TECHNICAL HANDBOOK

TABLE OF CONTENTS

INTRODUCTION
4.5 Open Web Steel Joists 44
Chapter Page
4.6 Hangar Door System 47
1.1 Introduction 1
4.7 Special Canopies 48
1.2 Drawings, Calculations & 2
4.8 Special Fascias 49
Company Profile
4.9 Built-up Roofs 50
1.3 Definition of Terms 4
4.10 Roof Monitor 52
4.11 Curved Built-up Members 53
SPECIFICATIONS 4.12 Secondary Members 54

2.1. General 16
2.2. Design 17 ENGINEERING DATA
2.3 Structural Framing 17
2.4 Roof and Wall Covering 18 5.1 Purlin & Girt 55
2.5 Accessories 20 200 Z 250 Z Section Properties
2.6 Sandwich Panel 24 5.2 Eave Strut - 0.5:10 & 1:10 56
Slope Section Properties
5.3 Cold Formed C Sections
STANDARD STRUCTURAL Section Properties 57
5.4 Base & Cap Channel 58
SYSTEMS Section Properties
5.5 Kirby Roof & Liner Sheeting ( KR) 59
3.1 Standard Frames 27
Section Properties & Load Tables (Steel)
3.2 Standard Loadings 28
5.6 Kirby Roof & Liner Sheeting ( KR) 60
3.3 Standard Buildings 30
Section Properties & Load
3.4 Standard Cable Bracing System 31
Tables(Aluminum)
3.5 Portal Frame Bracing System 32
5. 7 Kirby Wall Sheeting ( KW) 61
3.6 Knee Bracing System 32
Section Properties & Load Tables
3.7 Diaphragm Bracing System 33
(Steel)
3.8 Standard Eave Canopy 34
5.8 Kirby Wall Sheeting ( KW) 62
3.9 Standard Fascia 34
Section Properties & Load Tables
3.10 Standard Expansion Joint 35
(Aluminum)
3.11 Standard Endwall Systems 36
5.9 Kirby Decking ( KD), Light Decking 63
3.12 Standard Wind Column Spacing 37
Section Properties & Load Tables
3.13 Standard Wind Column Spacing 38
5.10 Kirby Insulated Sandwich Panels 65
with Mezzanine
Roof, Wall & Partition Panels
3.14 Standard Anchor Bolts Details 39
5.11 KRIP Sandwich Panel Data Sheet 66
5.12 KWIP Sandwich Panel Data Sheet 67
SPECIAL STRUCTURAL & PEB 5.13 KCIP Sandwich Panel Data Sheet 68
PRE-ENGINEERED BUILDING 5.14 Concealed Fastener Panels
5.15 Concealed Fastener Single Skin
69

SYSTEMS Cladding 70
5.16 Concealed Fastener Insulated
4.1 Rigid Frames with Overhead Cranes 40 Cladding Type KCIP 71
4.2 Multi-span Frames & Trusses 41 5.17 Concealed Fastener Insulated
4.3 Multi-storey Buildings 42 Panel Cladding 72
4.4 Mezzanine Flooring System 43 5.18 Fiber Glass Insulated Panels 73
5.19 Fiber Glass Insulated Panel 74 6.14 Kirby "M" Liner 115
6.15 Kirby "M" Partition 116
5.20 Self-Drilling Screw 76 6.16 Light Partitions 117
5.21 Cable Bracing 77 6.17 False Ceiling 118
5.22 ASTM A36 Anchor Bolts 78
5.23 ASTM A325 High Strength Bolts 79
5.24 Standard Crane System 80 INSTALLATION DETAILS
5.25 Standard Crane System Type K 81
5.26 Standard Crane System 7.1 Endwall Details 119
Type K Hoist Details 82 7.2 Purlins, Girts & Eave Strut
5.27 Standard Crane System Connections 129
Type K End Carriage Detail 83 7.3 Bracing Details 133
5.28 Standard Crane System 7.4 Expansion Joint Details 135
Type K Load Spectrum 84 7.5 Canopy & Lean-to Connections 137
5.29 Service Loads 7.6 Fascia Details 141
Hanging Details & Allowable Loads 85 7.7 Mansard Details 144
5.30 Ventilation Calculation 86 7.8 Roof Framed Opening Details 148
5.31 Ventilation Calculation Nomograph 87 7.9 Walk Door Details 150
5.32 Kirby Insulation ( KIB-12 ) 88 7.10 Slide Door Details 152
5.33 Roof Lighting Requirements 89 7.11 Sliding Folding Door Details 156
5.34 Roof Drainage Calculations 90 7.12 Roll-up Door Details 160
5.35 Fire Protection System 91 7.13 Hangar Door Details 164
5.36 Building Material Weights 92 7.14 Crane System Details 168
5.37 Conversion Factors 93 7.15 Mezzanine Details 171
5.38 Aircraft Dimensions 94 7.16 Roof & Wall Panel Details 175
7.17 Roof & Wall Liner Details 185
7.18 Insulation Details 191
ACCESSORIES 7.19 "KR" False Ceiling Details 193
7.20 Partition Details 194
6.1 Walk Doors 96 7.21 Ridge Ventilator Details 198
6.2 Sliding Doors 97 7.22 Roof Curb & Jack Details 199
6.3 Roll up Doors 100 7.23 Window & Louver Details 201
6.4 Insulation 103 7.24 Roof Sandwich Panel Details 204
6.5 Roof Curb 104 7.25 Standard Buildings 206
6.6 Roof Jack 105 (Continuation from Chapter 3.3)
6.7 Window 106
6.8 Louvers 107
a. Louver 107
b.Sand Trap Louver 108
6.9 Translucent Panels 109
6.10 Ventilators 111
a. Ridge Ventilators
b. Powered Ventilators
6.11 Gutters, Flashings & Trims 112
6.12 Gutters & Downspouts 113
6.13 Valley Gutter & Downspouts 114
INTRODUCTION
1.1 INTRODUCTION

The purpose of the Kirby Technical Handbook Dimensions and units used in this manual are
is to assist the building designer or potential in accordance with SI-the International System
metal building owner in the proper and of Units. Where applicable, the unit now in
economical use of the pre-engineered buildings common use is also shown for reference.
( PEB ) and structural steel systems.
It is further intended that building officials, This manual is the property of Kirby Building
architects, designers, consultants and engineers Systems and will be revised periodically as
will refer to and apply the data in this manual changes are innovated. Architectural, structural
when considering approval of Kirby buildings. and mechanical adaptations shown in this
manual are intended to be typical only and
Kirby buildings are designed by professional Kirby therefore accepts no responsibility unless
engineers and this manual was prepared under specifically agreed in writing.
their direct supervision.

1
1.2 DRAWINGS,
CALCULATIONS &
COMPANY PROFILE
Prices for all buildings include one set of Company profile:
printed building installation drawings, shipper
and one building installation procedure
Kirby Building Systems is the pioneer
manual sent with shipment and four sets of
manufacturer of steel buildings and
building installation drawings issued to the
structures in GCC, Middle East, Eastern
client via the sales office prior to the time of
Europe & CIS, Africa, Indian Sub-Continent
shipment.
and South East Asia. In operation since
If required, two sets of standard computer 1976, Kirby maintains a strong reputation
calculations for main frame cross section, and for providing cost effective solutions for
load tables for purlins, girts, and covering will buildings manufactured to the highest quality
be furnished upon request. If calculations are standards. Quality for KIRBY epitomizes
required, under no circumstances will Kirby a combination of speed of construction,
begin fabrication until one set is returned safety of the structure, sustainability against
approved, unless approval is waived in writing natural and man-made disasters, suitability to
by the client. In lieu of calculations, a Letter the purpose, unmatched pre and post sales
of Certification (signed by a Professional service, scalability, and substantial savings in
Engineer) can be furnished at no charge. terms of both time and money.

When requested, four sets of approval Kirbys state of the art manufacturing plants
building installation drawings will be furnished. produce hundreds of custom made steel
No further work will be done by Kirby until buildings each year. Kirby plants are located in
one set of drawings Is returned Approved Mina Abdullah- Kuwait, Ras Al Khaimah- UAE,
or Approved as Noted. Resubmittal of Hyderabad and Haridwar- India. Combined
approval drawings will be only at the request Kirby has a total production capacity of
of the client, otherwise Kirby will incorporate 425,000 MT per year. Kirby has been ISO
the noted amendments in the final building 9001:2008 certified company since 2010.
installation drawing when issued for
In the Middle East and African region, Kirby
construction.
manufactures Pre-Engineered and Structural
Drawings submitted for approval constitute Steel out of two manufacturing locations in
an integral part of the contract between the Ras Al-Khaimah, UAE and Mina Abdullah, Kuwait.
client and Kirby. The contents of the Approval In Southeast Asia, a manufacturing plant in Ho
Building installation drawings are intended Chin Minh City, Vietnam.
specifically for the job at hand; and therefore,
Kirbys sales and distribution network includes
they supersede, in case of contradiction, any
24 offices in the GCC countries (Kuwait, Saudi
other information published for general use.
Arabia- Riyadh, Dammam and Jeddah, Qatar,
Anchor bolt plans will be issued For Oman, Bahrain and Dubai and Abu Dhabi in
Construction after receipt of signed approval the UAE), the Middle East, and Africa.
drawings. Only drawing stamped For
Construction shall he used for setting anchor
bolts and building installation.

2
Kirby has designed, manufactured and The groups major areas of activity are trading
supplied more than 50,000 steel buildings and distribution of consumer electronics,
and established its presence as an industry- food and consumables, automotive vehicles
leading steel structures company. Kirby and products, industrial manufacturing,
delivers customized pre-engineered and steel engineering, technology, travel, shipping
structures to a broad range of customers and transportation services, advertising,
in sectors such as Oil & Gas, Infrastructure, insurance and contracting.
Industry and Commercial building applications.
Furthermore each of Alghanims separate
Kirbys customer base covers thousands of businesses employs operating autonomy
satisfied clients including General Motors, with its own general manager, marketing
AT&T, PepsiCo and Coca Cola, Ministries of managers and finance managers. Corporate
Defense, Oil companies and Petrochemical policy matters remain centrally controlled
projects and other key international and direction is provided through strategic
organizations over the world. business planning processes, quarterly
operating review meetings and long term
Kirby Building Systems is a wholly-owned forecasting.
subsidiary of Alghanim Industries. Alghanim
Industries has consistently maintained its Multinational in both outlook and operation,
position as a leading private sector trading Alghanim Industries has offices in countries
and industrial group both in Kuwait and the that span four continents. The diverse
GCC during the past 60 years. It is a privately nationalities of the employees contribute
owned, professionally managed holding to the companys strength and widen
company. The executive management is its perspective. Alghanim Industries has
composed of professionals with international
successfully fused progressive business
education and experience in varying areas
procedures, local market place requirements
of expertise. Overall, with the companys
and international resources.
wholly owned subsidiaries, joint ventures and
associations, Alghanim Industries employs
over 8,000 people from over 40 different
countries around the world.

3
1.3 DEFINITION OF TERMS

ACCESSORY - BASE CHANNEL -


A building component added to a basic Kirby A light gauge cold formed channel which
structure, such as door, window, ventilator, etc. replaces the base angle when liner panel or
AISI - double sheeted partitions are required.
American Iron and Steel Institute BASE PLATE -
AISC - A plate attached to that portion of a beam or
American Institute of Steel Construction column that rests on the supporting surface,
ALUMINIZED - usually secured with anchor bolts.
Aluminum coated steel BAY (END) -
ANCHOR BOLTS - The distance between first interior frame and
Bolts used to anchor structural members to a inside of endwall panel.
foundation or other support BAY (INTERIOR) -
ANCHOR BOLT DRAWINGS - The distance between center lines of two
Show the size, location and projection of all rigid frames or transverse bents, measured
anchor bolts for the components of the metal parallel to the ridge.
building system, the length and width of the BEAM -
foundation (which may vary from the nominal A structural member usually horizontal
size of the metal building system) and column carrying vertical loads which is ordinarily
reactions(magnitude and direction). The subjected to bending.
maximum base plate dimensions may also be BEAM, CANTILEVER -
shown. A beam supported at one end only and free
APPROVAL DRAWINGS - at the other; such as brackets, canopies,
Include anchor bolt drawing, framing plans, flagpoles.
elevations and sections through the building BEAM, CONTINUOUS -
for approval of the buyer / or his consultant. A beam which has more than two points of
ASSEMBLY - support, (continuous span).
Two or more components welded together. BEAM, SIMPLE -
AUTOMATIC WELDING - A beam simply supported at both ends,
A welding procedure utilizing a machine to theoretically with no rotational end restraint.
make a weld. BEARING FRAME -
AUXILIARY LOADS - Frame made up of beams and columns so
All dynamic live loads required by the contract constructed that joints are not capable of
documents such as cranes and material transferring moment due to lateral
handling systems. loads, usually used at sheeted endwalls of
A. W.S. - a metal building, and when not subject to
American Welding Society auxiliary loads or to further building
AXIAL FORCE - expansion.
A force tending to elongate and shorten a BILL OF MATERIALS -
member. A list of items or components used for
BC- fabrication, shipping, receiving and accounting
Beam and Column building. A single gable, rigid purposes.
frame building with interior columns. BIRD SCREEN -
BASE ANGLE Wire mesh used to prevent birds from entering
A continuos angle secured to foundation to the building through ventilators and louvers.
support wall panel

4
BLIND RIVET- forming a connection. Sometimes called a splice
A small headed pin with expandable shank for plate or bolted end plate.
joining light gauge metal. Typically used to attach BY-FRAMED WALL -
flashing, gutter, etc. A wall framing system where the girts are
BRACE RODS, ANGLES - mounted on the outside of the column.
Braces used in roof and walls to transfer BUTTERFLY CANOPY -
loads, such as wind loads, seismic and crane A free standing, single column supporting roof
longitudinal load to the foundation. structure, having a valley gutter at the centerline
BRACKET - of the building, and the two outer edges of the
A structural support projecting from a wall or roof projecting upwards.
column on which to fasten another structural C SECTION -
member. Examples are canopy brackets, lean-to A member cold formed from steel sheet in the
brackets and crane runway brackets. shape of a block C with or without lips at edge
BRIDGE CRANE - of flanges.
A load lifting system consisting of a hoist which CALORIE -
moves laterally on a beam, girder or bridge which Quantity of heat required to raise the
in turn moves longitudinally on a runway made temperature of one gram of water through 1C (1
of beams and rails. Loads can be moved to any BTU = 252 Calories)
point within a rectangle formed by the CAMBER -
bridge span and runway length. Upward curvature of a beam in the plane of its web
BRIDGING - before loading, to offset an anticipated deflection
Structural members used to give weak axis when load is applied
stability to open web joists. CANOPY -
BRITISH THERMAL UNIT (BTU) - A projecting beam that is supported and restrained at
one end only.
That amount of heat required to raise the
CAPILLARY ACTION -
temperature of one pound (0.454 kg.) of water
That action which causes movement of liquids when
by 1F (0.560C). in contact with two adjacent surfaces such as panel
BUILDER - sidelaps.
A general contractor or sub-contractor CAP PLATE -
responsible for providing and erecting pre- A plate located at the top of a column or end of a
engineered buildings. beam for capping the exposed end of the member.
BUILDING CODE - CAULK -
Regulations established by a recognized agency See sealant.
describing design loads, procedures and CHANNEL- HOT ROLLED -
construction details for structures. A c shaped member formed while in a semi-molten
BUILT-UP ROOFING - state at the steel mill to a shape having standard
A roof covering made up of alternating layers of dimensions and properties.
tar and asphaltic materials (mostly used for flat CLIP -
A plate or angle used to fasten two or more members
roofs).
together.
BUILT-UP SECTION -
CLOSURE STRIP -
A structural member, usually an I section, A resilient strip formed to the contour of ribbed
made from individual flat plates welded together. panels and used to seal around openings created
BUTT PLATE - by metal panels joining other components and at
The end plate of a structural member usually horizontal and vertical corners of a building.
used to rest against a plate of another member in COLD FORMING -

5
The process of using press brakes of rolling mills
to shape steel into desired cross sections at room CURTAIN WALL -
temperature. Perimeter wall panels which carry only their own
COLLATERAL LOAD - weight and wind load.
All additional dead loads required by the contract
DAMPER -
documents other than the weight of the metal
building system such as sprinklers, mechanical and
A baffle used to open or close the throat of
electrical systems and ceilings. ventilators.
COLUMN - DEAD LOAD -
A main member used in a vertical position on a The self weight of the metal building system
building to transfer loads from main roof beams, construction, such as framing, and covering
trusses, or rafters to the foundation members.
COMPONENT - DEFLECTION -
A part of a metal building system. The displacement of a structural member or
COMPRESSION - system under load.
The act of causing material to contract or shorten.
DESIGN LOADS -
CONCENTRATED LOAD -
A load applied on a member at a point or over a very
The loads expressly specified in the contract
short distance. documents which the metal building system is
CONTINUITY - designed to safely resist.
The terminology given to a structural system denoting DIAGONAL BRACING -
the transfer of loads and stresses from member to See Brace Rods
member as if there were no connections. DIAPHRAGM ACTION -
CONTRACT DOCUMENTS - The capacity of a roof, wall, or floor system to
The documents which define the responsibilities resist load in its own plane. (As building roof
of the parties involved in the sale, design, supply and wall systems resisting longitudinal wind load
and building installation ( if any ) of a metal building
without rod bracing).
system. Such documents normally consist of a
contract and specification. Plans may be included.
DOOR GUIDE -
CORNER TRIM - An angle or channel guide used to stabilize or
Preformed sheet metal trim used to close the junction keep plumb a sliding or rolling door during its
of sidewall and endwall sheets. operation.
COVERING - DOWNSPOUT -
The exterior metal roof and wall paneling of a metal A conduit used to carry water from the gutter of
building system. a building.
CRANE - DRIFT PIN -
A machine designed to move material by means of a A tapered pin used during building installation to
hoist.
align holes in steel members to be connected by
CRANE RAIL -
A track supporting and guiding the wheels of a bridge
bolting ( also called spud wrench).
crane or trolley system, and mounted on crane runway EAVE -
beams. The line along the sidewall formed by the
CRANE RUNWAY BEAM - intersection of the planes of the roof and wall.
The member that supports a crane rail and is EAVE GUTTER -
supported by columns or rafters depending on See Gutter.
the type of crane system. On under hung bridge EAVE HEIGHT -
cranes, runway beams also act as crane rail. The vertical dimension from bottom of column
CURB - base plate to top of the eave strut.
A raised edge on a concrete floor slab. EAVE STRUT -

6
A structural member located at the eave of a
building which supports roof and wall paneling. FIELD -
Also member which transmits longitudinal wind The job site, building site or general
forces on endwall from roof brace rods to wall marketing area.
brace rods. FILLER STRIP -
ELASTIC DESIGN - See Closure.
A design concept utilizing the proportional FIXED BASE -
behavior of materials when all stresses are A column base that is designed to resist rotation
limited to specified allowable values of the yield as well as horizontal or vertical movement
stress of the materials. (develops bending moment).
END FRAME - FLANGE -
A frame located at the end wall of a building The projecting portion of a structural member
which supports the loads from a portion of the ( C, I, H shapes ).
end bay. FLANGE BRACING -
END WALL - A bracing member used to provide lateral
An exterior wall which is perpendicular to the support to the compression flange of a beam,
ridge of the building. girder or column.
END WALL COLUMN - FLASHING -
A vertical member located at the end wall of a See Trim.
building which supports the girts. FLUSH FRAMES -
END WALL EXTENSION - A wall framing system where the outside flange
The projection of the roof past the endwall. of the girts and columns are flush.
BUILDING INSTALLATION - FOOTING -
The on-site assembling of fabricated A pad or mat, usually of concrete, located under
components to form a complete structure. a column, wall or other structural member, that
BUILDING INSTALLATION DRAWINGS - is used to distribute the loads from that member
A package of drawings, issued for construction into the supporting soil.
and includes anchor bolt drawings and roof and FOUNDATION -
Wall framing (building installation) plans that The substructure which supports a building or
identify individual components and accessories other structure.
furnished by Kirby in sufficient detail to permit FRAME -
proper building installation of the building. Primary structural members made up of columns,
EXPANSION JOINT - rafters which support secondary framing.
A break or space in construction to allow for FRAMED OPENING -
thermal expansion and contraction of the Jambs, headers and flashing which surround an
materials used in the structure. opening in the wall of a metal building.
FABRICATION - GABLE -
The manufacturing process performed in a The triangular portion of the endwalllocated
plant to convert raw material into finished metal above the elevation of the bottom of eave strut.
building components. The main operations are GABLE ROOF -
cold forming, cutting, punching, welding, cleaning A ridged roof that terminates in gables.
and painting. GAGE -
FASCIA - Distance between holes along transverse axis of
A structural framing member projecting from the plate.
face of a wall for decorative purposes. GAUGE -

7
Numerals referring to thickness of thin sheeting The deep-end portion of a column or rafter
materials. No direct mathematical relation designed to accommodate the higher bending
between gauge number and moments at such point. (Usually occurs at the
thickness; the higher the gauge number, the connection of column and rafter). Also referred
thinner the sheeting material. to as Knee.
GALVANIZED - HAUNCH BRACE -
Steel coated with Zinc for corrosion resistance. A diagonal brace from the intersection of the
GIRDER - column and rafter section of the rigid frame
A main horizontal or near horizontal structural to the eave to prevent lateral buckling of the
member that supports vertical loads. It may haunch.
consist of several pieces. HEADER -
GIRT - The horizontal framing member located at the
A horizontal structural member that is attached top of a framed opening.
to sidewall or endwall columns and supports HEM -
panelling. Edge of trim or flashing turned 180 degrees on
GLAZE OR GLAZING - itself for increased strength.
The process of installing glass in windows and HIGH STRENGTH BOLTS -
doors. Any bolt made from steel having a tensile
GRADE - strength in excess of 100,000 pounds per
The term used when referring to the ground square inch(690 MPa).
elevation around a building. HIGH STRENGTH STEEL -
GRADE BEAM - Structural steel having a yield stress in excess of
A concrete beam around the perimeter of a 36,000 pounds per square inch (250 MPa).
building. HINGED BASE -
GROUT - A column base which is designed to resist
A mixture of cement, sand and water used horizontal and vertical movement but not
to fill cracks and cavities. Sometimes used rotation. Also referred to as pinned base.
under base plates or leveling plates to obtain HIP ROOF -
uniform bearing surfaces. Not normally used in A roof which rises by inclined planes from all four
conjunction with metal building systems. sides of a building. The line where two adjacent
GUSSET PLATE - sloping sides of a roof meet is called the Hip.
A steel plate used to reinforce or connect HOIST -
structural elements. A mechanical lifting device usually attached to a
GUTTER - trolley which travels along a bridge, monorail or
A light gauge metal member at an eave, valley or jib crane. May be chain or electric operated.
parapet designed to carry water from the roof to HOOD -
downspouts or drains. Metal flashing to cover exterior sliding door track
H Section - along the full length of the door header.
A steel member with an H cross section. HOT ROLLED SHAPES -
HAIRPIN - Steel section (angles, channels, S-shapes,
U-shaped reinforcing steel or round bar hooked W-shapes, etc.) which are formed by rolling mills
around anchor bolts and embedded in concrete while the steel is in a semi-molten state.
floor mass, to transfer the horizontal thrust at IMPACT LOAD -
the base of the rigid frames to the concrete floor. A dynamic load resulting from the motion of
HAUNCH - machinery, elevators, crane ways, vehicles, and

8
other similar moving forces. See Auxiliary Loads. Standard corrugated panel used for roof, liner
IMPACT WRENCH - and soffits.
A pneumatic device used to tighten nuts on KIRBY-WALL PANELS -
bolts. Standard corrugated panel used for exterior
INSULATION - surface of walls.
Any material used in building construction to KNEE BRACE -
reduce heat transfer. A diagonal brace designed to resist horizontal
INTERNAL PRESSURE - loads usually from wind or moving equipment
Pressure inside a building which is a function connecting the column to a beam by forming a
of wind velocity and number and location of rigid triangle.
openings. LEAN - TO -
JACK BEAM - A structure such as a shed, having only one
A beam used to support another beam or rafter column and depending upon another structure
or truss and eliminate a column support. for partial support.
JAMB - LEVELING PLATE -
The vertical framing members located at the A steel plate used on top of a foundation or
sides of wall openings. other support on which a structural column can
JIB CRANE - rest.
A cantilevered boom or horizontal beam with LINER PANEL -
hoist and trolley. This lifting machine may pick up A metal panel attached to the inside flange of
loads in all or part of a circle around the column the girts, or the purlin.
to which it is attached. LINTEL -
JIG - A beam: concrete, steel or stone, in masonry
A device used to hold pieces of material in a walls, placed above doors, openings or windows
certain position during fabrication. to support masonry above.
JOIST - LIP -
Open web beam for supporting the floor or roof, A stiffener at the edge of flange of cold formed
made of continuous angular top and bottom members.
chords which are connected with vertical and LIVE LOAD -
diagonal angles. For open web joist, the joist can Any moving or variable load which the structure
be built-up or hot rolled. must support due to the use or occupancy of the
KICK-OUT - building.
An extension attached to the bottom of a LOUVER -
downspout to direct water away from a wall. Also An opening provided with fixed or movable,
referred to as Turn-Out or Elbow. slanted fins to allow flow of air.
KILO-CALORIE (K.CAL) - MAIN MEMBERS -
Quantity of heat required to raise the The main load carrying members of a structural
temperature of one Kilogram of water by 1c. system including columns,end wall posts, rafters
KILOGRAM - and other main support members.
Metric Unit of Mass. ( 1 Kg 2.2 Ibs). MANSARD FASCIA -
KIP - An imperial unit to measure force equal to A tilted fascia projected from the wall and
1000 pounds equivalent to 4.4 kilo newtons. extended above roof line to form as decorative
KIRBY-DECK PANEL - appearance and to hide the roof line.
Standard corrugated panel used for floor deck. MASONRY -
KIRBY-RIB PANEL - Construction materials such as bricks, concrete

9
blocks, ceramic blocks, and concrete. Raised gable or triangular portion of main
MASTIC - building at ridge location to allow lighting or
Material used to seal cracks, joints and laps. ventilation at vertical sides of monitor.
MBMA - MONOLITHIC CONSTRUCTION -
Metal Building Manufacturers Association. A method of pouring concrete grade beam
MBMA CODE OF STANDARD PRACTICES - and floor slab together to form the building
A listing of normal conditions that apply to the foundation without forming and pouring each
sale, design, fabrication and building installation separately.
of a metal building system. MONORAIL -
METAL BUILDING SYSTEM - A single rail support for a material handling
A metal building system consists of a group of system. Normally a standard hot rolled I-Beam.
coordinated components, including structural MPa -
members, exterior covering panels, fastening Mega Pascal
devices and accessories, which have been MULLION -
designed for specific loads, which will work Vertical member connecting two windows
together compatibly and which have been located side by side.
engineered so that they may be mass produced MULTI-SPAN BUILDING -
and assembled in various combinations, or in a Building consisting of more than one gable
combination with various collateral materials, across the width that may or may not have
to provide an enclosed or partially enclosed interior columns within each gable.
structure. NEWTON -
METER - Metric unit of force (1 N = O.2248 Ibf)
Metric unit of length (1 m = 3.28 ft.) PANEL -
MEZZANINE - Gauge metal sheets usually with ribbed
An intermediate floor within a metal building configuration and used for Roof and Wall skins
used for offices or storage, may or may not be PARAPET -
connected to main frame building, and consisting That portion of the wall which extends vertically
of beams, columns, joists, deck and edge angles above the roof line to form a fascia type
to receive reinforced concrete. appearance.
MICRON - PARTITION -
Equivalent to 0.001 Millimeter. An interior dividing wall.
MIL - PASCAL -
Equivalent to 0.001 inch Metric unit of stress or pressure, force per unit
MOMENT - area (N /M2)
The tendency of a force to cause rotation or PEAK -
bending about a point or axis. Force times a The uppermost point of a gable.
distance (Torque). PEAKPANEL -
MOMENT CONNECTION - A Kirby-Rib panel located at the building peak
A connection designed to transfer moment conforming to roof slopes.
as well as axial and shear forces between PEAK SIGN -
connecting members. A sign attached to the peak of the building
MOMENT OF INERTIA - at endwall showing Kirby as the building
A physical property of a member which helps manufacturer.
define strength and deflection characteristics. PERSONNEL DOOR -
MONITOR - A door used by personnel for access to and exit

10
from a building. ROOF SNOW LOAD -
PIECE MARK - The load induced by the weight of snow on the
A number given to each separate part of the roof of the structure.
building for building installation identification. ROPESEAL -
Also called mark number and part number. (See Sealant).
PIER - PRE-ENGINEERED BUILDING -
A concrete structure designed to transfer A building structure that consists of pre-
vertical load from base of column to a footing. engineered, pre-fabricated factory components
PIG SPOUT - that are combined together and
A sheet metal section designed to direct the flow engineered structurally.
of water out through the face of the gutter rather PRE-PAINTED COIL -
than through a downspout. Coil metal which received a paint coating prior to
PILASTER - the forming operation.
A reinforced or enlarged portion of a masonry PRESS BRAKE -
wall to provide support for roof loads or lateral A machine used in cold-forming metal sheet or
loads on the wall. strip into desired cross section.
PINNED BASE - PRESTRESSED CONCRETE -
A column base that is designed to resist Concrete in which the reinforcing cables, wires
horizontal and vertical movement, but not or rods in the concrete are tensioned before
rotation. there is load on the member, holding the
PIN CONNECTION - concrete in compression for greater strength.
A connection designed to transfer the axial and PRISMATIC BEAM -
shear forces between connecting members, but A beam with uniform rectangular cross section.
not moments. PURLIN -
PITCH - A horizontal structural member attached to the
Distance between holes along longitudinal axis of main frames which supports roof panels.
plate. RF -
PLASTIC DESIGN - A single gable rigid frame building.
A design concept based on multiplying the actual RAFTER -
loads by a suitable load factor using the yield The main beam of the frames supporting the
stress as the maximum stress in any member. roof system.
PLASTIC PANELS - RAKE -
See Translucent Light Panels. The intersection of the plane of the roof and the
PONDING - plane of the endwall.
The gathering of water at low or irregular areas RAKEANGLE -
on a roof. Angle fastened to purlins at rake for attachment
POP RIVET - of endwall sheets.
See Blind Rivet. RAKETRIM -
PORTAL FRAME - Sheet metal flashing used to cover the
A rigid frame structure so designed that it offers intersection of the roof and the endwall of a
rigidity and stability in its plane. It is used to building.
resist longitudinal loads where diagonal bracing REACTIONS -
is not permitted. (also Wind Bent). The resisting forces at the column bases of a
POST (END POST) - frame, holding the frame in equilibrium under a
See End Wall Column. given loading condition.

11
REINFORCING STEEL - A tension member used to limit the deflection of
The steel bars placed in concrete to help carry a girt or purlin in the direction of the weak axis.
the tension, compression and shear stresses, as SANDWICH PANEL -
well as temperature stresses. A panel assembly used as covering; consists of
RIDGE - an insulating core material with inner and outer
Highest point on the roof of the building which skins.
describes a horizontal line running the length of SAND TRAP LOUVER -
the building. A type oflouver having fixed C-shaped sections
RIDGE CAP - placed altenatively in a vertical configuration
A transition of the roofing materials along the allowing sand and heavy dust separation.
ridge of a roof. SCREEDING -
RIGID CONNECTION - The process of striking off the excess concrete to
See Moment Connection. bring the top surface of the concrete to proper
RIGID FRAME - finish and elevation.
A structural frame consisting of members joined SEALANT -
together with rigid (or moment) connections so Any material which is used to seal cracks, joints
as to render the frame stable with respect to the or laps.
design loads, without the need for bracing in its SECTION MODULUS -
plane. A physical property of a structural member. It
ROLL-UP DOOR - is used to design and basically describes the
Door that is supported on a shaft or drum and a bending strength of a member.
vertical track. SEISMIC LOAD -
ROOF COVERING - The assumed lateral load acting in any horizontal
The exposed exterior roof skin consisting of direction on a structural system due to the
panels or sheets, action of an earthquake,
ROOF LIVE LOAD - usually a proportion of dead load.
Those loads induced by the use and occupancy SELF DRILLING SCREW -
of the building, not including wind load, seismic A fastener which combines the functions of
load, dead load or snow load. drilling and tapping. It is used for attaching
ROOF OVERHANG - panels to purlins and girts.
A roof extension beyond the endwall or sidewall SELF TAPPIN G SCREW -
of a building. A fastener which taps its own threads in a pre-
ROOF PITCH - drilled hole. It is for attaching panels to purlins
Ratio of rise to total width of a single slope. and girts, for connecting trim, flashing, and panel
ROOF SLOPE - side lap.
The angle that a roof surface makes with the SHEAR -
horizontal. Usually expressed in units of vertical The force tending to make two contacting parts
rise to 10 units of horizontal run. slide upon each other in opposite directions
SS- parallel to their plane of contact.
Single Slope clear span buildings SHEET NOTCH -
SV- A notch or block formed along the outside edge
Space Saver building - a single gable clear span of the foundation to provide support for the wall
with straight columns and flush girts to offer panels and serve as a closure along their bottom
maximum clearances. edge,
SAG ROD, STRAP, OR ANGLE - SHEETING ANGLE -

12
An angle used to support sheeting. support condition for a beam, girt, purlin, etc,
SHIM - which offers no resistance to rotation at the
A piece of steel used to level base plates or supports; opposite to continuous.
square beams. SINGLE SLOPE -
SHIPPER - A slope in one plane. The slope is from one wall
A list that enumerates by part number or to the opposite wall.
describes each piece of material or assembly SINGLE SPAN -
to be shipped. Also called talley sheet or bill of A building or structural member without
materials. intermediate support.
SOLDIER COLUMN - SKYLIGHT -
A column in sidewalls, outside the main frame A translucent panel. A roof accessory to admit
lines, located in extended bays to support light, made of fiber glass reinforced polyester to
sidewall girts framed at top with the profiles of Kirby standard sheeting profiles.
jack beam to adjacent two main frames. SLIDING DOOR -
SHOP PRIMER PAINT - A single or double leaf door which opens on a
The initial coat of primer paint applied in the horizontal track by means of overhead trolleys.
shop. SLIDING FOLDING DOORS -
SHOULDER BOLT - A form of manual sliding doors where-in
A fastener used to attach wall and roof paneling the doors are made of leaves suspended and
to the structural frame. It consists of a large connected in a manner so as to fold
diameter shank and a small diameter stud. The against each other.
shank provides support for the panel rib. SOFFIT -
SHOT PIN - A metal panel which covers the underside of an
A device for fastening items by the utilization of overhang, canopy, or fascia.
a patented device that uses powdered charge to SOIL PRESSURE -
imbed the item in the concrete and/ or steel. The load per unit area a structure will exert
SI - through its foundation on the soil.
The International symbol for the metric unit used SPALL -
by the United States (Le Systeme International A chip or fragment of concrete which has
dUnites). chipped, weathered or otherwise broken from
SIDE LAP FASTENER - the main mass of concrete.
A fastener used to connect panels together at SPAN -
the side lap. The out-to-out of steel lines for building frames,
SIDE WALL - or the distance between supports of beams for
An exterior wall which is parallel to the ridge of secondary members.
the building. SPLICE -
SIDE WALL OVERHANG - A connection in a structural member.
A projection of the roof past the sidewall. STAINLESS STEEL -
SILL - An alloy of steel which contains a high
The bottom horizontal framing member of an percentage of chromium. Also may contain nickel
opening such as a window or door. or copper.
SILL ANGLE - STIFFENER -
See Base Angle A member used to strengthen a plate against
SIMPLE SPAN - lateral or local buckling. Usually a flat bar welded
A term used in structural analysis to describe a perpendicular to the longitudinal axis of the

13
member. expressed as BTU per hour per square foot per
STIFFENER LIP - inch thickness per F.
A short extension of material at an angle to the THERMAL CONDUCTANCE (C) -
flange of cold formed structural members, which The rate of heat flow, in BTUs per hour, through
adds strength to the member. a square foot of material of specified thickness
STILES - whose surfaces have a temperature differential
The vertical side members off ramed and of 1F.
paneled doors. THERMAL RESISTANCE (R) -
STRESS - Resistance to heat flow. The reciprocal of
A measure of the load on a structural member conductance (C).
in terms of force per unit area (kips per sq. in.) THERMAL TRANSMITTANCE (U) -
(MPa) . The rate of heat transmission in unit time
STRUT - through unit area of an assembly of materials
A brace fitted into a framework which resists for unit temperature difference,
axial compression forces. expressed as BTU per hour per square foot
STRUT PURLIN - per F. This is also referred to as the overall
An additional purlin in braced bays located close coefficient of heat transfer.
to the purlin at the intersection of roof brace THROAT -
rods and the frame rafter as required by design. Minimum width of ventilator air inlet.
STUD - THRUST -
A vertical wall member to which exterior or The horizontal component of a reaction
interior covering or collateral material may be TIE -
attached. May be either load bearing or non- A structural member that is loaded in tension
Ioad bearing. TORQUE WRENCH -
SUCTION - A wrench containing an adjustable mechanism
A partial vacuum resulting from wind loads on for measuring and controlling the amount of
a building which cause a load in the outward torque or turning force to be exerted, often used
direction. in tightening nuts and high strength bolts.
TAPERED MEMBER - TRANSLUCENT LIGHT PANELS -
A built-up plate member consisting of flanges Translucent plastic panels used to admit sunlight.
welded to a variable depth web. TRANSVERSE -
TEMPERATURE REINFORCING - The direction perpendicular to the ridge.
Light weight deformed steel rods or wire mesh TRIBUTARY AREA -
placed in concrete to resist possible cracks from The area which contributes load to a specific
thermal expansion or contraction. structural component.
TENSILE STRENGTH - TRIM -
The longitudinal pulling stress a material can The light gauge metal used in the finish of a
bear without tearing apart. building especially around openings and at
THERMAL BLOCK - intersection of surfaces. Often referred to as
A spacer of low thermal conductance material. flashing.
THERMAL CONDUCTIVITY (k) - TRACK -
The rate of heat transmission by conduction A metal guide for moving components; consisting
in unit time through unit area of an infinite of angles or channels, with fastenings, ties, etc.
slab in a direction perpendicular for a crane way, monorail or slide door.
to the surface for unit temperature difference, TRUSS -

14
A structure made up of three or more members, than its own weight.
with each member designed to carry a tension or WALL COVERING -
compression force. The entire structure in turn The exterior wall skin consisting of panels or
acts as a beam. sheets.
TURNOUT - WALL, NON BEARING -
See Kickout . Wall capable of supporting its own weight only.
TURN-OF-THE-NUT METHOD - WEB -
An approved method for pre-tensioning high That portion of a structural member between
strength bolts. The nut is turned from the snug- the flanges.
tight position, corresponding to a few blows of an WEB MEMBER -
impact wrench or the full effort of a man using an A secondary structural member vertical or
ordinary spud wrench, the amount of rotation diagonal interposed between the top and bottom
required being a function of the bolt diameter chords of a truss.
and length. WICKET DOOR -
UNIFORM LOAD - An access door within one leaf of a sliding door.
A load which is evenly spread over a large area of WIND BENT -
a framing system. See Portal Frame.
UPLIFT - WIND COLUMN -
Wind load on a building which causes a load in A vertical member supporting a wall system
the upward direction. (See Suction) designed to withstand horizontal wind loads
VALLEY GUTTER - usually at end walls.
A channel used to carry off water from the V of WIND LOAD -
roofs of multi-gabled buildings. The load caused by the wind blowing from any
VENTILATOR - horizontal direction.
An accessory, usually used on the roof, that Z SECTION -
allows the air to pass through. A member cold formed from steel coil in the
WAINSCOT - shape of a block Z.
Wall material, used in the lower portion of a wall, ZINC-ALUMINIUM COATED -
that is different from the material in the rest of Steel coated with zinc and aluminum for
the wall. corrosion resistance
WALL, BEARING -
Wall capable of supporting a vertical load, other

15
2 : SPECIFICATIONS
2.1 GENERAL

2.1.1 Scope:
building shall consist of single straight columns fixed
2.1.1.1 The standard building scope of supply shall include at base at each frame with a single cantilever roof
the structural framing, metal roofing & siding,bracing, sloping towards the column.
doors, windows. insulation, hardware, fasteners, sealants
and any other component parts for the metal building as 2.1.2.7 Lean-To Buildings: LT( Lean-To). The building
specified or shown on the drawings. shall have a single slope roof and connected on the
high side to the main building on which it depends for
2.1.1.2 All buildings shall have diagonal cable bracing partial support. The roof slope shall be either 1/10 or
in the roof, side walls; common walls between main 0.5/10 matching with the main building roof slope and
building and Lean-tos, between interior columns wall sheeted with flush girts.
under valley lines for multi span type buildings, unless
otherwise stated in KBS offer. 2.1.3 Building nomenclature:
2.1.1.3 In case of discrepancies, the provisions of the
Final Order Acknowledgement Form shall govern 2.1.3.1 The building width and length shall be
unless agreed by Kirby Building Systems in writing. measured from inside to inside of wall covering.
2.1.3.2 The building eave height shall be
2.1.2 Standard building description: measured from bottom of primary frame base
plate to top of the eave strut. The top of the
2.1.2.1 Clear-span, Rigid Frame Buildings: RF ( Rigid eave strut is the point of intersection between
Frame ). The building shall be a single gable, clear the inside surfaces of the wall and roof covering.
span, tapered column. pin base, by-frame girts, 1/10
roof slope, rigid frame type. 2.1.3.3 The bay spacing shall be measured as
follows:
2.1.2.2 Clear-span Spacesaver Buildings: SV (
Spacesaver ). The building shall be a single gable, a. Interior bays from center-line to center-line of
clear span, straight column, pin base, flush framed interior frames.
girts, 0.5/1 0 roof slope, rigid frame type.
b. End bays from inside of Endwall sheets to
2.1.2.3 Beam and Column Buildings: BC ( Beam center-line of first interior frame.
and Column ). The building shall be a single gable,
tapered column, pin base, by-frame girts, 1/10 roof
slope, rigid frame type, supported by intermediate
2.1.4 Drawings & calculations:
columns as shown on drawings.
The following shall be provided free of charge in
2.1.2.4 Clear Span, Single Slope Buildings: SS ( Single 3 sets each after the receipt of the Final Order:
Slope). The buildings shall have a single slope roof
with tapered columns pinned at base and straight 2.1.4.1 Anchor bolt setting plans will be provided by
rafters. The roof slope shall be 0.5/10 and sidewalls Kirby Building Systems or the franchised builder.
sheeted with by-framed girts.
2.1.4.2 Building installation drawings will be
2.1.2.5 T-Canopy Buildings: T-CAN ( T-Canopy ). The provided by Kirby Building Systems
building shall consist of single straight columns fixed
at base at each frame with a double cantilever roof 2.1.4.3 Preliminary drawings, design calculations
sloping towards the center columns. and/ or letter of Certification for the structural
framing and covering panels, signed by a
2.1.2.6 L-Canopy Buildings: L-CAN( L-Canopy). The Professional Engineer, may be submitted for
clients approval upon request.

16
2.2 DESIGN

2.2.1.1 All structural steel sections and welded 2.3.1.2 All framing members shall be cleaned by
plate members shall be designed in accordance power or hand-wire brushing to remove all dirt,
with the applicable sections, relating to design grease, oil, loose mill scale, weld slag, flux deposit
requirements and allowable stresses, of the and other foreign matter, and given one shop
latest edition of the American Institute of Steel coat of red oxide, air drying, phenol modified
Construction Specification for the Design, alkyd resin primer to a nominal dry film thickness
Fabrication and Building installation of the of 25 microns.
Structural Steel for Buildings.
2.3.2 Primary members :
2.2.1.2 All light-gauge, cold formed, structural
members and covering shall be designed in 2.3.2.1 Primary structural framing shall refer to
accordance with the applicable sections, relating the transverse rigid frames, lean-to rafters and
to design requirements and allowable stresses, columns canopy rafters, interior columns (beam
of the latest edition of the American Iron and and column frames), bearing frame rafters and
Steel Institute Specification for the Design of corner columns, and endwall wind columns.
Cold Formed Steel Structural Members. a. Members fabricated from plate or bar stock
shall have flanges and webs joined on one side
2.2.2 Design loads: of the web by a continuous welding process.
This plate or bar stock shall have a minimum
2.2.2.1 The design loads shall be as stated in part I ( yield strength of 345 MPa (50,000 psi) and will
Building description of Kirby Building Systems offer ) conform to the physical specifications of ASTM
A-572 (Grade 50) or equivalent.
2.2.2.2 Loads are applied as follows :
a. Seismic loads shall be applied in accordance to b. Members fabricated by cold forming process
International Building Code ( IBC ) shall have a minimum yield strength of 345 MPa
(50,000 psi) and will conform to the physical
b. Other loads applications :. specifications of ASTM A653 (Galvanised G90)
The minimum loads required in applying on or equivalent.
the structure in order to ensure the safety
c. Members fabricated from hot rolled structural
and serviceability of the building shall be in
shapes shall have a minimum yield strength
accordance to the International building Code
of 250 MPa (36,000 psi) and will conform to
( IBC ) latest edition.
the physical specifications of ASTM A-36 or
2.2.2.3 Basic design load combinations shall be equivalent.
in accordance to IBC latest edition. Other load
combination as applicable per MBMA code. d.Beam and Column interior columns will be
fabricated from tube sections according to
2.3 STRUCTURAL FRAMING ASTM A500 Grade C, which have a minimum
yield strength of 345 MPa (50,000 psi)
2.3.1 General:
2.3.3 Secondary members:
2.3.1.1 All framing members shall be shop
fabricated or bolted field assembly, unless 2.3.3.1 Secondary structural framing shall refer to
otherwise noted on building installation drawing. purlins, girts, eave struts, wind bracing, flange
bracing, base angles, clips and other

17
miscellaneous structural parts. with the applicable sections, relating to design
requirements and allowable stresses, of the
a. Purlins, girts and eave struts shall be cold latest editions of the American Welding Society
formed from steel which has a minimum yield Structural Welding Code.
strength of 345 MPa (50,000 psi) and will
conform to the physical specifications of ASTM
A-653 (Grade 50) or equivalent. 2.4 ROOF AND WALL COVERING
1. Purlins and girts shall be roll formed Z sections, 2.4.1 General:
200 mm deep with 64mm flanges. Each flange
shall have a 16mm stiffening lip formed at 45 to 2.4.1.1 Typical roof, wall and liner panels shall be
the flange. color coated, 26 gauge, galvalume or galvanized
coated steel, ribbed panels. (Other materials and
2. Eave struts are 200mm deep with a 105mm
thickness available upon request).
wide top flange, a 117.5mm wide bottom flange,
both are formed parallel to the roof slope. Each
flange has a 22.5mm stiffener. 2.4.2 Panel materials:

b .Cable bracing shall have a minimum tensile 2.4.2.1 Base material for color coated galvanized
force of 119 kn and will conform to the physical or galvalume substrate steel panels shall have a
specifications of ASTM A475 or equivalent. minimum yield strength of 345 MPa (50,000 psi)
All other miscellaneous secondary members and will conform to the physical specifications of
shall have a minimum yield strength of 250MPa ASTM A-653 or A-792 or equivalent.
(36,000 psi).
2.4.2.2 The zinc coating is a hot dip galvanization
2.3.4 Connections: process conforming to ASTM Specification A653
with a coating class of G-90 (0.90 oz/ft2 or 275
g/m2) or with galvalume coating to ASTM A-792 -
2.3.4.1 All field connections shall be bolted
AZ 150 (150 g/m2) or equivalent.
(unless otherwise noted).
2.4.2.3 The painting shall be baked enamel
a. All primary bolted connections, as shown on
polyester or High Durability ( HD ) polyester
drawings, shall be furnished with high strength
for color sheeting with a film thickness of 25
bolts conforming to the physical specifications
microns. The reverse side shall be white with 10
of ASTM A-325 (or equivalent). All high strength
microns film thickness.
bolts, nuts and washers shall be zinc plated with
a bronze iridite finish for easy identification.
2.4.3 Panel configuration:
b.All secondary bolted connections, as shown
on drawings, shall be furnished with machine 2.4.3.1 Kirby Rib panel shall have 32 mm deep
bolts conforming to the physical specifications of major ribs which taper in width from 11 mm to 40
ASTM A-307 (or equivalent). Machine bolts, nuts mm, and are spaced 333mm on center. Between
and washers will be zinc plated. major ribs are additional minor stiffening ribs
spaced at 111 mm on center. Each panel shall
2.3.4.2 All shop connections shall be welded provide one meter coverage.
using either submerged or shielded arc
process, and welding shall be in accordance 2.4.3.2 Kirby Wall panel shall have 26.4 mm

18
deep major ribs which taper in width from 29 the panel shall be spliced, and endlap shall be 100
mm to 59 mm and are spaced 333mm on center. mm wide (minimum) and occur over a wall girt.
Between the ribs the panel shall be formed into
a sculptured Valley shape. Each panel shall 2.4.6.3 Endwall panels shall be continuous from
provide one meter coverage. the eave to 40 mm below the column base plate,
except where the required panel length would
2.4.3.3 Kirby Deck panel shall have 41 mm exceed 9.0m. For a panel length in excess of
deep major ribs which taper in width from 12 9.0m, the panel shall be spliced and the endlap
mm to 42 mm, and are spaced 164 mm on center. shall be 100mm wide (minimum) and occur over a
Additional minor stiffening ribs are located wall girt. All endwall panels shall be square cut in
between major ribs, at 82 mm on center. Each the factory for 1:10 slope buildings, or bevel cut
panel shall provide 820 mm coverage. in the field for 3:10 slope buildings.

2.4.4 Fasteners: 2.4.6.4 All laps of roof panels shall be sealed


with a continuous ribbon of tape sealer.
2.4.4.1 Standard fasteners shall be No 14, Type 2.4.6.5 Roof panels shall be secured to
A, self-drilling sheet metal screws with metal intermediate framing members with No. 14 sheet
and EPDM washers, which conform to American metal screws at a maximum spacing of 333mm.
Standards Association Specifications. All screws At endlaps, the maximum spacing of screws shall
shall have hex heads. be 111 mm. At four corners of the buildings, panel
to structural fastener spacing shall not exceed 111
2.4.5 Sealer: mm, to an area equivalent to x2. Dimension x is
determined by the following rule:
2.4.5.1 Sealer for sidelaps, endlaps and self-
flashing windows shall be 6 mm wide x 5 A. The smaller of
mm thick, composed of synthetic rubbers,
plasticisers and inert fillers. The sealer shall be (1) 10 % of the least horizontal dimension of the
non-asphaltic, non-shrinking, non drying and non- building (span or length)
toxic and shall have superior adhesion to metals,
(2) 40 % of the eave height.
plastics and painted surfaces at temperatures
from -40C to +90C. B. But not less than

2.4.6 Installation of roof & wall panels: (1) 4% of the least horizontal dimension of the
building
2.4.6.1 Roof panels shall be continuous from
ridge to eave for buildings 18m wide or less, (2) 0.9 meter
where endlaps are required, the width shall
2.4.6.6 Wall panel shall be secured to
be approximately 150 mm (as specified on the
intermediate framing members with No. 14 sheet
drawings), and shall occur over a roof purlin.
metal screws at a maximum spacing of 333mm.
2.4.6.2 Sidewall panels shall be continuous from At endlaps, the maximum spacing of screws shall
the eave to 40 mm below the column base plate, be 166mm.
except where the required panel length would
2.4.6.7 Sidelaps of roof panels shall be stitched
exceed 9.0m. For a panel length in excess of 9.0m,
through the high rib with two, equally spaced,

19
2.5 ACCESSORIES

No. 14 sheet metal screws between supports 2.5.1 Personnel doors:


(screw spacing not to exceed 525 mm). Sidelaps
of wall panels shall be stitched through the low
2.5.1.1 Single swing doors are designated as
rib with one No. 14 sheet metal screw centered
3070M and 3070G. Double Swing doors are
between two supports (screw spacing not to
designated as 6070M and 6070G
exceed 1050 mm).
2.5.1.2 Door leaves shall be 45 mm thick, full
2.4.7 Flashing, trim & closures: flush, fabricated from electro galvanized steel of
0.9 mm nominal thickness (20 gauge) including
2.4.7.1 Flashing and/or trim shall be furnished the base steel and zinc coating. Door shall have a
at the rake, corners, eaves, framed openings, solid core of rigid polyurethane (foamed in place)
and wherever necessary to provide weather to completely fill the inside of door. 3070G and
tightness and finished appearance. Color shall be 6070G doors shall be provided with opening
selected from Kirby Building Systems standard for glass for field glazing (glass and glazing by
colors, with the exception of the corner trim, others).
which matches the building wall color.
2.5.1.3 3070 doors shall be furnished with a
2.4.7.2 Color coated steel for flashing, metal cylindrical lock set which meets or exceed U.S.
closure, trim and other miscellaneous uses shall Federal specification F.F.H. 106a -Series 160A.
be 26 gauge of the same specification as the roof
and walls covering material. 2.5.1.4 6070 doors shall be furnished with a
cylindrical lock set on one leaf and a cylindrical
2.4.7.3 A formed peak panel matching the slope handle set on the other leaf.
and profile of adjoining panels shall be provided
along the building ridge. 2.5.1.5 Inactive leaf of the 6070 door (R.H.
inactive) shall have a fool, head and a chain
2.4.7.4 Solid or closed cell, preformed, E.T.P. bolt supplied loose for field installation, unless
(Ethylene Polypropylene Terpolymer) closures specified otherwise astragal shall be installed on
matching the profile of the panel shall be right hand inactive leaf.
installed along the eave, rake and other locations
specified on Kirby Building Systems drawings. 2.5.1.6 Each door leaf shall swing from three 114
x 114mm galvanized steel, interlocking template
2.4.8 Color finish: butt hinges.

