x 0.75 1.5 2 x 18 16 266797 Included as standard with tunnel terminal
Degree of protection IP1X
Height or thickness of the control circuit terminals
NZM-XSTS = 2 mm

Cover
LZM4 3 pole NZM4-XKSA 1 off Type contains parts for a terminal located at top or bottom for 3 or 4 pole circuit-breakers.
LN4 266846 Protection against direct contact where cable lugs, busbars, flat cable terminals or tunnel terminals are used.
LZM4-4 4 pole NZM4-4-XKSA With module plates, flat braid terminals and tunnel terminals included in the kit.
LN4-4 266847 When using insulated conductor material to degree of protection: IP1X.

Connection cover, knockout


LZM4 3 pole NZM4-XKSFA 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
LN4 292193 Enhancement of the protection against direct contact to (simplified protection against contact with a finger).
LZM4-4 4 pole NZM4-4-XKSFA
LN4-4 292194

Phase isolators
LZM4 3 pole NZM4-XKP 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
LN4 281595 Included with the connection width extension.
Cannot be combined with the tunnel terminal NZM4(-4)-XKA, connection NZM4-XKR on rear.
Insulation protection where cable lugs, busbars, module plates or flat cable terminals are used.
LZM4-4 4 pole NZM4-4-XKP
LN4-4 281596

Cable lug
185 mm2 LZM3(-4) 3 and 4 pole NZM3-XKS185 3 off Type contains a cable lug for 3-pole or 4-pole switches.
LZM4(-4) 260040 Special cable lug, narrow style
900 mm2 LN3(-4) NZM3-XKS240
LN4(-4) 260041
40 Ordering
Plug-in units
NZM2-XSV Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

For use with Number of poles Part no. Price Part no. Price Std. Notes
Article no. when see price Article no. when see price pack
ordered with list ordered list
basic unit separately

Plug-in and withdrawable units


For circuit-breakers LZM and switch-disconnectors LN
Plug-in adapter elements
Complete
Only in combination with circuit-breaker
Terminal screws standard, terminals as accessories
LZM2 3 pole +NZM2-XSV 1 off Inmax. at:
LN2 266697 20 C: 250 A
LZM2-4 4 pole +NZM2-4-XSV 40 C: 230 A (LZM...2-...)
LN2-4 266698 Mounting position: vertical,
90 right, 90 left
Order control circuit plug unit
separately!

Sockets
e.g. for reserved slots
Retrofit of circuit-breaker with plug-in module.
Terminal screws standard, terminals as accessories

LZM2 3 pole NZM2-XSVS 1 off


LN2 266699
LZM2-4 4 pole NZM2-4-XSVS
LN2-4 266700

Removable module
Fits socket base
Only in combination with circuit-breaker
LZM2 3 pole +NZM2-XSVE 1 off
LN2 266701
LZM2-4 4 pole +NZM2-4-XSVE
LN2-4 266702

Control circuit plug unit


LZM2(-4) for auxiliary contact, NZM2-XSVHI 1 off
LN2(-4) shunt/undervoltage 266705
release
LZM2(-4) for remote operator NZM2-XSVR
LN2(-4) 266706
Ordering 41
Withdrawable units
http://catalog.moeller.net Moeller SK1230-1177GB NZM3-XAV

Circuit-breakers, switch-disconnectors
For use with Number of Part no. Price Part no. Price Std. Notes
poles Article no. when see price Article no. when see price pack
ordered with basic list ordered list
unit separately

Withdrawable unit
with control circuit plug unit
For circuit-breakers LZM and switch-disconnectors LN
Withdrawable unit with auxiliary plug-in adapter
Complete
Only in combination with circuit-breaker
Terminal screws standard, terminals as accessories
LZM3 3 pole +NZM3-XAV 1 off Inmax. at:
LN3 266707 20 C: 605 A (LZM3), 1600 A
LZM3-4 4 pole +NZM3-4-XAV (LZM4)
LN3-4 266708 40 C: 550 A (LZM3), 1500 A
(LZM4)
LZM4 3 pole +NZM4-XAV
LN4 266709 Mounting position
LZM4-4 4 pole +NZM4-4-XAV LZM3: vertical, 90 left
LN4-4 266710 LZM4: vertical

3 positions
Connected, test, disconnected
The 3 positions are indicated
mechanically.

Socket base Additionally, auxiliary contacts


e.g. for reserved slots are use for remote signalling. An
Retrofit of circuit-breaker with withdrawable carrier. optional M22-(C)K01normally
closed contact or M22-(C)K10
normally open contact per
Terminal screws standard, terminals as accessories position
LZM3 3 pole NZM3-XAVS 1 off Also see the RMQ-Titan
LN3 266711 control circuit device range in the
LZM3-4 4 pole NZM3-4-XAVS Main Catalogue
LN3-4 266712
All connections of auxiliary
LZM4 3 pole NZM4-XAVS switches (HIA, HIN, HIV) and
LN4 266713 voltage releases to the control
LZM4-4 4 pole NZM4-4-XAVS circuit plug units are already
LN4-4 266714 present.

Withdrawable carrier
LZM3 3 pole +NZM3-XAVE 1 off
LN3 266715
LZM3-4 4 pole +NZM3-4-XAVE
LN3-4 266716
LZM4 3 pole +NZM4-XAVE
LN4 266717
LZM4-4 4 pole +NZM4-4-XAVE
LN4-4 266718
42 Ordering Ordering 43
Auxiliary contact with screw terminals Auxiliary contact with screw terminals
LZM, M22- Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM, M22-
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
For use with Auxiliary contacts: f = safety Contact Part no. Price Part no. Price Std. pack Notes Notes
function, by positive opening to sequence Article no. when see price Article no. see price
IEC/EN 60947-5-1 ordered list when list
separately ordered
N/O = Normally N/C = Normally separately
open closed

Auxiliary contacts
Standard auxiliary contact (HIN)
Switching with the main contacts
Used for indicating and interlocking tasks
LZM1(-4), 2(-4), 3(-4), 4(-4) 1 N/O 1.X3 M22-K10 M22-CK10 20 off For Std. pack: The following can be clipped into the switches:
LN1(-4), 2(-4), 3(-4), 4(-4) 216376 216384 M22-(C)K... : LZM1- one standard auxiliary contact
1.X4 Std. pack = 20 off LZM2 - up to 2 standard auxiliary contacts M22-(C)K
1 N/C f 1.X1 M22-K01 M22-CK01 20 off LZM3 and LZM4 - up to 3 standard auxiliary contacts M22-(C)K
216378 216385 Any combinations of the auxiliary contact types ispossible.
1.X2
Marking on switch: HIN
With 3 m connection LZM1(-4), 2(-4), 3(-4), 4(-4) 1 N/O 1 N/C f 1.X3 1.X1 M22-CK11 20 off
cable instead of LN1(-4), 2(-4), 3(-4), 4(-4) 107940
screw termination. 1.X4 1.X2

2 N/O 1.X3 1.X3 M22-CK20


107898
1.X4 1.X4

2 N/C f 1.X1 1.X1 M22-CK02


107899
1.X2 1.X2

Early-make auxiliary contact


For interlocking and load shedding circuits, as well as for early make of the undervoltage release in main switch/Emergency-Stop
applications
With clamp terminal LZM1(-4) 2 N/O 3.13 3.23 NZM1-XHIV 1 off Not in conjunction with NZM-XU undervoltage release or
on the left-hand LN1(-4) 259426 NZM-XA shunt release
switch side. 3.14 3.24 Early make with switch on and switch off (manual actuation):
approx. 20 ms

With clamp terminal 2 N/O 3.13 3.23 NZM1-XHIVR


on the right-hand 292195
switch side. 3.14 3.24

With 3 m connection 2 N/O 3.13 3.23 NZM1-XHIVL


cable instead of 259432
screw termination. 3.14 3.24

LZM2(-4), 3(-4) 2 N/O 3.13 3.23 NZM2/3-XHIV


LN2(-4), 3(-4) 259430
3.14 3.24

LZM4(-4) 2 N/O 3.13 3.23 NZM4-XHIV Not in conjunction with undervoltage release NZM-XU, shunt release
LN4(-4) 266172 NZM-XA or remote operator NZM-XR
3.14 3.24 Early make with switch on (manual actuation): approx. 90 ms

Trip indicating auxiliary contact (HIA), (HIAFI)


General trip indication '+', when tripped by voltage release, overload release, short-circuit release or by the residual-current release
due to residual-current.
LZM1(-4), 2(-4), 3(-4), 4(-4) 1 N/O 4.X3 M22-K10 M22-CK10 20 off For Std. pack: The following can be clipped into the switches:
LN1(-4), 2(-4), 3(-4), 4(-4) 216376 216384 M22-(C)K... : LZM1 - one trip-indicating auxiliary switch
4.X4 Std. pack = 20 off LZM2 - one M22-(C)K trip-indicating auxiliary switch
1 N/C f 4.X1 M22-K01 M22-CK01 LZM3 - one M22-(C)K trip-indicating auxiliary switch
216378 216385 LZM4 - up to two M22-(C)K trip-indicating auxiliary switches
4.X2
Any combinations of the auxiliary contact types is possible.
With 3 m connection LZM1(-4), 2(-4), 3(-4), 4(-4) 1 N/O 1 N/C f 4.X3 4.X1 M22-CK11 Marking on switch: HIA
cable instead of LN1(-4), 2(-4), 3(-4), 4(-4) 107940 Labeling in FI-Block: HIAFI.
screw termination. 4.X4 4.X2
If the trip-indicating auxiliary contact in the fault-current block is used, the
2 N/O 4.X3 4.X3 M22-CK20 N/C contacts operates as a N/O contact and the N/C contact operates as an
107898 N/O contact (circuit symbol)
4.X4 4.X4

2 N/C f 4.X1 4.X1 M22-CK02


107899
4.X2 4.X2
44 Ordering
Undervoltage release with screw terminal
LZM1 Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

For use with Rated control voltage Part no. Price Std. pack Notes
Us Article no. when see price
ordered separately list
V

Undervoltage releases
Without auxiliary contact
Non-delayed disconnection of LZM circuit-breakers or LN switch-disconnectors
when the control voltage sinks below 35 70% US.
For use with Emergency-Stop devices in conjunction with Emergency-Stop button.

With clamp LZM1(-4) 24 V 50/60 Hz NZM1-XU24AC 1 off When the undervoltage


terminal on the LN1(-4) 259434 release is de-energized,
left-hand switch 110 V 130 V 50/60 Hz NZM1-XU110-130AC accidental contact with the
side. 259440 main contacts of the switch
during attempts to switch on,
208 V 240 V 50/60 Hz NZM1-XU208-240AC is safely prevented .
259442
380 V 440 V 50/60 Hz NZM1-XU380-440AC Undervoltage release cannot
259444 be installed simultaneously
with NZM...-XHIV... early-
D1 480 V 525 V 50/60 Hz NZM1-XU480-525AC
make auxiliary contact or
259446
U< NZM...-XA... shunt release.
D2 600 V 50/60 Hz NZM1-XU600AC
259448
12 V DC NZM1-XU12DC
259450
24 V DC NZM1-XU24DC
259452
110 V 130 V DC NZM1-XU110-130DC
259458
220 V 250 V DC NZM1-XU220-250DC
259460
With 3 m LZM1(-4) 24 V 50/60 Hz NZM1-XUL24AC 1 off
connection LN1(-4) 259462
cable instead of 110 V 130 V 50/60 Hz NZM1-XUL110-130AC
screw 259468
termination.
208 V 240 V 50/60 Hz NZM1-XUL208-240AC
259471
380 V 440 V 50/60 Hz NZM1-XUL380-440AC
259473
D1 480 V 525 V 50/60 Hz NZM1-XUL480-525AC
259475
U<
D2 600 V 50/60 Hz NZM1-XUL600AC
259477
12 V DC NZM1-XUL12DC
259479
24 V DC NZM1-XUL24DC
259481
110 V 130 V DC NZM1-XUL110-130DC
259487
220 V 250 V DC NZM1-XUL220-250DC
259489
Ordering 45
Undervoltage release with screw terminal
http://catalog.moeller.net Moeller SK1230-1177GB LZM2/3, LZM4

Circuit-breakers, switch-disconnectors
For use with Rated control voltage Part no. Price Std. pack Notes
Us Article no. when ordered see price
separately list
V

Undervoltage releases
Without auxiliary contact
Non-delayed disconnection of LZM circuit-breakers or LN switch-disconnectors
when the control voltage sinks below 35 70% US.
For use with Emergency-Stop devices in conjunction with Emergency-Stop button.

LZM2(-4), LN2(-4) 24 V 50/60 Hz NZM2/3-XU24AC 1 off When the undervoltage


LZM3(-4), LN3(-4) 259491 release is de-energized,
110 V 130 V 50/60 Hz NZM2/3-XU110-130AC accidental contact with the
259497 main contacts of the switch
during attempts to switch
208 V 240 V 50/60 Hz NZM2/3-XU208-240AC on, is safely prevented .
259499
380 V 440 V 50/60 Hz NZM2/3-XU380-440AC Undervoltage release cannot
259501 be installed simultaneously
with NZM...-XHIV... early-
480 V 525 V 50/60 Hz NZM2/3-XU480-525AC
make auxiliary contact or
259503
NZM...-XA... shunt release.
D1 600 V 50/60 Hz NZM2/3-XU600AC
259505
U<
D2 12 V DC NZM2/3-XU12DC
259507
24 V DC NZM2/3-XU24DC
259509
110 V 130 V DC NZM2/3-XU110-130DC
259515
220 V 250 V DC NZM2/3-XU220-250DC
259517
LZM4(-4) 24 V 50/60 Hz NZM4-XU24AC 1 off
LN4(-4) 266189
110 V 130 V 50/60 Hz NZM4-XU110-130AC
266192
208 V 240 V 50/60 Hz NZM4-XU208-240AC
266193
380 V 440 V 50/60 Hz NZM4-XU380-440AC
266194
480 V 525 V 50/60 Hz NZM4-XU480-525AC
266195
600 V 50/60 Hz NZM4-XU600AC
266196
D1 12 V DC NZM4-XU12DC
266203
U<
D2 24 V DC NZM4-XU24DC
266204
110 V 130 V DC NZM4-XU110-130DC
266207
220 V 250 V DC NZM4-XU220-250DC
266208
46 Ordering
Undervoltage release with screw terminal
LZM1, LZM2/3 Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

For use Rated control voltage Part no. Price Std. pack Notes
with Article no. when ordered see price
Us separately list
V

Undervoltage releases
With two early-make auxiliary contacts
For interlocking and load-shedding circuits, as well as for early-make of the
undervoltage release in main-switch applications.

With clamp LZM1(-4) 24 V 50/60 Hz NZM1-XUHIV24AC 1 off When the undervoltage


terminal on LN1(-4) 259531 release is de-energized,
the left-hand 110 V 130 V 50/60 Hz NZM1-XUHIV110-130AC accidental contact with the
switch side. 259537 main contacts of the switch
during attempts to switch on
208 V 240 V 50/60 Hz NZM1-XUHIV208-240AC is safely prevented.
259539 Early-make of the auxiliary
380 V 440 V 50/60 Hz NZM1-XUHIV380-440AC contacts with on and off
259541 switching (manual
operation): approx. 20 ms.
480 V 525 V 50/60 Hz NZM1-XUHIV480-525AC
Undervoltage releases cannot
D1 3.13 259543
be installed simultaneously
12 V DC NZM1-XUHIV12DC with NZM...-XHIV... early-
259545 make auxiliary contact or
24 V DC NZM1-XUHIV24DC NZM...-XA... shunt release.
D2 3.14
259547
110 V 130 V DC NZM1-XUHIV110-130DC
259553
220 V 250 V DC NZM1-XUHIV220-250DC
259555
With 3 m LZM1(-4) 24 V 50/60 Hz NZM1-XUHIVL24AC 1 off
connection LN1(-4) 259557
cable instead 110 V 130 V 50/60 Hz NZM1-XUHIVL110-130AC
of screw 259563
termination.
208 V 240 V 50/60 Hz NZM1-XUHIVL208-240AC
259565
380 V 440 V 50/60 Hz NZM1-XUHIVL380-440AC
259567
D1 3.13 480 V 525 V 50/60 Hz NZM1-XUHIVL480-525AC
259569
12 V DC NZM1-XUHIVL12DC
259571
3.14
24 V DC NZM1-XUHIVL24DC
D2
259573
110 V 130 V DC NZM1-XUHIVL110-130DC
259579
220 V 250 V DC NZM1-XUHIVL220-250DC
259581
LZM2(-4) 24 V 50/60 Hz NZM2/3-XUHIV24AC 1 off When the undervoltage
LZM3(-4) 259583 release is de-energized,
LN2(-4) 110 V 130 V 50/60 Hz NZM2/3-XUHIV110-130AC accidental contact with the
LN3(-4) 259589 main contacts of the switch
during attempts to switch on
208 V 240 V 50/60 Hz NZM2/3-XUHIV208-240AC is safely prevented.
259591 Early-make of the auxiliary
380 V 440 V 50/60 Hz NZM2/3-XUHIV380-440AC contacts with on and off
259594 switching (manual
operation): approx. 20 ms.
D1 3.13 480 V 525 V 50/60 Hz NZM2/3-XUHIV480-525AC Cannot be used in
259598 conjunction with NZM...-XR...
12 V DC NZM2/3-XUHIV12DC remote operator.
259600 Undervoltage releases cannot
be installed simultaneously
3.14
24 V DC NZM2/3-XUHIV24DC with NZM...-XHIV... early-
D2
259602 make auxiliary contact or
110 V 130 V DC NZM2/3-XUHIV110-130DC NZM...-XA... shunt release.
259608
220 V 250 V DC NZM2/3-XUHIV220-250DC
259610
Ordering 47
Undervoltage release with screw terminal
http://catalog.moeller.net Moeller SK1230-1177GB LZM4

Circuit-breakers, switch-disconnectors
For use with Rated control voltage Part no. Price Std. pack Notes
Article no. when ordered see price
Us separately list
V

Undervoltage releases
With two early-make auxiliary contacts
For interlocking and load-shedding circuits, as well as for early-make
of the undervoltage release in main-switch applications.

LZM4(-4) 24 V 50/60 Hz NZM4-XUHIV24AC 1 off When the undervoltage release is


LN4(-4) 266217 de-energized, accidental contact with the
110 V 130 V 50/60 Hz NZM4-XUHIV110-130AC main switches of the switch during
266220 attempts to switch on is safely prevented.
Early-make of the auxiliary contacts with
208 V 240 V 50/60 Hz NZM4-XUHIV208-240AC switch on (manual operation):
266221 approx. 90 ms.
380 V 440 V 50/60 Hz NZM4-XUHIV380-440AC Cannot be used in conjunction with
266222 NZM...-XR... remote operator.
Undervoltage releases cannot be
480 V 525 V 50/60 Hz NZM4-XUHIV480-525AC
installed simultaneously with
266223
NZM...-XHIV... early-make auxiliary
D1 3.13 12 V DC NZM4-XUHIV12DC contact or NZM...-XA... shunt release.
266231
24 V DC NZM4-XUHIV24DC
266232
3.14
110 V 130 V DC NZM4-XUHIV110-130DC
D2
266235
220 V 250 V DC NZM4-XUHIV220-250DC
266236
48 Ordering
Undervoltage release with screw terminal
LZM1, LZM2/3, LZM4 Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

For use with Rated control voltage Part no. Price Std. pack
Article no. when ordered separately see price
Us list
V

Undervoltage releases
With two separate early-make auxiliary contacts
Coil connection wired to clamp terminal, auxiliary switch connections wired with 3 m loose
connection cables
LZM1(-4), LN1(-4) 24 V 50/60 Hz NZM1-XUHIV20KL24AC 1 off
D1 3.13 3.23
284388
110 V 130 V 50/60 Hz NZM1-XUHIV20KL110-130AC
D2 3.14 3.24 284389
208 V 240 V 50/60 Hz NZM1-XUHIV20KL208-240AC
284400
24 V DC NZM1-XUHIV20KL24DC
284387
Coil connection with 3 m loose connection cables, auxiliary switch connections wired to clamp
terminal
LZM1(-4), LN1(-4) 24 V 50/60 Hz NZM1-XUHIV20LK24AC 1 off
D1 3.13 3.23
284402
110 V 130 V 50/60 Hz NZM1-XUHIV20LK110-130AC
D2 3.14 3.24 284403
208 V 240 V 50/60 Hz NZM1-XUHIV20LK208-240AC
284404
24 V DC NZM1-XUHIV20LK24DC
284401
Coil connection with 3 m loose connection cables, auxiliary switch connections wired to clamp
terminal
LZM2(-4), LN2(-4) 24 V 50/60 Hz NZM2/3-XUHIV20LK24AC 1 off
D1 3.13 3.23
LZM3(-4), LN3(-4) 285291
110 V 130 V 50/60 Hz NZM2/3-XUHIV20LK110-130AC
D2 3.14 3.24 284407
208 V 240 V 50/60 Hz NZM2/3-XUHIV20LK208-240AC
284408
24 V DC NZM2/3-XUHIV20LK24DC
284405

Contacts 3.23 and 3.24 with separate 3 m connection cables.


