Connecting Cables
Connect the FE port on the ECC500 with a personal computer (PC) using a crossover cable,
as shown in Figure 4-2.
Setting an IP Address
If the ECC500 communicates by GPRS, no IP address is required.
If the ECC500 communicates by IP, set the IP address (default value:192.168.1.168),
subnet mask (default value:255.255.255.0), and gateway (default value:192.168.1.1) on
the LCD.
Setting an IP Address of PC
Set the IP address of the PC to be on the same network segment as the IP address of the
ECC500.
Setting a LAN
If the ECC500 is connected to a local area network (LAN) and a proxy server has been
selected, you need to cancel proxy server setting.
If the ECC500 is connected to the Internet but the computer is connected to the LAN, you
cannot cancel proxy server setting; otherwise, you will fail to access the ECC500.
Login Page
Enter the IP address of the ECC500 in the Internet Explorer address box, choose English then
press Enter. A login page is displayed, as shown in Figure 4-5.
The preset User Name is admin, and the preset Password is 001.
If you disconnect the network cable or close the web page, you need to wait about 3 minutes before the
re-login succeeds. Otherwise, a message "[user name] is logged in. Please log out first." is displayed.
System Status
The System Status pane displays current alarms and information about connected equipment.
If the navigation tree is not displayed completely, hold down Ctrl while rotating the mouse
wheel to zoom in on the view.
System Configuration
The System Configuration pane allows you to configure parameters about the equipment
connecting to the ECC500. Figure 4-7 shows the pane for configuring site information. To
modify a parameter, select the parameter, change the value in the text box, and then click
Submit.
Network Configuration
The Network Configuration pane allows you to configure parameters about the network
parameter, NetEco. Figure 4-9 shows the Network Configuration.
Control
The Control pane allows you to modify the control parameters of the ECC500monitoring
equipment. Figure 4-10 shows the Control interface.
Statistics
Step 1 Click Statistics and select a value option as required from the Please Select The Statistics
Signal drop-down list box.
Step 2 Click Search.
The query result is displayed, as shown in Figure 4-11.
Step 3 Click Export to export statistics in HTML format, as shown in Figure 4-12.
Step 4 In the Save HTML Document dialog box, select a save path, change the file name, set
Language to Unicode, and then click Save, as shown in Figure 4-22.
----End
if you want to save the statistics in .xls document, add ".xls" in the end of the document name manually.
For example, hisStatLog.xls.
User Management
The User Management pane allows you to create, modify, and delete user information,
operation as shown in Figure 4-14 and Figure 4-15.