2.5.1.7 Door frame consisting of jambs and


2.4.8.1 Unless specified otherwise, all wall and header is of knock down type for field assembly
roof panels, flashing, trim and other exposed through bolted connections, jambs and header
steel surfaces shall be color coated. are made from cold formed 1.5mm thick 36 KSI
steel 210mm deep.
a. Color of panels and corner trim shall be
selected by the customer from Kirby Building 2.5.1.8 Door leaves and frames shall be shop
Systems standard colors. painted with one coat of vinyl base neutral gray
primer.
b. The gutters, downspouts, rake trim, eave trim and
door flashing shall be white unless otherwise selected 2.5.1.9 The threshold shall be an extruded aluminum
from Kirby Building Systems standard colors. shaped to provide adequate weather seal

20
2.5.2 Sliding doors: locking devices and handles, single slide doors
shall have a retainer at one end.
2.5.2.1 Sliding door shall be constructed from 2.5.2.9 Door framed opening jambs shall be cold
cold formed channel or Zee shaped steel formed shapes. The cold formed members shall
framing, having a minimum yield strength of 345 be given one shop coat of standard primer.
MPa (50,000 PSI). The framing shall be covered
on the outer face with panels as specified for the
wall. The door leaves shall be adequately flashed
2.5.3 Roll-up doors:
and counter flashed. Doors are field assembled
with bolted connections. Roll-Up doors are supplied as buyouts generally
in accordance with the following specifications:
2.5.2.2 Door leaf covering the framed opening
of the door when split into two parts, each part 2.5.3.1 Door curtain shall be color coated 22
sliding in the opposite direction shall be referred gauge galvanized steel having a minimum yield
to as double slide door. strength of 345 MPa (50,000 psi) and will
conform to the physical specifications of ASTM
2.5.2.3 Door leaf covering the framed opening of A653 or equivalent. Class G-90 (0.90 ozjft2
the door with a single leaf sliding in one direction or 275gjm2) or its equivalent. Curtain shall be
shall be referred to as single slide door. constructed of interlocking roll formed slats,
to provide curtain stiffness to withstand wind
2.5.2.4 The door leaves shall be suspended from pressures of 1.25 KNj m2. Alternate slats are to
trolley which is guided on a header assembly. be equipped with endlocks to prevent lateral
The header is cold formed C section, track is movement of the slats. Endlocks are made of
welded to header channel, header assembly is Nylon secured to the slat by Nylon rivets. The
supported at four points by brackets which are bottom of each curtain shall be reinforced by
connected to the building wall framing. Header cold formed steel trims.
assembly is protected by a counter flashed hood.
2.5.3.2 Guides are to be fabricated from 3mm
2.5.2.5 Trolleys are galvanized sheet metal minimum thickness steel having minimum yield
stamping having four wheels on two axel, the strength of 345 MPa (50,000 psi), assembled
axel is supported on nylon (teedelrin) bearings with 10 mm DIA. bolts to the door jambs.
housed in the trolley body. A pivoted bolt with
two nuts is provided at the center of the body 2.5.3.3 Door curtain is secured to spiders which
for suspending the door leaf. is welded to 40 N.B.M.S. pipe, each end of the
pipe is fitted with precision machined shafts to
2.5.2.6 Adequate weather sealing is provided at accept the bearing. Antifriction ball bearings are
center and at ends by neoprene rubber closures provided which are housed in a pillow block or
and strips. flange mounting.

2.5.2.7 Wind reaction and swaying at the bottom 2.5.3.4 Brackets are constructed from steel
is absorbed by V shaped cold formed guide plates of 6mm thick minimum or structural
made of 3.5mm thick 50 KSI steel embedded angles. Holes are prepunched on the bracket
in the concrete foundation through angle guide to install it on the supporting column or door
provided for this purpose. jambs, and to receive the bearing block and the
operator.
2.5.2.8 The doors shall have inside and outside

21
2.5.3.5 Operation: 2.5.4 Windows:
a) Manual Operator: 2.5.4.1 Aluminum windows are specifically
designed for installation with exterior wall panel.
Manually operated by means of endless Windows shall be singleslide
galvanized hand chain. Locking clip shall be
provided for securing the chain. Hand chain (horizontal) self flashing with preglazed clear
wheel is attached to worm reduction gear box, glass and removable half insect screen, complete
the output shaft of the reducer is connected to with latching device, weather stripping.
the door shaft by means of a rigid coupling.
2.5.4.2 Single windows are IM wide x IM high
b) Electric Operator: nominal size, double or multiple windows are
formed by joining the window jamb fins together.
Electric operation is by means of an integral
motor reducer, connected to the door shaft by 2.5.4.3 Windows shall be fitted with 2.4 mm (
a set of sprockets and roller drive chain. The 3/32 )D.S.B clear glass using vinyl glazing beads
unit is mounted on the support brackets. Motor and shall be back bedded
operates on 380- 415 volts, 3 phase 50/60 Hz.
rated for the specific application-with high 2.5.4.4 All structural members shall be
starting torque. Insulation class F or E, type of extruded aluminum with a minimum thickness
motor is T.E.F.C. of 1mm, assembled with screws and sealed
at junctions, and shall meet or exceed the
Primary reduction is by worm and worm wheel American Aluminum Manufacturers Association
with an extended shaft to accept a chain wheel Specification HS-B2.
for emergency manual operation by hand chain.
2.5.4.5 Nylon roller and roller housing is attached
Limit switches shall be provided for upper to each end of sash bottom rail.
and lower limit, mounted on reducer housing,
actuated by rotary gear with adjustable strikers. 2.5.5 Sky light:
Control buttons are set in a rigid box for up and
down door operation, with emergency stop and 2.5.5.1 Sky Light are made of translucent
built in overload cut out. fiberglass reinforced polyester to the profile
of Kirby rib panel called skylight and Kirbywall
Electro-magnetic spring set disc brake is fitted panel called wall light and are available only in
to the motor end, totally enclosed to protect 2.44 Kg/m2 (8 ounces/ft2). Conforming to U.S.
against damage from dust and moisture, manual Commercial Standard CS-214-517.
release attachment (auto reset) for emergency
operation in case of power failure is provided for 2.5.5.2 Each panel has a coverage of 1 meter.
hand chain operation. Standard length for skylight is 3305 mm and for
wall light is 4140mm. Panel shall be of 1.5mm thick.
Brakes are provided for door above 16M2 area
only, the braking is effected on smaller doors by 2.5.5.3 Color of the panel shall be white with
means of self-locking gear box. smooth surface finish with a light transmitting
capacity of 60 % 5%

2.5.5.4 Installation of light panels is similar to that

22
of steel panel, it can be worked with ordinary furnished to ensure weather tightness.
tools and may be drilled, sawed, punched
without damage to panel and are shatter 2.5.7.3 Individual ventilators are furnished with
resistant. one set of Standard accessory package for
damper control. Multiple units are furnished with
2.5.5.5 Light panels have low heat transmission one set of accessory package for two ventilators
acts as insulation. (K factor 1.0 to 1.5; U factor and shall be manually operated pull type.
1.09) and are not affected over a temperature
range of 50F below zero to 200F. (fire 2.5.7.4 Outer shell, damper, rain shield, end
resistance 25 flame spread, test according to UL- cap and skirts shall be fabricated from 26 GA
94 tunnel test). galvanized steel painted white base metal
conforming to ASTM specifications A653 Grade
Panels are corrosion resistant and most 50, G90 or its equivalent.
chemicals do not affect the panels.
2.5.7.5 Skeleton of the ventilator is made of
2.5.6 Eave gutters and down spouts: galvanized sheet metal stamping and cold-
formed members of 1mm thick minimum,
assembled with rivets.
2.5.6.1 Eave gutters shall be box shaped, color
coated, 0.5 mm nominal thickness (26gauge) 2.5.7.6 Ventilators shall be furnished with bird
galvanized steel. The outside face of the gutters screen.
shall be supported with color coated, 0.5 mm
nominal thickness (26 gauge) galvanized straps to
2.5.8 Louvers:
the eave member at a maximum spacing of 1.20 m.

2.5.6.2 Downspouts shall be rectangular shaped, 2.5.8.1 Std Louvers are adjustable with
color coated, 0.5mm nominal thickness (26 overlapping type blades providing maximum
gauge) galvanized steel. Downspouts shall have weather tightness while closed, allowing free air
a 45-degree elbow at the bottom and shall be flow while open. Standard nominal size of louver
supported by attachment to the wall covering at is 1M wide by 1M height, self supporting on K.W.
3.0 m maximum spacing. profile wall panel and self flashing,

2.5.7 Ventilators: 2.5.8.2 Sandtrap Louver

2.5.8.2 Multiple units are formed by joining the


There are 2 types of ventilators supportfins; suitable jamb supports shall be
furnished for multiple unit installation.
1. 300mm throat ( Standard with adjustable damper)
2.5.8.3 Std Louver frames are fabricated from
2. 600mm throat ( KRV-600 with fix type) 1.2mm thick (18 gauge) galvanized steel, and
blades from 0.9mm thick (20 gauge) galvanized
Ventilators shall be supplied in length of 3m
steel, conforming to ASTM specification
shopassembled. Ventilators shall be supplied in
A653 Grade 50 steel,G-90 galvanizing or its
length of 3m shop assembled.
equivalent. Louver shall be painted white.
2.5.7.2 Ventilators are designed specifically to
2.5.8.4 Std Louvers are furnished with crank
fit on top of Kirby rib roof panel, end cap skirt
and levers for the adjustment of blades and the
assembly, closure strips and sealants shall be

23
outside face of louver is fitted with removable manufactured from a self- extinguishing glass
insect screen. fiber reinforced polyester 3 mm thick with 15 mil
polyester gel coated weathering surface on
2.5.9 Insulation:

2.5.9.1 The insulation shall be fiber-glass, blanket exterior. Unit shall be white in color and opaque
type and suitable for application to roofs and to light. Base shall have the same configuration
walls of industrial buildings. The insulation shall as the Kirby rib profile. The top of the curb shall
be made of long and fine fiber-glass evenly provide a level surface at 1.10 roof slope.
distributed and of uniform density bonded with
phenolic thermosetting resins with a vinyl facing 2.5.10.2 Curbs shall be available in sizes of 600 x
resulting in strength, long life and low water 600 mm, 900 x 900 mm and 1200 x 1200 mm.
permeability.
2.5.11 Roof jack:
2.5.9.2 The standard insulation thickness shall be
50mm and 75mm supplied in rolls. The density
of the insulation shall be 10 kg/m3 with a thermal 2.5.11.1 Roof jacks shall be a one-piece
conductivity of 0.31 BTU in/ft2 hr F at a mean construction manufactured from self-
temperature of 77 F. extinguishing fiber glass reinforces polyester
3mm thick with 15 mil polyester gel coated
2.5.9.3 The fire resistance of the facing shall be in weathering surface on exterior. Unit shall be
accordance with the Underwriters Laboratories white in color and opaque to light. Base shall
Test Method UL723, and shall have a fire hazard have the same configuration as Kirby rib profile.
classification for flame spread 15 and smoke
developed 105 2.5.11.2 Roof jacks shall be available in opening
sizes of 50-100 mm and 150-300 mm in jack
2.5.9.4 The vinyl facing shall have a high vapor heights of 365 mm and 290 mm respectively.
barrier efficiency with a low perm rating to
prevent condensation. 2.6 SANDWICH PANEL
2.5.9.5 The insulation material shall neither POLYURETHANE
promote nor accelerate corrosion on steel. The
insulation shall be tough, resilient, dimensionally
INSULATED PANELS
stable and have a high ageing resistance. It shall
be odorless, non hygroscopic, chemically inert 2.6.1 General:
and resistant to humidity, corrosive vapors,
moisture and insects. Sandwich Panels shall be manufactured by
the press injection method to produce a rigid
2.5.9.6 The insulation shall be easy to install polyurethane core between exterior steel
and can be cut with an ordinary knife to allow facings. The manufacturing process shall be
installation even on special profiles, curves, carefully controlled with steel facings maintained
T-pieces etc. at around 40 C during the injection process to
ensure proper reaction and adhesion. Also the
2.5.10 Roof curb: pressure on the moulds shall not be released till
completion of reaction.
2.5.10.1 Curbs shall be one-piece construction

24
2.6.2 Panel types: 2.6.4 Panel thickness:

The Sandwich Panels are available in three types, Type KRIP Panels shall have a nominal thickness
i.e. KRIP, KWIP, and KCIP. Panel type KRIP is of 40mm, 50 mm, 60mm, 75 mm or 100 mm at
suitable for application as an exterior roof or wall bottom of ribs.
panel, Type KWIP is suitable for wall panel, and
KCIP for wall and partition panels. All three types Type KWIP panels shall have a nominal thickness of
of panels shall be supplied in 1 Meter net coverage. 40mm, 50 mm, 65 mm or 75 mm at bottom of ribs.

2.6.3 Panel facing: Type KCIP panels shall have a nominal thickness
of 50 mm, 60 mm, 75 mm or 100 mm.

Standard panels shall have both exterior and


2.6.5 Panel core:
interior facings of 26 Gauge steel galvanized and
color coated having a minimum yield strength
of 345 MPa (50,000 psi) and shall conform to Standard panels shall have core insulation of
the physical specifications of ASTM A-653 or rigid polyurethane foam which shall be foamed-
equivalent. The zinc coating shall be by hot dip in-place between panel facings and shall have
galvanization process G90 ( 0.90 oz/ft or 275 g/ an approximate total density of 40Kg/m3, with a
m2) and for galvalume coated panels to A-792 AZ heat transmission value of 0.0198 Watt/M2.
150 or its equivalent. The painting shall be baked
The mechanical properties of the foam shall have
enamel polyester (white) or silicon polyester
approximately the following values:
(color blue or gold) with a film thickness of 25
microns. The reverse side shall be white with 10
Compression Strength
microns film thickness.
(at 10% deformation) = 1.6 Kg/cm2
Compression Modulus = 36 Kg/cm2
The panel facing profiles shall be as follows:
Shear (with metal sheet) = 1.63 Kg/cm2
a) Type KRIP & KWIP Shear Modulus = 20.4 Kg/cm2
Adhesion to metal sheet = 1.5 Kg/cm2
Standard panels shall have exterior skin Water Vapor Transmission = 80 gr/24hm2
26 Gauge steel galvalume / galvanized and Water Absorption = 4 % in volume
prepainted Kirby rib or Kirby wall profile Closed Cell Content = 95 % min
sheets. The interior skin shall be 26 Gauge steel
galvanized and color coated, generally flat profile
2.6.6 Fasteners:
sheet with low ribs at 250 mm centers.
Standard fasteners shall be No. 14 self drilling
screws with EPDM washers. All screws shall have
b) Type KCIP
hex heads.
Standard panels shall have both exterior and 2.6.7 Sealer:
interior skins of 26 Gauge steel galvanized
or galvalume substrate and color coated of
generally flat profile. KCIP panels are provided Panel type KRIP shall have sealer for sidelaps
with tongue & groove joints with concealed and endlaps of 6mm wide x 5thick pressure
fasteners. sensitive butyl tape. The sealer shall be non-
asphaltic, non shrinking, non drying and non
toxic and shall have superior adhesion to metals,

25
plastics and painted surfaces at temperatures building
from 50C to + 104C. KCIP panels are supplied
(2) 0.9 meter
with tube sealant for field application and joints.
2.6.8.6 Wall panels shall be secured to
2.6.8 Installation of roof & wall panels intermediate framing members with No. 14 self-
(type KRIP/KWIP): drilling and tapping screws at a maximum spacing
of 333 mm. At endlaps the maximum spacing of
2.6.8.1 Roof panels shall be continuous from screws shall be 111 mm.
ridge to eave for buildings 18m wide or less,
where endlaps are required, the width shall 2.6.8.7 Sidelaps of roof and wall panels shall be
be approximately 150 mm (as specified on the stitched through the high rib with No. 12 sheet
drawings), and shall occur over a roof purlin. metal screws at 500 mm centers.

2.6.8.2 Sidewall panels shall be continuous from 2.6.9 Flashing, trim & closures:
the eave to 40 mm below me column base plate,
except where the required panel length would
2.6.9.1 Flashing and/or trim shall be furnished
exceed 9.0 m. For a panel length in excess of 9.0 m,
at the rake, corners, eaves, framed openings,
the panel shall be spliced, and endlap shall be 100
and wherever necessary to provide weather
mm wide (minimum) and occur over a wall girt.
tightness and finished appearance. Color shall be
2.6.8.3 Endwall panels shall be continuous from selected from Kirby Building Systems standard
the eave to 40 mm below the column base plate, colors, with the exception of the corner trim,
except where the required panel length would which matches the building wall color.
exceed 9.0 m. For a panel length in excess of 9.0
m, the panel shall be spliced and the endlap shall 2.6.9.2 Color-coated, galvanized steel for
be 100 mm wide (minimum) and occur over a wall flashing, metal closure, trim and other
girt. All endwall panels shall be square cut in the miscellaneous uses shall be 26 gauge of the
field for 3:10 slope buildings. same specification as the roof and walls covering
material.
2.6.8.4 All laps at roof panels shall be sealed with
a continuous ribbon of tape sealer, 2.6.9.3 A formed peak panel matching the slope
and profile of adjoining panels shall be provided
2.6.8.5 Roof panels shall be secured to along the building ridge.
intermediate framing members with No. 14 sheet
metal screws at a maximum spacing of 333 mm. 2.6.10 Color finish:
At endlaps, the maximum spacing of screws shall
be 111mm. At four corners of the buildings, panel
2.6.10.1 Unless specified otherwise, all wall and
to structural fastener spacing shall not exceed 111
roof panels, flashing, trim and other exposed
mm, to an area equivalent to x2 Dimension x is
galvanized steel surfaces shall be color coated.
determined by the following rule:
A. The smaller of a. Color of panels and corner trim shall be
selected by the customer from Kirby Building
(1) 10% of the least horizontal dimension of the
Systems standard colors.
building (span or length)
(2) 40% of the eave height. b.The gutters, downspouts, rake trim, eave trim
and door flashing shall be white unless otherwise
B. But not less than
selected from Kirby Building Systems-Kuwait
(1) 4% of the least horizontal dimension of the standard
26
3 : STANDARD STRUCTURAL SYSTEMS

3.1 STANDARD FRAMES


MAIN FRAMES
Standard frame types:
Suggested width range (metres) for most economical buildings.

- 3 6
1 L-CANOPY (L-CAN) D
.-,,::::: 3 18
,,,,
I LEAN-TO (L-TO)
J I I
6 12
I
BUTTERFLY CANOPY (T-CAN) D
6 18
I I I I
SPACE SAVER (SV)

r- 1 I
6 18
I
r- -,
SINGLE SLOPE (SS)

I
6 36 96
---------- -- ---- -- ---- -- ---------
I---------------------------------

r- T -,
RIGID FRAME (RF)

24 60

BEAM AND COLUMN (BC-1) I I


36 72
r I I
BEAM AND COLUMN (BC-2)
1 I I
,- I T I -w
BEAM AND COLUMN (BC-3)
48
I
96

24

r:.I :t
60
I I
Standard Eave height : 3 m - 8 m The table above is a general guideline on
Standard bay spacing : 6m / 7.5m / 9m recommended frame types for different widths.
Standard Loadings : Live load 0.5/0.6/1.0 kN/M2 Kirby custom designs each order to the specified
type, width, height, bay spacing, loading
Wind load 0.75/1.0/1.25 kN/M2 and other building parameters to customer
requirements.

27
3.2 STANDARD LOADINGS

Single Gable buildings:

DEA~OAD
DEAD LOAD
lT
LIVELOAD
I

~~
I

%1
I I

~~i l~
I
I I I

i
I
I I I I
I I I I
I I I
I
i i i
I I
i l j,~
I

j, j,
LOAD CONDITION: LOAD CONDITION :
DEAD LOAD+ LIVE LOAD DEAD LOAD+ WIND LOAD
Standard buildings are available for the following Design wind co-efficients for enclosed
loadings: single gable buildings
Dead load = building self weight Asce 7 -10
Live load = 0.57 Kn /m2 ( GCPe - GCPI )
Wind load = 1.25 Kn /m2

DESIGN WIND CO-EFFICIENTS FOR ENCLOSED SINGLE GABLE BUILDINGS


ASCE 7-10
( GCPe - GCPi )

C1 C2 C3 C4
h<60 ft.
Balanced +0.22 -0.87 -0.55 -0.47 w/h<1
Un-Balanced +0.58 -0.51 -0.18 -0.11

P = (wind pressure)
P = q (c ), where c is wind co-efficient

28
Single slope buildings:

LOAD CONDITION : LOAD CONDITION :


LOAD CONDITION :
DEAD LOAD +WIND LOAD DEAD LOAD+ WIND LOAD
DEAD LOAD + LIVE LOAD
(LEFT) (RIGHT)

T-canopy:

DL + LL
~ $
"" LL/2

~l$J ~ WL
.~~
w~ w~ ~~
T
LOAD CONDITION : LOAD CONDITION : LOAD CONDITION :

+LL/2 (HALF-SPAN)
LOAD CONDITION :
DEAD LOAD+ LIVE LOAD DEAD LOAD+ WIND LOAD DEAD LOAD+ WIND LOAD DEAD LOAD+ LIVE LOAD
+WIND LOAD

L-Canopy:

LOAD CONDITION : LOAD CONDITION :


DEAD LOAD+ LIVE LOAD DEAD LOAD +WIND LOAD

tandard loadings are same as for single gable


S applied as per table for single gable buildings.
buildings. ull wind load (c=1.3 ) Is applied for t-canopy &
F
Wind coefficients for single slope buildings are l-canopy structures.

29
3.3 STANDARD BUILDINGS

Width Length Eave height Bay Project no. Page


(M) (M) (M) spacing
36.00 48.00 6.00 8@6.00M. BC-36660 212
36.00 48.00 8.50 8@6.00M. BC-36685 218
36.00 48.00 6.00 6@8.00M. BC-36860 224
36.00 48.00 8.50 6@8.00M. BC-36885 230
18.00 48.00 6.00 8@6.00M. RF-18660 236
18.00 48.00 8.50 8@6.00M. RF-18685 242
18.00 48.00 8.50 6@8.00M. RF-18885 248
21.00 48.00 6.00 8@6.00M. RF-21660 254
21.00 48.00 8.50 8@6.00M. RF-21685 260
21.00 48.00 6.00 6@8.00M. RF-21860 266
21.00 48.00 8.50 6@8.00M. RF-21885 272
36.00 48.00 6.00 8@6.00M. RF-36660 278
36.00 48.00 6.00 8@6.00M. RF-36685 284
36.00 48.00 6.00 6@8.00M. RF-36860 290
I 36.00 48.00 8.50 6@8.00M. RF-36885 296 I

Building installation drawings are located at chapter 7,


7.26 Page 211- standard buildings continuation

30
3.4 STANDARD CABLE
BRACING SYSTEM

EAVE STRUTS

NUT&
WASHER THREADED ROD
TERMINAL

CABLE END CONNECTION

Wind forces acting transversely are transferred foundation. The reactions at the top of each wind
to the foundation by means of Frame Action. column is transmitted to the Roof system where
However, wind forces acting longitudinally (i.e. each braced bay takes it proportional share of
On the end wall) are transferred by means of wind reaction. Full Wind is applied in accordance
roof and walls bracing between frames. Number with asce 7 -10.
of braced bays depends on width and length of Standard roof and wall bracing consists of
building. galvanised extra high strength seven
Strand cable of 12.7Mm diameter ( 1/2) acting
All braced bays share equally in transmission always in tension.
of wind reactions from the wind column to the

31
3.5 PORTAL FRAME
BRACING SYSTEM

PORTAL FRAME BRACING SYSTEM

When sidewalls are open for access (passage) mounted on main frame columns just to clear the
or where there are accessories such as doors haunch connection of m.F. Column and rafter.
etc., Portal bracing (wind bents) is substituted The structural design of portal frames is based
in walls of braced bays instead of cable bracing. on rigid connection between portal
Horizontal and vertical clearance must be Columns and beam, and a pinned base condition.
considered since the portal bracing members are

3.6 KNEE BRACING SYSTEM


BEAM

ANGLE BRACE

MAIN COLUMN

KNEE BRACING SYSTEM

When diagonal bracing is not allowed in sidewalls continuous as required by design with diagonal
because of access or accessories such as doors angle braces connecting the beam to the main
etc. And portal frame cannot be used for bracing frame column web.
because of clearance, a knee brace is used as The structural design of knee brace is based on
shown in sketch above. the beam being pinned at both ends
A knee brace consists of a hot rolled beam in With the main column designed for weak axis
the purling line either only at braced bays or bending.

32
3.7 DIAPHRAGM BRACING
SYSTEM
Diaphragm bracing system
Diaphragm action:

Kirby wall panels properly fastened to sheeting acting as a diaphragm is approximately


supporting structural framing form structural 2.2 Kn/m (150 lbs/ft).
units capable of resisting loads through in-plane The minimum effective lenghts of sheeting
shear resistance. This shear resistance required at sidewalls of standard space saver
Effects a shear transfer of these loads to Buildings and at endwalls of all standard
the foundation with a minimum amount of buildings with bearing endwalls for the
Deflection. Such resistance is referred to as Standard windload of 1.25 Kn/m2 are shown
diaphragm action. in the following tables. The effective lengths
The wind loads acting on the endwalls of shall be exclusive of any framed openings for
standard space saver and lean-to buildings and accessories etc.
on a portion of the sidewall at standard bearing Diaphragm action table:
endwalls are transferred to the
Foundation by diaphragm action of the flush girts
Effective length of sidewall sheeting (meters)
and sheeted walls. The resistance of kirby-wall
required for diaphragm action:
Effective length of endwall sheeting (meters)
required for diaphragm action:

Span Eave height (meters)


(meters) 3 4 5 6 7 8
6 2.0 2.7 3.3 3.9 4.6 5.2
9 3.0 4.0 5.0 5.9 6.9 7.9
12 4.1 5.4 6.7 7.9 9.2 10.5
15 5.2 6.8 8.4 10.0 11.6 13.2
18 6.3 8.2 10.1 12.0 14.0 15.9

Effective length of endwall sheeting (meters)


required for diaphragm action:

Eave Ht. (Meters) 6.0 M End bay 7.5 M Endbay


3 2.0 2.4
4 2.6 3.2
5 3.3 4.1
6 3.9 4.9
7 4.5 5.7
8 5.2 6.5

33
1500 ( CANOPY) 200

3.8 STANDARD EAVE


CANOPY can be added to any of the standard frame type
buildings.
A standard eave canopy up to 1.5M wide and a
For canopies other than standard, refer to sales
standard endwall purlin extension of up to 1.73M
office or headquarters for a special price and
details.

3.9 STANDARD FASCIA


The standard fascia extends out 667 mm from
A standard fascia of upto 1.8 Meters height can the sidewall and endwall steel line, is single
be added to any of the standard frame type sheeted and provided with soffit.
buildings. For fascias other than standard refer to sales
office or headquarters for a special price and
details.

34
3.10 STANDARD
EXPANSION JOINTS
Expansion joint at roof:

ROOF PANEL EXP. PANEL

PURLIN

FLANGE BRACE
THIS SIDE ONLY

Expansion joint at wall:

EXP. PANEL

GIRT

FLANGE BRACE
THIS SIDE ONLY

A longitudinal expansion joint is provided for If the width of the building exceeds 120 meters,
buildings with length greater than 120 meters as double columns are used to cater for Expansion.
shown above.

35
3.11 STANDARD ENDWALL
SYSTEMS

ENDWALl ENDWALl
STEEL UNE STEEL UNE

RAKE lRIM 356 RAKE lRIM

BEARING FRAME MAIN ENDFRAME


RAFTER RAFTER
KW WALl KW WALl
PANEL PANEL

GIRT

STANDARD ENDWALL SYSTEMS MAIN END FRAMES

Standard endwall systems: Main end frames:

Endwalls of standard buildings have two light A main end frame is normally used when a future
endwalls. The light endwall rafter is a hot-rolled extension to the building is required. It is also used
I-section and is designed as a continuous beam over for buildings with cranes or full open endwalls. A main
wind column supports. The Standard corner columns end frame is designed for a full bay loading similar
are i-sections designed as pinned at both ends. to an interior frame. Main end frame centerline is
The endwall girts are fwsh with the wind columns. located 356 mm from the endwall steel line.
As there is no frame action at a light end frame, the
lateral wind-load from the half-bay tributary area A building with only two bays shall have at least one
acting on the frame is resisted by the diaphragm main end frame while building with only one bay shall
action of the sheeted endwall. have both main end frames.

36
3.12 STANDARD WIND
COLUMN SPACING

f RIDGE

$ $ $ $ $
7 AT 6M = 42 7 AT 6M = 42

6 AT 6M = 36 6 AT 6M = 36

72 M SPAN.
5 AT 6M = 30 5 AT 6M = 30

63 M SPAN.
4 AT 6 4 AT 6

60 M SPAN.
4 AT 6

L__---(i)------j~---.-~Ei)----t---$--e-------.-.------"1 54 M SPAN.
4 AT 6 l3 3 l 4 AT 6 l
"---$-+------$-+--+-----$,___---$-~)-----$------ll 48 M SPAN.
3 AT 6 l3 3 l 3 AT 6 l3l

42 M SPAN.

36M SPAN.

21M SPAN.

18M SPAN.

15M SPAN.

12M SPAN.
SIDEWALL
STEEL LINE

MAIN ENDFRAME
COLUMN

MAIN END CORNER LIGHT END CORNER

All dimensions are in meters

37
3.13 STANDARD WIND
COLUMN SPACING WITH
MEZZANINE
f RIDGE

$ $ $ $ $ $ $ ~ $ $ $ $ $ $ $
1
96 M SPAN.
l 16 AT pM - 96 I.
---r
I I
84 MSPAN.
l 7.5 I. 6 l 2 AT 7.5M l 6 l 7.5 7.5 l 6 I. 2 AT 7.5M I. 6 l 7.5 I.
I I
72 MSPAN.
l 12 AT pM = 72 I
---r
L I 63 M SPAN.
l 7.5 L 6 I 2 AT 7.5M 1.3 3 L 2 AT 7.5M L 6 I. 7.5 l
---1
I 1 60 M SPAN.

-1'-:._ _ $ __
$ __ $ _:9:_ :A~$T- 'j~:'.'C.M- =$=:_ :5~4-$_ _$_ _$__j,;. 54 M SPAN .

.,l--$__ $ -$-=--
8 -'-"AT__ =M_=_~_._.-8_$_ _$_----.f;. 48 M SPAN.
I .1. I
45 M SPAN.
l 6 AT 7.5M = 45 I.
l I
42 M SPAN.
L 7.5 l 6 I. 7.5 7.5 I. 6 I. 7.5 l
I
1 ---r
3 6 M SPAN.
6 AT BM = 36

30M SPAN.
4 AT 7.5M = 30

24M SPAN.

21M SPAN.

18M SPAN.

15M SPAN.

12M SPAN. SIDEWALL


STEEL LINE
/ SIDEWALL
I"
1
STEELLINE ~ 9MSPAN.
MAIN END FRAME
J2 At 4.~1 CORNER
COLUMN COLUMN

MAIN END CORNER LIGHT END CORNER

All dimensions are in meters

38
3.14 STANDARD ANCHOR
BOLTS DETAIL

~ 120 ANCHOR BOLTS

I
~--- t 75
---
II
STEEL LINE

I
I

I
- --------- 63
---------- I
I

~0
)7 v 5~v F
v F / G
/
/ F v G v F v
E DOOR WIDTH l E v
STANDARD BAY I/
/
L__
DOOR GUIDES REFER TO CHAPTER 7.10

BOLT PLAN FOR SLIDE DOOR

0
0
N

BOLT PLAN FOR I' SECTION I

CORNER COLUMN

BASE PLATE

END WALL STEEL LINE 4 (AS PER DESIGN )

BOLT PLAN
BOLT PLAN FOR I' SECTION I FOR INTERIOR
WIND COLUMN MEZZANINE COLUMN

39
4 : SPECIAL STRUCTURAL &
PRE-ENGINEERED BUILDING SYSTEMS
4.1 RIGID FRAMES WITH
OVERHEAD CRANES

Rigid frames with overhead cranes:


considered in the design of the main frames and
Rigid frame buildings with electric overhead the crane system. Cranes travelling outside the
travelling cranes are designed for the effect of building are supported on independent a or h
the loads in accordance with the aisc manual. frames as required.
Cranes of 3.2 Mt., 5.0 Mt. ,10.0 Mt. and 15.0
Mt. up to a span of 21 meters are mounted on
brackets welded to the main frame columns. For
Cranes:
crane capacities in excess of 1o ml. It is generally
recommended to provide independent support Buildings can be designed to support any
columns tied laterally to the main frame columns. required crane system. Generally, overhead
The complete crane system includes brackets/ travelling cranes up to 15 mt are supported on
columns, bracing beam and crane runway. brackets. for higher capacities, an independent
support system is provided. Crane support
In the design of the rigid frame an impact for overhead travelling cranes includes brackets,
allowance of 10 % of max. Wheel load is beams and bracings.
considered for pendant operated and 25 % of
max. Wheel load for cab operated cranes. The
lateral force due to the effect of moving crane
trolley is 20 % of the sum of the lifted load and
crane trolley (exclusive of other parts of the
crane). The longitudinal force is 10 % of the
max. Wheel load. The lateral and longitudinal
forces are applied at the top of rail. The loading
conditions in accordance with MBMA are:

Dead + wind load,


Dead + crane loads + one-half live or wind load
Dead + crane loads + 3/4 snow load
Whichever is critical.

In buildings with multiple Cranes effect of the


moving loads for the worst case of loading is Al-adasani pipe factory - kuwait

40
----------------------------~'
4.2 MULTI-SPAN FRAMES &
TRUSSES

MS- BC-2

Multi-span frames:
and building heights are possible by running
Multi-span frames up to 6 spans or 120 meters service pipes/ducts through the trusses.
are analysed without lateral expansion joint. For Foundation costs are also reduced due to fewer
frame widths in excess of the above, a double columns being required to support larger spans.
column expansion joint is provided. Exterior The kirby truss system structures are individually
columns are built-up sections tapered or straight, designed to meet the specific requirements of
pinned or fixed at base depending on eave each building and are fabricated utilizing high
height of building. Exterior columns have rigid quality efficient fixtures. The system allows for
(moment) connection at top and the rafters are easy building installation as all connections are
built-up sections and continuous throughout the field bolted. Except for field splices on very large
length. Interior columns are generally pinned at spans, no site welding is required.
both ends. Valley gutters are designed assuming
interior downspouts (supplied by others) at
bay spacing. However if internal drainage is not
allowed larger valley gutters can be supplied
depending on the drained area of the roof.

Trusses:

Kirby truss system is one of the companys most


popular and highly economical products. It is a
rigid structure, ideal for large span roof systems,
multiple bay buildings and as mezzanine floor
framing. Significant reductions in clearances Sultan centre - kuwait

41
4.3 MULTI-STOREY
BUILDINGS

I
I
I
I

I
I
I
I

r
'

l r l
TYPE-A TYPE.-.. 8 I

Multi storey bank building

l r l
TYPE-C TYPE - D

Multi-storey structures are available in


the following types:

Type No. of spans No. of floors


Al 1 2
A2 1 3
A3 1 4
Bl 2 2
B2 2 3
Cl 3 2
I Dl 4 2 I

Columns and joists are fabricated from hot deck is profiled galvanised sections suitable
rolled sections and beams from either hot for supporting the dead load of the reinforced
rolled or built-up sections. Floor and roof steel concrete slab and 0.5 Kn/m2 construction load.

The standard design loads are:


Floor - live load = 4 kn/m2 suitable for residential and office occupancy.
Dead load = 4 kn/m2 which covers self wt. of steel framing, concrete slab
(100 mm), light floor finishes (carpets, vinyl tiles) light weight
partitions, ceilings and services.
Roof - live load = 1 kn/m2
- Dead load = 5 kn/m2 which covers all loads as for floor plus built-up roof.
-Wind load = 1.25 Kn/m2
All beam to column connections are moment resisting connections field bolted with H.S. Bolts.

42
4.4 MEZZANINE FLOORING
SYSTEM

The standard mezzanine framing consists Beams and joists are designed as simply
of profiled steel deck, joists, beams and supported at both ends and the intermediate
intermediate support columns. Beams are support columns are designed as pinned at both
built-up sections spanning in the longitudinal ends. The standard design live load is 5 kn/m21
direction, joists are hot rolled sections spanning covering most of the occupancies encountered
in the lateral direction and intermediate support in usual practice per aisc tables and the Design
columns are either pipe sections or hot rolled Dead Load is 3 kn/m2 which covers self weight of
aisc shapes. framing, 100 mm concrete slab and light finishes.
Refer to tables for the standard intermediate
The standard mezzanine finished floor level is column spacings and the occupancies covered
3.5 Meters with a clear height at bottom of joists for the standard live load.
of 3.1 Meters. The total thickness of floor slab
inclusive of deck and finishings is assumed to be Mezzanine floors of non-standard dimensions
100 mm. and loading to suit special customer
requirements are also available upon request.

43
4.5 OPEN WEB STEEL
JOISTS
Definition:
increasing the weight.
The Open Web Steel Joist is a secondary steel
Ducts and mechanical accessories can be
truss member fabricated from crimped angles
installed in between the web openings .
welded onto top and bottom chords. The
Cambering will prevent tiles, partitions or
elements of the open joist are made of hot rolled
any other delicate finishings from cracks by
as well as cold formed grade 50 steel. Open
maintaining the finish floor level straight.
Web Steel Joists are used as mezzanine joists,
roof purlins, among others.

Advantages:

Offers an economical solution for long spans Aircraft Hangar with 14 m open web cantilever
carrying heavy loads or light loads compared joist erected at Kuwait International Airport.
to conventional steel structure .
Allows more clearance to the building by Kirby offered the customer a high quality
minimizing the mezzanine overall depth by economical solution using open web steel joists
designing beams at the short direction and in this project instead of a rival space frame
the joists at the long direction without option.

44
----------------------~'

Detailing:

A~
Kirby Rib
Roof Panel

False Ceilling _ /

Open Web Steel Joist Connection Detail Section A -A


rOpen Web Steel Joist

Rafter Or Beam

OPEN WEB STEEL JOIST


Specifications: Load tables:

Kirby Open Web Steel Joist is designed in Kirbys Open Web Steel Joists is recognized
accordance with the latest editions of: Steel Joists by Kirbys standard designation as follows: KJ
Institute (SJI), American Iron and Steel Institute (Depth mm)-(Chord Size-Letter) Example: KJ
(AISI), American Institute of Steel Construction 400-A.
(AISC), American Welding Society (AWS).

Material specifications are in accordance with


ASTM A570, A572, A10ll or equivalent.
Allowable total load (kN/lm) Open Web Steel
Joists
Span
(mm)
6000
KJ 300-A
7.20 kg/m
3.20
KJ 300-B
8.93 kg/m
4.80
KJ 300-C
10.74 kg/m
6.00
KJ 300-D
13.53 kg/m
8.50
KJ 300-E
16.03 kg/m
10.10
KJ 300-F
19.4 kg/m
13.00
KJ 300-G
22.6 kg/m
15.30
KJ 300-H
26.33 kg/m
18.40
l
7000 2.35 3.53 4.41 6.24 7.42 9.55 11.24 13.52
8000 1.80 2.70 3.38 4.78 5.68 7.31 8.61 10.35
9000 1.30 2.05 2.55 3.60 4.30 5.50 6.50 7.80
10000 1.05 1.66 2.07 2.92 3.48 4.46 5.27 6.32
11000 1.37 1.71 2.41 2.88 3.68 4.35 5.22

I 12000 1.10 1.30 1.90 2.30 3.00 3.50 4.20

45
Span KJ 400-A KJ 400-8 KJ 400-C KJ 400-D KJ 400-E KJ 400-F KJ 400-G KJ 400-H
(mm) 7.4 kg/m 9.21 kg/m 11.09 kg/m 13.96 kgm 16.37 kg/m 19.88 kg/m 23.4 kg/m 27.26 kg/m
6000 4.30 6.60 8.20 11.60 13.90 17.70 21.00 25.20
7000 3.16 4.85 6.02 8.52 10.21 13.00 15.43 18.51
8000 2.42 3.71 4.61 6.53 7.82 9.96 11.81 14.18
9000 1.80 2.80 3.50 4.90 5.90 7.60 9.00 10.70
10000 1.55 2.38 2.95 4.18 5.00 6.37 7.56 9.07
11000 1.28 1.96 2.44 3.45 4.14 5.27 6.25 7.50

Span KJ 600-A KJ 600-8 KJ 600-C KJ 600-0 KJ 600-E KJ 600-F KJ 600-G KJ 600-H


(mm) 8.22 kg/m 10.19 kg/m 12.29 kg/m 15.45 kg/m 18.32 kg/m 21.98 kg/m 25.5 kg/m 29.42 kg/m
6000 6.60 10.10 12.60 17.80 21.40 27.40 32.40 38.90
7000 4.85 7.42 9.26 13.08 15.72 20.13 23.80 28.58
8000 3.71 5.68 7.09 10.01 12.04 15.41 18.23 21.88
9000 2.80 4.30 5.40 7.60 9.20 11 .70 13.90 16.70
10000 2.27 3.48 4.37 6.16 7.45 9.48 11 .26 13.53
11000 1.87 2.88 3.61 5.09 6.16 7.83 9.30 11 .18
12000 1.50 2.50 2.95 4.20 5.00 6.50 7.70 9.20
13000 2.00 2.50 3.50 4.30 5.50 6.50 7.80
14000 1.72 2.16 3.02 3.71 4.74 5.60 6.73

Span KJ 800-C KJ 800-D KJ 800-E KJ 800-F KJ 800-G KJ 800-H KJ 800-1 KJ 800-J


(mm) 13.45 kg/m 16.54 kg/m 19.43 kg/m 23.34 kg/m 27.42 kg/m 31.63 kg/m 34.24 kg/m 35.61 kg/m
11000 4.79 6.86 8.26 10.58 12.56 15.04 16.28 17.52
12000 3.99 5.63 6.81 8.68 10.33 12.44 13.50 14.55
13000 3.40 4.80 5.80 7.40 8.80 10.60 11.50 12.40
14000 2.93 4.14 5.00 6.38 7.59 9.14 9.92 10.69
15000 2.50 3.53 4.21 5.46 6.49 7.85 8.42 9.10
16000 2.20 3.10 3.70 4.80 5.70 6.90 7.40 8.00
17000 2.75 3.28 4.25 5.05 6.11 6.56 7.09
18000 2.34 2.90 3.68 4.46 5.35 5.79 6.24
19000 2.10 2.60 3.30 4.00 4.80 5.20 5.60
20000 2.35 2.98 3.61 4.33 4.69 5.05
l I

For direct order, use the above tables 2. Move to the right until you Find your desired
load or nearest higher value.
as follows:
3. Read the column header KJ (Depth mm)-
(Size-Letter) and make your direct order from
Kirbys Sales Offices.
1. Select your span from the First left column
[SPAN (mm)]

46
4.6 HANGAR DOOR
SYSTEM

~111 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1~
CLEAR OPENING

Symme~ical
1
I about

~
~lb
.
r----
-r--
--=--=i-- I
EE
'(5,lg
I
. I <:F==~=======I I

OJ L-~----- f- - -4 ------------------------------~ ------


l : Clear opening I

Pocket I Lean-to_i out to out of main building


I




II II

Aircraft hangar - Jordan

Buildings with hangar doors are designed to The hangar door system is available as either
accommodate air crafts types DC8, DC9, B707, manually or electrically operated. For manually
B727 & B737. The maximum available door operated doors the top guide beams are hot
opening size is 51 meters clear width and 15 rolled angles or tee sections and for electrically
meters clear height. operated doors the top guide beams are hot
rolled i-sections which prevent the door leaves
For smaller doors up to a height of approx. 9 from slipping due to uplift of the frame from
meters an overhang header support system is wind forces. Hangar doors are supported on
provided and for larger doors above 9 meters rails embedded in concrete. The door leaf is
height an additional frame is used at the exterior adequately braced to resist the wind forces
to minimise deflection. and are offered with either one side sheeted or
both sides sheeted. Door pockets at ends are
supplied with either sheeted or open walls.

47
4.7 SPECIAL CANOPIES

------------ - - ---------- ------------ - - - - - - - ,


I I I I I I I 1 I

L_
I

_j _j_ _L
I
r--
I
I
I
I
c
---0 -

'---
I I I
-

I
-

I
-

I I 1
t- -
I
I
I
I
A
I
I
I
1------------
I I I I I I I I

1:::-,_
:::-,__

ROOF PLAN

Jrf-------::J=----------::!..IJ

-Lt-
ABOVE 2M. 1 VARIES
I

SECTION A SECTION B SECTION C

Special canopies of width in excess of the standard as required. Canopies are supplied with or without
canopy width of 1.5 Meters and up to 6 meters are soffit. Canopies exceeding 6 meters are treated as
made of either hot rolled i-sections or built -up part of the frame through continuation of the roof
sections bolted to rafter end plate or column flange rafter.

48
------------------~'
4.8 SPECIAL FASCIAS

- VERTICAL
, FASCIA - INCLINED
, FASCIA

/
----

~
~- ~-
H2
- 1-
- -- 1- H2
- 1- ~-
- - 1-

~-
I
I
I
I

Hl Hl

11 11
j/ j/

Special fascias:

Fascias are used for architectural purposes to Fascias are cantilevered from the main frame columns
conceal the gable of the building. A variety of fascias on the sidewall and from the wind columns on
either straight or inclined can be provided as shown the endwall. Flush fascias or parapets can also be
in the sketches. provided.

Fascias and canopies:

KIRBY provides fascias especially designed


to customer requirements. This can be either
vertical, horizontal or with curved sheeting to
enhance the architectural look of your building.
Wall canopies at eaves, endwalls, over doors and
windows are also available.
Kisr office building - Kuwait

49
4.9 BUILT-UP ROOFS

GRAVEL OR SLAG EMBEDDED


IN POURING OF BITUMEN

ALTERNATIVE LAYERS
OF BITUMEN AND FELT

KIRBY DECK

OPTIONAL
VAPOUR BARRIER
(OPTIONAL)

Built up roofs: 4.9A CONVENTIONAL


Built-up roofing is required for flat roofs and may be
BUILT-UP ROOFING SYSTEM
used for roofs with low slopes. It can be applied (not
by KBSK) over Kirby roof deck to weatherproof the Conventional built-up roof system may be
building to meet client specifications or architectural composed of some or all of the following elements
requirements. Buildings requiring built-up roofs shall depending on end use of the building, geographical
be identified at the design stage to ensure structural location, desired aesthetic effect, cost and other
adequacy for the required additional dead loads and factors. Roofing elements from inside to outside
compatibility to receive the specified built-up roofing of building over roof purlins/joists are Kirby steel
system. The two commonly used built-up roofing deck, vapor barrier, rigid insulation, reinforced
systems are briefly described below: concrete slab, alternate layers of saturated felt
and moppings of bitumen and an optional top
pouring of pitch or asphalt in which slag or gravel
may be embedded which completes the built-up
roof. Vapor barrier protects the insulation from
condensation wherever conditions of high humidity
exist inside the building or on roof decks in cold
climates and on decks of heated buildings where
winter temperature may fall below 7 C. Vapor
barrier materials commonly used are coated base
sheets, saturated felts, laminated kraft papers and
PVC sheets. Concrete slab supporting flat built-
up roofing is normally pitched towards drains at
the center of the slab areas connected to internal
drainage system.
50
4.9B INVERTED BUILT-UP
ROOFING SYSTEM

3/4" STONE--,
RIGID INSULATION---....~
ASPHALT ADHESIVE,
COAT

OF BITUMEN AND FELT


CONCRETE SLAB

Also known as upside down roof assembly, an This roofing system is based on the theory
inverted built-up roofing system consists of that the insulation set above the roofing both
several layers installed in a sequence as shown in insulates the building and protects the built-
sketch. First a standard built-up roofing (without up roofing from the harmful effects of thermal
insulation and vapor barrier) is applied directly cycling, ultraviolet degradation, weathering
to the concrete deck. Then, rigid insulation that and roof traffic. This virtually eliminates the
is impervious to moisture such as extruded common defects caused by these elements such
polystyrene foam is bonded to the top of the as blistering, ridging, cracking, alligatoring and
built-up roofing with a mopping of steep asphalt. wrinkling, however the inverted built-up roof
A layer of 3/4 inch crushed stone on top of the system is relatively heavier than the conventional
insulation completes the assembly. Gravel or slag built-up roof system due to the increased stone
should not be used because the sharp edges content.
would damage the bare insulation underneath.

51
4.10 ROOF MONITOR

Typical section of monitor roof:

ROOF MONITOR WIDTH

ROOF MONITOR
PURLIN

EAVE STRUT

CHANNEL FTER

CHANNEL COLUMN
I
I
I
I (O.W.)
I
SDS \ sds 2
FLASHING\ 1FLASHING
SYMMETRICAL
TO PREVENT \ ITO PREVENT
RAINWATER \ I RAIN WATER
FROM ENTERING 1 I FROM ENTERIN

M16x55 H.S. BOLTS


(TYP)
OPENING WIDTH
( o.w.)

A roof monitor is a structure mounted on the It is generally used when a standard ridge
ridge of the building and is used for ventilation ventilator is not adequate to give the required
purposes. It is fabricated from either cold number of air changes inside the building.
formed channel sections or hot rolled I-sections.

52
4.11 CURVED BUILT UP
MEMBERS
Curved process conducted during
fabrication:
Design and production system is integrated
with that of the building structure, ensuring
on-time delivery.
Accurate detailing and manufacturing
techniques assure correct appearance and
perfect fit at site.
Flanges range from 125mm x 5 mm to
400mm x 16mm.
Depth range from 200mm to 1200mm
Mass production of members with 10m
radius or more.
Variable depth and tapered members
Capability of curvature in three dimensions.

Semi auto curve beam welders:

a. Single Fillet to each flange in one pass


Min Fillet Size = 3mm
Max Fillet Size = 6.Smm
b. Length of Built up member
Min = 200mm
Max = 14000mm
c. Max Flange Thickness = 16 mm
d. Uniform Flange width per member
e. Max Web Taper = 0-10 Meters
f. Max Feed = -120 in\min
i.e= -3048 mm\min -3mm fillet
g. Filler AWS/ASME SF AS.l7 EM13K
Delhi Metro Station, India

Arc - Curved Aircraft Hangar, Yemen Curved Roof, Enma Mall, Bahrain

53
4.12 SECONDARY
MEMBERS

Bracings:
Cold formed members:
The Cable Bracing is a secondary structural
member that ensures the stability of the building Secondary structural framing refers to purlins,
against forces in the longitudinal direction such girts, eave struts, wind bracing, flange bracing,
as wind, cranes and earthquakes. base angles, clips and other miscellaneous
structural parts.
Purlins, girts, and eave struts are cold formed
from steel which has a minimum yield strength
of 345 MPa (50,000 psi) and will conform to the
physical specifications of ASTMA 570 (Grade
50) or ASTM A-653 (Grade 50) or equivalent.

Z - purlin / girt:

Purlins and girts shall be roll formed Z sections, 200 mm deep


with 64 mm flanges shall have a 16 mm stiffening lip formed at
45 to the flange.

Eave strut:

Eave struts are 200 mm deep with a 104 mm wide top flange, a
118 mm wide bottom flange, both are formed parallel to the roof
slope. Each flange has a 24 mm stiffener lip.

C - section:

C- Sections are 200mm deep with a 100mm flange. The flanges


are perpendicular to the web and have a 24mm stiffening lip.