LZM4(-4), LN4(-4) 24 V 50/60 Hz NZM4-XUHIV2024AC 1 off
D1 3.13 3.23
266244
110 V 130 V 50/60 Hz NZM4-XUHIV20110-130AC
D2 3.14 3.24 266247
208 V 240 V 50/60 Hz NZM4-XUHIV20208-240AC
266248
380 V 440 V 50/60 Hz NZM4-XUHIV20380-440AC
266249
24 V DC NZM4-XUHIV2024DC
266258

Notes When the undervoltage release is de-energized, accidental contact with the main switches of the switch during attempts to switch on is safely
prevented.
Early-make of the auxiliary contacts with on and off switching (manual operation): approx. 20 ms.
Cannot be used in conjunction with NZM...-XR... remote operator.
Undervoltage releases cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XA... shunt release.
Ordering 49
Undervoltage releases, off-delayed
http://catalog.moeller.net Moeller SK1230-1177GB LZM1, LZM2/3..., LZM4

Circuit-breakers, switch-disconnectors
For use with Part no. Price Std. pack Notes
Article no. when see price
ordered separately list

Undervoltage releases, off-delayed


Combination of separate delay unit and special tripping device.
Delay unit
Voltage dips of less than the setting between 0.06 16 s do not
cause disconnection of the NZM circuit-breaker or N switch-
disconnector.
LZM1(-4), 2(-4), 3(-4), 4(-4) UVU-NZM 1 off Adjustable delay time 70 ms 4 s.
LN1(-4), 2(-4), 3(-4), 4(-4) 260154 With additional capacitor up to 16 s.
A special tripping device is required.
50/60 Hz Cannot be installed simultaneously with
220 V 240 V NZM...-XHIV... or NZM...-XA... shunt release.
380 V 440 V Delay unit for separate installation
480 V 550 V (Fixing: top-hat rail or screws).
For other operating voltages use control
DC/AC transformer.
24 V

Special tripping device


For combination with separate delay unit
Without auxiliary contacts
NZM1-X with 3 m separate connection cables instead of screw
terminal, NZM2, 3 , 4 with screw terminal
D1 LZM1(-4), LN1(-4) NZM1-XUVL 1 off UVU-NZM delay unit is additionally required.
271607 Cannot be installed simultaneously with
U
LZM2(-4), LN2(-4) NZM2/3-XUV separate NZM...-XHIV early-make auxiliary
D2 contact or NZM...-XA... shunt release.
LZM3(-4), LN3(-4) 259527
LZM4(-4), LN4(-4) NZM4-XUV
266588
With 2 early-make auxiliary contacts
NZM1-X with 3 m separate connection cables instead of
screw terminal, NZM2, 3 , 4 with screw terminal
D1 3.13 LZM1(-4), LN1(-4) NZM1-XUVHIVL 1 off Cannot be used in conjunction with
271608 NZM...-XR... remote operator.
LZM2(-4), LN2(-4) NZM2/3-XUVHIV UVU-NZM delay unit is additionally required.
LZM3(-4), LN3(-4) 259684 Cannot be installed simultaneously with
U
separate NZM...-XHIV early-make auxiliary
D2 3.14 LZM4(-4), LN4(-4) NZM4-XUVHIV contact or NZM...-XA... shunt release.
266596 LZM1, 2, 3: Early-make of the auxiliary contacts
with on and off switching (manual operation):
approx. 20 ms.
LZM4: Early-make of the auxiliary contacts with
switch on (manual operation): approx. 90 ms.
With 2 separately operating early-make auxiliary contacts
NZM1-X with 3 m separate connection cables instead of
screw terminal, NZM2(3)(4)-X with screw terminal, contact
3.23 and 3.24 with 3 m separate connection cables.
LZM1(-4), LN1(-4) NZM1-XUVHIV20L 1 off Cannot be used in conjunction with
D1 3.13 3.23 271609 NZM...-XR... remote operator.
LZM2(-4), LN2(-4) NZM2/3-XUVHIV20 UVU-NZM delay unit is additionally required.
D2 3.14 3.24 LZM3(-4), LN3(-4) 259688 Cannot be installed simultaneously with
separate NZM...-XHIV early-make auxiliary
LZM4(-4), LN4(-4) NZM4-XUVHIV20 contact or NZM...-XA... shunt release.
266604 LZM1, 2, 3: Early-make of the auxiliary contacts
with on and off switching (manual operation):
approx. 20 ms.
LZM4: Early-make of the auxiliary contacts with
switch on (manual operation): approx. 90 ms.
50 Ordering
Shunt releases with screw terminal
LZM1, LZM2/3, LZM4 Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

For use Rated control voltage Part no. Price Std. Notes
with Article no. when ordered see price pack
Us separately list
V

Shunt releases
Without auxiliary contact
Switches are tripped by a voltage pulse or by the application of uninterrupted
voltage.
With clamp LZM1(-4) 12 V AC/DC NZM1-XA12AC/DC 1 off When the undervoltage
terminal on the LN1(-4) 259706 release is de-energized,
left-hand switch 24 V AC/DC NZM1-XA24AC/DC accidental contact with the
side. 259708 main contacts of the switch
during attempts to switch
110 V 130 V AC/DC NZM1-XA110-130AC/DC on, is safely prevented.
259724
Shunt release cannot be
installed simultaneously
C1 208 V 250 V AC/DC NZM1-XA208-250AC/DC with NZM...-XHIV... early-
259726 make auxiliary contact or
C2 380 V 440 V AC/DC NZM1-XA380-440AC/DC NZM...-XU... undervoltage
259728 release.
With 3 m LZM1(-4) 12 V AC/DC NZM1-XAL12AC/DC 1 off
connection cable LN1(-4) 259734
instead of screw 24 V AC/DC NZM1-XAL24AC/DC
termination. 259736
110 V 130 V AC/DC NZM1-XAL110-130AC/DC
259742

C1 208 V 250 V AC/DC NZM1-XAL208-250AC/DC


259744
C2 380 V 440 V AC/DC NZM1-XAL380-440AC/DC
259746
Without auxiliary contact
Switches are tripped by a voltage pulse or by the application of uninterrupted
voltage.
LZM2(-4) 12 V AC/DC NZM2/3-XA12AC/DC 1 off When the undervoltage
LZM3(-4) 259752 release is de-energized,
LN2(-4) 24 V AC/DC NZM2/3-XA24AC/DC accidental contact with the
LN3(-4) 259754 main contacts of the switch
during attempts to switch
110 V 130 V AC/DC NZM2/3-XA110-130AC/DC on, is safely prevented.
259760
208 V 250 V AC/DC NZM2/3-XA208-250AC/DC Shunt release cannot be
259763 installed simultaneously
with NZM...-XHIV... early-
C1 380 V 440 V AC/DC NZM2/3-XA380-440AC/DC make auxiliary contact or
259766 NZM...-XU... undervoltage
C2
release.

LZM4(-4) 12 V AC/DC NZM4-XA12AC/DC 1 off


LN4(-4) 266446
24 V AC/DC NZM4-XA24AC/DC
266447
110 V 130 V AC/DC NZM4-XA110-130AC/DC
266450
208 V 250 V AC/DC NZM4-XA208-250AC/DC
266451

C1 380 V 440 V AC/DC NZM4-XA380-440AC/DC


266452
C2
Ordering 51
Shunt releases with screw terminal
http://catalog.moeller.net Moeller SK1230-1177GB LZM...-X...

Circuit-breakers, switch-disconnectors
For use with Part no. Price Std. pack Notes
Article no. when see price
ordered list
separately

Shunt releases
Capacitor unit 230 V 50/60 Hz
in conjunction with NZM...-XA2082-50AC/DC
shunt release
Enclosure: degree of protection IP20
LZM1(-4) NZM-XCM 1 off Enables the safe use of circuit-breakers as mesh network circuit-breakers
LZM2(-4) 229413 in the range from 0 110 % Un with constant switch-off time of 40 ms.
LZM3(-4) If the mains voltage is absent, the installed capacitor supplies power for
LZM4(-4) actuating the shunt release for at least 12 hours.
LN1(-4) The configuration of the capacitor unit is undertaken independently of the
LN2(-4) circuit-breaker.
LN3(-4) Connect NZM-XCM to the power feed side.
LN4(-4)
Design note:
Connect a standard auxiliary contact as N/O in series with the shunt
release!
Standard auxiliary contact not included as standard.

For use Rated control Part no. Price Std. Notes


with voltage Article no. when ordered see price pack
separately list

Us
V

Shunt releases
Without auxiliary contacts
For mesh-network circuit-breakers
For intermittent operation
Maximum on time = 1 s
Operating range 10 110 % Us
C1 LZM3(-4) 230 V AC NZM3-XA-230AC-MNS 1 off Cannot be installed simultaneously with
LN3(-4) 274097 NZM...-XHIV... early-make auxiliary contact or
NZM...-XU... undervoltage release.
C2

Intermittent operation guaranteed by series


connection of an M22-(C)K10 make contact.
The maximum operating time of the shunt release
for mesh network circuit-breaker is 1 s.

C1 LZM4(-4) 230 V AC NZM4-XA-230AC-MNS 1 off L1 (L+)


LN4(-4) 274138
C2

a
-S11
0

1.13
Q M22-...K10
HIN 1.14

C1
-Q1 NZM...-XA...-MNS
C2

N (L-, L2)

a Reverse-power relay contact


-S11 Remote off
Q Standard auxiliary contact
-Q1 Shunt release
52 Ordering
Shunt releases with screw terminal
LZM1, LZM2/3, LZM4 Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

For use Rated control voltage Part no. Price Std. Notes
with Article no. when ordered see price pack
Us separately list
V

Shunt releases
With early-make auxiliary contact
Not in combination with remote operator.
With clamp LZM1(-4) 12 V AC/DC NZM1-XAHIV12AC/DC 1 off When the shunt release is
terminal on LN1(-4) 259772 energized, accidental
the left-hand 24 V AC/DC NZM1-XAHIV24AC/DC contact with the main
switch side. 259774 contacts of the switch
during attempts to switch on
110 V 130 V AC/DC NZM1-XAHIV110-130AC/DC is safely prevented.
259780 Early-make of the auxiliary
contact with on and off
switching (manual
C1 3.13 208 V 250 V AC/DC NZM1-XAHIV208-250AC/DC operation): approx. 20 ms.
259782 Shunt release cannot be
C2 3.14 380 V 440 V AC/DC NZM1-XAHIV380-440AC/DC installed simultaneously
259784 with NZM...-XHIV... early-
make auxiliary contact or
With 3 m LZM1(-4) 12 V AC/DC NZM1-XAHIVL12AC/DC 1 off NZM...-XU... undervoltage
connection LN1(-4) 259790 release.
cable instead 24 V AC/DC NZM1-XAHIVL24AC/DC
of screw 259792
termination.
110 V 130 V AC/DC NZM1-XAHIVL110-130AC/DC
259798

C1 3.13 208 V 250 V AC/DC NZM1-XAHIVL208-250AC/DC


259800
C2 3.14 380 V 440 V AC/DC NZM1-XAHIVL380-440AC/DC
259802
With early-make auxiliary contact
LZM2(-4) 12 V AC/DC NZM2/3-XAHIV12AC/DC 1 off When the shunt release is
LZM3(-4) 259808 energized, accidental
LN2(-4) 24 V AC/DC NZM2/3-XAHIV24AC/DC contact with the main
LN3(-4) 259810 contacts of the switch
during attempts to switch
110 V 130 V AC/DC NZM2/3-XAHIV110-130AC/DC on is safely prevented.
259816 Early-make of the auxiliary
208 V 250 V AC/DC NZM2/3-XAHIV208-250AC/DC contact with on and off
259818 switching (manual
operation): approx. 20 ms.
C1 3.13 380 V 440 V AC/DC NZM2/3-XAHIV380-440AC/DC Cannot be used in
259820 conjunction with
C2 3.14
NZM...-XR... remote
operator.
LZM4(-4) 12 V AC/DC NZM4-XAHIV12AC/DC 1 off Shunt release cannot be
LN4(-4) 266470 installed simultaneously
24 V AC/DC NZM4-XAHIV24AC/DC with NZM...-XHIV... early-
266471 make auxiliary contact or
NZM...-XU... undervoltage
110 V 130 V AC/DC NZM4-XAHIV110-130AC/DC release.
266474
208 V 250 V AC/DC NZM4-XAHIV208-250AC/DC
266475

C1 3.13 380 V 440 V AC/DC NZM4-XAHIV380-440AC/DC


266476
C2 3.14
Ordering 53
Shunt releases with screw terminal
http://catalog.moeller.net Moeller SK1230-1177GB NZM...-XAHIV-...

Circuit-breakers, switch-disconnectors
For use Rated control Part no. Price Std. pack
with voltage Article no. when ordered see price
Us separately list
V

Shunt releases
For mesh-network circuit-breakers
For intermittent operation
Maximum on time = 1 s
Operating range 10 110 % Us
C1 3.13 With early-make auxiliary LZM3(-4) 230 V AC NZM3-XAHIV-230AC-MNS 1 off
contact LN3(-4) 274141
C2 3.14

C1 3.13 230 V AC NZM4-XAHIV-230AC-MNS 1 off


274143
C2 3.14

Notes Cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XU... undervoltage release.
Cannot be used in conjunction with NZM...-XR... remote operator.

Intermittent operation guaranteed by series connection of a N/O contact M22-(C)K10 (standard auxiliary contact).
The maximum operating time of the shunt release for mesh network circuit-breaker is 1 s.
LZM3: Early-make of the auxiliary contact with on and off switching (manual operation): approx. 20 ms.
LZM4: Early-make of the auxiliary contact with switch on (manual operation): approx. 90 ms.
54 Ordering Ordering 55
Door coupling rotary handles Door coupling rotary handles
LZM1, LZM2, LZM3, LZM4 Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM1, LZM2, LZM3, LZM4
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
For a max. shaft length of 60 mm Extremely narrow fittings
For use with Part no. Price Std. pack Notes Part no. Price Std. pack Notes Part no. Price Std. pack Notes
Article no. see price Article no. see price Article no. see price
list list list

Door coupling rotary handle


Complete including rotary drive and coupling parts
An additional extension shaft is necessary with the NZM...-XT(V)D(V)(R)(-60) types.
Degree of protection IP66
Standard, black/grey
Lockable on the 0 position LZM1(-4), LN1(-4) NZM1-XTVD 1 off Door interlock NZM1-XTVD-60 1 off Door interlock NZM1-XTVD-0 1 off Door interlock
on the handle using up to 260166 Not defeated in the locked 271504 Not defeated in the locked OFF 279392 Not defeated in the locked OFF
3 padlocks. With door LZM2(-4), LN2(-4) NZM2-XTVD OFF and ON positions NZM2-XTVD-60 and ON positions NZM2-XTVD-0 and ON positions
interlock 260168 Can be modified such that it 271505 Can be modified such that it 279393 Can be modified such that it can
can be defeated from the can be defeated from the be defeated from the outside
LZM3(-4), LN3(-4) NZM3-XTVD outside using a screwdriver, NZM3-XTVD-60 outside using a screwdriver, NZM3-XTVD-0 using a screwdriver, when it is in
260170 when it is in the unlocked 271506 when it is in the unlocked ON 279394 the unlocked ON position.
LZM4(-4), LN4(-4) NZM4-XTVD ON position. NZM4-XTVD-60 position. NZM4-XTVD-0 Door can be opened in OFF
266614 Door can be opened in OFF 271507 Door can be opened in OFF 279395 NZM...-XTVD(V)-0
NZM...-XTVD(V) NZM...-XTVD(V)-60 For extremely narrow fittings
Lockable on the handle on LZM1(-4), LN1(-4) NZM1-XTVDV External warning plate/ NZM1-XTVDV-60 For maximum shaft length NZM1-XTVDV-0 With special short extension
the switch using up to 260172 designation label can be 271508 60 mm 279396 shaft
3 padlocks. Can be locked clipped on Without shaft support Cannot be combined with
LZM2(-4), LN2(-4) NZM2-XTVDV NZM2-XTVDV-60 Cannot be combined with NZM2-XTVDV-0 NZM...-XDZ additional handle
in 0 position on the handle, 260174 271509 279397
with adequate NZM...-XDZ additional handle External warning plate/
modification also in I LZM3(-4), LN3(-4) NZM3-XTVDV NZM3-XTVDV-60 External warning plate/ NZM3-XTVDV-0 designation label can be clipped
position. With door 260176 271510 designation label can be 279398 on
interlock. Lockable in the 0 LZM4(-4), LN4(-4) NZM4-XTVDV NZM4-XTVDV-60 clipped on NZM4-XTVDV-0
position 266616 271511 279399

Red-yellow for Emergency-Stop


Lockable on the handle on LZM1(-4), LN1(-4) NZM1-XTVDVR 1 off Door interlock NZM1-XTVDVR-60 1 off Door interlock NZM1-XTVDVR-0 1 off Door interlock
the switch using up to 260178 Not defeatable in the 271512 Not defeatable in the locked 279400 Not defeatable in the locked OFF
3 padlocks. Lockable in 0 locked OFF position. OFF position. position.
position on handle. With Can be modified such that it Can be modified such that it Can be modified such that it can
door interlock. Lockable in can be defeated from the can be defeated from the be defeated from the outside
the 0 position LZM2(-4), LN2(-4) NZM2-XTVDVR outside using a screwdriver, NZM2-XTVDVR-60 outside using a screwdriver, NZM2-XTVDVR-0 using a screwdriver, when it is in
260180 when it is in the unlocked 271513 when it is in the unlocked ON 279401 the unlocked ON position.
LZM3(-4), LN3(-4) NZM3-XTVDVR ON position. NZM3-XTVDVR-60 position. NZM3-XTVDVR-0 Door can be opened in OFF
260182 Door can be opened in OFF 271514 Door can be opened in OFF 279402 NZM...-XTVDVR-0
NZM...-XTVDVR NZM...-XTVDVR-60 For extremely narrow fittings
LZM4(-4), LN4(-4) NZM4-XTVDVR External warning plate/ NZM4-XTVDVR-60 For maximum shaft length NZM4-XTVDVR-0 With special short extension
266618 designation label can be 271515 60 mm 279403 shaft
clipped on Without shaft support Cannot be combined with
Cannot be combined with NZM...-XDZ additional handle
NZM...-XDZ additional handle External warning plate/
External warning plate/ designation label can be clipped
designation label can be on
clipped on

Extension shaft
Max. mounting depth: LZM1(-4), LN1(-4) NZM1/2-XV4 1 off Can be cut to required length
400 mm LZM2(-4), LN2(-4) 261232
LZM3(-4), LN3(-4) NZM3/4-XV4
LZM4(-4), LN4(-4) 261234
Max. mounting depth: LZM1(-4), LN1(-4) NZM1/2-XV6
600 mm LZM2(-4), LN2(-4) 260191
LZM3(-4), LN3(-4) NZM3/4-XV6
LZM4(-4), LN4(-4) 260193

Notes Circuit-breaker can also be installed in a lying position 90 left/right, with the handle still in the same position.
56 Ordering
Rotary handles
NZM-XDV Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

For use with Part no. Price Std. Notes


Article no. when see price pack
ordered separately list

Rotary handle on circuit-breaker


Complete with rotary drive
Standard, black/grey
Lockable on the 0 position LZM1(-4), LN1(-4) NZM1-XDV 1 off NZM1(2)(3)-X: Can also be
on the switch using up to 260125 combined with insulating surround.
3 padlocks. MODAN handle position detection by
LZM2(-4), LN2(-4) NZM2-XDV wire release can be retrofitted.
260127

LZM3(-4), LN3(-4) NZM3-XDV


260129
LZM4(-4), LN4(-4) NZM4-XDV
266608

Lockable on the 0 position LZM1(-4), LN1(-4) NZM1-XDVG 1 off Can also be combined with insulating
on the handle using up to 285247 surround.
3 padlocks.
LZM2(-4), LN2(-4) NZM2-XDVG
285248

Red-yellow for Emergency-Stop


Lockable on the 0 position LZM1(-4), LN1(-4) NZM1-XDVR 1 off NZM1(2)(3)-X: Can also be
on the switch using up to 260135 combined with insulating surround.
3 padlocks. MODAN handle position detection by
LZM2(-4), LN2(-4) NZM2-XDVR wire release can be retrofitted.
260137

LZM3(-4), LN3(-4) NZM3-XDVR


260140
LZM4(-4), LN4(-4) NZM4-XDVR
266610

Lockable on the 0 position LZM1(-4), LN1(-4) NZM1-XDVGR Can also be combined with insulating
on the handle using up to 285249 surround.
3 padlocks.
LZM2(-4), LN2(-4) NZM2-XDVGR
285280

Notes Circuit-breaker can also be installed in a lying position 90 left/right, with the handle still in the same position.
Ordering 57
Rotary handles with door interlock
http://catalog.moeller.net Moeller SK1230-1177GB NZM...-XDTV...

