Vous êtes sur la page 1sur 12

TEST REPORT FIRES-RF-028-16-AUNE

Aluminium Composite Panel type Alcotop

This is an electronic version of a test report which was made as a copy of test report officially issued in a paper form.
The electronic version of a test report shall be used only for informative purposes. Any information listed in this test

report is the property of the sponsor and shall not be used or published without written permission. Contents of this file
may only be modified by the editor i.e. Testing laboratory FIRES s.r.o. Batizovce. Sponsor is allowed to publish this test

report in parts only with written permission of the editor.

FIRES 004/S-20/12/2012-E-el
TEST REPORT
FIRES-RF-028-16-AUNE

Tested property: Reaction to fire


Test method: EN 13823+A1: 2015
Type of test: Accredited / Notified (NB 1396)
Date of issue: 21. 03. 2016

Name of the product: Aluminium Composite Panel type Alcotop

Manufacturer: World Mech' Tech' Co., Ltd., 8-105, Jangjae-ro 520 beon-gil,
Saengnim-myeon, Gimhae-si, Gyeongsangnam-do, Republic of Korea
Sponsor: World Mech' Tech' Co., Ltd., 8-105, Jangjae-ro 520 beon-gil,
Saengnim-myeon, Gimhae-si, Gyeongsangnam-do, Republic of Korea

Test carried out: FIRES, s.r.o., Testing laboratory


Project No.: PR-13-0217
Specimens received: 04. 02. 2016
Date of the tests: 04. 03. 2016

Technician responsible for the technical side of this report: Ing. Samuel Skokan

Number of pages: 11
Test reports: 3 Copy No.: 2

Distribution list:

Copy No. 1 FIRES, s. r. o., Osloboditeov 282, 059 35 Batizovce, Slovak Republic
(electronic version)
Copy No. 2 World Mech' Tech' Co., Ltd., 8-105, Jangjae-ro 520 beon-gil, Saengnim-myeon,
Gimhae-si, Gyeongsangnam-do, Republic of Korea (electronic version)
Copy No. 3 World Mech' Tech' Co., Ltd., 8-105, Jangjae-ro 520 beon-gil, Saengnim-myeon,
Gimhae-si, Gyeongsangnam-do, Republic of Korea
This report includes accreditation mark SNAS with additional mark ILAC-MRA. SNAS is signatory of ILAC-MRA, Mutual recognition
agreement (of accreditation), which is focused on promoting of international acceptance of accredited laboratory data and reducing
technical barriers to trade, such as the retesting of products on markets of signatories. More information about ILAC-MRA is on
www.ilac.org. Signatories of ILAC-MRA are e.g. SNAS (Slovakia), CAI (Czech Republic), PCA (Poland), DakkS (Germany) or BMWA
(Austria). Up to date list of ILAC-MRA signatories is on http://ilac.org/ilac-mra-and-signatories/. FIRES, s.r.o. Batizovce is full member of
EGOLF also, more information www.egolf.org.uk. Test reports issued by FIRES, s.r.o. are valid in United Arab Emirates based on list of
laboratories approved by United Arab Emirates Ministry of Interior Civil Defence (up-to-date list is available on: www.dcd.gov.ae/eng/).

FIRES 186/S-02/03/2016-E FIRES, s.r.o., Osloboditeov 282, 059 35 Batizovce, Slovak Republic
tel. 00421 52 775 22 98, fax. 00421 52 788 14 12, www.fires.sk
Notified Body No. 1396, Approved Body No. SK01, Member of EGOLF
FIRES-RF-028-16-AUNE

1. INTRODUCTION
This test report contains the results of test carried out by FIRES, s.r.o., Testing laboratory in Batizovce,
accredited by SNAS for testing. Certificate of accreditation No.: S-159. The purpose of the test was to gain
information for product classification.

test carried out by Ing. Samuel Skokan

2. MEASURING EQUIPMENT
Identification number Measuring equipment Note
F 90 014 Test chamber SBI
F 80 001 Gas analyser Horiba ENDA 600
F 81 001 System for light transmission measurement
PLC system for control and data acquisition for SBI
F 69 008
TECOMAT NS 950
F 40 012 Application SW SBI for PLC NS 950
F 40 013 Visualizing SW for SBI in Control Web 2000
F 40 014 Driver Tecomat-CW (SW)
F 71 013 Transducer of differential pressure (-50 to + 150) Pa
F 71 014 Transducer of differential pressure (-50 to + 150) Pa
F 54 059 Racking meter 5m
PLC system for control and data acquisition
F 69 009 ambient conditions
TECOMAT TC 604
F 60 001
Temperature and relative air humidity sensors ambient conditions
F 60 012
F 54 027 Digital calliper 0 200 mm
F 57 002 Digital stop-watch
F 08 601 Sheathed thermocouple 2 mm, type K
F 08 401 Sheathed thermocouple 0,5 mm, type K
F 08 402 Sheathed thermocouple 0,5 mm, type K
F 08 403 Sheathed thermocouple 0,5 mm, type K
F 58 006 Coriolis mass flowmeter

