PC 7
OBJECTIVES
KEYWORDS
Air flow, Ziegler Nichols Tuning, Air Flow control
2.1 Objective:
To measure the flow rate of a gas and to obtain the mass flow rate using pressure and
temperature correction.
2.2 Introduction:
The most common method of flow measurement is by using an orifice meter. The
differential pressure across the orifice meter is related to the volumetric flow rate. In the case
of a gas, density is related to pressure and temperature. Hence the mass flow rate can be
determined from the volumetric flow rate given by the orifice meter.
2.3 Theory:
35
EKC 493 Chemical Engineering Laboratory III
where
Q = Volumetric flowrate at temperature t10C and pressure P1 psia.
Cv = Orifice coefficient.
273 P
Q STP = Q 1 (2)
(273 + t 1 ) 14.7
The density at Standard Temperature and pressure can be derived from the ideal gas law.
m
PV = RT
M
m 14.7 x M
Therefore = = (3)
V R x 273
where = density
m = mass of gas
M = molecular weight
R = gas constant
P1 M 273
W = Q STP = C v P (4)
(273 + t 1 ) R 14.7
P1
= K P
(273 + t 1 )
The constants are given by
Cv
= 0.1513
K = 2.1218
36
EKC 493 Chemical Engineering Laboratory III
2.5 Procedures:
1. Set the air supply pressure at 3 bars with valve V1 shut. Release the valve to supply
air to the pressure tank T91.
2. Adjust the air flow rate by setting MV (manipulated variable) at 20% (refers to valve
opening).
3. Read the variables (I/O data) in the controller register as shown below.
X2 Temperature, % of 2000C
X3 Pressure, % of 60 psia.
4. Repeat the experiment at other flow rates by changing the MV to 30, 40, 50, 60, 70,
80, 90, 100%.
37
EKC 493 Chemical Engineering Laboratory III
Objectives:
Introduction:
It is necessary to control the flow of gases into process units to avoid buildup of pressure,
maintaining a certain concentration in the vessel, etc. Gas flow measurement involves
pressure and temperature compensation. The signal may contain noise and require special
methods.
Experimental Equipment:
The experimental equipment consists of the flow control pilot plant shown in Fig 2. The
following units are used
Rotameter FI 91
Procedures:
Part A: To control a gas flow process with PID controller
1. With FIC91 in the Manual (M) mode, open the control valve FCV91 fully with MV =
0%.
For confirmation, check the control valve stem indicator at FCV91. Note that FCV91
is Air-to-Close(ATC) type.
2. With FIC91 still in Manual mode, adjust its setpoint to about 20kg/hr.
3. Access the PID parameters of FIC91 and set the following first (I) trial PID values:-
38
EKC 493 Chemical Engineering Laboratory III
I
______________
PB = 200%
TI = 6 secs
TD = 0 secs
4. Press the RCD button at the front of the recorder with its swing glass cover opened.
5. Transfer FIC91 to AUTO (A) mode and watch the recorder response until the flow
(Blue pen) is fairly steady. Introduce a pulse disturbance by quickly opening and
shutting fully the by-pass valve around FCV91.
6. Repeat with a second (II) and third (III) set of trial PID values:-
II III
____________ _______________
PB = 150% PB = 100%
TI = 6 secs TI = 6 secs
TD = 0 secs TD = 0 secs
At each change of PID values, upset the process by the following ways:-
o Open and shut the by-pass valve around FCV91 to introduce a pulse
disturbance.
7. Make minor adjustment to PB and TI till there is almost quarter amplitude damping
(QAD) with minimum offset.
8. When the loop is tuned, introduce Derivative control mode. Start with very small TD
of a few seconds. Watch the loop become unstable with increasing TD to say 24 secs
or more. Damp the oscillation by increasing the PB to say 400% or more.
1. Set FIC91 with a setpoint of about 25 kg/hr and with the following PID values.
PB = about 30%
TD = 0 secs (min)
2. With FIC91 still in Manual (M) mode, adjust its output (MV) until the measurement (PV)
is close to the setpoint (SV = 25 kg/hr).
39
EKC 493 Chemical Engineering Laboratory III
5. Repeat the Closed Loop Method as above with a different PB until uniform (constant
amplitude) oscillation is observed.
Note the PB as PB* ultimate. Note that it will not oscillate at the setpoint but
will be based away from the setpoint as the OFFSET, because there is no
Integral control action.
Measure the distance between two adjacent peaks. This is Tn, the natural
period of oscillation in seconds by the conversion,
measured period in mm x 3600
Tn secs =
chart speed eg 500 mm / HR
Tn
PB = 2 x PB*, TI =
1.2
6. Set calculated values of PB, TI and TD into FIC91 and if the oscillation persists increase
the PB until the oscillation is damped out. Test the PID values with another pulse
disturbance. Fine-tune the PB and TI values to get as close to QAD as possible.
40
EKC 493 Chemical Engineering Laboratory III
41
EKC 493 Chemical Engineering Laboratory III
42