Circuit-breakers, switch-disconnectors
For use with Part no. Price Std. Notes
Article no. when see price pack
ordered separately list

Rotary handle on switch with door interlock


Complete with rotary drive and insulating surround
Standard, black/grey
Lockable on the LZM1(-4), LN1(-4) NZM1-XDTV 1 off Door interlock
0 position on the handle 260131 In the ON position, can be defeated from
using up to 3 padlocks, the outside using a 1 mm pin
can also be modified for Not defeated in the locked OFF and ON
the I position. Also positions
available with door LZM2(-4), LN2(-4) NZM2-XDTV Door can be opened in OFF
interlock e.g. for MCC 260133 Can only be switched ON when the door
service distribution. is closed

Red-yellow for Emergency-Stop

Lockable on the LZM1(-4), LN1(-4) NZM1-XDTVR 1 off


0 position on the handle 260142
using up to 3 padlocks.
Also available with door LZM2(-4), LN2(-4) NZM2-XDTVR
interlock e.g. for MCC 260144
service distribution

Rotary handle
Divergent to normal IEC handles: Door opening only possible with active
rotation beyond the 0 position.
Complete with rotary drive and insulating surround
Standard, black/grey
Lockable on the LZM1(-4), LN1(-4) NZM1-XDTV-NA 1 off Door interlock
0 position on the handle 271453 In the ON position, can be defeated from
using up to 3 padlocks. the outside using a 1 mm pin
Also available with door LZM2(-4), LN2(-4) NZM2-XDTV-NA Not defeated in the locked OFF and ON
interlock e.g. for MCC 271454 positions
service distribution. Door opening only possible with active
rotation beyond the 0 position.
Can only be switched ON when the door
Red-yellow for Emergency-Stop is closed
Lockable on the LZM1(-4), LN1(-4) NZM1-XDTVR-NA Cannot be combined with mechanical
0 position on the handle 271455 interlock
using up to 3 padlocks.
Also available with door LZM2(-4), LN2(-4) NZM2-XDTVR-NA
interlock e.g. for MCC 271456
service distribution.

Notes Circuit-breaker can also be installed in a lying position 90 left/right, with the handle still in the same position.
58 Ordering
Main switch assembly kit
NZM...-XHB..., NZM...-XS... Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Type For use with Part no. Price Std. pack


Article no. when see price
ordered separately list

Main switch assembly kit


Equipment supplied:
Rotary door-coupling handle
NZM...-XV4 extension shaft
External warning plate/designation label in German/English
Black and yellow flash
For enhanced protection against direct contact on the incomer side, IP2X protection against contact with a finger
can be ordered a 23
Other external warning plates/designation labels can be clipped on.
With black door coupling rotary handle
Lockable on the 0 position on the LZM1(-4), LN1(-4) NZM1-XHB 1 off
handle using up to 3 padlocks, can 266626
also be modified for the I position. LZM2(-4), LN2(-4) NZM2-XHB
With door interlock. 266627
LZM3(-4), LN3(-4) NZM3-XHB
266628
LZM4(-4), LN4(-4) NZM4-XHB
271779
With red door coupling rotary handle for using switch as Emergency-Stop device according to IEC/EN 602041
Lockable on the 0 position on the LZM1(-4), LN1(-4) NZM1-XHBR
handle using up to 3 padlocks. 266632
Lockable door as additional feature, LZM2(-4), LN2(-4) NZM2-XHBR
locking facility on circuit-breaker in 0 266633
position.
LZM3(-4), LN3(-4) NZM3-XHBR
266634
LZM4(-4), LN4(-4) NZM4-XHBR
271842
Main switch assembly kit for side panel mounting
Actuation of the switch on the control panel side wall
Switch mounting on mounting plate
Equipment supplied:
Door coupling rotary handle
NZM...-XV4 extension shaft
External warning plate/designation label in German/English
Black and yellow flash
For enhanced protection against direct contact on the incomer side, IP2X protection against contact with a finger
can be ordered a 23
Other external warning plates/designation labels can be clipped on.
Standard, black/grey
Lockable on the 0 position on the For operation on LZM1(-4), LN1(-4) NZM1-XS-L 1 off
handle using up to 3 padlocks, can the left 266641
also be modified for the I position. LZM2(-4), LN2(-4) NZM2-XS-L
266642
LZM3(-4), LN3(-4) NZM3-XS-L
266643
LZM4(-4), LN4(-4) NZM4-XS-L
289806
For operation on LZM1(-4), LN1(-4) NZM1-XS-R
the right 266644
LZM2(-4), LN2(-4) NZM2-XS-R
266645
LZM3(-4), LN3(-4) NZM3-XS-R
266646
LZM4(-4), LN4(-4) NZM4-XS-R
289807
Red-yellow for Emergency-Stop
Lockable on the 0 position on the For operation on LZM1(-4), LN1(-4) NZM1-XSR-L
handle using up to 3 padlocks. the left 266653
LZM2(-4), LN2(-4) NZM2-XSR-L
266654
LZM3(-4), LN3(-4) NZM3-XSR-L
266655
LZM4(-4), LN4(-4) NZM4-XSR-L
289808
For operation on LZM1(-4), LN1(-4) NZM1-XSR-R
the right 266656
LZM2(-4), LN2(-4) NZM2-XSR-R
266657
LZM3(-4), LN3(-4) NZM3-XSR-R
266658
LZM4(-4), LN4(-4) NZM4-XSR-R
289809
Ordering 59
Main switch assembly kit
http://catalog.moeller.net Moeller SK1230-1177GB NZM...XS(R)M...

Circuit-breakers, switch-disconnectors
Type For use with Part no. Price Std.
Article no. when see price pack
ordered separately list

Main switch assembly kit for side panel mounting with mounting bracket
For direct mounting of circuit-breaker and handle in the side wall of the control cabinet
Equipment supplied:
Door coupling rotary handle
Mounting bracket
Special short extension shaft
External warning plate/designation label in German/English
Black and yellow flash
For enhanced protection against direct contact on the incomer side, IP2X protection against contact with a finger can be
ordered a 23
Other external warning plates/designation labels can also be clipped on.
Standard, black/grey
Can be locked in 0 position, with adequate For operation on LZM1(-4), LN1(-4) NZM1-XSM-L 1 off
modification also in I position. Narrowest minimum the left 266663
clearance between enclosure side plates of control For operation on LZM2(-4), LN2(-4) NZM2-XSM-L
panel and circuit-breaker is defined by mounting the left 266664
bracket. Extensions cannot be used.
For operation on LZM1(-4), LN1(-4) NZM1-XSM-R
the right 266665
For operation on LZM2(-4), LN2(-4) NZM2-XSM-R
the right 266666
Red-yellow for Emergency-Stop
Lockable in 0 position on handle. Narrowest For operation on LZM1(-4), LN1(-4) NZM1-XSRM-L 1 off
minimum clearance between enclosure side plates the left 266671
of control panel and circuit-breaker is defined by For operation on LZM2(-4), LN2(-4) NZM2-XSRM-L
mounting bracket. Extensions cannot be used. the left 266672
For operation on LZM1(-4), LN1(-4) NZM1-XSRM-R
the right 266673
For operation on LZM2(-4), LN2(-4) NZM2-XSRM-R
the right 266674
Add-on plate
For fitting to the mounting bracket when using N conductor or PE conductor terminals K25, K50, K95 or K150.
LZM1(-4), LN1(-4) NZM1/2-XZB 1 off
LZM2(-4), LN2(-4) 266676

Additional terminal arrangement for side wall operator with mounting bracket
NZM1-XS(R)M-, NZM2-XS(R)M-
Additional terminals K25, K50, K95, K150 a 66

Actuation:
3 pole 4 pole
For operation on the right For operation on the left For operation on the right For operation on the left
MII MI MI MII
MI MII

Mounting areas MI MII


Variation options V1 V2 V3 V4 V1 V2
Maximum number of additional K25 2x
terminals K50 2x
K95 1x 1x
K150 1x 1x

Example: In mounting area MI, variation option 1 allows the K25 additional terminal to be mounted twice.
60 Ordering
Accessories
NZM...-XRAV..., ZFS..., BPF-... Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

For use with Part no. Price Std. pack Notes


Article no. when see price
ordered separately list

Rear drive
For direct rear connection of the switch to the side of the control panel or
control panel door. Switch actuation on rear through side plate or control
panel door.
For switch with toggle lever.
For enhanced protection against direct contact on the incomer side, IP2X
protection against contact with a finger can be ordered a 21
Degree of protection IP66, UL/CSA Type 4X
Standard, black/grey
Lockable on the LZM1, LN1 NZM1-XRAV 1 off External warning plate can be clipped on
0 position on the 107245
handle using up to LZM2, LN2 NZM2-XRAV
3 padlocks. 107247

Red-yellow for Emergency-Stop


Lockable on the LZM1, LN1 NZM1-XRAVR 1 off
0 position on the 107249
handle using up to LZM2, LN2 NZM2-XRAVR
3 padlocks. 107261

External warning plate/designtion label

German/English LZM1(-4), LN1(-4) ZFS61/62-NZM7 1 off A bilingual external warning plate/


LZM2(-4), LN2(-4) 272525 designation label in German/English is
German LZM3(-4), LN3(-4) ZFS61-NZM7 already included in the main switch
LZM4(-4), LN4(-4) 051089 assembly kit.
English ZFS62-NZM7
065957
French ZFS63-NZM7
065958
Blank (for engraving or printing) ZFS60-NZM7
065896
Further languages ZFS*-NZM7 External warning plates are available in the
999978 following languages:
64 Bulgarian 73 Romanian
65 Danish 74 Russian
66 Finnish 75 Swedish
67 Dutch 76 Serbo-Croatian
68 Italian 77 Spanish
69 Greek 78 Czech
70 Norwegian 79 Turkish
71 Polish 80 Hungarian
72 Portuguese 81 Afrikaans
To obtain the order number, insert the lan-
guage code number into the type reference
required.
Ordering example
External warning plate in Finnish:
ZFS66-NZM7
Lightning symbol
Including terminal marking for main switch
Small U X L1 T1 N PEN
V Y L2 T2
LZM1(-4), LN1(-4) BPF-NZM7 10 off Included as standard in main switch
W Z L3 T3 PE LZM2(-4), LN2(-4) 217294 assembly kit

Large U X
V Y
L1 T1 N PEN
L2 T2
LZM3(-4), LN3(-4) BPF-NZM10 10 off
W Z L3 T3 PE LZM4(-4), LN4(-4) 231363
Ordering 61
Accessories
http://catalog.moeller.net Moeller SK1230-1177GB NZM...-XDZ, NZM...-XBR, NZM...-X...

Circuit-breakers, switch-disconnectors
For use with Part no. Price Std. pack Notes
Article no. when see price
ordered separately list

Add-on handle
Enables switching when the control panel door is open
LZM1(-4), LN1(-4) NZM1/2-XDZ 1 off Push-fits on to the extension shaft
LZM2(-4), LN2(-4) 266621 100 mm free extension shaft required.
Cannot be combined with NZM...-XT...-60
LZM3(-4), LN3(-4) NZM3/4-XDZ 1 off door coupling rotary handles as well as
LZM4(-4), LN4(-4) 266622 NZM...-XT...-0.

Insulating surrounds
For toggle lever, rotary handle with rotary drive and remote operator.
Degree of protection IP40

LZM1(-4), LN1(-4) NZM1-XBR 1 off For oblong cut-out on doors and


260195 enclosures with material thicknesses of
1.5 5 mm.
External warning plate/designation label
LZM2(-4), LN2(-4) NZM2-XBR can be clipped on
260197 NZM4-XBR cannot be combined with
LZM3(-4), LN3(-4) NZM3-XBR rotary handle with rotary drive.
284645
LZM4(-4), LN4(-4) NZM4-XBR
284646
Toggle lever locking device
Off position lockable using up to 3 padlocks (hasp thickness 4 8 mm)
LZM1(-4), LN1(-4) NZM1-XKAV 1 off Cannot be combined with insulating
260199 surround.
LZM2(-4), LN2(-4) NZM2/3-XKAV 1 off
LZM3(-4), LN3(-4) 260201

Spacers
Enables fast and low-priced adjustment of differing frame sizes with/
without rotary handle to the same front depth
LZM1(-4), LN1(-4) NZM1/2-XAB 1 set Grid depth 17.5 mm, M4 thread
LZM2(-4), LN2(-4) 260203 Type contains 4 off spacer
Maximum component capacity:
LZM1: 4 units per fixing screw,
LZM2: 2 units per fixing screw
2 (LZM1) or 4 (LZM2) fixing screws
contained per circuit-breaker
LZM3(-4), LN3(-4) NZM3-XAB 1 set Grid depth 17.5 mm, M5 thread
LZM4(-4), LN4(-4) 260211 One set contains 4 spacers
LZM3, LZM4: 1 off per fixing screw
4 fixing screws per switch included

Clip plate
Enables snap-fit of the circuit-breaker to a DIN rail
LZM1(-4), LN1(-4) NZM1-XC35 1 off For top-hat rail 35 mm
260213

LZM2, LN2 NZM2-XC75 1 off For top-hat rail 75 mm


260215 Not suitable for circuit-breakers with
remote operator.
62 Ordering
Mechanical interlock
NZM...XMV(R)(L), NZM-XBZ... Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

For use with Part no. Price Std. pack Notes


Article no. when see price
ordered separately list

Mechanical interlocking of (door coupling) rotary handles

LZM1(-4), LN1(-4) NZM1-XMV 1 off Rotary handles on switches or door coupling


281581 rotary handles are additionally required.
Cannot be combined with paralleling
mechanisms, side wall operators and remote
operator as well as NZM4-XBR insulating
surrounds.
LZM2(-4), LN2(-4) NZM2-XMV In order to establish a mechanical interlock at
281582 least 2 interlock modules are required.
Possible combinations and interlock variants
a engineering
Order Bowden cable separately

LZM3(-4), LN3(-4) NZM3-XMV


281583
LZM4(-4), LN4(-4) NZM4-XMV
281584

Bowden cables
For mechanical interlocking of (door coupling) rotary handles

LZM1(-4), LN1(-4) NZM-XBZ225 1 off


LZM2(-4), LN2(-4) 281585
LZM3(-4), LN3(-4) NZM-XBZ600
LZM4(-4), LN4(-4) 281586
NZM-XBZ1000
281587
Mechanical interlock for remote operator
For 2 switches of the same or next frame size with each other.
Mounting beside one another.

LZM2(-4), LN2(-4) NZM2-XMVR 1 off Type contains parts for both switches.
+LZM2(-4), LN2(-4) 104543 Remote operator also required.
LZM2(-4), LN2(-4) NZM2/3-XMVR Maximum switching distance
+LZM3(-4), LN3(-4) 104544 a engineering
Cannot be combined with rotary handles,
LZM3(-4), LN3(-4) NZM3-XMVR door coupling rotary handles and early-make
+LZM3(-4), LN3(-4) 104545 auxiliary contacts.
LZM3(-4), LN3(-4) NZM3/4-XMVR
+LZM4(-4), LN4(-4) 104546
LZM4(-4), LN4(-4) NZM4-XMVR
+LZM4(-4), LN4(-4) 104547

For 2 switches of the same or different type with opposed operation.


Extra long Bowden cable for mounting one above the other or in
adjacent enclosures.

LZM2(-4), LN2(-4) NZM2-XMVRL 1 off Type contains parts for both switches.
+LZM2(-4), LN2(-4) 104548 Remote operator also required.
LZM2(-4), LN2(-4) NZM2/3-XMVRL Maximum switching distance
+LZM3(-4), LN3(-4) 104549 a engineering
Cannot be combined with rotary handles,
LZM3(-4), LN3(-4) NZM3-XMVRL door coupling rotary handles and early-make
+LZM3(-4), LN3(-4) 104550 auxiliary contacts.
LZM3(-4), LN3(-4) NZM3/4-XMVRL
+LZM4(-4), LN4(-4) 104551
LZM4(-4), LN4(-4) NZM4-XMVRL
+LZM4(-4), LN4(-4) 104552
Ordering 63
Multi-function device adapter
http://catalog.moeller.net Moeller SK1230-1177GB NZM...-XAD..., NZM...-XKR...

Circuit-breakers, switch-disconnectors
For use with Rated current Part no. Price Std. pack Notes
Article no. when see price
ordered list
separately
Ie
A

Component adapter for circuit-breakers and switch-


disconnectors for 60 mm busbar system
For installation on flat copper busbars 12 30 x 5 10,
double T and triple T profile
Rated operational voltage Ue: 690 V
Halogen free
Temperature resistant to 120 C
Self-extinguishing to UL 94
Approved for feeder branch circuits to UL508A up to 600 V
3 pole
LZM1, LN1 160 NZM1-XAD160 1 off For breakers with box terminal as standard connection
104554 Connection to system at top using the supplied
connection cable
In conjunction with IP2X protection against contact
with a finger
Enhancement of the protection against direct contact
on the switch outgoer side possible
LZM2, LN2 250 NZM2-XAD250 Connection to the system possible at top or bottom via
104555 connection on rear (+)NZM2-XKR4
Mounting using clamp and screw fixing.

LZM3, LN3 550 NZM3-XAD550 Connection to the system possible at top via connection
104556 on rear (+)NZM3-XK13
Mounting using clamp and screw fixing.

For use with Rated current Part no. suffix Price Part no. Price Std. pack
Article no. when ordered see price Article no. when ordered see price
with basic unit list separately list

Ie
A

Connection on rear for component adapters


For component adapters for LZM2, LZM3

LZM2, LN2 250 +NZM2-XKR4O NZM2-XKR4 1 off


281664 281666
LZM2, LN2 250 +NZM2-XKR4U NZM3-XKR13
281665 281668
LZM3, LN3 550 +NZM3-XKR13O
281667

Notes Part no. and part no. suffix include parts for one switch side at top or bottom (with LZM3 top only). Required with component adapter and
switch with connection on rear, see for example component adapter 104555 and 104556.
O = for fitting at the top
U = for fitting at the bottom
64 Ordering Ordering 65
Accessories Accessories
LZM2, LZM3, LZM4 Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM2, LZM3, LZM4
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
For use with Rated control voltage Part no. Price Std. pack
Article no. when ordered see price Notes
separately list
Us
V

Remote operator
For remote switching of circuit-breakers and switch-disconnectors.
ON and OFF switching and resetting by means of 2-wire or 3-wire control.
Can be synchronized.
Local switching by hand possible
Lockable in the 0 position of the remote operator with up to 3 padlocks (hasp thickness: 4 8 mm)
LZM2(-4), LN2(-4) 110 130 V 50/60 Hz NZM2-XR110-130AC 1 off
A standard auxiliary contact (HIN) for the switch position detection is supplied.
259830
When installing the NZM2-XR and NZM3-XR remote operators on 4 pole switches, an additional 4 pole NZM2-XAVPR or NZM3-XAVPR shroud is necessary.
208 240 V 50/60 Hz NZM2-XR208-240AC
259832 3-wire control
380 440 V 50/60 Hz NZM2-XR380-440AC1) L1 Terminal 70/71:
259834 (L1+)
0 I Please note during engineering:
H1
24 30 V DC NZM2-XR24-30DC Full current flows though the contact during make and break!
259836 70 71 72 RMQ series contact elements can be used for the NZM2(3,4)-XR remote operators.
110 130 V DC NZM2-XR110-130DC 75
259840 74
N
220 250 V DC NZM2-XR220-250DC (L1, L2)
259842
LZM3(-4), LN3(-4) 110 130 V 50/60 Hz NZM3-XR110-130AC
259848 2-wire control
208 240 V 50/60 Hz NZM3-XR208-240AC L1 Terminal 75:
(L1+) 0 I
259850 S Operational readiness signal when the cover is closed, and not locked.
H1
380 440 V 50/60 Hz NZM3-XR380-440AC1) AC-15: 400 V; 2 A
259852 70 71 72 DC-13: 220 V; 0.2 A
24 30 V DC NZM3-XR24-30DC 75
259854 74
N
110 130 V DC NZM3-XR110-130DC (L1, L2)
259858 Three-wire control with automatic reset to the 0 position after the switch has tripped
220 250 V DC NZM3-XR220-250DC L1
259860 (L1+)
0 I
LZM4(-4), LN4(-4) 110 130 V 50/60 Hz NZM4-XR110-130AC HIA H1
266684
70 71 72
208 240 V 50/60 Hz NZM4-XR208-240AC 75
266685 74
N
380 440 V 50/60 Hz NZM4-XR380-440AC1) (L1, L2)
266686
24 30 V DC NZM4-XR24-30DC Switching cycle:
266691 NZM2-XR
110 130 V DC NZM4-XR110-130DC 60 ms t>3s 60 ms
266693 r r r r
220 250 V DC NZM4-XR220-250DC OFF ON ON OFF OFF ON
266694
NZM3-XR
Shroud for 4th pole
80 ms t>3s 80 ms
Additional shroud for mounting the NZM2-XR... and NZM3-XR... on a 4-pole switch. r r r r
LZM2-4, LN2-4 NZM2-XAVPR 1 off OFF ON ON OFF OFF ON
266677
LZM3-4, LN3-4 NZM3-XAVPR 1 off NZM4-XR
266678 100 ms t>3s 100 ms
Clamp terminal springloaded clamp r r r r
OFF ON ON OFF OFF ON
Control circuit terminal springloaded terminals
NZM...-XR... NZM-XRC 1 off The time interval between OFF and ON is 3 seconds.
266696
On commands received during the time interval are ignored within the first 3 seconds after switch off.

