Vous êtes sur la page 1sur 5

CT Polarity on a SIPROTEC Relay Quick Start Instructions

These instructions are provided for the purpose on providing a quick start to CT Polarity on a
SIPROTEC 4 relay for commonly used 3 phase and restricted earth fault applications. Please refer
to the relevant relay manuals for full details or specialised applications.

Model Relevant manual sections


7SJ62/63/64 2.1.3.2 Power System Data 1: Polarity of Current Transformers
2.1.6.2 Power System Data 2: Inversion of Measured Power Values
A.3.1 Connection Examples for Current Transformers
7SJ80 2.1.3.2 Power System Data 1: Polarity of Current Transformers
2.1.6.2 Power System Data 2: Inversion of Measured Power Values
A.3 Connection Examples
7UT6 2.1.4.2 General Power System Data: Current Transformer Data for 3 Phase Measuring Locations &
Current Transformer Data for Further 1 Phase Current Inputs
2.1.6.1 Power System Data 2: Sign of Power
A.3.1 Current Transformer Connection Examples
7SD61 2.1.2.2 Setting Notes: Current Transformer Polarity
2.1.4.2 General Protection Data: Setting Notes: General Performance Data
2.3.1 Restricted Earth Fault Protection: Application Examples
A.3.1 Current Transformer Connection Examples
7SD5 2.1.2.1 Power System Data 1: Setting Notes: Polarity of the Current Transformers
2.1.4.1 General Protection Data: Setting Notes: General Line Data of the Distance Protection
2.10.1 Restricted Earth Fault Protection: Application Examples
A3.1 Current Transformer Connection Examples
7SA5 2.1.2.1 Power System Data1: Setting Notes: Current Transformer Polarity
2.1.4.1 Power System Data 2: Setting Notes: General Line Data
A.3.1 Connection Examples: Current Transformer Examples

This quick start describes:


Section 1) Phase CT polarity
Section 2) Positive power direction
Section 3) NCT connection for REF with a 7UT
Section 3) NCT connection for REF with a 7SD61/53/53

1 Phase CT polarity
When using the CT connection examples in the SIPROTEC manuals and in this document there are
two basic assumptions:
1. The P1 & S1 terminals are always drawn on the same side of the CT.

2. The non star-point side of the CTs are always connected to Q1, Q3, Q5 terminals.

Page 1 of 5 CT Polarity on a SIPROTEC - Quick Start.docx


In a line protection relay the possible options are that the CT star-point is towards the line or
towards the busbar. In a 7UT relay the options are that the star-point is towards the protected object
(eg. transformer) or not towards the protected object. This can easily be seen from the drawings and
applied as a relay setting.

If the CT secondary star-point connection is to the correct relay terminals then the CT primary
orientation can be either way without affect on the relay. This is shown in the following two
examples - a fault towards the line results in the same secondary currents into the relay, even
though the CT primary orientation has been swapped.

The default setting is for the CT star point towards the line or protected object. The currents used in
the relay algorithms and oscillographic records follow the convention that current into the
line/protected object will be in-phase with the voltage (if zero power factor is assumed). If the star-
point is connected opposite to this then the setting needs to be changed to towards busbar in a line
protection relay or NO in a 7UT relay. The relay will then invert the phase CT signals before
they are used in the protection elements or oscillographic records. This setting also swaps the
polarity of the I4 input in 7SJ6/7SD61/7SD5/7SA5 relays and the IN input in 7SJ80 relays.

Page 2 of 5 CT Polarity on a SIPROTEC - Quick Start.docx


SETTINGS

7SJ6/7SD61/7SD5/7SA5/7SJ80

Power System Data 1:

7UT5/7UT6

Power System Data 1:

2 Positive power direction


Measured power is usually considered positive if it is in the direction of the protected line/object. If
required, this can be swapped by changing setting P,Q operational measured values sign to
reversed. This affects all relay functions using these measured/metered values including any
reverse power elements.

SETTINGS

7SJ6/7SJ80

Power System Data 2:

7SD61/7SD5/7UT6 (with voltage option)

Power System Data 2:

7SD61/7SD5/7SA5

Power System Data 2:

Page 3 of 5 CT Polarity on a SIPROTEC - Quick Start.docx


3 NCT connection for REF in a 7UT
The value required for setting 0711 EARTH iX1 AT (or 0721 if the iX2 input is used) depends on
which relay terminal is connected to the CT secondary circuit that corresponds to the CT primary
closest to the transformer earth.

P1 towards earth, S1 connected to Q8. P1 towards earth, S1 connected to Q7.


Set 0711 EARTH iX1 AT = Q8 Set 0711 EARTH iX1 AT = Q7

P2 towards earth, S2 connected to Q7. P2 towards earth, S2 connected to Q8.


Set EARTH iX1 AT = Q7 Set EARTH iX1 AT = Q8

The secondary earthing of the CT is required but its location is not relevant to the setting. The
connection or setting of the phase CTs is also not relevant. Setting 711 inverts the current input if
necessary so that the signal in the protection elements and the oscillographic fault records follow
the convention that positive current flow is into the protected object.

SETTINGS

Power System Data 1:

if IX1 input is used:

if IX2 input is used:

Page 4 of 5 CT Polarity on a SIPROTEC - Quick Start.docx


4 NCT connection for REF in a 7SD61/52/53
The polarity of the I4 neutral CT input is dependent on setting 0201 CT Starpoint. The value
selected for this setting depends on the phase CT connection. If the I4 input is used for the
connection of a transformer NCT for REF protection then the CT connection must match the 0201
setting that has been applied.

0201=towards line, P2 towards earth. 0201 = towards bus, P2 towards earth.


Connect S2 to Q7. Connect S1 to Q7.

0201=towards line, P1 towards earth. 0201 = towards bus, P2 towards earth.


Connect S1 to Q7. Connect S2 to Q7.

The secondary earthing of the CT is required but its location is not relevant to the setting.

Page 5 of 5 CT Polarity on a SIPROTEC - Quick Start.docx

Vous aimerez peut-être aussi