SREX POWER INDIA PVT. LTD.

PRE-COMMISSIONING REPORT OF
LIGHTNING ARRESTER

1.0 EQUIPMENT DETAILS:

MAKE : CGL

MODEL : ZLA-3E

RATING : 60kV

MFG YEAR : 2015

SR. No. : R - PHASE :


Y - PHASE :
B - PHASE :

2.0 CHECK LIST BEFORE ELECTRICAL TESTING

Sr. No. DESCRIPTION

EQUPIMENT IS CLEANED AND FREE FROM DUST / DIRT FO


1 MATERIALS ETC.

EQUIPMENT IS FREE FROM ALL VISIBLE DEFECTS ON P


2 INSPECTION

3 SUPPORT STRUCTURES HAVE BEEN PROVIDED WITH DOUB


4 ALL NUTS AND BOLTS ARE TIGHTENED
5 CHECK TIGHTNESS OF TERMINAL CONNECTOR
6 LEVELLING AND ALIGNMENT OF STRUCTURE IS CHECKED

Page 1 of 24
SREX POWER INDIA PVT. LTD.

PRE-COMMISSIONING REPORT OF
LIGHTNING ARRESTER

CHECK ONE END OF SURGE COUNTER IS CONNECTED TO T


LA STACK AND OTHER END OF SURGE COUNTER HAS BEE
7

THE DIRECTION OF THE EXHAUST VENT PORTS ARE AWAY


8 PROTECTED EQUIPMENT AND OTHER ARRESTER POLES

CHECK THE SERIAL NO. AND SEQUENCE OF LA PARTS FOR ERECTION IN MU


9

CHECK ON CHARGING, THE SURGE COUNTER POINTER IS IN GREEN ZONE


10

3.0 INSULATION RESISTANCE MEASUREMENT

BETWEEN TERMINALS
TOP TO EARTH
ACROSS BASE INSULATOR BY 500V MEGGER

4.0 SURGE COUNTER TEST


APPLY 1-PH PULSE TO COUNTER

COUNTER
MAKE
Sr. No.
MODEL
INITIAL READING

Page 2 of 24
SREX POWER INDIA PVT. LTD.

PRE-COMMISSIONING REPORT OF
LIGHTNING ARRESTER

5.0 REMARKS

TESTED BY
SIGNATURE :
NAME :RAHUL JANGRA
ORGANISATION : SREX POWER

Page 3 of 24
DIA PVT. LTD. DOC NO. :
PROJECT : 66 kV GIS Substation
PLANT/AREA : Honda Motorcycle & Scooter India Ltd
G REPORT OF CLIENT : Honda Motorcycle & Scooter India Ltd
ER LOCATION : HONDA METERING BAY
EQUIPMENT IDENTIFICATION : LA - METERING BAY
DATE OF TESTING : 7/8/2015

169195
169194
169193

STATUS
DESCRIPTION
YES NO
D FREE FROM DUST / DIRT FOREIGN
YES

ALL VISIBLE DEFECTS ON PHYSICAL


YES

E BEEN PROVIDED WITH DOUBLE EARTH YES


IGHTENED YES
INAL CONNECTOR YES
T OF STRUCTURE IS CHECKED YES

Page 4 of 24
DIA PVT. LTD. DOC NO. :
PROJECT : 66 kV GIS Substation
PLANT/AREA : Honda Motorcycle & Scooter India Ltd
G REPORT OF CLIENT : Honda Motorcycle & Scooter India Ltd
ER LOCATION : HONDA METERING BAY
EQUIPMENT IDENTIFICATION : LA - METERING BAY
DATE OF TESTING : 7/8/2015

COUNTER IS CONNECTED TO THE BOTTOM OF


OF SURGE COUNTER HAS BEEN EARTHED
YES

AUST VENT PORTS ARE AWAY FROM THE


D OTHER ARRESTER POLES YES

CE OF LA PARTS FOR ERECTION IN MULTI STACK LA


YES

OUNTER POINTER IS IN GREEN ZONE


YES

VALUES MEASURED IN MEGA OHMS


R-PH Y-PH
>1000 >1000
>100 >100

R-PH Y-PH
CGL CGL
H-2014-2093 H-2014-2105
SC-07-1 SC-07-1
000005 000005

Page 5 of 24
DIA PVT. LTD. DOC NO. :
PROJECT : 66 kV GIS Substation
PLANT/AREA : Honda Motorcycle & Scooter India Ltd
G REPORT OF CLIENT : Honda Motorcycle & Scooter India Ltd
ER LOCATION : HONDA METERING BAY
EQUIPMENT IDENTIFICATION : LA - METERING BAY
DATE OF TESTING : 7/8/2015