Protective cover for door cutout


Transparent protective shroud to increase the degree of protection to IP54
RTR-NZM10 1 off Electrical remote switching and manual tripping (push to trip) are still possible.
034825
66 Ordering Ordering 67
Insulated enclosures Insulated enclosures
NZM...-XCI... Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB NZM...-XCI...
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Max. rated For use with Part no. Price Std. pack Insulated enclosure Retrofit terminals with 3-pole switches: for 4th and 5th (if Notes
uninterrupted Article no. when ordered see price description required) conductor (N, PE-conductor), with 4-pole
current separately list switches: for 5th conductor (PE conductor)
Iu
A

Insulated enclosures
With door coupling rotary handle
Complete incl. all necessary functional parts
Degree of protection IP65
not UL/CSA approved
Standard, black/grey
Lockable on the 0 position on the handle F 63 A NZM1, LN1 NZM1-XCI23-TVD 1 off CI23-150 K10/1, K25/1 Suitable for installation of circuit-breakers and switch-disconnectorsEnclosure
using up to 3 padlocks. Additionally with 271522 for separate mounting with top and bottom cable entry.
cover interlock. F 125 A NZM1(-4), LN1(-4) NZM1-XCI43-TVD CI43-150 K10/1, K25/1, K50/1, K95/1N/BR Include fixing straps for wall mounting.
271523 Short-circuit resistance at 415 V 50/60 Hz to 10 kA.
F 160 A NZM1(-4), LN1(-4) NZM1-XCI43/2-TVD CI43-200 K10/1, K25/1, K50/1, K95/1N/BR Cannot be used in combination with NZM-XR remote operator,
104645 NZM-XSV plug-in unit or NZM-XAV withdrawable unit.
F 200 A NZM2(-4), LN2(-4) NZM2-XCI43-TVD CI43-200 K10/1, K25/1, K50/1, K95/1N/BR, K150/1/BR, K240/1/BR Insulated additional terminal for 4th or 5th pole should be ordered separately.
271524
F 250 A NZM2(-4), LN2(-4) NZM2-XCI45-TVD CI45-200 K10/1, K25/1, K50/1, K95/1N/BR, K150/1/BR, K240/1/BR CI23 enclosure with flanges
280418 CI43, CI45 and CI48 feature gland plates.
F 400 A NZM3(-4), LN3(-4) NZM3-XCI48-TVD CI48-250 K95/1N/BR, K150/1/BR, K240/1/BR, K2X240/1/BR Only for switches with tunnel clamps for direct connection of cables.
271525
Red-yellow for Emergency-Stop
Lockable on the handle and on the switch F 63 A NZM1, LN1 NZM1-XCI23-TVDVR 1 off CI23-150 K10/1, K25/1
using up to 3 padlocks each. Lockable in 271527
0 position on handle. Cover interlock as F 125 A NZM1(-4), LN1(-4) NZM1-XCI43-TVDVR CI43-150 K10/1, K25/1, K50/1, K95/1N/BR
additional feature, locking facility on 271528
circuit-breaker in 0 position.
F 160 A NZM1(-4), LN1(-4) NZM1-XCI43/2-TVDVR CI43-200 K10/1, K25/1, K50/1, K95/1N/BR
104646
F 200 A NZM2(-4), LN2(-4) NZM2-XCI43-TVDVR CI43-200 K10/1, K25/1, K50/1, K95/1N/BR, K150/1/BR, K240/1/BR
271529
F 250 A NZM2(-4), LN2(-4) NZM2-XCI45-TVDVR CI45-200 K10/1, K25/1, K50/1, K95/1N/BR, K150/1/BR, K240/1/BR
279356
F 400 A NZM3(-4), LN3(-4) NZM3-XCI48-TVDVR CI48-250 K95/1N/BR, K150/1/BR, K240/1/BR, K2X240/1/BR
271530

Rated Terminal capacities Part no. Price Std. pack


uninterrupted Article no. when ordered see price
current separately list
Iu
A mm2

Additional insulated terminals


For looping through the neutral and protective conductor
1-pole
32 Flexible, 1 x (1.5 6) K10/1 10 off
093827
63 Flexible, 1 x (6 16), stranded, 1 x (16 25 ) K25/1
096200
100 Flexible, 1 x (10 35), stranded, 1 x (16 50) K50/1
098573
160 Stranded, 1 x (16 95) K95/1N/BR 1 off
012336
250 Stranded, 1 x (35 150), 2 x (16 70) K150/1/BR
014709
400 Stranded, 1 x (50 240), 2 x (25 120) K240/1/BR
017082
630 Stranded, 1 x (240 300), 2 x (50 240) K2X240/1/BR
019455
68 Ordering
Residual-current release frequency response
NZM...XFI... Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

For use with Part no. Price Std. Notes


Order number for see price pack
separate orders list

Earth-fault release
Suitable for use in three- and single-phase systems
Pulse current sensitive according to core-balance principle

For 3- and 4 pole LZM1(-4) circuit-breakers and LN1(-4) switch-disconnectors,


dependant on mains power Ue = 200 415 V 50/60 Hz,
Rated fault current NZM1 3 pole NZM1-XFI30R 1 off IEC/EN 60947-2
IDn = 0.03 A LN1 104603 With Idn = 0.03 A: delay time tv always
NZM1-4 4 pole NZM1-4-XFI30R fixed settings at 10 ms.
LN1-4 104606 Alarm message > 30 % Idn via yellow
LED.
Rated fault current NZM1 3 pole NZM1-XFI300R Trip indication max. 2 auxiliary contacts
IDn = 0.3 A LN1 104604 (HIAFI) can be fitted by user: N/O =
NZM1-4 4 pole NZM1-4-XFI300R M22-K01, N/C = M22-K10 are reset via
LN1-4 104607 the reset toggle lever.
Rated fault current NZM1 3 pole NZM1-XFIR If the trip-indicating auxiliary contact in
IDn = 0.03 0.1 0.3 0.5 1 3 A, LN1 104605 the fault current block is used, the N/C
delay time contacts operates as a N/O contact and
NZM1-4 4 pole NZM1-4-XFIR the N/C contact operates as an N/O
tv = 10 60 150 300 450 ms. LN1-4 104608 contact (see HIAFI marking).
Not in combination with insulated
Bottom mounting up to 100 A enclosure or main switch assembly kit
Rated fault current NZM1 3 pole NZM1-XFI30U1) for side panel mounting with mounting
IDn = 0.03 A LN1 104609 bracket
NZM1-4 4 pole NZM1-4-XFI30U NZM1-XFIU not in combination with
LN1-4 104612 shunt or undervoltage relase.
Rated ultimate short-circuit breaking
Rated fault current NZM1 3 pole NZM1-XFI300U capacity is determined by the fitted
IDn = 0.3 A LN1 104610 LZM1, LN1.
NZM1-4 4 pole NZM1-4-XFI300U If a switch-disconnector is applied by
LN1-4 104613 the backup fuse to be used
Rated fault current NZM1 3 pole NZM1-XFIU a Technical Data
IDn = 0.03 0.1 0.3 0.5 1 3 A, LN1 104611
delay time NZM1-4 4 pole NZM1-4-XFIU
tv = 10 60 150 300 450 ms. LN1-4 104614
Pulse current sensitive according to core-balance principle

For 4 pole circuit-breaker LZM2-4 and switch-disconnectors LN2-4 IEC/EN 60947-2


independent of mains voltage Ue = 280 690 V 50/60 Hz Auxiliary contacts (1 N/O, 1N/C
bottom mounting up to 250 A integrated) are reset via the reset
Rated fault current NZM2-4 4 pole NZM2-4-XFI30 1 off button.
IDn = 0.03 A LN2-4 292343 Not in combination with plug-in units,
insulated enclosure or main switch
Rated fault current NZM2-4 4 pole NZM2-4-XFI 1 off assembly kit for side panel mounting
IDn 0.1 - 0.3 - 1 - 3 A, LN2-4 292344 with mounting bracket.
delay time Rated ultimate short-circuit breaking
tv = 60 - 150 - 300 - 450 ms capacity is determined by the fitted
LZM2.
If a switch-disconnector is applied by
the backup fuse to be used
a Technical Data
Core-balance principle with AC/DC current sensitivity (in
range 0 100 kHz)

For 4 pole LZM2-4 circuit-breakers and switch-disconnectors LN2-4 IEC/EN 60947-2


internal power supply Ue = 50 400 V, Observe response threshold
bottom mounting up to 250 A dependence on frequency!
Rated fault current NZM2-4 4 pole NZM2-4-XFIA30 1 off See Frequency response
IDn = 0.03 A LN2-4 292345 characteristic curve
Auxiliary contacts (1 N/O, 1N/C
Rated fault current NZM2-4 4 pole NZM2-4-XFIA 1 off integrated) are reset via the reset
IDn 0.1 - 0.3 - 1 A, LN2-4 292346 button.
delay time Not in combination with plug-in units,
tv = 60 - 150 - 300 - 450 ms insulated enclosure or main switch
assembly kit for side panel mounting
with mounting bracket.
Rated ultimate short-circuit breaking
capacity is determined by the fitted
LZM2.
If a switch-disconnector is applied by
the backup fuse to be used
a Technical Data
Notes 1) Suitable for use in three-phase systems
Ordering 69
Residual-current release frequency response
http://catalog.moeller.net Moeller SK1230-1177GB NZM3, NZM4, PFR-...

Circuit-breakers, switch-disconnectors
For use with Part no. Price Std. pack Notes
Article no. when see price
ordered with list
basic unit

Earth-fault release, 3-pole, 4-pole


Not dependent on mains and control voltages LZM3 +NZM3-XT 1 off Only suitable for use in conjunction with
Ig = 0.35 0.4 0.5 0.6 0.7 0.8 0.9 1.0 x In LN3 260756 circuit-breakers having electronic
tg = 0 20 60 100 200 300 500 750 1000 ms LZM3-4 +NZM3-4-XT releases.
LN3-4 260757
LZM4 +NZM4-XT
LN4 266721
LZM4-4 +NZM4-4-XT
LN4-4 266722

Description Part no. Price Std. pack Notes


Article no. see price list

Residual current relay


Pulse-current sensitive
Rated control supply voltage: Us = 230 V AC (50/60Hz)
Integrated auxiliary contact (1 C/O)
Ring-type transformer must also be ordered
Rated fault current IdN = 0.03 A PFR-003 1 off
285555
Rated fault current IdN = 0.3 A PFR-03
285556
Rated fault current IdN = 0.03 5 A PFR-5 Adjustable fault current: 0.03, 0.1, 0.3,
Adjustable fault current and delay time 285557 0.5, 1, 3, 5 A
Fault current early warning by flashing, red LED Adjustable delay time: 0.02, 0.1, 0.3, 0.5,
1, 3, 5 A

Ring-type transformer
Rated operational voltage: 690 V (50/60 Hz)
Internal diameter: 20 mm PFR-W-20 1 off incl. fixing clip for DIN rail mounting
285558
Internal diameter: 30 mm PFR-W-30
285559

Internal diameter: 35 mm PFR-W-35 incl. screw fixing


285600 Alternative: fixing clip for DIN mounting
Internal diameter: 70 mm PFR-W-70 rail
285601 Design note:
Internal diameter: 105 mm PFR-W-105 The current transformer diameter must
285602 be selected 1.5 times larger than the
envelope diameter of the passed through
Internal diameter: 140 mm PFR-W-140 conductor.
285603
Internal diameter: 210 mm PFR-W-210
285604
Magnetic shielding
PFR-W-35 PFR-WMA-35 1 off Necessary for a load circuit with high
286001 inrush currents > 4 x In, such as for
example motors and
PFR-W-70 PFR-WMA-70
286002
PFR-W-105 PFR-WMA-105
286003
PFR-W-140 PFR-WMA-140
286004
PFR-W-210 PFR-WMA-210
286005
Fixing clip
for the DIN rail mounting of the PFR-W-35 PFR-WC 1 off 1 set = 2 pieces
current transformer and all larger 286006
70 Engineering Engineering 71
Selectivity: incoming circuit-breaker, outgoing circuit-breaker Selectivity: incoming circuit-breaker, outgoing circuit-breaker
LZM, FAZ-B(C), PKZ Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM, FAZ-B(C), PKZ
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Selectivity 415 V AC
Incomin between circuit-breakers enables separate shut-down of faulty system sections.
1 g
circuit- Selectivity (discrimination) exists between incoming breaker 1 and outgoing breaker 2 if,
2 3 4 breaker only outgoing breaker 2 trips at position 2 during a short-circuit.
System sections 3 and 4 continue to operate.
Incoming circuit-breaker (S1) Incoming circuit-breaker (S1) Incoming circuit-breaker (S1)
LZM...1-A... LZM...2-A... LZM...3-AE... LZM...3-VE... LZM...4-AE... LZM...4-VE...

Icu [kA] 18(25)(36) 25(36) 36(50) 36(50) 50 50


In [A] 20...40 50 63 80 100 125 160 160 200 250 300 630 400 630 800 1000 1250 1600 800 1000 1250 1600
Outgoing In Icu(415V) Selectivity threshold Is [kA] for selectivity between S2 and S1, overload and short-circuit release set to max. value Selectivity threshold Is [kA] for selectivity between S2 and S1, overload and short-circuit release set to max. value
circuit-breaker (S2) [A] [kA]
FAZB(C) 0.5 15 T T T T T T T T T T T T T T T T T T T T T T
1 15 T T T T T T T T T T T T T T T T T T T T T T
2 15 2 T T T T T T T T T T T T T T T T T T T T T
3 15 1.2 2 3 3 10 T T T T T T T T T T T T T T T T T
4 15 1.2 2 3 3 8 T T T T T T T T T T T T T T T T T
6 15 1.2 2 2.5 3 5 10 10 T T T T T T T T T T T T T T T
10 15 1.2 1.5 2 2 4 10 10 10 10 10 10 T T T T T T T T T T T
13 15 1 1.5 2 2 4 10 10 10 10 10 10 T T T T T T T T T T T
16 15 1 1.2 1.5 2 3 8 8 10 10 10 10 T T T T T T T T T T T
20 15 0.8 1.2 1.5 1.5 3 8 8 10 10 10 10 T T T T T T T T T T T
25 15 0.7 1.2 1.5 1.5 3 7 7 10 10 10 10 T T T T T T T T T T T
32 15 1.2 1 1.5 2 6 6 8 8 10 10 T T T T T T T T T T T
40 15 1 1.5 2 5 5 7 7 10 10 T T T T T T T T T T T
50 15 1.2 1.5 4 4 6 6 10 10 T T T T T T T T T T T
63 15 1.5 3 3 6 6 10 10 T T T T T T T T T T T
PKZM0-... 0.16 100 T T T T T T T T T T T T T T T T T T T T T T
0.25 100 T T T T T T T T T T T T T T T T T T T T T T
0.4 100 T T T T T T T T T T T T T T T T T T T T T T
0.63 100 T T T T T T T T T T T T T T T T T T T T T T
1 100 T T T T T T T T T T T T T T T T T T T T T T
1.6 100 T T T T T T T T T T T T T T T T T T T T T T
2.5 100 T T T T T T T T T T T T T T T T T T T T T T
4 100 T T T T T T T T T T T T T T T T T T T T T T
6.3 100 4 5 5 T T T T T T T T T T T T T T T T T T T
10 100 3 4 5 6 25 T T T T T T T T T T T T T T T T T
12 50 3 4 5 6 25 T T T T T T T T T T T T T T T T T
16 50 1.5 1.5 2 3 5 7 T T T T T T T T T T T T T T T T
20 50 0.8 1.5 1.5 2 3 5 T T T T T T T T T T T T T T T T
25 50 1 1.5 1.5 2.5 4 T T T T T T T T T T T T T T T T
32 50 1 1 2 3.5 T T T T T T T T T T T T T T T T
PKZ2/ZM-... 0.6 100 T T T T T T T T T T T T T T T T T T T T T T
1.0 100 T T T T T T T T T T T T T T T T T T T T T T
1.6 100 T T T T T T T T T T T T T T T T T T T T T T
2.4 100 1.2 2 2.5 10 T T T T T T T T T T T T T T T T T T
4 100 1 1.5 2 2.5 2.5 4 10 10 10 T T T T T T T T T T T T T
6 100 0.6 0.8 1 1.2 2 3 8 8 8 10 10 T T T T T T T T T T T
10 100 0.5 0.7 0.8 1 1.2 2 4 4 4 5 5 T 13 T T T T T T T T T
16 100 0.5 0.6 0.7 0.8 1.2 1.5 3 3 3 4 4 T 7 T T T T T T T T T
25 30 0.6 0.7 0.7 1.2 1.5 2 2 2 3 3 20 5 20 T T T T T T T T
32 30 0.6 0.7 1.2 1.5 2 2 2 3 3 15 3.5 15 T T T T T T T T
40 30 0.6 0.7 1 1.5 2 2 2 2 2 15 3.5 15 T T T T T T T T
PKZM4 16 100 0.5 0.8 0.8 0.8 2 5 5 5 5 5 5 45 16 45 T T T T T T T T
25 100 0.7 0.8 0.8 1.5 5 5 5 5 5 5 25 10 25 42 T T T 42 T T T
32 50 0.8 0.8 1.5 4 4 4 4 4 4 18 8 18 30 45 T T 30 45 T T
40 50 0.8 1.5 3 3 3 3 3 3 18 8 18 30 45 T T 30 45 T T
50 50 1 2.5 2.5 2.5 2.5 2.5 2.5 18 8 18 30 45 T T 30 45 T T
58 50 2.5 2.5 2.5 2.5 2.5 2.5 15 6.5 15 25 40 T T 25 40 T T
63 50 2 2 2 2 2 2 15 6.5 15 25 40 T T 25 40 T T
Notes T: full selectivity
72 Engineering Engineering 73
Selectivity: incoming circuit-breaker, outgoing circuit-breaker Selectivity: incoming circuit-breaker, outgoing circuit-breaker
LZM Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Selectivity 415 V AC
Incoming between circuit-breakers enables separate shut-down of faulty system sections.
1 circuit-breaker Selectivity (discrimination) exists between incoming breaker 1 and outgoing breaker 2 if,
only outgoing breaker 2 trips at position 2 during a short-circuit.
2 3 4 Outgoing System sections 3 and 4 continue to be operational.
circuit-breaker
Incoming circuit-breaker (S1) Incoming circuit-breaker (S1)
LZM...1-A... LZM...2-A... LZM...3-AE... LZM...3-VE... LZM...4-AE... LZM...4-VE...

Icu[kA] 18(25)(36) 25(36) 36(50) 36(50) 50 50


In[A] 20...40 50 63 80 100 125 160 160 200 250 300 630 400 630 800 1000 1250 1600 800 1000 1250 1600
Outgoing circuit- In Icu(415V) Prospective short-circuit current (kA). Set the overload and short-circuit release of the incoming Prospective short-circuit current (kA). Set the overload and short-circuit release of the incoming
breaker (S2) [A] [kA] circuit-breaker to the max. value. circuit-breaker to the max. value.
LZM...1-A... 20...40 25...100 0.5 0.7 0.8 1.5 1.5 1.5 2 3 3 20 25 25 T T T T T T T T
50 25...100 0.6 0.8 1.5 1.5 1.5 2 3 3 20 25 25 T T T T T T T T
63 25...100 0.8 1.5 1.5 1.5 2 3 3 15 20 20 T T T T T T T T
80 25...100 1.5 1.5 1.5 2 3 3 15 20 20 T T T T T T T T
100 25...100 1.5 1.5 2 3 3 15 20 20 T T T T T T T T
125 25...100 2 3 3 15 20 20 T T T T T T T T
160 25...100 2 3 3 15 20 20 T T T T T T T T
LZM...2-A... 160 25...150 2 2 10 15 15 T T T T T T T T
200 25...150 10 15 15 T T T T T T T T
250 25...150 10 15 15 T T T T T T T T
LZM...3-AE... 400 50...150 7.5 12 T T T T T T T T
630 50...150 T T T T T T T T
LZM...3-VE... 400 50...150 4 12 T T T T T T T T
630 50...150 T T T T T T T T
LZM...4-AE... 800 50...100 20 20 20 20
1000 50...100 20 20 20 20
1250 50...100 20 20
1600 50...100
LZM...4-VE... 800 50...100 20 20 20 20
1000 50...100 20 20 20 20
1250 50...100 20 20
1600 50...100
Notes T: total selectivity
74 Engineering
MCB, back-up protection
LZM1, LZM2, LZM3 Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Protection of PVC insulated cables against thermal overload with short-circuits


According to VDE 0100 part 430 cables and Short-circuit protection is provided by adjustable The tables indicate the minimum conductor cross-
conductors must be protected against short-circuit instantaneous releases, which open the main contacts section reliably protected by circuit-breakers during a
and overload. The overload protection is obtained by in less than 25 ms. The short-circuit total opening short-circuit. (Operating voltage UN = 415 V)
using LZM circuit-breakers with settable, current- time restricts the temperature rise of the cable to a
dependent, delayed overload release. minimum.