3. PREPARATION OF THE SPECIMENS


Testing laboratory noted down production data of specimens from certified production.
Test specimen data are listed in following table:
Place of production World Mech' Tech' Co., Ltd., 8-105, Jangjae-ro 520 beon-gil,
Saengnim-myeon, Gimhae-si, Gyeongsangnam-do,
Republic of Korea
Production number 04-0282 KS F 4737 F/R ALCOTOP AT-211 82 2015.11.26 09:34
Date of production 26. 11. 2015
Date of check out 26. 11. 2015
Number of certificate ISO 9001:2008 2003-113-4
Issuing Body Korea Institute of Construction Materials - Quality Assurance
Date of issuing 27. 07. 2015
Specimens were delivered to the testing laboratory in complete state by test sponsor.
Test specimens dimensions (exposed specimens surface) short wing (500 x 1500) mm;
long wing (1000 x 1500) mm.

FIRES 186/S-02/03/2016-E Page: 2/11


FIRES-RF-028-16-AUNE

4. PREPARATION OF THE TESTS


4.1 DESCRIPTION OF THE SPECIMENS STRUCTURE
Test specimens are made of Aluminium Composite Panel, 4 mm thick which consists of following layer:
- aluminium sheet 0,5 mm thick, on both side coated P.V.D.F. coating
(PCS = (7,829 0,110) MJ.kg-1), thickness 25 m;
- fire resistant core based polyethylene with mineral fillers: (Al(OH)3 90 %, PE 5 % and
5 % additives CaO, SiO4, Al2O3 (PCS = (0,632 0,132)MJ.kg-1), with density 1615 kg.m-3,
thickness 3 mm;
- aluminium sheet 0,5 mm thick chromate finished;
Each specimen consists of five parts with edges bent at a right angle towards to substrate. Width of the
folded edge is 24 mm. Edges are reinforced with aluminium profiles attached to panels with aluminium
blind rivets ( 3 x 8) mm.
Dimension of specimens parts: (500 x 1500) mm (width x height);
(230 x 500) mm (width x height);
(230 x 1000) mm (width x height);
(800 x 500) mm (width x height);
(800 x 1000) mm (width x height).
Specimens are mounted on standard non-combustible substrate (acc. to STN EN 13238: 2010 made of
plasterboards of reaction to fire A2-s1, d0, thickness (12 1) mm, bulk density 800 kg/m3) via spacers
(55 x 55 x 40) mm and drywall screws ( 3,5 x 35) mm. Gaps created by joining of specimens parts are
sealed by fire barrier sealant 3M Fire Barrier Sealant CP 25WB+ (latex-based, intumescent sealant)
(manufacturer: 3M Industrial Adhesives and Tape Division, USA).
Back boards were placed in compliance with STN EN 13823: 2003.
Three test specimens were used for the test results.
All the information about technical specifications of used materials, information about their type
designation and their producers were delivered by sponsor and was not subject of the specimens
inspection. Parameters which were checked are quoted in paragraph 4.2 INSPECTION OF SPECIMENS.

4.2 INSPECTION OF SPECIMENS


Specimens inspection was carried out before commencement of tests, which consisted of visual
observation of specimens and verification of specimens size.

4.3 CLIMATIC CONDITIONING OF SPECIMENS


Test specimens were stored in the hall of testing laboratory and were conditioned according to EN 13238:
2010 under the following climatic conditions:
Ambient air temperature [C]
mean 19,6
standard deviation 1,0
Relative air humidity [%]
mean 42,6
standard deviation 3,1
The humidity equilibrium state of test specimens was determined by repetitive balancing of specimens.
The humidity equilibrium state of test specimen was achieved.

FIRES 186/S-02/03/2016-E Page: 3/11


FIRES-RF-028-16-AUNE

5. CARRYING OUT OF THE TESTS


5.1 CONDITIONS OF THE TESTS
Values characterizing environment in the testing room directly before the tests:
Date of the test Relative air humidity [%] Ambient air temperature [C]
04. 03. 2016 38,9 40,0 20,0 20,3

5.2 RESULTS OF THE TESTS


Visual observation of the specimens during the course of the tests:
Darkening of specimens surface, cracking of paint, peeling paint, deformation of panels.
Specimen No. 1
Lateral flame spread:
Occurrence No
Reaching the edge of the test specimen No
Flaming droplets or particles:
Occurrence No
Fallen droplet/particle burning 10 s No
Fallen droplet/particle burning >10 s No

Specimen No. 2
Lateral flame spread:
Occurrence No
Reaching the edge of the test specimen No
Flaming droplets or particles:
Occurrence No
Fallen droplet/particle burning 10 s No
Fallen droplet/particle burning >10 s No

