SECTION 16780
PART 1 - GENERAL
B. General Provisions for Electrical Work, Section 16010 apply to work of this
section.
C. Raceways, Boxes And Fittings, Section 16110, applies to work of this section.
C. In case of conflict among the referenced standards and codes, the more stringent
provision will govern.
1.4 SUBMITTALS
C. Riser diagram: Submit riser diagram for the TV and Satellite Reception System
indicating type of different components in the system and also the calculations of
the signal levels at each point of the Building Television and radio outlets.
D. Compliance list: submit a detailed point by point compliance statement with this
specification. Where the proposed system does not comply or accomplish the
stated function or specification in a manner different from that described and
specified, a full description of the deviation shall be provided.
Where a full description is not provided it shall be assumed that the proposed
system does not comply with the requirements in the specification.
Guarantee equipment furnished under these specifications against defective parts and
workmanship under terms of the manufacturers and dealers standard warranties for a
period of not less than one years from date of initial start-up and Engineer acceptance
of the system and include labor and travel time for necessary repairs at the job site.
PART2 - PRODUCTS
2.2 INTRODUCTION
B. The contractor shall show evidence that he maintains a fully equipped service
organization capable of furnishing adequate maintenance of the installed
system.
C. After the system is installed the contractor shall furnish a complete set of
operating instructions, technical information and system drawings necessary
for the proper operation and maintenance of the system.
The drawings shall include signal levels throughout the system as they were on
the acceptance date of the system.
D. The contractor shall provide and install, all the required cable and wiring for
the systems specified.
E. The contractor shall investigate the electrical power standards of the local area
and the specific premises in which the equipment is to be installed. All
equipment shall be compatible with the local power supply, voltage and
frequency.
F. All major items of equipment shall be the product of one manufacturer, where
practicable, to ensure a uniform quality and compatible styling and appearance.
G. The system shall be rated and capable of continuous twenty-four (24) hour
operation.
A. The TV and Satellite Reception System installed shall comply with all
applicable, International standards and code of practice and Egyptian
Standards.
A. Wiring shall be carried out using the appropriate size of super low loss coaxial
cable. Coaxial cables shall be installed strictly in accordance with the cable
manufacturers recommendations.
B. The contractor shall install Television and Satellite Reception System outlets
as indicated on the drawings.
C. The contractor shall provide and install all power supplies necessary for the
correct operation of the system.
H. The signal level for each desired channel as measured at each or any correctly
terminated outlet shall be between + 82 dB and + 68 dB.
I. K-rating on pulse and bar shall be 5% or better from aerial input to each outlet
when correctly terminated.
K. MATV system risers shall all be of the super low loss 75 ohms, cu-core coaxial
type (attenuation at 800 MHz not exceeding 9 dB/100 mt.), run inside the mast
and securely clamped against vibration and whipping.
L. DISTRIBUTION SYSTEM
Distribution system main amplifier shall be broadband type to cover the range
of VHF and UHF frequencies.
The amplifier(s) shall be so rated and operated that the sync. compression at
any outlet is no more than 0.5 dB.
The amplifier(s) shall have the appropriate power level capability and flatness
of response that will enable the total system performance specifications to be
met.
All line splitters and directional couplers shall be of the passive type,
incorporating 75 Ohm hybrid design.
Tap-off units shall have 75 Ohm backmatched units. Isolation and insertion
loss shall be chosen for each location to enable the total system performance
specification to be met.
The contractor shall adjust the headend to provide frequency tilt to compensate
for the frequency discriminative characteristics of the system cable.
The system main coaxial cable shall be 75 Ohm impedance with an attenuation
of 9 dB/100 meters @ 800 MHz. It shall be sweep tested by the manufacturer
and certification shall be available on request.
Outlet sockets shall be in accordance with DIN 45330 for connecting T.V.
signals outlet shall be flush mounted and properly terminated at position
shown on drawings.
Decoupling : in accordance with DIN/ VDE 0855, part 11.
MATV distribution cables shall be low loss type coaxial cable, with copper
conductor (min.1.6 mm & attenuation not exceeding 16 dB/100 meter @ 800
MHz).
B. The following tests shall be carried out using a pattern generator with facilities
for all aspects of video and audio performance including :
i- Color Performance.
ii- Ghosting.
iii- Resolution.
iv- Synchronization performance, and any other measurements that
Engineer may which to perform.
v- System Performance.
vi- System Recording.
The generator shall provide crystal controlled carries at all channel frequencies
in bands I and III modulated with 1000 Hz. audio and appropriate video signal.
Output shall be variable between at least + 20 dB and +100 dB. The raw video
and audio signals shall also be available.
PART 3 - EXECUTION
3.1 INSPECTION
Examine areas and conditions under which The Building Television and satellite
system are to be installed and notify in writing of conditions detrimental to proper
completion of the work. Do not proceed with the work until unsatisfactory conditions
have been corrected.
3.2 INSTALLATION