Min. protected cross-section mm2 copper


LZM...1(-4)-...20 6
LZM...1(-4)-...25 160 10
LZM...2(-4)-...20 300 10
LZM...3(-4)-...250 630 16
LZM...4(-4)-...630 1600 95

Back-up protection
between LZM(N)(S) incoming circuit-breaker and LZM(E)(B)(C)(N) outgoing circuit-breaker
Incoming circuit-breaker a
LZM1 LZM2 LZM3
In up to 160 A up to 300 A up to 630 A
Icu(415 V) 25 kA 36 kA 25 kA 36 kA 50 kA
a Outgoing circuit-breaker b
Icu(415 V) In
LZME1 16 kA up to 160 A 25 36 25 36 50
LZMB1 25 kA up to 160 A 25 36 25 36 50
b LZMC1 36 kA up to 160 A 36 36 50
LZMB2 25 kA up to 300 A 25 36 25 36 50
LZMC2 36 kA up to 300 A 36 36 50
LZMC3 36 kA up to 630 A 50
LZMN3 50 kA up to 630 A 50

Where the prospective fault current at the point of The table shows which current-limiting circuit-breaker The selectivity limit is determined by the response
installation of circuit-breakers is very high, it is LZMN in combination with LZMB(C) are to be used to current of the non-delayed short-circuit release in the
conventional to use LZMN current-limiting circuit- provide protection at the network locations with high upstream incoming circuit-breaker. In many
breakers. An attractively priced alternative is to fit a short-circuit capacities. applications this is sufficient.
LZMN current-limiting circuit-breaker upstream of
LZMB(C) standard circuit-breakers, if the fault level is
too high for LZMB(C) switches.

between LZM...1-A... incoming circuit-breaker and FAZ-B(C)/PLSM-B(C)... outgoing circuit-breaker


Icc Outgoing circuit- Outgoing circuit-breaker
breaker LZM(B)(C)2-A... LZMC(N)1-A...
LZM...
FAZ-B(C)...
PLSM 0,5 16 25 kA 30 kA
20 40 20 kA 20 kA
50, 63 15 kA 15 kA
PLSM-B(C)...(/...)
0,5 16 25 kA 30 kA
20 40 20 kA 20 kA
50, 63 15 kA 15 kA

between LZM...2-A... incoming circuit-breaker and FAZ-B(C)/PLSM-B(C)... outgoing circuit-breaker


Icc Outgoing circuit- Incoming circuit-breaker
breaker LZMB(C)2-A... LZMN2-A...
LZM...
FAZ-B(C)...
PLSM 0,5 10 25 kA 50 kA
13 32 25 kA 30 kA
40 63 20 kA 20 kA
PLSM-B(C)...(/...)
0,5 10 25 kA 50 kA
13 32 25 kA 30 kA
40 63 20 kA 20 kA
Engineering 75
Direction of blow-out, minimum clearances, tube cable lugs
http://catalog.moeller.net Moeller SK1230-1177GB LZM1, LZM2, LZM3, LZM4

Circuit-breakers, switch-disconnectors
Direction of blow-out
Top, front Bottom,
rear
LZM1 X
LZM21) X X
LZM3 X X
LZM4 X
1) LZM2E(B)(C) A as LZM1

Minimum clearances
between two adjacently mounted switches
Minimum clearance a in mm
c

LZM1 LZM2 LZM3 LZM4


LZM1 0 5 5 15
LZM2 5 5 5 15
LZM3 5 5 5 15
d

LZM4 15 15 15 15
b a b
between switch and other parts
Minimum clearances in mm
b c d
F 690 V 1000 V F 690 V 1000 V F 690 V 1000 V
LZM1 0 60 0
LZM21) 5 5 35 35 35 35
LZM3 5 5 60 60 60 60
LZM4 15 15 100 200 0 0

1) LZM2B(C) A C= 60 mm, d = 0 mm

Dimensions
For pressing the cable lugs a press tool K22, HK60/22 or EK22
from the company Klauke is necessary with the following press inserts:
R22/95 for 95 mm2
h

R22/120 for 120 mm2


R22/150 for 150 mm2
i

R22/185 for 185 mm2


g
R22/240 for 240 mm2

d e
b

c
f

Cable lug For use with Rated cross Terminal bolt Dimensions in mm
section
mm2 o a b c d e f g h i
KS95-NZM7 LZM2 95 M8 53+2 23g0.5 18g0.2 10g1 19 8,5 25 13,5 4,4
KS120-NZM7 LZM2 120 M8 56+2 23g0.5 19.5g0.2 10g1 19 8,5 26 15 4,4
KS150-NZM7 LZM2 150 M8 61+2 23g0.5 21g0.2 10g1 19 8,5 30 16,5 4,4
NZM2-XKS185 LZM2 185 M8 65g1.5 22g1 24g0.3 9+1
0,5 19+2,5
0,5 8.5+0,05
0,1 30g2 19g0.4 7
NZM3-XKS185 LZM3, LZM4 185 M10 65 24,5 24 11,5 18 10,5 30 19 7.0g0.8
NZM3-XKS240 LZM3, LZM4 240 M10 72 31 26 11,5 19 10,5 35 21 5.0g0.8
76 Engineering
Auxiliary switches, trip-indicating auxiliary contacts
LZM1, LZM2, LZM3, LZM4 Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Front cut-out
Cut-out a Cut-out b
toggle lever rotary handle,
remote operator

Y Y

X X X

e
e

f f

c
d

Distance from mounting plate and Cut-out a Cut-out b


door cutout
c d e f e f
mm mm mm mm mm mm
LZM1 68 73 40 23 46 91
LZM2 103 108 79 36 96 101
LZM3 120.5 125.5 79 36 96 136
LZM4 138 146 101 105 118 204

Standard auxiliary contact Early-make auxiliary contact (HIV) Trip-indicating auxiliary


(HIN) contact (HIA)
I LZM 1, 2, 3 LZM 4 I
+ I I +
L1L2L3 + + L1L2L3
L1L2L3 L1L2L3
HIN HIA
HIV HIV
I I
+ I I +
L1L2L3 + + L1L2L3
L1L2L3 L1L2L3
HIN HIA
HIV HIV

+ I + I
+ + I + I +
L1L2L3 + + L1L2L3
L1L2L3 L1L2L3
HIN HIA
HIV HIV

0lI Switching on Q Contact closed


q Contact open
0mI Switching off

+mI Trip

Notes If early-make contacts are required in combination with shunt or undervoltage releases,
please select the combination type in the Release section.
Engineering 77
Mechanical interlock for (door-coupling) rotary handles
http://catalog.moeller.net Moeller SK1230-1177GB LZM, NZM-XBZ-

Circuit-breakers, switch-disconnectors
Interlocking variants and combination options
A B
OFF OFF
A B ON/TRIP ON

ON ON/TRIP

A B C
OFF OFF OFF
A B C ON ON/TRIP ON

ON/TRIP ON ON/TRIP

A B C
OFF OFF OFF
ON/TRIP ON ON
A B C
ON ON/TRIP ON

ON ON ON/TRIP

A B C D
OFF OFF OFF OFF
ON/TRIP ON ON/TRIP ON
A B C D
ON ON/TRIP ON ON/TRIP

x4P x4P
= Switch clearance 3 pole
x3P x3P = Switch clearance 4 pole

NZM-XBZ225 right switch


max. switch clearance LZM1 LZM2 LZM3 LZM4
X3P X4P X3P X4P X3P X4P X3P X4P
left switch mm mm mm mm mm mm mm mm
LZM1 3/4 pole 135 105 120 85 135 90 125 80
LZM2 3/4 pole 135 105 120 85 135 90 125 80
LZM3 3/4 pole 90 75 75 35 85 40 80 45
LZM4 3/4 pole 50 35 40 15 25 15

NZM-XBZ600 right switch


max. switch clearance LZM1 LZM2 LZM3 LZM4
X3P X4P X3P X4P X3P X4P X3P X4P
left switch mm mm mm mm mm mm mm mm
LZM1 3/4 pole 510 480 495 460 510 465 475 405
LZM2 3/4 pole 510 480 495 460 510 465 475 405
LZM3 3/4 pole 460 430 450 410 460 415 460 390
LZM4 3/4 pole 400 370 380 340 400 375 390 320

NZM-XBZ1000 right switch


max. switch clearance LZM1 LZM2 LZM3 LZM4
X3P X4P X3P X4P X3P X4P X3P X4P
left switch mm mm mm mm mm mm mm mm
LZM1 3/4 pole 910 880 895 860 910 865 865 795
LZM2 3/4 pole 910 880 895 860 910 865 865 795
LZM3 3/4 pole 820 790 850 810 860 815 860 790
LZM4 3/4 pole 750 720 730 700 800 775 790 720
78 Engineering
Mechanical interlock for remote operator, residual-current relay
NZM-XMVR(L) Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

XMVR mechanical interlock


(Mounting adjacent)
NZM...-XMVR
Max. switch clearance right switch
LZM2 LZM3 LZM4
X3p X4p X3p X4p X3p X4p
left switch mm mm mm mm mm mm
LZM2 3/4 pole 130 95 95 50
LZM3 3/4 pole 135 90 155 85
LZM4 3/4 pole 120 50

x4P

3P

X3p = max. switch clearance 3 pole


X4p = max. switch clearance 4 pole

XMVRL mechanical interlock


Mounting in adjacent enclosures
NZM...-XMVRL
Max. switch clearance right switch
LZM2 LZM3 LZM4
X3p X4p X3p X4p X3p X4p
left switch mm mm mm mm mm mm
LZM2 3/4 pole 350 315 420 385
LZM3 3/4 pole 400 365 460 390
LZM4 3/4 pole 420 350

XMVRL mechanical interlock


(Mounting one above the other)
NZM-XMVRL
Max. switch clearance Switch top
LZM2 LZM3 LZM4
3/4 pole 3/4 pole 3/4 pole
Y Y Y
Switch bottom mm mm mm
LZM2 3/4 pole 220 225
LZM3 3/4 pole 220 230
LZM4 3/4 pole 230

Y = max. switch clearance

Ring-type transformer
Maximum rated current [A] Diameter
Power Motor/capacitor Transformer part Max. conductor
distribution no. circumference
PFR-W- (mm)
d1 d2
50 50 20 13 d2
150 100 30 20 d1 f 1.5 x d2
150 100 35 23
400 200 70 47
600 250 105 70
1200 630 140 93
1800 800 210 140
Engineering 79
Sizes 1, 2: tripping characteristics
http://catalog.moeller.net Moeller SK1230-1177GB LZM1, LZM2

Circuit-breakers, switch-disconnectors
System and line protection with LZM1
2.5 h 8000 LZM1(-4)-A...
6000
Tripping time [s]

4000

2000

1000
800
(10 min) 600
400

200

100
80
(1 min) 60
40
Tolerance tr [s]

20

10
8
6
4

1 Setting range
0.8
0.6
0.4
Ii = 6 10x In
0.2

0.1
0.08
0.06
0.04

0.02

0.01
0.008
0.006
0.004

0.002

0.001
1 2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100
x Ir

System and line protection with LZM2 Systems, cable, selectivity and generator protection with LZM2
2.5 h 8000 2.5 h 8000 LZM2(-4)-VE...
LZM2(-4)-A...
6000 6000
Characteristics for Ir = 1,0 x In
Tripping time [s]

Tripping time [s]

4000 4000

2000 2000

1000 1000
800 800
(10 min) 600 (10 min) 600
400 400

200 200

100 100
80 80
(1 min) 60 (1 min) 60
40 40
Tolerance tr [s]

tr [s]
20 20
20 17
14
10 10 10
8 8 8
6 6 6
4 4 4

2 2 2
tsd [ms]
1 Setting range 1 1000
0.8 0.8 750
0.6 0.6 500
0.4 0.4
300
Ii = 6 10x In 200
0.2 0.2
100
0.1 0.1
0.08 60
0.08
0.06 0.06 20
0.04 0.04 Isd = 2 3 4 5 6 7 8 9 10 x Ir
0
0.02 0.02 Ii = 12 x In

0.01 0.01
0.008 0.008
0.006 0.006
0.004 0.004

0.002 0.002

0.001 0.001
1 2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100 1 2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100
x Ir x Ir
80 Engineering
Size 3: tripping characteristics
LZM3 Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

System and line protection with LZM3 Systems, cable, selectivity and generator protection with LZM3
2.5 h 8000 2.5 h 8000 LZM3(-4)-VE...
LZM3(-4)-AE...
6000 6000
Characteristics for Ir = 1,0 x In 4000 Characteristics for Ir = 1,0 x In

Tripping time [s]


4000
Tripping time [s]

2000 2000

1000 1000
800 800
(10 min) 600 (10 min) 600
400 400

200 200

100 100
80 80
(1 min) 60 (1 min) 60
40 40
tr [s]
20 20
20 17
14
10 10 10
8 8 8
6 6 6
4 4 4

2 2 2
tsd [ms]
1 1 1000
0.8 0.8 750
0.6 0.6 500 without I2t = constant function
0.4 0.4 300
Ii = 2 2.5 3 3.5 4 5 6 7 8 x In 630 A 200
0.2 0.2 Isd = 1.5 2 2.5 3 3.5 4 5 6 7 x Ir 630 A
100
0.1 0.1
0.08 60
0.08
0.06 0.06 20
0.04 0.04
0
0.02 Isd = 2 3 4 5 6 7 8 9 10 x Ir 400 A
0.02

0.01 0.01
0.008 0.008
0.006 0.006 Ii = 2 2.5 3 3.5 4 5 6 7 8 x In 630 A
0.004 0.004
Ii = 2 3 4 5 6 7 8 9 11x In 400 A
0.002 0.002

0.001 0.001
1 2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100 1 2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100

x Ir x Ir

Systems, cable, selectivity and generator protection with LZM3


2.5 h 8000
LZM3(-4)-VE...
6000
Tripping time [s]

4000 Characteristics for Ir = 1,0 x In

2000

1000
800
(10 min) 600
400

200

100
80
(1 min) 60
40
tr [s]
20 20
17
10 14
10
8 8
6 6
4 4

2 2

1
0.8
0.6
00 I2t = constant
0.4 10
......
20..
0.2 =
s]
[m
0.1 t sd
0.08
0.06 Isd = 1.5 2 2.5 3 3.54 5 6 7 x Ir 630 A
0.04 Isd = 2 3 4 5 6 7 8 910 x Ir 400 A
0.02

0.01
0.008
0.006
Ii = 2 2.5 3 3.5 4 5 6 7 8 x In 630 A
0.004
Ii = 2 3 4 5 6 7 8 9 11 x In 400 A
0.002

0.001
1 2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100
x Ir
Engineering 81
Size 4: tripping characteristics
http://catalog.moeller.net Moeller SK1230-1177GB LZM4

Circuit-breakers, switch-disconnectors
Systems, cable, selectivity and generator protection with LZM4 System and line protection with LZM4
2.5 h 8000 LZM4(-4)-VE... 2.5 h 8000 LZM4(-4)-AE...
6000 6000
4000 Characteristics for Ir = 1,0 x In 4000 Characteristics for Ir = 1,0 x In
Tripping time [s]

Tripping time [s]


2000 2000

1000 1000
800 800
(10 min) 600 (10 min) 600
400 400

200 200

100 100
80 80
(1 min) 60 (1 min) 60
40 40
tr [s]
20 20 20
17
14
10 10 10
8 8 8
6 6 6
4 4 4

2 2 2

1 1
0.8 0.8
0.6 0.6
00 I2t = constant
0.4 10 0.4
....
......
0.2 20.. 0.2
s] = Ii = 2 3 4 5 6 7 8 10 12x In
0.1 d
[m 0.1
ts
0.08 0.08
0.06 0.06
0.04 0.04
Isd = 2 3 4 5 6 7 8 9 10 x Ir
0.02 0.02

0.01 Ii = 2 3 4 5 6 7 8 10 12 x In 0.01
0.008 0.008
0.006 0.006
0.004 0.004

0.002 0.002

0.001 0.001
1 2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100 1 2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100
x Ir x Ir

Systems, cable, selectivity and generator protection with LZM4


2.5 h 8000 LZM4(-4)-VE...
6000
4000 Characteristics for Ir = 1,0 x In
Tripping time [s]

2000

1000
800
(10 min) 600
400

200

100
80
(1 min) 60
40
tr [s]
20 20
17
14
10 10
8 8
6 6
4 4

2 2
tsd [ms]
1 1000
0.8 750
0.6 500
without I2t = constant function
0.4 300
200
0.2
100
0.1 60
0.08 20
0.06 0
0.04
Isd = 2 3 4 5 6 7 8 9 10 x Ir
0.02

0.01 Ii = 2 3 4 5 6 7 8 10 12 x In
0.008
0.006
0.004

0.002

0.001
1 2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100
x Ir
82 Engineering
Size 1, 2, 3: let-through characteristics
LZM1, LZM2, LZM3 Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Let-through current xD
D 200 LZMB1(-4)-A(S)15...160 D 200 LZMC1-A20...160
[kA] [kA]

100 100
80 80
60 60
c

c
Ic

Ic
2x

2x
40 40

20 20
415 V
415 V+440 V 440 V
10 10
525 V
8 8
6 6
690 V
4 4
3 3

1 1
1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150 1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150
Icc rms [kA] Icc rms [kA]

D 200 LZMB2(-4)-A(S)1,6...300 D 200 LZMC2-A160...300


[kA] [kA]

100 100
80 80
60 60
c

c
Ic

Ic
2x

2x
40 40

20 20

10 10
8 8
6 6

4 4
3 3

1 1
1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150 1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150
Icc rms [kA] Icc rms [kA]

D 200 LZMN2(-4)-A(S,VE)1,6...250 D 200 LZMC3/N3(-4)-AE(VE)400...630


[kA] [kA]

100 100
80 80
60 60

40 40
c

c
Ic

Ic
2x

2x

20 20

10 10
8 8
6 6

4 4
3 3

1 1
1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150 1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150
Icc rms [kA] Icc rms [kA]
Engineering 83
Sizes 1, 2, 3: let-through characteristics
http://catalog.moeller.net Moeller SK1230-1177GB LZM1, LZM2, LZM3

Circuit-breakers, switch-disconnectors
Let-through energy J
7 7
Zy 10 Zy 10
8 LZMB1(-4)-A(S)15...160 8 LZMC1-A20...160
[A2 s] 6 [A2 s] 6

4 4

a a
2 2

106 106
8 8
6 6 415 V
4 4

415 V
2 2

105 105
8 8
6 6
4 4

2 2

104 104
1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150 1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150
Icc rms [kA] Icc rms [kA]

7 7
Zy 10 Zy 10
8 LZMB2(-4)-A(S)160...250 8 LZMC2-A160...250
[A2 s] 6 [A2 s] 6

4 4

a a
2 2

106 106
8 8
6 6
4 4

2 2

105 105
8 8
6 6
4 4

2 2

104 104
1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150 1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150
Icc rms [kA] Icc rms [kA]

7
Zy 10
8 LZMN3(-4)-AE(VE)400...630
[A2 s] 6

a
2

106
8
6
4

105
8
6
4

104
1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150
Icc rms [kA]

a 1 half-cycle
84 Engineering
Size 2: residual-current release frequency response
NZM2-4-XFIA Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Frequency response
NZM2-4-XFIA30 NZM2-4-XFIA
30 mA 100 mA
IDn 10000 IDn 10000
[mA] [mA]

1000 1000

100 100

10 10
1 10 100 1000 10000 100000 1 10 100 1000 10000 100000
f [Hz] f [Hz]

NZM2-4-XFIA
300 mA 1000 mA
IDn 10000 IDn 100000
[mA] [mA]