Specimen No. 3
Lateral flame spread:
Occurrence No
Reaching the edge of the test specimen No
Flaming droplets or particles:
Occurrence No
Fallen droplet/particle burning 10 s No
Fallen droplet/particle burning >10 s No

FIRES 186/S-02/03/2016-E Page: 4/11


FIRES-RF-028-16-AUNE

5.3 EVALUATION OF THE TESTS ACC. TO CLAUSE No. 7 OF EN 13501-1 + A1: 2009
SPECIMEN No. 1 2 3 Result*
FIGRA0,2MJ [W/s] 3,1 8,6 3,8 5,2
FIGRA0,4MJ [W/s] 3,1 8,6 3,8 5,2
THR600s [MJ] 0,6 1,1 0,9 0,9
SMOGRA [m2/s2] 1,6 1,3 1,1 1,3
TSP600s [m2] 32,9 31,2 25,8 30,0
LFS<specimen edge yes yes yes yes
Flaming droplets/particles no no no no
* Final value evaluated acc. to rules of clause No. 7 of EN 13501-1 + A1: 2009.
Graphs of the average heat release rate HRRav (t), total heat release THR (t), 1000 x HRRav (t) / (t-300),
SPRav (t), TSP (t) and 10 000 x SPRav (t) / (t-300) in time period 0 t 1500 s are listed in pages 6 and 7
of the report.

FIRES 186/S-02/03/2016-E Page: 5/11


FIRES-RF-028-16-AUNE

Graphs HRRav (t), THR (t), 1000 x HRRav(t) / (t-300)

4,0

3,5

3,0
HRRav(t) [kW]

2,5

2,0

1,5

1,0

0,5

0,0
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500

Specimen No. 1 Specimen No. 2 Specimen No. 3 time [s]

3,0

2,5

2,0
THR (t) [MJ]

1,5

1,0

0,5

0,0
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500

Specimen No. 1 Specimen No. 2 Specimen No. 3 time [s]

30
1000 x HRRav (t) [kW] / (t-300)

25

20

15

10

0
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500

Specimen No. 1 Specimen No. 2 Specimen No. 3 time [s]

FIRES 186/S-16/11/2015-E Page: 6/11


FIRES-RF-028-16-AUNE

Graphs SPRav (t), TSP (t), 10 000 x SPRav (t) / (t-300)

0,16

0,14

0,12
SPRav (t) [m2/s]

0,10

0,08

0,06

0,04

0,02

0,00
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500

Specimen No. 1 Specimen No. 2 Specimen No. 3 time [s]

120

100

80
TSP(t) [m2]

60

40

20

0
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500

Specimen No. 1 Specimen No. 2 Specimen No. 3 time [s]

7
10000 x SPRav [m2/s] / (t-300)

0
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500

Specimen No. 1 Specimen No. 2 Specimen No. 3


time [s]

FIRES 186/S-02/03/2016-E Page: 7/11


FIRES-RF-028-16-AUNE

PHOTOS TAKEN DURING THE COURSE OF THE TEST


Specimen No. 1

Before commencement of test 500th second of the test

900th second of the test After termination of test

FIRES 186/S-02/03/2016-E Page: 8/11


FIRES-RF-028-16-AUNE

PHOTOS TAKEN DURING THE COURSE OF THE TEST


Specimen No. 2

Before commencement of test 500th second of the test

900th second of the test After termination of test

FIRES 186/S-02/03/2016-E Page: 9/11


FIRES-RF-028-16-AUNE

PHOTOS TAKEN DURING THE COURSE OF THE TEST


Specimen No. 3

Before commencement of test 500th second of the test

900th second of the test After termination of test

FIRES 186/S-02/03/2016-E Page: 10/11


FIRES-RF-028-16-AUNE

6. FINAL PROVISION

The test results refer only to the tested subjects. This test report is not an approval of the tested product by
the test laboratory or the accreditation body overseeing the laboratorys activities. The tests were carried
out on testing equipment that is the property of FIRES Ltd. Without the written permission of the test
laboratory this test report may be copied and/or distributed only as the whole. Any modifications of the test
report can be made only by the fire resistance test laboratory FIRES Ltd. Batizovce.
The tests results relate to the behaviour of the test specimens of a product under the particular conditions
of the tests; they are not intended to be the sole criterion for assessing the potential fire hazard of the
product in use.

Approved by: Prepared by:

Ing. tefan Rstock Ing. Samuel Skokan


leader of the testing laboratory technician of the testing laboratory

7. NORMATIVE REFERENCES

EN 13823+A1: 2015 Reaction to fire tests for building products - Building products excluding
floorings exposed to the thermal attack by a single burning item
EN 13238: 2010 Reaction to fire tests for building products - Conditioning procedures and
general rules for selection of substrates
EN 13501-1+ A1: 2009 Fire classification of construction products and building elements. Part 1:
Classification using test data from reaction to fire tests

THE END OF THE TEST REPORT

FIRES 186/S-02/03/2016-E Page: 11/11