APPROVED BY
SIGNATURE :
NAME :
ORGANISATION :

Page 6 of 24
orcycle & Scooter India Ltd
orcycle & Scooter India Ltd
ETERING BAY
ERING BAY

REMARK
RECORD DEFICIENCIES, IF ANY

Page 7 of 24
orcycle & Scooter India Ltd
orcycle & Scooter India Ltd
ETERING BAY
ERING BAY

A OHMS
B-PH
>1000
>100

B-PH
CGL
H-2014-2104
SC-07-1
000008

Page 8 of 24
orcycle & Scooter India Ltd
orcycle & Scooter India Ltd
ETERING BAY
ERING BAY

:
HMSI

Page 9 of 24
SREX POWER INDIA PVT. LTD.

PRE-COMMISSIONING REPORT OF
LIGHTNING ARRESTER

1.0 EQUIPMENT DETAILS:

MAKE : CGL

MODEL : ZLA-3E

RATING : 60kV

MFG YEAR : 2015

SR. No. : R - PHASE :


Y - PHASE :
B - PHASE :

2.0 CHECK LIST BEFORE ELECTRICAL TESTING

Sr. No. DESCRIPTION

EQUPIMENT IS CLEANED AND FREE FROM DUST / DIRT FO


1 MATERIALS ETC.

EQUIPMENT IS FREE FROM ALL VISIBLE DEFECTS ON P


2 INSPECTION

3 SUPPORT STRUCTURES HAVE BEEN PROVIDED WITH DOUB


4 ALL NUTS AND BOLTS ARE TIGHTENED
5 CHECK TIGHTNESS OF TERMINAL CONNECTOR
6 LEVELLING AND ALIGNMENT OF STRUCTURE IS CHECKED

Page 10 of 24
SREX POWER INDIA PVT. LTD.

PRE-COMMISSIONING REPORT OF
LIGHTNING ARRESTER

CHECK ONE END OF SURGE COUNTER IS CONNECTED TO T


LA STACK AND OTHER END OF SURGE COUNTER HAS BEE
7

THE DIRECTION OF THE EXHAUST VENT PORTS ARE AWAY


8 PROTECTED EQUIPMENT AND OTHER ARRESTER POLES

CHECK THE SERIAL NO. AND SEQUENCE OF LA PARTS FOR ERECTION IN MU


9

CHECK ON CHARGING, THE SURGE COUNTER POINTER IS IN GREEN ZONE


10

3.0 INSULATION RESISTANCE MEASUREMENT

BETWEEN TERMINALS
TOP TO EARTH
ACROSS BASE INSULATOR BY 500V MEGGER

4.0 SURGE COUNTER TEST


APPLY 1-PH PULSE TO COUNTER

COUNTER
MAKE
Sr. No.
MODEL
INITIAL READING

Page 11 of 24
SREX POWER INDIA PVT. LTD.

PRE-COMMISSIONING REPORT OF
LIGHTNING ARRESTER

5.0 REMARKS

TESTED BY
SIGNATURE :
NAME :RAHUL JANGRA
ORGANISATION : SREX POWER

Page 12 of 24
DIA PVT. LTD. DOC NO. :
PROJECT : 66 kV GIS Substation
PLANT/AREA : Honda Motorcycle & Scooter India Ltd
G REPORT OF CLIENT : Honda Motorcycle & Scooter India Ltd
ER LOCATION : TRANSFORMER BAY
EQUIPMENT IDENTIFICATION : LA - T/F -02
DATE OF TESTING : 7/8/2015

169195
169194
169193

STATUS
DESCRIPTION
YES NO
D FREE FROM DUST / DIRT FOREIGN
YES

ALL VISIBLE DEFECTS ON PHYSICAL


YES

E BEEN PROVIDED WITH DOUBLE EARTH YES


IGHTENED YES
INAL CONNECTOR YES
T OF STRUCTURE IS CHECKED YES

Page 13 of 24
DIA PVT. LTD. DOC NO. :
PROJECT : 66 kV GIS Substation
PLANT/AREA : Honda Motorcycle & Scooter India Ltd
G REPORT OF CLIENT : Honda Motorcycle & Scooter India Ltd
ER LOCATION : TRANSFORMER BAY
EQUIPMENT IDENTIFICATION : LA - T/F -02
DATE OF TESTING : 7/8/2015

