This is an electronic version of a test report which was made as a copy of test report officially issued in a paper form.
The electronic version of a test report shall be used only for informative purposes. Any information listed in this test
report is the property of the sponsor and shall not be used or published without written permission. Contents of this file
may only be modified by the editor i.e. Testing laboratory FIRES s.r.o. Batizovce. Sponsor is allowed to publish this test
FIRES 004/S-20/12/2012-E-el
TEST REPORT
FIRES-RF-028-16-AUNE
Manufacturer: World Mech' Tech' Co., Ltd., 8-105, Jangjae-ro 520 beon-gil,
Saengnim-myeon, Gimhae-si, Gyeongsangnam-do, Republic of Korea
Sponsor: World Mech' Tech' Co., Ltd., 8-105, Jangjae-ro 520 beon-gil,
Saengnim-myeon, Gimhae-si, Gyeongsangnam-do, Republic of Korea
Technician responsible for the technical side of this report: Ing. Samuel Skokan
Number of pages: 11
Test reports: 3 Copy No.: 2
Distribution list:
Copy No. 1 FIRES, s. r. o., Osloboditeov 282, 059 35 Batizovce, Slovak Republic
(electronic version)
Copy No. 2 World Mech' Tech' Co., Ltd., 8-105, Jangjae-ro 520 beon-gil, Saengnim-myeon,
Gimhae-si, Gyeongsangnam-do, Republic of Korea (electronic version)
Copy No. 3 World Mech' Tech' Co., Ltd., 8-105, Jangjae-ro 520 beon-gil, Saengnim-myeon,
Gimhae-si, Gyeongsangnam-do, Republic of Korea
This report includes accreditation mark SNAS with additional mark ILAC-MRA. SNAS is signatory of ILAC-MRA, Mutual recognition
agreement (of accreditation), which is focused on promoting of international acceptance of accredited laboratory data and reducing
technical barriers to trade, such as the retesting of products on markets of signatories. More information about ILAC-MRA is on
www.ilac.org. Signatories of ILAC-MRA are e.g. SNAS (Slovakia), CAI (Czech Republic), PCA (Poland), DakkS (Germany) or BMWA
(Austria). Up to date list of ILAC-MRA signatories is on http://ilac.org/ilac-mra-and-signatories/. FIRES, s.r.o. Batizovce is full member of
EGOLF also, more information www.egolf.org.uk. Test reports issued by FIRES, s.r.o. are valid in United Arab Emirates based on list of
laboratories approved by United Arab Emirates Ministry of Interior Civil Defence (up-to-date list is available on: www.dcd.gov.ae/eng/).
FIRES 186/S-02/03/2016-E FIRES, s.r.o., Osloboditeov 282, 059 35 Batizovce, Slovak Republic
tel. 00421 52 775 22 98, fax. 00421 52 788 14 12, www.fires.sk
Notified Body No. 1396, Approved Body No. SK01, Member of EGOLF
FIRES-RF-028-16-AUNE
1. INTRODUCTION
This test report contains the results of test carried out by FIRES, s.r.o., Testing laboratory in Batizovce,
accredited by SNAS for testing. Certificate of accreditation No.: S-159. The purpose of the test was to gain
information for product classification.
2. MEASURING EQUIPMENT
Identification number Measuring equipment Note
F 90 014 Test chamber SBI
F 80 001 Gas analyser Horiba ENDA 600
F 81 001 System for light transmission measurement
PLC system for control and data acquisition for SBI
F 69 008
TECOMAT NS 950
F 40 012 Application SW SBI for PLC NS 950
F 40 013 Visualizing SW for SBI in Control Web 2000
F 40 014 Driver Tecomat-CW (SW)
F 71 013 Transducer of differential pressure (-50 to + 150) Pa
F 71 014 Transducer of differential pressure (-50 to + 150) Pa
F 54 059 Racking meter 5m
PLC system for control and data acquisition
F 69 009 ambient conditions
TECOMAT TC 604
F 60 001
Temperature and relative air humidity sensors ambient conditions
F 60 012
F 54 027 Digital calliper 0 200 mm
F 57 002 Digital stop-watch
F 08 601 Sheathed thermocouple 2 mm, type K
F 08 401 Sheathed thermocouple 0,5 mm, type K
F 08 402 Sheathed thermocouple 0,5 mm, type K
F 08 403 Sheathed thermocouple 0,5 mm, type K
F 58 006 Coriolis mass flowmeter
Specimen No. 2
Lateral flame spread:
Occurrence No
Reaching the edge of the test specimen No
Flaming droplets or particles:
Occurrence No
Fallen droplet/particle burning 10 s No
Fallen droplet/particle burning >10 s No
Specimen No. 3
Lateral flame spread:
Occurrence No
Reaching the edge of the test specimen No
Flaming droplets or particles:
Occurrence No
Fallen droplet/particle burning 10 s No
Fallen droplet/particle burning >10 s No
5.3 EVALUATION OF THE TESTS ACC. TO CLAUSE No. 7 OF EN 13501-1 + A1: 2009
SPECIMEN No. 1 2 3 Result*
FIGRA0,2MJ [W/s] 3,1 8,6 3,8 5,2
FIGRA0,4MJ [W/s] 3,1 8,6 3,8 5,2
THR600s [MJ] 0,6 1,1 0,9 0,9
SMOGRA [m2/s2] 1,6 1,3 1,1 1,3
TSP600s [m2] 32,9 31,2 25,8 30,0
LFS<specimen edge yes yes yes yes
Flaming droplets/particles no no no no
* Final value evaluated acc. to rules of clause No. 7 of EN 13501-1 + A1: 2009.
Graphs of the average heat release rate HRRav (t), total heat release THR (t), 1000 x HRRav (t) / (t-300),
SPRav (t), TSP (t) and 10 000 x SPRav (t) / (t-300) in time period 0 t 1500 s are listed in pages 6 and 7
of the report.
4,0
3,5
3,0
HRRav(t) [kW]
2,5
2,0
1,5
1,0
0,5
0,0
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
3,0
2,5
2,0
THR (t) [MJ]
1,5
1,0
0,5
0,0
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
30
1000 x HRRav (t) [kW] / (t-300)
25
20
15
10
0
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
0,16
0,14
0,12
SPRav (t) [m2/s]
0,10
0,08
0,06
0,04
0,02
0,00
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
120
100
80
TSP(t) [m2]
60
40
20
0
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
7
10000 x SPRav [m2/s] / (t-300)
0
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
6. FINAL PROVISION
The test results refer only to the tested subjects. This test report is not an approval of the tested product by
the test laboratory or the accreditation body overseeing the laboratorys activities. The tests were carried
out on testing equipment that is the property of FIRES Ltd. Without the written permission of the test
laboratory this test report may be copied and/or distributed only as the whole. Any modifications of the test
report can be made only by the fire resistance test laboratory FIRES Ltd. Batizovce.
The tests results relate to the behaviour of the test specimens of a product under the particular conditions
of the tests; they are not intended to be the sole criterion for assessing the potential fire hazard of the
product in use.
7. NORMATIVE REFERENCES
EN 13823+A1: 2015 Reaction to fire tests for building products - Building products excluding
floorings exposed to the thermal attack by a single burning item
EN 13238: 2010 Reaction to fire tests for building products - Conditioning procedures and
general rules for selection of substrates
EN 13501-1+ A1: 2009 Fire classification of construction products and building elements. Part 1:
Classification using test data from reaction to fire tests