1000 10000

100 1000

10 100
1 10 100 1000 10000 100000 1 10 100 1000 10000 100000
f [Hz] f [Hz]
Notes 85

http://catalog.moeller.net Moeller SK1230-1177GB

Circuit-breakers, switch-disconnectors
86 Technical data Technical data 87
Circuit-breakers Circuit-breakers
LZM1-I, LZM2-I, LZM3-I, LZM4-I Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM1-I, LZM2-I, LZM3-I, LZM4-I
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Rated uninterrupted current Rated uninterrupted current Rated uninterrupted current Rated uninterrupted current
max. 160 A max. 300 A max. 630 A max. 1600 A
LZME1 LZMB1 LZMC1 LZMB2 LZMC2 LZMC3 LZMN3 LZMN4

General
Standards IEC/EN 60947 IEC/EN 60947
Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100 Finger and back of hand proof to VDE 0106 Part 100

Climatic proofing Damp heat, constant, according to IEC 60068-2-78 Damp heat, constant, according to IEC 60068-2-78
Damp heat, cyclical to IEC 60068-2-30 Damp heat, cyclical to IEC 60068-2-30
Ambient temperature
Storage C 25+70 25+70
Operation C 25+70 25+70
Mechanical shock resistance (IEC/EN 60068-2-27) 20 (half-sinusoidal shock 20 ms) 20 (half-sinusoidal shock 20 ms)
Safe isolation to VDE 0106 Part 101 and Part 101/A1
Between auxiliary contacts and main contacts V AC 500 500
between the auxiliary contacts V AC 300 300
Mounting position LZM1, LN1: Vertical and 90 LZM2, LN2: Vertical and 90 in all directions
With residual-current release, With plug-in adapter With withdrawable unit, With withdrawable unit,
LZM1, LN1: Vertical and 90 in all directions LZM2, LN2: vertical and 90 right/left LZM3, LN3: vertical, 90 left, LZM4, LN4: vertical
with residual current release, with remote control, with remote control,
LZM2: vertical and 90 to all directions LZM3, LN3: vertical and 90 to all directions LZM4, LN4: vertical and 90 to all directions
Direction of incoming supply As required As required
Degree of protection
Device In the operating controls area: IP20 (basic degree of protection) In the operating controls area: IP20 (basic degree of protection)
Enclosures With insulating surround: IP40, with door coupling rotary handle: IP66 With insulating surround: IP40, with door coupling rotary handle: IP66

Terminals Tunnel terminal: IP10 Tunnel terminal: IP10


Phase isolator and strip terminal: IP00 Phase isolator and strip terminal: IP00
Circuit-breakers
Rated impulse withstand voltage Uimp
Main contacts V 6000 6000 6000 8000 8000 8000 8000 8000
Auxiliary contacts V 6000 6000 6000 6000 6000 6000 6000 6000
Rated operational voltage Ue V AC 415 415 415 415 415 415 415 415
Overvoltage category/pollution degree III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3
Rated insulation voltage Ui V 690 690 690 690 690 690 1000 1000
88 Technical data Technical data 89
Circuit-breakers Circuit-breakers
LZM1-I, LZM2-I, LZM3-I, LZM4-I Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM1-I, LZM2-I, LZM3-I, LZM4-I
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Rated uninterrupted current max. 160 A Rated uninterrupted current max. 300 A Rated uninterrupted current max. 630 A Rated uninterrupted current max. 1600 A
LZME1 LZMB1 LZMC1 LZMB2 LZMC2 LZMC3 LZMN3 LZMN4
Switching capacity
Rated short-circuit making capacity
240 V Icm kA 50 63 121 63 121 121 187 105
400/415 V Icm kA 36 53 76 53 76 76 105 105
Rated short-circuit breaking capacity Icn
Icu to IEC/EN 60947 operating sequence 240 V 50/60 Hz Icu kA 25 30 55 30 55 55 85 50
O-t-CO 400/415 V 50/60 Hz Icu kA 18 25 36 25 36 36 50 50
Ics to IEC/EN 60947 operating sequence 240 V 50/60 Hz Icu kA 12.5 15 27.5 15 27.5 27.5 42.5 25
O-t-CO-t-CO 400/415 V 50/60 Hz Icu kA 9 12.5 18 12.5 18 18 25 25
Maximum low-voltage h.b.c. fuse1) A gG/gL LZM.1-20100: 200 355 355 LZM.3-250, 400: 400
LZM.1-125, 160: 315 LZM.3-500, 630: 630
Utilization category to IEC/EN 60947-2 A A A A A A A B
Rated short-time withstand current
t = 0.3 s Icw kA 1.9 3.3 3.3 19.2
t=1s Icw kA 1.9 3.3 3.3 19.2
Rated making and breaking capacity
Rated operational current AC-1 400/415 V 50/60 Hz Ie A 160 160 160 300 300 630 630 1600
Lifespan, mechanical Operations 10000 10000 10000 10000 10000 7500 7500 5000
Maximum operating frequency Ops/h 30 30 30 30 30 30 30 30
Lifespan, electrical
AC-1 400/415 V 50/60 Hz Operations 5000 5000 5000 5000 5000 2500 2500 1500
Current heat loss per pole at Iu2) W 16.7 16.7 16.7 19 19 40 40 97
Total opening delay at short-circuit ms < 10 < 10 < 10 < 10 < 10 < 10 < 10 < 25
Notes 1) Maximum back-up fuse, if the expected short-circuit currents at the installation location exceed the switching capacity of the circuit-breaker.
2) For current heat loss per pole the specification refers to the maximum nominal current of the frame size.
90 Technical data
Switch-disconnectors
LN Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

LN1(-4) LN2(-4) LN3(-4) LN4(-4)


max. 160 A max. 250 A max. 630 A max. 1600 A

Switch-disconnectors
Rated impulse withstand voltage Uimp
Main contacts V 6000 8000 8000 8000
Auxiliary contacts V 6000 6000 6000 6000
Rated operational voltage Ue V AC 690 690 690 690
Rated uninterrupted current max.
IEC/EN 60947-2 annex L Iu A 160 250 630 1600
Technical data, divergent from the Iu A 125 160 550 1200
products for the IEC market UL489,
CSA 22.2 No. 5.1
Overvoltage category/pollution degree III/3 III/3 III/3 III/3
Rated insulation voltage Ui V AC 690 690 1000 1000
For use in IT electrical power networks V 690 690 690 525
Switching capacity
Rated short-circuit making capacity Icm kA 2.8 5.5 25 53
Rated short-time withstand current
t = 0.3 s Icw kA 2 3.51) 12 25
t=1s Icw kA 2 3.51) 12 25
Rated conditional short-circuit current
With back-up fuse A gG/gL PN1(N1)63125: 125 PN2(N2)-160250: PN3(N3)-400630: N4-6301600:
PN1(N1)-160: 160 250 630 2 x 800
400 415 V kA 100 100 100 100
With downstream fuse A gG/gL LN1-63125: 125 LN2-160250: LN3-400630: LN4-6301600:
LN1-160: 160 250 630 2 x 800
400 415 V kA 100 100 100 100
Rated making and breaking capacity
Rated operational current, AC-22/23A
415 V Ie A 160 250 630 1600
Lifespan, mechanical Opera 10000 10000 7500 5000
tions
Maximum operating frequency Ops./h 120 120 60 60
Lifespan, electrical to IEC/EN 60947-4-1
section B
AC-1
400/415 V Opera 5000 5000 2500 1500
tions
AC-3
400/415 V Opera 3000 3000 1000 750
tions
Current heat loss per pole at Iu2) W 12.7 16 40 97
Notes 1) The rated short time withstand current for PN2/N2 in conjunction with residual-current release NZM2-4-XFI... Icw = 1.5 kA
2) The current heat loss per pole ratings refer to the maximum current rating of the frame size.
Technical data 91
Temperature influence
http://catalog.moeller.net Moeller SK1230-1177GB

Circuit-breakers, switch-disconnectors
Response values of the overload release at temperatures deviating from the
reference temperatures
Device Type Release Temperature compensation coefficient
type
20 C 30 C 40 C 50 C 60 C 65 C 70 C
Thermomagnetic release (TM)
System protection Protection of systems (reference temperature 40 C)
LZM...1(-4)-A1580 TM 1.14 1.07 1 0.93 0.86 0.83 0.79
LZM...1(-4)-A90125 TM 1.14 1.07 1 0.93 0.86 0.83 0.79
LZM...1(-4)-A160 TM 1.08 1.04 1 0.96 0.92 0.90 0.88
LZM...2(-4)-A125200 TM 1.04 1.02 1 0.98 0.96 0.95 0.94
LZM...2(-4)-A250/300 TM 1.04 1.02 1 0.98 0.96 0.95 0.94
LZM...2(-4)-A125200 + XSV TM with XSV 1.04 1.02 1 0.98 0.96 0.95 0.94
LZM...2(-4)-A250/300 + XSV TM with XSV 1.04 1.02 1 0.98 0.96 0.95 0.94

Notes With temperatures which deviate from the reference temperature, a slight change of the overload protection properties occurs. In order to determine the
release time using the tripping characteristics the temperature compensation coefficient in accordance with the table must be considered.
Example: An LZM1-A100 is calibrated for a reference temperature of 40 C.
What happens when it is operated at an ambient temperature of 60 C?
At 60 C, the temperature compensation coefficient of 0.86 results in a reduced operating current of Ir = 100 A x 0.86 = 86 A. In other words
at an ambient temperature of 60 C the LZM1-A100 trips as if it were set to 86 A.

Reduction of the rated operational current (derating) under particular ambient


conditions (according to IEC 947)
Device Type Release Derating coefficient
type
20 C 30 C 40 C 50 C 60 C 65 C 70 C
Thermomagnetic release (TM)
System protection Protection of systems (reference temperature 40 C)
LZM...1(-4)-A1580 TM 1 1 1 1 1 1 1
LZM...1(-4)-A90125 TM 1 1 1 1 0.86 0.83 0.8
LZM...1(-4)-A160 TM 1 1 1 0.95 0.9 0.85 0.8
LZM...2(-4)-A15200 TM 1 1 1 1 1 1 1
LZM...2(-4)-A250 TM 1 1 1 1 0.9 0.85 0.8
LZM...2(-4)-A20200 + XSV TM with XSV 1 1 1 1 1 1 1
LZM...2(-4)-A250 + XSV TM with XSV 1 0.97 0.92 0.87 0.81

Notes The derating coefficient must be considered in accordance with the following table in order to determine the maximum permissible current loading at
different ambient temperatures.
Example: An LZM2-A250 should be operated at an ambient temperature of 65 C.
How high is the permissible rated operational current Ie?
At 65 C the derating coefficient is 0.85, this means Ie = 250 A x 0.85 = 212.5 A.
The LZM2-A250 may be operated at an ambient temperature of 65 C with a maximum Ie = 212.5 A.

Part no. Weight Part no. Weight


kg kg
Circuit-breaker Plug-in adapter elements
LZM...1-... 1.046 +NZM2-XSV 4.7
LZM...1-4-... 1.325 +NZM2-4-XSV 5.9
LZM...2-... 2.345 Withdrawable unit
LZM...2-4-... 3.5 +NZM3-XAV 21
LZM...3-... 6.34 +NZM3-4-XAV 27
LZM...3-4-... 8.4 +NZM4-XAV 52
LZM...4-... 21 +NZM4-4-XAV 65
LZM...4-4-... 27
92 Technical data
Temperature influence
Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Reduction of the rated operational current (derating) under particular ambient


conditions (according to IEC 947)
Device Type Release Derating coefficient
type
20 C 30 C 40 C 50 C 60 C 65 C 70 C
Electronic release (E)
System protection
LZM...3(-4)-AE630 E 1 1 1 1 0.9 0.85 0.8
LZM...3(-4)-AE630 + XAV E with XAV 0.96 0.92 0.87 0.83 0.78 0.75 0.73
LZM...4(-4)-AE800...1250 E 1 1 1 1 1 1 1
LZM...4(-4)-AE1600 E 1 1 1 1 0.87 0.85 0.82
LZM...4(-4)-AE800...1250 + XAV E with XAV 1 1 1 1 1 1 1
LZM...4(-4)-AE1600 + XAV E with XAV 1 0.98 0.93 0.89 0.85 0.83 0.8
Systems protection, cable protection, selectivity and generator protection
LZM...3(-4)-VE400 E 1 1 1 1 1 1 1
LZM...3(-4)-VE630 E 1 1 1 1 0.9 0.85 0.8
LZM...3(-4)-VE400 + XAV E with XAV 1 1 1 1 1 1 1
LZM...3(-4)-VE630 + XAV E with XAV 0.96 0.92 0.87 0.83 0.78 0.75 0.73
LZM...4(-4)-VE800...1250 E 1 1 1 1 1 1 1
LZM...4(-4)-VE1600 E 1 1 1 1 0.87 0.85 0.82
LZM...4(-4)-VE800...1250 + XAV E with XAV 1 1 1 1 1 1 1
LZM...4(-4)-VE1600 + XAV E with XAV 1 0.98 0.93 0.89 0.85 0.83 0.8

Notes The derating coefficient must be considered in accordance with the following table in order to determine the maximum permissible current loading at
different ambient temperatures.
Example: An LZM3-VE630 should be operated at an ambient temperature of 65 C.
How high is the permissible rated operational current Ie?
At 65 C the derating coefficient is 0.85, this means Ie = 630 A x 0.85 = 535.5 A.
The LZM3-VE630 may be operated at an ambient temperature of 65 C with a maximum Ie = 535.5 A.
Technical data 93
Effective power loss
http://catalog.moeller.net Moeller SK1230-1177GB LZM1, LZM2

Circuit-breakers, switch-disconnectors
LZM up to 250 A with thermomagnetic release (3- and 4-pole)
Fixed mounting Fixed mounting
LZM1- LZM2-
A... A...
In [A] P R P R
[W] [Ohm] [W] [Ohm]
20 9.8 8180 5.1 4250
25 8.8 4680 8 4250
26
30
32 9.1 3030 10 3140
33
35
40 11 2220 13 2800
45
50 13.5 1760 18 2270
60
63 14 1190 20 1700
70
80 15.5 850 22 1070
90
100 24 730 28 855
110
125 38 570 29 589
150
160 50 460 40 427
175
200 48 332
225
250 57 310
Note: The values stated in the table apply for 3- and 4-pole fixed mounted devices with an equal load distribution.
On 4-pole devices the current in the N-conductor is equal to zero.
The total resistive load is the measured value for a 3-pole or a 4-pole switch.
The total heat dissipation is the value measured at In, 50/60Hz for a 3-pole or 4-pole switch.
The heat dissipation can be calculated with the formula: P = 3 x R x I

LZM up to 1600 A with electronic release (3- and 4-pole)


Fixed mounting Supplementary Fixed mounting Supplementary Fixed mounting Supplemementary
LZM2- Plug-in units LZM3 Withdrawable units LZM4 Withdrawable units
R R R R R R
[Ohm] [Ohm] [Ohm] [Ohm] [Ohm] [Ohm]
275 100 100 70 37 10
Note: The values stated in the table apply for 3- and 4-pole devices with an equal load distribution.
On 4-pole devices the current in the N-conductor is equal to zero.
The total resistive load is the measured value for a 3-pole or a 4-pole switch
(independent of In and the type of release).
The total resistive load for a plug-in or withdrawable switch results from:
the resistive value for fixed mounted + resistive value for plug-in or withdrawable.
The heat dissipation can be calculated with the formula: P = 3 x R x I
94 Technical data Technical data 95
Terminal capacities Terminal capacities
LZM Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB LZM
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
LZM1 In1) LZM2 In1) LZM3 In1) LZM4 In1)
160 A A 300 A A 630 A A 1600 A A

Terminal capacities
Standard equipment Box terminal Screw terminal Screw terminal Screw terminal
Accessories Screw connection Box terminal Box terminal Tunnel terminal
Tunnel terminal Tunnel terminal Tunnel terminal Connection on rear
Connection on rear Connection on rear Connection on rear Strip terminal
Rated power of coil
Box terminal Solid mm2 1 x (10 16) 160 1 x (4 16) 250 2 x 16 500
2 x (6 16) 2 x (4 16)
Stranded mm2 1 x (25 70) 1 x (25 185) 250 1 x (35 240)
2 x 25 2 x (25 70) 2 x (25 120)
Tunnel terminal Solid mm2 1 x 16 160 1 x 16 250
Stranded Single hole mm2 1 x (25 95) 1 x (25 185) 1 x (25 185) 350
Double hole fitting mm2 1 x (50 240) 630
2 x (50 240) 2 x 185
4-hole mm2 4 x (50 240) 1400
Bolt terminal and rear-side connection
Direct on the switch Solid mm2 1 x (10 16) 160 1 x (4 16) 250 1 x 16 630
2 x (6 16) 2 x (4 16) 2 x 16 2 x 185
Stranded mm2 1 x (25 70)3) 1 x (25 185) 1 x (25 240) 1 x (120 185) 1250
2 x 25 2 x (25 70) 2 x (25 240) 4 x (50 185)
Module plate Single hole min. mm2 1 x (120 300) 1000
max. mm2 2 x (95 300)
Module plate Double hole min. mm2 2 x (95 185) 1400
max. mm2 4 x (35 185)
Connection width extension mm2 2 x 300 630 4 x 300 1600
2 x 185 6 x (95 240) 4 x 240
Al conductors, Al cable
Tunnel terminal Solid mm2 1 x 16 160 1 x 16 250 1 x 16 350
Stranded Single hole mm2 1 x (25 95) 1 x (25 185)2) 1 x (25 185)2)
Double hole fitting mm2 1 x (50 240) 630
2 x (50 240)
4-hole mm2 4 x (50 240) 1400
Bolt terminal and rear-side connection
Direct on the switch Solid mm2 1 x (10 16) 160 1 x (10 16) 250 1 x 16 400
2 x (10 16) 2 x (10 16) 2 x (10 16)
Stranded mm2 1 x (25 35) 1 x (25 50) 1 x (25 120)
2 x (25 35) 2 x (25 50) 2 x (25 120)
Module plate Single hole min. mm2 1 x (185 240) pleaes inquire
Single hole max. mm2 2 x (70 185) pleaes inquire
Module plate Double hole mm2 4 x 50
Connection width extension mm2 2 x 240 pleaes inquire
6 x (70 240)
Cu strip (number of segments x width x segment thickness)
Box terminal min. mm 2 x 9 x 0.8 160 2 x 9 x 0.8 250 6 x 16 x 0.8 630
max. mm 9 x 9 x 0.8 10 x 16 x 0.8 10 x 24 x 1.0
+ 5 x 24 x 1.0
(2 x) 8 x 24 x 1.0
Flat conductor terminal min. mm 6 x 16 x 0.8 1100
max. mm (2 x) 10 x 32 x 1.0
Module plate Single hole mm (2 x) 10 x 50 x 1.0 1250
(2 x ) 10 x 40 x 1.0
Bolt terminal and rear-side connection
Flat copper strip, with holes min. mm 2 x 16 x 0.8 250 6 x 16 x 0.8 630 (2 x) 10 x 50 x 1.0 1600
Flat copper strip, with holes max. mm 10 x 16 x 0.8 10 x 32 x 1.0 + 5 (2 x) 10 x 50 x 1.0
x 32 x 1.0
Connection width extension mm2 (2 x) 10 x 50 x 1.0 (2 x) 10 x 80 x 1.0 1600
2 x (10 x 50 x 1.0)
Copper busbar (width x thickness)
Bolt terminal and rear-side connection
Screw connection M6 M8 M10 M10
Direct on the switch min. mm 12 x 5 160 16 x 5 250 20 x 5 630 25 x 5 1600
max. mm 16 x 5 20 x 5 30 x 10 2 x (50 x 10) 2000
+30 x 5 2 x (80x 10)
Module plate Single hole min. mm 25 x 5 1250
max. mm 2 x (50 x 10) 2 x (40 x 10)
Module plate Double hole mm 2 x (50 x 10) 1500
Connection width extension min. mm 630 60 x 10 1600
max. mm 2 x (10 x 50) 10 x 40 2 x (80 x 10) 2 x (50 x 10)