54
CHAPTER 5 : ENGINEERING
DATA
5.1 PURLIN & GIRT
200Z / 250Z - SECTION
PROPERTIES

1~
10

Minimum Specified Yield Stress Fy= 34.5 Kn/cm2 (50 KSI)

Table of properties for Z section


Deflec- Allowa-
Elastic Allowable
General information tion ble
modulus moment
Section Inertia shear
Girth Area Weight Lx Sx Va Ma Ma* Ma**
(mm) (cm2) (Kg/1m) (cm4) (cm3) (KN) (KN-m) (KN-m) (KN-m)
200Z1 .5 346 5.19 4.07 310.11 26.02 10.90 5.37 3.49 3.76
200Z1.75 346 6.06 4.75 364.43 31 .51 17.35 6.50 4.23 4.55
200Z2.0 346 6.92 5.43 420.87 37.27 25.97 7.69 5.00 5.39
200Z2.5 346 8.65 6.79 520.33 48.80 45.35 10.07 6.55 7.05
250Z2.5 400 10.00 7.85 883.44 67.28 40.28 13.89 6.94 9.72

Section Properties are calculated in accordance with the 2001 Edition


of the American Iron and Steel Institute Specifications (A.I.S .I). Updated on 10 January 2003

1. Top Flange : Fully braced


2. Bottom Flange : Fully unbraced
3. Ma: Capacity under Gravity Load
4. Ma*: Wind Uplift for simply supported beam
5. Ma **: Wind Uplift for continuous beam
6. Stress Increment of 33% is not allowed any more

55
5.2 EAVE STRUT - 0.5:10
AND 1:10 SLOPE - SECTION
PROPERTIE

---.----- -
~u~4
y
o I
~
N
x- +-x
~ ~~4
\5tJ
0.5:10 AND 1:10 EAVE STRUT

Minimum Specified Yield Stress Fy = 34.5 Kn/


Cm2 (50 Ksi)

Table of properties for eave strut


Allowa- Allowa-
Top in Compression Bot in Compression
ble ble
General Information Slope
Shear Comp. Deflection Allowable Deflection Allowable
Section
Force Force Inertia Moment Inertia Moment
Girth Area Weight Slope Va Pa Deflx Ma Deflx Ma
(mm) (cm2) (Kg/1m) (:10) (KN) (KN) (cm4) (KN-m) (cm4) (KN-m)
200x1 .5 451 6.77 5.31 0.5 10.93 64.51 433.02 6.51 419.04 6.53
200x1 .75 451 7.89 6.20 0.5 17.40 80.29 502.09 8.06 487.52 8.21
200x2.0 451 9.02 7.08 0.5 26.04 97.30 575.48 9.34 561.50 9.57
200x2.5 451 11 .28 8.85 0.5 45.47 135.46 738.70 12.04 694.37 12.42
250x4.0 501 20.04 15.73 0.5 116.34 289.65 1947.42 28.88 1931 .01 29.76
200x1 .5 451 6.77 5.31 1.0 11 .02 64.52 430.59 6.39 419.56 6.44
200x1.75 451 7.89 6.20 1.0 17.54 80.30 499.67 7.76 488.34 8.18
200x2.0 451 9.02 7.08 1.0 26.25 97.31 572.24 8.99 562.69 9.54
200x2.5 451 11 .28 8.85 1.0 45.82 135.48 735.84 11 .59 693.44 12.37
250x4.0 501 20.04 15.73 1.0 117.03 289.87 1942.95 28.11 1927.81 29.37

Section Properties are calculated in accordance 1. Section is considered fully braced


with the 2001 Edition of the American Iron and 2. Stress Increment of 33% is NOT ALLOWED
Steel Institute Specifications (A.I.S.I). Updated ANY MORE
on 10 January 2003

56
=====---------------~'
5.3 COLD FORMED C
SECTIONS - SECTION
PROPERTIES
II1-=fC
v

<( X-
I
+-X

I
J 1-==tC
w
y

Minimum Specified Yield Stress Fy = 34.5 Kn/Cm2 (50 Ksi)


Table of properties for C section
Deflection Elastic Allowable Allowable
General Information
Interia Modulus Shear Moment
Section
Girth A IB IC Area Weight lx Sx Va Ma Ma* Ma**
(mm) (mm) (cm2) (Kg/1m) (cm4) (cm3) (KN) (KN-m) (KN-m) (KN-m)
100x50C1 .5 226 100 50 24 3.38 2.66 54.21 10.54 16.33 2.18 1.31 1.31
1 00x50C1. 7 5 226 100 50 24 3.95 3.10 62.54 12.63 20.25 2.61 1.56 1.56
100x50C2.0 226 100 50 24 4.51 3.54 70.68 14.27 23.01 2.95 1.77 1.77
100x50C2.5 226 100 50 24 5.64 4.43 86.37 17.44 28.44 3.60 2.16 2.16
1 00x50DC1.5 226 100 50 24 6.77 5.31 108.43 21 .08 32.65 4.35 2.61 2.61
100x50DC1 .75 226 100 50 24 7.89 6.20 125.09 25.25 40.50 5.21 3.13 3.13
1 00x50DC2.0 226 100 50 24 9.02 7.08 141 .35 28.54 46.02 5.89 3.53 3.53
1 00x50DC2.5 226 100 50 24 11.28 8.85 172.74 34.88 56.88 7.20 4.32 4.32
200x 1 OOC1 .5 451 200 100 35 6.77 5.31 412.67 32 .97 10.90 6.81 4.08 4.08
200x1 OOC1 .75 451 200 100 35 7.89 6.20 493.73 42.33 17.35 8.74 5.24 5.24
200x1 OOC2.0 451 200 100 35 9.02 7.08 577.30 50.78 25.97 10.48 6.29 6.29
200x1 OOC2.5 451 200 100 35 11.28 8.85 730.54 68.14 45.35 14.07 8.44 8.44
200x1 OODC1 .5 451 200 100 35 13.53 10.62 825.34 65.94 21 .80 13.61 8.17 8.17
200x1 OODC1 .75 451 200 100 35 15.79 12.39 987.45 84.65 34.70 17.48 10.49 10.49
200x1 OODC2.0 451 200 100 35 18.04 14.16 1154.61 101.57 51 .94 20.97 12.58 12.58
200x1 OODC2.5 451 200 100 35 22.55 17.70 1461 .08 136.28 90.70 28.13 16.88 16.88
250x80C1 .5 440 250 80 24 6.60 5.18 617.34 40.22 8.63 8.30 4.98 4.98
250x80C1 .75 440 250 80 24 7.70 6.04 727.55 50.37 13.73 10.40 6.24 6.24
250x80C2.0 440 250 80 24 8.80 6.91 826.83 59.31 20.54 12.24 7.35 7.35
250x80C2.5 440 250 80 24 11.00 8.64 1021 .94 77.49 40.28 16.00 9.60 9.60
250x80DC1.5 440 250 80 24 13.20 10.36 1234.68 80.43 17.26 16.60 9.96 9.96
250x80DC1 .75 440 250 80 24 15.40 12.09 1455.10 100.73 27.46 20.79 12.48 12.48
250x80DC2.0 440 250 80 24 17.60 13.82 1653.65 118.63 41 .08 24.49 14.69 14.69
250x80DC2.5 440 250 80 24 22.00 17.27 2043.88 154.98 80.56 31.99 19.20 19.20

1. Top Flange: Fully braced


Section Properties are calculated in accordance 2. Bottom Flange: Fully unbraced
with the 2001 Edition 3. Ma : Capacity under Gravity Load
of the American Iron and Steel Institute 4. Ma* Wind Uplift for sim ply supported beam
Specifications (AI.S.I ). Updated on 10 January 5. Ma**: Wind Uplift for continuous beam
2003 6. Stress Increment of 33% is NOT ALLOWED
ANY MORE
* not applicable for 100x50DC

57
5.4 BASE AND CAP CHANNEL
- SECTION PROPERTIES

76

y
I

~ x- H---x
I
y

Minimum Specified Yield Stress Fy= 34 .5 Kn/cm2 (50 Ksi)

Table of properties for cap channel


Deflection Elastic Allowable Allowable
General Information Moment
Inertia Modulus Shear
Section
Girth Area Weight Def lx Sx Va Ma Ma* Ma**
(mm) (cm 2)
(Kg/lm) (cm 4)
(cm ) 3
(KN) (Kn-m) (KN-m) (KN-m)
206x76C01.5 346 5.19 4.07 264.65 17.39 10.56 3.59 2.15 2.15
206x76CO1.75 346 6.06 4.75 313.45 23.65 16.82 4.88 2.93 2.93
206x76CO2.0 346 6.92 5.43 365.37 29.30 25.17 6.05 3.63 3.63
206x76CO2.5 346 8.65 6.79 476.88 38.86 45.35 8.02 4.81 4.81

Section Properties are calculated in accordance 1. Top Flange: Fully braced


with the 2001 Edition 2. Bottom Flange: Fully unbraced
of the American Iron and Steel Institute 3. Ma: Capacity under Gravity Load
Specifications (A.I.S.I). Updated on 10 January 4. Ma*: Wind Uplift for simply supported beam
2003 5. Ma**: Wind Uplift for continuous beam
6. Stress Increment of 33% is not allowed any
more

58
5.5 KIRBY - RIB, ROOF &
LINER SHEETING ( KR )
SECTION PROPERTIES &
LOAD TABLES ( STEEL )
11 l
00
, , . """""' Morn I
I 111.1 1 111.1 1 111.1 1 ~ . .

" /\ f?' T-- r


~ --W.-

Pull out Pull over


Fastener Data Sheet Purlin Thickness (mm) 1.50 1.75 2.00 2.50 Panel Thickness (mm) 0.50 0.60
Ultimate Pull Out (KN) 1.16 1.83 2.09 2.32 Ultimate Pull Over (KN) 5.12 5.72

Minimum specified yield stress fy = 34.5 Kn/cm 2 (50 ksi)

Steel panel properties (KR)


Panel Shear & Web
Top Flat in Compression Bot Flat in Compression
Nominal Crp
Thickness Girth Weight Va Pa (Def) lx Sx (top) Sx (bot) Ma (Def) lx Sx (top) Sx (bot) Ma
(mm) (mm) (kg/m2) (KN) (KN) (cm4) (cm3) (cm3) (KN-m) (cm4) (cm3) (cm3) (KN-m)
0.5 1145 3.93 5.39 3.27 4.82 1.45 7.10 0.30 4.12 1.75 3.12 0.36
0.6 1145 4.83 8.88 4.96 5.99 2.04 8.71 0.42 5.38 2.19 4.78 0.45

Section Properties are Calculated in accordance Steel Institute Specifications (AI.S.I). Updated
with the 2001 Edition of the American Iron and on 10 January 2003
Allowable Uniform Load (Kn/M2)
Panel Nominal Load Purlin
Thickness Case Thick Span (m)
(mm) (-) (mm) 1.00 1.20 1.40 1.50 1.60 1.75 2.00 2.20
D+L - 2.32 1.78 1.41 1.27 1.15 1.00 0.81 0.70
Roof system Allowable WP - 2.32 1.78 1.41 1.27 1.15 1.00 0.81 0.70
Capacity (KN/m2) based WS 1.50 1.55 1.29 1.11 1.03 0.97 0.88 0.74 0.61
0.5
on 3 spans and WS 1.75 2.44 2.00 1.48 1.30 1.14 0.96 0.74 0.61
3 fasteners per lm WS 2.00 2.79 2.00 1.48 1.30 1.14 0.96 0.74 0.61
WS 2.50 2.83 2.00 1.48 1.30 1.14 0.96 0.74 0.61
D+L - 3.22 2.45 1.93 1.73 1.57 1.36 1.09 0.92
Roof system Allowable WP - 3.22 2.45 1.93 1.73 1.57 1.36 1.09 0.92
0.6 Capacity (KN/m2) based WS 1.50 1.55 1.29 1.11 1.03 0.97 0.88 0.77 0.70
on 3 spans and WS 1.75 2.44 2.04 1.74 1.63 1.53 1.36 1.04 0.86
3 fasteners per lm WS 2.00 2.79 2.33 1.99 1.84 1.62 1.36 1.04 0.86
WS 2.50 3.10 2.58 2.11 1.84 1.62 1.36 1.04 0.86

1. D+L : Dead Load + Live Load WP. Wind 4. Fasteners Uplift Capacity is based on the
Pressure WS. Wind Suction manufacturers Pull Out and Pull Over Data
2. Minimum deflection = Span/180 for D+L 5. Shaded area indicates that fasteners pull out
3. Stress Increment of 33% is not allowed any capacity is governing
more
59
5.6 KIRBY - RIB, ROOF &
LINER SHEETING ( KR )
SECTION PROPERTIES &
LOAD TABLES ( ALUMINUM )

Pull out Pull over


Fastener Data
Purlin Thickness (mm) 1.50 1.75 2.00 2.50 Panel Thickness (mm) 0.50 0.70
Sheet
Ultimate Pull Out (KN) 1.16 1.83 2.09 2.32 Ultimate Pull Over (KN) 2.15 2.80
Minimum Specified Yield Stress Fy = 14.49 Kn/Cm 2 (21 Ksi)
ALUMINUM PANEL PROPERTIES (KR)
Panel
Shear & Web Crp Top Flat in Compression Bot Flat in Compression
Nominal
Thickness Girth Weight Va Pa (Def) lx Sx (top) Sx (bot) Ma (Def) lx Sx (top) Sx (bot) Ma
(mm) (mm) (kg/m ) 2
(KN) (KN) (cm ) 4
(cm ) 3
(cm ) 3
(KN-m) (cm )
4
(cm ) 3
(cm )3
(KN-m)
0.5 1145 1.55 3.09 1.93 5.76 1.81 8.44 0.16 5.03 2.10 4 .09 0.18
0.7 1145 2.11 5.81 3.48 7.98 3.00 11 .66 0.26 7.58 2.97 7.83 0.26
Section Properties are Calculated in accordance
with the 2001 Edition of the American Iron and Steel
Institute Specifications (AI.S.I). Updated on 10
January 2003
Allowable uniform load (Kn/M2)
Panel Nominal Load Purlin
Thickness Case Thick Span (m)
(mm) (-) (mm) 1.00 1.20 1.40 1.50 1.60 1.75 2.00 2.20
Roof system Allowable D+L - 1.28 0.97 0.77 0.69 0.62 0.54 041 0.31
Capacity (KN/m2) WP - 1.28 0.97 0.77 0.69 0.62 0.54 0.44 0.37
based on 3 spans and WS 1.50 1.50 1.06 0.78 0.69 0.60 0.51 0.39 0.32
0.5
3 fasteners per lm WS 1.75 1.50 1.06 0.78 0.69 0.60 0.51 0.39 0.32
WS 2.00 1.50 1.06 0.78 0.69 0.60 0.51 0.39 0.32
WS 2.50 1.50 1.06 0.78 0.69 0.60 0.51 0.39 0.32
D+L - 2.04 1.54 1.20 1.08 0.97 0.83 0.56 0.42
Roof system Allowable WP - 2.04 1.54 1.20 1.08 0.97 0.83 0.64 0.53
0.7 Capacity (KN/m2) based WS 1.50 1.55 1.29 1.11 1.03 0.97 0.84 0.64 0.53
on 3 spans and WS 1.75 2 .44 1.76 1.30 1.14 1.00 0.84 0.64 0.53
3 fasteners per lm WS 2.00 2.51 1.76 1.30 1.14 1.00 0.84 0.64 0.53
WS 2.50 2.51 1.76 1.30 1.14 1.62 0.84 0.64 0.53

1. D+L : Dead Load + Live Load WP. Wind 4. Fasteners Uplift Capacity is based on the
Pressure WS. Wind Suction manufacturers Pull Out and Pull Over Data
2. Minumum deflection = Span/180 for D+L 5. Shaded area indicates that fasteners pull out
3. Stress Increment of 33% is not allowed any capacity is governing
more

60
5.7 KIRBY WALL SHEETING
( KW)
SECTION PROPERTIES &
LOAD TABLES ( STEEL )
1OOOmm COVERING WIDTH

Pull out Pull over


Fastener Data
Purlin Thickness (mm) 1.50 1.75 2.00 2.50 Panel Thickness (mm) 0.50 0.60
Sheet
Ultimate Pull Out (KN ) 1.16 1.83 2.09 2.32 Ultimate Pull Over (KN) 5.12 5.72
Minimum specified yield stress Fy = 34.5 KN/cm 2 (50 KSI)
Aluminum panel properties (Kr)
Panel Nom- Shear & Web
Top Flat in Compression Bot Flat in Compression
inal Crp
Thickness Girth Weight Va Pa (Def) lx Sx (top) Sx (bot) Ma (Def) lx Sx (top) Sx (bot) Ma
(mm) (mm) (kg/m2) (KN) (KN) (cm4) (cm3) (cm3) (KN-m) (cm4) (cm3) (cm3) (KN-m)
0.5 1145 3.93 6.62 3.84 1.74 1.00 1.43 0.21 2.36 1.93 4 .09 0.30
0.6 1145 4.83 9.03 5.78 2.34 1.36 1.80 0.28 3.01 2.45 7.83 0.39
Section Properties are Calculated in accordance Institute Specifications (A.I.S.I). Updated on 1 0
with the 2001 Edition of the American Iron and Steel January 2003

Allowable uniform load (Kn/M2)


Panel Nominal Load Purlin I I I I I I I
Thickness Case Thick Span (m)
(mm) (-) (mm) 1.00 1.20 1.40 1.50 1.60 1.75 2.00 2.20
Wall system Allowable D+L - 2.32 1.67 1.05 0.86 0.71 0.54 0.36 0.27
Capacity (KN/m 2) based WP - 2.32 1.75 1.32 1.15 1.01 0.81 0.54 0.41
on 3 spans and ws 1.50 1.55 1.29 1.05 0.91 0.80 0.67 0.51 0.43
0.5
3 fasteners per lm ws 1.75 2.03 1.42 1.05 0.91 0.80 0.67 0.51 0.43
ws 2.00 2.03 1.42 1.05 0.91 0.80 0.67 0.51 0.43
ws 2.50 2.03 1.42 1.05 0.91 0.80 0.67 0.51 0.43
D+L - 3.24 2.25 1.42 1.15 0.95 0.73 0.49 0.37
Wall system Allowable WP - 3.24 2.44 1.79 1.56 1.37 1.09 0.73 0.55
06 Capacity (KN/m 2 ) based ws 1.50 1.55 1.29 1.11 1.03 0.97 0.88 0.70 0.58
on 3 spans and ws 1.75 2.44 1.93 1.42 1.24 1.09 0.91 0.70 0.58
3 fasteners per lm ws 2.00 2.76 1.93 1.42 1.24 1.09 0.91 0.70 0.58
....____ _____. _ _ _ _ _ -ws- _ 2.50 ,_2.76 1.93
,_ 1.42
- 1.24
- 1.09
- 0.91
- 0.70
- 0.58
__j

1. D+L : Dead Load+ Live Load WP Wind 4. Fasteners Uplift Capacity is based on the
Pressure WS: Wind Suction manufacturers Pull Out and Pull Over Data
2. Minimum deflection = Span/ 180 for D+L 5. Shaded area indicates that fasteners pull out
3. Stress increment of 33% is not allowed any capacity is governing
more

61
5.8 KIRBY WALL
SHEETING ( KW) SECTION
PROPERTIES & LOAD
TABLES (ALUMINUM)
1OOOmm COVERING WIDTH

333.3

Pull out Pull over


Fastener Data
Purlin Thickness (mm) 1.50 1.75 2.00 2.50 Panel Thickness (mm) 0.50 0.70
Sheet
Ultimate Pull Out (KN) 1.16 1.83 2.09 2.32 Ultimate Pull Over (KN ) 2.15 2.80
Minimum Specified Yield Stress Fy = 14.49 Kn/Cm 2 (21 Ksi)

Aluminum panel properties (KR)


Panel Nom- Shear & Web
Top Flat in Compression Bot Flat in Compression
inal Crp
Thickness Girth Weight Va Pa (Def) lx Sx (top) Sx (bot) Ma (Def) lx Sx (top) Sx (bot) Ma
(mm) (mm) (kg/m ) 2
(KN) (KN) (cm )
4
(cm )
3
(cm )3
(KN-m) (cm ) 4
(cm ) 3
(cm )
3
(KN-m)
0.5 1145 1.55 3.54 2.26 2.11 1.22 1.71 0.11 2.83 2.31 1.76 0.15
0.7 1145 2.11 4.92 4.03 3.49 1.92 2.37 0.17 3.94 3.22 2.59 0.23
Section Properties are calculated in accordance
with the 2001 Edition of the American Iron and
Steel Institute Specifications (AI.S.I). Updated
on 10 January 2003
Allowable uniform load (Kn/M2)
Panel Nominal Load Purlin I I I I I I I
Thickness Case Thick Span (m)
(mm) (-) (mm) 1.00 1.20 1.40 1.50 1.60 1.75 2.00 2.20
Wall system Allowable D+L - 1.19 0.69 0.43 0.35 0.29 0.22 0.15 0.11
Capacity (KN/m 2) based WP - 1.26 0.92 0.65 0.53 0.44 0.33 0.22 0.17
on 3 spans and WS 1.50 1.04 0.73 0.54 0.47 0.41 0.34 0.26 0.22
0.5
3 fasteners per lm WS 1.75 1.04 0.73 0.54 0.47 0.41 0.34 0.26 0.22
WS 2.00 1.04 0.73 0.54 0.47 0.41 0.34 0.26 0.22
WS 2.50 1.04 0.73 0.54 0.47 0.41 0.34 0.26 0.22
D+L - 1.97 1.14 0.72 0.58 0.48 0.37 0.25 0.18
Wall system Allowable WP - 2.01 1.45 1.06 0.87 0.72 0.55 0.37 0.28
Capacity (KN/m2) based WS 1.50 1.55 1.14 0.84 0.73 0.65 0.54 0.41 0.31
0.7
on 3 spans and WS 1.75 1.63 1.14 0.84 0.73 0.65 0.54 0.41 0.31
3 fasteners per lm WS 2.00 1.63 1.14 0.84 0.73 0.65 0.54 0.41 0.31
.....___ _......~ _ _ _ _ _ _ -WS- _2.50 ,_1.63 ,_1.14 _
0.84 _
0.73 _ 0.65 _
0.54 _
0.41 __j
0.31

1. D+L Dead Load+ Live Load WP Wind 4. Fasteners Uplift Capacity is based on the
Pressure WS: Wind Suction manufacturers Pull Out and Pull Over Data
2. Minimum deflection= Span/180 for D+L 5. Shaded area indicates that fasteners pull out
3. Stress Increment of 33% is not allowed any capacity is governing
more

62
5.9A KIRBY DECKING ( KD ),
LIGHT DECKING
SECTION PROPERTIES &
LOAD TABLES
820mm COVERING WIDTH

16.7 RADIUS

Minimum Specified Yield Stress Fy = 34.5 Kn/Cm2


(50 KSI)
Steel deck properties (Kd)
Panel Shear & Web Crp Top Flat in Compression Bot Flat in Compression
Nominal
Thickness Girth Weight Va Pa (Def) lx Sx (top) Sx (bot) Ma (Def) lx Sx (top) Sx (bot) Ma
(mm) (mm) (kg/m2) (KN) (KN) (cm )4
(cm ) 3
(cm )
3
(KN-m) (cm ) 4
(cm ) 3
(cm ) (KN-m)
3

0.5 1145 4.80 10.55 8.46 7.94 5.72 2.64 0.54 8.10 7.75 2.24 0.46
0.6 1145 5.89 18.43 12.65 10.24 7.82 3.33 0.69 10.55 9.51 3.05 0.63
0.7 1145 6.99 26.19 17.54 12.55 10.10 4.03 0.83 12.56 11.28 3.95 0.81

Section Properties are calculated in accordance


with the 2001 Edition of the American Iron and
Steel Institute Specifications (AI.S.I). Updated
on 10 January 2003
Allowable uniform load (Kn/M2)
Panel Type Load
Thickness of Case Span (m)
(mm) Span (-) 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90
2 Spans D+L 4.23 3.62 3.09 2.64 1.99 1.99 1.75 1.55 1.38 1.24
0.5
>3 Spans D+L 5.10 4.37 3.79 3.27 2.47 2.47 2.18 1.93 1.72 1.55
2 Spans D+L 5.95 5.02 4.22 3.60 2.71 2.71 2.39 2.12 1.89 1.70
0.6
>3 Spans D+L 7.19 6.15 5.26 4.49 3.38 3.38 2.98 2.64 2.36 2.12
2 Spans D+L 7.85 6.50 5.47 4.67 3.51 3.51 3.09 2.74 2.44 2.19
0.7
>3 Spans D+L 9.54 8.10 6.82 5.82 4.38 4.38 3.85 3.42 3.05 2.74

1- D+L : Dead Load + Live Load


2- Deflection Criteria L/240 for D+L
3- Web Cripling is based on a minimum Flange Width of 100
mm

63
5.9B KIRBY DECK PANEL
40-200 X 0.7 SECTION
PROPERTIES & LOAD TABLE
The 40 - 200 panels are designed in accordance The KD 40-200 panel is made from a 1219 coil unlike
with the 2001 Edition of the American Iron and Steel the KR and KW panels which are made from the 1145
Institute Specifications (A.I.S.I.). coil.
Kirby 40 - 200 X 0.7 Deck Panel is recognized by The Kirby Deck Panels of 0.7 mm thickness are
Kirbys standard designation as: KD 40-200 as the designed in accordance with the AISI specifications
application of the KCS panel has been extended to (2001) and is recognized by Kirby standards as: KD 0.7.
mezzanine deck panels. The thickness of the panel is This panel is made from 1145 coil.
0.7 mm.

Material Specification and Sizes:


1000mm COVERING WIDTH

200

KD 40-200 MEZZANINE DECK PANEL

1. The KD 40-200 and KD 0.7 are available in


820mm COVERING WIDTH steel only.
2. The specific yield stress for steel = Fy = 34.5
KN/cm2 as per ASTM A792 GRADE 50 or
ASTM A653 GRADE 50
3. The steel panel thickness is 0.7 mm.
4. KD 40-200 and KD 0.7 are available as
galvanized or AluZinc based on availability.
5. Deflection limited to l / 240 for gravity loads.

Allowable uniform load (KN/m2)


Deck Panel Span (m)
Type 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.75 1.8 1.9 2 2.2
KD 40-200 6.53 5.68 4.99 4.42 3.95 3.55 3.21 2.91 2.78 2.66 2.37 2.04 1.53
KD 0.7 9.54 8.10 6.82 5.82 5.02 4.38 3.86 3.42 3.23 3.05 2.74 2.38 1.79

NOTE:

1. Deck panel must be designed to withstand 3. F


or panel thickness of 0.5mm & 0.6mm
Concrete Wet Weight + 0.5 kN/m2 properties, check Kirby Decking (KD) Section
construction load Properties & Load Tables on Chapter 5.9a
2. The type of span is equal or greater than 3
continuous spans.

64
5.10 KIRBY INSULATED
SANDWICH PANELS ROOF,
WALL & PARTITION PANEL

KRIP SANDWICH PANEL


1039
1000 - COVERING WIDTH 2
333.33 333.33 333.33

249 250 249


41

KWIP SANDWICH PANEL


1039
1000 - COVERING WIDTH 2
2 333.33

249 250 249


998 ( 1) 42

KCIP SANDWICH PANEL

65
5.11 KRIP SANDWICH PANEL

KRIP SANDWICH PANEL - DATA SHEET


1039

,
1000 - COVERING WIDTH ( 2)
2C 333.33 333.33 333.33 19

~ ~
EXTERIOR FACE ~

":t
~;-,
'KR' PROFILE
jl ~
~l
--r
__ l ~ ~ ~ /
I
I
r ExTERIOR FAcE I
'KF' PROFILE
249 I 250 I 250 249
998 ( + 1) 41

Specifications:
Minimum Specified Yield Stress for Steel Fy = 34.5 kN/cm2 (50 KSI) ASTM A792 Grade 50
Panel Core Specifications are as follows:
Approximate Total Density = 40 kg/m3 Heat Transmission Value = 0.0198 W /m2
Compression Strength (at 10% deformation) = 1.6 kg/cm2 Compression Modulus = 36 kg/cm2
Shear (with metal sheet) = 1.63 kg/cm2 Shear Modulus = 20.4 kg/cm2
Adhesion to metal sheet = 1.5 kg/cm2 Water Vapour Transmission = 80 g/24h.m2
Water Absorption = 4% in volume Closed Cell Content = 95% (min)
Pull out Pull over
Fastener Data
Purlin Thickness (mm) 1.50 1.75 2.00 2.50 Panel Thickness (mm) 0.50 0.60
Sheet
Ultimate Pull Out (kN) 1.16 1.83 2.09 2.32 Ultimate Pull Out (kN) 5.12 5.72
Thermal Heat Transmission U-Values:
KRIP 40 KRIP 50 KRIP 60 KRIP 75 KRIP 100
BTU /FT2 h.f. 0.085 0.070 0.059 0.048 0.037
KCAL/M2K 0.414 0.340 0.288 0.234 0.179
WATT/M2K 0.482 0.396 0.335 0.273 0.208

Allowable Loading for KRIP 50, 60,65 and 75 mm (KN/m2):


Span in meters
1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00 3.25 3.50 3.75 4.00
KRIP 50 6.83 5.47 4.56 3.90 3.42 3.04 2.73 2.48 2.28 2.10 1.95 1.60 1.32
KRIP60 8.20 6.56 5.47 4.69 4.10 3.64 3.28 2.98 2.73 2.54 2.34 2.17 1.79
KRIP65 8.88 7.11 5.92 5.08 4.44 3.95 3.55 3.23 2.96 2.73 2.54 2.37 2.05
KRIP 75 10.25 8.20 6.83 5.86 5.13 4.56 4.10 3.37 3.42 3.15 2.93 2.73 2.56

All owab le Lo ad I' ng d ueto F asteners ca pac1ty (kN/m 2) ..

Span in meters
1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00 3.25 3.50 3.75 4.00
3 Fasteners/m 3.48 2.78 2.32 1.99 1.74 1.55 1.39 1.27 1.16 1.07 1.00 0.93 0.87
6 Fasteners /m* 6.96 5.56 4.64 3.98 3.48 3.10 2.78 2.54 2.32 2.14 2.00 1.86 1.74
*In case ofKRIP 50, please refer to the above Kirby Building Systems reserves the right to make
table values. changes without prior notice KBS-KRIP-2 80811-00

66
5.12 KWIP SANDWICH
PANEL
KWIP SANDWICH PANEL - DATA SHEET
1039

Specifications:
Minimum Specified Yield Stress for Steel Fy = 34.5 kN/cm2 (5O KSI) ASTM A792 Grade 5O
Panel Core Specifications are as follows:
Approximate Total Density = 40 kg/m3 Heat Transmission Value = 0.0198 W /m2
Compression Strength (at 10% deformation) = 1.6 kg/cm 2
Compression Modulus = 36 kg/cm2
Shear (with metal sheet) = 1.63 kg/cm2
Shear Modulus = 20.4 kg/cm2
Adhesion to metal sheet = 1.5 kg/cm 2
Water Vapour Transmission = 80 g/24h.m2
Water Absorption = 4% in volume Closed Cell Content = 95% (min)

PaneI StructuraI Properties:


Pull out Pull over
Fastener Data
Purlin Thickness (mm) 1.5o 1.75 2.oo 2.50 Panel Thickness (mm) 0.50 0.60
Sheet
Ultimate Pull Out [kN) 1.16 1.83 2.o9 2.32 Ultimate Pull Out [kN) 5.12 5.72
Thermal Heat Transmission U-Values:
KWIP 40 KWIP 50 KWIP65 KWIP75 KWIP100
BTU /FT2 h.f. 0.071 0.060 0.049 0.043
KCAL/M2K 0.347 0.293 0.238 0.211
WATT/M2K 0.404 0.341 0.277 0.246
Allowable Loading for KWIP (kN/m2):
Span In meters
1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00 3.25 3.50 3.75 4.00

KWIP 50 6.83 5.47 4.56 3.90 3.42 3.04 2.73 2.48 2.28 2.10 1.95 1.70 1.40
KWIP60 8.20 6.56 5.47 4.69 4.10 3.64 3.28 2.98 2.73 2.54 2.34 2.17 1.90
KWIP65 8.88 7.11 5.92 5.08 4.44 3.95 3.55 3.23 2.96 2.73 2.54 2.37 2.20
KWIP75 10.25 8.20 6.83 5.86 5.13 4.56 4.10 3.37 3.42 3.15 2.93 2.73 2.56

Allowable Loading due to Fasteners Capacity (kN/m2):


Span In meters
1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00 3.25 3.50 3.75 4.00

3 Fastenersjm 3.48 2.78 2.32 1.99 1.74 1.55 1.39 1.27 1.16 1.07 1.00 0.93 0.87

6 Fasteners fm* 6.96 5.56 4.64 3.98 3.48 3.10 2.78 2.54 2.32 2.14 2.00 1.86 1.74

Kirby Building Systems reserves the right


*In case ofKWIP 50, please refer to the previous to make changes without prior notice KBS-
table values. KWIP-050911-00

67
5.13 KCIP SANDWICH
PANEL

KCIP SANDWICH PANEL - DATA SHEET

Specifications:
Minimum Specified Yield Stress for Steel Fy = 34.5 kN/cm2 (5O KSI) ASTM A792 Grade 50
Panel Core Specifications are as follows:
Approximate Total Density = 40 kg/m3 Heat Transmission Value = 0.0198 W /m2
Compression Strength (at 10% deformation) = 1.6 kg/cm 2
Compression Modulus = 36 kg/cm2
Shear (with metal sheet) = 1.63 kg/cm2
Shear Modulus = 20.4 kg/cm2
Adhesion to metal sheet = 1.5 kg/cm 2
Water Vapour Transmission = 80 g/24h.m2
Water Absorption = 4% in volume Closed Cell Content = 95% (min)
PaneI Structural Properties:
Pull out Pull over
Fastener Data
Purlin Thickness (mm) 1.5o 1.75 2.oo 2.50 Panel Thickness (mm) 0.50 0.60
Sheet
Ultimate Pull Out (kN) 1.16 1.83 2.o9 2.32 Ultimate Pull Out [kN) 5.12 5.72
Thermal Heat Transmission U-Values:
Kcip 50 Kcip 60 Kcip 75 Kcip 100
BTU /FT2 h.f. 0.077 0.065 0.052
KCAL/M2K 0.038 0.315 0.252
WATT/M2K 0.440 0.367 0.293
Allowable Loading for KCIP (kN/m2):
Span in meters
1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00 3.25 3.50 3.75 4.00

KCIP 50 6.83 5.47 4.56 3.90 3.42 3.04 2.73 2.48 2.18 1.70 1.40 1.12 1.40
KCIP 60 8.20 6.56 5.47 4.69 4.10 3.64 3.28 2.98 2.73 2.47 1.98 1.62 1.90
KCIP 65 8.88 7.11 5.92 5.08 4.44 3.95 3.55 3.23 2.96 2.73 2.32 1.88 2.20
KCIP 75 10.25 8.20 6.83 5.86 5.13 4.56 4.10 3.37 3.42 3.15 2.93 2.50 2.56

Allowable Loading due to Fasteners Capacity (kN/m2):


Span in meters
1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00 3.25 3.50 3.75 4.00

3 Fasteners/m 3.48 2.78 2.32 1.99 1.74 1.55 1.39 1.27 1.16 1.07 1.00 0.93 0.87

6 Fasteners fm* 6.96 5.56 4.64 3.98 3.48 3.10 2.78 2.54 2.32 2.14 2.00 1.86 1.74

* In case of KCIP 50, please refer to the previous Kirby Building Systems reserves the right
table values. to make changes without prior notice KBS-
KCIP-050911-00

68
--------------------------~'
5.14 CONCEALED FASTENER
CLADDING
SINGLE SKIN CLADDING - TYPE KC

CAP FLASHING GIRT

LINER
KRPANEL-
PANEL

KRI CLOSURE 'KC' SINGLE SKIN PANEL BASE


FLASHING SKIN PANEL CHANNEL
BASE
FLASHING
SHEETING
ANGLE

DETAIL AT BASE

ENDWALL : ::::- =--: ::::::: =-----


- -- ------
- -- -- - --
- -- --
-- - ---------
---- -- ---------
- ----- - --- -
RAFTER ENDWALL :3------ GIRT
COLUMN

SECTION AT ENDWALL
T -- -------n;;---------:----- --T
A

L-~-No-.1-4-xZ-5-SD-TS--=.__j--+---'.KC' SINGLE=:J
SKIN PANEL

TYPICAL JOINT DETAIL ~

Features: Benefits:

Single concealed fastener cladding type- kc An attractive architectural look for


is used for exterior wall cladding and interior commercial and Institutional buildings .
roof and wall Liner panels . Flat surface without exposed fasteners & no
Panels have interlocking tongue & groove corrugation .
joints. For external panel only.
Supplied in covering widths of 333mm &
666mm with Thickness of 0.5 And 0.6Mm .
Available in all kirby standard colours.

69
5.15 CONCEALED FASTENER
SINGLE SKIN CLADDING
TYPE ( KC) SPECIFICATIONS
1.0 GENERAL hexagonal heads and shall be zinc plated and
1.1 The Kirby concealed fastener panel system color coated to match the panel colors.
type KC shall be furnished with other 5.2 No panel to panel fasteners are required .
integral components to form the exterior All fasteners shall be made from the outside,
envelope and/or the interior partitions of the hidden in the panel joint thus eliminating
building as described herein. exposed fasteners.
1.2 Installation of the panel system shall be in
accordance with Kirby Building installation 6.0 FLASHINGS AND TRIMS
drawings. 6.1 Flashing and trims shall be furnished at
2.0 PANEL DESCRIPTION corners, eaves, rake, framed openings and
2.1 Exterior wall panels shall be 333mm covering wherever necessary to provide weather
width, 26G or 24G thickness and interlocking tightness and a good finished appearance .
joints to conceal the fasteners to the 6.2 Flashing and trims shall be of the same
structural members within the joints . specifications as the panel materials.
2.2 Interior liner or Partition panels shall be 7.0 ACCESSORIES
either 333mm-26G/24G or 666mm-24G
thickness and interlocking joints to conceal 7.1 Accessories as specified such as doors
the fasteners to the structural members , windows, etc.. , shall be furnished or
within the joints . framed openings provided as shown in the
2.3 Panels shall be precision roll formed at the building installation drawings . Accessories
factory to a total panel depth of 35mm using when supplied shall be to Kirby standard
precoated sheeting coils. specifications unless otherwise noted on
2.4 Panels shall be one piece from base to top of wall building installation drawings.
or partition upto a maximum length of 9 meters. 7.2 Location and type of accessories shall be as
2.5 Both ends of the panel shall be square cut shown in Kirby building installation drawings .
and unpunched.
7.3 Blanket insulation may be used with the
3.0 PANEL MATERIAL AND FINISH panel system. Panel configuration can
3.1 Panel material shall be either zincalum accommodate up to 1OOmm thick, 12 Kg/m3
coated or galvanized steel to ASTM A792 density insulation.
Grade 50B AZ150 or ASTM A653 Grade 50
with G90 coating. 8.0 PACKAGING AND SHIPPING
3.2 The finish coating shall be polyester or 8.1 For shipments, panel faces and corners shall
silicon polyester coating 25 microns on be suitably protected . Panel bundles shall be
exterior face and 10 microns on interior packaged for safe and ease of handling and
face of the panel. Other finish coatings are transport.
available upon request. 9.0 FIELD INSTALLATION
3.3 Panel color shall be one of Kirby standard colors .
Other colors are available upon request. 9.1 Structural system shall be plumb within
4.0 PANEL DESIGN AISC/MBMA tolerances before wall/partition
panels are attached to girts.
4.1 Panel design shall be in accordance with AISI
Cold Formed Steel Design Manual and good 9.2 Sealant shall be applied at panel joints to
engineering practices . ensure weather tightness . Flashing and trim
5.0 FASTENERS shall be installed true and in proper alignment
for best appearance.
5.1 Panels shall be fastened to structural
9.3 All installation shall be done in accordance
members using #14 self tapping screws with
metal and EPDM washers. Screws shall have with Kirby building installation drawings and
good working practices.

70
5.16 CONCEALED
FASTENER INSULATED
CLADDING TYPE KCIP
---- ---- ----- - -- --- --- - -- - ------- - --- -- - - --
GIRT
{ 3 - - - - GIRT

CLIP SEALANT (OPTIONAL)


A ;- I
-- -- KCIP

#\
PANEL
NSULATION
1!1- =~-t-- SHEETING
SEALANT ____) No. 14x50 STS P=========~~ ANGLE
- RAKE
TYPICAL JOINT DETAIL ! GIRT ANGLE
:t!1! :t!1! :t!1!

Features: RAFTER

Sandwich panel concealed fastener cladding


type-kcip is used for exterior wall cladding SECTION AT ENDWALL
and exterior partition.
Panels have interlocking tongue & groove
joints.
Supplied in covering widths of 666mm &
1000mm and thickness of 0.5 & 0.6Mm ,top
& bottom skin thickness.
LINER
Available in all kirby standard colours. KCIP PANEL
WALL PANEL
BASE
Benefits: CHANNEL
BASE
FLASHING
An attractive architectural look for
.. I

commercial and Institutional buildings.


Flat surface without exposed fasteners & no DETAIL AT BASE
corrugation.
Ideal for internal office & room partitions.

71
5.17 CONCEALED FASTENER
INSULATED PANEL CLADDING
TYPE ( KCIP) SPECIFICATIONS
1.0 GENERAL 5.0 FASTENERS
1.1 The Kirby concealed fastener insulated 5.1 Panels shall be fastened to structural
panel system type 'KCIP' shall be furnished membersusing #14 self tapping screws with
with other integral components to form metal and EDPM washers. Screws shall have
the exterior envelope and/or the interior hexagonal heads and shall be zinc plated and
partitions of the building as described herein. color coated to match the panel colors.
1.2 Installation of the panel system shall be in 5.2 No panel to panel fasteners are required.
accordance with Kirby Building installation All fasteners shall be made from the outside,
drawings. hidden in the panel joint thus eliminating
2.0 PANEL DESCRIPTION exposed fasteners.
2.1 Exterior wall and partition panels shall be 6.0 FLASHINGS AND TRIMS
1000mm covering width and maximum 6.1 Flashing and trims shall be furnished at
possible length(not to exceed 9 meters), to corners, eaves, rake, framed openings and
minimise the number of joints. The panels wherever necessary to provide weather
shall be manufactured by the press injection tightness and a good finished appearance.
method to produce a rigid polyurethane core 6.2 Flashing and trims shall be of the same
of 35 Kg/m3 nominal density between steel specifications as the panel facing materials.
facings. Panels shall have a generally flat
7.0 ACCESSORIES
profile with minor ribs and interlocking joints
to conceal the fasteners to the structural 7.1 Accessories as specified such as doors,
members. windows, etc .. , shall be furnished or framed
2.2 The panels shall be available in nominal openings provided as shown in the building
thickness of 50mm, 60mm, 75mm and 100mm. installation drawings. Accessories when
2.3 Panels shall be one piece from base to top of wall supplied shall be to Kirby standard
or partition upto a maximum length of 9 meters. specifications unless otherwise noted on
2.4 Both ends of the panel shall be square cut building installation drawings.
and unpunched. 7.2 Location and type of accessories shall be as
3.0 PANEL MATERIAL AND FINISH shown in Kirby building installation drawings.
3.1 Panel facings shall be precision roll formed 8.0 PACKAGING AND SHIPPING
from either zincalum coated or galvanized 8.1 For shipments, panel faces and corners shall
steel substrate to ASTM A792 Grade 50B be suitably protected. Panel bundles shall be
AZ150 or ASTM A653 Grade 50 with G90 packaged for safe and ease of handling and
coating. transport.
3.2 The finish coating shall be polyester or 9.0 FIELD INSTALLATION
silicon polyester coating 25 microns on
exterior face and 1 0 microns on interior face 9.1 Structural system shall be plumb within
of the panel facings. Other finish coatings are AISC/MBMA tolerances before wall/
available upon request. partition panels are attached to girts.
3.3 Panel color shall be one of Kirby standard 9.2 Sealant shall be applied at panel joints to
colors. Other colors are available upon ensure weather tightness. Flashing and
request. trim shall be installed true and in proper
4.0 PANEL DESIGN alignment for best appearance.
9.3 All installation shall be done in accordance
4.1 Panel design shall be in accordance with AISI
with Kirby building installation drawings and
Cold Formed Steel Design Manual and good
engineering practices. good working practices.

72
5.18 FIBER GLASS
INSULATED PANEL

WITH EXCELLENT
PERFORMANCE
CHARACTERISTICS

Kimmco
Fiber Glass
FIRE SAFE
Insulation
SUPERB THERMAL
INSULATION

EXCELLENT ACOUSTIC
INSULATION

ENVIRONMENT FRIENDLY

Krgp- fiber glass insulated panel


For roof & wall

COST EFFICIENT
EASY TO INSTALL
SUITABLE TO RETROFIT
COMPATIBLE WITH KIRBY BLDGS

Kimmco
Fiber Glass
Insulation

KFGP- fiber glass insulated panel for partitions

73
5.19 FIBER GLASS
INSULATED PANEL
KRGP
Applications :

As Roof and Wall cladding system on:


New Pre-engineered steel buildings.
Retrofit applications on
existing steel buildings

333 334 333

Fiber glass insulated panel for roof & wall


Description:
Top facing : Trapezodial profile 32mm deep at 250 250 250 250
333mm spacing, Steel 26g or 24g.
Bottom facing : Generally flat profile with minor
1000 MM

stiffening ribs at 250 mm spacing, Steel 26g or


24g. The steel facings are high strength steel Dimensions :
to ASTM A 792 grade 345 Mpa with zincalum Length : upto 9000 mm
coating to AZ150. The substrate is polyester width : 1000 mm
coated to 25 microns nominal Thickness : 50,60,70 or
thickness on exposed side and 12 microns on 100 mm at low rib (add 32 mm to thickness at high rib)
reverse side. Available in full range of Kirby
standard colors. Insulation :
FIRE SAFE CFC free fiberglass insulation (which NOTE :
does not emit TOXIC SMOKE) laminated to the
steel facings with special chemical glue, completely Panels in other thickness can also made
filling the insulation cavity. available to meet any specified R or U value

Performance Values:
Thermal Heat Transmission (U-Value)

Krgp 50 Krgp 60 Krgp 75 Krgp 100


BTU/ft2 .h.f 0.108 0.092 0.076 0.59
W/M .K 2
0.613 0.524 0.431 0.332

Maximum working temperature - 230 C


80 Fire Safety - Non-combustible
60 Acoustics - KRGP 60 : STC - 32dB

~ 40 r-
~
20

0
,
----
125 250 500 1000 2000 4000
Third octave band (Hz)

74
----------------------------~'

KFGP
Applications :
AS Interior Partition Panels.
Interior wall liner Panels.

250 250 250 250

Fiber glass insulated panel for partitions 1000 MM

Description:
Top facing and Bottom facing : Trapezodial profile Dimensions :
32mm deep at 333mm spacing, Steel 26g or 24g. Length : upto 9000mm
Bottom facing : Generally flat profile with minor stiff- width : 1000mm
ening ribs at 250 mm spacing, Steel 26g or 24g. Thickness : 50, 60, 75 or
The steel facings are high strength steel to ASTM A 100 mm
792 grade 345 Mpa with zincalum coating to AZ150.
The substrate is polyester coated to 25 microns NOTE :
nominal thickness on exposed side and 12 microns on
reverseside. Available in full range of Kirby standard Panels in other thickness can also made
colors. available to meet any specified R or U value
Insulation : Performance Values:
FIRE SAFE CFC free fiberglass insulation (which
does not emit TOXIC SMOKE) laminated to the steel
facings with special chemical glue, completely filling
the insulation cavity.

Performance Values :

Thermal Heat Transmission (U-Value)

Krgp 50 Krgp 60 Krgp 75 Krgp 100


BTU/ft2 .h.f 0.114 0.097 0.079 0.60
W/M .K
2
0.645 0.548 0.447 0.342

80 Maximum working temperature - 230 C


Fire Safety - Non-combustible
60
Acoustics - KRGP 100 : STC - 37dB
v/
--
~ 40

20

0
125 250 500 1000 2000 4000

Third octave band (Hz)

75
5.20 SELF DRILLING
SCREW ( SDS )

Dimensions:
LENGTH

HEAD ACROSS FLATS 9.33 - 9.52 mm


THREAD DIA ( O.D ) 6.10 - 6.25 mm
THREAD DIA ( I. D ) 5.45 - 5.55 mm
EPDM WASHER DIA 19 mm

Pull out (Ultimate)


Purlin Thickness (mm) 1.50 1.75 2.00 2.50
Ultimate Pull Out (KN) 1.16 1.83 2.09 2.32

Pull over (Ultimate)


Panel Material Steel Aluminium
Purlin Thickness (mm) 0.5 0.6 0.5 0.7
Ultimate Pull Over (KN) 5.12 5.72 2.15 2.80

76
5.21 CABLE BRACING

Definition:

The Cable Bracing is a primary member suitable


to insure the stability of the building against
forces in the longitudinal direction due to Wind,
Cranes, Earth Quake ... etc.

Kirbys Cable Bracing is designed in accordance


with the latest edition of the American Institute
of Steel Construction AISC 2005.

Specifications: Advantages:

1. Cables are made of Galvanized Extra High Higher Strength 60 KN


Strength Seven Strand Cable of 1/2 diameter Better corrosion resistance (Galvanized)
conforming to ASTM A475 - 2003 Class 1 Easy packing and shipping (Round Packing)
(G40). Cable can be fabricated and shipped for any
2. Terminals are made of Galvanized (G40) 25 required length.
mm diameter rods conforming to ASTM A36 Easy building installation.
3. Hill Side Washers are made of Aluminum Light weight (Economical)
Alloy

Revision Date : 01-01-07

77
5.22 ASTM A36 ANCHOR
BOLTS COMPONENT
SECTION PROPERTIES &
LOAD TABLES
Standard specifications bolts:

ASTM designation - A36


Connection Type- N (Bearing type connection
with threads included in shear plane)
Hole Type- STD (Standard round holes)

Fu =58 ksi (39.98 kN/cm2)


Ft = 19.1 ksi (13.16 kN/cm2)
Fv = 9.9 ksi (6.82 kN/cm2)

Anchor Bolt Setting


Table 3.7.1 - Allowable Loads
Bolt L A B C D L a Pitch C/s
Diam e
mm mm mm mm mm mm mm (P) mm2
16 400 100 75 325 100 545 2.0 201.06
20 500 120 100 400 150 670 2.5 314.16
24 650 140 100 550 150 870 3.0 452.39
32 950 200 100 850 150 1290 3.5 804.24

Allowable Comb. Allowable comb.


Max Corresponding Corresponding Max Pull-out
shear tension shear tension strength
kN kN kN kN kN
13.68 9.90 4.43 26.55 30.13
21.37 15.46 6.91 41.49 46.31
30.78 22.27 9.96 59.75 62.90
54.72 39.59 17.70 106.21 93.26
Effective length, Le = C + A + 8*Bolt diameter - Bolt radius
NOTE:
4. Pull out strength is based on 28 days
1. Shear and tension loads based on gross concrete compressive strength 2.07 kN/cm2
nominal area of bolt. 5. Pull out strength is calculated as per ACI
2. Allowable loads are including combined (American Concrete Institute) Building Code 318.
shear and tension. 6. Bolt specifications based on AISC 2005
3. Stress Increase of 33% is NOT ALLOWED Edition.
ANY MORE.
REV DT 1 07/06/05 07/12/05

78
5.23 ASTM A325 HIGH
STRENGTH BOLTS
COMPONENT SECTION
PROPERTIES & LOAD TABLE
H BOLT LENGTH

Specifications:

Bolts, Nuts & Washers Finishing


Electro-Galvanized ASTM F 1135M Grade 1
Bolts Specification
Heavy Hex Structural ASTM A325M Type 1
Nuts Specification
Hex ASTM A 563M 10S
Washers Specification (Washers/Bolt)
Hardened Flat ASTM F 436M Type 1

For Detailers: 3 ERECTION


TOLERANCE
GRIP
List the Bolt, Nut and Washers Seperatly in Shipper
L = Grip + 3 + W + R + N
List Threads Length = L - (Grip + W) + R
Add 2% extra (Minimum Extra is 2 Bolts) N = 1 dia H = 0.7 dia

Bolts W Min-Max Grip (3 mm Building Allowable Forces


Installation Tolerance)
Nom Bolt Threaded Threads Nom Max Max Combined
Dia Length Length Pitch Thick 0 10 20 30 40 50 60 70 120 Tension S. Shear Tension
mm mm mm mm/Thr mm KN KN KN
18
12 40 Full 1.75 35.06 18.66 10.52
29
16 55 Full 2.00 3.10 62.33 33.18 18.70
39
20 70 Full 2.50 97.39 51.84 29.22
38
75 Full
24 3.00 4.0 58 140.24 74.64 42.07
95 Full
75
30 120 Full 219.12 116.63 65.74
3.50 4.50 73
32 120 Full 249.32 132.70 74.80

* Maximum Grip (including 3mm tolerance) = Bolt Length - 3mm Erection Tolerance - 1 Washer - 1 Nut - (2 x Threads)
X Y Z
117771777ZZZJ:. :1
X: Minimum Grip For Combined Tension and Shear refer to Table J3.2,
Y: Maximum Grip inluding 3mm erection tolerance and equations:
Z: Maximum Grip excluding 3mm erection tolerance (J3-2), (J3-3a), (J3-3b) from the AISC 2005 Edition

79
5.24 STANDARD CRANE SYSTEM

General:
on center, lathed toa diameter of 200 mm, and
The kirby standard crane system is a single properly aligned in a uniaxial direction, and
girder, pendant operated, top running system equipped with derailment protection suitable
which includes a structural bridge member for travel along rails (aisc 30 lb. Rail) which
fabricated by kirby building systems, and electro- are mounted on crane runway beams which in
mechanical components fabricated by selected turn are supported on shop welded brackets
vendors and supplied as a complete Package. to the frame columns. The rails are aligned by
hook bolts which interlock the flange of the cap
Crane bridge: channel of the crane .Runway beams and through
the adjusting nuts on. Either side of the rail neck.
The structural design of the crane bridge
conforms to the allowable stresses as defined Hoist and trolley:
in the american institute of steel construction
manual. The crane bridge is designed for the The hoisting trolley moves along the bonom
Crane capacity magnified by 10% for impact, flange of the crane bridge, and has special
and the total weight of bridge, hoist and trolley. mounting at which the hoist is bolted. The hoist
Deflection under total load is limited to 0.001 Of is a low headroom type to allow greater lifting
span. The ends of the crane bridge are prepared heights needed particularly in low spaces. The
with special connecting plates which are bolted hoist capacity is rated in accordance with fem
to the end carriage. Field welding is required 1am (federation europeenne de la manutention)
for the connection of bridge to end carriage standards which is based on load spectrum
and for bridges of spans larger than 12m require (% lifting load per % time), average operating
field welded splice to be performed under high time per day, daily working time and starting
quality control to ensure full penetration welds. frequency, and as shown on the following page .
Maximum span supplied with the standard end
carriage is 21 m to control grabbing.
Crane runway beams:
End carriage:
The crane runway beams are oriented in the
longitudinal direction of the crane travel and
The end carriages are made of reinforced consist of h-sections with cap channels, designed
welded box sections. Each end carriage is for maximum combinedstresses generated from
equipped with its separate travelling machinery maximum wheel loads positioned at critical
to eliminate the drawback of a long oscillating locations and acting vertically and Horizontally.
drive shaft. Motors are totally enclosed. The maximum wheel load is magnified by 10%
Insulation class f, protection ip54. The end for impact. The horizontal load is generated from
carriages come with double flange wheels, .3.4M 20% of the sum of the crane capacity and the
weights of hoist and trolley.

80
5.25 STANDARD CRANE
SYSTEM TYPE K
CLEARANCES & WHEEL LOADS

K I. THE LONGITUDINAL FORCE APPLIED


AT THE TOP OF RAIL, AT EACH WHEEL.
K II. THE LATERAL FORCE OF CRANE RUNWAY DUE TO
EFFECT OF MOVING LOAD AT THE TOP OF RAIL,
AT EACH WHEEL.

