Académique Documents
Professionnel Documents
Culture Documents
LAYOUT pg. no
1. INTRODUCTION [SUB STATION] -1
2. BUS BARS -4
3. ISOLATORS -7
4. PROTECTIVE RELAYS -11
5. CIRCUIT BREAKERS -16
6. POWER TRANSFORMER -25
7. CURRENT TRANSFORMER -31
8. CAPACITIVE VOLTAGE TRANSFORMERS -33
9. TRASNFORMER OIL AND ITS TESTING -36
10. LIGHTENING ARRESTORS -38
11. CONTROL ROOM -41
12. EARTHING OF THE SYSTEM -44
13. POWER LINE CARRIER COMMUNICATION -46
14. CORONA -47
CONCLUSION
REFERENCES
1. TIE FEEDERS.
2. RADIAL FEEDERS.
TIE FEEDERS:
There are 220KV tie feeders as follows.
1.220 KV KOTA-JAIPUR 1st & 2nd
2. Inter state 220KV KOTA DELHI
3. Tie from 220 KV Heerapura.
4. 220KV KTPS first & second.
RADIAL FEEDERS
BUS BARS
If the bus bars are of rigid type (Aluminum types) the structure heights are low
and minimum clearance is required. While in case of strain type of bus bars
suitable ACSR conductors are strung / tensioned by tension insulator discs
according to system voltages. In the widely used strain type bus bars stringing
tension is about 500 - 900 kg depending upon the size of conductor used.
Here proper clearance would be achieved only if require tension is achieved. Loose
bus bars would effect the clearances when it swings while over tensioning may
damage insulators. Clamps or even effect the supporting structures in low
temperature conditions.
The clamping should be proper, as loose clamp would spark under in full load
condition damaging the bus bars itself.
DOUBLE BUS BAR CONTAINING MAIN BUS I WITH MAIN BUS II:
This arrangement has been quite frequently adopted where the loads and continuity
of supply is necessary. In such a scheme a bus coupler breaker is mostly provided
as it enables on load change over from one bus bar to other.
The normal bus selection isolators cannot be used for breaking load currents. The
arrangement does not permit breaker maintenance without causing stoppage of
supply.
fig 2
INSULATORS
The insulators for the overhead lines provide insulation to the power conductors
from the ground so that currents from conductors do not flow to earth through
supports. The insulators are connected to the cross arm of supporting structure and
the power conductors passes through the clamp of the insulator. The insulators
provide necessary insulation between line conductors and supports and thus
prevent any leakage current from conductors to earth. In general, the insulators
should have the following desirable properties:
1. High mechanical strength in order to withstand conductor load, wind load
etc.
2. High electrical resistance of insulator material in order to avoid leakage
currents to earth.
3. High relative permittivity of insulator material in order that dielectric
strength is high.
4. The insulator material should be non porous, free from impurities and cracks
otherwise the permitivity will be lowered.
5. High ratio of puncture strength to flash over.
These insulators are generally made of glazed porcelain or toughened glass. Poly
come type insulators [solid core] are also being supplied in place of hast insulators
if available indigenously. The design of the insulator is such that the stress due to
contraction and expansion in any part of the insulator does not lead to any defect. It
TYPES OF INSULATORS:
1. Pin type- pin type insulator consists of a single or multiple shells adapted
to be mounted on a spindle to be fixed to the cross arm of the supporting
structure.
When the upper most shell is wet due to rain the lower shells are dry and
provide sufficient leakage resistance. These are used for transmission and
distribution of electric power at voltage up to voltage 33KV. Beyond
operating voltage of 33KV the pin type insulators thus become too bulky
and hence uneconomical.
Fig 3.1
2. Suspension type- suspension type insulators consist of a number of
porcelain disc connected in series by metal links in the form of a string.
Fig 3.2
3. Strain insulator- the strain insulators are exactly identical in shape with
the suspension insulators. These strings are placed in the horizontal plane
rather than the vertical plane. These insulators are used where line is
subjected to greater tension. For low voltage lines (<11kV) shackle
insulators are used as strain insulator.
PROTECTIVE RELAYS
A Protective relay is a device that detects the fault and initiates the operation of the
circuit breaker to isolate the defective element from the rest of the system.