Notes 1) The rated currents In have been determined conform to IEC/EN 60947 (switchgear standard) and generally relate
to the max. defined cross-sections and are intended for the purpose of orientation. The engineering standards which apply in
each case must be observed.
2) depending on the cable manufacturer up to 240 mm2 can be connected.
3) depending on the cable manufacturer up to 95 mm2 can be connected.
96 Technical data
Auxiliary contacts
M22-K, XHI(V) Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

at AC = 50/60 Hz M22-K NZM-XHIV NZM-XHI

Auxiliary contacts
Rated operational voltage
AC Ue V AC 500 500 500
DC Ue V DC 220 220 220
Conventional thermal current Ith = Ie A 4 4 4
Rated operational current
AC15 115 V Ie A 4 4 4
230 V Ie A 4 4 4
400 V Ie A 2 2 2
500 V Ie A 1 1 1
DC-13 24 V Ie A 3 3 3
42 V Ie A 1.7 1.5
60 V Ie A 1.2 0.8 1.2
110 V Ie A 0.8 0.5 0.5
220 V Ie A 0.3 0.2 0.2
Short-circuit protection
max. fuse A gG/gL 10 10 10
Max. miniature circuit-breaker A PKZM0-10/FAZ-B6 FAZ-B6 FAZ-B6
Early-make time compared to the main contacts ms LZM1, LN1: approx. 20
during switch on and off (switching times with LZM2, LN2: approx. 20
manual operation) LZM3, LN3: approx. 20
LZM4, LN4: approx. 90
With LZM4/N4 the HIV does
not feature early break.
Terminal capacities
Solid or flexible conductor with ferrule mm2 1 x (0.75 2.5) 1 x (0.75 2.5) 1 x (0.75 2.5)
2 x (0.75 2.5) 2 x (0.75 2.5) 2 x (0.75 2.5)
AWG 1 x (18 14) 1 x (18 14) 1 x (18 14)
2 x (18 14) 2 x (18 14) 2 x (18 14)
Technical data 97
Equipping with auxiliary contacts, time differences
http://catalog.moeller.net Moeller SK1230-1177GB LZM

Circuit-breakers, switch-disconnectors
Maximum equipment and position of the internal accessories
c b a
-XHIV(2S) HIA HIN Contacts per slot with
or -XA HIA and HIN
or -XU

LZM1, LN1 1 1 1 1 N/O


a LZM2, LN2 1 1 2 1 N/C
b LZM3, LN3 1 1 3 2 N/O
c LZM4, LN4 1 2 3 2 N/C
N/O = normally open contact
N/C = normally closed
contact

Time differences ON-OFF

Main contact

Auxiliary contact, early make


a b

Auxiliary contact, normal (HIN)


a b

Time difference a (ms) Time difference b (ms)


Manual operation Motor operators Manual operation Motor operators
HIV HIN HIV HIN HIV HIN HIV HIN
K10 K01 K10 K01 K10 K01 K10 K01

LZM1 202) 0 2.5 202) 0 2.5

LZM2 202) 3.5 6.5 Not 2.5 4.5 202) 3 4.5 Not 3 4
permissible permissible
LZM3 202) 4 8 Not 2 4 202) 3.5 8 Not 3 6.5
permissible permissible
LZM4 902) 7 11 Not on request on request 01)2) 12 15 Not on request on request
permissible permissible

Notes 1) With LZM4/N4 the HIV does not feature early break.
2) Minimum value, as it is dependent on the switching speed
98 Technical data
Undervoltage releases, shunt releases
NZM-XU, NZM-XA Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

NZM1(2/3)-XU... NZM4-XU

Undervoltage release
Rated control voltage
Alternating voltage at 50/60 Hz Us V AC 24600 24600
DC Us V DC 12250 12250
Operating range
Drop-out voltage x Us 0.35 0.7 0.35 0.7
Pick-up voltage x Us 0.85 1.1 0.85 1.1
Power consumption
AC
Pick-up AC VA 1.5 3.6
Sealing AC VA 1.5 3.6
DC
Pick-up DC W 0.8 2.5
Sealing DC W 0.8 2.5
Max. opening delay ms 19 23
(response time until the main circuits open)
Minimum command time ms 10 15 10 15
Terminal capacities
Solid or flexible conductor with ferrule mm2 1 x (0.75 2.5) 1 x (0.75 2.5)
2 x (0.75 2.5) 2 x (0.75 2.5)
AWG 1 x (18 14) 1 x (18 14)
2 x (18 14) 2 x (18 14)

UVU-NZM

Undervoltage releases, off-delayed


Rated operational voltage
Alternating voltage at 50/60 Hz Ue V AC 24, 220 550
DC Ue V DC 24
Inrush current (peak value) Ie mA < 500
Power consumption VA 50
Delay time tsd ms 70 4000
With additional external capacitor, 90.000 F f 35 V s To 16

With additional external capacitor, 30.000 F f 35 V s To 8

Terminal capacities
Solid or flexible conductor with ferrule mm2 1 x (0.5 2.5)
2 x (0.5 1.5)

NZM1(2/3)-XA... NZM4-XA... NZM2/3-XA...-MNS NZM4-XA-MNS

Shunt release
Rated control voltage
AC Us V AC 12440 12440 230 230
DC Us V DC 12440 12440
Frequency range Hz 0 400 0 400 50/60 50/60
Operating range
AC x Us 0.71.1 0.71.1 0.11.1 0.11.1
DC x Us 0.71.1 0.71.1
Power consumption
Pick-up AC/DC VA/W 2.5 2.5
Sealing AC/DC VA/W 2.5 2.5
Maximum current consumption at 110% Us (230 V 50 Hz) A 0.5 1
Max. opening delay (response time until the main circuits ms 20 22 20 22
open)
Duty factor ms L L 1000 ms 1000 ms
Minimum command time ms 10 15 10 15 10 15 10 15
Terminal capacities
Solid or flexible conductor with ferrule mm2 1 x (0.75 2.5) 1 x (0.75 2.5) 1 x (0.75 2.5) 1 x (0.75 2.5)
2 x (0.75 2.5) 2 x (0.75 2.5) 2 x (0.75 2.5) 2 x (0.75 2.5)
AWG 1 x (18 14) 1 x (18 14) 1 x (18 14) 1 x (18 14)
2 x (18 14) 2 x (18 14) 2 x (18 14) 2 x (18 14)
Technical data 99
Remote operator, capacitor units
http://catalog.moeller.net Moeller SK1230-1177GB NZM-XCM, NZM-XR

Circuit-breakers, switch-disconnectors
NZM-XCM

Capacitor unit for shunt release


Rated operational voltage Ue V AC 230
Rated operational current Ie mA < 10
Inrush current (peak value) Ie A 3
Terminal capacities
Solid or flexible conductor with ferrule mm2 1 x (0.5 2.5)
2 x (0.5 1.5)
AWG 1 x (20 14)
2 x (20 16)

NZM2-XR... NZM3-XR... NZM4-XR

Remote operator
Rated control voltage
AC Us V AC 110440 110440 110440
DC Us V DC 24250 24250 24250
Operating range
AC Us 0.851.1 0.851.1 0.851.1
DC Us 0.851.1 0.851.1 0.851.1
Motor rating
AC 110 130 V AC VA 350 350 350
208 240 V AC VA 350 350 350
380 440 V AC VA 350 350 350
DC 24 30 V DC W 250 250 250
110 130 V DC W 250 250 250
220 250 V DC W 250 250 250
Rated power of coil
AC 110 130 V AC VA 270 270 270
208 240 V AC VA 270 270 270
380 V 440 V AC VA 270 270 270
DC 24 30 V DC W 210 210 210
100 130 V DC W 210 210 210
220 250 V DC W 210 210 210
Total make time ms 60 80 100
Total opening delay ms 300 1000 3000
Minimum signal duration
with switch on ms 30 30 30
with switch off ms 150 250 500
Lifespan, mechanical Operations 20000 15000 10000
Maximum operating frequency Ops./h 120 60 20
Terminal capacities
Solid or flexible conductor with ferrule mm2 0.75 2.5 0.75 2.5 0.75 2.5
AWG 18 14 18 14 18 14
100 Technical data
Residual-current relay
PFR- Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

PFR-003 PFR-03 PFR-5

Electrical
Standards IEC/EN 60947-2, IEC 755, IEC 1008, IEC 1009
Sensitivity Pulse current sensitive, type A
Rated control voltage Us V AC 230 g20 % (50/60 Hz)
Motor rating Pe W 3 3 3
Rated fault currents IDn mA 0.03 0.3 0.03, 0.1, 0.3, 0.5, 1, 3, 5
Delay time tv s 0.02 (non-delayed) 0.02 (non-delayed) 0.02, 0.1, 0.3, 0.5, 1, 3, 5
Relay contacts 1 integrated changeover 1 integrated changeover 1 integrated changeover
contact contact contact
Rated voltage of the relay contact V AC/DC 250/100 250/100 250/100
Rated current of the relay contact A 6 6 6
Fault current warning Hz 0.5 = 25% 50% IDn
1 = 50% 75% IDn
2 = 75% 100% IDn
Mechanical
Standard front dimension mm 45 45 45
Device height mm 85 85 85
Device width mm 45 45 45
Mounting Snap fixing, top-hat rail DIN 46277, IEC/EN 60715
Terminals top and bottom Box terminals
Terminal protection Finger/back-of-hand proof to BGV A2, VDE 106 part 100

Terminal capacities mm2 2 x 0.75 2.5 solid, 2 x 0.75 1.5 flexible/with ferrules
Sealability yes
Notes 101

http://catalog.moeller.net Moeller SK1230-1177GB

Circuit-breakers, switch-disconnectors
102 Technical Data Technical Data 103
Residual-current releases Residual-current releases
NZM-XFI Moeller SK1230-1177GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1177GB NZM-XFI
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
NZM1(-4)-XFI30R NZM1(-4)-XFI300R NZM1(-4)-XFIR NZM1(-4)-XFI30U NZM1(-4)-XFI300U NZM1(-4)-XFIU +NZM2-4-XFI30 +NZM2-4-XFI +NZM2-4-XFIA30 +NZM2-4-XFIA

Electrical
Standards IEC/EN 60947-2 IEC/EN 60947-2 IEC/EN 60947-2 IEC/EN 60947-2 IEC/EN 60947-2 IEC/EN 60947-2 IEC/EN 60947-2 IEC/EN 60947-2 IEC/EN 60947-2 IEC/EN 60947-2
Sensitivity Pulse current sensitive according to core-balance principle Pulse current sensitive according to core-balance Pulse current sensitive Pulse current sensitive Sensitive to AC/DC (type Sensitive to AC/DC (type
principle according to core- according to core- B) B)
balance principle balance principle
Min. operating voltage
or detection of fault currents type A/ 80 V (dependent on 80 V (dependent on 80 V (dependent on 80 V (dependent on 80 V (dependent on 80 V (dependent on independent of mains independent of mains 0 V independent of 0 V independent of
AC mains voltage) mains voltage) mains voltage) mains voltage) mains voltage) mains voltage) voltage voltage mains voltage mains voltage
or detection of fault currents type B 50 V (dependent on 50 V (dependent on
mains power) mains voltage)
Suitability for the application In three- and single-phase systems In single-phase In single-phase In three- and single-phase systems
Rated operational voltage Ue V AC 200415 (3~) 200415 (3~) 200415 (3~) 200415 (3~) 200415 (3~) 200415 (3~) 280690 280690 50400 (3~) 50400 (3~)

Rated frequency f Hz 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60
Number of poles 3/4 3/4 3/4 3/4 3/4 3/4 4 4 4-pole 4-pole
Rated current range In A 15125 15125 15125 15100 15100 15100 15250 15250 15250 15250

Rated fault currents IDn A 0.03 0.3 0.030.10.3 0.03 0.3 0.030.10.3 0.03 0.10.313 0.03 0.10.31
0.513 0.513
Detection range of the fault current 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz with AC voltage: 0 100 with AC voltage: 0 100
kHz kHz
with pulsed DC voltage: with pulsed DC voltage:
50 Hz 50 Hz
Rated ultimate short-circuit making IDm A = ICU = ICU = ICU = ICU = ICU = ICU = ICU = ICU = ICU = ICU
capacity and -rated ultimate short-circuit
breaking capacity
Fault current warning f 0.3 x IDn f 0.3 x IDn f 0.3 x IDn f 0.3 x IDn f 0.3 x IDn f 0.3 x IDn

Mechanical shock resistance (IEC 60068-2-27) 20 (half-sinusoidal shock 20 ms) 20 (half-sinusoidal shock 20 ms)
Lifespan, mechanical (50 % with fault Operations 20000 20000 20000 20000 20000 20000 f 2000 f 2000 f 2000 f 2000
current)
Mechanical
Standard front dimension mm 45 45 45 45 45 45 96 96 96 96
Mounting on the right side sidewise on the right Bottom Bottom Bottom Bottom Bottom Bottom Bottom Bottom
Mounting position Vertical and 90 in all directions Vertical and 90 in all directions
Supply LZM1 from above LZM1 from above LZM1 from above LZM1 from above LZM1 from above LZM1 from above As required As required Bottom Bottom
Degree of protection IP20 in the operating component area IP20 in the operating component area
Ambient temperature C 5+40 5+40 5+40 5+40 5+40 5+40 25+70 25+70 25+70 25+70
Sealability yes, setting buttons yes, setting buttons yes, setting buttons yes, setting buttons

Terminal capacity
Flexible without ferrule mm2 such as LZM1 standard terminal such as LZM1 standard terminal with LZM2 standard connection

flexible with ferrules mm2 such as LZM1 standard terminal such as LZM1 standard terminal with LZM2 standard connection
104 Dimensions
Size 1: basic units
LZM1, LN1 Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Circuit-breaker 84.5
3 pole 68
LZME1 NZM...1-...-(C)NA

LZMB1 a
30 21

f 60
10.2
LZMC1 57

9.5
LN1

16 5

41.5
64

04
R1
112
126
145

F
45

90

63

162

SW4 M4 x 50/10
30 44.6
90

a Blow out area, minimum clearance to other parts f 60 mm

Circuit-breaker 84.5
4 pole 68
LZME1-4
LZMB1-4 a
60 21
f 60
9.5

LZMC1-4
LN1-4
16

89
5
41.5
64

04
R1
112
126
145

N
45
63

SW4 M4 x 50
30 44.6
120

a Blow out area, minimum clearance to other parts f 60 mm

Covers 21
NZM1(-4)-XKSA 16 4
Screw connection
NZM1(-4)-XKS IP2X

IP2X protection against


contact with a finger SW 4 M6 x 14
for shroud
34
26

NZM1(-4)-XIPA
Screw connection
64
296

158
80

90 a 59
120 b

a 3 pole
b 4 pole
Dimensions 105
Size 1: accessories
http://catalog.moeller.net Moeller SK1230-1177GB NZM1-XK, NZM1XIPK, NZM-XSTK

Circuit-breakers, switch-disconnectors
Tunnel terminal
NZM1(-4)-XKA
20 20 a 3 pole
b 4 pole

SW 5
48

SW 4 M6 x 14
32
64

90 a
120 b

Connection on rear
NZM1(4)-XKR
30 30 30
30 15

SW 4 M6 x 14 o 22
64

63

102
126
128

10 10 50
18

o 6.6 M4
30
90 25
120

30
15
M6 x 20
o 22
6

63

126
128

M4
15

Control circuit terminal IP2X protection against contact with a finger


NZM1-XIPK, NZM-XSTK NZM1(-4)-XIPK
46 10
13
91
108

76
64
89

90 a
90 a
120 b
120 b

a 3 pole
b 4 pole
106 Dimensions
Size 1: accessories
NZM1-XDV, NZM1-XTVD Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Rotary drive
Rotary handle on circuit-breaker
NZM1-XDV NZM1-XDTV
NZM1-XDVR

a
80.3

F 43

36
54
45

45
90
120

d
b

d=48
b f 34
a Up to 3 padlocks

Door coupling rotary handle


NZM1-XTVD(V)(R)
73.5
27.5
8

ZFS...-NZM7
o8
23

40
85

71
o
R4
6

71
85
25

a
35

d
b

d=48
b f 34
a Up to 3 padlocks
Dimensions 107
Size 1: accessories
http://catalog.moeller.net Moeller SK1230-1177GB NZM1-XTVD

Circuit-breakers, switch-disconnectors
Door coupling rotary handle with extension shaft
NZM1-XTVD(V)(R)
NZM1/2-XV4(6)
25 73
210 400(400 600) 27

55
o 45
8

NZM1/2-XV4(NZM1/2-XV6) 36 23g0.5

NZM1-XTVD(V)(R)-60 NZM1-XTVD(V)(R)-0
41 75
16 60

NZM1/2-XV...

167 210 23g0.5


a

128 167 23g0.5

a Special tip

Minimum door coupling rotary handle clearance from door pivot point

NZM...1-... f 130
108 Dimensions
Size 1: accessories
NZM1-XS, NZM1HIV Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Main switch assembly kit for side panel mounting


NZM1-XS(R)-L NZM1-XS(R)-R
41

51.5
2-5 12 129
12 2-5 129 15
73.5 95-310 90
90 95-310 73.5

Main switch assembly kit for side panel mounting with mounting bracket
NZM1-XS(R)M-L NZM1-XS(R)M-R
NZM1/2-XZB

145
145

NZM1/2-XZB

12 2-5 131.4
2-5 12 131.4
57.2 73.5 176
73.5 57.2 176
163 178.5
163 178.5
195.5
195.5

Undervoltage release
Shunt release
Early-make auxiliary contacts
20 20 23.2 a
NZM1-XA(HIV)
NZM1-XU(HIV)(20)
NZM1-XHIV
39.3

39.3

b
NZM1-XA(HIV)(L)
38.6

a c NZM1-XU(V)(HIV)(L)(20)
NZM1-XHIV(L)
b c
NZM1-XHIVR

Spacers Clip plate


NZM1/2-XAB NZM1-XC35
103
9.5

35
17.5
126
145
157

30 1.5

90 8.4
Dimensions 109
Size 1: accessories
http://catalog.moeller.net Moeller SK1230-1177GB NZM-X

Circuit-breakers, switch-disconnectors
Insulating surrounds
NZM1-XBR a Mounting aperture
9.5
1.5 5
ZFS...-NZM7

53
64

82

132

117 23 11.5
148.5 19

Rotary handle on switch with door interlock


NZM1-XDTV(R) a Mounting aperture
32
9.5
1.5 5
14.4
9
o4
11
40

53

132

11.5
19

Rear drive Toggle lever locking device


NZM1-XRAV(R) NZM-XKAV
NZM1-4-XRAV(R)
45 32
1

a
46.3
145

F 80
117 a 115

148 b

a NZM1-XRAV(R)
d
b NZM1-4-XRAV(R)
b

d=48
b f 34
a Up to 3 padlocks
110 Dimensions
Size 1: accessories
NZM1-XMV, NZM1-XTV Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Mechanical interlock
NZM1-XMV + NZM1-XDV(R)

29.2
80.3

51
27
45
22.5

31
7
45 5
90 40
120 143 40

NZM1-XMV + NZM1-XTVD(V)(R)
Part no. x
NZM1/2-XV4 (NZM1/2-XV6)
NZM1/2-XV4 245 400
NZM1/2-XV6 400 600

245 400 (400 600)

NZM1-XMV + NZM1-XTVD(V)(R)-60 NZM1-XMV + NZM1-XTVD(V)(R)-0

NZM1/2-XV... a

163 202

202 245

a Special tip
Dimensions 111
Size 1: accessories
http://catalog.moeller.net Moeller SK1230-1177GB NZM1-XCI, NZM1-XAD

Circuit-breakers, switch-disconnectors
Insulated enclosures
NZM1-XCIK5-T... NZM1-XCI23-T...
280

250
8

8
200 160
187.5 175
231
246

NZM1-XCI43-T... NZM1-XCI43/2-T...