Crane C E1 E2 Span of H Wheel loan KD


Capacity M.t. mm mm mm Bridge mm Dyn.max Ki Kii
6 500 21.0 2.1
9 500 23.9 2.39
12 500 26.2 2.62
3.2 660 740 825 1.74
15 750 31.3 3.13
18 750 31.3 3.13
21 800 32.0 3.20
6 500 30.4 3.04
9 500 34.4 3.44
12 500 37.3 3.73
5.0 590 815 790 2.65
15 750 40.7 4.07
18 750 43.2 4.32
21 900 43.6 4.36
6 600 59.9 5.99
9 600 64.2 6.42
12 600 68.0 6.80
10.0 685 1015 1110 5.32
15 850 72.0 7.20
18 900 75.8 7.58
21 1000 77.5 7.75

81
5.26 STANDARD CRANE
SYSTEM TYPE K HOIST
DETAILS

Crane Hoist Hoist Ht. Hoisting Cross Dimensions


capacity type Wt. Lift speed travel speed A B C D L
M.t. Kg M M/Min M/Min mm mm mm mm mm
3.2 1221G 340 8 8 20 108 480 660 950 910
5 1441F 400 8 5 20 108 535 590 950 1080

Crane Fem Hoisting motor Wire rope


Capacity M.t. group K.W. % ED NoS. DIA. mm
3.2 1 AM 4.5 30 2 10
5 1 AM 4.5 30 4 10

D NOTE :
-l I A. THE TRAVEL SPEED BY 2 STEP POLE
! CHANGE MOTOR.

Crane Hoist Ht. Hoisting Cross Dimensions


Capacity Hoist Wt. Lift speed travel speed A B C D L
M.t. type Kg M M/Min M/Min mm mm mm mm mm
10 2441B 850 8 4 20 125 670 685 820 1255

Crane Fem Hoisting motor Wire rope


Capacity M.t. Group K.W. % ED NoS. DIA. mm
10 1 AM 7.5 50 4 14

82
------------------~'
5.27 STANDARD CRANE
SYSTEM TYPE K END
CARRIAGE DETAIL
L3

Electrical Specifications:

( FOR 3.2 T , 5.0 T & 10 T )


1. Motor voltage - 380v i 440v
r CRANE BRIDGE

2. Control voltage - 220v


3. Frequency - 3 phase, 50 cis 60 cis r'.s.~~. . ~'! -tl I 40

4. Push button pendant control I


IH
t lt l1 t i1 H1
l L .1 l I
I' I d J _j_ fOP OF RAIL
"J~~Jij;U1_:;
I.

'
-
~--- RAIL ASCE 30Lbs
r l
t----CRANE BEAM

CRANE BRACKET

Type L L1 L2 L3 D H H1 B Long travel speed


M / Min
USP 3680 3400 140 3820 200 325 300 200 32 AND 10
206

83
5.28 STANDARD CRANE
SYSTEM TYPE K LOAD
SPECTRUM
Fem group Fem 1Am I Fem 2Am I Fem 3Am
load spectrum Operating time Hours / Day
LIGHT < =4 4-8 8-16
100
Light
0
<(
g 33 -,'----1
10 -
1
-- -- ~
-
n so 100
TIME 0
/o

MEDIUM < =2 2-4 4-8

~:bo
Medium
~46.7 -L..
<( ; -~
0 2 .,. . ~- ..
..J , ~-1 : 5~.1 100
33.4
TIME t.

HEAVY <= 1 1-2 2-4


Heavy

Severe SEVERE < 0.5


= 0.5-1 1-2
100 1 - - - - - - - ,
8(} - - - - . -

~
g
I
I
90 100

RATED REDUCED REDUCED


CAPACITY CAPACITY CAPACITY
EQUIVALET CRANE
CAPACITIES (TONS)
3.2 2.5 2.0
FOR HIGHER FEM GROUP
CLASSIFICATION 5.0 4.0 3.2

10.0 8.0 6.3

84
5.29 SERVICE LOADS
HANGING DETAILS &
ALLOWABLE LOADS
Service loads may be suspended from the Kirby roof for roof slope upto 10%. Multiple suspended loads
purlins provided that the intensity and location of shall be equispaced in a bay.
these loads are predefined at time of sales. Only suggested suspension details as shown should
For standard buildings, where service loads are not be used to prevent localized buckling of purlins. For
precalculated, the suggested hanging details and heavier auxiliary loads, additional framing members
maximum allowable suspended load table may be will be needed.
used for a specific bay length, purlin size and lap, and The suspension angles and fasteners are not supplied
number of suspended loads per bay. by Kirby.
The recommended suspension details are intended

E . I. Eq.
1
i
t
~
... LAP 4
I '
t
' I
1
'

tp tp A tp . rp

,l BAY
MAIN FRAME RAFTER I
SECTION -A

Maximum allowable suspended load, p ( kg), in addi-


tion to Roof live load of 0.6 Kn / m2

Bay spacing (meter)


6.0 7.5
Purlin Lap
No. of loads / bay No. of loads / bay
1 2 3 4 1 2 3 4
200 Z 107 65 45 30 25 0 0 0 0
1.5
706 130 95 65 50 30 20 15 10
107 140 100 70 55 40 30 20 15
1.8
706 245 180 120 100 105 80 50 45
107 275 205 135 110 145 105 70 60
2.5
706 445 330 220 185 245 185 120 100 I

85
5.30 VENTILATION
CALCULATION

The number of standard Kirby ridge ventilators and Procedure:


louvers can be determined from following proce-
dure based on a given unit of air changes and known
building geometry.
Using the following nomograph, draw a line con-
necting the known value of air changes per hour
Building volume: and the volume of the building to get the rate of
air flow (cfm-m3/min). Then draw a line connecting
the determined value of the rate of air flow and the
V = W X L X (EH + WS/40) stack height (sh) to find the length of ridge ventilator
W = SPAN, L = LENGTH required, divide the length of ridge ventilator by 3m
EH = EAVE HEIGHT to get the number of kirby standard ridge ventilators.
S = ROOF SLOPE IN TERMS OF 10 Wall openings ( louvers, doors and windows) must be
provided and well distributed. To ensure air inlet and
proper ventilation cycle for each linear meter of ridge
ventilators, one square meter of wall opening for air
Ventilation rates for types of building: inlet is required.

If the required air changes cannot be achieved using


Type Of Building Air Changes / Hour natural ventilation as above, forced ventilation using
power vents may be provided: consult head office
Boiler house/engine room 15-30 for details. Refer to accessories for Kirbys standard
Living quarters, rooms & louver and ridge ventilator details.
wards 15-20
Classrooms, canteen 5-15
Offices, commercial shops,
factories 5-10

86
5.31 VENTILATION
CALCULATION NOMOGRAPH

AIR CHANGES MINUT ES PER


NOMOGRAPH
PER HOUR AIR CHANGE
2-,::- 30
For Determining Ridge Ventilators / Louvers
LENGTH OF RIDGE VENTILATOR
VOLUME (12" THROAT SIZE)
(Ft 3 ) (M~) C FM . M3/MIN. ( F t.) (M. )
1 000 000 26 316
900000
600 000 22 654
700 000
4 15 10 000 000 2 63166 10 000 3 048
600 000 16990
6 000 000 6 000
500 000 6000 1 826
169 900
400 000 11327
113 267 4 000 1220
6 10
300 000 8 495
9
6 56633 2000 609

200 000 5 667

10 6 26 316 1000 304 8


600
12 5 16990 600
100 000 2 632
11 327 90 000 400 122
15 4 80 000 2 265
70 000
200000 5 663 60 000 1700 610
3
50 000

100000 2 632 40000 1132 100 305


80000 60
2 60000 1700 30 000 60

40000 1132 40 122


20000 566 30

20000 566 20 61

10000 263 10 000 2&3 10 305

STACK HEIGHT~
(F-t) (M} * Stack Height Is Actual
Distance From Top Of Inlet
5 15 15 4-6 Sill To Elevation Of
Ventilator Stack Effect Is
Based On 15F Temperature
Differential.

20 61
25
30
40 122
50 15-3

87
5.32 KIRBY INSULATION
( KIB-12) INSTALLED U
VALUES

Column

AT ROOF

AT WALL

At roof with 50 mm insulation At wall with 50 mm insulation


Element Construction Resistance R Element Construction Resistance R
1 Outside surface 0.25 1 Outside surface 0.25
(7.5 Mph wind) 2 Wall sheeting 0.00
2 Roof sheeting 0.00 3 Insulation 50 mm 6.79
3 Insulation 50 mm (@100f) 6.79 4 Air space 0.52
EXAMPLE :
4 Air space 1.62 5 Liner 0.00
5 Liner 0.00 6 Inside surface (still air) 1.35
6 Inside surface (still air) 1.10 Total 8.91
Total 9.76

INSULATION INSTALLED VALUES:

AT ROOF WITH 50mm INSULATION AT WALL WITH 50mm INSULATION


U= 1= 1 = 0.102 BTU / HRFt2F U= 1= 1 = 0.112 BTU / HRFt2F
= 0.500 K Cal / HR M C
2
= 0.548 K Cal / HR M2C

Table of insulation installed values


Thickness of U values
insulation At roof At wall
mm K cal / hr m c2
Btu / hr ft f
2
K cal / hr m c
2
Btu / hr ft2 f
50 0.500 0.102 0.548 0.112
75 0.371 0.076 0.397 0.081
100 0.295 0.060 0.311 0.064
150 0.215 0.044 0.220 0.045

88
5.33 ROOF LIGHTING
REQUIREMENTS
Recommended roof lighting: ....:
z
Daylight factors recommended for diferent activities ~
(/) 3 \
are shown in table below: z \
0
u \
In order to obtain the net area of skylights required,
apply a multiplication factor from the
graph to cover variations in wall to floor area ratio and
z
0
.....
<t 2 \
""'~1--- 1---
Very dirty

u ~----' ;-r-- Industrial


location.
To allow for possible change in the use of a building, a
c[
.....
~ I
Clean
daylight factor below 5 % is not recommended. Also ..J "I-- 1'--
::> I
any required daylight factors above 10 % should be ~ _l
supplemented by local artificial lighting. This minimis- OS 1.0 1.5 2.0 25 3.0
es the heat transmission from sunlight. FLOOR ARE~
WALL AREA

Operation or type of building recommended %


Daylight factor
Warehouses, packing, large assembly heavy forging or casting, 2.0
sawmills
Ordinary bench and machine work, average general lighting, fine 4.0
casting, motor repair, general office work, Indoor tennis.
Drawing work, medium assembly, weaving. small type setting. 6.0
Small inspection and assembly.
Small bench and machine work. 10.0

EXAMPLE :

Building in an industrial area of 30m span x 60m


long x 8m eave ht.
Used as a weaving mill.
Floor area = 30x60 = 1800m2
Wall area = 8x180 = 1440 m2
Floor area = 1.25
Wall area

From table, daylight factor = 6 %


From graph multiplication constant = 1.9
, . Net area of lighting required = 1.9X6x30x60 = 205 m2
100
Approx. net area of one skylight (3305 lg) = 3 m2
No. of skylights required = 205/3 = 68.33, Say 70 nos.
Use 70 nos. Skylights evenly distributed on each
roof slope.

89
5.34 ROOF DRAINAGE
CALCULATIONS
Drainage calculations: Valley gutters:

The assumed standard rainfall to be used on Kirby Since it would be undesirable to have valley gutters
buildings shall be as follows: overflow even on extreme conditions.
The value of 12 inches per hour shall be used unless
Eave gutters: otherwise specified. The following
appropriate design coefficients may be used to obtain
the size of the gutter.
Since it would not normally cause trouble to have the 12 In/hr = 2.35 Sq. In of valley gutter per
eave gutter overflow under extreme conditions. = 100 sq.ft. of roof area
drained
The value of 7 inches per hour shall be used unless
otherwise specified. The following approximate design
Down spouts:
coefficients may be used to obtain the size of the
gutter. Standard downspouts are provided along each
7 In/hr = 1.66 Sq. In. of eave gutter per 100 sq. ft. of sidewall at spacing as recommended on roof drainage
roof area drained. reuirements have been based on formula derived by
The Copper Development Association Inc. From
tests conducted on level gutters at the U.S. bureau
of standards in washington D.C. The formula are as
follows:

= 28/13 16/13
DOWNSPOUT S (U) (M)
(0.4810 28/13 (W1/43200) 10/13

WHEN GUTTER CAPACITY GOVERNS
OR S = 1200A
WI WHEN DOWNSPOUT CAPACITY GOVERNS

Where S = downspout spacingin feet


U = average width of gutter (ft)
M = depth/width of gutter
W = width of area being drained (ft)
I = maximum intensity of rainfall (in/hr)
A = area of downspout (sq.In)

The following approximate design coefficient may be used to calculate size of downspouts.

7 1/2 In/hr = 187.5 Sq.Ft. of roof area drained per so. In of downspout area.

90
5.35 FIRE PROTECTION
SYSTEM
Fire resistant coating mandoval p20 or equal can be
applied to Kirby steel structure to achieve a given fire
rating. Applied by spray, it provides a monolithic tex-
tured finish and has good in sulation, sound absorp-
tion and bonding properties. The material is factory
Pre-mixed and consists of vermiculite and portland
cement. It does not spall or crack under impact and
also highly resistant to both hot and cold thermal
shocks. Mandolite p-20 contains no asbestos or fibre
content and presents no known health hazard during
or after application. An alkali resistant paint is applied
to the main frames to receive the coating and on gal-
vanised surfaces no special paint is required.

Physical properties (Mandolite p-20)

Density - 320 kg/m3


Bond strength - to bare steel 62 kn/m2
To galvanised steel 59 kn/m2
Compressive strength - 380 kn/m2
Ph value - 12 -12.5
Thermal conductivity - 0.078 Kcal m/m2 hr c

..----------EXT WALL SHEETING

ROOF SHEETING

PURLIN
~+---G ALVAN I ZED
LINER
COLUMN

...
:-i : GALVANIZED
LINER

H---FIRE RESISTANT _ _ _ ___J

COATING ( MANDOLITE P-20


OR EQUAL) '-----RAFTER

SECTION - 'A- A' SECTION - ' B - B '

91
5.36 BUILDING MATERIALS
WEIGHTS
Materials weight Materials weight
Psf kg/m2 PSF kg/m2
Ceilings Roofs
Channel suspended system 1 4.9 Kirby-rib 26g 1 4.8
Accoustical fiber tile 1 4.9 Kirby-rib 24g 1.2 5.9
Partitions 3-Pl y ready roofing 1 4.9
Clay tile 3-Ply felt & gravel 5.5 26.9
31 IN. (76MM) 17 83.0 5-Pl y felt & gravel 6 29.3
4 IN. (100MM) 18 87.9 Shingles
Wood 2 9.8
6 IN. (150MM) 28 136.7
Asphalt 3 14.7
8 IN. (200MM) 34 166.0
Clay tile 9-14 43.9-68.4
10 IN. (250 MM) 40 195.3
Slate 1/4 in. (6MM) 10 48.8
Gypsum block Sheathing
21 IN. 9.5 46.4 Wood 3/4 in. (19MM) 3 14.7
31 IN. 10.5 51 .3 Gypsum 1 in. (25MM) 4 19.5
41 IN. 12.5 61.0 Insulation 1 in.(25MM)
51 IN. 14.0 68.4 Loose 0.5 2.5
61 IN 18.5 90.3

}
Poured in place 2 9.8
Wood studs 2x4 (50xl00mm) Rigid 1.5 7.3
12-16 In.(300-400Mm/o.C.) 2 9.8 Walls
Steel partitions 4 19.5 Kirby-wall 26g 1 4.8
Plaster 1 in. (25Mm) Kirby-wall 24g 1.2 5.9
Cement 10 48 Brick
Gypsum 5 24.4 4 In. (100MM) 40 195.3
Lathing 8 In . (200MM) 80 390.6
Metal 0.5 2.4 12 In .(300MM) 120 586.0
Gypsum board 1/2 in. (12Mm) 2 9.8 Hollow concrete
Floors Block ( heavy Aggregate)
Kirby deck-26g 1.1 5.5 4 In . (100MM) 30 146.5
Concrete reinforced 1 in. (25Mm) 6 In. (150MM) 43 210.0
Stone 12.5 61.0 8 In. (200MM) 55 268.6
Slag 11 .5 56.2 12.5 In. (318Mm) 80 390.6
Lightweight 6-10 29.3-48.8 Hollow concrete
Block (light aggregate)
Concrete plain 1 in. (25Mm)
Concrete plain 1 in. (25MM)
Stone 12 58.6
4 IN. (100MM) 21 102.6
Slag 11 53.7
6 IN. (150MM) 30 146.5
Lightweight 3-9 14.7-43.9 8 IN. (200MM) 38 185.6
Fills 1 in. (25Mm) 12 IN. (300MM) 55 268.6
Gypsum 6 29.3 CLAY TILE (LOAD BEARIN)
Sand 8 39.1 4 IN . (100MM) 25 122.1
Cinders 4 19.5 61N. (150MM) 30 146.5
Finishes 8 IN. (200MM) 33 161.2
Terrazzo 1 in. (25Mm) 13 63.5 12 IN. (300MM) 45 219.7
Ceramic tile 3/4 in. (19Mm) 10 48.8 STONE 4 IN. (100MM) 55 268.6
Linoleum 1/4 in. (6Mm) 1 4.9 Glass block 4 in. (100MM) 18 87.9
Mastic 3/4 in. (19Mm) 9 43.9 Windows, glass, frame & Sash 8 39.1
Hardwood 7/8 in. (22Mm) 4 19.5 Struct. Glass 1 in. (25Mm) 15 73.3
Softwood 3/4 in. (19Mm) 2.5 12.2
}
Corrugated cement
Asbestos 1/4 in. (6MM) 3 14.7

92
5.37 CONVERSION
FACTORS
MEASURE TO CONVERT MULTIPLY BY

From TO
Length Inch mm 25.40
Foot meter 0.3048
Micron meter 1.0 X 10-6
Mil meter 2.540 X 10-5
Area Mile meter 1609.30
Yard meter 0.9144
Inch2 mm2 645.16
Foot2 meter2 0.0929
Volume Acres kilometer2 4.04687 X 10-3
Inch 3
meter3 1.638706 X 10-5
Foot meter3
3
2.831685 X 10-2
Gallon (U .S.) Meter3 3.785412 X 10-3
Mass Gallon (U .S.) Liters 3.78543
Gallon (British Imperial) gallon (U.S.) 1.20091
Meter3 liters 1000.0
Pounds kilograms 0.45359
Velocity Metric Ton pounds 2204.62
Metric Ton long ton 0.98421
Metric Ton short ton 1.10231
Foot/hour mile/hour 0.000190
Pressure Mile/hour (U . S . ) Kilometer/hour 1.609344
Or Feet/minute meter/second 0.00508
Stress Miles/hour meter/second 0.44704
Pound force/foot newton/meter2 47.88026
Kg/cm 2
newton/meter2 9.806650 X 104
Kn/m 2
pounds/Foot2 (psf) 20.885
Density Kn/cm 2
kips/in2 (ksi) 1.4504
Kg/mm 2
newton/mm2 (pascal) 9.8066
Pounds/ft3 kg/m3 16.0185
Pounds/inch3 grams/cm3 27.680
Temperature F C (F-32)/1.8
C F (C x 1.8) + 32
BTU/FT2 KCal/m2 2.71
Heat BTU/FT HR F
KCal/m2 Hr C 4.88
BTU/FPHR F
WATT/m2C 5.674466

93
5.38 AIRCRAFT DIMENSION

~ - - - - -----r--

I
I

WL____ - -
Ir -------'-----

~----~~
H

Aircraft
L (m) W(m) H (m)
type
Tupolev
TU-154 154B-2 54.10 44.84 16.50
154M 54.10 44.84 16.50

Aircraft L (m) W(m) H (m)


type
EMBRAER
170 29.90 26.00 9.85
175 31.68 26.00 9.73
190 36.24 28.72 10.57
195 38.65 28.72 10.55
94
Aircraft
type
L (m)
BOEING
W(m) H (m) Aircraft
type l L (m)

AIRBUS
I
W(m)
I
020 41.25 39.90 12.65
600 54.10 44.84 16.50
B707 120B 44.07 39.90 12.93
320B 46.61 44.42 12.93 A300 600F 54.10 44.84 16.50
B717 200 37.80 28.47 8.92 600ST 56.75 44.84 17.24
100 40.60 32.90 10.30 A310 - 46.66 43.90 15.80
B727 200 46.70 32.90 10.30 A319 33.84 34.10 11.76
200F 46.70 32.90 10.30
A320 A320 37.57 34.10 11.00
100 28.65 28.35 11.23
200 30.53 28.35 11.23 A321 44.51 34.10 11.76
300 33.40 28.90 11.10 200 58.82 60.30 17.39
B737 400 36.40 28.90 11.10 A330 200F 58.82 60.30 16.88
500 31.00 28.90 11.10 300 63.69 60.30 16.83
600/700 31.20 34.30 12.60
300 63.69 60.30 16.91
800/900 42.10 35.80 12.60
100B 70.60 59.60 19.30 200 59.40 60.30 16.80
A340
200B 70.60 59.60 19.30 500 67.93 63.45 17.28
B747 300 70.60 59.60 19.30 600 75.36 63.45 17.22
400/400ER 70.60 64.40 19.40 800 60.54 64.75 17.10
8I 76.25 68.50 19.40
A350 900 66.89 64.75 17.10
200 47.32 38.05 13.56
B757 200F 47.32 38.05 13.56 1000 73.88 64.75 17.90
300 54.47 38.05 13.56 A380 800 72.72 79.75 24.09 I

200 48.50 47.60 15.80


200ER 48.50 47.60 15.80
300 48.50 47.60 15.80 Aircraft type L (m) W(m) H (m)
B767
300ER 48.50 47.60 15.80 Comac
300F 54.90 47.60 16.00 C919 - 38.90 35.80 11.95
400ER 61.40 51.90 16.80 700 33.50 27.30 8.40
200 63.70 60.90 18.50 700ER 33.50 27.30 8.40
ARJ21
200ER 63.70 60.90 18.50 900 36.40 27.30 8.40
200LR 63.70 64.80 18.60 900ER 36.40 27.30 8.40
B777
Freighter 63.70 64.80 18.60
300 73.90 60.90 18.50
300ER 73.90 64.80 18.50 Aircraft type L (m) W(m) H (m)
8 57.00 60.00 17.00 Canadian regional jet
B787
9 63.00 60.00 17.00 Bombardier crj-1000
39.10 26.20 7.10
Aircraft type L (m) W(m) H (m) I I I
ANTONOV
100A 29.10 28.90 87.30
AN-148 100B 29.10 28.90 87.30
100E 29.10 28.90 87.30 I
Aircraft L (m) W(m) H
type (m)
Sukhoi
SSJ 95 29.80 27.80 10.30
Superjet 100
SSJ 95LR I 29.80 I 27.80 I10.30

95
6 : ACCESSORIES
6.1 WALK DOORS

Specifications:

Doors are fabricated from electro-galvanised Standard sizes are 914 mm wide x 2134 mm high
steel (20 gauge), with a solid core of rigid (ref 3070 M or G) single swing doors and 1830
polyurethane insulation: Doors are provided mm wide x 2134 mm high (ref 6070 M or G)
either all metal (ref M), or with opening for glass double swing doors. All universal swing type. All
(ref G). Glass and glazing are not supplied by doors shop painted one coat vinyl based. neutral
Kirby. grey primer.

Each single door is supplied complete with one Availability:


cylindrical lock, double doors have a cylindrical
handle also. Panic hardware is available on special order as
are removable mullions for 6070 doors where
both leaves are active.

For standard details refer Installation Drawings.

96
6.2A SLIDING DOORS

Specifications:
1. Doors are located in increments of 167mm
All structural components are from cold formed The maximum dimension a single slide door
steel sections. with panels on the outerface, can extend beyond the jamb is the door
to match with the building walls. Doors will be width + 167mm.
provided with liner if the building has also K.R. 2. The maximum dimension a double slide door
liners. can extend beyond the jamb is half the door
width+167mm.
Doors are suspended by top track system within
3. No doors or windows may be located within
a header assembly and fitted with guides only at
operating limits of slide doors.
the base.
4. Doors are not operable beyond the corner of
Single sliding door height available 3000(M), the building, nor within 500mm of the corner
3500(M), 4000(M), 4500(M), 5000(M), of a side wall with down spouts.
5500(M) Door width available 3000(M), 5. A maximum of one door may be located in each bay.
4000(M), 5000(M), 6. Jamb to header member connections must
be field drilled, girt and base angles must be
Double sliding door height availability 3000(M), field cut.
3500(M), 4000(M), 4500(M), 5000(M), 7. Slide direction for single slide doors must
5500(M) 6000(M) double width available always be specified.
3000(M), 4000(M), 5000(M), 6000(M) 8. For single slide door details refer Installation
Dwg. 7.10
Availability: 9. For double slide door details refer Installation
Dwg. 7.10
10. For slide door details in masonry walls refer
The following parameters should be followed: Installation Dwg. 7.10

97
6.2B SLIDING FOLDING
DOOR

Description:

Kirby Sliding Folding Doors (KSFD) consist of without additional structural framing
1040 mm leaves suspended and connected in and additional cost.
a manner in order to move by folding against Track header is concealed without additional
each other and designed to have maximum clear flashing.
opening with minimum occupied space. Aluminium and neoprene strip are provided
for tight closure to prevent the penetration
Door leaf is covered with KR, KW, KCS or KC of light and dust from outside
panels with standard colors. The width of the Bottom guide can be set after the door is
opening is minimum 3.5 m and maximum 16 m; erected to provide a better alignment
in excess of 16 m width, floating door units are Variety of profile colors is available for door
used. sheeting.
Easy to relocate and reinstall with minimum
Features: foundation cost

K SFD provides a large clear opening with


easy movement
Doors are supported on top guide roller
assembly
Leaf frames are manufactured and shipped Kirby Building Systems reserves the right to
with ready to erect condition make changes without prior notice
Track headers are manufactured from built- KBS-KSFD-120911-00
up members that are very easy to install

98
--------------------------~'
Material Specification:

Specific Yield stress of steel, Fy = 34.5 kN/cm2 (ASTM A792 grade 50)
Door leaf frame 100 mm x 50 mm channel (pre-galvanized) with thicknesses 1.75,
2.0 and 2.5 mm
Top guide LG-305 Kirby standard door guide
Door Guide Brackets 3A-305 and 3A-305C Kirby standard support brackets
Hangar Trolley Kirby standard hanger trolley designed to turn 360
Bottom roller Kirby standard 104P /97
Bottom guide Kirby standard channel guide 97P /3000 with channel lugs and
universal coupler
Hinges Heavy duty hinge
Panels KC panels (333 coverage), KR, KWand KCS panels (1000 mm
coverage)
Top stud roller Top stud roller assembly with bronze bush

DOOR STOPPER BOTTOW GUIDE CHNL DOOR STOPPER


0 OPEN CONDITION 0 OPEN CONDITION

Plan showing door @ closed condition

Detail of door leaf with top guide Detail of door leaf with bottom guide
Kirby building systems reserves the right to make
changes without prior notice Kbs-ksfd-120911-00

99
6.3 ROLL-UP DOORS -
MANUALLY OPERATED

IJ
OUTSIDE
220 DOOR WIDTH 520

..., X
I

c r::o

[_
INSIDE ~X HEADER
~
::1:
(!)
iii
PLAN ::1:
0::
0
0
Q

FIN. FL. LVL.

VIEW X-X

Door height (m) A (mm) B (mm) C (mm) D (mm)


3.0 50 610 580 640
3.5 40 620 580 640
4.0 30 630 580 640
4.5 20 670 600 690
5.0 - 690 600 690

Standard door sizes


DOOR WIDTH (M) DOOR HEIGHT (M)
3.0, 4.0 3.0,3.5, 4.0, 4.5, 5.0
5.0 3.0, 3.5, 4.0

100
6.3 ROLL-UP DOORS -
ELECTRICALLY OPERATED

OUTSIDE
r
200 DOOR WIDTH
420 ~X
JAMB __f.STEEL LINE

CURTAIN.

------ -----
CURTAIN SHAFT ,_;
:I:
INSIDE !:2
c UJ .
J:
cr
0
0
0
PLAN JAMB

FIN . FL.LVL.

VIEW X- X,I

Door height (m) A (mm) B (mm) C (mm) D (mm)


3.0 380 650 590 660
3.5 350 660 590 660
4.0 340 670 590 660
4.5 485 680 680 690
5.0 465 680 680 690
5.5 455 710 700 730
6.0 445 730 700 730

I Standard door sizes


Door width (m) Door height (m) Motor
3.0, 4.0 3.0,3.5, 4.0, 1 H.P.
4.0 4.5,5.0, 5.5, 6.0 2 H.P
5.0, 6.0 3.0,3.5, 4.0, 4.5, 5.0,6.0 2 H.P

POWER SUPPLY: NOTE:


1 H.P. -{220/380 V.
3-50/60 Hz.
2 H.P. -{220/460 V. Operating voltage to be furnished, while
3-50/60 Hz. ordering the electrically operated roll-up door.

101
6.3 ROLL-UP DOORS -
CLEARANCES
A. Doors in a sidewall:

t1000t ~ II
I
- I
I
i - I I
I I I
i I I
:EAV E
DOOR I DOOR 1 - -E NDW.bli.
I HEIG HT OPENING I OPENING I STEEL
I I LINE

l_
I I
I
I
I I
I I
l .1

~ BAY LENGTH
p,sg 7sqj
1
BAY LENGTH
~~
l INTERIOR BAY I END BAY

B. Doors in a light (bearing) endwall:

DOOR DOOR
OPENING OPENING

t--t--LONGER WIND SHORTER WIND


COLUMN COLUMN

5
WIND COL. COL . SPACING

INTERIOR BAY END BAY

C. Doors in a main frame endwall:

DOOR DOOR
OPENING OPENING

LONGER WI NO
COLUMN

INTERIOR BAY EN 0 BAY

Dimensions are determined per job to ensure


that drive system and fittings clear main
frame.

102
6.4 INSULATION

Physical Properties:

Type - KIB / 12
Density - 12 Kg / M3

Thermal properties
Mean temp. K U (Btu / Ft2 Hr of)
Deg. F. Btu In/Ft2 Hr of 50mm 75mm 100mm 150mm
50 0.27 0.137 0.091 0.069 0.046
100 0.29 0.147 0.098 0.074 0.049
125 0.34 0.173 0.115 0.986 0.058
150 0.39 0.198 0.132 0.099 0.066

Conversion factors:

1 Btu ft2 hr of = 4.88 K cal / m2 Hrc

= 5.67 W / m2 c

103
6.5 ROOF CURB

Specifications: Design:
Curbs shall be a one-piece construction The top of the curb provides a level surface at the 1:
manufactured from a self-extinguishing glass fiber 10 roof slope.
reinforced polyester, 3mm thick, with 15 mil polyester
gel coated weathering surface on exterior. Unit shall The upper end of the monolithic panel of the curbs
be white in colour and opaque to light. Base shall is reduced in thickness to 2 mm to provide nesting
have the same configuration as the Kirby Rib profile. under the above splice panel. The upper end splice
portion may be cut off to install the unit as a patch on
Availability: an existing roof.

The roof curbs are designed for installation on Kirby


rib profile. Care should be taken in using either
type unit in areas where the temperature exceeds
93 degrees C. as the strength of the unit will be
reduced.

CURBED OPENING DIMENSIONS


Curb Size Curb height Adapter Panel Weight (Kg)
Dimensions
Front(min) Back(min) Width Length
1200 x 1200 360 mm 240 mm 1667 mm 1700 mm 21.00 max.
900 x 900 330 mm 240 mm 1334 mm 1700 mm 17.00 max.
600 x 600 300 mm 240 mm 1000 mm 1700 mm 13.50 max.

104
6.6 ROOF JACK

Specifications: Design:

Roof Jacks shall be a one-piece construction manufac-


tured from.a self-extinguishing glass fiber reinforced The upper end of the monolithic adapter panel of
polyester, 3 mm thick, with 15 mil polyester gel coated the curbs is reduced in thickness to 2 mm to provide
weathering surface on exterior. Unit shall be white in nesting under the above splice panel. The upper end
color and opaque to light. Base shall have the same splice portion may be cut off to install the unit as a
configuration as Kirby rib profile. patch on an existing roof.

Availability:

The Roof Jacks (all sizes) are designed for installation


on Kirby rib profiles. Care should be taken in using
either type unit in
areas where the temperature exceeds 93 degrees C
as the strength of the unit will be reduced.

Roof Jack Dimensions


Opening size Jack height Base dimensions Weight (Kg)
Width Length
50mmt0100mm 265mm 334mm 500mm 2.25 MAX.
150mm to 300mm 290mm 667mm 700mm 4.00 MAX.

105
6.7 WINDOWS

Sliding windows
( Aluminum )

Specifications: Availability:

All structural members are from extruded Windows are self flashing if located at a standard
aluminium, with a minimum thickness of 1mm. location within K.W. panel. When using multiple
Windows are single slide; supplied preglazed units to form continuous
with clear glass and complete with half insect
screen. windows, jamb fins are butted together and pop
riveted.
Standard, nominal window size is 1m wide x 1 m
high. For standard location of windows refer to
standard building installation Dwg. No. C-18.

106
6.8 LOUVER

6.8A ADJUSTABLE LOUVER


Specifications: Availability:

Louver frames are fabricated from 1.2 mm Single unit is self supporting and self flashing
thick (18 gauge) galvanized steel with 0.9 thick when used with K.W.panel only. When using
(20 gauge) galvanized steel blades. Blades are multiple units, with K.W. panel, to form
adjusted by use of a hand crank. All louvers are continuous louvers supporting jambs are
complete with bird screens. Finished color of provided.
louvers is white.
For use with K.R., supporting jambs are provided
for both single and continuous louvers. For
standard location of louvers refer to Installation
Details.

107
6.8 B. SAND TRAP LOUVER

!i

~l-~- ~ 0
0
0
E
E

. ,
l rn
N
oCJ
E
E

111
0
0

-- . -----
~

. . ...... -... - ........


Sand trap louver - data sheet
Description:
The specific yield stress for steel = fy = 34.5
The sand trap louver is recognized by kirbys
Kn/cm2 as per astm a792 grade 50.
Standard designation as: stl 1000 or stl 2000
Since it can be produced with a 1 m or 2 m
Height. Engineering and performance data:
U - shaped profiles are placed alternatively in a
vertical configuration allowing sand and heavy
dust separation. These vertically arranged Effective area factor.
sections and the opening at the bottom ensure
that the sand trap louver is self-cleaning and Air flow rate
maintenance free.
The sizes of the stl 1000 and stl2000 are 1.0 Vf - face velocity (m/s)
M height x 1.0M width and 2.0 M height x 1.0M L sand trap louver length (mm)
width, respectively. The stl is available in 24 H sand trap louver height (mm)
Ga (0.6 Mm) steel only.

Air flow rate values in I/s For STL 1000 and STL 2000
H 1000 2000
L
Vf = 1.0 Vf = 1.5 Vf = 1.0 Vf = 1.5
1000 254 382 554 832

Filtration Efficiency :
For normal operation conditions, Sand Trap Louvers
The filtration performance is dependant on the dust used for natural ventilation purpose are rated at a rec-
type and the velocity of the air. ommended Face velocity not exceeding 1.0 - 1.5 m/s.

Partical size range Approx. Filtration efficiency in (%)


@ 1.0 m/s @ 1.5 m/s
350-700 80 75
75-700 55 35

108
6.9 TRANSLUCENT PANELS

333.333 333.333 333.333

111.111 111.111 I 32
____I

CROSS SECTION

Skylights and wall lights: Translucent panels:

Made of translucent GRP to match Kirby roof and wall Skylights and wall lights are translucent corrugated
panels, with an estimated light transmitting capacity sheets matching the profile of kirby-rib and kirby-wall
of 60%. sheets respectively. The translucent sheets are made
from glass fiber reinforced polyester structural plastic
panels and provide an economic form of general pur-
pose natural lighting.

109
6.9 TRANSLUCENT PANEL

Specifications: Mechanical Properties:


Thickness = 1.5 mm Tensile Strength = 8.7 kN/cm2 (ASTM D638)
Covering Width = 1 m Compressive Strength = 16.2 kN/cm2 (ASTM D695)
Standard Length = 3.305 m Flexural Strength = 13.83 kN/cm2 (ASTM D790)
Light Transmission = 60% (ASTM D1494) Flexural Modulus = 728 kN/cm2 (ASTM D790)
Solar Transmission = 35% (ASTM E424) Shear Strength = 10.34 kN/cm2 (ASTM D732)
Infra-red Transmission = <10% (ASTM E424) Barcol Hardness = 40 to 60 (ASTM D2583)
Impact Strength = 470 J/m (ASTM D256)
Physical Properties:
Density = 1431.9 kg/m3 (ASTM D792) Thermal Properties:
Water Absorption = <0.25% (ASTM D570) Thermal Transmittance (U Value) = 5.7 W/m2.K
(ASTM C518)
Operating Temperature: Linear Thermal expansion Coefficient = 1.6 x 10 -6 / F
The parameter is -30 C to + 75 C (ASTM D 696)

Panel Structural Properties:

Pull out
Fastener Data Sheet Purlin Thickness (mm) 1.50 1.75 2.00 2.50
Ultimate Pull Out (kN) 1.16 1.83 2.09 2.32

Base Material Thickness Covering Weight Area Full Elastic


(mm) width (kg/m) (cm2) section modulus (E)
(mm) (Ix) (cm4) kN/cm2
Fibre Glass 1.50 1000 2.387 17.17 15.82 718

Allowable Uniform Loads kN/m2):


Thickness Span in Meters
(T) No. of Load
(mm) Spans Case 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50

1.5 D+L 2.99 1.92 0.99 0.57 0.36 0.24 0.17 0.12
1 WP 2.99 1.92 0.99 0.57 0.36 0.24 0.17 0.12
WS 2.99 1.92 0.99 0.57 0.36 0.24 0.17 0.12
D+L 1.96 1.31 0.93 0.69 0.53 0.42 0.34 0.28
2 WP 1.96 1.31 0.93 0.69 0.53 0.42 0.34 0.28
WS 1.96 1.31 0.93 0.69 0.53 0.42 0.34 0.28
The Allowable loads for winds are without 33% NOTE:
increase
D+L - Dead + Live Load WP - Wind Pressure Skylights are not designed for walk-on. Building
Load WS - Wind Suction Load installation/ maintenance staff should avoid
Allowable Deflection = Span / 45 crawling boards walking on the skylights else
that span over the skylight must be used.
Kirby Building Systems reserves the right to
make changes without prior notice KBS-SKY-l10811-01

110
----------------------~'
6.10 VENTILATORS

. -

RIDGE VENTILATORS Availability:

Specifications: Continuous ventelators are formed by joining


end skirts together. Providing the building length
is divisible by 3 m, maximum length of ventilator
Ventilators are gravity type, fabricated from
is building length minus 333mm.
galvanized steel sheets, shop assembled with
pop rivets.
Powered Ventilators:
Minimum throat width is 300 mm, with each
complete length being 3m. Manually operated Kirby C whirlwind low silhouette extract
mechanical control dampers are provided, one ventilator with spun aluminum non- return
set for each 6m length of continuous vent or one shutter and one
single vent. Bird screens are also provided. piece base and throat.

Mounted on GRP roof curb moulded to suit


Kirby rib roof panels.

111
6.11 GUTTERS, FLASHINGS
& TRIMS

STEEL
__,____ _ _ LINE

~VI -=---=---=---=---=--""1r
r-

- II
--=:.-

~~ -~~-=r=--
n11
Qr--
11 1111
~c~ ~ ===============II1111111111
II 1111 J\
II lllh-----=---=---=--
230 II II STEEL LINE
-%-li---
EAVE GUTTER MASONRY TRIM

I "' STEEL LINE

-%-li---
EAVE TRIM DRIP TRIM

35

"' "---
F=========
- - ____/'-._ - -

lrlll
I 11:
I 1
I 11
1
1
I 11
1
1111 - --
1 lib=========
150 I I STEEL LINE
~

RAKE TRIM
CORNER TRIM

---~---
EXPANSION TRIM

112
6.12 GUTTERS &
DOWNSPOUTS

S = DOWNSPOUT
S/2 = ONE HALF DOWNSPOUT SPACING

Span Downspout spacing


6,9 & 12M 24.00M.O.C.
15M 22.00M.O.C.
18M 19.00M.O.C.
501 Series

20M 17.50M.O.C.
21M 17.00M.O.C.
24M 15.00M.O.C.

GU- 501 OS- 501 30M 13.00M.O.C.


36M 11.00M.O.C.
42M 10.00M.O.C.
45M 9.50M.O.C.

48M 13.50M.O.C.
54M 12.50M.O.C.
502 Series

60M 11.50M.O.C.
72M 10.00M.O.C.
84M 8.50M.O.C.
96M 8.00M.O.C.

GU- 502 OS- 502

113
6.13 VALLEY GUTTER &
DOWNSPOUT

I
I

* To be calculated based on drained area and downspout Spacing as given in formulae on sheet #
5.34

114
6.14 KIRBY M LINER

c ROOF PAN EL
J.

~
J
~FLASHING :'1(

E-
::c:
\.:)
;~ ROOF LINER
FLASHING ~!
Q r- .
WALL PANEL
::c:
l:.tl FLASHING 1:--'
:>
;5o
N
N
N
WAINSCOT
(PARTIAL HEIGHT LINER)
WALL LINER --
-'--L..

Specifications: Availability:

Kirby M liner consists of sheet metal panel and Wall liners are supplied either full height or
flashing (26Ga.) attached to the girt from inside partial height. Partial height wall liners are
of the building by self tapping screws. Standard stopped at a standard girt locations. If the liners
panelling is Kirby rib profile, galvanised or color are stopped at non-standard girt locations an
coated (white only). additional line of girt is required to support the
liner.

At translucent panels, the liner panel shall be cut


and the ends are trimmed with flashing unless
double layer of translucent panels are ordered.

Slide doors shall be lined for building with wall


liner. All framed openings and cut edges shall be
furnished with flashings around the opening.

Wall liners are supported by base channel at


base (base channel is supplied plain without
holes.holes are to be field drilled to the exact
spacing of anchor bolts as cast on site), by girts
at the middle and by liner support flashing at
eave. Roof liners are supported by the purlins.

115
6.15 KIRBY M PARTITION

BASE ANGLE

SINGLE SHEETED LONGITUDINAL DOUBLE SHEETED TRANSVERSE


PARTITION PARTITION

Specifications:

Kirby M partitions consist of steel frame work Standard transverse partitions are located
of columns and girts covered with galvanised 356mm minimum away from the center line of
color coated panel, either one side or both sides. main frame.Transverse partitions can also be
Standard partition panels are 26 Ga. Kirby rib in the center line of the main frame provided
profile color coated ( white only ). the flange width of the frame does not exceed
200mm.
Availability:
An angle section shall be provided at base and
rake to support sheeting for single side sheeted
Longitudinal partition columns are connected
partitions. A channel section shall be provided
at base to foundation slab and at top to the
for double side sheeted partition.Base channel
rafter, generally same bay spacing as main frame
is supplied plain for field drilling of holes to the
columns. Girts are flush framed into the column.
set-out anchor bolt dimensions.
When sheeted from both sides of the framework
it gives a neat appearance. Single side sheeted Standard partitions are not supplied with
partitions are sheeted on one side of the insulation. However, insulation can be provided if
framework. specified.

Accessories such 3070 and 6070 doors, slide


doors, roll-up doors etc. can be fitted to the
partition

116
6.16 LIGHT PARTITIONS

CROSS SECTION OF PARTITION

ELEVATION
PLAN - X

Light partitions are generally not supplied by Kriby, Gypsum board panelS-shall be 13mm thick
consisting of a core of gypsum reinforced with
Following are suggested specifications only as a
approximately 40 mm long glass fiber pieces on
guideline to specifiers:
both sides. The gypsum board shall be covered by
The partition system shall be a complete and 0.8mm glued vinyl wall paper. Meanwhile board
functional system suitable for interior partitions panels shall consist of 12mm chipboard covered
or wall liner with acoustical and fire resistant on both sides by white melamine (80 g/m) added
properties and supplied as a finished product to the chipboard under pressure and heat.
with no further treatment like painting, etc,
Covered gypsum boards are used in dry areas
required prior to occupation, The partition
like offices, shops, bedrooms, etc .. , melamine
system shall allow for change in layout with all
boards in semi dry areas like kitchen, toilets, etc.
components fully reusable, The partition system
and plain gypsum boards to which ceramic tiles
shall be supplied in modular width of 0,9m x
can be glued (by others) are used in wet areas
2,7,1 m height with boards finished with vinyl wall
like bathrooms, etc.
paper of light grey color. The partition system
shall comprise of gypsum board or melamine Insulation shall be 50mm glass wool in rolls of 0.9
board panels mounted on both sides of vertical x 10 m with a heat transmission value of 0.0387
Z shaped steel studs and held by aluminum Kca/m 2 Hr. C, and density of approx 14 kg/m3,
connection profiles which shall envelop the
Galvanized steel profiles shall be of commercial
board panels to conceal the vertical joints, The
quality with a thickness of 0.75mm and
aluminum profiles shall be fixed to vertical Z
galvanized on both sides.
steel studs from either side by self penetrating
screws. The vertical Z studs shall be spaced at Aluminum profiles shall be made of natural
cms C/C and held into their vertical position by anodized materials. Thickness of profile shall be
bottom horizontal steel rails and top aluminum 1.0/1 .2/2.25 mm depending on type of profile
ceiling profiles. The bottom steel rails shall be with an anodization thickness of 10 microns.
C shaped profiles fixed to floor by suitable Internal doors in partitions shall consist of 830 x
fasteners. Aluminum C profiles shall be used 2040mm mahogany veneered channel door leaf
as upper rails and wall starters and fixed to the in aluminum frame fixed to partition by special
ceiling or wall by means of suitable fasteners. fittings . The door shall be furnished with a steel
Black vinyl profile shall be used to cover the door handle and cylinder lock.
screws in the aluminum connection profiles.
At corners, steel corner profiles shall be used Internal windows shall be 880 x 970 mm
instead of steel studs and supported by upper provided with aluminum profile window frames
and lower rail. and suitable for glazing (by others) with 4mm
glass which is secured with vinyl window profiles.

117
6.17 FALSE CEILING

t-----------1~- GALVANIZED WIRES (GW)

~- EDGE MOULDING
I ( KSS)

MAIN RUNNER ( HBT)

(MFLF, ALP)

False Ceilings are generally not supplied by parallel to one another at a module of 120 cm in
Kirby. which the cross T form the network which hold
the tile in position. The main runners shall be
Following are suggested specifications only as a held to the structural ceiling by galvanized wires
guideline to specifiers: at intervals of 120cm.
The suspended ceiling shall be a flexible modular Edge moulding shall be L-shaped profiles to be
system of visible structure type and easily used as edge trim around the perimeter of the
demountable. Suspended ceiling tiles shall be room . These shall be secured to the wall by
60 x 60cm either of mineral fiber for application suitable fasteners at a spacing of 50cm.
in dry areas or asbestos tiles for application
in wet areas. Mineral fiber tiles shall consist All galvanized steel for main runner, cross T and
of 15mm hard pressed mineral wool and glue. edge moulding shall be hot dipped galvanized to
The exposed surfaces shall be sprayed white. 20 micron Zinc. The steel thickness shall be 0.4
Asbestos ceiling tiles shall be of non-inflammable mm for cross T and main runner and 0.25mm for
asbestos cellulose cement manufactured by the edge moulding. The edge moulding shall be
using asbestos fiber, cellulose and cement. The covered on the two outer sides by epoxy primer
tiles shall be hard pressed with a plain surface whereas the main runner and cross T shall be
and a greyish color. The material composition coated on exposed side only. Edge moulding
shall provide fire resistant properties, strength shall be finished on one side by 20 micron
and flexibility. polyester coating with 20% light reflection
according to girder 60 degree.
Main runners shall be T-shaped profiles running

118
7 : INSTALLATION DETAILS
7.1 ENDWALL DETAILS -
MAIN END FRAME

CLIP 1-221 SHOP-WELDED

2-M12x30
M.S. BOLTS

2-M12x30
M.S. BOLTS

4-M16x40 H.S. BOLTS


CLIP 1-110
5-120 M.S. Washers
(between clip &eave
stllll@ inside bolt only)

WIND COLUMN

GIRT TO EAVE STRUT CONNECTION


AT MAIN END ENDWALL

ENDWALL COLUMN (C-SECTION) CONNECTION


TO MAIN END RAFTER

119
7.1 ENDWALL DETAILS -
MAIN END FRAME

CLIP 1-2~21.!:1Q!~~----,

4-M16x40 H.S. BOLTS

~--WIND COLUMN
(200 mm DEEP)

ENDWALL COLUMN (HOT ROLLED) CONNECTION ENDWALL COLUMN (C-SECTION) CONNECTION


TO MAIN END RAFTER TO MAIN END RAFTER

(MORE THAN
200mm DEEP)

ENDWALL COLUMN (HOT ROLLED) ENDWALL COLUMN CONNECTION


CONNECTION TO MAIN END RAFTER TO MAIN END RAFTER AT PEAK

NOTE :

1. Details shown on this drawing may not occur all 2. All high strength bolts shall have one H.S.
together in one building. Use those details which Washers and one H.S. Nut and shall be installed
comply with the structural framing, refer building in accordance with astm a 325 bolt specifications.
installation drawing.

120
7.1 ENDWALL DETAILS - C
BEARING FRAME

I 1

TYPE 'A' ENDWALL TYPE 'B' ENDWALL

DETAIL 'A'
EAVE STRUT & BEARING RAFTER DETAIL 'A1'
CONNECTION TO C CORNER COLUMN EAVE STRUT & BEARING RAFTER
CONNECTION TO 'H' CORNER COLUMN

DETAIL 'B'
BEARING RAFTER & PURLIN CONNECTION DETAIL '81'
TO INTERMEDIATE 'C' WIND COLUMN BEARING RAFTER & PURLIN CONNECTION
TO INTERMEDIATE DOUBLE 'C' WIND COLUMN

121
DETAIL 'D'
ro:~~~EAK

NOTE:
NOTE:
Rake angle at top & bottom of purlin for
buildings with insulation up to roof slope 1. Details shown on this drawing may not occur
1.25:10. Rake angle at top of purlin only all together in one building. Use those details
for roof slopes 1.3:10 And above (with or which comply with the structural framing,
without insulation). refer building installation drawing.
Building installation marks shown on this 2. All high strength bolts shall have one H.S.
drawing is for building with roof slope 1:10. Washer and one H.S. Nut and shall be
See table below for corresponding building installed in accordance with astm a 325 bolt
installation marks for roof slopes other than specifications.
1:10.
Building installation Corresponding building installation mark for Remarks
Mark for slope 1:10 Slope 0.5:10 Slope 3:10 others
1-114 1-115 1-114 See Building installation Dwg. For Flush Frame Slog.
1-114 For By-Frame Slog.
1-83 1-85 1-84 See Building installation Dwg.
1-3 1-10 1-8 See Building installation Dwg.

~
1-13 1-13 1-13 1-13
I
1-1 1-5 1-6 See Building installation Dwg.
3-1250 Ur 3-1250Ur 3-1250Ur 3-1250Ur

122
7.1 ENDWALL DETAILS- I
BEARING FRAME (ALT,L)

TYPE "A' ENDWALL TYPE "B' ENDWALL

RAKE TRIM
EAVE STRUT

RAKE ANGLE
STSTO PURLIN
2-M12 x 30
H.S. BOLTS
4-M16 x 55
H.S. BOLTS

'H' SECTION CORNER COLUMN

DETAIL 'A' SECTION 'X'


EAVE STRUT & RAFTER CONNECTION
TO 'H' SECTION CORNER COLUMN

DETAIL 'C'
DETAIL 'B' PURLINS & RAFTER CONNECTION
PURLIN & RAFTER CONNECTION TO 'H' SECTION COLUMN ON PEAK LINE
TO INTERMEDIATE 'H' SECTION COLUMN

123
7.1 ENDWALL DETAILS- I
BEARING FRAME (ALT,L)

DETAIL 'D' DETAIL 'E'


RAFTER & PURLIN CONNECTION
PURLINS & RAFTER CONNECTION
TO 'C' INTERMEDIATE COLUMN
TO DOUBLE 'C' COLUMN ON PEAK LINE

PURLIN

2-M16x55
H.S. BOLTS
CLIP 1-228 L
DETAIL 'F'
RAFTER & PURLIN CONNECTION WIND COLUMN
TO DOUBLE 'C' INTERMEDIATE COLUMN

DETAIL 'G'
PURLINS & RAFTER CONNECTION
TO 'C' COLUMN ON PEAK LINE

NOTE :

1. Details shown on this drawing may not occur


all together in one building use. Those details
which comply with the structural framing,
refer to building installation drawings.
2. All high strength bolts shall have one H.S.
Washers and one H.S. Nut and shall be
installed in accordance with astm a 325 bolt
specifications.
PURLIN CONNECTION
TO RAFTER AT PEAK

124
7.1 ENDWALL DETAILS- I
BEARING FRAME (ALT,2)

TYPE 'A' ENDWALL TYPE 'B' ENDWALL

EAVE STRUT
RAKE TRIM

RAKE ANGLE
STSTO PURLIN
4-M16x55
H.S. BOLTS LIGHT END RAFTER
356
WALL PANEL
'H' SECTION CORNER COLUMN

DETAIL 'A'
EAVE STRUT & RAFTER CONNECTION
SECTION 'X'
TO 'H' SECTION CORNER COLUMN

4-M16x40
H.S. BOLTS

WIND COLUMN

DETAIL 'B'
RAFTER & PURLIN CONNECTION
TO 'H' SECTION INTERMEDIATE COLUMN

DETAIL 'C'
PURLINS & RAFTER CONNECTION
TO 'H' SECTION COLUMN ON PEAK LINE

125
4-M16x55
H.S. BOLTS
RAFTER
2-M16x55
H.S. BOLTS
CLIP 1-228L

WIND COLUMN

DETAIL 'D' DETAIL 'G'


PURLINS & RAFTER CONNECTION PURLINS & RAFTER CONNECTION
TO DOUBLE 'C' COLUMN ON PEAK LINE TO 'C' COLUMN ON PEAK LINE

NOTE:

1. Details shown on this drawing may not occur


all together in one building use. Those details
which comply with the structural framing,
refer to building installation drawings.
2. All high strength bolts shall have one H.S.
Washer and one H.S. Nut and shall be
installed in accordance with astm a 325 bolt
specifications.
3. Part marks given are for 1:10 roof slope only.
Refer to building installation drawings if roof
PURLIN CONNECTION
TO RAFTER AT PEAK

slope is other than 1:10.