The relays detect the abnormal condition in the electrical circuits by constantly
measuring the electrical quantities i.e. voltage, current, frequency, phase angle
which are different under normal and fault conditions. Having detected the fault,
the relay operates to close the trip circuit of the breaker, which results in opening
of the breaker and disconnection of the faulty circuit.
When a short circuit occurs at point F on the transmission line the current
increases to enormous value. This results in a heavy current flow through the relay
coil, causing the relay to operate by closing its contacts. This in turn closes the trip
circuit of the breaker, making the C.B. open and isolating the family section from
the rest of the system. In this way, the relay ensures the safety of the circuit
equipment
from damage and normal working of the healthy portion of the system.
1.) Selectivity
2.) Speed
3.) Sensitivity
4.) Reliability
5.) Simplicity
6.) Economy
DIFFERENTIAL RELAYS
BUCHHOLZ RELAY
CONSTRUCTION
It takes the form of a domed vessel pipe between the main tank and the
OPERATION
gets entrapped in the upper part of the relay chamber. when a pre determined
amount of gas gets accumulated, it exerts sufficient pressure on the float to
cause it tilt and close the contacts of the mercury switch attached tom it.
This completes the alarm circuits to to sound an alarm.
(ii)If a serious fault occurs in the transformer, enormous amount of gas
is generated in the main tank. The oil in the main tank rushes to the
conservator via the Buchholz relay and in doing so tilts the flap to close
the contacts of the mercury switch. This completes the trip circuit to open
the circuit breaker controlling the transformer.
ADVANTAGES
DISADVANTAGES
(i) It can only be used with oil immersed transformers equipped with conservator
tanks.
(ii) The device can detect only faults below oil level in the transformer. therefore
separate protection is needed for connecting cables.
CIRCUIT BREAKERS
OPERATING PRINCIPLES
When a short circuit occurs, a heavy current flows through the contacts of the C.B.
before they are opened by the protective system. At the instant when the contacts
begin to separate, the contact area decreases rapidly and large fault current causes
increased current density and hence rise in temperature. The heat produced in the
medium
between contacts is sufficient to ionize the arc or vaporize and ionize the oil. The
ionized air or vapour acts as conductor and an arc is set between the contacts. The
potential difference between the contacts is quite small and is sufficient to maintain
the arc. the arc provides a low resistance path and as a result the current in the
circuit remains uninterrupted so long as the arc persists.
During the arcing period the current flowing between the contacts depends
on the arc resistance. The greater the arc resistance, the smaller the current that
flows between the contacts. The arc resistance depends upon:
They are generally classified on the basis of the medium used for arc elimination
(i) Oil circuit breakers, which employ some insulating oil for arc extinction.
(ii) Air-blast circuit breakers in which high pressure air blast is used for
extinguishing the arc.
(iii) Sulphur hexa fluroide C.B. in which SF6 gas is used for arc extinction.
(iv) Vacuum C.B. in which vacuum is used for arc extinction.
In such breakers, sulphur hexaflouride (SF6) gas is used as the arc quenching
medium. The sf6 is an electro-negative gas and has a strong tendency to absorb
free electrons. The SF6 circuit breakers have been found to be very effective for
high power and high voltage service.
CONSTRUCTION
The bushing are also insulated with SF6 the conductor is in the from of
copper tube supported at both end by porcelain shields. SF6 gas is supplied from
the high pressure tanks. Shields are provided with gasket seals to eliminate leakage
of gas from beginnings.
In the closed position of the breaker the contacts remain surrounded by SF6 gas at
a pressure of about 2.8 kg/sq cm. When the breaker operates, the moving contact is
pulled apart and an arc is struck between the contacts. The
movement of the moving contact is synchronised with the opening of a valve
which permits SF6 gas at 14kg/sq cm pressure from the reservoir to the arc
interruption chamber. the high pressure flow of SF6 rapidly absorbs the free
electrons in the arc path to form immobile negative ions which are ineffective as
charge carriers. The result is that the medium between the contacts quickly builds
up high dielectric strength and causes the extinction of the arc. After
the breaker operation the valve is closed by the action of a set of springs.