COUNTER IS CONNECTED TO THE BOTTOM OF


OF SURGE COUNTER HAS BEEN EARTHED
YES

AUST VENT PORTS ARE AWAY FROM THE


D OTHER ARRESTER POLES YES

CE OF LA PARTS FOR ERECTION IN MULTI STACK LA


YES

OUNTER POINTER IS IN GREEN ZONE


YES

VALUES MEASURED IN MEGA OHMS


R-PH Y-PH
>1000 >1000
>100 >100

R-PH Y-PH
CGL CGL
H-2014-2093 H-2014-2105
SC-07-1 SC-07-1
000005 000005

Page 14 of 24
DIA PVT. LTD. DOC NO. :
PROJECT : 66 kV GIS Substation
PLANT/AREA : Honda Motorcycle & Scooter India Ltd
G REPORT OF CLIENT : Honda Motorcycle & Scooter India Ltd
ER LOCATION : TRANSFORMER BAY
EQUIPMENT IDENTIFICATION : LA - T/F -02
DATE OF TESTING : 7/8/2015

APPROVED BY
SIGNATURE :
NAME :
ORGANISATION :

Page 15 of 24
orcycle & Scooter India Ltd
orcycle & Scooter India Ltd
RMER BAY

REMARK
RECORD DEFICIENCIES, IF ANY

Page 16 of 24
orcycle & Scooter India Ltd
orcycle & Scooter India Ltd
RMER BAY

A OHMS
B-PH
>1000
>100

B-PH
CGL
H-2014-2104
SC-07-1
000008

Page 17 of 24
orcycle & Scooter India Ltd
orcycle & Scooter India Ltd
RMER BAY

:
HMSI

Page 18 of 24
SREX POWER INDIA PVT. LTD.

PRE-COMMISSIONING REPORT OF
LIGHTNING ARRESTER

1.0 EQUIPMENT DETAILS:

MAKE :

MODEL :

RATING :

MFG YEAR :

SR. No. : R - PHASE :


Y - PHASE :
B - PHASE :

2.0 CHECK LIST BEFORE ELECTRICAL TESTING

Sr. No. DESCRIPTION


1 EQUPIMENT IS CLEANED AND FREE FROM DUST / DIRT FO
2 MATERIALS ETC.
EQUIPMENT IS FREE FROM ALL VISIBLE DEFECTS ON P
3 INSPECTION
SUPPORT STRUCTURES HAVE BEEN PROVIDED WITH DOUB
4 ALL NUTS AND BOLTS ARE TIGHTENED
5 CHECK TIGHTNESS OF TERMINAL CONNECTOR
6 LEVELLING AND ALIGNMENT OF STRUCTURE IS CHECKED
CHECK ONE END OF SURGE COUNTER IS CONNECTED TO T
LA STACK AND OTHER END OF SURGE COUNTER HAS BEE
7

THE DIRECTION OF THE EXHAUST VENT PORTS ARE AWAY


8 PROTECTED EQUIPMENT AND OTHER ARRESTER POLES

CHECK THE SERIAL NO. AND SEQUENCE OF LA PARTS FOR ERECTION IN MU


9

CHECK ON CHARGING, THE SURGE COUNTER POINTER IS IN GREEN ZONE


10
3.0 INSULATION RESISTANCE MEASUREMENT

BETWEEN TERMINALS
TOP TO EARTH
ACROSS BASE INSULATOR BY 500V MEGGER

4.0 SURGE COUNTER TEST


APPLY 1-PH PULSE TO COUNTER

COUNTER
MAKE
Sr. No.
MODEL
INITIAL READING

5.0 REMARKS

TESTED BY
SIGNATURE :
NAME :
ORGANISATION :
DIA PVT. LTD. DOC NO. :
PROJECT :
PLANT/AREA :
G REPORT OF CLIENT :
ER LOCATION :
EQUIPMENT IDENTIFICATION :
DATE OF TESTING :

STATUS
DESCRIPTION
YES NO
D FREE FROM DUST / DIRT FOREIGN
ALL VISIBLE DEFECTS ON PHYSICAL
E BEEN PROVIDED WITH DOUBLE EARTH
IGHTENED
INAL CONNECTOR
T OF STRUCTURE IS CHECKED
COUNTER IS CONNECTED TO THE BOTTOM OF
OF SURGE COUNTER HAS BEEN EARTHED

AUST VENT PORTS ARE AWAY FROM THE


D OTHER ARRESTER POLES

CE OF LA PARTS FOR ERECTION IN MULTI STACK LA

OUNTER POINTER IS IN GREEN ZONE


VALUES MEASURED IN MEGA OHMS
R-PH Y-PH

R-PH Y-PH

APPROVED BY
SIGNATURE :
NAME :
ORGANISATION :
REMARK
RECORD DEFICIENCIES, IF ANY
A OHMS
B-PH

B-PH