126
7.1 ENDWALL DETAILS-
GABLE

ENDWALL FRAMING ELEVATION


(PARTIALLY OPEN WITH STUB COLUMNS & KICKERS)

ENDWALL FRAMING ELEVATION


(OPEN UPTO EAVE - GABLE SHEETED)

RAKE TRIM

RF-501

T
10
ONE ~
RAKE ANGLE ~ (eJRL
(STS TO PURLIN) .------.

~
F--
=-----"
WALL PANEL

~ ~ lii
MF-501 A
!i:! ~

DRIP FLASHING ~

SECTION - "X' GABLE SHEETTING ELEVATION

127
'H' PURLIN

4-M16 x 55
2-M16 x 40
H.S. BOLTS H.S. BOLTS

'H' SECTION KICKER


CHANNEL KICKER 4-M16x40
H.S. BOLTS

STUB COLUMN
'C' OR 'H' SECTION

4-M16 x 40
H.S. BOLTS
CLIP 1-227

DETAIL 'A' DETAIL 'B'

M12 x 30

4-M16x40
H.S. BOLTS
4-M16x40
2-M16 x40 H.S. BOLTS
H.S. BOLTS
STUB COLUMN
STUB COLUMN 'C' OR 'H' SECTION
'C' OR 'H' SECTION
BRACKET- REQD. FOR STUBS
DEEPER THAN RAFTER)

DETAIL 'C' DETAIL 'D'

NOTE:

1. Details shown on this drawing may not occur 2. All high strength bolts shall have one H.S.
all together in one building use. Those details Washer and one H.S. Nut and shall be
which comply with the structural framing, installed in accordance with astm a 325 bolt
refer to building installation drawings. specifications.

128
7.2 PURLINS, GIRTS & EAVE
STRUT CONNECTIONS

PURLIN/GIRT CONNECTION DETAIL PURLIN/GIRT CONNECTION DETAIL


At Lines 3-9 At Lines 2 & 9

PURLIN/GIRT CONNECTION DETAIL PURLIN/GIRT CONNECTION DETAIL


At Lines 3-9 At Lines 2 & 9

ENDWALL

ENDWALL
250

RAFTER
625

PURLIN/GIRT CONNECTION DETAIL PURLIN/GIRT CONNECTION DETAIL


At Lines 1 & 9 At Lines 1 & 9

129
DETAIL AT EAVE DETAIL AT EAVE

-~=----.-n~1 1toof Slope


10

6-M12x40
H.S. BOLTS

4-M12x40
H.S. BOLTS

DETAIL AT EAVE DETAIL AT EAVE

CONNECTION
PLATE 1-236

FLANGE BRACE
AS REOUI

H & ZEE PURLIN/GIRT CONNECTION H & ZEE PURLIN/GIRT CONNECTION


AT 107 & 165 LAPS AT 706 & 1062 LAPS

130
7.2 GIRT CONNECTIONS

CLIP 1-25
CLIP1-61
SHOP WELDED
TO COLUMN
2-M12x30
M.S. BOLTS 2-M12 X 30
M.S. BOLTS

DETAIL 'A' DETAIL 'B'


FLUSH GIRT- 'H' SECTION COLUMN FLUSH GIRT - 'H' SECTION COLUMN
Flange Width - 150 mm Flange Width - Over 150 mm

DETAIL 'D' DETAIL 'F'


FLUSH GIRT- SINGLE 'C' COLUMN FLUSH GIRT- DOUBLE 'C' COLUMN

131
STEEL LINE

DETAIL 'G' DETAIL 'H'


BEARING FRAME - 'C' SECTION CORNER COLUMN BEARING FRAME - 'H' SECTION CORNER COLUMN

2-M12x30
M.S. BOLTS

CLIP2-150

DETAIL 'A' OR 'B' DEPENDING


ENDWALL GIRT
ON COLUMN FLANGE WIDTH
DETAIL 'A' SHOWN

CLIP 1-86

C.L.OFCOLUMN C.L. OF COLUMN

2-M12 x 30 M.S. BOLTS


(GIRT TO CLIP CONN.) CLIP1-B6

2-M12 x 30 M.S. BOLTS


(GIRT TO COLUMN CONN.) CLIP2-150
FIX WITH 2-# 14x25 SDS
SIDEWALL GIRT
SIDEWALL GIRT

DETAIL 'J' DETAIL 'K'


MAIN FRAME ENDWALL CORNER DETAIL MAIN FRAME ENDWALL CORNER DETAIL
SIDEWALL GIRTS- BY-FRAMED SIDEWALL GIRTS- FLUSH

132
7.3 BRACING DETAILS

BRACINGS AT ROOF

BRACINGS AT SIDEWALL

EAVE STRUT
STIFFENER
1-48

M12DIA.
H.S. BOLTS

DETAIL 'A' SECTION -1 DETAIL 'C'

RAFTER

BRACE ROD

DETAIL 'D' DETAIL 'B'

BRACE ROD FIXING DETAILS

133
DETAIL "E" SECTION 2- 2
ALT. # 1 (REF. DESIGN)

DETAIL "F" SECTION 3 - 3


DETAIL "G"

M120 H.S. BOLTS


AT STANDARD
GIRT SPACINGS

DETAIL "H"
ALT # 1 (REF.DESIGN)
DETAIL ' K'
SECTION 4 - 4

SPLICE DETAIL
AS PER DESIGN I

DETAIL 'L' I
DETAIL "M" ALT. #1 SECTION 5- 5

NOTE :
of diaphragm strength of the fully sheeted
1. Details shown on this drawing may not occur wall.
all together in one building, use those details 4. When a sidewall of "s.V. Building" or light
which comply with the structural framing endwall (all buildings) is opened to a height
drawings furnished with the building greater than 2.2M rod bracing must be
2. Brace rods are indicated thus: 2r-6940 on installed.
building installation drawings, meaning 160 5. Bracings should never be dismantled for
rod 6940mm long. whatsoever the reasons may be. Connection
3. ( 1R=120, 3r=200, 4r=220 , 5r=240) bracing are bolts & nuts to be tight
not used in light endwalls or "s.V. Buildings" 6. And brace rods to be inspected periodically
in fully sheeted condition as the lateral wind for anyslackness.
force is carried to the foundation by means

134
7.4 EXPANSION JOINT
DETAILS

START OR Ill MF-531


END SHEETING

2-M12x40 M.S. BOLTS W/


2 NUTS & 2 WASHERS. NUTS
TO BE SNUG TIGHT AND CLENCHED.

FLANGE BRACE
THIS SIDE ONLY

DETAIL 'A' SECTION 1


AT PURLIN & ROOF PANEL

START OR
END SHEETING MF-532

2-M12x40 M.S. BOLTS W/


2 NUTS & 2 WASHERS. NUTS
TO BE SNUG TIGHT AND CLENCHED.

FLANGE BRACE
THIS SIDE ONLY

DETAIL 'B' SECTION 2


AT GIRT & WALL PANEL

2-M12x40 H.S. BOLTS


W/ 2 NUTS & 2 WASHERS.
NUTS TO BE SNUG TIGHT
AND CLENCHED.

DETAIL c SECTION 3
AT EAVE STRUT

135
EF-506 l L ROOF PANEL

GUTIER
~t
WALL PANEL
L EAVE STRUT

EXPANSION JOINT

DETAIL 'D' SECTION 4


AT EAVE GUTTER

r - - - -,_---RIDGEVENTILATORS ---- r-----.

ROOF PANEL

DETAIL 'E'
AT RIDGE VENTILATOR

EXPANSION JOINT

DETAIL 'F' SECTION 5


AT VALLEY GUTTER

EXPANSION JOINT

FIELD CUT, BEND AND


------ SEAL WITH MASTIC
INSIDE AND OUTSIDE ...... ..._...
I I

TRIM _j J4o 40l LAP \__ No. 12x20 SOTS (TYP.)


LAP AS SHOWN

DETAIL 'G' DETAIL 'H'


EXPANSION TRIM AT PEAK MISCELLANEOUS TRIM LAPS

136
7.5 CANOPY & LEAN-TO
CONNECTIONS TO MAIN
BUILDING
'KIRBY-RIB'
WALL PANEL 'KIRBY-WALL'
PANEL
CONNECTION
CONNECTION BRACKET
BRACKET

CUT PANEL AT TOP AND


BOTIOM OF CONNECTION
BRACKET TO CLEAR BOLTS

SLIT PANEL TO ALLOW IT


TO BEND WHILE BOLTS ARE
BEING TIGHTENED
FIELD CUT HIGH RIB
CUT TO CLEAR BOLTS
CAULK AFTER ERECTION
NOTE
ERECT WALL PANELS BEFORE ERECTING NOTE
LEAN-TO OR CANOPY RAFTERS. ERECT WALL PANELS BEFORE ERECTING
LEAN-TO OR CANOPY RAFTERS.

DETAIL 'A' DETAIL 'B'


CUTTING DETAILS FOR K.R. PANELS CUTTING DETAILS FOR K.W. PANELS

KIRBY RIB INSIDE CLOSURE KIRBY RIB INSIDE CLOSURE No. 14x25 SDS @333 O.C.
(FOR CANOPIES ONL (FOR CANOPIES ONLY)

No.12x20 SOTS
@3330.C.
REF. DETAIL 'A' OR ' B ' - f - - - - - -111
(FOR SHEETED WALL)

DETAIL 'C' DETAIL 'D'


BY-FRAMED CANOPY & LEAN-TO CONNECTION FLUSH-FRAMED CANOPY & LEAN-TO CONNECTION
AT MAIN BUILDING EAVE HEIGHT AT MAIN BUILDING EAVE HEIGHT

14x25 SDS @333 O.C.

DETAIL ' E' DETAIL ' F'


BY-FRAMED CANOPY & LEAN-TO FLUSH-FRAMED CANOPY & LEAN-TO
CONNECTION AT SIDEWALL CONNECTION AT ENDWALL

137
7.5 EAVE CANOPY & PURLIN
EXTENSION DETAILS

LENGlli (OUT TO OUT OF STEEL)


BAY SPACING BAY SPACING 10650R1730

~
~
CANOPY

,- 4-125L FOR 1065 CANOPY


4-126L FOR 1730 CANOPY

DETAIL-A

I
~
~
~

Ill~
-~
""'--.....
7

~I
2-CANOPY RAFTERS
BACK TO BACK

DETAIL - B "
/"""<

I EAVESTRUT

CANOPY RAFTE
t_L: B
127 FOR 1055 CANOPY
126 FOR 1730 CANOPY

E~125R FOR
~ 10
CANOPYBRACE7-205
BAY SPACING 7m AND ABOVE
F06~ ~ L EAVEPURLIN 1065 CANOPY
~126R
FOR 1730 CANOPY

COMBINATION EAVE & PURLIN EXTENSION CANOPY

LENGTH (OUT TO OUT OF STEEL)

~
~
LENGTH (OUT TO OUT OF STEEL) 1 10650R1730
CANOPY
I


@ f-t1 25L FOR 1065 CANOPY
26L FOR 1730 CANOPY
:::>
I
~
1!5

I
~
,.~ I EAVESTRUT -

:::>
< r- RAKE CHANNEL

'3
~
~ - ,.~
b
DETAIL-E
-

-~
r u

L EAVEPURLIN EAVE STRUT _ _ /


\ \
\__ 5-516 FOR 1065 CANOPY
5-517 FOR 1730 CANOPY

EAVE CANOPY PURLIN EXTENSION CANOPY

EAVESTRU

CANOPY BRACE
7-205

EAVEPURLIN

DETAIL 'A' DETAIL '8' DETAIL 'C' DETAIL 'D'

138
------------------~'

2-206x76C CANOPY RAFTERS


6-100 BACK TO BACK

RAFTER - @
CANOPY,
MAIN~Rf--ffiE

1500
ALTERNATE DETAIL
FOR SPACE SAVER

SECTION '1'

PURLIN LAP

*ASDRAWINGS
PER ERECTION

SECTION '2' SECTION '3'

10650R1730
RAKE
I PURLIN EXTENSION CHANNEL

BEARING FRAME
356 MAIN END FRAME

SECTION '4' SECTION '5'

100

CLIP1-72

CLIP1-114

SECTION '6' SECTION '7' SECTION '8' SECTION '9'

NOTE :
709 (PURLIN LAP) I

1. All canopy eave purlins as well as eave purlin


laps are same as the required purlins in the
SECTION '1 0' main building.
2. Rake channel is made of un punched material
(206x76cx1 .8)
3. All dimensions are in millimeters.
4. Part marks shown on this drawing are for roof
slope 1:10 only.Refer to building installation
drawings if roof slope is other than 1:10.

139
7.5 OVERHANG CANOPY
DETAILS

DETAIL 'A'
OVERHANG CANOPY AT BY-FRAME SIDEWALL

DETAIL 'B'
OVERHANG CANOPY AT BY-FRAME SIDEWALL DETAIL 'C'
(All OTHER DETAILS SAME AS IN DETAIL 'A'l AT BY-FRAME SIDEWALL OR ENDWALL

5mm ELASTOMERIC
SEALANT BEAD

SEALING TAPE
K.W.O. CLOSURE
EAVE TRIM
EF-504

DETAIL 'D' DETAIL 'E'


AT FLUSH FRAME SIDEWALL OR ENDWALL PANEL & TRIM INSTALLATION

OVERHANG CANOPIES AT DOORS FRAMED OPENINGS ETC.

BAY SPACING

- ~~ANE~CL~~ - No.12x20SDTS
WALl PANEL

~ ~N=OSDTS
c:F~~
) - CLIP125 >- 200Z 3 ~I
SECTION '1'

PLAN VIEW SECTION '2'


'KIRBY-WALL'
PANEL
CUT PANEL ATTOP AND
No.12x20SOTS~5000.C
. BOTIOM OF CONNECTION
PLATETOCLEARBOLTS
RAKE TRIM SLIT PANEL TO ALLOW IT
2 TO BEND WHILE BOLTS ARE
ROOFPANEL RF-50
BEING TIGHTENED
POP RIVETS
SOFFIT PANEl CAULK AFTER ERECTION
RF502
NOTE
No.12x20SOTS@5000.C. ERECT WALL PANELS BEFORE
ERECTING CANOPY RAFTERS.

SECTION '3' WALL PANEL CUTOUT


DETAIL AT FLUSH FRAME

140
7.6 VERTICAL FASCIA
DETAILS
WI MAIN ENDWALL

1200 & 1800 FASCIA ELEVATION

M12x25 RND. HD. BOLTS

SECTION -A SECTION- 8
(TYPICAL CORNER DETAIL (TYPICAL CORNER DETAIL
AT LIGHT ENDWALL) AT MAIN ENDWALL)

667
ENDWALL STEEL LINE
/'.. _/\

PROFILE CUT

V:~"~">'"
K.R. PANEL

LLSTEELLIN No.14x25 SDS


@3330.C.

+
D
>
c + !ii
DRIP FLASHING
MF-505@3200 MF-514@620
(F.CUT FROM 6200)

+ SECTION- C
~ FLASHING MF-505

PLAN SHOWING SOFFIT PANEL


LAYOUT AT CORNERS

(STEEL NOT SHOWN FOR CLARITY)

BRACE ANGLE
K.R. PANEL L.50x50x4
SIDEWALL STEEL LINE START SHEETING
OR END SHEETING
No.14x25 SDS
2 @VERT. BRACES
3 @ DIAG. BRACES

J]ct====;:::====t
FLASHING DRIP FLASHING
MF-528@700 MF-505@3200

SECTION- D SECTION- E

141
SEE ENLARGED DETAIL SEE ENLARGED DETAIL

~~ f--- STUB COLUMN

~~
356

::1.
UJ UJ
zz
STUB COLUMN ~~ ROOF PA NEL
0::0:: I"
EAVE GUTTER
:::..:::~

- Cr ,............. ~
~It"'
LIN
EARING FRAME
OR MAIN FRAME
RAFTER

_u ~
1/
4-M16x55

K.R. PANEL
MF-502 @3200 J~ H.S. BOLTS

@620 No.1 4 SDS - ENDWALL COLUM


@3330.C.
~
-

667 BUILDING SPAN


OUT TO OUT STEEL

TYPICAL SECTION THRU' FASCIA AT SIDEWALL TYPICAL SECTION THRU' FASCIA AT ENDWALL

No.14 SDS@ 333 O.C.

GIRT (C 206x76)
K.W. WALL PANEL
No.14SDS
@3330.C. FASCIA
BRACKET

CUT PANEL ATTOP AND


BOTTOM OF FASCIA ---tr-t+-tw
BRACKET TO CLEAR BOLTS
SLIT PANEL TO ALLOW IT
TO BEND WHILE BOLTS ARE
K.R. PANEL BEING TIGHTENED

CAULK AFTER ERECTION

NOTE
ERECT WALL PANELS BEFORE
ERECTING FASCIA BRACKET.

MF-505 DETAIL AT WALL PANEL


@ 3200

ENLARGED DETAILS

NOTE :

SCREWS 333 O.C. At each support for k.R. Panel stitch


(one@each support and (one) between per side
333 O.C. At each girt for k.W. Panel stitch (2 lap.
nos.) Between girt per side lap, 500 o.C. For mf
501a both sides.

142
------------------~'
7.6 FLUSHWALL FASCIA
DETAILS

GIRT

No. 14 SDS No. 14x25


@3330.C. SDS@3330.C.

KW PANEL

4M16x40
H.S. BOLTS

CAULK

FIELD-CUT-
SIDEWALL PANEL
DETAIL 'A' DETAIL ' B'
SECTION AT SIDEWALL SECTION AT ENDWALL

DETAIL ' C'


DOWNSPOUT INSTALLATION

ENDWALL GIRT \. _),_.:.Jill---till-- SHEETING ANGLE


(206x76C) F==='~===='~~ ~ L100x75x3.5
ENDWALL PANEL

DETAIL ' D' DETAIL ' E'


SECTION - 1
AT PEAK
SECTION AT CORNER

143
7.7 VERTICAL MANSARD
DETAILS

1500 (SUGGESTED MAX.)


CAP FLASHING
CAP CHANNEL
200x76

INNER MANSARD PANEL


SIDEWALL STEEL LINE

MANSARD COLUMN
200x100 C

EAVE PURLIN

COLUMN

SECTION AT SIDEWALL

1500 SUGGESTED MAX)

206x76 CAP CHANNEL CAP FLASHING


I
-:-OUTER
SIDEWALL STEEL LINE
~ MANSARD PAN INNER
:::;: MANSARD PANEL
0
w
t; MANSARD COLUMN
w 200x100 C ROOF PANEL
(.')
(.')
::l
~ 200GIRT
INSIDE CLOSURE I EAVE STRUT j PURLIN
-----J

~ 1 ==
0
l eER

~ I IIII MANSARD EAVE STRUT


~

MANSARD RAFTER I 8 n= o~n


~:::;;
-
~
'I' 1'1" 'I'"'
RAFTER

MANSARD BEAM I COLUMN


l.o. _.,
BOTTOM CHANNEL ----- r--- 200ZGIRT

~uT
206x76
DRIP FLASHING SOFFI -------------.,
FLA...!::!!!::lQ_

D
SIDEWALL GIRT

SECTION AT SIDEWALL

144
200x76 CAP CHANNEL

INNER MANSARD PANEL

RAKE ANGLE
50x40x1 .75

CONNECTION PLATE

206x76 C
BOTTOM CHANNEL
DRIP FLASHING

SECTION AT ENDWALL

1500 (SUGGESTED MAXIMUM)

CAP FLASHING 206x76 CAP CHANN EL


I
INNER MANSARD PANEL
l<:
ENDWALL STEEL LINE
INSIDE CLOSURE L1i
a_

SHm'NG N<GCE ~ ~
z
""""""' '""""~
100x75x1 .75
~
0
ROOF PANEL
~
1- ...n..l ./"\ /""'- ./"\ /""'- ~ ./"\
-

(! 200Z GIRT
en
~~
I ~
L1J
p
:;a::

EN DWALL RAFTER
~
z- 206x76 RAKE CHANNEL

OUTER
MANSARD PANE L

200x100 C
(SH1AI"'t: VAKit:O>} MANSARD COLl MN

ENDWALL COLUMN
~
I MANSARD BEA~

..! Ia.. ....


I
\
200x100 C
SOFFIT PANEL BOTTOMCHANNEL
200x100 C FLASHING DRIP FLASHING
ENDWALL GIRT SHEETING CHANNEL

~ FLASHING

ENDWALL PANEL

SECTION AT ENDWALL

145
7.7 CONVENTIONAL
MANSARD DETAILS
TYPE- III:

OUTER MANSARD PANEL

MANSARD COLUMN ENDWALL RAFTER


(SHAPE VARIES)
MANSARD BEAM

ENDWALL COLUMN

SECTION AT SIDEWALL SECTION AT SIDEWALL

TYPE-V:

ANGLE GIRT

50x50ANGLE

MANSARD COLUMN ----1'-11'>/


ANGLE50x50

No.14x25 SDS
(TYP)

L.50x50GIRT

SECTION AT SIDEWALL

146
TYPE- IV:

SECTION AT SIDEWALL
SECTION AT ENDWALL
TYPE-V:

SECTION AT ENDWALL

147
7.8 ROOF FRAMED
OPENING DETAILS

I SEALING TAPE
WELDED FRAME----J 1---""'------1
STS TO PURLINS
--
-----J
-------""

FRAMED OPENING AT PEAK


DETAIL 'A' FRAMED OPENING FOR CHIMNEY
DETAIL '8'

SEALING TAPE
~~ ROOFPANEL
\'~INSIDE CLOSURE

(SHA~SEALINGTAPE
TYPICAL DETAIL OF FIXING
ROOF PANEL WITH FLASHING

FRAME BEAM -SUPPORTED


OVER RAFTERS (SIZE &
CONN. BOLTS AS PER DESIGN

FLASHING

r-

FLASHING
-----
I
~~
L.SLIT ROOF PANEL AND
APPLY WEATHER SEALANT

TYPICAL DETAIL AT CORNERS


FRAMED OPENING FOR CHIMNEY
DETAIL 'C'

148
MASTIC

FlAS=fiNG:
No 14x25SDS
ROOF PANEL

POP RIVETS
BOLTS M120 (MAX.)

SECTION 1

SECTION 2

MASTIC
FRAMED OPENING FOR LIGHT WEIGHT FANS FLASH No 14x25 SDS
DETAIL 'D' ROOF PANEL

BOLTS
120(MAX.)

SECTION 3

--~ FLASHING

*
PRIVETS
o 14x25 SDS
ROOF PANEL

__ J :[
SECTION 4

FRAME BEAM SUPPORTED


CONN~L~'%T~~~ b~~~~
FLASHING

EQUIPMENT SUPPORT
(NOT BY KIRBY)]_
MASTIC ---- -------------
(NOT BY KIRBY)
SECTION 5

FLASHING ~~~~~~L=J~======j~~~~r;o...(

FLASHING TO BE BENT

FRAMED OPENING WITH EQUIPMENT SUPPORT


DETAIL 'E'
'"" ~-~'
&OUTSIDE
CLOSURES ROOF PANEL

SEALINGTA?EC:INSIDE CLOSURE

SECTION 6

149
7.9 WALK DOOR DETAILS

jC ~070

ml~Jmnrr~
~x'

DF-501 A&B
@2200 =
DF-501 A&B

0
LOCK SET f ' HANDLE SET

IFIELD-CUT WALL PANELS I


3070 WALK DOOR 6070 WALK DOOR
(914X2134) (1830X2134)

m
F ---------- -l-
~T ~1 .75

- r- --- ------ =)
m
II

2-M10x20/25 M.S. BOLTS ~EADER

DOORJAMBS

COLUMN (TYP)

~

~GLE
rl\ Lt
\_.y
JA
DOOR FRAME ERECTION

JAMB FLASHING
DF-501 A&B

TRIM DETAIL AT'X' DETAIL AT'Y'

150
------------------~'

607o door accessory package:


30 PAN HEAD
SHEET METAL SCREWS
ALUMINIUM & VINYL
WEATHER STRIPS One no. Lockset consisting of:
2-Circular handles, 1-single point latch, 1-strike
and 8-fixing screws.
SECTION -A SECTION -8 6 Nos. Hinges with 108-fixing screws. One no.
Foot bolt set consisting of: 1-6" foot bolt, 1-base
strike,1-bolt housing,1-surface strike,1-sprjng,
(SW~
DOOR LEA~ No14x25SDS
1-Chajn, 1-chain clip and
10-Screws. One no. Threshold.
2 Nos. Aluminium strips.
2 Nos. Vinyl strips.
SECTION -C SECTION -D
14 Nos. Screws.
8 Nos. No.10Tampins.
4 Nos. M10x20/25 m.S. Bolts with nuts.
25 Nos. No.12X20 SDTS

307o door accessory package:


One no. Lockset consisting of:
2-Circular handles, 1-single point latch,
1-Strike and 8-fixing screws.
~--~ ~
3 Nos. Hinges with 54-fixing screws.
One no. Threshold.
CHAIN BOLT FOOT BOLT
IF DOOR OPENS OUT, LOCATE BOLTTO CLEAR STOP AND USE ANGLE STRIKE. APPLY TO INSIDE OF DOOR WITH CASE, EVEN WITH BOTTOM OF DOOR;

One no. Aluminium strips.


IF DOOR OPENS IN, LOCATE BOLTFLUSH WITH TOP OF DOOR AND USE BORE 22 0 HOLE 25 mm DEEP IN FLOOR AND COVER WITH STRIKE.
SURFACESTRIKE. PRE-ORILL30PILOTHOLESANDFIXWITHSTS. PRE-ORIU 30 PILOT HOLES AND FIX WITH STS.

NOTE : One no. Vinyl strips.


8 Nos. Screws.
4Nos. No.10Tampins.
1. Glass & glazing for doors 6o7og and 307og not 4 Nos. M10x20125 M.S. Bolts with nuts.
by kirby. 25 Nos. No.12X20 SDTS
2. A stragal installed on right hand inactive Door
leaf as a standard for 6o7o doors . Installation
on left hand on request .

INSIDE OF BUILDING INSIDE OF BUILDING

INSIDE OF BUILDING INSIDE OF BUILDING

c OUTSIDE OF BUILDING
cJ J OUTSIDE OF BUILDING

LEFTHAND OUTSIDE LEFTHANDINSIDE RIGHTHAND OUTSIDE RIGHTHAND INSIDE


l!d!QJ Jh!ill JBJ!QJ ~

3o7o DOOR JAMB POSITION FOR L.H.O., L.H.I., R.H .O. & R.H .I. DOORS

6o7o DOOR JAMB POSITION FOR SWING-OUT & SWING-IN DOORS

151
7.10 SINGLE SLIDE DOOR
DETAILS

HEADER MEMBER
GIRT OR EAVE STRUT

mlillDVL
HOOD FLASHING
18
r---
OUTSIDE CLOSURE
~A'- I
~R
l DOOR TRACK
LG-305

-
L_ BRACKET ~ 'f
w
COLUMN
1------

FIELD-CUT GIRT(S) />$ RECID. DOORJAMB


L M f--

=
r----------1
----.:::::"
I ~

COLUMN K.W. WALL PANELS


-

) ~ ~N
I
[ 1' 1J '"' "
~ {

f-
FIELD LOCATE DOOR OPENING FIELD LOCATE

SIDEWALL OR ENDWALL BAY

SINGLE SLIDE DOOR FRAMING ELEVATION

FRAME </; FRAME </;


DOOR WIDTH
M10x90
EXPANSION BOLTS

20 0 ROO x 30 DOOR STOPS FIELD-WELD


TOSUIT OPENING OF DOOR LEAVES

PLAN- BOTTOM DOOR GUIDES

152
Door stile schedule
DOOR HEIGHT LEFT HAND STYLE RIGHTHAND SffiE CENTER STYLES
30 0 0 10 x-1 1 0 L 1 0x-1 1 0 R 1 0x-2 1 5 L & R
3 50 0 10 x-1 1 2 L 1 0x-1 1 2 R 1 0x-2 1 6 L & R
40 0 0 10 x-1 1 4 L 1 0x-1 1 4 R 1 0x-2 1 7L & R
4 50 0 10 x-1 1 6 L 1 0x-1 1 6 R 1 0x-2 1 8 L & R
50 0 0 10 x-1 1 8 L 1 0x-1 1 8 R 1 0x-2 1 9 L & R
550 0 10 x-1 2 0 L 1 0x-1 2 0 R 1 0x-2 2 2 L & R

Door jamb schedule


DOOR HEIGHT DOORJAMB
3000 6-3x0
3500 6-3x5
4000 6-4x0
4500 6-4x5
5000 6-5x0
5500 6-5x5

Door track & bracket schedule


DOOR TRACK (LG-305) BRACKET
DOOR WIDTH LENGTH QTY. 3A-305C 3A-305
3000 6000 ONE 2 6
4000 6000+2000 ONE EACH 2 11
5000 6000+4000 ONE EACH 2 12

175 <f OF DOOR TROLLEY <f OF DOOR TROLLEY 175

For 5500 HIGH


DOOR

DOOR LEAF ERECTION DOOR LEAF ERECTION


(FOR 3000, 3500 & 4000 HIGH DOOR) (FOR 4500, 5000 & 5500(AS NOTED) HIGH DOORS)

153
7.10 SINGLE SLIDE DOOR
DETAILS

BOTTOM GUIDE CHANNEL

UNIVERSAL COUPLER

GUIDE CHANNEL ANCHORING DETAIL GUIDE CHANNEL SPLICE DETAIL

M16x55 H.S. BOLTS

TMCK -~~1~35-~~T
HEADER ~

\ 1-507

SECTION- 8

HEADER MEMBER
GIRT OR EAVE STRUT

DOOR TROLLEY
56 CIS

000000
000000
OLOOLOOLO
M M V V lO lO
hHr----. --!1------'>,.-11--J_..J. g g g g g g
u. u.. u_ u.. u.. u..
CLIP1-505g g g g g g
MCOMOOMOO
M M V V LO LO

SECTION- D

SECTION- C

154
DETAIL- E SECTION- F SECTION- G

OUTSIDE
STYLE

CLIP 1-34

SECTION- M DETAIL- J DETAIL- K

DOORJAMB
HASP&
STAPLE SET
DOORJAMB
DOOR RETAINER

NEOPRENE
STRIP-1 00x3
25x3 FLAT BAR
DPM-2
6 0 U-BOLTS
W/4-NUTS
FLASHING DF-513
OF WALL PANELS

SECTION- L SECTION- M SECTION- N

STEEL LINE

115
<t DOOR GUIDE

97 P/3000 200R0Dx30
DOOR STOPS FIELD WELDED
JIDE ROLLER
104 P/97
SECTION- P SECTION- Q

NOTE:

1. Check the level of trackheader assembly and 2. Door handle w/dpm-1 to be fixed inside or
make sure that it matches clear opening of outside of building on any steel member of
door before building installation of door leaf. door leaf.

155
7.11 SLIDING FOLDING DOOR
DETAILS

~ .\
-.\ REF.DET-A
KW-0.5-4925
DOOR PANEL

OUTSIDE

FM-5000
200x79x1.5C
(3)
FIXED IN FLOOR
CORNER
SECOND STAGE FLOOR LEVEL
CONCRETING ~~~<::_il!l./r.i,_--"_,
J- "-
2 o REF.DET - AS

SECTION -X

15000 (DOOR WIDTH)

BOTTOM GUIDE CHANNEL


97P-3000(5)
DOOR TRACK HEADER

---r~-~;~~~-~~-~~~~~-~~-~-~ __l _ _
DOOR- OPEN CONDITION
HINGE PLAN VIEW HINGE BRACKET
(TYP) (TYP.) 3A-305(22)
3A-305C ONLY
DOOR LEAF I INSIDE I @TRACK ENDS
CLOSEDCONDITION /)~ /)~ /)~ =c:::J<:= ~ ,_:

~\_~;.~~~'=:~~~-~~~~~:::,:
M16x55 HSB.

BELOW. _..-'b"'JJI"t!l"'";;e:t:----+-~
_1_,u_

DOOR- CLOSED CONDITION FLASHING


MF-505@3200
PLAN VIEW
DOOR LEAF
GIRT 19A
TOP CHANNEL

ANGLE

SHEETING ANGLE 50 THK. FSK INSULATION


2-5200 (OPTIONAL)

FLASHING WALL PANEL


DF-501 A&B

SECTION -H DETAIL A
NOTE :

Door to be assembled on a level surface all


corners to be 90' after completion door leaves to
be sheeted in position

156
INSULATION FSK-50-10
@20M LONG ROLL
(4CUT/ROLL)
ANGLE
104 P-97
BOTIOM ROLLER
IOUTSIDE II
I
DOOR PANEL
BOTIOM GUIDE CHANNEL
97-P-3000 (5) FIELD CUT
KWO LEG FIT INTO INTERMEDIATE HOLES
ALUM. &VINYL WEATHERSTRIP FOR SETIING INTO CONCRETE
12 0 PIN (150 LG.)
SECOND STAGE 1.0 MC/C (NOT BY KIRBY)
CONCRETE FLOOR LEVEL
(DOWELS)

100

DETAIL OF DOOR LEAF W/ BOTTOM GUIDE


DETAIL A-5

Position all doors (leaf) accurately lined & then second stage of conc. Tobe Done (to have botiom guide
in lined after alignment)

CHANNEL LUG
M6 x16 CSK SCREWS CLUB ALUM
~ ~
GUIDE CHANNEL ANCHORING DETAIL
VINYL STRI
p~l"
c LO

"'
~

WEATHER STRIP

UNIVERSAL COUPLER 4-M6 x16 CSK BOLTS


uc

GUIDE CHANNEL SPLICE DETAIL

157
I r--- - - DOOR LEAF
r-----_,/ : ~~~--~s CLOSURE
~~HANNEL
~CH~NEL KWO
I ANGLE (UP)
I
I
INSULATION FSK-50-10.
\ I V DOORSTILE @20. MLONG (4ROLLS)
(4 CUT/ROLL)
\ I DOOR PANEL
\ I I KW-0.5-4925
\ I
.I
II VOOLOCiKING ARRANGEMENT ,...,
1 TSIDE &INSIDE) "--'
\. II [i ,__.,
c
I. I. "' c--'

I .
I.I
I ~HEAVY DUTY HANDLE loUT SID@ I INSIDE I
f'I.
I I.
< I I
. I
[
I . - SDS # 1425
I. I. (TYP.) 'n

I I VLOClKING ARRANGEMENT :'--"


I I TSIDE & INSIDE)

I
.
I
I. "'
[i r-. c
.I
f--.-'

I
I.
' I DOOR STOPPER
v~ SIDE &INSIDE)
1
\ r BOTTOM CHANNEL
~LE(DOWN)

r
FLOOR LEVEL
~----~JI~ II~+----1~~ C=LO~S'{J.t,UR;f-E---1~....{/:.____QInD"OQQ"OR LEAF
KWO - - - BOTTOM CHANNEL

.JA
(FOR LOCKING ARRANGEMENT) SECTION A INSULATION & DOOR
DETAIL-A6 PANEL ARRANGEMENT)

DOOR LEAF STILE


ANGLE PA-5000
(L75x50x1.75) 19A
NOTCH@ HINGE LOCATION
HEAVY DUTY HINGE

KW PANEL@ 4925 DETAIL-A2


12 12 12 12
470 1040 685

HEAVY DUTY HINGE


DET-A1
(TYP.)

PLAN VIEW

DETAIL-A6
LOCKING ARRANGEMENT
CLIP

158
ANGLE
PA-5000
(L75x50x1.75)
19A
HEAVY DUTY HINGE
NOTCH@ HINGE LOCATION

'r0N PANEL@ 4925


HEAVY DUTY HINGE

470 1040 (TYP.)

WITH WALL PANEL

DETAIL -A1
FOLDING SLIDE DOOR LEAF

---~-~~~~~~~~~~~~~j~
--

~ KC PANEL@ 4925
1040

WITH CONSEALED PANEL

f-J r "'-/
-------------- ------------ ---

KR PANEL@ 4925
~

1040

I WITH KR PANEL I

--- . ----- . ----- . -----. ----- ' ---


f-L \5I' '-I \d L

1040

I WITH KW PANEL I

159
7.12 ROLL-UP DOOR
DETAILS

(1)

GENERAL VIEW OF RUD.


VIEW FROM INSIDE

0 ROLLED PLASTIC WRAPPED DOOR

BRACKETS (LEFT AND RIGHT HANDED)

ROLLED PLASTIC WRAPPED


D
1) Double Saddle

0 DOOR GUIDE (LEFT AND RIGHT HANDED)


2) Keeper Plate
3) Head Stop
4) Head Stop

Part list:

1-2 Left & Right Brackest 10 Bottom Bar Angle

I 3-4
5
Right & Left Door Guide
Guide Brackets
11
12
WEATHER STRIP
HEAD STOP
I

6 Double Saddle 13 ALUM. STRIP

I I
8-9
Door curta1n
Locking Assembly
16-20
21
Axle- Spring BKT.
CUSHION HEAD STOP
I

9A-9B Outside & Inside Locking Bar 22 KEEPER PLATE

I 23 JAMB I

160
GIRT
200 z clip 1-25 Clip - 1-500R

HEADER /

200x100C '' CHAIN WHEEL


PULLY
THIS CLIP REQD. FOR ELCTRICALLY (.!)
z '
X~ OPERATED DOORS ONLY zw
//~HAIN CLIP
a_
0
USE 12X25 RDND. BOLTS
~
-'
1- 8 DOORJAMB u
200x 100C

CHAIN CLIP
"" F/ DRILLING HLS. IN GUIDE)
"
--------'D=--=Oc-=O~R-'-'W=ID-'-'TH-'---------11
II

160ANCHORBOLT '
I - 160ANCHORBOLT "
II
II

"
II
II
I I

ELEVATION (VIEW FROM INSIDE BLDG.) I I


I'
1 I
1 I
I I
ROLL UP DOOR 1
1 I
I

(USE 12 X 30 MS BOLTS. FOR F.O.) (U. NTD.) lJ


ViewX1
Showing Drive Chain

GIRT

KW. PANELS
CLIP - 1-500R
100
Clip
1-500L
I INSIDE I

I DOORWIDTH
~~----------~ i
BRACKET Std Clip
_L__-----,L__-----'-1 - - - - - - - - - - - - f--------------------------------------- _j 1-501
DOOR CLEARANCE LINE
BRACKET

PLAN VIEW X-X

STEEL LINE DOORJAMB

6 mm PL.

SECTION Y
ANCHOR BOLT PLAN

161
7.12 ROLL-UP DOOR
DETAILS
Step-1 bracket fixing:

1. Fix left & right bracketto the clip 1-500l &


1-500r respectively
2. General tolerance for rud. Framing dimension
shall not exceed+/- 2 mm for vertical &
horizontal level.
3. Check all dimension and make sure that the
dimension are within tolerance limits before
assembling door.

~(23)

Step-2 position door on bracket:

With the door correct way round (the curtain


rolls down rear of the opening) carefully lift
door onto the brackets, using block and tackles
attached to the door axles, or other suitable
lifting equipments.
A. Do not cut the band that holds the door in a
roll.
B. Rest axle between two cast iron saddles and
loosely secure to bracket arms with keeper
plate, bolts, nuts and washer provided. See
sketch b below. If chain gear is fitted, ensure (B)
that the chain is placed around the chain
wheel and hangs down freely. As shown in
view x1
POSITION THE BOTTOM RAIL HERE

Before tightening saddle bolts, position the door


1. So that it overlaps the opening evenly both
side.
2. So that the axle is positioned on the bracket
arm slots as far forward
Possible, while still allowing the bottom rail to
pass the lintel or header when the door roll is
rotated. See sketch a. 3) Rotate both the door
and the axle so that bottom rail is level with
bracket arm . See sketch a.

(A)

162
Fixing or above the bracket arm
by dimension 'G' for restricted headroom
Door height dimension 'G'
upto4200mm 65mm
4200mm to 5100 mm 45mm

Step 3 Install guide:

Guide must be the correct length, top of the


guide should be level with top of bracket arm for
door height. If guides need to be shortened cut
from the bottom of guide.

Position the guide true and plumb of each side of


the opening allowing 3-4 mm of working clearance
between the door and the inside of each guide,
mark, drill and fix both the guides with coach
screw and washer supplied.

Step 4 Spring tensioning and bottom


rail sto:

Check top of the guide-in to ensure that the


door does not make contact when rotated apply
tension to spring by rotating door approximately
two complete turn in a forward direction (see
arrow on sketch a) after ensuring axle is securely
clamped. The amount of tension required for
satisfactory operation may vary with individual
doors, depending on size. Hold the door firmly
cut the bands, feed the door down into guides
below the head stop. Fit bottom rail stop using
self locking nuts provided. Allow the door to rise
and to rest against head stop.
(See sketch b) (A)
Operate door up and down a number of times to
check the operation.

SELF
LOCK
NUT

(B)
163
7.13 HANGAR DOOR
DETAILS

POCKET / POCKET I
LEAN-TO LEAN-TO
'A' 'A'
BUILDING WIDTH
'B'

HANGAR DOOR ELEVATION

1 BUILDING &
eft-- DOORFRAME
1[ SYMMETRY
I
DOOR 10GAP
LEAF
WIDTH
2
-- +-

CLEAR DOOR OPENING

DOOR LEAF PLAN


I
4
:_ DOOR FRAME
(TYP)
,ME& RAIL

1 LEVELING ANGLE
(L50x50x4)

WHEEL
FINISH FLOOR LEVEL

FIN. FLOOR LEVEL

LEVELING ANGLE TO
BE SET BY ADJUSTING
THESE TWO NUTS.
TACK WELD RAILS TO
H~'"T"---------cr--'-------c---'t-H-r-----71. ANGLES AND RECHECK
FOR REQUIRED LEVELS,
BEFORE FINAL
SECTION: 1 CONCRETE POURING.

012 ANCHOR BOLTS


DETAIL: 5
NOTE :

1. Clear height & clear opening are customers'


option.
2. Dimensions 'a' & 'b' are determined by type
of doors, cladding etc.
3. For common usage customer is required
to specify the range of aircraft to be
considered.

164
HANGAR DOOR ELEVATION

1. Clear height & clear opening are


customers' requirement.
2. Dimensions 'a' & 'b' are detirmined by
type of doors, cladding etc.
3. For common usage customer is
required
HANGAR#1

DOOR LEAF PLAN


To specify the range of aircraft to be
considered.
DIMENSIONS
DEPENDING
SUPPORT ON CUSTOMER
ANGLE REQUIREMENT
L275x85x2.5 AND DESIGN.
( WALL GIRTS
FIELD CUT
DOOR
ASREQD
FIXW/SDS
l;~~~j:4' WALL PAN ELS PANELS
FLASHING

2-M12ROUND L120X120X2.5
DOOR
HEAD BOLTS FRAM TACK WELD@
INTERVALS

DETAIL
CLEAR WALL GIRTS
DOOR OPENING
HANGAR# 1

SECTION: R
DETAIL
(TYP) DOOR LEAF
LAP DETAIL
DETAIL

500 (MIN) (MIN) (MIN) (MIN) (MIN) (MIN) (MIN)
(AS (AS (AS (AS (AS (AS (AS
REQ'D) REQ'D) REQ'D) REQ'D) REQ'D) REQ'D) REQ'D)

! M16X55H . S . ~OLTS

i
i
I
i
i
BOTTOM OF ~OFFIT
PANEL SUPPORT TOP OF DOOR
ANGLE.

SECTION

I T - - -- - f iN. FL. LVL

LEVELING ANGLE TO

TACK WELD RAILS TO


ANGLES AND RECHECK
FOR REQUIRED LEVELS,

SECTION : 1

165
11240

11074

A~
I

- ~
! ~
I
--'k-- I = = = F
hfi
= = l l= 1/
I

~ +- --
~ =~'
~ I
~ ~~ CJ F ~ I:~ l =It=======~!
rf -
E

~~- ~~~~~~~~~~~~~~~~~=======3F=~======~
N ~ I
I ~I~ I'(
-'~<-- = = = I= II=!Fif==========~
I :1 ~PANELS I
~-k---- 1 = = = I* ' F= = = 14===~
=====F=IE=LD=CUT
==~II
PANEL AS
I - - - ~Qn I

lli ( FLASHING
if ~ I ~

11 _u iJL.lllt/
A~ L GLASS NOT BY K RBY

DOOR LEAF FRAMING & CLADDING DETAIL SECTION A-A

FLASHING DOES
I - NOTOCCURAT
.fl-- - - - - - - - - - -1'-"12p'40' - - - - - - - - - - - - - - - +---J.I'
f LAST LEAF END STYLE

4-------------1~ -------------...L~-f_~ FLASHING


K FLASHING FLASHINJ

SECTION B-B

DOOR ROLLER
ASSEMBLY

FLASHING
GLASS
NOT BY KIRBY. NEOPRENE

E9
K.R.O. CLOSURE
FILLER

FLASHING
STRIP
DETAIL E
NOT BY KIRBY

DETAIL C9
#12X20 SOTS
@333C/C DETAIL AT FRAME TOP BOOM

\ #14X25 SDS @300 C/C


\ FLASHING

DETAIL DETAIL

#12X20 SOTS

DETAIL @) DETAIL
AT WINDOW STYLE

166
450 5000 8833

/
/ KICKER

/
DOOR SUPPORT@ ENDWALL

SECTION SECTION Q)
SECTION

SECTION @ SECTION Q)
SUPPORT ANGLE (L 50x50x4)
VERTICAL FIELD CUT, BEND
CLADDING AND S.O.S. TO OTHER MEMBERS

FLASHING
FILED CUT TO SOFFIT PANELS
REQUIRED LENGTH
AND INSTALL
TAIL_r-1
PASSAGE I SECTION @)
FLASHING

SECTION
~L50X40X1.
i, '"~orr7mo
5
2<5075&SDS

SECTION SECTION

167
7.14 CRANE SYSTEM DETAILS

CROSS SECTION AT CRANE (RIGID FRAME)

I-
I
(!)
w
I
w
:;: I
w

CRANE SPAN = c/c RAILS CRANE SPAN = c/c RAILS

CROSS SECTION AT CRANE (BEAM & COLUMN)

!i:
(!)
w
I
w u..
0
~ I [l_
o1-
~
CRANE SPAN = c/c RAILS CRANE SPAN = c/c RAILS

CROSS SECTION AT CRANE (MULTI-SPAN)

TYPICAL RAIL FIXING DETAIL

f ') ':}'j}'o { ~/r"~"


i
SPECIAL BOLT
W/ NUT

ROUND
2 mm GAP II SPRING WASHER
WASHER

SUGGESTED RAIL SPLICE DETAIL

168
7.14 CRANE BEAM & RAIL
DETAILS

CRANE BEAM

DIAPHRAGM ANGLE

DETAIL ' A' PLAN 8-B

D D
~ ------.::::::"

L. 70x70x6
DIAPHRAGM

CRANE RAIL

M20 l1l HS BOLTS CRANE BEAM

4-M20x70 4-M20x70
H.S. BOLTS H.S. BOLTS

SHOP WELDED
BRACKET

DETAIL ' C'

NOTE :
6-M20 x 70 150 90 90 75
H.S. BOLTS Crane beam support bracket is provided with
CRANE RAIL
slotted holes for easy assembly of bracing and
diaphragm angles. Adjustment of rail centers are
to be carried out by hook bolts. Where welded
bar rails are used, the adjustment of rail centers
are carried out by cranebeam. After aligning, if
the bracing and diaphragm angles does not fit
CRANE BEAM properly, weld them at the column end to their
Respective clips. Scrapepaint at welding area.
Repaint all field welds.
DETAIL AT CRANE STOP

169
7.14 CRANE BEAMS &
RAILS- EXPANSION JOINT
DETAILS

CRANE BEAM EXPANSION JOINT DETAILS

300
12
r-

~x12
WEB 6THK.
@ 400

DETAIL OF CRANE BEAM

CRANE RAIL EXPANSION JOINT DETAILS DETAIL OF SUPPORT BRACKET


RAIL BY OTHERS AT EXPANSION JOINT

170
7.15 MEZZANINE DETAILS

COVERING WIDTH = 810 mm COVERING WIDTH = 810 mm


SIDE LAP SIDE LAP
I
T
I

I EDGE AN GLE
"'( 100x75x3.5
(.9
I
z
(3
it
en
I

r-
en I

Q <( I

\__ No.14x25 SDS


v I ATEDG EANGLE
MAX. SPACING
300 c/c

SIDE LAP STITCH I

No.12x20SDTS

No.14x25SDS
@EACH JOIST
~
L
FLOOR JOIST (TYP)

DECK PANEL FASTENER LAYOUT

REINFORCEMENT AS REQD.
DECK PANEL (Not by KIRBY)

M16x55 M16x55
H.S. BOLT H.S. BOLT
FLANGE BRACE FLANGE BRACE AT FIRST FLANGE BRACE
L.75x75x6 L.75x75x6
JOIST FROM MEZZANINE
SUPPORTING COLUMN

DETAIL- A DETAIL- B
AT INTERMEDIATE BEAM AT END BEAM

~ t- ~ ......

4-M12x40 8 mm GAP 2-M12x40 EDGE AN GLE


H . S.BOLTS ~ H.S.BOLTS ~ L.100x75x3.5

"- ~.

-"' "- -~

MEZZ. BEAM
1 MEZZ. JOIST MEZZ. JOIST 1
MEZZ. BEAM
~ ~ ....
"'"'"
PLAN 1-1 PLAN 2-2

171
EDGE ANGLE
~ L.100x75x3.5 FIELD-C UT
I" '&
WELD AROUND co LUMN

I
F/CUT DECK PANEL
I I
AROUND COLUMN
KIRBY DECK FLOOR JOIST
PANEL

L.1 00x75x3.5 END LAPS ALWAYS OCCUR AT AJOIST


FIELD-CUT DECK PANEL DECK IS FASTENED TO JOIST AT EACH SIDE
F/CUT & WELDED
AROUND COLUMN
FLOOR JOIST
DETAIL- G
DECK PANEL END LAPS
DETAIL- E
EDGE ANGLE
PLAN AT RIGID FRAME COLUMNS

DETAIL- F
PLAN AT WIND COLUMNS

CONCRETE (Not by KIRBY)


CONCRETE KIRBY DECK PANEL
No.14x25 SDS MAX. DEPTH= 100 mm
(Not by KIRBY)
@ 300 c/c MAX.

CONTINUOUS EDGE ANGLE


100x75x3.5

MEZZANINE BEAM

WALL PANEL
CONNECTION BOLTS
{AS PER DESIGN)

COLUMN
COLUMN
H.R. OR PIPE

DETAIL- D DETAIL- H
MEZZANINE BEAM FRAMING TO COLUMN WEB MEZZANINE SUPPORT COLUMN

I , .," "' \
--:-

~DE~
CONCRETE
810

REINFORCEMENT A
j(Not by KIRBY)
REQD.

EDGE AN GLE
L.100x75x3 .5

~
1 ,.
SIDE LAP OF DECK PANEL FLOOR JOIST

MEZZANINE BEAM

DETAIL- J
--
PANEL SIDE LAPS

172
------------------------~'

-~

CONCRETE (Not by KIRBY)


No.14x20 SOTS MAX. DEPTH= 100 mm
@ 300 c/c MAX.
I r
KIRBY DECK PANEL

CONTINUOUS EDGE ANGLE .:., : :.!


100x75x3.5

. . ...
1
BRACKET I CONNECTION BOLTS
SHOP-WELDED

...
(AS PER DESIGN)
'
WALL PANEL

I MEZZANINE BEAM

~
~

DETAIL- C
MEZZANINE BEAM FRAMING TO COLUMN FLANGE

DETAIL- K
MEZZANINE FRAMING PLAN
AT BEARING FRAME ENDWALL

General notes:

1. Mezzanine floors and flat roofs are designed


for concrete slab of a maximum thickness of
100mm including the thickness of corrugated
'kirby' deck panel.
2. Concrete is not the responsibility of kirby
building systems and must be designed by a
qualified civil engineer.
DETAIL- L
MEZZANINE FRAMING PLAN
3. Reinforcing steel or wire mesh shall be placed
AT MAIN FRAME ENDWALL in the concrete as required by the design and
Design data: in accordance with the concrete compressive
strength and recognized Building codes.
1. Large openings in the mezzanine slab which 4. Live load deflection of structural members
require the partial removal of steel joists are limited to L/240 unless otherwise
must be specified in size and location to required or specified.
'kirby' and will require steel framed openings. 5. The mezzanine deck panel is considered
Any loading, from staircase, for example, on to carry only the Weight of the concrete
the steel framed openings must be defined (100mm maximum thickness).
in magnitude and location. The supply of 6. The concrete slab should be designed to
staircase by 'kirby' is limited to only when top carry the full Live load and any additional
of concrete is at 3.5 And 4.0 M from bottom floor finishes.
of base plate.
2. Mezzanine i flat roof live load must be 7. Concentrated loads due to storage of materials
specified in addition to any loadings from and Placing of concrete should be avoided.
floor finishes, suspended ceiling, mechanical 8. Mezzanine deck panels must be fastened at
ducts, piping, etc. every Corrugation to mezzanine joist using
3. Top elevation of concrete or clearance under s.O.S. Fasteners.
steel Joists i beams must be specified. 9. Openings in the mezzanine slab between
4. Depth of mezzanine construction varies steel joists May be made without affecting
between 60 em And 100 em depending on the steel mezzanine Framing, provided
loading support column Spacing and other proper reinforcement around the Openings
design criteria. is considered in the design of the slab.
173
7.15 STAIRCASE DETAILS

~
II

ELEVATION

I I, .I

~
4400 ~
.---

I J .,
TYPICAL TREAD DETAIL CONNECTION TO MEZZANINE FLOOR JOIST
FRAMED OPENING FOR STAIRS

4000
,-----v--- 1500
~E ANG LE
I 5x2.5

~ !
~
J SECTION -A SECTION- C

,...._ l:l
~ ~ I 250x100 .5

~p ~ ~100 .5
I=

VIEW-D SECTION- E

174
7.16 WALL PANEL &
DOWNSPOUT DETAILS

SECTION AT
VERTICAL LAP CORNER DETAIL

No 14x25 SDTS@ 333 0 C


~lRUT
AT EACH SUPPORT

L ~
~
TRIM

G~
p
No.12x20 SDTS SCREWS FOR CORNER
STITCH S CREWS
4 @2220 SPACE &
,_ TRIM TOM ATCH
r- STITCH & MEMBER
2 BETWEE N MEMBERS SCREWS IN ALL PANELS

~ SDS I SOTS TABLE


BA
BASE CHANNEL
p
INSULATION PANEL TO PANEL TO
SIZE STRUCTURE PANEL
K.W. WALL PANEL FASTENER LAYOUT
0 to 60 No. 14 x 25 No. 12 x 20
75 to 100 No. 14 x 50 No. 12 x 20
110 to 150 No. 14 x 76 No. 12 x 20

175
Span
SPAN Down-
DOWN- Span Down-
SPOUT
{U {0 spout
SPACING
spout
spacing Spacing
1f)? G~
~ 6,9&12m 24.0 m O.C.
DS-501
6,9&12m 24.0 m O.C.
O.C. 48 m 13.5 m O.C.
15m 22.0 m

~~
15m 22.0 m O.C.
O.C. 54m 12.5 m O.C.
18m 19.0 m

"Iu
18m 19.0 m O.C.
O.C. 60 m 11.5m0.C.
20m 17.5 m
s. DOWNSPOUT SPACING {0 20m
24m 17.5 m
15.0 m O.C.
O.C.
72 m 10.0 m O.C.
l
S/2 = ONE HALF DOWNSPOUT SPACING ~

GU-502
~
DS-502
24m
30m
30m
15.0 m
13.0
13.0
m O.C.
O.C.
m O.C.
I 84m
96 m
8.5m0.C.
8.0m0.C.
36m 11.0m0.C.
36m
42 m 11.0m0.C.
10.0 m O.C.
42 m
45 m 10.0 m O.C.
9.5mO.C.
GUTTER & DOWNSPOUT REQUIREMENTS 45 m 9.5mO.C.