1. Due to the superior arc quenching property of SF6, such circuit breakers
have very short arching time.
2. Since the dielectric strength of SF6 gas is 2 to 3 times that of air, such
breakers can interrupt much larger currents.
3. The SF6 circuit breakers gives noiseless operation due to its closed gas
circuit and no exhaust to the atmosphere unlike the air blast circuit breaker.
4. The closest gas enclosure keeps the interior dry so that there is no moisture
problem.
5. There is on risk of fire in such breakers because SF6 gas is not inflammable.
There are no carbon deposits so that tracking and insulation problems are
eliminated.
6. The SF6 breakers have low maintenance cost, light foundation requirement
and minimum auxiliary equipment.
7. Since SF6 breakers are totally enclosed and sealed from atmosphere they are
particularly suitable where explosion hazard exists e.g., coal mines.
APPLICATIONS
SF6 C.B. have been developed for voltages 115 KV to 230 KV, power ratings 10
MVA to 20 MVA and interrupting time less than 3 cycles.
The transformer is a static apparatus, which receives power/energy at it, one circuit
and transmits it to other circuit without changing the frequency. With this basic
conception we can use the voltages at our desired level while utilizing the power.
As, the voltage used to generate at modern power houses at 11 KV or so and
afterwards we get it step up at a level of 33 KV, 66 KV, 132 V, 220 KV or 400 KV,
750 KV for transmission to minimize the distribution losses. Again we get it step
down with the help of transformer to use at our wishes at 11 KV, 6.6 KV or even
415, 230 volts at our houses.
Fig 6.1
DESCRIPTION OF PLANT:
Fig 6.2
RATING DATAS.
VOLTS
HV: 400 KV
IV: 220 KV
LV: 33 KV
LINE AMPERES
HV: 273 / 364 / 455
IV: 497 / 662 / 828
LV: 1104 / 1471 /1839
IMPEDANCE VOLTAGE
HV to IV 12.65% on 315 MVA Base
HV to LV 39.16 % on 315MVA Base
IV to LV 26.66 % on 315 MVA Base
NUMBER OF PHASES
Three HV, LV, IV
FREQUENCY IN Hz
50 Hz
COOLING FANS:
PUMPS:
Rating: 1818 liters per minute.
Type: a landless A to 8c sentiment.
Number of pump per transformer: one working, one standby.
Pump motor: direct on line starts weather proof.
Squirrel cage IM
These transformers are used with low range ammeter to measure currents in high
voltage alternating current circuits where it is not practicable to connect
instruments and meters directly to lines. In addition to insulating the instrument
from the high voltage line, they step down the current in the known ratio. The
current (or series) transformers has a primary coil of 1 or more turns of thick wires
connected in series with the line whose current is to be measured. The secondary
consist of a large number of turns of fine wire and is connected across the ammeter
terminals (usually of 5 amp bracket should be removed or 1 amp range)
POTENTIAL TRANSFORMER
These transformers are extremely accurate ratio step down transformers and are
used in conjunction with standard low range voltmeter (usually 150 volt) whose
deflection when divided by voltage transformation ratio, gives the true voltage on
the high voltage side. In general, they are of the shell type and do not differ much
from the ordinary two winding transformer, except that their power rating is
extremely small. Up to voltage of 5000 potential transformers are usually of dry
type, between 5000 and 13800 volts, they may be either dry type or oil immersed
type, although for voltage above 13800 they are oil type. Since their secondary
windings are required to operate instruments or relays or pilot lights, their ratings
are usually 42 to 100 watts.
DESCRIPTION:
Fig 8
APPLICATION:
RATING OF CVT
Voltage: 22/sqrt 3 KV
Total o/p:500MVA
Operating voltage: 400/sqrt 3 max.
Voltage factor: 1.5/30 sec.
Test voltage: 630 KV for 1 min
Impulse withstands voltage: 1.2/ 50 s. 1425KV max.
Frequency : 50Hz
High frequency capacitance: 4400pF
Primary capacitance: 4657pF
Secondary capacitance: 80000 pF
The prime function of oil is to convey the heat from the core and winding to the
tank where it can be dissipated. Besides these, the oil provides additional insulation
between primary and secondary windings. So, the oil must be completely free from
dirt, moisture and other un-wanted solid matter. The oil used in the transformer is
natural mineral oil and should undergo the following tests if required:
BREAKDOWN VOLTAGE:
The voltage at which the oil breaks down when subjected to an electric field.