60
60
495
375

375
495
8
8

80 60 80 60

250 175 250 225

246 296

Component adapter
NZM1-XAD160
200

90 65.5
112 Dimensions
Size 1: accessories
NZM1-XFI, PFR- Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Residual-current relay
PFR-003 5 6 7 8

PFR-03
PFR-5 a

85
67
45

1 2 3 4

36 44
68
73

Current transformer
PFR-W-2030 PFR-W-35...210
F Part no. A B C D E F
PFR-W-35 100 79 26 48.5 35 35
I PFR-W-70 130 110 32 66 70 52
G
J

E PFR-W-105 170 146 38 94 105 72


B
H

PFR-W-140 220 196 48.5 123 140 97


PFR-W-210 299 284 69 161 210 141
A 33

F G H I J
PFR-W-20 32 60 24 46 21
46

PFR-W-30 32 70 30 59 30
6.5

F
C D

Fixing clip
PFR-WC PFR-WMA
Part no. A B C A1 A2
PFR-WMA-35 91 28 40 35 28
oB
oC

PFR-WMA-70 105 62 75 35 35
51.7
32.7

PFR-WMA-105 153 98 110 35 60


A1 A2
PFR-WMA-140 153 133 145 35 60
A PFR-WMA-210 153 203 215 35 60
6.0
12.5

Residual-current release
NZM1(-4)-XFI...R
80.1
68
145
145
220

45
220

42.5

135 105

NZM1(-4)-XFI...U
80.1
68
23.1
145

145

45
42.5

120 90.15
Dimensions 113
Size 2: Basic units
http://catalog.moeller.net Moeller SK1230-1177GB LZM2, LN2

Circuit-breakers, switch-disconnectors
Circuit-breaker 149
3 pole 103
LZMB2 35
NZM...2-...(C)NA 25 5
b
LZMC2
a

f 35
LN2 M8 x 22

11
19.5

24.5
3
4
80

R 12

95
184
145
135
100
64

72.5
217

M4 x 85/20
f 35

a SW5 b 78.7
35
f5 105 f 5 NZM...2-...-(C)NA(> 480 V)
NS2-...-NA
a Blow out area, minimum distance to other parts f 35 mm
b Minimum distance to adjacent parts f 5 mm

Circuit-breaker 149
4 pole 103
LZMB2-4
LZMC2-4 b a
70 25 5
f 35

LN2-4 M8 x 22
19.5

24.5

3
80

24
R1

95

N
145
135

184

100
72.5

SW5 M4 x 85/20
f 35

35 78.7
a b
f5 140 f5

a Blow out area, minimum distance to other parts f 35 mm


b Minimum distance to adjacent parts f 5 mm
114 Dimensions
Size 2: accessories
NZM2-XK, NZM2-XIP, NZM2-XST Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Box terminal Tunnel terminal


(+)NZM2(-4)-...-XKC(O)(U) NZM2(-4)-XKA
IP2X protection against contact with a finger
NZM2(-4)-XIPK
65 25 30
25
19 F 22.1

SW 8
M10

55
37
SW 5 M8 x 22
20
111

80
80

SW 5

105 a
140 b
105 a
140 b

a 3 pole
b 4 pole
Covers Control circuit terminal
NZM2(-4)-XKSA NZM2-XSTS
Cable lug NZM-XSTK
NZM2-XKS185
IP2X protection against contact with a finger for shroud
NZM2(-4)-XIPA
100

SW 5 M8 x 22
80

105
337

105 a
175

140 b
81

105 a 87
140 b

a 3 pole
b 4 pole
Dimensions 115
Size 2: accessories
http://catalog.moeller.net Moeller SK1230-1177GB NZM2-XKR, NZM2-XDV, NZM2-XDTV

Circuit-breakers, switch-disconnectors
Connection on rear
(+)NZM2(-4)-XKR(O)(U)
35 35 35

SW 4 o 22
80

80
72

160
145
100
10 10 48
18

M4
105 35 17.5
o 8.6
140 70

35 35
M8 x 30
o 30
o 20
6

80
72
145

160

M4
18
35

Rotary drive
Rotary handle on circuit-breaker
NZM2-XDV NZM2-XDTV
NZM2-XDVR NZM2-XDTV2 d
b

a d=48
b f 34
a Up to 3 padlocks
F 67
75

59
100
95
R4
6

52
104
140
116 Dimensions
Size 2: accessories
NZM2-XTV, NZM1/2-XV4(6) Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Door coupling rotary handle


NZM2-XTVD(V)(R)...

73.5
d
27.5

b
d=48
8 b f 34
a Up to 3 padlocks
ZFS...-NZM7

o8
23

40
85

71
o
R4
6

71
85
25

a
35

Door coupling rotary handle with extension shaft


NZM2-XTVD(V)(R)
NZM1/2-XV4(6)
25 73
245 400(400 600) 27
8

55
o 45
17

NZM1/2-XV4(NZM1/2-XV6) 36 23g0.5
Dimensions 117
Size 2: accessories
http://catalog.moeller.net Moeller SK1230-1177GB NZM2-XTVD, NZM2-XS

Circuit-breakers, switch-disconnectors
Door coupling rotary handle with extension shaft
NZM2-XTVD(V)(R)-60 NZM2-XTVD(V)(R)-0 Minimum door coupling rotary handle clearance from door
pivot point
16 60 41 75

NZM...2-... f 130

NZM1/2-XV...

205 249 23g0.5 a

172 205 23g0.5

a Special tip

Main switch assembly kit for side panel mounting


NZM2-XS(R)-L

2-5 0.5
73.5 95-310 105 170.5

NZM2-XS(R)-R
41
51.5

0.5 2-5 15
105 95-310 73.5 170.5
118 Dimensions
Size 2: accessories
NZM2-XS, NZM2-XRAV Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Main switch assembly kit for side panel mounting with mounting bracket
NZM2-XS(R)M-L

NZM1/2-XZB

185

2-5 0.5 172.1


73.5 47.2 216
168 218.5
200.5

NZM2-XS(R)M-R
185

NZM1/2-XZB
0.5 2-5 172.1
47.2 73.5 216
168 218.5
200.5

Rear drive
NZM2-XRAV
184

133 a 145

168 b

a NZM2-XRAV(R)
b NZM2-4-XRAV(R)
Dimensions 119
Size 2: accessories
http://catalog.moeller.net Moeller SK1230-1177GB NZM-XAB, NZM2-XBR, NZM2-XDTV

Circuit-breakers, switch-disconnectors
Spacers Clip plate
NZM1/2-XAB NZM2-XC75
17.5 2

130
169
NZM1/2-XAB
35 17
120.5 105

Insulating surrounds
NZM2-XBR
9.5 a Mounting aperture
1.5 5
ZFS...-NZM7

103
132
64

142

127
10
158.5 23
17.5

Rotary handle on switch with door interlock


NZM2-XDTV(R)
32 a Mounting aperture
9.5 10.4
1.5 5 9

NZM2-XDTV(R) o4
a
9
63

103

142
10
17.5
120 Dimensions
Size 2: accessories
NZM2-XKAV Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Toggle lever locking device


NZM2/3-XKAV
a 50
d

b
d=48
b f 34
1.3

a Up to 3 padlocks

a
92.5

F 88

Part no. a
LZM2, LN2 52.5
LZM3, LN3 70
Dimensions 121
Size 2: accessories
http://catalog.moeller.net Moeller SK1230-1177GB NZM2-XMV, NZM2-XTVD, NZM2-XD

Circuit-breakers, switch-disconnectors
Mechanical interlock
NZM2-XMV + NZM2-XD

36

73
75

50
95
47.5

50
50 9.6

52.5 6

105 41

140 180 46

NZM2-XMV + NZM2-XTVD(V)(R)

NZM1/2-XV4(6)

Mechanical interlock
NZM2-XMV + NZM2-XTVD(V)(R)-60 NZM2-XMV + NZM2-XT(V)D(V)(R)-0

a
NZM1/2-XV...

240 284 207 240

a Special tip
122 Dimensions
Size 2: accessories
NZM2-XR Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Remote operator
NZM2-XR...
322.8 a Up to 3 padlocks
235.5 b Remote operator hinged
35 135
d
NZM2-XAVPR

b
d=48
b f 34
7.2

21.5
F 13.7

105
a

250
105 52.5
b
105
140
Dimensions 123
Size 2: accessories
http://catalog.moeller.net Moeller SK1230-1177GB NZM2-XCI, NZM2-XAD, NZM2-XSV

Circuit-breakers, switch-disconnectors
Insulated enclosures
NZM2-XCI43-T... NZM2-XCI45-T...
60

80
17
375
495

17
500
660
187.5

250
80 60
250 225
296
190 60
375 225
296

Component adapter
NZM2-XAD250
20

145

190
145

20

35 63
35 35
106

Plug-in units
+NZM2(-4)-XSV
190.5
92.3
87.5 148.3
35 25
15.7

M8 x 22
67.1

NZM2(-4)-XSVS
57.5

109.7
396

184
241
237
205

NZM2(-4)-XSVE

M4 x 93

SW5
M4 x 85

35 78.7
105
140
124 Dimensions
Size 2: accessories
NZM2(-4)-XFI, NZM-XDMI, UVU-NZM Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Residual-current release
NZM2(-4)-XFI...

252
265
291

29.5 22
22
22

22
29.5

29.5

87.7

70 6 103
35 108
140 149

Undervoltage releases, off-delayed


UVU-NZM
Capacitor unit
NZM-XCM
M5 X 16
78

60
50

M4 X 16

100 115 85
Dimensions 125
Size 3: Basic units
http://catalog.moeller.net Moeller SK1230-1177GB LZM3, LN3

Circuit-breakers, switch-disconnectors
Circuit-breaker
3 pole 166
LZMC3 120.5
NZM...3-...-4(C)NA
LZMN3
b
a
LN3 45 31 5

f 60
20.5
11
M10 x 30

28 29.5
135

R 205
123.5

95
216
234
275

315.5
117

SW5 M5 x 75
f 60

45 69.7
b
a

f5 140 f5

a Blow-out space, minimum distance to other parts f 60 mm


b Minimum distance to adjacent parts f 5 mm

Circuit-breaker
4 pole 166
LZMC3-4 120.5
LZMN3-4
b a
LN3-4 90 31 5
f 60
20.5

M10 x 30
28 29.5

135
123.4

R 205

N
95
234
216

275

117

SW5 M5 x 75
45
f 60

69.7
a b

f5 185 f5

a Blow-out space, minimum distance to other parts f 60 mm


b Minimum distance to adjacent parts f 5 mm
126 Dimensions
Size 3: accessories
NZM3-XK, NZM3-XIP, NZM3-XST Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Box terminal Tunnel terminal


(+)NZM3(-4)-XKC(O)(U) NZM3(-4)-XKA1(2)
IP2X protection against contact with a finger
NZM3(-4)-XIPK
75 54
26.5 31 F 18.7 25 32 27

M12
SW 8

25

35 25
SW 8 SW 8

80
M10 x 30
172
124

124
SW 5
140
185

140
185

Covers Control circuit terminal


NZM3(-4)-XKSA NZM3/4-XSTS
Cable lug NZM-XSTK
NZM3-XKS185
IP2X protection against contact with a finger
NZM3(-4)-XIPA

M10 x 30
148

SW 8
124

149
459

140 a
253

185 b
96

140 103
185

a 3 pole
b 4 pole
Dimensions 127
Size 3: accessories
http://catalog.moeller.net Moeller SK1230-1177GB NZM3XK

Circuit-breakers, switch-disconnectors
Connection width extension
NZM3(-4)-XKV70
Terminals 70 70
NZM3(-4)-XK22X21 45 26.5 37 24
NZM3(-4)-XK300 33 70 70 70 6
43 20 50 18 50 6
o 13

a
M10 x 30
o 6.4
5.75
11.5
28

123.5
401

616

295
401
433

433
295

200
b

45 45 45 45 45 49
140 24 185 36.5
188 258
255 325

a NZM3(-4)-XK22X21
b NZM3(-4)-XK300
Connection on rear
(+)NZM3(-4)-XKR(O)(U)
45 45 45
SW 8 o 30
123.5

124
117

247
234

112
11 11 57
22

140 35 M5
o 11 90
185

M10 x 35 45 45
o 28

o 30
10

124
117
234

247

M5
22
45
128 Dimensions
Size 3: accessories
NZM3-XKP, NZM3-XAB, NZM3-XBR Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Phase isolators
NZM3-4-XKP

616
599
200

161.6

3.5 100

45
90
210
255

Spacers Insulating surrounds


NZM3-XAB NZM3-XBR a Mounting aperture

138 9.5
17.5 1.5 5
ZFS...-NZM7

110
132
64

NZM3-XAB
177

162
193.5 23

10
17.5
Dimensions 129
Size 3: accessories
http://catalog.moeller.net Moeller SK1230-1177GB NZM3-XDV, NZM3-XTVD

Circuit-breakers, switch-disconnectors
Rotary drive
Rotary handle on circuit-breaker
NZM3-XDV
NZM3-XDVR a
d

b
d=48
b f 34
a Up to 3 padlocks
105

F82.6
7
R8
124
95

140
185

Door coupling rotary handle


NZM3-XTVD(V)(R)...
95
27.5

ZFS...-NZM7

o8
23

40
85

71
o

R87

71
85

25
35

d
b

d=48
b f 34
a Up to 3 padlocks
130 Dimensions
Size 3: accessories
NZM3-XTVD Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Door coupling rotary handle with extension shaft


NZM3-XTVD(V)(R)
NZM3/4-XV4(6)

25 95
X 27
8

59
o 60
32.5

36 23g0.5
NZM3/4-XV4(6)

29

Part no. x
NZM3/4-XV4 270 400
NZM3/4-XV6 400 600

NZM3-XTVD(V)(R)-60 NZM3-XTVD(V)(R)-0

18 60
42 77.5

NZM3/4-XV... a

199.5 235 23g0.5


235 277 23g0.5

a Special tip

Minimum door coupling rotary handle clearance from door pivot point

NZM...3-... f 180
Dimensions 131
Size 3: accessories
http://catalog.moeller.net Moeller SK1230-1177GB NZM3-XS

Circuit-breakers, switch-disconnectors
Main switch assembly kit for side panel mounting
NZM3-XS(R)-L

105
25 86 433 195
95 25

NZM3-XS(R)-R

105

39.1 24.1

86 433 25 195
95 25
132 Dimensions
Size 3: accessories
NZM3-XMV, NZM3-XTVD, NZM3-XDV Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Mechanical interlock
NZM3-XMV + NZM3-XDV(R)

34.5
105

73.2
50
95
47.5

50
96.5

20
99 5

140 40
185 196 69

NZM3-XMV + NZM3-XTVD(V)(R)

NZM3/4-XV4(NZM3/4-XV6)

305 400(400 600)

NZM3-XMV + NZM3-XTVD(V)(R)-60 NZM3-XMV + NZM3-XTVD(V)(R)-0

a
NZM3/4-XV...

270 312 235 270

a Special tip
Dimensions 133
Size 3: accessories
http://catalog.moeller.net Moeller SK1230-1177GB NZM3-XCI, NZM3-XAD

Circuit-breakers, switch-disconnectors
Insulated enclosures Component adapter
NZM3-XCI48-TD NZM3-XAD550
80

270
229
32.5

910
750

45 45 38
375

140 63

29 60
190 275
375 369
134 Dimensions
Size 3: accessories
NZM3-X Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Remote operator
NZM3-XR...
358
d

b
260.5 d=48
b f 34
60.5 143.5
a Up to 3 padlocks
NZM3-XAVPR
5.5

10

17

28
F 13

140
a

95

291.5
b

140 70
140
185

Withdrawable unit
+NZM3(-4)-XAV
309 d
299 e
271 f

225.5 5
91
25

175.8

171

30
R1
200

341.6
313.5
170.8

130
151.8

c
25

SW 8 M10 x 30
45 31
96 400
200 a 520
227 a
250 b
272 b

a 3-pole d withdrawn
d
b

b 4-pole d=48 e test


b f 34 f connected
c Up to 3 padlocks
Dimensions 135
Size 4: Basic units
http://catalog.moeller.net Moeller SK1230-1177GB LZM4, LN4

Circuit-breakers, switch-disconnectors
Circuit-breaker
3 pole
LZMN4 207
LN4 204 138
70 33 8

ba

f 100

44
108

119
171.5
180

313
401

117
21
87.5

F
15

o 10.5 M5 x 110
b
15

45 25 100 100
f 15 70 f 15
210

a Blow out area, minimum distance to other parts f 100 mm


b Minimum distance to adjacent parts f 15 mm
136 Dimensions
Size 4: accessories
LZM4, LN4, LZM4-XK Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Circuit-breaker
4 pole
LZMN4-4 207
LN4 138
33 8
140

b
a

f 100

44
108

119
171.5
180

21
117
313
401

N
87.5
15

M5 x 110
o 10.5
b
15

100 100
45 70 25
f 15 f 15
280

a Blow out area, minimum distance to other parts f 100 mm


b Minimum distance to adjacent parts f 15 mm

Covers Tunnel terminal


NZM4(-4)-XKSA NZM4-4-XKA
c 60
128
f 100

53 32

c
108.5

f 100

4 x SW8
73.5

25

M10 x 60
2 x SW16
30.5
531

171.5

210 a
280 b

210 a
280 b

a 3 pole
b 4 pole
c Clearance from conductive parts f 100 mm
Dimensions 137
Size 4: accessories
http://catalog.moeller.net Moeller SK1230-1177GB NZM4-XKM

Circuit-breakers, switch-disconnectors
Screw connection
Module plate Flat cable terminal Part no. a b
Single hole NZM4(-4)-XKB NZM4(-4)-XKM1 36 47
NZM4(-4)-XKM1 NZM4(-4)-XKM2 32 40
2-hole NZM4(-4)-XKB 47
NZM4(-4)-XKM2
43 40 50 a 3 pole
43 b 4 pole
25
c Clearance from conductive parts f 100 mm

NZM4-XKM2 NZM4(-4)-XKB NZM4(-4)-XKB


o 11 SW5
M10 50
b

SW16
a

NZM4-XKM1
171.5

210 a
280 b

Module plate
2 holes, vertical
NZM4(-4)-XKM2S...
33
o 13
70 70 70 70 70 x
o 13
16

16

M 10 x 50
32
32

SW16
171.5
486
518
486
518

50 50

210 280

Part no. x
NZM4(-4)-XKM2S-1250 12
NZM4(-4)-XKM2S-1600 20
138 Dimensions
Size 4: accessories
NZM4-XKV Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Connection width extension


NZM4-XKV95 NZM4-XKV110
95 95 107.5 107.5 48
50 77 18 50 77 30.5 15
o 11 o 11

M10 x 50
15

15
SW16

171.5
543
573
543
573

30 30
210 28.5 210 41
267 292

NZM4-4-XKV95 NZM4-4-XKV120
95 47.5 47.5 95
18 18 18 122 122 122
48
50 77 80 42 42 42
o 11 15
30 o 11 50

M10 x 50
15
15

171.5
543
573

595
625

30 18 30
41 280 83
362 446
Dimensions 139
Size 4: accessories
http://catalog.moeller.net Moeller SK1230-1177GB NZM4(-4)-XKP, NZM4(-4)-XKR

Circuit-breakers, switch-disconnectors
Connection on rear
NZM4(-4)-XKR Fitting on mounting plate
278
139 Rear connection possible also with
rotation by 90.
SW16
a 3 pole
M10 x 30
b 4 pole

72
172

180
411
88
30
15
M5

206
9.5

210 a 16
70
280 b 3-5
140

208
o 11
104
25
45

72

180
411
87.5

M5
205.5

35
70

Phase isolators
NZM4-4-XKP
190

3.5 114
70
140
140 Dimensions
Size 4: accessories
NZM4-XDV, NZM4-XTVD Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Rotary handle on circuit-breaker


NZM4-XDV(R)
57 69
204 5
33

221.5
a

f 89.5
73.5

R 137
117
58.5

60.5

162
210
280

d
b

d=48
b f 34
a Up to 3 padlocks

Door coupling rotary handle


NZM4-XTVD(V)(R)...
70

ZFS...-NZM7 18
o8
23

40

71
85

85 R1
37 71

a
a Up to 3 padlocks
d
b

d=48
b f 34
Dimensions 141
Size 4: accessories
http://catalog.moeller.net Moeller SK1230-1177GB NZM4-XTVD, NZM4-XV, NZM4-XS

Circuit-breakers, switch-disconnectors
Door coupling rotary handle with extension shaft
NZM4-XTVD(V)(R)
NZM3/4-XV4(6)
300 400(400 600)
25 95
5 27
59 8
o 60
21

36 23g0.5

NZM3/4-XV4(NZM3/4-XV6)

57

NZM4-XTVD(V)(R)-60 NZM4-XTVD(V)(R)-0

18 60 42 77.5

NZM3/4-XV... a
270 312 23g0.5 234.5 270 23g0.5

a Special tip
Minimum door coupling rotary handle clearance from door pivot point

NZM...4-... f 180

Main switch mounting kits for side-wall mounting


NZM4-XS(R)-L
NZM4-XS(R)-R
229

86 433 34.1
25 24.1
221.5

100
142 Dimensions
Size 4: accessories
NZM4-XBR, NZM4-XMV, NZM4-X Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Insulating surrounds
NZM4-XBR
9.5 a Mounting aperture
1.5 5

ZFS...-NZM7

a
154

125
64

246
231 23
262.5

10
17.5

Mechanical interlock
NZM4-XMV + NZM4-XDV(R)
34.5
221.5

73.2
50
95

50
47.5

20
5
162 40
210 230 69
280

NZM4-XMV + NZM4-XTVD(V)(R) NZM4-XMV + NZM4-XTVD(V)(R)-60

NZM3/4-XV4(NZM3/4-XV6)
NZM3/4-XV...

335 400(400 600) 305 347


Dimensions 143
Size 4: accessories
http://catalog.moeller.net Moeller SK1230-1177GB NZM4-XMV, NZM4-X

Circuit-breakers, switch-disconnectors
Mechanical interlock
NZM4-XMV + NZM4-XTVD(V)(R)-0

270 305

a Special tip

Remote operator
NZM4-XR
435.2
313.4
175.4

12.5
204 F13.4

19.4

306.4
45.5
55.6

189

454.4
117

a
84.4

189.5 189.5
208 208
210 280

d
b

d=48
b f 34
a Up to 3 padlocks
Remote operator folded
144 Dimensions
Size 4: accessories
NZM4-XAV Moeller SK1230-1177GB http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Withdrawable unit
+NZM4-4-XAV

353.5 d
341 e
313 f
243 8

M6 x 12
25 25

217
274.5

30
R1
300

509
451

c
25 25

70 131 33
275 560
297 a 680
350
367 b

a 3-pole d Disconnected
d
b 4-pole e Test
b

d=48
b f 34
f Connected
c Up to 3 padlocks