GUTTER

DOWNSPOUT STRAP
DS-501 OR DS-502 S-503
POP RIVET
CAULK WITH
ELASTOMERIC
SEALANT F/CUT AT BOTTOM OF FASTENERS TO
GUTTER AND BEND DOWNSPOUT STRAP BLOCKWORK
DOWNSPOUT DOWN INTO DOWNSPOUT S-501 OR S-504 (Not by KIRBY)

DETAIL 'A'
GUTTER & DOWNSPOUT ASSEMBLY

General notes
WALL PANEL
1. Panel module- there is a plus or minus
tolerance Bull t into K.W. Panel.
DOWNSPOUT STRAP
Measure and mark *1000 O.C. (Begining on
S-502 OR S-505
@ 3000 CRS (MAX) the Steel line for endwalland '167 from steel
DETAIL s Line for sidewall) along base angle to check
Any dimensional gain or loss during
installation.
*Dimensions are applicable for buildings
having 333 Increments. Refer building
installation drawings for others.
2. Foundation must be square, level and of
correct Out to out dimensions for the
TYPICAL DOWNSPOUT DETAIL required building.
AT FULLY OPEN SIDEWALL
3. Building must be tight and plumb before
Sheeting begins.
4. Installation of panels should always Be as
showm in section 'a-a'.
5. Building installation crew is to clean all wall
panels Before leaving job site.

176
7.16 WALL PANEL DETAILS
WITH EAVE TRIM

END LAPS
ROOF PANEL l 0 ROOF PANEL
ROOF PANEL TO SKYLIGHT ~
ROOF PANEL TO PEAK PANEL

INSTALL No.14 SDS


TWO ON EACH LOWER SIDE OF THE MAJOR
RIB AND ONE BETWEEN MINOR RIB

INSTALL No.12x20 SDTS STITCH


SCREWS ONE AT EACH MEMBER
AND THREE IN BETWEEN
KRI CLOSURE

AVE STRUT
No.14 SDS (iil333 O.C.
AT EACH MEMBER

RAKE TRIM RF-501


EAVE TRIM EF-501

LAP RAKE TRIM OVER


END CAP (USE POP RIVETS)

ROOF PANEL INSTALLATION

EAVE STRUT r"'" ~IN PEAK PURLIN


PURLIN A =

ST~CH
I j No.12x20 SDTS
ONE AT EACH SUPPORT AND
SCREWS

AT 300 O.C. (MAX.) IN BETWEEN

No.14 SDS AT
1660.C.
No.14 SDS@ 333 O.C.
AT EACH INTERMEDIATE PURLIN No.14 SDS 2 ON EACH LOWER
SIDE OF THE MAJOR RIB AND
ONE BETWEEN MINOR RIBS

ROOF PANEL FASTENER LAYOUT

177
SEALING TAPE
ROOF PANEL

RAKE TRIM RF-501 RAKE TRIM RF-50

No.14 SDS@ 333 O.C.


FLASHING EF-506

DETAIL 'C' DETAIL 'D'


SHEETED ENDWALL OPEN ENDWALL

RAKE SECTIONS
No.14 SDS@ 166 O.C.
No.14 SDS@ 166 O.C.
No.12x20 SDTS
@6670.C. No.12x 20 SDTS
@6670.C.
EAVE TRIM EF-501
EAVE TRIM EF-501

DETAIL 'D'
DETAIL 'A' OPEN SIDEWALL
SHEETED SIDEWALL
No.14 SDS@ 166 O.C.

No.12X20 SDTS@ 166 O.C.

EAVE TRIM EF-501

DETAIL 'E'
PARTIALLY OPEN SIDEWALL

SIDE WALL EAVE SECTIONS

General sheeting notes

1. The building is to be tight and plumb before


sheeting is to begin.
2. Sheeting is to begin at the leeward end of
SDS I SOTS TABLE building so that all Panel laps will be away
INSULATION PANEL TO PANEL TO
from prevailing wind.
SIZE STRUCTURE PANEL 3. Skylights receive same screw pattern as roof
0 to 60 No. 14 x 25 No. 12 x 20 panels except Skylight to skylight stitch. Use
75 to 100 No. 14 x 50 No. 12 x 20
grommet screws at this Condition.
4. After building installation, fill all unused
110 to 150 No. 14 x 76 No. 12 x 20
screw holes in the roof with No. 17X20 self
tapping screws.
5. Building installation crew is to sweep roof
panels clear of all metal shavings.
6. All dimensions are in millimeters.

178
7.16 WALL PANEL DETAILS
WITH EAVE GUTTER
END LAPS
ROOF PANEL TO ROOF PANEL
ROOF PANEL TO SKYLIGHT ~
ROOF PANEL TO PEAK PANEL

INSTALL No.14 SDS


lWO ON EACH LOWER SIDE OF THE MAJOR
RIB AND ONE BElWEEN MINOR RIB

INSTALL No.12x20 SOTS STITCH


SCREWS ONE AT EACH MEMBER
AND THREE IN BETWEEN
KRI CLOSURE

sTRUT

RAKE TRIM RF-501

LAP RAKE TRIM OVER END AND CUT


GUTTER GU-502 TO FLASH GUTTER - 1/10 ROOF SLOPE

ROOF PANEL INSTALLATION

EAVESTRUT I'" ~ PEAK PURLIN I'"


PURLIN .4 ==

8E3E3EIBE!E~LAP

j ST~CH
No.1 2x20 SOTS
ONE AT EACH SUPPORT AND
SCREWS No.14 SDS@ 333 O.C.
AT EACH INTERMEDIATE PURLIN
No.14 SDS 2 ON EACH LOWER
/_ AT 300 O.C. (MAX.) IN BElWEEN SIDE OF THE MAJOR RIB AND
ONE BETWEEN MINOR RIBS
No.14 SDS AT
1660.C.

ROOFPANELFASTENERLAYOUT

179
No.12x20 SOTS@ 166 O.C.

PANEL CAP FLASHING MF-515


INSTALL WITH ROOF PANEL
IF ROOF SHEETING IS DONE
BEFORE WALL SHEETING

GUTTER GU-501
GUTTER GU-501
ORGU-502
ORGU-502

No.14X25 SDS @333 O.C.

DETAIL 'A' DETAIL 'B'


SHEETED SIDEWALL OPEN SIDEWALL

SIDE EAVE SECTIONS

RAKE TRIM RF-501


No.12x20 SOTS@ 333 O.C.

No.1 4SDS@3330.C.---tlt~===~~~~

RAKE ANGLE AS SHOWN FOR


1/10 ROOF SLOPE. ATTOP OF
PURLIN FOR 1.3/10 AND ABOVE

DETAIL 'C' DETAIL 'D'


SHEETED ENDWALL OPEN ENDWALL

RAKE SECTIONS

General sheeting notes:

1. The building is to be tight and plumb before


sheeting is to begin.
2. Sheeting is to begin at the leeward end of
building so that all Panel laps will be away
LAP RAKE TRIM OVER ENDCAP
from prevailing wind.
12 mm FOR 1.3/10 ROOF SLOPE AND ABOVE
3. Skylights receive same screw pattern as roof
panels except Skylight to skylight stitch. Use
DETAIL 'E'
grommet screws at this Condition.
4. Building installation crew is to sweep roof
panels clear of all metal shavings.
5. All dimensions are in millimeters.
SDS I SOTS TABLE
INSULATION PANEL TO PANEL TO
SIZE STRUCTURE PANEL
0 to 60 No. 14 x 25 No. 12 x 20
75 to 100 No. 14 x 50 No. 12 x 20
110 to 150 No. 14 x 76 No. 12 x 20

180
7.16 ROOF PANEL DETAILS
WITH VALLEY GUTTER

END LAPS
ROOF PANEL TO ROOF PANEL
ROOF PANEL TO SKYLIGHT ~
ROOF PANEL TO PEAK PANEL

INSTALL No.14 SDS


TWO ON EACH LOWER SIDE OF THE MAJOR
RIBAND ONE BETWEEN MINOR RIB

KRI CLOSURE
WI SEALING TAPE INSTALL No.12x20 SOTS STITCH
@TOP &BOTTOM SCREWS ONE AT EACH MEMBER
AND THREE IN BETWEEN

EAVE STRUT

RAKE TRIM RF-501

FIELD CUT CONDUCTOR HEAD

ROOF PANEL INSTALLATION

LAP LAP
t t
? .. . . . . . . . . . ~

_j
~
PURLIN

No.14 SDS 2 ON EACH LOWER


SIDE OF THE MAJOR RIB AND
ONE BETWEEN MINOR RIBS

~1
~
PURLIN

.:r
~ ~ No.14 SDS@ 333 O.C.
AT EACH INTERMEDIATE PURLIN

v
? ~

PURLIN
_j

:::, No.12x20 SOTS STITCH SCREWS


---------.._, ONE AT EACH SUPPORT AND
.. . . ~ - AT 300 O.C. (MAX.) IN BETWEEN

PURLIN
_j ~ No.14 SDS AT
1660.C.

ROOFPANELFASTENERLAYOUT

181
No.14SDS
@333D.C
INSIDE
CLOSURE
CORNER DETAIL

VALLEY GUTTER AT FLUSH WALL

VALLEY GUTTER AT
HIGH-LOW ROOF TRANSITION

VALLEY GUTTER WITH OPEN END

VALLEY GUTTER
WITH CLOSED END

SECTION X DOWNSPOUT INSTALLATION

General sheeting notes:

1. The building is to be tight and plumb before


sheeting is to begin.
2. Sheeting is to begin at the leeward end of
FIELD SPLICE FOR
1.0 mm Thk. OR HEAVIER GUTTERS
building so that all Panel laps will be away
from prevailing wino.
3. Skylights receive same screw pattern as roof
panels except Skylight to skylight stitch. Use
SDS I SOTS TABLE grommet screws at this Condition.
INSULATION PANEL TO PANEL TO 4. Afitr building installation. Fill all unused screw
SIZE STRUCTURE PANEL holes in the roof with No. 17X20 self tapping
0 to 60 No. 14 x 25 No. 12 x 20 screws.
75 to 100 No. 14 x 50 No. 12 x 20 5. Building installation crew is to sweep roof
110 to 150 No. 14 x 76 No. 12 x 20 panels clear of all metal shavings.
182
7.16 PANEL & TRIMS
FOR EAVE & PUR LIN
EXTENSION CANOPIES

PIG SPOUT
PS-501

DETAIL 'A'
1500 EAVE CANOPY WITH SOFFIT

MF-510UR
ATRAFTE
(REF. SECTION 'X')
PIG SPOUT
PS-501

DETAIL 'B'
1500 EAVE CANOPY WITHOUT SOFFIT

CANOPY RAFTER

SECTION 'X'
AT CANOPY RAFTER

183
ROOF PANEL
PEAK PANEL

DETAIL ' C' DETAIL 'F'


SECTION THRU' EAVE CANOPY SECTION THRU' PEAK
WITHOUT GUTTER

No.1 2x20 SOTS 333 O.C

DETAIL 'D' DETAIL 'G'


PURLIN EXTENSION CANOPY EAVE CANOPY WITH
WITH SOFFIT SOFFIT & GLASS WALL

ENDWALL
STEEL LINE

NOTE
ClOSDRE I SOFFIT MATERIAL
TOBE FURNISHED BY OTHERS

ENDWALL PANELS
F/CUT @PURLINS

DETAIL ' E' DETAIL ' H'


PURLIN EXTENSION CANOPY OPEN ENDWALL FRAME WITH
WITHOUT SOFFIT PURLIN EXTENSION CANOPY

KRI CLOSURE KRI CLOSURE

DETAIL 'J' DETAIL 'K'


SECTION THRU' EAVE OF SECTION THRU' EAVE OF
PURLIN EXTENSION WITH SOFFIT PURLIN EXTENSION WITHOUT SOFFIT

184
7.17 WALL LINER PANEL
DETAILS
LAP(TYP)

No.l4x20SDS
MEMBER SCREWS~ 33)------j 1/
D.C. @EACH SUPP"ORT~

===I
TYPICAL LINER LAYOUT PLAN
SCREW LAYOUT FOR LINER PANELS

DETAIL "A1" DETAIL II A2'' DETAIL "A3"


BEARING FRAME C CORNER COLUMN BEARING FRAME H.R. CORNER COLUMN BY-FRAME MAIN END CORNER COLUMN

K.R. Uffi PANEL

DETAIL "81'' DETAIL "82''


DETAIL "A4" FOR INTERMEDIATE END WALL FOR INTERMEDIATE END WALL
FLUSH FRAME MAIN END CORNER COLUMN COLUMN DEPTH OVER 250 mm COLUMN DEPTH UP TO 200 mm

DETAIL "83" DETAIL "C1' DETAIL "C2"


FOR INTERMEDIATE END WALL AT FLUSH FRAME
AT BY-FRAME SIDEWALL COLUMNS
SIDEWALL COLUMNS
COLUMN AND INTERIOR COLUMN

185
RAKE TRIM RF-501

SHEETING ANGLES
SHEETING ANGLE FLASHING
L.125x50x2.5 STS --1-/---ll.l~ ENDWALL COLUMN
OR F/WELD TO RAFTER ~DTS
ENDWALL PANEL
ENDWALL PANEL K.R. LINER PANEL
K.R. LINER PANEL- INSTALL
BEFORE OUTSIDE PANEL

DETAIL 'D' DETAIL 'E' DETAIL 'F'


SECTION AT BEARING FRAME SECTION AT MAIN FRAME SECTION AT SIDEWALL
ENDWALL RAFTER ENDWALL RAFTER WITH WALL LIGHT

W A L L P ; U A N LWALL LINER
OF-502
MF-527

DETAIL ' H' DETAIL 'J'


SECTION AT JAMBS FOR SECTION AT HEADER FOR
FRAMED OPENINGS/DOORS FRAMED OPENINGS/DOORS

DETAIL ' G'


SECTION AT SIDEWALL WITH
WALL LINER & SKYLIGHT LINER

EAVESTR
CAP TRIM
MF52~WF502 CAP TRIM WF-502
WF-502
WALLP:UNEL- No.12x20SOTS
WALLLINER No.12X20SDTS @3330.C.
MF-505 @333 0.C.
MF-529 WALLPANEL-ll ~- WALLLINER WALL LINER
WALL LINER

DETAIL 'K' DETAIL 'L' DETAIL 'M' DETAIL 'N'


SECTION AT HEADER SECTION AT SILL SECTION AT EAVE SECTION AT GIRT
FOR OPEN CONDITION FOR FRAMED OPENINGS

FLASHING
EF-504
NOTE :
POP RIVET
rSTEELLINE
No.l2x20SOTS
WALLPAN~L- tfWALLLINER

1. Details shown on this drawing may not Occur


RF-502
No.l2x20SOTS
BASE CHANNEL FLASHING @3330.C
EF-506
206x76Cxl.5
No.l2x20SOTS J
all together in one building. Use those details
No.I4SOS
WALL PANEl
ALL LINER
WALLLIGH FLASHINGMF-529

which comply with the Structural framing.


Fl!lRILLBASECHANNEL
FORI20ANCHORBOLTS

SECTION AT BASE SECTION X-X DETAIL 'Y'


REFER DETAIL 'F' REFER DETAILS ' F' & ' G' Refer to building installation Drawing.
2. Refer sheet no. For roof and wall liner
Combination.
3. All dimensions are in millimeters.

186
DETAIL A DETAIL B
AT EAVE- WITHOUT WALL LINER AT EAVE- WITH WALL LINER

DETAIL C DETAIL D
AT PURLINS -WITH END LAP AT PURLINS

~.12x20SDTS
@667 O.C. (TYP.)
END SKIRT OF
VENTILATOR

DETAIL E
AT PEAK
MF-527

No.14x20 SDTS@ 333 O.C. _j No. 14x25 sos-:..1


@1670.C.

DETAIL F SECTION 1
AT PEAK- WITH VENTILATOR
FOR 7500 BAY

CLIP
1-71
M12x30
M.S. BOLTS

ENDWALL
FLASHING MF-540
PANEL

682 682 FOR 706 PURLIN LAP - - ENDWALL LINER

DETAIL G DETAIL H
AT INTERIOR RAFTERS AT LIGHT ENDWALL ' C' RAFTERS

187
MF-517A(2)

No12x20SDTS
l
~ MF-517AORB
KR PANEL

@500 0 C (TYP )
ENDWALL
PANEL-- SHEETING ANGLE MAIN END RAFTER
ENDWALL
PANEL 356
- - - ENDWALL LINER

DETAIL K DETAIL L
AT LIGHT ENDWALL H.R RAFTERS AT MAIN END WITHOUT WALL LINER

+ +

Z
MF-529

F/CUT FLASHING TO PROFILE


AND LAP- CONN. W/ STS

DETAIL M SECTION "2''


AT SKYLIGHT

SIDE LAP SIDE LAP SIDE LAP

~~ N

- No.14x25 SDS MEMBER SCREWS


No.12x20 SDTS STITCH SCREWS
@333 O.C. AT EACH PURLIN
ONE ATEACH PURLIN
AND ONE IN BETWEEN

TYPICAL SCREW LAYOUT


ROOF LINER PANELS

188
7.17 LINER PANEL DETAILS
FOR SLIDE DOORS

8p
I '----- f-1

,---
'---- f-1

.Q._ _,g. .Q._ __.Q.


.--- ,---
'---- f-1

~ ,--- C),
/~
'---- f-1
~
FIELD-WORK FLASHINGS
TYPICAL AT JUNCTIONS

I c b

8~

DOOR LEAF - 3.5 m HIGH DOOR LEAF- 4.5 m & 5.5 m HIGH

SINGLE SLIDE DOORS

8~
I

AP
I

~ __..g ~ __..g
'

c: ~
~ /~
FIELD-WORK FLASHINGS
TYPICAL AT JUNCTIONS

A~ 8~
N

"'

DOOR LEAF- 3.5 m HIGH DOOR LEAF - 4.5 m & 5.5 m HIGH DOOR LEAF
WITH 3o7o WICKET DOOR

DOUBLE SLIDE DOORS

189
TOP
DF-515
CHANNEL

TOP
CHANNEL DF-515

K.R.PANEL@560
FOR 4.5 mHIGH DOOR
K.R.PANEL@1560 DF-515
FOR 5.5 mHIGH DOOR

SECTION C-C
K.R. PANEL
DF-515
@1 150

K.R.PANEL
@1540

DF-515

SECTION D-D
DF-515

K.R. PANEL
@1050

OF-515 WICKET DOOR JAMB


K.R.LINER PANELS

DOOR GIRT
(TYP.)

K.R.PANEL POP RIVETS


@1050 POP RIVETS
@300 O.C.(TYP.)
K.R.PANEL DF-515
@1050 DF-515 No.14x25STS @2200
No.14x25SDS
@300 O.C.(TYP.)
No.14x25SDS
@333 O.C.(TYP.)
DOOR GIRT
(TYP.)
DF-515 SECTION - E
BOTIOM DF-515
CHANNEL
K.R. PANEL
@1050

SECTION A-A

LINER PANEL

BOTIOM DF-515
POP RIVETS
CHANNEL

DF-515

SECTION B-B
No. 14x25 SDS

NOTE:
ANGLE SUPPORT

WICKET DOOR
Keep girt connection bolt head direction facing HEADER

upward and use round head bolts at flashings. SECTION- F

190
7.18 INSULATION DETAILS

PANEL TO PANEL STITCH


No.14 SDS
@333 o.c.

FLASHING
DF-501 A& B

SECTION THRU' JAMB


j No.14x25 SDS for hlsulot<m______j
r-upto65mmthick.
No.14x50SDSforlnsulotion
from 75 to 100 mm thick.
No.14x76 SDS for hlsulotion
from 110 to 150 mm thick.

PANEL TO STRUCTURE STITCH

SECTION AT PEAK SECTION THRU' WINDOW HEAD

No.14 SDS@ 333 O.C.

SECTION AT EAVE SECTION THRU' WINDOW JAMB

WINDOWSILL
INSULATION
K.W. WALL PANEL
BASEANGLE

.._ ,. _
~
'"" sos. '" o.c. ..:..i[
.. .!.J/
::C ; / '

SECTION AT BASE SECTION THRU' WINDOW SILL

191
CORNER DETAIL- INSULATED WALLS

RAKE DETAIL -INSULATED ROOF


K.R. ROOF PANEL

SKYLIGHT

J
SECTION THRU' SKYLIGHT

INSULATION
FOLD TABS AND STAPLE
@ 300mm O.C. (Max.)
No.12x20 ~15 (Staples not by KBSK)
K.R. ROOF PANEL

ENDWALL RAFTER
(Shape varies)
SECT ION X
INSULATION SIDE LAP
SECTION THRU' RAKE

NOTE:

1. An additional rake angle (on 1:10 bldg. Only) 3. For building having insulation of 80 & 150 mm
andacorner Angle will be furnished by k.B.S. thick blanket Type, use# 14 x 50 sds to fasten
When customer specifies That building is to panel to structure and 12 X 20 sdts panel to
be insulated (see details) panel.
2. For building having insulation of 50 & 75 mm 4. Slide doors are to be insulated if waiuls have
thick blanket Type, use# 15x25 sds to fasten insulation
panel to structure and Panel to panel. 5. All dimensions are in millimeters.
6. Patching tape is provided for patching of torn
vinyl facing.

192
7.19 KR FALSE CEILING
DETAILS

SUPPORT & PANEL LAYOUT OF FALSE CEILING

PRE-PUNCHED
HOLE 08

No.14x25 SDS
@ 333 o.c. KR
FALSE CEILING PANELS
SECTION:A-A

SECTION DET: C
NOTE:

1. The building is to be tight and plumb


before Panel-support is erected; however,
it is preferred To be done after external
sheeting is completed.
OF SUSPENSION
2. Panel-supportto be checked for constant
level Througholt before panel fixing begins.
KR
FALSE CEILING PANELS
3. Alignment of cutouts and misc. Fixings;
(lighting, Ducts, etc.) Are the responsibility
of the building installers.
4. F.C. Panels shall be installed in the
v sequence shown.
It>
550
(MIN.) I lr No.14x25 SDS
if>
STITCH SCREW~ - j
SDTS12x20 I
5. Protective measures are to be taken to
@3330.C.
1' i I I
"]

2000 2000 2000


' prevent Personnel damaging the panels.
6. Do not punch holes or make marks with
SECTION:B-8 permanent Ink or paint on the visible face.
7. Building installation crew is to clear off all
metal shavings and No sharp edges to be
left projecting hazardously.

193
7.20 SINGLE SHEETED
PARTITION DETAILS
LE NGTH (OUT TO OUT STEEL)
BAY SPACING
(TYPICAL)
-~~ 1
~

~ ~
~
(!)
z I-- (D f-
::0

~ <(
0 r- ---t- ~6
0
0
"'::;;z a:t_ '\ f-
f-

3
DET. A \ '---
~ ~ ::0
Q.
0 \ r J:
0 f-
~ \ LONGITUDINAL
~
0
~
PARTITION

SECTION -1 (TRANSVERSE PARTITION)

PARTITION WALL PLAN

4-M12x30 GIRT
M.S. BOLTS 4-M12x30
GIRT
CLI P 1-86 M.S. BOLTS
OR 1-25

GIRT GIRT
FI ELD DRILL
GIRT FOR
12 0 BOLTS

K.W. PAN EL
CLOSURE TRIM MF-525 CLOSURE T RIM MF-525
(Profi le cut to girt in field) (Profile cut to girt in field)

DETAIL ' A' DETAIL 'B'


PLAN SHOWING PARTITION GIRT PLAN SHOWING INTERSECTION OF
CONNECTION & CLOSURE FLASHING TRANSVERSE & LONGIT UDINAL PARTITION WALLS

No.12x20 SDTS
@ 333 o.c. RAFTER

SH EETING ANGLE

SHOP WELDED
4-M16x40 CLIP 1-221
H.S. BOLTS
PARTITION COLUMN

K.R. PANEL

DETAIL 'C' DETAIL ' D'


TRANSVERSE SECTION SHOWING COLUMN & GIRT LONGITUDINAL SECTION SHOWING
CONNECTION AT ROOF BETWEEN TWO FRAMES PARTITION COLUMN CONNECTION
TO RAFTER & FLASHING AT ROOF

194
PARTIT ION GIRT

CONNECTION
M12x30 M 12x30
CLIP CONN ECT ION CLIP
M.S. BOLTS M.S. BOLTS

FLASHING
MF-519

CLOSURE
FLASH ING

PARTITION PAN EL
PARTITION COLUMN

DETAIL 'E' DETAIL 'F'


TRANSVERSE SECTION SHOWING TRANSVERSE SECTION SHOWING PARTITION
PARTITION SUPPORT & SHEETING AT PEAK SUPPORT & SHEETING BETWEEN EAVE AND PEAK

PROFILE CUT FLASH ING


TO Z LAP AND POP
.RIVET IN~ ROOF PAN EL

FLAS HING FLASHING _(


\, -j--
- POP RIVET

~~
MF-512 MF-512
No.12x20 SOTS
@ 333 O.C.
- +

_1
-
I K.R. PART ITION PAN ELS

SECTION- 2 SECTI0~ 1 .,

NOTE :

1. Details shown on this drawing may not occur


all together in One building. Use those details
which comply with the Structural framing,
refer building installation drawing.
2. Column and girt spacing for partition walls is
same as that Required end wall.
3. All column and girt connections (unless
noted) are same As standard girt
connections.
4. All dimensions are in millimeters.

SECTION- 5 SECTION -6

195
7.20 DOUBLE SHEETED
PARTITION DETAILS

LENGTH (OUT TO OUT STEEL)


BAY S PACING
(TYPICAL)
- ~~ 1
~

~
w
,_w
(!)
z 1-- (D ,_
(/)

::>
~ ;?u / -t- ~6
0
,_0
(/)
,_
~
z
~ ~
::;; '\ DET. A \ '-- ::>
Q.
30 \ r
u H - ,_
I

~ \ '- ~ 0
LONGIT UDI NAL
PARTITION

SECTION -1 (TRANSVERSE PARTITION)


PARTITION WALL PLAN

GIRT

GIRT
FIELD DRILL
GIRT FOR
12 0 BOLTS

K.W. PANEL

DETAIL ' B'


DETAIL 'A'
PLAN SHOWING INTERSECTION OF
PLAN SHOWING PARTITION GIRT
TRANSVERSE & LONGITUDINAL PARTITION WALLS
CONNECTION & CORNER FLASHING

No.12x20 SOTS
@ 333 o.c.

SHEETI NG ANGLE
RAFTER

4-M16x40 FLASHING MF-519


H.S. BOLTS
PARTITION COLUMN
DETAIL c K.R. PAN EL
K.R. PAN EL

TRANSVERSE SECTION SHOWING COLUMN & GIRT


CONNECTION AT ROOF BETWEEN TWO FRAMES
DETAIL ' D'
LONGITUDINAL SECTION SHOWING
PARTITION COLUMN CONNECTION
TO RAFTER & FLASHING AT ROOF

196
CONNECTION CLIP
CONNECTION CLIP

PARTITION GIRT

FLASHIN G
MF-519
RAFTER
CLOSURE
2-M 12x30 FLASHING
M.S. BOLTS
PARTITION PAN EL
PARTITION COLUMN

DETAIL 'E' DETAIL 'F'


TRANSVERSE SECTION SHOWING TRANSVERSE SECTION SHOWING PARTITION
PARTITION SUPPORT & SHEETING AT PEAK SUPPORT & SHEETING BETWEEN EAVE AND PEAK

PARTITION 100
STEEL LI NE
PARTITION

FLAS HING
MF-512

DETAIL ' G'


TRANSVERSE SECTION SHOWING
LONGITUDINAL PARTITION CONNECTION
TO ROOF WITH LINER SECTION -2 SECTION- 3

PURLI N
POP RIVETS

SPACER ROO F LINER


CLIP
FLAS HING
No.12x20 SDTS MF-512
@ 333 o.c.
206x76 CHANN EL

PARTITION PANEL PARTITION COLUMN

SECTION- 3 SECTION -4 SECTION- 5


(WITH ROOF LINER)
NOTE :

1. Details shown on this drawing may not occur


all together in One building. Use those details
which comply with the Structural framing,
refer building installation drawing.
2. Column and girt spacing for partition walls is
same as that Required end wall.
SECTION -6 3. All column and girt connections (unless noted)
are same As standard girt connections.
4. All dimensions are in millimeters.

197
7.21 RIDGE VENTILATOR
DETAILS
RAIN SHIELD
3000
BIRD SCREEN \
-----------Tf-------------------------------------------------------__\ ___________ --- fj-8irrLE-- --------
1
II .#"rcRANK '-- SLIDE
f_ .--- DAMPER GUIDE
II#
1\\ t----- 1\\
\\ \\
PULL CHAIN \1 c::'OPERATOR BAR

SECTIONAL ELEVATION 1
VENTILATOR END CAP

SECTION THRU VENTILATOR

OPERATOR BAR CONN. AT MULTl UNITS


OPERATORBAR U ULLEYBLOCK
CLAMP 1-301 CLIP
END SKIRT MUST
BE AT MAJOR RIB U-BOLT

CONTINUOUS VENTILATOR INSTALLATION


-~'- - - -"1'o~o
MIN
------,!'-----:":":--
150

MIN
----.~f
~ II
- ooc

CORD ATTACHMENT DETAIL


BET. OPERATOR BAR & 1301 CLIP
-....__
-....__

CLIP1 -301
NOTE:

1. Single and continuous ventilators are shipped


OPERATOR CORD
With end caps installed. Each vent package
Contains two end skirt assemblies and one
Mul tl unit splice drain To install single unit
U-BOLT& ''pop rivet" end skirt Assembly to each end
cap and locate vent over Major ribs When
PULLEY BLOCK

1st alling a continuous run of Ventilators 'pop


river end skirt assembly to First and last vent
OPERATOR CORD ATTACHMENT SCHEMATIC and locate multi unit splice Drain under buti
50 0PERATOR
joints of middle units
CORD
2. Continuous ventilators One opera tor
GIRT
CLAMP
EYE BOLT
package is supplied with every two
2-#14X25 Ventilators and each package contains:
CORD ATTACHMENT DETAIL 1- Pulley attachment angle (1-301)
TO GIRT
2- Eye bolt clips (1~)
NOTE: 2- 'U' bolts, pulleys and clamps &- Eye bolts
1- Turn buckle with two eye bolts
Opera tor cord schematic is shown For r.F. 4- 6Mm x 15 csk bolts w/nuts
Bld'g. For b.C. Type bld'g. The cord is to run
along the nearest Interior column

198
7.22 ROOF CURB DETAILS

ROOF CURB

K.R. ROOF PANEL

SECTION AT ROOF CURB


PURLIN (TYP.)

NOTE:
No.14 SDS

Roof curb shall be installed as roof is sheeted


and in the sequence shown.

Protective measures are to be taken to prevent


personnel damaging the roof curb. Do not walk
ROOF CURB PANEL
ROOF PANEL
on the roof curb.

SIDE LAP DETAIL

199
7.22 ROOF JACK DETAILS

ROOF JACK

PURLIN (TYP.)

SECTION AT ROOF JACK


ROOF JACK ADAPTOR PANEL SHOULD BE LOCATED WITHIN A ROOF PANEL
WHICH IS SUPPORTED ON AT LEAST TWO PURLINS ON EITHER SIDE OF
THE ROOF JACK

NOTE:
No.14 SDS

Roof jack shall be installed as roof is sheeted


Field cut appropriate opening for roof jack in
Roof panel.
ROOF CURB PANEL
ROOF PANEL Protective measures are to be taken to prevent
Personnel damaging the roof jack.

SIDE LAP DETAIL

200
7.23 WINDOW DETAILS

SINGLE WINDOW INSTALLATION

:~- LI NER PANEL J

I~
. (OPTIONAL) 'vGIRT

X
WINDOW
HEADER
@400clc
I/ ,~
L siLLANGLE
SECTION - B (At Head) 2-1075

JAMB ANGLE 9-1

SILL ANGLE

II 1 r:~
BASE ANGLE FINISHED
c=======hl===============~rl=======~ -~--~~JFLOOR
ELEVATION ~;:$:\;i';';:
.SECTION

l~-~"
INSIDE
CLOSURE SINGLE WINDOWS
(WITH OR WITHOUT LINER PANELS)

WALL PANEL

SECTION - C (At Sill)


FLASHING
f------MF-536

JAMB ANGLE 9-1

3mm BEAD POP RIVETS WINDOW JAMB


CAULKING @3330.C.

WINDOW JAMB

No.14x25STS
@3330.C.
POSITION AFTER
WINDOW IS INSTALLED

SECTION- D (At Jamb) SECTION- A (At Jamb)

201
DOUBLE OR MULTIPLE WINDOW INSTALLATION

J
'vGIRT

I~ / I~ /
X X
v ~ v
41LLANGLE
~
~
2-1075

JAMB ANGLE 9-1

BASEANGLEj FINISHE
FLOOR

ELEVATION df'/ii/'
SECTION

DOUBLE WINDOWS
(WITHOUT LINER PANELS)
NOTE:

1. Opening for windows are field cut unless


otherwise noted on building installation
~STEEL LINE drawings furnished with the building.
I r .TART SHEETING 2. Details shown are for windows at standard
I 1000 OR 1000 INCREMENTS (IF PANELS ARE I!-'===='-'====='~ locations.
, 16 7 k SHOP-CUT), 333 INCREMENTS IF PANELS ARE,
'
I
' FIELD-CUT) REQUIRED SO THAT MAJOR RIB OF ' 3. Windows are self flashing when rtted at
WALL PANEL ALIGNS WITH WINDOW JAMB.
standard locations.
STANDARD LOCATIONS 4. Double windows in way of liner panels should
have a sill girt also.

202
7.23 ADJUSTABLE LOUVER
DETAILS
Louver details: FILLER STRIP

GUTTER

KIRBY WALL
HEADER PANEL

LINER PANEL (OPTIONAL)


SDS #14x25
(TYP)
FLASHING (OPTIONAL)

......
'A' FILLER STRIP

RUBBER STRIP

SCREEN

HEAD SECTION -NORMAL

GIRT

KIRBY WALL
LINER PANEL (OPTIONAL)
SILL PANEL

HEAD SECTION -AT EAVE STRUT

KIRBY
WALL
PANEL

LINER PANEL
SDS #14x25 AND FLASHING
(TYP) (OPTIONAL)

- \ ' POP RIVET


SCREEN
\_ MF-539
(OPTIONAL)

LOUVER PACKAGE SDS #14x25


HEADER (TYP)
PANEL

HAND CRANK

SECTION - 'A' SILL SECTION -FLOOR POSITION

203
7.24 ROOF SANDWICH
PANEL DETAILS

PANEL FASTENERS

~-- STITCH SCREWS AT 300 O.C. (MAX.)

EAVE STRUT J-----SEALING TAPE

PANEL FASTENERS @33 O.C.


AT EACH MEMBER

APPLY MASTIC

No.14x25 STS@ 166 O . C . --~


RAKE TRIM RF-501
GUITER GU-501--__/

No.14x25 STS@ 166 o . c.--~


LAP RAKE TRIM OVER END AND CUT
GUTTER GU-502 --~ TO FLASH GUTTER - 1/10 ROOF SLOPE

SANDWICH ROOF PANEL INSTALLATION

STITCH SCREWS
FOR SECTION 'B'

I I
PANEL FASTE NERS
FOR SECTION 'B'

PURLIN
PANEL FASTENERS
I
_j [""\_
~ /""\_ /
FOR SECTION 'A' .....

50 333
.. ...

333 _ QQ f--1 STITCH SCREWS:12x20SDTS I


1000 PANEL PANEL FASTENERS: See Shipper
DETAIL 'D'
SANDWICH PANEL END LAP
(STANDARD) SECTIONS A & B

204
WALL SANDWICH PANEL
RAKE CHANN

DETAIL 'A' DETAIL 'B'


SECTION AT EAVE SECTION AT RAKE (LEFT END)

General sheeting notes

1. The building is to be tight and plumb before


sheeting is to begin.
2. Sheeting is to begin at the leeward end of
building so that all Panel laps will be away
from prevailing wind.
WALL SANDWICH PANEL 3. Fiberglass insulation for filling the gaps to be
fixed With adhesive tape to prevent it from
flying. (Tape not supplied by kirby.)
DETAIL 'C' 4. Building installation crew is to sweep roof
SECTION AT RAKE (RIGHT END) panels clear of all metal shavings.

END LAP
EAVE STRUT ~IN p~ VII~ r" PEAK PURLIN
PURLIN
A~ --------A ,--- ------A

LAP

LAP

= ---------..y'
~ ~

/_ v ~.,~OOffl~'"~
ONE AT EACH SUPPORT AND
AT 300 D.C. (MAX.) INBETWEEN
No.12x20 SOTS@ 333 D.C.
AT EACH INTERMEDIATE PURUN
""
No.12x20 SOTS 2 ON EACH LOWE
SIDE OF THE MAJOR RIB AND
ONE BETWEEN MINOR RIBS
No.14SDSAT
1660.C.

ROOFPANELFASTENERLAYOUT

205
7.25 SUSPENSION OF
LOADS FROM MAIN &
SECONDARY MEMBERS
FROM PURLIN

NOT ALLOWED

SUSPENSION ROD OR WIRE SUSPENSION ROD OR WIRE


FOR MISCELLANEOUS FIXINGS FOR MISCELLANEOUS FIXINGS
( LIGHTINGS, DUCTS, ETC. ) ( LIGHTINGS, DUCTS, ETC.) .__ _ _ _ _ _ _ _ _ __ .

FROM RAFTER

/ I ALLOWED I NOT ALLOWED

SUSPENSION ROD OR WIRE


FOR MISCELLANEOUS FIXINGS
( LIGHTINGS, DUCTS, ETC. )
ALWAYS ON CENTER

NOTE :

1. Drawing details shows the proper methods of 2. The total load suspended from purlin & rafter
suspending Loads from purlins & rafters. shall not Exceed the value of collateral load
indicated on this Drawing. If in doubt, please
contact kirby's nearest Representative for
confirmation.

206
7.25 STANDARD BUILDINGS
ERECTION DRAWINGS
( CONTINUATION FROM
CHAPTER 3.3 )
Index for standard buildings:

Width Length Eave height Bay Project no. Page


(m) (m) (m) spacing
36.00 48.00 6.00 8@6.00 M. BC-36660 212
36.00 48.00 8.50 8@6.00 M. BC-36685 218
36.00 48.00 6.00 6@8.00 M. BC-36860 224
36.00 48.00 8.50 6@8.00 M. BC-36885 230
18.00 48.00 6.00 8@6.00 M. RF-18660 236
18.00 48.00 8.50 8@6.00 M. RF-18685 242
18.00 48.00 8.50 6@8.00 M. RF-18885 248
21.00 48.00 6.00 8@6.00 M. RF-21660 254
21.00 48.00 8.50 8@6.00 M. RF-21685 260
21.00 48.00 6.00 6@8.00 M. RF-21860 266
21.00 48.00 8.50 6@8.00 M. RF-21885 272
36.00 48.00 6.00 8@6.00 M. RF-36660 278
36.00 48.00 6.00 8@6.00 M. RF-36685 284
36.00 48.00 6.00 6@8.00 M. RF-36860 290
36.00 48.00 8.50 6@8.00 M. RF-36885 296

207
STANDARD STRUCTURAL
SYSTEM
3.3 STANDARD BUILDINGS -
BC-36660

cp 48080 0/0 ~RETE


48000 0/0 STEEL LINE
NOTCH cp
4 40
LEF END 6000 6000 6000 6000 6000 6000 6000 6000 LEF

11 5887 I I 5887 3
~ I I I I ,_
0 t- -- i0 0t -- i0 .

w
I I
i i
0--- r--- i Ji
i I "'
~ i I"
-
r--gr-
i ~
~~
i I
w ~ ~ i i i
~ r- >- i ~ t-- !
______, _______;_---+=--- ~---+ ~ --=----.,
----1 j-- -8--- -<P-- ~
~ j j ~
~
;r:~ ~
I
~ r-
! i I
~f- i i
i j"
w i I~
i I
r---
i
i I
~
~2\0+----------+0
i i
(A) 0i (A) (A) -------- -+0 ' 1-
... 613 1 ~1~ 3059 ~1~ 1500

ANCHOR BOLT PLAN

C?T00 (D& 9 (D& 9


~ ------
!--"'-- 1--"-- -----
~ J~
24 !11 A.BOLTS 5050
r-m I-- ~ E
20 !11 A.BOLTS 5050 20 !11 A.BOLTS 75 63
~ ~~
~---~
D
I
c J ~l
16Thick
I t1 BASEPLATE :il
~~ ~
~] ~
:il
t::f N~ ~~ I

&
I :2
~ 302
"
A
! ___!1L
r-!1L ~
cp! !l ~~
-----
SIDEWALLSTEELLINE I A DETAIL 'C'
CONCRETE LINE "' I SIDEWALLSTEELUNE

DETAIL 'A' "'


DETAIL 'B'

(D& 9
-----
~ J~
TTO~ABOLTS
:il

n
20 111 A.BOLTS 75 63
;!l
F
J~J I
-
i
Lw
:il
D i:i
B
"j~J
:il - ;!l
I :il

~ 200 1 16Thick
" 330 BASEPLATE

DETAIL 'D'
----- DETAIL 'E'

208
Main frame column reactions:

Sign convensions:
Positive hor.Reaction : to the right
Positive ver.Reaction : upward
Positive moment : counter clockwise

~------__.:.17.5

L~L)
17.5 113 (D .L+L.L)
~HL ~H1 ~HR

L,
MAX BRACED BAY
L(DHW.L)

MAX WIND COL


Mainframe- 2-8 REACTIONS (KNS) REACTIONS (KNS)

Reaction For Combined Loads:

Description Horz Vert Momt Load


KN KN KN-m combination
INT. COL. 1 0.0 88.9 KN-M 1DL+1LL
INT. COL. 1 0.0 -30.9 0.0 1DL+1WLL
INT. COL. 1 0.0 -30.9 0.0 1DL+1WLR
INT. COL. 1 0.0 18.4 0.0 1DL+1SEI

I LEFT COL. 13.2 37.9 0.0 1DL+1LL


LEFT COL. -10.3 -19.1 0.0 1DL+1WLL
LEFT COL. 2.7 -6.7 0.0 1DL+1WLR
LEFT COL. 0.1 7.6 0.0 1DL+1SEI
I
RIGT COL. -13.2 37.9 0.0 1DL+1LL
RIGT COL. -2.7 -6.7 0.0 1DL+1WLL
RIGT COL. 10.3 -19.1 0.0 1DL+1WLR
RIGT COL. -5.1 9.2 0.0 1DL+1SEI

209
cp 38?,9 3~3 38?,3 358?,3
PURLIN
200ZX1.5
(TYP)

48000 0/0 STEEL LINE


3~3 33 7~3 cp
11 113
I LEF OEND

@-- .----- 1 1DC-5990(UNO) II

'' /
/

', .,,.tf~ '' /


/

' /

Jf/' /'
/
/
''
/
'' /
/
''
0--- '
/ /
ZA-67U
ON6rP)
-
'' '' /
/

' '1!>17 / '' ~


/
/

'f. /
/'
/ ''
/ /
/ / ''
0---- - ~
'' /
'' /
/

" ' ' '#?/ iV

'v /
/

/;" '' /
/
''
'

~
/
/
''
- f+--- ------j --; II- J--- ---! --1'1-- -{ ~ -
~ ' / ~
~ ' / ~

' /

', , _b.~~/ ' /

~<f./,
' /' /

;/ ' /
/
''
/ ''
- ~
/
'' /
''
0----
/ /

' /
' /

' /
' /

',~ ~
/

'' / /

r;~/ ' , /

' / ''
/ /
''
0----
/ /
-
'' /
/
'' /
/

',~/
'' /
/

' '/ /

~ '' /
/
''
/
'
0-- L_- /STRUT TIJBE{TYP~ '

1DC59 9 0(U NO)

ROOF FRAMING PLAN

PURLIN CONNECTION DETAIL PURLIN CONNECTION DETAIL


FROM GRID LINE 3- 7 At Lines 2 & 8

113

PURLIN CONNECTION DETAIL


AT GRID LINE 1 & 9

210
CLIOF SYMMETRY
342 342
I.Ol:::::::o,._
-,-0- -,0-
-"..L
16577 ~-
-- -- -.~
11 @ 1507 "" 16577
l1 @ 1507 ....,- -,...
_, 700 r-
400 I I ,= iel 400
..,..---_- -- ' ~ ~
--
eo:- -- --
-.-- --.-
~1
- -----==:!.- 400
-- ~to -,.... :r~
400
oO\ @ /4o Fj
~ ! o~ B
I 0!

: ~3-14 3 10~
~~ ~
03
~ r- ~I 3- ~
~ '

~0 2~
18000 OUT TO RIDGE 18000 RIDGE TO OUT
36000 0/0 STEEL

CROSS SECTION @ GRIDS 2-8

211
8-
- M20X70
--

I~ I HSB
I

BOLTS ~ ~
8No.M24 BOLTS I~
~ ~ 1-
8- M24X85
HSB
4- M20X70 oo
""
HSB
-
I I

~ ~ 1- r- ~ . 1 1 ~
16 THK v
SPLICE LATE g

~ ~ 1- [b r- ~ ~------L.J---:;- J
20 THK
I - I 16 THK / '"
SP LI CE LATE 1-
DETAIL "A" SPLICE LATE
DETAIL "B" DETAIL "C"
~ '""';:'<,~, ~
35 53 353 353
9 ~~' '~' 48000 0/0 STEEL UNE '~' ;~; '~' cp
LEF @END I 6000 6000 6000 6000 6000 6000 6000 6000 I LEF @END
113 I
5887 5887 I 113
13SBTI 13SBTI

0
0 / /
r-' N / /
:r: N / /
'' ''
' ~--v ZA-6706(TYP) /
w /
0
''
>
<( a:J
' )b~~'( (UNO) ' '-/
w ;:: /'-
0
~ 9J'<'/ '
/
0 0 / /
N / /
iS ~ ~ ' BASE ANGLE ~ ~ ~ ~
''
N '~ ' ~
N / / ~
1~1 kl ' 1 z sooo '
SIDE WALL FRAMIMNG ELEVATION@ GL A (AS DRAWN)
SIDE WALL FRAMIMNG ELEVATION@ GL G (OPP HAND)
S.W.D @ GL-A ONLY

212
r-'
:r:
w
>
<(
w
0
0
0

"'
STAR T/ END OF PANEL
-1 67mm FROM STEEL LIN E 48 PANELS RUN ONE W/333 LAP

SIDE WALL SHEETING ELEVATION @ GL A (AS DRAWN)


SIDE WALL SHEETING ELEVATION @ GL G (OPP HAND)
S.W.D @ GL-A ONLY
()(006l)V ~OS J~

0--- - -
r--- ~0~-~: ---------
<(

9M
~
~
<n OVL9-M>I
:::>

0 ,I OVZ9-M>I
0
0
lD
t Ot9-M~

J~
11
OVV9 - M>I
il
OVS9-M>I
- -
fI i
01'99-M>I
i
01>'!9-M>I
fI 1
0 OV89-M>I
0 i
0
lD
fd Ot69-M~

I OVOL-M>I ......