FLASH POINT:
The temperature, at which the oil gives off so many vapors, when mixed with air
forms an ignitable mixture and gives a momentary flash with small pilot flame.
An electric discharge between cloud and earth, between cloud and the charge
centers of the same cloud is known as lightening.
The earthing screens and the ground wires can well protect the electrical system
against direct lightening strokes but they fail to provide protection against
travelling waves which may reach the terminal apparatus. The lightening arrestors
or the surge diverters provide protections against such surges.
THYRITE TYPE:
Ground wire run over the tower provides an adequate protection
against lighting and reduce the induced electrostatic or electromagnetic voltage but
such a shield is inadequate to protect any traveling wave, which reaches the
terminal of the electrical equipment, and such wave can cause the following
damage.
Lightening arrestors are provided between the line and earth provided the
protection against traveling wave surge the thyrite lightening arrestor are provided
at GSS. This type of LA has a basic cell made of thirties, which is a particular type
of clay, mixed with carborendum. Thirties has a particular property of being
insulator one voltage
At high voltage It will behave like a conducting material the electrical resistance of
thyrite depends upon the voltage each time the voltage is made twice the resistance
decrease in such a manner as to allow an increased current of 12.5 times the
change in current is independent of rate of application voltage and its instantaneous
value.
The above law is followed by this material without any limit on the voltage
increase and after the surge has passed the thyrite againretain its original property
A standard cell is rated for 1KV and is formed into a disc, which is sprayed on both
the sides of to give good contact with each disc. The dimensions of the discs are
stacked i.e. 16 cm in diameter and 17.5 cm thick these discs are stacked one upon
each other and they are further placed in to a porcelien container with a suitable
arrangement of gap between them.
COLOUR CODING
* 33KV GREEN
* 132 KV BLACK
* 220KV BROWN
* 440 VOLTS VOILET/INDIGO
* 110 VOLTS ORANGE
REACTOR
It is used to lower the over excited capacitor. Capacitor bank is connected in shunt
over the reactor. Capacitors main purpose is to boost up the voltage. so when we
want to lower the voltage we use reactors. it is also use to stop the sudden change.
the commonly used reactor is NGR(Neutral ground reactor).
BUS COUPLERS
It is used to equalize the load on both Bus bars.
DISTURBANCE RECORDER
It records the distance & fault on graph with voltage w.r.t time.
EVENT LOGGER
it monitors as well as provides the details as a printed material.
These details may contain the sequence of operation, switching time, closing time
etc.
Fig 11
NO LOAD TAP CHANGER (NLTC)
in this we change the tap manually for which we have to shut down the
transformer.
When the load increases the voltage across the primary drops but the secondary
voltage can be kept at the previous value by placing the movable arm on to a
higher stud. Whenever a tapping is to be changed in this type of transformer, the
load is kept off and hence the name off load tap-changing transformer.
SYNCHRONOSCOPE
CORONA EFFECT
The phenomenon of violet glow, hissing noise and production of ozone gas
in an overhead transmission line is known as corona.
Corona has many advantages and disadvantages. In the correct design of a high
voltage overhead line, a balance should be struck between the advantages and
disadvantages.
Advantages
1. Due to corona formation, the air surrounding the conductor becomes
conducting and hence virtual diameter of the conductor is increased. The
increased diameter reduces the electro-static stresses between the
conductors.
2. Corona reduces the effect of the transients produced by surges.
Disadvantages
A technician needs to have not just theoretical but practical as well and so
every student is supposed to undergo a practical training session after III year
where I have imbibed the knowledge about transmission, distribution, generation
and maintenance with economical issues related to it.
During our 30 days training session we were acquainted with the repairing of
the transformers and also the testing of oil which is a major component of
transformer.
At last I would like to say that practical training taken at 220KV GSS has
broadened my knowledge and has widened my thinking as a professional.
REPORT BY-
Kapil Kumar
SKIT,JAIPUR