-
+-- f-
t1 L OVLL-M>I
0
~
0 (.!)
OV'l!-M>I

t~.;
0
en
=- t- OVL-M>I
I
z en
0 z OVVL-M>I
o_
0 0...J
...J
0
8:0 0 fI i "'"'"~"'~
<(
_j

~
~
0
0::
~
n _j
OSSL-M~
0
w I- C")
w
(ij tI 1~ lll
w
~""'/1 1
0'-- I- 01>'9!-M>I
z
0
lll s .....J
0
en 0
.....J
w I ~ OVLL-M>I
z w
=- :---
0
~
0 (.!) \ ~
::J
[)" ~
(.!)
0
en 0 z
OVLL-M>I

lll
z ...J
=>
=-t- 0 \
Ot9L-M~
_j
i= en
w w z
~
0 I

lD z
w UJ
~\
n
8B u.
OSSL -M~

"'"'"~"'~
<(
o_ I en
~~ .....J
OVVL-M>I lD
n
(/)
.....J
=>
.....J \ .....J
-t-

~
OV!-M>I

~
0
0
en i OVZL-M>I

=-t--t- 0 0
z f~ \ OVLL-M>I z
w 'i'~ w
~;:;_ i OtOL-M~

w~'-o..
0 01>'69-M>I
0 \
0
lD
I Ot89-M~

\
OVL9-M>I

\ 01>'99-M>I
-'-

" \ OVS9-M>I

1~ \ Ott9-M~

0 i OV9-M>I
0 zw
0 <Z
~:J
lD
l OVZ9-M>I
:0

~
z
OVL9-M>I

~
I_' L __~o~-~~ -- - -- - - - -
~
I

r~O[OL~Lb9L~ Olll
1H 3/\ \1'3 0009
1H 3/\\1'3 0009 ()(006l)V ~OS J~

213
3.3 STANDARD BUILDINGS -
BC-36685

cp cp
48080 OUT/OUT OF CONCRETE
cp
48000 OUT/OUT OF STEEL

LEF LE

0--- --;:t-

-;:t-

</;;OF RIDGE

--+

ANCHOR BOLT PLAN

...-~ -
ll
lllj
Iii

II
I 125 125

-srm.UNE I
CCINCIIEIE liE
.
DETAIL-'A' DETAIL-'B' DETAIL-'C'

DETAIL-'D' DETAIL-'E'

214
Main frame column reactions:

Sign convensions:
Positive hor.Reaction : to the right
Positive ver.Reaction : upward
Positive moment : counter clockwise

~HL ~H1 ~HR

Mainframe- 2-8
Reaction For Combined Loads:

Description Horz Vert Momt Load


KN KN KN-M combination
INT. COL. 1 0.0 88.9 0.0 1DL+1LL
INT. COL. 1 0.0 -30.9 0.0 1DL+1WLL
INT. COL. 1 0.0 -30.9 0.0 1DL+1WLR
INT. COL. 1 0.0 18.4 0.0 1DL+1SEI
LEFT COL. 13.2 37.9 0.0 1DL+1LL
LEFT COL. -10.3 -19.1 0.0 1DL+1WLL
LEFT COL. 2.7 -6.7 0.0 1DL+1WLR
LEFT COL. 0.1 7.6 0.0 1DL+1SEI
I
RIGT COL. -13.2 37.9 0.0 1DL+1LL
RIGT COL. -2.7 -6.7 0.0 1DL+1WLL
RIGT COL. 10.3 -19.1 0.0 1DL+1WLR
RIGT COL. -5.1 9.2 0.0 1DL+1SEI

N.L- l "~''
t13 (D.L+L.L)

L t5 (D.L+W.L)

MAX BRACED BAY REACTIONS (KNS) MAX WIND COL REACTIONS (KNS)

215
cr 33?09 323 3?.3 PURUN
200ZX1.5
(TYP) 3~53 3S3 35~53 72 3 cr
48000 OUT/OUT OF S1EEL LINE

113 113
LFOEND LEFOEND
ZA6706 (24) ZA6706 (2A) ZA6706 (2A) ZA6706 (2A) ZA6706 (2A) ZA6706 (2A) ZA6706 (2A) ZA6706 (2A)
-- 11SBT1 11SIT1
' /

... ''
' /
/
/

... ... ... ~ . '' /


/
..
Ill / "' / "' Ill
/
' /
'
/
' /
'
--
/
' /
'
'' /
/
'' /
/

I'll '' /
/
I'll I'll I'll I'll I'll ' /
/
I'll
/ "' / ''
/
' /
'
/
/
'' /
/
''
- '' /
' /
/
' /

s- '" /
/

~ ~ ~ ~ s- ''
"
/
--0
iii /
/
'' /
/
'' iii
/
/
''
/
'
@-- -- - -+
~ <:FRI DGE

~
!!! ' '
', ~"5 '
~"\/ !!! !!! !!! 5 - '
'
'' /
/
/
/
!!!
~

--
0-
/

'
/
"""
/
'
''
~ ~ ~ ~ 0-
/
/
/
/ " '
'
''
--s

~""'!/ ' /

' ' /

ii: ', ~ "/ ii: !i ii: !i !i '' /


/
ii:
/'
(I~ '' /
/
''
/
/
'' /
/
''
-- '' ~;/ '' /
/

~ -~~- ~
/

'" /

~/ ' /
''
i ' i i i i ~ / i
/ /
11SBT1 11SIT1

--- 1 EC6992 (2)


( ~~
(TYP)
1DC6'/to(JYP)
b (TYP)
1EC6992 (2)

ROOF FRAMING PLAN


~ EREC110N MARK

353 353

625 625

PURLIN CONNECTION DETAIL


PURLIN CONNECTION DETAIL PURLIN CONNECTION DETAIL At Lines 2 & 8
At Lines 1 & 9 At Lines 3-7

216
f51(-50T~IIIS\li.A'!IOII{1QKQ/fll3)-l0000 {4B)(I1Pl "
',------" ~'

r____. . _____J
~~~~
~

11!000 0/C OF STEEL 11!000 C/OOF STEL

36000 0/0 OF STEEL

CROSS SECTION AT GL-(2-8)

217
8-M24x85 75 8-M20x70
- -
H.S. BOLTS H.S. BOLTS
~ 0
:
.....
gl
~ ~I
16 Thk.
~
SPLICE PL. CAP PL.

20 Thk.
SPLICE PL.

0
0>

0
~ .....
1 150 1

DETAIL 'A' DETAIL-S DETAIL C


GIRT GIRT GIRT GIRT GIRT GIRT GIRT GIRT
y 200Z!1.75(TYP)
3Wa9
200ZX1.5 (TYP)
3S?s3
200Z!1.5(TYP)
ST?s3
200Z!1.5(TYP)
3~3 200Z!1.5(TYP)
3Ws3
200ZX1.5(TYP)
3~3 200ZX1 .5(TYP)
7~3 ZOOZX1.75(TYP)
cp
ZB-PG-6706 ZA-PG-6706 ZA-PG-6706 ZA-PG-6706 ZA-PG-6706 ZA-PG-6706 ZA-PG-6706 ZB-PG-6706

48000 (0/0)

6000 6000 6000 6000 6000 6000 6000 6000


5887 5887 .I 11 3

~ \ I
\ I
\ I
~ X
0
0 I \
"'ro I \ ~
I \

\
" \
\

SIDE WALL FRAMING ELEVATION@ GL-A(AS DRAWN)


SIDE WALL FRAMING ELEVATION@ GL-G(OPP HAND)

218
g~=~~: ~z~~5
y ~F-515-2950(17l(n cp Cf cp cp
48000 (0/0)
C? Cf C? GU-501R-2950 (1)
cp
4 8 PAN EL RUN S W/STD. LAP ( END PANEL W/ 333 LAP)
I I

I 167mm.START/END or PANEL FRO~ STEEL LINE


I

I
0 I 0
z z
I
0
"' 0
"'
0 I ~ 0

I
" I
"
! ~
I 0
0
~ 0
~
~ I "' "'ro ~
J,
0
I

I ~
:r~I
~~
3oX7o

SIDE WALL SHEETING ELEVATION @ GL-A(AS DRAWN)


SIDE WALL SHEETING ELEVATION @ GL-G(OPP HAND)
(dAU
(~) 12l:t 't"LOS ~W

1HSII3H 31\'<13 oogg


ogr ~ ozzz
-- og~ OOOl os~a

~~+ ~
L:>~n
1/fBJ
~

{ ;s;;:
:

~
u ;:;;~ ci,
!!! ooee so M~

c
><
<3 [ .. ~ <D
006t so M~

/
r~
j __ooo_t__s_o_M-~--~~--------------~

G-
J/ 1b ~:>~e
OOLtS"OM~ I
I

II
~~+
~~ S"OM~

~
:1/ ci, ooe~ so M~
: T @
!!!
oat~ so M~
~ <3 [ ~ ~ :

<D
c
>< ~

li i~ 009~ so M~

@ ~::>~6
@--- ~
:1/ ooe~soM~
"l~"'
!
1

X X

1 11 /f JL-------006~ M~ , 1 - - - - -
0 "'
g +~ so-------t
I I

~ ~ 1
z
~ 0
z
~
i.; <3 ~ <D
0 OOLS S"O M~
><

@---
!(
" @1
"
"

~r~
~ ~
I
~
<D

I
:::J

~
ts
~
[jj
.....J
w
.....J
w
CD
LO~OL w z
otL
~ CD i=
w
z
~

~
c
><
<3 [ t\ll ~ <D
"' ~
~
LL
OOLS S"O M~
w
I
Cl)
.....J
"" "'~
.....J

Jr ~
.....J

1r~
I

~ .....J 006~ so M~
1

~ ~
:2. I I

~ ~ ooe~ so M~ 0
--- ~ I@ L:>~6
0 DOL~ so M~
I
z
w
z I

w so M~
~
009~

: Jl c-
~
~
0~~~
[ ~
<D

~
<3
.;
~ "
~

>< ~

1r~
so M~
~
ooe~

I I

\\, ~ ~
-- "I' @ L:>~e
OOL~S" OM~
I

~
.;
<3 [
N'

~
1l a
bjg
::i<D

<D
w---oo_6_e_
s_o__M_~--~:~-!9_d_o6_o_s_s_o__M_~----~ ~

__e__s_o__M_~--4---------------~
w--ooe t

\\~ IJ~
><
~

@----
~L
~

I
:::.

I
lr
I
L:>~n J
I
lr-OOL_e__so_
009tS"OM~
M_~_____,lf - - - - - - - - - - - j ~
: ~
I ogre oooz: os~a ozzz
1HSI I3H 31\'<13 008
1HSI I3H 3AV3 om;s

219
3.3 STANDARD BUILDINGS -
BC-36860
~ cp cp
brt-----------------==:__::_:=------------------m,""
NOTC

~~
0--' "' 1 1 1
f@ --10 --10

0-- :----+ t - - - --~

@ @


,r+'l--- --~

--.~

@ @
1---+t--- --~

ANCHOR BOLT PLAN

DETAIL 'C'
DETAIL '8'

230 20~ A BOLTS

L<
IJ' /
~

Lf
I/' "'
16Thick
330 BASE PLATE

DETAIL 'D' DETAIL 'E'

220
N.:: L~"
t17 (D.L+L.L)

L L~ t8 (D.L+W.L)

MAX BRACED BAY REACTIONS (KNS) MAX WIND COL REACTIONS (KNS)

~HL ~H1 ~HR

Mainframe- 2-8
Reaction For Combined Loads:

Description Horz Vert Momt Load


KN KN KN-M combination
INT. COL. 1 0.0 92.8 0.0 1DL+1LL
INT. COL. 1 0.0 -35.7 0.0 1DL+1WLL
INT. COL. 1 0.0 -35.7 0.0 1DL+1WLR
INT. COL. 1 0.0 19.5 0.0 1DL+1SEI
LEFT COL. 7.6 36.7 0.0 1DL+1LL
LEFT COL. -11.9 -21.6 0.0 1DL+1WLL
LEFT COL. 9.0 -5.7 0.0 1DL+1WLR

I LEFT COL.
RIGT COL.
-1.1
-7.6
7.4
36.7
0.0
0.0
1DL+1SEI
1 DL+1LL
RIGT COL. -9.0 -5.7 0.0 1DL+1WLL
RIGT COL. 11.9 -21.6 0.0 1DL+1WLR
RIGT COL. -4.1 9.8 0.0 1DL+1SEI

221
y ZDOZX1.15(T11') ~ 200Zll1.~{riP)
'~' ZDOZX1.5D(llP) ~ '~' y
@--- "'
{U.Hm)ZB-8706 (TYP

c-1EC-PG-7992
* ~"' ~
4!1000 (0/0)

~1DC-PG-7990(TYP)
7887
jiEC-PG-7992
"'
'' /
/

' /

' /
' ~"'!;''
/ ''' , .>"~" ',
/
'
/
/
'' /
/
''
0--- '' /
/
''
' /
/
/

'' /
/

' "'~ /
' /

/
/
'' )~ ",
/
'
/
/
'' /
/
''
0---- '' /
/
'' /
/

'' /
/
'' /
/

' /
' /

/
/
'' f:g, ''
/
'' ''
0-i
/ /

- -
/
' - -
/
'
~............ ~..........
/
~ / /

' /
' /

' X
/
/
'' /
/

/
/
'' /
/
''
/
' /
'
@--- /
/
'' /
/
''
'' /
/
'' /
/

'' /
/
'' /
/

' /
' /

/
/
'' /
/
''
/
' /
''
/
'' /

---- /

'' /
/
/

''
'
/
/

/ /

' '' /
' '' /

/
/
'' /
/
''
/
'
0-- I LIEC-PG-7092
~) L1DC-PG-7990(1YP)(5) L,EC-PG-7992

SlARTIENDOrPANELfliOW SlERLIIE
4B PANEL RUNSW/STD.LAP

ROOF FRAMING PLAN

PURLIN CONNECTION DETAIL PURLIN/GIRT CONNECTION DETAIL


At Lines 1 & 7 At Lines 2 & 6

353 353

PURLIN/GIRT CONNECTION DETAIL


At Lines 3-5

222
,,------"- -"----,,

T T

180000/COFSTEEL 1BOOOC/O OFSTEEL

360000/00FSTEEL

CROSS SECTION AT GL-(2-6)

223
560 75 8-M20x70
lso 100 260 100 50 ~-M24x8 5 H.S. BOLTS
0 4-M20 x 70 230 40
.Q, H.S. BOLIS .....
H.S. BOLTS 16 Thk.
~ ~I CAP PL.

~
SPLICE PL.
r 0
~ r-
t<')
J

~
20 Thk.
SPLICE PL.
1
~ 0
..... ~
310

155 155
1 150 1

DETAIL-'A' DETAIL-S DETAIL C


GIRT GIRT GIRT GIRT GIRT GIRT
cp 200ZX2.5(TYP)
S2, 200ZX1.0(1YP)
3~3 200ZX1.75(TYP)
3,3
200ZX1.75(TYP)
3Ws3
200ZX2.0(TYP)
7~3 200ZX2.5(TYP)
cp
48000 (0/ 0)
BODO BODO BODO BODO BODO BODO
1131, 7887 7887 ,1113

.... / .... /
.... / .... /
.... , / .... /
ZD-PG-8706 ZC-PG-8706 / ' ZC-PG-8706 /
(2) .... ..._(2) /
/ (2)/
....
'-/ '-/
/'- /'-
/ .... ill} / ....
ill} / .... ....
.... ....
.... #0' ....
#~' .... / ....
6~ ~0

SIDE WALL FRAMING ELEVATION@ GL-A

224
,F-515-3050 (161
cp 0
cp cp y
48000 (0/0)
cp cp GU-501R-&150 (1)
cp
~~=~~l ~6~~~ (~J
48 PANEL RUN S W/STD.LAP (END PANEL W/ 333 LAP) _I
I
I 167mm.START/EHD or PANEL FROW STEEL LINE
I

I
I !
0
I 0
0
LJ, '-1 J,
0
~AL DO &__ I
~-
3 X7o ~

OF -501 A-2200(2)
OF -5018-2200"(2}
~
SIDE WALL SHEETING ELEVATION@ GL-A
3.3 STANDARD BUILDINGS
BC-36860

0 90 , OL!a Olll

0---- 0----
( ~) 0 7f-Z l ( ~) 0009 - Z l

E
I
') ~~

%
~

~I
i]
8---- "'
! l~
~~

19

"'
~
~I 1 E OOOT ;;
~ r-....I c:
r-....I ....J
8--- ....J (!) ~
~1 (!)
M'
.....
......
z z 0
0
0 0
0 i=
0
~
~ ~ ('I)
"' ~ .
! w
~ w
~~ r'"\ ....J ~
....J w
!~I
0
w ~:~ .....
@--- (!)
~~3:-
'-'-'
(!)
z z
~1 z i=
0

"' ~ w
w
~
~
~
...J
~
~ :::c =>
CJ)
LL (/)
~
....J ....J ~
....J ....J I

~ ~
1-
~~ 0
LO
~[ 0 0 ~
0---- E ~~
z
w
z
w
(/)
LL

~L i OOOT
"'~ ot69-~'0-M>I

~
19 "
J[
~ ~
"' ~ ~
~\ 1 ij
~

0---- ~

t
~L
;i;
E.
[ E
~
~~
J
~

I ~~
0--- I
(~) oo-rr-z J (~) 0009 - Z _j

I
0--- ]
I

225
3.3 STANDARD BUILDINGS -
BC-36885

cp
48080 OUT/OUT OF CONCRETE

48000 OU T/OU T OF STEEL

LEF 8000 8000 8000 8000 8000 8000 LE


I~ 7887 _I L 7887 1l
I I I I I

~ +-- -------- -- + l +-- -------- -- +


!I I I
I i I
0--- ,--h- i -::-

I i
w I i
I i
f- iI
--::-

I~ ,_ ,_
~~ ~ 0 ~
c----1~ - - - ;-$- ~-
! - ! ~ - -
I - ~-
$- - - - fr- - - - -$- -_:f- -f-- <f;OF RI DGE
@ @ @ @ @
~ I
w
I ~~ I
I~ i
~-
--+
i
I i
I i
c----~- i --::-

w
!I i I
I 3070WALK.
i I
t@/ DOOR ~ t --===--===- --: j T t -- == =-- === - --: j

ANCHOR BOLT PLAN

250

5050 24;A.BOLTS

r---!1-L r-4Q_ENDWALL ~ = c= =
--------
~
~ r-- STEEL LINE ~
LINE
20;A.BOLTS 5050 CONCRETE LINE ~ 20;A.BOLTS 75 63
~I
16Thick

E
BASEPLATE L I
:ill
~I :ill
~

! ::ll ! 125 125 ~ I

~~I
I
~ 31 0 40

STEEL LINE k~ SIDEWALL STEEL LINE


CONCRETE LINE
~I
--------
DETAIL-'A' DETAIL '8' DETAIL-'C'

--------
270 20 ; A.BOLTS ~
~
LINE
:1l 20;A.BOLTS 75 63

- r ~l -

E
I
Jo
r;;
:l _L ~ -
H I

~
:1l
1 16 Thick
BASEPLATE
312 40
370

--------
DETAIL-'D' DETAIL-'E'

226
Mainframe- 2-6
Reaction For Combined Loads:

Description Horz Vert Momt Load


KN KN KN-M combination
INT. COL. 1 0.0 124.1 0.0 1DL+1LL
INT. COL. 1 0.0 -48.2 0.0 1DL+1WLL
INT. COL. 1 0.0 -48.2 0.0 1DL+1WLR
INT. COL. 1 0.0 25.8 0.0 1DL+1SEI
[ LEFT COL. 9.1 47.6 0.0 1DL+1LL
LEFT COL. -15.7 -29.7 0.0 1DL+1WLL
LEFT COL. 12.1 -8.4 0.0 1DL+1WLR
[ LEFT COL. -1 .6 8.9 0.0 1DL+1SEI
RIGT COL. -9.1 47.6 0.0 1DL+1LL
RIGT COL. -12.1 -8.4 0.0 1DL+1WLL
RIGT COL. 15.7 -29.7 0.0 1DL+1WLR
RIGT COL. -5.0 11.9 0.0 1DL+1SEI

Main frame column reactions:

Sign convensions:
Positive hor.Reaction : to the right
Positive ver.Reaction : upward
Positive moment : counter clockwise
~HL ~H1 ~HR

N.: L~"
I17 (D.L+L.L)

L L
MAX BRACED BAY REACTIONS (KNS)
tO (D.L+W.L)

MAX WIND COL REACTIONS (KNS)

227
Cf PURLIN
200 ZX2.0
(TYP) 35~09 PU RLIN
200 ZX1.75
(TYP) 35p ,53
PU RLIN
200ZX1.5
(TYP) 3~53 PURLIN
200ZX1.5
(TYP) 35~53 PU RLIN
200 ZX1 .75
(TYP) 70~53 PU RLIN
2 DOZX2. 0
(TYP)
cp
48000 0UT/OUT OFSTEELLINE

113 113
LEF=:f:ND LEF@fND
ZC8706(2J Z88706(..) ZA8706(2J ZA-8706(..) Z88706(..) ZC8706(2J
-
/ /
'' /
/
'' /
/

/' /'
/
/
'' /
/
''
/
/
'' /
/
''
/
' /
'
--- '' /
/
'' /
/

' /
' /

'' /
/
'' /
/

' /
' /

/
/
'' /
/
''
/
' /
'
/
/
'' /
/
''
/
' /
'
- '' /
/
'' /
/

' /
/
' /
/

' '/ /
' '/ /

/
/
'' /
/
''
/
' /
'
/
/
'' /
/
''
~~RIDGE
-- '' _...., / '' /
/

',, ,o"Yo_,.~- '' /


/

' /' /

eft " , , /
/
''
/
/
'' /
/
''
@--
/
' /
'
'' At'Y/
/
'' /
/

' ' /

',,,<#" ''
' /
/
/

~~" ' ' ''


/
/

' /
'
/
/
'' /
/
''
/
' /
'
-- '' _,o'\/
/
'' /
/

' ' /

',,.;e" ' '/ /


/

/~ '' ''
/
/

' /
'

-- lEC-7992(2) :~~1DC7990(TYP)
(
(TYP ) 6 (TYP)
lEC-7992(2)

ROOF FRAMING PLAN

353 353

625 625

PURLIN CONNECTION DETAIL PURLIN CONNECTION DETAIL


At Lines 1 & 7 At Lines 3-5

PURLIN CONNECTION DETAIL


At Lines 2 &6

228
cp GIRT
200ZX2.5(TYP)
,Sf?,, GIRT
200ZX2.0(1YP)
,Sf?,, GIRT
200ZX1.75(TYP)
,,, GIRT
200ZX1.75(TYP)
,Sf?,, GIRT
200ZX2.0(1'fP)
,sp,, GIRT
200ZX2.5(1'fP) C?
48000 (0/0)

11~1, 7887 j_,


1 I I r
ru= ' ' /
' / / /
'' /
''
r- ' / '' / /
' / ' /
'x / / x, N ~
l--- .[j / ' N - >ll ~
!
>l"
I /
/ ' '
>l"l \II u'~ l // ''
.

~- ' ~ '
.:#~" ', I. I. .:#~" ', I. 2-PG-6000(8)
~--
/ '' /
/
LLJ~L------,=,---__[~L--''----
''

SIDE WALL FRAMING ELEVATION@ GL-A(AS DRAWN)


SIDE WALL FRAMING ELEVATION@ GL-G(OPP HAND)

229
MF-515-2950(1?l
cp 0
cp cp cp
48000 (0/0)
y cp GU-501R-2950(1)
C?
~~=~~1 ~2~~~ (~~
48 PANEL RUNS W/STD.LAP (END PANEL W/ 333 LAP)

167mm.START/END OF PANEL FROt.l STEEL LINE

I
0 I
I
0 0
I
~I ~I I
I !
~ ~
I
~ I
I
I h
I ?
I ~
p c.A}~
3o ~~Q_ ~

DF-501A-2200(2)
DF-501 B-2200(2)
H~~
SIDE WALL SHEETING ELEVATION @ GL-A(AS DRAWN)
SIDE WALL SHEETING ELEVATION @ GL-G(OPP HAND)
230
MF 501 A 4300 (3)
2-PG-4350 ID
8500 EAVE HEI GHT
~~~~ ~ ~ '~ ~
~ ~~ ~
2220 1580 L UUU
--- I ' """ I I JJU I
KW 0.5 3600 ---J ---J
~
12EC1
~ t: -
- ~~\
I KW 0.5 3700 ')'
~ I s~
la
~ J~ 1r ~ )(
1: KW 0.5 3800 ~ !:1
~~ I I ~gG) ~
0 ~~ ~ ~
PI KW 0.5 5090 (36) I KW 0.5 3900
(n ~
I;
1
I KW 0.5 4000
[
I
II KW 0.5 4100
1:
BEC1
I I
I KW 0.5 4200 !:1
\\\1 ----@
I~ ;
.
~
I KW 0.5 4300 J~
I )(
~
KW 0.5 4400
~ @ ~ "=!8G) ~
1: 'e ~~~ ~
2220 ~
0 0
I KW 0.5 4500 "' ..
I ~ ~
I KW 0.5 4600
jf 0
I m ~~~..
m I KW 0.5 4700 z
z 1: II 9EC1
0 0 ~ ---@
I I KW 0.5 4800
I ~
II KW 0.5 4900 ~ J~ ;r
1:
~
r I r
r ~
-e ~
r I KW 0.5 5000
I~ "'Tl "=i'gG) ~
0
~ :r;~=o ~
~ '--'t'-> --1 ~
~ "'::e (/)
:::c KW 0.5 5100
I I ~
~;:. m ~
..... m II KW 0.5 5200
s:: 0
1:
~... ~:::! I z 0 -::::
~ z G) ~ _;
I KW 0.5 5300
0 G)
:;;om
I! ,., I
m ~ 10EC1

~\\ ---@
I r ~
I KW 0.5 5300
~~ r 1~1
L_j
m
::z:;ii m I ~ J~
KW 0.5 5200
~ ... < 1: II
~ )>
;,.,z
I I ~ iii ~
@if N i!j
KW 0.5 5100
!2 e -I 1:
to 0 0
~ 3 ~~~ E
~ 0- (;, ::..
I; KW 0.5 5000 z ~ll
I ~
z I ~ ')'
KW 0.5 4900
1: II ~
G)
G) I C;
I KW 0.5 4800 +I~ ;::
I' ~
~ II 0 9EC2 ~ ---@
1: KW 0.5 4700 @ .::
0 I
I -....!
KW 0.5 4600
-....! I~ n
!1 i!j
I I KW 0.5 4500 ')' N '
II () 0
11: ~
KW 0.5 4400 6 ~~~ ~
II @J C; ,_,~ --1 ~
~ ~ ;::
I KW 0.5 4300
~')' t
<II 1
I KW 0.5 4200 ~ +I~
I I~ 11
I BEC2 11 ----B
1: ~ KW 0.5 4100 lt9
II
I I KW 0.5 4000
1:
II -=; Q ~
1;
I KW 0.5 3900
..
~
0
~ ~ ~
I KW 0.5 3800
1: ~ ~
I I KW 0.5 3700 -
J
I' - Ja ~
II ~ 12EC1
+I~ ~! ~~/
KW-0.5-3600 1!
II ---@ -
2220 1580 2000 1350 1350 ---@
i:"' 8500 EAVE HEI GbT
PG-5000(1)
MF 501 A 4300 (3) 2-PG-6000 !21
10 10
I~ ~I

T T
~~;~

180000/COFSTEEL 18000C/OOFSTEEL

JSOOOO/ OOFSTEEL

CROSS SECTION AT GL-(2-6)

231
8-M24x85 75 8-M20x70
H.S. BOLTS H.S. BOLTS
~ 0
...
gl
~ ~I

~ 16 Thk.
SPLICE PL. CAP PL.

20 Thk. <{")
.....
SPLICE PL.


~
0
~ ...
1 150 1

'"

DETAIL 'A' DETAIL-S DETAIL C


3.3 STANDARD BUILDINGS -
RF-18660

1
cp cp cp cp
48 0 80 0 / 0 OF CONCRETE
cp cp cp 9

48 000 0/0 OF STEEL


60 00 6000 60 00 60 0 0 6000 6000 600 0 6000
113 LEF@ Ef>!, 5887 5887
-1- I
D
0 CABLE BRACIN G(TYP )
0 0 0 0 CABLE BRACING(TYP@

~
0---- ~~ @ @
"'"'
U"'
z>-
o "'
Uc. ~ ~
~ ~~
O F RIDGE
"u
'"' +- "u -
~ !;:;-
oo "'"'"' "'"'"'
~ g @ @
0----~ ~

~
0 CABLE BRACIN G(TY~ 0 0 0 0 CABLE BRACING{TY~

-=--------.,
A
3" s o

ANCHOR BOLT PLAN

1 &
Q)To@ v-
250 " 200

24 ~ A.BOLTS 50 50 ~200
ENDWALL

I~~
20 Thick 1- STEEL LINE 20 ~ A. BOLTS
BASE PLATE

----------
,_
"'
N ENDWALL
~E
~I
CONCRETE LINE
0
,_
"' 0
N
;;J!
""""
\
125 125 l 1oo ~ 100

&@--1 1
I
0
0
~I
N
~ I
I
A
!siDEWALL I CONCRETE LIN SIDEWALL STEEL LINE j lsiDEW~LL
SIDEWALL STEEL LINE 1 CONCRETE LIN

DETAIL 'A' DETAIL 'B'

232
'---_1_4 (W.L)

113 (D.L+L.L)

),3 (D.L+W.L)
~HL ~HR

MAX WIND COL REACTIONS CKNS)

Main frame column reactions:

Sign convensions :
Positive hor.Reaction : to the right
Positive ver.Reaction : upward
Positive moment : counter clockwise
---- 8

Mainframe- 2-8
Reaction For Combined Loads: MAX BRACED BAY REACTIONS (KNS)

Description Horz Vert Momt Load


KN KN KN-M combination
LEFT COL. 19.5 41.6 0.0 1DL+1LL
LEFT COL. -13.0 -18.7 0.0 1DL+1WLL
LEFT COL. 0.8 -8.9 0.0 1DL+1WLR
LEFT COL. 2.4 8.4 0.0 1DL+1SEI
RIGT COL. -19.5 41.6 0.0 1DL+1LL
r
RIGT COL. -0.8 -8.9 0.0 1DL+1WLL
RIGT COL. 13.0 -18.7 0.0 1DL+1WLR
RIGT COL. -5.0 10.0 0.0 1DL+1SEI

233
,
3~9 3~3 3~3 3~3 3,3 7~3
9
323 48000 0/0 OF STEEL
6000 6000 6000 6000 6000 6000 6000 6000
113 LEF 0 EN9 SBB? ' PURLIN 5887 13
PUR LIN PURLIN PUR LIN PURUN PURLIN
PURLIN~1)200ZX1.5(TYP) 200ZX1.5(TYP) 200ZX1.5(TYP) 200ZX1.5(TYP) 200ZX1.5(TYP) 200ZX1.5(TYP) 200Z~1-~(TYP)
200ZX1.5(T 1DC-s?i0(1) 1EC 5992 1
D
(TYP)
I'- ,.v I'- .v
~,.$f ~ ..:!'
~
0--- ~
- ~ ~'e~ - - - - - #~'o> - ~

v' 'Q v' ~~

~
'--....._ce~n. ~ F'--- c~e;,.,. ~
0 0 ~ '~ ~OF RIDGE ~ '~
0--- ~g '--....._
.;;::- -......_
.;:;'
[OF

i Vc..~ -=::::::-
0

vc;""'" -.. . ._
I'- 4- I'- ,j
0--- - ~ ~~
~"'
- - - - - ~ ~q,~O> - ~

~
~

/~ /~

A
1EC 5992(1)
/
1ac,r;~o<1> "' ~: )
/
"' 1EC!iiU(1)

ROOF FRAMING PLAN

353 353

PURLIN CONNECTION DETAIL


PURLIN CONNECTION DETAIL
At Lines 3-7
At Lines 2 & 8
ENDWALL
STEEL LINE

RAFTER
OR COLUMN

PURLIN/GIRT CONNECTION DETAIL


@GRID 1&7

234
iNSULATiON FSK -5011-iK -1 OKG/M' INSULATION FSK -50 THK -1 OKG/M'
ct_ OF RIDGE

GU~50 GU-501
5-502 S-502

5-502 S-502

DS-501- DS -5 01 -
5900( 1 5900(1)
5-502 S-502

5-502 S-502

5-502 S-502

9000 OUT/CENTER OF RIDGE 9000 CENTER OF RIDGE/OU T


18000 0/0 OF STEEL

235
CROSS SECTION @ GRID -2-8

* !;i'l

~ ,
12-M20X70
.. ~~" ' ~

16 THK PLATE ~T ~
H.S. BOLTS

50 90 90 * 90 90 50 \
22 *
WALL PANEL
'-----
I

"'r--: ~I ~
I DS- 501
,-----
0
DOWNSPOUT STRAP
1
I

16 Thk. SPLICE PL. I


l 8-M20X70
H.S. BOLTS
- 75
....
S-502
@ 3000 CRS. (MAX.)

DETAIL 'A' DETAIL '8'


DOWNSPOUT STRAP FASTEN TO WALL PANEL
GIRT (2) GIRT GIRT (4) GIRT (5) GIRT GIRT GIRT GIRT
200ZX1.5(TYP) 35~09 200ZX1.5(TYP) 200ZX1.5(TYP) 35~53 200ZX1.5(TYP) 200ZX1.5(TYP) 200ZX1.5(TYP) 200ZX1.5(TYP) 200ZX1.5(TYP)
35~53 35 ~ 53 35~53 35w53 70w53
48000 0/0 OF STEEL

RF-1866
6000 6000 6000 6000 6000 6000 6000 6000
113 LEF C EN 11
ZA-6706(3)
(TYP)

~ """ ~...
~~..... "
~'If ~::P ..... ..... ..... U
oc
~
~
U

"
~ ..<;
%"
u.;!J.;!!
u
N
u
N
u
N
u
N
~
"/
/
X
"-.
IN
II
13"7"SWD(I )JY ""' "-.
Nl , F(v _L2-5740(1)(TYF')_ """ v """
1

~ ~
SIDEWALL FRAMING ELEVATION @GRID-A
3.3 STANDARD BUILDINGS -

cp cp

236
6000 6000 6000
Cf 6000
~
48000 0/0 OF STEEL
6000
Cf y 6000
cr 6000

48 PANELS RUN W/STD LAP LAST PANEL TO BE 333 LAP

START /END OF PANEL 0 167 FROM STEEL LINE

GU-501 L-6150(1 )~ MF-5 STYP


MF-515-3050(16)
GU-501-6150{6) GU-501 R-6150(1)

1500 LG PIECE
1
FSK-50 THK-10KG/M INSULATION(TYP)

SIDEWALL SHEETING ELEVATION@ GRID-A


KW-PANEL0.5MM THK(ARCTIC WHITE)
GIRT GIRT GIRT
200ZX2.5(TYP) 200ZX2.5(TYP) 200ZX2.5(TYP)
XD-5511 (3) XD-5836(3) XD-5511 (3)
cr 10
cr 9 10
cr
2-4550 "L) ..::-4550(2)

RF-18660
2-4600(?1 ~ ~ 2-4600(2)
r-- ~
0
I~,------
0
"' @
f--
1---=-
0 0
" ~
"' ""'
0 f-- 1- 0
0 0 0 0
0 <D <D 0
<D <D
F
1-
0 0
2-5490(1) 2-5790(1) 2-5490(1) I
~I "'~I
"'"'"' ~ .. "'"'
"'
200
I 5800
I I 5800 l20o~
I
6000 6000 6000

18000 0/0 OF STEEL


I I
3.3 STANDARD BUILDINGS -

ENDWALL FRAMING ELEVATION@ GRID 9

237
cr cr RF-504 1) 9 cr
10 10
1r- -----,1
RF -501-4715(2) Rf-501-4715(2) RAKE TR1M
RAKE TRIM

.-----
~ =;

!Iii I
I I I I I I I I I I I I I I I I I

L__L_~_ _~_ __ L_ __ L_ _~--~--~--L_~--~_ __ L_ __ L_ __ L_ _~_ _~_ _L __ _L_~

START/END OF PANEL FROM STEEL LINE


18 PANELS RUNS W/STD LAP

18000 0/0 OF STEEL

ENDWALL FRAMING ELEVATION@ GRID 9


KW PANEL-0.5MM THK(ARCTIC WHITE)
C? <f> cr C? C? C? <? C? ~
41!0800U T/OUTOFCONCRETE

480000UT/OUT OFSTEEL UNE

6000 6000
"'" '"" '""" """ '""" """
I I
" "" I I I I I
"" '
--

RF-18685

I I
: : : : : : :
~ I I I I I I I I I
I I I I I I I I I
@)-

I I I I I I I -~1
I I I I I I I
~ I

I ~ I I
lt-- - ------t - - 5- - - t---- - --+- - - - -+ ~RI~E- - -+-- - - - ----t - - 5- - - t-- - - - ---t
I I I ~ I I
~ ;is"
g I ~ I I I I I ~ I I
I I I I I I I
" I
~I

- I I I I I I I
I I I I I I I I I

~
I I I I I I I I I
I I I I I I I I I
J- ___ __ ___ --f J- ___ __ ___ --f
3.3 STANDARD BUILDINGS -

+ + +
0--- '~' W
A
i:OR 2486
I

238
ANCHOR BOLT PLAN

llj
cp& CD&y
r-- cpTO
'! 250
40 2QQ
sa lsa I 24 A. BO LTS
CONCRETE LINE 2oo I
CONCRETE LINE
,on ion 20 0 A. BOLTS 20 Thk. PL. I i lI I .-
ENDWALL I 16 Thk. I'L.
STEEL LINE I
i
~
Li' ~ N
""'
~L
17~ 17~ t-- ~ 0
0 :2]
N
t- -~
0
0
N

** 0
0
LJJ &
N <
& ~ ~--~~----~~ ~
0--- ~ l SIDEWALL STEEL LI NE
CONCRETE LINE 1 lsiDEWALL S. --- - -

ANCHOR BOLT DETAIL @ ANCHOR BOLT DETAIL @ ANCHOR BOLT DETAIL


~
11

11
l ~"
t
21

13 (D.L +L.L)

t6 t16
t5 (D.L+W.L)

~HL ~HR MAX BRACED BAY REACTIONS (KNS) MAX WIND COL REACTIONS (KNS)

Main frame column reactions:

Sign convensions:
Positive hor.Reaction : to the right
Positive ver.Reaction : upward
Positive moment : counter clockwise

Mainframe- 2-8
Reaction For Combined Loads:

Description Horz Vert Momt Load


KN KN KN-M combination
LEFT COL. 13.2 42.3 0.0 1DL+1LL
LEFT COL. -13.2 -20.4 0.0 1DL+1WLL
LEFT COL. 6.8 -5.8 0.0 1DL+1WLR
LEFT COL. 1.1 8.6 0.0 1DL+1SEI

I RIGT COL.
RIGT COL.
-13.2
-6.8
42.3
-5.8
0.0
0.0
1DL+1LL
1DL+1WLL
RIGT COL. 13.2 -20.4 0.0 1DL+1WLR
RIGT COL. -3.9 11.2 0.0 1DL+1SEI

239
,~<f,~ ~,<f,~ ,~<f~, ~'~'~ '~~~' ~,9,~ ,~~~' <f
ZA,71N(12)

9:l
200Z ~ 1 .~ 200ZK 1.5 200Z K1.5 200Z K 1 .~ 200ZK1.5 2!10Z K 1.~ 200ZK 1.5 :WOZ K 1. ~

480000UT/OOT OF"STEEL UNE

--
il:~ J~~EN~
I I~~
I ~ ~
'' /
/
'' /
/

' '~/ /
'' /
/

/ / / "'~~ /
/ '

--
/ ''
/ /
'' ''
-
/ /

-~.)>,~~

'
I
i! t- -

I'
'' /
/
'' /
/

-- / /

' '/ /
'v /

/
/ '' /
/
''
/
/ '' /
/
''
@---
~

ROOF FRAMING PLAN

353 353

625 625 625

PURLIN CONNECTION DETAIL PURLIN CONNECTION DETAIL


At Lines 1 & 9 At Lines 3-7

PURLIN CONNECTION DETAIL


At Lines 2 & 13

240
cp ZB-6706(4) ZA-6706(4) ZA-6706(4) ZA- 6706{4) ZA- 6706{4) ZA- 6706{4) ZA-6706(4) ZB-6706{4)
353cr709 353~353 353Cf353 353cp353 353cp353 353Cf353 709Cf353 cr
GIRT GIRT GIRT GIRT OR T GIRT GIRT GIRT
200Z X 1. 75 200Z X 1.5 200Z X 1.5 2DOZ X 1.5 200ZX 1. 5 200Z X 1. 5 200Z X 1.5 200Z X 1.75

48000 OU T/OUT OF STE EL LINE

_L \
\ I \ I
\ I \ I
\ r-, 1 \ I
~/
\ ~~I \ I
irl;:; j;i \ o.S}- \ I irl;:;
i:il i:il Ill X
Ill
1- ----r---';:-
DOOR HE ADER I \ I \
IW/ L50X40X1 .75
I \ I \

I \ I \
~ I \ I \
I \ I \
soo
~,.,, 1 1

SIDEWALL FRAMING ELEVATION@ GRID- A

241
cp cr cr
48000 OUT/OUT OF STEEL LINE

48 PANELS RUNS W/STD. LAP & LAS T PANEL W/334 LAP

1
T:~~M F~6~ ~Ei~Fll~ ~
GU- 501L- 6150 {1) GU- 5011 - 6150 (1)

MF- 515- 3075 {!!}_

!:
~
d
n
J~ l
~
I

2-PG-6000 {8)

SIDEWALL SHEETING ELEVATION@ GRID -A


KW-O.STHK. ARCTIC WHITE WALL PANELS
FSK-SOTHK INSULATION WITH 10Kg/m3 DENSITY
XD. 5511 (5) XD 5836 (4) XD 5511 (5)

GIRT GIRT GIRT


200Z X 2.5 200Z X 2.5 200Z X 2.5

10
) 2-P G
4590 (1+11 _di,._QF RIDGE 2 PG 4590(1+1)
- _.t__ -
10
---, 1
1o - 1
2-PG-4570(1+ ~ - ~- ~ ---- ~ 2-PG-4570(1+ 1)

g H~ 1\<=o ~~ @) w<=J -- ~
~ ICI g @ Cl ~~

~H ~o 2 1/1m4 w1~ w~ ~
~r' I~IP
-- (10)
o
:;;
~P
(20)
6G1
~': "

~ t' ~~=-------~~--------~~----,-=ss=o~H~E~A=oE=R--~--_.=g.-----------------~~~ ~
ili XD-1406 X 1406 ili II
3M~~~MH ~
~ ~ ~
! I !
0

"""
1500 3000 1500

6000 6000 6000


9000 OU T/CEN OF RIDGE I 9000 CEN OF RIDG E/OU T

18000 OUT /OUT OF STEEL LI NE

END WALL FRAMING ELEVATION@ GRID- 9

RF 504 (1)
~P(1)
10 10
1o - Rf 501 4725(21 RF. 501 4725 (2) ---,1

~
-r
~
~
~
~
8
101
~
~
~
~ ~
~ ~
~
~
8
101
~
8
;
~
~ ~
~ ~
~
~
l
~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~
f-
I I I
GIRT #3
"'j' '-- ---'

'!;' ~ ~
:5 I ~ ~ ~ I
0
0 :i!
0
3: 3:
"'
00
~

~
I
..
~ SSD
3MWX3MH
I

2 PG 6 00(3)
I I I

18000 OU T/OU T OF STEEL LINE

END WALL SHEETING ELEVATION@ GRID- 9


KW-0.5THK. ARCTIC WHITE WALL PANELS
USE 8 ROLLS W/20M LENGTH FSK-50THK INSULATION WITH 10Kg/m3 DENSITY

242
1 r--- 9025
t OF RI DGE

9025
~1
1166 ::342 1 342 1166

4
D l507 .. 6026 -~ 401507-so2a

-" -~ -~ ~ - ""
1469
~
" Cf
~-
350
\;.
" "';' - - - . : : 350

f-
~ "' ~
~
'
~ ." 1-

II II
~ I
I
I

+
'
~
I
I~
I
Jo i
~~ .p
'
II
I

I
+i!;lf
d I
'

lu4
II
I

I
r'

-~
I

+
I ' I
~
1

H
' I I '
I I

~ I
~
I ,, ' ,, I
w '\~
9000 OUT/CEN OF RIDGE 9000 OUT/CEN OF RIDGE

16000 OUT/OUT OF STEEL UNE

CROSS SECTION @ GRID - 2-8

8- M20X70
~ HSB

~ 1
~

~
8- M20X70 " "
HSB
I " I I ~ ~
-~ ~ ~ ~

~ { -~ ~ ~ ~ ~
~ ~- L:L
~

~ ~-
16 THK I ,00 ~
PLATE
16 THK
PLATE
I - -

DETAIL @ DETAIL @
243
T T T
48080 0/0 OF CONCRETE
T T
48000 0/0 OF STEEL

8000 8000 8000 8000 BODO BODO


113 LEF 0 END 113 LEF 0 ENC

- - 1--- -
0 0 0 0 0

}---
>- >-
;;; ;;;
0 t OF RIDGE 0
~ I -
(.)
- -
(.)
1-
~ ~

}---
~~~

244
0 0 0 0 I:==
0
= = =
~~~~~
ANCHOR BOLT PLAN

1)&0
qyo
250
24 ~ A.BOLTS 50 50
ENDWALL
20 Thick 1- STEEL LINE
BASE PLATE ........__
N ENDWALL
CONCRETE LINE
~I @ &(Cl I ~Ill I II I~
:2[
I
125 125 (
~ ~I !;'I
f- ENDWALL CONCRETE LINE
boEWALL I CONCRETE Ll.
--- .. ~-- STEEL LINE I
DETAIL 'A' DETAIL 'B' DETAIL 'C'
rr----y-____.:.11

r-HL

Main frame column reactions:


L~L)
f17 (D.L+l.L)
Sign convensions:
Positive hor.Reaction : to the right
Positive ver.Reaction : upward t O (D.L +W.L)
Positive moment : counter clockwise

Description Horz Vert Momt Load


KN KN KN-M combination
LEFT COL. 17.9 55.6 0.0 1DL+1LL
LEFT COL. -17.7 -28.0 0.0 1DL+1WLL
LEFT COL. 8.9 -8.6 0.0 1DL+1WLR
LEFT COL. 1.7 10.8 0.0 1 DL+1SEI

I RIGT COL.
RIGT COL.
-17.9
-8.9
55.6
-8.6
0.0
0.0
1DL+1LL
1DL+1WLL
RIGT COL. 17.7 -28.0 0.0 1DL+1WLR
RIGT COL. -5.1 14.0 0.0 1DL+1SEI

245
PURLIN 200ZX1.75 0
3531353
PURLIN 200ZX1.5 ffi
353 353
PURLIN 200ZX1.5 PURUN 200ZX1.75 0
7091353
48000 0/0 STEEL LINE

LEF ~ N,Di---~;;----t------=-=----ii---="-------j------==---j----="-------j---___;;.w;-----jl~~: CEND


1

~ :--
~
~ :---- -r-- - - -- --r-

cv! :--

0-- ~
L--~~..----L-.-\_-.,~,,~,-.,."o __ _ L_ _-w~.---L--~~m.m---L--~~m---i---.~~--~'

EAVE STRUT 200EX2.0


(TYP)

ROOF FRAMING PLAN

353 353

PURLIN CONNECTION DETAIL PURLIN CONNECTION DETAIL


FROM GRID LINE 3- 5 At Lines 2 & 6

PURLIN CONNECTION DETAIL


AT GRID LINE 1 & 7

246
GIRT 200ZX2.5 GIRT 200ZX2.0 GIRT 200ZX1.75 ~ GIRT 200ZX1.75 GIRT 200ZX2.0 GIRT 200ZX2.5
cp 3553 35~ 353 3553 7053 cp
48000 OjO STEEL LINE
35~09
_EF 8000 8000 8000 8000 8000 8000 @END
7887 7887

0
-I~ ZD-8706(TYP) 1'. ZC-8706(TYP) ZB-8706(TYP) ZB-8706(TYP) ZC-8706(TYP) ZD-8706(TYP)
k
0 /
/ /
0
0 / /
''
/ /
''
f--
:r: " ' ''
<)~/
w 0
> 0 '' ~'9/ ' f!c"'/
<{ 0
N ':,:*;"'.~ ~'<,
w
0 fl(/ vA.:'
0
0 co
l{)
cf/ ' '
co ~ ' '""""/ ''
/ /
0 / /
N
N / /
'' ''
N ~ 0
[~~. @ GL 'A' ~ ' u ~ 2-6000(8)(TYP) ~ ~ /
' u ~
~o/ '"' '"'
SIDE WALL FRAMING ELEVATION@ GLA

247
y =
cp cp MF -515@6050(8)
cp cp cp cp
c;U-501L@6150(1) GU-501 @6150(6) GU-501 R@6150(1)

r' ~
:r: (f)
::]
w
>
<{
~~
w 8=>
0 :s~
0 Nf--
l{) 1:::>
co :iiU
Ia
'<'0
(f)"'
"-"'

START/ END OF PANEL


167mm FROM STEEL LINE 48 PANELS RUN ONE W/333 LAP

SIDE WALL SHEETING ELEVATION@ GL A


GIRT 200ZX2.5
c
2-4600(2)
GIRT 200ZX2.5
- 2-4600(2)
B
om=m.o ~
~1.0-~.~
10
I
::.--.L-_1.0~
10
- ---r - ---"'- -- -- i -- -- -r- -- : - -
I ~
~ F.\
"-"
,!, ~
..~, 7:< -j
"-"
0
~

~
0
n
~
)
0
!--" L[)
:r: ~ lD ~
X0-5B36(TYP) ~

w
> 0
<C I'
w ~ L[)
X0-5511 (TYP) 6G1 XD-5511(TYP) ~ ,..! 2-3875(1)
0
0
L[)
~ ~ ~
OCJ
~ ~
i
XD 1 06 ~ ... XD 1406
":;~~'?~
0
x
~
~2-6D00(3)(TYP)
r
"
~
r
"
~
0
N
N
N
0
X
~

115001 3000 115001


6000 1 5ooo I
6000
1 I
18000 0/0 STEEL

END WALL FRAMING ELEVATION@ GRID 1

PEAK BOX
RF-504
W/MF-533P
D A
RF -501 (2114700) 1_0 1':--,.
10

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

.,.,
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
~ ~ ~ ~ ~ ; N
"'I "'"'I "'"'I "'"'I
N
"'I ;;: 0
., .,.... .,"'
I I I I I I I "' I I I I I
~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~

Girt#3

START/ END OF PANEL


FROM STEEL LINE 18 PANELS RUN W/STD LAP

END WALL SHEETING ELEVATION@ GRID 1

248
CL.OF! SYM~ETRY
~1.0 1.0~
10 10

CROSS SECTION @ GL.(2-6)

8-M20X70

n HSB

~ ~- ~

8-M24X85
~ +--- f - -
" "' '"' "
HSB .,_.y
I I

[b f-~ ~
r-~ ~
~ ~
~ ~
16 THK
SPLI CE LATE
/ ~

~
~- r---
~- f - -

~

~ I - <f - I
SPLICE LATE

DETAIL "A" DETAIL "B"

249
T T T T
48080 0/0 OF CONCRETE
T T T
48000 0/0 OF STEEL

6000 6000 6000 6000 6000 6000 6000 6000


113 LEF 0 END 11
\
I

RF-21660
~ABLE BRACING(TYP)0 ~ABLE 8RACING(TYP)0
0 0 0 0 0
'!!

)--- c--

:;; ~

>-
>- ;;\
;;\ ft OF RIDGE
)--- 0
~~ 0 lr\ - - lr\
LJ 0 I -I 8u LJ
~ ci"
0 0 u
~
~ ~ :~ ~
i~
3.3 STANDARD BUILDINGS -

)--- ~

250
'!!

0 ~ABLE ~(TYP) .:;2_ 0 0 0 0 ~ABLE ~(TYP) .:;2_


\ -------.,
'Z"7

ANCHOR BOLT PLAN

~Tc@
250
24 - A.BOLTS 50 50
ENDWALL
20 Thick 1- STEEL LINE
BASE PLATE .........___
N ENDWALL
CONCRETE LINE
~I
:2[
\
I
125 125
~ ~~ I
!:11
)--
!siDEWALL I CONCRETE Ll ..
"""" .. ~"" STEEL LINE 1
DETAIL 'A' DETAIL 'B' DETAIL c
9

,____ 15 (W.L)

113 (D.LL.L)
- 9

t L (D.LW.L)

MAX BRACED BAY REACTIONS (KNS) MAX WIND COL REACTIONS (KNS)

Main frame column reactions:

Sign convensions:
Positive hor.Reaction : to the right
Positive ver.Reaction : upward
Positive moment : counter clockwise
~HL ~HR

Mainframe- 2-8
Reaction For Combined Loads:

Description Horz Vert Momt Load


KN KN KN-M combination
LEFT COL. 27.3 48.6 0.0 1DL+1LL
LEFT COL. -15.6 -21.0 0.0 1DL+1WLL
LEFT COL. -2.1 -11.1 0.0 1DL+1WLR
LEFT COL. 3.8 10.0 0.0 1DL+1SEI

I RIGT COL.
RIGT COL.
-27.3
2.1
48.6
-11.1
0.0
0.0
1DL+1LL
1DL+1WLL
RIGT COL. 15.6 -21.0 0.0 1DL+1WLR
RIGT COL. -6.8 11.6 0.0 1DL+1SEI

251
.f2.
48DOOD/DDf5TEEL

ZA-170814
(~)

ROOF FRAMING PLAN

353 353

>

625
I

PURLIN CONNECTION DETAIL


PURLIN CONNECTION DETAIL
At Lines 3-7
At Lines 2 & 8

PURLIN/GIRT CONNECTION DETAIL


@GRID 1&7

252
200ZX1 .5(TYPJ
35~09 35;-r;53 35;-r;53 35;-r;53 35;-r;53 35;-r;53 70;r;53
48000 0/0 OF STEEL
ouuu ouuu ouuu ouuu ouuu ouuu ouuu ouuu
13 LEF 0 END_ ' 1 3 LEF 0 END

~'I/ I"- /
N
ZA-6706(2)
"' .,.rf/).'1 /
,------- (TYPJ "04-~q,"':fJO
~
2-!.QZQ..Uj ~ """cl'~ ~ ~ ~ ~ ~ """ X ~
:----
r /
N ~( j """ v """ "'
BASE ANGLE
"'
SIDEWALL FRAMING ELEVATION@ GRID-A

253
T T T 48000 o;d OF STEEL T T T
6000 6000 6000 6000 6000 6000 6000 6000
48 PANELS RUN W/STD LAP LAST PANEL TO BE 333 LAP

START END OF PANEL 0 167 FROM STEEL LINE

GU-501 L-4940(1) 16 ROLLS EACH ROLL CUT INTO 3 EQUAL PIECES


GU-50!DYE)
~5-3050(16)
~"---. GU-501 -4940(8) ~ GU-501 R-4940(1)
/
I
70
~ ,_k1 I
g~ I
~
I
0[ ~~ I
DF-501A-2200 j/ \ 3"7'SWD(M)(FIELD LOCATE)

SIDEWALL SHEETING ELEVATION@ GRID-A


KW-PANEL-0.5MM THK(ARCTIC WHITE)
GIRT GIRT GIRT GIRT
200ZX 1. 7 5(TYP) 200ZX2.5(TYP) 200ZX2.5(TYP) 200ZX 1. 75(TYP)
XB-4011 (3) XD-5836(3) XD-5836(3) XB-4011 (3)

....U"l0

g
~
I
N

0 0
N N
N
N
2-5790 1 N
N
BASE ANGLE

200 200
6000

21 000 0/0 OF STEEL

ENDWALL FRAMING ELEVATION @GRID 9

,;
7 5 ROLLS EACH ROLL CUT IN 3 PIECES

1,---
Cf fl' f 10
-1
E

RF-501-5480(2) RF -so 1-5480(2)


RAKE TRIM RAKE TRIM

c...- .........,
l
I

~~I
~ >-
~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~

>-
... 51
I 0
I 0... 0... 0... 0... 0...;1; 0... 0 0... 0... 0 0... 0 0... ...[;;
0 0 0... 0... 0... 0... ...
0 0...
~I ~I ~I ~I
0
z
0U"l ~ > "';:;\ ~ <D ~ ::l ~ [;; :ll ....0 :ll ~ ;1; ::l ~ <D ~
J..
81 I
;;;:
I
;;;:
I
;;;:
I
;;;:
I
;;;:
I
;;;: ;;;:
I
;;;:
I
;;;: ;;;:
I
;;;: ;;;:
I
;;;:
I
;;;: ;;;:
I
;;;:
I
;;;:
I
;;;:
I
;;;:
I
;;;:
I
;;;:
:::;;
"' "' "' "' "' "' "' "' "' "' "' "' "' "' "' "' "' "' "' "' "'

START/END OF PANEL FROM STEEL LINE


21 PANELS RUNS W/STD LAP

21 000 0/0 OF STEEL

ENDWALL SHEETING ELEVATION @ GRID 9


KW PANEL-0.5MM THK(ARCTIC WHITE)

254
ctDrRIOGE

10
1 r---

10500 OUT/CENTER or RIDGE 10500 CENTER or RIDGE/OUT

21000 0/0 or STEEL

CROSS SECTION @GRID -2-8

~I
,-
8 - M24X85
16 THK PLATE ~l ~
H.S. BOLTS
~0 100 ' 100 50 \
*
~
~

J
I

0
~j m
0
0

I
,_
,-----
I ~I
8-M20X70 75
1 I
20 Thk. SPLICE PL. I H.S. BOLTS

DETAIL 'A' DETAIL 'B'

255
T T T T
48080 0/0 OF CONCRETE
T T T
48000 0/0 OF STEEL

6000 6000 6000 6000 6000 6000 6000 6000


113 LEF 0 END 11

F= F=

RF-21685
0 0 0 0 0 0 0
~

-
!----
I
:il

>- >-
til til
l. OF RIDGE
fr\ - - fr\
L_/ I -I L_/
!---- -80 80
~ ~
~~
3.3 STANDARD BUILDINGS -

!---- 1

256
'!!
0 t==
0 0 0 0 0 t==
0
\ -------:1 = =
ANCHOR BOLT PLAN

~To@
250
24 ~ A.BOLTS 50 50
ENDWALL
20 Thick 1- STEEL LINE
BASE PLATE -----..._

N ENDWALL
CONCRETE LINE
~I
t:JI
I
125 125 I
~ ~l t
~I
)--
!siDEWALL f CONCRETE Ll .
""""""""" STEEL LINE 1
DETAIL 'A' DETAIL 'B' DETAIL 'C'
13

-
13

L
~Hl ~HR
MAX BRACED BAY REACTIONS (KNS)

L~L)
Main frame column reactions: ~13 (D.L+L. L)

Signconvensions:
Positive hor.Reaction : totheright t 5 (D.L+W.L)

Positive ver.Reaction : upward


Positive moment : counter clockwise
MAX WIND COL REACTIONS (KNS)

Mainframe- 2-8
Reaction For Combined Loads:

Description Horz Vert Momt Load


KN KN KN-M combination
LEFT COL. 19.2 49.8 0.0 1DL+1LL
LEFT COL. -16.6 -24.6 0.0 1DL+1WLL
LEFT COL. 4.8 -9.5 0.0 1DL+1WLR
LEFT COL. 2.1 10.7 0.0 1DL+1SEI

I RIGT COL.
RIGT COL.
-19.2
-4.8
49.8
-9.5
0.0
0.0
1DL+1LL
1DL+1WLL
RIGT COL. 16.6 -24.6 0.0 1DL+1WLR
RIGT COL. -5.5 13.3 0.0 1DL+1SEI

257
cp PURLIN
200ZX1.5 2~~~\~s 3s~s3 2~~~\~s
48000 o/~kEL LINE
PURLIN
200ZX1 .5
PURLIN
200ZX1.5
PURLIN
200ZX1 .5

i--='----jjll3
r.-.1.-1~==~~~==~-.--~~-.~~~--.-~==~~~==~-.--==~-.~~~-.11_
ZA,706(TYP)

/
/
''

~
/
/
'' /
/
''
c-t+-- - -
r- - --- -~-

'' /
/
'' /
/

Oi ',,~>/
'' /
/

~~", , iii
~ ;?
=
(;;\___ / ', /' ''
~ rr-----~----~-~---t---~-~--~--i----~~----~
/
''
" ~
' /
' -~>-'
!''1~~,
,.."' ', / ''
~ ~L_-~~-~-~o.m-_i--..~~-L_-.~..,-~-. . .~--~--..~..--i_-~~-_L-,..""".-~ -

ROOF FRAMING PLAN

353 353

625 625 625 625

PURLIN CONNECTION DETAIL PURLIN CONNECTION DETAIL


FROM GRID LINE 3-7 At Lines 2 & 8

END WALL
STEEL LINE

RAFTER

PURLIN CONNECTION DETAIL


AT GRID LINE 1 &9

258
GIRT GIRT GIRT GIRT GIRT GIRT GIRT
GIRT
200ZX1. 75 200ZX1.5 200ZX1.5 200ZX1.5 200ZX1.5 200ZX1.5 200ZX1.5 200ZX1.75
cp
353 709 3553 35~53 48000 0/
35
~ 53
TEEL LINE
35~53 3553 70~53 cp
LEF 6000 6000 6000 6000 6000 6000 6000 6000 <9ND

'~
5887 I 5887
'

ZB-6706(TYPJ ZA-6706(TYPJ ZA-6706(TYPJ ZA-6706(TYPJ ZA-6706(TYPJ ZA-6706(TYPJ ZA-6706(TYPJ ZB-6706(TYPJ


~
0
~

0 I
'\ '\ I
0
'\ '\ I
f- ~ '\
~-.../ '\
:r: '\ I
0
w 0
', ~I,. ~7 '\ I
> 0 '\ I
<{ N
w X
Q/
#< '\ I '\
0 0
0 OJ I '\ I '\
l{) I '\ I '\
ro ~ '\ I '\
0 I '\ I '\
N I '\ '\
N u I
I '\ .., I '\
N
!rl:>: ~ ..,u ..,u I 2-6000(8)(TYPJ ..,u ..,u ..,u :>:
'---
.. 1#1 ..!rl
SIDE WALL FRAMIMNG ELEVATION@ GLA

259
cp ~
cp ~ ~ MF-515@3050(16) cp cp y cp cp
<>U-501 L@4940(1) GU-501@4940(8) GU-501 11@4940(1)

r'
:r:
w
>
<{
w
0
0
l{)
ro

START/ END OF PANEL


167mm FROM STEEL LINE 48 PANELS RUN ONE W/333 LAP

SIDE WALL SHEETING ELEVATION@ GL A


(E) (D) (c) (B) (A)
I
GIRT 200ZX17.5

XB-4011(TYP) I
GI RT 200ZX2.5

XD-5B36(TYP) I GIRT 200ZX2.5

XD-5B36(TYP) I
GIR T 200ZX17.5

XB-4011(TYP) I
~ 1.0 2.-3090 (2.) ~ 1 " 309 0(2.~- .! ~90{2) 2-3090 (2) 10 L::::::::::,_
0 2.-4580_(2.)- - ry~ ~~~ 10

- % .~
A- c. ~ -~ W8X10 ~ - @~~ib -r-
~ I(A) \ (A ~ 1 ::::
~ W8X10 '<--' I~
0 ~ ~--1~
n
~-w
8f1'- ~
~
f- OL() i 1'1 .:,
:r: r 1~ H -
r.D v b
w ~- t-+
>
~-----------1!~~-----------------ll~-------------------l!l-----------~ v ~

<r::
0
/'--
I\._1-86CLIP(10) !I \._1-25CUP(30J
~:)
w \..()
J ~ ~ 6Q
0 o- ~-------------li ---------------------II~--~----~7G~1 ----~---Ii l------------~ b
0
L()
co
(.0
~
~ ~r "- XD-1406 1-x_o_-1_40_6_ -18
~ ~.
::;"-_ _ _ _ _ ____, cr- _
~- I 1111

i X j i:l I!
"'
~~ ~~ ~
N
0 i
~
i
0
N x i :
N ~ BASE ANGLE i BASE ANGLE I~ ~ .
N 2-3990(2) i 2-5790 (4) ~~
--- I I -~

1500 1 3000 11500


I I
4500 6000 6000 4500
21000 oyo STEEL

END WALL FRAMING ELEVATION@ GRID 1

1.0L::::::::::,_ (A)
RAKE TRIM
RF-501-3620 (3)
-
10 I
~- ~
- - - I 8ESP1 I

~
~
~
~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~
~
8
;:
8
;: ~
~ ~ ~ ! ! ! ! ! ! ! ! ! ! ! ! ! ~ ~ ~
I-- -- - -- - - -- - 1-- - - - -- -- - 1--- - - -- - -- --

:
~iL'
;!I:

..
~il:'
!-
5!~
~X:-
~ ~->;+:<)
"3 c,

I START/ END OF PAN EL


: FROM STEEL LINE
21 PANELS RUN W/STD LAP

END WALL SHEETING ELEVATION@ GRID 1


FSK-50THK. (10) ROLLS W/20000 LENGTH

260
~1.0 CL.or!sYM~E"ffiY
10

105000UT/RIDGE 10500RIDGE/OUT

210000/0STEll

CROSS SECTION@ GRIDS 2-8

8-M24X85
HSB "
r
""
I
""
I
"" "'
I

~
fi r-~ 11
r-~ 11 ~
""
~

~
~

~
16 THK
SPLICE LATE

SPLICE LATE

DETAIL "A" DETAIL "8"

261
~ f-
cp ~ 48080 0/0 ~RETE NOTCH
cp ~ cp
QI,_ 48000 0/0 STEEL LINE JA-o
4
LEF @ENDII 8000 8000 8000 8000 8000 8000 ILEF @END
0 1131 7887 7887 113

RF-21860
7
@-~!l~ t ~E
if i 8 ====~@F~-~-~~==~--~==~~-=_JE.@======E~====~@F~-~-~~==~--~==~~=--E~@=====3
0
0
'!)
I I I I I
I i I o
--- I I I c ~
I
0
r=' 0 I I I i I
0
0
z _J <!)
~
w w
r-w
w r- I r I I i r I
"' Cj)

0--10'- --l---=-l-lt-tltf-l=--- _ _ _ ~ _ CL. ~~ _ ~ _ --i-- _ -----=>-IHI--1-


u 0
0
,o0
+- _ _-+ ____ t- + ___
0 ~ 1 ~ I I i ~ I
0
00
0
N
3.3 STANDARD BUILDINGS -

I ! ! I ! ! ~
I I I I I
0

262
--- I I I I I c

~~ I I I I I
..,.
; --===--===-- ; ; ; --===--===-- ;
0---
"~ ~7epT00 ANCHOR BOLT PLAN

250 40
ENDWALL
20 - A.BOLTS STEEL LINE
20 Thick
BASE PLATE
16 Thick
BASE PLATE
.....
"' CONCRETE LINE
"'~
.....
"'
:3
& ~

16 Thick
0
..... BASE PLATE 200 1140
CONCRETE LINE DETAIL 'A' DETAIL 'B' DETAIL 'C'
SIDEWALL STEEL LINE
15 (W.L)

t17 (D.L+L.L)

~18 (D.L+W.L)

~Hl
MAX WIND COL REACTIONS
{KNS)

Main frame column reactions:

Sign convensions:
Positive hor.Reaction : to the right
Positive ver.Reaction : upward
Positive moment : counter clockwise

Mainframe- 2-6
Reaction For Combined Loads: MAX BRACED BAY
REACTIONS (KNS)

Description Horz Vert Momt Load


KN KN KN-M combination
LEFT COL. 36.3 64.2 0.0 1DL+1LL
LEFT COL. -21.1 -28.5 0.0 1DL+1WLL
LEFT COL. -3.0 -15.4 0.0 1DL+1WLR
LEFT COL. 5.0 12.8 0.0 1DL+1SEI

I RIGT COL.
RIGT COL.
-36.3
3.0
64.2
-15.4
0.0
0.0
1DL+1LL
1DL+1WLL
RIGT COL. 21.1 -28.5 0.0 1DL+1WLR
RIGT COL. - 8.8 14.8 0.0 1DL+1SEI

263
ROOF FRAMING PLAN

353 353

PURLIN CONNECTION DETAIL PURLIN CONNECTION DETAIL


FROM GRID LINE 3- 5 At Lines 2 & 6

END WALL
STEEL LINE

RAFTER

PURLIN CONNECTION DETAIL


AT GRID LINE 1 & 7

264
GIRT 200ZX2.5 GIRT 200ZX2.0 GIRT 200ZX1.75 ~ GIRT 200ZX1.75 GIRT 200ZX2.0 GIRT 200ZX2.5
cp 35~09 35~53 353 353 35~53 7~53 cp
48000 0/0 STEEL LINE
8000 8000 8000 8000 8000 8000
7887 7887 11113

___ ....
0
0 /
f-! N / /
:I: N
'' ''
ZD 8706(TYP) ' 7C-8706(TYB\ / ZB 87nofTVo\ 7R-R706(1YP) 'w-_nnofTVo'-'~G / 7n 8706(1YP)
/
~ 0
llO '' /
<
w ,cl...~~( ~~/
~ ~ r.1 :;,"'-
0 s:-"j'?
0 ,~--- 1..'
0 0
N ~:,~" '' /
''
N j;j / BASE ANGLE j;j j;j /
"' N ~ ":l 0 Gl.. 'A' /
' ' ..... ~ 12 sooo<a> /
'' ..... ~ ~
1~~.

SIDE WALL FRAMIMNG ELEVATION @ GL A

265
T HO _ ... ,rn;; .. -z
f-!
:I:

~
i::5
0
0
0

"'
48 PANELS RUN ONE W/333 LAP

SIDEWALL SHEETING ELEVATION @ GL A


cp GIRT200""7.5

.-::::::::::::J1 .0
C? GIRT 200ZX2.5

10

XD-5836 TYP XD-5836 TYP


r-=
:r:
w
>
<.(
w
0
0
0
CD

END WALL FRAMING ELEVATION@ GRID 1

c__ PEAK BOX C? A

t:-
RAKE TRIM(TYP)
RF -501 (5480)(2)
I ''''"lnt=i:::=::
- -10~ :::!
r l
:~
0
g
0

~I
0

~I
0

~I
0

~I
0
;:!;
0

~I ~ R 0

~I
0

~I
...
0 0
g
.....
I I "'I "'I "'I I
~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~

~~
~~4>

i \. i
I
I
I
START/ END OF PANEL
FROM STEEL UNE 21 PANELS RUN W/STD LAP
\
USE TWO 20m FULL ROULS
I
I
I

FOR FIRST 3PANELS CUT INTO


3 EQUAL PIECES C GL A&E

END WALL SHEETING ELEVATION@ GRID 1

266
~1. 0
10

148Sl

21000 0/0 STEEL

CROSS SECTION @GRIDS 2-6

8-M2 0X70

r HSB

~ ~- _______:
~

-$-
14- M24X85
HSB
I I I

'[{
N -
-~
- -$- -$-
~ ~
-$- -$-
16 TH K
SPLI CE LATE
v -$- -$-- -
~

-$- -$-- -
20 TH K
SPLI CE LATE
I ~

DETAIL IIAII 11 11
DETAIL 8

267
y cp cp 48080 OU T OF CONCRETE cp cp cp
<Moo oo ' 1 o m me""'
IT,
8000 8000 8000 8000 8000 8000

LF@ END 11
l
I 7887 7887
I
I 13LF @ END

0--- '~ ~
1
t-- -- --1@ t @t-- -- -- t

RF-21885
0
0

"'.,_
~
0 I I I I I
0---- 0

~
"'
~ 0 c~
0
~ 0
~~
0 ~ "' I ~ I I I ~ I
u ill
"- 0
0 ~ 0

"'
@--- 6 -- + __!__ -+---[-"'=""-- +-l_ +-- ~
" '
~ 0


N I I I I I

f-- rL ~
0----
0
3.3 STANDARD BUILDINGS -

0 I I I I I
':;
' ' ' '

SINGLE
WALK DOOR
@+------------ +@ t @+------------ +

268
0--- 3486 F1 3487
4
ANCHOR BOLT PLAN

qxi) ((?)
40-

~O NCRETE LINE
0 20 A.BOLTS
~ 250 I 24 A.BOL TS
.~
20 A.BOLTS
ENDWALL
STEEL LINE
n I
50,50
I
16 Thick
1/BASE PLATE
~
16 Thi ck

0
~ J- f-- 0
N

~
f--*~ <D

T I
I(
w
f--
1;! 1 ~
1 SIDE -- u
CONCRETE LINE 1 z
0
u

DETAIL -A DETAIL- B DETAIL- C


,_____22 (W.L)

117 (D.LL.L)

L(D.LW.L)

MAX WIND COL REACTIONS (KNS)

~HL
13

Main frame column reactions:

Sign convensions:
Positivehor.Reaction : to the right
Positive ver.Reaction : upward
Positivemoment : counter clockwise -
13

I,. I,.
MAX BRACED BAY REACTIONS (KNS)

Mainframe- 2-6
Reaction For Combined Loads:

Description Horz Vert Momt Load


KN KN KN-M combination
LEFT COL. 25.1 64.2 0.0 1DL+1LL
LEFT COL. -22.2 -28.5 0.0 1DL+1WLL
LEFT COL. 6.3 -15.4 0.0 1DL+1WLR
LEFT COL. 6.3 12.8 0.0 1DL+1SEI

I RIGT COL.
RIGT COL.
-25.1
-6.3
64.2
-15.4
0.0
0.0
1DL+1LL
1DL+1WLL
RIGT COL. 22.2 -28.5 0.0 1DL+1WLR
RIGT COL. 22.2 14.8 0.0 1DL+1SEI

269
cp :ZOOZX2.0
S~. 200ZX1.75

'~" ,;,~~~ '


48000 OUT
~
/;
,;,~~~ '
f13F STEEL LINE
"~' 200ZX1.75

'~" 200ZX2.0
C?
8000 8000 8000 8000 8000

za-1170&(1<1) ZA-11708(1<1)

0---- 1<, />1 f t',, //1 ~


/
' ' /
/

i \'!P_...."" ...... i i i /
X

' i
"
I_/ ~'(~
',,, I I 1// ',,, J
0---- -

'' /
/
'' //-;
' /

::J ;;I ''


' /
/
/
;I ;;I ;;I ' '/
/
/
I
~
w I ~~~,-:;' ' ' 1 I I /
/
'' 1
' /
'
I // ',_I I I // '<I
-- --+---
I ',
-------.-
//1 I
--+----
I ', /I
- -----+1

I '' /
/

I I '' /
/
0
' /
/
I ' /
I
/', /'
I
;;I ~ ;;I ;;I ' '
/

c~' ', /
o;
/7'
/
' '
' '-,;. /
/

'
--- -

1"',,, ////1 I I.',, //1


' ' /

~ ~
'
~
/ /
X X
:;' /
' ' ! ! /
' '
t//
/ /

[/ /
'
',] i '
',-
0- '---'-
Lm_,,,
~~mo;]
1EC-7tn--J

(~)
IDC-7990(1)

ROOF FRAMING PLAN

353 353

PURLIN CONNECTION DETAIL PURLIN CONNECTION DETAIL


At Lines 3-5 At Lines 2 & 6

PURLIN CONNECTION DETAIL

At Lines 1 & 7

270
GIRT GIRT GIRT GIRT GIRT
200Z X2 .5 200Z X2 .0 206iR~1.7 m 200Z X1. 7 200Z X2.0 200Z X2.5
cp 353 353 cp
35~09 35~53 4 BOOO OUT I OUT OF STEEL 35~53 70~53
BODO BODO 8000 BODO BODO BODO

13 7BB7 7BB7 11 3 LF 0 END

ZD-8706(4 ) ZC-8706(4) ZB-8706(4) ZB-8706(4) ZC-8706(4) ZD-8706( 4)

IT ~
Ul / /
m ,---- ' '
0 / /
Ul / /
f-- ~ / /
'' ''
I c---- ' '
0 / ' ,_o /
w 0 ~ ' .......... /i\ ~
> 0 ~ ' ''i!!-c. / ~ ~ ~ ~
<( N ~ g,...'f'-~/ ~.,><../~ ~
w G /'-
0 ~ /
0
0 co ~~~~-, /
Ul "<'\,:/ 1...: /
'' ''
co ~ ,---- ' '
0 / /
N / /
N / /
'' ''
N I;; I~ ! / /
-~
'' ''
3 4 B6 ~ 1~ 34B7
SINGLE WAL; DOOR

SIDEWALL FRAMING ELEVATION@ A

271
cp GU-SOIL-49-40(1)
Cf y ~U-501-4940(8) y ~ GU-SOIR- 49-40(1 )
C?
t.lF-515-3000 (16)

f--
~~ I
I
~ 'ii:'
w ci ~ I
>
::5 ~ I
0
0 I
Ul
co
I

5 1
~
i~~ Fto~N~T~LP~ZfL 4B P AN ELS RUN S WISTD LAP, LAS T P ANEL 333 LAP

4 BOOO OU T I OU T OF STEEL

SIDEWALL SHEETING ELEVATION @ A


GIRT GIRT GIRT GIRT
200Z X 1.7 200Z X 2.5 200Z X 2.5 200Z X 1.7
10
1r-- XB - 4011(5) xo - 5836(3)
2-3090(2) = = 2-3 90(2)
xo - 5836(5) XB - 4011 (5)

2-3090(2) == 2 3090(2)
2-4580(2)
-= == 2 4580(2)

-r---- L9
W8X10
fl ~
~
W8X10
[L9 -
[16! 0 l6J
0
n

I~ ~I
~

~ 0
(TYP) ~ (TYP) "- l[)
"'
X lD
"'
N ~

:r
0
x
~ iI , 7G1
r
~
0
I'
l[)
~

~
il 0
X

XD-1406(1)
\ , r
~ "~I
'\..._ XD-140~1
S S D
3MW X 3MH

~ ~ ~
N N

~
(.)
N
N "'
_11500] 3000 _11500
4500 J
~0500
bUUU 6000
10500
J 4500

21000 OUT I OUT OF STEEL

ENDWALL FRAMING ELEVATION@ GRID 1

10
RF-504
10
C?
1r-- RF 501-3650(3) Rr 501-3650(3) ~1

0 0 0 0 0 0

.,"
0 0 0 0 0
.,"
0

~ ~
"'""I
I

"' "'~ X "'


I

1--
0
I
0
I
0
I ~ 0
I I-
:r: ~ ~ ~ ~ ~ ~ :r:
w
> ~
<( 8(
w KW-C .5-20 0(3) ~
0 "' b
~
0 0
l[)
CXJ "'0 "-
~
"'J, E.
S S D
3MW X 3MH ~
~

START /END OF PANELS


FROM STEEL LINE 21 PANELS RUNS WISTD LAP
21000 OUT I OUT OF STEEL

ENDWALL SHEETING ELEVATION @ GRID 1

272
C? y cp
10 10
1 ~ ~ 1

0
L(]
Ol
-,----

0
L(]

~
-:---
f--
:r: 0
0 f--
w 0 :r:
>
<{
N
[L'
w _j

0 -:--- u
0 L(]
L(]
0 N
co co C'-
~ C'-

-:---

0
N
N
N

10500 0/C 10500 C/0


I
I

21000 OUT /OUT OF STEEL

CROSS SECTION @ 2-6

EO. I ' 100 ' I EO .

~
I 810 _I
I
-
W- f-
I

0
50 100 100 50 =f= FF S'
510 M24x85
I I
H.S. BOLTS
-:-r---- 0

:1
M24X85 0
8 H.S. BOLTS
;;:; 0
<D

0
-
0
0
=F= '=F= S'
8 I

-r----

I
VAR IES
f I

I
20 Thk .
SPLICE PL.
20 Thk.
SP LICE PL. .I *I.200
L(]

""

DETAIL A DETAIL B

273
3.3 STANDARD BUILDINGS -
RF-36660

0-- ~ " l l l l l
I j -- --~@ I@ I@ I@ j -- j I
I I I I I I I I I
,____._ r--------t-------~------t------l-------t-------l------~------ ~
i I i I i I i
i I i I i I i
i I i I i I i
(r---~---~--~---1---~--~---r--~

~ ~ ~.. ,,.,,,, i I i I i I i
i ~ I i I i I ~ i
:r-H-=------+---+--+------+------1------+------+--~--+-------~
" i ~ I i I i I ~ i
~ ~ !""''"'' i I i I i I i
~~r---J ___ L __ _l ___ J_ _ _ l __ _J ___ L ___ ~
I I I I I I I
i I i I i I i
i I i I i I i
,____._ r------~------ l------t------j------t------1 ------t------- ~
I i I i I i I i I
I (W~::,~,,.,i@"'"'"'"'''"'l i I i I i I
GrU4-,,~.~,.~,,~.~L~-~~--~--~--~--~=~=====F=I==~I====~I=====~0-~--~-~--~-~~==~

ANCHOR BOLT PLAN

Q)m0
250
50 50 24 Thick
=r I

~PLATE

_ill__A._B_OLTS

~
"'
~

:2

ll ~1 I
125 i 125 1
l
I
00--
SIDEWALLSTEELLij
' ~LINE
DETAIL 'A'

DETAIL 'D'

274
~_1_7(W.L)

113 (D.LLL)
~HL ~HR

L(D.LW.L)

MAX WIND COL REACTIONS (KNS)

.--------....------'-17.5

Main framecolumnreactions:

Sign convensions:
Positive hor.Reaction : to the right
Positivever.Reaction : upward -----
17.5

Positivemoment : counterclockwise
L. L.
MAX BRACED BAY REACTIONS (KNS)

Mainframe- 2-8
Reaction For Combined Loads:

Description Horz Vert Momt Load


KN KN KN-M combination
LEFT COL. 86.6 86.9 0.0 1DL+1LL
LEFT COL. -32.5 -30.1 0.0 1DL+1WLL
LEFT COL. -19.8 -17.8 0.0 1DL+1WLR
LEFT COL. -16.5 21.2 0.0 1DL+1SEI

I RIGT COL.
RIGT COL.
-86.6
19.8
86.9
-17.8
0.0
0.0
1DL+1LL
1DL+1WLL
RIGT COL. 32.5 -30.1 0.0 1DL+1WLR
RIGT COL. -22.7 23.0 0.0 1DL+1SEI

275
cp PURLIN
200ZX1.5
(TYP)U.NTD.
~
353 709

48000 0/0 STEEL LINE

LEF C ENDI---'-'-'-'----t-----'-'-'-'---t-------'-:_:_:_--+----'-'_:_:_--+---'-'-:_:_--t----'-'-'"------1----'-'-'-''---f---:..:..:..:C----t LEF @END


11 113

~
EAVE STRUT.
1EC-5992(1) 1DC-5990(1)(TYP) )

~r--~==~~~~======~~==~~~==j=========~=========j==~====~======~~~~~EC~-~59~92~1~--
ZA-6706(24)(TYP) '- -0' -0'y

0---
~------t--'-~---~~~--+----~----~----+-----+-----~~~~--1-----~ ~
d~ d~
v ~ / '

v ~
t--~:::::::::::::==::::-::::::=t::.=::=::::::::::::=:::::=-tf-:::::::==::::::::::::::::::::::::$::::::=::==:::===::::::+::::::::::::::==::====
- =j:=::==:::===:::::::::::=-
=$
/ ~
-::::::::==::::=::::::::::::::=t=::::::::::::==:=~::::::~- CL. OF RIDGE

~ / ' /

,,.,-!'"' / ;;-
// v0-~ / '''V0-~
/
--- '
' '-'"'-!>~. /
/

/
OQ~
1EC-5992(1) /. 11SBT1(TYP) -,._ /. .,., 1EC 5992(1)
--

1DC-5990(1)(TYP) \ooWNSPOUTS(TYP)

START END OF SHEETING


FROt.iSTEELLINE 48 PANELS RUNS W/STD LAP

ROOF FRAMING ELEVATION

353 353

PURLIN CONNECTION DETAIL


PURLIN CONNECTION DETAIL
At Lines 3-7
At Lines 2 & 8
ENDWALL
STEEL LINE

PURLIN/GIRT CONNECTION DETAIL


@GRID 1&7

276
r-'
GIRT 3s;-ros 35~53 35~53 35~53 35~53 35~53 70~53
200ZX1.5(TYP) 48000 0/0 OF STEEL
bUUU bUUU bUUU bUUU bUUU bUUU bUUU bUUU
13 LEF 0 ENn 1' 3 LEF 0 END

ZA-6706(2) /
(TYP) ~" /
"'
1----
"" ~~" "" /
~q,'\"\v
- 1-- .. """ ~~ ~
.. . .. .. . """ X ..
.y /
2-6000(TYP)
"' Il J I / I """ "" / """ ""

SIDEWALL FRAMING ELEVATION @GRID-A

277
9
Cf ~ ~ ~
48000 0/0 OF STEEL
cp cy ~
600 6000 6000 6000 6000 6000 6000 6000
T 48 PANELS RUN W/STD LAP LAST PANEL TO BE 333 LAP

START /END OF PANEL 0 167 FROM STEEL LINE

MF-515 TYP
~I~ "F-515-30 0(16)
~ / GU-501-6150(6) GU-501 R-6150(1)

I
g~ g
w ~ I
OE. m~
I

3"7"SWD(")

SIDEWALL SHEETING ELEVATION@ GRID-A


KW-PANEL-0.5MM 1HK(ARCT1C WH1TE)
(L)ooog z
1H 3A'i3
0009 (L)0009- LVLOS-..:Ir'l

I OSOL I OLSL I 09LL I ~=:NI~l~:3N~~OJ:===========~


n 0---- ' ,-c-

~I
L:l3Hl
/@J

- "
l!
~
!r
~I 1[ ~

# @J ~I Z:l3H9

! ~
@J
~ f
; ~
I
....... ~ .......
I I
~ Z:l3H6
....J ....J
(!) (!)
! ~I
z z
; 0 0

~
~ i=

~
w
~
w
2 ....J ....J
w w
,@ (!) ~ 8 (!)
z ~~ j
z
~I
X
L:l3HOL
:::-
~ i=
\...-J w
~ ~ ~
u.
w
I
~
~ ....J
en

'
....J ....J
....J

g \
~ ~
0
i z 0
z
w
~I ~ w
~ L:l3H6

E.
@~
~ ~
l:.
g i ~

\ @J
l 1!~
L:l3H9

~L ~
- i:;;
~

@J
!l iJ L:l3Hl

u ]~
~----------~'-~
~---~~~--~

(L)0009 Z
Nl~l ~3N~O:>
(L)0009- LVLOS-..:Ir'l

278
~~

T T

18000 0/C OF STEEL 18000 C/O OF STEEL

36000 0/0 OF STEEL

CROSS SECTION AT GL-(2-8)


FSK-50THK INSULATION (10Kg/m3)-(6666x3)=20000 Length &
-6000+6666+ 7333=20000 Length

279
1DO 8-M24x85
H.S. BOLTS
STIFFNER U')
"<I'
85
0
TS 0 ~I
20Thk. SPLICE PIL.

0
0

U')
"<I'
SPLICE PL.
I I

DETAIL 'A' DETAIL-S


3.3 STANDARD BUILDINGS -
RF-36685

cp ~080 ~Rm0/0 NOTCH

48000 0/0 STEEL LINE


cp
40 140
LEF\UEND 6000 6000 6000 6000 6000 6000 6000 6000 LEF

11 5887 I I 5887 1113

G
~ I I I I I I I

!- ---== -i@ @! @! @! !-=---- --t


I I
~
i i
0---- c--
--
i
i
--
~
i ~
-
~
'ol--

~~ I
~[---
--
i
i
i
--

I"
~ ~r- ~ i ~
0-1 ~
~r-
--t-~--+-----j---~~R!D~---+--tJ-
~ i i ~
~-_@ -
~ ~
~ ~~
.i ii
~

--
:I- i
@-- J-r---- -
i ~
i ~
i _.,...,

'

0-- :----- ~-
i
~
i
i
i--- ___ ----i @i @i @i i--- -- ----i
0-- ~ 1 1

ANCHOR BOLT PLAN

EN OWALL
STEEL LINE

16Thick
BASE PLATE

SIDEWALL STEEL LINE

DETAIL 'A' DETAIL 'B'

DETAIL 'C' DETAIL 'D'

280
24 (W.L)

t
13 {D.L+L.L)

~HL Ls {D.L+W.L)

MAX WIND COL


REACTIONS (KNS)
Main frame column reactions:
~---,__---=
30
Sign convensions:
Positive hor.Reaction : to the right
Positive ver.Reaction : upward
Positive moment : counter clockwise

-- 30

Mainframe- 2-8
L
MAX BRACED BAY
t3
Reaction For Combined Loads: REACTIONS (KNS)

Description Horz Vert Momt Load


KN KN KN-M combination
LEFT COL. 61.3 89.0 0.0 1DL+1LL
LEFT COL. -30.1 -33.5 0.0 1DL+1WLL
LEFT COL. -9.7 -17.8 0.0 1DL+1WLR

I LEFT COL.
RIGT COL.
RIGT COL.
10.6
-61.3
9.7
22.7
89.0
-17.8
0.0
0.0
0.0
1DL+1SEI
1DL+1LL
1DL+1WLL
RIGT COL. 30.1 -33.5 0.0 1DL+1WLR
RIGT COL. -17.4 25.7 0.0 1DL+1SEI

281
S?,
3~3
2 PURLIN
00ZX1 .5 2
(TYP)

353 709
48000 0/0 STEEL LIN E

LEF~ND_f~--~~---+--~~---r---==---,_--~~--+---~~--r---==~~--~==--~--~~--~
~ ~r'-'. ~~r-~~~--F========4~~~~~--~~~-r--~~~-r--~~~~========~~~~~~~,~
/

', .:lF
$'"' ~

' ZA-6700(1YP / ZA-6706TYP ' ZA6706fTYP

' #-~~ / ;?
~-----+~~--~----~~----~------+------4~~--~----~
']/ "

/~ -'
-
' #f') /
'"
/
/ "
/ j/ '
/

- - -- -r--
' ~-

/
'
' /

/ " '
- /
'"

"

/
'
/
'"
/
'

ROOF FRAMING PLAN

PURLIN CONNECTION DETAIL PURLIN CONNECTION DETAIL


FROM GRID LINE 3- 7 At Lines 2 & 8

PURLIN CONNECTION DETAIL


AT GRID LINE 1 & 9

282
GIRT GIR T GIRT GIR T GIR T GIRT
200ZX1 .75 200ZX1.5 200 ZX1.5 200 ZX1 .5 200ZX1.5 200ZX1.5 200 ZX1.5 200 ZX1.7 5
"'" ~ "'"'
353 353
cp ,S:~ '~' ~~' 48000 0/0 STEEL LI NE '~' '~' '~' y
LEF @END 6000 6000 6000 6000 6000 6000 6000 6000 I LEF @EN D

11]. 5887 5887 113


11SBT1 IISBT1
--.
0
/ /
0
r' N / /
I N /
"" ""
ZB-6706{TYP) ~~'v ZA-6706{TYP) " / ZB-6706(TYP)
w /
""
> 0 "'" / ''
<! co ~~ '-/
w ~ f:.J~q:./', /'-
0
~ /
0 0 / /
N '-' / '-' '-' '-' '-' /
''
~ N
'' ~ BAS E ANGLE ' ~ ~
N / /
~ 1 ~ 1 ~I ' I z 6oootBJ '
L.@~L-A ONL

SIDE WALL FRAMING ELEVATION@ GL A (AS DRAWN)


SIDE WALL FRAMING ELEVATION@ GL G (OPP HAND)

283
r'
I o:-
w b
>
<! ~
w
0 ~
0
0
(!)

l1 ~
I ~AONL
STAR T/ END OF PA NEL
167m m FROM STEEL LINE 48 PAN ELS RUN ON E W/333 LAP

SIDE WALL SHEETING ELEVATION @ GL A (AS DRAWN)


SIDE WALL SHEETING ELEVATION@ GL G (OPP HAND)
0
"' (l)(OO>t)VIOS-JN

e~
~~."'-~--,-~--
(dAl) (dA!)

~ ~
-------------------------- <(
r----0;.:.-:-.--;

!~
[<ip {
~
tXOO 83M
=~ ~" I
~ ~ Ul OOL-.M.>I
:::> I
I
I 0 OOQ-M>
0 11 I
f 0
tD 006-M>
! I

~~ i ooov-M>

OOIV-M>
I

- i I

oozt-.M.>I
i I

OOtr-.M.>I
i I

0
0
0
~ ootv-M> I

tD ,I oosv-M> I
II
~~~ I oo9v-M> I
~! .....
~~ I OOLv-M>
I
0
0
0 OOQt-.M.>I
I 0::
LJ)
! I (!)
--=-r- !
006tr-.M.>I
I

I
0 0 z i1
OOOS-M> OL91-M>
-~-~~
z
0 0
0 I
0
~~"
~
0 0
i= :5ll..
~
I") tD _j
OOIS-M> OL91-M>
w I

or- w
I-
(f) I
OOlS-M>
I
~
w
0
I-
en
0
~

>I
LJ)
0 ...J OOS-M>
0 ...J
--=- 1---- "'-- w I 0
0 w z
f~l
0 0 (l) tD
(!) OOS-M>
I (dA1)060S-M> (!) ::J
0 I")
a::
LJ)

--=-r-
0
0
z I z en
__.
0
~
OOlS-M> I
i= w
tD
w
!
z
0
0
0
0
I")
(2 j OOIS-M> I OL91-M>
-~-~~
w
I
~
0
I")
0
tD
LL OOOS-M> I OL91-M> ~~" en tO
('I)
...J \
...J i I ...J
-f- 006t-.M.>I ...J
~
0

~
0 I
LJ) \ OOQv-M>
~
I
0
z
n. . 0
I
I OOLv-M>
w I z
I oo9v-M> w
~r- \I
I
0 oosv-M>
0 \ I
0
tD oovv-M>
1 I

l
\
OOt-.M.>I
I

ooztr-.M.>I
I
0
\ VXOO 83M \ OOIV-M> I

~~
I t,;Xt,;ZL S~l.:J

~ \ ooov-M> I

I ~ 0 i 006-M> I

t 0

~, ~
0 \I
I tD OOQ-M> I
\ \
~I 1
OOL-.M.>I
I

I
\ t:;p i>'XOO 83M
t;X!OZL S~l.:J

L __ _,~~~o~> __; --------------------------

foLoz / oc;gll oLe; li09lll ozzz I 1H 3/\\1'3 ooc;g


'lH 3/\\1'3 ooc;g (l)(OO>t)VLOS-JN

284
CL.OFI SYMMETRY

~1.0 1.0~
10 10

36000 0/0 STEEL

CROSS SECTION @ GRIDS 2-8

285
8-M24X85
lrl HSB
I I
-$- -$- '~ -
-$- "'
12-M24X95 so 1oo
HSB
I I I I

r-~ ~ ~ ~
20 THK v -$- -$-
f--$- -$- -$- -e- -$- -$- SPLICE LATE
!f{ ~ -$- -$-
-
.,
24 THK I '-
SPLICE LATE I ~ f ~ I

DETAIL "A"
DETAIL "8"
3.3 STANDARD BUILDINGS -
RF-36860

4110000/00FSTEEL

--- '" 1 1 1
j0- -- ---~0 j0 j0 ---~0
8 1 1

. I I I I i I I
0--- ~--------~----------t---------1---------t--------~--------f"
1 i i I i i
~ I i i I i i
I i i I i i
0- ~1----~----~----1----~----r---f"
~ ~ ~.. ,,.,,,, I I I I I
. i i I i i
0- ~ t---------+--------+--------1-------+--------f---------f"
" i i i I i
~ ~ !""'''"' i i I i i
0-- c!~ ____ j ____ l ____ l _ _ _ _ l ____ L ____ f"
I I I I I I
~ I i i I i i
I i i I i i
0--- ~--------~---------~--------j- ------~---- ----r---------f"

I i i I i i I
I l. i I i i I
~:~r-~'0. _____ ----i 0 01 f0. _____ ----i 0
0--
ANCHOR BOLT PLAN

DETAIL 'A'

DETAIL 'C' DETAIL 'D'

286
,____17 (W.L)
117 (D.L+L.L)

~HL ~HR L(D.LW.LJ

MAX WIND COL REACTIONS (KNS)

Main frame column reactions:


. . . . - - - - - --.-----'-
17.5
Sign convensions:
Positive hor.Reaction : to the right
Positive ver.Reaction : upward
Positive moment : counter clockwise

- 17.5

L L
MAX BRACED BAY REACTIONS (KNS)

Mainframe- 2-6
Reaction For Combined Loads:

Description Horz Vert Momt Load


KN KN KN-M combination
LEFT COL. 113.7 114.9 0.0 1DL+1LL
LEFT COL. -43.9 -41.1 0.0 1DL+1WLL
LEFT COL. -27.0 -24.6 0.0 1DL+1WLR
LEFT COL. 21.1 27.3 0.0 1DL+1SEI

I RIGT COL.
RIGT COL.
-113.7
27.0
114.9
-24.6
0.0
0.0
1DL+1LL
1DL+1WLL
RIGT COL. 43.9 -41.1 0.0 1DL+1WLR
RIGT COL -29.1 29.7 0.0 1DL+1SEI

287
y ~.75(1YI') ~ ~.50(1YP) .~. ~.SD(TtP) ~ .~. y
*
(U.Hm) 4!1000(0/0)

h~
8000
""
@---
::;II 7887

lEC-PC-7992 I r""-""""'"' ~ I
~1DC-PG-7990(TYP)(5)
I llEC-PG-7992

'' /
/

' '-""'/
' /

/ ''' ,.>""',
/
'
'' /
/

0--- '' /
/
''
' /
/
/

'' /
/

' ,~'
' /

'' ,~',,
/
/
/
'
/
/
'' /
/
''
0---- '' /
/
,_,_,,.
(24)(TYP)U.NTD.
'' /
/

'' /
/
'' /
/

' /
' /

/
/
X

'' - ,,:q, ''


/
'' ''
0-i
/ /

-
/
' /
'
~ '' / '' /
/

' /
' /

'' X
/ '' /
/

/
/
'' /
/
''
/
' /
'
@--- /
/
'' /
/
''
'' /
/
'' /
/

'' /
/
'' /
/

' /
' /

/
'' /
''
"", '
/ /
/

/ /
/
''
---- /

'' /
/
/

''
'

' ' / ' ' /

'' ''
/
/
'' /
/
''
/
'
0-- I LIEC_,_,., ~) )
L,oc-PG-7990(TYP)(5) L,EC-PG-7992

: STARTf!NDDri'ANELFIIDWSTEELLJIE
(.!!PANELRUNSWjSTD.LAP

ROOF FRAMING PLAN

PURLIN/GIRT CONNECTION DETAIL


PURLIN CONNECTION DETAIL
At Lines 1 & 7 At Lines 2 & 6

353 353

PURLIN/GIRT CONNECTION DETAIL


At Lines 3-5

288
GIRT GIRT GIRT GIRT GIRT GIRT
cp 200ZX2.5(TYP) 200ZX2.0(TYP)
,,, 200ZX1.75(TYP)
,S2, 200ZX1.75(TYP)
,S2, 200ZX2.0(TYP)
,S2, 200ZX2.5(TYP)
cp
48000 (0/0)

= = = = = = I

' ~'I 7887 7887 I' I I

I
'*'
~~~--------------------,----------------------,----------------------~--------------------,----------------------,--------------------~

~ ~', /1 I ~', /1
N ZD-PG-8706 I ' ' ZC-PG-8706 / / I ZB-PG-8706 I ZB-PG-8706 I ' ' ZC-PG-8706 / / I ZD-PG-8706
2 2
o ~ " <2 l 'i I ' ,< 2 J / / 'i I <2l , I <J , I , 2 l/
< , I <J "
~ i!! ~~ ::: ( ~~ \li \li ::: ( \li i1!

1 1 1 1

~ c--- ~~WIALK OOIO~R) l~l. --~~ . . / '- '- '- 'J

3oX7o c/t..~
~~
// '- '- '- 'J . ._
~= 1 1
/ ~~~ ,
6~ ~0

SIDE WALL FRAMING ELEVATION@ GL-A

289
cp ,F-515-3050 (16) cp cp cp cp cp cp
0
~~=~~l ~6~~~ ,w 48000 (0/0) GU-501R-6150 (1)

48 PANEL RUNS W/STD.LAP (END PANEL W/ 333 LAP)


I

I 167mm.START/END or PANEL FROt.l STEEL LINE

I
I .,
- F-5C 2-1C 70 f--
..
0
~
0
0
I
~
0
0
0
<D
"'~
- ~AL DO &._
3 X7o ~
~~ OF -501 A-2200(2)
OF -5018-2200\2)
~ ,
SIDE WALL SHEETING ELEVATION@ GL-A
8--- 8---
I') il
~

r
:;;:

~
~I
il
8---- "'
f ~-

!9 ;;;
i
- ~
:;;:t ~
~I f 1'-
..;;
I 1'-
G- ~I
...J
(!)
I
...J
(!)

z z c:
0 0 ~

!
"' ~
~
w ~
~
~
0
0
0

~"~
0
...J "'"" w ~
w ~:~
!~l ...J M

w :><:-,
8--- ~I
(!)
z
lk~~
'-'
(!) ~
~
z :z
0
"' i= ~
~ w =>
~

"
~
LL
w en
~
:::c
...J
...J
en :><:
:::c
I-
0
...J
~
Ll'>

~J ...J ~
en
)f ~
LL

0
G- :;;: ~I
z
w 0
z
~L ! r--oom
;;;
,..
E.
w
~
!9
r-~ l ~
"

"' i
e- ! il
~

~L

f
~if
1!
~ L
J
~

ij
~

0--- 0---

290
10 10

T T

18000 0/C OF STEEL 18000 C/0 OF STEEL

36000 0/0 OF STEEL

CROSS SECTION AT GL-(2-6)

291
100 10-M24x85
H.S. BOLTS
U"l
"<!"
STIFFNER 12-M24x95
0 :gj
H.S. BOL TS 0

- 20Thk. SPLICE PL.


8

8
0
0

U"l
"<!"
SPLICE PL.
1 200 1

DETAIL 'A' DETAIL-S


3.3 STANDARD BUILDINGS -
RF-36885

48080 OUT/OUT OF CONCRETE LINE

48000 OUT/OUT Of STEEL UNE

8000 8000 8000 8000 8000 8000

,,
LEFCIENO
7887 7887 113
L>:F. .NO

@--- _::::=--.::-= ==--c:= --


- -
, ,
~ I I
--- 1--
'

i

~
I i
-- ! i
~ i
~ l~i i
@--- ~
~
@
+--1-----t -----t--"-OFR1~'!_-t--- ;---+---------i
> ' @

~ ~~I
~
~ i
~ '
@---
~
r--=
i
~
~
~
I i
il

~ I i
-- 1--
i
~ I
'
i
@--==---c==--:@ @---=---c:---:
>00~~ 5059
~~wol

ANCHOR BOLT PLAN

ANCHOR BOLT DETAIL@ ANCHOR BOLT DETAIL@

G)&cp

SIDEWALL SlEEL UNE

ANCHOR BOLT DETAIL @ ANCHOR BOLT DETAIL @

292
L(WL)
117 (D.L+L.L)

~HL ~HR
L(D.LW.L)
MAX WIND COL REACTIONS (KNS)

26
Main frame column reactions:
Sign convensions:
Positive hor.Reaction : to the right
Positive ver.Reaction : upward
Positive moment : counterclockwise

----
26

L L
MAX BRACED BAY REACTIONS (KNS)

MAINFRAME - 2-8
REACTION FOR COMBINED LOADS:

Description Horz Vert Momt Load


KN KN KN-M combination
LEFT COL. 79.5 117.7 0.0 1DL+1LL
LEFT COL. -40.0 -45.7 0.0 1DL+1WLL
LEFT COL. -12.7 -24.6 0.0 1DL+1WLR
LEFT COL. 13.5 29.4 0.0 1DL+1SEI

I RIGT COL.
RIGT COL.
-79.5
12.7
117.7
-24.6
0.0
0.0
1DL+1LL
1DL+1WLL
RIGT COL. 40.0 -45.7 0.0 1DL+1WLR
RIGT COL. -22.3 33.2 0.0 1DL+1SEI

293
cy PURLIN
200 ZX2.0
(TYP) 35~09 PURLIN
200 ZX1.75
(1YP) 35 23
PURLIN
200ZX1.5
(1YP) 3~53 PURLIN
20 0 ZX1.5
(TYP) 35~53 PURLIN
200 ZX1.75
(TYP) 70~53 PURLIN
200ZX2. 0
(1YP) ?
7744 OUT/ OUT OF STEEL LINE

113 113
LEFCIEND LEFCIEND
ZC-8706(24) Z8-8706(24) ZA-8706(24) ZA-8706(24) za-8706(24) ZC-8706(24)
@--
/ /

'' /
/
'' /
/

1l / " ' 1l / " '


/
' /
'
/
/
'' /
/
''
/
' /
'
-- '' /
/
'' /
/

' /
' /

'' /
/
'' /
/

' /
' /

/
/
'' /
/
''
/
' /
'
/
/
'' /
/
''
/
' /
'
-- '' /
/
'' /
/

' /
/
' /
/

'" /
'" /

/
/
'' /
/
''
/
' /
'
/
/
'' /
/
''
-- -- -- - r-- rCL -OFRIDGE
--
'' /
/
'' /
/

',, 1J~; '' /


/

' /

c,!J >',, / " '


/
'
/
/
'' /
/
''
@--
/
' /
'
'' /
/
'' /
/

' ~' ' ' /

',, ~q')oY> '' /


/

' /

~tF '' ''


/
/

' /
'
/
/
'' /
/
''
' '
--
/ /

'' /
/
'' /
/

""''"
' ', ,,f-y ' /
/

'" /

,"' ''
' /
/
/
''
'

---
~
lEC-7992(2) ~~ 1DC-7990(TYP) lEC-7992(2)
(
(TYP) X .
(TYP)

ROOF FRAMING PLAN

353 353

625 625

PURLIN CONNECTION DETAIL PURLIN CONNECTION DETAIL


At Lines 1 & 7 At Lines 3-5

PURLIN CONNECTION DETAIL


At Lines 2 & 6

294
295

~
;
~
!:l MF - 501A- 4300(2)

vI
2-PG-4350 (2)
20.0M ROLLS 12NO'S(CU1 & USE)
8500 EAVE HEIGHT
8500 EAVE HEIGHT
t I goo
~
1800

---) ---)
~~ ~ I' KW-0.5-3700 I~ \
n~ ~
~ \
nu-- 'f ':' la
:: :
la ~
~~ G\
!l
r-.,

"~
~p
KW - 0.5 - 5090(36)
KW-0.5-3800

KW - 0.5 3900
i'l
8 l,; ~~l 'l'g
.._.N-t

~ ~ 1!
KW 0.5 - .WOO

TT

\l~!
KW- 0.5 - 4100
I ---@
KW - 0.5 - 4200 !:

I I! n~-4400 'l~i~t I! n

~ ~
!l
e
~
KW 0.5

KW - 0.5 - 4500 0 1 3
KW 0.5 - 4600
m
jjf
KW - 0.5 - 4700
z
0 ((): ':'
m 9EC1
G\ --@
z
0
KW - 0.5 - 4800
~
r
51~
~+! i(
-1 ~
!
'::
,;
~ ~ ~
KW - 0.5 - 4900
r
"'T1 ><
r KW - 0.5 5000
II
r
~ ~ '9~l ~
~~--~ t
~ ~ en KW- 0.5-5100
~ ()\ =e
c:..::e I
5I c. m TT KW - 0.5 - 5200
zG)
~ ~
I
"'"' m
~ ;! -I
~~
.,,. z I II KW-0.5-5300 oo-- m
~ 1~;
r --@
Q G)
~
~nom '~" 1 ji n u - -
~~ r ~
I KW - 0.5 - 5200 .;2
><
:Z:iij ~ n -

~ ~ )>
KW - 0.5-5100 0 ~g., ~
,. m -I z ~~~ E
~r;; KW - 0.5 - 5000
;o ~
~ 0 fh CD ':'
z G)
~,~
KW - 0.5 - 4900
il
::0
KW - 0.5 - 4800
i5 ! ---@
~w~l
G) TT KW - 0.5 - 4700
9EC2
::0 I -....!
i5 KW 0.5 - 4600 '31~
~
-....! KW 0.5 - 4500 ~ !l
8 N '
~ 18
~ KW - 0.5 - 4400
!g
@l ~~~ E
----~--~ :!i

~':' I; I t~
;1 .
KW - 0.5-4300

KW - 0.5-4200 1g
II
8EC2 -G
E KW 0.5 - 4100

KW - 0.5 - .WOO

KW 0.5 - 3900
~ ~~~ ~
KW - 0.5 - 3800

KW - 0.5 - 3700 Jo
;o "'
~.,~
~ i ~I
l Jo
3

1: KW-0.5-3600 ~ l i 7EC1 ~!:

l --@ 2220 1sao 1 zooo 1aoo 1 goo --@


'5 8500 EAVE HEIGHT

2-PG-4350 (21
MF - 501A- 4300(2)
cy ZD 8706{4) zc- 8706{4) ZB 8706{4) ZB 8706{4) zc- 8706{4) ZD 8706{4)
,,Cf709 ,,7,, ,,Cf,, ,,cr,, 709cr,, cr
48000 OUT/OUT OF STEEL LINE

6000 6000 6000 6000 6000 6000

,, 7887 7887 ,
LEF 0 END LEF 0 END
yp
~
~
/ /
/ /
/ /
'' ''
' ' /
~/
8 0 ' ' / 0
~ ',~-$of: /
~ ~ ~ ~ ~ ' ' '-/ ~ ~

14111 FIELD DRILL HOLES


<)/ /
~ /"JAM L AuuN ) / ' / '
/ '' / ''
/ /
/ /
~ SWD <"~
7
SWD I
'' ''
~71~~ 11,~ ~ ~/ ', ~/ ',
~ I sose 1914lsool

SIDEWALL FRAMING ELEVATION@ GRID- A

296
cy Cf cr
48000 OUT/OUT OF STEEL LINE

48 PANELS RUNS W/STD. LAP & LAST PANEL W/J34 LAP

TART N F HFFTING
167Mt.1 FRO M STEEL LINE

GU 501L 6150 {1) GU-501-6150 6 GU 5011 6150 (1)

MF 515 3050 16)

I
I
I
I
I
I
I
I
!: I
8 I
:a
I
d I
wo ~ I
I
~7~ ~~l
~{8)

SIDEWALL SHEETING ELEVATION@ GRID -A


KW-0.5THK. ARCTIC WHITE WALL PANELS
FSK-50THK INSULATION WITH 10Kg/m3 DENSITY
f- f-
:r: :r:
0 0

18000 OUT /R IDGE 18000 RIDGE/OUT

36000 OUT/OU T OF STEEL UNE

297
CROSS SECTION @GRID- 2- 6

10- M24X85
~
l[)
I~ I
"""
~I 0
S'
~1
12-M24X95 50 100 100 560 100 100 50

~
l[)
0
n
HSB )
60 )
)
~ ~
I I I
l[)
F 0
n
11-
N 0 ~ ~ ~
N -
0
-~ ~ ~ ~ ~ ~ S'
~ ~ l[)
f! - :3
?-1 TI-H< I 1060
(
~ =
"""
PLATE IK I
PLATE

DETAIL@ DETAIL@
NOTES:

298
www.kirbyinternational.com
Follow us at

Middle East & Africa Corporate Office & India Corporate Office & Hyderabad Plant Southeast Asia Corporate Office &
Kuwait Plant Vietnam Plant
Kirby Building Systems India Ltd.
Kirby Building Systems - Kuwait Plot No 8-15, IDA Phase III, Kirby Building Systems Southeast Co Ltd
Mina Abdullah Industrial Area Pashamylaram, Medak Dist. - 502 307 7th Floor, SPT Building,
P.O. Box 23933 Safat, 13100, Kuwait Telangana, India 199 Dien Bien Phu, Ward 15,
Binh Thanh District,
Tel.: +965 2326 2800 Tel.: +91 8455 224401 / 02 / 03 / 04
Hochiminh City, Vietnam
Fax: +965 2326 1793 / 8 Fax: +91 8455 224419 / 27
Email: kirbymarketing@alghanim.com Email: kirby@kirby-india.com Tel.: +84 5422 1155
Fax: +84 5422 1156
Ras Al Khaimah Manufacturing Plant, UAE Haridwar Plant, India
Email: sales@kirby.vn
Kirby Building Systems - UAE LLC, Kirby Building Systems India (Uttaranchal)
Kirby is a wholly owned subsidiary of
Al Jazeera Industrial Area II, Pvt. Ltd.
Alghanim Industries
Behind RAK Ceramics, Plot No 2, Sector 11,
PO Box No. 6624, Integrated Industrial Estate,
Ras Al Khaimah, UAE. Haridwar, Uttarakhand - 249403, India
Tel.: +971 7204 3333 Tel: +91 1334 235317, 235318, 235319
Alghanim Industries,
Fax: +971 7244 7830 Fax: +91 1334 235314, 235397
P.O. Box 223, Safat,
Email: kirbyrak@alghanim.com Email: kirby@kirby-india.com
Kuwait 13003

Vous aimerez peut-être aussi